HomeMy WebLinkAbout1600 FARADAY AVE; ; CB982562; Permit09/28/98 11:16
Page 1 of 1
B U I L D I N G P E R M I T Permit No: CB982562
Project No: A9803380
Development No:
Job Address: 1600 FARADAY AV
Permit Type: INDUSTRIAL TENANT
Parcel No! 212-130-42-00
Jl.~luation: 157,472
IMPROVEMENT
Suite:
Lot#: 1570 09/28/98 0001 01 02
C-PRMT 1098u00 Construction Type: "NEW
Occupancy Group:
Description: ITI
: R &
,Reference#:
5624 SF-OFFICE,LIGHT MANU
D
Status: ISSUED
Applied: 08/13/98
Apr/Issue: 09/28/98
Entered By: JM
Appl/Ownr : KINOSUTA MICHAEL
2211 CAMBRIDGE AVE
760 603-0833
CARDIFF BY THE SEA CA 9200'2 . ..._ ..
*** Fees Required *** _,,-,-¾"*~*---Fees··GQllected & Credi ts ***
----------------------------//-------,,,0.--:.:---' ------»------------------------/ ,/) 1! :',' ,·,., ~ Fees : 1 , 6 3 4 . 0 o. , c, ,. ·. 1• / t,_, • ' , -, , ~
/'. , ••. \ / .. '...., \ •·' ! " ' Adjustments: .)30 r~,,·-<'\\ -·.1.Cit~J{,1.qr~di ts:, . 00
Total Fees: 1, 631,t: 00 \ \_-~~> ,, -Total Paf~E:11~t;! \ 536. 00
/ \ '·-· / ,-,:;;;..,. __ Ba;J..:,9-~e\ Due,:" \ 1, o 98. o o
Fee description / :~-~::, // "':~f/.1; .-.1:':~\t'S ',,f~<5~it\ Ext fee Data ----------------------1 -',, ---:--------., v·\. ------« ·-~----~\ _______________ _
Building Permit / ~ /1
'~:-~ .... ·..-:.::::::-::::.:.-:::~·~:::::-::.-:;;;, ,<7 \ C:1-;-·) \ 824. 00 Plan Check I C,·---. '-"""'~-.:-··.::::.·:--:::-:-,, .-<;:> ' }// \ 536.00
I ---..) I '\ ' -~'-' .,..;, / ;::--\ " I,
Strong Motion Fee ! (( ·;·-, i "", · .. i;..~,.} ..-'/ ~]\ r;:: .. ~; \ 33. 00
Enter "Y II for Plumb if' q \l-s-s6.11
Fee 1>"' ,.. ·..._ ,/ /'2 l \ \...J 1 i 20. oo Y -........-' 1 ' ~ ~-,7 --/ J;._ ' '-.. / I Each Plumbing Fixtur. or Tr P\~ /1 11 ·, f-7, :; s:-~"~ /7. 0·0 I 35. 00
Each Install/Repair 1/~ater Li\r~'"',)/L '\m~1 {1J~f ,17,00 j 7.00
Gas Piping System \ \ ·,. <~ b·{ ti Q"i ·&:· / 7. 00 / 7. 00
Enter 11 Y11 for Electric Issue Fee )j"-.:.:., i,'{ff,-{--· 9-/ 1, 10.00 Y
Remodel/Alter Per AMP \ _ ~ (,_;> J\if ,_400 / . 25 100. 00 • -e.\ ,..-· ',. ~ .... INCORPORATED /.. /'-·,
I
Enter 'Y' for Mechan1ca9, I~fu:e 1-'e~~ 1a:5z ,,,/ ,. \\)::;) / 15.00 Y
Install Furn/Ducts/Heat 'p~ump~-~; ~'-·--_> _ .. -___ ,,, 3 \'\\\;9. oi 27. oo
Each Exhaust Fan ...,. .. ,<! l>r:-·~ ,.---·,j\--;::,\\> "'6/50 19.50
#"-' / j / ..... .,.... .. ''\ \ 0 ' '\ "'-.-~ ,/'
I ''-.. ; I '. : ( \ > \; /
I "'--., '· ' _.,I, / "'""... ....__,_,..,~ .,.,,,.,,,,.,.,.,.,..,,,,
.......... ~--·--·--... ,_ ,~ ... .,.._ -... -·· ....
,------__,______ ....
FINAL APPRovAc--
lNSP.:::L:itW DATE /~ _
CLEARANCE=====~~---'
CITY OF CARLSBAD
2075 Las Palmas Dr., Carlsbad, CA 92009 (619) 438-1161
V ·ll7c{v
PERMIT APPLICATION
CITY OF CARLSBAD BUILDING DEPARTMENT
2075 Las Palmas Dr., Carlsbad CA 92009
(760) 438-1161
FOR OFFICE USE O~
PLAN CHECK NO. LfJ 25' 0~
EST. VAL. t~Lf72.-, .
Plan Ck. Deposit s:10uQ) ~:~:ated By J~!if /2, ~~a
0073 08/13/98 0001 01 02
Unit No. Phase No. Total # of units
.. ~.1\..
-'-CJ\.
City State/Zip Telephone# Fax#
Name
:!h ,JlQl'\!tM.9t9!L·J::p_wp~!\I.Y'N~M.!: .. ··--·---·-· ., ... · ..... H'h'"',"" ,; H,,,v,,,-,,' , ,,,_ ,' --:;; '~-
(Sec. 7031.5 Business and Professions Code: Any City or County which requires a permit to construct, alter, improve, demolish or repair any structure, prior to its
issuance, also requires the applicant for such permit to file a signed statement that he is licensed pursuant to the provisions of the Contractor's License Law
[Chapter 9, commending with Section 7000 of Division 3 of the Business and Professions Code) or that he is exempt therefrom, and the basis for the alleged
exe ption. A violaf n f Se ion 7031.~by.~ c!J;Pli; rt for a permit su jects the applicant to a civil penalty JU not more than five hundred dollars ($5001). , _ e-~ -1-1 vi ~ r c ~ )6 , 9-7: 7 c;,, ----/ Address ,'0 City ~ State/Zip 6 ....._ Tel~one #
State License# <;;,L_ · 7 Vt, License Class __ _,, . .!,;L_="''-------City Business License# // 7_:::J;::[,? 3
Designer Name Address City
State License # _________ _
\6~~woR~ERS~ .QOMPEl\lfATIJ:[N'-N,h, _, q_,_,._ .. "'"'-~~ ,.,, "" "q_,,,. .... ,.,, ----«-~,M'"<vn-"~-~ __ -.,., ''., ,,,~, ---=~---VH ----,. _ ,
Workers' Compensation Declaration: I hereby affirm under penalty of perjury one of the following declarations:
State/Zip Telephone
0 I have and will maintain a certificate of consent to self-insure for workers' compensation as provided by Section 3700 of the Labor Code, for the performance
of the work for which this permit is issued.
~/4ave and will maintain workers' compensation, as required by Section 3700 of the Labor Code, for the performance of the work for which0hi permit is
issued. My worker's 19~1:iensation ins~n?!carrier and policy number are: . /, ,,fr,. / / ~"> /...,! J.-,,_, . . / 0 fl~ (-
Insurance Company l/ f/n()es .,U ti:/1@ Policy Not.A..,/~[; J / <f'~./ Exp1rat1on Date • '--f rr--
(THIS SECTION NEED NOT BE COMP ED F THE PERMIT IS FOR ONE HUNDRED DOLLARS [$100) OR LESS)
D
WARNING: Failure to secure wo rrs' co ensation co er e i nlawful, and shall subject an employer· to criminal penal ·es and civil fines up to one hundred
thousand dollar~ ($100,000), in ii 1tio · he est o m ens ti n, damages as provided for in Section 3706 of the bor ode,lm ~a attorney's fees.
SIGNATUi'i:!~,__--:_.:...;_':..-:..-::.~1-u.-1.1-"'~~'-1+::;.._-=----"<--+-----------DATE 1/, cQ. O I T
ii,::. ':::_q,VV.N!L '.!J'.l:i~@~JJL.tt .N".' ~:: -~~·:. '~::.'.':.:·.: ... ·"':: ::.:_::_::::>.~ .. ·-.. ~ ... :, . -.... ... .. ,_ .. ... .. · ' .::.,,.: ..
I hereby affirm that I am exempt from the Contractor's License L for the following reason:
0 I, as owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not intended or offered for sale
(Sec. 7044, Business and Professions Code: The Contractor's License Law does not apply to an owner of property who builds or improves thereon, and who does
such work himself or through his own employees, provided that such improvements are not intended or offered for sale. If, however, the building or improvement is
sold within one year of completion, the owner-builder will have the burden of proving that he did not build or improve for, the purpose of sale).
0 I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions Code: The
Contractor's License Law does not apply to an owner of property who builds or improves thereon, and contracts for such projects with contractor(s) licensed
pursuant to the Contractor's License Law).
D I am exempt under Section ______ Business and Professions Code for this reason:
1. I personally plan to provide the major labor and materials for construction of the proposed property improvement. D YES ONO
2. I (have / have not) signed an application for a building permit for the proposed work.
3. I have contracted .with the following person (firm) to provide the proposed construction (include name / address / phone number / contractors license ,number):
4. I plan to provide portions of the work, but I have hired the following person to coordinate, supervise and provide the major work (include name / address / phone
number/ contractors license number): _____________________________________________ _
5. I will provide some of the work, but I have contracted (hired) the following persons to provide the work indicated (include name / address / phone number / type of work): _______________________________________________________ _
PROPERTY OWNER SIGNATURE _____________________ _
~~Q.M~(i;ttI!:!!$ .si¢I:!Q!if fQS:@tv.:Rtef«?ll'Ntl~I'~!iJ,P!N~·P!IR.refit$ Q~~Y::L ~
Is the applicant or future building occupant required to submit a business plan, acutely hazardous materials registration form or risk management and prevention
program under Sections 25505, 25533 or 25534 of the Presley-Tanner Hazardous Substance Account Act? 0 YES O NO
Is the applicant or future building occupant required to obtain a permit from the air pollution control district or air quality management district? D YES D NO
Is the facility to be constructed within 1,000 feet of the outer boundary of a school site? 0 YES O NO
IF ANY OF THE ANSWERS ARE YES, A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR IS MEETING THE
REQUIREMENTS OF THE OFFICE OF EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT.
rt~::,,,£Q~~i:a®t•9fi,\~lN~A~N9Y~~ , ___ ----~ _ ~ _ .:,:~ ~ , __ ~ '~~ -~ ~~--,,: _-_ ~ ~ ~~~ N_-__ ---, ~--~ -,_ -
I hereby affirm that there is a construction lending agency for the performance of the work for which this permit is issued (Sec. 3097(i) Civil Code).
LENDER'S NAME
I certify that I have read the application and state that the above information is correct and that the information on the plans is accurate. I agree to comply with all
City ordinances and State laws relating to building construction. I hereby authorize representatives of the Citt of Carlsbad to enter upon the above mentioned
property for inspection purposes. I ALSO AGREE TO SAVE, INDEMNIFY AND KEEP HARMLESS THE CITY OF CARLSBAD AGAINST ALL LIABILITIES,
JUDGMENTS, COSTS AND EXPENSES WHICH MAY IN ANY WAY ACCRUE AGAINST SAID CITY IN CONSEQUENCE OF THE GRANTING OF THIS PERMIT.
OSHA: An OSHA permit is requir d for excavations over 5'0" deep and demolition or construction of structures over 3 stories in height.
EXPIRATION: Every permit is by the Building O i 1al under the provisions of this Code shall expire by limitation and become null and void if the building or
or abandoned at any time af r e r mme ce f a period of 180 days (Section 106.4.4 Uniform Building Code). -;-/,
work authorized by such per I not · ced it in 365 days from the date of such permit or if the building or work authorize~d bv, such permit is suspended
APPLICANT'S SIGNATURE ~'-"-''..:c.4 _',.c.''-i,''""/~-V"--111-'-+--'<s:'-..::--------------DATE fl j~~
WHITE: File YELLOW: Applicant PINK: Finance
PERMIT# CB982562
DESCRIPTION: ITI 5624 SF-
R & D
CITY OF CARLSBAD
INSPECTION REQUEST
FOR 11/20/98
OFFICE,LIGHT MANU
INSPECTOR AREA TP
PLANCK# CB982562
OCC GRP
TYPE: ITI
JOB ADDRESS: 1600 FARADAY AV
APPLICANT: KINOSUTA MICHAEL .
CONTRACTOR:
OWNER:
REMARKS: C/TERRY/801-1993
SPECIAL INSTRUCT:
TOTAL TIME:
--RELATED PERMITS--PERMIT#
FS960022
AS960069
FS970002
WM970001
CO970003
TYPE
FIXSYS
ASC
FIXSYS
WMETER
COFO
STE:
CONSTR. TYPE NEW
LOT:
PHONE: 760 603-0833
PHONE:
PHONE: /7
INSPECTOR r --,<,i,,----------
STATUS
ISSUED
ISSUED
ISSUED
ISSUED
ISSUED
CD LVL DESCRIPTION ACT COMMENTS
19 ST Final Structural £ ------'-----------29 PL Final Plumbing
39 EL Final Electrical
49 ME Final Mechanical += ----
------------------
------------------------------------
***** INSPECTION HISTORY*****
DATE
111698
111398
111298
110998
110998
110998
110598
110598
110598
110598
103098
102998
101398
100998
100298
100298
100298
093098
092998
DESCRIPTION
Final Combo
Final Combo
Final Combo
Frame/Steel/Bolting/Welding
Rough Electric
Rough/Ducts/Dampers
Frame/Steel/Bolting/Welding
Rough Electric
Rough/Ducts/Dampers
Frame/Steel/Bolting/Welding
Rough Combo
Rough Combo
Interior Lath/Drywall
Interior Lath/Drywall
Rough Electric
Rough/Topout
Frame/Steel/Bolting/Welding
Ftg/Foundation/Piers
Underground/Under Floor
ACT
co
NR
NR
AP
AP
AP
AP
AP
AP
AP
NR
CA
AP
AP
AP
AP
AP
AP
AP
INSP
TP
TP
TP
TP
TP
TP
TP
TP
TP
TP
TP
TP
DH
TP
TP
TP
TP
TP
TP
COMMENTS
SEE NOTICE ATTACHED
T-BAR CEIL 2ND FLR CONF RM
CEIL LITES 2ND FLR CONF RM
DUCTS CEIL 2ND FLR CONF RM
T-BAR GRID 1ST FLR
CEIL LITES 1ST FLR
DUCTS,PLMNS 1ST FLR
ROOF STRUCT REINF@ NEW UNIT
CEIL NOT COMP.
SEE CARD
WALLS
SLAB PREP ND 3000 PSI VERF.
~/
FINAL BUILDING INSPECTION
DEPT: BUILDING ENGINEERING cE.rl.l~ PLANNING CMWD ST LITE
PLAN CHECK#: CB982562
PERMIT#: CB982562
PROJECT NAME: ITI 5624 SF-OFFICE,LIGHT MANU
R & D
ADDRESS: 1600 FARADAY AV
CONTACT PERSON/PHONE#: C/801-1993
SEWER DIST: CA WATER DIST: CA
INSPECTED
BY: fU · $/A.hi, b1.14/JA.l
INSPECTED
BY:
INSPECTED
BY:
COMMENTS:
DATE
INSPECTED:
DATE
INSPECTED:
DATE
INSPECTED:
!_t. &_o If K t I
DATE: 11/12/98
PERMIT TYPE: ITI
: ... :: 1: 1998
APPROVED ---1):: DISAPPROVED
APPROVED DISAPPROVED
APPROVED DISAPPROVED
EsGil Corporation
'l.n Partnersliip witli (]overnment for '.Buifaing Safetg
DATE: 9 /21/98
JURISDICTfON: Carlsbad
PLAN CHECK NO.: 98-2562
PROJECT ADDRESS: 1600 Faraday
PROJECT NAME: Invitrogen TI
SET: III
D APPLICANT . ..,,o~ru~
~"'"Pt:;ii:N REVIEWER
D FILE
• The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
D The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
D The applicant's copy of the check list has been sent to:
• Esgil Corporation staff did not advise the applicant that the plan check has been completed.
D Esgil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Telephone#:
Date contacted: (by: ) Fax #:
Mail Telephone Fax In Person
• · REMARKS: .The additional sheets M-1,M-3 & M~ must be incorporated into the city set of
plans to make a second set of .approved plans.
By: Chuck Mendenhall
Esgil Corporation
D GA D MBi D EJ D PC _-1 . walk in trnsmtl.dot
9320 Chesapeake Drive, Suite 208 + San Diego, California 92123 + (619) 560-1468 + Fax (619) 560-1576
EsGil Corporation
'l.n Partnersliip witli {jovemment for 'lJuilifing Safetg
DATE: 9 / 17 / 98
JURISDICTION: Carlsbad
PLAN CHECK NO.: 98-2562
PROJECT ADDRESS: 1600 Faraday
PROJECT NAME: Invitrogen TI
SET: II
D APeblCANT (Q JURIS)
D PLAN REVIEWER
D FILE
D The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
• The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
• The applicant's copy of the check list has been sent to:
Michael Kinoshita, AIA
2211 Cambridge Way, Cardiff, CA 92007
• Esgil Corpo_ration staff did not advise the applicant (except by mail) that the plan check has been
completed.
D Esgil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Telephone#:
Date contacted: CJ/;~ (by: ...-?Z,) Fax #:
Mail/ Telephone Fax In Person
D REMARKS:
By: Chuck Mendenhall
Esgil Corporation
• GA O MB O EJ O PC
Enclosures:
9/8/98 trnsmtl.dot
9320 Chesapeake Drive, Suite 208 + San Diego, California 92123 + (619) 560-1468 + Fax (619) 560-1576
Carlsbad, 98-2562, Set II
Date: 9/17/98
Note: The items listed below refer to the item numbers form the previous list. These remaining items
have not been adequately addresses. The note in bold at the end of each item is to emphasize the
remaining problem.
• MECHANICAL
1. Specify on the plans the max quantities of chemicals that will be in open use. The report
submitted assumes that all the chemicals listed are in storage. The max quantities in open use
are much more restrictive than the storage quantities.
A. Detail exhaust ventilation system compliance with UMC Chapters 5 & 6.
1. Detail the required make-up air as per UMC, Section 505.6. The make-up air
must be outside air for the exhaust hoods. The quantities quoted in the
response is the supply. This supply air is recirculated air for the most part.
