HomeMy WebLinkAbout1525 FARADAY AVE; 200; CB052867; PermitCity of Carlsbad
1635 Faraday Av Carlsbad, CA 92008
09-12-2005 Commercial/Industrial Permit Permit No: CB052867
Building Inspection Request Line (760) 602-2725
Job Address:
Permit Type:
Parcel No:
Valuation:
Occupancy Group:
Project Title:
Applicant:
1525 FARADAY AV CBAD St: 200
Tl Sub Type:
2121302700 Lot#:
$369,706.00 Construction Type:
Reference #:
GOODSOURCE SOLUTIONS-11,926 SF
SHELL TO OFFICES
INDUST
0
111
Owner:
Status:
Applied:
Entered By:
Plan Approved:
Issued:
Inspect Area:
Plan Check#:
ISSUED
08/04/2005
RMA
09/12/2005
09/12/2005
DESIGN GROUP NEWPORT NATIONAi/CORNERSTONE LL C
C/0 SCOTT BRUSSEAU NEWPORT NATL
1525 FARADAY AVE #100
858 794-3222
Building Permit
Add'I Building Permit Fee
Plan Check
Add'I Plan Check Fee
Plan Check Discount
Strong Motion Fee
Park Fee
LFM Fee
Bridge Fee
BTD#2 Fee
BTD #3 Fee
Renewal Fee
Add'I Renewal Fee
Other Building Fee
Pot. Water Con. Fee
Meter Size
Add'I Pot. Water Con. Fee
Reel. Water Con. Fee
$1,378.16
$0.00
$895.80
$0.00
$0.00
$77.64
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
CARLSBAD CA 92008
Meter Size
Add'I Reel. Water Con. Fee
Meter Fee
SDCWAFee
CFD Payoff Fee
PFF (3105540)
PFF (4305540)
License Tax (3104193)
License Tax (4304193)
Traffic Impact Fee (3105541)
Traffic Impact Fee (4305541)
PLUMBING TOTAL
ELECTRICAL TOTAL
MECHANICAL TOTAL
Master Drainage Fee
Sewer Fee
Redev Parking Fee
Additional Fees
TOTAL PERMIT FEES
$0.00
$0.00
$0.00
$0.00
$6,728.65
$0.00
$0.00
$0.00
$5,012.00
$0.00
$34.00
$310.00
$111.50
$0.00
$15,509.92
$0.00
$0.00
$30,057.67
Total Fees: $30,057.67 Total Payments To Date: $30,057.67 Balance Due: $0.00
Inspector: --~-------
~ETJ;;glfcr~8
_ATTACHED
SWf\"'2-1.>
Clearance: ------
NOTICE: Please take NOTICE that approval of your project includes the "Imposition" of fees, dedications, reservations, or other exactions hereafter collectively
referred to as '1ees/exactions." You have 90 days from the date this permit was issued to protest imposition of these fees/exactions. If you protest them, you must
follow the protest procedures set forth in Government Code Section 66020(a), and file the protest and any other required information with the City Manager for
pro.cessing in accordance with Carlsbad Municipal Code Section 3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack,
review, set aside, void, or annul their imposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection fees and capacity
changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this project. NOR DOES IT APPLY to any
fees/exactions of which ou have revi usl been iven NOTICE similar o this or s o which the st ute of limitations has reviousl otherwise ex ired.
PERMIT APPLICATION
CITY OF CARLSBAD BUILDING DEPARTMENT
1635 Faraday Ave., Carlsbad, CA 92008
Subdivision Name/Number ~ Unit No. Phase No. Total # of units
I 0..2.. earls.load... f(ec.-9,P.A---t:h Cen iev-~982 08/0/4/0~ 000? fl1 O?
Assessor's Parcel # Existing ~h.,?l ( Pro~SE;R >I;: ~ e c GP 895. 80 212.-r;3O .-2-rz-Q? ?' C/ ~~
, YV""~ '""'-'<";~ A,v., , , "-' ,!3. '_\ll(Qft!,{E,R,$,~ !:)OMPl:~S:ATl,Oij " , ,
Workers' Compensation Declaration: I hereby affirm under penalty of perjury one of the following declarations:
0 I have and will maintain a certificate of consent to self-insure for workers' compensation as provided by Section 3700 of the Labor Code, for the performance
of the work for which this permit is issued.
