HomeMy WebLinkAbout1207 CARLSBAD VILLAGE DR; I; CB920749; Permit05-09-2007
City of Carlsbad
1635 Faraday Av Carlsbad, CA 92008
Building Permit Permit No:CB920749
Building Inspection Request Line (760) 602-2725
Job Address 1207 CARLSBAD VILLAGE DR CBAD St I
Permit Type ITI Sub Type
Parcel No 1561804500 Lot #
Valuation $0 00 Const Type NEW
OccGroup Reference #
Project Title 1020SF DENTIST OFFICE
Status
Applied
Entered By
Appr/Issued
Inspect Area
EXPIRED
07/31/1992
MDP
Applicant
MORRISON, MARK
1207 CARLSBAD VILLAGE DR #J
CARLSBAD CA 92008
619 634-0811
Owner
ROBINSON BETTY A TR
Total Fees
$0 00
$168 00 Payments To Date $168 00 Balance Due
Description
Other
Fee
168 00
Inspector
FINAL APPROVAL
Date Clearance
NOTICE Please take NOTICE that approval of your project includes the "Imposition" of fees, dedications, reservations, or other exactions hereafter collectively
referred to as lees/exactions" You have 90 days from the date this permit was issued to protest imposition of these fees/exactions If you protest them, you must
follow the protest procedures set forth in Government Code Section 66020(a}, and file the protest and any other required information with the City Manager for
processing in accordance with Carlsbad Municipal Code Section 3 32 030 Failure to timely follow that procedure will bar any subsequent legal action to attack,
review, set aside, void, or annul their imposition
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection fees and capactiy
changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this project NOR DOES IT APPLY to any
fees/exactions of which you have previously been qiven a NOTICE similar to this, or as to which the statute of limitations has previously otherwise expired
PERMIT APPLICATION
City of Carlsbad Building Department
2075 Las PaI mas Dr., Carlsbad, CA 92009 (619) 438-1161
1 PtHMI I
A - U Commercial D New Building DTTenanl Improvement
B - D Industrial D New Building D Tenant Improvement
C - Q Residential D Apartment D Condo D Single Family Dwelling D Addition/Alteration
D Duplex D Demolition D Relocation D Mobile Home D Electncal D Plumbing
D Mechanical DPool D Spa D Retaining Wall Q Solar D Other
2. PRCUfrjCT INIX)RMATION
Address ~~
PLAN CHECK NO.
EST VAL
PLAN CK DEPOSI
VALID BY .f\Aj
DATE
C-PRMT
FOR OFFICE USE ONLY
168.00
Building or Suite No
Cross Street
Lot No Subdivision Name/NumberLEGAL Unit No Phase No
CIIFCK Bl'LOW IF SUBMIITEL) ~
D 2 Energy Calcs D 2 Structural Calcs d 2 Soils Report D 1 Addressed Envelope
ASSESSOR'S PARCEL
DESCRIPTION OF WORK "]-£-jOrVA "jPt*"
SQ FT IO^-O t^ # OP
NAME f-Ofr^C f
CIIY C/VpcsPA"
t aillerent trom applicant)
9 STATE CA
EXISTING USE PROPOSED USE
STORIES CN 15-
AOlJHiiSS 1 jf'O1 1 J vjip^v^*1"^ I ^
ZIP CODE *^POO & DAY TELEPHONE d>3 Y OS I t
4 APPLICANT UUJNIKACIOR U AtitN 1 1 OK UJN 1 KAU1UK LJUWNh'K BffAGKNT FUR OWNER
NAME * ADDRESS
CITY STATE ZIP CODE DAY TELEPHONE
5 PROPERTY OWNKK
CITY C/^_5(3/^
b CUN TKAdtik
NAME .., »\i\ft{i,
CITY
ULMGNhK NAMb
CITY
j^ot»rA>s&^
rD STATE C/V
^O\IA>(^
STATE
STATE LIC #
STATE
ADDRESS 6»Mo <TOf£T£- 0^( C^_J>^ 0
ZIP CODE Te)-OO | DAY TELEPHONE 7 3 6 2~C* 7- I
ADDRESS
ZIP CODE DAY TELEPHONE
LICENSE CLASS CITY BUSINESS LIC #
AUUKLbb
ZIP CODE DAY TELEPHONE STATE LIC #
7 WORKlilto' UUMHLNSAT1UN
Workers Compensation Declaration I hereby aflirm That I have a certiTicate of consent to seTTinsure issued by the Director of Industrial
Relations, or a certificate of Workers' Compensation Insurance by an admitted insurer, or an exact copy or duplicate [hereof certified
by the Director of the insurer thereof filed with the Building Inspection Department (Section 3800, Lab C)
INSURANCE COMPANY POLICY NO EXPIRATION DATE
Certilicate ot Exemption I certify mat in the performance of the work for which this permit is issued, I shall not employ any person in any manner
so as to become subject to the Workers' Compensation Laws of California
SIGNATURE DATE
8 OWNER-BUILDIJt DhQARAnON
Owner-Builder Declaration I hereby aihrm that I am exempt from the Contractors License Law lor the following reason
I, as owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not intended or
offered for sale (Sec 7044, Business and Professions Code The Contractor's I acense Law does not apply to an owner of property who builds
or improves thereon, and who does such work himself or through his own employees, provided that such improvements are not intended
or offered for sale If, however, the building or improvement is sold within one year of completion, the owner-builder will have the burden
of proving that he did not build or improve for the purpose of sale )
1, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec 7044, Business and Professions
Code The Contractor's License law does not apply to an owner of property who builds or improves thereon, and contracts for such projects
with contractor^) licensed pursuant to the Contractor's License Law)
1 am exempt under Section _ Business and Professions Code for this reason
(Sec 7031 5 Business dnd Professions Code Any City or County which requires a permit to construct, alter, improve, demolish, or repair
any structure, prior to its issuance, also requires the applicant for such permit to file a signed statement that he is licensed pursuant to the
provisions of the Contractor's License Law (Chapter 9, commencing with Section 7000 of Division 3 of the Business and Professions Code)
or that he is exempt therefrom, and the basis for the alleged exemption Any violation of Section 7031 5 by any applicant for a permit
subjects*! heiappliprk lo a civil peifclty of /Tdl/mire than five hundred dollars [$500]) s\
°ATE / "^ / *"* ^ ___SIGNATURE
- COMPLETE THIS s
Is the applicant or future building occupant required to submit a business plan, acutely hazardous matenals registration form or risk management and
prevention program under Sections 25505^15533 or 25534 of the Presley-Tanner Hazardous Substance Account Act?
D YES Er NO
Is the applicant or future building occupant required to obtain a permit from the air pollution control distnct or air quality management district?
D YES D^NO/
Is the facility to be constructed within l,000ieet of the outer boundary of a school site?
D YES CkNO
IF ANY OF Tl IE ANSWERS ARE YfeS, A FINAL a JITTFICATL OF OCCUPANCY MAY NOT BE ISSUED AFTER JULY 1, 1989 UNLESS THE APPLICANT
HAS MET OR IS MEETING THE REQUIREMENTS OF Tllfc OFFICE OF EMERGENCY SERVICES AND THE AIR PQI JJJT1ON CONTROL DISTRICT
9 CUNkTUUlTlUN IJJJUlNti
I hereby attirm that there is a construction lending agency lor the performance of the work lor which this permil is issued (.Sec 30970J
LENDER'S NAME n LENDER'S ADDRESS |JIPAPPLICANT _ _ ,___,„_-, _ ,___.__I certify that I havt. read the application and stale that the above information is correct I dgree to comply with all City ordinances and Slate laws
relating to building construction I hereby authorize representatives of the City of Carlsbad to enter upon the above mentioned property for inspection
purposes I ALSO AGREF TO SAVE INDEMNu"Y AND KEEP HARMLESS THE CITY OF CARLSBAD AGAINST ALL LIABILITIES, JUDGMENTS, COSTS
AND EXPENSES WHICH MAY IN ANY WAY ACCRUE AGAINST SAID CITY IN CONSEQUENCE OF THF GRANTING OF THIS PERMIT
OSIIA An OSHA permit is required for excavations over 5'0" deep and demolition or construction of structures over 3 stones in height
Expiration Fvery permit issued by the Building Official under the provisions of this Code shall expire by limitation and become null and void if the
building or work authorized by such permit is not commenced within 365 days from the date of such permit or if the building or work authorized by
such permit is suspended or abandoned at any lime after the work is commenced for a penod of 180 days (Section 303(d) Uniform Building Code)
/ Jf I *• —APPLICANT,DATE
WHITE: File YELLOW: Applicant PINK. Finance
DATE: 06/25/93
TO: MORRISON, MARK
1207 CARLSBAD VILLAGE DR. #J
CARLSBAD CA 92008
PLAN CHECK EXPIRATION
PC# CB920749 DATE: 07/31/93
ADDRESS: 1207 CARLSBAD VILLAGE DR #1
You have applied to have your plans checked on the date shown
above, and you have not obtained your building permit.