2. Detail the exhaust outlet clearances as per UMC, Section 609.10. EF-2 is
located within 10' of existing HP and EF-1 is located within 10' of GH-1. See
sheet M-4 Mechanical roof plan.
3. Clearly show the duct materials are suitable for the intended use. UMC, Section
609.1 the ducts conveying corrosives must have cleah outs every 10' and at
every change in direction.
4. Clearly show the exhaust duct material and gage used for each duct size. See
UMC, Table 5-8. The GA and duct material is listed on sheet M-3 but there
isn't enough information on the plans to determine whether the sizing is
correct or the spacing of supports required. You must include the negative
pressure and the support spacing in accordance with UMC Table 5-B
5. Detail minimum duct conveying velocities as per UMC, Section 505.4 and Table
5-A. No response to this item
To speed up the review process, note on this list (or a copy) where each correction item has
been addressed, i.e., plan sheet, note or detail number, calculation page, etc.
The jurisdiction has contracted with Esgil Corporation located at 9320 Chesapeake Drive,
Suite 208, San Diego, California-92123; telephone number of 619/560-1468, to perform the
plan review for your project. If you have ahy questions regarding these plan review items,
please contact Glen Adamek at Esgil Corporation. Thank you.
EsGil Corporation
1.n Partnersfiip witfi (Jovemment for '.BuiUing Safety
DATE: 8/26/98
JURISDICTION:. Carlsbad
PLAN CHECK NO.: 98-2562
PROJECT ADDRESS: 1600 Faraday
PROJECT NAME: Invitrogen TI
SET:I
D APPLICANT
e:::JUR~
D PLAVIEWER
D FILE
D The plans transmittec;i herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department
staff.
D · The plans transmitted herewith have significant ds3ficiencies identified on the enclosed check list
and should be corrected an~ resubmitted for a complete recheck.
• The check list tra~smitted .. her~with is for your information. The plans are bei.ng held at Esgil
Corporation until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
• The applicant's copy of the check list has been sent to:
Michael Kindshita; Architect
2211 Cambridge Way, Cardiff, CA 92007
• Esgil Corporation staff did not advise the applicant (except by mail) that the plan check has
been completed.
D Esgil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Telephone#:
Date contacted: &/,z,1 /tJPJ (by:P.>1"1,..-) Fax #:
Mail / Telephone
D REMARKS:
Fax In Person
By: Chuck Mendenhall
Esgil Corporation
D GA [] CM D EJ D PC
Enclosures:
8/17/98 trnsmtl.dot
9320 Chesapeake Drive, Suite 208 + San Diego, California 92123 + (619) 560-1468 + Fax (619) 560-1576
Carlsbad 98-2562
8/26/98
PLAN REVIEW CORRECTION LIST
TENANT IMPROVEMENTS
PLAN CHECK NO.: 98-2562
OCCUPANCY: B
TYPE OF CONSTRUCTION: III N
ALLOWABLE FLOOR AREA:
SPRINKLERS?: yes
REMARKS:
DATE PLANS RECEIVED BY
JURISDICTION:
JURISDICTION: Carlsbad
USE: R &D and offices
ACTUAL AREA: 5624 TI Only
STORIES: two
HEIGHT:
OCCUPANT LOAD: 75
DATE PLANS RECEIVED BY
ESGIL CORPORATION: 8/17/98
DATE-INITIAL PLAN REVIEW,.
COMPLETED: 8/26/98
PLAN REVIEWER: Chuck Mendenhall
FOREWORD (PLEASE ~EAD):
This plan review is limited to the technical requirements contained in the Uniform Bu_ilding
Code, Uniform Plumbing Code, Uniform Mechanical Code, National Electrical Code and state
laws regulating energy conservation, .noise attenuation and access for the disabled. This plan
review is based on regulations enforced by t_he Building Department. You may have other
corrections based on laws and ordinances enforced by the Planning Department, Engineering
Department, Fire Department or other departments. Clearance from those departments may be
required prior to the issuance of a b~ilding permit.
Code sections cited are bas~d on the 1994 UBC.
The following items listed heed clarification, modification or change. All items must be satisfied
before the plans will be in conformance with the cited codes and regulations. Per Sec. 106.4.3,
1994 Uniform Building Code, the approval of the plans does not permit the violation of any
state, county or city law.
To speed up the recheck process, please note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet number, specification section, etc.
Be sure to enclose the marked up list when you submit the revised plans.
LIST NO. 40, TENANT IMPROVEMENTS WITHOUT SPECIFIC ENERGY DATA OR POLICY SUPPLEMENTS (1994UBC) tiforw.dot
Carlsbad 98-2562
8/26/98
1. Please make all corrections on the original tracings, as requested in the
correction list.
Submit three sets of plans for commercial/industrial projects ·(two sets of plans
for residential projects). For expeditious processing, corrected sets can be
submitted in one of two ways:
1. Deliver all corrected sets of plans and calculations/reports directly to
the City of Carlsbad Building Department, 2075 Las Palmas Drive, Carlsbad, CA
92009, (619) 438-1161. The City will route the plans to EsGil Corporation and
the Carlsbad Planning, Engineering and Fire Departments.
2. Bring one corrected set of plans and calculations/reports to EsGil
Corporation, 9320 Chesapeake Drive, Suite 208, San Diego, CA 92123, (619)
· 560-:1468. Deliver all remaining sets of plans and calculations/reports __ directly to
the City of Carlsbad Bl:lilding Department for routing to their Planning,
Engineering and Fire Departments.
NOTE: Plans that are submitted directly to EsGil Corporation only will not
be reviewed by the City Planning, Engineering and Fire Departments until review
by EsGil _Corporation is complete.
2. Each.sheet of the plans must be signed.by the person responsible for their
_ preparation, even though there are no structural changes. Business and
Professions Code. This applies to plumbing, rriech and electrical· plans.
3. Provide a note on the plans indicating if any hazardous materials will be stored
and/or used within the building which exceed the quantities listed in UBC Tables
3-D and 3-E. ·
4. A complete description of the activities and processes that will occur in this
tenant space should be provided. A listing of all hazardous materials should be
included. The materials listing should be stated in a form that would make
classification in Tables 3-D and 3-E possible. The building official may require a
technical report to identify and develop methods of protection from hazardous
materials. Section 307.1.6.
5. Glazing in the following locations should be of safety glazing material in accordance
with Section 2406.4 ;
• Windows at the second floor offices that are within 24" of the door.
6. Note on the plans: "All exits are to be openable from inside without the use of a key
or special knowledge."
• DEPARTMENT OF STATE ARCHITECT NON RESIDENTIAL
TITLE 24 DISABLED ACCESS REQUIREMENTS
7. Show or note that all hand-activated door opening hardware meets the following
requirements, per Section 1004.3.1: ·
Carlsbad 98-2562
8/26/98
a)
b)
Is to be centered ~30" but ~44" above floor.
Latching, or locking, doors in a path of travel are operated with a single
effort by:
i) Lever-type hardware.
ii) Panic bars.
• COUNTERS AND TABLES
8. The tops of tables _anq counters shall be 28" to 34" from the floor. Where_ a
single counter contains more than one transaction station, such as a bank
counter with multiple teller window or a retail sales counter with multiple cash
register stations, at le.ast 5% (but never less than one of each type .. of station)
shall be located ·at a section of counter that is at least 36" long and no more than
28" to 34" high. Section 11228.4.-See the counter eleva,tions on sheet A-8 of
the plans.
• MECHANICAL
9. Detail overflow (secondary) condensate discharge from air conditioning units
that are 111 a ceiling ·space, to a readily observable location. (UMC Section
310.1.1.) .
a) In Groups 8, F, M, and S Occupancies, or portions thereof, where Class I,
II, or Ill-A liquids are used (in any amount), mechanical exhaust shall be
provided sufficient to produce six air changes per hour. Such mechanical
exhaust shall be taken from a point at or near the floor. U8C, Section
1202.2.2. Do you intend to use any quantities of Class I, II or Ill-A
liquids?
b) Detail exhaust ventilation system compliance with UMC Chapters 5 & 6.
i) Detail the required make-up air as per UMC, Section 505.6.
ii) Detail the exhaust outlet clearances as per UMC, Section 609.10.
iii) Clearly show the type of material to be exhausted by each exhaust
system.
iv) Clearly show the duct materials are suitable for the intended use.
UMC, Section 609.1
v) Clearly show the exhaust duct material and gage used for each
duct size. See UMC, Table 5-8.
vi) Detail ducts conv~ying explosives or flammable vapors, fumes or
dusts shall extend directly to the exterior of the building without
entering other spaces. UMC, Section 505.1.
Carlsbad 98-2562
8/26/98
vii) Detail minimum duct conveying velocities as per UMC, Section
505.4 and Table 5-A.
• ENERGY
10. show on the plans that the existing exterior concrete walls will be insulated with
R-11. See the energy design form ENV-1
To speed up the review process, note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet, note or detail number,
calculation page,· etc.
Please indicate here if any changes have been made to the plans that are not a
result of corrections from this list. If there are o"ther changes, please briefly
describe them and where they a~e located in the plans.
Hav~ changes been made to the plans not resulting from this correction
: list? Please indicate: .
;-:, ..
Yes D No D
The jurisdiction has contracted with Esgil Corporation located at 9320
Chesapeake Drive, Suite 208, San Diego, California 92123; telephone number
of 619/560-1468, to perform the plan review for your project. If you have any
questions regarding these plan review items, please contact Chuck Mendenhall
at Esgil Corporation. Thank you. ·
Carlsbad 98-2562
8/26/98
VALUATION AND PLAN CHECK FEE
JURISDICTION: Carlsbad PLAN CHECK NO.: 98-2562
DATE: 8/26/98 PREPARED BY: Chuck Mendenhall
BUILDING ADDRESS: 1600 Faraday
BUILDING OCCUPANCY: B TYPE OF CONSTRUCTION: III N
BUILDING PORTION BUILDING AREA VALUATION VALUE
(ft. 2) MULTIPLIER ($)
Tl 5624 28 157,472
--
,,
-
Air Conditioning
Fire Sprinklers
" ' -
TOTAL VALUE 157,472
D 199 UBC Building Permit Fee • Bldg. Permit Fee by ordinance: $ 824.07
D 1·99 UBC Plan Check Fee • Plan Check Fee by ordinance: _ $ 535.64
Type of Review: • Complete Review D Structural Only D Hourly
D Repetitive Fee Applicable D Other:
Esgil Plan Review Fee: $ 329.62
Comments:
Sheet 1 of 1
macvalue.doc 5196
" ---..
City of Carlsbad
•¥ih•11 h441 1li·l•l4•kiiii,t4,il
DATE: 8/';f/l'f~
BUILDING ADRESS:
BUILDING PLANCHECK CHECKLIST
PLANCHECK NO.:
PROJECT DESCRIPTION:
ASSESSOR'S PARCEL NUMBER: t:PJJ. -/ .30 -ol.5
ENGINEERING DEPARTMENT
APPROVAL
EST. VALUE: /S7, L/7/l
I
DENIAL
The item you have submitted for review has been
approved. The approval is based on plans,
information and/or specifications provided in your
submittal; therefore any changes to these items after
this date, including field modifications, must be
reviewed by this office to insure continued
conformance with applicable codes. Please review
carefully all comments attached, as failure to comply
with instructions in this report can result in
suspension of permit to build.
CA Right-of-Way permit is required prior to
construction of the following improvements:
Please see~h attached report of deficiencies
marked with . Make necessary corrections to plans
or specificati s for compliance with applicable
codes and standards. Submit corrected plans and/or
specifications to this office for review.
~~
By.
Date: ~
Date:
By: Date:
FOR OFFICIAL USE ONLY
ENGINEERING AUTHORIZATION TO ISSUE BUILDING PERMIT:
D
D Dedication Checklist
D Improvement Application
D Improvement Checklist
D Future Improvement Agreement
D Grading Permit Application
D Grading Submittal Checklist
D Right-of-Way Permit Application
O Right-of-Way Permit Submittal Checklist
and Information Sheet
D Sewer Fee Information Sheet
Date:
ENGINEERING DEPT. CONTACT PERSON
Name: JOANNE JUCHNIEWICZ
City of Carlsbad
Address: 2075 Las Palmas Dr., Carlsbad, CA 92009
Phone: (619)438-1161,ext.4510
CFD INFORMATION
Parcel Map No:
Lots:
Recordation:
Carlsbad Tract:
A-4
H:1woRm~1175-s~S1gp!!mF'l"l~Ss@)t1.Fam@-arlsbad, CA 92009-1j576 • (760) 438-1161 • FAX (760) 4'@.121:§!lY69
0
BUILDING PLANCHECK CHECKLIST
SITE PLAN
2ND,/ 3RD,/
0 0 1. Provide a fully dimensioned site plan drawn to scale. Show:
0
0 0
A. North Arrow D. Property Lines
B. Existing & Proposed Structures E. Easements
C. Existing Street Improvements F. Right-of-Way Width & Adjacent Streets
G. Driveway widths
2. Show on site plan:
A. Drainage Patterns
1. Building pad surface drainage must maintain a minimum slope of one
percent towards an adjoining street or an approved drainage course.
2. ADD THE FOLLOWING NOTE: "Finish grade will provide a minimum positive
drainage of 2% to swale 5' away from building."
B. Existing & Proposed Slopes and Topography
3. Include on title sheet:
A. Site address a _ Assessor's Parcel Number
C. Legal Description
For commercial/indL1stcial buildings and tenant improvement projects, include:
.. total building square footage with the square footage for each different use;
existing sewer permits showing square footage of different uses (manufacturing,
warehouse, office. etc ) previously approved.
EXISTING PERMIT NUMBER DESCRIPTION
DISCRETIONARY APPROVAL COMPLIANCE
4a. Project does not comply with the following Engineering Conditions of approval for
Project No. ________________________ _
4b. All conditions are in compliance. Date: __________ _
H.IWORO\DOCS\CHKLSnBuild1ng Plancheck Cklst BP0001 Form JJ doc 2 Rev 12/26/96
0
0 0
BUILDING PLANCHECK CHECKLIST
DEDICATION REQUIREMENTS
5. Dedication for all street Rights-of-Way adjacent to the building site and any storm
drain or utility easements on the building site is required for all new buildings and
for remodels with a value at or exceeding $ ______ , pursuant to Carlsbad
Municipal Code Section 18.40.030.
Dedication required as follows: ________________ _
Dedication required. Please have a registered Civil Engineer or Land Surveyor
prepare the appropriate legal description together with an 8 ½" x 11" plat map
and submit with a title report. All easement documents must be approved and
signed by owner(s) prior to issuance of Building Permit. Attached please find an
application form and submittal checklist for the dedication process. Submit the
completed application form with the required checklist items and fees to the
Engineering Department in person. Applications will not be accept by mail or fax.
Dedication completed by:____________ Date: ___ _
IMPROVEMENT REQUIREMENTS
6a. All needed public improvements upon and adjacent to the building site must be
constructed at time of building construction whenever the value of the
___ construction exceeds $ __ -----'-----' pursuant to Carlsbad Municipal Code
Section 18.40.040.
Public improvements required as follows: _____________ _
Attached please find an application form and submittal checklist for the public
improvement requirements. A registered Civil Engineer must prepare the
appropriate improvement plans and submit them together with the requirements
on the attached checklist to the Engineering Department through a separate plan
check process. The completed application form and the requirements on the
checklist must be submitted in person. Applications by mail or fax are not
accepted. Improvement plans must be approved, appropriate securities posted
and fees paid prior to issuance of building permit.
Improvement Plans signed by: _________ _ Date: ----
6b. Construction of the public improvements may be deferred pursuant to Carlsbad
Municipal Code Section 18.40. Please submit a recent property title report or
current grant deed on the property and processing fee of $ _______ so
we may prepare the necessary Future Improvement Agreement. This agreement
must be $igned, notarized c;1nd approved by the City prior to issuance of a
Building permit.
Future public improvements required as follows:
H:\WORDIDOCSICHKLSnBuilding Plancheck Cklst BP0001 Form JJ.doc 3 Rev. 12/26/96
•
1 st.r
0
0
0
0
0
0
0 0
0 0
0
0
0
BUILDING PLANCHECK CHECKLIST
6c. Enclosed please find your Future Improvement Agreement. Please return
agreement signed and notarized to the Engineering Department.
Future Improvement Agreement completed by:
Date:
6d. No Public Improvements required. SPECIAL NOTE: Damaged or defective
improvements found adjacent to building site must be repaired to the satisfaction
of the City Inspector prior to occupancy.
GRADING PERMIT REQUIREMENTS
The conditions that invoke the need for a grading permit are found in Section
11.06.030 of the Municipal Code.
7a. Inadequate information available on Site Plan to make a determination on grading
requirements. Include accurate grading quantities (cut, fill import, export).
7b. Grading Permit required. A separate grading plan prepared by a registered Civil
Engineer must be submitted together with the completed application form
attached. NOTE: The Grading Permit must be issued and rough grading
approval obtained prior to issuance of a Building Permit.
Grading Inspector sign off by: Date: ----------
0 7c. Graded Pad Certification required. (Note: Pad certification may be required even
if a grading permit is not required.)
~7d.No Grading Permit required.
0
0
7e.lf grading is not required, write "No Grading" on plot plan.
MISCELLANEOUS PERMITS
8. A RIGHT-OF-WAY PERMIT is required to do work in City Right-of-Way and/or
private work adjacent to the public Right-of-Way. Types of work include, but are
not limited to: street improvements, tree trimming, driveway construction, tieing
into public storm drain, sewer and water utilities.
Right-of-Way permit required for:
H:\WORD\DOCSICHKLSnBu1ldmg Plancheck Cklst BP0001 Form JJ.doc
BUILDING PLANCHECK CHECKLIST
4 Rev. 12128/96
0
0
0 0 0
SEWER PERMIT is required concurrent with the building permit issuance. The
fee is noted in the fees section on the following page.
10. INDUSTRIAL WASTE PERMIT If your facility is located in the City of Carlsbad
sewer service area, you need to contact the Carlsbad Municipal Water Distric;:t,
located at 5950 El Camino Real, Carlsbad, CA 92008. District personnel can
provide forms and assistance, and will check to see if your business enterprise is
on the EWA Exempt List. You may telephone (760) 438-2722, extension 153, for
assistance.