'vf' I have and will maintain workers' compensation, as required by Section 3700 of the Labor Code, for the performance of the work for which this permit is
~ued. My worker's compensation insurance carrier and policy number are: •
Insurance Company €'1fu -re. {er$ fkpt?iyt &5uttlr: wme:i1Y?licy No.bT{E----CO -%130! oA Expiration Da~e !!13/o I IO 6
(THIS SECTION NEED NOT BE COMPLETED IF THE PERMIT IS FOR ONE H N6RED DOLLARS [$100] OR LESS)
D CERTIFICATE OF EXEMPTION: I certify that in the performance of the work for which this permit is issued, I shall not employ any person in any manner so as
to become subject to the Workers' Compensation Laws of California.
WARNING: Failure to secure workers' compensation coverage is unlawful, and shall subject an employer to criminal penalties and civil fines up to one hundred
thousand dollars ($100,000), i 11ition to f compensation, damages as provided for in Section 3706 of the Labor code, interest and attorney's fees.
SIGNATURE r . DATE &/ + /o5
:7._· '.Q:WN.Eil-!3P!LJ>_ -D _cµu~tl~ _ . , . · . .·, .. ~ ... -, , ~ . -·.. -. ' . . . . . .
I hereby affirm that I am exempt from the Contractor's License Law for the following reason:
0 I, as owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not intended or offered for sale
(Sec. 7044, Business and Professions Code: The Contractor's License Law does not apply to an owner of property who builds or improves thereon, and who does
such work himself or through his own employees, provided that such improvements are not intended or offered for sale. If, however, the building or improvement is
sold within one year of completion, the owner-builder will have the burden of proving that he did not build or improve for the purpose of sale).
0 I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions Code: The
Contractor's License Law does not apply to an owner of property who builds or improves thereon, and contracts for such projects with contractor(s) licensed
pursuant to the Contractor's License Law).
0 I am exempt under Section ______ Business and Professions Code for this reason:
1. I personally plan to provide the major labor and materials for construction of the proposed property improvement. 0 YES ONO
2. I (have / have not) signed an application for a building permit for the proposed work.
3. I have contracted _with the following person (firm) to provide the proposed construction (include name / address I phone number I contractors license number):
4. I plan to provide portions of the work, but I have hired the following person to coordinate, supervise and provide the major work (include name / address / phone
number/ contractors license number):, _____________________________________________ _
5. I will provide some of the work, but I have contracted (hired) the following persons to provide the work indicated (include name / address / phone number / type of work):. ________________________________________________________ _
PROPERTY OWNER SIGNATURE _____________________ _ DATE _________ _
;CQM~LETifTHJS SECTION FQ'R ·NQN>RESlDENflAL BUl~DIN.G PERMITS 9NL Y
Is the applicant or future building occupant required to submit a business plan, acutely hazardous materials registration form or risk management and prevention
program under Sections 25505, 25533 or 25534 of the Presley-Tanner Hazardous Substance Account Act? 0 YES O NO
Is the applicant or future building occupant required to obtain a permit from the air pollution control district or air quality management district? 0 YES O NO
Is the facility to be constructed within 1,000 feet of the outer boundary of a school site? 0 YES O NO
IF ANY OF THE ANSWERS ARE YES, A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR IS MEETING THE
REQUIREMENTS OF THE OFFICE OF EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT. s.~:-~ :co_N$TflU:CTJONLEijp1jij~"AG~NCY . :. . , . ,
I hereby affirm that there is a construction lending agency for the performance of the work for which this permit is issued (Sec. 3097(i) Civil Code).
LENDER'S NAME _____________ _ LENDER'S ADDRESS. _______________________ _
:-g_, · AP.PPCJ:\NT Cl;ijTIF.lfiATlON.,
I certify that I have read the application and state that the above information is correct and that the information on the plans is accurate. I agree to comply with all
City ordinances and State laws relating to building construction. I hereby authorize representatives of the Cit\' of Carlsbad to enter upon the above mentioned
property for inspection purposes. I ALSO AGREE TO SAVE, INDEMNIFY AND KEEP HARMLESS THE CITY OF CARLSBAD AGAINST ALL LIABILITIES,
JUDGMENTS, COSTS AND EXPENSES WHICH MAY IN ANY WAY ACCRUE AGAINST SAID CITY IN CONSEQUENCE OF THE GRANTING OF THIS PERMIT.
OSHA: An OSHA permit is required for excavations over 5'0" deep and demolition or construction of structures over 3 stories in height.
EXPIRATION: Every permit issued by the building Official under the provisions of this Code shall expire by limitation and become null and void if the building or work
authorized by such permit is not commenced within 180 days from the date of such permit or if the building or work authorized by such permit is suspended or abandoned
at any time after the work is commenced for a pe · f 180 da ec · n 106.4 niform Building Code).