The provisions of Section 304(d) of the Uniform Building Code
state:
"Section 304(d) Expiration of Plan Review
Applications for which no permit is issued
within one year following the date of
application shall expire by limitation, and
plans and other data submitted for review
may thereafter be returned to the applicant
or destroyed by the Building Official.
In order to renew action on an application
after expiration, the applicant shall resubmit
plans and pay a new plan review fee."
Please check the appropriate box indicating your choice
and return this letter to the BUILDING DEPARTMENT.
PROJECT ABANDONED. I WILL PICK UP PLANS WITHIN 10 DAYS
PROJECT ABANDONED. PLANS MAY BE DESTROYED.
If you have any questions, please contact the Building
Department at (619) 438-1161.
DORIS COSMAN
Building Department
207'5 Las Palmas Drive - Carlsbad, California 92OQ9-1576 - (619) 438-1161
ESGIL CORPORATION
932O CHESAPEAKE DR., SUITE 208
SAN DIEGO, CA 92123
(619) 560-1468
V
DATE:
JURISDICTION:
PLAN CHECK NO:
PROJECT ADDRESS:
PROJECT NAME:
CARLSBAD
SET:
/^07
QAPPLICANT
QPLAN CHECKERQFILE COPY
QUPS
[JDESIGNER
The plans transmitted herewith have been corrected where
necessary and substantially comply with the jurisdiction's
building codes.
The plans transmitted herewith will substantially comply
with the jurisdiction's building codes when minor deficien-
cies identified are resolved and
checked by building department staff.
The plans transmitted herewith have significant deficiencies
identified on the enclosed check list and should be corrected
and resubmitted for a complete recheck.
The check list transmitted herewith is for your information.
The plans are being held at Esgil Corp. until corrected
plans are submitted for recheck.
The applicant's copy of the check list is enclosed for the
jurisdiction to return to the applicant contact person.
The applicant's copy of the check list has been sent to:
Esgil staff did not advise the applicant contact person that
plan check has been completed.
Esgil staff did advise applicant that the plan check has
been completed. Person contacted:
Date contacted:
REMARKS:
Telephone #
By:PF
ESGIL CORPORATION
iGA Si! CM
Enclosures
PLAN CORRECTION SHEET
TENANT IMPROVEMENT
PLAN CHECK HO.:
JDRISDICTION: CARLSBAD
TO:
PROJECT DATA
OCCUPANCY:
BUILDING USE:
TYPE OF CONSTRUCTION:
ACTUAL AREA;
ALLOWABLE AREA:
STORIES
HEIGHT:
SPRINKLERS:
OCCUPANT LOAD:TX
REMARKS:
Date plans received by jurisdiction:
Date plans received by Esgil Corporation:
Date initial plan check completed:
6/73 hi- Bv:
Applicant contact person:
Tel.
FOREWORD: PLEASE READ
Plan check is limited to technical requirements
contained in the Uniform Building Code, Uniform
Plumbing Code, Uniform Mechanical Code, National
Electrical Code and state laws regulating energy
conservation, noise attenuation and access for the
handicapped. The plan check is based on
regulations enforced by the Building Inspection
Department. You may have other corrections based
on laws and ordinances enforced by the Planning
Department, Engineering Department, Fire Department
or other departments. Code sections cited are
based on the 1988 UBC.
The circled items listed need clarification,
modification or change. All items must be
satisfied before the plans will be in conformance
with the cited codes and regulations. Per Sec.
303(c), 1988 Uniform Building Code, the approval of
the plans does not permit the violation of any
state, county or city law.
To speed up the recheck jprp_ces_s. note on this list
for a copy) where each correction item has-been
addressed, i.e.j n plan sheet, specification, etc
Be sure to enclose the marked up .list __whgn you
submit the revised plans.
NOTE: PAGE NUMBERS ARE 1»OT IK SEQUENCE AS PAGES HAVING NO ITEMS NEEDING CORRECTIONS WERE DELETED.
LIST NO. 56 CARLSBAD TENANT IMPROVEMENT WITHOUT SPECIFIC ENERGY ZONE DATA OR POLICY SUPPLEMENTS, 1988 UBC
X
Please make all corrections on the original
tracings and submit two new sets of prints, and
any original plan sets that may have been
returned to you by the jurisdiction, to-
Esgil Corporation, 9320 Chesapeake Drive,
Suite #208, San Diego, CA 92123,
(619) 560-1468.
Please make all corrections on the original
tracings and submit two new sets of prints, and
any original plan sets that may have been
returned to you by the jurisdiction, to:
The jurisdiction's building department.
Indicate on the Title Sheet of the plans, the
name of the legal owner and name of person
responsible for the preparation of the plans.
Section 302(d).
Each sheet of the plans must be signed by the
person responsible for their preparation, even
though there are no structural changes .
Business and Professions Code.
Plans and calculations shall be signed by the
California state licensed engineer or architect
where there are structural changes to existing
buildings or structural additions. Please
include the California license number, seal,
date of license expiration and date plans are
signed. Business and Professions Code.
Provide the correct address and suite number of
tenant space on the plans. Section 302(d).
Provide a note on the site plan indicating the
previous use of the tenant space or building
being remodeled. Section 302.
When the character of the occupancy or use
changes within a building, the building must be
made to comply with current Building Code
requirements for the new occupancy. Please
provide complete details to show the building
with comply. Section 502.
UBC Section 304 requires the Building Official
to determine the total value of al 1
construction work proposed under this permit.
The value shall include all finish work,
painting , roofing , electrical , plumbing ,
heating, air conditioning, elevator, fire
extinguishing systems and any other permanent
equipment. Please provide a signed copy of the
designer's or contractor's construction cost
estimate of all work proposed.
Provide a plot plan showing the distance from
the building to the property lines and the
location of tenant space (or remodel) within
the building.
\j.
On the first sheet of the plans indicate:
Type of construction of the existing building,
present and proposed occupancy classifications
of the remodel area and the occupant load of
the remodel areas and the floor where the
tenant improvement is located. ~f~rt-£ tof COI-/ST 11 3Z~ I \-\R_ p £_z_ CITY
Provide a note on the plans indicating if any
hazardous materials will be stored and/or used
within the building which exceed the
quantities listed in UBC Tables 9-A and 9-B.
A complete description of the activities and
processes that will occur in this tenant space
should be provided. A listing of all
hazardous materials should be included. The
materials listing should be stated in a form
that would make classification in Tables 9-A
and 9-B possible. The building official may
require a technical report to identify and
develop methods of protection from hazardous
materials. Section 901(f).
If control areas are used for exceeding the
exempt amounts of hazardous materials from
Tables 9-A and 9-B, they shall be constructed
of not less that required for a one-hour
occupancy separation. Section 404.
The number of control areas within a building
used for retail/wholesale stores shall not
exceed two; the number of control areas in
buildings with other uses shall not exceed
four. Footnote 1, Tables 9-A and 9-B.
The aggregate quantity of any hazardous
materials "in use" and "in storage" shall not
exceed the quantity listed in Tables 9-A and
9-B for "storage". Footnotes 2 and 3, Tables
9-A and 9-B. \
Provide a statement on the Title Sheet of the
plans that this project shall comply with
Title 24 and 1988 UBC, UMC and UPC and 1990
NEC.
Provide a fully dimensioned floor plan showing
the size and use of all rooms or areas within
the space being improved or altered. Draw the
plans to scale and indicate the scale on the
plan. Section 302(d).
Indicate the use of all spaces adjacent to the
area being remodeled or improved.
Show any existing fire rated area separation
walls, occupancy separation walls, demising
walls, shafts or rated corridors. Identify
and provide construction details for proposed
new fire rated walls.
Specify on the plans the 'fire ratings of
assemblies to protect proposed openings in
existing or new fire walls.
7/10/91
113 Identify existing walls to be removed, existing
walls to remain and proposed new walls.
Identify bearing walls, non-bearing walls, and
shear walls.
23.} Provide a section view of all new interior
partitions. Show:
(a) Type, size and spacing of studs Indicate
gauge for metal studs. Specify
manufacturer and approval number or
indicate "to be ICBO approved".
(b) Method of attaching top and bottom plates
to structure. (NOTE: Top of partition
must be secured to roof or floor framing,
unless suspended ceiling has been designed
for partition lateral load).
(c) Wall sheathing material and details of
attachment (size and spacing of
fasteners).
(d) Show height of partition and suspended
ceiling, and height from floor to roof
framing or floor framing.
Provide notes and/or details to show that the
floor and wall finish in toilet rooms are
surfaced with a smooth hard non-absorbent
material extending five inches up the wall.
Similar surfacing shall be provided on the
walls from the floor to a height of 4 feet
around urinals and within water closet
compartments. Section 510(b).
Note on the plans: "All interior finishes must
comply with Chapter 42 of the UBC". Specify
"Class flame spread rating (minimum)
for ."
