HomeMy WebLinkAbout1695 FARADAY AVE; ; CB992872; Permit1'
06/20/2000
City of Carlsbad
Commercial/Industrial Permit Permit No: CB992872
Job Address:
Permit Type:
Parcel No:
Valuation:
Occupancy Group:
Project Title:
Applicant:
MULVANIA ED
Building Inspection Request Line (760) 602-2725
1695 FARADAY AV CBAD
Tl Sub Type:
2121303400 Lot#:
$35,000.00 Construction Type:
Reference #:
RACK SYSTEM
COMM
0
NEW
Status:
Applied:
Entered By:
Plan Approved:
Issued:
Inspect Area:
ISSUED
08/03/1999
JM
06/20/2000
06/20/2000
5807 VAN ALLEN WAY
CARLSBAD CA 92008
760-929-7588
0617 06/20/00 0001 01
C-PRMT
Total Fees: $515.27
Building Permit
Add'I Building Permit Fee.
Plan Check
Add'I Plan Check Fee
Plan Check Discount
j
I !
Strong Motion Fee '
Park Fee \
LFM Fee \
Bridge Fee
BTD #2 Fee
BTD #3 Fee
Renewal Fee
Add'I Renewal Fee
Other Building Fee
Pot. Water Con. Fee
Meter Size
Add'I Pot. Water Con. Fee
Reel. Water Con. Fee
Inspector:
·:(otal P?Jyments·'fii;q~te: . ,$:$200:bQ '·<,;-, C :Bal~i:ice Due: (, .... ,., / ;/' i /\ \\.~ \ 's..,./ \
/'",. / t'v,, \
'~,/....__..,, "·~ ,:' .. ,·---.. ----,,----~ ___,.,.-._,_., '--. -~-"'/ \. ·, .:-·-·
$0.00
$0.00
FINAL APPROVAL
$315.18
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$515.27
Date: _____ _ Clearance: _____ _
NOTICE: Please take NOTICE that approval of your project includes the "Imposition" of fees, dedications, reservations, or other exactions hereafter collectively
referred to as "fees/exactions." You have 90 days from the date this permit was issued to protest imposition of these fees/exactions. If you protest them, you must
follow the protest procedures set forth in Government Code Section 66020(a), and file the protest and any other required information with the City Manager for
processing in accordance with Carlsbad Municipal Code Section 3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack,
review, set aside, void, or annul their imposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection fees and capactiy
changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this project. NOR DOES IT APPLY to any
fees/exactions of which vou have oreviouslv been aiven a NOTICE similar to this or as to which the statute of limitations has oreviouslv otherwise exoired.
CITY OF CARLSBAD
2075 Las Palmas Dr., Carlsbad, CA 92009 (760) 438-1161
02
/. ·, :1 } / \.'
I 'I I
315-18
~L::tt1 /41 &
PERM,ff APPLICATION ~ ,,
C1TY OF CARLSBAD BUILDING DEPARTMENT
2075 Las Palmas Dr., Carlsbad CA 92009
(760) 438-11,61 Validated By__.,<d---#<-'-:;,,,,,,,.--E:rl7'7--#:n-":r-
Date _________ """" ...... _ _..--J...__
1695 FARADAY AVE. Address'(inclµde Bldg/Suite #I CARLSBAD, Business Name (at this address) CA 920Q8 SMAC
WAREHOUSE 109 CARLSBAD RESEARCH Legal Description Lot No. Subdivision Name/Number CENT~ 08107 199 0001 Oif ;?,~ Unit~. 4
7fhase Nt'-PRMTotal; u~.09
212-130-34-000~094 WAREHOUSE WAREHOUSE ~
Assessor's Parcel # Existing Use Proposed Use
FINISHED PRODUCT RACKING N/A N/A N/A N/A
Description of Work SQ. FT. #of Stories # of Bedrooms # of Bathrooms
~g~~~~~lf!miit?~tf~~1wR,:1fff~~~~¥~rt.r0·1l{::~~~x~;~~~B~~.~);~~~~~~~;t~~§1:~~1:f4~·~~~~~,=-~ s a a
Name Address City State/Zip Telephone # Fax #
mr~~~1~~w.m.¥faW"~.1\l~~~a1r-.wr~ · ~e6.Fiw,~~;::011;t.~t'it,0~f:I~.r:~~:r@~G-~1t~·~:z;~;~
SMAC EN WAY 5
Name Address Telephone#
Name Address City S,tate/Zip Telephone #
lffi{JfflNR•8l~~l~~~~tik~~~i~~:~~~~<~~~~~:~~f.!:?l-\fi~~J,~¥.0s.:t:)~i;;,'1~~~::t~'fJ~2::t\~0.~~rif:}~~:;;t;~s~a::~;:
(Sec. 7031.5 Business and Professions Code: Any City or County which requires a permit to construct, alter, improve, demolish or repair any structure, prior to its
issuance, also requires the applicant for such permit to file a signed statement that he is licensed pursuant to the provisions of the Contractor's License Law
[Chapter 9, commending with Section 7000 of Division 3 of the Business and Professions Code] or that he is exempt therefrom, and the basis for the alleged
exemption. Any violation of Section 7031.5 by any applicant for a pe~mit subjects the applicant to a civil penalty of not more than five hundred dollars [$5001).