APPLICANT'S SIGNATURE ~-,......u ~ DATE &=I+ I CJS
WHITE: File YELLOW: Applicant PINK: Finance
City of Carlsbad Bldg Inspection Request
For: 11/29/2005
Permit# CB052867
Title: GOODSOURCE SOLUTIONS-11,926 SF
Description: SHELL TO OFFICES
Type: Tl
Job Address:
Suite:
Location:
Sub Type: INDUST
1525 FARADAY AV
200 Lot 0
APPLICANT DESIGN GROUP
Owner: NEWPORT NATIONAL/CORNERSTONE LL C
Remarks:
Total Time:
CD Description Act Comment
Inspector Assignment: JM
Phone: 8589675918
Inspector:
Requested By: STEVEN
Entered By: JANEAN
19 Final Structural f&S_ _______ _
29 Final Plumbing
39 Final Electrical
49 Final Mechanical
Comments/Notices/Hold
Associated PCRs/CVs
lnst;1ection Histoiy
Date Description Act lnsp Comments
11/18/2005 19 Final Structural co JM LIST AT SITE
11/18/2005 29 Final Plumbing co JM
11/18/2005 39 Final Electrical AP JM METER RELEASE
11/18/2005 49 Final Mechanical AP JM
11/16/2005 89 Final Combo CA JM STEVEN
11/15/2005 89 Final Combo NR JM
11/09/2005 84 Rough Combo AP JM ON 11/8
11/08/2005 84 Rough Combo AP JM OK TO SET ALL TILE
10/31/2005 84 Rough Combo AP JM VERIFY ALL CORRIDOR & STAIR WELL FIRE CAULKING
10/20/2005 41 Underground Ducts NR TP
10/20/2005 44 Rough/Ducts/Dampers NR TP
09/21/2005 17 Interior Lath/Drywall AP JM
09/21/2005 22 Sewer/Water Service WC JM
City of Carlsbad Bldg Inspection Request
For: 11/18/2005
Permit# CB052867
Title: GOODSOURCE SOLUTIONS-11,926 SF
Description: SHELL TO OFFICES
Type: Tl
Job Address:
Suite:
Location:
Sub Type: INDUST
1525 FARADAY AV
200 Lot 0
APPLICANT DESIGN GROUP
Owner: NEWPORT NATIONALICORNERSTONE LL C
Remarks: PM PLEASE
Total Time:
CD Description Act Commenr
19 Final Structural 1+ L,«
29 Final Plumbing
Inspector Assignment: JM ---
Phone: 8589675918
Inspector:
Requested By: STEVEN
Entered By: CHRISTINE
39 Final Electrical 4R &M &~
49 Final Mechanical -I-
Comments/Notices/Hold
Associated PCRs/CVs
lnsgection Histo!Y
Date Description Act
11/16/2005 89 Final Combo CA
11/15/2005 89 Final Combo NR
11/09/2005 84 Rough Combo AP
11/08/2005 84 Rough Combo AP
10/31/2005 84 Rough Combo AP
10/20/2005 41 Underground Ducts NR
10/20/2005 44 Rough/Ducts/Dampers NR
09/21/2005 17 Interior L~th/Drywall AP
09/21/2005 22 Sewer/Water Service WC
09/21/2005 24 Rough/Topout AP
09/16/2005 14 Frame/Steel/Bolting/Welding AP
09/16/2005 16 Insulation PA
lnsp Comments
JM STEVEN
JM
JM ON 11/8
JM OK TO SET ALL TILE
JM VERIFY ALL CORRIDOR & STAIR WELL FIRE CAULKING
TP
TP
JM
JM
JM
JM
JM WALLS ONLY EXEMPT FROM HEALTH DEPART APPROVAL-FOOD
WHOLESALE.
Carlsbad 05-2867
9/7/05
EsGil Corporation
In Partnersfiip witfi (jovernment for '13uiCaing Safety
DATE: 9/7 /05
JURISDICTION: Carlsbad
PLAN CHECK NO.: 05-2867 SET:11
PROJECT ADDRESS: 1525 Faraday Ave. Suite 250
PROJECT NAME: Goodsource Solutions Office TI
D APPLICANT
C::::: D JURIS. _::;,
D PLAN REVIEWER
D FILE
• The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's building codes when
minor deficiencies identified below are resolved and checked by building department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
D The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
D The applicant's copy of the check list has been sent to:
• Esgil Corporation staff did not advise the applicant that the plan check has been completed.
