Description: ZAMALLOA: 390 SF ADDITION FOR FAMILY ROOM// 350 SF REMODEL KITCHEN
Owner: Contractor:
COOWNER ZAMALLOA JOEL ANO LIPSIE
SARAH
SUFFRIDGE DESIGN AND BUILD INC
BUILDING PERMIT FEE ($2000+)
BUILDING PLAN CHECK FEE (BLDG)
1511 Basswood Ave
CARLSBAD, CA 92008
ELECTRICAL BLDG RESIDENTIAL NEW/ADDITION/REMODEL
GREEN BUILDING STANDARDS PLAN CHECK & INSPECTION
MECHANICAL BLDG RESIDENTIAL NEW/ADDITION/REMODEL
PLUMBING BLDG RESIDENTIAL NEW/ADDITION/REMODEL
SB1473 GREEN BUILDING STATE STANDARDS FEE
STRONG MOTION-RESIDENTIAL
Total Fees: $1,298.43 Total Payments To Date: $1,298.43
6912 Halifax St
San Diego, CA 92120-1020
619-203-3216
Balance Due:
Please take NOTlCE that approval of your project includes the "Imposition" of fees, dedications, reservations, or other exactions hereafter
collectively referred to as "fees/exaction." You have 90 days from the date this permit was issued to protest imposition of these
fees/exactions. If you protest them, you must follow the protest procedures set forth in Government Code Section 66020(a), and file the
protest and any other required information with the City Manager for processing in accordance with Carlsbad Municipal Code Section
3.32.030. Failure to timely follow that procedure will bar any subsequent lega\ action to attack, review, set aside, void, or annul their
imposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection
fees and capacity changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this
project. NOR DOES IT APPLY to any fees/exactions of which you have previously been given a NOTICE similar to this, or as to which the
statute of limitation has previously otherwise expired.
$0.00
1635 Faraday Avenue, Carlsbad, CA 92008-7314 I 760-602-2700 I 760-602-8560 f I www.carlsbadca.gov
$552.19
$386.53
$43.00
$170.00
$52.00
$80.00
$4.00
$10.71
• THE FOLLOWING APPROVALS REQUIRED PRIOR TO PERMIT ISSUANCE: 0PLANNlNG 0ENGINEERING
(city of
Carlsbad
JOB ADDRESS
\$1
CT/PROJECT# LOT# PHASE
Building Permit Application
1635 Faraday Ave., Carlsbad, CA 92008
Ph: 760-602-2719 Fax: 760-602-8558
email: building@carlsbadca.gov
www.carlsbadca.gov
SUITEf/SPACEf/UN1Tf
NITS # BEDROOMS # BATHROOMS
DESCRIPTION OF WORK: Include Square Feet of Affected Area(s)
0BUILD1NG 0FIRE 0HEALTH
COI/-JS"TRDC.T A~?RO'-t.. -.:390 S:r
1<'.E-1(\'\0DE. <... ~ \ ~ \-\t;::G (l{:' 0 RO)<
~COM (-\Q:) ) n 61\-.J
?::.s'"O Sf-
EXISTING USE DECKS (SF)
ADDRESS
5'\ \
CITY
VlQ..LS
PHONE
EMAIL
0HAZMATIAPCD
ADDRESS
~~~'"-=S-~9'---'----,-'--'.t?,~(~·J~J_•=dn~~___,_,__..=-~-""_,,____-+=~=---__,____.__~.L-'.=~~~=,,,'-=='=""-=-----'--=-"=-~-w-
CITY Jo. I\ /) I e SGA-ZIP
PHONE
EMAIL
STATE UC.#
'1.i't.fJ'i'
(Sec_. 7031.5 Business and Professions Code: Any City or County which requires a permit to construct, alter, Improve, demolish or repair any structure, prior to its issuance, also requires the applicant for such per_mit to file a signed statement that he 1s licensed pursuant to the provisions of the Contractor's License Law !Chapter 9, commending with Section 70_00 of Division 3 of the Business and Professions Code} or that he 1s exemP.t therefrom, and the basis for the alleged exemption. Any violation of Section 7031.5 by any applicant for a permit subJects the applicant to a civil penalty of not more than five hundred dollars {$500}).
WORKERS' COMPENSATION
Workers' Compensation Declaration: I hereby affirm under penalty of perjury one of the following declarations:
Q 1 have and will maintain a certificate of consent to self-Insure for workers' compensation as provided by Section 3700 of the Labor Code, for the performance Of the work for which this permit is issued. M1 have and will maintain workers' compensation, as requirei Section 3700 of th!!::abor Code, for the performan~of the work for which this permit is issued. My workers' compensation insurance carrier and policy
oomb""" '"'""""' r:,,Jil'J.k..M_/YJf-~"' 6'> ,MJ, f-11,.,) _ Pol,cy No. 0 :[3 'i / J t 7 B<piration Date '1-:,._'1-It
~section need not be completed if the permit is for one hundred dollars ($100) or less LJ Certificate of Exemption: I certify that in the performance of the work for which this permit is issued, I shall not employ any person 1n any manner so as to become subJect to the Workers' Compensation Laws of
California. WARNING: Failure to secure workers' compe satlon coverage Is unlawful, and shall subject an employer to criminal penalties and civil fines up to one hundred thousand dollars (&100,000), in
addition to the cost of compensation, damages as provl f ctlon 3706 of the Labor code, interest and attorney's fees.
kS CONTRACTOR SIGNATURE 'fle-1, ectA Ju Alr,--J.sc-~GENT
I hereby affirm that I am exempt from Contractor's License Law for the following reason:
D
0
D
I, as owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not intended or offered for sale (Sec. 7044, Business and Professions Code: The Contractor's
License Law does not apply to an owner of property who builds or improves thereon, and who does such work himself or through his own empioyees, provided that such improvements are not intended or offered for
sale. If, however, the building or improvement is sold within one year of completion, the owner-builder will have the burden of proving that he did not bu11d or improve for the purpose of sale).
I, as owner of the property, am exclusively contracting with licensed contractors to construct the project {Sec. 7044, Business and Professions Code; The Contractor's License Law does not apply to an owner of
property who builds or improves thereon, and contracts for such projects with contractor(s) licensed pursuant to the Contractor's License Law).