Industrial Waste permit accepted by:
Date:
11. NPDES PERMIT
Complies with the City's requirements of the National Pollutant Discharge
Elimination System (NPDES) permit. The applicant shall provide best
management practices to reduce surface pollutants to an acceptable level prior to
discharge to sensitive areas. Plans for such improvements shall be approved by
the City Engineer prior to issuance of grading or building permit, whichever
occurs first.
12. 0 Required fees are attached
-_ · O No fees required
13. Additional Comments:
H:IWORD\OOCS\CHKLSnBu,lding Plancheck Cklst BP0001 Fenn JJ.doc 5 Rev. 12/26/96
PLANNING/ENGINEERINC 'APPROVALS
PERMIT NUMBER CB· C/IJ-Z---S-62...
RESIDENTIAL
RESIDENTIAL ADDITION MINOR
< < $10,000.00)
PLANNER{/~
ENCINEER --------
DoCS/MlsformS/Planning Engineering Approvals
DATE ,4! 2J-'1 fl
TENANT IMPROVEMENT
PLAZA CAMINO REAL
CARLSBAD COMPANY STORES
VILLACE FAIRE
COMPLETE OFFICE BUILDING ---
DATE rJ~cJ-?'f3
DATE -------
City of Carlsbad -{> 98296
Fire Department • Bureau of Prevention
Plan Review: Requirements Category:
Date of Report: Tuesday, August 25, 1998
Building Plan Check
R~e~d~:--~~-~--L~--
Contact Name Michael Kinoshita
Address 2211 Cambridge Av
City, State Cardiff CA 92007
Bldg. Dept. No. CB982562 Planning No.
Job Name lnvitrogen
Job Address 1600 Faraday ____ ..__ _____________ _ Ste. or Bldg. No. ____ _
~ Approved -The item you have submitted for review has been approved. The approval is
based on plans; information and/or specifications provided in your submittal;
therefore any changes to these items after this date, including field modifica-
tions, must be reviewed by this office to insure continued conformance with
applicable codes. Please review carefully all comments attached, as failure
to comply with instructions in this report can result in suspension of permit to
construct or install improvements.
D Disapproved -Please see the attached report of deficiencies. Please make corrections to
plans or specifications necessary to indicate compliance with applicable
codes and standards. Submit corrected plans and/or specifications to this
office for review.
For Fire Department Use Only
Review 1st. __ _ 2nd. __ _ 3rd __ _
Other Agency ID
CFD Job# __ 98_2_9_6 __ File# ___ ~
2560 Orion Way • Carlsbad, California 92008 • (619) 931-2121
Location:
Latitude:
Longitude:
Time Zone:
Elevation:
Barometric Pressure:
Air Density:
Air Specific Heat:
Density-Specific Heat Product:
Latent Heat Factor:
Enthalpy Factor:
Project Name: INVITROGEN
-=====:.-...:=='7::T:'Z¥;;.;=;;;.;;·=ZE..;;Vv..lMII ___________________________ _
~-'ii
,· -. .;
..... ~ --~ .. --11!11!! 19'!9! TRACE® Load 700
. . -ar.&' version 2.0 -? .. --By G.E.M. Engineering
Project Name: INVITROGEN
Dataset Name: C:\CDS\LOAD700\PROJECTS\INVITRO.
Location: Carlsbad, California
Building Owner:
Program User: D. Berry
Company: GEM Engineering
Comments:
San Diego, California (CTZ07)
32.0deg
117.0 deg
8
19ft
29.9 in Hg
0.0760 lb/cu ft
0.2444 Btu/lb-deg F
1.1147 Btu/hr-cfm-deg F
4,906.9 Btu-min/hr-cu ft-lb
4.5604 lb-min/hr-cu ft
Summer Design Dry Bulb:
Summer Design Wet Bulb:
Winter Design Dry Bulb:
Summer Clearness Number:
Winter Clearness Number:
Summer Ground Reflectance:
Winter Ground Reflectance:
Design Simulation Period: June through November
Cooling Load Methodology: TETO-TA 1
Heating Load Methodology: UATD
87 F
69 F
38 F
1.05
0.95
0.20
0.20
TRACE® Load 700 calculated at 10.38 AM on 08/06/19'
Dataset Name: C:\CDS\LOAD700\PROJECTSIINVITRO.LDS
Conference Room -2nd floor
Room Checksums
By G.E.M. Engineering
·-. --""" -· ·---------
COOLING COIL PEAK ;CLG SPACE PEAK: HEATING COIL PEAK TEMPERATURES
I I
I I Peaked at Time: Mo/Hr: 8 / 16 I Mo/Hr: 8 / 17 I Mo/Hr: 13/1 Clg Htg Outside Air: OADB/WB/HR: 89 / 71 / 83 I OADB: 88 I OADB: 38 SADB 50.2 73.8 I I
I I Plenum 78.5 68.0 Space Ret. Air Ret. Air Net Percent : Space Percent : Space Peak Coil Peak Percent Return 79.1 68.0 Sens.+ Lat. Sensible Latent Total Of Total 1 Sensible Of Total , Space Sens Tot Sens Of Total ReUOA 88.9 39.0 Btuh Btuh Btuh Btuh (%): Btuh (%) Btuh Btuh (%) Fn MtrTD 0.1 0.2 Envelope Loads I Fn BldTD 0.2 0.2 Skylite Solr 0 0 0 0.00 : 0 0.00 0 0 0.00 Fn Frict 0.7 0.7 Skylite Cond 0 0 0 0.00 I 0 0.00 0 0 0.00 Roof Cond 0 1,625 1,625 I
AIRFLOWS 8.02 I 0 0.00 0 -939 7.96 Glass Solar 0 0 0 0.00 : 0 0.00 0 0 0.00 Glass Cond 0 0 0 0.00 I 0 O.OQ 0 0 0.00 Cooling Heating Wall Cond 0 0 0 0.00 : 0 0.00 0 0 0.00 Vent 294 294 Partition 476 476 2.35 I 473 5.63 -1,044 -1,044 8.85 lnfil 0 0 Exposed Floor 0 0 0.00 : 0 0.00 0 0 0.00 Supply 303 303 Infiltration 0 0 0.00 I 0 0.00 -0 -0 0.00 Mincfm 0 0 Sub Total ==> 476 1,625 2,101 10.36 : 473 5.63 : -1,044 -1,983 16.81 Return 303 303 Internal Loads I I Exhaust 294 294 Lights 2,004 0 2,004 9.89 : 2,004 23.86 : 0 0 0.00 Rm Exh 0 0 People 7,830 7,830 38.62 I 4,796 57.09 I 0 0 0.00 Auxil 0 0 Misc 668 0 0 668 3.30 : 668 7.95 : 0 0 0.00 Sub Total==> 10,502 0 0 10,502 51.80 : 7,468 88.90 : 0 0 0.00 ENGINEERING CKS Ceiling Load 436 -436 0 0.00 I 459 5.47 I -252 0 0.00 Outside Air 0 0 0 8,456 41.71 : 0 0.00 : 0 -10,474 88.82 Cooling Heating Sup. Fan Heat 360 1.77 I 0.00 I 0 0.00 %QA 96.8 96.8 Ret. Fan Heat 180 180 0.89 : 0.00 : 0 0.00 cfm/sq ft 0.78 0.78 Duct Heat Pkup 0 0 0.00 I 0.00 I 0 0.00 cfmlton 179.60 OVIUNDR Sizing 0 0 0.00 : 0 0.00 : 0 0 0.00 sq ft/ton 231.72 Exhaust Heat -1,325 0 -1,325 -6.53 I 0.00 I 665 -5.64 Btu/hr-sq ft 51.79 -30.12 Terminal Bypass 0 0 0 0.00 : 0.00 : 0 0.00 No. People 20
I I
I I Grand Total==> 11,415 44 0 20,274 100.00 I 8,400 100.00 I -1,296 -11,792 100.00 HEATING COIL SELECTION I I
COOLING COIL SELECTION AREAS Capacity Coil Airfl Ent Lvg
MBh cfm F F Total Capacity Sens Cap. Coil Alrfl Enter DB/WBIHR Leave DB/WB/HR Gross Total Glass Main Htg -11.8 303 39.0 73.8 tons MBh MBh cfm F F gr/lb F F gr/lb : sq ft (%) Aux Htg 0.0 0 0.0 0.0
Floor 392 Preheat -3.4 303 39.0 49.1 Main Clg 1.7 20.3 13.4 303 88.9 70.5 82.9 49.1 48.9 51.2 Part 363 Reheat 0.0 0 0.0 0.0 Aux Clg 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 ExFlr 0 Humidif 0.0 0 0.0 0.0 Opt Vent 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 Roof 392 0 0 Opt Vent 0.0 0 0.0 0.0
Wall 0 0 0 Totals 1.7 20.3 Total -11.8
Project Name: INVITROGEN
Dataset Name: C:\CDS\LOAD700\PROJECTS\INVITRO.LDS TRACE® Load 700 calculated at 01:34 PM on 08/05/1998
Lunch Room
COOLING COIL PEAK
Peaked at Time: Mo/Hr: 8/16
Outside Air: OADBNVB/HR: 89 / 71 / 83
Room Checksums
By G.E.M. Engineering
: CLG SPACE PEAK :
I I
I I
I Mo/Hr: 7/18 I
I OADB: 85 I
I I
I I
HEATING COIL PEAK
Mo/Hr: 13 / 1
OADB: 38
Space Ret. Air Ret. Air Net Percent : Space Percent : Space Peak Coil Peak Percent
Sens.+ Lat. Sensible Latent Total Of Total , Sensible Of Total 1 Space Sens Tot Sens Of Total
Bluh Btuh Btuh Btuh (%): Btuh (%) : Btuh Btuh (%)
Envelope Loads I I
Skylite Solr 0 0 0 0.00: 0 0.00 ·: 0 0 0.00
Skylite Cond 0 0 0 0.00 I 0 0.00 I 0 0 0.00
Roof Cond 0 0 I 0 0,00 I 0 I 0,00 I 0 0 0.00
Glass Solar 907 0 907 1.61 : 1,361 4.46 : 0 0 0.00
Glass Cond 1,104 0 1,104 1.96 I 764 2.50 I -2,722 -2,722 9.29
Wall Cond 3,068 1,289 4,358 7.75 : 3,369 11.04 : -6,866 -9,751 33.30
Partition 0 0 0.00 I 0 0.00 I 0 0 0,00
Exposed Floor 0 0 0.00 : 0 0.00 : 0 0 0.00
Infiltration 0 0 0.00 I 0 0.00 I -0 -0 0.00
Sub Total==> 5,079 1,289 6,369 11.33 : 5,493 18.00 : -9,588 -12,473 42.59
Internal Loads I I
Lights 4,246 ~ 0' ;aon 4,246 7.55 I 4,246 13.92 : 0 0 0.00
People 18.248 cl a 18,248 32.46 9,124 29.90 I 0 0 0.00
Misc 11,434..-0 0 11,434 20.34 11,434 37.47 : 0 0 0.00
Sub Total ==> 33,928 0 0 33,928 60.35 24,804 81.28 : 0 0 0.00
Ceiling Load 198 -198 0 0.00 218 0.71 I -444 0 0.00
Outside Air 0 0 0 14,331 25.49 0 0.00 : 0 -17,752 60.61
Sup. Fan Heat 1,539 2.73 0.00 I 0 0.00
Ret. Fan Heat 768 768 1.37 0.00 : 0 0.00
Duct Heat Pkup 0 0 0.00 0.00 I 0 0.00
OV/UNDR Sizing 1 1 0.00 : 1 0.00 : 0 0 0.00
Exhaust Heat -714 0 -714 -1.27 I 0.00 I 938 -3.20
Terminal Bypass 0 0 0 0.00 : 0.00 : 0 0.00
I I
I I
Grand Total==> 39,207 1,145 0 56,219 100.00 I I 30,516 100.00 I
I
-10,032 -29,288 100.00
COOLING COIL SELECTION AREAS
Total Capacity Sens Cap. Coll Alrfl Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass
tons MBh MBh cfm F F gr/lb F F gr/lb sq ft (%)
Floor 829
Main Clg 4.7 56.2 40.6 1,296 81.3 66.1 72.1 52.8 51.7 55.5 Part 0
Aux Clg 0.0 0.0 i· 0 0.0 0.0 0.0 0.0 0.0 0.0 ExFlr 0
Opt Vent 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 Roof 0 0 O·
-6 Wall 850 76 9
Totals 4.7 56.2
TEMPERATURES
Clg Htg
SADB 53.9 76.9
Plenum 75.8 68.3
Return 76.3 68.3
Ret/OA 81.3 56.7
Fn MtrTD 0.1 0.2
Fn BldTD 0.2 0.2
Fn Frict 0.7 0.7
AIRFLOWS
Cooling Heating
Vent 498 498
lnfil 0 0
Supply 1,296 1,296
Mincfm 0 0
Return 1,296 1,296
Exhaust 498 498
Rm Exh 0 0
Auxil 0 0
ENGINEERING CKS
Cooling Heating
%OA 38.4 38.4
cfm/sq ft 1.56 1.56
cfm/ton 276.60
sq ft/ton 177.05
Btu/hr-sq ft 67.78 -35.31
No. People 33
HEATING COIL SELECTION
'.
