HomeMy WebLinkAbout1570 MARTINGALE CT; ; CB141332; PermitCity of Carlsbad
1635 Faraday Av Carlsbad, CA 92008
06-20-2014 Residential Permit Permit No: CB141332
Building Inspection Request Line (760) 602-2725
Job Address: 1570 MARTINGALE CT CBAD
Permit Type: RESDNTL Sub Type: SFDR Status: ISSUED
Parcel No: 2150722800 Lot #: 0 Applied: 06/12/2014
Valuation: $373,298.00 Constuction Type: 5B Entered By: JMA
Occupancy Group: Reference #: Plan Approved: 06/20/2014
# Dwelling Units: 1 Structure Type: Issued: 06/20/2014
Bedrooms: 0 Bathrooms: 0 Inspect Area:
Orig PC #: CB982263 Plan Check #:
Project Title: GREIG: LIKE FOR LIKE REBUILD
DUE TO FIRE = 3,079 LV, 726 SF GAR, 89 SF DECK I/FOUNDATION
REPAIR II FIRE SPRINKLERS ARE REQUIRED.
Applicant: Owner:
HOLLY JACQUES GREIG MICHAEL J&RENAE
4715 60TH ST 1570 MARTINGALE CT
SAN DIEGO CA 92115-3802 CARLSBAD CA 92011
619-994-5557
Building Permit $1,769.70 Meter Size
Add'I Building Permit Fee $0.00 Add'I Red. Water Con. Fee $0.00
Plan Check . $1,238.79 Meter Fee . $0.00
Add'] Plan Check Fee ($1,238.79) SDCWA Fee $0.00
Plan Check Discount $0.00 CFD Payoff Fee $0.00
Strong Motion Fee . $37.33 PFF (3105540) $0.00
Park in Lieu Fee $0.00 PFF (4305540) . $0.00
Park Fee $0.00 License Tax (3104193) $0.00
LFM Fee $0.00 License Tax (4304193) . $0.00
Bridge Fee $0.00 Traffic Impact Fee (3105541) $0.00
Other Bridge Fee $0.00 Traffic Impact Fee (4305541) $0.00
BTD #2 Fee $0.00 Sidewalk Fee $0.00
BTD #3 Fee $0.00 PLUMBING TOTAL $159.00
Renewal Fee $0.00 ELECTRICAL TOTAL $59.00
Add'I Renewal Fee $0.00 MECHANICAL TOTAL $60.84
Other Building Fee $0.00 Housing Impact Fee $0.00
HMP Fee $0.00 Housing lnLieu Fee $0.00
Pot. Water Con. Fee .$0.00 Housing Credit Fee . $0.00
Meter Size Master Drainage Fee $0.00
Add'I Pot. Water Con. Fee $0.00 Sewer Fee $0.00
Red. Water Con. Fee $0.00 Additional Fees $0.00
Green Bldg Stands (5B1473) Fee $12.00 Fire Sprinkler Fees $0.00
Green Bldg Stands Plan Chk Fee $0.00
TOTAL PERMIT FEES $2,097.87
Total Fees: $2,097.87 Total Payments to Date: $2,097.87 Balance Due: $0.00
flt I FINAL APPROVAL
Inspector: ( hrk4 Date: 2j / 2f 1A'I' Clearance:
NOTICE: Please take NOTIE tha'approval of your project includes the "Imposition" of fees, dedications, reservations, or other exactions hereafter collectively
referred to as "fees/exactions. You have 90 days from the date this permit was issued to protest imposition of these fees/exactions. If you protest them, you must
follow the protest procedures set forth in Government Code Section 66020(a), and file the protest and any other required information with the City Manager for
processing in accordance with Cartsbad Municipal Code Section 3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack,
review, set aside, void, or annul their imposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection fees and capacity
changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this project. NOR DOES IT APPLY to any
fees/exactions of which you have oreviously been given a NOTICE similar to this, or as to which the statute of limitations has previously otherwise expired.
THE FOLLOWING APPROVALS REQUIRED PRIOR TO PERMIT ISSUANCE: 0 PLANNING D ENGINEERING 0 BUILDING 0 FIRE 0 HEALTH HAZMATIAPCD
0 Building Permit Application
1635 Faraday Ave., Carlsbad, CA 92008
C ITY OF Ph: 760-602-2719 Fax: 760-602-8558
CAR LS BA email:buildingcarlsbadca.gov
'—' www.carlsbadca.gov
rlk Plan Check No. IL4 (;3Z
Est. Value
Plan Ck De sit 7' Date (fILfa4. Iswppp
JOB ADDRESS j 57,) r- 71.7 V7a ail,SUITE#/SPACE#/UNITa AP
- - -
CT/PROJECT if LOT if PHASE if ' J #OFUNITS if BEDROOMS if BATHROOMS TENANT BUSINESS NAME CONSTR. TYPE 0CC. GROUP
DESCRIPTION OF WORK: Include Square Feet of Affected Area(s) . •; < I,
EXISTING USE,
FD
PR0POEPJ.ISE
t-D
GARAGE (SF)
S
PATIOS (SF) DECK(SF) FIREPLACE
YES D#. NO[:]
AIR CONDITIONING
YES DNOE
I FIRESPRINKLERS
YESNO
APPLICANT NAME J/ kA - UO -ô PROPERTY OWNER NAME rn i
ADD7)5
6t_~)
ADDRESS
)57 fl/)
oL TA L q2 - oj
PHONE FAx
EMAIL j2cr , y EMAIL
DESIGI4 PROFESSIONAL flJ 5JyjV19 CONTRACTOR BUS. NAME
)__ )" l._.J/,,,JC .Q[jl
ADDRESS
— ADDR7SO8/5 )/a41d3 av C1 j JJ[ CITY STA . zl 7
PHONEP
77X ) gqj,, 44g
EMAIL EMAIL
ST5I STATE 7C/44 CLASS ClIYeUSuC#7
\
ç
(Sec. 7031.5 Business and Professions Code: Any City or County which requires a permit to construct, alter, improve, demolish or repair any structure, prior to its issuance, also requires the applicant for such permit to file a signed statement thathe is licensed pursuant to the provisions of the Contractor's License Law (Chapter 9, commending with Section 7000 of Division 3 of the Business and Professions Code) or that he is exempt therefrom, and the basis for the alleged exemption. Any violation of Section 7031.5 by any applicant for a permit subjects the applicant to a civil penalty of not more than five hundred dollars ($500)(.
0.;
.
Workers' Compensation Declaration: I hereby affirm under penalty of perjury one of the following declarations: II p have and will maintain a certificate of consent to self-insure for workers' compensation as provided by Section 3700 of the Labor Code, for the performance of the work for which this permit is issued.
LI I have and will maintain work , as 1ct
0 '7r rCo7,pe of 7 is issued. My
: ZTjT7 crfld policy
number are: Insurance Co. ficyllio.
