HomeMy WebLinkAbout1281 MAGNOLIA AVE; ; CB020883; PermitW, 0 1 -2002
City of Carlsbad
1635 Faraday Av Carlsbad, CA 92008 99
Residential Permit Permit No: CB020883
Building Inspection Request Line (760) 602-2725
RAD Status: ISSUED
0 Applied: 03/25/2002
VN Entered By: JM
Plan Approved: 11/01/2002
Issued: 11/01/2002
0 Inspect Area:
Orig PC#:
Plan Check#:
0316 11/01/02 0002 01 02
Job Address:
Permit Type:
Parcel No:
Valuation:
Occupancy Group:
# Dwelling Units:
Bedrooms:
Project Title:
1281 MAGNOLIA AV CBAD
RESDNTL Sub Type:
2052803900 Lot#:
$30,336.00 Construction Type:
Reference #:
0 Structure Type:
0 Bathrooms:
FUNKHOUSER - DEMO EXIST GARAGE
NEW GAR 440 SF & RAD 192 SF
Applicant: Owner: COP 361.58
BLACKFORD ROY FUNKHOUSER DAVID R&MICHELE
3616 OXFORD STREET 1281 MAGNOLIA AVE
CARLSBAD CA 92008 ALSBDC 2O
760-729-0553
Total Fees: $523.14 / Total PaymentsTo Date:-' - $161.56'' // Balance Due: $361.58
Building Permit 7 \ $248.55'-, Meter Size 11, \ \ Addl Building Permit Fee , \ ' $0.00'..-. Add'l Red. Water Coin. Fee.-" C" \ $0.00
Plan Check / $161.56 Meter F664 \ \O $0.00
AddI Plan Check Fee/ 1'L. 7 $0.00 "SDCWA Fee '\ '-.--' \ $0.00
Plan Check Discount' --..Jj'- / _.CFD Payoff Fee ,,...._ -., ., $0.00
Strong Motion Fee ' r'- .
' / N$3.03 -PFF-. '\ i $0.00
Park in Lieu Fee -'---; / '$0.00. PFF (CFD Fund) (./ $0.00
Park Fee - - $0.00 Licénse Tax c' $0.00
LFM Fee ) $0.00 License Tax (CFI Fund) I $0.00
Bridge Fee I $0.00 I ,,Traffic Impact Fee f $0.00
Other Bridge Fee $000 Traffic lnpact (CFD Fund) / $0.00
BTD #2 Fee '-$0.00 Sidewalk Fee' -\''- I I $0.00
BTD #3 Fee \ $0.00 ' PLUMBING TOTAL"1 7 / $41.00
Renewal Fee \ \ \ $0.00 ELECTRICALTOTAL2, / $45.00
Add'I Renewal Fee \ "-.$O.00 MECHANICAL TOTAL / / $24.00
Other Building Fee \ $0.00 \Housin'g Impact Fee / / $0.00
Pot. Water Con. Fee \ $0.00 Housing InLieu Fee / / $0.00
Meter Size \ ,- NCO1 Master Drainage Fee' '-'-..., / $0.00
Addi Pot. Water Con. Fee'\ 1' ("•' $0.00 Sewer Fee \,..) / $0.00
Red. Water Con. Fee \ \, ..') $0.00-. Additional Fees $0.00
'J / •'' TOTAL PERMIT FEES" \ " / $523.14
\ '; ./
/7 F ,.• c\) /
1)) / FINAL APPROVAL
Inspector: r' Y'4 Date: _____________ Clearance:
NOTICE: Please take NOTICE At approval of your project includes the 'Imposition" of fees, dedications, reservations, or other exactions hereafter collectively
referred to as "fees/exactions." You have 90 days from the date this permit was issued to protest imposition of these fees/exactions. If you protest them, you must
follow the protest procedures set forth in Government Code Section 66020(a), and file the protest and any other required information with the City Manager for
processing in accordance with Carlsbad MunicipalCode Section 3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack
review, set aside, void, or annul their imposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection fees and capacity
changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this project. NOR DOES IT APPLY to any
fees/exactions of which you have previously been given a NOTICE similar to this, or as to which the statute of limitations has previously otherwise expired.
6 PERMIT APPLICATION
CITY OF CARLSBAD BUILDING DEPARTMENT
1635' Faraday Ave., Carlsbad, CA 92008
I FOR OFFICE USE ONLY
PLAN CHECK NO.
l.EST,. VAL. O%
Plan Ck. Deposit
I Validated Bv7\..
Addre'ss (include Bidg/Site#) ' Business Name (at this address)
Pô -T 9-T— 1041 (a A ' - -, -- -.
Legal Description Lot No. Subdivision Name/Number Uñif't46 Q67 N6d(A/.. T6tal # if.ijnits
46' & 1 V' C M J•4i Assessor s Parcel # ,
j 4 A
Existing se Proposed Use
',tO 4if iiüO 1'VLJ e 4tJr. Description of Work SQ.. FT. , I #of # of Be oms # of Bathrooms
[2, CONT ifff u) ,. .
ôxr 'i cvbfr2 cg
Name Address City State/Zip Telephone #7 Fax #
APPUCNT CnUacr A frcti D Cne7 Agè' fOn r 1i270 k7 71
OAO ktO-Mica& 1I wia p 14'D -Tels
Name Address ' City State/Zip Telephone #
Name Address - City State/Zip Telephone #
cONTRAQLQR'.cbMPANY&,NAME
(Sec. 7031.5 Business and Professions Code: Any City or County which requires a permit to construct, alter, improve, demolish or repair any structure, prior to its
issuance, also requires the applicant for such permit to file a signed statement that he is licensed pursuant to the provisions of the Contractor's License Law
[Chapter 9, commending with Section 7000 of Division 3 of the Business and Professions Code) or that he is exempt therefrom, and the basis for the alleged
exemption. Any violation of Section 7031.5 by any applicant for a permit subjects the applicant to a civil penalty of not more than five hundred dollars [$5001).