I am exempt under Section ____ Business and Professions Code for this reason:
1. I personally plan to provide the major labor and materials for construction of the proposed property improvement. 0Yes 0No
2. I (have I have not) signed an application for a building permit for the proposed work
3. I have contracted with the following person (firm) to provide the proposed construction (include name address I phone I contractors' license number):
4. I plan to provide portions of the work, but I have hired the following person to coordinate, supeivise and provide the major work (include name I address I phone I contractors' license number):
5. I will provide some of the work, but I have contracted (hired) the fol\owirg persons to provide the work indicated (include name I address I phone I type of work):
k$ PROPERTY OWNER SIGNATURE QAGENT DATE
COMPLETE THIS SECTION FOR NON-RESIDENTIAL BUILDING PERMITS ONLY
Is the applicant or future building occupant required to submit a business pla~y hazardous materials registration form or risk mana]ement and prevention program under Sections 25505, 25533 or 25534 of the
Presley-Tanner Hazardous SLJbstance Account Ac(! Yes ~ _
Is the appl_icant or fllture building occupant required to obtain a permit from the air pollution control district or air quality management district? Yes ei,/
Is the facility to be constructed within 1,000 feet of the outer boundary of a school site? Yes c;;V
IF ANY OF THE ANSWERS ARE YES, A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR IS MEETING THE REQUIREMENTS OF THE OFFICE OF
EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT.
I certify that I have read the application and state that the above information Is correct and that the Information on the plans is accurate. I agree to rompl>j with all City ordinances and State laws relating to building construction.
\ hereby authorize representative of the City of Carlsbad to enter upon the above mennoned property for inspection purposes. I ALSO AGREE TO SAVE, INDEMNIFY AND KEEP HARMLESS THE CITY OF Ci\RLSB.A..D
AGAINST ALL LIABILITIES, JUDGMENTS, COSTS AND EXPENSES WHICH . ANY WAY ACCRUE AGAINST SAID CITY IN CONSEQUENCE OF THE GRANTING OF THIS PERMIT
OSHA: An OSHA pennlt is required for excavations over 5'0' deep and de construction of structures over 3 stories in height
EXPIRATION: Every pennlt issued by the Building Offdal under the pro · · of this Code shall expire by limitation and berome null and voi::l W the bui'ding or v.ork authorized by such i:ennit is not mmmenced 'Mthin
180 days from the date of sudl i:ermit or iflhe building or di pennit is susi:;ended or abandoned at any tine after the mo< is mmmenced fo/a period of 100 days (Sec!On 100.4.4 Unifonn Building Code).
,@S' APPLICANT'S SIGNATURE DATE 10 ,a"' / ,.7 T I
STOP: THIS SECTION NOT REQUIRED FOR BUILDING PERMIT ISSUANCE.
Complete the following ONLY if a Certificate of Occupancy will be requested at final inspection.
Fax (760) 602-8560, Email bui1ding@carl5badca.gov or Mail the completed form to City of Carlsbad, Building Division 1635 Faraday Avenue, Carlsbad, California 92008.
CO#: (Office Use Only)
CONTACT NAME OCCUPANT NAME
ADDRESS BUILDING ADDRESS
CITY STATE ZIP CITY STATE
Carlsbad CA
PHONE FAX
EMAIL OCCUPANT'S BUS. UC. No.
OELIYERY OPTIONS
PICK UP: CONTACT (Listed above) OCCUPANT (Listed above)
CONTRACTOR (On pg_ 1)
MAIL TO: CONTACT (Listed above)
CONTRACTOR (On Pg. 1)
OCCUPANT (listed above)
MAIL/ FAX TO OTHER:-----------------
A5 APPLICANT'S SIGNATURE
ASSOCIATED CB#'-------------
NO CHANGE IN USE/ NO CONSTRUCTION
CHANGE OF USE/ NO CONSTRUCTION
DATE
ZIP
PERMIT INSPECTION HISTORY REPORT (CBR2017-2581)
Permit Type: BLDG-Residential Application Date: 1012612017 Owner: COOWNER ZAMALLOA JOEL AND
LIPSIE SARAH
Work Class: Addition Issue Date: 12/05/2017 Subdivision: SANDALWOOD DALE UNIT# 2
Status: Closed -Finaled Expiration Date: 01107/2019 Address: 1511 Basswood Ave
Carlsbad, CA 92008-1946
IVR Number: 7258
Scheduled Actual
Date Start Date Inspection Type Inspection No. Inspection Status Primary Inspector Reinspection Complete
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Yes
BLDG-41 055322·2018 Passed Tim Frazee Complete
Underground Ducts
(Mech)
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Yes
BLDG-84 Rough 065462·2018 Passed Tim Frazee Complete
Combo{14,24,34,44)
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Yes
BLDG-14 Yes
Frame-Steel-Bolting-Welding
(Decks)
BLDG-24 Rough-Topout Yes
BLDG-34 Rough Electrical Yes
BLDG-44 Yes
Rough-Ducts-Dampers
06/03/2018 06102/2018 BLDG-17 Interior 066897·2018 Passed Tim Frazee Complete
Lath/Drywall
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Yes
07/09/2018 07/19/2018 BLDG-Final 063401-2018 Passed Tim Frazee Complete
Inspection
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Waiting for the recycling and trash receipts Yes
Received the paperwork Friday 7/19/2018
BLDG-Plumbing Final Yes
BLDG-Mechanical Final Yes
BLDG-Structural Final Yes
BLDG-Electrical Final Yes
July 23, 2018 Page 2 of2
PERMIT INSPECTION HISTORY REPORT (CBR2017-2581)
Permit Type: BLDG-Residential Application Date: 10/26/2017 Owner: COOWNER ZAMALLOA JOEL AND
LIPSIE SARAH
Work Class: Addition Issue Date: 1210512017 Subdivision: SANDALWOOD DALE UNIT#2
Status: Closed -Finaled Expiration Date: 01/07/2019 Address: 1511 Basswood Ave
Cartsbad, CA 92008-1946