This section need not be completed if the permit is for one hundred doll ($100) or less. S
[J Certificate of Exemption: I certify that in the performance of the work for which this permit is issued, I shall not employ any person in any manner so as to become subject to the Workers' Compensation Laws of
California. WARNING: Failure to secure workers' compensation coverage is unlawful, and shalt subject an employer to criminal penalties and civil fines up to one hundred thousand dollars (&100,000), in
addition to the cost of compensati , m As as provided for in Section 3706 of the Labor code, interest and attorney's fees.
-
DATE 4. 2AGENT
LP
0
H
I hereby affirm that lam exempt from Contractor's License Law for the following reason:
S
[=1 I, as owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not intended or offered for sale (Sec. 7044, Business and Professions Code: The Contractor's
License Law does not apply to an owner of property who builds or improves thereon, and who does such work himself or through his own employees, provided that such improvements are not intended or offered for
sate. If, however, the building or improvement is sold within one year of completion, the owner-builder will have the burden of proving that he did not build or improve for the purpose of sale).
[] I, as owner of the properly, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions Code: The Contractor's License Law does not apply loan owner of
property who builds or improves thereon, and contracts for such projects with contractor(s) licensed pursuant to the Contractor's License Law). 0
[] I am exempt under Section Business and Professions Code for this reason: S 0 I personally plan to provide the major labor and materials for construction of the proposed property improvement (jves lilNo
((have / have not) signed an application for a building permit for the proposed work. .
I have contracted with the following person (firm) to provide the proposed construction (include name address/phone/contractors' license number):
I plan to provide portions of the work, but (have hired the following person to coordinate, supervise and provide the major work (include name / address! phone / contractors' license number):
I will provide some of the work, but I have contracted (hired) the following persons to provide the work indicated (include name / address / phone / type of work):
,.PROPERTY OWNER SIGNATURE .
0
' flAGENT . DATE S
'
7LL>1 ¶LtD3 cjf Th32 JjP
Is the applicant or future building occupant required to submit a business plan, acutely hazardous materials registration form or risk management and prevention program under Sections 25505, 25533 or 25534 of the
Presley-Tanner Hazardous Substance Account Act? 0 Yes 0 No
Is the applicant or future building occupant required to obtain a permit from the air pollution control district or air quality management district? 0 Yes 0 No
Is the facility to be constructed within 1,000 feet of the outer boundary of a school site? 0 Yes 0 No
IF ANY OF THE ANSWERS ARE YES, A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR IS MEETING THE REQUIREMENTS OF THE OFFICE OF
EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT.
4:'1 1 r'
I hereby affirm that there is a construction lending agency for the performance of the work this permit is issued (Sec. 3097 (I) Civil Code).
Lender's Name Lender's Address
7E !i COCJC
I cerfitythati have read the application and state thatthe above information is conectand thatthe information on the plans is accurate. I agree to cemptywith all Cityordinances and State laws relating to building construction.
I hereby authorize representative of the City of Carlsbad to enter upon the above mentioned property for inspection purposes. I ALSO AGREE TO SAVE, INDEMNIFY AND KEEP HARMLESS THE CITY OF CARLSBAD
AGAINST ALL LIABILITIES, JUDGMENTS, C.QSAND EXPENSES WHICH MAY IN ANY WAY ACCRUE AGAINST SAID CITY IN CONSEQUENCE OF THE GRANTING OF THIS PERMIT..
OSHA: An OSHA permit is required for e 0 4rer 50' deep and demolition or construction of structures over 3 stories in height. .
EXPIRATION: Every permit issued by l'e Br in at under the provisbns of this Code shall expire by Imitation and me nut and void tithe building or work authorized by such permit is not commenced within 180 days from the date of such permit • cit permit is suspended or abandoned at any time after the work is commenced for a period of 180da (Section 106.4.4 Uniform Building Code).
.APPLICANT'S SIGNATURE • DATE tO 1 L.
Inspection List
Permit#: CB141332 Type: RESDNTL SFDR GREIG: LIKE FOR LIKE REBUILD
DUE TO FIRE = 3,079 LV, 726 SF GAR, 89
Date Inspection Item Inspector Act Comments
02/11/201589 Final Combo - RI
02/11/2015 89 Final Combo PY AP
02/06/2015 89 Final Combo - RI COF
02/06/2015 89 Final Combo MC CO NOTICE
11/05/2014 18 Exterior Lath/Drywall PY AP
10/09/2014 82 Drywall/Ext Lath/Gas Test PY AP
09/29/2014 84 Rough Combo PY AP
09/26/2014 84 Rough Combo PY CO
09/17/2014 13 Shear Panels/HD's PY AP
08/15/2014 13 Shear Panels/HD's PY PA
08/15/2014 15 Roof/Reroof PY AP
07/31/2014 14 Frame/Steel/Bolting/Weldin PY NR
07/10/2014 21 Underground/Under Floor PY AP
07/10/2014 32 Const. Service/Agricultural PY AP.
Thursday, February 12, 2015 Page 1 of 1
--
___
1 'tVJ wL,KnOuiLaoi
.t
--
- 1P M I1 rU5
VIAIOU
1 -
-
- --
__
Mw
tivmiiTi -- -- - -
- 4 - ,-
--
-
ot
-_p__
L --
rnj
.-- 'I- -j- — ' - -- -- ---..
d,f1 - - --
cti -. c
I441U - - '-
___
LY
-• - rf4 1 t
411 MVII4 03 UAN41 JIM I0
'
______ J f turn 4t1ilt1UiDijt1fl i; - --
_-Hfl £,
- - .. - -• l - ___;.. - - . - - -
- I 1DH j7
J $jHhLq SI'IYA tH
. I -
____ -
-•, - •--- •t'-:i
- 4
ttI$4CA
diu1)s3UgI it
. - •_i - - ., - .
'Iti t__J.,,_ •
- -
-=- r -
rno 1CM ELI
to o"m
Tlv",
- —
-
- — ,- - - - !PrI — - —'i- — -. • - --- - - - --- --- - - -- — 4el • -
- - -
-
T iL''
tLtZ0*L :r-j -
NDLJ4LbII 4Q
L? tI4A a
080 3I N0I1 3dçp
!II I • •I•'- I
I r. •I . ' 'I • t'fltit - 1.1 fl;_.tIt •
' rt. I ,!I.7 ill
'It I II I-' • I. tI I
J 31VNILV GLfl CCt'LU3
- T a - K_'.-• -' -.
•• •
1 _-__•'-' *...--, .., •--.. ,,--•- ..-.
