Project Title: HARRIS RES-ADD 390 SF FAMILY
RM@ 1ST FLOOR, 198 SF STORAGE ROOM ATTACHED, 242 SF
CARPORT,72 SF COVERED ENTRY
Applicant:
SAM WRIGHT
2911 STATE ST
CARLSBAD CA 92008
760 213-1460
Building Permit
Add'l Building Permit Fee
Plan Check
Add'l Plan Check Fee
Plan Check Discount
Strong Motion Fee
Park in Lieu Fee
Park Fee
LFM Fee
Bridge Fee
Other Bridge Fee
BTD #2 Fee
BTD #3 Fee
Renewal Fee
Add'l Renewal Fee
Other Building Fee
HMP Fee
Pot. Water Con. Fee
Meter Size
Add'l Pot. Water Con. Fee
Reel. Water Con. Fee
Green Bldg Stands (SB1473) Fee
Green Bldg Stands Plan Chk Fee
$547.32
$0.00
$383.12
$0.00
$0.00
$10.63
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$4.00
$163.00
Total Fees: $1,278.84 Total Payments to Date:
Inspector:
Owner:
HARRIS TODD J
1630 BASSWOOD AVE
CARLSBAD CA 92008
Meter Size
Add'l Reel. Water Con. Fee
Meter Fee
SDCWA Fee
CFD Payoff Fee
PFF (3105540)
PFF (4305540)
License Tax (3104193)
License Tax (4304193)
Traffic Impact Fee (31 05541)
Traffic Impact Fee (4305541)
Sidewalk Fee
PLUMBING TOTAL
ELECTRICAL TOTAL
MECHANICAL TOTAL
Housing Impact Fee
Housing lnlieu Fee
Housing Credit Fee
Master Drainage Fee
Sewer Fee
Additional Fees
Fire Sprinkler Fees
TOTAL PERMIT FEES
$1,278.84 Balance Due:
Clearance:
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$80.00
$46.00
$44.77
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$1,278.84
$0.00
NOTICE: Aease take NOTICE Ita awtMli c:i yw: ~ed irdudes tt-e "lfTllCS!ion" c:i fees, ds:icatiCJlS, reservalioos, or dher exadims hereafter oolledively
referred to as "fees'exadicn;," You 1-eve 00 days fn:m tt-e date this pemit Y.eS issued to prdest irrpositioo c:i these fees'exadicn;, If~ prdest them, ~ nust
fdlo.vtt-e prdest ~set fath in <?oJerrvreri Ccxle Sedioo66J2l(a), !I'll file tt-e prdest !I'll fnl cther reqliral irtarratioo wth tt-e aty M:n:ger for
~rg in acxm:lcrrewth Ca1stm M.ridpal CcxleSectim3.32.030. Faih.retotirrelyfdlo.vthat pocecirewlll:a'fnfSlJ:eeq.Jert legal ooimto attock,
review, set aside, \odd, or crn.d their iJllXlSition.
You ae ller"el'f R.RTH:R NOTIAEDthat yw: rigt to prdest tt-e specifiedfees'ex<rlims OC£S NOT APA...Ytowcter !I'll SEMercxn'lEldioofees ard capacity
da'lges, nor plmrg, mrg, g;:drg or dher sinilw awicaioo ~rg or servlre fees in cxn'lEldim wth this ~ed. I'm OC£S IT APR.. Y to fnl . . . . . . li . . . . .
'
City of Carlsbad
1635 Faraday Av Carlsbad, CA 92008
05-11-2016
Storm Water Pollution Prevention Plan (SWPPP) Permit
Permit No:SW160056
Job Address:
Permit Type:
Parcel No:
Reference #:
CB#:
Project Title:
Applicant:
SAM WRIGHT
760 213-1460
Emergency Contact:
SAM WRIGHT
760 213-1460
1630 BASSWOOD AV CBAD
SWPPP
2050602800
CB160551
HARRIS ADDITION
SWPPP Plan Check
SWPPP Inspections
Additional Fees
TOTAL PERMIT FEES
Status:
Lot#: 0 Applied:
Entered By:
Issued:
Inspect Area:
Owner:
HARRIS TODD J
1630 BASSWOOD AVE
CARLSBAD CA 92008
Tier:
Priority:
ISSUED
02/11/2016
RMA
05/11/2016
1
L
$49.00
$59.00
$0.00
$108.00
Total Fees: $108.00 Total Payments To Date: $108.00 Balance Due:
FINAL APPROVAL
DATE#CIEARAHCE. __ _
SIGNATURE ~
$0.00
THE FOLLOWING APPROVALS REQUIRED PRIOR TO PERMIT ISSUANCE: 0PLANNING D ENGINEERING 0BUILDING OFIRE 0HEA';.TH D HAZMAT/APCD
Ccicyof Building Permit Application Plan Check No. {_:/~ ll~_Zl ~55"
1635 Faraday Ave., Carlsbad, CA 92008 Est. Value ~~~ 8'1 ~~'c.t
Ph: 760-602-2719 Fax: 760-602-8558 ~. Carlsbad PlanCk. Dep ~sit r
email: building@carlsbadca.gov ~A-
Date f1 J \1 (L ISWPPP www.carlsbadca.gov
JOB\'CP?c
SUITEt/SPACEt/UNITI V
5~-s.s.~~(,:,\? /'"fe__ rPN 2oS -o'-O -?.b -00
CT/PROJECT # JLOT# _I PHASE#
1
#OF UNITS r BEDROOMS #BATHROOMS I TENANT BUSINESS NAME I CONSTR. TYPE I occ. GROUP
DESCRIPTION OF WORK: Include Square Feet of Affected Area(s) LJ~ ~ .. " .. C>~ <.. rP..'-''~'t ~\--t ) -::: ~4 c:::> -
-=::.\'o,~ ~'--Cii:-/{tHifl -17{Mff£!) -:::: \~b
<:..-P--\=>0 ........ '"\ -24-'1.-72. rls 6fJTnj -
EXISTING USE 1-=.:0POSED USE I GARAGE (SF) PATIOS (SF) l DECKS (SF) FIREPLACE ~c¢1 I AIR c~liJ1oNING I FIRE SPRINKLERS
-;.,~. \?. "'~ ... o * YESO N YES NOD YES0Nol:21
APPLICANT NAME SA-A ~F"o\~~T" ~:RTY OWNER NAME k~~y \..-4f'l".~\'"-\""$ Prlnarv Contact 0 \.'"::>\.""";> ,.,"\_Q
ADDRESS ADDRESS
2 ~"' 4>f--~ ...o:>'l· (to~O 1.? .-< ~ \..u t:X..:><.-;::. f-...ve..-•
CITY STATE ~IP CITY STATE ZIP
G--~P.>~ ~Po.. 7.-CJO'C;> <::-P..IIL-"" \?~? C::...A· 9l-0u~
PHONE I FAX PHONE I FAX
7(,p<.:> • "2..\ ~ • \4-~D
EMAIL EMAIL w ~ .. (._.("'(.4. r \-4 flo-.... -s. e ~o~~'-'""'""'C..._ ~ C. ~~\
DESIGN PROFESSIONAL CONTRACTOR BUS. NAME p a.J s C/t?J-17 /2-A-t/T/ Nq
ADDRESS ADDR5-.z.-g6 t#lt?~ j24R. I
CITY STATE ZIP CITY STATC::ft-ZIP q~4 CA 12~$ ff A-2J
PHONE I FAX PHONE ~:X 7~-g"41--~y-? I 7bo -~.2~-UZ-
EMAIL EMAIL ~ I}AA..._ ~q~·~ rt?"115 ;, I STATE uc. # STATELIC.# '! e'd V~ rLASS 6 lc7 ~r; -zR g-
(Sec. 7031.5 Busmess and Professions Code: Any City or County wh1ch requ1res a perm1t to construct, alter, Improve, demolish or repa1r an~ structure, pnor to 1ts 1ssuance, also requ1res the applicant for such permit to file a signed statement that he is licensed pursuant to the provisions of the Contractor's License Law !Chapter 9, commending with Section 7000 of Division 3 of the Business and Professions Code] or that he is exempt therefrom, and the basis for the alleged exemption. Any violation of Section 7031.5 by any applicant for a permit subjects the applicant to a civil penalty of not more than five hundred dollars [$500)).
WORKERS' COMPENSATION
Workers' Compensation Declaration: I hereby affirm under penalty of perjury one of the following declarations: D I have and will maintain a certificate of consent to self-insure for workers' compensation as provided by Section 3700 of the Labor Code. for the performance of the work for which this permit is issued. D I have and will maintain workers' compensation. as reQuired by Section 3700 of the Labor Code. for the performance of the work for which this permit is issued. My workers' compensation insurance carrier and policy
number are: Insurance Co. Policy No. Expiration Date ________ _
. ......!fiis section need not be completed W the permit is for one hundred dollars [$1 00) or less.
'g/Certlficate of Exemption: I certify that in the performance of the work for which this permit is issued, I shall not employ any person in any manner so as to become subject to the Workers' Compensation Laws of
CaiWomia. WARNING: Failure to secure workers' compensation coverage is unlawful, and shall subject an employer to criminal penalties and civil fines up to one hundred thousand dollars (&100,000), in
addition to the cost of compensation, for in Section Labor code, interest and attorney's fees .
.ft5 CONTRACTOR SIGNATURE
I hereby affirm that I am exempt from Contractor's Ucense Law for the following reason:
D
D
D
I, as owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not intended or offered for sale (Sec. 7044, Business and Professions Code: The Contractor's
License Law does not apply to an owner of property who builds or improves thereon, and who does such work himseW or through his own employees, provided that such improvements are not intended or offered for
sale. If, however, the building or improvement is sold within one year of completion, the owner-builder will have the burden of proving that he did not build or improve for the purpose of sale).
I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions Code: The Contractor's License Law does not apply to an owner of
property who builds or improves thereon, and contracts for such projects with contractor(s) licensed pursuant to the Contractor's License Law).
I am exempt under Section Business and Professions Code for this reason:
1. I personally plan to provide the major labor and materials for construction of the proposed property improvement. DYes 0No
2. I (have I have not) signed an application for a building permit for the proposed work.
3. I have contracted with the following person (firm) to provide the proposed construction (include name address I phone I contractors' license number):
4. I plan to provide portions of the work, but I have hired the following person to comdinate, supervise and provide the major work (include name I address I phone I contractors' license number):
5. I will provide some of the work, but I have contracted (hired) the following persons to provide the work indicated (include name I address I phone I type of work):
.ft5 PROPERTY OWNER SIGNATURE 0AGENT DATE
I
I I
COMPLETE THIS SECTION FOR NON-RESIDENTIAL BUILDING PERMITS ONLY
Is the applicant or future building occupant required to subm~ a business plan, acutely hazardous materials registration form or risk management and prevention program under Sections 25505, 25533 or 25534 of the
Presley-Tanner Hazardous Substance Account Act? 0 Yes 0 No
Is the applicant or future building occupant required to obtain a permit from the air pollution control district or air quality management district? 0 Yes 0 No
Is the facility to be constructed within 1,000 feet of the outer boundary of a school site? 0 Yes 0 No
IF ANY OF THE ANSWERS ARE YES, A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR IS MEETING THE REQUIREMENTS OF THE OFFICE OF
EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT.
I certify that I halle read the application and state that the above infonnation Is correct: and that the infonnation on the plans is accurate. I agree to comply l'fith all CH¥ on:linances and Slate laws relating to building construction.
I hereby aulhorize representative of the C~ of Carlsbad to enter upon the above mentioned property br inspection pufj:X)SeS. I ALSO AGREE TO SAVE, INDEMNIFY AND KEEP HARMLESS THE CITY OF CARLSBAD
AGAINST ALL LIABILITIES, JUDGMENTS, COSTS AND WHICH MAY IN ANY WAY ACCRUE AGAINST SAID CITY IN CONSEQUENCE OF THE GRANTING OF THIS PERMIT.
OSHA: An OSHA permtt is required for excavations over of structures over 3 stories in height.
EXPIRATION: Everypermtt issued by the Building · I i by limitation and become nun and void ~the building oroork authorized by such permit is not commenced 'Mthin
180 days rom the date of such permtt or if the or abandoned at any time after the oork is commenced for a period of 180 days (Section 100.4.4 Uniform Building Code).
