HomeMy WebLinkAbout1440 BUENA VISTA WAY; ; CB072033; Permit10-162007
Job Address
Permit Type
Parcel No
Valuation
Occupancy Group
# Dwelling Units
Bedrooms
Project Title
City of Carlsbad
1635 Faraday Av Carlsbad CA 92008
Residential Permit Permit No CB072033
Building Inspection Request Line (760) 602 2725
1440 BUENA VISTA WY CBAD
RESDNTL Sub Type 2DU
1561205200 Lot# 0
$61 401 00 Construction Type VN
Reference #
1 Structure Type MF2 4
1 Bathrooms 1
HALL RES 499 SF 2DU DETACHED &
389 SF ADJOINING WORKSHOP
Status
Applied
Entered By
Plan Approved
Issued
Inspect Area
Ong PC#
Plan Check#
ISSUED
08/01/2007
RMA
10/16/2007
10/16/2007
Applicant
HALL FAMILY TRUST 07 24 06
1440 BUENA VISTA WAY
CARLSBAD CA 92008
Owner
HALL FAMILY TRUST 07 24 06
1440 BUENA VISTA WAY
CARLSBAD CA 92008
Building Permit
Add I Building Permit Fee
Plan Check
Add I Plan Check Fee
Plan Check Discount
Strong Motion Fee
Park in Lieu Fee
Park Fee
LFM Fee
Bridge Fee
Other Bridge Fee
BTD #2 Fee
BTD #3 Fee
Renewal Fee
Add I Renewal Fee
Other Building Fee
HMP Fee
Pot Water Con Fee
Meter Size
Add I Pot Water Con Fee
Reel Water Con Fee
$400 26
$000
$26017
$000
$000
$614
$000
$000
$000
$000
$000
$000
$000
$000
$000
$000
$000
$000
$000
$000
Meter Size
Add I Reel Water Con Fee
Meter Fee
SDCWA Fee
CFD Payoff Fee
PFF (31 05540)
PFF (4305540)
License Tax (31 041 93)
License Tax (43041 93)
Traffic Impact Fee (3105541)
Traffic Impact Fee (4305541)
Sidewalk Fee
PLUMBING TOTAL
ELECTRICAL TOTAL
MECHANICAL TOTAL
Housing Impact Fee
Housing InLieu Fee
Housing Credit Fee
Master Drainage Fee
Sewer Fee
Additional Fees
TOTAL PERMIT FEES
$000
$000
$000
$000
$1 11750
$1 031 54
$000
$000
$324 30
$365 70
$000
$13200
$2250
$4350
$2 925 00
$000
$000
$000
$1 058 00
$000
$7 686 61
Total Fees $7 686 61 Total Payments To Date $26517 Balance Due $7,421 44
Inspector
FINAL
Date Clearance
NOTICE Please take NOTICE that approval of your project includes the Imposition of fees dedications reservations or other exactions hereafter collectively
refer ed to as fees/exactions You have 90 days from the date this permit was issued to protest imposition of these fees/exactions If you protest them you must
follow the protest procedures set forth in Government Code Section 66020(a) and file the protest and any other required information with the City Manager for
processing in accordance with Carlsbad Municipal Code Section 3 32 030 Failure to timely follow that procedure will bar any subsequent legal action to attack
review set aside void or annul their imposition
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection fees and capacity
changes nor planning zoning grading or other similar application processing or service fees in connection with this project NOR DOES IT APPLY to any
fees/exactions of which you have previously been given a NOTICE similar to this, or as to which the statute of limitations has previously otherwise expired
City of Carlsbad
1635 Faraday Ave Carlsbad CA 92008
760-6022717/2718/2719
Fax 7606028558
Building Permit Application
Plan Check No
Plan Ck Deposit
Date 1
JOB ADDRESS SUITE#/SPACE#/UNIT#
CT/PROJECT*# BEDROOMS # BATHROOMS TENANT BUSINESS NAME CONSTR TYPE OCC GROUP
DESCRIPTION OF WORK
359
EXISTING USE PROPOSED USE GARAGE (SF)PATIOS (SF)
"fa
DECKS (SF)FIREPLACE
YES D #NO.R
AIR CONDITIONING
YES D
FIRE SPRINKLERS
YES** NOD
CONTACT NAME (If Different fom Applicant)APPLICANT NAME
ADDRESS ADDRESS
VIST*
CITY STATE ZIP CITY ZIP
PHONE FAX PHONE
EMAIL EMAIL
PROPERTY OWNER NAME CONTRACTOR BUS NAME
ADDRESS ADDRESS
CITY STATECA ZIP CITY STATE ZIP
PHONE FAX PHONE FAX
EMAIL EMAIL
ARCH/DESIGNER NAME & ADDRESS CLASS CITY BUS LIC#
(Sec 70315 Business and Professions Code Any City or County which requires a permit to construct, alter, improve demolish or repair any structure, prior to its issuance also requires the applicant for such permit to file a signed statement that he ist—j . .. .L , .L. /•__. i ..... r/-<,apter 9 commending with Section 7000 of Division 3 of the Business and Professions Code) or that he is exempt therefrom and the basis for the alleged exemption Any violation of
- -•' —'- -' --• more than five hundred dollars {$500}) '
licensed pursuant to the provisions of the Contractors ... , ,
Section 70315 by any applicant for a permit subjects the applicant to a
Workers Compensation Declaration / hereby affirm under penalty of perjury one of the following declarations
L"J I have and will maintain a certificate of consent to self insure for workers compensation as provided by Section 3700 of the Labor Code for the performance of the work for which this permit is issued
n I have and will maintain workers compensation as required by Section 3700 of the Labor Code for the performance of the work for which this permit is issued My workers compensation insurance carrier and policy
number are Insurance Co Policy No Expiration Date
This section need not be completed if the permit is for one hundred dollars ($100) or less
n Certificate of Exemption I certify that in the performance of the work for which this permit is issued I shall not employ any person in any manner so as to become subject to the Workers Compensation Laws of
California WARNING Failure to secure workers compensation coverage is unlawful and shall subject an employer to criminal penalties and civil fines up to one hundred thousand dollars (&100 000) in
addition to the cost of compensation damages as provided for in Section 3706 of the Labor code interest and attorney s fees
J£$ CONTRACTOR SIGNATURE DATE
affirm that I am exempt from Contractors License Law for the following reason
B I as owner of the property or my employees with wages as their sole compensation will do the work and the structure is not intended or offered for sale (Sec 7044 Business and Professions Code The Contractors
License Law does not apply to an owner of property who builds or improves thereon and who does such work himself or through his own employees provided that such improvements are not intended or offered for
sale If however the building or improvement is sold within one year of completion the owner builder will have the burden of proving that he did not build or improve for the purpose of sale)
O I as owner of the property am exclusively contracting with licensed contractors to construct the project (Sec 7044 Business and Professions Code The Contractor s License Law does not apply to an owner of