Capacity Coil Airfl Ent Lvg
MBh cfm F F
Main Htg -29.3 1,296 56.7 76.9
Aux Htg 0.0 0 0.0 0.0
Preheat 0.0 1,296 56.7 52.8
Reheat 0.0 0 0.0 0.0
Humidif 0.0 0 0.0 0.0
Opt Vent 0.0 0 0.0 0.0
Total -29.3
Project Name: INVITROGEN TRACE® Load 700 calculated at 01 :34 PM on 08/05/1998
Dataset Name: C:\CDS\LOAD700\PROJECTS\INVITRO.LDS
Room -102
Room Checksums J By G.E.M. Engineering
·-·,---. ---··---"------·-------------
I
COOLING COIL PEAK ; CLG SPACE PEAK ; HEATING COIL PEAK
I I
I I
Peaked at Time: Mo/Hr: 8 / 14 I Mo/Hr: 8114 I Mo/Hr: 13 / 1
Outside Air: OADB/WB/HR: 89 / 71 I 83 I OADB: 89 I OADB: 38 I I
I I
Space Ret. Air Ret. Air Net Percent ; Space Percent : Space Peak Coil Peak Percent
Sens.+ Lat. Sensible Latent Total Of Total 1 Sensible Of Total , Space Sens Tot Sens Of Total
Btuh Btuh Btuh Btuh (%): Btuh (%) : Btuh Btuh (%)
Envelope Loads I I
Skylite Solr 0 0 0 0.00 0 0,00 : 0 0 0.00
Skylite Cond 0 0 0 0.00 0 0.00 I 0 0 0.00
Roof Cond 0 0. 0 0.00 0 I 0.00 I 0 0 0.00
Glass Solar 1,152 0 1,152 7.93 1,152 15.76 : 0 0 0.00
Glass Cond 1,051 0 1,051 7.24 1,051 14.38 I -2,592 -2,592 23.64
Wall Cond 789 445 1,234 8.50 789 10.80 : -1,958 -3,061 27.92
Partition 0 0 0.00 0 0.00 I 0 0 0.00
Exposed Floor 0 0 0.00 0 0.00 : 0 0 0.00
Infiltration 0 0 0.00 0 0.00 I -0 -0 0.00
Sub Total ==> 2,993 445 3,437 23.67 : 2,993 40.94 : -4,550 -5,653 51.55
Internal Loads I I
Lights 1,376 0 1,376 9.48 : 1,376 18.83 : 0 0 0.00
People 5,041 5,041 34.72 I 2,521 34.48 I 0 0 0.00
Misc 344 0 0 344 2.37 : 344 4.71 : 0 0 0.00
Sub Total ==> 6,761 0 0 6,761 46.56 : 4,241 58.02 : 0 0 0.00
Ceiling Load 13 -13 0 0.00 I 76 1.03 I -187 0 0.00
Outside Air 0 0 0 4,355 29.99 : 0 0.00 : 0 -5,395 49.19
Sup. Fan Heat 0 0.00 I 0.00 I 0 0.00
Ret. Fan Heat 0 0 0.00 : 0.00 : 0 0.00
Duct Heat Pkup 0 0 0.00 I 0.00 I 0 0.00
OV/UNDR Sizing 0 0 0.00 : 0 0.00 : 0 0 0.00
Exhaust Heat -33 0 -33 -0.23 I 0.00 I 82 -0.75
Terminal Bypal?S 0 0 0 0.00 : 0.00 : 0 0.00
I I
I I Grand Total==> 9,767 399 0 14,521 100.00 I
I 7,309 100.00 I
I -4,738 -10,966 100.00
COOLING COIL SELECTION AREAS
Total Capacity Sens Cap. Coil Airfl Enter D8/WBIHR Leave DB/WB/HR Gross Total Glass
tons MBh MBh cfm F F gr/lb F F gr/lb sq ft (%)
Floor 202
Main Clg 1.2 14.5 10.0 254 83.5 67.6 76.0 49.2 48.4 49.3 Part 0
Aux Clg 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 ExFlr 0
Opt Vent 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 Roof 0 0 0
Wall 313 72 23
Totals 1.2 14.5
TEMPERATURES
Clg Htg
SADB 49.2 86.7
Plenum 75.2 69.5
Return 75.2 69.5
Ret/OA 83.5 50.8
Fn MtrTD 0.0 0.0
Fn BldTD 0.0 0.0
Fn Frict 0.0 0.0
AIRFLOWS
Cooling Heating
Vent 151 1·51
lnfil 0 0
Supply 254 254
Mincfm 0 0
Return 254 254
Exhaust 151 151
RmExh 0 0
Auxil 0 0
ENGINEERING CKS
Cooling Heating
¾OA 59.5 59.5
cfm/sq ft 1.26 1.26
cfm/ton 209.95
sq Wton 166.63
Btu/hr-sq ft 72.01 -49.75
No. People 10
HEATING COIL SELECTION
Capacity Coil Airfl Ent Lvg
MBh cfm F F
Main Htg -10.0 254 50.8 86.7
Aux Htg 0.0 0 0.0 0.0
Preheat 0.0 254 50.8 49.2
Reheat 0.0 0 0.0 0.0
Humidif 0.0 0 0.0 0.0
Opt Vent 0.0 0 0.0 0.0
Total -10.0
Project Name: INVITROGEN TRACE® Load 700 calculated at O 1 :34 PM on 08/05/1998
Dataset Name: C:\CDS\LOAD700\PROJECTS\INVITRO.LDS
Room -104
Room Checksums _J By G.E.M. Engineering
. --,. ----------·-···--·-------
COOLING COIL PEAK : CLG SPACE PEAK : HEATING COIL PEAK
I I
I I Peaked at Time: Mo/Hr: 8 / 17 I Mo/Hr: 8 / 17 I Mo/Hr: 13 / 1
Outside Air: OADB/WB/HR: 88 / 71 / 84 I OADB: 88 I OADB: 38 I
I
Space Ret. Air Ret. Air Net Percent Space Percent : Space Peak Coil Peak Percent
Sens.+ Lat. Sensible Latent Total Of Total Sensible OfTotal , Space Sens Tot Sens Of Total
Btuh Btuh Btuh Btuh (%) Btuh (%) : Btuh Btuh (%)
Envelope Loads I
Skylite Solr 0 0 0 0.00 0 0.00 : 0 0 0.00
Skylile Cond 0 0 0 0.00 0 0.00 I 0 0 0.00
Roof Cond 0 0 0 0.00 I
I 0 0.00 I 0 0 0.00
Glass Solar 0 0 0 0.00 : 0 0.00 : 0 0 0.00
Glass Cond 0 0 0 0.00 I 0 0.00 I 0 0 0.00
Wall Cond 869 331 1,200 14.97 : 869 15.68 : -1,866 -2,575 44.14
Partition 855 855 10.67 I 855 15.43 I -1,887 -1,887 32.36
Exposed Floor 0 0 0.00 : 0 0.00 : 0 0 0.00
Infiltration 0 0 0.00 I 0 0.00 I -0 -0 0.00
Sub Total ==> 1,724 331 2,055 25.64 : 1,724 31.11 I -3,754 -4,462 76.50 I Internal Loads I I
Lights 1,791 0 1,791 22.35 : 1,791 32.32 : 0 0 0.00
People 1,181 1,181 14.73 I 656 11.84 I 0 0 0.00
Misc 1,344 0 0 1,344 16.76 : 1,344 24.24 : 0 0 0.00
Sub Total ==> 4,316 0 0 4,316 53.85 : 3,791 68.40 : 0 0 0.00
.Ceiling Load 27 -27 0 0.00 I 27 0.49 I -129 0 0.00
Outside Air 0 0 0 1,104 13.77 : 0 0.00 : 0 -1,404 24.07
Sup. Fan Heat 385 4.81 I 0.00 I 0 0.00
Ret. Fan Heat 193 193 2.40 : 0.00 : 0 0.00
Duct Heat Pkup 0 0 0.00 I 0.00 I 0 0.00
OV/UNDR Sizing 0 0 0.00: 0 0.00 : 0 0 0.00
Exhaust Heat -37 0 -37 -0.47 I 0.00 I 34 -0.58
Terminal Bypass 0 0 0 0.00 : 0.00 : 0 0.00
I I
I I
Grand Total==> 6,067 459 0 8,015 100.00 I 5,542 100.00 I -3,883 -5,833 100.00 I I
COOLING COIL SELECTION AREAS
Total Capacity Sens Cap. Coil Airfl Enter DB/WBIHR Leave DB/WBIHR Gross Total Glass
tons MBh MBh cfm F F gr/lb F F gr/lb sq ft (%)
Floor 262
Main Clg 0.7 8.0 7.0 325 77.4 63.9 67.2 58.6 55.8 61.9 Part 655
Aux Clg 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 ExFlr 0
Opt Vent 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 Roof 0 0 0
Wall 203 0 0
Totals 0.7 8.0
TEMPERATURES
Clg Htg
SADB 59.7 80.7
Plenum 75.3 69.2
Return 75.8 69.2
Ret/OA 77.4 65.5
Fn MtrTD 0.1 0.2
Fn BldTD 0.2 0.2
Fn Frict 0.7 0.7
AIRFLOWS
Cooling Heating
Vent 39 39
lnfil 0 0
Supply 325 325
Mincfm 0 0
Return 325 325
Exhaust 39 39
RmExh 0 0
Auxil 0 0
ENGINEERING CKS
Cooling Heating
%QA 12.1 12.1
cfm/sq ft 1.24 1.24
cfmlton 486.58
sq ft/ton 392.93
Btu/hr-sq ft 30.54 -20.82
No. People 3
HEATING COIL SELECTION
Capacity ,: Coil Airfl Ent Lvg
MBh cfm F F
Main Htg -5.5 325 65.5 80.7
Aux Htg 0.0 0 0.0 0.0
Preheat 0.0 325 65.5 58.6
Reheat 0.0 0 0.0 0.0
Humidif 0.0 0 0.0 0.0
Opt Vent 0.0 0 0.0 0.0
Total -5.5
Project Name: INVITROGEN TRACE® Load 700 calculated at 01:34 PM on 08/05/1998
Dataset Name: C:\CDS\LOAD700\PROJECTS\INVITRO.LDS
Room -152
COOLING COIL PEAK
Peaked at Time: Mo/Hr: 9 / 15
Outside Air: OADB/WB/HR: 89 / 71 / 85
Room Checksums
By G.E.M. Engineering
: CLG SPACE PEAK :
I I
I I
I Mo/Hr: 8 / 15 I
I OADB: 90 I
I
I
HEATING COIL PEAK
Mo/Hr: 13 / 1
OADB: 38
Space Ret. Air Ret. Air Net Percent : Space Percent Space Peak Coil Peak Percent
Sens.+ Lat. Sensible Latent Total Of Total 1 Sensible OfTotal Space Sens Tot Sens OfTotal
Btuh Btuh Btuh Btuh (%): Btuh (%) Btuh Btuh (%)
Envelope Loads I
Skylite Solr 0 0 0 0.00 : 0 0.00 0 0 0.00
Skylite Cond 0 0 0 0.00 I 0 0.00 0 0 0.00
RoofCond 0 0 I 0 0.00 I 0 0.00 0 0 0.00
Glass Solar 0 0 0 0.00 : 0 0.00 0 0 0.00
Glass Cond 0 0 0 0.00 I 0 0.00 0 0 0.00
Wall Cond 0 0 . 0 0.00 : 0 0.00 I 0 0 0.00
Partition 0 0 0.00 I 0 0.00 I 0 0 0.00
Exposed Floor 0 0 0.00 : 0 0.00 : 0 0 0.00
Infiltration 0 0 0.00 I 0 0.00 I -0 -0 0.00
Sub Total ==> 0 0 0 0.00 : 0 0.00 : -0 -0 0.00
Internal Loads I I
Lights 1,201 0 1,201 13.58 : 1,201 17.77 : 0 0 0.00
People 1,517 1,517 17.15 I 759 11.22 I 0 0 0.00
Misc 4,800 0 0 4,800 54.26 : 4,800 71.01 0 0 0.00
Sub Total==> 7,519 0 0 7,519 84.99 : 6,760 100.00 0 0 0.00
Ceiling Load 0 0 0 0.00 I 0 0.00 0 0 0.00
Outside Air 0 0 0 1,328 15.01 : 0 0.00 0 -1,624 100.00
Sup. Fan Heat 0 0.00 I 0.00 0 0.00
Ret. Fan Heat 0 0 0.00 : 0.00 0 0.00
Duct Heat Pkup 0 0 0.00 I 0.00 0 0.00
OV/UNDR Sizing 0 0 0.00 : 0 0.00 I 0 0 0.00
Exhaust Heat 0 0 0 0.00 I 0.00 I 0 0.00
Terminal Bypass 0 0 0 0.00 : 0.00 : 0 0.00
I I
I I
Grand Total==> 7,519 0 0 8,847 100.00 I
I 6,760 100.00 I
I -0 -1,624 100.00
COOLING COIL SELECTION AREAS
Total Capacity Sens Cap. Coil Airfl Enter DB/WB/HR Leave DB/WBIHR Gross Total Glass
tons MBh MBh cfm F F gr/lb F F gr/lb sq ft (%)
Floor 176
Main Clg 0.7 8.9 7.5 354 76.8 63.7 67.5 57.9 55.5 61.9 Part 0
Aux Clg 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 ExFlr 0
Opt Vent 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 Roof 0 0 0
Wall 0 0 0
Totals 0.7 8.9
TEMPERATURES
Clg Htg
SADB 57.9 70.1
Plenum 75.0 70.0
Return 75.0 70.0
Ret/OA 76.8 65.9
Fn MtrTD 0.0 0.0
Fn BldTD 0.0 0.0
Fn Frict 0.0 0.0
AIRFLOWS
Cooling Heating
Vent 46 46
lnfil 0 0
Supply 354 354
Mincfm 0 0
Return 354 354
Exhaust 46 46
Rm Exh 0 0
Auxil 0 0
ENGINEERING CKS
Cooling Heating
%OA 12.8 12.8
cfm/sq ft 2.01 2.01
cfm/ton 480.75
sq ft/ton 238.74
Btu/hr-sq ft 50.26 -9.45
No. People 3
HEATING COIL SELECTION
Capacity Coil Airfl Ent Lvg
MBh cfm F F
Main Htg -1.7 354 65.9 70.1
Aux Htg 0.0 0 0.0 0.0
Preheat 0.0 354 65.9 57.9
Reheat 0.0 0 0.0 0.0
Humidif 0.0 0 0.0 0.0
Opt Vent 0.0 0 0.0 0.0
Total -1.7 ;
Project Name: INVITROGEN TRACE® Load 700 calculated at 01:34 PM on 08/05/1998
Dataset Name: C:\CDS\LOAD700\PROJECTS\INVITRO.LDS
Room -154
Room Checksums
By G.E.M. Engineering
-.... ·--· ... -···--·-------
COOLING COIL PEAK :cLG SPACE PEAK: HEATING COIL PEAK
I I
I I
Peaked at Time: Mo/Hr: 9 / 15 I Mo/Hr: 8/15 I Mo/Hr: 13 / 1
Outside Air: OADB/WB/HR: 89 / 71 / 85 I OADB: 90 I OADB: 38 I I
I I
Space Ret. Air Ret. Air Net Percent : Space Percent : Space Peak Coil Peak Percent
Sens.+ Lat. Sensible Latent Total Of Total 1 Sensible Of Total , Space Sens Tot Sens Of Total
Btuh Btuh Btuh Btuh (¾): Btuh (%): Btuh Btuh (%)
Envelope Loads I I
Skylile Solr 0 0 0 0.00 : 0 0.00 : 0 0 0.00
Skylite Cond 0 0 0 0.00 I 0 0.00 I 0 0 0.00
I I Roof Cond 0 0 0 0.00 I 0 0.00 I 0 0 0.00
Glass Solar 0 0 0 0.00 : 0 0.00 : 0 0-0.00
Glass Cond 0 0 0 0.00 I 0 0.00 I 0 0 0.00
Wall Cond 0 0 0 0.00 : 0 0.00 : 0 0 0.00
Partition 0 0 0.00 I 0 0.00 I 0 0 0.00
Exposed Floor 0 0 0.00 : 0 0.00 : 0 0 0.00
Infiltration 0 0 0.00 I 0 0.00 I -0 -0 0.00
Sub Total ==> 0 0 0 0.00: 0 0.00 : -0 -0 0.00
Internal Loads I I
Lights 988 0 988 2.19 : 988 5.26 : 0 0 0.00
People 1,448 1,448 3.21 I 724 3.85 I 0 0 0.00
Misc 1,800 0 0 1,800 3.99 : 1,800 9.58 : 0 0 0.00
Sub Total ==> 4,236 0 0 4,236 9.38 : 3,512 18.70 : 0 0 0.00
Ceiling Load 0 0 0 0.00 I 0 0.00 I 0 0 0.00
Outside Air 0 0 0 25,643 56.79 : 0 0.00 : 0 -46,373 100.00
Sup. Fan Heat 0 0.00 I 0.00 I 0 0.00
Ret. Fan Heat 0 0 0.00 : 0.00 : 0 0.00
Duct Heat Pkup 0 0 0.00 I 0.00 I 0 0.00
OV/UNDR Sizing 15,272 15,272 33.83 : 15;272 81.30 : -0 -0 0.00
Exhaust Heat 0 0 0 0.00 I 0.00 I 0 0.00
Terminal Bypass 0 0 0 0.00 : 0.00 : 0 0.00
I I
I I
Grand Total==> 19,508 0 0 45,151 100.00 I 18,784 100.00 I -0 -46,373 100.00
I I
COOLING COIL SELECTION AREAS
Total Capacity Sens Cap. Coil Airfl Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass
tons MBh MBh cfm F F gr/lb F F gr/lb sq ft (%)
Floor 145
Main Clg 3.8 45.2 38.7 1,300 88.7 70.8 84.8 62.0 60.8 77.9 Part 0
Aux Clg 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 ExFlr 0
Opt Vent 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 Roof 0 0 0
Wall 0 0 0
Totals 3.8 45.2
TEMPERA TURES
Clg Htg
SADB 62.0 70.1
Plenum 75.0 70.0
Return 75.0 70.0
Ret/OA 88.7 38.0
Fn MtrTD 0.0 0.0
Fn BldTD 0.0 0.0
Fn Frict 0.0 0.0
AIRFLOWS
Cooling Heating
Vent 1,300 1,300
lnfil 0 0
Supply 1,300 1,300
Mincfm 0 0
Return 1,300 1,300
Exhaust 1,300 1,300
Rm Exh 0 0
Auxil 0 0
ENGINEERING CKS
' Cooling Heating
%OA 100.0 100.0
cfm/sq ft 8.98 8.98
cfm/ton 345.51
sq Wton 38.47
Btu/hr-sq ft 311.90 -321.34
No. People 3
HEATING COIL SELECTION
Capacity Coil Airfl Ent Lvg
MBh cfm F F
Main Htg -46.5 1,300 38.0 70.1
Aux Htg 0.0 0 0.0 0.0
Preheat -34.8 1,300 38.0 62.0
Reheat 0.0 0 0.0 0.0
Humidif 0.0 0 0.0 0.0
Opt Vent 0.0 0 o.o· 0.0
Total -46.5
--------------------------------·--------·----------------
Project Name: INVITROGEN
Dataset Name: C:\CDS\LOAD700\PROJECTS\INVITRO.LDS
. ---·· -----·-·---~~~-E®-L~-~d-;-0~-ca~~;;!~-te~;:~ ~-~;,~ ___________ .,.
Room Checksums J
By G.E.M. Engineering
----------------------
Room -154
COOLING COIL PEAK : CLG SPACE PEAK : HEATING COIL PEAK TEMPERATURES
I I
I I
Peaked at Time: Mo/Hr: ~ / 15 I Mo/Hr: 8 / 15 I Mo/Hr: 13 / 1 Clg Htg
Outside Air: OADBNVB/HR: 89 / 71 / 85 I OADB: 90 I OADB: 38 SADB 57.3 70.1 I I
I I Plenum 75.0 70.0
Space Ret. Air Ret. Air Net Percent : Space Percent : Space Peak Coil Peak Percent Return 75.0 70.0
Sens.+ Lat. Sensible Latent Total OfTotal , Sensible Of Total , Space Sens Tot Sens Of Total ReUOA 78.3 62.2
Btuh Btuh Btuh Btuh (%) : Btuh (%): Btuh Btuh (%) Fn MtrTD 0.0 0.0
Envelope Loads I Fn BldTD 0.0 0.0
Skylite Solr 0 0 0 0.00 : 0 0.00 0 0 0.00 Fn Frict 0.0 0.0
Skylite Cond 0 0 0 0.00 I 0 0.00 0 ·o 0.00
Roof Cond 0 0 0 I 0.00 I 0 0.00 0 0 0.00 AIRFLOWS
Glass Solar 0 0 0 0.00 : 0 0.00 0 0 0.00
Glass Cond 0 0 0 0.00 I 0 0.00 0 0 0.00 Cooling Heating
Wall Cond 0 0 0 0.00 : 0 0.00 0 0 0.00 Vent 43 43
Partition 0 0 0.00 I 0 0.00 0 0 0.00 lnfil 0 0
Exposed Floor 0 0 0.00 : 0 0.00 0 0 0.00 Supply 178 178
Infiltration 0 0 0.00 I 0 0.00 -0 -0 0.00 Mincfm 0 0
Sub Total==> 0 0 0 0.00: 0 0.00 -0 -0 0.00 Return 178 178
Internal Loads I Exhaust 43 43
Lights 988 0 988 17.94 : 988 28.10 0 0 0.00 Rm Exh 0 0
People 1,448 1,448 26.29 I 724 20.58 0 0 0.00 Auxil 0 0
Misc 1,800 0 0 1,800 32.68 : 1,800 51.19 I 0 0 0.00
Sub Total ==> 4,236 0 0 4,236 76.91 : 3,512 99.87 0 0 0.00 ENGINEERING CKS
Ceiling Load 0 0 0 0.00 I 0 0.00 0 0 0.00
Outside Air 0 0 0 1,267 23.01 : 0 0.00 0 -1,549 100.00 Cooling Heating
Sup. Fan Heat 0 0.00 I 0.00 0 0.00 ¾OA 24.3 24.3
Ret. Fan Heat 0 0 0.00 : 0.00 0 0.00 cfm/sq ft 1.23 1.23
Duct Heat Pkup 0 0 0.00 I 0.00 0 0.00 cfm/ton 388.90
OVIUNDR Sizing 4 4 0.08 : 4 0.13 0 0 0.00 sq ft/ton 315.43 ' Exhaust Heat 0 0 0 0.00 I 0.00 0 0.00 Btu/hr-sq ft 38.04 -10.84
Terminal Bypass 0 0 0 0.00 : 0.00 0 0.00 No. People 3
I
I I
Grand Total==> 4,240 0 0 5,507 100.00 I 3,516 100.00 I -0 -1,549 100.00 HEATING COIL SELECTION
I I
COOLING COIL SELECTION AREAS Capacity Coil Airfl Ent Lvg
MBh cfm F F
Total Capacity Sens Cap. CoilAirfl Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Main Htg -1.6 178 62.2 70.1
tons MBh MBh cfm F .F gr/lb F F gr/lb sq ft (%) Aux Htg 0.0 0 0.0 0.0
Floor 145 Preheat 0.0 178 62.2 57.3
Main Clg 0.5 5.5 4.2 178 78.3 64.7 69.8 57.3 54.6 59.3 Part 0 Reheat 0.0 0 0.0 0.0
Aux Clg 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 ExFlr 0 Humidif 0.0 0 0.0 0.0
Opt Vent 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 Roof 0 0 0 Opt Vent 0.0 0 0.0 0.0
Wall 0 0 0
Totals 0.5 5.5 Total -1.6
. -----· -------------------·----------------·-
Project Name: INVITROGEN
Dataset Name: C:\CDS\LOAD700\PROJECTS\INVITRO.LDS
----------------·---·· .... ,;. ~=-:=~---· ·:· ·::-~
TRACE® Load 700 _calculated 'at 01 :34 PM on 08/05/1998 ) '-----·------
l
Room -155
COOLING COIL PEAK
Peaked at Time: Mo/Hr: 9 / 15
Outside Air: OADB/WB/HR: 89 / 71 / 85
Room Checksums
By G.E.M. Engineering
: CLG SPACE PEAK :
I I
I I
I Mo/Hr: 8 / 15 I
I OADB: 90 I
I I
I I
HEATING COIL PEAK
Mo/Hr: 13 / 1
O.A,DB: 38
Space Ret. Air Ret. Air Net Percent : Space Percent : Space Peak Coil Peak Percent
Sens.+ Lat. Sensible Latent Total OfTotal 1 Sensible Of Total , Space Sens Tot Sens Of Total
Btuh Btuh Btuh Btuh (%): Btuh (%) : Btuh Btuh (%)
Envelope Loads I I
Skylite Solr 0 0 0 0.00 : 0 0.00 : 0 0 0.00
Skylite Cond 0 0 0 0.00 I 0 0.00 I 0 0 0.00
Roof Cond 0 0 0 I 0.00 I 0 I 0.00 I 0 0 0.00
Glass Solar 0 0 0 0.00 : 0 0.00 : 0 0 0.00
Glass Cond 0 0 0 0.00 I 0 0.00 I 0 0 0.00
Wall Cond 0 0 0 0.00 0 0.00 : 0 0 0.00
Partition 0 0 0.00 0 0.00 0 0 0.00
Exposed Floor 0 0 0.00 0 0.00 0 0 0.00
Infiltration 0 0 0.00 0 0.00 -0 -0 0.00
Sub Total ==> 0 0 0 0.00 0 0.00 -0 -0 0.00
Internal Loads
Lights 1,314 0 1,314 11.60 1,314 15.67 0 0 0.00
People 2,139 2,139 18.89 1,069 12.76 0 0 0.00
Misc 6,000 0 0 6,000 52.98 6,000 71.57 0 0 0.00
Sub Total==> 9,453 0 0 9,453 83.47 I 8,383 100.00 I 0 0 0.00
Ceiling Load 0 0 0 0.00 I 0 0.00 I 0 0 0.00
Outside Air 0 0 0 1,872 16.53 : 0 0.00 : 0 -2,289 99.99
Sup. Fan Heat 0 0.00 I 0.00 I 0 0.00
Ret. Fan Heat 0 0 0.00: 0.00 : 0 0.00
Duct Heat Pkup 0 0 0.00 I 0.00 I 0 0.00
OV/UNDR Sizing 0 0 0.00 : 0 0.00 : -0 -0 0.00
Exhaust Heat 0 0 0 0.00 I 0.00 I 0 0.00
Terminal Bypass 0 0 0 0.00 : 0.00 : 0 0.00
I I
I I
Grand Total==> 9,453 0 0 11,325 100.00 I 8,383 100.00 I -0 -2,289 100.00
I I
COOLING COIL SELECTION AREAS
Total Capacity Sens Cap. Coil Airfl Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass
tons MBh MBh cfm F F gr/lb F F gr/lb sq ft (%)
Floor 193
Main Clg 0.9 11.3 9.4 426 77.1 63.9 67.9 57.3 55.1 61.4 Part 0
Aux Clg 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 ExFlr 0
Opt Vent 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 Roof 0 0 0.