Name Address City State/Zip Telephone #
State License # ' License Class . City Business License #
Designer Name Address City State/Zip Telephone
State License # ,
QRC 1IPN'
Workers' Compensation Declaration: I hereby affirm under penalty of perjury one of the following declarations:
o •l have and will maintain a certificate of consent to self-insure for workers' compensation as provided by Section 3700 of the Labor Code, for the performance
of the work for which this permit is issued.
C3 I have and will maintain workers' compensation, as required by' Section 3700 of the Labor Code, for the performance of the work for which this permit is
issued. My worker's càmpensation insurance carriei and policy number are:
Insurance Company Policy No. Expiration Date___________________
(THIS SECTION NEED NOT BE COMPLETED IF THE PERMIT IS FOR ONE HUNDRED DOLLARS [$1001 OR LESS)
C] CERTIFICATE OF EXEMPTION: I certify that in the performance of the work for which this permit is issued, I shall not employ any person in any manner so as
to become subject to the Workers' Compensation Laws of California.
WARNING: Failure to secure workers' compensation coverage is unlawful, and shall subject an employer to criminal penalties and civil fines up to one hundred
thousand dollars ($100,000), in addition to the cost of compensation, damages as provided for in Section 3706 of the Labor code, interest and attorney's fees.
SIGNATURE DATE
I hereby affirm that I am exempt from the Contractor's License Law for the following reason:
I, as owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not intended or offered for sale
(Sec. 7044, Business and Professions Code: The Contractor's License Law does not apply to an owner of property who builds or improves thereon, and who does
such work himself or through his own employees, provided-that such improvements are not intended or offered for sale. If, however, the building or improvement is
sold within one year of completion, the owner-builder will have the burden of proving that he did not build or improve for the purpose of sale).
50 I, as owner of the property, am exclusively contracting with licensed contractors to construct the.project (Sec. 7044, Business and Professions Code: The
Iontractor's License Law does not apply to an owner of property who builds or improves thereon, and contracts for such projects with contractor(s) licensed
pursuant to the Contractor's License Law).
I am exempt under Section Business and Professions Code for this reason:
I personally plan to provide the major labor and materials for construction of the proposed property improvement.,,S'ES ONO
I (have I have not) signed an application for a building permit for, the proposed work. '
I have contracted with the following person (firm) to provide the, proposed construction (include name / address / phone number / contractors license number):
I plan to provide portions of the work, but I have hired the following person to coordinate, supervise and provide the major work (include name / address / phone
number / contractors license number):
I will provide some of the work, but I have contracted (hired) the following persons to provide the work indicated (include name / address / phone number / type
of work):
R0PERTY OWNER SIGNATURE ' - DATE Foz
- I
Is the applicant or future building occupant required to submit a business plan, acutely hazardous materials registration form or risk management and prevention
program under Sections 25505, 25533 or 25534 of the Presley-Tanner Hazardous Substance Account Act? 0 YES 0 NO
Is the applicant or future building occupant required to obtain a permit from the air pollution control district or air quality management district? 0 YES, 0 NO
Is the facility to be constructed within 1,000 feet of the outer boundary of a school site? 0 YES 0 NO . .
IF ANY OF THE ANSWERS ARE YES, A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR IS MEETING THE
REQUIREMENTS OF THE OFFICE OF EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT.
j * -
I hereby affirm that there is a construction lending agency for the performance of the work for which this permit is issued (Sec. 30970) Civil Code).
LENDER'S NAME . - LENDER'S ADDRESS__________________________________________________________
LICLcERIjFjCAnON
I certify that I have read the application and state that the above information is correct and that the, information on the plans is accurate. I agree, to comply with all
City ordinances and State laws relating to building construction. I hereby authorize representatives of the Cit' of Carlsbad to enter upon the above mentioned
property for inspection purposes. I ALSO AGREE TO SAVE, INDEMNIFY AND KEEP HARMLESS THE CITY OF CARLSBAD AGAINST ALL LIABILITIES,
JUDGMENTS, COSTS AND EXPENSES WHICH MAY IN ANY WAY ACCRUE AGAINST SAID CITY IN CONSEQUENCE OF THE GRANTING OF THIS PERMIT.
OSHA: An OSHA permit is required for excavations over 5'0" deep and demolition or construction of structures over 3 stories in height.
EXPIRATION: Every permit issued by the building Official under the provisions of this Code shall expire by limitation and become null and void if the building or work
authorized by such permit is not commenced within 180/eyys from the date of such permit or if the building or work authorized by such permit is suspended or abandoned
,at any time after the work 1s comnq,ced JNr "p0drol 1POAdqns (Section 106.4.4 Uniform Building Code). -
APPLICANT'S SIGNATURE MAU "&. Vbt7'4 )ML40TjfPL' DATE 40 MM- o'2._
) WHITE: File YELLOW: Applicant PINK: Finance ,
City of Carlsbad Bldg Inspection Request
For: 06/14/2004
Permit# CB020883
Title: FUN KHOUSER - DEMO EXIST GARAGE
Description: NEW GAR 440 SF & RAD 192 SF
Type: RESDNTL Sub Type: RAD
Job Address: 1281 MAGNOLIA AV
Suite: Lot 0
Location:
APPLICANT BLACKFORD ROY
Owner: FUNKHOUSER DAVID R
Remarks:
Total Time:
Inspector Assignment: PY
Phone: 6199949592
Inspector:
Requested By: DAVE
Entered By: ROBIN
CD Description
19 Final Structural
29 Final Plumbing
39 Final Electrical
49 Final Mechanical
Comment
Associated PCRs/CVs
Inspection History
Date Description Act Insp Comments
11/13/2003 89 Final Combo NA PY EXTEND PERMIT
08/27/2003 31 Underground/Conduit-Wiring AP JIM CWB TO WATER SERVICE OK
06/19/2003 82 Drywall/Ext Lath/Gas Test AP PY
06/17/2003 16 Insulation AP PY
06/13/2003 84 Rough Combo AP PY
04/24/2003 13 Shear Panels/HD's AP JE
04/24/2003 15 Roof/Reroof AP JE
04/11/2003 13 Shear Panels/HD's AP PY
04/09/2003 15 Roof/Reroof PA PY OK TO BUILD PARAPETS
03/24/2003 11 Ftg/Foundation/Piers AP PY
03/21/2003 21 Underground/Under Floor AP PY
EsGil Corporation
in Partners/up with Government for Building Safety
DATE: 08/23/02
JURISDICTION: Carlsbad.
