Loading...
HomeMy WebLinkAbout1769 BLACKBIRD CIR; ; CB152220; Permit07-16-2015 City of Carlsbad 1635 Faraday Av Carlsbad, CA 92008 Plumbing/Mechanical/Electrical (PME) Permit Permit No: CB 152220 Building Inspection Request Line (760) 602-2725 Job Acidress: Permit Type: Parcel No: Reference #: PC #: Project Title; 1769 BLACKBIRD CR CBAD PME 2156023600 Lot #: WILLIAMS RES - REPLACE FAU, INSTALL NEW A/C, GROUND MOUNTED Status: Applied: Entered By: Plan Approved: Issued: Inspect Area: ISSUED 07/16/2015 SLE 07/16/2015 07/16/2015 Applicant: AIR PLUS MECHANICAL STE 103-507 4203 GENESSEE AV SAN DIEGO CA 92117 858-220-3322 Owner: WILLIAMS REVOCABLE LIVING TRUST 01-29-98 1769 BLACKBIRD CIR CARLSBAD CA 92011 Plumbing Fees Electrical Fees Mechanical Fees Other PME Fees $0.00 $0.00 $160.00 $0.00 TOTAL PERMIT FEES $160.00 Total Fees: $160.00 Total Paynnents To Date: $160.00 Balance Due: $0.00 Inspector: /^txXi^l FINAL APPROVAL Date: ^'V'^t/^^ Clearance: NOTICE: Please take NOTICE that approval of your project includes the "Imposition" of fees, dedications, reservations, or other exactions hereafter collectively referred to as "fees/exactions." You have 90 days from the date this pemiit was issued to protest imposition of these fees/exactions. If you protest them, you must follow the protest procedures set forth in Govemment Code Section 66020(a), and file the protest and any other required information with the City Manager for processing in accordance with Carlsbad Municipal Code Section 3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack, review, set aside, void, or annul their imposition. You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection fees and capacity changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this project. NOR DOES IT APPLY to any fees/exactions of whieh vou have previouslv been given a NOTICE similar to this, or as to which the statute of limitations has previouslv othenwise expired. THE FOLLOWING APPROVALS REQUIRED PRIOR TO PERMIT ISSUANCE: QPLANNING nENGINEERING nBUILDING OFIRE DHEALTH nHAZMAT/APCD ^0»: Ccityof Carlsbad Building Permit Appiication 1635 Faraday Ave., Carlsbad, CA 92008 Ph: 760-602-2719 Fax:760-602-8558 email: building(gcarlsbadca.gov www.carlsbadca.gov Plan Check No.(y>) t^Q 2-2.2JD Est. Value Plan Ck. Deposit Date-1-iU-l€ SWPPP JOB ADDRESS ,.^.^ SUITE*/SPACE«/UNIT# APN CT/PROJECT # LOT# PHASES # OF UNITS # BEDROOMS # BATHROOMS TENANT BUSINESS NAM E jCONSTR.TYPE OCC. GROUP DESCRIPTION OF WORK: Include Square Feet of Alfected Area(s) , EXISTING USE PROPOSED USE GARAGE (SF) PATIOS (SF) DECKS (SF) FIREPLACE AIRCONDITIONING FIRESPRINKLERS YESQ# Noj 1 YESI^NOQ YES] | N0| | APPLICANTNAME j / - . J J. , >t Primary Contact SM/LlQ {/6 PROPERTYOWNER ^^^^^ ^,^^^^ ADDRESS , ' , . /2/5 k. sr/if^BT. J'^'fh. (^ui6/2^ ADDRESS CITY ' STATE ^ ZIP ^ CITY , ^ STATE . ZIP _ PHONE, . -FAX ' PHONE , , EMAIL / J /\ EMAIL DESIGN PifOFESSIONAL CONTRACTOR BUS. NAME^/^ ^^^^ ^^y^^^ COOLW6 ADDRESS ADDRESS ^^^y C//^S^^e/fi^^ IPA . JTZ^. CITY STATE ZIP CITY ^ ^ , ^ ^ ^ STATE ZIP „ PHONE FAX FAX EMAIL STATE LIC. # STATE LIC.# , , , _ CLASS CITY BUS. LIC.# . applicant for suoh permit to file a signed statement that he is licensed pursuant to the provisions of the Contractor's License Law ICnapter 9, commending with Section 7000 of Division 3 of the Business and Professions Code) or that he is exempt therefrom, and the basis for the alleged exemption. Any violation of Section 7031.5 by any applicant for a permit subjects the applicant to a civil penalty of not more than five hundred dollars ($500)). •MM K.ffR J ' C O «t P g N S A f-I Workers' Compensation Declaration: / hereby affinn under penalty of perjury one ofthe foiiowing deciarations: • I hayft«fRl will maintain a certificate of consent to self.insure for workers' compensation as provided by Section 3700 of the Labor Code, tor the perfomiance of the worii for which this pemilt Is issued. I^nhaveand will maintain workers' compensation, as required bv Section 370Qof the Labor Code, forthe perfomiance of the worii tor whichjiis permit Is Issued. My workers' compensation insurant carrier and policy number are: Insurance Co.. Policy No. _ Expiration Date _ Thjs section need not be completed if the permit Is for one hundred doiiars ($1 OOf or less!^^ ^^^^OZ(- //J^ . I I Certificate of Exemption: I certify that in the perfomiance of the worii for which this pemnit Is issued, I shall not employ any person in any manner so as to become subject to the Workers' Compensation Laws of Califomia. WARNING: Failure to secure workers' compensatioi^cou^ge is unlawful, and shall subject an employer to criminal penalties and civil fines up to one hundred thousand dollars (£100,000), in aririifinn tn tha i-nrt nf i-nmpencatinn riamaf|»c ac prnuiricri fnrih SiHinn yjtjf the I g[)pr rnric interact anri aHf\mBY'« f»P<; I I ^eS" CONTRACTOR SIGNATURE .