Name Address City State/Zip Telephone#
State License # · N/A License Class N/A City Business License # N/A
Designer Nall)e Address City State/Zip Telephone
State License # NIA
F~&rPB1ft~lQ~Rfflffllfiffli~~t~~)kf ¥~£;:~R~l.:{~M~~~~{la{f~~:~(~¥~~~J;rntt1~-~~~:~~(.~1::;i_~;.t1r~::~~'.-'lfty~~£~~~G}::::~~~;>;\~:-;~:~~* ~
Workers' Comp1msation Declaration: I hereby affirm under penalty of perjury one of the following declarations:
0 I have and will maintain a certificate of consent to self-insure for workers' compensation as provided by Section 3700 of the Labor Code, for the performance
of the work for which this permit is issued.
Iii I have and will maintain workers' compensation, as required by Section 3700 of the Labor Code, for the performance of the work for which this permit is
issued. My worker's compensation insurance carrier and policy number are:
lnsuranceCompany REPUBLIC INDEMNITY PolicyNo. 005485-08 Expiration Date 4/20/2000
(THIS SECTION NEED NOT BE COMPLETED IF THE PERMIT IS FOR ONE HUNDRED DOLLARS ($100) OR LESS)
0 CERTIFICATE OF EXEMPTION: I certify that in the performance of the work for which this permit is issued, I shall not employ any person in any manner so as
to become subject to the Workers' Compensation Laws of California.
WARNlr,.IG: Failure to secure workers' compensation coverage is unlawful, and shall subject an employer to criminal penalties and civil fines up to one hundred
thousand dollars ($100, n to thi;, cost of compensation, damages as provided for In Section 3706 of the Labor code, i terest and attormiy's fees.
SIGNATURE-::::;;i!'!-,~~=2 ~~S-,~~~~===-~-=:-::::-:=::7"'.-:-::-::::-:::-::-:-:-:::-.:-::::--:-::-. DATE _r...,e,.,,£,Ji!!!=-,..<:~'--4'---£fij~~f11WB~! llu)i~~ ~~ ~~J1tt.1,a~1.1&Sfi~·~ll;~~w21l:;;rrtt~::rr1~"t-~fl.~11:~~I :t{~11/1J:::;;~~0;~~~1-:r1g~_i;fEJR:;t~1~:~~TI{(~l~::;;~~;~:(1~±::r;·~~.t::1:-1:\~
I hereby affirm that I am exempt from the Contr tor's License Law for the following reason:
.IK\ I, as owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not intended or offered for sale
(Sec. 7044, Business and Professions Code: The Contractor's License Law does not apply to an owner of property who builds or improves thereon, and who does
such work himself or through his own employees, provided that such improvements are not intended or offered for sale. If, however, the building or improvement is
sold within one year of completion, the owner-builder will have the burden of proving that he did not build or improve for the purpose of sale).
0 I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions Code: The
Contractor's License Law does not apply. {o an owner of property who builds or improves thereon, and contracts for such projects with contractor(s) licensed
pursuant to the Contractor's License Law).
0 I am exempt under Section ______ Business and Professions Code for this reason:
1. I personally plan to provide the major labor and materials for construction of the proposed property improvement. 0 YES ONO
2. I (have / have not) signed an application for a building permit for the proposed work.
3. I have contracted _with the following person (firm) to provide the proposed construction (include name / address I phone number / contractors license number):
4. I plan to provide portions of the work, but I have hired the following person to coordinate, supervise and provide the major work (include name / address / phone number/ contractors license number): _____________________________________________ _
5, I will provide some of the work, but I have contracted (hired) the following persons to provide the work indicated (include name / address / phone number / type
of work):, __________ 7"'::::...7"-g,.,:;_,;.~=---=-----,,--------------------,----.--:-----------
Is the applicant or future building occupant required to sub 1t a business plan, acutely hazardous materials registration form or risk management and prevention
program under Sections 25505, 25533 or 25534 of the Presley-Tanner Hazardous Substance Account Act? 0 YES 1jJ NO
Is the applicant or future building occupant required to obtain a permit from the air pollution control district or air quality management district? 0 YES '.l8J' NO
Is the facility to be constructed within 1,000 feet of the outer boundary of a school site? 0 YES 8 NO
IF ANY OF THE ANSWERS ARE YES, A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR IS MEETING THE
REQUIREMENTS OF THE OFFICE OF EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT.