PLAN CHECK NO.: 02-883 SET: III
PROJECT ADDRESS: 1281 Magnolia Street
4JS
'PLAN REVIEWER
U FILE
PROJECT NAME: Rebuilt Garage/Room Addition for Funkhouser Residence
The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
LI The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
LI The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
R The applicant's copy of the check list has been sent to:
Esgil Corporation staff did not advise the applicant that the plan cheek has been completed.
LI Esgil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Telephone #:
Date contacted: (by: ) Fax #:
Mail Telephone Fax In Person
LI REMARKS:
By: Ray Fuller Enclosures:
Esgil Corporation
EIIJGA fIlIMB EJ F1 PC 08/19/02 trnsrntLdot
9320 Chesapeake Drive, Suite 208 • San Diego, California 92123 • (858) 560-1468 • Fax (858) 560-1576
EsGil Corporation
In Partnership with Government for Building Safety
DATE: 05/16/02
JURISDICTION: Carlsbad
PLAN CHECK NO.: 02-883
PROJECT ADDRESS: 1281 Magnolia Street
SET: 11
U F21XNT
URI
U PLAN REVIEWER
U FILE
PROJECT NAME: Rebuilt Garage/Room Addition for Funkhouser Residence
LII The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
The plans transmitted herewith will substantially comply with the jurisdiction's building' codes
when minor deficiencies identified below are resolved and checked by building department staff.
The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
LI The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
LnJ The applicant's copy of the check list has been sent to:
Roy Blackford
Post Office Box 2046 Carlsbad, Ca. 92018
Esgil Corporation staff did not advise the applicant that the plan check has been completed.
Esgil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Roy Blackford Telephone #: (760) 729-0553
Date contacted: 6! / o/bZ (by:fA, Fax #: (760) 7290553*77
Mai-ieIephone Fax— In Person
REMARKS:
By: Ray Fuller Enclosures:
Esgil Corporation
EJGA LJMB LEJ M PC 05/09/02 trnsmtLdot
9320 Chesapeake Drive, Suite 208 • San Diego, California 92123 • (858) 560-1468 • Fax(858)560-1576
Carlsbad 02-883
05/16/02
RECHECK PLAN CORRECTION LIST
JURISDICTION: Carlsbad
PROJECT ADDRESS: 1281 Magnolia Street
DATE PLAN RECEIVED BY
ESGIL CORPORATION: 05/09/02
REVIEWED BY: Ray Fuller
PLAN CHECK NO.: 02-883
SET: II
DATE RECHECK COMPLETED:
05/16/02
FOREWORD (PLEASE READ):
This plan review is limited to the technical requirements contained in the Uniform Building Code,
Uniform Plumbing Code, Uniform Mechanical Code, National Electrical Code and state laws
regulating energy conservation, noise attenuation and disabled access. This plan review is
based on regulations enforced by the Building Department. You may have other corrections
based on laws and ordinances enforced by the Planning Department, Engineering Department
or other departments.
The following items listed need clarification, modification or change. All items must be satisfied
before the plans will be in conformance with the cited codes and regulations. Per Sec. 106.4.3,
1997 Uniform Building Code, the approval of the plans does not permit the violation of any
state, county or city law.
To facilitate rechecking, please identify, next to each item, the sheet of the plans upon
which each correction on this sheet has been made and return this sheet with the
revised plans.
The following items have not been resolved from the previous plan reviews. The original
correction number has been given for your reference. In case you did not keep a copy of
the prior correction list, we have enclosed those pages containing the outstanding
corrections. Please contact me if you have any questions regarding these items.
Please indicate here if any changes have been made to the plans that are not a result of
corrections from this list. If there are other changes, please briefly describe them and where
they are located on the plans. Have changes been made not resulting from this list?
UYes DNa
Carlsbad 02-883
05/16/02
The items listed below are from the previous list. These remaining items have not
been adequately addressed. The remarks in bold are to emphasize the remaining
problem.
1. Please make all corrections on the original tracings, as requested in the correction list.
Submit three sets of plans for commercial/industrial projects (two sets of plans for
residential projects). For expeditious processing, corrected sets can be submitted in one of
two ways:
Deliver all corrected sets of plans and calculations/reports directly to the City of
Carlsbad Building Department, 1635 Faraday Ave., Carlsbad, CA 92009, (760) 602-2700.
The City will route the plans to EsGil Corporation and the Carlsbad Planning, Engineering
and Fire Departments.
Bring one corrected set of plans and calculations/reports to EsGil Corporation,
9320 Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-1468. Deliver all
remaining sets of plans and calculations/reports directly to the City of Carlsbad Building
Department for routing to their Planning, Engineering and Fire Departments.
NOTE: Plans that are submitted directly to EsGil Corporation only will not be
reviewed by the City Planning, Engineering and Fire Departments until review by EsGil
Corporation is complete.
2. Plans, specifications and calculations shall be signed and sealed by the California state
licensed engineer or architect responsible for their preparation. Final sets. The plans
have used delta I for revisions and delta for the sher walls. This could cause
inspection problems in the field.
Specify connection at corners of covered area with intersecting beams i.e. the 6 x 12 to
6 x 10. Response was see detail G13. Detail G13 is reflecting 6 x 10 to 6 x 10 and
plans are stating 6x 12 at left and a 6 x 10 on the right side at the trellis area.
Detail and reference 5 1/4 PLM supporting ridge /hips where sets on 6 x10 beam . Show
maximum taper cut if beam is to be flush. Size footings accordingly. On sheet J13,
detail M/2 is showing a 5 1/4 PLM but depth of beam is not stated and roof framing
plan does not reflect this and no detail provided for the taper cut where resting on
6 x 12's.
20. Specify lengths and nailing of shear walls shown for addition. Please review
calculations and confirm that plans match the calculations provided. For example
on line 4 shear wall 6 is required and 5 is shown instead. Detail and reference how
retrofitting additional anchor bolts at existing foundation with new shear walls.