Wall 0 0 0
Totals 0.9 11.3
TEMPERATURES
Clg Htg
SADB 57.3 70.1
Plenum 75.0 70.0
Return 75.0 70.0
Ret/OA 77.1 65.2
Fn MtrTD 0.0 0.0
Fn BldTD 0.0 0.0 '.
Fn Frict 0.0 0.0
AIRFLOWS
Cooling Heating
Vent 64 64
lnfil 0 0
Supply 426 426
Mincfm 0 0
Return 426 426
Exhaust 64 64
Rm Exh 0 0
Auxil 0 0
ENGINEERING CKS
Cooling Heating
¾OA 15.1 15.1
cfmlsq ft 2.21 2.21
cfm/ton 450.88
sq ft/ton 203.97
Btu/hr-sq ft 58.83 -12.14
No. People, 4
HEATING COIL SELECTION
Capacity Coil Airfl Ent Lvg
MBh cfm F F
Main Htg -2.3 426 65.2 70.1
Aux Htg 0.0 0 0.0 0.0
Preheat 0.0 426 65.2 57.3
Reheat 0.0 0 0.0 0.0
Humidif 0.0 0 0.0 0.0
Opt Vent 0.0 0 0.0 0.0
Total -2.3
Project Name: INVITROGEN TRACE® Load 700 calculated at 01 :34 PM on 08/05/1998
Dataset Name: C:\CDS\LOAD700\PROJECTS\INVITRO.LDS
Room -156
l Room Checksums_J
By G.E.M. Engineering
-··-. •h-·-------·--------·
COOLING COIL PEAK : CLG SPACE PEAK : HEATING COIL PEAK
I I
I I Peaked at Time: Mo/Hr: 8 / 14 I Mo/Hr: 8 / 14 I Mo/Hr: 13 / 1
Outside Air: OADB/WB/HR: 89 / 71 / 83 I OADB: 89 I OADB: 38 I I
I I
Space Ret. Air Ret. Air Net Percent : Space Percent : Space Peak Coil Peak Percent
Sens.+ Lat. Sensible Latent Total OfTotal , Sensible OfTotal , Space Sens Tot Sens Of Total
Btuh Btuh Btuh Btuh (%): Btuh (%) : Btuh Btuh (%)
Envelope Loads I I
Skylite Solr 0 0 0 0.00 : 0 0.00 : 0 0 0.00
Skylite Cond 0 0 0 0.00 I 0 0.00 I 0 0 0.00
Roof Cond I I 0 o· 0 0.00 I 0 0.00 I 0 0 0.00
Glass Solar 1,728 0 1,728 2.29 : 1,728 3.31 : 0 0 0.00
Glass Cond 1,577 0 1,577 2.09 I 1,577 3.02 I -3,888 -3,888 12.01
WallCond 581 435 1,016 1.34 : 581 1.11 : -1,440 -2,520 7.78
Partition 0 0 0.00 I 0 0.00 I 0 0 0.00
Exposed Floor 0 0 0.00 : 0 0.00 : 0 0 0.00
Infiltration 0 0 0.00 I 0 0.00 I -0 -0 0.00
Sub Total==> 3,885 435 4,321 5.72 : 3,885 7.44 : -5,328 -6,408 19.79
Internal Loads I I
Lights 8,748 0 8,748 11.58 : 8,748 16.74 : 0 0 0.00
People 4,033 4,033 5.34 I 2,241 4.29 I 0 0 0.00
Misc 37,303 0 0 37,303 49.36 : 37,303 71.38 : 0 0 0.00
Sub Total==> 50,085 0 0 50,085 66.27 : 48,292 92.41 I
I 0 0 0.00
Ceiling Load 84 -84 0 0.00 I 49 0.09 -209 0 0.00
Outside Air 0 0 0 21,310 28.20 : 0 0.00 0 -26,397 81.52
Sup. Fan Heat 0 0.00 I 0.00 0 0.00
Ret. Fan Heat 0 0 0.00 : 0.00 0 0.00
Duct Heat Pkup 0 0 0.00 I 0.00 0 0.00
OV/UNDR Sizing 30 30 0.04: 30 0.06 0 0 0.00
Exhaust Heat -171 0 -171 -0.23 I 0.00 425 -1.31
Terminal Bypass 0 0 0 0.00 : 0.00 0 0.00
I
I
Grand Total==> 54,084 180 0 75,574 100.00 I
I
52,256 100.00 -5,537 -32,380 100.00
COOLING COIL SELECTION AREAS
Total Capacity Sens Cap. Coil Airfl Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass
tons MBh MBh cfm F F gr/lb F F gr/lb sq ft (%)
Floor 1,282
Main Clg 6.3 75.6 64.2 2,904 78.8 64.8 69.7 58.9 56.4 64.3 Part 0
Aux Clg 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 ExFlr 0
Opt Vent 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 Roof 0 0 0
Wall 306 108 35
Totals 6.3 75.6
TEMPERATURES
Clg Htg
SADB 58.9 71.7
Plenum 75.2 69.5
Return 75.2 69.5
ReUOA 78.8 61.5
Fn MtrTD 0.0 0.0
Fn BldTD 0.0 0.0
Fn Frict 0.0 0.0
AIRFLOWS
Cooling Heating
Vent 740 740
lnfil 0 0
Supply 2,904 2,904
Mincfm 0 0
Return 2,904 2,904
Exhaust 740 740
Rm Exh 0 0
Auxil 0 0
ENGINEERING CKS
Cooling Heating
%OA 25.5 25.5
cfm/sq ft 2.27 2.27
cfm/ton 461.15
sq fUton 203.50
Btu/hr-sq ft 58.97 -25.89
No. People 9
HEATING COIL SELECTION
Capacity Coil Airfl Ent Lvg
MBh cfm F F
Main Htg -33.2 2,904 61.5 71.7
Aux Htg 0.0 0 0.0 0.0
Preheat 0.0 2,904 61.5 58.9
Reheat 0.0 0 0.0 0.0
Humidif 0.0 0 0.0 0.0
Opt Vent 0.0 0 0.0 0.0
Total -33.2 ----
---------------------·---------··----···-·--------------~.. . -. -~
TRACE® Load 700 calculateU::r1t 10:38 AM on 08/06/1998) Project Name: INVITROGEN
Dataset Name: C:\CDS\LOAD700\PROJECTS\INVITRO.LDS . --------------.
Room -156
Room Checksums j By G.E.M. Engineering
------.. , -------------------------
COOLING COIL PEAK ;CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
I
I Peaked at Time: Mo/Hr: 8 / 14 I Mo/Hr: 8/14 Mo/Hr: 13 / 1 Clg Htg Outside Air: OADB/WB/HR: 89 / 71 / 83 I OADB: 89 OADB: 38 SADB 60.3 71.5 I
I Plenum 75.2 69.5 Space Ret. Air Ret. Air Net Percent : Space Percent Space Peak Coil Peak Percent Return 75.2 69.5 Sens.+ Lat. Sensible Latent Total Of Total , Sensible Of Total Space Sens Tot Sens OfT otal Ret/OA 75.8 68.2 Btuh Btuh Btuh Btuh (%): Btuh (%) Btuh Btuh (%) Fn MtrTD 0.0 0.0 Envelope Loads I Fn BldTO 0.0 0.0 Skylite Solr 0 0 0 0.00 : 0 0.00 0 0 0.00 Fn Friel 0.0 0.0 Skylite Cond 0 0 0 0.00 I 0 0.00 0 0 0.00 Roof Cond 0 0 I
AIRFLOWS 0 0.00 I 0 0.00 0 0 0.00 Glass Solar 1,728 0 1,728 2.96 : 1,728 3.31 0 0 0.00 Glass Cond 1,577 0 1,577 2.71 I 1,577 3.02 -3,888 -3,888 34.93 Cooling Heating Wall Cond 581 436 1,016 1.74 : 581 1.11 I -1,440 -2,521 22.65 Vent 134 134 Partition 0 0 0.00 I 0 0.00 I 0 0 0.00 lnfil 0 0 Exposed Floor 0 0 0.00 : 0 0.00 : 0 0 0.00 Supply 3,187 3,187 Infiltration 0 0 0.00 I 0 0.00 I -0 -0 0.00 Mincfm 0 0 Sub Total==> 3,885 436 4,321 7.41 : 3,885 7.44 : -5,328 -6,409 57.57 Return 3,187 3,187 Internal Loads I I Exhaust 134 134 Lights 8,748 0 8,748 15.01 : 8,748 16.74 : 0 0 0.00 RmExh 0 0 People 4,033 4,033 6.92 I 2,241 4.29 I 0 0 0.00 Auxil 0 0 Misc 37,303 0 0 37,303 64.01 : 37,303 71.39 : 0 0 0.00 Sub Total ==> 50,085 0 0 50,085 85.94 : 48,292 92.42 : 0 0 0.00 ENGINEERING CKS -Ceiling Load 80 -80 0 0.00 I 45 0.09 I -112 0 0.00 Outside Air 0 0 0 3,871 6.64 : 0 0.00 : 0 -4,796 43.08 Cooling Heating Sup. Fan Heat 0 0.00 I 0.00 I 0 0.00 %OA 4.2 4.2 Ret. Fan Heat 0 0 0.00 : 0.00 : 0 0.00 cfmlsq ft 2.49 2.49 Duct Heat Pkup 0 0 0.00 I 0.00 I 0 0.00 cfmlton 656.12 OV/UNDR Sizing 33 33 0.06 : · 33 0.06 : -0 -0 0.00 sq ft/ton 263.89 Exhaust Heat -29 0 -29 -0.05 I 0.00 I 73 -0.65 Btu/hr-sq ft 45.47 -9.34 Terminal Bypass 0 0 0 0.00 : 0.00 : 0 0.00 No. People 9
I I
I I Grand Total==> 54,082 327 0 58,281 100.00 I 52,255 100.00 I -5,440 -11,132 100.00 HEATING COIL SELECTION I I
COOLING COIL SELECTION AREAS Capacity CoilAirfl Ent Lvg
MBh cfm : F F Total Capacity Sens Cap. Coil Airfl Enter O8/WBIHR Leave O8/WBIHR Gross Total Glass Main Htg -12.0 3,187 68.2 71.5 tons MBh MBh cfm F F gr/lb F F gr/lb sq ft (%) Aux Htg 0.0 0 0.0 0.0 Floor 1,282 Preheat 0.0 3,187 68.2 60.3 Main Clg 4.9 58.3 54.8 3,187 75.8 63.0 65.7 60.3 57.0 64.3 Part 0 Reheat 0.0 0 0.0 0.0 Aux Clg 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 ExFlr 0 Humidif 0.0 0 0.0 0.0 Opt Vent 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 Roof 0 0 0 Opt Vent 0.0 0 0.0 0.0 Wall 306 108 35 Totals 4.9 58.3 Total -12.0
Project Name: INVITROGEN
Dataset Name: C:\CDS\LOAD700\PROJECTS\INVITRO.LDS
--· ------.. ···-···--·--_____________ ,·:-.:::.-~ -------~
TRACE® Load 700_ calculate~08/05/1998_)
Room Checksums I
By G.E.M. Engineering
'---------------~--------
Room -157
COOLING COIL PEAK : CLG SPACE PEAK : HEATING COIL PEAK TEMPERATURES
' I
I I Peaked at Time: Mo/Hr: 9 / 15 I Mo/Hr: 8 / 15 I Mo/Hr: 13 / 1 Clg Htg
Outside Air: OADB/WB/HR: 89 / 71 / 85 I OADB: 90 I OADB: 38 SADB 60.5 76.9 I I
I I Plenum 75.2 69.5
Space Ret. Air Ret. Air Net Percent : Space Percent : Space Peak Coil Peak Percent Return 75.2 69.5
Sens.+ Lat. Sensible Latent Total Of Total , Sensible Of Total , Space Sens Tot Sens Of Total ReUOA 75.5 68.9
Btuh Btuh Btuh Btuh (%): Btuh (%) : Btuh Btuh (%) Fn MtrTD 0.0 0.0
Envelope Loads I I Fn BldTD 0.0 0.0
Skylile Solr 0 0 0 0.00 : 0 0.00 : 0 0 0.00 Fn Frict 0.0 0.0
Skylite Cond 0 0 0 0.00 I 0 0.00 I 0 0 0.00
Roof Cond I I AIRFLOWS 0 0 0 0.00 I 0 0.00 I 0 0 0.00
Glass Solar 0 0 0 0.00 : 0 0.00 : 0 0 0.00
Glass Cond 0 0 0 0.00 I 0 0.00 I 0 0 0.00 Cooling Heating
Wall Cond 0 0 0 0.00 : 0 0.00 : 0 0 0.00 Vent 14 14
Partition 0 0 0.00 I 0 0.00 I 0 0 0.00 lnfil 0 0
Exposed Floor 0 0 0.00 : 0 0.00 : 0 0 0.00 Supply 671 671
Infiltration 0 0 0.00 I 0 0.00 I -0 -0 0.00 Mincfm 0 0
Sub Total==> 0 0 0 0.00 : 0 0.00 : -0 -0 0.00 Return 671 671
Internal Loads I I Exhaust 14 14
Lights 614 0 614 5.36 I 614 5.66 : 0 0 0.00 Rm Exh 0 0
People 450 450 3.93 225 2.07 I 0 0 0.00 Auxil 0 0
Misc 10,000 0 0 10,000 87.26 10,000 92.21 I 0 0 0.00
Sub Total :=> 11,064 0 0 11,064 96.54 10,839 99.95 0 0 0.00 ENGINEERING Ct<S
Ceiling Load 6 -6 0 0.00 0 0.00 0 0 0.00
Outside Air 0 0 0 394 3.44 0 0.00 0 -482 8.60 Cooling Heating
Sup. Fan Heat 0 0.00 0.00 0 0.00 %0A 2.0 2.0
Ret. Fan Heat 0 0 0.00 0.00 0 0.00 cfmlsq ft 7.45 7.45
Duct Heat Pkup 0 0 0.00 I 0.00 0 0.00 cfmlton 702.48
OV/UNDR Sizing 5 5 0.05 : . 5 0.05 -5, 128 -5, 128 91.53 sq ft/ton 94.24
Exhaust Heat -3 0 -3 -0.03 I 0.00 7 -0.13 Btu/hr-sq ft 127.34 -66.44
Terminal Bypass 0 0 0 0.00 : 0.00 0 0.00 No. People· 1
I
I
Grand Total==> 11,075 -9 0 11,461 100.00 I I 10,845 100.00 -5, 128 -5,602 100.00 HEATING COIL SELECTION
COOLING COIL SELECTION AREAS Capacity Coil Airfl Ent ~vg
MBh cfm F F
Total Capacity Sens Cap. Coil Alrfl Enter DB/WBIHR Leave DB/WB/HR Gross Total Glass Main Htg -6.0 671 68.9 76.9
tons MBh MBh cfm F F gr/lb F F gr/lb sq ft (%) Aux Htg 0.0 ·o 0.0 0.0
Floor 90 Preheat 0.0 671 68.9 60,5
Main Clg 1.0 11.5 11.1 671 75.5 62.8 65.3 60.5 57.2 64.8 Part 0 Reheat 0.0 0 0.0 0.0
Aux Clg 0,0 0,0 0.0 0 0.0 0.0 0.0 0,0 0.0 0.0 ExFlr 0 Humidif 0.0 0 0.0 0.0
Opt Vent 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 Roof 0 0 0 Opt Vent 0.0 0 0.0 0.0
