Loading...
HomeMy WebLinkAbout1702 BLACKBIRD CIR; ; CBR2016-0147; PermitPrint Date: 02/06/2017 Job Address: Permit Type: Parcel No: Valuation: Occupancy Group: #Dwelling Units: Bedrooms: Project Title: 1702 Blackbird Cir BLDG-Residential 2156026200 $0.00 City of Carlsbad 1635 Faraday Av Carlsbad, CA 92008 Residential Permit www.carlsbadca.gov Work Class: P/M/E Lot#: Reference #: Construction Type: Bathrooms: Orig. Plan Check#: Plan Check#: Description: SIESEL: REPLACE EXIST. FAU/ SAME LOCAL PLUMBING, ELECTRICAL, AND MECHANICAL PERMIT Total Fees: $166.00 Owner: TRUST SIESEL 2010 TRUST 06-04-10 1702 Blackbird Cir CARLSBAD, CA 92011 Total Payments To Date: $166.00 Status: Applied: Issued: Finaled: Inspector: Contractor: COASTAL REFRIGERATION 6525 Paseo Frontera, Apt L Carlsbad, CA 92009-4534 760-683-5683 Balance Due: Please take NOTICE that approval of your project includes the "Imposition" of fees, dedications, reservations, or other exactions hereafter collectively referred to as "fees/exaction." You have 90 days from the date this permit was issued to protest imposition of these fees/exactions. If you protest them, you must follow the protest procedures set forth in Government Code Section 66020(a), and file the protest and any other required information with the City Manager for processing in accordance with Carlsbad Municipal Code Section 3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack, review, set aside, void, or annul their imposition. You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection fees and capacity changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this project. NOR DOES IT APPLY to any fees/exactions of which you have previously been given a NOTICE similar to this, or as to which the statute of limitation has previously otherwise expired. Permit No: CBR2016-0147 Closed -Finaled 11/21/2016 11/21/2016 MColl $166.00 $0.00 ' • i THE FOLLOWING APPROVALS REQUIRED PRIOR TO PERMIT ISSUANCE: 0 PLANNING D ENGINEERING {"atyof Carlsbad EXISTING USE APPLICANT NAME Primary Contact ADDRESS CITY PHONE EMAIL DESIGN PROFESSIONA ADDRESS CITY PHONE EMAIL Building Permit Application 1635 Faraday Ave., Carlsbad, CA 92008 Ph: 760-602-2719 Fax: 760-602-8558 email: building@carlsbadca.gov www.carlsbadca.gov SUITE#/SPACEI/UNITI #BEDROOMS #BATHROOMS PROPOSED USE STATE ZIP FAX STATE FAX STATE LIC. # 0BUILDING DFIRE Plan Check No. Est. Value PlanCk. Date SWPPP OCC. GROUP (Sec. 7031.5 Business and Professions Code: Any City or County which requires a permit to construct, alter, improve, demolish or repair an~ structure, prior to its issuance, also requires the applicant for such permit to file a signed statement that he is licensed pursuant to the provisions of the Contractor's License Law [Chapter 9, commending with Section 7000 of Division 3 of the Business and Professions Code} or that he is exempt therefrom, and the basis for the alleged exemption. Any violation of Section 7031.5 by any applicant for a permit subjects the applicant to a civil penalty of not more than five hundred dollars {$500}). WORKERS' COMPENSATION Workers' Compensation Declaration: I hereby affirm under penalty of perjury one of the following declarations: ~ve and will maintain a certificate of consent to self-insure for workers' compensation as provided by Section 3700 of the Labor Code, for the performance of the work for which this permit is issued. ~I have and will maintain work~~on,:s required by Section 3700 of the Labor Code, for the performance of the work f~hich this ~rmitis issued. y workers' compensation i urance rrier and policy number are: Insurance Co. ~,L Policy No. Expiration Date ~~,e.,~-fi;tL-"""L-....L.c... 'j:lli§,section need not be completed if the permit is for one hundred dollars ($100) or less. U Certificate of Exemption: I certify that in the of the work for which this permit is issued, I shall not employ any person in any manner so as to become subject to the Wo California. WARNING: Failure to secure is unlawful, and shall subject an employer to criminal penalties and civil fines up to one of the Labor code, interest and attorney's fees. I hereby affirm that I am exempt from Contractor's Ucense Law for the following reason: D D D I, as owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not intended or offered for sale (Sec. 7044, Business and Professions Code: The Contractors License Law does not apply to an owner of property who builds or improves thereon, and who does such work himself or through his own employees, provided that such improvements are not intended or offered for sale. If, however, the building or improvement is sold within one year of completion, the owner-builder will have the burden of proving that he did not build or improve for the purpose of sale). I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions Code: The Contractors License Law does not apply to an owner of property who builds or improves thereon, and contracts for such projects with contractor(s) licensed pursuant to the Contractors License Law). I am exempt under Section Business and Professions Code for this reason: 1. I personally plan to provide the major labor and materials for construction of the proposed property improvement. DYes 0No 2. I (have I have not) signed an application for a building permit for the proposed work. 3. I have contracted with the following person (firm) to provide the proposed construction (include name address I phone I contractors' license number): 4. I plan to provide portions of the work, but I have hired the following person to coordinate, supervise and provide the major work (include name I address I phone I contractors' license number): 5. I will provide some of the work, but I have