I hereby affirm that there is a construction lending agency for the performance of the work for which this permit is issued (Sec. 3097 (ii Civil Code).
LENDER'S NAME N / A LENDER'S ADDRESS N / A ----------------------------
I certify that I have read the application and state that the above information is correct and that the information on the plans is accurate. I agree to comply with all
City ordinances and State laws relating to building construction. I hereby authorize representatives of the Cit\' of Carlsbad to enter upon the above mentioned
property for inspection purposes. I ALSO AGREE TO SAVE, INDEMNIFY AND KEEP HARMLESS THE CITY OF CARLSBAD AGAINST ALL LIABILITIES,
JUDGMENTS, COSTS AND EXPENSES WHICH MAY IN ANY WAY ACCRUE AGAINST SAID CITY IN CONSEQUENCE OF THE GRANTING OF THIS PERMIT.
OSHA: An OSHA permit is required for excavations over 5'0" deep and demolition or construction of structures over 3 stories in height.
EXPIRATION: Every permit issued by the Building Official under the provisions of this Code shall expire by limitation and become null and void if the building or
work authorized by such permit is not co enced within 365 days from the date of such permit or if the building or work authorized by such permit is suspended
or abandoned at any time after the w e ed for a period of 180 days (Section 106.4.4 Uniform Building Code).
DATE -~-r~'----::~.,.,_~------,...,_~---
YELLOW: Applicant PINK: Finance
City of Carlsbad
1-1! 11 G 11 Ii~ i •J4 ·El iii ,14 Iii
November 10, 2000
SMAC PARTNERS LP
5807 VAN ALLEN WAY
CARLSBAD CA 92008
RE: BUILDING PERMIT EXPIRATION
PERMIT TYPE: TI
Permit Number:
Issue Date:
CB992872
6/20/2000'
ADDRESS: 1695 FARADAY AV
PLEASE CALL FOR AN INSPECTION IF WORK IS
COMPLETE
Our records indicate that your building permit will expire by limitation of time on 12/17/2000.
The provisions of UBC, Section 106.4.4 as amended by the Carlsbad Municipal Code state: "EXPIRATION.
Every permit issued by the Building Official under the provisions of this code shall expire by limitation and
become null and void. if the. btiiJding or. wor):c authoriz~d by such· permit is not coIT.menced within 1-80 days
from the date of such permit (unless issued prior to 7 /1/99 which is one year from date of permit), or if the
building or work authorized by such permit is stopped at any time after the work is commenced for a period of
180 days or if the building or work authorized by such permit exceeds three calendar years from the issuance
date of permit. Work shall be presumed to have commenced if the permittee has obtained a required inspection
approval of work authorized by the permit by the Building Official within 180 days of the date of permit
issuance. Work shall be presumed to be stopped if the permittee has not obtained a required inspection
approval of work by the Building Official within each 180 day period upon the initial commencement of work
authorized by such permit.
Before such work can be recommenced, a new permit shall be obtained to do so, and the fee, therefore, shall
be one-half the amount required for a new permit for such work, and provided that no changes have been made
or will be made in the original plans and specifications for such work, and provided further that such
suspension or abandonment has not exceeded one year. In order to renew action on a permit after expiration,
the permittee shall pay a new permit fee.
Any person holding an unexpired permit may apply for an extension of the time within which work may
commence under that permit when the permittee is unable to commence work within the time period required
by this section for good and satisfactory reasons. The Building Official may extend the time for action by the
permittee for a period not exceeding 180 days on written request by the permittee showing that circumstances
beyond the control of the permittee have prevented action from being taken. No permit shall be extended more
than once.
Please check helow indicating your Lritentions and return this letter to us.
/ Project abandoned. A new permit will be ob~ained prior to commencing work.
No fee extension requested for 180 days. (attach a letter of explanation)
Renewal permit requested.
