HomeMy WebLinkAbout1339 Knowles Ave; ; CBR2018-0310; Permit{city of
Carlsbad
Residential Permit
Print Date: 09/26/2018 Permit No: CBR2018-0310
Job Address:
Permit Type:
Parcel No:
Valuation:
Occupancy Group:
# Dwelling Units:
Bedrooms:
Project Title:
1339 Knowles Ave
BLDG-Residential
1561641400
$55,385.36
Work Class:
Lot#:
Reference#:
Construction Type:
Bathrooms:
Orig. Plan Check#:
Plan Check#:
1339 KNOWLES AVE LOT LEGALITY
Addition
DEV2018-0072
Status:
Applied:
Issued:
Permit
Finaled:
Inspector:
Final
Inspection:
Description: SMITH: 262 SF ADDITION TO BEDROOM 5 // REMODEL 14D SF LAUNDRY & 96 SF MASTER BATH
Applicant:
BA WORTHING INC
BROOKS WORTHING
640 Grand Ave, G
Carlsbad, CA 92D08-236S
760-729-3965
BUILDING PERMIT FEE ($2000+)
BUILDING PLAN CHECK FEE (BLDG)
Owner:
COOWNER STEVE & ALLY SMITH
1339 Knowles Ave
CARLSBAD, CA 920D8
ELECTRICAL BLDG RESIDENTIAL NEW/ADDITION/REMODEL
GREEN BUILDING STANDARDS PLAN CHECK & INSPECTION
MECHANICAL BLDG RESIDENTIAL NEW/ADDITION/REMODEL
PLUMBING BLDG RESIDENTIAL NEW/ADDITION/REMODEL
SB1473 GREEN BUILDING STATE STANDARDS FEE
STRONG MOTION-RESIDENTIAL
SWPPP INSPECTION FEE TIER 1-Medium BLOG
SWPPP PLAN REVIEW FEE TIER 1-MEDIUM
Total Fees: $1,384.59 Total Payments To Date: $1,384.59
Contractor:
BA WORTHING INC
640 Grand Ave, G
Carlsbad, CA 92008-2365
76D-729-3965
Balance Due:
Please take NOTICE that approval of your project includes the "Imposition" of fees, dedications, reservations, or other exactions hereafter
collectively referred to as "fees/exaction." You have 90 days from the date this permit was issued to protest imposition of these
fees/exactions. If you protest them, you must follow the protest procedures set forth in Government Code Section 66020(a), and file the
protest and any other required information with the City Manager for processing in accordance with Carlsbad Municipal Code Section
3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack, review, set aside, void, or annul their
imposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection
fees and capacity changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this
project. NOR DOES IT APPLY to any fees/exactions of which you have previously been given a NOTICE similar to this, or as to which the
statute of limitation has previously otherwise expired.
Closed -Finaled
02/07/2018
05/02/2018
PBurn
9/26/2018 2:41:34PM
$0.DO
$432.58
$302.81
$43.DO
$17D.DO
$52.00
$80.00
$3.00
$7.20
$238.00
$56.00
1635 Faraday Avenue, Carlsbad, CA 92008-7314 I 760-602-2700 I 760-602-8560 f I www.carlsbadca.gov
---=-·-------------------------------------------------~ □ ENGINEERING THE FOLLOWING APPROVALS REQUIREO PRIOR TO PERMIT ISSUANCE: 0 PLANNING □BUILDING □FIRE □HEALTH 0 HAZMATIAPCD
Plan Check No.
Est. Value
Plan Ck. Deposit
(~city of
Carlsbad
Building Permit Application
1635 Faraday Ave., Carlsbad, CA 92008
Ph: 760-602-2719 Fax: 760-602-8558
email: building@carlsbadca.gov
www.carlsbadca.gov Date SWPPP
JOB ADDRESS SUITEf/SPACEf/UHITI
T/PROJE # LOT# PHASE# # BATHROOMS TENANT BUSINESS NAME
DESCRIPTION OF WORK: Include Square Feet of Affected Area(s)
f::...oJ-2(9,Z ~~~ /tr ~ooNl '?
(2.~\ 6)(\%--~-e/'t(t~N 'to hRruN&<V) ((OO'YV)
(<'~;l,.e\ ~~~~CR~ f-~
EXISTING USE PROPOSED USE GARAGE (SF) PATIOS (SF) DECKS (SF) FIREPLACE
YESO NO□
ADDRESS I ~ K \ .II -t.L) 3-.,.........., , f\JOVi ~ ,rv-c
FIRE SPRINKLERS
YESON0□
CITY ~t~\,.:,~ STATC,4-ZIP~zcoe
Ffv(.
DESIGN PR0F£5S I0NAL
ADDRESS Ca4o
PHONE
1
EMAIL
STATELIC.# -?Yre 14'4-
(Sec. 7031.5 Business and Professions Code: Any Cll:y or County which requires a permit to construct. alter, Improve, demolish or repair any structure, prior to Its Issuance, also requires the applicant for such permit to Ille a signed statement ttiathe Is licensed pursuant to the provisions of the Contractor's Ucense·Law (Chapter"S, commending with SecUon 7000 of Division 3 of the Business and Professions Code) or that he Is exempt therefrom, and the basis for the alleged exemption. Any vlolallon of Section 7031.5 by any applicant for a permit subjects the applicant to a civil penalty of not more than five hundred dollars ($500)).