Address: PflTilt Number:
Owner: .ff. f-Gl. Phone: I Area in Sq. Ft. Contractor:,444 _(_ccqJc_ _Phone:
PANEL: Ib.t I)C.... 2i5i pl.ivt.O A.I.C./aDJtO VOLTS 3 0 - ._ WIRE
CKT WIRE MISC _______LOCATION REC REC LTG MISC _____WIRE _____ BKR
SIZECKT LOCATION ZE 11'PE SiZE riPE
JBKR
!L J / Ti-J o
L? TWO / /2- T/MtJ
r&
(9i>
'— /2- rf(..J ) 6
e i&J i_ _I_ 0 m*J 40 8
9- 4 I I Th*4 çb - .~aA
f-IC 4 / Ti1-J 3D
D1 1.J ;1c I T7flhJ /? 17t4 cD
(n AtAA C_/Q- Thif 16
- / /a T7*-.i c9D 18
T?2~ 9A 19 / 7Th 2.. iq- Ttf(-,-( /, 20 r,S 21 rtt( /22
23 /3 .__
('.t 774tjJ ./J 24 jZtCfffr,
25 1St ThFI /s 26
27 . . /4 ni#( /S 28
29 30...
31 32
33 34
35 . . . 36
37 38
39 E 40
41 . . 42
MAIN: Qoo AMP BRK/FUSE U MLO Computed Load / (' / AMPS
BUS: 9it AMP See Calculation Worksheet on back
Service entrance or feeder conductors:
A) Size: No: '3/-Z B) Type: U CU 'AL
Branch circuits required:
A) Lighting Circuits 220— 3(b), 4(d)
C) Insulation: 0) Conduit Size: All Two Small Appliance Circuits 210— 11(e)
Laundry Circuit 220— 16(b) Service ground/bond: .
h WU U A) Size: No. 4 B) Type: AL
0) Central He Equipment 422-12
E) Bathroom 210- 52(d)
C) Clamp location(s):
(4 Remarks: /4__-t'CT P.T.c*icJ.-I LIFER FER 250-50(c) .
ater Pipe 250-104 .
E
ji,, L-i .', ,J(
Rod 250-52 "'gt p -r-
0
GFCI locations 210-8,680 - 70: I cèrtils/ that all terminations have been torqued in accordance with manufacturers
u-Bathroom(s). Kitchen instructions and that the work shown on this circuit card represents the full extent of
Garage(s) . lydromassage Tub the work performed under this permit.
Outdoors 0 0 Owner
AFCI Protected Circ. 210-12 - Contractor...4 -
%Bedroom(s) ixsignedc4 Date g-111'f
Mis
rcity of
Carlsbad
CIRCUIT CARD
B-36
Development Services
Building Division
1635 Faraday Avenue
760-602-2719
www.carlsbadca.gov
TR1S CARD MUST 1W PII.T,FI) (MiT ÂME) AVAIT.A141 .Tt AT TIfF SFR VICF P()T)1PMFWT F()R TMF R(M 1U rwSPrrnflN
B-36 Page lof2 Rev. 03/09
SINGLE-FAMILY DWELLING
ELECTRICAL SERVICE LOAD CALCULATION
As an alternative method, the STANDARD METHOD
found in ARTICLE 220 of the National Electric Code, may be used
1. GENERAL LIGHTING LOADS
Dwelling Q sq. ft. x 3. VA = 220-3(a) /Lh400 VA
Small appliance loads - 220-16(a) 1500 VA a circuits = VA
Laundry load - 220-16(b) 1500 VA circuits = /5bc. VA
General Lighting Total / 1Z4C1WVA
2.. COOKING EQUIPMENT LOADS - NmepIate Value '.! . .,
Range q00 VA= 'j'7O VA
Cooktop &6toy VA = L cto VA
Oven (s) VA= -' VA
Cooking Equipment Total VA
3. ELECTRIC DRYER 220-18 (Nameplate, 5000 VA minimum) .
Dryer 7Y7 VA = ,. Dryer.Total''O VA,
4 FIXED APPLIANCE LOADS 230-30 (b) (3)
Dishwasher ' . / VA
Disposal = . . VA
Compactor = . - VA
- Water Heater = VA
Hydromassage Bathtub = . - VA
Microwave Oven = . / Sp VA
Built-in Vacuum = . - VA
151 = ./ow VA
Fixed Appliance Total 133 S0 VA
S. OPTIONAL SUBTOTAL (Add all of the above totals) . 57/ co VA
APPLYING DEMAND FACTORS - TABLE 220-30
First 10,000 VA 100% . 10,000 VA
Optional Subtotal (from line 5){ Remaining 41 10 VAx 40%=6660 VA.
HEATING OR AC LOAD - TABLE 220-30
Larger of the Heating or AC Load = . /c OO VA
OPTIONAL LOADS TOTAL (Add totals from lines 6 and. 7) = 34, 6 VA
MINIMUM SERVICE SIZE = Optional Loads Total = / 6/. . Ampere
240 Volt . . :..
(Please put total on front of card under Computed Load)
JW
i
4Lity 0f
Carlsbad
CIRCUIT CARD
B-36
Development Services
Building Division
1635 Faraday Avenue
760-602-2719
www.carlsbadca.gov
THIS CARD MUST BE FILLED OUT AND AVAILABLE AT THE SERVICE EQUiPMENT FOR THE ROUGH INSPECTION
Address: Permit Number:
Owner: PIP, .srC1 Phone:
Area in Sq. Ft.
Conractor:44,,4. C;fC- I
' PANEL: UPm'(_ _/C20 AC. _VOLTS 0 WIRE
LOCATION CKT BKR
SIZE
WIRE MISC REC REC LTG MISC _____WIRE BKR
SIZE C KT LOCATION SIZE TYPE SIZE TYPE
_____ i 3 /Lf r4-( 'S.— IL c)i€
/ $ iJ . /c( pJ 'S
/ i 7f 17f#( /ç 6
Lcs L_ / Lt_ - /0 14 IVtf ___
(, STL.4 9. i9T) - ___ ___ 1r9-.. Th-fFrl 9i 10
12
_ 90 16: T L /? rff-fI-J gn 14 1 in
1LQ177YW -L 16.
17 18
19 F 1 20
21 22
23 24,
25 26
27 28
29 30
31, 32
33 34
35 36
37
_ _ _
38
_.•_
39 40
41
_ _ _
.42
/ 1. MAIN:,R 906 AMP BRK/FUSE U MLO Computed Load ' AMPS
BUS: AMP _________________ See Calculation Womsheet on back
Service entrance or feeder conductors:
A) Size: No. 3(i, B) Type: OrCLI U AL
Branch circuits required:
Lighting Circuits ' 220- 3(b), 4(d)
C) Insulation: 0) Conduit Size: Two Small Appliance Circuits
. C) Laundry Circuit
210- 11(e)
220- 16(b) Service ground/bond' n 0) Central Heating Equipment 422-12
B) Type: A) Size: No. AL E) Bathroom 210- 52(d)
Clamp location(s):
JUFER 250-50(c) Remarks:
Pipe 250-104 . ,,Water .