contracted (hired) the following persons to provide the work indicated (include name I address I phone I type of work): _.KS PROPERTY OWNER SIGNATURE 0AGENT DATE I COMPLETE THIS SECTION FOR NON-RESIDENTIAL BUILDING PERMITS ONLY Is the applicant or future building occupant required to submit a business plan, acutely hazardous materials registration form or risk management and prevention program under Sections 25505, 25533 or 25534 of the Presley-Tanner Hazardous Substance Account Act? DYes D No Is the applicant or future building occupant required to obtain a permit from the air pollution control district or air quality management district? DYes D No Is the facility to be constructed within 1,000 feet of the outer boundary of a school site? D Yes D No IF ANY OF THE ANSWERS ARE YES, A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR IS MEETING THE REQUIREMENTS OF THE OFFICE OF EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT. Lender's Name I certify that I have read the application and state that the above infonnation is conectand that the infonnation on the plans is accurate. I agree to comply with all City ordinances and State lav.s relating to building consbucllon. I hereby authorize representative of the City of Carlsbad to enter upon the above mentioned property for inspection purposes. I ALSO AGREE TO SAVE, INDEMNIFY AND KEEP HARMLESS THE CITY OF CARLSB<\D AGAINST ALL LIABILITIES, JUDGMENTS, COSTS AND WHICH MAY IN ANY WAY ACCRUE AGAINST SAID CITY IN CONSEQUENCE OF THE GRANTING OF THIS PERMIT. OSHA: An OSHA permft is required for excavations over ' or construction of structures over 3 stories in height. EXPIRATION: Every permtt issued by the Building i · expire by limttation and become null and void ~the building or v.or1< authorized by permit is not commenced within 180 days from the date of such permtt or suspended or abandoned at any time after the v.or1< is commenced for a (Section 106.4.4 Uniform Building Code). ~APPLICANT'S SIGNATURE DATE STOP: THIS SECTION NOT REQUIRED FOR BUILDING PERMIT ISSUANCE. Complete the following ONLY if a Certificate of Occupancy will be requested at final inspection. Fax (760) 602-8560, Email building@carlsbadca.gov or Mail the completed form to City of Carlsbad, Building Division 1635 Faraday Avenue, Carlsbad, California 92008. DELIVERY OPTIONS D PICK UP: o CONTACT (Listed above) o OCCUPANT (Listed above) o CONTRACTOR (On Pg, 1) D MAIL TO: o CONTACT (Listed above) o OCCUPANT (Listed abcve) o CONTRACTOR (On Pg. 1) D MAIL/ FAX TO OTHER:----------------- A! APPLICANT'S SIGNATURE (Office Use Only) CA o ASSOCIATEDCB#------------ o NO CHANGE IN USE/ NO CONSTRUCTION o CHANGE OF USE/ NO CONSTRUCTION DATE PERMIT INSPECTION HISTORY REPORT (CBR2016-0147) Permit Type: BLDG-Residential Application Date: 11/21/2016 Owner: TRUST SIESEL 2010 TRUST 06-04-10 Work Class: P/M/E Issue Date: 11/21/2016 Subdivision: Status: Closed -Finaled Expiration Date: 08/02/2017 Address: 1702 Blackbird Cir Carlsbad, CA 92011-5008 IVR Number: 371 Scheduled Actual Date Start Date Inspection Type Inspection No. Inspection Status Primary Inspector Reinspection Complete 02/03/2017 02/03/2017 BLDG-43 Air 012463-2017 Passed Michael Collins Complete Cond./Fumace Set BLDG-Final 012464-2017 Failed Michael Collins Reinspection Complete Inspection Checklist Item COMMENTS Passed BLDG-Plumbing Final No BLDG-Mechanical Final Need HERS report. No BLDG-Electrical Final No 02/06/2017 02/06/2017 BLDG-Final 012766-2017 Passed Michael Collins Complete Inspection Checklist Item COMMENTS Passed BLDG-Mechanical Final T-24/HERS report received. Yes BLDG-Electrical Final No BLDG-Plumbing Final No BLDG-Mechanical Final Need HERS report. No February 06, 2017 Page 1 of 1 CERTIFICATE OF INSTALLATION CF2R·MCH-20-H Duct Leakage Diagnostic Test (Page 1 of 3) Project Name: SIESEL Enforcement Agency: City of Permit Number: on site Carlsbad Dwelling Address: 1702 Blackbird cir City: Carlsbad Zip Code: 92011 A. System Information 01 Space Conditioning System Identification or Name System 1 02 Space Conditioning System Location or Area Served Location 1 03 Building Type from CF-1R Single family 04 Verified Low Leakage Ducts in Conditioned Space No, credit is not taken (VLLDCS) Credit from CFlR? 05 Verified Low Leakage Air Handling Unit (VLLAHU) Credit No, credit is not taken from CF1R? 06 Duct System Compliance Category Alteration using smoke test .(#·'.!:· I :.'""~:r·./ ,.h,.<,/ci'' 7:'""L''lrh,1• ·r~~t1Lt1f' .;;i·t··rh ~! MCH-20e -Sealing All Accessibl~teaks fing s"}9k,Tft~ ;'''''"' i . ,,~{ t~ ;,, it''Mti; :,:~ ll't ~:,, ': ~' ~ ·~ ~ i"K 2c. " +" 7&fihliii:# 'l,;,,,,,,t[' ''L'l'funfu tdl' ''1Lcl'l'''i'•'fu' (!~li¥!il'~,!(: Jllf l)T ~7 bfu . 'l~(f' l'l', B. Duct Leakage Diagnostic Testf+~~, ( '' ,, I, i 01 Condenser Nominal Cooling Capacity (ton) 0 02 Heating Capacity (kBtu/h) 71 03 Conditioned Floor Area served by this HVAC system (ft2) 2400 04 Duct Leakage Test Condition Test final OS Duct Leakage Test Method Total leakage 06 Leakage Factor 0,15 07 Air Handling Unit Airflow (AHUAirflow) Determination Heating system method Method 08 Measured AHUAirflow This field or section is not applicable 09 Calculated Target Allowable Duct Leakage (cfm) 231 10 Actual duct leakage rate from leakage test measurement 749 (cfm) Registration Date/Time: 2016-12-28 15:50:18 HERS Provider: CaiCERTS Registration Number: 216-A0478383A-M2000002A-OOOO CA Building Energy Efficiency Standards Report Version: 2013 Rev 1.008 Schema Version: 2013.1.007 Report Generated: 2016-12-28 15:50:19 2013 Residential Compliance CERTIFICATE OF INSTALLATION CF2R-MCH-20-H Duct Leakage Diagnostic Test (Page 2 of 3) B. Duct Leakage Diagnostic Test Compliance Statement: System passes using