,-~~it::~~~~~@:¥iffl ., ... ;~~,;.~cy~B~i~,6!:1~,;r,·
Workers' Compensation Declaration:/ hereby affirm under penalty of perjixyone of the fol/owing declarations:
0 l have and will maintain a certificate of consent lo self-Insure for wolkers' compensallon as provided by Secllon 3700 or Iha Labor Code, for Iha petformance or Ille work for whlch lhls permil Is Issued.
~ I have and will maintain workers' comoensaUon. as required by Se~lion 3700 or the Labor Code, for Ille petlormance of Jhe work for which lhls oermll Is Issued. My workers' compensallo0 Insurance carrier and policy
numberare:lnsuranceCo._U!,,1.c:'2f.:9!~:2_~ ~, Co PollcyNo.~l.. 6)Dq~S':'.l ExplrationDal' 1/(/\q __ _
This section need nol be compleled 111 rmll ls for one hundred dollars ($100) or less. O Certificate of Exemption: I certify thal In Ille petlormance or the work ror which lhls permil is Issued, I shall nol employ any person In any maMer so as lo become subject Jo the Wo!kers' Compensalion Laws or
California. WARNING: Failure to secure workers' compensation coverage Is unlawful, and shall subject an employer lo criminal penalties and civil fines up to one hundred thousand dollars (&100,000), In
addition to the cost or compensation, dama ~• rovld or In Se Ion 706 fthe Labor code, Interest and allomey's fees,
,,€f CONTRACTOR SIGNATURE □AGENT DATE :2 ==,...,,,.,,-,.::-==-:-=~'.':ic:1!::-::::=::~,::o:-=====::i ;tr ,· ~1!¥~~~/;'-,_ .ili1J~~l:!'.. ·~ilttt~t~I~1~r~~1~t: ,.., ;;~ii!~}}!ir~-
l hereby affirm that I am exempt from Conlfllctots License Lew for the lot/owing resso . O 1, as owner ol Jhe property or my empoyees wllh wages as !heir ~la.compe ation, wm do Iha work and Iha slruclure Is nol Intended or offered for sale (Sec. 7044, Business and Professions Code: The Conlraclo(s
license Law does nol apply to an owner of property who builds or Improves thereon, and who does such work hlmsell or lhrough his own employees, provided lhal such lmprovemenls era not Intended or offered /or
sale. II, however, the building or lmprovemenlls sold wllhln one year of complellon, Iha owner-bullderwll have Iha burden of proving lhal he d'Jd nol build or Improve for Iha purpose of sale).
□
□
1, as owner of Iha property, am exclusively conlracllng wilh llcensed contractors lo conslrucl Ille pro)ecl (Sec. 7044, Business end Professions Code: The Contracto(s License Law does nol apply lo an owner or
property who builds or Improves !hereon, and conlracls for such pro)ecls wilh contraclor(s) licensed pursuant to lhe Contraclo(s l.lcense Law).
I am exempt under Section ____ Business and Professions Code for lhls reason:
1. I personally plan lo provide Ille major labor and materials for conslrucllon ol lhe proposed property lmprovemenl 0Yes ONo
2.1 (have I have nol) signed an appllcallon for a building permll for Iha proposed work.
3.1 have contracled wilh lhe foUowlng person (firm) Jo provide Iha proposed conslrucllon Onclude name address I phone I conlraclors' license number):
4. J plan lo JlfOvlde portions ol the work, but I have hired lhe following person lo coortflnale, supervise and provide Iha major work [111clude name I address I phone/ contraclors' license number):
5. 1 will provide some ol lhe work, but I have conlracted (hired) Ille following persons lo provide lhe work Indicated (Include name I address I phone/ lype of work):
1§5 PROPERTY-OWNER SIGNATURE □AGENT DATE
Is thq applicant or fulure building occupant required to submit a business plan, acutely hazardous materials registration form or risk management and prevention program under Sections 25505, 25533 or 25534 of the
Presley-Tanner Hazardous Substance Account Act? 0 Yes O No Is the applicant or future building occupant required to oblain a permit from the air pollution control dislltct or air quaily management district? O Yes O No
Is the facility lo be constructed within 1,000 feet or !he outer boundary or a school site? o Yes O No
IF ANY OF THE ANSWERS ARE YES, A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR IS MEETING THE REQUIREMENTS OF THE OFFICE OF
EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT.
I hereby affirm that there is a construction leoding agency for the performance of the work !his permit is issued (Sec. 3097 (i) Civil Code).
Lende~s Name Lender's Address
I certify thatl have read tile application and state that tile above information Is correct and that the Information on the plans Is accurate. I agree to complywfth all City ordinances and St.ate law.; relating to building construction.
I hereby aulholize representative of lhe City of Gar1sbad to enler upon the above mentklned property br ilspecoon pu!p)ses. I ALSO AGREE TO SA VE, INDEMNIFY AND KEEP HARMLESS THE CITY O' CAALSBAD
AGAINST ALL LIABILITIES, JUDGMENTS, COSTS AND EXPENSES WHICH MAY IN ANYWAY ACCRUE AGAINST SAID CITY IN CONSEQUENCE O' THE GRANTING OF THIS PERMIT.
OSHA: An OSHA permit is required for excavations OVef sa deep and demolfon or consll\Jclion of struclures over 3 slories in height.