A$ APPLICANT'S SIGNATURE DATE II . ~ . 2 0 c (p
Inspection List
CB160551 RESDNTL RAD HARRIS RES-ADD 390 SF FAMILY
Date Inspection Item Inspector Act Comments
RM @ 1ST FLOOR, 198 SF STORAGE RO
Permit#: Type:
16 Insulation AEK AP08/04/2016 HOUSE WALLS
18 Exterior Lath/Drywall AEK AP08/03/2016
84 Rough Combo AEK AP08/03/2016
13 Shear Panels/HD's PY AP07/27/2016
13 Shear Panels/HD's PB NR07/26/2016
15 Roof/Reroof AEK AP07/13/2016
14 Frame/Steel/Bolting/Weldin AEK PA07/06/2016 ROOF FRAMING
15 Roof/Reroof AEK PA07/06/2016 1ST LAYER ROOF SHEETING
15 Roof/Reroof AEK CO06/24/2016 REVISE PLAN DETAIL TO SHOW
CURRENT CONDITION
11 Ftg/Foundation/Piers AEK AP05/23/2016
12 Steel/Bond Beam AEK AP05/23/2016
Thursday, December 22, 2016 Page 1 of 1
PERMIT INSPECTION HISTORY REPORT (CB160551)
BLDG-Residential 02/11/2016Application Date:Permit Type:Owner:SALT AND LOOM
Subdivision:Addition 05/11/2016Work Class:Issue Date:
1630 Basswood Av
Carlsbad, CA 92008
Address:01/31/2017Expiration Date:Status:
IVR Number: 712387
Closed - Finaled
Scheduled
Date Inspection Type Inspection No.Inspection Status Primary Inspector Reinspection CompleteActual
Start Date
12/19/2016 12/19/2016 BLDG-Final
Inspection
006138-2016 Failed Andy Krogh Reinspection Complete
COMMENTS PassedChecklist Item
BLDG-Plumbing Final Yes
BLDG-Mechanical Final Yes
BLDG-Structural Final Yes
BLDG-Electrical Final Outlets at carport roof to be GFCI protected No
12/21/2016 12/21/2016 BLDG-Final
Inspection
006498-2016 Passed Andy Krogh Complete
COMMENTS PassedChecklist Item
BLDG-Plumbing Final Yes
BLDG-Mechanical Final Yes
BLDG-Structural Final Yes
BLDG-Electrical Final Yes
December 21, 2016 Page 1 of 1
C City of
Carlsbad
SPECIAL INSPECTION
AGREEMENT
B-45
Development Services
Building Division
1635 Faraday Avenue
760-602-2719
www.carlsbadca.gov
In accordance with Chapter 17 of the California Building Code the following must be completed when work being performed
requires special inspection, structural observation and construction material testing.
Project/Permit: C.BilA055 (
A. THIS SECTION MUST BE COMPLETED BY THE PROPERTY OWNER/AUTHORIZED AGENT. Please check if you are Owner-Builder
D. (If you checked as owner-builder you must also complete Section B of this agreement.)
Name: (Please print1-l __ -::=:;_""""'---~,A_~:.=_=-----__:\~=-=F-'--=-"\.._~,_.,~--'-( ___________________ _
(First) (M.L) (Last)
c-p..
Phone: 7 f.t::C> • 7 7... o · 7 <.P ~ I
I am: I:JProperty Owner JrlProperty Owner's Agent of Record I:JArchitect of Record I:JEngineer of Record
State of California Registration Numbe · Expiration Date: _______ _
AGREEMENT: I, the undersigned, declare under penalty of perjury under the laws of the State of California, that I have read,
understand, acknowledge and promise to comply with the City of Carlsbad requirements for special inspections, structural
observations, constructio materia sting and off-site fabrication of building components, as prescribed in the statement of
special inspections note on the rov plans and, as required by the California Building Code.
Signatur · Date: 10" N/14-t l.ol <4
B. CONTRACTOR'S STATEMENT OF RESPONSIBILITY (07 CBC, Ch 17, Section 1706). This section must be completed by the
contractor I builder I owner-builder.
Contractor's Company Name: yuJl ~ t#YlWI¢-1/ N ~
Name: (Please print) at) IJ IJ?D ())I
(First) (M.L)
Mailing Address: 5.z ~b /1(1.?1~ f2ri'.
Email: t"-41?:)+ed-~MaR1@ J#ft:ftj · Cl!n1'1
State of California Contractor's License Number: ~ f o 2-2-~
Please check if you are Owner-Builder 0
5"1.1! If f) 111 ;HJ
(Last)
Phone0 'c;-5"' 2--~-"2.-2--2-2.-
Expiration Date: / / 3; /17
' I
• I acknowledge and, am aware, of special requirements contained in the statement of special inspections noted on
the approved plans;
• I acknowledge that control will be exercised to obtain conformance with the construction documents approved by the
building official;
• I will have in-place procedures for exercising control within our (the contractor's) organization, for the method and
frequency of reporting and the distribution of the reports; and
• I certify that I will have a qualified person within our (the contractor's) organization to exercise such control.
• I will provide a final report I letter in compliance with CBC Section 1704.1.2 prior to requesting final
inspection.
Signature: ~~/{~ Date: _s--f--/-'---!/---F-/_1 ~--~ (1
B-45 Page 1 of 1 Rev. 08/11
DAVID THOMAS ENGINEERING, APC
35~5 Del Mar Heigh1s Road, Suite 331
San Diego, Ca&fomia 92130
(858) 336 . 9902
david@dllnpl.com
RECORD COPY
JoeHARRIS RESIDENCE 16105
SHEETNO. I 2 ____ .!..__ __ OF---==----
CALCULATEDBY DT DATE 6-21-16
CHECKED BY;;-:;:;---==-...,.,----
SCALE N.T.S. (REVISED DETAIL 1/SD-5)
RECEIVED
JUL 0 6 20:3
_____ _.., '
;:;;:;.._ .
-~ -'._ . ~ .
( '
Porter Structural Inspections & Consulting
1536 Downs Street
Oceanside, CA 92054
Phone (760) 889-9762
Fox (760) 754-2729
E-mail : piersurfl @aol.com
.... for Wee!< Ending Job No.
REGIS'nRED INSPECTOR'S DAILY REPORT I I
TYPE OF 0 Reinforced Concrete 0 Structural Steel Assembly OQuality Control
INSPECTION 0 Post Tensioned Concrete CJ fire Proofing OOther
REQUIRED []Reinforced Mosonry 0 Epoxy Anchors
JobAddress B-.30 ~~ ~~ ... ~ City c ·E
Job Name '~ .r,.,~ "'-g~ Permit No. I PIOnFile
Type of structure -Aidlitect
Material Description jtype, grade, source) b\ ~"f\~o l Y P Engineer
...... ' Contractor CD. v.Jr'-c-\.....~
lnspec:tor(s) Name Ht...'-, \ ~12..-l·l"'rv-Sub Contractor \)
TYPE OF SAMPLE SlUMP QUANTITY IN SET ADOmONAL REMARKS ON SAMPLES
Inspection Summary -locations of work inspected, test samples taken, work rejected, job problems, progress, remarks, etc. Includes
information about amounts of material placed or work performed, number, type & ident, number of test samples
-·-taken: struct, connections (weld mode H.T. bobs torqued) checked, etc.
_\_·elC_Ctl. rmP~ C"P -""'l_-y-,·a 0 • V\ <;.r"Jedteh -U.:,. ~v. Cl. .AA. c.. L.t.t...a-
'~ s~ \ \o.. -\--, .~_r... A<.' ..nn lll"ll J.~ '.:r: r\ "'•'1<er¥Prl ~ ~11e.J ht\ l ~ < rux. '""'\ ~ Urtu.. t..\' \. . ;).. 0 r\r• ~t t .:'A h1»\e~ ( ~.., "'"~ ~~
ft\t!•.s-. -'
~"--"~ tt)C./c::> b.rcA.C. henl n.-...r-l
--tn -1 V\ s-\-all~+~ i\ ..... •
CERTIFICATION OF COMPliANCE
I HEREBY CERTIFY THAT I HAVE OBSERVED TO THE BEST Of MY KNOWlEDGE
All OF THE ABOVE REPORTED WORK UNlESS OTHERWISE NOTED. I HAVE
FOUND THIS WORK TO COMPLY WITH THE APPROVED PlANS,
SPECIACATIONS, AND APPLICABLE SECTIONS OF THE GOVERNING
BUilDING lAWS.
c~~
ctRTNO.
~\-.... ~-() 1 C>rl.oA (\II' t'~-
f
TIME IN TIMEOUT REG. HOURS Q.T.HOURS CYliNDERS
4
AI inspediofts based..,o lllillilnuMol ~haoorlond-~haoorl-8 ._......,_in odclilion. 2-~-lo<job ................
Appooedby
l'nljoc:tSoop.* ...........
TESTING SERVICES
&
INSPECTION, INC.
••A Quality Assurance Finn"
3030 Main Street
San Diego, CA 92113
tsi-sandiego.com
(619) 234-9904
fax (619) 234-4931
tsi92113@yahoo.com
REPORT OF COMPRESSION TESTS
Project Name: HARRIS RESIDENCE
Project Address: 1630 BASSWOOD A VENUE CARLSBAD ADDmval Nwnber: CBI60551
Architect: WRIGIIT DESIGN I EJWnccr:: DAVID TIIOI\IAS ENGINEERING Plan/File Nwnber: N/A
Contmctor: R\VS CONTRAcnNG
Contmctor Doing Reponed Work: RWS CONTRAcnNG
s IDta ample a
Report of: Grout Mortar ~onere~ Other:
Supplier: Placcmcnl Date: Time:
ROBERTSON•s 51'..4/16 9:30AM
Mix Descriplion: MixNwnber: Ticket No.: Load No.: . RSlGOP-11 1559714 -I
Design Slrellgth: Required Stn:ngth (fc): Air Content: Concn:te T~"'llp.:
lOOOPSI JOOO PSI -88F
Type Cement Admi:r."tun:: Tnne in Mixer: --65MINliTES
Unit Weight Slump: -4~ ..
location of Placement:
STEEL COLUMN FOOTINGS BT. GRID LINES A-D & 1~13
Special Test Instruction or Relnarts:
I AT7 DAVS.2AT28 DA\'S.I HOLD
ASTM Test (s) Performed
ta SAMPLING FRESHLY MIXED CONCRETE(C172, T141) a SLUMP(C143,Tl 19) li1l TEMPERATURE(C1064,T309) a MAKING & CURING CONCRETE IN FIELD (Cli,"PJ)
0 AIR CONTENT BY PRESSURE METHOOCC'JJ,TISll 0 AIR CONTENT BY VOLUMETRIC METIIODCCI13l 0 UNIT \VEIG}JT. YIELD.(Clli.Tilll
Samples Made by: Dale Received in Lob: Date Issued to Client:
MICHAEL VIDOVICH (SfRUCllJRAL INSPE.cnO:"'lS) 5126116 6122/16
Labo ratory D t a a
Age Lab Control Date Dimensions Average Test Area Max Load Compressive Type of
Field Nnmber Tested Inches Diameter inebes Square lnehes Pounds Strength PSI Fracturr
ldrndty (nearest 10 PSI)
7 193-16 5-31-16 4x8 4.00 12.56 44940 3580 A
28 193-16 6-21-16 4x8 4.00 12.56 57 ISO 4550 A
28 193-16 6-21-16 4x8 4.00 J:!.S6 59280 4720 A
H
TESTS PERFORMED UNDER THE RESPONSIBLE Lab Use
CfL4RGE OF RC£ #C26676 DENNIS ZIMMER.ltL-IN ~ Q D D r;r:
" ••• ,, •••
D DOES NOT CONFORM
I \ ••• ~CONFORMS LL...! '-'-'-
A B c D E D FOR INFORMATION ONLY Cone Cone& Cone Shear Columnar
ASTM Test(s) performed: OC617 liiC123I OC39 Split Shear
AASHTO Test(s) performed: OT'..3 1 DT22
Sketches ofTvoes ofFmctures per ASTM C39
Unspection Report
Project Name: Harris Residence Page; 1 ol 1 Rapon#:
Project Addreu: 1630 Basswood Ave1 Carlsbad Permit#: CB160551
Architect: Wright Design file#:
Enjneer: David Thomas Engineering DSA#:
Canuactor: RWS ContractlnQ Other:
INSPECTION MATEIUAL SAMPLING QTY MATEIUAL ~CRIPTION INSPECTION CHECKLIST
--Swucanl SalOl --H.S. Bolts --H.S.Bolu --PlansiSpecs
-Muanrr --Prisms --__ .x_ t;anc.PSI 3000 --Cle;mmcas
_lL Concreta fwlaruriGrau' --· -. Graul PSI __ Poskions
-~ X Co~ t;ylinden _4_ --MonarPSI --Slus
-Ep01C)' --FirapnJof ----Sulel _Laps
_Other: --Omar: ----Elec:UW'I"II --t;ansolcladon
--Other: ·--Odler: ----flrapraal --Torque Ft. Lbs:
--Othllr: --omar: ----Ol:her: --Other:
Other: -Odu!r: -Other: Other:
Arrived on site to provide continuous special inspection during the concrete placement at steel column footings
between grid Hnes A-D & 10-13. Verified reinforcing steel was secure and had adequate clearance. All loose material
was removed from bottom of footings. Approximately 10 cubic yards of Robertson's. mix design# RS300P41. were
pumped Into place. Required design strength Is 3000 psi. Fabricated 1 set of 4 test cylinders for compressive strength
testing. Concrete temperature was 88 degrees F with a 4.6" slump. Air temperature was 84 degrees F and partly cloudy.
CERTIACATION OF COMPUANCE: All reported work, unl• otherwfle noted, complies with apprcwed plans. speclflcatlons and applicable sections
of the bultdln& codes. This n=port covers me locations or the work Inspected and does not consdwce opinion or proJect conuol.
