HomeMy WebLinkAbout1580 CANNON RD; ; CB140680; Permit04-23-2014
Job Address:
Permit Type;
Parcel No:
Valuation:
Occupancy Group:
Project Title:
City of Carisbad
1635 Faraday Av Carlsbad, CA 92008
Cogeneration Permit Permit No:CBl40680
Building Inspection Request Line (760) 602-2725
1580 CANNON RD CBAD
COGEN Sub Type: PHOTO
2081860500 Lot#: 0
$13,200.00 Constuction Type: NEW
Reference #:
Status: ISSUED
Applied: 03/26/2014
Entered By: LSM
Plan Approved: 04/23/2014
Issued: 04/23/2014
Inspect Area:
Plan Check #:
AGUA HEDIONDA LAGOON FOUND
INSTALL ROOF MNT PV SYSTEM 33 MODULES NO PANEL UPGRADE
Applicanf:
TMAG INDUSTRIES DBA STELLAR SOLAR
SUITE 105-444
6965 EL CAMINO REAL
CARLSBAD OA 92009
Owner:
AGUA HEDIONDA LAGOON FOUNDATION
1580 CANNON RD
CARLSBAD CA 92008
760-445-1627
Building Permit $166.07 PLUMBING TOTAL $0.00
Add'l Building Permit Fee $0.00 ELECTRICAL TOTAL $0.00
Plan Check $116.25 MECHANICAL TOTAL $0.00
Add'! Plan Check Fee $33.75 Additional Fees $0.00
Plan Check Discount
Strong Motion Fee
Green BIdg Stands (SB1473) Fee
$0.00
$1.32
$1.00
TOTAL PERMIT FEES $318.39
Total Fees: $318.39 Total Payments To Date: $318.39 Balance Due: $0.00
Inspector
FINAL APPROVAL
Date: Clearance:
NOTICE: Please take NOTICE that approval of your project includes the "Imposition" of fees, dedications, reservations, or other exactions hereafter collectively
referred to as "fees/exactions." You have 90 days from the date this pemnit was issued to protest imposition of these fees/exactions. If you protest them, you must
follow the protest procedures set forth in Government Code Section 66020(a), and file the protest and any other required information with the City Manager for
processing in accordance with Carlsbad Municipal Code Section 3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack,
review, set aside, void, or annul their imposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection fees and capacity
changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this project. NOR DOES IT APPLY to any
fees/exactions of which vou have previously been given a NOTICE similar to this, or as to which the statute of limitations has previouslv othenwise expired.
THE FOLLOWING APPROVALS REQUIRED PRIOR TO PERMmSSUANCE: nPLANNING nENGINEERING DBUILDING OFIRE •HEALTH nHAZMAT/APCD
^ CITY OF
CARLSBAD
Building Permit Application
1635 Faraday Ave., Carlsbad, CA 92008
Ph: 760-602-2719 Fax:760-602-8558
email: building@carlsbadca.gov
www.carlsbadca.gov
Plan Check No. M0(£> ^
Est. Value I3^0c)
Plan Ck. Deposit /SO
Date A/glfc?//^-/ SWPPP
JOB ADDRESS /
4
SUITE#/SPACE*/UNIT* APN
-
CT/PROJECT # t/ LOT# PHASE# # OF UNITS # BEDROOMS # BATHROOMS TENANT BUSINESS NAME CONSTR. TYPE OCC. GROUP
EXISTING USE PROPOSED USE GARAGE (SF) PATIOS (SF) DECKS (SF) FIREPLACE
YEsQ* N0| I
AIR CONDITIONING
YES QNO I 1
FIRE SPRINKLERS
YES I |NO| I
APPLICANT NAME
Primary Contact
PROPERTYOWNER M \\ \ J ^"^Sr^ ll Myt^<K !-)<• 0/\ro>^« t. (-0«^'.vrft^<fiv~-^
ADDRESS ADDRESS ii. STATE
tra
ZIP CITY STATE ZIP
PHONE FAX PHONE FAX
EMAIL EMAIL
DESlSN PROFESSIONAL CONTRACTOR BUS. NAME
ADDRESS ADDRESS
CITY STATE ZIP STATE ZIP
PHONE FAX PHONE FAX
EMAIL EMAIL 1-
cuss CITY BUS. LIC.#
(Sec. 7031.5 Business and Professions Code: Any City or County which requires a permit to construct, alter, improve, demolish or repair any structure, prior to its issuance, also requires the applicant for such permit to file a signed statement that he is licensed pursuantto the provisions ofthe Contractor's License Law (Chapter 9, commendingwlth Section 7000 of Division 3 ofthe Business and Professions Code) or that he is exempt therefrom, and the basis for the alleged exemption. Any violation of Section 7031.5 by any applicant for a permit subjects the applicant to a Civil penalty of not more than five hundred dollars ($500)).
