HomeMy WebLinkAbout1624 CORTE ORCHIDIA; ; CB153386; PermitCity of Carlsbad
1635 Faraday Av Carlsbad, CA 92008
Plumbing/Mechanical/Electrical (PME) Permit
10-08-2015 Permit No: CB153386
Building Inspection Request Line (760) 602-2725
Job Address: 1624 CORTE ORCHIDIA CBAD
Permit Type: PME Status: ISSUED
Parcel No: 2159500600 Lot #: 0 Applied: 10/08/2015
Entered By: RMA
Reference #: Plan Approved: 10/08/2015
PC #: Issued: 10/08/2015
Inspect Area:
Project Title: REID RES-NEW A/C UNIT
Applicant: Owner:
OAK ISLAND HEATING AND AIR
STE 103
1250 PACIFIC OAKS PL
ESCONDIDO CA 92029
760 839-8383
Plumbing Fees
Electrical Fees
Mechanical Fees
Other PME Fees
TOTAL PERMIT FEES
Total Fees: $163.00 Total Payments To Date
$0.00
$0.00
$163.00
$0.00
$163.00
$163.00 Balance Due: $0.00
FINAL A ROVAL
Inspector: �'-�'P��"�S Date: ZDiS Clearance:
NO nCE Please take NONCE that approval of your project includes the °Irrpositic ' ot fees, dedcaticns, reservations, or other exactions hereafter collectively
referred to as "fees/exactions." You have 90 days from the date this permit was issued to protest imposition of these fees/exactions. If you protest them you mist
follow the protest procedures set forth in Goverrrnent Code Section 66020(a), and file the protest and any other required information with the City Manager for
processing in accordance with Carlsbad Municipal Code Section 3.32.030. Failure to timely follcwthat procedure will bar any subsequent legal action to attack,
redew, set aside, void, or annul their imposition.
You are hereby FURTHER NOTIFIED that you right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection fees and capacity
changes, nor planing, zoning, grading or other similar application processing or service fees in eoruiection with this project. NOR DOES ITAPPLYto any
fees/exactions of which you have Pre\Acusly been cpven a NOTICE similarto this or as to which the statute of limitations has previously otherwise red.
THE FOLLOWING APPROVALS REQUIRED PRIOR TO PERMIT ISSUANCE: PLANNING ENGINEERING BUILDING FIRE HEALTH HAZMATIAPCD
Building Permit Application
Plan Check No.
Est. Value
1635 Faraday Ave., Carlsbad, CA 92008
C I T Y 0 t Ph: 760-602-2719 Fax: 760-602-8558
Plan Ck. Depos't
CARLSBAD email: building@carlsbadca.gov
www.carlsbadca.gov
Date SWPPP
JOB ADDRESS 1624 CORTE ORCHIDIA
SUITE#/SPACE#/UNIT
APN - - -
CT/PROJECT #
LOT #
PHASE # # OF UNRS
# BEDROOMS
# BATHROOMS TENANT BUSINESS NAME
CONSTR. TYPE
OCC. GROUP
DESCRIPTION OF WORK: Include Square Feet of Affected Area(s)
ADD 1 NEW A/C UNIT
TO AN A/C PREPPED HOME
i
EXISTING USE
PROPOSED USE
GARAGE (SF)
PATIOS (SF)
DECKS (SF)
FIREPLACE
AIR CONDITIONING IFIRESPRINKLERS
YESD NO[::]
YES❑N0E-1
I YESONOF]
APPLICANT NAME TOM WOOD
PROPERTY OWNER NAME MIKE REID
Prins Contact
ADDRESS
ADDRESS
1250 PACIFIC OAKS PL. #103
1624 CORTE ORCHIDIA
_
CITY STATE ZIP
CITY STATE ZIP
_ ESCONDIDO CA 92029
CA_RLSBAD CA 92011
PHONE
FAX
PHONE
FAX
760 839-8383
760 839-8380
760-815-2032
EMAIL
_
EMAIL
INFO@OAKISLANDAC.COM
DESIGN PROFESSIONAL
CONTRACTOR BUS. NAME
ISLAND HEATING AND AIR
ADDRESS
_OAK
ADDRESS
1250 PACIFIC OAKS PL #103
CITY STATE ZIP
CITY STATE ZIP
ESCONDIDO CA 92029
PHONE
_
FAX
PHONE
FAX
760 839-8383
760 839-8380
EMAIL
EMAIL
IN_FO@OAKISLANDAC.COM
STATE LIC. it
STATE LIC.#
CLASS
CITY BUS. LIC.#
745400
C.
1212710
(Sec. 7031.5 Business and Professions Code: Any City or County which requires a permit to construct, alter, improve, demolish or repair any structure, prior to its issuance, also requires the
applicant for such permit to file a signed statement that he is licensed pursuant to the provisions of the Contractor's License Law ((Chappter 9, commending with Section 7000 of Division 3 of the
Business and Professions Code) or that he is exempt therefrom, and the basis for the alleged exemption. Any violation of Section 7031.5 by any applicant for a permit subjects the applicant to a
civil penalty of not more than five hundred dollars ($500)).
Workers' Compensation Declaration: I hereby affirm under penalty of perjury one of the following dedarations:
I have and will maintain a certificate of consent to self -insure for workers' compensation as provided by Section 3700 of the Labor Code, for the performance of the work for which this permit is issued.
✓ I have and will maintain workers' compensation, as required by Section 3700 of the Labor Code, for the performance of the work for which this permit is issued. My workers' compensation insurance carrier and policy
number are: Insurance Co. EVEREST NATIONAL INSURANCE Policy No. 7600000635141 Expiration Date 011011120116
Th's section need not be completed if the permit is for one hundred dollars ($100) or less.