Detail and reference pier method using i.e. at line 3 and show all shear extending
to roof sheathing. The LTT 20B shown on roof framing plan on sheet 3 should be
detailed and referenced to the plans. Is this to be attached to the existing masonry
wall and if so show type of connection etc. i.e. expansion bolt or epoxy?
Carlsbad 02-883
05/16/02
30. Special inspection required for epoxy anchor bolts using for ledger for detail B13 and
complete attached form. The detail is stating that the lag bolts are to used? There will
be special inspection required for the retro fit hold down shown on sheet 3. The
retrofit hold down needs to be detail and referenced to the plans i.e. show all tread
size, epoxy type and depth of embedment.
32. Clearly note on plans that no cooking facilities at the addition will be provided and
that this is not a 2 dwelling.
To speed up the review process, note on this list (or a copy) where each correction item has
been addressed, i.e., plan sheet, note or detail number, calculation page, etc.
Please indicate here if any changes have been made to the plans that are not a result of
corrections from this list. If there are other changes, please briefly describe them and where
they are located in the plans.
Have changes been made to the plans not resulting from this correction list? Please
indicate:
Yes El No c:
The jurisdiction has contracted with Esgil Corporation located at 9320 Chesapeake Drive,
Suite 208, San Diego, California 92123; telephone number of 858/560-1468, to perform the
plan review for your project. If you have any questions regarding these plan review items,
please contact Ray Fuller at Esgil Corporation. Thank you.
Carlsbad 02-883
05/16/02
BUILDING DEPARTMENT
NOTICE OF REQUIREMENT FOR SPECIAL INSPECTION
Do Not Remove From Plans
Plan Check No. 02-883
Job Address or Legal Description 1281 Magnolia Street
Owner Address
You are hereby notified that in addition to the inspection of construction provided by the Building
Department, an approved Registered Special Inspector is required to provide continuous inspection
during the performance of the phases of construction indicated on the reverse side of this sheet.
The Registered Special Inspector shall be approved by the City of Carlsbad Building
Department prior to the issuance of the building permit. Special Inspectors having a
current certification from the City of San Diego, Los Angeles, or ICBO are approved as
Special Inspectors for the type of construction for which they are certified.
The inspections by a Special Inspector do not change the requirements for inspections by
personnel of the City of Carlsbad building department. The inspections by a Special
Inspector are in addition to the inspections normally required by the County Building
Code.
The Special Inspector is not authorized to inspect and approve any work other than that for which he/she
is specifically assigned to inspect. The Special Inspector is not authorized to accept alternate
materials, structural changes, or any requests for plan changes. The Special Inspector is required to
submit written reports to the City of Carlsbad building department of all work that he/she
inspected and approved. The final inspection approval will not be given until all Special Inspection
reports have been received and approved by the City of Carlsbad building department.
Please submit the names of the inspectors who will perform the special inspections on each of the items
indicated on the reverse side of this sheet.
(over)
Carlsbad 02-883
05/16/02
SPECIAL INSPECTION PROGRAM
ADDRESS OR LEGAL DESCRIPTION:
PLAN CHECK NUMBER: OWNER'S NAME:
I, as the owner, or agent of the owner (contractors may not employ the special inspector), certify that I,
or the architect/engineer of record, will be responsible for employing the special inspector(s) as
required by Uniform Building Code (UBC) Section 1701.1 for the construction project located at
the site listed above. UBC Section 106.3.5.
Signed
I, as the engineer/architect of record, certify that I have prepared the following special inspection program as
required by UBC Section 106.3.5 for the construction project located at the site listed above.
Engineers/Architect's Seal
& Signature Here
Signed
1. List of work requiring special inspection:
IJ Soils Compliance Prior to Foundation Inspection Field Welding
Ill Structural Concrete Over 2500 PSI Eli High Strength Bolting
LI Prestressed Concrete j Expansion/Epoxy Anchors
Structural Masonry fl Sprayed-On Fireproofing
Designer Specified Other
2. Name(s) of individual(s) or firm(s) responsible for the special inspections listed above:
3. Duties of the special inspectors for the work listed above:
site.
Special inspectors shall check in with the City and present their credentials for approval prior to beginning work on the job
EsGil Corporation
In Partnership with government for Building Safety
DATE: 04/02/02 D APP NT
JURIS
JURISDICTION: Carlsbad 0 PLAN REVIEWER
0 FILE
PLAN CHECK NO.: 02-883 SET: I
PROJECT ADDRESS: 1281 Magnolia Street
PROJECT NAME: Rebuilt Garage/Room Addition for Funkhouser Residence
The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
The applicant's copy of the check list has been sent to:
Roy Blackford
Post Office Box 2046 Carlsbad, Ca. 92018
Esgil Corporation staff did not advise the applicant that the plan check has been completed.
Esgil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Roy Blackford Telephone #: (760) 729-0553
Date contacted: z..- (by: Pa-) Fax #: (760) 7290553*77
Mail - Telephone— Fax.— In Person
Eli REMARKS:
By: Ray Fuller Enclosures:
Esgil Corporation
E1GA EJ MB UEJ LI PC 03/26/02 trnsmtl.dot
9320 Chesapeake Drive, Suite 208 • San Diego, California 92123 • (858) 560-1468 • Fax(858)560-1576
Carlsbad 02-883
04/02/02
PLAN REVIEW CORRECTION LIST
SINGLE FAMILY DWELLINGS AND DUPLEXES
PLAN CHECK NO.: 02-883 JURISDICTION: Carlsbad
PROJECT ADDRESS: 1281 Magnolia Street
FLOOR AREA:
Garage 440
Addition 192
REMARKS:
DATE PLANS RECEIVED BY
JURISDICTION: 03/25/02
DATE INITIAL PLAN REVIEW
COMPLETED: 04/02/02
STORIES: 1
HEIGHT: 12 ft per UBC
DATE PLANS RECEIVED BY
ESGIL CORPORATION: 03/26/02
PLAN REVIEWER: Ray Fuller
FOREWORD (PLEASE READ):
This plan review is limited to the technical requirements contained in the Uniform Building Code,
Uniform Plumbing Code, Uniform Mechanical Code, National Electrical Code and state laws
regulating energy conservation, noise attenuation and access for the disabled. This plan review
is based on regulations enforced by the Building Department. You may have other corrections
based on laws and ordinance by the Planning Department, Engineering Department, Fire
Department or other departments. Clearance from those departments may be required prior to
the issuance of a building permit.