WORKERS' COMPENSATION
Workers' Compensation Declaration: / hereby affinn under penalty of perjury one ofthe following declarations:
11 have and will maintain a certificate of consent to self-Insure for workers' compensation as provided by Section 3700 of the Labor Code, for the performance of the wortt for which this permit is issued.
^^•Thave and will maintain workers' compensation, as required bv Section 3700 of the Labor Code, for the perfomiance of the wortt for which this permitjs issued. My woriters' compensation insurance earner
number are: Insurance Co, CCV.'PJ'-^^^ 3^>^-^w-v-t< CJ Policv No. ^ t<' ^CeOM. | g oV 6 Expiration Date __g/^J.^l!t
to the Workers' Cor
Iiundred thousand
AGENT DATE
and policy
This section need not be completed if the permit is for one hundred dollars ($100) or less.
I I Certificate of Exemption: I certifythatintheperfonnanceof the wortt forwhich this pemiit Is issued, I shall not employ any person in any manner so as to become subject to the Woriters'Compensation Laws of
California. WARNING: Failure to secure workats'iompensation coverage is uniawful, and shall subject an employerto criminai penalties and civil fines up to one hundred thousand dollars (&100,000), in
addition to the cost of compensation, damage/ayprovided for in Section 3706 of the Labor code, Interest and attomey's fees.
CONTRACTOR SIGNATURE /JMA "QAGt
OWNER-BUItDEf DECLARATION
/ hereby affinn that I am exempt from Contractor's Ucense Law for the following reason:
I I I, as owner of the property or my employees with wages as their sole compensation, will do the wortt and the stmcture is not intended or offered for sale (Sec. 7044, Business and Professions Code: The Contractor's
License Law does not apply to an owner of property who builds or improves thereon, and who dees such worit himself or through his own employees, provided that such improvements are not intended or offered for
sale. If, however, the building or improvement is sold within one year of completion, the owner-builder will have the burden of proving that he did not build or improve for the purpose of sale).
I I I, as owner of the property, am exclusively contracting with licensed contractors to constmct the project (Sec. 7044, Business and Professions Code: The Contractor's Ucense Law does not apply to an owner of
property who builds or improves thereon, and contracts for such projects with contractor(s) licensed pursuant to the Contractor's License Law).
I I I am exempt under Section Business and Professions Code for this reason:
1.1 personally plan to provide the major labor and matertals for constmction of the proposed property impravement. •Yes riNo
2.1 (have / have not) signed an application for a building pemiit for the proposed work.
3.1 have contracted with the following person (fimi) to provide the proposed constmction (include name address / phone / contractois' license number):
4.1 plan to provide portions of the wortt, but I have hired the following person to cooidinate, supenise and provide the major wortt (include name / addiess / phone / contractors' license number):
5.1 will provide some of the work, but I hayfe colitracterf (hired) the following peisons to provide the worit indicated (include name / address / phone / type of worit):
jeTpROPERTY OWNER SIGNATURE ^$7CGI ,GENT DATE
IDENTIAL BUILDING PERMITS Oti'lY
Is the applicant or future building occupant required to submit a business plan, acutely hazardous materials registration form or risk management and prevention program under Sections 25505,25533 or 25534 of the
Presley-Tanner Hazardous Substance Account Act? Yes No
Is the applicant or future building occupant required to obtain a permit from the air pollution control district or air quality management districf? Yes No
Is the facility lobe constracted within 1,000 feet of the outer boundary of a school site? Yes No
IF ANY OF THE ANSWERS ARE YES, A FINAL CERTiFiCATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR IS MEETING THE REQUIREMENTS OF THE OFFICE OF
EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT.