Certificate of Exemption: I certify that in the performance of the work for which this permit is issued, I shall not employ any person in any manner so as to become subject to the Workers' Compensation Laws of
California. WARNING: Failure to secure workers' compensation cov ge is unlawful, and shall subject an employer to criminal penatties and civil fines up to one hundred thousand dollars (&100,000), in
addition to the cost of compensation, damages as provided for inn 3706 of the Labor code, Interest and attorney's fees.
.ES CONTRACTOR SIGNATURE �J v [Z]AGENT DATE ' '�17
1 hereby affirm that I am exempt from Contractor's license Law for the following reason:
El I, as owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not intended or offered for sale (Sec. 7044, Business and Professions Code: The Contractor's
License law does not apply to an owner of property who builds or improves thereon, and who does such work himself or through his own employees, provided that such improvements are not intended or offered for
sale. If, however, the building or improvement is sold within one year of completion, the owner -builder will have the burden of proving that he did not build or improve for the purpose of sale).
I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions Code: The Contractor's License Law does not apply to an owner of
property who builds or improves thereon, and contracts for such projects with contractor(s) licensed pursuant to the Contractor's License Law).
I am exempt under Section _ Business and Professions Code for this reason:
1. 1 personally plan to provide the major labor and materials for construction of the proposed property improvement. QYes [::]No
2. 1(have / have not) signed an application for a building permit for the proposed work.
3. 1 have contracted with the following person (firm) to provide the proposed construction (include name address I phone / contractors' license number):
4. 1 plan to provide portions of the work, but I have hired the following person to coordinate, supervise and provide the major work (include name / address / phone I contractors' license number):
5. 1 will provide some of the work, but I have contracted (hired) the following persons to provide the work indicated (include name / address / phone / type of work):
)KPROPERTY OWNER SIGNATURE []AGENT DATE
Is the applicant or future building occupant required to submit a business plan, acutely hazardous materials registration form or risk management and prevention program under Sections 25505, 25533 or 25534 of the
Presley -Tanner Hazardous Substance Account Act? O Yes O No
Is the applicant or future building occupant required to obtain a permit from the air pollution control district or air quality management district? O Yes O No
Is the facility to be constructed within 1,000 feet of the outer boundary of a school site? O Yes 173 No
IF ANY OF THE ANSWERS ARE YES, A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR IS MEETING THE REQUIREMENTS OF THE OFFICE OF
EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT.
I hereby affirm that there is a construction lending agency for the performance of the work this permit is issued (Sec. 3097 (i) Civil Code).
Lender's Name Lender's Address
I certifythatl have read the application and statethatthe above information is correctand ihatthe information on the plans isaccurate. I agreetn oompywifh all City ordhmoesand State laws relatingto buildingcoratruction.
I hereby authorize representative of the City of Carlsbad to enter upon the above mentioned property for inspection purposes. I ALSO AGREE TO SAVE, INDEMNIFY AND KEEP HARMLESS THE CITY OF CARLSBAD
AGAINST ALL LIABILITIES, JUDGMENTS, COSTS AND EXPENSES WHICH MAY IN ANY WAY ACCRUE AGAINST SAID CITY IN CONSEQUENCE OF THE GRANTING OF THIS PERMIT.
OSHA: An OSHA permit is required for excavations over 50' deep and demolition or construction of structures over 3 stories in height.
EXPIRATION: Every permit issued by the Building Official under the provisions of this Code shall expire by limitation and become null and void 4 the building or work authorized by such permit is not commenced within
180 days from the date of such permit or if the building or work authorized by su permit is suspended or abandoned at any time after the work is commenced for a period of 180 days (Section 106.4.4 Uniform Building Cade).
r
,JK
APPLICANT'S SIGNATURE � � V-4 QV- DATE ��
Inspection List
Permit#: CB153386 Type: PME
Date Inspection Item
Inspector Act
11/05/2015 43
AirCond/Furnace Set
- RI
11/05/2015 43
AirCond/Furnace Set
MC AP
11/05/2015 49
Final Mechanical
RI
11/05/2015 49
Final Mechanical
MC FI
REID RES-NEW A/C UNIT
Comments
10-12 PLEASE
10-12 PLEASE
Friday, November 06, 2015 Page 1 of 1
CERTIFICATE OF COMPLIANCE
Alterations to Space Conditioning Systems (formerly CF-IR-ALT-HVAC)
Project Name:
REID RESIDENCE I Date Prepared:
CF 1 R-ALT-02-E
(Page 1 of 3 )
2015-10-07
A. General Information
MR-ALT-02 is applicable to multiple space conditioning systems contained within a single dwelling unit. When multiple dwelling units must be documented,
use one CHR-ALT-02 document for each dwelling unit.
01
Project Name
REID RESIDENCE
02
Date Prepared
2015-10-07
03
Project Location
1624 CORTE ORCHIDIA
04
Building Type
Single family
05
CA City
Carlsbad
06
Dwelling Unit Name
REID RESIDENCE
07
Zip Code
92011
08
Dwelling Unit Conditioned
2388
Floor Area (ft2)
Number of space conditioning
09
Climate Zone
7
10
(SC) systems in this dwelling
1
unit.
B. Space Conditioning (SC) System informationw'' w-a"�°
01
02
03
04;':s
,a , 6
Oi
09
10
i
,<,
y
n
iTk
GIs the S
. "te,
stalling a
'w», �%
r...
