HomeMy WebLinkAbout1525 Faraday Ave; 200; CBC2018-0013; Permit(city of
Carlsbad
Commercial Permit
Print Date: 05/31/2018 Permit No: CBC2018-0013
Job Address:
Permit Type:
Parcel No:
Valuation:
Occupancy Group:
# Dwelling Units:
Bedrooms:
1525 Faraday Ave, 200
BLDG-Commercial
2121302700
$139,530.00
Work Class:
Lot#:
Reference#:
Construction Type:
Bathrooms:
Orig. Plan Check#:
Tenant Improvement Status:
Applied:
Issued:
Permit
Finaled:
Inspector:
Closed -Finaled
01/12/2018
03/08/2018
MColl
Plan Check#:
Final
Inspection: 5/31/2018 9:21:17AM
Project Title:
Description: HUB INTERNATIONAL: 3,000 SF T.I. OFFICE TO OFFICE
Applicant: Owner: Contractor:
JOSE RODRIGUEZ EMERALD LAKE CORPORATION CENTRE LP JACOR CONSTRUCTION INC
858-794-3222
1525 Faraday Ave
CARLSBAD, CA 92D08
10612 Prospect Ave, Suite 101
Santee, CA 92071-8500
619-562-8183
BUILDING PERMIT FEE ($2000+)
BUILDING PLAN CHECK FEE (BLDG)
ELECTRICAL BLDG COMMERCIAL NEW/ADDITION/REMODEL
MECHANICAL BLDG COMMERCIAL NEW/ADDITION/REMODEL
PLUMBING BLDG COMMERCIAL NEW/ADDITION/REMODEL
561473 GREEN BUILDING STATE STANDARDS FEE
STRONG MOTION-COMMERCIAL
Total Fees: $1,580.67 Total Payments To Date: $1,580.67 Balance Due:
Please take NOTICE that approval of your project includes the "Imposition" of fees, dedications, reservations, or other exactions hereafter
collectively referred to as "fees/exaction." You have 90 days from the date this permit was issued to protest imposition of these
fees/exactions. If you protest them, you must follow the protest procedures set forth in Government Code Section 66020(a), and file the
protest and any other required information with the City Manager for processing in accordance with Carlsbad Municipal Code Section
3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack, review, set aside, void, or annul their
imposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection
fees and capacity changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this
project. NOR DOES 1T APPLY to any fees/exactions of which you have previously been given a NOTICE similar to this, or as to which the
statute of limitation has previously otherwise expired.
$0.00
1635 Faraday Avenue, Carlsbad, CA 92008-7314 I 760-602-2700 I 760-602-8560 f I www.carlsbadca.gov
$768.00
$537.60
$89.DO
$55.00
$86.00
$6.00
$39.07
\
,;:-HE FOLLOWING APPROVALS REQUIRED PRIOR TO PERMIT ISSUANCE: 0PLANNING 0ENGINEERING
#~, "\\ 4· ,
~-CITY OF
CARLSBAD
Building Permit Application
1635 Faraday Ave., Carlsbad, CA 92008
Ph: 760-602-2719 Fax: 760-602-8558
email: building@carlsbadca.gov
www.carlsbadca.gov
surr&•/SPACE./UNITf JOB ADDRESS 1525 Faraday Ave Carlsbad, CA 92107
0BUILD1NG OFIRE
Plan Check No.
Est. Value
Plan Ck. Deposit
Date SWPPP
APN
200 212 130 27 00
CT/PROJECT# LOT# PHASE# # OF UNITS # BEDROOMS # BATHROOMS CONSTR. TYPE OCC. GROUP
102 0 0 0 VB B
DESCRIPl'ION OF WORK: Include Square Feet of Aff'ected Area(s)
Tenant improvement in existing office building. Removal of walls and finish flooring. Construction of new walls, lighting, power, and ductwork only to serve remodeled
EXlSTING USE
APPLICANT NAME
Prlm1ry Contact
ADDRESS
CITY
Office
San Die110
PHONE
areas. No structural, plumbing or HVAC equipment.
Approximately 3,000 sq. ft. of affected area in approximately 11,362 usable sq. ft. of office space.
PROPOSED USE GARAGE (SF) PATIOS (SF) DECKS (SF) FIREPLACE AIR CONDITIONING
Office 0 0 YESQ No[ZJ YESIZJNoO
Designcorp • Jose Rodriguez PROPERTY OWNER Jeffry Brusseau -
ADDRESS 4944 Collingwood Drive 1525 Faraday Ave Suite 100
STATE ZIP CITY STATE ZIP
CA 92109 Carlsbad CA 92008
FAX PHONE FAX
858-794-3222x305 858-490-0364 760-607 -4282 X 103 760-607 -4286
EMAIL EMAIL
jrodriguez@ldesigncorpsd.com
DESIGN PROFESSIONAL Designcorp • Christine Jordan
ADDRESS 4944 Collingwood Drive
CITY STATE ZIP
San Dieao CA 92109
PHONE FAX
858-794-3222 X 308 858-490-0364
EMAIL
cjordan@ldesigncorpsd.com
STATE UC.#
3850
(Sec. 7031.5 Business and Professions Code: Any City or County which requires a permit to construct, alter, Improve, demolish or repair an)'. structure, prior to its issuance, also requires the
applicant for such permit to file a signed statement ttlat he Is licensed pursuant to the provisions of the Contractor's License Law JChapter 9, commending with Section 7000 of Div1s1on 3 of the Business and Professions Code} or that he Is exempt therefrom, and the basis for the alleged exemption. Any violation of Section 031.5 by any applicant for a permit subjects the applicant to a
civil penalty of not more than five hundred dollars {$500}).