D Esgil Corporation staff did advise the applicant that the plan check .has been completed.
Person contacted: Telephone#.: ••
Date contacted: (by: ) Fax #:
Mail Telephone Fax In Person
• REMARKS: Replacement sheets T2, Tl-1, Tl-5, M0.1, M0.2 & E-3 at the City must be incorporated
in the original set of City plans to make an approved 2nd set of plans ident.ical to the approved
plans form EsGil Corp.
By: Chuck Mendenhall
Esgil Corporation
D GA D MB D EJ D PC 8/30/05
Enclosures:
trnsmtl.dot
DATE: 8/17/05
JURISDICTION: Carlsbad
EsGil Corporation
In Partnersliip wit/i (jovemment for 'Builaing Safety
PLAN CHECK NO.: 05-2867 SET: I
PROJECT ADDRESS: 1525 Faraday Ave. Suite~
PROJECT NAME: Goodsource Solutions Office TI
CJ .faEELJQANT
~
D PLAN REVIEWER
D FILE
D The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies ·identified below are resolved and checked by building department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and r§lsubmitted for a complete recheck.
• The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the Jurisdiction to forward to the applicant
·contact persori': :.; : --·-:--! rr.··
• The applf~ant's copy ~f the check list has been sent to: ' . -:: . -..
Designcorp; Att'n: Christine Jordan
444 S. Cedros Ave.,· #175, Solana Beach, CA 92075
..... __ ,.
'· . -~--· ·,
D Esgil Corporation staff did not advise the applicant that the plan check has been completed.
• Esgil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Christine Jordan Telephone #: (858) 794-3222
Date contacted: t(r? {o5 (by: {A... ) Fax #: (858) 794-~ 322 I
Mail _.-,Telephone
D REMARKS:
Fax.,....,. In Person
By: Chuck Mendenhall
-Esgil Corporation
D GA D MB D EJ D PC
Enclosures:
8/8/05 tmsmtl.dot
9320 Chesapeake Drive, Suite 208 + San Diego, California 92123 + (858) 560-1468 + Fax (858) 560-1576
Carlsbad 05-2867
8/17/05
PLAN REVIEW CORRECTION LIST
TENANT IMPROVEMENTS
PLAN CHECK NO.: 05-2867·
OCCUPANCY: B
TYPE OF CONSTRUCTION: II lHR
ALLOWABLE FLOOR AREA: no change
SPRINKLERS?: Yes
REMARKS:
DATE PLANS RECEIVED BY
JURISDICTION:
JURISDICTION: Carlsbad
USE: office
ACTUAL AREA: 11926 TI Only
STORIES: no change
HEIGHT: no change
OCCUPANT LOAD: 97
DATE PLANS RECEIVED BY
ESGIL CORPORATION: 8/8/05
DATE INITIAL PLAN REVIEW
COMPLETED: 8/17 /05
PLAN REVIEWER: Chuck Mendenhall
FOREWORD (PLEASE READ): . . . . . . ._ . . . ~
1 .. ::·. '
This plan review is limited to the technical requirements contained in the Uniform Building Code,:
Uniform Plumbing Code, Uniform Mechanical Code, National Electrical Code and state'·laws
regulating energy conservation, noise attenuation and access for the disabled. This.plan r~yiew-
is based on regulations enforced by the Building 'Department. You may have other corrections
based on laws and ordinances enforced by the Planning Department, Engineering Department,
Fire Department or other departments. Clearance from those departments may be required
prior to the issuance of a building permit.
Code sections cited are based on the 1997 UBC.
The following items listed need clarification, modification or change. All items must be satisfied
before the plans will be in conformance with the cited codes and regulations. Per Sec. 106.4.3,
1997 Uniform Building Code, the approval of the plans does not permit the violation of any
state, county or city law.
To speed up the recheck process, please note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet number, specification section, etc.
Be sure to enclose the marked up list when you submit the revised plans.
TENANT IMPROVEMENTS WITHOUT SPECIFIC ENERGY DATA OR POLICY SUPPLEMENTS (1997UBC) tiforw.dot
Carlsbad 05-2867
8/17/05
• Please make all corrections on the original tracings, as requested in the correction list.
Submit three sets of plans for commercial/industrial projects (two sets of plans for
residential projects). For expeditious processing, corrected sets can be submitted in
one of two ways:
1. Deliver all corrected sets of plans and calculations/reports directly to the City of
Carlsbad Building Department, 1635 Faraday Ave., Carlsbad, CA 92009, {760) 602-
2700. The City will route the plans to EsGil Corporation and the Carlsbad Planning,
Engineering and Fire Departments.