^=5^ |2*GENT DATE 7//^ /^-^ NER-aUILDER DECLARATIO / hereby affm that t am exempt from Contractor's Ucense Law for the foiiomng reason: I I I, as owner of the property or my employees with wages as their sole compensation, will do the worii and the structure is not intended or offered for sale (Sec. 7044, Business and Professions Code: The Contractor's License Law does not appiy to an owner of property who builds or improves thereon, and who does such work himself or through his own employees, provided that such improvements are not intended or offered for sale. If, however, the buiiding or improvement Is sold within one year of completion, the owner-builder will have the burden of proving that he did not build or Improve for the purpose of sale). I I I, as owner of the praperty, am exclusively contracting with licensed contractors to constnict the project (Sec. 7044, Business and Professions Code: The Contractor's License Law does not apply to an owner of praperty who builds or improves thereon, and contracts for such projects with contractor(s) licensed pursuant to the Contractor's License Law). I [ I am exempt under Section ^ _Business and Professions Code for this reason: 1.1 personally plan to provide the major labor and materials for construction of the proposed property improvement. I lYes •NO 2.1 (have / have not) signed an application for a building pemiit for the praposed work. 3.1 have contracted with the following person (fimi) to pravide the praposed constmction (include name address / phone / contractors' license number): 4.1 plan to pravide portions of the worii, but I have hired the following person to coordinate, supervise and pravide the major worii (include name / address / phone / contractors' license number): 5.1 will pravide some of Ihe worti, but I have contracted (hired) the following persons to pravide the worti indicated (include name / address / phone / type of worii): >€S'PR0PERTY OWNER SIGNATURE QAGENT DATE COMPLETE THIS S E C Tl O N I«i3ii M IIW*^^^ BUiLDING P E R M i$f OfifiY Is the applicant or future building occupant required to submit a business plan, acutely hazanjous materials registration form or risk management and prevention program under Sections 25505,25533 or 25534 of the Presley-Tanner HazanJous Substance Account Act? Yes No Is the applicant or futuro buiiding occupant required to obtain a pemilt fram the air pollution control district or air quality management district? Yes No Is the facility to be constnicted within 1,000 feet of the outer boundary of a school site? Yes No IF ANY OF THE ANSWERS ARE YES, A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR IS MEETING THE REQUIREMENTS OF THE OFFICE OF EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT. CONSTRUCTION LENDING AGSNCY 1 hereby aflirm that there is a construction lending agency for the performance of the work this pennit i Lender's Name Lender's Address 3 Issued (Sec. 3097 (i) Civil Code). APPLICANT CE»TiF|cATI ON I certif that I have read the applkatkin and state that the above infbmiation is conect and that the Intbrniation on the plans Is accurate. I agiee to comply witti all Ci^ ordinances and State laws relating to bulldlng constnictkin. I hereby auihorize representative of the City of Carisbad to enter upon the above mentioned property for inspectbn purposes. I ALSO AGREE TO SAVE, INDEMNIFY AND KEEP HARMLESS THE CITY OF CARLSBAD AGAINST AU. LIABILITIES, JUDGMENTS, COSTS AND EXPENSES WHICH MAY IN ANY WAY ACCRUE AGAINST SAID CITY IN CONSEQUENCE OF THE GRANTING OF THIS PERMfT. OSHA: An OSHA pemiit is required for excavations over 5'0' deep and damollitton or constmctbn of stmctures over 3 stories in heght. EXPIRATION: Every permit Issued by the BuiUing Official under the prawns of this Code shall expire by limitation and become null and void if the buikling or worti authorized by such pemiit is not commenced within 180 days from the date of such pemiit or if the buikting or vwrii auttigj^l/by sy^^gsj^ fesgspBHded or abandoned at any time after the worti Is commenced for a periody<f 180 days (Sictbn 106.4.4 Unifomi Buikling Code). APPLICANT'S SIGNATURE DATE ^^.^ STOP: THIS SECTION NOT REQUIRED FOR BUILDING PERMIT ISSUANCE. Complete the following ONLY if a Certificate of Occupancy will be requested at final inspection. Fax (760) 602-8560, Email buildinQ(5)carlsbadca.Q0V or Mail the completed form to City of Carlsbad, Building Division 1635 Faraday Avenue, Carlsbad, Califomia 92008. C0#: (Office Use Only) CONTACT NAME OCCUPANT NAME ADDRESS BUILDING ADDRESS CITY STATE ZIP CITY STATE ZIP Carlsbad CA PHONE FAX EMAIL OCCUPANT'S BUS. LIC. No. DELIVERY OPTIONS PICK UP: CONTACT (Listed above) OCCUPANT (Listed above) CONTRACTOR (On Pg. 1) MAILTO: CONTACT (Listed above) OCCUPANT (Listed above) CONTRACTOR (On Pg. 1) IVIAIL / FAX TO OTHER: ASSOCIATED CB# NO CHANGE IN USE / NO CONSTRUCTION CHANGE OF USE / NO CONSTRUCTION ASSOCIATED CB# NO CHANGE IN USE / NO CONSTRUCTION CHANGE OF USE / NO CONSTRUCTION ^APPLICANT'S SIGNATURE DATE Inspection List Permit#: CB152220 Type: PME WILLIAMS RES - REPLACE FAU, INSTALL NEW A/C, GROUND MOUNTED Date Inspection Item Inspector Act Comments 09/01/2015 43 AirCond/Furnace Set - Rl 09/01/2015 43 AirCond/Furnace Set MC AP 09/01/2015 49 FinalMechanical - Rl 09/01/2015 49 FinalMechanical MC Fl Tuesday, September 01, 2015 Page 1 of 1 # # # CERTIFICATE OF COMPLIANCE CF1R-ALT-02-E Alterations to Space Conditioning Systems (formerly CF-IR-ALT-HVAC) (Page 1 of 3 ) Project Name: Williams Date Prepared: 2015-07-14 A. General Information CFlR-ALT-02 is applicable to multiple space conditioning systems contained within a single dweiling unit. When multiple dwelling units must be documented, use one CFlR-ALT-02 document for each dwelling unit. 01 Project Name Williams 02 Date Prepared 2015-07-14 03 Project Location 1769 Blackbird Circle 04 Building Type Single family 05 CA City Carlsbad 06 Dwelling Unit Name Williams 07 Zip Code 92011 08 Dwelling Unit Conditioned Floor Area (ft2) 2250 09 Climate Zone 7 10 Number of space conditioning (SC) systems in this dwelling unit. 1 B. Space Conditioning (SC) System Information 01 02 03 04 05 06 07 08 09 10 SC System Identification or Name SC System Location or Area Served CFA served by this SC System (ft2) Is these system a ducted system? Installing a refrigerant