Lateral bracing for suspended ceiling must be
provided. (UBC Table 23-P) Where ceiling is
not supporting interior partitions, ceiling
bracing shall be provided by four No. 12 gauge
wires secured to the main runner within 2
inches of the cross runner intersection and
splayed 90 degrees from each other at an angle
not exceeding 45 degrees from the plane of the
ceiling. A strut (adequate to resist the
vertical component from lateral loads) fastened
to the main runner shall be extended to and
fastened to the structural members of the roof
or floor above. These horizontal restraint
points shall be placed 12 feet o.c. in both
directions with the first point within 6 feet
of each wall. Attachment of restraint wires to
the structure above shall be adequate for the
load imposed. UBC Standard 47-18.
7-
In buildings having floors and roofs of wood
frame construction, other than dwelling or
hotel occupancies, draft stop the area between
the ce 11 ing and f 1 oor above so that no
concealed space exceeds 1,000 s.f. and no
horizontal dimension exceeds 60 L F. (if space
has sprinklers, then 3,000 s.f. and 100 L.F.).
Section 2516(f).
In buildings having floors and roofs of wood
frame construction, other than dwelling or
hotel occupancies, draft stop the area between
the c_eil_ing and roof above so that no
concealed space exceeds 3,000 s.f. and no
horizontal dimension exceeds 60 L.F. (if space
has sprinklers, then 9,000 s.f. and 100 L.F.).
Section 2516(f).
Storage areas exceeding 1000 sq. ft. in
connection with wholesale or retail sales
shall be separated from the public area by a
one-hour occupancy separation. If the entire
building has an automatic sprinkler system,
then the occupancy separation need not be
provided.
An automatic sprinkler system shall be
installed in rooms used by the occupants for
the consumption of alcohol and in accessory
uses where the total area of such unseparated
rooms and assembly uses exceeds 5000 square
feet. Section 3802(c).
The tenant space and new and/or existing
facilities serving the remodeled area roust be
accessible to and functional for the
physically disabled. See the attached
correction sheet. Title 24, Part 2.
The width of the required level area on the
side into which doors swing shall extend 24
inches past the strike edge for exterior doors
and 18 inches past the strike edge for
interior doors. Section 2-3304, Title 24.
Specify lever-type hardware for passage doors
on floors accessible to the disabled. Section
2-3304, Title 24.
If both sexes will be employed and the number
of employees exceeds four, provide separate
toilet facilities for men and women. If "both
sexes will be employed and the total number of
employees will not exceed four", and only one
restroom is provided, note the words in
quotation above on the floor plan. Section
705.
In areas where the occupant load exceeds
two exits are required. See
. Table 33-A.
2/15/90
Provide an exit analysis plan (may be 8 1/2" x
11" or any convenient size). t_jilt-
/•
Exits should have a minimum separation of one-
half the maximum overall diagonal dimension of
the building or area served. Section 3303(c).
The maximum number of required exits and their
required separation must be maintained until
egress is provided from the structure. Section
3303(a).
Rooms with more than 10 occupants may have one
exit through one adjoining room. Revise exits
to comply. Section 3303(e).
Exit signs are required for exits serving an
occupant load exceeding 49. Show all required
exit sign locations. Section 3314(a).
Show that exits are lighted with at least one
foot candle at floor level. Section 3313(a).
Show the locations of existing exits from the
building and show the path of travel from the
remodel area to the existing exits.
Note on the plans: "All exits are to be
openable from inside without the use of a key
or special knowledge". In lieu of the above,
in a Group B occupancy, you may note "Provide a
sign on or near the exit doors reading THIS
DOOR TO REMAIN UNLOCKED DURING BUSINESS HOURS".
This signage is only allowed at the main exit.
Section 3304(c).
Exit doors should be a minimum size of 3 feet
by 6 feet 8 inches with a minimum door swing of
90 degrees. Maximum leaf width is 4 feet.
Section 3304(f).
Exit doors should swing in the direction of
egress when serving an occupant load of 50 or
more or when serving any hazardous area.
Section 3303(b). Applies to door(s)
Regardless of occupant load, a floor or landing
not more than 1/2 inch below the threshold is
required on each side of an exit door used for
disabled access (may be 1" maximum where not
used for disabled access). Section 3304(i).
Doors should not project more than 1 inches
into the required corridor width when fully
opened, nor more than one-half of the required
corridor width when in any position. Section
3305(d).
Revolving, sliding and overhead doors are not
permitted as exit doors if the occupant load
exceeds 9 or the exit door serves a hazardous
area. Section 3304(h).
5Y.
Exit doors from assembly rooms with 50 or more
occupants shall not be provided with a latch
or lock unless it is panic hardware. Section
3318.
Double acting doors are not allowed when
serving a tributary occupant load of more than
100, or when part of a fire assembly, or part
of smoke and draft control assemblies or when
equipped with panic hardware. Section
3304(b).
Corridors must provide continuous protection
to the exterior of the building.
Interruptions by an intervening room is not
permitted. Foyers, lobbies or reception rooms
constructed as required for corridors are not
considered intervening rooms. Section 3305.
Corridors and exterior exit balconies serving
10 or more occupants must be a minimum 44
inches wide and 1 feet high to the lowest
projection. Corridors serving less than 10
occupants must be a minimum of 36 inches in
width. Section 3305(b).
When two exits are required, dead end
corridors and exit balconies are limited to 20
feet. Section 3305(e).
Corridors serving 30 or more occupants shall
have walls and ceilings of one-hour
construction except:
a. Corridors greater than 30 feet wide when
the occupants have an exit independent
from the corridor.
b.
c.
Exterior sides
balconies.
of exterior exit
T
Corridor walls and ceilings need not be
of fire-resistive construction within
office spaces having an occupant load of
100 or less when the entire story in
which the space is located is equipped
with an automatic sprinkler system
throughout and smoke detectors are
installed within the corridor in
accordance with their listing. Section
3305 (g).
Section 3305(g), Exception 5, cannot be used
for non-rated corridors in a fully sprinklered
office space if the occupant load in the space
exceeds 100.
Section 3305(g), Exception 5 does not apply to
common corridors where the corridor serves as
an exit for non-office areas (manufacturing,
warehouse, etc.).
2/14/90
67.
Section 3305(g), Exception 5 is applicable only
for corridors on one floor; the corridors on
the lower level(s) must be rated if these lower
corridors have openings into them from other
levels
If non-rated corridors are used per Section
3305fg), Exc. 5, provide a reference to the
corridors on the floor plan, noting:
1. Corridors are non-rated per Section
3305(g), Exception 5.
2. Smoke detection system must be listed by
the State Fire Marshal1 and be a
supervised low voltage system.
3. Smoke detectors shall be maximum 30' on
center.
U. Power supply shall be dedicated branch
circuit. Circuit disconnecting means
shall be accessible only to authorized
personnel and shall be clearly marked FIRE
ALARM CIRCUIT CONTROL, vith a lock-on
device.
If a tenant space utilizes Section 3305(g),
Exception 5, then that tenant space shall be
separated from adjacent spaces by a demising
wall constructed as for a one-hour corridor
wall.
Clearly show where the non-rated corridor
system terminates and a rated corridor system
commences.
One-hour fire-rated corridors shall have door
openings protected by tight-fitting smoke and
draft control assemblies rated 20 minutes,
except openings in interior walls of exterior
exit balconies. Doors shall be maintained
self-closing or be automatic-closing by action
of a smoke detector per Section 4306(b). Doors
shall be gasketed to provide a smoke and draft
seal where the door meets the stop on sides and
top. Section 3305(h).
Show rated corridors, lobbies, reception or
foyers cross-hatched on the floor plans.
Total area of all openings, except doors, in
any portion of an interior corridor, shall not
exceed 25 percent of the area of the corridor
wall of the room which it is separating from
the corridor. Such openings shall be protected
by fixed, approved 1/4 inch thick wired glass
installed in steel frames. Section 3305(h).
Provide a complete architectural section of
the corridor, or exterior exit balcony,
showing all fire-resistive materials and
details of construction for all floors, vails,
ceiling and all penetrations. Section
3305(g).
Show the location of fire dampers. Provide
fire dampers at duct penetrations of fire-
rated occupancy and area separations, shafts
and corridor walls and ceilings. Section
A306(j).
If a room with an exhaust fan has a door
opening into a rated corridor, show how make-
up air will be provided to the room. The door
cannot be undercut, nor can a louver in the
door be provided. Section 3305(h)l.
If building exceeds two stories and has an
elevator opening into a rated corridor, show
how the smoke and draft control provision of
Section 3305(h) v.ill be met. Either provide a
separated elevator lobby or a second door at
the elevator entry meeting the provision.
If a second door is provided at the elevator
entry, note that it will be readily openable
from the car side without a key, tool or
special knowledge or effort. Section 5106.
Provide evidence of Health Department approval
(for restaurants or for tenants using X-ray
equipment).