Present California law mandates that residential construction comply with the 1998 edition of
the California Building Code (Title 24), which adopts the following model codes: 1997 UBC,
1997 UPC, 1997 UMC and 1996 NEC (all effective 7/1/99).
The above regulations apply to residential construction, regardless of the code editions adopted
by ordinance.
The following items listed need clarification, modification or change. All items must be satisfied
before the plans will be in conformance with the cited codes and regulations. Per Sec. 106.4.3,
1997 Uniform Building Code, the approval of the plans does not permit the violation of any
state, county or city law.
To speed up the recheck process, please note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet number, specification section, etc.
Be sure to enclose the marked up list when you submit the revised plans.
Carlsbad 02-883
04/02/02
. PLANS
Please make all corrections on the original tracings, as requested in the correction
list.
Submit three sets of plans for commercial/industrial projects (two sets of plans for
residential projects). For expeditious processing, corrected sets can be submitted
in one of two ways:
Deliver all corrected sets of plans and calculations/reports directly to the
City of Carlsbad Building Department, 1635 Faraday Ave., Carlsbad, CA 92009,
(760) 602-2700. The City will route the plans to EsGil Corporation and the
Carlsbad Planning, Engineering and Fire Departments.
Bring one corrected set of plans and calculations/reports to EsGil
Corporation, 9320 Chesapeake Drive, Suite 208, San Diego, CA 92123, (858)
560-1468. Deliver all remaining sets of plans and calculations/reports directly to
the City of Carlsbad Building Department for routing to their Planning, Engineering
and Fire Departments.
NOTE: Plans that are submitted directly to EsGil Corporation only will not
be reviewed by the City Planning, Engineering and Fire Departments until review
by EsGil Corporation is complete.
2. Plans, specifications and calculations shall be signed and sealed by the
California state licensed engineer or architect responsible for their preparation.
Specify on the plans the sg footage of covered porches and trellis area.
. GARAGE
The minimum width of shear panel to be conventional framed is 2'8". The
alternative to this is design calculations and detailing and referencing how 3 1/2
to I ratio is meant or adding strong walls. If adding strong walls provide details
and reference to the plans and will required deepen footings for hold downs
required (SSTB28's with 25" embedment.)
Braced /shear walls are required to be shown within 8 ft of each braced wall line.
No braced wall or shear wall shown within 8 ft of door as shown on south
elevation.
All braced/shear walls need to specify type of panel, nailing size, spacing edge
and field and the length.
Could not determine why spread footings are not shown under PLM ridge beam.
Should reference shear transfer details to front and south side.
Could not locate the ceiling joist size at the garage. If not dry walling then show
lateral cross bracing at the plate lines for each corner.
Carlsbad 02-883
04/02/02
Specify ICBO number for tile roof and name and manufacturer of the product.
ADDITION.
Specify connection from existing top plates to new i.e. some type of strap at the
left side.
As shown the ledger is in cross grain in bending and will need to provide a
design to show roof connections to masonry walls, per Section 1605.2.3:
a) Connections shall resist 200 pounds per lineal foot or the actual design
load, whichever is greater (using Allowable Stress Design; otherwise, see
Section 1612).
Is existing wall adequate for additional dead loads and was it reinforced?
Specify how sleepers are to attach to roof joist.
Foundation plan does not reflect size and depth of spread footings required for
trellis areas. Show width, depth, any steel required. Specify post to spread
footing connection and minimum 8" above grade for wood post.
Specify roofing type material for covered area attached to the garage. Is this to
be spaced sheathing also. If using solid material then design for lateral to
included uplift from wind.
Specify connection at corners of covered area with intersecting beams i.e. the
6 x 12 to 6 x 10.
Detail and reference 5 1/4 PLM supporting ridge /hips where sets on 6 x10 beam.
Show maximum taper cut if beam is to be flush. Size footings accordingly.
Could not locate where detail G and K were referenced to the plans.
Specify lengths and nailing of shear walls shown for addition.
Show window A to be tempered.
Show how 2 nd dwelling is to be heated and service size and location.
Show GFCI outlets at front and rear of dwelling.
There must be a 1 hour separation with minimum STC rating of 50 between
dwelling units. Is there any portion of 2d dwelling in common with existing house
that is not masonry extending to the roof sheathing? If so then detail assembly to
show 1 hour and STC of 50.
Carlsbad 02-883
04/02/02
25. Provide plans, calculations and worksheets to show compliance with current
energy standards.
26. The window schedule shall clearly describe the required U-factor and solar heat
gain coefficient (SHGC) values and demonstrate compliance with the Title 24
energy calculations.
27. All sheets of the latest CF-1 R form must be imprinted onto the plans (sheets 1 of
3, 2 of 3 and 3 of 3 must be included).
28. A mechanical duct sealing certification test must be performed by a certified
HERS inspector or compliance with the "Alternate to Package D" requirements
shall be shown on the CFI -R form. (This requirement is valid for all new low rise
residential construction including room additions greater than 100 square
feet that are using the Prescriptive energy calculation method.)
29. Show the method of compliance on the CF1 -R form for the following two
Prescriptive requirements (either one is necessary for new homes and additions
exceeding 100 square feet located in Climate Zones 2, 4 (Radiant Barrier Only),
and 8-15):
A radiant (roof) barrier is required for new low rise residential construction.
The installation of a TXV valve or a technician certification for split system
air conditioner or heat pump systems. Requires HERS Inspector
verification. (In lieu of Inspector certification the "Alternative to Package D"
requirements may be specified on the CFI-R form).
30. Note on cover sheet that special inspection required for epoxy anchor bolts
using for ledger for detail B/3 and complete attached form. The detail is stating
that the lag bolts are to used?
31. Note on the plans: "The manufactured windows shall have a label attached
certified by the National Fenestration Rating Council (NFRC) and showing
compliance with the energy calculations."
. CITY OF CARLSBAD REQUIREMENTS
32. If this is to be a 2 nd dwelling now i.e. kitchen was not existing then must comply
with solar requirements listed below.