EXPIRATION: Every permit issued by the 9.Jikling Official under lhe provisions of this Code shall expre by limitation and become nul and voo if the building or 1100< authorized by such perm ii is not commenaid within
180 days m the date of such permit or if the bulldirg or IIOO( u W/uch rm' · suspended or abandoned al any lime after the 1100< is oommenced for a period of 1B0days (Sectoo 100.4.4 lkliform 9.Jildilg Code).
,£$'APPLICANT'SSIGNATURE M, DATE 2./ 7 IB
PERMIT INSPECTION HISTORY REPORT (CBR2018-0310)
Permit Type: BLDG-Residential Application Date: 02/07/2018 Owner: COOWNER STEVE & ALLY SMITH
Work Class: Addition Issue Date: 05/02/2018 Subdivision:
Status: Closed -Finaled Expiration Date: 03/06/2019 Address: 1339 Knowles Ave
Carlsbad, CA 92008-1548
IVR Number: 9397
Scheduled Actual
Date Start Date Inspection Type Inspection No. Inspection Status Primary Inspector Reinspection Complete
05/18/2018 05/18/2018 BLDG-11 058467-2018 Passed Paul Burnette Complete
Foundatlon/Ftg/Pler
s (Rebar)
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Yes
07/1712018 07/17/2018 BLDG-16 Insulation 064235-2018 Passed Paul Burnette Complete
Checklist Item COMMENTS Passed
BLOG-Building Deficiency Yes
08/09/2018 08/09/2018 BLDG-18 Exterior 066606-2018 Passed Paul Bumette Complete
Lath/Drywall
Checklist Item COMMENTS Passed
BLDG•Building Deficiency No
09/07/2018 09/07/2018 BLDG-21 069325-2018 Passed Paul Bumette Complete
Underground/Underf
loor Plumbing
Checklist Item COMMENTS Passed
BLDG•Building Deficiency No
09/26/2018 09/26/2018 BLDG•Flnal 071185•2018 Passed Paul Burnette Complete
Inspection
Checklist Item COMMENTS Passed
BLDG•Building Deficiency No
BLDG•Plumbing Final No
BLDG•Mechanical Final No
BLDG•Structural Final No
BLDG•Electrical Final No
September 26, 2018 Page 1 of 1
City of Carlsbad cbR2017-1434
July 10, 2017
«1 ~ CITY OF
CARLSBAD
SPECIAL INSPECTION
AGREEMENT
B-45
RECEIVED
APR 16 2018
BUILD/NG DIVISION
Development Services
Building Division
1635 Faraday Avenue
760-602-2719
www.carlsbadca.gov
In accordance with Chapter 17 of the California Building Code the following must be completed when work being performed
requires special Inspection, structural observation and construction matertal testing.
>roject/Permit: Ce, fl., v:>l 8-0 3 1 0
A. THIS SECTION MUST BE COMPLETED BY THE PROPERTY OWNER/AUTHORIZED AGENT. Please check if you are O'M'ler-Builder
□. (lf you checked as owner-builder you must also complete Section B of this agreement.)
Name: (Please print) ~< ~
"""' ',.''. _ I\. -{£..c,..., , ''r~ q-=,;;i Mailing Address· l ½'11 /sN(JIN):e'z tt:::li:, 1/,t'X' ,;,..IV-d'C' ~ ~
Email A::1)17tei;&. o/~lj:t,~ lt,M,A.<\. CtoYY) Phone:114(-(oq7-'2..7S~
I am: ~roperty owner □Property Owner's Agent of Record □Architect of Record □Engineer of Record
State of California Registration Numbe~·------------Expiration Date_· _______ _
AGREEMENT: I, the undersigned, declare under penalty of perjury under the laws of the state of California, that I have read,
understand, acknowledge and promise to comply with the City of Carlsbad requirements for special inspections, structural
observations, construction matertals testing and off-site fabrication of building components, as prescribed in the statement of
special inspections noted on the approved plans and, as required by the California Building Code.
Signature· ~l,~v!L_ Date: 4/Lw;e
B. CONTRACTOR'S STATEMENT OF RESPONSIBILITY (07 CBC, Ch 17, Section 1706). This section must be completed by the
contractor/ builder I owner-builder.
Contractor's Company Name: t> I\: J !:I ?:tY I A.,14 !tu~(,~-_____ Please check If you ere OWner-Bullder □
Name: (Please prlnl) _......,l?,__,,/l.o=-"'o'-'k=--=sc..... ______________ ~r,j=..co_?:t1:<=f-,'-~l '-'.-\L=L-,"-----
(F,r51) (M.IJ ~
Mailing Address: __ __f__Q___&-"o-")O'----.,.__/ O"---'c.(_( __ ~-~'--'"~---'4,-c-=f::,~-=CA-~-"'~w=~' ~B~------
Email:---'~"'-"4:-0= .. ~=l--=''-'-'.r.;.tu=w'c•M ..... L<....Ci>.._,'-/w4-st=t'"'D"'Q'-'-•-"Y"'9'-'""=------Phone_· _ __,'t'-'(.,"'()"---''---=z.'--q.L---'3'--"t~"'"-"--£,
State of California Contractor's License Number_· ~3_9~~_-r_b_'i~---Expiration Date: 1 / 1 / zo z.o
• I acknowledge and, am aware, of special requirements contained in the statement of special inspections noted on
the approved plans;
• I acknowledge that control will be exercised to obtain conformance with the construction documents approved t>y the
building official;
• I will have in-place procedures for exercising control within our (the contractor's) organization, for the method and
frequency of reporting and the distribution of the reports; and
• I certify that I will have a qualified person within our (the contractor's) organization to exercise such control.