containing component? Installing new SC system components? instaHing more than 40 feet of ducts? Installing entirely new duct system? Installing entirely new SC system? Alteration Type System 1 Whole House 2250 Yes Yes Yes No No No Altered space conditioning system C. Extension of Existing Duct System, Greater Than 40 Feet (Sectionl50.2(b)lDiib) This section does not apply to this project. Registration Number: 215-A0193193A-000000000-0000 CA Building Energy Efficiency Standards - 2013 Residential Compliance Registration Date/Time: 2015-07-14 16:32:03 Report Version; 2014-03-31 Schema Version; 0.555SDD HERS Provider: CalCERTS Report Generated; 2015-07-14 16;32;31 CERTIFICATE OF COMPLIANCE CF1R-ALT-02-E Alterations to Space Conditioning Systems (formerly CF-IR-ALT-HVAC) (Page 2 of 3 ) D. Altered Space Conditioning System (Sections 150.Z(b)lE and F) 01 02 03 04 05 06 07 08 09 10 11 12 System Identification or Name Heating System Type Altered Heating Components Heating Efficiency Type Heating Minimum Efficiency Value Cooling System Type Altered Cooling Components Cooling Efficiency Type Cooling Minimum Efficiency Value Required Thermostat Type New or Replaced Duct Length New Duct R-Value System 1 Central gas furnace All new heating components AFUE 80 Central split AC All new cooling components SEER 14 Setback Less than or equal to 40 feet R-6 Reauired Docunnentation: CF2R-MCH-01-E - Space Conditioning Systems Ducts and Fans -Duct insulation requirement for new plenums: R6. CF2R-MCH-20-H & CF3R-MCH-20-H - Duct Leakage testing required when heating or cooling components are installed in ducted systems, or when more than 40 ft of duct length is replaced. -Leakage rate compliance: < 15%, or < 10% leakage to outside, or seal all accessible leaks. CF2R-MCH-25-H & CF3R-MCH-25-H Refrigerant Charge Verification required when refrigerant containing components are installed or altered (applicable in CZ 2, 8-15). CF2RCF3R-MCH-23 & CF3R-MCH-23 Air Flow 2 300 CFM/ton required when MCH-25 is required. Exceptions: -Duct systems registered with HERS provider as previously sealed are exempt from MCH-20 Duct Leakage Testing requirements. -Heating-only systems and Air Handler/Furnace changes do not require verification of Air Flow IVICH-23, or Refrigerarrt Charge MECH-2S. -Existing duct systems constructed, insulated or sealed with asbestos are exempt from MGH-20 Duct Leakage Testing requirements. E. Entirely New or Complete Replacement Duct System, with or without Equipment Changeout (Sections 150.2(b)lDiia and 150.2(b)lE, F) This section does not apply to this project. F. Entirely New or Complete Replacement Space Conditioning System (Section 150.2(b)lC) This section does not apply to this project. Registration Number; 215-A0193193A-000000000-0000 CA Building Energy Efficiency Standards - 2013 Residential Compliance Registration Date/Time; 2015-07-14 16:32:03 Report Version: 2014-03-31 Schema Version: 0.555SDD HERS Provider: CalCERTS Report Generated; 2015-07-14 16;32;31 CERTIFICATE OF COMPLiANCE CF1R-ALT-02-E Alterations to Space Conditioning Systems (formerly CF-IR-ALT-HVAC) (Page 3 of 3) Documentation Author's Declaration Statement 1.1 certify that this Certificate of Compliance documentation is accurate and complete. Documentation Author Name: Warner, Kim Documentation Author Signature: (~IP /^Jt Company: AIR PLUS MECHANICAL INC Signature Date: 2015-07-14 16:32:03 Address: 4203 GENESEE AVE STE 103#507 CEA/ HERS Certification Identification (if applicable): 616223 City/State/Zip: SAN DIEGO CA 92117 Phone: (858) 505-8711 Responsible Person's Declaration statement 1 certify the following under penalty of perjury, under the laws of the State of California: 1. The information provided on this Certificate of Compliance Is true and correct. 2. 1 am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design or system design identified on this Certificate of Compliance (responsible designer). 3. That the energy features and performance specifications, materials, components, and manufactured devices for the building design or system design identified on this Certificate of Compliance conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of Regulations. 4. The building design features or system design features identified on this Certificate of Compliance are consistent with the information provided ort other applicable compliance documents, worksheets, calculations, plans and specifications submitted to the enforcement agency for approvai with this building permit application. 5. 1 will ensure that a registered copy of this Certificate of Connpliance shall be made available with the buitding permit(s) issued for the tniilding, and made avaitable to the enforcement agency for all applicable inspections. 1 understand that a registered copy of this Certificate of Compliance is required to be included with the documentation the builder provides to the building owner at occupancy. Responsible Designer Name: Warner, Kim Responsible Designer Signature: (~-rp ,, Company : AIR PLUS MECHANICAL INC Date Signed: 2015-07-14 16:32:03 Address: 4203 GENESEE AVE STE 103#507 License: 616223 City/State/Zip: SAN DIEGO CA 92117 Phone: (858) 505-8711 Digitally signed by CalCEflTS. This digital signature is provided in order to secure the content of this registered document, and in no way implies Registration Provider responsitiility for the accuracy of the information. Registration Number; 21S-A0193193A-000000000-0000 CA Building Energy Efficiency Standards - 2013 Residential Compliance Registration Date/Time; 2015-07-14 16:32:03 Report Version; 2014-03-31 