Wall 0 0 0
Totals 1.0 11.5 Total -6.0
----·---·-,. ____ ...... -· --
Project Name: INVITROGEN TRACE® Load 700 calculated at 01 :34 PM on 08/05/1998
Dataset Name: C:\CDS\LOAD700\PROJECTS\INVITRO.LDS
Room -158
Room Checksums J By G.E.M. Engineering
COOLING COIL PEAK :cLG SPACE PEAK: HEATING COIL PEAK
I I
I I
Pe'aked at Time: Mo/Hr: 8 / 14 I Mo/Hr: 8 / 14 I Mo/Hr: 13 / 1
Outside Air: OADB/WB/HR: 89 / 71 / 83 I OADB: 89 I OADB: 38 I I
I I
Space Ret. Air Ret. Air Net Percent : Space Percent : Space Peak Coil Peak Percent
Sens.+ Lat. Sensible Latent Total Of Total 1 Sensible OfTotal 1 Space Sens Tot Sens Of Total
Btuh Btuh Btuh Btuh (%) : Btuh (%) : Btuh Btuh (%)
Envelope Loads I I
Skylite Solr 0 0 0 0.00: 0 0.00 : 0 0 0.00
Skylite Cond 0 0 0 0.00 I 0 0.00 I 0 0 0.00
Roof Cond I I 0 0 0 0.00 I 0 0.00 I 0 0 0.00
Glass Solar 576 0 576 11.39 : 576 13.45 : 0 0. 0.00
Glass Cond 526 0 526 10.40 I 526 12.27 I -1,296 -1,296 44.65
Wall Cond 279 178 457 9.03 : 279 6.51 : -691 -1, 132 39.01
Partition 0 0 0.00 I 0 0.00 I 0 0 0.00
Exposed Floor 0 0 0.00 : 0 0.00 : 0 0 0.00
Infiltration 0 0 0.00 I 0 0.00 I -0 -0 0.00
Sub Total ==> 1,380 178 1,558 30.82 : 1,380 32.23 : -1,987 -2,428 83.66
Internal Loads I I
Lights 614 0 614 12.15 : 614 14.34 : 0 0 0.00
People 450 450 8.90 I 225 5.25 I 0 0 0.00
Misc 2,048 0 0 2,048 40.50: 2,048 47.82 : 0 0 0.00
Sub Total==> 3,112 0 0 3,112 61.55 : 2,887 67.41 I
I 0 0 0.00
Ceiling Load 6 -6 0 0.00 I 15 0.36 I -38 0 0.00
Outside Air 0 0 0 389 7.69 : 0 0.00 : 0 -482 16.59
Sup. Fan Heat 0 0.00 I 0.00 I 0 0.00
Ret. Fan Heat 0 0 0.00 : 0.00 : 0 0.00
Duct Heat Pkup 0 0 0.00 I 0.00 I 0 0.00
OV/UNDR Sizing 0 0 0.00: 0 0.00 : 0 0 0.00
Exhaust Heat -3 0 -3 -0.06 I 0.00 I 7 -0.25
Terminal Bypass 0 0 0 0.00 : 0.00 : 0 0.00
I I
I I
Grand Total ==> 4,498 169 .o 5,056 100.00 I
I
4,283 100.00 I -2,025 -2,903 100.00 I
COOLING COIL SELECTION AREAS
Total Capacity Sens Cap. Coil Airfl Enter O8/WB/HR Leave O8/WBIHR Gross Total Glass
tons MBh MBh cfm F F gr/lb F F gr/lb sq ft (%)
Floor 90
Main Clg 0.4 5.1 4.7 265 75.9 63.1 65.9 60.5 56.8 63.2 Part 0
Aux Clg 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 ExFlr 0
Opt Vent 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 Roof 0 0 0
Wall 125 36 29
Totals 0.4 5.1
-·------· -----------------------------.. -----·---·-·-----·------·
TEMPERATURES
Clg Htg
SADB 60.5 76.9
Plenum 75.2 69.5
Return 75.2 69.5
Ret/OA 75.9 67.9
Fn MtrTD 0.0 0.0
Fn BldTD 0.0 0.0
Fn Frict 0.0 0.0
AIRFLOWS
Cooling Heating
Vent 14 14
lnfil 0 0
Supply 265 265
Mincfm 0 0
Return 265 265
Exhaust 14 14
Rm Exh 0 0
Auxil 0 0
ENGINEERING CKS
Cooling Heating
¾OA 5.1 5.1
cfm/sq ft 2.94 2.94
cfm/ton 628.82
sq ft/ton 213.60
Btu/hr-sq ft 56.18 -29.10
No. People· 1
HEATING COIL SELECTION
Capacity Coil Airfl Ent Lvg
MBh cfm F F
Main Htg -2.6 265 67.9 76.9
Aux Htg 0.0 0 0.0 0.0
Preheat 0.0 265 67.9 60.5
Reheat 0.0 0 0.0 0.0
Humidif 0.0 0 0.0 0.0
Opt Vent 0.0 0 0.0 0.0
Total -2.6
Project Name: INVITROGEN TRACE® Load 700 calculated at 01 :34 PM on 08/05/1998
Dataset Name: C:\CDS\LOAD700\PROJECTS\INVITRO.LDS
Room -159
Room Checksums~
By G.E.M. Engineering
-·----------·---·-··----------
COOLING COIL PEAK : CLG SPACE PEAK : HEATING COIL PEAK
I I
I I Peaked at Time: Mo/Hr: 8/14 I Mo/Hr: 8 / 14 I Mo/Hr: 13 / 1
Outside Air: OADB/WB/HR: 89 / 71 / 83 I OADB: 89 I OADB: 38 I I
I I
Space Ret. Air Ret. Air Net Percent : Space Percent : Space Peak Coil Peak Percent
Sens.+ Lat. Sensible Latent Total Of Total , Sensible Of Total , Space Sens Tot Sens Of Total
Btuh Btuh Btuh Btuh (%): Btuh (%) : Btuh Btuh (%)
Envelop.e Loads I I
Skylite Solr 0 0 0 0.00 : 0 0.00 : 0 0 0.00
Skylite Cond 0 0 0 0.00 I 0 0.00 I 0 0 0.00
Roof Cond I I 0 0 0 0.00 I 0 0.00 I 0 0 0.00
Glass Solar 1,829 0 1,829 5.69 : 1,829 8.01 : 0 0 0.00
Glass Cond 1,669 0 1,669 5.20 I 1,669 7.31 I -4, 115 -4, 115 33.36
Wall Cond 618 458 1,075 3.35 : 618 2.70 : -1,532 -2,669 21.64
Partition 0 0 0.00 I 0 0.00 I 0 0 0.00
Exposed Floor 0 0 0.00 : 0 0.00 : 0 0 0.00
Infiltration 0 0 0.00 I 0 0.00 I -0 -0 0.00
Sub Total==> 4,115 458 4,573 14.24 : 4,115 18.02 : -5,647 -6,784 . 55.00
Internal Loads 1 I
Lights 7,254 0 7,254 22.59 : 7,254 31.76 : 0 0 0.00
People 4,782 4,782 14.89 1 2,657 11.63 I 0 0 0.00
Misc 8,705 0 0 8,705 27.11 : 8,705 38.11 : 0 0 0.00
Sub Total ==> 20,742 0 0 20,742 64.59 : 18,617 81.51 I
I 0 0 0.00
Ceiling Load 109 -109 0 0.00 I 109 0.48 1 -212 0 0.00
Outside Air 0 0 0 4,591 14.29 : 0 0.00 : 0 -5,687 46.10
Sup. Fan Heat 1,575 4.90 I 0.00 I 0 0.00
Ret. Fan Heat 787 787 2.45 : 0.00 0 0.00
Duct Heat Pkup 0 0 0.00 1 0.00 0 0.00
OV/UNDR Sizing 0 0 0.00 : 0 0.00 0 0 0.00
Exhaust Heat -152 0 -152 -0.47 I 0.00 136 -1.10
Terminal Bypass 0 0 0 0.00 : 0.00 0 0.00
I
1
Grand Total==> 24,966 985 0 32,116 100.00 I
I 22,841 100.00 -5,859 -12,335 100.00
COOLING COIL SELECTION AREAS
Total Capacity Sens Cap. Coil Airfl Enter DB/WB/HR Leave DB,WB/HR Gross Total Glass
tons MBh MBh cfm F F gr/lb F F gr/lb sq ft (%)
Floor 1,063
Main Clg 2.7 32.1 27.9 1,329 77.5 63.9 67.2 58.5 56.0 62.8 Part 0
Aux Clg 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 ExFlr 0
Opt Vent 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 Roof 0 0 0
Wall 325 114 35
Totals 2.7 32.1
TEMPERATURES
Clg Htg
SADB 59.6 74.0
Plenum 75.3 69.2
Return 75.8 69.2
ReUOA 77.5 65.5
Fn MtrTD 0.1 0.2
Fn BldTD 0.2 0.2 ' Fn Frict 0.7 0.7
AIRFLOWS
Cooling Heating
Vent 159 159
lnfil 0 0
Supply 1,329 1,329
Mincfm 0 0
Return 1,329 1,329
Exhaust 159 159
RmExh 0 0
Auxil 0 0
ENGINEERING CKS
Cooling Heating
%OA 12.0 12.0
cfm/sq ft 1.25 1.25
cfm/ton 496.39
sq ft/ton 397.10
Btu/hr-sq ft 30.22 -11.84
No. People 11
HEATING COIL SELECTION
Capacity Coil Airfl Ent Lvg
MBh cfm F F
Main Htg -12.6 1,329 65.5 74.0
Aux Htg 0.0 0 0.0 0.0
Preheat 0.0 1,329 65.5 58.5
Reheat 0.0 0 0.0 0.0
Humidif 0.0 0 0.0 0.0
Opt Vent 0.0 0 0.0 0.0
Total -12.6 '.
Project Name: INVITROGEN TRACE® Load 700 calculated at 01:34 PM on 08/05/1998
Dataset Name: C:\CDS\LOAD700\PROJECTS\INVITRO.LDS
Room Checksums J By G.E.M. Engineering .
• •----·---M••---------------------·-----
Room -160
COOLING COIL PEAK : CLG SPACE PEAK : HEATING COIL PEAK TEMPERATURES
I I
I I Peaked at Time: Mo/Hr: 8 / 16 I Mo/Hr: 8 / 16 I Mo/Hr: 13 / 1 Clg Htg
Outside Air: OADBNVB/HR: 89 / 71 / 83 I OADB: 89 I OADB: 38 SADB 59.7 80.7 I I
I I Plenum 75.3 69.2
Space Ret. Air Ret. Air Net Percent ' Space Percent : Space Peak Coil Peak Percent Return 75.8 69.2
Sens.+ Lat. Sensible Latent Total Of Total Sensible Of Total , Space Sens Tot Sens Of Total Ret/OA 78.0 64.2
Btuh Btuh Btuh Btuh (%) Btuh (%) : Btuh Btuh (%) Fn MtrTD 0.1 0.2
Envelope Loads I Fn BldTD 0.2 0.2
Skylite Solr 0 0 0 0.00 0 0.00 : 0 0 0.00 Fn Frict 0.7 0.7
Skylite Cond 0 0 0 0.00 0 0.00 I 0 0 0.00
RoofCond 0 0 0 0.00 0 I AIRFLOWS 0.00 I 0 0 0.00
Glass Solar 0 0 0 0.00 0 0.00 : 0 0 0.00
Glass Cond 0 0 0 0.00 0 0.00 I 0 0 0.00 Cooling Heating
Wall Cond 0 0 0 0.00 0 0.00 : 0 0 0.00 Vent 20 20
Partition 181 181 5.79 181 8.60 I -396 -396 18.32 lnfil 0 0
Exposed Floor 0 0 0.00 0 0.00 0 0 0.00 Supply 123 123
Infiltration 0 0 0.00 0 0.00 -0 -0 0.00 Mincfm 0 0
Sub Total==> 181 0 181 5.79 I 181 8.60 -396 -396 18.32 Return 123 123
Internal Loads Exhaust 20 20
Lights 901 0 901 28.86 901 42.89 0 0 0.00 RmExh 0 0
People 594 594 19.03 330 15.71 0 0 0.00 Auxil 0 0
Misc 676 0 0 676 21.65 676 32.16 0 0 0.00
Sub Total ==> 2,171 0 0 2,171 69.54 1,907 90.76 0 0 0.00 ENGINEERING CKS
Ceiling Load 14 -14 0 0.00 14 0.64 I 0 0 0.00
Outside Air 0 0 0 570 18.26 0 0.00 : 0 -706 32.68 Cooling Heating
Sup. Fan Heat 146 4.68 0.00 I 0 0.00 %OA 16.1 16.1
Ret. Fan Heat 73 73 2.34 0.00 : 0 0.00 cfm/sq ft 0.93 0.93
Duct Heat Pkup 0 0 0.00 I 0.00 I 0 0.00 cfm/ton 473.58
OV/UNDR Sizing 0 0 0.00 0 0.00 : -1,076 -1,076 49.78 sq ft/ton 507.39
Exhaust Heat -19 0 -19 -0.60 I 0.00 I 17 -0.78 Btu/hr-sq ft 23.65 -17.41
Terminal Bypass 0 0 0 0.00 : 0.00 : 0 0.00 No. People 1
I I
I I
Grand Total ==> 2,365 41 0 3,122 100.00 I 2,101 100.00 I -1,472 -2, 161 100.00 HEATING COIL SELECTION I I
COOLING COIL SELECTION AREAS Capacity CoilAirfl Ent Lvg
MBh cfm F F
Total Capacity Sens Cap. Coil Airfl Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Main Htg -2.3 123 64.2 80.7
tons MBh MBh cfm F F gr/lb F F gr/lb sq ft (%) Aux Htg 0.0 0 0.0 0.0
Floor 132 Preheat 0.0 123 64.2 58.6
Main Clg 0.3 3.1 2.6 123 78.0 64.2 67.9 58.6 55.9 62.6 Part 138 Reheat 0.0 0 0.0 0.0
Aux Clg 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 ExFlr 0 Humidif 0.0 0 0.0 0.0
Opt Vent 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 Roof 0 0 0. Opt Vent 0.0 0 0.0 0.0
Wall 0 0 0
Totals 0.3 3.1 Total -2.3
Project Name: INVITROGEN TRACE® Load 700 calculated at 01:34 PM on 08/05/1998
Dataset Name: C:\CDS\LOAD700\PROJECTS\INVITRO.LDS
Room -163
Room Checksums
By G.E.M. Engineering
---------------·-------------
COOLING COIL PEAK : CLG SPACE PEAK : HEATING COIL PEAK
Peaked at Time:
Outside Air:
Envelope Loads
Skylite Solr
Skylite Con'd
Roof Cond
Glass Solar
Glass Cond
Wall Cond
Partition
Exposed Floor
Infiltration
Sub Total ==>
Internal Loads
Lights
People
Misc
Sub Total ==>
Ceiling Load
Outside Air
Sup. Fan Heat
Rel. Fan Heat
Duct Heat Pkup
OVIUNDR Sizing
Exhaust Heat
Terminal Bypass
Grand Total==>
Space
Sens.+ Lat.