IVR Number: 7258
Scheduled Actual
Date Start Date Inspection Type Inspection No. Inspection Status Primary Inspector Re inspection Complete
01/29/2018 01/2912018 BLDG-11 047118-2018 Passed Tim Frazee Complete
Foundation/Ftg/Pier
s (Rebar)
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Yes
02/05/2018 02(05/2018 BLDG-SW-Pre-Con 047815-2018 Passed Tim Frazee Complete
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Yes
02108/2018 02/08/2018 BLDG-13 Shear 048302-2018 Passed Tim Frazee Complete
Panels/HD (ok to
wrap)
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Yes
BLDG-15 048301-2018 Passed Tim Frazee Complete
Roof/ReRoof (Patio)
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Yes
03/08/2018 03/08/2018 BLDG-21 051147-2018 Passed Tim Frazee Complete
Underground/Underf
loor Plumbing
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Yes
BLDG-31 051148-2018 Passed Tim Frazee Complete
Underground/Condu
It-Wiring
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Yes
04/12/2018 04/12/2018 BLDG-16 Insulation 054731-2018 Passed Tim Frazee Complete
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Yes
04/18/2018 04/1812018 BLDG-14 065461-2018 Passed Tim Frazee Complete
Frame/SteelfBoltlng/
Welding (Decks)
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Yes
BLDG-31 055324-2018 Passed Tim Frazee Complete
Underground/Condu
It-Wiring
July 23, 2018 Page 1 of 2
RJS Inspection & Material Testing
P.O. Box 2450, Alpine, CA 91903
Ph. 619-540-0612
FAX 619-445-5889
SPECIAL INSPECTION REPORT
Project: Zamalloa addition
Address: 1511 Basswood ave
City: Carlsbad, CA
Permit Number: CBR2017-2581
TYPE OF OBSERVATIONS:
Reinforcing Steel __ Reinforced Concrete __ Structural Masonry __ Field Welding __
Epoxy__!_ Prestressed Concrete __ Shop Welding __ Boltin_g __ Wedge Anchors __
Number of Samples Type:-----------------------
Materials/DesignMix/Psi., Simpson Set XP ICC ER-2508 (exp. 08/19)
Date: 2-6-I 8
REPORT
Epoxy procedure: Verified that holes are clean, dry, right size & depth. Observed the installation of(2) 5/8"
HDU4 threaded rod anchors into 3/4" holes, embedded a minimum of 12.5" and (3) 5/8" threaded rod AB
into 3/4" holes, embedded a minimum of 5", all into existing concrete with Simpson Set XP. Installation is
per Holdown Schdule on SI and Shear Wall Schedule note #4 on SI of approved plans.
Sub Contractor: Frevert Builders
WORK INSPECTED CONFORMS WITH APPROVED PLANS AND SPECIFICATIONS UNLESS OTHERWISE NOTED
815
Authorized Job Site Contact Signature
Inspection & Material Testing
COVERING WORK PERFORMED REQUIRING
APPROVAL BY THE SPECIAL INSPECTOR OF:
P.O. Box 2450
Alpine, CA 91903
Phone 619-540-0612
Fax 619-445-5889 ---
DAY 72.\
D Reinforced Concrete
DATE
Struct. Steel Assembly
(One inspection per Report) D Pre-Stressed Concrete D Fireproofing
TIME ON
SITE
1 o: u
TIME OFF
SITE HOURS
Project~ {L '7--IJ l
ev1s1on
O.T.
HOURS
#OFTEST
SPECIMENS
Sig ature of Registered Inspector /172-
Date of Report Registered Number
CERTIFICATE OF COMPLIANCE
TO THE BEST OF MY KNOVVLEDGE, THE ABOVE REPORTED WORK, UNLESS
OTHERWISE NOTED, IS IN CONFORMANCE WITH THE APPROVED PLANS AND
SPECIFICATIONS AND THE APPLICABLE WORKMANSHIP PROVISIONS OF THE
GOVERNING STANDARDS.
RECEIVED
APR O 2 2018
r-~~~~~~~~~~~~~~~~~~~~~,...,..,"""""~~~LSBAD
'W CIT¥ O J
CARLSBAD
SPECIAL INSPECTION
AGREEMENT
B-45
BUILDING D
Develo1, ,nf!nt suvice
Building Division
1635 Faraday Avenue
760-602-2719
www.carlsbadca.gov
In accordance with Chapter 17 of the California Bulldlng Code the following must be completed when work being performed
requires special Inspection, structural observation and construction matenal testing.
)roject/Permit: GB R 2.0 n-"Z,.!;i I Project Address: \ ' ( l ~AS$w't.O _.!) A vt
A. THIS SECTION MUST BE COMPLETED BY THE PROPERTY OWNER/AUTHORIZED AGENT. Please check rt you are °"1ner-Builder
..l (If you checked as owner-builder yo1. must also comple~ Sectio, B of th,s agreement.)
Name !Please prtnn ~.., f +r, c\'T,e
Mailing Address.~ 1,, ~ I Z. ·_ ~A\ '~ p...\c 5 r 'I S An ~ 1 ~o C ~ '1 2..1 l.,O
L
Erria11 \(c.i"~v'tf(1d~~ {;;t/1,,11, (Oh l Phone
I am .JProperty Owner )'Property Owrer s Agen: of Record
State of Cahforria Registration I\L.mber l\ S \ 0 ~ f;
.JArch1tect of Record
Expiration Date
...!Engineer or Record
z-:?1-,1
AGREEMENT I the undersigned declare unde• penalty of perJ.iry under the laws of the State of Ca:1forn1a that I have react
understand acknowledge and promise to comply wrth the City of Carlsbad requ rements for special inspections structural
observations construction 'Tlatenals test,ng and off-sl1e fabnca1t0n of bu1ld11"1g components as prescribed 1ri the statement of
special insPl\c,ns ~ed o')the apprrved plans and as required by the California Bui1d1ng Code
S1gnature._ _ _\.-~lt . Ci4\/ _ Date ~f-z.c /J lf
B. CONTRACTOR'S STATEMENT OF RESPONSIBILITY (07 CBC Ch 17 Section 1706). This sect!Of1 must be completed by the
contractor I builder I owner-builder d 1;,, '1
C I'/ r,011
Contractors Company Name -....JV t "t (" \ ,\ 'a: e b, es,~ P.\. Please checiri!you are °"flef-BJ l(W ,
Name.1P1mep11n11 }~ti L J Svj \d~-'
Mailing Address l 4 I 2. t-114-{' r A-)< <; ' S,o.,,...., ~ ' e ~ c.. (.":\ q 2. I ""L 0
Email \~ .. .(!-,9; 0.'r{ (9, A1 A ( J ( ~ M Phone ~I~ Z t.?_s · ,~ \ L.,
State of Cahforr.1a Contractors License Number· <'.j 8 l f Y ~ fxpration Date ~ -l t • \ t.