SC System
SC System
CFA served
"system a t
rrigetnstallirg
ne�,C
�nstal)�g
nstall�telg
installing
Identification or
Location or Area
by this SC
ducted
containing
system
more than 40
entirely new
entirely new
Name
Served
System (ft2)
system?
component?
components?
feet of ducts?
duct system?
SC system?
Alteration Type
System 1
Location 1
2388
Yes
Yes
No
No
No
No
Altered space
conditioning system
C. Extension of Existing Duct System, Greater Than 40 Feet (Section 150.2(b)1Diib)
This section does not apply to this project.
Registration Number: 215-A6351004A-000000000-0000
Registration Date/Time
2015-10-07 13:28:57
HERS Provider: CaICERTS
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version: 2013-1.006 Report Generated: 2015-10-07 13:28:52
CERTIFICATE OF COMPLIANCE CF1R-ALT-02-E
Alterations to Space Conditioning Systems (formerly CF-iR-ALT-HVAC) (Page 2 of 3 )
D. Altered Space Conditioning System (Sections 150.2(b)lE and F)
01
02
03
04
05
06
07
08
09
10
11
12
Heating
Cooling
System
Heating
Altered
Heating
Minimum
Altered
Cooling
Minimum
Required
New or
Identification
System
Heating
Efficiency
Efficiency
Cooling
Cooling
Efficiency
Efficiency
Thermostat
Replaced
New Duct
or Name
Type
Components
Type
Value
System Type
Components
Type
Value
Type
Duct Length
R-Value
Central gas
No heating
This field or
This field or
C
Central split
Outdoor
Less than or
System 1
furnace
component
section is not
section is not
AC
condensing
SEER
16
Setback
equal to 40
R-6
altered
applicable
applicable
unit
feet
Required Documentation:
CF2R-MCH-01-E - Space Conditioning Systems Ducts and Fans
-Duct insulation requirement for new plenums: R6.
CF2R-MCH-20-H & CF3R-MCH-20-H — Duct Leakage testing required when heating or cooling components are installed in ducted systems, or when
more than 40 ft of duct length is replaced.
-Leakage rate compliance: < 15%, or <_ 10% leakage to outside, or seal all accessible leaks.
CF2R-MCH-25-H & CF3R-MCH-25-H Refrigerant Charge Verification required when refrigerant containing components are installed
or altered (applicable
in CZ 2, 8-15).
CF2RCF3R-MCH-23 & CF3R-MCH-23 Air Flow 2 300 CE'M/ton required when MCH-25 is required.
Exceptions:
Duct systems registered with HERS provider as previously sealed are exempt from (yfl-20 Duct L age Tef grwh a1
-Heating-only systems and Air Handler Furnace changes do not require venficat', ''of"Ait FI MC 23nake Ciq
1ii(x
-Existing duct systems constructed, insulated or sealed with asbesto re exem from MCIi u ''L age Test "` ui
MAN,;,, mr:r
E. Entirely New or Complete Replacement Dem, wi hpr with out Egy#pmentTy^. hang�e fut (SectiQna•1)�Dliaznd41 0.2(b)1E, F)
This section does not apply to this project.
F. Entirely New or Complete Replacement Space Conditioning System (Section 150.2(b)1C)
This section does not apply to this project.
Registration Number: 215-A6351004A-000000000-0000 Registration Date/Time: 2015-10-07 13:28:57 HERS Provider: CaICERTS
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version: 2013-1.006 Report Generated: 2015-10-07 13:28:52
CERTIFICATE OF COMPLIANCE CF1R-ALT-02-E
Alterations to Space Conditioning Systems (formerly CF-iR-ALT HVAC) (Page 3 of 3 )
Documentation Author's Declaration Statement
1. 1 certify that this Certificate of Compliance documentation is accurate and complete.
Documentation Author Name:
Documentation Author Signature:
Young, Les
e
Company:
Signature Date:
OAK ISLAND HEATING AND AIR CONDITIONING INC
2015-10-07 13:28:57
Address:
CEA/ HERS Certification Identification (if applicable):
1250 PACIFIC OAKS PL # 103
City/State/Zip:
Phone:
ESCONDIDO CA 92029
760-839-8383
Responsible Person's Declaration statement>
I certify the following under penalty of perjury, under the laws of the State of California:
1. The information provided on this Certificate of Compliance is true and correct.
2, 1 am eligible under Division 3 of he Business and Professions Code to accept • responsibility for the building design or system design identified on this Certificate of Compliance (responsible designer).
3. That the energy features and performance specifications, materials, tor7lponents and rpanufactured devices for the buildin design or system desig n identified on this Certificate of Compliance conform to the
requirements of Title 24, Part 1 and Part' 6 of the California Code of 1�'ti'ons. 'i, Axs` y
6t9
4, The building design features or system design features �entified or his Certifi at , f it lance are rtej to yet l . ii ormd�ra provided or�',o t ¢ ica� ct�mpliance documents, worksheets,
calculations, plans and specifications submitted to the e�rcemengency falwi^„this bung pera Jicati k .
^ a..
y.
5. I will ensure that a registered copy of this CertificAo pliance &qwwrit ail ile wit, lie AlWft p#m!tM issued for,01 g, an a ava 666inforcement agency for all applicable
inspections. I understand that a registered copy of t 11 icate of Cornp1 nce is regyi,red to be.included wlth the, documentation the bNtile er prs�yides N the biilli ing owner at occupancy.
Responsible Designer Name: i` s
Respon 4ble Designer Signature,
Young, Les4l
Company:
Date Signed:
OAK ISLAND HEATING AND AIR CONDITIONING INC
2015-10-07 13:28:57
Address:
License:
1250 PACIFIC OAKS PL # 103
745400
City/State/Zip:
Phone:
ESCONDIDO CA 92029
760-839-8383
Digitally signed by Ca10ERTS. This digital signature is provided in order to secure the content of this registered document and in noway implies Registration Provider responsibility for the accuracy of the information.
