HomeMy WebLinkAbout1808 ASTON AVE; 270; CB100370; PermitBuilding Permit Application
1635 Faraday Ave., Carlsbad, CA 92008
760-602-2717 / 2718 / 2719
Fax 760-602-8558
www.carlsbadca.gov
Plan Check No.
Est. Value
Plan Ck. Deposit
Date 3 (3 |
JOB ADDRESS
CT/PROJECT #LOT
20-0=7- -0&
DESCRIPTION OF WORK: Include Square Feet of Affected Area(s)
t*to0,fl£W iftfCM&v '
^ztzdncMt
1JSE GARAGE (SF)PATIOS (SF)DECKS (SF)FIREPLACE
YES| |#
AIR CONDITIONING FIRE SPRINKLERS
CONTACT NAME (If Different Fon, Applicant)APPLICANT NAME Roberts & Bennett
ADDRESS ADDRESS
1010 University Ave, Suite C203
CITY STATE ZIP CITY STATE
92103
(Sec. 7031.5 Business and Professions Code: Any City or County which requires a permit to construct, alter, improve, demolish or repair any structure, prior to its issuance, also requires theappMcant for such permit to file a signed statement that he is licensed pursuant to the provisions of the Contractor's License Law (Chapter 9, commending with Section 7000 of Division 3 of theBusiness and Professions Code) or that he is exempt therefrom, and the basis for the alleged exemption. Any violation of Section 7031.5 by any applicant for a permit subjects the applicant to acivil penalty of not more than five hundred dollars {$500}).
>M^^P^:/ ;;'''1^ •.-4'^-ff*- •*'*:
Workers' Compensation Declaration: / hereby affirm under penalty of perjury one of the following declarations:
LJ I have and will maintain a certificate of consent to self-insure for workers' compensation as provided by Section 3700 of the Labor Code, for the performance of the work for which this permit is issued.
I 11 have and will maintain workers' compensation, as required bv Section 3700 of the Labor Code, for the performance of the work for which this permit is issued. My workers' compensation insurance carrier and policy
number are: Insurance Co O \O* V—C'riJ*-'*-^ ' * ^* Policy No- rVvf^lJJ J (g *-i \O^fO Expiration Date &[ I \
This section need not be completed if the permit is for one hundred dollars ($100) or less.
I | Certificate of Exemption: I certify that in the performance of the work for which this permit is issued, I shall not employ any person in any manner so as to become subject to the Workers' Compensation Laws of
California. WARNING: Failure to secure workers' compensation coverage is unlawful, and shall subject an employer to criminal penalties and civil fines up to one hundred thousand dollars (&100.000), in
addition to the cost of compensation, damages as provided feiyn Section, 3706 of the Labor code, interest and attorney's fees.
j£$ CONTRACTOR SIGNATURt-'^rAv^ £\^^DATE
t-- ?7^;^i;
/ hereby affirm that I am exempt from Contractor's License Law for the following reason:
| | I, as owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not intended or offered for sale (Sec. 7044, Business and Professions Code: The Contractor's
License Law does not apply to an owner of property who builds or improves thereon, and who does such work himself or through his own employees, provided that such improvements are not intended or offered for
sale. If, however, the building or improvement is sold within one year of completion, the owner-builder will have the burden of proving that he did not build or improve for the purpose of sale).
| | I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions Code: The Contractor's License Law does not apply to an owner of
property who builds or improves thereon, and contracts for such projects with contractor(s) licensed pursuant to the Contractor's License Law).
I am exempt under Section _.Business and Professions Code for this reason:
1.1 personally plan to provide the major labor and materials for construction of the proposed property improvement. | |Yes I [No
2.1 (have / have not) signed an application for a building permit for the proposed work.
3.1 have contracted with the following person (firm) to provide the proposed construction (include name address / phone / contractors' license number):
4.1 plan to provide portions of the work, but I have hired the following person to coordinate, supervise and provide the major work (include name / address / phone / contractors' license number):
5.1 will provide some of the work, but I have contracted (hired) the following persons to provide the work indicated (include name / address / phone / type of work):
^PROPERTY OWNER SIGNATURE QAGENT DATE
.-^^%\i¥^^BEJfv^A ? •>?;&'J^llS-M'&f^ ^'
Is the applicant or future building occupant required to submit a business Dlaif acutely hazardous materials registration form or risk management and prevention program under Sections 25505,25533 or 25534 of the
Presley-Tanner Hazardous Substance Account Act? I I Yes V^lNo \ X
Is the applicant or future building occupant required to obtain a permit fronuhe air pollution control district or air gualkv management district? I JYes IXI No
Is the facility to be constructed within 1,000 feet of the outer boundary of a school site? I JYes IVfNo / *
IF ANY OF THE ANSWERS ARE YES, A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUEDJdNLBSS THE APPLICANT HAS MET OR IS MEETING THE REQUIREMENTS OF THE OFFICE OF
EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT.