When nonflammable supply cylinders for medical
gas systems are located inside buildings, they
shall be in a separate room or enclosure
separated from the rest of the building by not
less than one-hour fire-resistive
construction. Doors to the room or enclosure
shall be self-closing smoke- and draft-control
assemblies having a fire-protection rating of
not less than one hour. Rooms shall have at
least one exterior wall in which there are not
less than two vents of not less than 36 square
inches in area. One vent shall be within 6
inches of the floor and one shall be within 6
inches of the ceiling. When an exterior wall
cannot be provided for the room, automatic
sprinklers shall be installed within the room
and the room shall be vented to the exterior
through ducting contained within a one-hour-
rated shaft enclosure. Approved mechanical
ventilation shall provide six air changes per
hour for the room. Section 702(b)4.
6/13/90
ELECTRICAL
Submit plan showing location of all panels.
CCUPLETCO
Submit^panels schedules.
Submit electrical load calculations
Indicate existing main service size.
Indicate existing total main service load
Indicate new additional loads
Indicate wiring method, i.e. EMT, metal flex.
Show exit signs on the electrical lighting
plan(s). As per Section 3313 and 3314 of the
1988 UBC, provide two sources of power to exit
signs and exit illumination.
Provide receptacle(s) within 25' of HVAC units.
UMC Section 509
Provide multiple switch lighting controls per
Title 24, 5319.OUAL -Sv.lTCUJCa fe3^ Foe
SAc^ PU CJrC U*-3£3~TProvide an electrical plan for the alarm system
shoving compliance with criteria described
under earlier correction number 58.
MECHANICAL
Provide mechanical ventilation in all rooms
capable of supplying a minimum of 5 cubic feet
per minute of outside air with a total
circulation of not less than 15 cubic feet per
minute per occupant. Section 605 and 705, UBC.
83.^ Provide mechanical plans showing existing and
proposed HVAC equipment, ducts and access to
equipment.
%&. Provide drain, waste and vent plans.
%n. Provide water line sizing calculations. UPC
/ Section 1009.
90. Detail how floor drain trap seal is to be
maintained. UPC Section 707 (floor drain trap
priming).
Show P & T valve on water heater and detail
drain line route from P & T valve to the
exterior. UPC Section 1007(e)
on drain and waste92 ^ Show 1/4" per 12" slope
lines. UPC Section 407.
Provide a drinking fountain at each floor
level in assembly occupancies (except drinking
and dining establishments). UBC Section 605.
(94 \ New \,ater closets and
^—-^ valves, if any, shall
^gallons per
Detail access
equipment.
and working clearances to HVAC
associated flushometer
use ___np more than 1 6
flush and "sha"ll~ meet performance""
standards established by the American National
Standards Institute Standard A112.19.2, and
urinals and associated flushometer valves, if
any, shall use no more than one gallon per
flush and shall meet performance standards
established by the American National Standards
Institute Standard A112.19.2. H & S Code,
Section 17921.3(b).
ENERGY
95 J Provide complete energy design calculations,
including all existing design and new energy
design for this building. See attached non-
residential energy design checklist.
For remodels in an existing conditioned space,
show that the remodeled space will not use
more energy than the existing space or show
the remodeled space will conform to latest
energy design standards.
CITY OF CARLSBAD SUFFLfMEHX
Cooling coils or cooling units located in attic
or furred space, where damage may result from
condensate overflow, shall be provided with an
additional water tight pan of corrosion
resistant material to catch overflow if primary
condensate drain becomes clogged. Section
1205, UMC.
One-hour corridors shall not be used as an
integral part of a duct system. This includes
the space above a dropped ceiling within the
one-hour corridor. UMC Section 706(b).
FUMBIHG
Provide gas line plans and calculations,
showing pipe lengths and gas demands. UPC
Section 1219.
Floor drains
Policy).
must have auto-prune (City
A grease interceptor is required. Show
details complying with City Policy 83-34.
Roof mounted equipment must be screened and
roof penetrations should be minimized (City
Policy 80-6).
Condensate drains must connect to a wet trap
(dry traps are not permitted). (Memo
1/14/83).
Show fans are duct type; City Policy does not
permit ductless fans.
1/23/92
r!02j Komex is not permitted in industrial or
commercial buildings. (City Policy)
103^ No wiring is permitted on the roof of a
building and wiring on the exterior of a
building requires approval by the Building
Official. (City Policy)
\w(.. All roof-mounted equipment shall be concealed
from view. Provide structural detailing for
the screening.
All panel boards shall have a minimum 100 amp
rating or approved by the Building Official.
The minimum rating of
100 amperes.
a service disconnect is
The minimum size conductor to receptacles and
lighting fixtures in commercial and industrial
buildings shall be #12 Cu.
AC(BX) cable is not allowed in group A, B, E, H
and I occupancies (see Ord. for exception)
Only tank-type vater closets that use an
average of 16 gallons of water per flush or
less, and urinals and associated flushoroeter
valves, that use an average of 1 gallon of
water per flush or less shall be installed in
new construction. These provisions shall apply
to existing buildings only when toilets are
being replaced in existing bathrooms or
installed in new bathrooms.
MISCELLANEOUS
. Plea.se see additional corrections or remarks
that follow.
Ill J To speed up the recheck process, note on this
^-—/ list (or a copy) where each correction item has
been addressed, i e., plan sheet, note or
detail number, calculation page, etc.
Plea.se indicate here if any changes have been
made to the plans that are not a result of
corrections from this list. If there are other
changes, please briefly describe them and where
they are located in the plans.
Have changes been made to the plans not
resulting from this correction list? Please
check.
Yes No
NOTE:
The following provisions are contained in Title 2**,
Part 2, California Building Code, as adopted and
enforced by the State Fire Marshal. They are
provided here as a courtesy to assist designers in
developing the project documents. All applicable
provisions may not necessarily be included Please
direct any questions regarding interpretations of
these provisions to the local Fire Department.
Walls of corridors and exterior exit balconies
in Groups A,E,I,R-1 and C Occupancies having
an occupant load of more than six persons and
in all other occupancies having an occupant
load of 30 or more shall be not less than one-
hour fire-resistive construction. Section
3305(g)l.
Note on the plans that approved floor-level
exit signs shall be provided. This applies to
A, E and I occupancies.
Area separation walls shall not be considered
to create separate buildings for the purpose
of automatic fire-sprinkler system
requirements as set forth in Chapter 38,
Section 505(e)6.
EXCEPTION: Buildings separated by continuous
area separation walls of four-hour fire-
resistive construction without openings.
Buildings required to have automatic fire-
sprinkler protection as set forth in Section
13113 of the Health and Safety Code (homes for
children or the aged) are prohibited from
using area separation walls in lieu of
automatic fire-sprinkler protection.
In educational occupancies, storage and
janitor closets shall be of one-hour fire-
resistive construction with openings protected
by assemblies having at least a three-fourths-
hour fire-resistive rating. Section 802(c).
. Section 1807 should be reviewed for all high-
rise buildings.
The exception in Section 3318 of the UBC has
been revised so as to allow the omission of
panic hardware at the main exit in churches
(by using signage), only when the occupant
load of the church is less than 300.
If emergency warning systems are required,
they shall activate a means of warning the
hearing impaired. Flashing visual warnings
shall have a frequency of not more than 60
flashes per minute.
1/23/92
The jurisdiction has contracted with Esgil
Corporation located at 9320 Chesapeake Drive, Suite
208, San Diego, California 92123; telephone number
of 619/560-1A68, to perform the plan check for your
project. If you have any questions regarding these
plan check items, please contact _
F^fSt at Esgil
Corporation
Thank you.
Enclosures:
1.
2.
3.
TYPE.AT A LI AJ
/^ AW TV/A/
/IA/O L f ;/?, t?v/=> A 7
Cf IL.f S
T\+f.
<^& )
1/23/92
MECHANICAL, PLCKBIHG, ENERGY
PLAN OORKECnOH SHEET
X? /ft DATE:
FLAN CHECK NUMBER:
GLEN ADAHEK
PLAN CHECKER:
D
;/T A- •
C.
C, ^ 7*c,.30 g
5 r
5
VIto01oo13
CJrtUHH
OQ)D.W
TJCd
mr-l
^
C~Mr~~w
Jj
0)>o
•a ••0) AJ3 CO
rH Ed> aX)
O AJ
D Od ccdUJ UrH
CJ 10•a uo eE 001 SLi OLi•rt
C 3Q) o<x: ai
S rf
rt <3
*0 Q)
0) AJAJ dp. a!
•SI rlo ood -orH01 3XI 0
O If)
AJ Co10 H
01 AJrt d
AJ rH
I-H EQrt <D0 LidUj01
**+AJ ZJCCJ X)f-H 13
d rt> »rt
cr o)01 Ucu dS rt
O I-H
rH p.rH §rd oUSd AJ
r-l O
rta IHx: AJH w
«
I-H
LiO
rHduH
W>>x:CX.