WORKERS' COMPENSATION
Workers' Compensation Declaration: I hereby affirm under penally of pe,jury one of the following declarations:
B I have 1nd will malntlln a certificate of consent to 1elf.ln1ur1 for 'Mlrkers' compensation as provided by Section 3700 of the Labor Code, for the performance of the work for which this permit Is issued.
I have 1nd will malntlln workers' compensation, as reQUired bv Section 3700 of the Labor Code, for the performance of the work for which this permit is issued. My workers' compensation i[rar carrier and policy
numbefare:lnsuraoceeol~SIJ~'i Cctt.Q""1,X of'~ PoloyNo'#,.)$0'50'ZZ.1'2..'3 ExpralonDate \.0 \ \I!',
~section need not be completed If the permit is for one hundrad dollars ($100) or less. ~,; LJ Certificate of Exemption: I certify that in the performance of the work for which this permit is issued, I shall not employ any person in any manner so as to become subject to the Workers' Compensation Laws of
Gallfomla. WARNING: F1llur1 to secure pen11tlon cove111ge 11 unlawful, ind shall subject 1n employer to crlmlnal penalties ind clvll fines up to one hundred thouund dollars (&100,000), In
addition to the cost of compenutl rovlded for In Section 3706 otthe Labor code, Interest and attorney's fees.
8$ CONTRACTOR SIGNATURE
I hereby affirm that I am exempt from Contractor's License Law for the following reason: O I, as owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not Intended or offered for sale (Sec. 7044, Business and Professions Code: The Contractor's
license Law does not apply to an owner of property who builds or improves thereon, and who does sll'.:h work himself or through his own employees, provided that such improvements are not intended or offered for
sale. tt, however, the building or improvement is sold within one year of completion, the owner-builder will have the burden of proving that he did not build or improve for the purJX)se of sale).
D
D
I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions Code: The Contractor's license Law does not apply to an owner of
property who builds or improves thereon, and con~ for such projects with contractor(s) licensed pursuant to the Contractor's license Law).
I am exempt under Section Business and Professions Code for this reason:
1. I personally plan to provide the major labor and materials for construction of the proposed property improvement. Oves Do
2. I (have I have not) signed an application for a building permit for the proposed work.
3. I have contracted with the following person (firm) to provide the proposed construction (include name address I phone I contractors' license number):
4. I plan to provide portions of the work, but I have hired the following person to coordinate, supervise and provide the mapr worll (include name I address I phone I contractors' license number):
5. r will provide some of the work, but I have contracted (hired) the following persons to provide the worll indicated (include name I address I phone I type of worll):
6$ PROPERTY OWNER SIGNATURE 0AGENT DATE
'•
COMPLETE THIS SECTION FOR NON-RliSfDENTIAL BUILDING PERMITS ONLY ,
Is the applicant or future building occupant required to submit a business plan, acutely hazardous materials registration form or risk management and prevention program under Sections 25505, 25533 or 25534 of the
Presley-Tanner Hazardous Substance Account Act? Yes I No
Is the applicant or future blilding occupant required to obtain a pennit from the air pollution conlrol district or air Quality management dislrict? Yes I No
Is the facility to be consb'ucted 'Mlhin 1,COO feet of the outer boundary of a school site? Yes ./ No
IF ANY OF THE ANSWERS ARE YES, A ANAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR IS MEETING THE REQUIREMENTS OF THE OFFICE OF
EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT.
I cenlfy that I have read the application and state that the above Information Is oo11'8Ctand that the information on the plans Is ao::uate. I agme to oomplyYtffll all Clfy ordinances and State 1aM ielatlngto building construction.
I hereby-representative of the c~ of Qrlsbad toen\erUiXJO lhe above menooned property !Jr inspection purposes. I ALSO AGREE TO SAVE, INDEMNIFY AND KEEP HARMLESS THE CITY Cl' CARLS8'\D
AG'-INST ALL UMllllTIES, JUDGMENTS, COSTS AND EXPENSES WHICH MAY IN ANY WAY ACCRUE AGAINST SAID CITY IN COOSEC!JENCE Cl' THE GRANTING Cl' THIS PERMrT.
OSHA: AA OSHA pennlt is ra<Jlired for excavations over 5' deep and demolioon or conslnK:oon of structures over 3 stories il heght.
EXARA TION: E"'~ pennl osued by the Bul:li · · · s of tho Code shall expire by onltation and beoolre null and voo I the bui~ing or v.oik aulhorized by sud1 pem;t • not oommenced .;ii,.,
100days ftom Ille date of sudl · · ildilg or such permit is suspended or abandoned at any time after the v.ork is oommenced b' ape · of 100days ( · 100.4.4 Unibm Building Code).
DATE
• STOP: THIS SECTION NOT REQUIRED FOR BUILDING PERMIT ISSUANCE.
Complete the following ONLY if a Certificate of Occupancy will be requeated at final inspection.
Fax (760) 602<1560, Email building@carlsbadca.gov or Mail the completed fonn to City of Garlsbad, Building Di~sion 1635 Faraday Avenue, Carlsbad, California 92006.
CO#: (Office Use Only)
CONTACT NAME OCCUPANT NAME
ADDRESS BUILDING ADDRESS
CITY STATE ZIP CITY STATE
Carlsbad CA
PHONE FAX
EMAIL OCCUPANT'S BUS. LIC. No.