CONSTRUCTION LENDING AGENCY
I hereby affirm that there is a construction lending agency for the performance of the work this permit is Issued (Sec. 3097 (i) Civil Code).
Lender's Name Lender's Address
A, P.P' |., I .C A N T, C E R T I F I C A T I O i
I certify that I have lead the appikatkin and state that the above inlbmiation is conect and that the intbnnatxin on
I hereby authorize representative ofthe City of Carisbad to enter upon the above mentioned propefty Ibr inspection purposes. I ALSO AGREE TO SAVE, INDEMNIFY AND KEEP HARMLESS THE CITY OF CARLSBAD
AGAINST Aa UABILmES, JUDGMENTS, COSTS AND EXPENSES WHICH MAY IN ANY WAY ACCRUE AGAINST SAID CITY IN CONSEQUENCE OF THE GRANTING OF THIS PERMIT
OSHA: An OSHA pemiit is nequired fbr excavations over 5'0' deep and demolition or constmction of stmctures over 3 stories in height.
EXPIRATION: Every pernilt issued by the BuHding 0|liclal unrfer the provisions of this Code shall expire by limitatbn and become null and void if the building orwrit authorized by such pernilt Is not commenced within
180 days from the date of such pemnit or if the hpiid/g or vdk authorized by such pemnit is suspended or abandoned at any time after the wortt is commenced fbr a period ot 180 days (Section 106.4.4 Unifonn Building Code).
^eS*APPLICANT'S SIGNATURE DATE
STOP: THIS SECTION NOT REQUIRED FOR BUILDING PERMIT ISSUANCE.
Complete the following ONLY If a Certificate of Occupancy will be requested at final inspection.
Fax (760) 602-8560, Email buildinaiS)cai1sbadca.Q0V or Mail the completed form to City of Carisbad, Building Division 1635 Faraday Avenue, Carisbad, California 92008.
C0#: (Office Use Only)
CONTACT NAME OCCUPANT NAME
ADDRESS BUILDING ADDRESS
CITY ZIP CITY STATE
Carlsbad CA
PHONE FAX
EIVIAIL OCCUPANT'S BUS. LIC. No.
DELIVERY OPTIONS
PICK UP: CONTACT (Listed above) OCCUPANT (Listed above)
CONTRACTOR (On Pg. 1)
MAIL TO: CONTACT (Listed above) OCCUPANT (Listed above)
CONTRACTOR (On Pg. 1)
IVIAIL / FAX TO OTHER:
ASSOCIATED CB#-
NO CHANGE IN USE / NO CONSTRUCTION
CHANGE OF USE / NO CONSTRUCTION
.ef APPLICANT'S SIGNATURE DATE
Inspection List
Permit*: CB140680 Type: COGEN PHOTO
Date Inspection Item
07/08/2014 35 Photo Voltaic (PV)
07/08/2014 35 Photo Voltaic (PV)
07/08/2014 39 Final Electrical
07/08/2014 39 Final Electrical
Inspector Act
Rl
PB AP
Rl
PB AP
AGUA HEDIONDA LAGOON FOUND
INSTALL ROOF MNT PV SYSTEM 33 MOD
Comments
Wednesday, July 09, 2014 Page 1 of 1
EsGil Corporation
In PartnersAip witA government for BuiCding Safety
DATE: 04/21/2014 • APPLICANT
• JURIS.
JURISDICTION: City of Carlsbad • PLAN REVIEWER
• FILE
PLAN CHECK NO.: 14-0680 SET: II
PROJECT ADDRESS: 1580 Cannon Rd.