property who builds or improves thereon and contracts for such projects with contractor(s) licensed pursuant to the Contractor s License Law)
O I am exempt under Section Business and Professions Code for this reason
1 I personally plan to provide the major labor and materials for construction of the proposed property improvement O Yes D No
2 I (have / have not) signed an application for a building permit for the proposed work
3 I have contracted with the following person (firm) to provide the proposed construction (include name address / phone / contractors license number)
4 I plan to provide portions of the work but I have hired the following person to coordinate supervise and provide the major work (include name / address / phone / contractors license number)
5 I will provide some of the work but I have contracted (hired) the following persons to provide the work indicated (include name / address / phone / type of work)
Is the applicant or future building occupant required to submit a business plan acutely hazardous materials registration form or risk management and prevention program under Sections 25505 25533 or 25534 of the
Presley Tanner Hazardous Substance Account Act' O Yes CJ No
Is the applicant or future building occupant required to obtain a permit from the air pollution control district or air quality management district' n Yes O No
Is the facility to be constructed within 1 000 feet of the outer boundary of a school site' D Yes O No
IF ANY OF THE ANSWERS ARE YES
EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT
I hereby affirm that there is a construction lending agency for the performance of the work this permit is issued (Sec 3097 (i) Civil Code)
Lender's Name Lender's Address
I cerdfythatl have read the application and state thattheabove information iscorrectandthatthemformaton on the plans isaccurate I agree to comply with all Cityordmancesand State laws relaftngtobuildingconstruction
thereby authorize representative of the City of Carlsbad to enter upon Die above mentioned property for inspection purposes I ALSO AGREE TO SAVE INDEMNIFY AND KEEP HARMLESS THE CITY OF CARLSBAD
AGAINST ALL LIABILITIES JUDGMENTS COSTS AND EXPENSES WHICH MAY IN ANY WAY ACCRUE AGAINST SAID CITY IN CONSEQUENCE OF THE GRANTING OF THIS PERMIT
OSHA An OSHA permit is required for excavations over 5 0 deep and demolition or construction of structures over 3 stones in height
EXPIRATION Every permit issued by the Building Official under the provisions of this Code shall expire by limitation and become null and void if the building or work authonzed by such permit is not commenced within
180 days from the date of such permit or if th§ bj^lellh^prjiprk authonzed b/such permit is suspended or abandoned at any time after the work B commenced for a penod of 180 days (Section 106 4 4 Uniform Building Code)
> APPLICANTS SIGNATURE DATE
City of Carlsbad Bldg Inspection Request
For 03/31/2008
Permit* CB072033
Title HALL RES 499 SF 2DU DETACHED &
Description 389 SF ADJOINING WORKSHOP)
Type RESDNTL Sub Type 2DU
Job Address 1440 BUENA VISTA WY
Suite Lot 0
Location
APPLICANT HALL FAMILY TRUST 07 24 06
Owner HALL FAMILY TRUST 07 24 06
Remarks AM PLEASE
Total Time
Inspector Assignment PC
Phone
Inspector
Requested By NA
Entered By CHRIS
CD Description
19 Final Structural
29 Final Plumbing
39 Final Electrical
49 Final Mechanical
Act—v Comments
N6HE?.
Comments/Notices/Holds
Notice HOUSING FEE OF $2925 MUST BE PROCESSED WITH THE BUILDING FEES AND PAID ALL AT ONCE
Associated PCRs/CVs Original PC#
CommentsDate
02/19/2008
01/24/2008
01/24/2008
01/15/2008
01/15/2008
01/15/2008
11/27/2007
11/27/2007
11/19/2007
11/19/2007
11/14/2007
11/14/2007
Inspection History
Description
17 Interior Lath/Drywall
14 Frame/Steel/Boltmg/Welding
44 Rough/Ducts/Dampers
13 Shear Panels/HDs
15 Roof/Reroof
24 Rough/Topout
31 Underground/Conduit Wiring
34 Rough Electric
11 Ftg/Foundation/Piers
23 Gas/Test/Repairs
21 Underground/Under Floor
23 Gas/Test/Repairs
Act
AP
AP
AP
AP
AP
AP
AP
AP
AP
AP
AP
PA
Insp
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC
PC VISUAL ON GAS LINE OK
EsGil Corporation
In Partnership with government for 'Smlding Safety
DATE 9/26/07
'JURISJ)
JURISDICTION Carlsbad tTPCATTREVIEWER
a FILE
PLAN CHECK NO 072033 SET III
PROJECT ADDRESS 1440 Buena Vista Way
PROJECT NAME Hall Accessory Dwelling unit with Workshop
The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction s building codes
IXI The plans transmitted herewith will substantially comply with the jurisdiction s building codes
when minor deficiencies identified below are resolved and checked by building department staff
The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck
The check list transmitted herewith is for your information The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck
I The applicant s copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person
The applicant s copy of the check list has been sent to
Esgil Corporation staff did not advise the applicant that the plan check has been completed
Esgil Corporation staff did advise the applicant that the plan check has beeri
Person contacted Telephone #
Mail Telephone Fax In Person
REMARKS Please add City soils stamp to the plan
By Tamara Fischer Enclosures
Esgil Corporation
D GA D MB D EJ D PC 9/18/07
9320 Chesapeake Drive Suite 208 + San Diego California 92123 * (858)560 1468 + Fax (858) 560 1576
EsGil Corporation
In Partnership with government for 'Budding Safety
DATE 9/5/07 O^APPI ICANT
JURISDICTION Carlsbad a PLAN REVIEWER
a FILE
PLAN CHECK NO 072033 SET II
PROJECT ADDRESS 1440 Buena Vista Way
PROJECT NAME Hall Accessory Dwelling unit with Workshop
I I The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction s building codes
The plans transmitted herewith will substantially comply with the jurisdiction s building codes
when minor deficiencies identified below are resolved and checked by building department staff
The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck
A] The check list transmitted herewith is for your information The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck
The applicant s copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person