Schema Version; 0.555SDD HERS Provider: CalCERTS Report Generated; 2015-07-14 16;32;31 m CERTIFICATE OF INSTALLATION CF2R-MCH-01-E Space Conditioning Systems, Ducts, and Fans (Page 1 of 7) Project Name: Williams Enforcement Agency: City of Carlsbad Permit Number: PENDING Dwelling Address: 1769 Blackbird Cirde City: Cartsbad Zip Code: 92011 A. General Information 01 Dwelling Unit Name Williams 02 Climate Zone 7 03 Dwelling Unit Conditioned Floor Area (ft2) 2250 04 Number of space conditioning (SC) systems being altered in this dwelling unit. 1 05 Certificate of Compliance Type Prescriptive alterations (CFIR-ALT) 06 Method used to calculate HVAC loads NotApplicableEquipmentChangeout 07 Calculated dwelling unit Sensible Cooling Load (Btuh) This field or section is not applicable 08 Calculated Dwelling Unit Heating Load (Btuh) This field or section is not applicable IVICH-Olb Prescriptive Alterations - Space Conditioning Systems Ducts and Fans B. Space Conditioning (SC) System Information 01 02 03 04 OS 06 07 08 09 10 SC System Identification or Name SC System Location or Area Served CFA served by this SC System (ft2) Is the SC system a ducted system? Installing a refrigerant containing component? installing new SC system components? Installing more than 40 feet of ducts? installing entirely new duct system? Installing entirely new SC system? Alteration Type System 1 Whole House 2250 Yes Yes Yes No No No Altered space conditioning system Registration Number; 215-A0193193A-M0100002A-0000 CA Building Energy Efficiency Standards - 2013 Residential Compliance Registration Date/Time: 2015-07-21 14:25:53 Report Version: 2014-05-13 Schema Version; 0.555SDD HERS Provider: CalCERTS Report Generated: 2015-07-20 15:54:03 CERTIFICATE OF INSTALLATION CF2R-MCH-01-E Space Conditioning Systems, Ducts, and Fans (Page 2 of 7 ) C. Space Conditioning (SC) System Alterations Compliance Information 01 02 03 04 05 06 07 08 09 10 11 12 13 System Identification or Name Heating System Type Altered Heating Component Heating Efficiency Type Heating Minimum Efficiency Value Cooling System Type Altered Cooling Component Cooling Efficiency Type Cooling Minimum Efficiency Value Required Thermostat Type New or Replaced Duct Length New Duct R-Value Central Fan Integrated (CFI) Ventilation System Status System 1 Central gas furnace All new heating componen ts AFUE 80 Central splitAC All new cooling components SEER 14 Setback N/A - no ducts replaced This field or sectio n is not applic able Not a CFI system D. Installed IHeating Equipment information 01 02 03 04 05 06 07 System Identification or Name Heating Efficiency Type Heating Efficiency Value Heating Unit Manufacturer Heating Unit Model Number Heating Unit serial number Rated Heating Capacity, Output (BTUH) System 1 AFUE 80 Trane TUD2C100A9V5VB B 15243W3L1G 80000 Notes: Registration Number: 215-A0193193A-M0100002A-0000 CA Building Energy Efficiency Standards - 2013 Residential Compliance Registration Date/Time: 2015-07-21 14:25:53 Report Version; 2014-05-13 Schema Version; 0.555SDD HERS Provider; CalCERTS Report Generated; 2015-07-20 15:54:03 CERTIFICATE OF INSTALLATION CF2R-MCH-01-E Space Conditioning Systems, Ducts, and Fans (Page 3 of 7 ) E. Installed Cooling Equipment information: 01 02 03 04 05 06 07 08 Condenser or Package Unit System Identification or Name Cooling Efficiency Type Cooling Efficiency Value Condenser or Pacl(age Unit Manufacturer Condenser or Package Unit Model Number Condenser or Package Unit Serial Number System Rated Cooling Capacity at Design Conditions (BTUH) Condenser Rated Nominal Capacity (ton) System 1 SEER 14 ICP NH4A448AKA1 00 X1S1790107 48000 4 Notes; F. Extension of Existing Duct System, Greater Than 40 Feet This section does not apply to this project. G. Installed Duct System information This section does not apply to this project. H. Installed Air Filter Device Information This section does not apply to this project. I. Air Filter Device Requirements This section does not apply to this project. Registration Number; 215-A0193193A-M0100002A-0000 CA Building Energy Efficiency Standards - 2013 Residential Connpliance Registration Date/Time: 2015-07-21 14:25:53 Report Version; 2014-05-13 Schema Version; 0.555SDD HERS Provider: CalCERTS Report Generated; 2015-07-20 15:54:03 CERTIFICATE OF INSTALLATION CF2R-MCH-01-E Space Conditioning Systems, Ducts, and Fans (Page 4 of 7 ) J. HERS Verification Requirements 01 02 03 04 05 06 07 08 09 10 MCH20 MCH21 MCH22 MCH23 MCH25 MCH28 SC System Identification or Name SC System Location or Area Served Exemption From Duct Leakage Requirements Duct Leakage Test Exemption from Minimum R-Value for Ducts In Conditioned Space Ducts Located In Cond Space Verification AHU Fan Efficacy (W per cfm) AHU Airflow Rate (cfm per ton) Refrigerant Charge Return Duct Design Table 150.0-C or D System 1 Whole House No exemptions Yes Not applicable No No No No No Registration Number: 215-A0193193A-M0100002A-0000 CA Building Energy Efficiency Standards - 2013 Residential Compliance Registration Date/Time: 2015-07-21 14:25:53 Report Version; 2014-05-13 Schema Version; 0.555SDD HERS Provider: CalCERTS Report Generated; 2015-07-20 15:54:03 CERTIFICATE OF INSTALLATION CF2R-MCH-01-E Space Conditioning Systems, Ducts, and Fans (Page 5 of 7 ) K. Space Conditioning Systems, Ducts and Fans Mandatory Requirements and Additional Measures Note; Additional mandatory requirements from Section 150.0 that are not iisted here may be applicable to some systems. These requirements may be applicable to only newly installed equipment or portions of the system that are altered. Existing equipment may be exempt from these requirements. Heating Equipment 01 Equipment Efficiency: All heating equipment must meet the minimum efficiency requirements of Section 110.1 and Section 110.2(a) and the Appliance Efficiency Regulations. 