PROJECT NAME: Agua Hedionda Lagoon Proposed Roof Mounted 8 kW PV System
Existing 5 kW PV System
XI The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
I I The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
I I The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
I I The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
I I The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
I I The applicant's copy of the check list has been sent to:
Stellar Solar
EsGil Corporation staff did not advise the applicant that the plan check has been completed.
I I EsGil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: John Telephone #: 760-529-7267
Date contacted: (by: ) Email: john(5)stellarsolar.net Fax #:
Mail Telephone Fax In Person
• REMARKS:
By: Aaron Goodman Enclosures:
EsGil Corporation
• GA • EJ • MB • PC 04/14/2014
9320 Chesapeake Drive, Suite 208 • San Diego, Califomia 92123 • (858) 560-1468 • Fax (858) 560-1576
EsGil Corporation
In PartnersAip witA government for (BuiCding Safety
DATE: 04/07/2014 n, APPLICANT
JURISDICTION: City of Carlsbad • PLAN REVIEWER
\ At rf ^ "^"-E
PLAN CHECKNO.: i3=2944 IH ' OUyO SET. II
PROJECT ADDRESS: 1580 Cannon Rd.
PROJECT NAME: Agua Hedionda Lagoon Proposed Roof Mounted 8 kW PV System
Existing 5 kW PV System
I I The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's codes.
I I The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
I I The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
XI The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
I I The applicant's copy of the check list is enclosed for the junsdiction to fonward to the applicant
contact person.
X The applicant's copy of the check list has been sent to:
Stellar Solar
I I EsGil Corporation staff did not advise the applicant that the plan check has been completed.
1X1 EsGil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: John Telephone #: 760-529-7267
Date contacted:'^ll (by: Email: iohn(5).stellarsolar.net Fax #:
^Mail Telephone Fax In Person
• REMARKS:
By: Aaron Goodman Enclosures:
EsGil Corporation
• GA • EJ • MB • PC 04/01/2014
9320 Chesapeake Drive, Suite 208 • San Diego, Califomia 92123 • (858) 560-1468 • Fax (858) 560-1576
City of Carlsbad 13-2944
04/07/2014
1. Please make all corrections and submit two new complete sets of prints, to:
Esgil Corporation, 9320 Chesapeake Drive, Suite 208, San Diego, California 92123,
(858) 560-1468.
2. There is apparently an existing 5 kW PV System at this site. Please show the location of
the inverter, disconnects and modules on the plans.
3. The #8 grounding electrode conductor is required to be continuous to the rack. CEC
690.47 and 250.
4. To speed up the review process, note on this list (or a copy) where each correction item
has been addressed, i.e., plan sheet, note or detail number, calculation page, etc.
The jurisdiction has contracted with Esgil Corporation located at 9320 Chesapeake Drive, Suite
208, San Diego, California 92123; telephone number of 858/560-1468, to perform the plan
review for your project. If you have any questions regarding these plan review items, please
contact Aaron Goodman at Esgil Corporation.
Thank you.
City of Carlsbad 13-2944
, 04/07/2014
[DO NOT PAY- THIS IS NOT AN INVOICE]
VALUATION AND PLAN CHECK FEE
JURISDICTION: City of Carlsbad
PREPARED BY: Aaron Goodman
BUILDING ADDRESS: 1580 Cannon Rd.
PLAN CHECK NO.: 13-2944
DATE: 04/07/2014
Set I
BUILDING OCCUPANCY: B TYPE OF CONSTRUCTION: V
BUILDING
PORTION
AREA
( Sq. Ft)
Valuation
Multiplier
Reg.
Mod.