If the project has been completed and only a final inspection is needed, please call the inspection request line at
(760) 602-2725.
If you have any questions, please contact the Building Inspection Department at (760) 602-2700.
PAT KELLEY
Principal Building -Inspector
1,
1635 Faraday Avenue• Carlsbad, CA 92008-7314 • (760) 602-2700 • FAX (760) 602-8560 @
City of Carlsbad
i=i!iit?Hii~i•J4•Eiiii,14iil
06/12/2000
MULVANIAED
5807 VAN ALLEN WAY
CARLSBAD CA92008
Re:
Application Date: 8/3/1999
Plan Check #: CB992872
Address: 1695 FARADAY AV
Expiration Date: 8/2/2000
You applied to have your plan~ checked on the date noted above. To date, the related
building permit has not been obtained. The original plan review application will expire as
no building permit has been issued.
Plans submitted and not retrieved from the building department prior to the pian check
expiration date noted above will be destroyed.
The provisions of sections 304 (d) of the Uniform Building Code state:
"Section 304 9d) Expiration of Plan Review
Applications for which no permit is issued within one year following the date
of application shall expire by limitation, .and plans and other data submitted
for review may thereafter be returned to the applicant or destroyed by the
Building Official.
In order to renew action on an application after expiration, the applicant shall
resubmit plans and pay a new plan review fee."
In order to provide better service, please indicate your handling choice for the plans
originally submitted and return this letter to the Building Department.
__ Project Abandoned -I will pick up plans within 1 O days
__ Project Abandoned -Plans may be destroyed.
If you have any questions, please contact the Building Department at (760) 602-2718.
Raenette Abbey
Building Department
1635 Faraday Avenue• Carlsbad, CA 92008-7314 • (760) 602-2700 • FAX (760) 602-8560 @
.City of Carlsbad Bldg Inspection Request
Permit# CB992872
Title: RACK SYSTEM
Description:
For: 6/28/2000
Type:Tl Sub Type: ·COMM
Job Address: 1695 FARADAY AV
Suite: Lot
Location:
APPLICANT MULVANIA ED
Owner: SM AC PARTNERS LP
Remarks: RACK INSPECTION
Total Time:
0
CD Description Act Comments
Inspector Assignment:
Phone:
Inspector: ~
Requested By: ED
Entered By: CHRISTINE
14 Frame/Steel/Bolting/Welding ;V!l. C:t:Jv~-1? &tttf:E:,wR AH,() 11> l>i?/7 µo PH. -:/J::.
Associated PCRs
Inspection History
Date Description Act lnsp Comments
EsGil Corporation
'l.n Partnersliip witli government for '13uiCaing Safety
DATE: 9/27 /99
JURISDICTION: Carlsbad
PLAN CHECK NO.: 99-2872 SET: II
D APPLICANT ~
D PLAN REVIEWER
D FILE
PROJECT ADDRESS: 1695 Faraday Ave.
PROJECT NAME: Storage Racks for SMAC
D The plans transmitted herewith have been corrected where necessary and substantially comply
with the Jurisdiction's building codes.
[8J The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
D
D
D
The plans transmitted herewith have significant deficiencies identified on the er:iclosed check list
and should be corrected and resubmitted for a complete recheck. .
•' ..
The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
The applicant's copy of the check list is_ enclosed for the jurisdiction to forward to the applicant
contact person. ,,
\
The applicant's copy of the check list has been sent to:
Esgil Corporation staff did not advise the applicant that the plan check has been completed.
Esgil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Telephone#:
Fax#:
Mail Telep~on ax In Person
Date contacte~: (by: )
REMARKS: 1 · y to review that the path of travel from the handicapped parking space to the
racks area and the·bathrooms serving the rack area comply with all the current disabled access
requirements. 2. File Depa1t111eA-t--approval is requiroo. 3. Note on the plan to provide minimum
4" between the racks and existing walls and columns. t· Please slip the rack layout sheet into
the city set l(at building department). 6[~
By: David Yao Enclosures:
Esgil Corporation
D GA D MB D EJ D PC 9/16 trnsmtl.dot
9320 Chesapeake Drive, Suite 208 + San Diego, California 92123 + (858) 560-1468 + Fax (858) 560-1576
EsGil Corporation
'l.n Partnersliip witli qovernment for 'Buiufing Safety
DATE: 8/13/99
JURISDICTION: Carlsbad
PLAN CHECK NO.: 99-2872
PROJECT ADDRESS: 1695 Faraday Ave.