• I will provide a final report I letter in compliance with CBC Section 1704.1.2 prior to requesting final
Inspect/on. ,A~
Signature~: ______ -!:il_...,,_.,,----cs-='--'----'---'----=-..,....-------'Date: ___ if_/ l_-z,_f_,_e ____ _
B-45 Page 1 of 1 Rev. 08/11
DATE: 04/26/18
JURISDICTION: City of Carlsbad
✓• EsG1I
AS.A.Ff built Coinpany
PLAN CHECK#.: cbR2018-0310
PROJECT ADDRESS: 1339 Knowles Ave.
SET: II
PROJECT NAME: Addition and Remodel for Smith Residence
□ APPLICANT
~RIS.
IZ] The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's
codes when minor deficiencies identified below are resolved and checked by building
department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
D The check list transmitted herewith is for your information. The plans are being held at EsGil
until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
D The applicant's copy of the check list has been sent to:
Brooks Worthing
IZ] EsGil staff did not advise the applicant that the plan check has been completed.
D EsGil staff did advise the applicant that the plan check has been completed.
Person contacted:
Date contacted:
Br~ing Telephone#: 760-729-3965
,---(f>~} ) Email: baworthinginc@yahoo.com
0 REMARKS:
By: Javier Snider (RM)
EsGil
Enclosures:
04/19/18
9320 Chesapeake Drive, Suite 208 ♦ San Diego, California 92123 ♦ (858) 560-1468 ♦ Fax (858) 560-1576
DATE: Feb 20, 2018
JURISDICTION: City of Carlsbad
✓• EsG1I
PLAN CHECK#.: cbR2018-0310
PROJECT ADDRESS: 1339 Knowles Ave.
SETI
PROJECT NAME: Addition and Remodel for Smith Residence
D APPLICANT /4 JURIS.
D The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's
codes when minor deficiencies identified below are resolved and checked by building
department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
~ The check list transmitted herewith is for your information. The plans are being held at EsGil
until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
~ The applicant's copy of the check list has been sent to:
Brooks Worthing
D EsGil staff did not advise the applicant that the plan check has been completed.
~ EsGil staff did advise the applicant that the plan check has been completed.
Person contacted: Brooks Worthing Telephone#: 760-729-3965
Date contacted: 2 l,1 Ilg, (by:..-P:P} Email: baworthinginc@yahoo.com
£1Y\A--tt. ~~WIS
0 REMARKS:
By: Rich Moreno
EsGil
Feb 12, 2018
Enclosures:
9320 Chesapeake Drive, Suite 208 ♦ San Diego, California 92123 ♦ (858) 560-1468 ♦ Fax (858) 560-1576
City of Carlsbad cbR2018-0310
Feb 20, 2018
PLAN REVIEW CORRECTION LIST
SINGLE FAMILY DWELLINGS AND DUPLEXES
PLAN CHECK#.: cbR2018-0310 JURISDICTION: City of Carlsbad
PROJECT ADDRESS: 1339 Knowles Ave.
FLOOR AREA:
Addition: 262 sq-ft
Remodel: 236 sq-ft
REMARKS:
DATE PLANS RECEIVED BY
JURISDICTION:
DATE INITIAL PLAN REVIEW
COMPLETED: Feb 20, 2018
FOREWORD (PLEASE READ):
STORIES: 2
HEIGHT: 22-ft ( 12-ft addition)
DATE PLANS RECEIVED BY
ESGIL CORPORATION: Feb 12, 2018
PLAN REVIEWER: Rich Moreno
This plan review is limited to the technical requirements contained in the California version of
the International Residential Code, International Building Code, Uniform Plumbing Code,
Uniform Mechanical Code, National Electrical Code and state laws regulating energy
conservation, noise attenuation and access for the disabled. This plan review is based on
regulations enforced by the Building Department. You may have other corrections based on
laws and ordinance by the Planning Department, Engineering Department, Fire Department or
other departments. Clearance from those departments may be required prior to the issuance of
a building permit.
Present California law mandates that construction comply with the 2016 edition of the California
Code of Regulations {Title 24), which adopts the following model codes: 2015 IRC, 2015 IBC,
2015 UPC, 2015 UMC and 2014 NEC.
The above regulations apply, regardless of the code editions adopted by ordinance.
The following items listed need clarification, modification or change. All items must be satisfied
before the plans will be in conformance with the cited codes and regulations. Per Sec. 105.4 of
the 2015 International Building Code, the approval of the plans does not permit the violation of
any state, county or city law.
To speed up the recheck process, please note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet number, specification section, etc.
Be sure to enclose the marked up list when you submit the revised plans.
City of Carlsbad cbR2018-0310
Feb 20, 2018
[DO NOT PAY -THIS IS NOT AN INVOICE}
VALUATION AND PLAN CHECK FEE
JURISDICTION: City of Carlsbad
PREPARED BY: Rich Moreno
BUILDING ADDRESS: 1339 Knowles Ave.