Registration Number: 215-A6351004A-000000000-0000 Registration Date/Time: 2015-10-07 13:28:57 HERS Provider: CaICERTS
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version: 2013-1.006 Report Generated: 2015-10-07 13:28:52
CERTIFICATE OF INSTALLATION
CF2R-MCH-01-E
Space Conditioning Systems, Ducts, and Fans
(Page 1 of 7 )
Project Name: REID RESIDENCE
Enforcement Agency: City of Carlsbad
Permit Number:
on site
Dwelling Address: 1624 CORTE ORCHIDIA
City: Carlsbad
Zip Code:
92011
A. General Information
01
Dwelling Unit Name
REID RESIDENCE
02
Climate Zone
7
Dwelling Unit Total Conditioned Floor
Number of space conditioning (SC)
03
Area (ft2)
2388
04
systems being altered in this dwelling
1
unit.
05
Certificate of Compliance Type
Prescriptive alterations (CF1R-ALT)
06
Method used to calculate HVAC loads
NotApplicableEquipmentChangeout
07
Calculated dwelling unit Sensible
Cooling Load (Btuh)
This field or section is not applicable
08
Calculated Dwelling Unit Heating Load
This field or section is not a licable
pp
(Btuh)
09
Dwelling Unit Number of Bedrooms
4 m„
�:
qch s"z
MCH-01b Prescriptive Alterations
ng
0,
B. Space Conditioning (SC) System Information p
01
02
03
04
05
06
07
08
09
10
CFA served
Is the SC
Installing a
Installing
SC System
SC System
by this SC
system a
refrigerant
Installing new SC
Installing more
entirely
Installing
Identification or
Location or Area
System
ducted
containing
system
than 40 feet of
new duct
entirely new
Name
Served
(ft2)
system?
component?
components?
ducts?
system?
SC system?
Alteration Type
Altered space
System 1
Location 1
2388
Yes
Yes
Yes
No
No
No
conditioning
system
Registration Number: 215-A6351004A-M0100002A-0000
Registration Date/Time:
2015-10-29 1851:41
HERS Provider: CalCERTS
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version: 2013-1.006 Report Generated: 2015-10-29 12:53:51
CERTIFICATE OF INSTALLATION CF2R-MCH-01-E
Space Conditioning Systems, Ducts, and Fans (Page 2 of 7 )
C. Space Conditioning (SC) System Alterations Compliance Information
01
02
03
04
05
06
07
08
09
10
11
12
13
Central Fan
Integrated
Heating
Cooling
New or
(CFI)
System
Altered
Heating
Minimum
Altered
Cooling
Minimum
Required
Replaced
New
Ventilation
Identification
Heating
Heating
Efficiency
Efficiency
Cooling
Cooling
Efficiency
Efficiency
Thermostat
Duct
Duct
System
or Name
System Type
Component
Type
Value
System Type
Component
Type
Value
Type
Length
R-Value
Status
This field
No heating
or
This field
All new
System 1
Central gas
furnace
componen
section is
or section
Central
cooling
SEER
14
Setback
LTE40Ft
R6
Not a CFI
t altered
,not
is not
split AC
components
system
applicabi
applicable
e
D. Installed Heating Equipment information ,, r .'r: :&
f'
r r"
�o not a
IlkThis t�n�tly to
isole+
,�
dez
u
E. Installed Cooling Equipment information:
01
02
03
04
05
06
07
08
Condenser or Package Unit
Condenser or
Condenser or
Condenser or
System Rated Cooling
Condenser Rated
System Identification
Cooling Efficiency
Cooling Efficiency
Package Unit
Package Unit
Package Unit
Capacity at Design
Nominal Capacity
or Name
Type
Value
Manufacturer
Model Number
Serial Number
Conditions (BTUH)
(ton)
System 1
SEER
14
Lennox
xc14-0 48-230-
5815g13422
48000
4
Notes:
Registration Number: 215-A6351004A-M0100002A-0000
Registration Date/Time:
2015-10-29 1 &51:41
HERS Provider: CaICERTS
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version: 2013-1.006 Report Generated: 2015-10-29 12:53:51
CERTIFICATE OF INSTALLATION CF2R-MCH-01-E
Space Conditioning Systems, Ducts, and Fans (Page 3 of 7 )
F. Extension of Existing Duct System, Greater Than 40 Feet
This section does not apply to this project.
G. Installed Duct System information
This section does not apply to this project.
H. Installed Air Filter Device information
This section does not apply to this project.
I. Air Filter Device Requirements
This section ,Goes not apply to this project.