smoke test of an altered HVAC system in an existing building. No visible smoke exits the accessible portions of the duct system. Smoke is only emanating from air-handling unit (AHU) cabinet and non 11 accessible portions of the duct system. Note-Accessible is defined as having access thereto, but which first may require removal or opening of access panels, doors, or moving similar obstructions. If access to the ducts requires an object to be demolished or deconstructed then sealing of those ducts is not required C. Additional Requirements for Compliance 01 System was tested in its normal operation condition. No temporary taping allowed. Outside air (OA) duct connections to the central forced air duct system shall not be sealed/taped off during duct leakage 02 testing. OA ducts used for Central Fan Integrated (CFI) Indoor Air Quality ventilation systems, or Central Fan Ventilation Cooling Systems, that utilize dampers that open only when OA is required and automatically close when OA is not required, may configure the OA damper to the closed position during duct leakage testing. 03 All supply and return register boots were sealed to the drywall. 04 Building cavities were not used as plenums or platform returns in lieu of ducts. c c<'?'iw ' ,:"''R'f,c i1Y24Hc!', ;Jcf<\ iw;,;,iw!!J,; ,,v,,c ,,: OS If cloth backed tape was used it was co~ered witl1<JA1as5c ~d draJfbaqdsi(ri:,: :, C,"'," ;~i ]! h« ,,;,;;+t ,,, '" ~,' ;:k 06 All connection points bet~ee(l,the air hltidler Jndthesup~ly and ~etui'n plen~ms a:~e compl~te!Y seal~d. "'"'~-,;,! ' ' ,, If the system complies using the Smoke Test method, the smoke test was conducted in accordance with the requirements of 07 Reference Residential Appendix RA3.1.4.3.6. Systems that comply using smoke test shall not be included in sample groups for HERS verification compliance. The responsible persons signature on this compliance document affirms that all applicable requirements in this table have been met. Registration Number: 216-A0478383A-M2000002A-OOOO CA Building Energy Efficiency Standards 2013 Residential Compliance Registration Date/Time: 2016-12-28 15:50:18 HERS Provider: CaiCERTS Report Version: 2013 Rev 1.008 Schema Version: 2013.1.007 Report Generated: 2016-12-28 15:50:19 CERTIFICATE OF INSTALLATION CF2R-MCH-20-H Duct Leakage Diagnostic Test (Page 3 of 3) Documentation Author's Declaration Statement 1. I certify that this Certificate of Installation documentation is accurate and complete. Documentation Author Name: Documentation Author SignatureS~~~ Seth Woolson Company: Signature Date: 2016-12-28 15:50:18 COASTAL REFRIGERATION HEATING & CONDITIONING Address: CEA/ HERS Certification Identification (if applicable): 6525 PASEO FRONTERA UNIT I City/State/Zip: Phone: CARLSBAD CA 92009 760-683-5683 X123 Responsible Person's Declaration statement I certify the following under penalty of perjury, under the laws of the State of California: 1 The information provided on this Certificate of Installation is true and correct. 2 I am eligible under Division 3 of the Business and Professions Code in the applicable classification to accept responsibility for the system design, construction, or installation of features, materials, components, or manufactured devices for the scope of work identified on this Certificate of Installation and attest to the declarations in this statement (responsible builder/installer), otherwise I am an authorized representative of the responsible builder/installer. 3. The constructed or installed features, materials, components or manufactured devices (the installation) identified on this Certificate of Installation conforms to all applicable codes and regulatio~~. ~nd the install~tion c~ntormsJ?z~~ r~94.~r.~:men:ij,J~~~n on ~h~ plans and.~pecifications approved by the enforcement agency. . • • · .,'.-'. ·,f ·;, .r; · ·' ·' 4. I understand that a HERS rater v,tiJl check th~j'lnstallation to)J!rifi, coihpliance, ~l!ldtltat" hecig id~ defects; l~m ~~~~ ~if.!lke corrective action at my e se.'t~!-!nderstan~~hat En~y ~m~ssl?e and HErf Provi;t • sentltives perfornt~~u<\.!tv a;tttce checking of installations, including oved as pal!t:of,;i sample grltp bot.AQt-t~;by 'HERLaterf'~md ft'. ioiallatiolls f311 to ·eet'tfle.;: requirements of such quality e checking, the required corrective action anda<!ditional checking/te~ngpf~~her ~llatiansin t'lPtHERS sample group will be performed at"~ expense.! ; '· ~ :. ~·· : r ( ~ ·r, ·· I ~ " f : } ' I ,j ~ _, ,> 5. I reviewed a copy of the Certificate of Compliance approved by the enforcement agency that identifies the specific requirements for the scope of construction or installation identified on this Certificate of Installation, and I have ensured that the requirements that apply to the construction or installation have been met. 6. I will ensure that a registered copy of this Certificate of Installation shall be posted, or made available with the building permit(s) issued for the building, and made available to the enforcement agency for all applicable inspections. I understand that a registered copy of this Certificate of Installation is required to be included with the documentation the builder provides to the building owner at occupancy. Responsible Builder/Installer Name: Responsible Builder/Installer Signature: Seth Woolson ~~,Z,L. //.. Company Name: {Installing Subcontractor or General Contractor or Position With Company (Title): Builder /Owner) Owner COASTAL REFRIGERATION HEATING & CONDITIONING Address: CSLB License: 6S25 PASEO FRONTERA UNIT I 974929 City/State/Zip: Phone: I Date Signed: CARLSBAD CA 92009 760-683-5683 X123 2016-12-28 15:50:18 Third Party Quality Control Program (TPQCP) Status: Name of TPQCP (if applicable): Digitally