1 hereby certify that 1 have ab5erved to me best or my knowledge all of the above reported work unless otherwise noted. I have round this worlt to
comply with the approved plans. spedfltadons, and applfr:able sections or dte governing building laws. . " .
Inspector: Michael VIdovich Cere: 8292714/1262 , . . (.. 6/24/16
Data
. ln5p. Data: Day 1: Dayl: Dayl: :Day<\: DayS:
TlmaStan:
Tune Stop:
A~r~Br--------------------------------
NON-DESTRUCTIVE TE~TING FIELD REPORT
PROJECT NAME: f"1 "-£ r ~ '{ I_ 1 ~ 1 & # "r.l' .er~ #: ..: DATE: '·t.t-tC..
LOCATION: 1'(.5/ .S 1 111\'0 '{ol\ iPltt.rr .,.J'J~, \ M. ~ f' ) SHOP: ./ AELD:
METHOD: UT MT PT VT • \A T I EQUIPMEN'fMFGIMODEL: IQ F ,-:: '?'J)~@\OBE ANGLES: o"'· ;o-MHz: 2..-2-) I
TRANSDUCER SIZES: ,(, 2-~, C. 2.-x.l \ f MT DRY..:::::.._ MT WET -PARTICLE MFG: -COLOR: -
BASE MATERIAL: A ~Uu coDE/SECTION: Aul 5 .1:> 1 .4 ENGINEER:
REPRESENTING: .t:" I. 1 CONTRACTOR: R._ \.J 5 I ...o A+ra. c...h"'-4
LEVEL II TECHNIC~: J c..S 0 n \I".Oi\f-lofb""" LEVEL II CERTIACATION: .f=" ,,.-09 Z.911 -f,22~CJTYNDT: .J
FLOOR lOCIPC# DESCRIPTION .. ACC REJ REMARKS
V£ r t=..r ""' J \1 ,+-.1'6 <DAI {'_ IJlcf),-~, ....
DA .., . <fr_.oi'Vlnl;:: .. , n.o 1\4, +.,. ,.'":\l.'nfo\
lt-a~·q .J ,..,,\, l,...Q_<~ r-.... ~ I ~4 -~ N1. .
1-fl rvb€.~,] r·cJ tJaM Jl -r F"JAAl1 hnl\~ ,
1\lfl I -r.<. ..,dN'\ +D ('?-........ ~ /.ol t.JM 11-1 K
"') 11 .._ /I ( I I y
.:2 "'" "" -~ x
~
~
~
' "\.
'\.
"\.
"\.
"\.
" "\.
"\.
" '\.
" " '\. ." ' '\..
"\.
" 1\.
"\. 'I Note all repaired welds as "REPAIR-in remarks coiUJJVl above. ~
TOtAL NO. OF WELDS TESTED: l-j TOTAL NO. ACCEPTED: -=7 TOp!. NO. REJECTED: ~ ,
TOTAl NO. OF REJECTED WElDS REPAIRED AND ACCEPTED THIS DATE: '
COMMENTS:
REGU7 TIME HOURS: L..f A~ I ----~T TECHNICIAN SIGNATURE CUENT'S SIGNATURE
/ v
~48><;;wooD W
~ObD'l
f.\, (,; · Porter Structural Inspections & Consulting
1536 Downs Street
Oceanside, CA 92054
Phone (7 60) 889-97 62
Fax (760) 754-2729
E-mail : piersurf 1 @aol.com
.-for Week Ending Job No.
REGISTERED INSPECTOR'S DAILY REPORT I I
TYPE OF 0 Reinforced Concrete 0 Structural Steel Assembly 0 Quality Control
INSPECTION [] Post Tensioned Concrete 0 Fire Proofing OOther
REQUIRED lJ Reinforced Masonry 0 Epoxy Anchors
Job Address f i~ .3 Q t<'.c . <:: ~t '" 1r-.. ..1 City C .t_~
Job Nome \--b ,_,...,., :r ~0~ Permit No.~ l3 It J) <r'5" J 1 PlanFile
Type of structure Architect
Material Description (type, grade, source) E:.. \ """',I\ <:"n l. Y fl Engineer
....... r Contractor <!;,. VoJ'\r \.C' k-\-;
lnspector(s} Nome Hh..'"a \ ·\--6~ Sub Contractor \}
TYPE OF SAMPLE SLUMP QUANTITY IN SET ADDITIONAL REMARKS ON SAMPLES
Inspection Summary -locations of work inspected, test samples taken, work rejected, job problems, progress, remarks, etc. Includes
information about amounts of material placed or work performed, number, type & ident, number of test samples
taken: struct, connections (weld made H.T. bolts torqued} checked, etc.
\ ev-Ca. rme£'1 .<-~ .• .'aO 'Y\ ~ t')QC.:hbJr'\. ~/' ~\C. t:::::t..AA c..~" lr\
' ~ s-k \ \o.. ~' .~_loo.... a. ( ' -D n J l"' ' ;_-::;: '.r Y\ -<::'!'1<?f'~E"'.r~l ~ ~ v-. 'I ( e..cJ hi\' e_ ~
( J,l x It?" \ ~ ~tA t.i'' ;). o A;·~\ \~A ho\e.~ -(~.., "'''~ ~~ n. \b '$. -J
~~c t, \~/~ b.ru....{ ~enl ~l"'k
+o -,V\.sWla.+.~-·
CERTIFICATION OF COMPLIANCE
I HEREBY CERTIFY THAT I HAVE OBSERVED TO THE BEST OF MY KNOWLEDGE
AU OF THE ABOVE REPORTED WORK UNLESS OTHERWISE NOTED. I HAVE
FOUND THIS WORK TO COMPLY WITH THE APPROVED PLANS,
SPECIFICATIONS, AND APPLICABLE SECTIONS OF THE GOVERNING
BUILDING LAWS.
c~~ 7/~1. REGISTERED INSPECTOR T JE
CERTNO.
~\rvPA f?.lorLtA {)II','~--..
TIME IN TIMEOUT REG. HOURS Q.T.HOURS CYUNDERS
4
All impedions booed 01> o minim.,. ol A houB ond ower A houB -8 hour.,....,.., in ocldition.
2 hour show-up minimum lor job mncallations.
Appro..~ by Project~ --
ROOF RAFTER
PER PLAN
146 PER AR.c.H'L.
JOIST 6LK'6. VOl/ C.LIP
PER Sjll, SC.HED.
(INSTALL "ASS" o 24"
0 .C.. ELSEJI'iHERE)
EXPOSED FALSE RAFTERS
PER AR.c.H'L.
JOIST 6LK'6. VOl/ C.LIP PER S.JI'i.
sc.HED. (INSTALL "AS5" o 24"
0 .C.. EL5EJI'iHERE)
D6L. TOP PLATES
2x STUD Jl'iALL
PER PLAN
ROOF 5HEATHIN6
PER PLAN
"L TPS" C.LIPS @ 12" O.C..
RI61D INSULATION PER AR.c.H'L.
RAFTER TAIL PER ARC.H'L.
(9'-0" MIN. 6AC.K-SPAN)
(INSTALL VERTIC.AL TO ENSURE
NAILIN6 INTO 6LK'6. 4 2x PLATE)
SHEAR PANEL PER PLAN
(JI'iHERE OC.C.URS)
~
ICJ
... ; ~.:::. ........ !is l!lfl ~·,j .... ~~: ·a z li~~-
~ £ ~ m Pl ;zl i ~I ~ lfl
............ ~ <
lfl m Q
Q
~~ ~
)>
r
$
Q
I ~I
~iz :;::.P -,.. ~
~ ; I ffi I :r: ~ )>
AJ AJ
lfl
AJ m lfl
Q m z 0
Iii ,m
-·G"
()
Ul
~
())
()
\Y --....)>
~(/'
0 "' 0(~
CJ)8
\J
~
<._
DAVID THOMAS ENGINEERING, APC
35~5 Del Mar Heights Road, Suite 331
San Diego, Caifomia 92130
(858) 336 • 9902
david@dtenpd.com
EXPOSED RID6E
BEAM PER PLAN
RECORD COPY
JOB HARRIS RESIDENCE 16105
SHEETNO. 2 OF. _ ____!2~--
CALCULATEDBY DT DATE 6-21-16
CHECKED BY DATE----,---
SCALE N.T.S. (REVISED DETAIL S/SD-6)
RECEIVED
JUL 06 z;J;)
CITY OF CARLSBAD
BUILDING DIVISION
KIN6 POST PER PLAN
BEAM PER PLAN
SIMPSON "MSTC.bb"
/STRAP
CONNECTION DETAIL
DATE: May 6, 2016
JURISDICTION: Carlsbad
PLAN CHECK NO.: 16-0551
EsGil Corporation
In (l'artnersliip witli <]o11ernment for (8uiftfing Safety
SET: III
PROJECT ADDRESS: 630 Basswood Ave.
q APPLICANT
~IS.
1:1 PLAN REVIEWER
1:1 FILE
PROJECT NAME: Room Additions/ Attached Storage/Carport (Garage?)/Covered Entry
for Harris Residence
D The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
~ The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
D The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
D The applicant's copy of the check list has been sent to:
EMail
~ EsGil Corporation staff did not advise the applicant that the plan check has been completed.
D EsGil Corporation staff did advise the applicant that the plan check has been completed.
Person contacter-/\ ~ Telephone #:
Date contacted:~ ~t:::fc:J Email:
Mail Telephone Fax In Person
I:8J REMARKS: 1) Sheets A-4, A-9, A-11, E-1 and SD-2 were submitted to EsGII as slip-sheets.
Person responsible for plan preparation to add the mentioned sheets to set 2 of the plans held
at the city to make a complete matching set 3 to the plan set being approved by EsGil. 2)
Designer to complete the city's "Special Inspection Agreement" at the city prior to permit
issuance.
By: Rich Moreno for R.F. Enclosures:
EsGil Corporation
0 GA 0 EJ 0 MB 0 PC May 2, 2016
9320 Chesapeake Drive, Suite 208 + San Diego, California 92123 + (858) 560-1468 + Fax (858) 560-1576
DATE: Mar 17, 2016
JURISDICTION: Carlsbad
PLAN CHECK NO.: 16-0551
EsGil Corporation
In cpartnersliip witli (}oflemment for 0uiftfing Safety
SET: II
PROJECT ADDRESS: 1630 Basswood Ave.
QJ',PPLICANT
Af JURIS.
[J PLAN REVIEWER
[J FILE
PROJECT NAME: Room Additions/ Attached Storage/Carport (Garage?)/Covered Entry
for Harris Residence
D The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
~ The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
~ The applicant's copy of the check list has been sent to:
Sam Wright E Mail
D EsGil Corporation staff did not advise the applicant that the plan check has been completed.
~ EsGil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Sam Wright Telephone#: (760) 213-1460
_))ate c%.acted::> J I f:J (by:f'.U Email: wrighthaus@roadrunner.com
~ Mail "~phon~ Fax In Person
D REMARK¥:·(\'\.
By: Rich Moreno for R.F. Enclosures:
EsGil Corporation
D GA D EJ D MB D PC Mar 10, 2016
9320 Chesapeake Drive, Suite 208 + San Diego, California 92123 + (858) 560-1468 + Fax (858) 560-1576
Carlsbad 16-0551
Mar 17,2016
NOTE: The items listed below are from the previous correction list. These
remaining items have not been adequately addressed. The numbers of the items
are from the previous check list and may not necessarily be in sequence. The
notes in bold font are current.
1. Please make all corrections, as requested in the correction list. Submit THREE
sets of plans for residential projects). For expeditious processing, corrected sets
can be submitted in one of two ways:
1. Deliver all corrected sets of plans and calculations/reports directly to the City of
Carlsbad Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760)
602-2700. The City will route the plans to EsGil Corporation and the Carlsbad
Planning, Engineering and Fire Departments.
2. Bring one corrected set of plans and calculations/reports to EsGil Corporation,
9320 Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-1468.
Deliver all remaining sets of plans and calculations/reports directly to the City of
Carlsbad Building Department for routing to their Planning, Engineering and Fire
Departments.
NOTE: Plans that are submitted directly to EsGil Corporation only will not be
reviewed by the City Planning, Engineering and Fire Departments until review by
EsGil Corporation is complete.
2. An instantaneous water heater is shown on the plans. Please include a gas
pipe sizing design (isometric or pipe layout) for all gas loads. This cannot be
a deferred item. Option is to provide a appropriate size dedicated gas line from
the meter to the tankless water heater noting maximum developed length etc.
Please provide an isometric or pipe layout per table 1216.2(1) of the CPC to
verify if the existing gas line will suffice for this project.
22. Plans to reflect whether or not existing dwelling and/or addition is or will be fire
sprinklered. See carport has eaves are closer than 5 ft to property line.
a) Projections must comply with the following:
If structure is not fire sprinklered then projections (i.e. eaves/fascia)
must be 1 hour rated on the underside when between two and five
feet from property line. (No projections are allowed closer than 24"
to property line.) Example of one eave protection is stucco, wood
siding over 5/8X drywall, Hardie panels over Titen backer board or
5/8X type drywall, heavy timber i.e. 2x T&G decking over minimum
4 x 6 roof rafters, 3x fascia. Please detail and reference method
choosing to applicable locations on the plans.