2. Bring one corrected set of plans and calculations/reports to EsGil Corporation,
9320 Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-1468. Deliver
all remaining sets of plans and calculations/reports directly to the City of Carlsbad
Building Department for routing to their Planning, Engineering and Fire Departments.
NOTE: Plans that are submitted directly to EsGil Corporation only will not be
reviewed by the City Planning, Engineering and Fire Departments until review by EsGil
Corporation is complete.
1. The interior nonbearing walls must be designed to resist 5PSF out-of-plane load
per UBC 1611.5. the braces at the top of the wall shown in 1/Tl-5 may not
exceed 6'-0" OC to·comply with the code.
2. Two exits are required from the Meeting/Break Room #211. One of the exits may
lead to the hallway which then leads to the fire rated corridor system. The 2nd .
required exit must lead d_irectly to the fire rated corridor system. As shown on the
floor plan the exits do no~ comply for this room. See USC Table 10-Aand : .
Section 1004.2.2. . .... -. ·: · . . ' .. ~ . ..... . ~ . ' ...
3. Exit.doors from rooms or ·areas serving more than 50 occupants must swing in
the direction of exit travel. Exit doors from Rm 211 must swing in the direction of
exit travel from the room.
4. Provide multiple switch lighting controls per Title 24, Part 6. It is not clear on the
lighting plan how the multiple light control switching will be provided in the large
open office area (Rooms 220 & 219).
• MECHANICAL
5. Detail overflow (secondary) condensate discharge from air conditioning units that
are in a ceiling space, to a readily observable location. (UMC Section 1105.12)
6. Provide smoke detection in the supply air duct of an "air-moving system' for
required shut-off of equipment for smoke control. UMC Section 609.2. An "air-
moving system" is a system designed to provide heating, cooling, or ventilation
in which one or more air-handling units are used to supply air to a common
space or to draw air from a common plenum or space. UMC Section 203.0. All
HVAC units must be equipped with smoke detection as the systems mix
and the combined CFM exceeds 2000.
Carlsbad 05-2867
8/17/05
END OF REVIEW
To speed up the review process, note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet, note or detail number,
calculation page, etc.
The jurisdiction has contracted with Esgil Corporation located at 9320
Chesapeake Drive, Suite 208, San Diego, California 92123; telephone number of
858/560-1468, to perform the plan review for your project. If you have any
questions regarding these plan review items, please contact Chuck Mendenhall
at Esgil Corporation. Thank you.
Carlsbad 05-2867
8/17/05
!VALUATION AND PLAN CHECK FEE
JURISDICTION: Carlsbad PLAN CHECK NO.: 05-2867
PREPARED BY: Chuck Mendenhall DATE: 8/17/05
BUILDING ADDRESS: 1525 Faraday Ave. Suite 250
BUILDING OCCUPANCY: B TYPE OF CONSTRUCTION: II lHR
BUILDING AREA Valuation Reg. VALUE
PORTION (Sq.Ft.) Multiplier Mod.
Tl 11926 City Est
·-
Air Conditioning
Fire Sprinklers
TOTAL VALUE
-Jurisdiction Code . cb By Ordinance
Bldg. Permit Fee by Ordinance I• I
Plan Check Fee by Ordinance f ... j
Type of Review: 0 Complete Review D Structural Only
D Repetitive Fee ~ Repeats
Comments:
D Other
D Hourly I Hour *
Esgil Plan Review Fee
'
($)
369,706
.. •"'·
·· ."-.!_,369,70.6
. '
$1,378.161
$895.801
$771.771
Sheet 1 of 1
macvalue.doc
''t '
PLANNINC/ENCINEERING APPROVALS
PERMIT NUMBER CB oe:;-t,-0 {o f
"RESIDENTIAL
RESIDENTIAL ADDITION MINOR
( < $10,000.00)
DATE OB-(2--(h ___ ___;;_~-
PLAZA CAMINO REAL
CARLSBAD COMPANY STORES
VILLAGE· FAIRE
COMPLETE OFFICE BUILDING
OTHER ________________ _
DATE
(6
ENGINEER. _ ___,i_~;;....;...;;.. __ _
~ alf,rtl
DATE f lrf/ol / ---+,----
DDCSIMU:fDrms/Plannlna l;nalnHIIM .&llnmvalc
'\
-l
ENGINEERING DEPARTMENT
FEE CALCULATION WORKSHEET
D Estimate based on unconfirmed information ~rom applicant.