Ground Rod 250-52
GFCI locations 210 - 8, 680 - 70: 1 certiIy that all terminations have been torqued in accordance with manufacturer's JR Bathroom(s) Kitchen . instructions and that the work shown on this circuit card represents the full extent of
Garage(s) NAydromassage Tub the work performed under this permit.
Outdoors U 0 Owner
AFCI Protected Circ. 210-12 'Contractor tt.-tc71Vrc..
,WBedroom(s) .Signed Date.'/-
B-36 Page 1 of 2 Rev. 03/09
SINGLE FAMILY DWELLING
ELECTRICAL SERVICE LOAD CALCULATION
As an alternative method, the STANDARD METHOD
found in ARTICLE 220 of the National Electric Code, may be used
GENERAL LIGHTING LOADS
Dwelling sq. ft. x 3. VA = 2203(a), .: - . VA
Small appliance loads.- 220-16(a) 1500 VA x circuits = - VA
Laundry load - 220-16(b) 1500 VA circuits = VA
General Lighting Total VA
COOKING EQUIPMENT LOADS - Nameplate Value .
Range . VA= ,. . VA
Cooktop VA= VA
Oven (s) . VA = . ... . VA
Cooking Equipment Total VA
ELECTRIC DRYER 220-18 (Nameplate, 5000 VA minimum) .
Dryer. VA = .. . . Dryer,Total . VA
4.. FIXED APPLIANCE LOADS 230-30 (b) (3)
Dishwasher = . VA
Disposal = . VA
Compactor = . VA
Water Heater = . . . VA
Hydromassage Bathtub = . . VA
Microwave Oven = . . . . VA
Built-in Vacuum = . VA
= . . . VA
Fixed Appliance Total VA
OPTIONAL SUBTOTAL (Add all of the above totals) VA
APPLYING DEMAND FACTORS - TABLE 220-30
First l0,000VAx100% . 10,000 VA
Optional Subtotal (from line 5) { Remaining VA x 40% VA.
HEATING OR AC LOAD - TABLE 220-30
Larger of the Heating or AC Load = .' . . VA
OPTIONAL LOADS TOTAL (Add totals from lines 6 and 7) = VA
9.' MINIMUM SERVICE SIZE = OptionalLoadsTotal .. Ampere
240 Volt. . .
(Please put total on front of card 'under Computed Load) '
13
CITY. OF
CARLSBAD
PLAN CHECK
REVIEW
TRANSMITTAL
Community & Economic
Development Department
1635 Faraday Avenue
Carlsbad CA 92008
www.carlsbadca.gov
DATE: 6/12/14 PROJECT NAME: Greig : like for like rebuild PROJECT ID: CT 93-09
PLAN CHECK NO: CB141332,SET#:I ADDRESS: 1570 Martingale Ct APN:215-072-28
VALUATION: APPLICANT CONTACT: permits@cox.net
71 TI-is plan check review transmittal is to notify you of clearance by:
LAND DEVELOPMENT ENGINEERING DIVISION
Final Inspection by the Construction & Inspection Division is required: Yes 0 No
For status from a division not marked below, please call 760-602-2719
This plan check review is NaCOMPLETE Items missing or incorict are listed
on the attached checklist. Please resubmit amended plans as required.
hW LAND DEVELOPMENTENG.
-602-275
El Chris Sexton Kathleen Lawrence
• [fl Greg Ryan
L 760-602-4624 760-602-2741 L_1 760-602-4663
Chris.Sexton@carlsbadca.gov Kathleen.Lawrence@carlsbadca.gov Gregory.Ryan@carlsbadca.gov
Gina Ruiz Linda Ontiveros ri Cindy Wong L 760-602-4675 I- 760-602-4662 760-602-2773
Gina.Ruiz@carlsbadca.gov Linda.Ontiveros@carlsbadca.gov Cynthia.wong@carlsbadca.gov
r Dominic Fieri L 760-602-4664
Dominic.Fieri@carlsbadca.gov
Remarks:
PLANNING DIVISION Development Services BUILDING PLAN CHECK Planning Division
1635 CITY OF' Faraday Avenue APPROVAL
(760) 602-4610 CARLSBAD P29
DATE: 6/13/14 PROJECT NAME: FIRE REBUILD PROJECT ID:
PLAN CHECK NO: CB141332 SET#: ADDRESS: 1570 MARTINGALE CT APN:
This plan check review is complete and has been APPROVED by the PLANNING
Division.
By: GINA RUIZ
A Final Inspection by the PLANNING Division is required Yes Z No
You may also have corrections from one or more of the divisions listed below. Approval
from these divisions may be required prior to the issuance of a building permit.
Resubmitted plans should include corrections from all divisions.
This plan check review is NOT COMPLETE. Items missing or incorrect are listed on
the attached checklist. Please resubmit amended plans as required.
Plan Check APPROVAL has been sent to: PERMITS@COX.NET
For questions or clarifications on the attached checklist please contact the following reviewer as marked:
.;.. .....-7,... -..-•.t ;.•:• 2 :--...-. . ., .. ..,.... .;..........,.-. t7 PLANNING ENGINEERING ,, FIRE PREVENTION,
7606024610 76O6O2275O 76O6O24665'
....-.. .... . .......... ....: . ... :-....... •: . .-. . ., .
Chris Sexton - Kathleen Lawrence Greg Ryan
760-602-4624 760-602-2741 760-602-4663
Chris.Sexton@carlsbadca.gov KathIeen.Lawrence@carIsbadca.gov Gregorv.Rya n@carIsbadca.ov
Gina Ruiz J Linda Ontiveros Cindy Wong
760-602-4675 760-602-2773 7606024662
Gina.Ruiz@carlsbadca.gov Linda.Ontiveros@carlsbadca.gov Cynthia.Wong@carIsbadca.gov
Dominic Fieri
760-602-4664
Dominic.Fieri@carlsbadca.gov
Remarks:
4 h e, CITY OF
CARLSBAD RECORD COPY
Community & Economic Development www.carlsbadca.gov
June 13, 2014
Deborah N. Lee
District Manager
California Coastal Commission
San Diego' Coast District
Suite 103
7575 Metropolitan Drive
San Diego, CA 92108
SUBJECT: : COASTAL PERMIT EXEMPTION FOR POINSETTIA FIRE RECONSTRUCTION
ADDRESS: 1570 MARTINGALE CT
ASSESSOR PARCEL NUMBER: 215-072-28-00
Dear Ms. Lee,
This letter is to document that reconstruction at the above referenced location was found to comply with
Section 30610 (g) of the California coastal Act. Section 30610 lists developments authorized without
permit. Specifically Section 30610 (g)(1) exempts the following from the requirement to obtain a coastal
development permit: '
The replacement of any structure, other than a public works facility, destroyed by a disaster.
The replacement structure shall conform to applicable existing zoning requirements, shall be
for the same use as the destroyed structure, shall not exceed either the floor area, height, or
bulk of the destroyed structure by more than 10 percent, and shall be sited in the same
location on the affected property as the destroyed structure.