33. New residential units must be pre-plumbed for future solar water heating. Note
"two roof jacks must be installed" where the water heater is in the one story garage
and directly below the most south facing roof (City Ordinance No. 8093).
34. Note "two 314" copper pipes must be installed to the most convenient future solar
panel location when the water heater is not in a one story garage and is not
directly below the most south facing roof. (City Ordinance No. 8093).
Carlsbad 02-883
04/02/02
35. All piping for present or future solar water heating must be insulated when in areas
that are not heated or cooled by mechanical means (City Policy).
To speed up the review process, note on this list (or a copy) where each correction
item has been addressed, i.e., plan sheet, note or detail number, calculation page,
etc.
Please indicate here if any changes have been made to the plans that are not a
result of corrections from this list. If there are other changes, please briefly describe
them and where they are located in the plans.
Have changes been made to the plans not resulting from this correction list?
Please indicate:
Yes El No LJ
The jurisdiction has contracted with Esgil Corporation located at 9320 Chesapeake
Drive, Suite 208, San Diego, California 92123; telephone number of 858/560-1468,
to perform the plan review for your project. If you have any questions regarding
these plan review items, please contact Ray Fuller at Esgil Corporation. Thank
you.
Carlsbad 02-883
04/02/02
VALUATION AND PLAN CHECK FEE
JURISDICTION: Carlsbad PLAN CHECK NO.: 02-883
PREPARED BY: Ray Fuller DATE: 04/02/02
BUILDING ADDRESS: 1281 Magnolia Street
BUILDING OCCUPANCY: R3 Ui TYPE OF CONSTRUCTION: VN
BUILDING
PORTION
AREA
(Sq. Ft.)
Valuation
Multiplier
Reg.
Mod.
VALUE ($)
Garage 440 Per City Est. 30,336
Addition 192
Air Conditioning
Fire Sprinklers
TOTAL VALUE 30,336
Jurisdiction Code 1CB By Ordinance
Bldg. Permit Fee by Ordinance
Plan Check Fee by Ordinance FVI
Type of Review: Ei Complete Review Structural Only
LI Other
__ E] Repetitive' Fee
Repeats Hourly Hour *
Esgil Plan Review Fee
I $248.551
I $161.561
I $139.191
Comments:
Sheet 1 of 1
macvalue.doc
Citv of Carlsbad
oj Pubuic Works jEng ineering
BUILDING PLANCHECK
DATE: PLANCHECK NO.: CB O -
BUILDING AdDRESS: (2_$/ .J.
PROJECT DESCRIPTION: j,(• '
ASSESSOR'S PARCEL NUMBER: c2O- Sv- EST. VALUE:
ENGINEERING DEPARTMENT
APPROVAL
The item you have submitted for review has been
approved. The approval is based on plans,
information and/or specifications provided in your
submittal; therefore any changes to these items after
this date, including field modifications, must be
reviewed by this office to insure continued
conformance with applicable codes. Please review
carefully all comments attached, as failure to comply
with instructions in this report can result in
suspension of permit to build.
LI A Right-of-Way permit is required prior to
construction of the following improvements:
DENIAL
Please see thé\ attached report of deficiencies
marked With 0. Make necessary corrections to plans
or specficatiçrifor compliance with applicable
codes antnuards. Submit corrected plans and/or
specifications to this office for review.
.1' Jate - -
By: Date:
By: Date:
FOR OFFICIAL USE ONLY
eate
ENGINEERING AUTHORIZATION TO ISSUE BUILDING PERMIT:
By: c I/1,tA_ Date:
.
V/.
ATTACHMENTS
LI Dedication Application
LI Dedication Checklist
LI Improvement Application
LI Improvement Checklist
LI Future Improvement Agreement
LI Grading Permit Application
LI Grading Submittal Checklist
LI Right-of-Way Permit Application
ENGINEERING DEPT. CONTACT PERSON
Name: Karen Niemi
City of Carlsbad
Address: 1635 Faraday Avenue, Carlsbad, CA 92008
Phone: (760) 602-2775
CFD INFORMATION
Parcel Map No:
Lots:
Recordation:
LI Right-of-Way Permit Submittal Checklist Carlsbad Tract: and Information Sheet
LI Sewer Fee Information Sheet
CA 92008i7314. (760) 602-2720• FAX (760) 602,8562 S
BUILDING PLANCHECK CHECKLIST
SITE PLAN
1ST1/ 2ND 3RD
)ZI U LI 1. Provide a fully dimensioned site plan drawn to scale. Show:
,A"North Arrow .P " Right-of-Way Width & Adjacent Streets ,V Existing & Proposed Structures Driveway widths
,% Existing Street Improvements ){'. Existing or proposed sewer lateral
ji Property Lines ,A Existing or proposed water service
Easements ,c( Existing or proposed irrigation service
fl 2. Show on site plan:
/ Drainage Patterns
Building pad surface drainage must maintain a minimum slope of one
percent towards an adjoining street or an approved drainage course,
ADD THE FOLLOWING NOTE: "Finish grade will provide a minimum positive
/ drainage of 2% to swale 5' away from building."
. Existing & Proposed Slopes and Topography
,ø Size, type, location, alignment of existing or proposed sewer and water service
(s) that serves the project. Each unit requires a separate service, however,
second dwelling units and apartment complexes are an exception.
Sewer and water laterals should not be located within proposed driveways, per
standards.
0 LI 3. Include on title sheet:
Site address
Assessor's Parcel Number
Legal Description
For commercial/industrial buildings and tenant improvement projects,, include:
total building square footage with the square footage for each different use,
existing sewer permits showing square footage of different uses (manufacturing,
warehouse, office, etc.) previously approved.
EXISTING PERMIT NUMBER DESCRIPTION
H:\W0RO\30CS\C3HK(.S1'.Ou11d PIaz,thedc Cklst Form (Genelc).doc 2 Rev. 714I00
BUILDING PLANCHECK CHECKLIST
1ST 2ND 3 rd DISCRETIONARY APPROVAL COMPLIANCE
LI LI 4a. Project does not comply with the following Engineering Conditions of approval for I' Project No.____________________________________________________________
LI LI LI 4b. All conditions are in compliance. Date:
DEDICATION REQUIREMENTS
LI LI 0 5. Dedication for all Street Rights-of-Way adjacent to the building site and any storm
drain or utility easements on the building site is required for all new buildings and
for remodels with a value at or exceeding $15.000, pursuant to Carlsbad
Municipal Code Section 18.40.030.