D Calculation b~ed on uil ing plancheck plan submittal. to _
Address: 1-rzs VLV•--, Bldg. Permit No. ()J -~ 7
Checked by: ___ _ Date: -----
EDU CALCULATIONS: List types and square footages for all uses.
Types of Use: ·6/J1 Sq. Ft./Units: // ') 2. (o
Types of Use:·_______ Sq. Ft./Units: _____ _
·ADT CALCULATIONS: List types· and square footages for all uses.
Types of Use: ?5}) Sq. Ft./Units: // 1 ')ll .. D
EDU's: _q_,__._z_c/~
EDU's: ----~
ADT's: l!7 ------. Wu .
· Types of Use: _______ Sq. Ft./Units: _____ _ ~DT's: _____ _
FEES REQUIRED:
WITHIN CFO: DYES (no bridge & thoroughfare fee in District #1; reduced Traffic Impact Fee) o· NO
D 1. PARK-IN-LIEU FEE PARK AREA&·#: ----~ FEE/UNIT: ____ _
D 2. TRAFFIC IMPACT FEE
ADT's/UNITS:
1 /7;
D 3. BRIDGE AND THOROUGHFARE FEE
x NO. UNITS: __ _
X FEE/ADT: ___,L_(e_
(DIST. #1 DIST. #2
= $___ ~
=$
. DIST. #3 )
ADT's/UNITS:_____ X FEE/ADT: ___ _ =$~
D 4. FACILITIES MANAGEMENT FEE . ZONE:. l{Jrrf"' l'h!,l)el'vvlr -rj
D
UNIT/SQ.FT.: ____ _
5. SEWER FEE ,/
EDU's: 1~
BENEFIT AREA: =
EDU's: :J:. --z_'(
D 6. SEWER LATERAL ($2,500)
D 7. DRAINAGE FEES PLDA ___ _
ACRES: ------,---
0 8. POTABLE WATER FEES
UNITS CODE CONNECTION FEE
X
X
X
FEE/SQ.FT./UNIT: ___ _
FEE/EDU, / z_?
FEE/EDUp2Ycf ~
=$
=$ _____ _
HIGH ___ .. /LOW __ _
X FEE/AC: ___ _ =$ _____ _
METER FEE SDCWA FEE IRRIGATION
. 1 of2
tal--.J\l'\---'••1-c---u•·--,....., .......... ..,_ ,,.,_..., .. ...,.,..,.. Rev. 7/14/00
)
H C)1-<t,(trN =
Ctv-j_J-
~.lo:S
z. 3~ -----Y.L'/
Carlsbad Fire Department
Plan Review Requirements Category: TI , INDUST
Date of Report: 98-10-2005
Name:
Address:
Permit #: CB052867
Job Name:
Job Address:
GOODSOURCE SOLUTIONS-11,926 SF
1525 FARADAY AV CBAD St: 200
INC01'1PLETE The item )'Ott have sttbmitted for review is ifl:eomp±ete. l\.t this time, this offiee cannot
ad@qaat@ly condact a r@Yi€}1.V to determine compliaHc@ vlith the applicabh\l codes med/or stanaards. Please re¥iew
ca,refully all cornmSE.ts attachsa. :Please resubmit tlw necessary plans a.Hd.lor specificatiens, 1.vith c:aanges "clouded",
to this office for review ffiJ:d approval:
Conditions:
Cond: CON0000634
APPROVED: THIS PROJECT HAS BEEN REVIEWED
AND APPROVED FOR THE PURPOSES OF ISSUANCE
OF BUILDING PERMIT.
THIS APPROVAL IS SUBJECT TO FIELD INSPECTION
AND REQUIRED TEST, NOTATIONS HEREON,
CONDITIONS IN CORRESPONDENCE
AND CONFORMANCE WITH ALL APPLICABLE REGULATIONS.
THIS APPROVAL SHALL NOT BE HELD TO PERMIT
OR APPROVE THE VIOLATION OF ANY LAW.