(2) As used in this subdivision:
'Disaster" means any situation in which the force or forces which destroyed the
structure to be replaced were beyond the control of its owner.
"Bulk" means total interior cubic volume as measured from the exterior surface of the
structure.
"Structure" includes landscaping and any erosion control structure or device which is
similar to that which existed prior to the occurrence of the disaster.
Based on the review of the plans for the proposed construction the proposal was found to comply With
the applicable Coastal Act provision listed above. Should you have any questions concerning the
applicability of the proposed exemption, I can be reached at (760) 602-4675 or at
Gina.Ruiz@carlsbadca.gov.
Sincerely,
GINA RUIZ'.
Planning Technician II
C: Don Neu, City Planner
Chris DeCerbo, Principal Planner
Will Fàss, Building Official
Mike Peterson, Development Services Manager
Planning Division
1635 Faraday Avenue, Carlsbad, CA 92008-7314 T 760-602-4600 F 760-602-8559 '
CITY OF
_C41
PLAN CHECK
REVIEW
TRANSMITTAL
LJ
n
SMIüint
v
y & Economic
Development Department
1635 Faraday Avenue
Carlsbad CA 92008
www.carlsbadca.gov
DATE: 06.18.2014 PROJECT NAME: GREIG RESIDENCE PROJECT ID: CB141332
PLAN CHECK NO: I SET#: I ADDRESS: 1570 MARTINGALE CT APN: 215-072-28-00
. This plan check review, is complete and has been APPROVED by the FIRE Division.
By: G.RYAN . .
A Final Inspection by the FIRE Division is required Z Yes No
This plan check review is NOT COMPLETE. Items missing or incorrect are listed on
the attached checklist. Please resubmit amended plans as required.
Plan Check Comments have been sent to: H. JACQUES
You may also have corrections from one or more of the divisions listed below. Approval
from these divisions may be required prior to the issuance of a building permit.
Resubmitted plans should include corrections from all divisions.
For questions or clarifications on the attached checklist please contact the following reviewer as marked:
PLANNING ENGINEERING FIRE PREVENTION
760-6024610 7606022750 7606024665
Chris Sexton H Kathleen Lawrence . . Greg Ryan
760-602-4624 760-602-2741 760-602-463
Chris.Sexton@carlsbadca.gov Kathleen. Lawrence@carlsbadca.gov . . Gregory.Ryan@carlsbadca.goy
Gina Ruiz Linda Ontiveros Cindy Wong
760-6024675 760-602-2773 760-6024662
Gina.Ruiz@carlsbadca.gov . Linda.Ontiveros@carlsbadca.gov Cynthia.Wong@carlsbadca.gov
J Dominic Fieri
760-602-4664
Dominic.Fieri@carlsbadca.gov
Remarks: See Attached
BUILDING DEPt
Carlsbad Fire Department cOP'!
Plan Review Requirements Category: RESDNTL, SFDR
Date of Report:
Name:
Address:
Permit #:
Job Name:
Job Address:
06-18-2014
HOLLY JACQUES
4715 60TH ST
SAN DIEGO CA
92115-3802
CB141332
GREIG: LIKE FOR LIKE REBUILD
1570 MARTINGALE CT CBAD
Reviewed by: 444t
Please review carefully all comments attached.
Conditions:
Cond: C0N0007384
[MET] CITY OF CARLSBAD FIRE DEPARTMENT - APPROVED: WI REQUIREMENTS
THIS PROJECT HAS BEEN REVIEWED AND APPROVED FOR THE PURPOSES OF ISSUANCE OF
BUILDING PERMIT.
THIS APPROVAL IS SUBJECT TO FIELD INSPECTION AND REQUIRED TEST, NOTATIONS HEREON,
CONDITIONS IN CORRESPONDENCE AND CONFORMANCE WITH ALL APPLICABLE REGULATIONS.
THIS APPROVAL SHALL NOT BE HELD TO PERMIT OR APPROVE THE VIOLATION OF ANY LAW.
AN APPROVED A UTOMA TIC FIRE SPRINKLER SYSTEM SHALL BE REQUIRED. PLANS FOR SPRINKLER
SYSTEM SHALL BE A SEPARATE SUBMITTAL.
INFORMATION SPECIFIC TO RESIDENTIAL SPRINKLER DESIGN MAY BE OBTAINED BY
CONTACTING DEPUTY FIRE MARSHAL - GREG RYAN AT 760-602-4663.
Entry: 06118/2014 By: GR Action: AP
7710 Balboa Ave. structural Suite 206C
San Diego, CA 92111 engineers Ph: 858.442.7771
Fax: 619.996.2082
STRUCTURAL CALCULATIONS.-
for: Greig Residence - Fire Damage Repair
1570 Martingale Court
Carlsbad, CA 92011-4035
Date: June 9, 2014
Job No.: 1403.
C&ILI IV 11010
I
z
i: :::: T1I1 tIfl
0O73 ( Tr4
1r T ti 1-1 "T
---------- _
iI 1t1 - Nut______________________ -____ • 7T1OBeASii2O6.0
iv.. structural San DWMCA92111 4 6 1 at engineers hc.rA71FmcSi
NUSGS, Design Maps Summary Report
User—Specified Input
Report Title Greig Residence
Tue June 3, 2014 17:18:53 UTC
Building Code Reference Document ASCE 7-10 Standard
(which utilizes USGS hazard data available in 2008)
Site Coordinates 33.11530N, 117.28931W
Site Soil Classification Site Class D - "Stiff Soil"
Risk Category 1/11/111
.\ç. J
USGS—Provided Output
..
.-
IL .. .'.. 3•_I..
:
.z ncinitas
j -620.141
r•L?
t
Ss = 1.091 g 5MS = 1.160 g S,, = 0.773 g
S1 0.420 g SMZ = 0.664 g SD1 = 0.443 g
For information on how the SS and Si values above have been calculated from probabilistic (risk-targeted) and
deterministic ground motions in the direction of maximum horizontal response, please return to the application
and select the "2009 NEHRP" building code reference document.
Design Response Spectrum
0.22
0 0.42
M 0.40
O. 20
0.16
0.32-
0.09--
0.00 i I I. .1 I I I
0.00 0.20 0.40 0.60 0.90 1.00 1.20 1.40 1.60 1.20 2.00
Period. T (sec)
GtLc C - EICJ
MCEA Response Spectrum
1.20--
1.08--
0.72--
N
0.c0
0.42--
0.36--
0.24--
0.12
0.00
0.00 0.20 0.40 0.60 0.20 1.00 1.20 1.40 1.60 1.20 2.00
Period, T (sec)
For PGA,, TL, C, and CR1 values, please view the detailed report.
IIi .i1uI i_ i I I I I IT
EIkE E 16 E W E*t BE
III'I1IIII[IIIiIIIIIiiI1IIIII
Let
F-31
- T711
-,----
w - ?J! H--
H-
H-
-1-•----
4- -
- - -.