02 Controls: All unitary heating systems, including heat pumps, must be controlled by a setback thermostat. These thermostats must be capable of allowing the occupant to program the temperature set points for at least four different periods in 24 hours. See Sections 150.0(1), 110.2(b). 03 Sizing: Heating load calculations must be done on portions of the building served by new heating systems to prevent inadvertent undersizing or oversizing. See sections 150.0(h)land 2). 04 Furnace Temperature Rise: Central forced-air heating furnace installations must be configured to operate at or below the furnace manufacturer's maximum inlet-to-outlet temperature rise specification. See Section 15G.0(h)4. 05 Standby Losses and Pilot Lights: Fan-type central furnaces may not have a continuously burning pilot light. Section 110.5 and Section 110.2(d). Cooling Equipment 06 Equipment Efficiency: All cooling equipment must meet the minimum efficiency requirements of Section 110.1 and Section 110.2(a) and the Appliance Efficiency Regulations. 07 Refrigerant Line Insulation: All refrigerant line insulation in split system air conditioners and heat pumps must meet the R-value and protection requirements of Section 150.0(j)2 and 3, and Section 150.0(m)9. 08 Condensing Unit Location: Condensing units shall not be placed within five (5) feet of a dryer vent outlet. See Section 150.0(h)3A. 09 Sizing: Cooling load calculations must be done on portions ofthe building served by new cooling systems to prevent inadvertent undersizing or oversizing. See Section 150.0(h)land 2. Air Distribution System Ducts, Plenums and Fans 10 Insulation: In all cases, unless ducts are enclosed entirely in directly conditioned space, the minimum duct insulation value is R-6. Note that higher values may be required by the prescriptive or performance requirements. See Section 150.0(m)l. Registration Number; 215-A0193193A-M0100002A-0000 Registration Date/Time: 2015-07-21 14.25:53 HERS Provider: CalCERTS CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version; 2014-05-13 Report Generated; 2015-07-20 15:54:03 Schema Version; 0.555SDD CERTIFICATE OF INSTALLATION CF2R-MCH-01-E Space Conditioning Systems, Ducts, and Fans (Page 6 of 7 ) K. Space Conditioning Systems, Ducts and Fans Mandatory Requirements and Additional Measures Note: Additional mandatory requirements from Section 150.0 that are not listed here may be applicable to some systems. These requirements may be applicable to only newly installed equipment or portions of the system that are altered. Existing equipment may be exempt from these requirements. 11 Connections and Closures: All installed air-distribution system ducts and plenums must be, sealed and insulated to meet the requirements of CMC Sections 601.0, 602.0, 603.0, 604.0, 605.0 and ANSI/SMACNA-006-2006: Supply-air and return-air ducts and plenums must be insulated to a minimum installed level of R-6.0 or enclosed entirely in directly conditioned space as confirmed through field verification and diagnostic testing in accordance with the requirements of Reference Residential Appendix RAB.1.4.3.8. Heat Pump Thermostat 12 A thermostat shall be installed that meets the requirements of Section 110.2(b) and Section 110.2(c). 13 The thermostat shall be installed in accordance with the manufacturers published installation specifications 14 First stage of heating shall be assigned to heat pump heating. 15 Second stage back up heating shall be set to come on only when the indoor set temperature cannot be met. The responsible person signature on this compliance document affirms that all applicable requirements in this table have been met. Registration Number; 215-A0193193A-M0100002A-0000 Registration Date/Time; 2015-07-21 14:25:53 HERS Provider: CalCERTS CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version; 2014-05-13 Report Generated: 2015-07-20 15:54:03 Schema Version; 0.555SDD CERTIFICATE OF INSTALLATION CF2R-MCH-01-E Space Conditioning Systems, Ducts, and Fans (Page 7 of 7 ) Documentation Author's Declaration Statement 1.1 certify that this Certificate of Installation documentation is accurate and complete. Documentation Author Name: Edgar, Bruce Documentation Author Signature: - Company: The Energuy CA LLC Signature Date: 2015-07-20 15:55:40 Address: 1215 K St., 17th Floor CEA/ HERS Certification Identification (if applicable): CC2006305 City/State/Zip: Sacramento CA 95814 Phone: 1-877-600-0123 Responsible Person's Declaration statement 1 certify the following under penalty of perjury, under the laws of the State of California: 1. The information provided on this Certificate of Installation is true and correct. 2. lam eligible under Division 3 of the Business and Professions Code in the applicable classification to accept responsibility for the system design, construction, or installation of features, materials, components, or manufactured devices for the scope of worl< identified on this Certificate of Installation, and attest to the declarations in this statement (responsible builder/installer), otherwise 1 am an authorized representative of the responsible builder/installer. 3. The constructed or installed features, materials, components or manufactured devices (the installation) identified on this Certificate of Installation conforrra to atl applicable codes and regulations, and the installation conforms to the requirements given on the plans and specifications approved by the enforcement agency. 