PROJECT NAME: Storage Racks For SMAC
SET:I
~ANT
~
CJ PLAN REVIEWER
CJ FILE
D The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
[8J The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
~ The applicant's copy of the check list has been sent to:
SMAC (Ed Mulvania) 5807 Val Allen Way Carlsbad CA 92008
[8J Esgil Corporation staff did not advise the applicant that the plan check has been completed.
D Esgil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Telephone#:
Date contacted: (by: ) Fax#:
Mail Telephone Fax In Person
D REMARKS:
By: David Yao Enclosures:
Esgil Corporation
D GA D MB D EJ D PC 8/5 trnsmU.dot
9320 Chesapeake Drive, Suite 208 + San Diego, California 92123 + (858) 560-1468 + Fax (858) 560-1576
Carlsbad 99-2872
8/13/99
· GENERAL PLAN CORRECTION LIST
JURISDICTION: Carlsbad
PROJECT ADDRESS: 1695 Faraday Ave.
DATE PLAN RECEIVED BY
ESGIL CORPORATION: 8/5
REVIEWED BY: David Yao
FOREWORD (PLEASE READ):
PLAN CHECK NO.: 99-2872
DATE REVIEW COMPLETED:
8/13/99
This plan review is limited to the technical requirements contained in the Uniform Building Code,
Uniform Plumbing Code, Uniform Mechanical Code, National Electrical Code and state laws
regulating energy conservation, noise attenuation and disabled access. This plan review is
based on regulations enforced by the Building Department. You may have other corrections
based on laws and ordinances enforced by the Planning Department, Engineering Department
or other departments.
The following items listed need clarification, modification or change. All items must be satisfied
before the plans will be in conformance with the cited codes and regulations. Per Sec. 106.4.3,
1997 Uniform Building Code, the approval of the plans does not permit the violation of any
state, county or city law.
1. Please make all corrections on the original tracings, as requested in the correction list.
Submit three sets of plans for commercial/industrial projects (two sets of plans for
residential projects). For expeditious processing, corrected sets can be submitted in one of
two ways:
1. Deliver all corrected sets of plans and calculations/reports directly to the City of
Carlsbad Building Department, 2075 Las Palmas Drive, Carlsbad, CA 92009, (760) 438-
1161. The City will route the plans to EsGil Corporation and the Carlsbad Planning,
Engineering and Fire Departments.
2. Bring one corrected set of plans and calculations/reports to EsGil Corporation,
9320 Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-1468. Deliver all
remaining sets of plans and calculations/reports directly to the City of Carlsbad Building
Department for routing to their Planning, Engineering and Fire Departments.
NOTE: Plans that are submitted directly to EsGil Corporation only will not be
reviewed by the City Planning, Engineering and Fire Departments until review by EsGil
Corporation is complete.
2. To facilitate rechecking, please identify, next to each item, the sheet of the plans
upon which each correction on this sheet has been made and return this sheet
with the revised plans.
,,
Carlsbad 99-2872
8/13/99
3. Please indicate here if any changes have been made to the plans that are not a result of
corrections from this list. If there are other changes, please briefly describe them and
where they are located on the plans. Have changes been made not resulting from this
list?
D Yes D No
4. Provide a rack layout plan showing the location of all racks.(Please clearly identify the
locations of type A rack, type 8 rack and type C rack.
5. Provide a statement on the Title Sheet of the plans that this project shall comply with
Title 24.
6. Provide a note on the plans indicating if any hazardous materials will be stored and/or
used within the building which exceed the quantities listed in UBC Tables 3-D and 3-E.
7. The tenant space and new and/or existing facilities serving the remodeled area must be
accessible to and functional for the physically disabled. See the attached correction
sheet. Title 24, Part 2.
8. Obtain Fire Department approval for groups F, Mand S occupancy storage per UBC.
9. Indicate the clearance from the new racks to the existing building walls and building
columns.
10. Provide forklift protection.
Recheck the "pallet" racks as follows:
11. Recheck all connections on sheet 1 as follows:
a) The rivet bearing capacity is only dtF u = 0.406(0.0747)65 = 2 kips.
b) Provide calculations for all beam to bracket weld capacities per Section 2330
(allowable weld stress is the member thickness times 26 ksi times 1.33, or the
weld stress, whichever is lower).
c) Check the bracket maximum weak axis moment.
12. Indicate the safety pin size and verify it is adequate for the 1000# load.
13. Recheck the base plate anchors as follows:
a) Check the transverse seismic for overturning with only the top shelf loaded with
the force acting through the center of gravity of the top load per Section 2237.7.