-1-L - 4- - - -
- - - - - - - - ....
1 1 -14-
.__ pr* '7R
structural SDCA1 '0 3 _Pop 73> g____ engineers Foc 81M PreudB
'a -
IL
##k -'412 S (o'. c'es.
L[ sr'cc.z I 0
e/&4"N. so"4
A. @
A6.Gt140.(.
t#P4.'A i4,'e.'. ,çw;
A'.( L6O..
iOE,'
6G
*g&, 6P
I I41ITf+17±1f±I I
b Log
4tt t1'TwK ' T
- f
t Tj
I
'1LL. OI.(Ctz ,d 13 L" ITT I:w Az 13I
fl1OBaAve,S6.0 .I S
p G(
structural Sego,CAO2III 3 g
engineers Fc619.99& ___ //4
• _____ ____ ___
i T
1H t .1I I I (4L4e
TTTJ~,466 ?t
Sc
)
-
4
I
,
I
ki-
o
rt_y/ I I
O/-& t2 •O; I
I
I
I I I
t ill -t I -
I
zo
Ill 33O
C-3 kbi
I tA3,. 31
? TWK cT1T'
0. LA -S
--
t
I
I
4 1
I I
I I { I- iII
U
structural Son DbACA 92111 p 1.4- b 3 3 Psg_____ engineers F619.9962O92
Load and Geometry
Load factor source: ACI 318 Section 9.2
Load combination: not set
Seismic design: No
Anchors subjected to sustained tension: No
Apply entire shear load at front row: No
Anchors only resisting wind and/or seismic loads: No
<Figure 1>
-*Ib
Oft-lb 0
A' L (VC.
A/-Ic '-,c,/t
t1ikiII'Ji• Anchor DesignerTM
I fgv Software
- Version 2.0.5154.1
a
Company: /Z - Date: 6/5/2014
Engineer: Z'— Page: 1/4
Project: G&f L
Address:
Phone:
E-mail:
Project description:
Location:
Fastening description:
Base Material
Concrete: Normal-weight
Concrete thickness, h (inch): 24.00
State: Uncracked
Compressive strength, f c (psi): 3000
4'c,V: 1.0
Reinforcement condition: B tension, B shear
Supplemental reinforcement: Yes
Do not evaluate concrete breakout in tension: No
Do not evaluate concrete breakout in shear: No
Hole condition: Dry concrete
Inspection: Continuous
Temperature range: 1
Ignore 6d0 requirement: Not applicable
Build-up grout pad: No
Base Plate
Length x Width x Thickness (inch): 4.00 x 4.00 x 0.35
1.Proiect information
Customer company:
Customer contact name:
Customer e-mail:
Comment:
2. Input Data & Anchor Parameters
General
Design method:ACI 318-11
Units: Imperial units -
Anchor Information:
Anchor type: Bonded anchor
Material: A193 Grade 87
Diameter (inch): 1.000
Effective Embedment depth, hef (inch): 16.000
Code report: ICC-ES ESR-2508
Anchor category: -
Anchor ductility: Yes
hmin (inch): 21.00
cac (inch): 36.88
(inch): 1.75
Smin (inch): 3.00
- ---------
- Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility.
Simpson Strong-Tie Company Inc. 5956W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.com
A4
I1Ik'AI.1:'TI Anchor Designer TM
Software
I Version 2.0.5154.1
0
<Figure 2>
Company: /\$.3- - Date: 6/5/2014
Engineer: '6'-i I Page: 2/4
Project:
Address:
Phone:
E-mail:
Recommended Anchor
- Anchor Name: SET-XP® - SET-XP WI 10 A193 Cr. 87
Code Report Listing: ICC-ES ESR-2508
Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility.
Simpson Strong-Tie Company Inc. 5956W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.com
A,fCio/?
I'iI1'JhI Anchor DesignerTM
Software
Version 2.0.5154.1
3. Resulting Anchor Forces
Company: t't C. Date: 6/5/2014
Engineer: ZTç4 v'.. Page: 3/4
Project: 6,-cA5 1 4
Address:
Phone:
E-mail:
Anchor Tension load, Shear load x, Shear load y, Shear load combined, Nu. (lb) Vu.. (lb) Vrny (lb) (Vuax)2+(Vuay)2 (lb)
1 21700.0 0.0 0.0 0.0
Sum 21700.0 0.0 0.0 0.0
Maximum concrete compression strain (%o): 0.00 <Figure 3>
Maximum concrete compression stress (psi): 0
Resultant tension force (lb): 21700
Resultant compression force (lb): 0
Eccentricity of resultant tension forces in x-axis, e'N (inch): 0.00
Eccentricity of resultant tension forces in y-axis, e (inch): 0.00
Steel Strength of Anchor in Tension(Sec. D.5.1)
Nsa (lb) 0 ON.. (lb)
75750 0.75 56813
Concrete Breakout Strength of Anchor in Tension (Sec. D.5.21
Nb = kcAa4f'che?5 (Eq. D-6)
k. A.a f (psi) h0, (in) Nb (lb)
24.0 1.00 3000 16.000 84130
ØNcs = 0 (ANC/ANO)POI.N9'C,N-'CP.NNb (Sec. D.4.1 & Eq. D-3)
ANC (in 2) ANCO (in 2) Wed.N Pc,N ap,N Nb (I b) 0 q5Ncb (lb)
2304.00 2304.00 1.000 1.00 1.000 84130 0.65 54685
Adhesive Strength of Anchor in Tension (Sec. 5.5)
Vçunc, = rlcuncrfsha,ue,mKsat
Vw,,c, (psi) fso,i-ie,m Ksat m,wicr (psi)
1555 1.00 1.00 1555
Nba = 2araac,irdsher(Eq. D22)
A0 T,,,c, (psi) da (in) hei (in) Nba (lb)
1.00 1555 1.00 16.000 78163
ØN0 = Ø(ANa/ANao)Pa.NaWcp.NaNba (Sec. D.4.1 & Eq. D-18)
AN. (in 2) ANaO (in 2) p0dN. Nba (lb) 0 ON. (lb)
565.45 565.45 1.000 1.000 78163 0.65 50806
4
Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility.
Simpson Strong-Tie Company Inc. 5956W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.com
1III1JU Anchor Designer TM
Software
Version 2.0.5154.1
a
11. Interaction of Tensile and Shear Forces (Sec. D.7
,&I)L-1.
Company: Date: 6/5/2014
Engineer: <3'x K_ Page: 4/4
Project:
Address:
Phone:
E-mail:
Tension Factored Load, N8 (lb) Design Strength, øN (lb) Ratio Status
Steel 21700 56813 0.38 Pass
Concrete breakout 21700 54685 0.40 Pass
Adhesive 21700 50806 0.43 Pass (Governs)
SET-XP WI l"ø A193 Gr. B7 with hef = 16.000 inch meets the selected design criteria.