I acknow edge and am aware of special requiremerts contained ,n the statement or special nspectJons noted on
the app<olied plans
I acknow edge that control will be exercised to otxa,n conforrr.ance with the construcoor. dOcurrents approved by the
bu1ldlng off:c1al
I will have in-place procedures for exercising control wrth1r our (the contractors) organization, for the metnoo and
frequency or reporting and the d1su1bl..t1on of the reports and
' certi'"y that wi11 have a qual,f1ed person w1th1n our (the contractors) organization to exercise such contro:
• / will P[OVide s final report I letter In compliance with CBC Section 1704.1.2 prior to requesting final
S1gnatur~nspec\°z £: 4, rf '(,t. Date 3-20 -\ <"/
S-45 Page· ot 1 Rev 08/11
ISION
DATE: 11/29/2017
JURISDICTION: Carlsbad
PLAN CHECK#.: CBR2017-2581
/. EsG1I
A SAF'Ebu1lt Company
SET: II
PROJECT ADDRESS: 1511 Basswood Ave.
PROJECT NAME: Zamalloa Remodel and Addition
~PP LI CANT ,,,,;,a JURIS.
D The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
~ The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building
department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
D The check list transmitted herewith is for your information. The plans are being held at EsGil
until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
D The applicant's copy of the check list has been sent to:
~ EsGil staff did not advise the applicant that the plan check has been completed.
D EsGil staff did advise the applicant that the plan check has been completed.
Person contac~O Telephone#:
Date contacted: '~ 0 ) Email:
Mail Telephone Fax In Person
REMARKS: Please provide city soils stamp for applicant to sign prior to fin,1 approval at the
jurisdiction. \( r r.t5 '\ 1
By: Ryan Murphy Enclosures: (J-/.-l"
EsGil 7
11/20/2017
9320 Chesapeake Drive, Suite 208 + San Diego, California 92123 + (858) 560-1468 + Fax (858) 560-1576
DATE: 11/08/2017
JURISDICTION: Carlsbad
PLAN CHECK#.: CBR2017-2581
~ Es Gil
.f\ SAFl:built Co1np;ihy
SET: I
PROJECT ADDRESS: 1511 Basswood Ave.
PROJECT NAME: Zamalloa Remodel and Addition
D APPLICANT
.)YJUR/S.
D The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
0 The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
0 The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
~ The check list transmitted herewith is for your information. The plans are being held at EsGil
until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
~ The applicant's copy of the check list has been sent to:
Larry Hawes
0 EsGil staff did not advise the applicant that the plan check has been completed.
~ EsGil staff did advise the applicant that the plan check has been completed.
Person contacted: Larry Hawes Telephone#: (760)940-8910
~ate/,contacted:\ I\ B (by(\C--} Email: Larry@haweshomedesign.com
t)t1ail Telephone Fax In Person
D REMARKS:
By: Ryan Murphy
EsGil
Enclosures:
10/30/2017
9320 Chesapeake Drive, Suite 208 + San Diego, California 92123 + (858) 560-1468 + Fax (858) 560-1576
Carlsbad CBR2017-2581
11/08/2017
PLAN REVIEW CORRECTION LIST
SINGLE FAMILY DWELLINGS AND DUPLEXES
PLAN CHECK#.: CBR2017-2581 JURISDICTION: Carlsbad
PROJECT ADDRESS: 1511 Basswood Ave.
FLOOR AREA: Addition: 490 sq. ft.
Kitchen Remodel: 350 sq. ft.
REMARKS:
DATE PLANS RECEIVED BY
JURISDICTION: 10/26/2017
DATE INITIAL PLAN REVIEW
COMPLETED: 11/08/2017
FOREWORD (PLEASE READ):
STORIES: no change
HEIGHT: 13'9"
DATE PLANS RECEIVED BY
ESGIL CORPORATION: 10/30/2017
PLAN REVIEWER: Ryan Murphy
This plan review is limited to the technical requirements contained in the California version of
the International Residential Code, International Building Code, Uniform Plumbing Code,
Uniform Mechanical Code, National Electrical Code and state laws regulating energy
conservation, noise attenuation and access for the disabled. This plan review is based on
regulations enforced by the Building Department. You may have other corrections based on
laws and ordinance by the Planning Department, Engineering Department, Fire Department or
other departments. Clearance from those departments may be required prior to the issuance of
a building permit.
Present California law mandates that construction comply with the 2016 edition of the California
Code of Regulations (Title 24), which adopts the following model codes: 2015 IRC, 2015 IBC,
2015 UPC, 2015 UMC and 2014 NEC.
The above regulations apply, regardless of the code editions adopted by ordinance.
The following items listed need clarification, modification or change. All items must be satisfied
before the plans will be in conformance with the cited codes and regulations. Per Sec. 105.4 of
the 2015 International Building Code, the approval of the plans does not permit the violation of
any state, county or city law.
To speed up the recheck process, please note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet number, specification section, etc.
Be sure to enclose the marked up list when you submit the revised plans.
Carlsbad CBR2017-2581
11/08/2017
Please make all corrections, as requested in the correction list. Submit FOUR new
complete sets of plans for commercial/industrial projects (THREE sets of plans for
residential projects). For expeditious processing, corrected sets can be submitted in one
of two ways:
1. Deliver all corrected sets of plans and calculations/reports directly to the City of
Carlsbad Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760) 602-
2700. The City will route the plans to EsGil and the Carlsbad Planning, Engineering and
Fire Departments.
2. Bring TWO corrected set of plans and calculations/reports to EsGil, 9320 Chesapeake
Drive, Suite 208, San Diego, CA 92123, (858) 560-1468. Deliver all remaining sets of
plans and calculations/reports directly to the City of Carlsbad Building Department for
routing to their Planning, Engineering and Fire Departments.
NOTE: Plans that are submitted directly to EsGil only will not be reviewed by the City
Planning, Engineering and Fire Departments until review by EsGil is complete.
• PLANS
1. Will reconfirm that all sheets of plans are signed by the person responsible for
their preparation as well as structural sheets signed and sealed by EOR.
(California Business and Professions Code).
2. Provide a statement on the Title Sheet of the plans stating that this project shall
comply with the 2016 California Residential Code, which adopts the 2015 IRC,
2015 UMC, 2015 UPC and the 2014 NEC. Section R106.1.
3. The application indicated that you are remodeling the kitchen as well (350 sq.
ft.). The plans do not show any changes. Is this to be included in the scope of
work? If so, include in scope of work on sheet 1 and show extent of remodel on
plans.