01Lld
0)
Ll
0)
taw0)rH
•o. C)
P, >-rt rtx: d10 3•oLl 01d xi
AJo o
rH C
X! §d dc oo(0 10d 10
01 01Ll UC 03 •<
•CJ
W C >>tO Q) Xtai x;0 S T3U / 01d / >. rtrH 5) (rt.
rH y £
3 CUH d Ort LlLl -H CQ
<1> D.x: & cJJ O Ort o rt0) j-ldM C AJC O rtH rt rH•a AJ rtrt [3 ot> AJ d2-rt UH
rHD, H AJa cAJ nj Q]C UH I-Hoi rai- jj >0 C rtLi ai 3
P, r-t CTd at
AJ >d rt53 -0cr co dM
I- LiO O Wrt M
H 0) 01Ll O 0d c oxi d drt
i-H rHd p, x!on if 3
t» O O~< o .a
S
>>A
•a01Llrt3cr0)Ll
(0rt
COrtAJdortUHrt
AJdLi
•*
rHd
rt
Ort
UHUH
O
AJC •01 -0e LI01 du oLl «0i-t M
C rH0) CQ
01ffl a.
XJ 0,3 <
•o
S
5
rHd3
01x:H
,.
uLl
OOrHUH
Li01
O,4
•o
Ll<0 01C f\O 0.rt =)• AJto ptJ e L,MOOO X UHO 0)E wB -u ca: c od rta: u§tn rtc: >o oCt, -rt Ll1 AJ 0,rH QH 01iJ UP x£ W rH
1 *>> w
•-H C0) OAJ -rtd AJ> drt JJ
Lt Mp.CJC OM rt
= £01
» MAJrt Q]
Xi rH3 CJrt
J3
(0 0)
>1 >13Ifl Ll0)
00m c
• 0)m wu-l too\ dON ClirH•aC 01O rtrt LlAJ 0O AJ
0) 10W 1rt
Cl AJ•a -HO 3u e
>> TJ
AJ 0)
0) T3UH Cd 3u UH
* Ll rH
M O 01c >O M 0)
0) Ll rH00 O
Ll O -03 rH C
M UH 3OTJ * LiSO) M•oo0 IH10 a
U IH
rt rt oo x; o
rt A4 rHU] UHX 0x: AJ
O. 4Jto
AJ LlUH U rtO Q) UH
r^
XI CUW 3 X!0) 10 3O
rt -V ^UH 10 oUH 00 rHO C a)-3 -°
S H 1ej 3 d
AJ X)C 01Q) >
O Q) O0 X!00 rt piC (wrt UH u)
O. O rHP. 0)o -a >x: c £W fl rH
IH UO L<JJ O(3 O
> rH
0) UH
rH
0) X!
UL, 3O W
t o•^
L> (0
(/](3 0)
OUH Urt ffl
W UAJ rt
C rH0) Xi
S 3S o,LiH 0)
3 TJCf rt01 >b OLiO Q,W
O O5 *o
E -•0 XIL. d
UH rHrtAJ dC, >s do
X -J01 O
01LI tad rt
C L,H O
* WAJ Llffl O
X! OAJ rHUH
10>j *d wW 00c•rt
•J3 T3
U1 rHO rta« 3t-l XI
cO -DH C)AJ rtU Li01 O
W AJ10
at rt
*O AJ
O rH0 i
>.AJ -a01 09VH -a« stO 3r UH• 13 1M e >.i-H d rH
CJ 0)> x: AJa) 3 d-H i-H >
d rtLi CD Lio s P.
^N
AJ rHfrHd
X UH
01 O
0 CLl 0
d rt
AJ
--H Li01 O> a,01
rH Cl
rH
TS J3S S3 CO OIH tooo d01
Ll IHO13Ll
OO UH
rH rtUHto
AJ AJM CLi 01
UH 5
L(
ffl rt
5 g.01Li0)>O 01XI tod ai
u 3
rrta ^
> 0a LIrH UH
•o -a0) Cci ra
o•a AJcflj Q)
>-HAJ X)x: rt00 103 10O Q)10 Oora>,
-H 0)
rH Lltj d
6 000 CC rt•o
tl) rH
C rt03 =rt XIAJ (0d d cT3 O2 x; wB O IH630)O M Q,o ^O T3
13 C 01rt -H
XI•yg o d
6 rt U]
d rH rtja -a
ifl 34) p. >iH XI
AJrt O O
-* XI rHrt Zi Xlo d(3 >> 10UH Xi 3
o
craLl
a:
6
10 Cc d
liance is required for remodels including:I"oy
10Ul01Uod
rH
rH
.?ravel to remodeled area.ingsrdsAJ M M dIH -H NUH ra ra _do a, & X
5 ^ ^d d x) o
.
rH Rampssatorsntrance to remodeled area.ancesDoorsfacilities serving remodeled area.fountains and telephones serving remodeled area.X> d. > O Li AJU E 5 AJ rt >, 003d—">.CXLiCoortJ LI u) w nj rtSAJ J£rt C
•^jCJUnLidXidiH
• • •cs ri -3
inn
»
CVJf--
V»
P
tnw_a
^coc
au
•rt
rH§•oo
to100)uud
mn•9•>
NI-.
V*
1Jj
W100)t-H
J-Jd
-oCJ3
d
<DLid
M
rH
O"Uo
0)Li
CCJ to the specific area being remodeled when an•a01j->
rt
Srt
rH
01XI
>»s dship is determined by the enforcing agency.LId£
03l-H.aSoto"?01Li termination of unreasonable hardship shall beForm HCA-1, which shall be filed in the projecto•o
o
tHUH 01 0)IQ "CJ «— Ij-i d rt
CO c **H
.
rH required work outside of the remodeled area (l.a0)
AJ
C
0)
.N
oAJ•a
1
U-lo
J-ltoou
0)5
«*Hogi~H
10TJ0101UXQ)
0)
OXI(3
W
i-H
fOUt
5 n the remodeled area, an unreasonable hardshiprt
0)
O•o
01,a found to exist (criteria is staff guideline).01XI
rH
rHdJZw sonable hardship finding may be by observation13ClIH
01£
.
C*l
W
Ort
JHO
0)5
JH•rt
rl
O
V)
<U
tJ
•ar- 1
Qx;n
frt
Sn:
ou.
V)3
Ort>J3
O
CQ)
i
TITLE 24 HANDICAPPED ACCESS CORRECTION LIST
Jurisdiction
Plan Check No.
References to section numbers with prefix "2" are to Title 24, California Code of Regulations, Part 2
(California Building Code), Prefix "3" is for Part 3 (California Electrical Code). Prefix "5" is for
Part 5 (California Plumbing Code).
Exemptions claimed for any item shall be requested in writing and shall include all data needed to
determine "unreasonable hardship" as described in Section 2-422.
SITE DEVELOPMENT
HANDICAPPED PARKING SPACES
a. Provide _handicapped spaces,
0
2-7102(b)
b. Space shall be so located that
handicapped persons are not compelled to
wheel or walk behind parked cars other
than his/her own. 2-7102(c)
c. Parking space shall be a minimum of 9
ft.xlS ft. with adjacent marked 5 ft.
loading zone. Double space shall be 23
ft. wide. Where a single space is
provided, the loading/unloading zone
shall be on the passenger side of the
vehicle. 2-7102(c),
d. Maximum slope of parking surface in any
direction shall not exceed 1/4" per
foot. 2-7102(e).
e. Parking space(s) shall be identified
with the International Symbol of
Accessibility on reflectorized sign
affixed to post or wall, and also
duplicated on parking surface (symbol to
be 36"x36" and painted at the back of
the parking stall). 2-7102(f)
f. Entrance to parking area (or at each
stall) shall have a sign stating that
unauthorized vehicle(s) parking in
handicapped space(s) may be subject to
tow-away. 2-7102(f)
g. If covered parking is provided, then a
reasonable portion of the total number
of stalls reserved for the disabled
shall also be covered. 2-7102(a)
h. Entrances to and vertical clearances
within accessible levels of parking
structures shall be 8 ft. 2 in. to anystructural member, duct or pipe.
2-7102(g)
CURB RAMPS
a. Curb ramps shall be located wherever
pedestrian path crosses curb. (2-
7l03(a))
b. Curb ramp shall be 48" mm. width (2-
7l03(b)) with maximum slope of 1 in 12.
2-7103(d)
c. A level 48" mm, depth landing is
required at top of curb ramps over
entire curb ramp width. 2-7103(d)
d. If no landing is provided, the slope of
flared sides shall not exceed 1 in 12.
2-7103(d)
Surface is to be slip
contrasting finish
sidewalk. 2-7103(f)
resistant and a
from adjacent
f. Border markings shall be 12" wide of
l/4"xl/4M grooves, 3/4" apart, located at
top and sides. 2-7103(h)
WALKS
a. Site development and grading shall be
designed to provide access to primary
entrances and access to normal paths of
travel and where necessary to provide
access shall incorporate pedestrian
ramps, curb ramps, etc. 2-7101(a)
b. Walks sloping greater than 5% (1 in 20)
Bust comply with ramp requirements of
Sec. 2-3307. 2-3325(c)
c. Walk width shall be 48" minimum, and
shall have slip-resistant surfaces.