Registration Number: 215-A6351004A-M0100002A-0000
Q�
'P�
41
71
0
§ Abhp
Registration Date/Time: 2015-10-29 18:51 41
HERS Provider: CalCERTS
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version: 2013-1.006 Report Generated: 2015-10-29 12:53:51
CERTIFICATE OF INSTALLATION CF2R-MCH-01-E
Space Conditioning Systems, Ducts, and Fans (Page 4 of 7 )
J. HERS Verification Requirements
01
02
03
04
05
06
07
08
09
10
MCH2O
MCH21
MCH22
MCH23
MCH25
MCH28
Exemption
from
Minimum
Exemption
R-Value for
AHU Fan
AHU
SC System
SC System
From Duct
Duct
Ducts In
Ducts Located
Efficacy
Airflow
Identification or
Location or Area
Leakage
Leakage
Conditioned
In Cond Space
(W per
Rate (cfm
Refrigerant
Return Duct Design
Name
Served
Requirements
Test
Space
Verification
cfm)
per ton)
Charge
Table 150.0-C or D
System 1
Location 1
No
exemptions
Yes
Not
applicable
No
No
No
No
No
Notes:
Of
'ia�t 4,
act s
i
ro
7
M
ai
�
t
y
Registration Number: 215-A6351004A-M0100002A-0000
Registration Date/Time
2015-10-29 18:51:41
HERS Provider: CalCERTS
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version: 2013-1.006 Report Generated: 2015-10-29 12:53:51
CERTIFICATE OF INSTALLATION CF2R-MCH-01-E
Space Conditioning Systems, Ducts, and Fans (Page 5 of 7 )
K. Space Conditioning Systems, Ducts and Fans Mandatory Requirements and Additional Measures
Note: Additional mandatory requirements from Section 150.0 that are not listed here maybe applicable to some systems. These requirements maybe applicable to only newly! nstalled equipment or portions of the
system that are altered. Existing equipment may be exempt from these requirements.
Heating Equipment
01
Equipment Efficiency: All heating equipment must meet the minimum efficiency requirements of Section 110.1 and Section 110.2(a) and the Appliance Efficiency
Regulations,
02
Controls: All unitary heating systems, including heat pumps, must be controlled by a setback thermostat. These thermostats must be capable of allowing the occupant
to program the temperature set points for at least four different periods in 24 hours. See Sections 150.0(i), 110.2(b).
03
Sizing: Heating load calculations must be done on portions of the building served by new heating systems to prevent inadvertent undersizing or oversizing. See sections
150.0(h)1 and 2).
04
Furnace Temperature Rise: Central forced -air heating furnace installations must be configured to operate at or below the furnace manufacturer's maximum
inlet -to -outlet temperature rise specification. See Section 150.0(h)4.
05
Standby Losses and Pilot Lights: Fan -type central furnace,,,Ai yhot haves ccp*lh6ot ly, ur lr}i r 1. on 110. and Section 110.2(d).
Cooling Equipment,,'
ar• ,G.:. F ! R+ r, ! fin''.: x'vW: A+b'' N' ^Lx A'T• :6c^ 'p '¢F,'
06 Equipment Efficiency: All cooling equipment m meet the3 0tinimllttXt ei gency requlretn,, nts 'Sec its 11p.14'anc( Se fti 1 0 2(a end the Appliance Efficiency
Regulations. n
07
Refrigerant Line Insulation: All refrigerant line insulation in split system air conditioners and heat pumps must meet the R-value and protection requirements of Section
150.0(j)2 and 3, and Section 150.0(m)9.
08
Condensing Unit Location: Condensing units shall not be placed within five (5) feet of a dryer vent outlet. See Section 150.0(h)3A.
09
Sizing: Cooling load calculations must be done on portions of the building served by new cooling systems to prevent inadvertent undersizing or oversizing. See Section
150.0(h)1 and 2.
Air Distribution System Ducts, Plenums and Fans
10
Insulation: In all cases, unless ducts are enclosed entirely in directly conditioned space, the minimum duct insulation value is R-6. Note that higher values may be
required by the prescriptive or performance requirements. See Section 150.0(m)1.
Registration Number: 215-A6351004A-M0100002A-0000
Registration Date/Time:
2015-10-29 18:51:41
HERS Provider: CaICERTS
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version: 2013-1.006 Report Generated: 2015-10-29 12:53:51
CERTIFICATE OF INSTALLATION CF2R-MCH-01-E
Space Conditioning Systems, Ducts, and Fans (Page 6 of 7 )
K. Space Conditioning Systems, Ducts and Fans Mandatory Requirements and Additional Measures
Note: Additional mandatory requirements from Section 150.0 that are not listed here may be applicable to some systems, These requirements may be applicable to only newly installed equipment or portions of the
system that are altered. Existing equipment may be exempt from these requirements.
Connections and Closures: All installed air -distribution system ducts and plenums must be, sealed and insulated to meet the requirements of CIVIC Sections 601.0,
11
602.0, 603.0, 604.0, 605.0 and ANS I/S MAC NA-006-2006: Supply -air and return -air ducts and plenums must be insulated to a minimum installed level of R-6.0 or
enclosed entirely in directly conditioned space as confirmed through field verification and diagnostic testing in accordance with the requirements of Reference
Residential Appendix RA3.1.4.3.8.
Heat Pump Thermostat
12
A thermostat shall be installed that meets the requirements of Section 110.2(b) and Section 110.2(c),
13
The thermostat shall be installed in accordance with the manufacturers published installation specifications
14
First stage of heating shall be assigned to heat pump heating.
15
Second stage back up heating shell be set to come on only when the Indoor set temperature cannot be met
k' ilk'. �y�f'• E^t V'6 mh M^", i�% '•diV
l
The responsible person signature on this complianceAocume t affirm 't It l plicabli a ,elqull tts 104,114 le have b en °iet,
row+;, •a.
Registration Number: 215-A6351004A-M0100002A-0000
Registration Date/Time: 2015-10-29 18:51:41
HERS Provider: CaICERTS
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version: 2013-1.006 Report Generated: 2015-10-29 12:53:51
CERTIFICATE OF INSTALLATION CF2R-MCH.01-E
Space Conditioning Systems, Ducts, and Fans (Page 7 of 7 )
Documentation Author's Declaration Statement
1.1 certify that this Certificate of installation documentation is accurate and complete.