Dedication required as follows:
Dedication required. Please have a registered Civil Engineer or Land Surveyor
prepare the appropriate legal description together with an 8 h/2U x 11" plat map
and submit with a title report. All easement documents must be approved and
signed by owner(s) prior to issuance of Building Permit. Attached please find an
application form and submittal checklist for the dedication process. Submit the
completed application form with the required checklist items and fees to the
Engineering Department in person. Applications will not be accept by mail or fax.
Dedication completed by: Date:
IMPROVEMENT REQUIREMENTS
0 0 LI 6a. All needed public improvements upon and adjacent to the building site must be
constructed at time of building construction whenever the value of the
construction exceeds $75000, pursuant to Carlsbad Municipal Code Section
18.40.040.
Public improvements required as follows:
Attached please find an application form and submittal checklist for the public
improvement requirements. A registered Civil Engineer must prepare the
appropriate improvement plans and submit them together with the requirements
on the attached checklist to the Engineering Department through a separate plan
check process. The completed application form and the requirements on the
H:\WORDDOCS\CHK'SP8ung PIanthed Cklst Form (RIDDLE HARVEY 7-12-00)doc 3 Rev. 12126196
BUILDING PLANCHECK CHECKLIST
1 ST ND 3RD
checklist must be submitted in person. Applications by mail or fax are not
accepted. Improvement plans must be approved, appropriate securities posted
and fees paid prior to issuance of building permit.
Improvement Plans signed by: Date:
El El El 6b. Construction of the public improvements may be deferred pursuant to Carlsbad
Municipal Code Section 18.40. Please submit a recent property title report or
current grant deed on the property and processing fee of $310 so we may
prepare the necessary Future Improvement Agreement. This agreement must be
signed, notarized and approved by the City prior to issuance of a Building permit.
Future public improvements required as follows:
El El El 6c. Enclosed please find your Future Improvement Agreement. Please return
agreement signed and notarized to the Engineering Department.
Future Improvement Agreement completed by:
Date:
0 0 6d. No Public Improvements required. SPECIAL NOTE: Damaged or defective
7 improvements found adjacent to building site must be repaired to the satisfaction
of the City Inspector prior to occupancy.
GRADING PERMIT REQUIREMENTS
The conditions that invoke the need for a grading permit are found in Section
11.06.030 of the Municipal Code.
El El El 7a. Inadequate information available on Site Plan to make a determination on grading
requirements. Include accurate grading quantities (cut, fill import, export).
U El El 7b. Grading Permit required. A separate grading plan prepared by a registered Civil
Engineer must be submitted together with the completed application form
attached. NOTE: The Grading Permit must be issued and rough gradJg
approval obtained prior to issuance of a Building Permit.
Grading Inspector sign off by: Date:
El El U 7c. Graded Pad Certification required. (Note: Pad certification may be required even
if a grading permit is not required.)
H:\WORD\DOCS\cHKST\8uiIdin9 Plnchock Mist Form (Generic 7-I4.00).doc 4 Roy. 7/14/00
BUILDING PLANCHECK CHECKLIST
1S, 2ND 3RD
7d No Grading Permit required.
LI 0 0 7e. If grading is not required, write "No Grading" on plot plan.
MISCELLANEOUS PERMITS
,1
F1 0 8. A RIGHT-OF-WAY PERMIT is required to do work in City Right-of-Way and/or
private work adjacent to the public Right-of-Way. Types of work include, but are
not limited to: street improvements, tree trimming, driveway construction, tying
into public storm drain, sewer and water utilities.
Right-of-Way permit required for: 3" 6- U a(
El El [1 9. INDUSTRIAL WASTE PERMIT If your facility is located in the City of Carlsbad
sewer service area, you need to contact the Carlsbad Municipal Water District,
a located at 5950 El Camino Real, Carlsbad, CA 92008. District personnel can itf'ft provide forms and assistance, and will check to see if your business enterprise is
on the EWA Exempt List. You may telephone (760) 438-2722, extension 7153,
for assistance.
Industrial Waste permit accepted by:
Date:
LI El LI 10. NPDES PERMIT
Complies with the City's requirements of the National Pollutant Discharge fl Elimination System' (NPDES) permit. The applicant shall provide best
management practices to reduce surface pollutants to an acceptable level prior to
discharge to sensitive areas. Plans for such improvements shall be approved by
the City Engineer prior to issuance of grading or building permit, whichever
occurs first.
12" LI U 11. U Required fees are attached
7 No fees required
WATER METER REVIEW
LI LI LI 12a. Domestic (potable) Use
Ensure that the meter proposed by the owner/developer is not oversized.
Oversized meters are inaccurate during low-flow conditions. If it is oversized, for
the life of the meter, the City will not accurately bill the owner for the water used.
All single family dwelling units received "standard" 1" service with 5/8" service.
H:WORD00CSCHKl.Sfl9tA1ing Par,thed, CkI3t Form (Geneflc).doc 5 Rev. 1114I00
BUILDING PLANCHECK CHECKLIST
1ST 2ND 3RD
If owner/developer proposes a size other than the "standard", then
owner/developer must provide potable water demand calculations,
which include total fixture counts and maximum water demand in gallons
per minute (gpm). A typical fixture count and water demand worksheet is
attached. Once the gpm is provided, check against the "meter sizing
schedule" to verify the anticipated meter size for the unit.
Maximum service and meter size is a 2" service with a 2" meter.
If a developer is proposing a meter greater than 2", suggest the
installation of multiple 2" services as needed to provide the anticipated
demand. (manifolds are considered on case by case basis to limit
multiple trenching into the street).