14. Provide calculations for the column weak axis bending plus axial for transverse seismic
loading. The axial load is the maximum compression load at the base from vertical plus
seismic overturning. The column moment will probably be maximum for the lateral load
from the base plate to the first diagonal brace (not only to the first horizontal member).
Carlsbad 99-2872
8/13/99
. . .
15. The jurisdiction has contracted with Esgil Corporation located at 9320 Chesapeake
Drive, Suite 208, San Diego, California 92123; telephone number of 858/560-1468, to
perform the plan review for your project. If you have any questions re.garding these plan
review items, please contact David Yao at Esgil Corporation. Thank you.
..
Carlsbad 99-2872
8/13/99
· VALUATION AND PLAN CHECK FEE
JURISDICTION: Carlsbad
PREPARED BY: David Yao
BUILDING ADDRESS: 1695 Faraday Ave.
BUILDING OCCUPANCY:
BUILDING PORTION BUILDING AREA
(ft.2)
Storage racks
Air Conditioning
Fire Sprinklers
TOTAL VALUE
PLAN CHECK NO.: 99-2872
DATE: 8/13/99
TYPE OF CONSTRUCTION:
VALUATION
I
VALUE
MULTIPLIER ($)
35000
(per city)
D 199 USC Building Permit Fee [:8J Bldg. Permit Fee by ordinance:$ 307.83
D 199 USC Plan Check Fee [:8J Plan Check Fee by ordinance: $ 200.09
Type of Review: D Complete Review D Structural Only D Hourly
D Repetitive Fee Applicable D Other:
Esgil Plan Review Fee: $ 160.07
Comments:
Sheet 1 of 1
macvalue.doc 5196
I
PLANNING/ENGINEERING APPROVALS
PERMIT NUMBER CB qq ,J-fJ?J-/) -1·7 ,,Clo/ DATE __ O __ /_/ __ _
ADDRESS __ / b_. C/_5_H_~_--f,'11£::....--1v_f_---.--___ _
.RESIDENTIAL
RESIDENTIAL ADDITION MINOR
( < $10,000.00)
PLAZA CAMINO REAL
CARLSBAD COMPANY STORES
VILLACE FAIRE
COMPLETE OFFICE BUILDINC
OTHER ----------J~----------
DATE ------
DATE--;-,J~/t/ ~f'J2_
~ .• BY ·~·: .. ·~a--:~:~·~·~,·~ 01' TE ................................. .
SUBJECT. .......................... ~
,;_ ;_., A··c_ , I (, &J 5
. ,
RACK DESIGN & ENGINEERING CO.
3788 LA CRESCENTA A VE., SUITE 204-
GLENDALR, CA. 01208
TEL:(818)957-2980 FAX:(818)9&7-8603
ft-t~ A 1:>A '-L , Ct1ttR. LrlJ A-l:>1 CA .
f SHEET NO ........................ .
JOB NO •....... t3..0..Y'.~.8.0
q , Y-1--1 • ...t. C <-~,-,R Aut. E
l 0. ()e,1<tJtF1 ./tll"1 i1-t~ 7 ~A 11. v~I.! r/1-f,~tl"' 7 ~ c. tlM II
CA vr~ e. o ,,.,_Aft~ oF "(il1J1 8A-y , Tlt'-c K~A.,.
w ti...(.. !vffoAT' 1~t ~IJTt,t{ L•A,1
r~ ~ '' ·1
k > 2 )( I• '1 :s 1. .• g ~ .. ..( C5 'd' ..,
fl -"°' ;;, "l.-k.. ,,, 't J le..
1/
S p,., C.,-,,t [Ci"-~ -t ( / .._"' 2 ,, ) J ><'I· 3.3.r
f'Aa W(!'l/J ~ (J.f "-f '2 'I) )( tO 7t,~ '' )(.. f • JJ: /1 .. J •'Jr..
·• Tc-M ~" N ,./ s I 'L
( l,) . .,. ./l. ,, ti ~H(.~ •
. k. '"-:. • 87 ~ '2 :r I· 7
I "I .. .... C\ -,_,_ '1 , 1 , q -r1 8 -
C:0 39\;td I9N3 QN1;t N9IS3Q ~81;1~
Sept. 13, 1999
SMAC
5807 VAN ALLEN WAY, CARLSBAD, CA 92008
TEL: (760) 929-7575 FAX: (760) 929-7588
City of Carlsbad Building Dept.