2-3325(a)
d. The maximum cross slope shall not exceed
1/4" per foot. 2-3325(a)3
e. Gratings are not allowed whenever
possible. 2-3325(b)
f. At each gate or door a 60"x60" level area
is required when the gate swings toward
the walk. 2-3325(e)
g. A 48"x44" deep level area is required
when the gate swings away from the walk.
2-3225(e)
h. A 24" clear space is required at strike
side of gate or door. 2-3325(e)
PEDESTRIAN RAMPS
a. A path of travel with a slope greater
than 1 in 20 shall be considered a ramp.
2-3307(a)
b. The maximum slope shall be 1 in 12.
2-3307(c.l)
c. The width shall be 48" minimum. A
minimum width of 60" is required where a
ramp serves as a primary entrance to
buildings having an occupant load of 300
or more. Group R Occupancies may be 36"
when the occupant load is 50 or less. 2-
3307(b.l)
d. The surface of ramps shall be slip-
resistant. 2-3307(g)
e. A 60" intermediate landing is required
at maximum elevation change of 30" and
72" landing at each change of direction
(over 30 degrees). 2-3307(d.l)
f Landings are required at top and bottom
of ramps. 2-3307(d.l)
g. Bottom landing shall be minimum of 72"
in the direction of travel. Fig. 2-33-
11A
b. Headroom of
maintained for
etc. 2-522(f)
80" minimum shal1 be
walks, corridors, aisles,
h. Top landing
2-3307(d.l)
shall be 60" x 60" minimum.
i. When door swings onto top landing,
minimum depth of landing required is
door width plus 42". 2-3307(d.l.)
j. Top landing shall have 60" mm. width
when door swings onto the landing, with
24" on strike side of door at exterior
ramp, or 18" at interior ramp.
2-3307(d.l)
k. Ramp handrails are required on each side
of ramp, when slope exceeds 1 in 15. 2-
3307(e.l)
1. Ramp handrails shall be continuous,
located 30"-34" m height above ramp
surface, with 12" extensions beyond top
and bottom, and the ends returned.
2-3307(e.l)
m. Handrails shall be 1-1/4" to 2" cross
section, spaced minimum of 1-1/2" from
wall. 2-3307(e.l)
n. A 2" high curb or wheel guide rail
centered 3" ± 1" above ramp surface is
required on both sides where not
otherwise bounded by walls when the ramp
exceeds 10 feet in length.
2-3307(h.l)
SPECIAL ACCESS LIFTS
a. Lifts may be provided between levels, in
lieu of elevator, when the vertical
distance between landings, structural
elevator, structural design and
safeguards are as allowed by the State
of California, Department of Industrial
Relations, Division of Occupational
Safety and Health. 2-5107(a)
b. The lift platform shall be of sufficient
size to accommodate a wheelchair
(30"x48"). 2-5107(a)
c. There shall be a level and clear floor
area or landing (60"x60") at each level
for access to the lift. 2-5107(a)
HAZARDS
a. Provide 80" headroom from walkway
surface to any overhanging obstruction.
2-3326(b)
c. Protruding objects with leading edges
between 27" and 80" above finished floor
shall not protrude more than 4" into
walks, corridors, etc. 2-522(f)
d. Free standing objects mounted on posts
between 27" and 80" above the floor may
project a maximum of 12". 2-522(f)
e. Abrupt changes in level exceeding 4"
adjacent to walks, except between walks
and adjacent streets or drives, shall be
identified by 6" high warning curbs above
walk surface. 2-3326(a)
ENTRANCES AND CDtCOLATIOH
7'.) ENTRANCES, DOORS, VESTIBULES AND CORRIDORS
(. All primary entrances to buildings shall
be accessible to the handicapped.
2-3301(f)
/. All required passage doors shall have 32"
clear opening at 90 degrees (36" door).
2-3304(f)
At least one of a pair of doors shall
meet the minimum 32" clear entrance width
requirement. 2-3304(f)
s*~^\_( d. /Threshold shall be no higher than 1/2"
i the floor. Edge to be beveled with
a slope no greater than 1 in 2, if more
than 1/4". 3304(i.l)
e. txterior level landing may slope up to
^—•xl/4" per i foot in any direction for
surface drainage. 2-413
f.lDoor hardware shall be of the lever or
>—/push type, mounted 30" to 44" above the
floor and be operable with a maximum
effort of 8.5 Ibs. for exterior doors and
5 Ibs. for interior doors. 2-3304(c), 2-
3304(i.2)
lower 10" of the door shall be of
smooth, plane surface (no recess or trap)
except at automatic and sliding doors.
2-3304(i.3)
f—TVI hyBuilding entrance(s) shall be identified
— by sign with the International Symbol of
Accessibility. Show location on plan.
The symbol shall be a white figure on
blue background. 2-522(b)
At turnstile, provide an access gate, 32"
clear width opening, within 30 feet of
turnstile. 2-3304(i.4)
There shall be a clear area on each side
of door, 60" deep in direction of door
swing and 44" deep in opposite direction
of door swing. 2-3304(i.l)
k./Width of clear area on the swing side ofV •'the door shall extend 2V past strike
jamb for exterior doors and 18" past
strike jamb for interior doors.
2-3304(i.l)
ALL
The space between two consecutive doors
(vestibule) shall provide a minimum of
48" clear depth between the open door
and a second closed door.Doors in a
series at a vestibule shall swing in the
same direction, or away from the space
between them. 2-3304(i.l)
For corridors over 200 feet long, see
special requirements of Sec. 2-3305(b)2.
8/ FLOORS
X- Floors of a given story shall be a
common level throughout or shall be
connected by pedestrian ramps, passenger
elevators, or s pecial access lifts.
2-522(e)
STAIRWAYS
NOTE: Only applies where disabled access is
provided or required to other levels.
a. Treads shall have smooth, rounded
exposed edges and be slip resistant. 2-
3306(s)
b. Nosing shall not project more than
1-1/2 inches past face of the riser
below. 2-3306(s)
c. Risers shall be sufficiently solid.
2-3306(s)
d. The upper approach and lower tread of
each flight of stairs shall be marked
with a contrasting colored strip 2" in
width. 2-3306(r)
e. On exterior stairs, each tread shall be
marked as noted above. 2-3306(r)
f. Handrails are required on each side of
stairway. 2-3306
g. Handrails shall be located 30" to 34"
above nosing,extend 12" beyond top riser
and 12" plus tread width beyond bottom
nosing and returned to wall/newel post.
2-3306(j.l).
h. Handrails shall be 1-1/4" to 2" in
gripping cross section and 1-1/2" clear
of vail. 2-3306(j.l)
Approved stairway identification signs
shall be located at each floor level in
all enclosed stairways in buildings two
or more stories in height. The sign
shal1 identify the stairway, indicate
whether there is roof access, the floor
level, and the upper and lower tenninus
of the stairway. The information shall
be presented using raised Arabic numerals
and raised braille symbols which conform
to Section 522(b)3. The sign shall be
located approximately 5 feet above the
floor landing immediately adjacent to the
door on the strike side. Signs shall
comply with requirements of U B C.
Standard No. 33-2.
Iff. ELEVATORS
a. Provide clear inside elevator car
dimensions as required by U.B.C. Section
5103(d) 6 and Title 24 2-S103(d.l).
1. At least one elevator in buildings 4
or more stories in height: 80" by
54", with a 42-inch side slide door.
Applies only to: high-rise buildings,
A/E/I occupancies, State-owned
buildings, residential care homes,
hotels, motels, apartments and
condominiums.
2. Elevator in buildings more than two
stories or buildings where disabled
access is required to upper level(s):
68" by 54", with a minimum clear door
width of 36".
3. Elevators other than in (b) above
serving less than 50 occupants shall
have a minimum inside platform of 4
feet 6 inches by 4 feet 6 inches and a
minimum clear door width of 36 inches.
b. Raised Braille markings and Arabic
numerals are required on control buttons
and door jambs. 2-5103(d.l)
SAHUARI FACTT.TTTKS
TOILET FACILITIES ACCESS
When located on accessible floors,
sanitary facilities shall be made
accessible to physically handicapped.
(2-511.l(a))
Doorways shall have 32'
opening width. 2-511.1
minimum clear
£. There shall be a level area with 60"
clear depth in the direction of the door
swing, and a level area with 44" clear
depth in opposite direction of door
swing. 2-511.l(a)
MULTIPLE ACCOMMODATION TOILET FACILITIES
Provide clear area
high - or clear space
high. 2-511.l(a)
60" diameter x 27"
56" x 63" x 27"
Doors (other than handicap compartment)
are not to encroach more than 12" into
above mentioned clear space.
2-511. l(a)
Provide a 28" clear space between water
closet and fixture or 32" clear space
between water closet and wall.
2-511. l(a)
A 48" long clear space is required in
front of water closet. A 60" clear
space is required when the toilet
compartment has a side door.