signed by Ca/CERTS. This digital signature is provided in order to secure the content of this registered document and in no way implies Registration Provider responsibl1ity for the accuracy of the information. Registration Number: 216-A0478383A-M2000002A-OOOO CA Building Energy Efficiency Standards 2013 Residential Compliance Registration Date/Time: 2016-12-28 15:50:18 HERS Provider: CaiCERTS Report Version: 2013 Rev 1.008 Schema Version: 2013.1.007 Report Generated: 2016-12-28 15:50:19 CERTIFICATE OF INSTALLATION CF2R-MCH-01-E Space Conditioning Systems, Ducts, and Fans (Page 1 of 7) Project Name: SIESEL Enforcement Agency: City of Carlsbad Permit Number: on site Dwelling Address: 1702 Blackbird cir City: Carlsbad Zip Code: 92011 A. General Information 01 Dwelling Unit Name SlESEL 02 Climate Zone 7 03 Dwelling Unit Total Conditioned Floor 2400 04 Number of Space Conditioning 1 Area (tt2) Systems in this Dwelling Unit. OS Certificate of Compliance Type Prescriptive alterations {CFlR-ALT) 06 Method used to calculate HVAC Loads NotApplicableEquipmentChangeout 07 Calculated Dwelling Unit Sensible This field or section is not applicable 08 Calculated Dwelling Unit Heating load This field or section is not applicable Cooling Load (Btuh) (Btu h) 09 Dwelling Unit Number of Bedrooms 3 ;wz'/ ,<' ,, ' '\ i MCH-Olb Space Conditioning Systems Ducts and],fans-~4"escriptive Alterations i; ,,,' ~ '''lJY\,;, f? ;,'1': ,:w :,' ," j '''il~W;~~t ;;; B. Space Conditioning (SC) System Information '"'~J; <, 01 02 03 04 OS 06 07 08 09 10 SCSystem SCSystem CFAserved Is the SC Installing a Installing new SC Installing more Installing Installing Identification or Location or Area by this SC system a refrigerant system than 40 feet of entirely new entirely new SC Alteration Type Name Served System (ft2) ducted containing components? ducts? duct system? system? system? component? System 1 Location 1 2400 Yes Registration Number: 216-A0478383A-M0100002A-0000 CA Building Energy Efficiency Standards-2013 Residential Compliance No Yes No Registration Date/Time: 2016-12-28 15:50:18 Report Version: 2013 Rev 1.008 Schema Version: 2013,1.008 Altered space No No conditioning system , __ L__ , __ -- HERS Provider: CaiCERTS Report Generated: 2016-12-28 15:49:16 CERTIFICATE OF INSTALLATION Space Conditioning Systems, Ducts, and Fans C. Space Conditioning {SC) System Alterations Compliance Information 01 02 03 04 OS 06 07 08 09 Heating Cooling System Altered Heating Minimum Altered Cooling Minimum Identification Heating Heating Efficiency Efficiency Cooling Cooling Efficiency Efficiency or Name System Type Component Type Value System Type Components Type Value This field All new No cooling or Central gas heating Central section is System 1 AFUE 78 component SEER furnace componen split AC altered not ts applicabl e D. Installed Heating Equipment Information F~~<:C ~··~ ~ < ,: 01 02 03 7~<; <~ ~ ~:04y ~ : ~ os~ System Identification or ; He~tinrr,E~ncf ~:;;,:,fieating'tJ.ik Heating<Un it' Name Heating Efficiency Ty~t: Value '~Manufacturer Model Number I 80g1uh090bp161-System 1 AFUE 78 ACPRO 55 Notes: L__________._ ___ --- E. Installed Cooling Equipment information This section does not apply to this project. F. Extension of Existing Duct System, Greater Than 40 Feet Registration Number: 216-A0478383A-M0100002A-0000 CA Building Energy Efficiency Standards -2013 Residential Compliance This section does not apply to this project. Registration Date/Time: 2016-12-28 15:50:18 Report Version: 2013 Rev 1.008 Schema Version: 2013.1.008 CF2R-MCH-01-E (Page 2 of 7) I 10 11 12 13 ! Central Fan I Integrated I New or (CFI) Required Replaced New Ventilation I Thermostat Duct Duct System Type Length R-Value Status ! Not a CFI I Setback LTE40Ft R6 system ! ! ' :l ~D6,~' 07 'lie~tingUnlt'serral Rated Heating capacity, number Output (BTUH) I ' 1716h30328 71000 HERS Provider: CaiCERTS Report Generated: 2016-12-28 15:49:16 CERTIFICATE OF INSTALLATION Space Conditioning Systems, Ducts, and Fans G. Installed Duct System information H. Installed Air Filter Device Information I. Air Filter Device Requirements Registration Number: 216-A0478383A-M0100002A-OOOO CA Building Energy Efficiency Standards-2013 Residential Compliance This section does not apply to this project. This section does not apply to this project. This section does not apply to this project. Registration Date/Time: 2016-12-28 15:50:18 Report Version: 2013 Rev 1.008 Schema Version: 2013.1.008 CF2R-MCH-Ol-E (Page 3 of 7) HERS Provider: CaiCERTS Report Generated: 2016-12-28 15:49:16 CERTIFICATE OF INSTALLATION Space Conditioning Systems, Ducts, and Fans J. HERS Verification Requirements 01 02 03 04 MCH20 Exemption System SC System From Duct Duct Identification or Location or Area Leakage Leakage Name Served Requirements Test System 1 location 1 No Yes exemptions Notes: Registration Number: 216-A0478383A-M0100002A-OOOO CA Building Energy Efficiency Standards-2013 Residential Compliance 05 06 07 MCH21 MCH22 Exemption from Minimum R-Valuefor Ducts In Ducts Located AHU Fan Conditioned In Cond Space Efficacy Space Verification (W/cfm) No Exemption No No Registration Date/Time: 2016-12-28 15:50:18 Report Version: 2013 Rev 1.008 Schema Version: 2013.1.008 CF2R-MCH-Ol-E (Page 4 of 7) 08 09 10 MCH23 MCH25 MCH28 AHU Airflow Rate Refrigerant Return Duct Design (dm/ton) Charge Table 150.0-C or D I i No No No I I I HERS Provider: CaiCERTS Report Generated: 2016-12-28 15:49:16 CERTIFICATE OF INSTALLATION CF2R-MCH-01-E Space Conditioning Systems, Ducts, and Fans {Page 5 of 7) K. Space Conditioning Systems, Ducts and Fans Mandatory Requirements and Additional Measures Note: Additional mandatory requirements from Section 150.0 that are not listed here may be applicable to some systems. These requirements may be applicable to only newly installed equipment or portions of the system that are altered. Existing equipment may be exempt from these requirements. Heating Equipment 01 Equipment Efficiency: All heating equipment must meet the minimum efficiency requirements of Section 110.1 and Section 110.2(a) and the Appliance Efficiency Regulations. 