El 0 0 12b. Irrigation Use (where recycled water is not available)
All irrigation meters must be sized via irrigation calculations (in gpm) prior
to approval. The developer must provide these calculations. Please follow
these guidelines:
If the project is a newer development (newer than 1998), check the recent
improvement plans and observe if the new irrigation service is reflected on
the improvement sheets. If so, at the water meter station, the demand in
gpm may be listed there. Irrigation services are listed with a circled "I",
and potable water is typically a circled "W". The irrigation service should
look like:
Q STA 1+00 Install 2" service and
1.5: meter (estimated 100 gpm)
If the improvement plans do not list the irrigation meter and the
service/meter will be installed via another instrument such as the building
plans or grading plans (w/ a right of way permit of course), then the
applicant must provide irrigation calculations for estimated worst-case
irrigation demand (largest zone with the farthest reach). Typically, Larry
Black has already reviewed this if landscape plans have been prepared,
but the applicant must provide the calculations to you for your use. Once
you have received a good example of irrigation calculations, keep a set for
your reference. In general the calculations will include:
Hydraulic grade line
Elevation at point of connection (POC)
Pressure at POC in pounds per square inch (PSI)
Worse case zone (largest, farthest away from valve
Total Sprinkler heads listed (with gpm Use per head)
Include a 10% residual pressure at point of connection
3. In general, all major sloped areas of a subdivision/project are to be
irrigated via separate irrigation meters (unless the project is only SFD with
no HOA). As long as the project is located within the City recycled water
H:\WORD\DOCS\CHLST\Bufldlng Plancbeck Cklst Fain, (Genesic).doc 6 Rev. 7/14/00
BUILDING PLANCHECK CHECKLIST
1ST 2ND 3RD
service boundary, the City intends on switching these irrigation
services/meters to a new recycled water line in the future.
U U J 12c. Irrigation Use (where recycled water is available)
1. Recycled water meters are sized the same as the irrigation meter above.
2. If a project fronts a street with recycled water, then they should be
connecting to this line to irrigate slopes within the development. For
subdivisions, this should have been identified, and implemented on the
improvement plans. Installing recycled water meters is a benefit for the
applicant since they are exempt from paying the San Diego County Water
Capacity fees. However, if they front a street which the recycled water is
there, but is not live (sometimes they are charged with potable water until
recycled water is available), then the applicant must pay the San Diego
Water Capacity Charge. If within three years, the recycled water line is
charged with recycled water by CMWD, then the applicant can apply for a
refund to the San Diego County Water Authority (SDCWA) for a refund.
However, let the applicant know that we cannot guarantee the refund, and
they must deal with the SDCWA for this.
0 0 0 13. Additional Comments:
WORD\DOCSCHK1ST8uiJding Planclieck Cktst FoTen (Genedc).doc 7 Rev. 7/14100
Discretionary Action Required: YES NO TYPE
APPROVAL/RESO. NO. - DATE
PROJECT NO.
OTHER RELATED CASES:
ME
p
PLANNING DEPARTMENT
BUILDING PLAN CHECK REVIEW CHECKLIST
Plan Check No /C B *' 3 Address 7"9'
Planner /97Jj.I Phone (760) 602-
APN: 705
75 Type of Project & Use:___ SIQL ______________ Net Project Density: DU/AC
Zoning:j2.-I General Plan: Facilities Management Zone: (
CFD 1inI0110 #Date of participation: Remaining net dev acres:______ Circle One
(For non-residential development: Type of land used created by
e o w q this permit:_______________________________________________________ . . - o '0 C • .. . ( t ,'• * ., a- CL
Legend: Item Complete
Environmental Review Required:
DATE OF COMPLETION:
Compliance with conditions of approval?
Conditions of Approval:
Compliance with conditions or approval?
Conditions of Approval:____________
If not, state conditions which require action.
If not, state conditions which require action.
Item Incomplete - Needs your action
YES NO TYPE
Coastal Zone Assessment/Compliance
0
Project site located in Coasfal Zone? YES NO____
CA Coastal Commission Authority? YES NO____
If California Coastal Commission Authority: Contact them at1— 7575 Metropolitan Drive, Suite 103,
San Diego CA 92108-4402; (619) 767-2370
Determine status (Coastal Permit Required Zo!m mpt)
Coastal Permit Determination Form already d? YES NO____
If NO, complete Costal Permit Determination Form' now. •
Coastal Permit Deterr!nination Lo ' g#:
4
'Follow-Up Actions: • *
1
Stamp Building Plans as' "'Exempt," or "Coastal Permit Required" (at minimum
Floor Plans). 0
.
'
Complete Coastal Permit Determination Log as needed.
H :\ADMI N\COUNTER\BldgPlnchkRevChklst .
F-1 F-1 Inclusionary Housing Fee required: YES NO
/'s.../ (Effective date of Inclusionary Housing Ordinance - May 21, 1993.)
Data Entry Completed? YES NO .,
(A/P/Ds, 'Activity Maintenance, enter CB#, toolbar, Screens, Housing Fees, Construct Housing Y/N, Enter Fee, UPDATE!)
Site Plan:
J1 1. Provide a fully dimensional site plan drawn to scale. Show: North arrow,
property lines, easements, existing and proposed structures, streets, existing
street improvements, right-of-way width, dimensional setbacks and. existing
topographical lines (including all side and rear yard slopes).
2. Provide legal description of propety and assessor's parcel number.
Zoning: 0,1A4,111, W
1.Sethacks:
Front: Required C? Shown / 6
Interior Side: Required Shown
Street Side: Required __ Shown ___________
Rear: Required ' Shown
Top of slope: Required Shown
F1 F-1 2. Accessory structure setbacks:
Front: Required ctJ Shown cfO
Interior Side: Required "" , Shown
Street Side: ' Required 5 t Shown
Rear: Required - Shown
Structure separation: Required / - Shown /0 '
VF-1 F-1 3. Lot Coverage: Required <110 Shown L
LkTI1 4. Height: Required 30 Shown /
LI 5. Parking: Spaces Required' Shown
(breakdown by uses for commercial and industrial projects required)
Residential Guest paces Required • Shown V
Additional na I Co m1k& Gr (A A"'
'f' -PW ts '
110 AJ a-?) j-t' J Ic ° t1 C)
E,A L!iU fs'fte jji -t 4
'I, 4'