Btuh
0
0
0
1,152
1,051
186
570
0
0
2,959
2,457
1,200
1,638
5,296
49
0
0
8,304
Mo/Hr: 8 / 14
OADB/WB/HR: 89 / 71 / 83 I
I
Ret. Air Rel. Air
Sensible Latent
Btuh Btuh
0
0
o·
0
0
211
211
0
0
0
-49
0
268
0
-34
0
396
0
0
0
0
0
0
Net
Total
Btuh
0
0
0
1,152
1,051
397
570
0
0
3,171
2,457
1,200
1,638
5,296
0
1,037
535
268
0
0
-34
0
Percent :
Of Total 1
(%):
I
0.00 :
0.00 I
0.00
11.22
10.23
3.87
5.55
0.00
0.00
30.87
I
23.92
11.68
15.95 I
51.55 :
0.00
10.09
5.21
2.61
0.00
0.00
-0.33
0.00
10,272 100.00
COOLING COIL SELECTION
Total Capacity Sens Cap. Coil Airfl Enter DB/WBIHR
tons MBh MBh cfm F F gr/lb
Main Clg 0.9 10.3 9.2 452 76.9 63.5 66.4
Aux Clg 0.0 0.0 0.0 0 0.0 0.0 0.0
Opt Vent 0.0 0.0 0.0 0 0.0 0.0 0.0
Totals 0.9 10.3
Mo/Hr: 8 / 14
OADB: 89
Mo/Hr: 13 / 1
OADB: 38
Space
Sensible
Percent : Space Peak
Space Sens
Coil Peak Percent
Btuh
0
0
0
1,152
1,051
186
570
0
0
2,959
2,457
600
1,638
4,696
49
0
0
7,704
Of Total 1
(%) :
0.00 :
0.00 I
0.00 I
14.95 :
13.64 I
2.41 :
7.40 I
0.00 :
0.00 I
38.41 :
I
31.90 :
7.79 I
21.26 :
60.95 :
0.64 I
0.00 :
0.00 I
0.00 :
0.00 I
0.00 :
0.00 I
0.00 :
I
100.00 I
I
Leave DB/WB/HR
F F gr/lb
Floor
58.6 56.1 63.1 Part
0.0 0.0 0.0 ExFlr
0.0 0.0 0.0 Roof
Wall
Tot Sens Of Total
Btuh
0
0
0
0
-2,592
-461
-1,404
0
-0
-4,457
0
0
0
0
-122
0
-819
-5,397
AREAS
Gross Total
480
488
0
0
150
Btuh (%)
0 0.00
0 0.00
0 0.00
0 0.00
-2,592 36.75
-986 13.97
-1,404 19.90
0 0.00
-0 0.00
-4,982 70.62
0 0.00
0 0.00
0 0.00
0 0.00
0 0.00
-1,284 18.21
0 0.00
0 0.00
0 0.00
-819 11.61
31 -0.44
0 0.00
-7,054 100.00
Glass
sq ft (%)
0 0
72 48
TEMPERATURES
Clg Htg
SADB 59.7 80.7
Plenum 75.3 69.2
Return 75.8 69.2
Ret/OA 76.9 66.8
Fn MtrTD 0.1 0.2
Fn BldTD 0.2 0.2
Fn Friel 0.7 0.7
AIRFLOWS
Vent
lnfil
Supply
Mincfm
Return
Exhaust
Rm Exh
Auxil
Cooling
36
0
452
0
452
36
0
0
Heating
36
0
452
0
452
36
0
0
ENGINEERING CKS
%QA
cfmlsq ft
cfmlton
sq ft/ton
Btu/hr-sq ft
No. People
Cooling
8.0
0.94
527.78
560.76
21.40
2
Heating
8.0
0.94
-14.65
HEATING COIL SELECTION
Main Htg
Aux Htg
Preheat
Reheat
Humidif
Opt Vent
Total
Capacity Coil Airfl
MBh cfm
-7.0 452
0.0 0
0.0 452
0.0 0
0.0 0
0.0 0
-7.0
Ent Lvg
F F
66.8 80.7
0.0 0.0
66.8 58.6
0.0 0.0
0.0 0.0
0.0 0.0
Project Name: INVITROGEN TRACE® Load 700 calculated at 01 :34 PM on 08/05/1998
• Dataset Name: C:\CDS\LOAD700\PROJECTS\INVITRO.LDS
Room -164
Room Checksums
By G.E.M. Engineering
COOLING COIL PEAK : CLG SPACE PEAK : HEATING COIL PEAK
I I
I I
Peaked at Time: Mo/Hr: 8 / 14 I Mo/Hr: 8 / 15 I Mo/Hr: 13 / 1
Outside Air: OADB/WB/HR: 89 / 71 / 83 I OADB: 90 I OADB: 38 I
I
Space Ret. Air Ret. Air Net Percent Space Percent : Space Peak Coil Peak Percent
Sens.+ Lat. Sensible Latent Total Of Total Sensible OfTotal 1 Space Sens Tot Sens Of Total
Btuh Btuh Btuh Btuh (%) Btuh (%) : Btuh Btuh (%)
Envelope Loads I
Skylite Solr 0 0 0 0.00 0 0.00 : 0 0 0.00
Skylite Cond 0 0 0 0.00 0 0.00 I 0 0 0.00
Roof Cond I 0 0 0 0.00 0 0.00 I 0 0 0.00
Glass Solar 0 0 0 0.00 I 0 0.00 : 0 0 0.00
Glass Cond 0 0 0 0.00 I 0 0.00 I 0 0 0.00
WallCond 0 0 0 0.00 : 0 0.00 : 0 0 0.00
Partition 0 0 0.00 I 0 0.00 I 0 0 0.00
Exposed Floor 0 0 0.00 : 0 0.00 ~ 0 0 0.00
Infiltration 0 0 0.00 I 0 0.00 I -0 -0 66.67
Sub Total ==> 0 0 0 0.00 I 0 0.00 : -0 -0 66.67
Internal Loads I
lights 710 0 710 14.75 710 15.59 : 0 0 0.00
People 520 520 10.81 260 5.71 I 0 0 0.00
Misc 3,584 0 0 3,584 74.44 3,584 78.69 : 0 0 0.00
Sub Total ==> 4,814 0 0 4,814 100.00 4,554 100.00 I 0 0 0.00
Ceiling Load 0 0 0 0.00 0 0.00 0 0 0.00
Outside Air 0 0 0 0 0.00 0 0.00 0 0 0.00
Sup. Fan Heat 0 0.00 0.00 0 0.00
Ret. Fan Heat 0 0 0.00 : 0.00 0 0.00
Duct Heat Pkup 0 0 0.00 I 0.00 0 0.00
OV/UNDR Sizing 0 0 0.00 : 0 0.00 -0 -0 33.33
Exhaust Heat 0 0 0 0.00 I 0.00 0 0.00
Terminal Bypass 0 0 0 0.00 : 0.00 0 0.00
I
I
Grand Total==> 4,814 0 0 4,814 100.00 I 4,554 100.00 -0 -0 100.00
I
COOLING COIL SELECTION AREAS
Total Capacity Sens Cap. Coil Airfl Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass
tons MBh MBh cfm F F gr/lb F F gr/lb sq ft (%)
Floor 104
Main Clg 0.4 4.8 4.6 231 75.0 62.6 65.0 57.3 55.6 63.3 Part 0
Aux Clg 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 ExFlr 0
Opt Vent 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 Roof 0 0 0
Wall 0 0 0
Totals 0.4 4.8
·----·-·---·------
TEMPERATURES
Clg Htg
SADB 57.3 70.1
Plenum 75.0 70.0
Return 75.0 70.0
Ret/OA 75.0 70.0
Fn MtrTD 0.0 0.0
Fn BldTD 0.0 0.0
Fn Frict 0.0 0.0
AIRFLOWS
Cooling Heating
Vent 0 0
lnfil 0 0
Supply 231 231
Mincfm 0 0
Return 231 231
Exhaust 0 0
Rm Exh 0 0
Auxil 0 0
ENGINEERING CKS
Cooling Heating
%OA 0.0 0.0
cfm/sq ft 2.22 2.22
cfm/ton 576.17
sq ft/ton 259.34
Btu/hr-sq ft 46.27 -0.25
No. People 1
HEATING COIL SELECTION
Capacity Coil Airfl Ent Lvg
MBh cfm F F
Main Htg -0.0 231 70.0 70.1
Aux Htg 0.0 0 0.0 0.0
Preheat 0.0 231 70.0 57.3
Reheat 0.0 0 0.0 0.0
Humidif 0.0 0 0.0 0.0
Opt Vent 0.0 0 '0.0 0.0
Total -0.9
Project Name: INVITROGEN TRACE® Load 700 calculated at 01:34 PM on 08/05/1998
Dataset Name: C:\CDS\LOAD700\PROJECTS\INVITRO.LDS
..
Room Checksums J
By G.E.M. Engineering
-·----·-. -. ·----·---·-. ------------
Room -165
COOLING COIL PEAK : CLG SPACE PEAK : HEATING COIL PEAK TEMPERATURES
I I
I I Peaked at Time: Mo/Hr: 9 / 15 I Mo/Hr: 8/15 I Mo/Hr: 13 / 1 Clg Htg
Outside Air: OADB/WB/HR: 89 / 71 / 85 I OADB: 90 I OADB: 38 SADB 57.3 70.1 I I
I I Plenum 75.0 70.0
Space Ret. Air Ret. Air Net Percent : Space Percent : Space Peak Coil Peak Percent Return 75.0 70.0
Sens.+ Lat. Sensible Latent Total Of Total 1 Sensible Of Total , Space Sens Tot Sens Of Total Ret/OA 77.8 63.5
Btuh Btuh Btuh Btuh (%) : Btuh (%) : Btuh Btuh (%) Fn MtrTD 0.0 0.0
Envelope Loads I I Fn BldTD 0.0 0.0
Skylite Solr 0 0 0 0.00 : 0 0.00 : 0 0 0.00 Fn Frict 0.0 0.0
Skylite Cond 0 0 0 0.00 I 0 0.00 I 0 0 0.00
Roof Cond 0 0 I 0 0.00 I 0 I 0.00 I 0 0 0.00 AIRFLOWS
Glass Solar 0 0 0 0.00 : 0 0.00 : 0 0 0.00
Glass Cond 0 0 0 0.00 I 0 0.00 I 0 0 0.00 Cooling Heating
Wall Cond 0 O· 0 0.00 : 0 0.00 : 0 0 0.00 Vent 40 40
Partition 0 0 0.00 I 0 0.00 I 0 0 0.00 lnfil 0 0
Exposed Floor 0 0 0.00: 0 0.00 : 0 0 0.00 Supply 195 195
Infiltration 0 0 0.00 I 0 0.00 -0 -0 0.00 Mincfm 0 0
Sub Total ==> 0 0 0 0.00: 0 0.00 -0 -0 0.00 Return 195 195
Internal Loads I Exhaust 40 40
Lights 1,814 0 1,814 32.01 : 1,814 47.25 0 0 0.00 Rm Exh 0 0
People 1,328 1,328 23.45 I 664 17.31 0 0 0.00 Auxll 0 0
Misc 1,360 0 0 1,360 24.01 : 1,360 35.44 0 0 0.00
Sub Total ==> 4,502 0 0 4,502 79.47 I 3,838 100.00 0 0 0.00 ENGINEERING CKS
Celling Load 0 0 0 0.00 0 0.00 0 0 0.00
Outside Air 0 0 0 1,163 20.52 0 0.00 0 -1,422 100.00 Cooling Heating
Sup. Fan Heat 0 0.00 0.00 0 0.00 ¾OA 20.5 20.5
Ret. Fan Heat 0 0 0.00 0.00 0 0.00 cfmlsq ft 0.73 0.73
Duct Heat Pkup 0 0 0.00 0.00 0 0.00 cfmlton 412.65
OV/UNDR Sizing 0 0 0.00 0 0.00 -0 -0 0.00 sq Wton 562.80
Exhaust Heat 0 0 0 0.00 0.00 0 0.00 Btu/hr-sq ft 21.32 -5.43
Terminal Bypass 0 0 0 0.00 0.00 0 0.00 No. People 3
I
I !
Grand Total ==> 4,502 0 0 5,665 100.00 I
I
3,838 100.00 -0 -1,422 100.00 HEATING COIL SELECTION
COOLING COIL SELECTION AREAS Capacity Coil Airfl Ent Lvg
MBh cfm F F
Total Capacity Sens Cap. Coll Airfl Enter DB/WB/HR Leave DB/WBIHR Gross Total Glass Main Htg -1.4 195 63.5 70.1
tons MBh MBh cfm F F gr/lb F F gr/lb sq ft (%) Aux Htg 0.0 0 0.0 0.0
Floor 266 Preheat 0.0 195 63.5 57.3
Main Clg 0.5 5.7 4.5 195 77.8 64.4 69.0 57.3 54.8 60.2 Part 0 Reheat 0.0 0 0.0 0.0
Aux Clg 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 ExFlr 0 Humidif 0.0 0 , 0.0 0.0
Opt Vent 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 Roof 0 0 0 Opt Vent 0.0 0 0.0 0.0
Wall 0 0 0
Totals 0.5 5.7 Total -1.4
Project Name: INVITROGEN TRACE® Load 700 calculated at 01:34 PM on 08/05/1998
• Dataset Name: C:\CDS\LOAD700\PROJECTS\INVITRO.LDS
.,.
·. TIFICATE OF COMP:µANCE--:~: ---= -:· ._--_. · -_(Partl ofl) _:· .-· :_ -. · ENV-1 ·_
I PROJECT NAME
-·";EC! ADDRESS y _:.:J /6(}fJ ---A£ADA VEt/0E
BUILDING TYPE bZ)
PHASE OF CONSTRUCTION D
METHODOFENVELOPE
COMPLIANCE
BUILDING CONDlTJONED FLOOR AREA f;'3 ) 7
NONRESIDENTIAL D HIGH RISE RESIDENTIAL
NEW CONSTRUCTION D ADDITION iXf ALTERATION
COMPONENT D OVERALL ENVELOPE
BwldJng Pemm #
Chcci<ed by/Date
Enior=nc:m Agency Use
I CLIMATE ZONE /
D HOTEUMOTEL GUEST ROOM
0 UNCONDITIONED (file affidavit)
D PERFORMANCE
STATEMENT.OF-COMPLIANCE.-.·_-.-::·.,-. -. ·'. ~---· · ,.,.-:'.',::,.··· · __ :--· · ., -.-,_~:-.. · -·-_, .. ··: ·: :·.. ·_ · .-.... · · .< ;,_-_·:.-:-.~~ _::
!This Certificate of compliance lists the building features and performance specifications need to comply with Title 24, Parts 1
and 6 of the California Code of Regulations. This certificate applies only to building envelope requirements.
The documentation preparer hereby certifies that the documentation is accurate and complete.
DATE~ ')'}
The Principal Envelope Designer hereby certifies tllat the proposed building design represented in this set of constructio~
docume?ts is cons_istent ':i~ t~e othe: com~lia~ce forms and worksh_ee~, with the speci_fications, and with any other ~ ~
-~lat1ons submitted with this permit apphcat10n. The proposed butldmg has been designed to meet the envelope \._j
·--. rements contained in sections 110, 116 through 118, and 140, 142, 143, or 149 ofTitle 24, Part 6.
Please check one:
JZJ I hereby affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code to sign this
document as the person responsible for its preparation; and that I am a civil Engineer or Architect.
0 I affirm that I am eligibl~ under the exemption to Division 3 of the Business and Professions Code by section 5537.2 of the
Business and Professions Code to sign this document as the person responsible for its preparation; and that I am a licensed
contractor preparing documents for work that I have contracted to perform.
D I affirm. that I am eligible under the exemption to Division 3 of the Business and Professions Code by section ___ _
of the------''--------Code to sign this document as the person responsible for its preparation; and for the
following reasons: ________________________ _
PRINCll'AL ENVELOPE DESIGNER-NAME SIGNATURE DATE LlC.a
Indicate location on plans of Note Block for Mandatory Me~ures/ '-.... M_.... .... ! ___ .,_o ______________ __.
!Fr,.---Qetailed instructions on the use of this and all Energy Efficiency Standards compiiance forms, please refer to the Nonresidential Manual
'·, )hed by the California Energy Commission .
. J-1: Required on plans for all submittals. Part 2 may be incorporated in schedules on plans. /'7 .tRQ-::72
jENV-2: Used for all subrnittals; choose appropriate version depending on method of envelope compliance. ~c?"t(J • :-{i'iG V
fNV-3: Optional. Use if default U-values are not used. Choose appropriate version for assembly U-value to be calculated.
Nonresidential Compliance Form January 1996
CERrIFJCATEOFCOMPLJANCE (Part2of2)·· _. .-· . .-_ENV-t:·
!:; I PROJECTNAME JJJ ri-rgo:,erJ TI.
INSULATION R-VALUE
(cg. R-19, R-22, etc.) (eg. Block, Wood, Metal)
All f<.-J/
WINDOWS_-·_..,, ____ .... -~= -~ _.:; ---=-·---'..,_ .-·· _ .. -----..... --:.....· _ ... _ --'$ •• ·-.: ... -.. ; ; •.. · .. : -~·''. --~-• .::_·'!. _..;(~.:-f~·.i -·~-.:.:..-.. :-~-::.---. --. ...... -~ --.
WINDOW NAME NO.OF U-VALUE FRAME TYPE EXTERIOR OVERHANG GLAZING TYPE NOTE TO FIELD
(eg. Windq_w-1) PAINS (Metal, Wood. etc.) SHADE? CREDIT? (eg. Clear. Tinted) Building Dept. Use
JJIA I, ~:>(~ ~~}
l ..,/
-~ _._ ..
) ..
-~::-----
SKYLIGHTS (. .. . . . . .. : :
SKYLJGHT NAME NOOF U-VALUE FRAME TYPE SKYLJGHT MATERIAL GLAZJNG TYPE NOTE TO FIELD
(cg. Sky-I) PANES (Metal, Wood. etc.) (Glass. Plastic. etc.) (Clear, Low-E, etc.) Building Dept. Use
N/11
I
l~[Oiiif.ii•JWliill•OM•ffllfili·ld•Ji1!!,i11ii•ii•tttm\P-
1"·
\._
Nonresidential Comoliance Form January 1996
ENVELOPE COMPONENT METHOD -· . . ·,. --_-.-_._-. ; .· ENV.:2:
[ PROJECT NAME (lJ 1/ Jr[! 0 h &J rr;
DOW AREA CALCULATION SKYLIGHT AREA CALCULATION •
GROSS WALL DISPLAY ATRIUM HEIGHT I Irr AREA(GWA) PERIMETER (DP
GWA x 0.4 DP x 6
IF:!>!IT l
I I IF> 55 IT
I ~ GREATER OF 0.10 I X I I = I I l I 0.05 IX I I I l 'I -If the PROPOSED
I I MAXIMUM WINDOW AREA is GROSS ROOF AREA ALLOWED SKY. AREA
greater than the ALLOWABLE
~ WINDOW AREA
MAXIMUM
ALLOWABLE
WINDOW AREA, go If the ACTUAL SKYLIGHT AREA is greater
to another method. ~ PROPOSED than the ALLOWED SKYLIGIIT AREA. go to
WINDOW another method. ACTUAL SKY. AREA
OP.AQUE"SURFACES .-~ --:···...:. ---C .-.. -,_,;---. : .... , ~:•:•., • ,-:-:1,.:_ :·~·:.::::-• •w,;:,:, ~• ,: ""• • .. :..,., :---· • ..,·~· -.:<-=-___:.•-l..., ;.-'"-..:•--,,._ .,.._ a • .... ;
ASSEMBLY U-VALUE
TABLE
ASSEMBLY NAME TYPE HEAT INSULATION R-VALUE VALUES?
(cg. Wall-!, Floor-!) (eg. Roof, Wall. Floor) CAPACITY PROPOSED MIN. ALLOWED PROPOSED I y I NI MAX. ALLOWED
f,NAll WALL 12-J) J?.-1) OD
.... DD
DD
DD
DD
* For each assembly type, meet the minimum insulation R-value or the maximum assembly U-value.
WINDOWS ... ·.··:· .. : .. -· . ' . .. . . .....
PROPOSED RSHG
WINDOW NAME ORIENTATION U-VALUE #OF PROP. ALLOW.
(e.g., Winqow-1, Wandow-2) N I E I s I w PROP. ALLOW. PANES SC H V HIV OHF RSHG RSHG
JJ//4 D D D D
D D D D
D D D D
D D D D
SKYI.IGHTS .. .. . -. . . . '
SKYLIGHT NAME GLAZING #OF U-VALUE SHADING COEFFICIENT
(e.g.,,Sky-1, Sky-2) TRANSLUCENT I TRANSPARENT PANES PROPOSED ALLOWED PROPOSED ALLOWED
JJ/A D D
I D D
__ }:. D D
D D
Nonresidential Compliance Form January 1996
PROPOSED MASONRY WALL·ASSEMBLY: .-.. -· · ·.. . ··ENV-3-::
~ I PROJE~ ~AME L JJ iJ J T RtJ at N TJ:
' -·
ASSEMBLY NAME
DESCRIPTION 71/.f.1
' 6~1'/CIETl
(. OF ASSEMBLY
v w w 0
(f) .., 0 ,.
f-(f) :::, .. z
0 (
i \
SKETCH OF ASSEMBLY
WALL'R-VALUEandHEATCAPACITY .. · . ·.·· . ·,:·-.-· .. -··,··:· ··. :,'.·.'..:·.:. · .-·. · : · .·: ·. : .. .-.