Water closet compartment door to provide
32" clear width for end entry and 34"
clear width for side entry. Door to be
self-closing. 2-511. l(a)
3. SINGLE ACCOMMODATION TOILET FACILITIES
Water closet shall be located 28" from a
fixture or 32" from a wall. 2-511.l(a)
Minimum clear space in front of *ater
closet shall be 48". 2-511.l(a)
In an existing building, a single
accommodation toilet facility may have a
space 36" wide x 48 " long in front of
water closet. 2-511.l(a)
GRAB BARS AT WATER CLOSET
One at side 42" long extending 24" in
front of water closet; one at rear 36"
long centered on water closet; both
mounted 33" above floor. Where a tank-
type toilet is used, grab bar may be as
high as 36". 2-511. l(a)
Bars shall be 1-1/4" to 1-1/2" in
diameter with 1-1/2" clearance to wall.
2-511. l(a)
Bar fasteners and mounting support shall
be able to withstand 250 Ibs./ft. in
bending, shear and tension.
2-511. l(a)
15.WATER CLOSET
a. Height of water closet seat shall be 17"
to 19" above floor. 5-1502
b. Controls shall be operable with one
hand, and shall not require tight
grasping, pinching or twisting of the
wrist. 5-1502
c. Controls for the flush valves shall be
mounted on the wide side of toilet
areas, no more than 44" above the floor.
5-1502
d. The force required to activate controls
shall be no greater than 5 pounds force.
5-1502
. URINALS
Where urinals are provided, the run of at
least one shall project 14" from the wall
and be located 17" maximum above floor.
5-1503(a)
'. The force required to activate the flush
valve shall be 5 Ibs. maximum and located
44" maximum above floor.
5-1503(b)
:. Provide 30" x 48
forward approach.
clear floor space for
2-511. l(b)
( 17^LAVATORIES
/. Provide 30" x 48" clear floor space for
forward approach. Said clear floor space
may include knee and toe space under
lavatory described below.
2-511.l(b)
b.lProvide clear space beneath lavatories
V X29" high by 30" wide by 8" deep at top
and 9" high by 30" wide by 17" deep at
bottom from front of lavatory (toe
space). The maximum counter surface
height should be 34". 5-1504(a)
underc.Hot water and drain pipes
lavatories shall be insulated.
5-1504(b)
Faucet controls and operating mechanism
(operable with one hand) shall be of the
type not requiring tight grasping,
pinching or twisting of the wrist (such
as lever-operated) and an operating force
not exceeding 5 Ibs. 5-1504(c)
e.Olf self-closing valves are used, they
V / shall remain open for at least 10
seconds. 5-1504(c)
18.JTOILET ROOM ACCESSORIES
a. Mirror bottom edge shall be located 40"
maximum above floor. 2-511.l(b)
b. Toilet tissue dispensers shall be mounted
within 12" from the front edge of toilet
seat. 2-511.l(b)
c. Operating parts of dispensing and
disposal fixtures (towels, waste, coin
slots, etc.) shall be within 40" of
floor. 2-511.1(b)
S^\f 19 J SANITARY FACILITIES IDENTIFICATION
a. On doorways leading to sanitary
facilities the symbols to be provided are
12" Equilateral triangle for men, 12"
diameter circle for women, and 1/4"
thick, centered on door, 60" high and
contrasting color. Unisex facilities
shall be identified by the circle with
the triangle superimposed within the
circle. 2-511.l(a)
H OCCUPANCY REQUIREMENTS
Accessible sanitation facilities m all
Group H Occupancies shall be provided as
specified in Chapter 2-5. 2-913(a)
Accessible floors and levels shall
comply with the requirements specified
in Chapter 2-5. 2-913(a)
Employee work areas shall be accessible
by means of a 36-inch minimum aisle
width, and a 32-inch minimum clear
opening door width 2-913(a)
ADDITIONS, ALTERATIONS AND REPAIRS TO EXISTING
(2-110A(b)ll)
area of specific addition, alteration
and/or repair, shall comply with the
provisions of Title 2k. Additionally:
a. The primary entrance to the building and
path of travel to the specific area
shall be accessible to the handicapped
persons.
Compliance must be shown, beginning from
the existing parking area and leading to
the area of alteration.
b. Existing restrooms, water fountains, and
public telephones which serve said
specific area must be shown to be
accessible to and functional for
handicapped persons.
c. Information regarding handicapped
accessibility shall be posted in lobby
per Sec. 2-522.
DOCUMENTATION OF UNREASONABLE HARDSHIP - -
Job Address Plan Check No_
Owner Date
It is requested that the above named project be granted an exception from
the requirements of the State of California Title 24 handicapped
accessibility provisions, as specifically noted below:
1. EXCEPTIONS REQUESTED ESTIMATED COST OF ITEMS TO BE EXEMPTED
2. The cost of all construction without excepted items, is: ._
3. The impact on financial feasibility of the project, if the requestedexception is not approved is: .
4. The facility is used by the general public for-the purpose o£:
5, The exceptions being requested will not penalize handicappedaccessibility as equivalent facilities are available as follows:
6. Exceptions requested, and data provided, by
NAME
AJJJJKttbb
Ja-UiNATUKE'• I XELE^iiUNE
Department Use Only
Findings and Decision of the Enforcing Official:
Signature of Enforcing Official Date
HA-1 010190
Date i Jurisdiction CARLSBAD
Prepared byi
P£TE. rat "** VALUATION AND PLAN CHECK JFEE
Bldg. Dept.
Esgil
PLAN CHECK K0._ 9
BUILDING ADDRESS
APPLICANT/CONTACT
BUILDING OCCUPANCY
TYPE OF CONSTRUCTION
PHONE NO.
&Z,DESIGNER PHONE
CONTRACTOR PHONE
BUILDING PORTION
M-»tDiOV- O F-f=-
Air Conditioning
Commercial
Residential
Res. or Comm.
Fire S-orinklers
Total Value
BUILDING AREA
loos'
VALUATION
MULTIPLIER
-? r-C>o
@
0
e
VALUE
3>T/7^
3r /7S~
Building Permit Fee $.
Plan Check Fee $$ 2-/0
C 0 H H E N TS
SHEET OF
12/87
City of Carlsbad
DATE -4- 4UQ 92.
BUILDING ADDRESS I IfD
Engineering Department
BUILDING PLANCHECK CHECKLIST
PLANCHECK NO CB 92-^
V//LI AC
PROJECT DESCRIPTION CftM TT
ASSESSOR'S PARCEL NUMBER-EST VALUE
ENGINEERING DEPARTMENT
APPROVAL
The item you have submitted for review has been
approved The approval is based on plans,
information and/or specifications provided in your
submrttal, therefore any changes to these items
after this date, including field modifications, must
be reviewed by this office to insure continued
conformance with applicable codes Please review
carefully all comments attached, as failure to
comply with instructions in this report can result in
suspension of permrt to build.
DENIAL
attached report of deficienciesPlease see theJ-vmarked withj^l Make necessary corrections to
plans or specifications for compliance with
applicable codes and standards Submit corrected
plans and/or specifications to this office for review
By S.SGHEDELL Date-
By
By
Date
Date
BY:
FOR QFRCAL USE ONLY
AUTHORIZATION TO ISSUE BUlLDlNO PERMIT:
DATE
ATTACHMENTS
O Dedication Application
d Dedication Checklist
CH Improvement Application
C3 Improvement Checklist
[_] Future Improvement Agreement
CONTACT PERSON
NAME
ADDRESS.
PHONE
P \doc*Vchkl»t\bpOO01 .frm REV 6/5/92
2O75 Las Palmas Dr • Carlsbad, CA 92OO9-1576 • (619) 438-1161 - FAX (619) 438-O894
BUILDING PLANCHECK CHECKLIST
SITE PLAN
IsV 2nd\/ 3rd\/
0 D n 1. Provide a fully dimensioned site plan drawn to scale Show
A North Arrow D. Property Lines Easements
B Existing & Proposed Structures E Easements
C Existing Street Improvements F Right-of-Way Width & Adjacent Streets
D D D 2 Show on site plan
N/ft
A Drainage Patterns C Existing Topography
B Existing & Proposed Slopes
D D D 3 Show on a section drawing or include a note stating that there is a minimum of 6"
difference between the finished floor and the finished grade elevation adjacent to the
structure
D D CI 4 Include note "Surface water to be directed away from the building foundation at a 2%
gradient for no less than 5' or 2/3 the distance to the property line (whichever is less)"
[Per 1985 UBC 2907(d)5]
*On graded sites, the top of any exterior foundation shall extend above the elevation
of the street gutter at point of discharge or the inlet of an approved drainage device
a minimum of 12 inches plus two percent" (per 1990 UBC 2907(d)5.).