4. On sheet 4, only number 2 from the key/legend is called out on the plans. Also,
per structural sheets and calculations, the wall being removed is a bearing wall.
Please revise to show bearing wall being demoed and call out the remainder of
the legend accordingly for clarification.
5. On sheet 4, legend no. 6 notes: "Construct (n) patio and patio roof." This was not
included in the scope of work and I do not see proposed patio included in the
framing or foundation plan. Please remove patio from architectural sheet 4, or
contact the city to add to scope of work and provide framing and foundation plan
for proposed patio. Additional fees may apply from the city.
6. The roof framing plan shown on sheet 6 does not match the roof framing plan
shown on sheet S2. Specifically, in area where proposed addition meets existing,
structural shows existing framing bearing on RB-1 (over demoed wall). Please
coordinate architectural sheets to match structural.
Carlsbad CBR2017-2581
11/08/2017
7. Sheet 2 and 4 are labeled "firsUsecond floor." Please relabel to reflect conditions
(1 floor). Also, relabel these sheets in sheet index on sheet 1.
8. Please show the required insulation in exterior walls (R-13) and ceilings (R-30)
on the plans at proposed addition.
9. Show location of attic access with a minimum size of 22"x30", unless the
maximum vertical headroom height in the attic is less than 30". Access must be
provided to each separated attic area (if over 30 sq. ft.), shall be located in a
hallway or other readily accessible location and 30" headroom clearance is
required above the opening. Section R807.1.
• FIRE PROTECTION
10. In existing buildings, when alterations, repairs or additions requiring a permit
occur (or when one or more sleeping rooms are added), the dwelling unit shall
be provided with smoke alarms located as required for new dwellings; the
smoke alarms shall be interconnected and hard wired. Exception: Smoke alarms
in existing areas need not be interconnected and hard wired where the
alterations or repairs do not result in the removal of interior wall or ceiling finishes
exposing the structure, unless there is an attic, crawl space, or basement
available which could provide access for hard wiring and interconnection without
the removal of interior finishes. Section R314.8.1.
11. When alterations, repairs or additions are proposed for dwelling units within
which fuel-burning appliances are installed (and in dwelling units having attached
garages), the dwelling unit shall be provided with carbon monoxide alarms
located as required for new dwellings; the carbon monoxide alarms shall be
interconnected and hard wired. Exception: Carbon monoxide alarms in existing
areas need not be interconnected and hard wired where the alterations or repairs
do not result in the removal of interior wall or ceiling finishes exposing the
structure, unless there is an attic, crawl space, or basement available which
could provide access for hard wiring and interconnection without the removal of
interior finishes. Section R315.2.
• STRUCTURAL
12. In the calculations provided, RH-1 was designed with a 1700 lb point load from
hip truss AH-1. Per AH-1 calculations, girder truss is bearing 2695 lb at each
end. Please revise calculations for roof headers RH-1 and 2 to reflect this.
13. Please provide evidence that the engineer-of-record (or architect) has reviewed
the truss calculation package prepared by others (i.e., a "review" stamp on the
truss calculations or a letter). CBC Section 107.3.4.1.
14. Based off your calculations for RB-1, it appears that there will be a 4.87 kip point
load at existing 12"x 12" continuous footing. Please provide design calculations
showing how existing continuous footing will support this load here.
Carlsbad CBR2017-2581
11/08/2017
15. In addition to the special inspection for expansion anchors already indicated in
the plans, the plans shall indicate that special inspection will be provided for the
following work. (CBC Chapter 17 and Section 107.2):
a. Structural wood. Periodic special inspection is required for nailing < 4" o.c.
Section 1705.11.1.
• MECHANICAL
12. Are you modifying the mechanical system in any way? If not, please remove note
10 on sheet 1. Also, show on the plans the location, type and size (Btu's) of all
heating and cooling appliances or systems.
• ELECTRICAL
13. Show on the plan the amperage of the electrical service, the location of the
service panel and the location of any sub-panels. If the service is over 200
amperes, submit a single line diagram, panel schedules, and provide service
load calculations.
14. Note on the plans that receptacle outlet locations will comply with CEC Article
210.52.
• MISCELLANEOUS
• Please provide city soils stamp for applicant to sign prior to final approval at the city.
To speed up the review process, note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet, note or detail number,
calculation page, etc.
Please indicate here if any changes have been made to the plans that are not a
result of corrections from this list. If there are other changes, please briefly
describe them and where they are located in the plans.
• Have changes been made to the plans not resulting from this correction list?
Please indicate:
Yes 0 No 0
The jurisdiction has contracted with EsGil, located at 9320 Chesapeake Drive,
Suite 208, San Diego, California 92123; telephone number of 858/560-1468, to
perform the plan review for your project. If you have any questions regarding
these plan review items, please contact Ryan Murphy at EsGil. Thank you.
Carlsbad CBR2017-2581
11/08/2017
[DO NOT PAY -THIS JS NOT AN INVOICE]
VALUATION AND PLAN CHECK FEE
JURISDICTION: Carlsbad PLAN CHECK#.: CBR2017-2581
PREPARED BY: Ryan Murphy DATE: 11/08/2017
BUILDING ADDRESS: 1511 Basswood Ave.
BUILDING OCCUPANCY: R-3/U
BUILDING AREA Valuation
PORTION ( Sq. Ft.) Multiplier
SFD addition 390
SFD remodel 350 city est.
Air Conditioning
Fire Sprinklers
TOTAL VALUE
Jurisdiction Code cb By Ordinance
Bldg. Permit Fee by Ordinan-c~-~ . ~]
Plan Check Fee by Ordinance
Type of Review: 0 Complete Review
0 Repetitive Fee --;.1 Repeats
--~
Comments:
D Other
D Hourly
EsGil Fee
Reg. VALUE
Mod.
D Structural Only
,__ __ __,,Hr.@*
Sheet 1 of 1
($)
82,384
82,384
$547.29!