DELMRY OPTIONS
PICK UP: CONTACT (Listed above) OCCUPANT (Listed abOve)
CONTRACTOR (On Pg. 1)
MAIL TO: CONTACT (LISted above)
CONTRACTOR (On Pg. 1)
OCCUPANT (Listed abOve)
MAIL/FAXTOOTHER:~~~~~~~~~~~~~~~~
AS APPLICANT'S SIGNATURE
NO CHANGE IN USE/ NO CONSTRUCTION
CHANGE OF USE/ NO CONSTRUCTION
DATE
ZIP
Pcrinit Type: BLDG-Commercial Application Date: 01/12/2018 Owner:
Work Class: Tenant Improvement Issue Date: 03/08/2018 Subdivision:
Status: Closed -Finaled Expiration Date: 10/29/2018 Address:
IVR Number: 8877
Scheduled
Date
Actual
Start Date Inspection Type Inspection No. Inspection Status Primary Inspector
05/30/2018 05/3012018
05/3112018 05/31/2018
May 31, 2018
BLDG-Fire Final 059061-2018
BLDG-Final
Inspection
Checklist Item
FIRE-Building Final
059556-2018
Checklist Item
BLDG-Building Deficiency
BLDG-Electrical Final
BLDG-Building Deficiency
BLOG-Plumbing Final
BLDG-Mechanical Final
BLDG-Electrical Final
Passed Dominic Fieri
COMMENTS
Passed Michael Collins
COMMENTS
EM/exit signage lighting ok
Complete EM lighting. Ok to set up IT.
EMERALD LAKE CORPORATION
CENTRE LP
CARLSBAD. TCT#85-24 UNIT#05
1525 Faraday Ave, 200
Carlsbad, CA 92008-7374
Re inspection
Passed
Yes
Passed
Yes
Yes
No
No
No
No
Complete
Complete
Complete
Page 3 of 3
%!{", ,,»~. ' ' ,} 00\}P\'
' , t (1 f ,;;; , c " e ;, PERMIT INSPECTi<:>N HISTORY REPORT (CBC2018-0013) ·
' . .
Pcnnit Typo: BLDG-Commercial Application Date: 01/12/2018 Owner:
Work Class: Tenant Improvement lssuo Date: 03/08/2018 Subdivision:
Status: Closed -Finaled El<piration Date: 10/29/2018 Address:
IVR Number: 8877
Scheduled Actual
Date Start Date Inspection Type Inspection No. Inspection Status Primary Inspector
_,, _______
03/29/2018 03/28/2018 BLDG-24 053013-2018 Failed Michael Collins
Rough/Topout
Checklist Item
BLDG-Building Deficiency
03/30/2018 03/30/2018 BLDG-24 053252-2018
RoughfTopout
Checklist ltc1n
BLDG-Building Deficiency
BLDG-Building Deficiency
04/03/2018 04/03/2018 BLDG-84 Rough 053719-2018
Combo(14,24,34,44)
Checklist lte1n
BLDG-Building Deficiency
BLDG-14
Frame-Steel-Bolting-Welding
(Decks)
BLDG-34 Rough Electrical
04/05/2018 04/05/2018 BLDG-84 Rough 053986-2018
Combo(14,24,34,44)
Checklist ltcrn
BLDG-Building Deficiency
BLDG-14
Frame-Steel-Bolting-Welding
(Decks)
BLDG-34 Rough Electrical
BLDG-Building Deficiency
BLDG-14
Frame-Steel-Bolting-Welding
(Decks)
BLDG-34 Rough Electrical
04/12/2018 04/12/2018 BLDG-17 Interior 054784-2018
Lath/Drywall
Checklist Item
BLDG-Building Deficiency
04/1612018 04/16/2018 BLDG-44 054561-2018
Rough/Ducts/Dampe
rs
Checklist Item
BLDG-Building Deficiency
04/24/2018 04/24/2018 BLDG-34 Rough 055835-2018
Electrical
----·----· May 31, 2018
COMMENTS
Not ready, no test
Passed Michael Collins
COMMENTS
Waste/vent & water supply, see card.
Not ready, no test
Partial Pass Michael Collins
COMMENTS
Rm's 214-215,222-227 only.
Passed Michael Collins
COMMENTS
Rm's 207-212,216-220,229,231-233
Rm's 214-215,222~227 only.
Passed Michael Collins
COMMENTS
Walls only
Passed Chris Renfro
COMMENTS
Failed Michael Colllns
EMERALD LAKE CORPORATION
CENTRE LP
CARLSBAD TCT#85-24 UNIT#05
1525 Faraday Ave, 200
Carlsbad, CA 92008-7374
Reinspection Complete
Reinspection Complete
Passed
No
Complete
Passed
Yes
No
Reinspection Incomplete
Passed
Yes
Yes
Yes
Complete
Passed
Yes
Yes
Yes
Yes
Yes
Yes
Complete
Passed
Yes
Complete
Passed
Yes
Reinspection Complete
Page 1 of 3
Perrnit Ty pc:
Work Class:
Stntus:
Scheduled
Date
04/26/2018
05/01/2018
05/23/2018
05/24/2018
05129/2018
---··--May 31, 2018
BLDG-Commercial Application Date: 01/1212018 Owner:
Tenant Improvement Issue Date: 0310812018 Subdivision:
Closed -Finaled Expiration Date: 10/2912018 Address:
Actual
Start Date
04/26/2018
05/01/2018
05/23/2018
05/24/2018
05/29/2018
IVR Number: 8877
Inspection Type Inspection No.