D D 5 Include on title sheet
A Site address
B Assessor's Parcel Number
C. Legal Description
For commercial/industrial buildings and tenant improvement projects, include. Total
building square footage with the square footage for each different use, existing sewer
permits showing square footage of different uses (manufacturing, warehouse, office,
etc.) previously approved
EXISTING PERMIT NUMBER DESCRIPTION
-. 212. EMGu 0-fB2kUsrso.oo/urorr TO
P:\docs\chkist\bpoooi.frm Page 1 of 4 REV 6/5/92
1 BUILDING PLANCHECK CHECKLIST
H/A DISCRETIONARY APPROVAL COMPLIANCE
1stv/ 2ndv/ 3rcK/
D D D 6 Project does not comply with the following Engineering Conditions of approval for
Project No
Conditions were complied with by. Date
DEDICATION REQUIREMENTS
D D 7. Dedication for all street Rights-of-Way adjacent to the building site and any storm
drain or utility easements on the building site is required for all new buildings and for
remodels with a value at or exceeding $ -pursuant to Code Section
1840030
Dedication required as follows
Attached please find an application form and submittal checklist for the dedication
process Provide the completed application form and the requirements on the
checklist at the time of resubmittal
Dedication completed by Date
IMPROVEMENT REQUIREMENTS
D D D 8a. All needed public improvements upon and adjacent to the building site must be
constructed at time of building construction whenever the value of the construction
exceeds $ -pursuant to Code Section 18 40 040
Public improvements required as follows
Please have a registered Civil Engineer prepare appropriate improvement plans and
submit them together with the requirements on the attached checklist for a separate
plancheck process through the Engineering Department Improvement plans must be
approved, appropriate securities posted and fees paid prior to issuance of permit
Attached please find an application form and submittal checklist for the public
improvements requirements Provide the completed application form and the
requirements on the checklist at the time of resubmittal
Improvement Plans signed by Date
P:\doct\chktet\bp0001.frm Page 2 Of 4 REV 6/5/92
BUILDING PLANCHECK CHECKLIST *
1st/ 2ndv/ 3rd\/
D D CI 8b. Construction of the public improvements may be deferred pursuant to code Section
18.40 Please submit a recent property title report or current grant deed on the
property and processing fee of $ so we may prepare the
necessary Future Improvement Agreement This agreement must be signed, notarized
and approved by the City prior to issuance of a Building Permit
Future public improvements required as follows
D D 8c Enclosed please find your Future Improvement Agreement Please return signed and
notarized Agreement to the Engineering Department
Future Improvement Agreement completed by
Date
D D D 8d No Public Improvements required SPECIAL NOTE' Damaged or defective
improvements found adiacent to building site must be repaired to the satisfaction of
the City Inspector prior to occupancy
GRADING PERMIT REQUIREMENTS
The conditions that invoke the need for a grading permit are found in Section 11 06 030
of the Municipal Code <
D D D 9a Inadequate information available on Site Plan to make a determination on grading
requirements Include accurate grading quantities (cut, fill import, export)
D D EH 9b Grading Permit required A separate grading plan prepared by a registered Civil
Engineer must be Submitted together with the completed application form attached
NOTE The Grading Permit must be issued and rough grading approval obtained prior
to issuance of a Building Permit
Grading Inspector sign off by Date
0 D Q 9c No Grading Permit required
BUILDING PLANCHECK CHECKLIST
P \docs\chklst\bp0001 frm Page 3 Of 4 REV 6/5/92
MISCELLANEOUS PERMITS
2ndv/ 3rd>/
D D 10. A RIGHT-OF-WAY PERMIT is required to do work in City Right-of-Way and/or
. private work adjacent to the public Right-of-Way. Types of work include, but are not
limited to street improvements, trees, driveways
A separate Right-of-Way permit issued by the Engineering Department is required for
the following.
Please complete attached Right-of-Way application form and return to the Engineering
Department together with the requirements on the attached Right-of-Way checklist, at
the time of resubmittal
D D D 11 A SEWER PERMIT is required concurrent with the building permit issuance The fee
is noted in the fees section on the following page
D CH 12 INDUSTRIAL WASTE PERMIT is required Applicant must complete Industrial
Waste Permit Application Form and submit for City approval prior to issuance of a
Permit
Industrial waste permit accepted by Date
P-\doc»\chkl«t\bp0001.frm Page 4 Of 4 REV 6/5/92
CALCULATIONS WORKSHEET
EDU CALCULATIONS EDU's-
APT CALCULATIONS- A_DTs
N/A FEES REQUIRED-
WITHIN CFD.
D YES (NO BRIDGE & THOROUGHFARE FEE, REDUCED TRAFFIC IMPACT FEE)
DNO
D 1 PARK-IN-LIEU FEE
PARK AREA FEE/UNIT
D 2 TRAFFIC IMPACT FEE
ADT's FEE/ADT.
D 4 FACILITIES MANAGEMENT FEE•
ZONE FEE/EDU
D 5 PUBLIC FACILITIES FEE
D 6. SEWER FEES PERMIT No
EDU's FEE/EDU
BENEFfT AREA FEE"
7 SEWER LATERAL REQUIRED (2,500 DEPOSIT)
REMARKS
P:\doc«\chld«t\bp0001 trm REV 6/5/92
PLANNING CHECKLIST
Plan Check No. CB^2W?Address /Zfr7iT ,
Planner VAN LYNCH Phone 438-1161 ext. **325
(Name)
APN: 'Pc)fi-/9-Z- 30
41 V U Type of Project and Use ^^^^g" x.
Zone fL~r Facilities Management Zone /
Legend
u u o
C C CO <0 0
a. a. a.
Item Complete
Item Incomplete - Needs your action
1, 2, 3 Number in circle indicates plancheck number where deficiency was
identified
D Environmental Review Required: YES NO X TYPE
DATE OF COMPLETION: _^______
Compliance with conditions of approval? If not, state conditions which require action
Conditions of Approval
D D Discretionary Action Required: YES NO X TYPE
APPROVAL/RESO. NO. DATE:
PROJECT NO.
OTHER RELATED CASES:
Compliance with conditions of approval? If not, state conditions which require action.
Conditions of Approval
D D California Coastal Commission Permit Required: YES NO
DATE OF APPROVAL:
San Diego Coast District, 3111 Camino Del Rio North, Suite 200, San Diego, CA. 92108-1725
(619) 521-8036
Compliance with conditions of approval? If not, state conditions which require action.
Conditions of Approval . .
a Landscape Plan Required: YES _ NO
See attached submittal requirements for landscape plans
Site Plan:
LJ D
a
C1.D
D D
D
Zoning:
2.
3.
4.
Provide a fully dimensioned site plan drawn to scale. Show North
arrow, property lines, easements, existing and proposed structures,
streets, existing street improvements, nght-of-way width and
dimensioned setbacks.
Show on Site Plan: Finish floor elevations, elevations of finish grade
adjacent to building, existing topographical lines, existing and proposed
slopes and driveway
Provide legal description of property
Provide assessor's parcel number.
Setbacks:
p,
tyr
&UU
E^D,
sf — ~\
fopD
/DpD
*• — -/
*//t v Front: Required
' Int. Side: Required
Street Side. Required
Rear: Required
/\jo/Ct/Wf& 2 Lot coverage: Required
Ub/erffi**^ 3. Height: Required
4. Parking: Spaces Required
Guest Spaces Required
Additional Comments p£&££r £3&t//d& S&UA&&' ?£&T~%6&'
H&Q/Cdt- Oj^fcg'. fcl-mt)Jt* ) fbfL AAJ J6<&t&M&v'7~ 0f=-
ffl^ PfofJZS'^ £ n A(^So £*&?]///)& "JbTJOL- 3fel/js^T^ft$-~ o/^ £ty
/3iJ£ft-$KL&~ £>/J £"/7^£
Shown
Shown
Shown
Shown
Shown
Shown
Shown
Shown
' o£ &QCtf £J£&( of7?cer
f~777&" jQ(J$/£-A&/E/yt/ '
fcM.;/v(> <ZPsQc&\
OK TO ISSUE AND ENTERED APPROVAL INTO COMPUTER DATE
PLNCK.FRM
City of Carlsbad 92165
Fire Department • Bureau of Prevention
Plan Review: Requirements Category: Building Plan Check
Date of Report Friday, August 7,1992 Reviewed by OoXfcX Ac
Contact Name Mark Morrison
Address 1207 Carlsbad Vlg Dr Ste J
City, State Carlsbad CA 92008
Bldg Dept No 92-749 Planning No
Job Name Dr Robert Young
Job Address 1207 Carlsbad Village Ste or Bldg No I
Approved - The item you have submitted for review has been approved The approval is
based on plans, information and/or specifications provided in your submittal,
therefore any changes to these items after this date, including field modifica-
tions, must be reviewed by this office to insure continued conformance with '
applicable codes Please review carefully all comments attached, as failure
to comply with instructions in this report can result in suspension of permit to
construct or install improvements
Disapproved - Please see the attached report of deficiencies Please make corrections to
plans or specifications necessary to indicate compliance with applicable
codes and standards Submit corrected plans and/or specifications to this
office for review
For Fire Department Use Only
Review 1st 2nd 3rd
Other Agency ID
CFDJobtf 92165 File#
2560 Orion Way • Carlsbad, California 92008 • (619) 931-2121