The applicant s copy of the check list has been sent to
Kevin Hall
1440 Buena Vista Way Carlsbad CA 92008
Esgil Corporation staff did not advise the applicant that the plan check has been completed
Esgil Corporation staff did advise the applicant that the plan check has been completed
Person contacted Kevin Hall Telephone # 760 758 5370
Date cojijacted yy/-/rf(b$fa) Fax # 858550-3410
Mail/ Telephone/ Fax l/ln Personv y
REMARKS Please note that the area breakdown is slightly different than I reported on
the original transmittal 499 sq ft dwelling, 389 sq ft garage
By Tamara Fischer Enclosures
Esgil Corporationn GA n MB n EJ n PC 8/28/07
9320 Chesapeake Drive Suite 208 + San Diego California 92123 *• (858)560 1468 + Fax (858) 560 1576
Carlsbad 072033
9/5/07
Please make all corrections as requested in the correction list Submit three new
complete sets of plans for commercial/industrial projects (two sets of plans for residential
projects) For expeditious processing corrected sets can be submitted in one of two
ways
1 Deliver all corrected sets of plans and calculations/reports directly to the City of
Carlsbad Building Department 1635 Faraday Ave , Carlsbad CA 92008 (760)602
2700 The City will route the plans to EsGil Corporation and the Carlsbad Planning
Engineering and Fire Departments
2 Bring one corrected set of plans and calculations/reports to EsGil Corporation 9320
Chesapeake Drive Suite 208 San Diego CA 92123 (858)5601468 Deliver all
remaining sets of plans and calculations/reports directly to the City of Carlsbad Building
Department for routing to their Planning Engineering and Fire Departments
NOTE Plans that are submitted directly to EsGil Corporation only will not be reviewed by
the City Planning Engineering and Fire Departments until review by EsGil Corporation is
complete
NOTE The items listed below are from the previous correction list These items
have not been adequately addressed The numbers of the items are from the
previous check list and may not necessarily be in sequence The notes in bold are
current
I All sheets of plans must be signed by the person responsible for their
preparation (California Business and Professions Code) Current sets are
signed This will be verified on final sets Current sets are signed This will be
verified on final sets
I1 Garage requires one hour fire protection (i e 5/8 Type X drywall) on the garage
side of walls and ceiling common to the dwelling Table 3 B Section 302 4
Section shows that workshop/dwelling wall does not extend to the roof
sheathing Provide 2 layers 5/8 type x on the ceiling Section shows that
ceiling joists are 16 o c while framing plans shows 24 oc 1 layer of 1/2
type C will not work for 24" o c spacing
12 Applicant to sign City Soils stamp prior to permit issuance agreeing to provide a
soil report if the inspector detects problems This will be done at the City
14 If hold downs are required note on plan that hold down anchors must be tied in
place prior to foundation inspection Section 108 5 2 See correction #22 below
Unable to find this noted on the foundation plan
15 Please revise section A on sheet A2 0 to show footings extending minimum 12
below lowest adjacent grade show interior footing and show that finish grade
slopes away from the building to provide drainage Please dimension 12
below the bottom of the slab at interior footing on section A and detail 1 on
sheet A2 0
Carlsbad 072033
9/5/07
16 Please show the outline of the existing bomb shelter If the loads from the
proposed structure will impact the bomb shelter at all a licensed engineer or
architect will be required to provide a design
a) Because the building is impacting the existing bomb shelter
structure, please provide a design by a California licensed engineer
or architect and have him or her stamp and sign the plans
b) Detail 3 of A2 0 shows footings on both sides of the bomb shelter,
but only one footing is shown on the foundation plan
c) Show spacing of floor joists on detail 3 of A2 0 and specify all wood
framing at that detail to be pressure treated
d) How will the underfloor space (abandoned bomb shelter) be
ventilated9
e) Please provide an accurate detail for footing above bomb shelter
Detail 2/A2 which is referenced does not show the bomb shelter
22 In order to make the building comply with the conventional construction
provisions for braced panels in section 2320 provide the following otherwise
provide lateral calculations by a licensed engineer or architect
c) A minimum 4 braced panel or 2 8 alternate braced panel at the west wall
of living room within 8 of the north corner of the building Alternate
braced panel requires hold downs at each end and a minimum of 2
anchor bolts and must be plywood not OSB Please specify the nailing
of the plywood at alternate braced panel
23 Detail shear transfer connections at walls where rafters are parallel and at
interior shear walls Please show interior shear walls to extend to the roof
sheathing as the shear transfer detail provided is only intended when you
have drag trusses on either side of the shear wall
37 New residential units must be pre-plumbed for future solar water heating Note
"two roof jacks must be installed where the water heater is in the one story garage
and directly below the most south facing roof (City Ordinance No 8093) This
correction still applies even if the water heater is outside the building
envelope
38 Note two 3/4 copper pipes must be installed to the most convenient future solar
panel location when the water heater is not in a one story garage and is not directly
below the most south facing roof (City Ordinance No 8093) See bold remarks
at #37
39 All piping for present or future solar water heating must be insulated when in areas
that are not heated or cooled by mechanical means (City Policy) See bold
remarks at #37
Carlsbad 072033
9/5/O7
• To speed up the review process note on this list (or a copy) where each
correction item has been addressed i e plan sheet note or detail number
calculation page etc
• Please indicate here if any changes have been made to the plans that are not a
result of corrections from this list If there are other changes please briefly
describe them and where they are located in the plans
• Have changes been made to the plans not resulting from this correction list?