Even though the old code allowed for 3-ft. projections not to be 1-hr rated,
the 2012 IBC and subsequent 2013 CRC code require a 1-hr rating eave
projections lesser that 5ft from the property line.
a. The structural plans show that the roof of the carport shall be sloped per
architectural plans, but the architectural plans do not show a slope, please
add to the architectural sheets at least matching the minimum recommended
ICC-ESR slope.
Carlsbad 16-0551
Mar 17, 2016
• CITY of CARLSBAD REQUIREMENTS
32. When special inspection is required, the designer shall complete the city's
"Special Inspection Agreement". Special inspection is required for this
project, as noted on plan sheet S-1. Please fill the special inspection
attached at the end of the correction list or provide a note similar to plan
16-0459.
• Note on this list (or a copy) where each correction item has been addressed,
i.e., plan sheet, note or detail number, calculation page, etc.
• Please indicate here if any changes have been made to the plans that are not a
result of corrections from this list. If there are other changes, please briefly describe
them and where they are located in the plans.
• Have changes been made to the plans not resulting from this correction list?
Please indicate:
Yes ( ) No ( )
• The jurisdiction has contracted with Esgil Corporation located at 9320 Chesapeake
Drive, Suite 208, San Diego, California 92123; telephone number of 858/560-1468,
to perform the plan review for your project. If you have any questions regarding
these plan review items, please contact Rich Moreno for R.F. at Esgil Corporation.
Thank you.
.. Carlsbad 16-0551
Mar 17,2016
/:£r~ ·..;:t,~ ·~ CITY OF
CARLSBAD
SPECIAL INSPECTION
AGREEMENT
B-45
Development Services
Building Division
1635 Faraday Avenue
760-602-2719
www .carlsbadca .gov
In accordance with Chapter 17 of the California Building Code the following must be completed when work being performed
requires special inspection, structural observation and construction material testing.
lroject/Permit: _________ _ Project Address: ________________ _
A. THIS SECTION MUST BE COMPLETED BY THE PROPERTY OWNER/AUTHORIZED AGENT. Please check if you are Owner-Builder
CJ. (If you checked as owner-builder you must also complete Section B of this agreement.)
Name: (Please print,__ ___ -::::-,-----------,--,------------,----,----------
IF"st) (M I) (Last)
Mailing Addres.,_,_ ________________________________ _
Email_·------------------------Phone: __________ _
I am DProperty Owner DProperty Owner's Agent of Record DArchitect of Record DEngineer of Record
state of California Registration NumbeL.· _____________ Expiration Date: _______ _
AGREEMENT: I, the undersigned, declare under penalty of perjury under the laws of the state of California, that I have read,
understand, acknowledge and promise to comply with the City of Carlsbad requirements for special inspections, structural
observations, construction materials testing and off-site fabrication of building components, as prescribed in the statement of
special inspections noted on the approved plans and, as required by the California Building Code.
Signatur"'------------------------Date: ___________ _
B. CONTRACTOR'S STATEMENT OF RESPONSIBILITY (07 CBC, Ch 17, Section 1706). This section must be completed by the
contractor I builder I owner-builder.
Contractor's Company Name: ------------------· Please check if you are Owner-Builder 0
Name: (Please print)------=------------,-,.,--------------------
{Fmon IMl) (last)
Mailing Address: _________________________________ _
Email: _________________________ Phone: ___________ _
state of California Contractor's License Number: __________ Expiration Date: _______ _
• I acknowledge and, am aware, of special requirements contained in the statement of special inspections noted on
the approved plans;
• I acknowledge that control will be exercised to obtain conformance with the construction documents approved by the
building official;
• I will have in-place procedures for exercising control within our (the contractor's) organization, for the method and
frequency of reporting and the distribution of the reports; and
• I certify that I will have a qualified person within our (the contractor's) organization to exercise such control.
• I will provide a final report I letter in compliance with CBC Section 1704.1.2 prior to requesting final
inspection.
Signature~: ______________________ Date: __________ _
B-45 Page 1 of 1 Rev. 08/11
EsGil Corporation
In (['artnersliip witli government for (]Jui{tlino Safety
DATE: 02/23/16
JURISDICTION: Carlsbad
PLAN CHECK NO.: 16-0551
PROJECT ADDRESS: 630 Basswood Ave.
SET: I
PROJECT NAME: Room Additions/ Attached Storage/Carport (Garage?)/Covered Entry
for Harris Residence
D The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
C8J The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
C8J The applicant's copy of the check list has been sent to:
Sam Wright E Mail
D EsGil Corporation staff did not advise the applicant that the plan check has been completed.
~ EsGil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Sam Wrigt{) Telephone#: (760) 213-1460
Date contacted: [,." 13 (by:~ ) Email: wrighthaus@roadrunner.com
Q,Mail 'I-Telephone \1M Fax In Person
D REMARKS:
By: Ray Fuller Enclosures:
EsGil Corporation
D GA D EJ D MB D PC 02/16/16
9320 Chesapeake Drive, Suite 208 + San Diego, California 92123 + (858) 560-1468 + Fax (858) 560-1576
Carlsbad 16-0551
02/23/16
PLAN REVIEW CORRECTION LIST
SINGLE FAMILY DWELLINGS AND DUPLEXES
PLAN CHECK NO.: 16-0551 JURISDICTION: Carlsbad
PROJECT ADDRESS: 630 Basswood Ave.
FLOOR AREA:
Additions 390
Storage 198
Carport (Garage ) 242
Covered Entry 72
REMARKS:
DATE PLANS RECEIVED BY
JURISDICTION: 02/11/16
DATE INITIAL PLAN REVIEW
COMPLETED: 02/23/16
FOREWORD (PLEASE READ):
STORIES: 1
HEIGHT: 10ft per CRC
DATE PLANS RECEIVED BY
ESGIL CORPORATION: 02/16/16
PLAN REVIEWER: Ray Fuller
This plan review is limited to the technical requirements contained in the California version of
the International Residential Code, International Building Code, Uniform Plumbing Code,
Uniform Mechanical Code, National Electrical Code and state laws regulating energy
conservation, noise attenuation and access for the disabled. This plan review is based on
regulations enforced by the Building Department. You may have other corrections based on
laws and ordinance by the Planning Department, Engineering Department, Fire Department or
other departments. Clearance from those departments may be required prior to the issuance of
a building permit.
Present California law mandates that construction comply with the 2013 edition of the California
Code of Regulations (Title 24), which adopts the following model codes: 2012 IRC, 2012 IBC,
2012 UPC, 2012 UMC and 2011 NEC.
The above regulations apply, regardless of the code editions adopted by ordinance.
The following items listed need clarification, modification or change. All items must be satisfied
before the plans will be in conformance with the cited codes and regulations. Per Sec. 105.4 of
the 2012 International Building Code, the approval of the plans does not permit the violation of
any state, county or city law.
To speed up the recheck process, please note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet number, specification section, etc.
Be sure to enclose the marked up list when you submit the revised plans.
Carlsbad 16-0551
02/23/16
1. Please make all corrections, as requested in the correction list. Submit THREE
sets of plans for residential projects). For expeditious processing, corrected sets
can be submitted in one of two ways:
1. Deliver all corrected sets of plans and calculations/reports directly to the City of
Carlsbad Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760)
602-2700. The City will route the plans to EsGil Corporation and the Carlsbad
Planning, Engineering and Fire Departments.
2. Bring one corrected set of plans and calculations/reports to EsGil Corporation,
9320 Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-1468.
Deliver all remaining sets of plans and calculations/reports directly to the City of
Carlsbad Building Department for routing to their Planning, Engineering and Fire
Departments.
NOTE: Plans that are submitted directly to EsGil Corporation only will not be
reviewed by the City Planning, Engineering and Fire Departments until review by
EsGil Corporation is complete.
2. Verify final sets of architectural sheets will again be signed by designer and that
the structural sheets and any new calculations will be stamped and signed by
engineer. S2 and S3 sheets were not stamped or signed.
3. Specify on the Title Sheet of the plans the gross floor area of each element of
this project, including what appears to be a 72 sq ft covered porch. In addition
the storage is a garage as has a garage door. Scope of work on cover sheet to
include adding tankless water heater and heat pump.
4. Provide a statement on the Title Sheet of the plans stating that this project shall
comply with the 2011 NEC (noting 2010 NEC on cover sheet?).
5. The existing floor plan seems to reflect tankless as existing and energy
calculations are stating new and taking a 27.6 % credit for it.
6. An instantaneous water heater is shown on the plans. Please include a gas
pipe sizing design (isometric or pipe layout) for all gas loads. This cannot be
a deferred item. Option is to provide a appropriate size dedicated gas line from
the meter to the tankless water heater noting maximum developed length etc.
7. Provide the following design requirements for all new gas water heaters
installed to serve individual dwelling units:
a) Provide on the plans a complete gas pipe design. The gas load for the water
heater shall be a minimum of 200,000 BTU/hr
b) A condensate drain installed no higher than 2" above the base of the heater
that also allows for gravity drainage.
c) D The "B" vent installed in a straight position (no bends) from the room
containing the water heater to the roof termination (for future possible
sleeving for high efficiency heater venting.)
d) A 120 volt receptacle accessible to the heater installed within 3 feet.
e) Pressure relief must extend to the exterior.
Carlsbad 16-0551
02/23/16
f) Verify adequate combustion air is provided (unless mounted outdoors or
noted on plans to be direct vented.
8. Owner/designer to sign the CF1-R forms.
9. City of Carlsbad limits you to 1000 psf for soil bearing design (unless a soil
report is provided) and structural calculations and S-1 have used 1500?
10. Please clearly indicate on the cover sheet of the plans whether the existing
residence has a fire sprinkler system installed or not and or if proposing to be fire
sprinklered. If existing structure is fire sprinklered then provide a note stating
that any additions/alterations will also be provided with an automatic residential
fire sprinkler system. Section R313.2.
11. Please clearly indicate on the cover sheet of the plans whether the existing
house was built before or after 1994. For additions or improvements to a
residence built before 1994 please add the following note on the cover sheet of
the plans " All existing "noncompliant" fixtures (toilets that use more than 1.6
gallons of water per flush, urinals that use more than one gallon of water per
flush, showerheads that have a flow capacity of more than 2.5 gallons of water
per minute, and interior faucets that emit more than 2.2 gallons of water per
minute) shall be replaced. Certification of compliance shall be given to the
building inspector prior to final permit approval. California SB407".
12. Plans to reflect location of heat pump (taking 57.8% credit for it).
13. Is existing electrical panel location unaffected by proposed addition(s) and is it
adequate for the additional sq footage proposing?
14. No electrical plan provided. Show on the plans how the receptacle outlet
locations will comply with NEC Art. 210-52(a). Must show outlets within 6ft of
any opening and not to exceed 12 apart. Any isolated wall 2 ft or wider to have
outlets.
15. Include on the plans the following specifications for electrical devices installed
in dwellings:
Tamper resistant receptacles for all locations described in 210.52 (i.e., all
receptacles in a dwelling).
16. A porch that is greater in area than 20 square feet and is accessible from the
interior of the dwelling will require a minimum of one receptacle outlet. CEC
21 0.52(E). This receptacle must be WP and GFCI protected. See new entry.
17. Show the locations of one wall switch-controlled lighting outlet to be installed in
every habitable room attached garages, and at the exterior side of outdoor
entrances or exits. NEC Art. 21 O(a). See new exterior doors, laundry, family
room and garage for example.
Carlsbad 16-0551
02/23/16
18. Specify on the plans that any existing smoke alarms that are more than 10 years
old will be replaced. Section R314.3.2
19. Show that smoke alarms will be provided in all existing bedrooms and hallways
leading to bedrooms. Section R314.3.1
20. Show that carbon monoxide alarms will be provided outside each separate
sleeping area in the immediate vicinity of all bedrooms and on each story.
Section R315.2
21. Residential energy lighting requirements: ES 150.0(k)
• Show on electrical plan that the Lighting installed in garages. laundry
rooms. and utility rooms shall be high efficacy and be controlled by vacancy
sensors.
• High efficacy fixtures are required for all other rooms (not described above) or
low efficacy fixtures are allowed if controlled by a dimmer or a vacancy
sensor.
• _Show on electrical plan that outdoor lighting fixtures that are attached to a
building are required to be high efficacy or be controlled by a combination
photo-control/ motion sensor.
22. Plans to reflect whether or not existing dwelling and/or addition is or will be fire
sprinklered. See carport has eaves are closer than 5 ft to property line.
a) Projections must comply with the following:
If structure is not fire sprinklered then projections (i.e. eaves/fascia)
must be 1 hour rated on the underside when between two and five
feet from property line. (No projections are allowed closer than 24"
to property line.) Example of one eave protection is stucco, wood
siding over 5/8X drywall, Hardie panels over Titen backer board or
5/8X type drywall, heavy timber i.e. 2x T&G decking over minimum
4 x 6 roof rafters, 3x fascia. Please detail and reference method
choosing to applicable locations on the plans.