VALUE ($)
PV System
Air Conditioning
Fire Sprinklers
TOTAL VALUE
Jurisdiction Code Cb
Plan Check Fee by Ordinance
Type of Review:
By Ordinance
BIdg. Permit Fee by Ordinance ^^•l
• Complete Review/
$161.25
• Structural Only
D Repetitive Fee
~g Repeats
Based on hourly rate
• Other
g Hourly
EsGil Fee
1.5
$86.00
Hrs. @
$129.00
Comments:
Sheet 1 of 1
macvalue.doc +
CITY OF
CARLSBAD
PLANNING DIVISION
BUILDING PLAN CHECK
APPROVAL
P-29
Development Services
Planning Division
1635 Faraday Avenue
(760) 602-4610
ww/w/.carlsbadca.eov
DATE: 3/27/14 PROJECT NAME: SOLAR PANELS PROJECT ID:
PLAN CHECK NO: CB140680 SET#: ADDRESS: 1580 CANNON RD APN:
This plan check review is complete and has been APPROVED by the PLANNING
Division.
By: GINA RUIZ
A Final Inspection by the PLANNING Division is required • Yes ^ No
Vou may also have corrections from one or more of the divisions listed below. Approval
from these divisions may be required prior to the issuance of a building permit
Resubmitted plans should include corrections from all divisions.
[] This plan check review is NOT COMPLETE. Itenns missing or incorrect are listed on
the attached checklist. Please resubmit amended plans as required.
Plan Check APPROVAL has been sent to:
For questions or clarifications on tiie attached checklist please contact the following reviewer as marked:
PLANNING
760-602-4610
ENGINEERING
760-602-2750
FIRE PREVENTION
760-602-4665
1 Chris Sexton
760-602-4624
Chris.Sexton@carlsbadca.sov
[~] Kathleen Lawrence
760-602-2741
Kathleen.Lawrence@carlsbadca.^ov
1 Greg Ryan
760-602-4663
Gregory.Ryan@carlsbadca.gov
Gina Ruiz
760-602-4675
Glna.Ruiz@carlsbadca.gov
1 1 Linda Ontiveros
760-602-2773
Linda.Ontiveros@carlsbadca.fiov
Q Cindy Wong
760-602-4662
CYnthia.Wonfi@carlsbadca.gov
• 1 1 Dominic Fieri
760-602-4664
Dominic.Fieri@carlsbadca.fiov
Remarks:
^ CITY OF
CARLSBAD
PLAN CHECK
REVIEW
TRANSMITTAL
Community & Economic
Development Department
1635 Faraday Avenue
Carlsbad CA 92008
www.carlsbadca.gov
DATE: 04/22/14 PROJECT NAIVIE: agua hedionda pv system
PLAN CHECK NO: cbl40680 SET#: I ADDRESS: 1^^ nnon road
PROJECTID:
APN:
This plan check review is complete and has been APPROVE
By: cwong
A Final Inspection by the Division is required |^ Yes • No
e fire Division.
y
• This plan check review is NOT COMPLETE. Items missing or incorrect are listed on
the attached checklist. Please resubmit amended plans as required.
Plan Check Comments have been sent to:
You may also have corrections from one or more of the divisions Usted below. Approval
from these divisions may be required prior to the issuance of a buildmg permit.
Resubmitted plans should include corrections from all divisions.
For questions or clarifications on the attached checklist please contact the following reviewer as marked:
msRff!=siliit^ •
1 1 Chris Sexton
760-602-4624
Chrls.Sexton@carlsbadca.gov
1 1 Kathleen Lawrence
760-602-2741
Kathleen.Lawrence@carlsbadca.gov
1 1 Greg Ryan
760-602-4663
GregorY.RYan@carlsbadca.gov
1 1 Gina Ruiz
760-602-4675
Gina.Rulz@carlsbadca.fiov
1 1 Linda Ontiveros
760-602-2773
Linda.Ontlveros@carlsbadca.fiov
X Cindy Wong
760-602-4662
CYnthia.Wong@carlsbadca.fiov
• • 1 1 Dominic Fieri
760-602-4664
Dominic.Fieri@carlsbadca.gov
Page 1 of 3
x^^x PLANCHECK community & Economic
Development Department
•^5^ CITY OF KtVltW 1635 Faraday Avenue
AD\ CD A Pi TRANSMITTAL carisbad CA 92008
V^/»l\LOD/%Ly www.carlsbadca.gov
Page 2 of 3
**APPROVED:
THIS PROJECT HAS BEEN REVIEWED AND APPROVED FOR THE PURPOSES OF ISSUEANCE
OF A BUILDING PERMIT.