4. 1 reviewed a copy of the Certificate of Compliance approved by the enforcement a|^ney that identifies the specific requirements for tlie scope of construction or installation identified on this Certificate of Installation, and 1 have ensured that the requirements that apply to the construction or installation have been met. 5. 1 will ensure that a registered copy of this Certificate of Inrtallation shall be posted, or made available with the buiWing permit(s) issued forthe building, and made available to the enforcement agency for all applicable inspections. 1 understand that a registered copy of this Certificate of Installation is required to be included with the documentation the builder provides to the building owner at occupancy. Responsible Builder/Installer Name: Warner, Kim Responsible Builder/Installer Signature: ^ n Company Name: (Installing Subcontractor or General Contractor or Builder/Owner) AIR PLUS MECHANICAL INC Position With Company (Title): Manager Address: 4203 GENESEE AVE STE 103#507 CSLB License: 616223 City/State/Zip: SAN DIEGO CA 92117 Phone: Date Signed: (858)505-8711 2015-07-21 14:25:53 Digitally signed by CalCERTS. This digital signature is provided in order to secure the content of this registered document, and in no way implies Registration Provider responsibility for the accuracy of the information. Registration Number: 215-A0193193A-M0100002A-0000 CA Building Energy Efficiency Standards - 2013 Residential Compliance Registration Date/Time: 2015-07-21 14:25:53 Report Version; 2014-05-13 Schema Version; 0.555SDD HERS Provider; CalCERTS Report Generated; 2015-07-20 15:54:03 CERTIFICATE OF INSTALLATION CF2R-MCH-20-H Duct Leakage Diagnostic Test (Page 1 of 3) ^ Project Name: Williams Enforcement Agency: Carlsbad City of Permit Number: PENDING Dwelling Address: 1769 Blackbird Circle City: Carlsbad Zip Code: 92011 A. System Information 01 Space Conditioning System Identification or Name System 1 02 Space Conditioning System Location or Area Served Whole House 03 Building Type from CF-IR Single family 04 Verified Low Leakage Ducts in Conditioned Space (VLLDCS) Credit from CFIR? No, credit is not taken 05 Verified Low Leakage Air Handling Unit (VLLAHU) Credit from CFIR? No, credit is not taken 06 Duct System Compliance Category Alteration using smoke test MCH-20e - Sealing All Accessibte Leaks using Smolie Test rB, Duct Leakage Diagnostic Test 01 Condenser Nominal Cooling Capacity (ton) 4 02 Heating Capacity (kBtu/h) 80 03 Conditioned Floor Area served by this HVAC system (ft2) 2250 04 Duct Leakage Test Condition Test final 05 Duct Leakage Test Method Total leakage 06 Leakage Factor 0.15 07 Air Handling Unit Airflow (AHUAirflow) Determination Method Heating system method 08 Measured AHUAirflow This field or section is not applicable 09 Calculated Target Allowable Duct Leakage (cfm) 260 10 Actual duct leakage rate from leakage test measurement (cfm) 351 1" Compliance Statement: System passes using smoke test of an altered HVAC system in an existing building. No visible smoke exits the accessible portions ofthe duct system. Smoke is only emanating from air-handling unit (AHU) cabinet and non accessible portions of the duct system. Note - Accessible is defined as having access thereto, but which first may require Registration Number: 215-A0193193A-M2000002A-0000 Registration Date/Time: 2015-07-21 14:25:53 HERS Provider; CalCERTS CA Building Energy Efficiency Standards Report Version; 2014-05-08 Report Generated: 2015-07-20 15:54:42 2013 Residential Compliance Schema Version; O.SISDD CERTIFICATE OF INSTALLATION CF2R-MCH-20-H Duct Leakage Diagnostic Test (Page 2 of 3) B. Duct Leakage Diagnostic Test removal or opening of access panels, doors, or moving similar obstructions. If access to the ducts requires an object to be demolished or deconstructed then sealing of those ducts is not required C. Additional Requirements for Compliance 01 System was tested in its normal operation condition. No temporary taping allowed. 02 Outside air (OA) ducts for Central Fan Integrated (CFI) ventilation systems, shall not be sealed/taped off during duct leakage testing. CFI OA ducts that utilize controlled motorized dampers, that open only when OA ventilation is required to meet ASHRAE Standard 62.2, and close when OA ventilation is not required, may be configured to the closed position during duct leakage testing. 03 All supply and return register boots were sealed to the drywall. 04 Building cavities were not used as plenums or platform returns in lieu of ducts. 05 If cloth backed tape was used it was covered with Mastic and draw bands. 06 All connection points between the air handler and the supply and return plenums are completely sealed. 07 1 If the system complies using the Smoke Test method, the smoke test was conducted in accordance with the requirements of Reference Residential Appendix RAS.1.4.3.6. Systems that comply using smoke test shall not be included in sample groups for HERS verification compliance. The responsible persons signature on this compliance document affirms that all applicable requirements in this table have been met. Registration Number; 215-A0193193A-M2000002A-0000 Registration Date/Time; 2015-07-21 14:25:53 HERS Provider; CalCERTS CA Building Energy Efficiency Standards Report Version; 2014-05-08 Report Generated: 2015-07-20 15:54:42 2013 Residential Compliance Schema Version: O.SISDD CERTIFICATE OF INSTALLATION CF2R-MCH-20-H Duct Leakage Diagnostic Test (Page 3 of 3) Documentation Author's Declaration Statement 1.1 certify that this Certificate of Installation documentation is accurate and complete. Documentation Author Name: Bruce Edgar Documentation Author Signature: Company; The Energuy CA LLC Signature Date: gOI 5-07-20 15:55:40 Address: 1215 KSt., 17th Floor CEA/ HERS Certification Identification (if applicable): CC2006305 City/State/Zip: Sacramento CA 95814 Phone: 1-877-600-0123 Responsible Person's Declaration statement I certify the following under penalty of perjury, underthe laws ofthe State of California: 1. The information provided on this Certificate of Installation is true and correct. 