Checklist Item
BLOG-Building Deficiency
BLDG-85 T-Bar, 056174-2018
Ceiling Grids,
Overhead
Checklist Item
BLDG-Building Deficiency
BLOG-85 T-Bar, 056687-2018
Celllng Grids,
Overhead
Checklist Item
BLDG-Building Deficiency
BLDG-Building Deficiency
BLOG-44
Rough-Ducts-Dampers
BLDG-14
Frame-Steel-Bolting-Welding
(Decks)
BLDG-34 Rough Electrical
BLDG-Flnal 058832-2018
Inspection
Checklist ltetn
BLDG-Building Deficiency
BLDG-Plumbing Final
BLDG-Mechanical Final
BLDG-Structural Final
BLOG-Electrical Final
BLDG-Final 059012-2018
Inspection
Checklist Item
BLDG-Building Deficiency
BLOG-Plumbing Final
BLDG-Mechanical Final
BLDG-Electrical Final
BLDG-Final 059294-2018
Inspection
Checklist Item
BLDG-Building Deficiency
BLDG-Building Deficiency
BLDG-Plumbing Final
BLOG-Mechanical Final
BLDG-Structural Final
BLDG-Electrical Final
Inspection Status Primary Inspector
----·-----·
COMMENTS
Not ready
Fa lied Michael Collins
COMMENTS
Not ready and no Fire Dept. approval.
Passed Michael Collins
COMMENTS
Not ready and no Fire Dept. approval.
Failed Mlchael Colllns
COMMENTS
See card
Partial Pass Michael Collins
COMMENTS
Complete EM lighting. Ok to set up IT.
Failed Michael Collins
COMMENTS
05/29/18, complete EM/exit lighting
See card
EMERALD LAKE CORPORATION
CENTRE LP
CARLSBAD TCT#85-24 UNIT#05
1525 Faraday Ave, 200
Carlsbad, CA 92008-7374
Reinspection
Passed
No
Reinspection
Passed
No
Passed
No
Yes
Yes
Yes
Yes
Reinspection
Passed
No
No
No
No
No
Reinspection
Passed
No
No
No
No
Reinspection
Passed
No
No
No
No
No
No
Complete
Complete
Complete
Complete
Incomplete
Complete
Page 2 of 3
v.: EsG1I
DATE: 02/08/2018
JURISDICTION: Carlsbad
PLAN CHECK#.: CBC2018-0013
PROJECT ADDRESS: 1525 Faraday Ave.#200
SET II
PROJECT NAME: Hub International Tenant Improvement
0 APPLICANT
~RIS
[:8J The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's
codes when minor deficiencies identified below are resolved and checked by building
department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
D The check list transmitted herewith is for your information. The plans are being held at EsGil
until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
D The applicant's copy of the check list has been sent to:
[:8J EsGil staff did not advise the applicant that the plan check has been completed.
D EsGil staff did advise the applicant that the plan check has been completed.
Person contacte.~d.i.·~--Telephone#:
Date contacted: (Wl Email:
Mail Telephone Fax In Person
D REMARKS:
By: Dwight Ashman (For J.P.)
EsGil
01/30/2018
Enclosures:
9320 Chesapeake Drive, Suite 208 + San Diego, California 92123 + (858) 560-1468 + Fax (858) 560-1576
DATE: 1/23/2018
JURISDICTION: Carlsbad
PLAN CHECK#.: CBC2018-0013
~ EsG1I
A S.f\FEhc1lt Company
SETI
PROJECT ADDRESS: 1525 Faraday Ave.#200
PROJECT NAME: Hub International Tenant Improvement
~ ~LICANT
~URIS
D The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's
codes when minor deficiencies identified below are resolved and checked by building
department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
~ The check list transmitted herewith is for your information. The plans are being held at EsGil
until corrected plans are submitted for recheck.
0 The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
~ The applicant's copy of the check list has been sent to:
Jose Rodriguez
0 EsGil staff did not advise the applicant that the plan check has been completed.
~ EsGil staff did advise the applicant that the plan check has been completed.
Person contacted: Jose Rodriguez Telephone#: 858-794-3222 x 305
_.L!Jate ci:n cted:) ,~ (by:YD Email: jrodriguez@designcorpsd.com
~ Mail Vphone"\ Fax In Person
D REMAR : ,((\.
By: Jason Pasiut
EsGil
1/17/2018
Enclosures:
9320 Chesapeake Drive, Suite 208 + San Diego, California 92123 + (858) 560-1468 + Fax (858) 560-1576
Carlsbad CBC2018-0013
1/23/2018
PLAN REVIEW CORRECTION LIST
TENANT IMPROVEMENTS
PLAN CHECK#.: CBC2018-0013
OCCUPANCY: B
TYPE OF CONSTRUCTION: V-B
ALLOWABLE FLOOR AREA: within
SPRINKLERS?: YES
REMARKS:
DATE PLANS RECEIVED BY
JURISDICTION: 1/12/2018
DATE INITIAL PLAN REVIEW
COMPLETED: 1/23/2018
FOREWORD (PLEASE READ):
JURISDICTION: Carlsbad
USE: Office
ACTUAL AREA: 3,000s.f.
STORIES: 3
HEIGHT: unchanged
OCCUPANT LOAD: 148
DATE PLANS RECEIVED BY
ESGIL CORPORATION: 1/17/2018
PLAN REVIEWER: Jason Pasiut
This plan review is limited to the technical requirements contained in the California version of
the International Building Code, Uniform Plumbing Code, Uniform Mechanical Code, National
Electrical Code and state laws regulating energy conservation, noise attenuation and access for
the disabled. This plan review is based on regulations enforced by the Building Department.
You may have other corrections based on laws and ordinances enforced by the Planning
Department, Engineering Department, Fire Department or other departments. Clearance from
those departments may be required prior to the issuance of a building permit.
Code sections cited are based on the 2016 CBC, which adopts the 2015 IBC.
The following items listed need clarification, modification or change. All items must be satisfied
before the plans will be in conformance with the cited codes and regulations. Per Sec. 105.4 of
the 2015 International Building Code, the approval of the plans does not permit the violation of
any state, county or city law.
To speed up the recheck process, please note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet number, specification section, etc.