Entry: 08/10/2005 By: gr Action: AP
l·
i ·1
I
I
I
VOi M,L/ V.L J"l'\..l J..1. • ":10 rl1.A U.LU' -1tJO &...1 I 0
OFFICE USE ONLY
H# _______ _
SAN DIEGO REGIONAL BP DATE _ __..____._ __
SA/M ______ _
APCO ______ _
HAZARDOU~ MATERIALS QUESTIONNAIRE
Plan filell
Plan File#/Permlt#
Indicate by circling the item, whether your business will use, process, or store any of the following hazardous materials. If any of the items are
circled, applicant must contact the Fire Protection Agency with Jurisdiction prior to plan submittal, ·
1. Explosive or Blasting Agents 4. Flammable Solids 7. Pyrophorics 10. Cryogenics 13.-Corroslves .
2. Compressed Gases 6. Organic Peroxides B. Unstable Reactives 11. Highly Toxic or Toxic Materials 14. Other Health Hazards
3. Flammable or Combustible Liquids 6. Oxidizers 9. Water Reactlves 12. Radioactives
PAR! 11; SAN DIEGO COUNTY DEPARTMENT OF ENVIRONMENTAL HEALTH • HAZARDOUS MATERIALS MANAGEMENT DIVISION IHMMDI;
If the answer to any ot the questions is ye.s. applicant must contact the County of S~n Diego Hazardous Materials Management
Olvlslon, 1265 Imperial Avenue, 3rd Floor, San Diego, CA 92101. Telephone (6191 338-2222 prior to the iss1:1ance of a building O CalARP Exempt
department permit. -
Date Initials
FEES MAY BE REQUIRED
·ves No 0 CalARP Required
Date Initials ·
1. § Z1syour business listed on the reverse side.of this form?
2. ~ WIii your business dispose of Hazardous Substances or Medical Wasta in any amount? .
3. [5?' Will your business store or handle Hazar'clous Substances in quantities equal to or greater than 55 gallons, tJ CalARP Complete 500 pounds, 200 cubic feet or carcinogens/reproductive toxins In ahy quantity?
Will your business use an existing or Install an underground storage tank?
Will your business store or handle Regulated Substances (CalARPI 7 Date Initials
WIii your business use or install a Hazardous Waste Tank S stem (Title 22, Article 101
G O T
If the answer ta any of ~he questions is yes, applicant must contact the Air Pollution Control District, 9150 Chesapeake Or!ve, San Diego, CA 92123.
Telephone ·1 (868) 650-4550 prior to the issuance of a building department permit.
YES NO,..... • • :
1, 0 I)(: Will the Intended occupant tnatall or use anv of the equipment llsted on the Listing of Air-Pollution Control District Permit Categories, on the
reverse side of this form? ~-0 0 (ANSWER ONLY IF QUESTION 1 IS YES.J WIii the subject facility be located withln-1;000 feet of the outer boundary of a school lK through
121 as listed in the current Directory of School and Community College Districts, publlshed by the San Diego Counw Office of Education and
the current California Private School Directory, compiled in accordance with provisions of Education Code Section 331907
3. Ooes the buildin or structure for which this ermlt is re uested contain an friable asbestos?
Briefly describe business activity and proposed pro/ect:
Date
I declare under penalty of perjury that to the best of my knowledge and belief the responses made herein are true an
FOR OFFICIAL.USE ONL V:
FIRE DEPARTMENT OCCUPANCY CLASSIFICATION: ___ __,'-------------------~------BY:. ___________________________ _.;. ______ Date:_,. ______________ _
EXEMPT OR NO RJRTHS/l lNFOAMATION REQUIREO RE!.eASl:D FOR eu11.OING PERMIT eUT NOT FOR OCCUPANCY
COUNTY0HMMO APCO COUNTY-HMMO APCO
RELEASED FOR OCCUPANCY
COUNTY-HMMD APCO
County o/ San -Oiego
Department or-Environmental Health
J
. fcERTIFICATE OF COMPLIANCE Part 1 of 2 MECH-11
PROJECT NAME DATE
Good Source Solutions 8/25/2005
PROJECT ADDRESS
Emerald Lake Corporate Centre Suite 220 Carlsbad
PRINCIPAL DESIGNER. MECHANICAL TELEPHONE Building Permit#
Greater San Diego Air Conditioning Co. Inc. (619) 469-7818
DOCUMENTATION AUTHOR TELEPHONE Checked by/Date Greater San Diego Air Conditioning Co. Inc. (619) 469-7818 Enforcement Agency tJse
GENERAL INFORMATION
DATE OF PLANS ;J BUILDING CONDITIONED FLOOR AREA I CLIMA 7 ZONE 7-29-05 11,400 Sq.Ft.