THIS APPROVAL IS SUBJECT TO FIELD INSPECTIONS, ANY REQUIRED TESTS, FIRE
DEPARTMENT NOTATIONS, CONDITIONS IN CORRESPONDENCE AND COMPLIANCE WITH
ALL APPLICABLE CODES AND REGULATIONS.
THIS APPROVAL SHALL NOT BE HELD TO PERMIT OR APPROVE ANY VIOLATION OF THE
LAW.
***Place the following note***
1. Lighting fixtures shall have an unobstructed vertical clearance of not less than 13 feet 6 inches (FD Access).
503.2.1 CFC 2014
Carlsbad Fire Department
Plan Review Requirements Category: COGEN , PHOTO
Date of Report: 04-22-2014 Reviewed by:
Name: TMAG INDUSTRIES DBA STELLAR SOLAR
Address: SUITE 105-444
6965 EL CAMINO REAL
CARLSBAD CA
92009
Pennit #: CB140680
Job Name: AGUA HEDIONDA LAGOON FOUND
Job Address: 1580 CANNON RD CBAD
INCOMIWLETE The item you have submitted for review is incomplete. At this time, this office cannot
adequately "-"ii In I 11 "1 I J^trrmiTT'"^rrfl'i'^"" with tiiP appiiVah|g p,pHpg gnH/nr ctanHarrlg Piffagp review
carefully all comments attached. Fli i i n iiinilil Iln iwi ""Ilj "T iii iinriii specifications, with changes "clouded",
to this office for review and approval
Conditions:
Cond: CON0007206
[MET]
** APPROVED:
THIS PROJECT HAS BEEN REVIEWED AND APPROVED FOR THE PURPOSES OF ISSUEANCE OF A
BUILDING PERMIT.
THIS APPROVAL IS SUBJECT TO FIELD INSPECTIONS, ANY REQUIRED TESTS, FIRE DEPARTMENT
NOTATIONS,
CONDITIONS IN CORRESPONDENCE AND COMPLIANCE WITH ALL APPLICABLE CODES AND
REGULATIONS.
THIS APPROVAL SHALL NOT BE HELD TO PERMIT OR APPROVE ANY VIOLATION OF THE LAW.
Entry: 04/22/2014 By: cwong Action: AP
CITY OF
CARLSBAD
PLAN CHECK REVISION
APPLICATION
B-15
Development Services
Building Division
1635 Faraday Avenue
760-602-2719
www.carlsbadca.gov
^an Check Revision No. Y \^ ^ ^ Original Plan Check No,
Project Address [^^O C—tw^ot^ Date
Contact^ &W\
Email ^o'^-^CP 'g -I e- ll otr o\ OWT.-^ ^ 4-
Contact Address 5\Q-'3- A^-c<^:d ^ City
^General Scope of Work 1^.^.U^o^ j ^ ('/i'^l^ '^^sA^^^
Original plans prepared by an architect or engineer, revisions must be signed & stamped by that person.
1 ir£lements revised:
"^lans • Calculations • Soils • Energy • Other
2.
Describe revisions in detail
3.
List page(s) where
each revision is
shown
4.