23. Could not determine what is being proposed at front of carport? It appears to be
some type of gate/solid or open wall/fence as shown on A4. Please clarify what
this, type of construction/material, height (greater than 6 ft required permit) etc,
24. Not sure how keynote 55 applies as referenced to inside of garage (storage ) on
A4?
25. Plans to reflect garage floor to sloping towards main vehicle entry doorways or
towards a approved drainage system. R309.1
26. Detail the dryer exhaust duct design from the dryer to the exterior with
termination to be a minimum of 3 ft from any opening and 5 ft from the AC
Carlsbad 16-0551
02/23/16
condensers per ES150.0.h 3 (a). The maximum length is 14 feet with a
maximum of two 90-degree . CMC Section 504.3.
27. Could not determine how window F meets egress as the bottom portion is noted
to be 48" x 26" SH? Even if awning does not appear would provide the 24" clear
vertical opening? Please clarify how this meets egress.
28. No door information provided for door 5 on A 1 0?
29. Could not determine why keynote 11 on GN1 states 1.6 instead of 1.2 for water
closets?
30. Do not see how P2 applies to carport footings as shown on S3 as this notes 30"
sq by 18" deep with 3 #4's? Please clarify
• CITY of CARLSBAD REQUIREMENTS
31. All new residential buildings, including additions, require a soils report. An update
letter is required if the report is more than 3 years old. If a room addition is less
than ~QO sq. ft. in area and only one story, then a soils report is not required. The
maximum allowable soil bearing value used in any design must be 1 000 psf
for this exception.
32. When special inspection is required, the designer shall complete the city's "Special
Inspection Agreement".
• Note on this list (or a copy) where each correction item has been addressed,
i.e., plan sheet, note or detail number, calculation page, etc.
• Please indicate here if any changes have been made to the plans that are not a
result of corrections from this list. If there are other changes, please briefly describe
them and where they are located in the plans.
• Have changes been made to the plans not resulting from this correction list?
Please indicate:
Yes ( ) No ( )
• The jurisdiction has contracted with Esgil Corporation located at 9320 Chesapeake
Drive, Suite 208, San Diego, California 92123; telephone number of 858/560-1468,
to perform the plan review for your project. If you have any questions regarding
these plan review items, please contact Ray Fuller at Esgil Corporation. Thank you.
Carlsbad 16-0551
02/23/16
[DO NOT PAY-THIS IS NOT AN INVOICE]
VALUATION AND PLAN CHECK FEE
JURISDICTION: Carlsbad PLAN CHECK NO.: 16-0551
PREPARED BY: Ray Fuller DATE: 02/23/16
BUILDING ADDRESS: 630 Basswood Ave.
BUILDING OCCUPANCY: R3 U TYPE OF CONSTRUCTION VB
BUILDING AREA Valuation
PORTION ( Sq. Ft.) Multiplier
Additions 390 166.81
Carport 242 25.78
Storage/Garage 198 36.40
Covered Entry 72 16.68
Air Conditioning 390 5.31
Fire Sprinklers
TOTAL VALUE
Jurisdiction Code cb By Ordinance
Bldg. Permit Fee by Ordinance
Plan Check Fee by Ordinance ... j
Type of Review: 0 Complete Review
0 Repetitive Fee
3Repeats
D Other
D Hourly
EsGil Fee
Reg. VALUE
Mod.
.
D Structural Only
1-------11 Hr. @ •
($)
65,056
6,239
7,207
1,201
2,071
81,774
$542.861
$352.861
$304.001
c~~~~~,~t~.:, ···.··· ..•... tr:li·a·acntlonlo'the above fee, an additi(matf~e ()f;,$~3·•Js due (.5 houf@
$8olnr:)'l9r·the·~~~G~~!n?teview.
Sheet 1 of 1
macvalue.doc +
Ccityof
Carlsbad
PLAN CHECK
REVIEW
TRANSMITTAL
DATE: 02/19/2016 PROJECT NAME: HARRIS FAMILY ADDITION
Community & Economic
Development Department
1635 Faraday Avenue
Carlsbad CA 92008
www.carlsbadca.gov
PLAN CHECK NO: 1 SET#: 1 ADDRESS: 1630 BASSWOOD AVE
PROJECT ID:CB160551
APN: 2050602800
VALUATION: $75,199 SCOPE OF WORK: 390 SF ADDITION 1ST FlR 198 SF STORAGE ROOM
ATTACHED 242 SF CARPORT
D
This plan check review is complete and has been APPROVED by:
LAND DEVELOPMENT ENGINEERING DIVISION
Final Inspection by Construction Management & Inspection Division is required: Yes No X
This plan check review is NOT COMPLETE. Items missing or incorrect are listed on
the attached checklist. Please resubmit amended plans as required.
Plan Check Comments have been sent to: WRIGHTHAUSE@ROADRUNNER.COM
To determine status by one of the divisions listed below, please contact 760-602-2719.
760-602-4624
Chris.Sexton@carlsbadca.gov Gregory.Ryan@carlsbadca.gov
Gina Ruiz
760-602-4675
Gina.Ruiz@carlsbadca.gov
Remarks:
Linda Ontiveros
760-602-2773
VaiRay Nelson
760-602-27 41
VaiRay.Marshall@carlsbadca.gov
Cindy Wong
760-602-4662
Cynthia. Wong@ca rlsbadca.gov
Dominic Fieri
760-602-4664
Dominic.Fieri@carlsbadca.gov
HARRIS FAMILY ADDITION PLAN CHECK NO# 1
Please Read
Instructions:
Outstanding issues are marked with X Items that conform to permit
requirements are marked with ..f or have intenUonally been left blank.
1. SITE PLAN
Provide a fully dimensioned site plan drawn to scale. Show:
North arrow
Existing & proposed structures
Existing street improvements
Property lines (show all dimensions)
Easements
' :ZJ Right-of-way width & adjacent streets
Show on site plan:
DriV13Way widths
Existing or proposed sewer lateral
Existing or proposed water service
Submit on signed approved plans:
DWG No.
Drainage patterns and proposed site elevations. Show all high points.
Building pad surface drainage must maintain a minimum slope of one percent towards an adjoining
street or an approved drainage course.
r~7]ADD THE FOLLOWING NOTE: "Finish grade will provide a minimum positive drainage of 2% to swale
5' away from building".
Existing & proposed slopes and topography
Size, location, alignment of existing or proposed sewer and water service(s) that serves the project.
Each unit requires a separate service; however, second dwelling units and apartment complexes are an
exception.
Sewer and water laterals should not be located within proposed driveways, per standards.
Include on title sheet:
Assessor's parcel number
Legal description/lot number
For commercial/industrial buildings and tenant improvement projects, include: total building
square footage with the square footage for each different use, existing sewer permits
showing square footage of different uses (manufacturing, wa~rehouse, office, etc.) previously
approved.
Show all existing use of SF and new proposed use of SF.
Example:
Tenant improvement for 3500 SF of warehouse to 3500 SF= of office.
LoUMap No.: 01661 TCT 123
Subdivision/Tract: CARLSBAD LANDS
Reference No(s):
E-36 Page 2 of 6 REV 6/01112
HARRIS FAMILY ADDITION PLAN CHECK NO# 1
N/A
CURRENT
ROW IS GO'
BASSWOOD
AND GO'
JAMES
IMPROVEMEN
TS EXISTING
E-36
2. DISCRETIONARY APPROVAL COMPLIANCE
Project does not comply with the following engineering conditions of approval for project no.:
3. DEDICATION REQUIREMENTS
Dedication for all street rights-of-way adjacent to the building site and any storm drain or
utility easements on the building site is required for all new buildings and for remodels with a
value at or exceeding $ 24 000 00 , pursuant to Carlsbad Municipal Code Section 18.40.030.
Dedication required as follows:
4. IMPROVEMENT REQUIREMENTS
All needed public improvements upon and adjacent to the building site must be constructed
at time of building construction whenever the value of the construction exceeds
$120.000.00, pursuant to Carlsbad Municipal Code Section 18.40.040.
Public improvements required as follows:
Construction of the public improvements must be deferred pursuant to Carlsbad
Municipal Code Section 18.40. Please submit a recent property title report or current grant
deed on the property and processing fee, so we may prepare the necessary Neighborhood
Improvement Agreement. This agreement must be signed, notarized and
approved by the city prior to issuance of a building permit.
Future public improvements required as follows:
Page 3 of 6 REV6/01/12
HARRIS FAMILY ADDITION PLAN CHECK NO# 1
N/A
E-36
5. GRADING PERMIT REQUIREMENTS
The conditions that require a grading permit are found in Section 15.16 of the Municipal
Code.
CJinadequate information available on site plan to make a determination on grading
requirements. Include accurate grading quantities in cubic yards (cut, fill, import, export and
remedial). This information must be included on the plans. If no grading is proposed
write: "NO GRADING"
Grading Permit required. NOTE: The grading permit must be issued and rough grading
approval obtained prior to issuance of a building permit.
Graded Pad Certification required. (Note: Pad certification may be required even if a grading
permit is not required.) All required documentation must be provided to your Engineering
Construction Inspector The inspector will then
provide the engineering counter with a release for the building permit.
[{J No grading permit required.
Minor Grading Permit required. See additional comments for project-specific requirements.
6. MISCELLANEOUS PERMITS
0 RIGHT -OF-WAY PERMIT is required to do work in city right-of-way and/or private work
adjacent to the public right-of-way. Types of work include, but are not limited to: street
improvements, tree trimming, driveway construction, tying into public storm drain, sewer and
water utilities.
Right-of-way permit required for:
Page 4 of 6 REV 6/01/12
HARRIS FAMILY ADDITION PLAN CHECK NO # 1
E-36
7. STORM WATER
Construction Compliance
Project Threat Assessment Form complete.
Enclosed Project Threat Assessment Form incomplete.
Requires Tier 1 Storm Water Pollution Prevention Plan (E-29). Please complete attached form
and return (SW16-56 )
Requires Tier 2 Storm Water Pollution Prevention Plan. Requires submittal of Tier 2
SWPPP, payment of processing fee and review by city.
Post-Development (SUSMP) Compliance
Lf J Storm Water Standards Questionnaire.
Project is subject to Standard Storm Water Requirements. See city Standard Urban
Storm Water Management Plan (SUSMP) for reference.
Indicate areas of impervious surfaces (patios, walkway, etc. ) and pervious areas (landscaping).
Project needs to incorporate low impact development strategies throughout in one or
more of the following ways:
Rainwater harvesting (rain barrels or cistern)
Vegetated Roof
Bio-retentions cell/rain garden
Pervious pavement/pavers
Flow-th'rough planter/vegetated or rock drip line
Vegetated swales or rock infiltration swales
Downspouts disconnect and discharge over landscape
Other:
Page 5 of6 REV 6/01/12
*** Fee Calculation Worksheet ***
ENGINEERING DIVISION
Prepared by: Date: GEO DATA: LFMZ: I B&T:
Address: Bldg. Permit#:
Fees Update by: Date: Fees Update by: Date:
EDU CALCULATIONS: List types and square footages for all uses.
Types of Use: Sq.Ft./Units
Types of Use:
Types of Use:
Sq.Ft./Units
Sq. Ft./Units
Types of Use: Sq.Ft./Units
ADT CALCULATIONS: List types and square footages for all uses.
Types of Use: Sq.Ft./Units
Types of Use:
Types of Use:
Types of Use:
FEES REQUIRED:
Sq. Ft./Units
Sq.Ft./Units
Sq.Ft./Units
EDU's:
EDU's:
EDU's:
EDU's:
ADT's:
ADT's:
ADT's:
ADT's:
Within CFD:OYES (no bridge & thoroughfare fee in District #1, reduces Traffic Impact Fee) NO
1. PARK-IN-LIEU FEE: []NW QUADRANT NE QUADRANT 0SE QUADRANT OW QUADRANT
ADT'S/UNITS: I X FEE/ADT: I =$
2.TRAFFIC IMPACT FEE:
ADT'S/UNITS: I X FEE/ADT: I =s
3. BRIDGE & THOROUGHFARE FEE: DIST. #1 DIST.#2 DIST.#3
(USE SANDAG)ADT'S/UNITS I X FEE/ADT: I =s
4. FACILITIES MANAGEMENT FEE ZONE:
ADT'S/UNITS: IX FEE/SQ. FT./UNIT: I =s
5. SEWER FEE
EDU's IX FEE/EDU: I =s
BENEFIT AREA:
EDU's IX FEE/EDU: I =s
6. DRAINAGE FEES: PLDA: L]HIGH MEDIUM []LOW
ACRES: IX FEE/AC: I =s
7. POTABLE WATER FEES:
UNITS CODE CONN. FEE METER FEE SDCWAFEE TOTAL
***This may not represent a comprehensive list of fees due for this project.
Please contact the Building division at (760) 602-2719 for a complete listing of fees***
~~ ~ CITY OF
CARLSBAD
STORM WATER COMPLIANCE FORM
TIER 1 CONSTRUCTION SWPPP
E-29
STORM WATER COMPLIANCE CERTIFICATE
./ My project is not in a categorY of permit types exempt from the Construction
SWPPP requirements
./ My project is not located inside or within 200 feet of an environmentally
sensitive area with a significant potential for contributing pollutants to nearby
receiving waters by way of storm water runoff or non-storm water
discharge(s).