12. Warnings
- Concrete compressive strength used in concrete breakout strength in tension, adhesive strength in tension and concrete pryout strength in
shear for SET-XP adhesive anchor is limit to 2,500 psi per ICC-ES ESR-2508 Section 5.3.
- Designer must exercise own judgement to determine if this design is suitable.
- Refer to manufacturer's product literature for hole cleaning and installation instructions.
Input data and results must be checked for agreement with the existing circumstances, the standards and guidelines must be checked for plausibility.
Simpson Strong-Tie Company Inc. 5956W. Las Positas Boulevard Pleasanton, CA 94588 Phone: 925.560.9000 Fax: 925.847.3871 www.strongtie.com
I
structural
engineers
7710 Balboa Ave.
Suite 206-C
San Diego, CA 92111
Ph: 858.442.7771
Fax: 619.996.2082
RECORD COPY June 17, 2014
Mr. Jeff Poison
AAA - Auto Club of Southern California
800 La Terraza Blvd.
Escondido, CA 92025
Subject: Limited Structural Investigation
Greig Residence - Fire Damage Investigation
1570 Martingale Court, Carlsbad, CA 92011
[MJSE Job Number 14035]
Insurance Claim #: 011505505
Dear Mr. Polson:
At your request, we have undertaken a limited structural investigation of the post-tensioned
concrete slab and foundation at the subject property. Our investigation was undertaken on May
28 and June 11 and 16, 2014. At the time of our site visits, the structure framing had been
demolished and removed and the entire concrete slab could be observed.
We understand that the fire damage to the structure occurred on or around May 14, 2014 and we
understand that the subject residence was damaged as a result of a wildfire. The intent of our site
visits was to investigate the extent of the structural damage to the post-tensioned concrete slab
and foundation and, if necessary, to develop preliminary, repair or replacement recommendations
for the observed damage for the limited purpose of assisting in your claims processing activity.
Thesubject residence was a two-story, wood-framed structure and we understand that it was
originally constructed around 2001. The residence reportedly contained four bedrooms and three
bathrooms and it measured approximately 3,079 square feet in living area excluding the attached
two-car garage. The footprint of the subject residence measures approximately 2,330 square feet
in plan.
As part of our structural investigation, we reviewed the original building drawings titled
"Cantamar - Carlsbad, CA" prepared by JBZ Architecture & Planning, dated January 29, 1999
(City of Carlsbad Permit Number: CB982263).
AAA - Auto Club of Southern California
Greig Residence - Fire Damage Investigation
June 17, 2014
Page 2 of 7
Observations, Opinions, and Recommendations
The following is a list of our observations, opinions and recommendations related to the structural
investigation of the post-tensioned concrete slab and foundation at subject property:
From the original building drawings and our field observations, the slab typically appears to
be 4Y2 inches thick and reinforced with Y2-inch diameter, 7-wire, steel strands spaced roughly
4 feet on-center. The foundation consists of interior and exterior footings that are typically
12 inches in width and extend 12 to 24 inches in depth. At the exterior garage walls there is
concrete curb measuring 6 inches in width and height.
2. From our observations, the concrete slab, curbs, and foundation are in fair to good condition.
We did not observe discoloration of the concrete or significant spalling of the slab which
would indicate damage from heat. We did observe that portions of the concrete slab,
concrete curbs, anchor bolts, and holdowns have been damaged by the demolition activities.
We observed spalled curbs and bent anchor bolts. Please refer to Photographs Number 3
through 5. We recommend repairing the concrete slab and curb as appropriate and adding
additional adhesive anchors as required. We observed that several of plumbing penetrations
through the slab have also been damaged. Please refer to Photograph Number 6. We
recommend locally removing the concrete around the piping as required to provide a proper
coupling and patching the concrete as appropriate.
To investigate the concrete compressive strength of the slab, we engaged the services of
NV5 - Testing Engineers VerticalFive (NV5). A copy of NV5's report is included as
Attachment A. NV5 performed rebound hammer testing at 10 locations. The average
rebound hammer test results were fairly consistent over the, entire slab and ranged from 40.8
at location 9 to 47.8 at location 6. According to the NV5 report, these rebound hammer test
values indicate the concrete compressive strength of the slab is approximately 4,000 to 5,000
pounds per sqüare,inch (psi). The original building drawings specify a concrete compressive
strength of 2,500 psi for the slab. Based on the test results, it is our opinion that the concrete
slab or foundation was probably not structurally damaged by the subject fire. It is also our
opinion that the subject fire and resulting heat likely had no appreciable effect on the
structural properties of the existing concrete at the subject residence.
4. To investigate the condition of the post-tensioned tendons, a small portion of the concrete
slab was locally removed exposing two intersecting tendons. Please refer to Photographs
Number 7 and 8. This area coincides with Location 9 in the NV5 report and it was chosen
since this area received the most severe fire damage. From our observations, the plastic
sheathing around the post-tension strands is in very good condition and it does not appear to
have been affected by the heat.
We determined the original seismic design forces using the 1995 California Building Code
(CBC) and compared these forces to the current 2013 CBC. We determined that the original
seismic base shear to be approximately 0.14 times the seismic mass of the structure. The
current seismic forces are approximately 0.08 times the seismic mass of the structure, using
allowable stress design (ASD) forces. In our opinion, the original seismic system (including
the concrete foundation) is likely general compliance with the seismic requirements of the
current CBC.
AAA - Auto Club of Southern California
Greig Residence - Fire Damage Investigation
June 17, 2014
Page 3 of 7
Based on our observations and testing, the post-tensioned concrete slab and foundation
appear to be in good structural condition.. In our opinion, the post-tensioned concrete slab
and foundation were not structurally damaged by the fire/heat. In addition, it is our opinion
that the future structural performance of the post-tensioned concrete slab and foundation will
be similar or the same as prior to the fire loss. In our opinion, replacement of the post-
tensioned concrete slab and foundation is not required. In our opinion, the portions of the
concrete slab and curbs damaged during the demolition activities can be repaired by
patching utilizing standard concrete repair techniques.
Closure
Our professional structural engineering services for this investigation have been provided for the
confidential use of our client (AAA - Automobile Club of Southern California). No opinion or
warranty about the general or specific condition of the property as it affects the owner or
prospective future owners or other interested parties is given, expressed or implied.
Authorization for use of this report is reserved pending our written approval as. a mutual
protection to our client, the public and ourselves.
Be advised that the opinions and recommendations made in this report are based only on our
limited visual investigation performed at this time period, on our experience with similar types of
structures, and on our knowledge and professional judgment. We have not performed a
comprehensive structural analysis of the subject building nor undertaken any testing. We have
performed our professional services in accordance with the generally accepted local structural
engineering practices for projects of this type and no warranty is either expressed or implied.
Before any repairs, alterations, or modifications are initiated, the services of a qualified design
and/or construction professional should be obtained to develop appropriate construction
procedures, recommendations and details.