Documentation Author Name:
Young, Les
Documentation Author Signature:
Company:
Signature Date:
OAK ISLAND HEATING AND AIR CONDITIONING INC
2015-10-29 18:51:41
Address:
CEA/ HERS Certification Identification (if applicable):
1250 PACIFIC OAKS PL # 103
City/State/Zip:
Phone:
ESCONDIDO CA 92029
1760-839-8383
Responsible Person's Declaration statement
I certify the following under penalty of perjury, under the laws of the State of California:
1. The information provided on this Certificate of Installation is true and correct.
2. 1 am eligible under Division 3 of the Business and Professions Code in the applicable classification to accept responsibility for the system design, construction, or installation of features, materials,
components, or manufactured devices for the scope P of work identified on this Certificate of Installation, and attest to the declarations in this statement (responsible builder/installer), otherwise I am an
authorized representative of the responsible builder/installer, ;. �,,r k' r .
3.
The constructed or installed features, materials, components or mnufactureC€'ces`thinstallati,ld,ntied o^yithisrtifi� of Installatiopco to 1t'��'plicable codes and regulations, and the
.
installation conforms to the requirements Ivan on th ;a.
q g , pns and cificatro v�r0 d the en ement' f t
4, I reviewed a copy of the Certificate CornPiianclw
of r d by the �n thifi�P00 fic quirentsfrtl s�pe ofinuctEn o I on identified on this Certificate of
Installation, and I have ensured that the requireme
apply to the construction or installation have been met,
5. 1 will ensure that a registered copy of this Certificate of In" ilation shad b posted or tW da avar4�able with tku bui It tg po mit�s) is $ a for'the t wlc(jng and made vailable to the enforcement agency for all
applicable inspections. I understand that a registered copy o`'f this Certificate oflrrstallation is required to be included with the "documentation thb builder provides to the building owner at occupancy.
Responsible Builder/Installer Name:
Young, Les
Responsible Builder/Installer Signature: es
Company Name: (Installing Subcontractor or General Contractor or Builder/Owner)
Position With Company (Title):
OAK ISLAND HEATING AND AIR CONDITIONING INC
MGR
Address:
CSLB License:
1250 PACIFIC OAKS PL # 103
745400
City/State/Zip:
Phone:
—72015-10-29
Date Signed:
ESCONDIDO CA 92029
760-839-8383
18:51:41
Digitally signed by CaICERTS. This digital signature is provided in order to secure the content of this registered document, and in noway implies Registration Provider responsibility for the accuracy of the information.
Registration Number: 215-A6351004A-M0100002A-0000 Registration Date/Time: 2015-10-29 18:51:41 HERS Provider: CaICERTS
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version: 2013-1.006 Report Generated: 2015-10-29 12:53:51
CERTIFICATE OF INSTALLATION
CF2R-MCH-20-H
Duct Leakage Diagnostic Test
(Page 1 of 3 )
Project Name: REID RESIDENCE
Enforcement Agency:
Carlsbad
City of
Permit Number: on site
Dwelling Address: 1624 CORTE ORCHIDIA
City:
Carlsbad
Zip Code: 92011
A. System Information
01
Space Conditioning System Identification or Name
System 1
02
Space Conditioning System Location or Area Served
Location 1
03
Building Type from CF-111
Single family
04
Verified Low Leakage Ducts in Conditioned Space
(VLLDCS) Credit from CF1R?
No, credit is not taken
05
Verified Low Leakage Air Handling Unit (VLLAHU) Credit
from CF1R?
No, credit is not taken
06
Duct System Compliance Category
Alteration
MCH-20d -Complete Repiacemi.0t or At�red Dlify�evg-
B. Duct Leakage Diagnostic Test
01
Condenser Nominal Cooling Capacity (ton)
4
02
Heating Capacity (kBtu/h)
0
03
Conditioned Floor Area served by this HVAC system (ft2)
2388
04
Duct Leakage Test Condition
Test final
05
Duct Leakage Test Method
Total leakage
06
Leakage Factor
0.15
07
Air Handling Unit Airflow (AHUAirflow) Determination
Method
Cooling system method
08
Measured AHUAirflow
This field or section is not applicable
09
Calculated Target Allowable Duct Leakage (cfm)
240
10
Actual duct leakage rate from leakage test measurement
(cfm )
163
11
Compliance Statement
System passes leakage test
Registration Number: 215-A6351004A-M2000002A-0000 Registration Date/Time: 2015-10-29 18:51:41 HERS Provider: CaICERTS
CA Building Energy Efficiency Standards Report Version: 2013-1.006 Report Generated: 2015-10-29 12:54:34
2013 Residential Compliance Schema Version: 2013.1.006
CERTIFICATE OF INSTALLATION CF2R-MCH-20-H
Duct Leakage Diagnostic Test (Page 2 of 3 )
C. Additional Requirements for Compliance
01
System was tested in its normal operation condition. No temporary taping allowed.
Outside air (OA) ducts for Central Fan Integrated (CFI) ventilation systems, shall not be sealed/taped off during duct leakage
02
testing. CFI OA ducts that utilize controlled motorized dampers, that open only when OA ventilation is required to meet
ASHRAE Standard 62.2, and close when OA ventilation is not required, may be configured to the closed position during duct
leakage testing.
03
If a complete replacement, all supply and return register boots were sealed to the drywall.
04
Building cavities were not used as plenums or platform returns in lieu of ducts.
05
If cloth backed tape was used it was covered with Mastic and draw bands.
06
All connection points between the air handler and the supply and return plenums are completely sealed.
If the system complies using the Smoke Test method, the smoke test was conducted in accordance with the requirements
07
of Reference Residential Appendix RA3.1.4.3.6. Systems that comply using smoke test shall not be included in sample
groups for HERS verification compliance.