./ My project does not require a grading plan pursuant to the Carlsbad
Grading Ordinance (Chapter 15.16 of the Carlsbad Municipal Code)
./ My project will not resuH in 2,500 square feet or more of soils disturbance
including any associated construction staging, stockpiling, pavement
removal, equipment storage, refueling and maintenance areas that meets
one or more of the additional following criteria:
• located within 200 feet of an environmentally sensitive area or the
Pacific Ocean: and/or,
• disturbed area is located on a slope with a grade at or exceeding 5
horizontal to 1 vertical; and/or
• disturbed area is located along or within 30 feet of a storm drain inlet. an
open drainage channel or watercourse; and/or
• construction will be initiated during the rainy season or will extend into
the rainy season (Oct. 1 through April 30).
I CERTIFY TO THE BEST OF MY KNOWLEDGE THAT ALL OF THE ABOVE
CHECKED STATEMENTS ARE TRUE AND CORRECT. I AM SUBMITTING
FOR CITY APPROVAL A TIER 1 CONSTRUCTION SWPPP PREPARED IN
ACCORDANCE WITH THE REQUIREMENTS OF CITY STANDARDS.
I UNDERSTAND AND ACKNOWLEDGE THAT I MUST: (1) IMPLEMENT BEST
MANAGEMENT PRACTICES (BMPS) DURING CONSTRUCTION ACTIVITIES
TO THE MAXIMUM EXTENT PRACTICABLE TO MINIMIZE THE
MOBILIZATION OF POLLUTANTS SUCH AS SEDIMENT AND TO MINIMIZE
THE EXPOSURE OF STORM WATER TO CONSTRUCTION RELATED
POLLUTANTS; AND, (2) ADHERE TO, AND AT ALL TIMES, COMPLY WITH
THIS CITY APPROVED TIER 1 CONSTRUCTION SWPPP THROUGHOUT THE
DURATION OF THE CONSTRUCTION ACTIVITIES UNTIL THE
CONSTRUCTION WORK IS COMPLETE AND APPROVED BY THE CITY OF
CARLSBAD.
/(. ~. ~01 ~ ~ DATE OWNER(S
STORM WATER POLLUTION PREVENTION NOTES
1. ALL NECESSARY EQUIPMENT AND MATERIALS
SHALL BE AVAILABLE ON SITE TO FACILITATE
RAPID INSTALLATION OF EROSION AND
SEDIMENT CONTROL BMPS WHEN RAIN IS
EMINENT.
2. THE OWNER/CONTRACTOR SHALL RESTORE
ALL EROSION CONTROL DEVICES TO
WORKING ORDER TO THE SATISFACTION OF
THE CITY ENGINEER AFTER EACH RUN-OFF
PRODUCING RAINFALL.
3. THE OWNER/CONTRACTOR SHALL INSTALL
ADDITIONAL EROSION CONTROL MEASURES
AS MAY BE REQUIRED BY THE CITY
ENGINEERING OR BUILDING INSPECTOR DUE
TO UNCOMPLETED GRADING OPERATIONS OR
UNFORESEEN CIRCUMSTANCES WHICH MAY
ARISE.
4. ALL REMOVABLE PROTECTIVE DEVICES SHALL
BE IN PLACE AT THE END OF EACH WORKING
DAY WHEN THE FIVE (5) DAY RAIN
PROBABILITY FORECAST EXCEEDS FORTY
PERCENT (40%). SILT AND OTHER DEBRIS
SHALL BE REMOVED AFTER EACH RAINFALL.
5. ALL GRAVEL BAGS SHALL BE BURLAP TYPE
WITH 3/41NCH MINIMUM AGGREGATE.
6. ADEQUATE EROSION AND SEDIMENT
CONTROL AND PERIMETER PROTECTION BEST
MANAGEMENT PRACTICE MEASURES MUST BE
INSTALLED AND MAINTAINED.
SPECIAL NOTES
E-29 Page 1 of 3 .
Development Services
Land Development Engineering
1635 Faraday Avenue
760-602-2750
www .carlsbadca.gov
PROJECT INFORMATION
Site Address\. I.:::> ~0 e.~Po-~lo\..o.X)...,,<> ,_.
Assessor's Parcel Number: Z..e. S' ~ l?>CPC> • ~
Project ID: JfA2 } bOD,,S6
Construction Permit No.: C/J/ ~ pcSSJ
Estimated Construction Start Date \'-•\ ,.. ..... 'l S"
Project Duration 4 Months
Emergency Contact:
Name:-:::5>.,..._e-\ ~~~~""C""
24 hour Phone: 7'voo • 72..-0 '7~ 3(
Perceived Threat to Storm Water Quality
~ Medium
~
If medium box is checked, must attach a site plan
sheet showing proposed work area and location
of proposed structural BMPs
For City Use Only
Approved By: \0 1U l"'iM,f <JV c v w r-
Date: a ·J.'\. "( LQ ~
REV 4/30/10
2-CI ~ l,o:
..
Erosion Control Tracking Non-Storm Water Waste Management and Materials Sediment Control BMPs Control BMPs BMPs Management BMPs Pollution Control BMPs
c: c: c: c: c: 0 0 0 "'0 ~ Q) "'0 Q) c: n :g c: Cl E c: E "'0 ~ 0 c: Cl 111 c: 111 2 2 '6 a. Q) $ -cliJ E Q) ~ 'E '5 ~ 111
::::?: Cl (jj 'lii"' 'lii c: Cl "' $ Cl c:-a. Q) c: E 2: (9 'E r::r Q) 111 c: ~ Best Management Practice c: 111 ~ ·c. 'E c: "' c: w ,;?: c: 0 "' oil :2 "' ~ Ill OQ) 0 Q) Q) Q) 111 ~ m-Q)Cl 111 () ~ * 3'd (BMP) Oescription ~ "' .5:! ~~ c: E Cl Ill c: ()o... "' "'0 "'0 Q) "' ::::?: -~ "' ~ .5 'iij c: "'CCl c: c: Q) "' ~ ::;, Q) c: 111 111 "'0;., 0 c: ij 0 ::J > ::;, Q) E ~ ::::?: 0 0 0 Ill enE Cl .... 0 Q)!:!:! Q) 111 () 111 )J ~ ~-~ ~ 0 og> 0 c: Q) 111 0·-Q) 'iii -Q a:: E~ NUl ~3: Cl ·c. 'E ~ t $ "'0 Q) E .>< ~ -::;, ..0 :=Ul f :0 ·c: i .s::.c: Q) u. 0 (jj Q) ::;, "'0 :c~ ·-"'0 c: Q) .>< :2 111 o n 0 0 t::: ·-a. '6 Q) !!! ~0 c: ..Om ·:;; ~ m 0 N c: c Q) ~ 111!!! 0 Q) .s:::. ..0 111 .se 111Cl ~~ 111 a ~~ ~~ o n (9 Ci5 c;; u:: (9 -m Ci5.E ~c ::::?: ():::i wo en () en> en en c.. !l.. !l..
CASQA Designation ~ ...... "'? en ...... ...... (') .,. 10 <9 "';-"'? 0 ...... ~ ...... ;z "';-CX) ...... ~ '? .,. 10 <9 CX) c.) c.) ...... w w w ~ 0:. ch ch ~ ~ ~ () c.) w w w w a:: en ~ ~ ~ ~ w w w en en en en en en en 1-1-z z z z Construction Activity w en
,)< Grading/Soil Disturbance ><:::
)(" Trenching/Excavation >< Stockpiling
Drilling/Boring
~ Concrete/Asphalt Saw ~ cutting
Concrete flatwork t:X.
Paving
Conduit/Pipe Installation
X Stucco/Mortar Work ., Waste Disposal .;=.<;.
Staging/Lay Down Area
Equipment Maintenance
and Fueling
Hazardous Substance
Use/Storage
Dewatering
Site Access Across Dirt
Other (list):
Instructions: Begin by reviewing the list of construction activities and checking the box to the left of any activity that will occur during the proposed construction. Add any other activity descriptions in the
blank activity description boxes provided for that purpose and place a check in the box immediately to the left of the added activity description. For each activity descrribed, pick one or more best
management practices (BMPs) from the list located along the top of the form. Then place an X in the box at the place where the activity row intersects with the BMP column. Do this for each activity that was
checked off and for each of the selected BMPs selected from the list. For Example -If the project includes site access across dirt, then check the box to the left of "Site Access Across Dirt". Then review
the list for something that applies such as "Stabilized Construction Ingress/Egress" under Tracking Control. Follow along the "Site Access Across Dirt" row until you get to the "Stabilized Construction
Ingress/Egress" column and place an X in the box where the two meet. As another example say the project included a stockpile that you intend to cover with a plastic sheet. Since plastic sheeting is not on
the list of BMPs, then write in "Cover with Plastic" in the blank column under the heading Erosion Control BMPs. Then place an X in the box where the "Stockpiling" row intersects the new "Cover with
Plastic" column.
To learn more about what each BMP description means, you may wish to review the BMP Reference Handout prepared to assist applicants in the selection of appropriate Best Management Practice
measures. The reference also explains the California Stormwater Quality Association (CASQA) designation and how to apply the various selected BMPs to a project.
E-29 Page 2 of3 REV 4/30/10
«~ ~ CITY OF
CARLSBAD
STORM WATER
STANDARDS
QUESTIONNAIRE
E-34
Development Services
Land Development Engineering
1635 Faraday Avenue
760-602-2750
www.carlsbadca.gov
To address post-development pollutants that may be generated from development projects, the City requires that new development and
significant redevelopment priority projects incorporate Permanent Storm Water Best Management Practices (BMP's) into the project
design per the City's Standard Urban Stormwater Management Plan (SUSMP). To view the SUSMP, refer to the Engineering Standards
(Volume 4, Chapter 2) at www.carlsbadca.gov/standards.
Initially this questionnaire must be completed by the applicant in advance of submitting for a development application (subdivision,
discretionary permits and/or construction permits). The results of the questionnaire determine the level of storm water standards that
must be applied to a proposed development or redevelopment project. Depending on the outcome, your project will either be subject to
'Standard Stormwater Requirements' or be subject to additional criteria called 'Priority Development Project Requirements'. Many
aspects of project site design are dependent upon the storm water standards applied to a project.
Your responses to the questionnaire represent an initial assessment of the proposed project conditions and impacts. City staff has
responsibility for making the final assessment after submission of the development application. If staff determines that the questionnaire
was incorrectly filled out and is subject to more stringent storm water standards than initially assessed by you, this will result in the return
of the development application as incomplete. In this case, please make the changes to the questionnaire and resubmit to the City.
If you are unsure about the meaning of a question or need help in determining how to respond to one or more of the questions, please
seek assistance from Land Development Engineering staff.
A separate completed and signed questionnaire must be submitted for each new development application submission. Only one
completed and signed questionnaire is required when multiple development applications for the same project are submitted concurrently.
In addition to this questionnaire, you must also complete, sign and submit a Project Threat Assessment Form with construction permits
for the project.
Please start by completing Step 1 and follow the instructions. When completed, sign the form at the end and submit this with your
application to the city.
1. Is your project LIMITED TO constructing new or paved sidewalks, bicycle or trails that meet
the following criteria: (1) Designed and constructed to direct storm water runoff to adjacent vegetated areas, or
other non-erodible permeable areas; OR (2) designed and constructed to be hydraulically disconnected from
paved streets or roads; OR (3) designed and constructed with permeable pavements or surfaces in
USEPA Green Streets ·
YES NO
If you answered "yes" to one or more of the above questions, then your project is NOT a priority development project and therefore is
NOT subject to the storm water criteria required for priority development projects. Go to step 4, mark the last box stating "my
project does not meet PDP requirements" and complete applicant information.
answered "no" to both 2.
E-34 Page 1 of 3 Effective 6/27113
«~~ ~ CITY OF
CARLSBAD
STORM WATER
STANDARDS
QUESTIONNAIRE
E-34
Development Services
Land Development Engineering
1635 Faraday Avenue
760-602-2750
www.carlsbadca.gov
To determine if your project is a priority development project, please answer the following questions:
1. Is your project a new development that creates 10,000 square feet or more of impervious surfaces collectively
over the entire project site? This includes commercial, industrial, residential, mixed-use, and public
develo ment ro ·ects on ublic or rivate land.
2. Is your project creating or replacing 5,000 square feet or more of impervious surface collectively over the entire
project site on an existing site of 10,000 square feet or more of impervious surface? This includes commercial,
industrial, residential, mixed-use, and ublic develo ment ro ·ects on ublic or rivate land.
3. Is your project a new or redevelopment project that creates 5,000 square feet or more of impervious surface
collectively over the entire project site and supports a restaurant? A restaurant is a facility that sells prepared
foods and drinks for consumption, including stationary lunch counters and refreshment stands selling prepared
foods and drinks for immediate consum tion.