BUILDING OCCUPANCY: R-3/U
BUILDING AREA Valuation
PORTION ( Sq. Ft.) Multiplier
Addition 262
Remodel 236
Air Conditioning
Fire Sprinklers
TOTAL VALUE
Jurisdiction Code cb By Ordinance
1997 UBC Building Permit Fee
1997 UBC Plan Check fee • I
Type of Review: 0 Complete Review
D Repetitive Fee ····-· • I Repeats
Comments:
□ Other
D Hourly
EsGII Fee
PLAN CHECK#.: cbR2018-0310
DATE: Feb 20, 2018
Reg. VALUE ($)
Mod.
55,385
55,385
$427.68!
$277.991
D Structural Only
1-------11Hr. @ •
$243.781
Sheet 1 of 1
City of Carlsbad cbR2018-0310
Feb 20, 2018
• PLANS
1. Please make all corrections, as requested in the correction list. Submit FOUR new
complete sets of plans for commercial/industrial projects (THREE sets of plans for
residential projects). For expeditious processing, corrected sets can be submitted in
one of two ways:
1. Deliver all corrected sets of plans and calculations/reports directly to the City of
Carlsbad Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760) 602-
2700. The City will route the plans to EsGil Corporation and the Carlsbad Planning,
Engineering and Fire Departments.
2. Bring IJl1SJ. corrected set of plans and calculations/reports to EsGil Corporation, 9320
Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-1468. Deliver all
remaining sets of plans and calculations/reports directly to the City of Carlsbad Building
Department for routing to their Planning, Engineering and Fire Departments.
NOTE: Plans that are submitted directly to EsGil Corporation only will not be reviewed
by the City Planning, Engineering and Fire Departments until review by EsGil
Corporation is complete.
2. All sheets of plans to once again be signed by the person responsible for their
preparation on re-submittal. (California Business and Professions Code).
3. Current energy standard code is 2016. See cover sheet.
• GENERAL RESIDENTIAL REQUIREMENTS
4. Is existing door for Master bedroom to remain at proposed new Hallway?
5. 8040 dual Sleeping rooms shall have a window or exterior door for emergency
escape. Section R310.
a) Windows must have an openable area of at least 5.7 square feet, with the
minimum openable width 20" and the minimum openable height 24". Plans
show 8040 dual sliders with same size panels. These types of windows typically
do no fully open unless windows are casement types. Please clarify window
model to verify egress requirement.
6. Landings at exterior doors. There shall be a landing or floor on each side of each
exterior door. The width of each landing shall not be less than the door served and
have a minimum or 36-inches measured in the direction of travel. Exterior landings
shall be permitted to have a slope not to exceed ¼-inch per foot. Landings or finished
floors shall not be more than 1.5 inches lower than the top of the threshold for outward
swinging exterior doors or 7.75" for doors that do not swing outwards. R311.3.
7. The following locations shall require the use pressure-preservative treated wood
(Section R317.1):
a) All sill plates that rest on concrete or masonry exterior walls and are less than
8" above exposed ground.
City of Carlsbad cbR2018-0310
Feb 20, 2018
8. Callouts on plan sheet A-5 references plan sheet A-4.
• MECHANICAUELECTRICAUPLUMBING
9. Show on the plans the location, type and size (Btu's) of all heating and cooling
appliances or systems.
10. Detail the dryer exhaust duct design from the dryer to the exterior. The maximum
length is 14 feet with a maximum of two 90-degree elbows or provide the
manufacturer's duct length specification description on the plans: Include the dryer
specifications (manufacturer, model, and fuel type) as well as the duct description
(size and type). CMC Section 504.4.2.
11. Please verify service size with electrician. 100-AMP panel appears to be too small for
new footprint.
12. Include on the plans the following specifications for electrical devices installed in
dwellings: CEC Article 210 & 406
a) Arc-fault protection for all outlets (not just receptacles) located in rooms
described in NEC 210.12(A): Kitchens, laundry areas, family, living,
bedrooms, dining, halls, etc.
• MISCELLANEOUS
13. If CalGreen requires a Waste Management Plan, the applicant shall submit the
Carlsbad special form attached at the end of this list.
14. If special inspection is required, the designer shall complete the city's "Special
Inspection Agreement" attached at the end of this list.
15. To speed up the review process, note on this list (or a copy) where each correction
item has been addressed, i.e., plan sheet, note or detail number, calculation page,
etc.
16. Please indicate here if any changes have been made to the plans that are not a result
of corrections from this list. If there are other changes, please briefly describe them
and where they are located in the plans.
• Have changes been made to the plans not resulting from this correction list?
Please indicate:
Yes □ No □
17. The jurisdiction has contracted with Esgil Corporation located at 9320 Chesapeake
Drive, Suite 208, San Diego, California 92123; telephone number of 858/560-1468, to
perform the plan review for your project. If you have any questions regarding these
plan review items, please contact Rich Moreno at EsGil Corporation. Thank you.