Please indicate
• Yes Q No a
• The jurisdiction has contracted with Esgil Corporation located at 9320
Chesapeake Drive Suite 208 San Diego California 92123 telephone number of
858/560 1468 to perform the plan review for your project If you have any
questions regarding these plan review items please contact Tamara Fischer at
Esgil Corporation Thank you
EsGil Corporation
In Partnership a/it/i government for 'BuiUing Safety
DATE 8/9/07
_
JURISDICTION Carlsbad a PLAN REVIEWER
a FILE
PLAN CHECK NO 072033 SET I
PROJECT ADDRESS 1440 Buena Vista Way
PROJECT NAME Hall Accessory Dwelling unit with Workshop
The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction s building codes
The plans transmitted herewith will substantially comply with the jurisdiction s building codes
when minor deficiencies identified below are resolved and checked by building department staff
The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck
X] The check list transmitted herewith is for your information The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck
The applicant s copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person
XI The applicant s copy of the check list has been sent to
Kevin Hall
1440 Buena Vista Way Carlsbad CA 92008
Esgil Corporation staff did not advise the applicant that the plan check has been completed
XI Esgil Corporation staff did advise the applicant that the plan check has been completed
Person contacted Kevjn Hall Telephone # 760 758-5370
Date contacted^/<?/c?7(b>/^ Fax # 8585503410
Mail Telephone./ Fax ./In Person
REMARKS
By Tamara Fischer Enclosures
Esgil Corporation
D GA D MB D EJ D PC 8/2/07
9320 Chesapeake Drive Suite 208 + San Diego California 92123 * (858)560 1468 + Fax (858) 560 1576
Carlsbad O72O33
8/9/07
PLAN REVIEW CORRECTION LIST
SINGLE FAMILY DWELLINGS AND DUPLEXES
PLAN CHECK NO 072033 JURISDICTION Carlsbad
PROJECT ADDRESS 1440 Buena Vista Way
STORIES 1
HEIGHT 12 approxperUBC
FLOOR AREA 561 sq ft dwelling
327 sq ft workshop
REMARKS
DATE PLANS RECEIVED BY
JURISDICTION
DATE INITIAL PLAN REVIEW
COMPLETED 8/9/07
DATE PLANS RECEIVED BY
ESGIL CORPORATION 8/2/07
PLAN REVIEWER Tamara Fischer
FOREWORD (PLEASE READ)
This plan review is limited to the technical requirements contained in the Uniform Building Code
Uniform Plumbing Code Uniform Mechanical Code National Electrical Code and state laws
regulating energy conservation noise attenuation and access for the disabled This plan review
is based on regulations enforced by the Building Department You may have other corrections
based on laws and ordinance by the Planning Department Engineering Department Fire
Department or other departments Clearance from those departments may be required prior to
the issuance of a building permit
Present California law mandates that residential construction comply with the 2001 edition of
the California Building Code (Title 24) which adopts the following model codes 1997 UBC
2000 UPC 2000 UMC and 2002 NEC
The above regulations apply to residential construction regardless of the code editions adopted
by ordinance
The following items listed need clarification modification or change All items must be satisfied
before the plans will be in conformance with the cited codes and regulations Per Sec 106 4 3
1997 Uniform Building Code the approval of the plans does not permit the violation of any
state county or city law
To speed up the recheck process, please note on this list (or a copy) where each
correction item has been addressed, i e. plan sheet number, specification section, etc
Be sure to enclose the marked up list when you submit the revised plans
Caflsbad O72033
8/9/07
Important Notice Regarding the 2007 CBC
If you are an architect engineer designer or contractor that performs work within the
State of California please be advised that a new building code will take effect on
January 1 2008 The new building code is based on the 2006 International Building
Code (IBC) and it is significantly different than the Uniform Building Code (UBC)
All plan review applications submitted after December 31. 2007 will be required to
comply with the new code
The 2007 CBC is currently available for purchase directly from the International Code
Council at www iccsafe org
Please make all corrections as requested in the correction list Submit three new
complete sets of plans for commercial/industrial projects (two sets of plans for residential
projects) For expeditious processing corrected sets can be submitted in one of two
ways
1 Deliver all corrected sets of plans and calculations/reports directly to the City of
Carlsbad Building Department 1635 Faraday Ave Carlsbad CA 92008 (760)602-
2700 The City will route the plans to EsGil Corporation and the Carlsbad Planning
Engineering and Fire Departments
2 Bring one corrected set of plans and calculations/reports to EsGil Corporation 9320
Chesapeake Drive Suite 208 San Diego CA 92123 (858)5601468 Deliver all
remaining sets of plans and calculations/reports directly to the City of Carlsbad Building
Department for routing to their Planning Engineering and Fire Departments
NOTE Plans that are submitted directly to EsGil Corporation only will not be reviewed by
the City Planning Engineering and Fire Departments until review by EsGil Corporation is
complete
1 All sheets of plans must be signed by the person responsible for their
preparation (California Business and Professions Code) Current sets are
signed This will be verified on final sets
2 Specify on the Title Sheet of the plans the gross floor area of each element of
this project including dwelling and workshop Please separate out the areas (It
should be 561 sq ft dwelling 327 sq ft workshop)
3 Please dimension the distance between the proposed building and the existing
house on the site plan
4 Openable window area in bathrooms and water closet compartments is required
to be 1/20 of area 2 sq ft is required while 1 5 sq ft provided Section
12033
5 Provide mechanical ventilation capable of providing five air changes per hour in
bathrooms and water closet compartments if required openable windows are not
Carlsbad 072033
8/9/07
provided Section 1203 3
6 Dimension on the plans 30 clear width for water closet compartments Section
2904
7 Glazing in the following locations should be of safety glazing material in
accordance with Section 2406 4 (see exceptions)
a) Fixed or operable panels adjacent to a door where the nearest exposed
edge of the glazing is within a 24 inch arc of either vertical edge of the door
in a closed position and where the bottom exposed edge of the glazing is
less than 60 inches above the walking surface Window next to door in
living room
8 Required exit doorways shall be not less than 36" in width and not less than 6 8
in height Section 1003 3 1 3 (Workshop door)
9 Per local ordinance a Class A roof is required Please specify composite
shingles to be Class A
10 Show the required ventilation for attics (or enclosed rafter spaces formed where
ceilings are applied directly to the underside of roof rafters) The minimum vent
area is 1/150 of attic area (or 1/300 of attic area if at least 50% of the required
vent is at least 3 feet above eave vents or cornice vents) Show area required
and area provided Section 1505 3
11 Garage requires one hour fire protection (i e 5/8 Type X drywall) on the garage
side of walls and ceiling common to the dwelling Table 3 B Section 302 4
Section shows that workshop/dwelling wall does not extend to the roof
sheathing Provide 2 layers 5/8 type x on the ceiling
12 Applicant to sign City Soils stamp prior to permit issuance agreeing to provide a
soil report if the inspector detects problems
13 If required show size embedment and location of hold down anchors on
foundation plan Section 106 3 3 See correction #22 below