2075 Las Palmas Dr.
Carlsbad, CA. 92009
The attached information and Rack Layout Print for our SMAC Storage Rack Project, Plan
Check #99-2872 is in response to the General Plan Correction List which we had received from
EsGil Corp. Please advise if any additional information is needed.
Thank You;
EdMulvania
BY ......... 9.: ... .9.~A~!.~.~···.
DATE ...... ?::.?.~.-::-.~.~······· . .
SUBJE;CT ... ~ ..................... .
RACK DESIGN & ENGINEERING CO.
3786 LA CRESCENTA AVE., SUITE 204
GLENDALE. CA. 91206
'J'EL:(818)957-2980 FAX:(818)957-8603
STRUCTURAL CALCULATIONS OF "LMT"
STORAGE RACKS FOR:
SMAC
1695 FARADAY
CARLSBAD, CA. 92008
PER UBC 1 997 EDITION
STORAGE RACKS CAPACITY:
1 800 # / LEVEL
REF: CALCS. 1 THRU 6
DRAWINGS: RD-4080
SH. 1
SHEET NO •........... 1-.. ......... .
JOB NO ........ R.!?.~.4:9.!?.9 .. .
BY ........ .9 ..... .9..1:!At!!A.~ ... .
DATE ...... ?.::-:-.?_~::-:-.~.~······· ' .
SU9JECT .... ~ ..................... .
130"
OJ a,
OJ a,
TYPE "A" FRONT VIEW
1
130" l
'N I(} N, ...
I(}
. N st
TYPE "C" FRONT VIEW
RACK DESIGN & ENGINEERING CO.
3786 LA CRESCENTA AVE., SUITE 204
GLENDALE, CA. 91208
TEL:(818)957-2980 FAX:(818)957-8603
SHEET NO, ........... ?. ........... .
JOB NO ........ R.P.::-:.49.~9. ..
SIDE VIEW
SIDE VIEW
. (X) I(}
130'' l 1 56" r
TYPE 11 811 FRONT VIEW SIDE VIEW
LBF354 BEAM
1800 # / LEVEL + 25% IMPACT LOAD
1000 #/BEAM
1 7/8" n
~
,l 2 3/4" l
M= 130"x1 K = 16.3 "K
8
"K
SR= 16-3 = .54<.76 30
Ix= 1.47
Sx =. 76
KSI. Fy =50
3 b:. = 5xWxL = _57,, < 130 = .72"
384xl xXE 180
BY
DATE
G. OHANIAN
7-23-99 SHEET NO.
JOB NO.
3
RD-4080
SUBJECT •
RACK DESIGN & ENGINEERING CO.
3786 LA CRESCENTA AVE., SUITE 204
GLENDALE, CA .. 91208
TEL:(818)957-2980 FAX:(818)957-8603
SEISMIC DESIGN
V= 2.SxCaxl x W
R
Ca=.44xNa
Ca=.44x1 .2=.53
LOAD PER COLUMN TYPE "A"
K K
P= 2x1.8 =1.8
2
( 8 K 7 ) = 1 .4 K W=.1 + 1. x. D.L. L.L. UTIL.
V= 2.5x.53x1 .4
5.6
V= 2.5x.53x1 .4
4.4
V= 2x.42 = .84 K
K =.33
K = .42
LONGIT. SEISMIC
;
CX)
(J)
------.--;-· 17"
,___ ________ 15 K 8.2 "K
15,8 "K
.99
1800 # / LEVEL
use 1997 SEC. 2222
1=1
R=5.6
Rw=4.4
LONGIT. DIR. (MOM. CONN.)
TRANSV. DIR. (BRACED)
Na= 1.2
W:::D.L.+L.L.
TABLE 16.5
"K
BASE SHEAR PER COLUMN LONGITUDANAL DIRECTION
BASE SHEAR PER COLUMN TRANSVERSE DIRECTION
BASE SHEAR PER FRAME TRANSVERSE DIRECTION
15.8 "K
"K .99
TYPE "8"
K K P= 4x1 .8 =3.6
2
W=.1 +(3.6K x. 7 ) =2. 6 K
D.L. L.L. UTIL.
K H "K
M = .61 x56 =17
COL. 2
TYPE "C"
K K
P= 5x1.8 =4.5
2 1
W (4 5 K 7 ) :::::3.2K =.1 + . x.
D.L. L.L. UTIL.
S K tt "K M =: .7 x28 =10,5
COL. 2
K V= .61
BY ......... 9: .... 9..t!A~!A.~ ... .
DATE ..... .!.:-:-:.?.~::.~.~ ....... .
SUBJECT .... ~ .................... ..