4. Is your project a new or redevelopment project that creates 5,000 square feet or more of impervious surface
collectively over the entire project site and supports a hillside development project? A hillside development
project includes development on any natural slope that is twenty-five percent or greater.
5. Is your project a new or redevelopment project that creates 5,000 square feet or more of impervious surface
collectively over the entire project site and supports a parking lot. A parking lot is a land area or facility for the
temporary arkin or storage of motor vehicles used ersonally for business or for commerce.
6. Is your project a new or redevelopment project that creates 5,000 square feet or more of impervious surface
collectively over the entire project site and supports a street, road, highway freeway or driveway? A street,
road, highway, freeway or driveway is any paved impervious surface used for the transportation of
automobiles, trucks, motorc cles, and other vehicles.
7. Is your project a new or redevelopment project that creates or replaces 2,500 square feet or more of
impervious surface collectively over the entire site, and discharges directly to an Environmentally Sensitive
Area (ESA)? "Discharging Directly to" includes flow that is conveyed overland a distance of 200 feet or less
from the project to the ESA, or conveyed in a pipe or open channel any distance as an isolated flow from the
ro ·ect to the ESA i.e. not commin les with flows from ad·acent lands .*
8. Is your project a new development that supports an automotive repair shop? An automotive repair shop is a
facility that is categorized in any one of the following Standard Industrial Classification (SIC) codes: 5013,
5014, 5541, 7532-7534, or 7536-7539.
9. Is your project a new development that supports a retail gasoline outlet (RGO)? This category includes RGO's
that meet the following criteria: (a) 5,000 square feet or more or (b) a project Average Daily Traffic (ADT) of
100 or more vehicles erda .
10.1s your project a new or redevelopment project that results in the disturbance of one or more acres of land and
are expected to generate pollutants post construction?
11.1s your project located within 200 feet of the Pacific Ocean and (1) creates 2,500 square feet or more of
impervious surface or (2) increases impervious surface on the property by more than 1 0%?
YES NO
I
I
J
I
If you answered "yes" to one or more of the above questions, you ARE a priority development project and are therefore subject to
implementing structural Best Management Practices (BMP's) in addition to implementing Standard Storm Water Requirements such
as source control and low impact development BMP's. A Storm Water Management Plan (SWMP) must be submitted with your
application(s) for development. Go to step 3 for redevelopment projects. For new projects, go to step 4 at the end of this
questionnaire, check the "my project meets PDP requirements" box and complete applicant information.
If you answered "no" to all of the above questions, you ARE NOT a priority development project and are therefore subject to
implementing only Standard Storm Water Requirements such as source control and low impact development BMP's required for all
developmenfprojects. A Storm Water Management Plan (SWMP) is not required with your application(s) for development. Go to step
4 at the end of this questionnaire, check the "my project does not meet PDP requirements" box and complete applicant
information.
E-34 Page 2 of 3 Effective 6/27/13
«~II!'> ~ CITY OF
CARLSBAD
STORM WATER
STANDARDS
QUESTIONNAIRE
E-34
Development Services
Land Development Engineering
1635 Faraday Avenue
760-602-2750
www.carlsbadca.gov
you answered "yes, structural MP's required for Devel ment Projects apply only to the creation or replacement of
impervious surface and not the entire development. Go to step 4, check the "my project meets PDP requirements" box and
complete applicant information.
If you answered "no," the structural BMP's required for Priority Development Projects apply to the entire development. Go to step 4,
check the meets PDP irements" box and com licant information.
D My project meets PRIORITY DEVELOPMENT PROJECT (PDP) requirements and must comply with additional stormwater
criteria per the SUSMP and I understand I must prepare a Storm Water Management Plan for submittal at time of application.
I understand flow control (hydromodification) requirements may apply to my project. Refer to SUSMP for details.
My project does not meet PDP requirements and must only comply with STANDARD STORMWATER REQUIREMENTS per
the SUSMP. As part of these requirements, I will incorporate low impact development strategies throughout my project.
Applicant Information and Signature Box
Address: \. ~ -~ 0 ~ ;~ ~ :::. '-0 ._;,..._,._? Accessor's Parcel Nuru.ber(s): 2-.o S"" -D ~',. D . """"""'""' ,---Applicant Title:
~~+-r-~
Date:
This Box for City Use Only
City Concurrence:
By:
Project ID:
NO
* Environmentally Sensitive Areas include but are not limited to all Clean Water Act Section 303(d) impaired water bodies; areas
designated as Areas of Special Biological Significance by the State Water Resources Control Board (Water Quality Control Plan for the
San Diego Basin (1994) and amendments); water bodies designated with the RARE beneficial use by the State Water Resources
Control Board (Water Quality Control Plan for the San Diego Basin (1994) and amendments); areas designated as preserves or their
quivalent under the Multi Species Conservation Program within the Cities and County of San Diego; and any other equivalent
environmentally sensitive areas which have been identified by the Copermittees.
E-34 Page 3 of 3 Effective 6/27113
•
«~~ ~ CITY OF
CARLSBAD
STORM WATER
COMPLIANCE
ASSESSMENT
B-24
Development Services
Building Division
1635 Faraday Avenue
760-602-2719
www .carlsbadca.gov
I am applying to the City of Carlsbad for the following type(s) of construction permit: f Building Permit 0 Right-of-Way Permit
D My project is categorically EXEMPT from Electrical Fire Additional the requirement to prepare a storm water Fire Alarm
pollution prevention plan (SWPPP) because it Fixed Systems
only requires issuance of one or more of the Mechanical
following permit types: Mobile Home
Patio/Deck
Photo Voltaic
Re-Roofing
Sign
Spa-Factory
Sprinkler
Plumbing Water Discharge
Project Storm Water Threat Assessment Criteria*
No Threat Assessment Criteria
0 My project qualifies as NO THREAT and is exempt from the requirement to prepare a storm water pollution prevention plan (SWPPP) because
it meets the 'no threar assessment criteria on the City's Project Threat Assessment Worksheet for Determination of Construction SWPPP Tier
Level. My project does not meet any of the High, Moderate or Low Threat criteria described below.
Tier 1 -Low Threat Assessment Criteria 'd My project does not meet any of the Significant or Moderate Threat criteria, is not an exempt permit type (See list above) and the project ~ meets one or more of the following criteria:
• Results in some soil disturbance; and/or
• Includes outdoor construction activities (such as saw cutting, equipment washing, material stockpiling, vehicle fueling, waste stockpiling).
Tierk Moderate Threat Assessment Criteria
My project does not meet any of the Significant Threat assessment Criteria described below and meets one or more of the following criteria:
• Project requires a grading plan pursuant to the Carlsbad Grading Ordinance (Chapter 15.16 of the Carlsbad Municipal Code); or,
• Project will result in 2,500 square feet or more of soils disturbance including any associated construction staging, stockpiling, pavement
removal, equipment storage, refueling and maintenance areas and project meets one or more of the additional following criteria:
• Located within 200 feet of an environmentally sensitive area or the Pacific Ocean, and/or
• Disturbed area is located on a slope with a grade at or exceeding 5 horizontal to 1 vertical, and/or
• Disturbed area is located along or within 30 feet of a storm drain inlet, an open drainage channel or watercourse, and/or
• Construction will be initiated during the rainy season or will extend into the rainy season {Qct. 1 through April30).
Tier 3 -Significant Threat Assessment Criteria
D My project includes clearing, grading or other disturbances to the ground resulting in soil disturbance totaling one or more acres including any
associated construction staging, equipment storage, stockpiling, pavement removal, refueling and maintenance areas: and/or
0 My project is part of a phased development plan that will cumulatively result in soil disturbance totaling one or more acres including any
associated construction staging, equipment storage, refueling and maintenance areas: or,
0 My project is located inside or within 200 feet of an environmentally sensitive area (see City ESA Proximity map) and has a significant
potential for contributing pollutants to nearby receiving waters by way of storm water runoff or non-storm water discharge(s).
I certify to the best of my knowledge that the above
checked statements are true and correct I understand
and acknowledge that even though this project does
not require preparation of a construction SWPP, I must
still adhere to, and at all times during construction ·
activities for the permit type(s) check above comply
with the storm water best management practices
pursuant to Title 15 of the Carlsbad Municipal Code
and to City Standards.
Project Address: Assessor Parcel No.
'The City Engineer may authorize minor variances from the Storm
Water Threat Assessment Criteria in special circumstances where it
can be shown that a lesser or higher Construction SWPPP Tier Level is
warranted.
B-24
l~3o 6P.-5S~ooo /"-'..J(£... '2.o~ · O(pt!>. ~
Owner/Owner's Authorized Agent Name: Tifle:
Page 1 of 1 Rev.03/09
& ~ CITY OF
CONSTRUCTION THREAT
ASSESSMENT WORKSHEET FOR
DETERMINATION OF PROJECT'S
PERCEIVED THREAT TO
STORM WATER QUALITY
E-33
Development Services
Land Development Engineering
1635 Faraday Avenue
760-602-2750
www.carlsbadca.gov CARLSBAD
Construction Perceived
SWPPPTier Construction Threat Assessment Criteria* Threat to
Storm Water Level Quality
Tier 3 -High Construction Threat Assessment Criteria D Project site is 50 acres or more and grading will occur during the rainy season
D Project site is 1 acre or more in size and is located within the Buena Vista or Agua Hedionda
Lagoon watershed, inside or within 200 feet of an environmentally sensitive area (ESA) or
discharges directly to an ESA High D Soil at site is moderately to highly erosive (defined as having a predominance of soils with
Tier3 D
USDA-NRCS Erosion factors kt greater than or equal to 0.4)
Site slope is 5 to 1 or steeper
D Construction is initiated during the rainy season or will extend into the rainy season (Oct. 1
D
through April 30).
Owner/contractor received a Storm Water Notice of Violation within past two years
Tier 3 -Medium Construction Threat Assessment Criteria Medium D All projects not meeting Tier 3 High Construction Threat Assessment Criteria
Tier 2 High Construction Threat Assessment Criteria
D Project is located within the Buena Vista or Agua Hedionda Lagoon watershed, inside or
within 200 feet of an environmentally sensitive area (ESA) or discharges directly to an ESA
D Soil at site is moderately to highly erosive (defined as having a predominance of soils with
USDA-NRCS Erosion factors kt greater than or equal to 0.4) High
D Site slope is 5 to 1 or steeper Tier2 D Construction is initiated during the rainy season or will extend into the rainy season (Oct. 1
through April 30).
D Owner/contractor received a Storm Water Notice of Violation within past two years
D Site results in one half acre or more of soil disturbance
Tier 2 -Medium Construction Threat Assessment Criteria Medium D All projects not meeting Tier 2 High Construction Threat Assessment Criteria
Tier 1 -Medium lnsQection Threat Assessment Criteria
D Project is located within the Buena Vista or Agua Hedionda Lagoon watershed, within or
directly adjacent to an environmentally sensitive area (ESA) or discharges directly to an ESA ® D Soil at site is moderately to highly erosive (defined as having a predominance of soils with
USDA-NRCS Erosion factors kt greater than or equal to 0.4)
Tier 1 ~Site slope is 5 to 1 or steeper
Construction is initiated during the rainy season or will extend into the rainy season (Oct. 1
through April 30).
D Owner/contractor received a Storm Water Notice of Violation within past two years
D Site results in one half acre or more of soil disturbance
Tier 1 -Low lnsQection Threat Assessment Criteria Low D All projects not meeting Tier 1 Medium Construction Threat Assessment Criteria
Exempt -Not Applicable -Exempt
*The c1ty eng1neer may authonze mmor vanances from the construction threat assessment cntena m spec1al circumstances
where it can be shown that a lesser or higher amount of storm water compliance inspection is warranted in the opinion of
the city engineer
E-33 Page 1 of 1 REV 4/30/10
•
«~ ~ CITY OF
CARLSBAD
PLANNING DIVISION
BUILDING PLAN CHECK
APPROVAL
P-29
Development Services
Planning Division
1635 Faraday Avenue
(760) 602-4610
www.carlsbadca.e:ov
DATE: 3/9/2016 PROJECT NAME: SFR ADDITION/CARPORT PROJECT ID:
PLAN CHECK NO: CB160551 SET#: 2 ADDRESS: 1630 BASSWOOD AVE APN:
[2J This plan check review is complete and has been APPROVED by the
PLANNING Division.
By: VERONICA MORONES
A Final Inspection by the PLANNING Division is required DYes [g) No
You may also have corrections from one or more of the divisions listed below.
Approval from these divisions may be required prior to the issuance of a building
permit. Resubmitted plans should include corrections from all divisions.
D This plan check review is NOT COMPLETE. Items missing or incorrect are
listed on the attached checklist. Please resubmit amended plans as
required.