14 If hold downs are required note on plan that hold down anchors must be tied in
place prior to foundation inspection Section 108 5 2 See correction #22 below
15 Please revise section A on sheet A2 0 to show footings extending minimum 12
below lowest adjacent grade show interior footing and show that finish grade
slopes away from the building to provide drainage
16 Please show the outline of the existing bomb shelter If the loads from the
proposed structure will impact the bomb shelter at all a licensed engineer or
architect will be required to provide a design
Carlsbad O72O33
8/9/07
17 The footing at detail 1 of A2 0 cannot be used for bearing or shear walls (It
would need 12 depth below lowest adjacent grade an additional #4 bar at the
top and 5/8 anchor bolts with plate washers for shear walls) It appears ceiling
joists are bearing on interior walls as they would be overspanned otherwise
18 Please identify what PT sole plates are sitting on at detail 3/A2 0 and show 18
minimum clearance to floor joists unless they are pressure treated
19 Show double top plate with minimum 48 lap splice Section 2320 11 2 Wall
section sheet A2 0 shows one top plate
20 Show stud size and spacing
21 Please specify the lengths of shear panels shown
22 In order to make the building comply with the conventional construction
provisions for braced panels in section 2320 provide the following otherwise
provide lateral calculations by a licensed engineer or architect
a) A minimum 4 braced panel to the roof sheathing at wall between bath
and workshop
b) A minimum 4 braced wall panel to roof sheathing at wall between
bedroom and kitchen
c) A minimum 4 braced panel or 2 8 alternate braced panel at the west wall
of living room within 8 of the north corner of the building Alternate
braced panel requires hold downs at each end and a minimum of 2
anchor bolts and must be plywood not OSB
23 Detail shear transfer connections at walls where rafters are parallel and at
interior shear walls
24 Specify roof diaphragm plywood and/or particle board thickness grade and
panel span rating Table 23 ll-E-1
25 Show location of attic access with a minimum size of 22 x30 unless the
maximum vertical headroom height in the attic is less than 30 Access must be
provided to each separated attic area shall be located in a hallway or other
readily accessible location and 30 headroom clearance is required above the
opening Section 1505 1
26 Note on the plans that receptacle outlet locations will comply with NEC Art
210-52(a) As shown bedroom and living room do not comply
27 For a single family dwelling unit (and for each unit of a duplex) show that at least
one receptacle outlet accessible at grade level will be installed outdoors at the
front and back of the dwelling NEC Art 210 52 (e) This receptacle must be
GFCI protected
Carlsbad O72033
8/9/O7
28 GFCI protected receptacle outlets are required within 25 feet of all mechanical
equipment (heating air conditioning and refrigeration equipment) Please show
on plans NEC 21063
29 All bedroom branch circuits now require arc fault protection Note clearly on the
plans that Bedroom branch circuits will be arc fault circuit protected NEC Art
210-12(b)
30 Show on the plan that ground fault circuit interrupter protection complies with
NEC Art 2108 which reads as follows AII125-volt single phase 15 and 20
ampere receptacles installed in bathrooms garages (workshop) outdoors and
kitchen counters
31 Specify the water heater type and capacity on the plans Provide manufacturer s
information for water heater showing it is approved for an outdoor location
32 Show T and P valve on water heater and show route of discharge line to exterior
UPC Section 608 5
33 In Seismic Zones 3 and 4 show that water heater is adequately braced to resist
seismic forces Provide two straps (one strap at top 1/3 of the tank and one strap
at bottom 1/3 of the tank) UPC Section 510 5
34 Package D requires a maximum SHGC of 4 for fenestration products (windows)
CF-1R shows SHGC of 65
35 The values shown for area of fenestration products on page 2 of CF 1R are
incorrect They should match the areas shown on the fenestration worksheet
36 Show on the plans compliance with the residential energy lighting requirements
(Mandatory requirement)
a) In the kitchen at least one half of the wattage rating of the fixtures must be
high efficacy with non-high efficacy fixtures switched separately Note
Approximately % of the fixtures will be required to be of the high efficacy
variety Fixture shown on electrical plan does not appear to be high
efficacy
b) In bathrooms and workshop all fixtures must be high efficacy style or be
controlled by a manually on occupancy sensor
c) Outdoor lighting fixtures are required to be high efficacy or controlled by a
combination photocontrol/motion sensor
Note Generally a high efficacy style of fixture is fluorescent complete with electronic
ballasts Regular incandescent quartz halogen and halogen MR lamps do not comply
Carlsbad 072033
8/9/07
37 New residential units must be pre-plumbed for future solar water heating Note
two roof jacks must be installed where the water heater is in the one story garage
and directly below the most south facing roof (City Ordinance No 8093)
38 Note two 3/4 copper pipes must be installed to the most convenient future solar
panel location when the water heater is not in a one story garage and is not directly
below the most south facing roof (City Ordinance No 8093)
39 All piping for present or future solar water heating must be insulated when in areas
that are not heated or cooled by mechanical means (City Policy)
• To speed up the review process note on this list (or a copy) where each
correction item has been addressed i e plan sheet note or detail number
calculation page etc
• Please indicate here if any changes have been made to the plans that are not a
result of corrections from this list If there are other changes please briefly
describe them and where they are located in the plans
• Have changes been made to the plans not resulting from this correction list9
Please indicate
• Yes Q No a
The jurisdiction has contracted with Esgil Corporation located at 9320
Chesapeake Drive Suite 208 San Diego California 92123 telephone number of
858/560 1468 to perform the plan review for your project If you have any
questions regarding these plan review items please contact Tamara Fischer at
Esgil Corporation Thank you
Carlsbad 072033
8/9/07
VALUATION AND PLAN CHECK FEE
JURISDICTION Carlsbad PLAN CHECK NO 072033
PREPARED BY Tamara Fischer DATE 8/9/07
BUILDING ADDRESS 1440 Buena Vista Way
BUILDING OCCUPANCY R3/Ul TYPE OF CONSTRUCTION VN
BUILDING
PORTION
sfd dwelling
workshop
Air Conditioning
Fire Sprinklers
TOTAL VALUE
Jurisdiction Code
AREA
(Sq Ft)
561
327
cb
Valuation
Multiplier
101 99
2661
By Ordinance
Reg
Mod
VALUE ($)
57216
8701
65,918
Bldg Permit Fee by Ordinance
Plan Check Fee by Ordinance
Type of Review
I I Repetitive Fee
Repeats
Complete Review
D Other
i—I Hourly
D Structural Only
Hour
Esgil Plan Review Fee
Comments
$406 661
$264 33
$227 73
Sheet 1 of 1
macvalue doc
City of Carlsbad
BUILDING PLANCHECK CHECKLIST
DATE /£/Q7
BUILDING ADRESS
PROJECT DESCRIPTION
ASSESSOR S PARCEL NUMBER
PLANCHECK NO CB Q
ENGINEERING DEPARTMENT
APPROVAL
The item you have submitted for review has been
approved The approval is based on plans
information and/or specifications provided in your
submittal therefore any changes to these items after
this date including field modifications must be
reviewed by this office to insure continued
conformance with applicable codes Please review
carefully all comments attached as failure to comply
with instructions in this report can result in
suspension of permit to build
D A Right of Way permit is required prior to
construction of the following improvements