02 Controls: All unitary heating systems, including heat pumps, must be controlled by a setback thermostat. These thermostats must be capable of allowing the occupant to program the temperature set points for at least four different periods in 24 hours. See Sections lSO.O(i), 110.2(b). 03 Sizing: Heating load calculations must be done on portions of the building served by new heating systems to prevent inadvertent undersizing or oversizing. See sections lSO.O{h)l and 2). 04 Furnace Temperature Rise: Central forced-air heating furnace installations must be configured to operate at or below the furnace manufacturer's maximum inlet-to-outlet temperature rise specification. See Section 150.0(h)4. 05 Standby Losses and Pilot Ughts: Fan-type central furnaces.may not have~a c~tinuously"6uminltp11otm~ht.;Section llO.S and Section 110.2(d). ;. • i'j ;:•: ' j'{ .D • ·D ••> .. D ·"· Cooling Equipment { ~ ·~.· . ''· ,, .. ,, .·,·::""' D. • ••• Jt?\ .,,. l~ '? ,., .· 1. •{i' 06 Equipment Efficiency: All cooling equipment misstmeet the minimum efficiencyrequirementsofSection 110.1 and Section 110.2(a) and the Appliance Efficiency -' ' - Regulations. 07 Refrigerant Une Insulation: All refrigerant line insulation in split system air conditioners and heat pumps must meet the R-value and protection requirements of Section 150.0(j)2 and 3, and Section 150.0(m)9. 08 Condensing Unit Location: Condensing units shall not be placed within five (5) feet of a dryer vent outlet. See Section 150.0(h)3A. 09 Sizing: Cooling load calculations must be done on portions of the building served by new cooling systems to prevent inadvertent undersizing or oversizing. See Section 1SO.O(h)1 and 2. Air Distribution System Ducts, Plenums and Fans 10 Insulation: In all cases, unless ducts are enclosed entirely in directly conditioned space, the minimum duct insulation value is R-6. Note that higher values may be required by the prescriptive or performance requirements. See Section 150.0(m)1. Registration Number: 216-A0478383A-M0100002A-OOOO CA Building Energy Efficiency Standards-2013 Residential Compliance Registration Date/Time: 2016-12-28 15:50:18 Report Version: 2013 Rev 1.008 Schema Version: 2013.1.008 HERS Provider: CaiCERTS Report Generated: 2016-12-28 15:49:16 CERTIFICATE OF INSTALLATION CF2R-MCH-01-E Space Conditioning Systems, Ducts, and Fans (Page 6 of 7) K. Space Conditioning Systems, Ducts and Fans Mandatory Requirements and Additional Measures Note: Additional mandatory requirements from Section 150.0 that are not listed here may be applicable to some systems. These requirements may be applicable to only newly installed equipment or portions of the system that are altered. Existing equipment may be exempt from these requirements. Connections and Closures: All installed air-distribution system ducts and plenums must be, sealed and insulated to meet the requirements of CMC Sections 601.0, 11 602.0, 603.0, 604.0, 605.0 and ANSI/SMACNA-006-2006: Supply-air and return-air ducts and plenums must be insulated to a minimum installed level of R-6.0 or enclosed entirely in directly conditioned space as confirmed through field verification and diagnostic testing in accordance with the requirements of Reference Residential Appendix RA3.1.4.3.8. - Heat Pump Thermostat 12 A thermostat shall be installed that meets the requirements of Section 110.2(b) and Section 110.2(c). 13 The thermostat shall be installed in accordance with the manufacturers published installation specifications 14 First stage of heating shall be assigned to heat pump heating. 15 Second stage back up heating shall be set to come on only ~.~,~n the ind~or set temperature cann~t.~~,'Y'e!."ccr ,',: The responsible person signature on this complianc~,docum~ affirm~t~t ''' applicableorequitem~nts i~ thisi~1e have~¥., .f.!'·' Registration Number: 216-A0478383A-M0100002A-OOOO CA Building Energy Efficiency Standards -2013 Residential Compliance Registration Date/Time: 2016-12-28 15:50:18 Report Version: 2013 Rev 1.008 Schema Version: 2013.1.008 .. HERS Provider: CaiCERTS Report Generated: 2016-12-28 15:49:16 CERTIFICATE OF INSTALLATION CFZR-MCH-01-E Space Conditioning Systems, Ducts, and Fans (Page 7 of 7) Documentation Author's Declaration Statement 1. I certify that this Certificate of Installation documentation is accurate and complete. Documentation Author Name: Seth Woolson Documentation Author Signature: s~v~ Company: Signature Date: COASTAL REFRIGERATION HEATING & CONDITIONING 2016-12-28 15:50:18 Address: CEA/ HERS Certification Identification (if applicable): 6525 PASEO FRONTERA UNIT I City/State/Zip: Phone: CARLSBAD CA 92009 760-683-5683 X123 Responsible Person's Declaration statement I certify the following under penalty of perjury, under the laws of the State of California: 1. The information provided on this Certificate of Installation is true and correct. 2. I am eligible under Division 3 of the Business and Professions Code in the applicable classification to accept responsibility for the system design, construction, or installation of features, materials, components, or manufactured devices for the scope of work identified on this Certificate of Installation, and attest to the declarations in this statement (responsible builder/installer), otherwise I am an 3. 4. 