Be sure to enclose the marked up list when you submit the revised plans.
Carlsbad CBC2018-0013
1/23/2018
Please make all corrections, as requested in the correction list. Submit FOUR new
complete sets of plans for commercial/industrial projects (THREE sets of plans for
residential projects). For expeditious processing, corrected sets can be submitted in one
of two ways:
1. Deliver all corrected sets of plans and calculations/reports directly to the City of
Carlsbad Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760) 602-
2700. The City will route the plans to EsGil Corporation and the Carlsbad Planning,
Engineering and Fire Departments.
2. Bring TWO corrected set of plans and calculations/reports to EsGil Corporation, 9320
Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-1468. Deliver all
remaining sets of plans and calculations/reports directly to the City of Carlsbad Building
Department for routing to their Planning, Engineering and Fire Departments.
NOTE: Plans that are submitted directly to EsGil Corporation only will not be reviewed by
the City Planning, Engineering and Fire Departments until review by EsGil Corporation is
complete.
• PLANS
1. Please re-arrange sheets to match the index. The Electrical and Mechanical
sheets are reversed.
2. Please revise the occupant load for the following rooms on sheet T2:
a) Conference room 202 to 33. The occupant load factor for the conference
room is 15.
b) Conference room 221 to 13.
c) Collaboration room 242 to 15.
d) The total occupant load calculates to 209. This does not change the
egress requirements.
3. Please correct the following sheets I notes:
a) Sheet TS sanitary facilities note 1 to state 44". 118-403.5.1 (5).
b) Sheet TS water closet II to state 51bs. 11 8-309.
c) Sheet TS doors and hardware note b. to state 34" and 44". 11 B-404.2. 7.
d) Update the occupant load calculations on sheet T2.
e) Required egress door width to be 209 x .15 = 31.35"
f) Stairway egress door width required to be 209 x .20 = 41.80"
g) Sheet Tl-1.1 Green Building Requirements recycling to be 65%.
Carlsbad CBC2018-0013
1/23/2018
h) Sheet Tl-3 General mechanical note 2 to state CEC 120.1.b.1.
• PARTITIONS AND GLAZING
4. Please clarify with greater detail what the existing glazing is at conference room
202 by labeling it E as the other windows are labeled. Is the glazing tempered?
5. Please provide the proposal for corner connections and header construction for
the new interior partitions.
6. Provide a note on the plans stating: "Penetrations of fire walls shall be protected
with through-penetration fire stops and membrane-penetration fire stops in
accordance with IBC Section 714."
• PLUMBING
7. Please provide plumbing isometric drawings showing new water and waste/ vent
pipes being installed for water lines to new refrigerators and for the new sink in
copy room 203. Show vent pipe size, clean-outs,
• MECHANICAL
8. Please provide proposal for achieving the required .50 cfm per s.f. minimum
exhaust rate for the copy rooms. CMC Table 403.7.
9. When new rooms or spaces are constructed and the existing mechanical system
is not to be altered other than relocation of existing duct work; please note or
show mechanical ventilation will be provided capable of supplying the minimum
rate of outside air required per minute per occupant as shown in Table 402.1 of
the CMC.
10. Please show how the altered duct system meets the requirements of 2016
Building Energy Efficiency Standards section 141(b) 2 D. (Altered duct systems
that meet the requirements of 140.4 (I) 1,2, and 3 shall be sealed as confirmed
through field verification and diagnostic testing that meets either 141(b) 2 Di or
ii).
• ACCESSIBILITY FOR REMODELS, ADDITIONS, AND REPAIRS
The following disabled access items are taken from the 2016 edition of California Building
Code. Per Section 1.9.1.2, all privately funded public accommodations and commercial
facilities shall be accessible to persons with disabilities.
Where existing elements or spaces are altered, each altered element or space shall
comply with applicable requirements of Division 2, including CBC section 11 B-202.4. CBC
section 11 B-202.4 states that when alterations or additions are made to existing buildings,
Carlsbad CBC2018-0013
1/23/2018
an accessible path of travel to the specific area of alteration shall be provided. See
exceptions to 11 B-202 .4.
Detail on the plans the following elements of the existing path of travel that are required
to comply with the 2016 accessibility standards:
11. Existing signage at parking stall, building entrance, route to accessible features
and the accessible features themselves:
a) Existing accessible parking signs per 11 B-502.8 for unauthorized vehicle
parking.
b) Show the location of the proposed tactile exit signs per CBC 1013.4.
• END OF REVIEW
To speed up the review process, please note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet, note or detail number, calculation
page, etc.
Please indicate here if any changes have been made to the plans that are not a result
of corrections from this list. If there are other changes, please briefly describe them
and where they are located in the plans.
Have changes been made to the plans not resulting from this correction list?
Please indicate: D Yes D No
The jurisdiction has contracted with Esgil Corporation located at 9320 Chesapeake
Drive, Suite 208, San Diego, California 92123; telephone number of 858/560-1468, to
perform the plan review for your project. If you have any questions regarding these plan
review items, please contact Jason Pasiut at Esgil Corporation. Thank you.
Carlsbad CBC2018-0013
1/23/2018
[DO NOT PAY -THIS IS NOT AN INVOICE]
VALUATION AND PLAN CHECK FEE
JURISDICTION: Carlsbad PLAN CHECK#.: CBC2018-0013
PREPARED BY: Jason Pasiut DATE: 1/23/2018
BUILDING ADDRESS: 1525 Faraday Ave.#200
BUILDING OCCUPANCY: B
BUILDING AREA Valuation
PORTION ( Sq. Ft.) Multiplier
3000 46.51
Air Conditioning
Fire Sprinklers
TOTAL VALUE
Jurisdiction Code cb By Ordinance
1997 UBC Building Permit Fee
-,
1997 UBC Plan Check Fee .... 1
Type of Review: [2J Complete Review
0 Repetitive Fee ~1 Repeats
Comments:
D Other
D Hourly
EsGil Fee
Reg. VALUE
Mod.