2. lam eligible under Division 3 of the Business and Professions Code in the applicabie classification to accept responsibility for the system design, construction, or installation of features, materials, components, or manufactured devices for the scope of work identified on this Certificate of Installation and attest to the declarations in this statement (responsible builder/installer), otherwise I am an authorized representative ofthe responsible builder/installer. 3. The constructed or installed features, materials, components or manufactured devices (the installation) identified on this Certificate of Installation conforms to all applicable codes and regulations, and the installation conforms tQ the requirements given on the plans and specifications approved by the enforcement agency. 4. I understand that a HERS rater will check the installation to verify compliance, and that such checking identifies defects; I am required to take corrective action at my expense. I understand that Energy Commission and HEfe Provider representatives will also perform quality assuri^ce checking of installations, including those a^iroved as part of a sample group but not chetted by a HERS rater, and if those installations fail to noeet the requirements of such quality asstffance checking, the required corrective action and additional checking/testing of other installations in that HERS sample group will be performed at my expense. 5. I reviewed a copy of the Certificate of Compliance approved by the enforcement agency that identifies the specific requirements for the scope of construction or installation identified on this Certificate of Installation, andl have ensured that the requirements that apply to the construction or installation have been met. 6. I will ensure that a registered copy of this Certificate of Installation shall be posted, or made available with the building permit(s) issued for the building, and made available to the enforcement agency for all applicable inspections. I understand that a registered copy of this Certificate of Installation is required to be included with the documentation the builder provides to the building owner at occupancy. Responsible Builder/Installer Name: Kim Warner Responsible Builder/Installer Signature: Company Name: (Installing Subcontractor or General Contractor or Builder/Owner) AIR PLUS MECHANICAL INC Position With Company (Title): Manager Address: 4203 GENESEE AVE STE 103#507 CSLB License: 616223 City/State/Zip: SAN DIEGO CA 92117 Phone: Date Signed: (858)505-8711 2015-07-21 14:25:53 Third Party Quality Control Program (TPQCP) Status: Name of TPQCP (if applicable): Digitally signed by CalCERTS. This digital signature is provided in order to secure the content of this registered document, and in no way implies Registration Provider responsibility for the accuracy ofthe information. Registration Number; 215-A0193193A-M2000002A-0000 Registration Date/Time: CA Building Energy Efficiency Standards 2013 Residential Compliance Report Version; 2014-05-08 Schema Version: O.SISDD 2015-07-21 14:25:53 HERS Provider; CalCERTS Report Generated; 2015-07-20 15:54:42 CERTIFICATE OF VERIFICATION CF3R-MCH-20-H Duct Leakage Diagnostic Test (Page 1 of 3 ) ^ Project Name: Williams Enforcement Agency: Carlsbad City of Permit Number: PENDING Dwelling Address: 1769 Blackbird Circle City: Carlsbad Zip Code: 92011 A. System Information 01 Space Conditioning System Identification or Name System 1 02 Space Conditioning System Location or Area Served Whole House 03 Building Type from CF-IR Single family 04 Verified Low Leakage Ducts in Conditioned Space (VLLDCS) Credit from CFIR? No, credit is not taken 05 Verified Low Leakage Air Handling Unit (VLLAHU) Credit from CFIR? No, credit is not taken 06 Duct System Compliance Category Alteration using smoke test MCH-20e - Sealing All Accessible Leaks using Smoke Test B. Duct Leakage Diagnostic Test 01 Condenser Nominal Cooling Capacity (ton) 4 02 Heating Capacity (kBtu/h) 80 03 Conditioned Floor Area served by this HVAC system (ft2) 2250 04 Duct Leakage Test Condition Test final 05 Duct Leakage Test Method Total leakage 06 Leakage Factor 0.15 07 Air Handling Unit Airflow (AHUAirflow) Determination Method Heating system method 08 Measured AHUAirflow This field or section is not applicable 09 Calculated Target Allowable Duct Leakage Rate (cfm) 260 10 Actual duct leakage rate from leakage test measurement (cfm) 351 1" Compliance Statement: System passes using smoke test of an altered HVAC system in an existing building. No visible smoke exits the accessible portions ofthe duct system. Smoke is only emanating from air-handling unit (AHU) cabinet and non accessible portions ofthe duct system. Note - Accessible is defined as having access thereto, but which first may require Registration Number: 215-A0193193A-M20OOO02A-M20A Registration Date/Time: 2015-07-20 15:55:31 HERS Provider; CalCERTS CA Building Energy Efficiency Standards Report Version; 2014-05-08 Report Generated; 2015-07-20 15:55:14 2013 Residential Compliance Schema Version; 0.551SDD CERTIFICATE OF VERIFICATION CF3R-MCH-20-H Duct Leakage Diagnostic Test (Page 2 of 3) B. Duct Leakage Diagnostic Test removal or opening of access panels, doors, or moving similar obstructions. If access to the ducts requires an object to be demolished or deconstructed then sealing of those ducts is not required 12 Notes: C. Additional Requirements for Compliance 01 System was tested in its normal operation condition. No temporary taping allowed. 