BUILDING TYPE [X] NONRESIDENTIAL D HIGH RISE RESIDENTIAL D HOTEUMOTEL GUEST ROOM
PHASE OF CONSTRUCTION [X] NEW CONSTRUCTION D ADDITION D ALTERATION D EXISTING + ADDITION
METHOD OF MECHANICAL [X] PRESCRIPTIVE D PERFORMANCE
COMPLIANCE
PROOF OF ENVELOPE COMPLIANCE D PREVIOUS ENVELOPE PERMIT D ENVELOPE COMPLIANCE ATTACHED
STATEMENT OF COMPLIANCE
This Certificate of Compliance lists the building features and performance specifications needed to comply with Title 24,
Parts 1 and 6 of the California Code of Regulations. This certificate applies only to building mechanical requirements.
The documentation preparer hereby certifies that the documentation is accurate and complete.
DOCUMENTATION AUTHOR
/SIG~~~ /DAT~;~~) T.L. Harmon J
, .,,. .I The Principal Mechanical Designer hereby certifies that the proposed building design represented in this set of construction, "
documents is consistent with the other compliance forms and worksheets, with the specifications, and with any other
calculations submitted with this permit application. The proposed building has been designed to meet the mechanical
requirements contained in Sections 110 through115, 120 through 124, 140 through 142,144 and 145.
Please check one:
D I hereby affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code to sign this
document as the person responsible for its preparation; and that I am licensed in the State of California as a civil engineer, or
mechanical engineer or I am a licensed architect. D I affirm that I am eligible under the exemption to Division 3 of the Business and Professions Code by Section 5537.2 or
6737.3 to sign this document as the person responsible for its preparation; and that I am a
licensed contractor performing this work.
D I affirm that I am eligible under the exemption to Division 3 of the Business and Professions Code to sign this document
because it pertains to a structure or type of work described pursuant to Business and Professions Code sections 5537, 5538,
and 6737.1. -
PRINCIPAL MECHANICAL DESIGNER· NAME J.,siGlif""~-
Greater San Dieao Air Conditionina Co. ---./.1 IDAl/t_f/os-JLIC.# V 37 !5
MECHANICAL MANDAT&RY MEASURES t I
Indicate location on plans of Note Block for Mandatory Measures I I
INSTRUCTIONS TO APPLICANT
For detailed instructions on the use of this and all Energy Efficiency Standards compliance forms, please refer to the
Nonresidential Manual published by the California Energy Commission.
MECH-1: Required on plans for all submittals. Parts 2 may be incorporated in schedules on plans.
MECH-2: Required for all submittals, but may be incorporated in schedules on plans.
MECH-3: Required for all submittals unless required outdoor ventilation rates and airflows are shown on plans per Section 4.3.4.
MECH-4: Required for Prescriptive submittals.
MECH-5: Optional. Performance use only for mechanical distribution summarv.
EnergyPro 3.1 By EnergySoft User Number: 6272 Job Number: Page:1 of 19
'ti. ,
18 05 10:3Sa
designcorp
FACSIMILE TRANSMITTAL SHEET
TO: FROM:
Stephen Brindley AmyTobia
COl\,ll'ANY: DATT:'.:
Pacific Building Group 9/16/05
F,\X NUMBER:
760-607-4286
TOTAL NO. OF PAGES !NCLUDING COVER:
2
PHONE NUt.ffiER: PROJECT#:
RE: PROJECT NAMn:
Building Inspector Kitchen Use Inquiry GoodSow:ce TI
@°URGENT fi2f PORREV!E\XI D PLEASE COMMENT 0 PLEASE. RBPL Y D FOR APPROVAL
Please see the attached printout of the country sUilldard for health department inspections on a project
Based on the definition of what our client is doing, we believed they do not require an inspection.
Goodsource is a food wholesaler. They purchase and distribute food -mostly frozen -to large institutional
clients. The storage and test kitchen in their corporate headquarters has space to only to allow for the
verification of product quality through random sampling. Food is not prepared for sale or mass
consumption.
A food establishment is defined by code CURFFL Section 11370 as a place where "unpackaged" food
items are prepared for consumption. All products stored and tested in the GoodSource test kitchen are
pre-packaged and require only reheating for sample testing. ·
Based on these facts, we feel the test kitchen in the GoodSource Corporate Offices do not requite an
inspection.
Please feel free to contact Designco.tp if additional information is needed,
AmyTobia
Sr.Designer,Designco.tp
444 SOUTH CEDROS AVENUE, STUDIO 175, SOLANA BEACH, CALIFORNIA 92075
PHONE: (858) 794-3222, l'AX: (858) 794-3220, EMAIL: A1'QRTA@DE$IGNC:ORPSD CQM
p. 1