D Structural Only
1------11 Hr. @ •
($)
139,530
139,530
$768.061
$499.241
$437.791
Sheet 1 of 1
I~ • SAN DIEGO REGIONAL
HAZARDOUS MATERIALS
QUESTIONNAIRE
RECORDID#~~~~~~~~~~.,-.....::::.(,.;:o..,4-~~-I
PLANCHECK#~~~~~~...-~-"''1,4,1-,:~..:...J1£Jt;!,..J
Malling Address City State
Same as above
Project Contact Applicant E-mail Telephone#
Jose Rodri uez ·rodri uez desi ncor sd.com 858-794-3222
The following questions represent the faclllty's actlv ties, NOT the specific project description.
PART I: FIRE DEPARJMENT -l'I\ZARDOUS MATERIALS DIVISION: OCCUPANCY CLJ\SSIFICATION: (not required for proiects within the City of San
Q!!.as!l: Indicate by circling the item, whether your business will use, process, or store any of the following hazardous materials. If any of the items are circled,
applicant must contact the Fire Protection Agency with jurisdiction prior to plan submittal.
Occupancy Rating: Faclltty's Square Footage (including proposed project):
1. Explosive or Blasting Agents 5. Organic Peroxides 9. Water Reactives 13. Corrosives
2. Compressed Gases 6. Oxidizers 10. Cryogenics 14. Other Health Hazards
3. Flammable/Combustible Liquids 7. Pyrophorics 11. Highly Toxic or Toxic Materials 15. None of These.
4. Flammable Solids 8. Unstable Reactives 12. Radioactives
PART 11: SAN DIEGO COUNTY DEPARTMENT OF ENVIRONMENTAL HEI\LTH -HAZARDOUS MATERIALS DIVISION (HMDl: If the answer to any of the
questions is yes, applicant must contact the County of San Diego Hazardous Materials Division, 5500 Overland Avenue, Suite 110, San Diego, CA 92123.
Call (858) 505-6700 prior to the issuance of a building permit. 0 CalARP Exempt
I
FEES ARE REQUIRED Project Completion Date: Expected Date of Occupancy:
1.
2.
3.
4.
5.
6.
7.
8.
YES NO
§ I
D D D D D I
(for new construction or remodeling projects)
Is your business listed on the reverse side of this forrn? (check all that apply).
Will your business dispose of Hazardous Substances or Medical Waste in any amount?
Will your business store or handle Hazardous Substances in quantities greater than or equal to 55 gallons, 500
pounds and/or 200 cubic feet?
Will your business store or handle carcinogens/reproductive toxins in any quantity?
Will your business use an existing or install an underground storage tank?
Will your business store or handle Regulated Substances (CalARP)?
Will your business use or install a Hazardous Waste Tank System (Title 22, Article 10)?
Will your business store petroleum in tanks or containers at your facility with a total facility storage capacity equal to
or realer than 1,320 allons? California's Above round Petroleum Stora e Act .
Date lnltlals
D CalARP Required
I
Date Initials
D CalARP Complete
Date Initials
PART 111: SAN DIEGO COUNTY AIR POLLUTION CONTROL DISTRICT (APCDl: Any YES" answer requires a stamp from APCD 10124 Old Grove Road, San
Diego, CA 92131 apcdcomp@sdcounty.ca.gov (858) 586-2650). rNo stamp required If Q1 Yes s!!ll! Q3 Yes and Q4-Q6 No]. The following questions are intended
to identify the majority of air pollution issues at the planning stage. Projects may require additional measures not identified by these questions. For comprehensive
requirements contact APCD. Residences are typically exempt, except -those with more than one building• on the property; single buildings with more than four
dwelling units; townhomes; condos; mixed-commercial use; deliberate bums; residences forrning part of a larger project. rExcludes garages & small outbuildings.]
1.
2.
3.
YES NO
§ I Will the project disturb 160 square feet or more of existing building materials?
Will any load supporting structural members be removed? Notification may be required 10 working days prior to commencing demolition.
(ANSWER ONLY IF QUESTION 1 or 2 IS YES) Has an asbestos suivey been performed by a Certified Asbestos Consultant or Site Surveillance
Technician?
4. D (ANSWER ONLY IF QUESTION 3 IS YES) Based on the survey results, will the project disturb any asbestos containing material? Notification
may be required 10 working days prior to commencing asbestos removal.
5. D
D
ltJ Will the project or associated construction equipment emit air contaminants? See the reverse side of this form or APCD factsheet
(www.sdapcd.org/info/facts/perrnits.pdf) for typical equipment requiring an APCD permit.
~ (ANSWER ONLY IF QUESTION 5 IS YES) Will the project or associated construction equipment be located within 1,000 feet of a school 6.
boundarv
Briefly describe business activities: Office
Briefly describe proposed project: ·-HUB International -Suite 200
I dedare under penalty of perjury that to the best of my knowledge and belief s made herein are true and correct. ot /2 I ,,----·/ ~r I
Name of Owner or Authorized Aaent -=inn"'"""" nl 'wner-or Authorized Aaent Date
FOR OFFICl'J r1JSE ONLY: FIRE DEPARTMENT OCCUPANCY CLASSIFICATION:
BY: J DATE: I I
EXEMPT OR NO FURTHER INFORMATION REQUIRED RELEASED FOR BUILDING PERMIT BUT NOT FOR OCCUPANCY RELEASED FOR OCCUPANCY
COUNTY-HMO* APCD COUNTY-HMO APCD COUNTY-HMO APCO
IB
. . . A stamp m this box 2n!Y exempts businesses from completing or updating a Hazardous Matenals Business Plan. Other permitting requirements may still apply .