City of Carlsbad cbR2018-0310
Feb 20, 2018
Ccityof
Carlsbad
WASTE MANAGEMENT
PLAN
B-59
Dcvcloement Scrvtccs Bulldlnc Division
1635 Faraday Avenue
760-602-2719
www.carbbadca-aov
Job~;_·------------PhoneNumber.c.._ _____________ _ -It. _____________ Estimaledr.ostd~ ~-----------
Type of Project: 0 New COnatructloo O Remodel or T .I. 0 Residential O COmme<tial O Demolition
(cl1eckalllhalapply) QOlhor _________________________ _
Non-llazanlous construcUon -_,... during Ille COUt!l8 of lllls project Shall be reqcled and/or aalva&ad to, re-use at
a minimum of 50% per CAlGreen Sec. 5.408.1. F8'1ura to comply may result In a penany fee up to $1,000. For projects which
ca,sJst of mainly equipment OIWJ/or racklnll, that have a combinad wel()lt of oow construction disposal that dooS not 9l<C8fld
2 Iba per square foal of buildln& area affected by this permtt. may be deemed to meet the 50% minimum requ"1tment upon
approval of llulldlng Department.
Al. TERNATIVE FORMS OF COMPLIANCE: (W Mleetad, do not complete T-1 & 2 below)
0 COnstrucUon -Shall not -2 lbs. per sf. of am. All rec:eip!S -I be proylClad to Iha Bulkllng Ofllctal prior to
final. {This opllon not aPl)lk:able lo< moot construction --) Square feat of construction a,aa ______ x 2 lbs.• _______ tbs. of allowable waste.
0 I plan on using a WASTE MANAGEMENT rolJ.off bin. All rec:eiplS lhall be oro'1<1ad to the Bulldlng Ofllclal prior to final.
Table 1-Estimated Waste (To be fillad out prior to pennlt lssU811Ce •rof81touample on Page 2.)
MATERIALS b. d ,._le 10 be blken to Iba. d Wlta 10 be Wute HaullnC, Company or Re-Use Method lANORll RE..usEO« RECYCLED _,Cone_
Brick/-
C.rdboa<d
D,yw ..
.......... Debris
Lumber/ Wood ---,....,,
Other:
TOTAL.lb&:
Estimated Percentage to be Re-Used or Recycled _____ %
1 cenlfy 11181 the Information provided hnn. to the best of my knOWled&e, Is true anc1 correct.
,.
Offlcial Use Only
0 Plan -0 Plan Denied O Project Valuation Approved _,_by: _____________ _
Palt1af2
City of Carlsbad cbR2018-0310
Feb 20, 2018
Table 2 -Actual Waste rro be OOffll)lered atter oonstruc:tion.)
MATERIALS .._ofwastetallen1o .._.,_
IANDFlU. RE.lJSEOor RECYQ.EO _,Oonclwbt _,_
C.nllx,onl -........... """"'
Lumber/Wood --MilledW-.
Trnh/Ga--
Olher:
TOTAL Iba.:
Actual Percentaee Re-Used or Recycled. _____ ,r,
Official Use Only
w .... Hauln&Complnror Re-Use Mlthod ,_,...., ............. ,_,,
O~GoalAcllleYed O~GcelNolAchOeYOd □-COmpllanceAchleved PenattyPald $ _____ _
-/,lppo,edlJi:c.._ ___________ _
EXAMPLE: Uaa lhl ,-.,. example as a &ulda to canpletln& this form.
MA19IAI.S b.of--tobe ...... to lbs. of .... to .,. -H-USEDor HCYCLS)
_,c-0 :2000 __ ,_
100 '150
~ ' .,, -0 50 .___ 0 1'20
L1mlM'/Woad 500 0 -· 300 ;;_oo
Mi:adWU11 1500 0
Timhl-300 0
0dm: r-oot y,,o-...i.te D ~00
TOTALIK.: ·:,_-7-00 3r?;'O
Percentall!I to be Re-Used or Recycled 59 'Yo
Formula:
Tgtlf Ar:tmd or Btorlr1 X 100 • ,r, R&-OMd or Recyded
WGM HCllllrltg CoMpany cw t .. U.. M9ttiod
Al!.C HOwl.i>,.t\ C,,.
WM I C'#.IA.S,fl:d -g--'-1... OVl.•Si.t:1 ·--. . --
Al!.C HQwi.l"-'I Co.
Mu.ld1,ct £ Rt-w.se:d o..,.-sL.,.,,
waste Maa-\.A ,...~,...,.t
WM I Al!.C ~uU.,,,..
WM
WM
tA.S,tcA as cm.shed '&a.s.t o ....... si.te
(Total Comblnod -) 3870 X 100 • 59% R<Hlsed or llocyded
(2700 + 3870)
Since 59% flllC8eds lhl minimum requirement d ~. this plan coml)lles.
(;ity of Carlsbad cbR2018-0310
Feb 20, 2018
♦CITY OF
CARLSBAD
SPECIAL INSPECTION
AGREEMENT
8-45
Development Services
Building Division
1635 Faraday Avenue
760-602-2719
www.carlsbadca.gov
In accordance with Chapter 17 of the California Building Code the following must be completed when work being performed
requires special inspection, structural observation and construction material testing.
>roject/Permit: ___________ Project Address· _________________ _
A. THIS SECTION MUST BE COMPLETED BY THE PROPERTY OWNER/AUTHORIZED AGENT. Please check~ you are Owner-Builder
□. (If you checked as owner-builder you must also complete Section B of this agreement.)