NOMINAL INCHES
-·-....
WALL UNIT THICKNESS
MA TERlAL TYPE
CORE TREATMENT
WALL R-V ALUE
WALL HEAT CAPACITY
JJA
(L W CMU,MW CMU, NW CMU, CLAY UNIT. CLAY BRICK, CONCRETE.)
(SOLID. GROUTED, EMPTY. INSULATED. NA)
E--Rw (FROM TABLE B-5 or B-6)
17.fO HC (FROM TABLE B-5 or B-6)
FURRING/INSULATIONLAYER(INSIDEand/or-OUTS.IDEJF-ANY): .... ~.: :.-··' .-:,..: .'.·:·-·· . .-: !.:>.: .. ':·_.;,_·",.:
FURRING FRAMING MATERIAL
FURRING FRAMING SIZE
FURRING SPACE INSULATION
EXTERIOR INSULATING AREA
(WOOD. MET AL. NONE)
-? 1/-;i.. )\ I NOMINAL INCHES
~ .fl 8A7[ I TYPE
-I TYPE
12 // -
FURRING ASSEMBLY EFFECTIVE R-VALUE EXTERIOR INSULATING LA YER R-V ALUE
+ -· (FROM TABLE B-7) (FROM MANUFACTURER)
. INSULATION LAYER R-VALUE WALLR-VALl!,E WALL ASSEMBLY R-VALUE 7 I 5. ~! l+.__I __ J.--=-3R?-~--_ ___,l=I 6.§05 ~I
Nonresidential Compliance Form
ACTUAL INCHES
R-VALUE
R-VALUE
INSULATION
LAYER
R-VALUE
= 5. 2--5 !Rf
WALL ASSEMBLY U-V ALUE
01 JS-/ (:
I/Rt '-. .•
January 1991
CERTIFICATE OF COMPLIANCE -.. (Partt of3)_ . MECH-1
s-,3-1&
BUILDING TYPE ~ NONRESIDENTIAL o.HIGH RISE RESIDENTIAL
DATEC;' .,.,. /9 ;, 0 "->, , (7
Building Permit#
Checked byLDatc
Enforcement Agency Use
OHOTEL/MOTEL GUESTR00M
PHASE OF CONSTRUCTION D NEW CONSTRUCTION 0 ADDITION ~ ALTERATION OUNCONDIT10NED {file affidavit)
METHOD OF MECHANICAL
COMPLIANCE
~ PRESCRIPTIVE D PERFORMANCE
D ENVELOPE COMPLIANCE ATTACHED
This Certificate of Compliance lists the building features and performance specifications need to comply with Title 24, Parts l
and 6 of the California Code of Regulations. This certificate applies only to building mechanical requirements.
The documentation preparer hereby certifies that the documentation is accurate and complete.
DATE~-13 9~
The Principal Mechanical Designer hereby certifies that the proposed building design represented in this set of construction
documents is consistent with the other compliance fonns and worksheets, with the specifications, and with any other
J-J.culations submitted with this pennit application. The proposed building has been designed to meet the mechanical
0··.....::;... _-uirements contained in the applicable parts of Sections 110 through 115, 120 through 124, 140 through 142, 144 and 145.
Please check one:
~ I hereby affirm that I am eligible under the provisions of Division 3 of the ·Business and Professions Code to sign this
document as the person responsible for its preparation; and that I am a Civil Engineer, Mechanical Engineer, or Architect.
0 I affirm that I am eligible under the exemption to Division 3 of the Business and Professions Code by Section 5537.2 of
the Business and Professions Code to sign this document as the person responsible for its preparation; and that I am a
licensed contractor preparing documents for work that I have contracted to perform.
D I affirm that I am eligible under the exemption to Division 3 of the Business and Profession~ Code by Section ---of the ___________ Code to sign this document as the person responsible for its preparation; and for the
following reason(s): _______________________ _
SIGNATURE
Indicate location on plans of Note Block for Mandatory Measures .... / _fvJ ___ )'""'._(J _____________ ___,
INSTRUCTIONS.TO APPLICANT; ::.,·, . ·. ···. · .,,;., .. -·::_·>· .. , ···· :. · .. :,-~ .. ·'":·-.-· · .. -: ., : -. ,-. · ·
For Detailed instructions on the use of this and all Energy Efficiency Standards compliance forms, please refer to the Nonresidential Manual
published by the California Energy Commission.
MECH-!: Required on plans for all submittals. Parts· 2 & 3 may be incorporated in schedules on plans.
·-) ~.-C:CH-2: Required for all submittals; choose appropriate version depending on method of mechanical compliance .
._/ · .CH-3: Required for all submittals, but may be incorporated in schedules on plans
MECH-4: Required for all submittals unless required outdoor ventilation rates and airflows are shown on plans per Section 4.3 .4.
Nonresidential Compliance Form January I 996
I PROJECT NAME
WSTEMFEATURES·-.-'.: -.·· -. -· .. · ·. ;_· .. -· =._-.· :·:-, .. :_, -·. ·. ·:.:·.·.·-.--.-.-·_.··-· •.. ·:·=::-:·-:,·.-: .. ::··.-:·: -·.·
MECHANICAL SYSTEMS
/SYSTEM NAME FC./u1-
TIME CONTROL 5
SETBACK CONTROL 0
ISOLATION ZONES /Jiff
HEAT PUMP THERMOSTAT? N
ELECTRIC HEAT? )J
FAN CONTROL /1111/1
VA V MINIMUM POSITION CONTROL? }J
SIMULTANEOUS HEAT/COOL? N
HEAT AND COOL SUPPLY RESET? N
VENTILATION 8
OUTDOOR DAMPER CONTROL? /2
ECONOMIZER TYPE /\I
DESIGN AIR CFM (MECH-4, COLUMN H) S o-c
HEATING EQUIP. TYPE /JIA
HIGH EFFICIENCY? / IF YES ENTER EFF. # -I -
-) MAKE AND MODEL NUMBER
COOLING EQUIP. TYPE
-
$P}..l'T SYS,i,$/v1
HIGH EFFICIENCY? I IF YES ENTER EFF. # Al I -
MAKE AND MODEL NUMBER Tt.AtJl rw£/TWPOi :1D
CODE TABLES: Enter code from table below into columns above.
HEAT PUMP THERMOSTAT? TIME CONTROL SETBACK
CTRL.
ELECTRIC HEAT? S: Prog. Switch H: Heating
0: Occupancy Sensor C: Cooling
VA V MINIMUM POSITION CONTROL? Y: Yes M: Manual Timer B:Both
·SIMULT-:ANEOUS HEAT/COOL? N:No
HEAT AND COOL SUPPLY RESET? VENTILATION OUTDOOR
DAMPER
HIGH EFFICIENCY? B: Air Balance A:Auto
C: Outside Air Cert. G: Gravity
M: Out. Air Measure
D: Demand Control
N: Natural
I
I
ISOLATION
ZONES
Enter number of
Isolation Zones
ECONOMIZER
A:Au
W: Water
N: Not Required
NOTE TO FIELD
Building. Dept. Use
FAN
CONTROL
I: Inlet Vanes
P: V ariablc Pitch
V:VFD
0: Other
C: Curve
0.A. CFM
Enter Outdoor
AirCFM.
Note: This shall
be no less than
Column Gon
MECH-4.
1>10, :if.1 "' w • 5i .. •om 1® M HiJ ,w,m,;" rn, 1 iittt11t@ I . .
Nonresidential Comoliance Form January 199•
CERTIFICATE OF COMPLIANCE {Part3of3) · MECH-I
T INSULATION .
SYSTEM NAME
ALL HP !AN/1~
fc-1
All J.tP LIJ,!J T-'S
rc.-1
· SYSTEM NAME
DUCT TYPE
I DUCT TAPE I
DUCT LOCATION ALLOWED? DUCT INSULATION
(Supply, Return, etc.) (Roof, Plenum, etc.)
-;.111PPLY .J:r(rJl-
5"/IJPllY II lTJt,
R£TM/!tJ I ATfJl
KG11A~rl ff me,
PIPE TYPE
(Supply, Return, etc.)
I YIN I
D~
05?J
DEJ
0:0
DD
DD
DD
DD
DD
DD
DD
REQ'D?
y N
DD
DD
DD
DD
DD
DD
DD
DD
DD
R-VALUE
..{:,6
4.0
4.CJ
4. o
NOTE TO FIELD
Building. Dept. Use
NOTE TO FIELD
Building. Dept. Use
NOTES TO FIELD-For.Buildiqg Department Use Only · _: ·. . .. : · · . . · ·. . . · · · . · .. · ·-.
Nonresidential Comoliance Fonn January 1996
MECHANICAL SIZING AND FAN POWER·.-. · : : · . '·. · .:· ·. 'l\JEClll2<-
PROJECT NAME
SYS1EMNAME
j NOTE: Provide one copy of this fonn for each mechanical system when using the Prescriptive Approach.
SIZING and EQUIPMENT SELECTION · · -· · . ·. . . . · . , · · · · . , .. : : :
1. DESIGN CONDITIONS:
-OUTDOOR, DRY BULB TEMPERATURE (APPENDIX C)
(APPENDIX C)
(APPENDIX C)
COOLING I HEATING I
-OUTDOOR, WET BULB TEMPERATURE
-INDOOR, DRY BULB TEMPERATURE
2. SIZING
-DESIGN OUTDOOR AIR _______ ,CFM (MECH 4; COLUMN H)
-ENVELOPE LOAD
-LIGHTING WA ITS/ SF (LTG-2)
t--------1
-PEOPLE # OF PEOPLE (MECH 4; COLUMN E) ------i 1-----i
-MISC. EQUIPMENT WATTS/SF
-OTHER ( PROCESS LOADS. DUCT ) i--------. -,--------
-OTHER LOSS, INFILTRATION, ETC.. (Describe)
(Describe) TOTALS
SAFETY/ WARM UP FACTOR
MAXIMUM ADJUSTED LOAD (TOTALS FROM ABOVE x SAFETY/ WARMUP FACTOR)
3. SELECTION:
-B 1£ le:
INSTALLED EQUIPMENT CAPACITY (sEI m,~w MttJ T 5-t.Aco/11L£1 5-Jf--r rn-?)~,__ __ __.t....._l __ __,
Kbtu / Hr Kbtu / Hr
IF INSTALLED CAPACITY EXCEEDS MAXIMUM
ADJUSTED LOAD, EXPLAIN
FANPOWERCONSUMPTION · · . .. · . -· · 0 : ··,. , ·.-• ·.·,:·-:···.,'.:_: ., .... ·: :
DESIGN
FAN DESGRIPTION BRAKE HP
fJIA
./
OTE: Include only fan systems exceeding 25 HP (see§ 144).
Total Fan System Power Demand may not exceed 0.8 Watts/CFM for
constant volume systems or 1.25 Watts/CFM for VA V systems.
Nonresidential Compliance Form
EFFICIENCY
MOTOR DRIVE
NUMBER
OF FANS
TOTALS
PEAK WATTS CFM I i B x Ex 746 / (C x D) (Supply Fans)!
TOTAL FAN SYSTEM \·· ·
POWER DEMAND ...,.C-ot"""'. F-/ C-,-0-~-G
WATTS/CFM
January 199
I
MECHANICAL.EQUIPMENT . .-SUMMM{Y. ·· ... ·. · .. ·· -:. -':MEcH.;;,3.:
I -~0-JECTNAME ' I I DATE'& J t:>/ 1 f .,) ;NvJmof;EN yJ:-
LING EQUIPMENT-· ·· . . . . · . · . · -· ,-.
SYSTEM MAKE AND. DESIGN OUTPUT
NAME MODEL NO. (BTU /HR)
f/P-1 $ EE. JS.(l~ )P, Gc,flW 5ffj
f}f-(}_ /
ft,/ [,Vt-1 'I/
l>
TOTAL RATED EFFICIENCY
DESIGNCFM UNITS ALLOWED PROPOSED
flo'\--1 '--
I
r
\IJ
!ECONOMIZER I I y i Ni
D~
D~
D~
DD
DD
DD
DD
DD
.DD
DD
DD
DD
DD
DD
DD
HEATING EQUIPMENT·· · · · . · · · · · ·· _. . · · · --··· .-· ·: ·._·.,, .. ;.,.-··, .. _. · ..
SYSTEM MAKE AND DESIGN OUTPUT RA TED EFFICIENCY
NAME MODEL NO. (BTU /HR) UNITS ALLOWED PROPOSED
1-rP-l sr:e ,;rvv1 lf f;-cff&.o .. ~H1 m-, ......... -./
HP---:L J/ )
~I
"
) ·: --. r-·-·
Nonresidential Compliance Fenn January 1996
•
:
..___
MECHANICAL VENTILATION ·. · . . · .. · · ~MECH-4.-.;
/ PROJECTNAME JNY/Ttot£,J T!2 _ I DATEg/J'?l tJf:~
-\ SYSTEM NAME /, ) . l
_1 IJLL (5££ A7TACtJ.EO UJAD CIJl/,.b /1,Jp :;l{T /VJ.-/ /!Vi-+ fo:; l>E5!tit1 0-5A .·
)
I NOTE: Provide one copy of this form for each mechanical system.
MECHANICAL.VENTILATION · · · -· · ·· · -·· . ·, · ···.: · : .. · .. ,. ··. ~··\
SPACE
NO.
LL
AREA BASIS
COND MIN.
AREA CFM CFM
JSF) PER SF (BXC)
Ii ~-e= .... ..:, ,A7iA tl-leo •
\._
TOTALS (FOR MECH-2)
OCCUPANCY BASIS
REQ'D.
NO. MIN. 0.A. DESIGN
OF CFM (MAX.OF. OUTDOOR
PEOPLE (EX 15) DORF) AIR
~O~lJ CJ4l, ~ ~ ilf'vtJ 1,:;rr rn.,. l/fv'i-4 fo
/
II*
Based on Expected Number of Occupants or at least 50% of Chapter 33 UBC Occupant Density
Must be greater than or equal to G, or·use Transfer Air
[IJ
VAY MINIMUM
CFM
LARGEST DESIGN
MIN. MIN.
CFM CFM
f.' O£t;JeitJ -OSn)
TRANS-I
FER
AIR
r.,,. 1
j
i------1
IC; Minimum Ventilation Rate per Section§ 121, Table 1-F.
If zone reheat or recool is used. I must be less than or equal to G, or less than or equal to Total Design CFM X 0.3, or less than or equal to BX 0.4, or less,~ ..
or equal to 300 CFM, whichever is larger.
Must be less than or equal to I (if applicable), but no less than G, unless Transfer Air (K) is used .
Must be greater than or equal to (G -H), and,.for VAV, greater than or equal to (G -J).
Nonresidential Compliance Fann January 1996
''
~~P-08•98 10: 26 t . FROM-INVITROGEN 760-603-7201 T-447 P.OZ/02 F-483
September 8, 1998
City of Carlsbad
2075 .Las Palmas Dr
Carlsbad, CA 92009
Re: Invio:ogen building pen"tit
Dear City Official:
lam writing to inform yoµ o·: the designated use fo.r the space that will be improved at 1600
F~aday Avenue, Carlsbad. CA 92008.
~ooms 152, 154, 155 & l56 will lle used for light manufacturing of research products.
The research products are us,:d in the b1omedlcal industry.
Thank you for your consider:uion.
Troy W. Gardner
Assistant Di.rector, Engim:ering
HiOO F,ir..1My A11en1..e, Carlsbad, CA 92006
(800i %5-6288 ID!..i. i'REi: (715()) ov3-7200 1'110:vE 1760) 603-720i •·~-'I
:/~ / /
September 21. 19S•8
lnvitrogen Tenant Improvement
1600 Faraday Ave
Garlsbad, CA
Hazardous Materictl lnven1ory
Location Chemk:al Nani 1 -154 Acetonitrile
154 Tetrazole/ A•::etonitrile·
154 Acetonitrflei A.cetic Anhydride
154 Acetonitrile/Methylimidazole/
Pyridine
154 0,3% Trfchloroacetic Acid/Methylene
Chloride (Dablock)
154 o.OSM lodinerretrahydorfuran/
P~ri~!~~@:<idizer1
...
156 Ethyl Alcoh·JI
156 lsoproovl A:cohol
156 Acrviamide.'Bis-ac~lamide (19:1)
156 Bis-ac!)'.larr·ide
156 Acrylamide
156 Terned
156 Formamide
156 1 Sodium Borohydride
156 1 N Hvdrochloric Acid
156 1 N __ Sodium ~vdroxide
----·-...
Exempt Quantitie~; Summary
Classitieation Quantity Comments
1-8 57 oat.
1-B 4gal.
1-9, 1.5 gal.
Corrosive
1-B. 1,Sgal.
Corrosive
Corrosive 1.5 gal.
1-B, 1.5 gal.
Oxidizer
1-B 3 aal.
1-8 0.5 gal.
Toxic 5 lbs.(.5 aal.)
Toxic L21bs.
Toxic 11.1 lbs.
1-8 0.25 aal.
111-8 0.25 oal.
No class 0.251bs.
Corrosive 0.25 gal.
Corrosive 0.25 aal.
All material is use,j in Closed System or Storage. There is no Open Use of
material. The total amour:it of aggregate quantities for Closed and Storage is
less that the exerr t t II d th B O _;p amo1Jn s a owe us ccup~ncv
Classificatio'i
--Class 1-8
Flammable liQui d
Class 111-B
Combustible LIQ uid
zer Class 2 Oxidi
Corrosive -Toxic --·--
·-·--
Actual Quantities
In new Tenant
lmprcvement
-· 69.25 gal.
.25 g1:1t.
10.5 lbs. (1.5 gal.)
·-5 gal. -17.3 "bs.
-·
Actual Actual
Quantities Quantities
In remaining In Entire
bulldina Buildino
40gal. 109.5 gal.
5 gal. 5.25 gal.
10 lbs. (1 gal.) 20.Slbs. (2.5
gal.)
25 gal. 30 gal.
105 lbs. 122.3 lbs.
Allowable Quantities
per UBC Ta~es 3-D
and 3-E
-120 gal.
26.400 gal.
500 lbs.
1,000 gal.
1,000 lbs.