5. authorized representative of the responsible builder/installer. . .. · :.'"' !!"·-'' .?· •.• · Cv The constructed or installed features, materials, comp~~nts or m~~ufactured t!e)ljces jt~ installati<~n;ljs:J~ntl!l~,? ~this ~rtifi~2! lnstallatioQco~,to ,1l.~·applicable codes and regulations, and the installation conforms to the requirements given on th1ans and Sf)_,ecificatioJ'IS'&PJlroved by the enf~ement l!g\rtJilY· .~ ''l~' ~ .)f. ·~ J. I reviewed a copy of the Certificate of Complian~rWd by the enf9{~;eJTi'IP~aJen~ that~~fi~~ll~Wefific fi!.quir+ents.f~~ wPpe of~Pntfuct~ Olti(l~lla~on identified on this Certificate of Installation, and I have ensured that the requiremeri~:apply to the c~nstruction or installation have been met.. . . ' .... ·. . . I will ensure that a registered copy of this Certificate of i~llation sh~ll be posted, or made available with the bu\!d4l8 permitJs) issued forthe l?uii.!Jing, .nd ma(:ie-available to the enforcement agency for all applicable inspections. I understand that a registered copy oft his Certificate of Installation is required to be included with the documentation the builder' provides to the building owner at occupancy. Responsible Builder/Installer Name: Responsible Builder/Installer Signature: s~v~ Seth Woolson Company Name: (Installing Subcontractor-or GeneraiContraC:tor or Builder/Ownerj COASTAL REFRIGERATION HEATING & CONDITIONING Address: 6525 PAS EO FRONTERA UNIT I Position With Company (Title): Owner CSLB License: 974929 City/State/Zip: Phone: 1 Date Signed: CARLSBAD CA 92009 760-683-5683 X123 12016-12-28 15:50:18 Digitally signed by CaiCERTS. This digital signature is provided in order to secure the content of this registered document and in no way implies Registration Provider responsibility for the accuracy of the information. Registration Number: 216-A0478383A-M0100002A-OOOO CA Building Energy Efficiency Standards -2013 Residential Compliance Registration Date/Time: 2016-12-28 15:50:18 Report Version: 2013 Rev 1.008 Schema Version: 2013.1.008 HERS Provider: CaiCERTS Report Generated: 2016-12-28 15:49:16 CERTIFICATE OF VERIFICATION CF3R-MCH-20-H Duct Leakage Diagnostic Test (Page 1 of 3) Project Name: SIESEL Enforcement Agency: City of Permit Number: on site Carlsbad Dwelling Address: 1702 Blackbird cir City: Carlsbad Zip Code: 92011 A. System Information 01 Space Conditioning System Identification or Name System 1 02 Space Conditioning System Location or Area Served location 1 03 Building Type from CF-1R Single family 04 Verified low Leakage Ducts in Conditioned Space No, credit is not taken (VLLDCS) Credit from CF1R? OS Verified Low Leakage Air Handling Unit (VLLAHU) Credit No, credit is not taken from CFlR? 06 Duct System Compliance Category Alteration using smoke test <'<7' ,, ,,,,,,, < ''"'"""', ,,,,,, ,'H' :,, c,'<, ""' 7 ;,), ,} <;)' r« l<, '* :J, ' ,,,, MCH-20e-Sealing All Acces~,~?li{!eaks J,i~,~ ~n~~~f:rftt~:,, ,, 1:~ 1''~ ''7< ~~ 1 ~ dx ~ '', o_) ,:''',,::':''! }l ,', ' B. Duct Leakage Diagnostic Test 01 Condenser Nominal Cooling Capacity (ton) 0 02 Heating Capacity (kBtu/h) 71 03 Conditioned Floor Area served by this HVAC system (ft2) 2400 04 Duct Leakage Test Condition Test final 05 Duct Leakage Test Method Total leakage 06 Leakage Factor 0.15 07 Air Handling Unit Airflow (AHUAirflow) Determination Heating system method Method 08 Measured AH UAirflow This field or section is not applicable 09 Calculated Target Allowable Duct Leakage Rate (cfm) 231 10 Actual duct leakage rate from leakage test measurement 749 (cfm) Registration Number: 216-A0478383A-M2000002A-M20A CA Building Energy Efficiency Standards 2013 Residential Compliance Registration Date/Time: 2016-12-28 16:56:47 HERS Provider: CaiCERTS Report Version: 2013 Rev 1.008 Report Generated: 2016-12-28 16:56:01 Schema Version: 2013.1.007 CERTIFICATE OF VERIFICATION CF3R-M CH-20-H Duct Leakage Diagnostic Test (Page 2 of 3) B. Duct leakage Diagnostic Test Compliance Statement: System passes using smoke test of an altered HVAC system in an existing building. No visible smoke exits the accessible portions of the duct system. Smoke is only emanating from air-handling unit (AHU) cabinet and non 11 accessible portions of the duct system. Note-Accessible is defined as having access thereto, but which first may require removal or opening of access panels, doors, or moving similar obstructions. If access to the ducts requires an object to be demolished or deconstructed then sealing of those ducts is not required 12 Notes: C. Additional Requirements for Compliance 01 System was tested in its normal operation condition. No temporary taping allowed. Outside air (OA) duct connections to the central forced air duct system shall not be sealed/taped off during duct leakage 02 testing. OA ducts used for Central Fan Integrated (CFI) Indoor Air Quality ventilation systems, or Central Fan Ventilation Cooling Systems, that utilize dampers that open only when OA is required and automatically close when OA is not required, may configure the OA damper to the closed position during duct leakage testing. 03 All supply and return register boots were sealed to the;drywall. i1J,< ,": ' ; ', ,, ,",,, <>' ,:'<, 04 Building cavities were not us:~ as plertfms or ~::fJfr~r~~rns in i!fY,,s,>f~H~~;' !;; 'F~,'41l~,;;;;, !~ i, 't ,,; 05 tf cloth backed tape was tised'Jt was co~~red'vJhh~a~ic ~Md>tlraJ'tictnd~~ ~; ::' \'; ~: :j I', ', ,;lili~t~ '' "' 06 ::;"~ ';' , t 2 "' ~ '":{ " ~\, fv>''4' f 1{ "; ) '\ ,}I Lt 1;: , £ All connection points between tne air hartdler andthe''stipply and retu'rn plenums are'completely sealed. t \ If the system complies using the Smoke Test method, the smoke test was conducted in accordance with the requirements 07 of Reference Residential Appendix RA3.1.4.3.6. Systems that comply using smoke test shall not be included in sample groups for HERS verification compliance. 