$355.741
$311.961
Print Date: 07/24/2018
Job Address:
Permit Type:
Parcel No:
Valuation:
Occupancy Group:
# Dwelling Units:
Bedrooms:
Project Title:
1511 Basswood Ave
BLDG-Permit Revision
2051303900
$ 0.00
Revision Permit
Work Class: Residential Permit Revisi
Lot#:
Reference #:
Construction Type
Bathrooms:
Orig. Plan Check#: CBR2017-2581
Plan Check #:
(city of
Carlsbad
Permit No: PREV2018-0059
Status: Closed -Finaled
Applied: 03/08/2018
Issued: 04/03/2018
Permit 07/24/2018 Finaled:
Inspector: TFraz
Final
Inspection:
Description: ZAMALLOA: ADD 2 WINDOWS AND CHANGE HIP ROOF TO GABLE
Applicant:
SUFFRIDGE DESIGN AND BUILD INC
KEN SUFFRIDGE
6912 Halifax St
San Diego, CA 92120-1020
619-203-3216
FEE
BUILDING PLAN CHECK ADMIN FEE
MANUAL BUILDING PLAN CHECK FEE
Total Fees: $ 203.75
Building Division
Owner: Contractor:
COOWNER ZAMALLOAJOEL AND LIPSIE SARN SUFFRIDGE DESIGN AND BUILD INC
1511 Basswood Ave
CARLSBAD,CA 92008
Total Payments To Date : $ 168.75
6912 Halifax St
San Diego, CA 92120-1020
619-203-3216
Balance Due:
AMOUNT
$35.00
$168.75
$35.00
1635 Faraday Avenue, Carlsbad CA 92008-7314 I 760-602-2700 I 760-602-8560 f I www.carlsbadca.gov
C_ City of
Carlsbad
PLAN CHECK REVISION OR
DEFERRED SUBMITT~t\L
APPLICATION
B-15
Development Services
Building Division
1635 Faraday Avenue
760-602-2719
www .carlsbadca.gov
Original Plan Check Number L ~ R z.o 11 -1.S'Sl Plan Revision NumberPRot2D\b -0059
Project Address \ ~\ I \$ A. s; ~woo\) A Vil-
General Scope of Revision/D eferred Submittal: A t.> D J N ~ *w o + r AP ~ -z...o, .9 W i l'\J bo<.<J,,S
q\, (J'"'J\:r.4rl~e;1 \-\,,:> \loo~ tlO b'ASl ~ W th-.. <;,\ '2...-)..cQ, +-~55 . ' .
CONTACT INFORMATION:
Nam e ~\::N £vt~c, A~
Address((} 0\ \ 'L \~ ~\ \ ~~ S,,
l.J) \ q -203-'"b 2.\ \.!)
Phone U\ ~ z_ e-\ --t \ (;ft:s
City } t Zip q z._..l 2-. 0
Original plans prepared by a n a rchitect or engineer, r evisions must be signed & stamped by that person.
1 . Elements revised: :0· Plans Q5J. Calculations D Soils ;~ Energy D Other
2.
Describe revisions in detail
J7c./ b -Q_ ('~ A Q_ <t \<. ' ~ \rv\ f'.A fl V Ct h AV1 <+€. J
• (J . V .
,If ?o-~--1 '2uS ~ ~11+...., 6 o-.k' ('I Jh r.\.V\~
~ ' -
~ (;.,_.In --N~ T{LvS. \ {, ~~ i ,.,J
u ., k 1~ S2 -\ uJ t1 Dex (:}{ { .s ~-.!Slb \ ,e., vJ "~ she.ex-~AV\~'-
~ '
~ !;1,.-T, tJ'l, Z--<-{ C.,,h ~i\.\ (rl. 't:, \j ,L.., +-v 1 .._h.,,_Jov t't'~-brh c> V\ ~
" -
4. Does this revision, in any way, alter the exterior of the project?
5. Does this revision add A NY new floor area/s)? D Yes
6. Does this revision affect any fire related issues? D Yes·
7 ~#
• ls this a complete set? 0 Yes D No
Jg} Yes
E No
fl No
3.
List page(s) where each
revision is shown
r'a..-, G
V
?,..-16
0 -r Cy ~ -
V' c:.-.s. -1-.
"'
l,~-t z, \>~"') . v ·
D No
£5'Signature \[_s~ ~
• V
Da te ?-J-{£'
1635 Faraday Avenue, Carlsbad. CA 92008 Ph: 760-602-27 19 Fax: 760-602-8558 Email: buifding@carlsbadca.gov
www.carlsbadca.gov
DATE: 03/29/2018
JURISDICTION: City of Carlsbad
~ EsG1I
A SAF Ehuilt Company
:}1,PLICANT
( vURIS.
PLAN CHECK#.: PREV2018-0059 (for CBR2017-2581) ___ SET II
PROJECT ADDRESS: 1511 Basswood Ave.
PROJECT NAME: Revised Roof Addition and Additional Windows
D The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
[gj The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building
department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
D The check list transmitted herewith is for your information. The plans are being held at EsGil
until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
D The applicant's copy of the check list has been sent to:
[gj EsGil staff did not advise the applicant that the plan check has been completed.
D EsGil staff did advise thJ,applicant that the plan check has been completed.
Person contacted: / f Telephone#:
Date contacted: (b : ) Email:
Mail Telephone Fax In erson
[gj REMARKS: Please provide city's soils stamp for applicant to sign prior to final ap o
jurisdiction.
By: Ryan Murphy
EsGil
Enclosures:
03/20/2018
9320 Chesapeake Drive, Suite 208 + San Diego, California 92123 + (858) 560-1468 + Fax (858) 560-1576
'
DATE: 03/19/2018
JURISDICTION: City of Carlsbad
/. EsG1I
D APPLICANT I JURIS.
PLAN CHECK#.: PREV2018-0059 (for CBR2017-2581) ___ SET I
PROJECT ADDRESS: 1511 Basswood Ave.
PROJECT NAME: Revised Roof Addition and Additional Windows
D The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
~ The check list transmitted herewith is for your information. The plans are being held at EsGil
until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
~ The applicant's copy of the check list has been sent to:
Ken Suffridge
D EsGil staff did not advise the applicant that the plan check has been completed.
~ EsGil staff did advise the applicant that the plan check has been completed.
Person contacted: Ken Suffridge Telephone #: (619) 203-3216
Date ted: .;ll'l It~ (by~ Email: KenSuffridge@gmail.com
~ail Telephone WlY In Person
RE KS:
By: Ryan Murphy
EsGil
03/12/2018
Enclosures:
9320 Chesapeake Drive, Suite 208 + San Diego, California 92123 + (858) 560-1468 + Fax (858) 560-1576
PLAN REVIEW CORRECTION LIST
SINGLE FAMILY DWELLINGS AND DUPLEXES
PLAN CHECK#.: PREV2018-0059 (for CBR2017-2581)
Carlsbad
JURISDICTION: City of
PROJECT ADDRESS: 1511 Basswood Ave.