HM-9171 (08/15) County of San Diego-DEH -Hazardous Materials Division
LIST OF BUSINESSES WHICH REQUIRE REVIEW AND APPROVAL FROM THE COUNTY OF SAN DIEGO
DEPARTMENT OF ENVIRONMENTAL HEALTH -HAZARDOUS MATERIALS DIVISION
Check all that apply:
AUTOMOTIVE
D Battery Manufacturing/Recycling
0 Boat Yard
D Car Wash
D Dealership Maintenance/Painting
D Machine Shop
D Painting
D Radiator Shop
D Rental Yard Equipment
D Repair/Preventive Maintenance
0 Spray Booth
D Transportation Services
D Wrecking/Recycling
CHEMICAL HANDLING
D Agricultural supplier/distributor
D Chemical Manufacturer
D Chemical Supplier/Distributor
D Coatings/Adhesive
D Compressed Gas Supplier/Distributor
D Dry Cleaning
D Fiberglass/Resin Application
D Gas Station
D Industrial Laundry
0 Laboratory
D Laboratory Supplier/Distributor
0 Oil and Fuel Bulk Supply
D Pesticide Operator/Distributor
CHEMICAL HANDLING
D Photographic Processing
D Pool Supplies/Maintenance
D Printing/Blue Printing
D Road Coatings
D Swimming Pool
D Toxic Gas Handler
D Toxic Gas Manufacturer
METAL WORKING
D Anodizing
D Chemical Milling/Etching
D Finish.Coating/Painting
D Flame Spraying
0 Foundry
D Machine Shop·Drilling/Lathes/Mills
D Metal Plating
D Metal Prepping/Chemical Coating
D Precious Metal Recovery
D Sand Blasting/Grinding
D Steel Fabricator
D Wrought Iron Manufacturing
AEROSPACE
D Aerospace Industry
D Aircraft Maintenance
D Aircraft Manufacturing
OTHERS AND MISCELLANEOUS
0 Asphalt Plant
D Biotechnology/Research
D Chiropractic Office
D Co·Generation Plant
D Dental Clinic/Office
D Dialysis Center
D Emergency Generator
D Frozen Food Processing Facility
D Hazardous Waste Hauler
D Hospital/Convalescent Home
D Laboratory/Biological Lab
0 Medical Cllnlc/Office
D Nitrous Oxide (NOK) Control System
D Phannaceuticals
0 Public Utillty
D Refrigeration System
0 Rock Quarry
D Ship Repair/Construction
D Telecommunications Cell Site
D Veterinary Clinic/Hospital
D Wood/Furniture Manufacturing/Refinishing
ELECTRONICS
D Electronic Assembly/Sub·Assembly
D Electronic Components Manufacturing
D Printed Circuit Board Manufacturing
NOTE: THE ABOVE LIST INCLUDES BUSINESSES, WHICH TYPICALLY USE, STORE, HANDLE, AND DISPOSE OF HAZARDOUS SUBSTANCES.
ANY BUSINESS NOT INCLUDED ON THIS LIST, WHICH HANDLES, USES OR DISPOSES OF HAZARDOUS SUBSTANCES MAY STILL REQUIRE
HAZARDOUS MATERIALS DIVISION (HMD) REVIEW OF BUSINESS PLANS. FOR MORE INFORMATION CALL (858) 505-6880.
LIST OF AIR POLLUTION CONTROL DISTRICT PERMIT CATEGORIES
Businesses, which include any of the following operations or equipment, will require clearance from the Air Pollution Control District.
CHEMICAL
4 7 -Organic Gas Sterilizers
32 -Acid Chemical Milling
33 -Can & Coil Manufacturing
44 -Evaporators, Dryers & Stills Processing
Organic Materials
24 -Dry Chemical Mixing & Detergent Spray
Towers
35 -Bulk Dry Chemicals Storage
55 -Chrome Electroplating Tanks
COATINGS & ORGANIC SOLVENTS
27 -Coating & Painting
37 -Plasma Arc & Ceramic Deposition Spray
Booths
38 -Paint, Stain & Ink Mfg
27-Printing
27 -Polyester Resin/Fiberglass Operations
METALS
18 -Metal Melting Devices
19 -Oil Quenching & Salt Baths
32 -Hot Dip Galvanizing
39 -Precious Metals Refining
ORGANIC COMPOUND MARKETING
(GASOLINE. ETC)
25 -Gasoline & Alcohol Bulk Plants & Tenninals
25 -lntennedlate Refuelers
26 -Gasoline & Alcohol Fuel Dispensing
COMBUSTION
34 -Piston Internal -Combustion Engines
13 -Boilers & Heaters (1 million BTU/hr or larger)
14 -Incinerators & Crematories
15 -Bum Out Ovens
16 -Core Ovens
20 -Gas Turbines, and Turbine Test Cells & Stands
48 -Landfill and/or Digester Gas Flares
ELECTRONICS
29 -Automated Soldering
42 -Electronic Component Mfg
FOOD
12 -Fish Canneries
12-Smoke Houses
50 -Coffee Roasters
35 -Bulk Flour & Powered Sugar Storage
SOLVENT USE
28 -Vapor & Cold Degreasing
30 -Solvent & Extract Driers
31 -Dry Cleaning
ROCK AND MINERAL
04 -Hot Asphalt Batch Plants
05 -Rock Drills
06 -Screening Operations
07 -Sand Rock & Aggregate Plants
08 -Concrete Batch, CTB, Concrete Mixers, Mixers
& Silos
10 -Brick Manufacturing
OTHER
01 -Abrasive Blasting Equipment
03 -Asphalt Roofing Kettles & Tankers
46 -Reverse Osmosis Membrane Mfg
51 -Aqueous Waste Neutralization
11 -Tire Buffers
17 -Brake Oebonders
23 -Bulk Grain & Dry Chemical Transfer & Storage
45 -Rubber Mixers
21 -Waste Disposal & Reclamation Units
36 -Grinding Booths & Rooms
40 -Asphalt Pavement Heaters
43 -Ceramic Slip Casting
41 -Periite Processing
40 -Cooling Towers -Registration Only
91 -Fumigation Operations
56 -WWTP (1 million gal/day or larger) & Pump
Station
NOTE: OTHER EQUIPMENT NOT LISTED HERE THAT IS CAPABLE OF EMITIING AIR CONTAMINANTS MAY REQUIRE AN AIR POLLUTION
CONTROL DISTRICT PERMIT. IF THERE ARE ANY QUESTIONS, CONTACT THE AIR POLLUTION CONTROL DISTRICT AT (858) 586-2600.