The responsible persons signature on this cottrli lance. locuCipe a fien-W1. at ap�gfhh e r uirements 1 this table heye
been met.,
Registration Number: 215-A6351004A-M2000002A-0000 Registration Date/Time: 2015-10-29 18:51:41 HERS Provider: CaICERTS
CA Building Energy Efficiency Standards Report Version: 2013-1.006 Report Generated: 2015-10-29 12:54:34
2013 Residential Compliance Schema Version: 2013.1.006
CERTIFICATE OF INSTALLATION CF2R-MCH-20-H
Duct Leakage Diagnostic Test (Page 3 of 3 )
Documentation Author's Declaration Statement
1. I certify that this Certificate of Installation documentation is accurate and complete.
Documentation Author Name:
Documentation Author Signature
Les Young
Company:
Signature Date: 2015-10-29 18:51:41
OAK ISLAND HEATING AND AIR CONDITIONING INC
Address:
CEA/ HERS Certification Identification (if applicable):
1250 PACIFIC OAKS PL # 103
City/State/Zip:
Phone:
ESCONDIDO CA 92029
760-839-8383
Responsible Person's Declaration statement
I certify the following under penalty of perjury, under the laws of the State of California:
1. The information provided on this Certificate of Installation is true and correct.
2. 1 am eligible under Division 3 of the Business and Professions Code in the applicable classification to accept responsibility for the system design,
construction, or installation offeatures, materials, components, or manufactured devices for the scope of work identified on this Certificate of
Installation and attest to the' declarations in this statement (responsible builder/installer), otherwise I am an authorized representative of the
responsible builder/installer.
3. The constructed or installed features, materials, components or manufactured devices (the installation) identified on this Certificate of Installation
conforms to all applicable codes and regulations , rid the installation cots ms Wthe re u#remegg n on -the plans ands ecifications approved by
the enforcement agency.10 #
4. 1 understand that a HERS rater wql check th nsta11 tion to Wrif coliln ance, tat i Fchecl g �defit s defects I m Mqurr d ttt-Ae
t
corrective action at my exp rise inderstant rthat Enemy C mrx ssi a and HE Providrt re esenf ives will ego per, rrrt;qua ty asLrAce checking
fir. F
,
of installations, including tilt Zll l--,oved as p fi sa64i rr p Ak hAk0W �y1HER rater,and i p�� i allatioks fad to Meet t 0 .%
requirements of such quality asr:l ce checking, the required corrective action and addition heck /tesbngof�bPer installations in that HERS
sample group will be performed att expense.: '
S. I reviewed a copy of the Certificate of Compliance approved by the enforcement agency that identifies the specific requirements for the scope of
construction or installation identified on this Certificate of Installation, and I have ensured that the requirements that apply to the construction or
installation have been met.
6. 1 will ensure that a registered copy of this Certificate of Installation shall be posted, or made available with the building permit(s) issued for the
building, and made available to the enforcement agency for all applicable inspections. I understand that a registered copy of this Certificate of
Installation is required to be included with the documentation the builder provides to the building owner at occupancy.
Responsible Builder/Installer Name:
Responsible Builder/Installer Signature:
Les Young
ow
Company Name: (Installing Subcontractor or General Contractor or
Position With Company (Title):
Builder/Owner)
MGR
OAK ISLAND HEATING AND AIR CONDITIONING INC
Address:
CSLB License:
1250 PACIFIC OAKS PL # 103
745400
City/State/Zip:
ESCONDIDO CA 92029
Phone:
760-839-8383
Date Signed:
2015-10-29 18:51:41
Third Party Quality Control Program (TPQCP) Status:
Name of TPQCP (if applicable):
Digitally signed by CaICERTS. This digital signature is provided in order to secure the content of this registered document, and in noway implies Registration Provider
responsibility for the accuracy of the information.
Registration Number: 215-A6351004A-M2000002A-0000 Registration Date/Time: 2015-10-29 18:51:41 HERS Provider: CaICERTS
CA Building Energy Efficiency Standards Report Version: 2013-1.006 Report Generated: 2015-10-29 12:54:34
2013 Residential Compliance Schema Version: 2013.1.006
CERTIFICATE OF VERIFICATION
CF3R-MCH-20-H
Duct Leakage Diagnostic Test
(Page 1 of 3 )
Project Name: REID RESIDENCE
Enforcement Agency:
Carlsbad
City of
Permit Number: on site
Dwelling Address: 1624 CORTE ORCHIDIA
City:
Carlsbad
Zip Code: 92011
A. System Information
01
Space Conditioning System Identification or Name
System 1
02
Space Conditioning System Location or Area Served
Location 1
03
Building Type from CF-111
Single family
04
Verified Low Leakage Ducts in Conditioned Space
No, credit is not taken
(VLLDCS) Credit from CF1R?
05
Verified Low Leakage Air Handling Unit Credit from
No, credit is not taken
CF1R?
06
Duct System Compliance Category,;
Alteration
i
yYf i�
MCH-20d - Complete Replacem6t or Alkred
... q
n — t nn ♦
e� 5
is
v.