EST VALUE
DENIAL
?/
Please see the attached report of deficiencies
marked with D Make necessary corrections to plans
or specifications for compliance with applicable
codes and standards Submit corrected plans and/or
specifications to this office for review
By
By
By
Date
Date
Date
By
FOR OFFICIAL USE ONLY
N. r^^ENGINEERING AUTHORIZATION TO ISSUE BUILDING PERMIT
^X Date
D Dedication Application
D Dedication Checklist
D Improvement Application
D Improvement Checklist
D Future Improvement Agreement
D Grading Permit Application
D Grading Submittal Checklist
D Right of Way Permit Application
[] Right of Way Permit Submittal Checklist
and Information Sheet
D Sewer Fee Information Sheet
Name
ENGINEERING DEPT CONTACT PERSON
JOANNE JUCHNIEWICZ
City of Carlsbad
Address 1635 Faraday Avenue Carlsbad CA 92008
Phone (760) 602 2775
CFD INFORMATION
Parcel Map No
Lots
Recordation
Carlsbad Tract
e Car|sbad CA 92OO817314 • (76O) 602 2720 • FAX (760) 6O2
D D
BUILDING PLANCHECK CHECKLIST
SITE PLAN
1 Provide a fully dimensioned site plan drawn to scale Show
A North Arrow
B Existing & Proposed Structures
C Existing Street Improvements
D Property Lines
E Easements
2 Show on site plan
F Right-of-Way Width & Adjacent Streets
G Driveway widths
H Existing or proposed sewer lateral
I Existing or proposed water service
J Existing or proposed irrigation service
A Drainage Patterns
1 Building pad surface drainage must maintain a minimum slope of one
percent towards an adjoining street or an approved drainage course
2 ADD THE FOLLOWING NOTE Finish grade will provide a minimum positive
drainage of 2% to swale 5 away from building
B Existing & Proposed Slopes and Topography
C Size type location alignment of existing or proposed sewer and water service (s)
that serves the project Each unit requires a separate service however second
dwelling units and apartment complexes are an exception
D Sewer and water laterals should not be located within proposed driveways per
standards
3 Include on title sheet
A Site address
Assessor s Parcel Number
C Legal Description
n
&& oV
For commercial/industrial buildings and tenant improvement presets include
total building square footage with the square footage for each differenx use
existing sewer permits showing square footage of different uses (manufacturing
warehouse office etc) previously approved
EXISTING PERMIT NUMBER DESCRIPTION
F WILDING PLANCHECK CKLST FORM d
R 7/14/00
BUILDING PLANCHECK CHECKLIST
,ND RD
D D
3
D
DISCRETIONARY APPROVAL COMPLIANCE
4a Project does not comply with the following Engineering Conditions of approval for
Project No
CD CD 4b All conditions are in compliance Date
DEDICATION REQUIREMENTS
5 Dedication for all street Rights of Way adjacent to the building site and any storm
dram or utility easements on the building site is required for all new buildings and
for remodels with a value at or exceeding $ 17,000 pursuant to Carlsbad
Municipal Code Section 18 40 030
Dedication required as follows T _
Dedication required Please have a registered Civil Engineer or Land Surveyor
prepare the appropriate legal description together with an 8 V* x 11 plat map and
submit with a title report All easement documents must be approved and signed
by owner(s) prior to issuance of Building Permit Attached please find an
application form and submittal checklist for the dedication process Submit the
completed application form with the required checklist items and fees to the
Engineering Department in person Applications will not be accept by mail or fax
Dedication completed by Date
IMPROVEMENT REQUIREMENTS
D D 6a All needed public improvements upon and adjacent to the building site must be
constructed at time of building construction whenever the value of the
construction exceeds $ 82,000 pursuant to Carlsbad Municipal Code Section
1840040
Public improvements required as follows
Attached please find an application form and submittal checklist for the public
improvement requirements A registered Civil Engineer must prepare the
appropriate improvement plans and submit them together with the requirements
on the attached checklist to the Engineering Department through a separate plan
check process The completed application form and the requirements on the
F \BUILDING PLANCHECK CKLST FORM d
BUILDING PLANCHECK CHECKLIST
. ST
checklist must be submitted in person Applications by mail or fax are not
accepted Improvement plans must be approved appropriate securities posted
and fees paid prior to issuance of building permit
Improvement Plans signed by Date
6b Construction of the public improvements may be deferred pursuant to Carlsbad
Municipal Code Section 18 40 Please submit a recent property title report or
current grant deed on the property and processing fee of $410 so we may
prepare the necessary Neighborhood Improvement Agreement This agreement
must be signed notarized and approved by the City prior to issuance of a
Building permit
D
Future public improvements required as follows
6c Enclosed please find your Neighborhood Improvement Agreement
agreement signed and notarized to the Engineering Department
Please return
Neighborhood Improvement
Agreement completed by
Date
EH CH EH 6d No Public Improvements required SPECIAL NOTE Damaged or defective
improvements found adiacent to building site must be repaired to the satisfaction
of the City Inspector prior to occupancy
nan
a
GRADING PERMIT REQUIREMENTS
The conditions that invoke the need for a grading permit are found in Section
15 16 010 of the Municipal Code
7a Inadequate information available on Site Plan to make a determination on grading
requirements Include accurate grading quantities in cubic yards (cut fill import
export and remedial) This information must be included on the plans
7b Grading Permit required A separate grading plan prepared by a registered Civil
Engineer must be submitted together with the completed application form
attached NOTE The Grading Permit must be issued and rough grading
approval obtained prior to issuance of a Building Permit
Grading Inspector sign off by Date
7c Graded Pad Certification required (Note Pad certification may be required even
if a grading permit is not required )
F \BUILDING PLANCHECK CKLST FORM doc
u
BUILDING PLANCHECK CHECKLIST
..ST 2ND 3RD
n D D 7d No Grading Permit required
n D D 7e If grading is not required write No Grading on plot plan
MISCELLANEOUS PERMITS
D D D 8 A RIGHT OF WAY PERMIT is required to do work in City Right-of Way and/or
private work adjacent to the public Right of Way Types of work include but are
not limited to street improvements tree trimming driveway construction tying
into public storm dram sewer and water utilities
Right-of Way permit required for
D D D 9 INDUSTRIAL WASTE PERMIT If your facility is located in the City of Carlsbad
sewer service area you need to contact the Carlsbad Municipal Water District
located at 5950 El Cammo Real Carlsbad CA 92008 District personnel can
provide forms and assistance and will check to see if your business enterprise is
on the EWA Exempt List You may telephone (760) 438 2722 extension 7153
for assistance
Industrial Waste permit accepted by
Date
D D D 10 NPDES PERMIT
Complies with the Citys requirements of the National Pollutant Discharge
Elimination System (NPDES) permit The applicant shall provide best
management practices to reduce surface pollutants to an acceptable level prior to
discharge to sensitive areas Plans for such improvements shall be approved by
the City Engineer prior to issuance of grading or building permit whichever
occurs first
L~H d L~H 11 D Required fees are attached
D No fees required
WATER METER REVIEW
D D D 12a Domestic (potable) Use
Ensure that the meter proposed by the owner/developer is not oversized
Oversized meters are inaccurate during low flow conditions If it is oversized for