02 Outside air (OA) ducts for Central Fan Integrated (CFI) ventilation systems, shall not be sealed/taped off during duct leakage testing. CFI OA ducts that utilize controlled motorized dampers, that open only when OA ventilation is required to meet ASHRAE Standard 62.2, and close when OA ventilation is not required, may be configured to the closed position during duct leakage testing. 03 All supply and return register boots were sealed to the drywall. 04 Building cavities were not used as plenums or platform returns in lieu of ducts. 05 If cloth backed tape was used it was covered with Mastic and draw bands. 06 All connection points between the air handler and the supply and return plenums are completely sealed. Ifthe system complies using the Smoke Test method, the smoke test was conducted in accordance with the requirements of Reference Residential Appendix RAS.1.4.3.6. Systems that comply using smoke test shall not be included in sample groups for HERS verification compliance. 08 Verification Status: Pass - all applicable requirements are met 09 Correction Notes for this table: The responsible persons signature on this compliance document affirms that all applicable requirements in this table have been met unless otherwise noted in the Verification Status and the Corrections Notes in this table. D. Determination of HERS Verification Compliance All applicable sections of this document shall indicate compliance with the specified verification protocol requirements in order for this Certificate of Verification as a whole to be determined to be in compliance. 01 Complies: All specified verification protocol requirements on this document are met. Registration Number: 215-A0193193A-M2000002A-M20A Registration Date/Time: 2015-07-20 15:55:31 HERS Provider: CalCERTS CA Building Energy Efficiency Standards Report Version: 2014-05-08 Report Generated; 2015-07-20 15:55:14 2013 Residential Compliance Schema Version; 0.551SDD CERTIFICATE OF VERIFICATION CF3R-MCH-20-H Duct Leakage Diagnostic Test (Page 3 of 3 ) Documentation Author's Declaration Statement 1.1 certify that this Certificate of Verification documentation is accurate and complete. Documentation Author Name: Bruce Edgar Documentation Author Signature: Company: The Energuy CA LLC Date Signed: 2015-07-20 15:55:31 Address: 1215 KSt., 17th Floor CEA/ HERS Certification Identification (if applicable): City/State/Zip: Sacramento CA 95814 Phone: 1-877-600-0123 Responsible Person's Declaration statement I certify the following under penalty of perjury, under the laws of the State of California: 1. The information provided on this Certificate of Verification is true and correct. 2. I am the certified HERS Rater who performed the verification identified and reported on this Certificate of Verification (responsible rater). 3. The installed features, materials, components, manufactured devices, or system performance diagnostic results that require HERS verification identified on this Certificate of Verification comply with the applicable requirements in Reference Appendices RA2, RA3, and the requirements specified on the Certificate of Compliance for the building approved by the enforcement agency. 4. The information reported on applicable sections ofthe Certific3te(s) of Installation (CF2R) signed and submitted by the person(s) responsible for the construction or installation conforms to the requirements specified on the Certjflc3te(s) of Compliance (CFIR) approved by the enforcement agency. 5. I will ensure that a registered copy of this Certificate of Veriflcation shall be posted, or nnade available with the building permit(s| issued for the building, and made availabte to tte enforcement agency for all applicable inspections. 1 understand that a registered copy of thS CertificaSe of Verification is required to be induded with the documentation the builder provides to the building owner at occupancy. Builder Or Installer Information As Shown On The Certificate Of Installation Company Name (Installing Subcontractor, General Contractor, or Builder/Owner): AIR PLUS MECHANICAL INC Responsible Builder or Installer Name: CSLB License: Kim Warner 616223 HERS Provider Data Registry Information Sample Group Number (if applicable): Dwelling Test Status in Sample Group (if applicable) Tested HERS Rater Information HERS Rater Company Name: The Energuy CA LLC Responsible Rater Name: Responsible Rater Signature: - Bruce Edgar Responsible Rater Certification Number w/ this HERS Provider: Date Signed: CC2006305 2015-07-20 15:55:31 Digitally signed by CalCERTS. This digital signature is provided in order to secure the content of this registered document, and in no way implies Registration Provider responsibility for the accuracy ofthe information. Registration Number; 215-A0193193A-M2000002A-M20A CA Building Energy Efficiency Standards 2013 Residential Compliance Registration Date/Time: 2015-07-20 15:55:31 HERS Provider: CalCERTS Report Version; 2014-05-08 Report Generated; 2015-07-20 15:55:14 Schema Version; 0.551SDD