COLUMN ANALYSIS
I ,. 1:3
~[~-x ll::J
Kl-~-77 8 rx -1 .26 -·
RACK DESIGN & ENGINEERING CO.
3786 LA CRESCENTA AVE., SUITE 204
GLENDALE, CA. 91208
'l'EL:(818)957-2980 FAX:(818)957-8603
A=.62
lx=1.02
Sx =.68
rx = 1.26
KSI Fy =50
fy::::,87
Sy =.56
ry=1.16
SHEET NO ............ 1: ........... .
JOB N0 ........ ~.!?.:-:-:.19.~9 .. .
Fe>_ix_
2
F KSI
Fn =Fy (1-4;)= 36.8
"K
K
P0 =Fn xA = 22.8
COMBINED STRESS RATIO
L+ _M_ = _1d._ + 15·8 = .89< 1.33 Pa Max 11.9 20.4
L+_M_ == 2.66 + 21074 = 1.01 < 1.33 P0 Mox 14. .
BASE PLATE
"K K
ANCH. TENSION = ·99 -(1.4 x3") = 0 6"
ANCHOR SHEAR = ~ = . 17 K
2
USE (2)-1/2"¢ HILT! ANCH. (ICBO #4627)
3 1/2" EMB. (NO INSPECTION REQ'D)
DESIGNED FOR 1 /2 STRESS
TYPE ,, A,,
TYPE "8,,
[ .. .. --
.· .. . . . . .
K 1.4
j "K
.99
)
7"x4"x3/8"
BASE PLATE
... ,,4, . .
~ . .. .. .. I") .. . . . . ...
5 1/2"
7"
BY ......... q: .... 9.HA~!A.~ ....
7-23-99 DATE .................................. .
SUBJECT .... ~ ..................... .
RACK DESIGN & ENGINEERING CO.
3786 LA CRESCENTA AVE .• SUITE 204
GLENDALE, CA. 91208
TEL:(818)957-2980 FAX:(818)957-8603
MOMENT AT BEAM CONNECTION
.99+ 15.8 "K
M1= = 8.4
2
15.8+8.2 "K
M2= = 12
2
USE 3 PIN CONNECTOR
ALL LEVELS TYP.
I c" 095 Fy --79 KSI 7 1 o ¢ RIVET A = .
K Va= .095x79x.4 = 3.0
7 /16"¢ RIVET
ASTM A354-79
3 PIN CONNECTOR
TH'K:;:3/16"
K ,, "K Ma = 3.0 x4 x 1.33 = 16 CONN. '
c-
12
a.2~
I
I
t ~ l"K
~15.8
Mz
SHEET NO ...... : ..... ~ .......... ..
JOB N0 ........ ~.!?.:-:-:.19.~9 .. .
"K 12
BY
DATE
G. OHANIAN
7-23.-99
SUBJECT
0
RACK DESIGN & ENGINEERING CO.
3786 LA CRESCENTA AVE., SUITE 204
GLENDALE, CA. 91208
TEL:(818)957-2980 FAX:(818)957-8603
SHEET NO.
JOB NO.
TRANSVERSE SEISMIC
(OVERTURNING) TYPE "A" GOVERNS
K " ~ M0r = .84 x204 x.5x1 .15 = 98.5
K u "K MR = 1.4 x48 = 67 .2
"K "K
UPLIFT= 98.5 -;,67.2 =.65K
48
TWO 1 /2"¢ ANCHOR BOLTS PER BASE PLATE OK.
LOAD TO DIAGONAL
K P ::c: .84x 56 = 1 . 1
42
KSI Fy =50
A=.31
rx =.48
Q=.74
L= 56"
CHECK WELDS
KSI
Fa = 11.2
K Pa= 3.5
1 1/2"
~ t=t ~A-X
.,... i=.0711
SEC. A-A
TYP 1/8 1"
1/8" WELD 1.5" LONG EACH SIDE (3" TOTAL)
K 3x.125x. 707x70x.3 = 5.4
CHECK SLAB
<I
4500 I
4
6" CONCRETE SLAB 2000 PSI. CONC.
1000 PSF. SOIL
..
6.5" I, 6.2" ..
12.7" 12.7"
25.4"
SEC. 8-B
• 4500 ° 1000 ::: 4·5 4.5x144=648
0"
-J 648 =25.4"
2 "#
M= ( ~i ) x1 OOOx i x12= 1601.6
2
S= 12x6 =72 6
16~d-6 = 22.2< 1,6 -J 2000 =72
6
RD-4080