HM-9171 (08/15) County of San Diego -DEH -Hazardous Materials Division
INDUSTRIAL WASTEWATER DISCHARGE PERMIT
SCREENING SURVEY
Date ___ _
Business Name, _ ___i;;;Euro.1.taacaa.lwduL_,a..,k...,e,._,c.....,04rp.._01Lrai:IJtu.euC ... et:.oUJtwre=-.r:Hulnl Bi..ul Diil.t:aurn.li:a11t1"'· awDli:18LI Si:lllttwi1et::.....:2,uQ,uQ __ _
Street Address. _ _...:1.:5.::2:e.5 -'--F.,,a,._,ra,,,d:,:ai.y.,_A,_,_v,,_e.'--'C~a,.,r.,,ls"'b,,_a,,_d .,,C"--A'---'9"-'2,.,0"'0,,_8 _________ _
Email Address __ _,,jr"'o"'d"-'ri,,g.,.u,.ez"'@=d,_,,e.,.s,.,iq.,_n.,,c.,.o""rp.,,s.,d,_,_.c,.o"'m_,.,_ _____________ _
PLEASE CHECK HERE IF YOUR BUSINESS IS EXEMPT: (ON REVERSE SIDE CHECK TYPE OF BUSINESS)~
Check all below that are present at your facility:
Acid Cleaning Ink Manufacturing Nutritional Supplement I
Assembly Laboratory Vitamin Manufacturing
Automotive Repair Machining I Milling Painting I Finishing
Battery Manufacturing Manufacturing Paint Manufacturing
Biofuel Manufacturing Membrane Manufacturing Personal Care Products
Biotech Laboratory (i.e. water filter membranes) Manufacturing
Bulk Chemical Storage Metal Casting I Forming Pesticide Manufacturing I
Car Wash Metal Fabrication Packaging
Chemical Manufacturing Metal Finishing Pharmaceutical Manufacturing
Chemical Purification Electroplating (including precursors)
Dry Cleaning Electroless plating Porcelain Enameling
Electrical Component Anodizing Power Generation
Manufacturing Coating (i.e. phosphating) Print Shop
Fertilizer Manufacturing Chemical Etching I Milling Research and Development
Film I X-ray Processing Printed Circuit Board Rubber Manufacturing
Food Processing Manufacturing Semiconductor Manufacturing
Glass Manufacturing Metal Powders Forming Soap I Detergent Manufacturing
Industrial Laundry Waste Treatment/ Storage
SIC Code(s) (if known):----------------------
Brief description of business activities (Production I Manufacturing Operations): _____ _
Spec Suite Office Space
Description of operations generating wastewater (discharged to sewer, hauled or evaporated):
Estimated volume of industrial wastewater to be discharged (gal I day): _______ _
List hazardous wastes generated (type/volume): _______________ _
Date operation began/or will begin at this location: ----------------
Have you applied for a Wastewater Discharge Permit from the Encina Wastewater Authority?
Yes No If yes, when:---------------------
Site Contact __ 1 b:'±=-===;-----;---;---Title'---------------
Signature _ D Phone No. ___________ _
ENCINA WAS AUTHORITY, 62 0 Av nida Encinas Carlsbad, CA 92011 (760) 438-3941
FAX: (760) 476-9852
\
DISCHARGE PERMIT EXEMPT LIST
The commercial enterprises listed below are a partial listing of businesses that are exempt
from industrial wastewater discharge permitting under normal operating conditions. They
are exempt because (a) they discharge no process wastewater (i.e., they only discharge
sanitary wastewater with no pollutants exceeding any local limits), and (b) they have no
potential to negatively impact the EWPCF or other wastewater treatment plants in the
ESS. Any questions regarding exemptions should be referred to EWA Source Control
staff.
Automobile Detailers
Barber/Beauty Shops
X Business/Sales Offices
Carpet/Upholstery Cleaning Services
Childcare Facilities
Churches
Community Centers
Consulting Services
Contractors
Counseling Services
Educational Services (no auto repair/film developing)
Financial Institutions/Services
Fitness Centers
Gas Stations (no car wash/auto repair)
Grocery Stores (no film developing)
Home-based Businesses
Hotels/Motels (no laundry)
Laundromats
Libraries
Medical Offices (no x-ray developing)
Mortuaries
Museums
Nail Salons
Nursing Homes
Office Buildings (no process flow)
Optical Services
Pest Control Services (no pesticide repackaging for sale)
Pet Boarding/Grooming Facilities
Postal Services
Public Storage Facilities
Restaurants/Bars
Retail/Wholesale Stores (no auto repair/film developing)
Theaters (Movie/Live)