�Yy
B. Duct Leakage Diagnostic Test
01
Condenser Nominal Cooling Capacity (ton)
4
02
Heating Capacity (kBtu/h)
0
03
Conditioned Floor Area served by this HVAC system (ft2)
2388
04
Duct Leakage Test Condition
Test final
05
Duct Leakage Test Method
Total leakage
06
Leakage Factor
0.15
07
Air Handling Unit Airflow (AHUAirflow) Determination
Method
Cooling system method
08
Measured AHUAirflow
This field or section is not applicable
09
Calculated Target Allowable Duct Leakage Rate (cfm)
240
10
Actual duct leakage rate from leakage test measurement
(cfm)
163
11
Compliance Statement: System passes leakage test
Registration Number: 215-A6351004A-M2000002A-M20A Registration Date/Time: 2015-10-29 18:13:00 HERS Provider: CaICERTS
CA Building Energy Efficiency Standards Report Version: 2013-1.006 Report Generated: 2015-10-29 18:12:41
2013 Residential Compliance Schema Version: 2013.1.006
CERTIFICATE OF VERIFICATION CF3R-MCH-20-H
Duct Leakage Diagnostic Test (Page 2 of 3 )
B. Duct Leakage Diagnostic Test
12 Notes:
C. Additional Requirements for Compliance
01
System was tested in its normal operation condition. No temporary taping allowed.
02
Outside air (OA) ducts for Central Fan Integrated (CFI) ventilation systems, shall not be sealed/taped off during duct leakage
testing. CFI OA ducts that utilize controlled motorized dampers, that open only when OA ventilation is required to meet
ASHRAE Standard 62.2, and close when OA ventilation is not required, may be configured to the closed position during duct
leakage testing.
03
If a complete replacement, all supply and return register boots were sealed to the drywall.
04
Building cavities were not used as plenums or platform returns in lieu of ducts.
05
If cloth backed tape was used it was covered with Mastic and draw bands.
06
All connection, points between the air handier and the supply and return plenums are completely sealed.
07
If the system complies using the Smogtest me0", I$e inoke t t ras :on"cte m a ordance wilh t� ►'equir�Pri nts
of Reference Residential A dix RA �1.4.3 6 ll
pp �r�s i�at comply usin srr�ike trot shah nit be inin a�ttple
for HERS verifica
groups o pliance.
08
Verification Status
Pass - all applicable requirements are met-
09
Correction Notes for this table
The responsible persons signature on this compliance document affirms that all applicable requirements in this table have
been met unless otherwise noted in the Verification Status and the Corrections Notes in this table.
D. Determination of HERS Verification Compliance
All applicable sections of this document shall indicate compliance with the specified verification protocol requirements in order
for this Certificate of Verification as a whole to be determined to be in compliance.
01 1 Complies: All specified verification protocol requirements on this document are met.
Registration Number: 215-A6351004A-M2000002A-M20A Registration Date/Time: 2015-10-29 18:13:00 HERS Provider: CaICERTS
CA Building Energy Efficiency Standards Report Version: 2013-1.006 Report Generated: 2015-10-29 18:12:41
2013 Residential Compliance Schema Version: 2013.1.006
CERTIFICATE OF VERIFICATION CF3R-MCH-20-H
Duct Leakage Diagnostic Test (Page 3 of 3 )
Documentation Author's Declaration Statement
1.1 certify that this Certificate of Verification documentation is accurate and complete.
Documentation Author Name:
Documentation Author Signature. -
Jason Solarez
A"A���'�
Company:
Date Signed:
Air-Tite Duct Testing
2015-10-29 18:13:00
Address:
CEA/ HERS Certification Identification (if applicable):
2386 Warmlands Ave
City/State/Zip:
Phone:
Vista CA 92084
760-231-9444
Responsible Person's Declaration statement
I certify the following under penalty of perjury, under the laws of the State of California:
1. The information provided on this Certificate of Verification is true and correct.
2. 1 am the certified HERS Rater who performed the verification identified and reported on this Certificate of Verification (responsible rater).
3. The installed features, materials, components, manufactured devices, or system performance diagnostic results that require HERS verification
identified on this Certificate of Verification comply with the applicable requirements in Reference Appendices RA2, RA3, and the requirements
specified on the Certificate of Compliance for the building approved by the enforcement agency.
4. The information reported on applicable sectutNe Certifica(s) f?fillaWs(f21�dteifirby the perjn(s) responsible for the
construction or installation conforms to thlquiremen spec& the CeAicate(s f C p6ar a (C approved by ie met*-ftency.
5. I will ensure that a registered co;of this Cei#ificate ofy at(pn all be poet'or rieailabe with tilding perit(� issuiBd fir the
building, and made availal to tl enforcerf j a n (fQ 11 pil e P Slans, l nder Land fiat a f p eredcopy e tht tert $cat�of,.
Verification is required to be"' with the documentation the budder provides to the building owner afoccupi"hcy70
Builder Or Installer information As Shown On`The"Certificate Of Installation '
Company Name (Installing Subcontractor, General Contractor, or Builder/Owner):
OAK ISLAND HEATING AND AIR CONDITIONING INC
Responsible Builder or Installer Name:
CSL74B License:
Les Young
5400
HERS Provider Data Registry Information
Sample Group Number (if applicable):
Dwelling Test Status in Sample Group (if applicable)
Tested
HERS Rater Information
HERS Rater Company Name:
Air-Tite Duct Testing
Responsible Rater Name:
Responsible Rater Signature:
Jason Solarez
Responsible Rater Certification Number w/ this HERS Provider:
Date Signed:
CC2006013
2015-10-29 18:13:00
Digitally signed by CaICERTS. This digital signature is provided in order to secure the content of this registered document, and in noway implies Registration Provider
responsibility for the accuracy of the information.
Registration Number: 215-A6351004A-M2000002A-M20A Registration Date/Time: 2015-10-29 18:13:00 HERS Provider: CaICERTS
CA Building Energy Efficiency Standards Report Version: 2013-1.006 Report Generated: 2015-10-29 18:12:41
2013 Residential Compliance Schema Version: 2013.1.006