If you have any questions or if we can be of further assistance on this matter, please do not
hesitate to call. As always, the opportunity to be of service is sincerely appreciated.
Sincerely
James Miller
Principal
Enclosure: Photographs Number 1 through 8
Attachment A - NV5 Report, dated June 16, 2014
A
rn No. 4186 7,0
*\ Exp12 14 *
\
".OF
AAA - Auto Club of Southern California
Greig Residence - Fire Damage Investigation
June 17, 2014
Page 4of7
:1
Photograph Number I - View of subject residence from the front
(south).
-
• -i; -•-
734
4 • •-, --• -,.•
' •
__________________ •
-Photograph Number 2— View of subject residence from the rear
•
(north). •
Photograph Number 4— View of spalled concrete and bent anchor
bolt.
AAA - Auto Club of Southern California
Greig Residence - Fire Damage Investigation
June 17,2014
.
Page 6of7
0
0 :
H
000
Photograph Number 5 -View of bent anchor bolts.
H
1T1
- -
:
Photograph Number 6 - View of heat damage to Li plumbing pipe
penetrating the concrete slab.
1 structural El
engineers
7710 Balboa Ave.
Suite 206-C
San Diego, CA 92111
Ph: 858.442.7771
Fax: 619.996.2082
ATTACHMENT A
NV5 - Testing Engineers VerticalFive Report, dated
June 16, 2014.
Project: Greig Residence
Fire Damage Repair
1570 Martingale Court, Carlsbad, CA 92011
Job Number: 14035 .
N V 5
BEYOND ENGINEERING
MJ Structural Engineers
7710 Balboa Avenue, Suite 206-C
San Diego, CA 92111
Subject: Rebound Hammer Testing Report
Project: Fire Damaged Residence
1570 Martingale Court
Carlsbad, CA 92011
June 16, 2014
Project No.: 149646.00
email: jmiller@mj-se.com
NV5 West Inc. (NV5) was retained to perform rebound hammer testing at randomly spaced locations
throughout the concrete slab-on-grade of the referenced project. On June 11, 2014, representatives of
NV5 visited the site to perform Rebound Number of Hardened Concrete Tests in general accordance
with standard test method ASTM C805. Results of the testing were used as a comparative means
between various locations across the concrete slab. This letter presents the results of NV5 testing.
Project Background:
The subject structure consists of the remaining of a two story residence supported by concrete slab
foundation after being affected by fire during the events of the Poinsettia Fire in May, 2014. The fire
damaged structure and debris was removed from the site prior to testing. Concrete slab-on-grade
appears in good condition; however, the effects of the fire to the reinforcing steel within the concrete
are unknown. The purpose of this evaluation was to identify areas of weakened concrete to then
investigate the reinforcing steel in these areas (by others).
Testing and Results:
Rebound hammer testing was performed at 10 randomly chosen locations across the slab on grade
that would give a representation of the condition of the concrete. The testing was performed in
accordance with the ASTM C805 Standard Test Method. Approximate location of the tests is presented
on the attached Plot Plan, Figure 1. In accordance with the standard test method 10 individual rebound
numbers were obtained at each testing location. The standard average and corrected average
(discarding outliers) of each set of individual rebound numbers are presented in table 1, following the
relevant'test information, below.
Relevant Test Information.'
Date of testing: June 11, 2014
Time of testing: 9:30 AM
Air temperature at time of testing: 68°F (from weather report, not measured)
Age of Concrete: 14 years (from property public records)
Test Location: Concrete slab-on-grade foundation (See Plot Plan for specific location of each test)
Concrete Information: None known
0FF10E5 NATONW1OE Page 1
7895 CoNvoy Coupi, Sic 18 SAN Dicco, CA 92111 'wIw.NV5.coN I OFFICE 858715.5800 FAx 858.715.5810
CONTIUCTIQN OUAuT AaSUR4NCE iFR/.STRU.TURE E.NcaEeR!Nc, Mu:iciei. Our50uRei4G AEr M EMEr EvIRoHMENT.L 5RviCi5
o f,
Description of test area: Tests were performed on horizontal, smooth finished concrete. Surface was
hard-scrapped before testing. Testing was done on bare concrete after scraping test areas clean. Each
test area was approximately 2 by 10 inches.
Hammer Information: NDT James H-Meter s/n 1 F0775/86603.
Position for testing: Vertical, downward.
Table 1. Rebound Number Results
Location No. Ii 2 34567 8 1 9 10
44 42 1 46 45 44 48 47 44 1 40 42
- 44 42 42 44 42 44* 46 40* 1 48* 44
44 42 44 1 44 46* 50 47 45 42 44
44 42 46 . 46 L46 44[42 41*
Individual Rebound Numbers 42 42 45 1, 43 . 44 47 1 48 44 42 51*
. 42 41 46 42 46 46 46
38* 40 43 44 42 54* 48 46 I 38* 42
42 43 44 1 46 1 38* 11 48 45 48*1 41 43
44 40 42 46 44 49 46 441 40 I 46
44 40 44 46 44 48 47 42 41 42
Total Average 42.8 41.4 44.2 44.6 43.0 48.0 46.6 44.1 41.7 44.1
Non-outlier Average 1 43.3 - -- -- 43.3 47.8 -- 44.1 40.8 43.6
Note: * denotes that rebound number was discarded from the average calculation being either a high or low outlier.
Based on the information obtained from the rebound numbers, as well as field observations, the
integrity of the concrete slab appears to be adequate for the intended use. When discarding the
outliers, the average rebound number doesn't present a significant change, which indicates uniformity
of the concrete hardness and surface condition. Based on our experience with similar type projects, it
is our opinion that the rebound hammer test results indicate the approximate concrete compressive
strength of the post-tensioned slab to be between 4,000 and 5,000 psi. Note: Our opinions are based
on limited test results and the actual concrete compressive strength of the slab may be higher or lower.
Conclusion
No further analyses, conclusions, or recommendations have been developed by NV5.
NV5 appreciates the opportunity to provide this testing service for the referenced project. Please feel
free to contact our office if you have any questions concerning the content of this report or if you require
any additional service or information.
Sincerely,
NV5 West, mc.
Carlos'Mcero, RCE .67031
Senior Project Engineer
Attachments: Figure 1 Plot Plan
Distribution: (1) Addressee
(1) File
NIVI5 Page 2
couc-ro OuMjy Au.*,CC . irRA5JcTwc ENGINCERWC MuclpA .Assu $Rvur.
dl *
a
()_FIRST FLOOR PLAN lIl-.l,.O,
NV5 West, Inc Project No: 149646.00
NIV 5 7895 Convoy Court, Ste 18, San Diego, CA 92111 I KCM
Tel: (858) 715-5800, Fax: (858) 715-5810
Date: June, 2014
Plot Plan
Fire Damaged Residence
1570 Martingale Ct. Carlsbad, CA
Figure No. I