the life of the meter the City will not accurately bill the owner for the water used
• All single family dwelling units received standard 1 service with 5/8 service
F \BUILDING PLANCHECK CKLST FORM d
D D D i2b
BUILDING PLANCHECK CHECKLIST
• If owner/developer proposes a size other than the standard then
owner/developer must provide potable water demand calculations,
which include total fixture counts and maximum water demand in gallons
per minute (gpm) A typical fixture count and water demand worksheet is
attached Once the gpm is provided check against the meter sizing
schedule to verify the anticipated meter size for the unit
• Maximum service and meter size is a 2 service with a 2 meter
• If a developer is proposing a meter greater than 2 suggest the
installation of multiple 2 services as needed to provide the anticipated
demand (manifolds are considered on case by case basis to limit
multiple trenching into the street)
Irrigation Use (where recycled water is not available)
All irrigation meters must be sized via irrigation calculations (in gpm) prior
to approval The developer must provide these calculations Please follow
these guidelines
1 If the project is a newer development (newer than 1998) check the recent
improvement plans and observe if the new irrigation service is reflected on
the improvement sheets If so at the water meter station the demand in
gpm may be listed there Irrigation services are listed with a circled I
and potable water is typically a circled W The irrigation service should
look like
STA1+00 Install 2 service and
1 5 meter (estimated 100 gpm)
If the improvement plans do not list the irrigation meter and the
service/meter will be installed via another instrument such as the building
plans or grading plans (w/ a right of way permit of course) then the
applicant must provide irrigation calculations for estimated worst case
irrigation demand (largest zone with the farthest reach) Typically Larry
Black has already reviewed this if landscape plans have been prepared
but the applicant must provide the calculations to you for your use Once
you have received a good example of irrigation calculations keep a set for
your reference In general the calculations will include
• Hydraulic grade line
• Elevation at point of connection (POC)
• Pressure at POC in pounds per square inch (PSI)
• Worse case zone (largest farthest away from valve
• Total Sprinkler heads listed (with gpm use per head)
• Include a 10% residual pressure at point of connection
In general all major sloped areas of a subdivision/project are to be
irrigated via separate irrigation meters (unless the project is only SFD with
no HOA) As long as the project is located within the City recycled water
F BUILDING PLANCHECK CKLST FORM d
-ST 2ND 3RD
BUILDING PLANCHECK CHECKLIST
service boundary the City intends on switching these irrigation
services/meters to a new recycled water line in the future
D D D 12c Irrigation Use (where recycled water is available)
1 Recycled water meters are sized the same as the irrigation meter above
2 If a project fronts a street with recycled water then they should be
connecting to this line to irrigate slopes within the development For
subdivisions this should have been identified and implemented on the
improvement plans Installing recycled water meters is a benefit for the
applicant since they are exempt from paying the San Diego County Water
Capacity fees However if they front a street which the recycled water is
there but is not live (sometimes they are charged with potable water until
recycled water is available) then the applicant must pay the San Diego
Water Capacity Charge If within three years the recycled water line is
charged with recycled water by CMWD then the applicant can apply for a
refund to the San Diego County Water Authority (SDCWA) for a refund
However let the applicant know that we cannot guarantee the refund and
they must deal with the SDCWA for this
El EH d 13 Additional Comments
F \BUILDING PLANCHECK CKLST FORM d
ENGINEERING DEPARTMENT
FEE CALCULATION WORKSHEET
itimate based on unconfirmed information from applicant
Calculation based on building plancheck plan submittals^Ca
Address IWO WJ^^*- IA
^
Permit No 072035
Prepared by.Date Checked by Date
EDU CALCULATIONS List types and square footages for all uses
Types of Use ^^)V3 Sq Ft /Units
Types of Use Sq Ft/Units
APT CALCULATIONS List types and square footages for all uses
Types of Use C\)\J Sq Ft/Units
Types of Use Sq Ft /Units
EDUs
EDUs
ADTs .
ADTs
FEES REQUIRED
WITHIN CFD D YES (no bridge & thoroughfare fee in District #1 reduced Traffic Impact Fee)B^JO
PARK IN LIEU FEE
FEE/UNIT
PARK AREA & #
X NO UNITS/
2 TRAFFIC IMPACT FEE
ADTs/UNITS /
B BRIDGE AND THOROUGHFARE FEE
ADTs/UNITS
^j4 FACILITIES MANAGEMENT FEE
^ UNIT/SO FTs
5 SEWER FEE
EDUs /
j^fklEFITAREA
EDUs
X FEE/ADT ^ 7^
(DIST #1 DIST #2
X FEE/ADT
ZONE /
X FEE/SO FT /UNIT
X FEE/EDU (Ol '
X FEE/EDU
=$_
=$ h ¥2
DIST #3
=$_
=$_
=$
6 SEWER LATERAL ($2 500)
7 DRAINAGE FEES PLDA _
ACRES _ X
8 POTABLE WATER FEES
UNITS CODE CONNECTION FEE
=$-
=$_
HIGH
FEE/AC
/LOW
=$
METER FEE SDCWA FEE SDCWA FEE
F \FEECALCULATION WORKSHEET doc
1 of 2
Rev 7/14/00
r-
-* m J£o o o» » O
ooo
DD
D D
PLANNING DEPARTMENT
BUILDING PLAN CHECK REVIEW CHECKLIST
Plan Check No CB 0 I 'Ufflf)
Planner Gma Ruiz
Address \.°^CO ^U^NA N
Phone (760) 602 4675
mA WAV
APN \fy> \10 ^l 00
Type of Project & Use *& - £ **• t?U *fa
Zoning fc-1 General Plan KLVt
CFD (m/out) # Date of participation
£££?> Net Proiect Densitv
Facilities Management Zone 1
Remainma net dev acres
DU/AC
Circle One
(For non residential development Type of land used created by this
permit )
Legend £3 Item Complete D Item Incomplete Needs your action
Environmental Review Required YES NO X^ TYPE
DATE OF COMPLETION
Compliance with conditions of approval7 'If not state conditions which require action
Conditions of Approval
Discretionary Action Required
APPROVAL/PESO NO
PROJECT NO
YES
DATE
NO X TYPE
OTHER RELATED CASES
Compliance with conditions or approval7 If not state conditions which require action
Conditions of Approval
n
Coastal Zone Assessment/Compliance
Project site located in Coastal Zone7 YES
CA Coastal Commission Authority7 YES NO X
If California Coastal Commission Authority Contact them at - 7575 Metropolitan Drive Suite 103
San Diego CA 921084402 (619)7672370
Determine status (Coastal Permit Required or Exempt) _
NO-
Habitat Management Plan
Data Entry Completed7 YES
If property has Habitat Type identified-^ Table 11xofjHMP" complete HMP Permit application and
assess fees in Permits Plus
(A/P/Ds Activity Maintenance enter CB# toolbar Screens HMP Fees Enter Acres of Habitat Type
impacted/taken UPDATE') fi >
NO 'Inclusionary Housing Fee required YES
(Effective date of Inclusionary Housing Ordinance May 21 1993)
Data Entry Completed7 YEsX NO
(A/P/Ds Activity Maintenance enter CB# toolbar Screens Housing Fees Construct Housing Y/N
Enter Fee UPDATE')
H \ADMIN\COUNTER\BldgPlnchkRevChklst Rev 3/06
D
Site Plan
Provide a fully dimensional site plan drawn to scale Show North arrow property lines easements
existing and proposed structures streets existing street improvements right of way width
dimensional setbacks and existing topographical lines (including all side and rear yard slopes)
Provide legal description of property and assessor s parcel number
Policy 44 - Neighborhood Architectural Design Guidelines
D D 1 Applicability YES NO
D D 2 Project complies YES. NO_
DD
D D
S D D
H D D
Zoning
1 Setbacks
Front
Interior Side
Street Side
Rear
Top of slope
2 Accessory structure setbacks
Front
Interior Side
Street Side
Rear
Structure separation
3 Lot Coverage
Required
Required
Required
Required
Required
:ks
Required
Required
Required
Required
Required
Required
'(>V
&)*
hJ/A
ID'
KJ/A-
M*c??<
MA
}<?'