FLOOR AREA: No change
REMARKS:
DATE PLANS RECEIVED BY
JURISDICTION: 03/08/2018
DATE INITIAL PLAN REVIEW
COMPLETED: 03/19/2018
FOREWORD (PLEASE READ):
STORIES: no change
HEIGHT: N.C.
DATE PLANS RECEIVED BY
ESGIL CORPORATION: 03/12/2018
PLAN REVIEWER: Ryan Murphy
This plan review is limited to the technical requirements contained in the California version of
the International Residential Code, International Building Code, Uniform Plumbing Code,
Uniform Mechanical Code, National Electrical Code and state laws regulating energy
conservation, noise attenuation and access for the disabled. This plan review is based on
regulations enforced by the Building Department. You may have other corrections based on
laws and ordinance by the Planning Department, Engineering Department, Fire Department or
other departments. Clearance from those departments may be required prior to the issuance of
a building permit.
Present California law mandates that construction comply with the 2016 edition of the California
Code of Regulations (Title 24), which adopts the following model codes: 2015 IRC, 2015 IBC,
2015 UPC, 2015 UMC and 2014 NEC.
The above regulations apply, regardless of the code editions adopted by ordinance.
The following items listed need clarification, modification or change. All items must be satisfied
before the plans will be in conformance with the cited codes and regulations. Per Sec. 105.4 of
the 2015 International Building Code, the approval of the plans does not permit the violation of
any state, county or city law.
To speed up the recheck process, please note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet number, specification section, etc.
Be sure to enclose the marked up list when you submit the revised plans.
[DO NOT PAY-THIS IS NOT AN INVOICE]
VALUATION AND PLAN CHECK FEE
JURISDICTION: City of Carlsbad
(for CBR2017-2581)
PLAN CHECK#.: PREV2018-0059
PREPARED BY: Ryan Murphy DATE: 03/19/2018
BUILDING ADDRESS: 1511 Basswood Ave.
BUILDING OCCUPANCY: R-3
BUILDING AREA Valuation
PORTION ( Sq. Ft.) Multiplier
Structural Rev. 390 nla
Air Conditioning
Fire Sprinklers
TOTAL VALUE
Jurisdiction Code cb By Ordinance
--------' uildin P rmi F • 1997 UBC B g e t ee ---~
Type of Review: D Complete Review
D Repetitive Fee
~~~~~1 • I Repeats
* Based on hourly rate
Comments: Structural Revision
D Other
0 Hourly
EsGII Fee
Reg. VALUE
Mod.
D Structural Only
,___ ___ 1.-<51 Hrs.@•
$90.00_
($)
$168.751
$135.00!
Sheet 1 of 1
PLANS
Please make all corrections, as requested in the correction list. Submit FOUR new
complete sets of plans for commercial/industrial projects (THREE sets of plans for
residential projects). For expeditious processing, corrected sets can be submitted in one
of two ways:
1. Deliver all corrected sets of plans and calculations/reports directly to the City of
Carlsbad Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760) 602-
2700. The City will route the plans to EsGil and the Carlsbad Planning, Engineering and
Fire Departments.
2. Bring IY'iQ corrected set of plans and calculations/reports to EsGil, 9320 Chesapeake
Drive, Suite 208, San Diego, CA 92123, (858) 560-1468. Deliver all remaining sets of
plans and calculations/reports directly to the City of Carlsbad Building Department for
routing to their Planning, Engineering and Fire Departments.
NOTE: Plans that are submitted directly to EsGil only will not be reviewed by the City
Planning, Engineering and Fire Departments until review by EsGil is complete.
1. The window schedule provided on sheet 4 does not include additional fenestration.
(Proposed windows W08 and W11). Please coordinate T24 fenestration, proposed
floor plan, and window schedule to match.
2. Please revise Section A on sheet 4 to show scissor trusses.
STRUCTURAL
3. The revised calculation package which was received from the engineer of record
for this project was not signed and sealed. Please submit calculation package with
cover sheet signed and sealed by engineer of record.
4. Please provide evidence that the engineer-of-record has reviewed the truss
calculation package prepared by others (i.e., a "review'' stamp on the truss
calculations or a letter). CBC Section 107 .3.4.1.
5. Please fill out and submit the City of Carlsbad's Special Inspection Agreement
which is attached to the end of this list. (For indicated retrofit epoxy set hold-
downs).
6. Please revise roof shear transfer details provided on sheet S2 to match proposed
conditions (scissor trusses).
END OF REVIEW
• Please provide city's soils stamp for applicant to sign prior to final approval at the
jurisdiction.
To speed up the review process, note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet, note or detail number,
calculation page, etc.
Please indicate here if any changes have been made to the plans that are not a
result of corrections from this list. If there are other changes, please briefly
describe them and where they are located in the plans.
• Have changes been made to the plans not resulting from this correction list?
Please indicate:
Yes 1:1 No 1:1
The jurisdiction has contracted with EsGil, located at 9320 Chesapeake Drive,
Suite 208, San Diego, California 92123; telephone number of 858/560-1468, to
perform the plan review for your project. If you have any questions regarding
these plan review items, please contact Ryan Murphy at EsGil. Thank you.
STORM WATER POLLUTION PREVENTION NOTES
1. ALL NECESSARY EQUIPMENT AND MATERIALS SHALL BE
AVAILABLE ON SITE TO FACILITATE RAPID INSTALLATION
OF EROSION AND SEDIMENT CONTROL BMPs WHEN RAIN
IS EMINENT.
2. THE OWNER/CONTRACTOR SHALL RESTORE ALL EROSION
CONTROL DEVICES TO WORKING ORDER TO THE SATISFACTION
OF THE CITY INSPECTOR AFTER EACH RUN-OFF PRODUCING
RAINFALL.
3. THE OWNER/CONTRACTOR SHALL INSTALL ADDITIONAL EROSION
CONTROL MEASURES AS MAY BE REQUIRED BY THE CITY
INSPECTOR DUE TO INCOMPLETE GRADING OPERATIONS OR
UNFORESEEN CIRCUMSTANCES WHICH MAY ARISE.