I hereby affirm that there is a construction lending agency for the performance of the work this permit is issued (Sec. 3097 (i) Civil Code).
Lender's Name Lender's Address
I certify that I have read the application and slate that the above information is correct and that the information on the plans is accurate. I agree 'to comply with all City ordinances and State laws relating to building construction.
I hereby authorize representative of the City of Carlsbad to enter upon the above mentioned property for inspection purposes. I ALSO AGREE TO SAVE, INDEMNIFY AND KEEP HARMLESS THE CITY OF CARLSBAD
OSHA: An OSHA permit is required for excavations over SO deep and demolition or construction of structures over 3 stories in height.
EXPIRATION: Every permit issued by the Building Official under the provisions of this Code shall expire by limitation and become null and void if the building or work authorized by such permit is not commenced within
180 days from the date of such permit 0| if the building or workauth^ized by such permit is suspended or abandoned at any time after the word is commenced for a period of 180 days (Section 106.4.4 Uniform Building Code).
^APPLICANT'S SIGNATURE DATE - \V
EsGil Corporation
In Partnership with government for iBuifding Safety
DATE: 4/1/10 a APPLICANT
€ JURIS.
JURISDICTION: City of Carlsbad a PLAN REVIEWER
a FILE
PLAN CHECK NO.: PC10-0012 SET: II
PROJECT ADDRESS: 1808 Aston Ave Suite 25O & 270
PROJECT NAME: Wells Fargo - TI
IXI The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
The applicant's copy of the check list has been sent to:
XI Esgil Corporation staff did not advise the applicant that the plan check has been completed.
Esgil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Telephone #:
Date contacted: (by: ) Fax #:
Mail Telephone Fax In Person
REMARKS:
By: Doug Moody Enclosures:
EsGil Corporation
D GA D EJ D PC 3/31/10
9320 Chesapeake Drive, Suite 208 * San Diego, California 92123 4 (858)560-1468 + Fax (858) 560-1576
EsGil Corporation
In Partners/tip with government for (Building Safety
DATE: 3/11/10
g
JURISDICTION: City of Carlsbad a PLAN REVIEWER
a FILE
PLAN CHECK NO.: PC10-0012 SET: I
PROJECT ADDRESS: 1808 Aston Ave Suite 250 & 270
PROJECT NAME: Wells Fargo - TI
The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
X3 The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
XI The applicant's copy of the check list has been sent to:
Roberts and Bennett / Tara Norton
1010 University Ave Suite C203, San Diego, CA 92103
Esgil Corporation staff did not advise the applicant that the plan check has been completed.
Esgil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Tara Norton Telephone #: 619-297-1011
Date contactedL3//V//#(b^^) Fax #: 619-297-3832
Maili /^Telephone Fax v/^ln Person
REMARKS:
By: Doug Moody Enclosures:
EsGil Corporation
D GA D EJ D PC 3/4/10
9320 Chesapeake Drive, Suite 208 + San Diego, California 92123 4 (858)560-1468 + Fax (858) 560-1576
City of Carlsbad PC 10-0012
3/11/10
PLAN REVIEW CORRECTION LIST
TENANT IMPROVEMENTS
PLAN CHECK NO.: PC10-O012
OCCUPANCY: B
TYPE OF CONSTRUCTION: VA
ALLOWABLE FLOOR AREA:
SPRINKLERS?: YES
REMARKS:
DATE PLANS RECEIVED BY
JURISDICTION: 3/3/10
DATE INITIAL PLAN REVIEW
COMPLETED: 3/11/10
JURISDICTION: City of Carlsbad
USE: Office
ACTUAL AREA: 14018sf
STORIES: 2
HEIGHT:
OCCUPANT LOAD: 161
DATE PLANS RECEIVED BY
ESGIL CORPORATION: 3/4/10
PLAN REVIEWER: Doug Moody
FOREWORD (PLEASE READ):
This plan review is limited to the technical requirements contained in the International Building
Code, Uniform Plumbing Code, Uniform Mechanical Code, National Electrical Code and state
laws regulating energy conservation, noise attenuation and access for the disabled. This plan
review is based on regulations enforced by the Building Department. You may have other
corrections based on laws and ordinances enforced by the Planning Department, Engineering
Department, Fire Department or other departments. Clearance from those departments may be
required prior to the issuance of a building permit.