10'
<4o/
Shown t"
Shown ~T ' 3\ &> '
Shown
Shown 10'
Shown
Shown
Shown ^'^"T
Shown
Shown [Of
Shown U'f?'
Shown fyO \ot I
4 Height Required
Spaces Required
Shown
Shown5 Parking
(breakdown by uses for commercial and industrial projects required)
Residential Guest Spaces Required I Shown l_
Additional Comments AfPlPAN/lT 1*7
&& A CITV
^i $1' AIL
OK TO ISSUE AND ENTERED APPROVAL INTO COMPUTERL-^lUft Q>J^L DATE
H \ADMIN\COUNTER\BldgPlnchkRevChklst Rev 3/06
CITY OF CARLSBAD - AFFIDAVIT OF COMPLIANCE
FOR A SECOND DWELLING UNIT
Instructions to Property Owner (Affiant')
Please type or print complete and accurate answers in all blank spaces in Section I Please read
carefully, particularly Section II Please read, sign and date Section III indicating that you
understand and agree with the conditions of compliance
SECTION I - INFORMATION
Property owner(s)+
Name(s)
Property Address
Street Address
City
Assessor Parcel No
Subdivision
Project Number
Name
State
/
Lot/Block
07
Zip Code
Parcel No
SECTION II - CONDITIONS FOR COMPLIANCE
PLEASE READ CAREFULLY
1 A second dwelling unit is an attached or detached dwelling unit which is located on the same lot as
an existing owner occupied single family detached dwelling unit and is
a Suitable for use as a complete living facility with provisions within the facility for
cooking eating sanitation and sleeping
b Occupied by one or more persons and
c Subordinate to the mam dwelling unit
2 The Property Owner(s) listed above hereby certifies that he/she owns the above referenced
property as of the date of this affidavit and to his/her belief and knowledge there are no
conditions covenants or restrictions on the property prohibiting a second dwelling unit apartment
3 The Property Owner(s) agrees to the following terms and conditions
FRM0006 6/03 PAGE 1 OF 2
a The property and residence referenced above must not contain a second residential
dwelling unit unless it is in compliance with the second dwelling unit provisions of the
Zoning Ordinance of the City of Carlsbad
b The Property Owner(s) shall reside in either the mam dwelling unit or second dwelling
unit described above now and for the life of this agreement unless a lessee leases both
the mam dwelling unit and the second dwelling unit
c The Second Dwelling Unit may only be rented and shall not be sold separately from the
main dwelling unit unless the lot on which such units are located is subdivided
d The Property Owner(s) agree to rent the Second Dwelling Unit at a monthly rental rate
which shall not exceed an amount equal to 30% of the gross monthly income of a low
income household adjusted for household size at 80% of the San Diego County median
income
e A copy of this agreement and Affidavit must be given by the Property Owner(s) to
prospective purchasers of the property prior to entering into a sales contract for said
property
SECTION III - AFFIRMATION AND AGREEMENT
I HEREBY DECLARE AND AFFIRM under penalty of perjury that all matters and facts set forth in this
agreement are true and correct to the best of my knowledge information and belief and that I (we)
understand accept and will abide by the regulations requirements and standards governing the Second
Dwelling Unit
BY
-Property Owner Date
^roperty Owner Date
Owner s Telephone Number(s) £_
Home Office
FRM0006 6/03 PAGE 2 OF 2
CERTIFICATE OF COMPLIANCE RESIDENTIAL (Page l of 5) CF-1R
Project Title , /
rail A-6e£/ hu;?/l 4* Av/tfCsli
Project Address . /,
Date / /
1A ~l 1 2S*>lt>~l
o ' , c i1
IS uf?«*-<< I/ S rx_
/ A.h( <; 60^ ^ ^ #200 *?
Documentation Author
[j®!^ fH.0^f|£
Compliance-Method (Prescriptive)
Telephone
( "7(^0 ) Ip^ " ?3^7-
Climate Zone
Building Permit #
Plan Check / Date
Field Check /Date
Enforcement Agency Use Only
Alternative Component Package Method (check one)_D (Alternative)
Package C and Package D choices require HERS rater field verification and/or diagnostic testing (see CF 1R page 3)
For Package D Alternative see Appendix B Table 151 C Footnotes 8 14 in the Residential Compliance Manual (RCM)
ft2
GENERAL INFORMATION
Total Conditioned Floor Area (CFA) <-H
Average Ceiling Height ffi ft
Check Applicable Boxes
Building Type (check one or more) ^Single Family Multifamily Addition Alteration
(If adding fenestration fill-out WS-4R, Fenestration Maximum Allowed Area Worksheet and see Section 832
for Additions and 8 3 3 for Alterations in the RCM )
ft2 (from WS-4R)
" ft2 (from WS-4R)
Maximum Allowed Total Fenestration Area
Maximum Allowed West Facing Fenestration Area
Number of Stones \ Number jjf Dwelling Units (
Floor Construction Type (SlaEftlaised Floor j[circle one or both)
Front Orientation Norm/South / East /(Wesy All Orientations (input front orientation in degrees
from True North and circle one)
D RADIANT BARRIER (check box if required in climate zones 2.4.8 15)
OPAQUE SURFACES INCLUDING OPAQUE DOORS
Component
Type (Wall
Roof Floor
Slab Edge
Doors)
t^nUl
fWf
<*kVi
Frame
Type
(Wood or
Metal)
Ljff»fJ(
LV/ftodP
Cavity
Insulation
R Value
t ~»3.^•Ttf
Continuous
Insulation
R Value
GL-I-?
jt^-50
Assembly U
factor (for wood
metal frame and
mass
assemblies) '
{qo
40
Joint
Appendix
IV
Reference
tf f*Oa} fir*
Roof Radiant
Barrier
Installed2
Yes or No
Location
Comments
(attic garage
typical etc )
1) See Joint Appendix IV in Section IV 2 IV 3 and IV 4 which is the basis for the U factor criterion U factors can not exceed
prescriptive value to show equivalence to R values
2) This column is for the Inspector to verify installation of roof radiant barrier
Residential Compliance Forms December 2005