4. ALL REMOVABLE PROTECTIVE DEVlCES SHALL BE IN PLACE
AT THE END OF EACH WORKING DAY WHEN THE FIVE (5)
DAY RAIN PROBABILITY FORECAST EXCEEDS FORTY PECENT
(40%). SILT AND OTHER DEBRIS SHALL BE REMOVED AFTER
EACH RAINFALL.
5. ALL GRAVEL BAGS SHALL CONTAIN 3/4 INCH MINIMUM
AGGREGATE.
6. ADEQUATE EROSION AND SEDIMENT CONTROL AND PERIMETER
PROTECTION BEST MANAGEMENT PRACTICE MEASURES MUST
BE INSTALLED AND MAINTAINED.
7. THE CITY INSPECTOR SHALL HAVE THE AUTHORITY TO ALTER
THIS PLAN DURING OR BEFORE CONSTRUCTION AS NEEDED
TO ENSURE COMPLIANCE WITH CITY STORM WATER QUALITY
REGULATIONS.
OWNER'S CERTIFICATE:
I UNDERSTAND AND ACKNOWLEDGE THAT I MUST: (1) IMPLEMENT
BEST MANAGEMENT PRACTICES (BMPS) DURING CONSTRUCTION
ACTIVlTIES TO THE MAXIMUM EXTENT PRACTICABLE TO AVOID
THE MOBILIZATION OF POLLUTANTS SUCH AS SEDIMENT AND TO
AVOID THE EXPOSURE OF STORM WATER TO CONSTRUCTION
RELATED POLLUTANTS; AND (2) ADHERE TO, AND AT ALL TIMES,
COMPLY 1'11TH THIS CITY APPROVED TIER 1 CONSTRUCTION SWPPP
THROUGHOUT THE DURATION OF THE CONSTRUCTION ACTIVITIES
UNTIL THE CONSTRUCTION WORK IS COMPLETE AND APPROVED
BY THE CITY OF CARLSBAD.
I AQ,9-..':::'.\ ~5.
OWNER(S)/OWNER'S AGENT ~INT)
~
OWNER(~AME (SIGNATURE)
E-29
IOB)y j (7
'LJAIE'
STORM WATER COMPLIANCE FORM
TIER 1 CONSTRUCTION SWPPP ~7--;}5g/
BEST MANAGEMENT PRACTICES (BMP) SELECTION TABLE
Erosion Control Sediment Control BMPs Tracking Non-Storm Water Waste Management and Materials
BMPs Control BMPs Management BMPs Pollution Control BMPs
C C -C 0 -.2 .2 :;:; C C 'O "' 'O ., C --c> C E C "' 'O u u C c> E C -C -:, :, 0 £ ·.::: .9-C C C E "' L L :;:; 'O L "' "' ::::E 'O ., c> L --C .5 s:::. :, >, c> -C <> L .5 "' c ., ., ., er L C C ., "' c> Co C. "' ·.::: -C u, C > L L u.J !;! C 0 C--Best Management Practice* o'd C C a, C. L 0"' 0 L "' "' :;:; ;,: -.,
., 3 ., ,.!:: "' C C "' -"' C -c-..c C E (I) c> "0 C
UL u ., 'O ., ~ 'O <ij ., ::::E C <> C C :,:: C
(BMP) Description ~ ., u "'Vl ·a ., c> a, c> C C !;! _., ., "' "' (I) C 3c CC Cl ::, "' 3 ~ co L u -C 0 LO 'O u.J 'O >, 0 ., Cc> "' [g E " E ., E C Cl a, U) ·-c> .,, C 0 (I) :;:; Cl:;:; u 1l X ::::E Cl c> Cl C "' er _E C N Ul i:l C en:;:; "' <> C ""' 0 ·c. L-;,: "' 0"' -"' "' C ~ E ~ J .0 E~ i=fil =3 L•-:0 o·c ·cg "ki a. 0 c> ~ c> ~ c> (I) :, cC ~ L ~t, "' -'O ..C C u L (I) :, 'O L-·-'O •-L C <> L u --'O C -·-C. 'i5 "' .0 L .0 C •-C 0 0 LC -"' C LU C 0 0 ~8 --o -= C ~§ 0 .0 Cc> .8 0 CC ..c "' 0 "' ~ CL vi V, "' ..c G:: L -C C -L U) C ;;: ct 0 :§! u c-C -C. 0
"' u.J Cl Vl u "' VJ> Vl Vl a. v, er a.a a. ::::E Vl ::::E Vl VlU Vl ::::E
CASQA Designation ~ " a:, O'> ,.., .... "' "' " a:, 0 N ,.., " a:, N ,.., .... "' I I I ' ' I I I I I I ' I I ' I I I I I I I I
u u u u u.J u.J u.J w w u.J u.J w f!: f!: U) Vl U) U) i i i i i Construction Activity w u.J u.J w Vl Vl U) Vl U) Vl Vl Vl z z z z
Grading/Soil Disturbance IX
Trenchina /Excavation
Stockpilinq .X X
Drill in a /Barino
Concrete/Asohalt Sawcuttina
Concrete Flatwork
Pavina
Conduit/Pipe Installation
Stucco/Mortar Work
Waste Disposal X.
Staaina /Lav Down Area
Eauipment Maintenance and Fuelina
Hazardous Substance Use/Storaae "' Dewaterina
Site Access Across Dirt
Other rnst ):
Instructions:
1. Check the box to the left of all applicable construction activity {first column) expected to occur during construction.
2. Located along the top of the BMP Table is a list of BMP's with it's corresponding California Stormwater Quality Association {CASQA) designation number. Choose one
or more BMPs you intend to use during construction from the list. Check the box where the chosen activity row intersects with the BMP column.
3. Refer to the CASQA construction handbook for information and details of the chosen BMPs and how to apply them to the project.
PROJECT INFORMATION
Site Address: 15 I I D(l.,SS(,l:QoD F\ \If: .
cc NC cc
I::::E
"' I i
Assessor's Parcel Number: d[)'(· \30-39 · (X)
Emergency Contact:
Page 1 of 1
Name: KE-\0 '.:?Cl ~~R \ GG E.
24 Hour Phone:\o\C:I 003 3,Q.\(o
Construction Threat to Storm Water Quality
{Check Box)
0 MEDIUM ~OW
uc cC oc
U::::E
a:,
I i
'-,.::::
REV 02/16