08 verification Status: Pass-all applicable requirements are met 09 Correction Notes for this table: The responsible persons signature on this compliance document affirms that all applicable requirements in this table have been met unless otherwise noted in the Verification Status and the Corrections Notes in this table. D. Determination of HERS Verification Compliance All applicable sections of this document shall indicate compliance with the specified verification protocol requirements in order for this Certificate of Verification as a whole to be determined to be in compliance. 01 I Complies: All specified verification protocol requirements on this document are met. Registration Number: 216-A0478383A-M2000002A-M20A Registration Date/Time: 2016-12-28 16:56:47 HERS Provider: CaiCERTS CA Building Energy Efficiency Standards 2013 Residential Compliance Report Version: 2013 Rev 1.008 Schema Version: 2013.1.007 Report Generated: 2016-12-28 16:56:01 CERTIFICATE OF VERIFICATION CF3R-MCH-20-H Duct Leakage Diagnostic Test (Page 3 of 3) Documentation Author's Declaration Statement 1. I certify that this Certificate of Verification documentation is accurate and complete. Documentation Author Name: Documentation Author Signature: f~s~ Jason Solarez Company: Date Signed: Air-Tite Duct Testing 2016-12-28 16:56:47 Address: CEA/ HERS Certification Identification (if applicable): 2386 Warmlands Ave City/State/Zip: Phone: Vista CA 92084 760-231-9444 Responsible Person's Declaration statement 1 certify the following under penalty of perjury, under the laws of the State of California: 1. The information provided on this Certificate of Verification is true and correct. 2. I am the certified HERS Rater who performed the verification identified and reported on this Certificate of Verification (responsible rater). 3. The installed features, materials, components, manufactured devices, or system performance diagnostic results that require HERS verification identified on this Certificate of Verification comply with the applicable requirements in Reference Appendices RA2, RA3, and the requirements specified on the Certificate of Compliance for the building approved by the enforcement agency. 4. The information reported on applicable sectiQf!SIOf'the Certific~fe(s) pf~Wstallaptf'(CF~Rf· · ~~'~ubro:itte'tt by the per!9n(s) responsible for the construction or installation conforms to the ~quirements:s,p,eci(\f!d,jjh the Certifjcate(s lbf C liarite (C proved by:*he ~emejtltgency. 5. I w_ill ~nsure that a registered cdl)\'; of this C~ificate o~yerfa~n ~all be po'~~~r ila~ wit ilding pe~~it(~l iss~i!d ~r the bUild mg. and made ava1lab~,y> tl)~ enforcern~~. ~~e~};!~~ll lipphc~.\~J!JSI>i!}:J~~~· 1.. .. and ~at a r~ copy~ thfs; Certlflca.t9 .. of ~· Verification is required to be 111\llllcf~d with the documentation the buil~er provides. to tne building owner at occupfncy. · " · · I Builder Or Installer Information As Shown On The Certificate Of Installation Company Name (Installing Subcontractor, General Contractor, or Builder/Owner): COASTAL REFRIGERATION HEATING & CONDITIONING - Responsible Builder or Installer Name: CSLB License: Seth Woolson 974929 HERS Provider Data Registry Information Sample Group Number (if applicable): Dwelling Test Status in Sample Group (if applicable) Tested HERS Rater Information HERS Rater Company Name: Air-Tite Duct Testing Responsible Rater Name: Responsible Rater Signature: f~s~ Jason Solarez Responsible Rater Certification Number w/ this HERS Provider: Date Signed: CC2006013 2016-12-28 16:56:47 Digitally signed by GaiCERTS. This digital signature is provided it1 order to secure the content of this registered document and in no way implies Registration Provider responsibility for the accuracy of the information. Registration Number: 216-A0478383A-M2000002A-M20A CA Building Energy Efficiency Standards 2013 Residential Compliance Registration Date/Time: 2016-12-28 16:56:47 HERS Provider: CaiCERTS Report Version: 2013 Rev 1.008 Report Generated: 2016-12-28 16:56:01 Schema Version: 2013.1.007 CERTIFICATE OF COMPLIANCE CF1R-ALT-02-E Alterations to Space Conditioning Systems (formerly CF-1R-ALT-HVAC) (Page 1 of 3) Project Name: SIESEL Date Prepared: 2016-12-28 ----- A. General Information CFlR-ALT-02 is applicable to multiple space conditioning systems contained within a single dwelling unit. When multiple dwelling units must be documented, use one CFlR-ALT-02 document for each dwelling unit. 01 Project Name SIESEL 02 Date Prepared 2016-12-28 03 Project Location 1702 Blackbird cir 04 Building Type Single family OS CACity Carlsbad 06 Dwelling Unit Name SIESEL Dwelling Unit Conditioned 07 Zip Code 92011 08 Floor Area (ft2) 2400 Number of space conditioning 09 Climate Zone 7 10 (SC) systems in this dwelling 1 unit. ---------~ L__ ---~ --~ ------ B. Space Conditioning (SC) System Information ~·>---t,,, ~" ~--¥---F .-; --- .