Name: (Please print1-------=-------------------------------(F1rst1 (MI) (last)
Mailing Addres,-,.__ __________________________________ _
Email_· _________________________ Phone: __________ _
I am: □Property Owner □Property Owner's Agent of Record □Architect of Record □Engineer of Record
State of California Registration Numbe · Expiration Date: ________ _
AGREEMENT: I, the undersigned, declare under penalty of perjury under the laws of the State of California, that I have read,
understand, acknowledge and promise to comply with the C~y of Carlsbad requirements for special inspections, structural
observations, construction materials testing and off-site fabrication of building components, as prescribed in the statement of
special inspections noted on the approved plans and, as required by the California Building Code.
Signatur.,__ ________________________ Date: ____________ _
B. CONTRACTOR'S STATEMENT OF RESPONSIBILITY (07 CBC, Ch 17, Section 1706). This section must be completed by the
contractor/ builder/ owner-builder.
Contractor's Company Name: ___________________ Please check if you are OWner-Builder □
Name: (Please print>-------=--------------------------------
(F,rst) (MI) {Last)
Mailing Address: ___________________________________ _
Email: _________________________ Phone· ___________ _
state of California Contractor's License Number_· __________ Expiration Date: _______ _
• I acknowledge and, am aware, of special requirements contained in the statement of special inspections noted on
the approved plans;
• I acknowledge that control will be exercised to obtain conformance with the construction documents approved by the
building official;
• I will have in-place procedures for exercising control within our (the contractor's) organization, for the method and
frequency of reporting and the distribution of the reports; and
• I certify that I will have a qualified person within our (the contractor's) organization to exercise such control.
• I w/11 provide a final report/ letter in compliance with CBC Section 1704.1.2 prior to requesting final
Inspection.
Signature~: ________________________ ,Date: ___________ _
B-45 Page 1 of 1 Rev. 08/11
STORM WATER POLLUTION PREVENTION NOTES
1. All NECESSARY EQUIPMENT ANO MATERIALS SHALL BE
AVAILABLE ON SITE TO FACILITATE RAPID INSTALLATION
OF EROSION ANO SEDIMENT CONTROL BMPs \\liEN RAIN
IS EMINENT.
2. lHE 01\NER/CONTRACTOR SHALL RESTORE All EROSION
CONTROL DEVICES TO WORKING OROER TO 1HE SATISFACTION
OF lHE CITY INSPECTOR AFTER EACH RUN-OFF PRODUCING
RAINFALL
3. THE OWNER/CONTRACTOR SHALL INSTALL ADDITIONAL EROSION
CONTROL MEASURES AS MAY BE REQUIRED BY lllE CITY
INSPECTOR DUE TO INCOMPLETE GRADING OPERATIONS OR
UNFORESEEN CIRCUMSTANCES \\lilCH MAY ARISE.
4. ALL REMOVABLE PROTECTIVE DEVICES SHALL BE IN Pl.ACE
AT lHE END OF EACH WORKING DAV VMEN lllE AVE (5)
DAY RAIN PROBABILITY FORECAST EXCEEDS FORTY PECENT (40X). SILT AND OlHER DEBRIS SHALL BE REMOVED AIFTER
EACH RAINFALL
5. All GRAVEL BAGS SHALL CONTAIN 3/4 INCH MINIMUM
AGGREGATE.
6. ADEQUATE EROSION AND SEDIMENT CONTROL AND PERIMETER
PROTECTION BEST MANAGEMENT PRACTICE MEASURES MUST
BE INSTALLED AND MAINTAINED.
7. lllE CITY INSPECTOR SHALL HAVE lllE AUlllDRITY TO ALTER
llllS PLAN DURING DR BEFORE CONSTRUCTION AS NEEOED
TO ENSURE COMPLIANCE Wllll CITY STORM WATER QUALITY
REGULATIONS.
OWNER~ CERTIFICATE:
I UNDERSTAND AND ACKNO'M.£DGE THAT I MUST: (1) IMPl.£MENT
BEST MANAGEMENT PRACTICES (BMPS) DURING CONSTRUCllON
ACllvntES TO TiiE MAXIMUM EXlENT PRACllCABI..E TO AVOID
lHE MOBIUZAllON Of' POWJTANTS SUCH ;s SEDIMENT AND TO
A VOID lHE EXPOSURE OF STORM WA lER TO CONSTRUCTION
REIAlED POWITANlS; AND (2) ADHERE TO, AND AT AU TIMES,
COMPLY YflTH THIS 0TY APPR0\£0 llER 1 CONSTRUCTION SWPP
lHROUGHOUT THE DURATION OF TiiE CONSlRUCllON ACll\'lTIES
UNTIL TiiE CONS1RUCT10N WORK IS COMPL£TE AND APPRO'fE>
BY THE CITY Of CARLSBAD.
OWNER(S}/OWNER S AGENT NAME (PRINT)
OWNER(s)/OWNER's AGENT NAME (SIGNAlURE)
E-29
DATE
REc1=1v1=0 ,_
STORM WATER COMPLIANCE FORM
TIER 1 CONSTRUCTION SWPPP
'018
CITY OF CARLSBAD
BUJL0 1"1" ~·--
CB 14,CI\'-' 1 u y "'-1
E-29 ,,.,,_ ,__,. .. SW .