List revised sheets
that replace
existing sheets
1 I
\ /
5 • Does this revision, in any way, alter the exterior of the project? D Yes
6. Does this revision add ANY new floor area(s)? • Yes <^^[^No
7. Does this revision affect any fire related issues? DYes P^'No
8. Is this a comp\elMe\.l ^t^NYes • No
^Signature-
1635 FaradayAvenue, Carlsbad, CA 92008 PI3: 760-602-2719 Fax: 760-602-8558 Email: buiiding@carlsbadca.gov
www.carlsbadca.gov
06-24-2014
City of Carlsbad
1635 Faraday Av Carlsbad, CA 92008
Plan Check Revision Permit No:PCR14098
Building Inspection Request Line (760) 602-2725
Job Address:
Permit Type:
Parcel No:
Valuation:
Reference #:
PC#:
Project Title:
1580 CANNON RD CBAD
PCR
2081860500 Lot#:
$0.00 Construction Type:
CBI40680
Status: ISSUED
0
NEW
AGUA HEDIONDA LAGOON FOUNDATIO
N - REVISION TO TYE PV BREAKER INTO SUBPANEL
Applied:
Entered By:
Plan Approved:
Issued:
Inspect Area:
06/03/2014
SKS
06/24/2014
06/24/2014
Applicant:
STEMMERMAN JOHN
Owner:
AGUA HEDIONDA LAGOON FOUNDATION
5122 AVENIDA ENCINAS
CARLSBAD CA 92008
760-529-7267
1580 CANNON RD
CARLSBAD CA 92008
Plan Check Revision Fee
Fire Expedited Plan Review
Additional Fees
$161.25
$0.00
$0.00
Total Fees: $161.25 Total Paynnents To Date: $161.25 Balance Due: $0.00
Inspector:
FINAL APPROVAL
Date: Clearance:
NOTICE: Please take NOTICE that approval of your project Includes the "Imposition" of fees, dedications, reservations, or other exactions hereafter collectively
referred to as "fees/exactions." You have 90 days from the date this permit was issued to protest imposition of these fees/exactions. If you protest them, you must
follow the protest procedures set forth in Government Code Section 66020(a), and file the protest and any other required information vi/ith the City Manager for
processing in accordance with Carlsbad Municipal Code Section 3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack,
review, set aside, void, or annul their imposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection fees and capacity
changes, nor planning, zoning, grading or other similar application processing or service fees In connection with this project. NOR DOES IT APPLY to any
fees/exactions of which vou have previously been given a NOTICE similar to this, or as to which the statute of limitations has previouslv othenwise expired.
EsGil Corporation
In PartnersAip witA government for (BuiCding Safety
DATE: 06/13/2014 • APPLICANT
• JURIS.
JURISDICTION: City of Carlsbad • PLAN REVIEWER
• FILE
PLAN CHECK NO.: 14-0680(pcrl4-098) SET: IT
PROJECT ADDRESS: 1580 Cannon Rd.
PROJECT NAME: Agua Hedionda Lagoon Proposed Roof Mounted 8 kW PV System
Existing 5 kW PV System
I I The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's codes.
^ The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
I I The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
I I The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
I I The applicant's copy of the check list has been sent to:
Stellar Solar
EsGil Corporation staff did not advise the applicant that the plan check has been completed.
I I EsGil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: John Telephone #: 760-529-7267
Date contacted: (by: ) Email: iohn@stellarsolar.net Fax #:
Mail Telephone Fax In Person
XI REMARKS: Please transfer the clouded redlines on sheets PV-1 and PV-3 to all City sets prior
to issuing the permit. (I was able to clarify questions about this plan over the phone with the
applicant and use Set I.)
By: Aaron Goodman Enclosures:
EsGil Corporation
• GA • EJ • MB • PC 06/05/2014
9320 Chesapeake Drive, Suite 208 • San Diego, California 92123 • (858)560-1468 • Fax (858) 560-1576
EsGil Corporation
In PartnersAip witA government for (BuiCding Safety
DATE: 06/11/2014 • APPLICANT
B^JURIS.
JURISDICTION: City of Carlsbad • PLAN REVIEWER
• FILE
PLAN CHECK NO.: 14-0680(pcrl4-098) SET: I
PROJECT ADDRESS: 1580 Cannon Rd.
PROJECT NAME: Agua Hedionda Lagoon Proposed Roof Mounted 8 kW PV System
Existing 5 kW PV System
I I The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's codes.
I 1 The plans transmitted herewith will substantially comply with the jurisdiction's
codes when minor deficiencies identified below are resolved and checked by building
department staff.