Plan Check Comments have been sent to:
WRIGHTHAUS@ROADRUNNER.COM
For questions or clarifications on the attached checklist please contact the following reviewer as
marked:
D Chris Sexton D Chris Glassen D Greg Ryan
760-602-4624 760-602-2784 760-602-4663
Chris.Sexton@carlsbadca.gov Christopher.Giassen@carlsbadca.gov Gregory.Ryan@carlsbadca.gov
D Gina Ruiz D VaiRay Marshall D Cindy Wong
760-602-4675 760-602-27 41 760-602-4662
Gina.Ruiz@carlsbadca.gov VaiRay.Marshall@carlsbadca.gov Cynthia.Wong@carlsbadca.gov
Veronica Morones D Linda Ontiveros D Dominic Fieri 760-602-4619
veronica.morones@carlsbadca.gov 760-602-2773 760-602-4664
Linda.Ontiveros@carlsbadca.gov Dominic.Fieri@carlsbadca.gov
P-28 Page 1 of 4 07111
«~ ~ CITY OF
PLANNING DIVISION
BUILDING PLAN CHECK
APPROVAL
Development Services
Planning Division
1635 Faraday Avenue
(760) 602-4610
www.carlsbadca.szov CARLSBAD P-29
Remarks: NON CONFORMING STRUCTURE DUE TO SIDE YARD SETBACKS,
DOES NOT NEED NON CONFORMING CONSTRUCTION PERMIT [588 SQ FT
CHANGE< 640 SQ FT/40% OF SFR=1008 SQ FT] !2NDSUBMITIALJ: PER CW,
CARPORT IS CONSIDERED ATTACHED, DOES NOT NEED 10' SEPARATION.
PER 21.48.050, NON CONFORMING PARKING IS PROVIDED (DRIVE WAY AND
NEW CARPORT) EVEN THOUGH NEW GARAGE IS NOT 12'X20'SEETEAM MTG NOTES
FROM 3/9/16.
REVIEW#:
1 2 3
~~D
P-28
Plan Check No. CB160551 Address 1630 BASSWOOD AV Date 3/9/2016 Review# 1
Planner Veronica Morones Phone (760) 602-4619
APN:
Type of Project & Use: SFR ADDITION/CARPORT Net Project Density: DU/AC
Zoning: R-1 General Plan: R-4 Facilities Management Zone: 1
CFD (in/out) #_Date of participation: __ Remaining net dev acres: __
(For non-residential development: Type of land use created by this permit: __ )
Legend: ~ Item Complete
Environmental Review Required:
DATE OF COMPLETION:
D Item Incomplete -Needs your action
YES 0 NO 0 TYPE
Compliance with conditions of approval? If not, state conditions which require action.
Conditions of Approval:
Discretionary Action Required: YES 0 NO 0 TYPE __
APPROVAL/RESO. NO. DATE
PROJECT NO.
OTHER RELATED CASES:
Compliance with conditions or approval? If not, state conditions which require action.
Conditions of Approval: __
Coastal Zone Assessment/Compliance
Project site located in Coastal Zone? YES 0 NO ~
CA Coastal Commission Authority? YES 0 NO 0
If California Coastal Commission Authority: Contact them at-7575 Metropolitan Drive, Suite
103, San Diego, CA 92108-4402; (619) 767-2370
Determine status (Coastal Permit Required or Exempt):
Habitat Management Plan
Data Entry Completed? YES D NO D
If property has Habitat Type identified in Table 11 of HMP, complete HMP Permit application
and assess fees in Permits Plus
Page 2 of4 07111
«~ ~ CITY OF
PLANNING DIVISION
BUILDING PLAN CHECK
APPROVAL
Development Services
Planning Division
1635 Faraday Avenue
(760) 602-4610
www.carlsbadca.e:ov CARLSBAD P-29
Site Plan:
~~D
D~D
P-28
(A/P/Ds, Activity Maintenance, enter CB#, toolbar, Screens, HMP Fees, Enter Acres of
Habitat Type impacted/taken, UPDATE!)
lnclusionary Housing Fee required: YESD NOD
(Effective date of lnclusionary Housing Ordinance-May 21, 1993.)
Data Entry Completed? YES D NO D
(A/P/Ds, Activity Maintenance, enter CB#, toolbar, Screens, Housing Fees, Construct Housing
Y/N, Enter Fee, UPDATE!)
Housing Tracking Form (form P-20) completed: YES D NO D N/A D
Provide a fully dimensional site plan drawn to scale. Show: North arrow, property lines,
easements, existing and proposed structures, streets, existing street improvements, right-of-
way width, dimensional setbacks and existing topographical lines (including all side and rear
yard slopes). Provide legal description of property and assessor's parcel number.
City Council Policy 44-Neighborhood Architectural Design Guidelines
1. Applicability: YES D NO D
2. Project complies: YES D NOD
Zoning: STRUCTURE IS EXISTING NON CONFORMING
1. Setbacks:
Front:
Interior Side:
Street Side:
Rear:
Top of slope:
Required __ Shown_·_
Required __ Shown __
Required __ Shown __
Required __ Shown __
Required __ Shown __
2. Accessory structure setbacks: EXISTING NON CONFORMING STREET SIDE SETBACK
OF 5'; NEW ADDITIONS MEET STANDARDS OF 10'. CARPORT (ACCESSORY
STRUCTURE) MUST MEET 1 0' SEPI\RATIOI!-1 FROM RESIDENCE IF DETACHED.
PLEASE SHOW SETBACK ON PLANS. PLEASE DENOTE SETBACKS ON PLANS TO
POST RELATED TO CARPORT.
Front:
Interior Side:
Street Side:
Rear:
Structure separation:
Required 20'
Required 5'6"
Required 1 0'
Required 11'2"
Required 1 0'
Page 3 of4
Shown 20'
Shown 6'
Shown 1 0'/5'
Shown 12'
Shown N/A
07/11
«~ ~ CITY OF
PLANNING DIVISION
BUILDING PLAN CHECK
APPROVAL
Development Services
Planning Division
1635 Faraday Avenue
(760) 602-4610
www.carlsbadca.eov CARLSBAD P-29
D~D 3. Lot Coverage: Required S 40% Shown NOT SHO'IVN: PLEASE PROVIDE
D~D
D~D
TOTAL LOT AREA FOR NECESSARY CALCULATION 28%
4. Height: Required MAXIMUM 24'@ ROOF PITCH 2:12 SHOWN
Shown 14'@ 2:12 PITCH
5. Parking: SEE REMARKS Spaces Required __ Shown __
(breakdown by uses for commercial and industrial projects required)
Residential Guest Spaces Required__ Shown __
Additional Comments SITe PlAN: PLEASE SHOW ONLY PROPOSED STRUCTURES
ASSOCIATED WITH BUILDING PERMIT C916Q551 SCOPE OF VVORK. IS THE
PROPOSED SCREENING WALL WITHIN THE SCOPE OF THE PERMIT? IF NOT.
PLE-P.SE REMOVE FROM PLANS. PROPOSED SCREENING WALL IS 42" AND
PERMITTED IN FY SB-DOES NOT REQUIRE BLDG PERMIT PER B-39.
OK TO ISSUE AND ENTERED APPROVAL INTO COMPUTER 1414 DATE~ /t(p
P-28 Page 4 of4 07111
Ccityof
Carlsbad
RESIDENTIAL GREEN
BUILDING CODE
STANDARDS MANDATORY
MEASURES
CERTIFICATION
CHECKLIST
Development Services
Building Division
1635 Faraday Avenue
760-602-2719
www.carlsbadca.gov
B-51
Site Development Mandatory
4.106.2 A plan is developed and implemented to manage storm water drainage during construction. (X)
4.106.3 The site shall be planned and developed to keep surface water away from buildings. (X)
Construction plans shall indicate how site grading or a drainage system will manage all surface water
flows.
eri~t :etJici ric•', ' <'' ',;·,, '> ,· " ',,, :' . :"'J , ':.r: , ·. , ... .. ,.9Y ....... , .. ,, .. !.,. Y '·' · .. · ... """' '• ·' ... :. .,,,. .•.. ,. ........ ... :
4.201.1 Low-rise residential buildings shall meet or exceed the minimum standard design required by (X)
the California Energy Standards.
. . ,. . .· . .. ·•··· "'" ,. ,. ' ·: .. ""••' .. "• . · .. Wate Efficienc :arid Conserlation. , . .,. , ... , .. ,[ ... ,,., ..... ,., ... ,. Y.,.,. .. . ... ··,. . . ,. .,.. ,, .. ,., ·" ., '·'' .· ... ... >: ·,, ' " . ,,, . ···: .. ,,.; .';:,.':,: ,,. ,,, .. :.:.:>,,.,
lndoorWatir Use , · H,,~,,,,~r ,,, ,, ,'"'"':" ,(:~0;'~,;~~S;E: ': ., ··.'· ' " '':,·':,:· .. ·:.:,·•:, ~· " '' J' '""'"'''"' :;;:(' /< ,', ' 'i, '··' :'': ·h·,'' :i : •. ' ," ,, , ,,_~,,,'flit} -:,c/0','<" -,;c,;-,, ,' "'"''" "'' '"'' ',, <',< > ~:,<:<~v:, ,: ,: ,,:f, , .. ,,,. ,,· '. .. "
4.303.1 Indoor water use shall be reduced by at least 20 percent using one of the following methods: (X)
1. Water saving fixtures or flow restrictors shall be used. 7/01/2011
2. A 20 percent reduction in baseline water use shall be demonstrated.
4.303.2 When using the calculation method specified in Section 4.303.1, multiple showerheads shall not (X)
exceed maximum flow rates. 7/01/2011
4.303.3 Plumbing fixtures (water closets and urinals) and fittings (faucets and shower heads) shall (X)
comply with specified performance requirements . 7/01/2011
outdoor·vvaterus~ "'. . . ,, ?"'·''·: ,, ':: . ';'; '·" ,., :, .. , , .. '·· · ..
,,,>:''"'''" ''' <,,,,/,2,/"',,y;;-,,' : ..... ··'' . . : ·., ,{·
4.304.1 Automatic irrigation systems controllers installed at the time of final inspection shall be weather-(X)
based.
Enhaht,ecl 9M~~bility cind Reduc~d M~intenarice ·
4.406.1 Joints and openings. Annular spaces around pipes, electric cables, conduits or other openings
in plates at exterior walls shall be protected against the passage of rodents by closing such openings (X)
with cement mortar, concrete masonry or similar method acceptable to the enforcing agency.
Construction Wast~':Maria emer1t'·PI~r1 1 .· ..
' .. '''· . . . .:•.: ·<·· ..... ,., ... 9 .. ' .. . . . . ·.' :.,. '· ... . ' :•
4.408.1 A minimum of 50 percent of the construction waste generated at the site is diverted to recycle or (X)
salvage. Recycled material receipts from approved recyclers must be attached to this form.
4.408.2 Where a local jurisdiction does not have a construction and demolition waste management (X)
ordinance, construction waste management plan, per form B-59, shall be submitted for approval to the
enforcing agency.
Building M~,lriJ~nante and Qp~ratio.l} ....
.. ,.
4.410.1 An operation and maintenance manual shall be provided to the building occupant or owner. (X)
Environmental.· Qucility, '
:'' . ·' '•.
Fireplaces . ': ..,
·.,. ' ,,
4.503.1 Any installed gas fireplace shall be a direct-vent sealed-combustion type. Any installed
woodstove or pellet stove shall comply with US EPA Phase II emission limits where applicable. (X)
Woodstoves, pellet stoves and fireplaces shall also comply with applicable local ordinances.
B-51 Page 1 of 2 Rev.11/15
Poll
4.504.1 Duct openings component openings shall be covered
during construction.
4.504.2.1 Adhesive, sealants and caulks shall be compliant with VOC and other toxic compound (X)
limits. (X)
4.504.2.2 Paints, stains and other coatings shall be compliant with VOC limits. ( x)
4.504.2.3 Aerosol paints and coatings shall be compliant with product weighted MIR limits for
ROC and other toxic compounds. ( x)
4.504.2.4 Documentation shall be provided to verify that compliant VOC limit finish materials
have been used. ( x)
4.504.3 Carpet and carpet systems shall be compliant with VOC limits.
4.504.4 50 percent of floor area receiving resilient flooring shall comply with VOC-emission limits ( x)
defined in the Collaborative for High Performance Schools (CHPS) Low-emitting Materials List or
be certified under the Resilient Floor Covering Institute (RFCI) FloorScore program. ( x)
4.504.5 Particleboard, medium density fiberboard (MDF) and hardwood plywood used in interior
finish shall with low
4.507.1 Whole house exhaust have or covers
fan is off. Covers or louvers shall have a minimum insulation value of R-4.2.
4.507.2 Duct systems are sized, designed, and equipment is selected using the following
methods: (X)
1. Establish heat loss and heat gain values according to ACCA Manual J or equivalent.
2. Size duct systems according to ACCA 29-D (Manual D) or equivalent
3. Select and to ACCA 36-S
(X)
I, as the professional responsible for this project, certify that, to the best of my knowledge, the mandatory items
listed on this form have been incorporated into the project in order to comply with Title 24, Part 11 of the 2013
California Green Building Standards. All receipts for recycled materials have been attached to this form.
ProjectAddress: (C. S'c) 231~tv~l) ~
Print Name: /?o # /f'C Z, P.J . ..=5r~lh(J
Plan Check Number: CC) ((d)~S)
Signerl:~.~<hR? _ __.
License Number: f<go ZZ~ Date: !2-/ Is-/~ r 1
B-51 Page 2 of2 Rev. 11/15