---~ ,--± 01 02 03 04~ "'f]o5 -06~-'"'\ -- 07 08 -" 09 10 ·-Is the sc'"'' -qlfistalllng a f''" .,,_,___ -----~ -~"-; -- SCSystem SCSystem CFA served system a d!frigerant --Jnstam.jg.:new sc InstalUng lnstalliltg 1nstalling 1-. ~--entirely new Identification or Location or Area bythisSC ducted containing system more than 40 entirely new Name Served System (ft2) system? component? components? feet of ducts? duct system? SC system? Alteration Type System 1 Location 1 2400 Yes No Yes No No No Altered space conditioning system ------~ ------- C. Extension of Existing Duct System, Greater Than 40 Feet (Section150.2(b)1Diib) This section does not apply to this project. Registration Number: 216-A0478383A-000000000-0000 Registration Date/Time: 2016-12-28 15:46:32 HERS Provider: CaiCERTS CA Building Energy Efficiency Standards-2013 Residential Compliance Report Version: 2013 Rev 1.008 Schema Version: 0.555SDD Report Generated: 2016-12-28 15:46:38 i CERTIFICATE OF COMPUANCE CFlR-ALT-02-E Alterations to Space Conditioning Systems (formerly CF-1R-ALT-HVAC) (Page 2 of 3) D. Altered Space Conditioning System (Sections 150.2(b)1E and F) 01 02 03 04 OS 06 07 08 09 10 11 12 Heating Cooling System Heating Altered Heating Minimum Altered Cooling Minimum Required New or Identification System Heating Efficiency Efficiency Cooling Cooling Efficiency Efficiency Thermostat Replaced New Duct or Name Type Components Type Value System Type Components Type Value Type Duct length R-Value Central gas All new Central split No cooling This field or This field or Less than or System 1 furnace heating AFUE 78 AC component section is not section is not Setback equal to 40 R-6 components altered applicable applicable feet R~:gyir~ QQ~;ym~:!lti!tiQ!J: CF2R-MCH-Ql-E-Space Conditioning Systems Ducts and Fans -Duct insulation requirement for new plenums: R6. CF2R-MCH-20-H & CF3R-MCH-20-H-Duct Leakage testing required when heating or cooling components are installed inducted systems, or when more than 40ft of duct length is replaced. -Leakage rate compliance:~ 15%. or~ 10% leakage to outside, or seal all accessible leaks. CF2R-MCH-2S-H & CF3R-MCH-25-H Refrigerant Charge Verification required when refrigerant containing components are installed or altered (applicable in CZ 2, 8-15). CF2RCF3R-MCH-23 & CF3R-MCH-23 Air Flow;:, 300 CFM/ton required when MCH-25 is required. Em:11ti2!l~- -Duct_ systems registered with HERS provider as previously sealed are_ exempt fr~~~&J;!~20 Duct LE!JkageJ~ r~(jukeme,ll~' . . . ·.; -Heatmg-<>nly systems and A~r Handler/Furnace changes do not requrre venficatl.iltt of Arr FIQw MCI:;{I-23,.t1t Refngetant Chatge MECH-25: '\~?: ~::r.t:~ tl·"' -Existing duct systems constructed. insulated or sealed with asbest~are exem~ from MCn:'_!~ifu·l~kage Testi~g requirements. "''" '~'~: :'1' ~1 !. ·~;l, ·, '> l! 'i'1 ~ '\•':r\f; pp.t ·>:->>•>' ••xmW %•· •RW •f%%' .:; \ '' E. Entirely New or Complete Replacement DuctR~em, wi~h pr Vfitho~Jt.,Equipment Changeout (Sections 1'5P.2(b)~Dii~ and.:~0.2(b)1E, F) '<·.: ' ' ¥' ·.:·· ·. ;. ' ' :·· .:.·;, This section does not apply to this project. ---· --·---· --· ----· -----· ---· ----· -· F. Entirely New or Complete Replacement Space Conditioning System (Section 150.2(b)1C) This section does not apply to this project. Registration Number: 216.tA0478383A-OOOOOOOOO-OOOO Registration Date/Time: 2016-12-28 15:46:32 HERS Provider: CaiCERTS CA Building Energy Efficiency Standards -2013 Residential Compliance Report Version: 2013 Rev 1.008 Schema Version: O.SSSSDD Report Generated: 2016-12-28 15:46:38 CERTIFICATE OF COMPUANCE CFlR-ALT-02-E Alterations to Space Conditioning Systems (formerly CF-lR-ALT-HVAC) (Page 3 of 3) Documentation Author's Declaration Statement 1. I certify that this Certificate of Compliance documentation is accurate and complete. Documentation Author Name: Documentation Author Signature: St!DtV~ Woolson, Seth Company: Signature Date: COASTAL REFRIGERATION_HEATING & CONDITIONING 2016-12-28 15:46:32 Address: CEA/ HERS Certification Identification (if applicable): 6525 PAS EO FRONTERA UNIT I City/State/Zip: Phone: CARLSBAD CA 92009 760-683-5683 X123 Responsible Person's Declaration statement I certify the following under penalty of perjury, under the laws of the State of California: 1. The information provided on this Certificate of Compliance is true and correct. 2. I am eligible under Division 3 ofthe Business and Professions Code to accept responsibility for the building design or system design identified on this Certificate of Compliance (responsible designer). 3. That the energy features and performance specifications, materials, components, and manufactur!!d d~vices for th.e buildi"' design Ptsvstem design identified on this Certificate of Compliance conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of ~kitlons. ' ~ · ,:~ · • • · .;· •:i: ~·:·· ~);'· "' .•• ,::•.·.: •:·~ 4. The building design features or system design features i.Qfntified o~his Certifitate:of Com@iance are~teq~'the i~or~.E'fPVided oriOt~aj)p~ca~ compliance documents, worksheets, calculations, plans and specifications submitted to ~he 6iifprcement••gency forlpprov.,!. with this building permit ap'f)jicatiQI\. ·:!'; :::: ·~: · .lll. 5. I will ensure that a registered copy of this Certificlti'W ~pliance sft:a~be'madeavailable With:-b.itll!ting ~mit{i) issu~ for-fiil<(llg, and,\,aciit avalfabre•to.the':enforcement agency for all applicable inspections. I understand that a registered copy of thi~-cate of Compliance. is. required to be included yvith the,docum!lntption the. bdll9er p~)lides tp..the b~W.ing owner at occupancy. Responsible Designer Name: "\, l Responsible Designer Si~afure: '~. saiv~ Woolson, Seth Company: Date Signed: COASTAL REFRIGERATION_HEATING & CONDITIONING 2016-12-2815:46:32 Address: license: 6525 PASEO FRONTERA UNIT I 974929 City/State/Zip: Phone: CARLSBAD CA 92009 760-683-5683 X123 Digitally signed by Ca/CERT$. This digital signature is provided in order to secure the content of this registered document and in no way implies Registration Provider responsibility for the accuracy of the information. Registration Number: 216-A0478383A-OOOOOOOOO-OOOO CA Building Energy Efficiency Standards -2013 Residential Compliance Registration Date/Time: 2016-12-28 15:46:32 Report Version: 2013 Rev 1.008 Schema Version: 0.555SDD HERS Provider: CaiCERTS Report Generated: 2016-12-28 15:46:38