I I The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
XI The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
I I The applicant's copy of the check list is enclosed for the jurisdiction to fonward to the applicant
contact person.
AI The applicant's copy of the check list has been sent to:
Stellar Solar
I I EsGil Corporation staff did not advise the applicant that the plan check has been completed.
EsGil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: John Telephone #: 760-529-7267
Date contacted:^! I'Z- (by^^f^J^ Email: iohn(S).stellarsolar.net Fax #:
IVIail Telephone Fax In Person
• REMARKS:
By: Aaron Goodman Enclosures:
EsGil Corporation
• GA • EJ • MB • PC 06/05/2014
9320 Chesapeake Drive, Suite 208 • San Diego, Califomia 92123 • (858) 560-1468 • Fax (858) 560-1576
City of Carlsbad 14-0680(pcrl4-098)
06/11/2014
1. Please make all corrections and submit two new complete sets of prints, to:
Esgil Corporation, 9320 Chesapeake Drive, Suite 208, San Diego, California 92123,
(858) 560-1468.
2. There is apparently an existing 5 kW PV System at this site. Please show the location of
all existing and proposed inverters, disconnects and modules on the plans.
3. The inverter that complies with the DC arc fault requirement is SMA 8000-US-12. Please
correctly identify this inverter on the plans.
4. The single line sheet, PV-3, is only showing an 8 kW inverter and a 40 breaker. Where is
the inverter located that was permitted under 132944?
5. Where are the modules located that were permitted under 132944?
6. What size breaker was used for the inverter permitted under permit number 132499?
7. Where is that breaker located?
8. To speed up the review process, note on this list (or a copy) where each correction item
has been addressed, i.e., plan sheet, note or detail number, calculation page, etc.
The jurisdiction has contracted with Esgil Corporation located at 9320 Chesapeake Drive, Suite
208, San Diego, California 92123; telephone number of 858/560-1468, to perform the plan
review for your project. If you have any questions regarding these plan review items, please
contact Aaron Goodman at Esgil Corporation.
Thank you.
City of Carlsbad 14-0680(pcrl4-098)
06/11/2014
[DO NOT PAY- THIS IS NOT AN INVOICE]
VALUATION AND PLAN CHECK FEE
JURISDICTION: City of Carlsbad PLAN CHECK NO.: 14-0680(pcrl4-098)
PREPARED BY: Aaron Goodman DATE: 06/11/2014
BUILDING ADDRESS: 1580 Cannon Rd. Set I
BUILDING OCCUPANCY: B TYPE OF CONSTRUCTION: V
BUILDING
PORTION
AREA
(Sq.Ft.)
Valuation
Multiplier
Reg.
Mod.
VALUE ($)
PV System
Air Conditioning
Fire Sprinklers
TOTAL VALUE
Jurisdiction Code cb By Ordinance
BIdg. Permit Fee by Ordinance ^•J
Plan Check Fee by Ordinance
Type of Review: • Complete Review
$161.25
• structural Only
I I Repetitive Fee
^ j Repeats
Based on hourly rate
• Other
• Hourly
EsGil Fee
1.5
$86.00
Hrs. @
$129.00
Comments:
Sheet 1 of 1
macvalue.doc +
>Stellar Solar
San Diego's Best Solar
City of Carlsbad
Plan check no.: 14-0680
Project address 1580 Cannon Rd.
To whom it may concern.
The reason for this plan change is that the 40A 2-pole breaker shown in the previous submittal (tying
into the main service gear) is not actually manufactured/available. However, the existing 200A subpanel
in the electrical room had available breaker space and adequate wire size back to the main service gear
to add our PV breaker. The change in this plan submittal is tying our PV breaker into that subpanel. No
other changes are included in this submittal. ——
Sincerely,
Hector H. Holguin
Designer, Stellar Solar RECEIVED
JUN 0 3 2014
CITY OF CARLSBAD
BUILDING DIVISION
6965 El Camino Real, Suite 105-444 • Carlsbad, CA 92009
Phone: (866) 787-6527 • Fax: (760) 603-8964
www.stellarsolar.net