BEST MANAGEMENT PRACTICES (BMP) SELECTION TABLE -·~ ---Sediment Control BMPs c.:=,.. ·--Waste Management and Materials
BMP, Managemenl BMPs Polullon Conlrd BMPs
~ ~ 1 ,g I ~ i ~ ~ t i 5 i ! C ~ Ii
-i .5 0 ~-~ E I :r & Best Management Pracllce* .., E ij.!! 8-I i,g ·a
= -fj I~ j F m 8-8;, i i Ji 6 " -!] (BMP) Descriplion ➔ 8 i ~ ~ go c!E .§• 1& " I 1 .i i ~ m E :r 0 ii ]; .!! ~l ! g, j .: e] i g, !! .!! ~ l! ... '8 lij -i .,,. -~ l i'8 £1 ~ ~ s f:; .§ "'0 ii is •8 .... l :io -G ;d ffi !'I 6 ~ ~:!Z J in ,>; C ui& 3'~ lin ~ bl-=--➔ ~ ~ ~ '; ~ ~ ~ ~ : ~ m 0 'I ~ ~ m ' N ~ ~ ~ s ill ill ~ ' ;J; ' J, ' i! i! ' ' --·--[:! "' "' ~ ~ ii! ii! ii! " " " " ""'"• Disturbance
Trenchln """""' .
Sloclrnllnn
DrDlln
Concrete As----;;halt Sawcuttln"
Concrete Aalwork
Conduit e Installation
Stucco ortar Work
Waste 0 "" Stonin Down Area
ent Maintenance and Fuelh"
Hazardous SUbslance Use • Dewoterin"
Sile Access Across Ott
other 111st':
Instructions:
1. Check the box to the left of an •pllcable construction octMty (first column) expected to occur dul'fl9 construction.
2. loccded alot!.9 the lop of the BMP Tobie Is a list of BMP's with It's corresponding Cdlfomla Stormwater auarity Association (CASOA) de!ijgnotion number. Choose one or more BMPS }1)U Intend to use wring constructkln from the fist. Check the box where the chosen activity row Intersects with the Bl.IP column.
3. Refer to the CAS0A construction handbook• for ilfonnatlon and detois of the choaen BMPs and how to apply them to the project
PROJECT INFORMATION
-l! l-1; ]go
~5 "'" m ' ii!
$1eAdd<ns t!i&l KNowl~
Auessor"s '""" Number. \ ';,(p -l ~4--
-l! ii
.!l E bi §j
m ' ii!
SHOW THE LOCATIONS OF ALL CHOSEN BMPs ABOVE
ON THE PROJECTS SITE PLAN/EROSION CONTROL PLAN.
SEE THE REVERSE SIDE OF THIS SHEET FOR A SAMPLE
EROSION CONTROL PLAN. Nams :ltzroP'(".::> WV'f-tl'.\ll'Jf\
-BM P's are subject to field inspection-
Page 1 of 1
24 Hour Phone:
ConstrueUcn Threat to Storm Woter Quality
(Oieck Box)
0 MEDIUM !Si{LDW
REV 02/16
Apr1418,05:58a RECEJVE1)
APR 16 2018
SINGLE FAMILY DWELLING TY OF CAf\L~~:J?
ELECTRICAL SERVICE LOAD CALCULA1t~ON--JG DiVi;:;.;u:'1
OPTIONAL METHOD NEC 220-30
As an alternative method, the STANDARD METHOD,
found in ARTICLE 220 of the National Electric Code, may be used
( S M \ Tl.\-'f< e-:: t l'>G; ,-.,c_r,;·•)
l. GENERAL LIGHTING LOADS ..
Dwellin2 2 (,av Gq-ft." J VA= 713.!/0 VA
Small appliance loads -220-16 (a) 1500 VA x Lcircuits = 9000 VA
Laundry load -220-16(b) 1500 VA x _k_circuits = 3000 VA
General Lighting Tota! 19, fWO VA
2. COOKING EQUIPMENT LOADS -:Sameplate Va:ue
Range _____ VA=
Cooktop ____ VA =
Oven(s) ____ VA =
_.zrk;..__VA
-----""(Zj_ y A
_-""/$ __ VA
Cooking Equipment Total ___ VA
3. ELECTRIC DRYER 220-18 (Nameplate, 5000 VA minimum)
Dryer _____ VA =
4. FIXED APPLIANCE LOADS 230-30(b3)
Dish washer =
Disposal=
Compactor=
Water }:!eater =
Hydrornassage Bathtub=
Microwave Oven =
Built-in Vacuum=
Dryer Total ¢
/$00 VA
I ,';¢0 VA
--"'</!'-._VA
_ _,,~,,___VA
--"~--VA
/S:oa VA
VA
cl VA 0 {f VA
Fixed Appliance Total 'ff oO VA
5. OPTIONAL SUBTOTAL (Add all of the above totals) Z'I, '!,9() VA
6. APPLYING DEMA'.\'D FACTORS· TABLE 220-30
. . { F,n;t 10.000 VA x I 00% ~ Optional Silbtotal (from line 5) R -. /'I, ;;Q::) \'. 40"' ema1n1ng ..L.!.-L.?-• _ -... , x 1c ;;;;::
7. HEATING OR AC LOAD-TABLE 220-30
Larger of the Heating or AC Load =
8. OPTIONAL LOADS TOTAL (Add totals from lines 6 and 7) =
9. MINIMUM SERVICE SIZE= Option;~~~~tTotat =
(Please put lo!al on front of card under Compured Load)
10,000VA
2• 75", VA
/5'gt:J VA
/7, 2'5G:> VA
72-Ampere