Code sections cited are based on the 2007 CBC, which adopts the 2006 IBC.
The following items listed need clarification, modification or change. All items must be satisfied
before the plans will be in conformance with the cited codes and regulations. Per Sec. 105.4 of
the 2006 International Building Code, the approval of the plans does not permit the violation of
any state, county or city law.
To speed up the recheck process, please note on this list (or a copy) where each
correction item has been addressed, i.e.. plan sheet number, specification section, etc.
Be sure to enclose the marked up list when you submit the revised plans.
City of Carlsbad PC10-0012
3/11/10
Please make all corrections on the original tracings, as requested in the correction
list. Submit three sets of plans for commercial/industrial projects (two sets of plans
for residential projects). For expeditious processing, corrected sets can be
submitted in one of two ways:
1. Deliver all corrected sets of plans and calculations/reports directly to the City of
Carlsbad Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760)
602-2700. The City will route the plans to EsGil Corporation and the Carlsbad
Planning, Engineering and Fire Departments.
2. Bring one corrected set of plans and calculations/reports to EsGil Corporation,
9320 Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-1468.
Deliver all remaining sets of plans and calculations/reports directly to the City of
Carlsbad Building Department for routing to their Planning, Engineering and Fire
Departments.
NOTE: Plans that are submitted directly to EsGil Corporation only will not be
reviewed by the City Planning, Engineering and Fire Departments until review by
EsGil Corporation is complete.
1. Glazing in the following locations should be of safety glazing material in
accordance with Section 2406.3. Please revise the window schedule to show:
a) Fixed or operable panels adjacent to a door where the nearest exposed
edge of the glazing is within a 24-inch arc of either vertical edge of the door
in a closed position. And where the bottom exposed edge of the glazing is
less than 60 inches above the walking surface.
2. Please provide notes on the plans to show the suspended ceilings in Seismic
Design Categories D, E & F comply with ASCE 7-05 Section 13.5.6.2.1 as
follows:
a) The other end in each horizontal direction shall have a %" clearance from
the wall and shall rest upon and be free to slide on a closure angle or a
listed assembly.
b) Ceiling areas over 1,000 ft.2 must have horizontal restraint wires (typically
restraint would consist of four 12 gauge wires splayed 90° to each other
and sloped 45° to the horizontal, spaced 12" o.c.).
c) Ceiling areas over 2500 ft.2 must have seismic separation joints or full
height partitions that break the ceiling into areas not exceeding 2500 ft.2 .
d) Ceilings without rigid bracing must have 2" oversize trim rings for
sprinklers and other ceiling penetrations.
3. Please revise the lighting plan to show the lighting fixtures controlled by the
existing Lighting Control Panel.
4. Plumbing plan Provide complete plumbing plans, including:
b) Complete drain, waste and vent plans.
c) Provide complete water line sizing and developed pipe lengths. UPC
Section 610.0
d) Show water heater size, type and location on plans. UPC, Section 501.0
City of Carlsbad PC1O-OO12
3/11/1O
5. Please review the requirements, revise the plans appropriately and imprint on
the plans the City of Carlsbad Policies and Procedures for Roof Mounted
Equipment to the plans.
Note : When alterations, structural repairs or modifications or additions are made to an
existing building, that building, or portion of the building affected, is required to comply
with all of the requirements for new buildings, per Section 1134B.2. These requirements
apply as follows:
a) Existing sanitary facilities (this includes showers) that serve the remodeled
area must be shown to comply with all accessibility features.
6. Please revise the plans to show the non-commercial kitchen sink in the
employee staff room to provide the following:
a) A clear floor space at least 30"x 48" shall be provided for forward
approach.
b) The clear space shall extend a maximum of 19" underneath the sink.
c) The accessible sink shall be a maximum of 6 1/2" deep.
d) The sink shall be mounted with the counter or rim no higher than 34"
e) Knee clearance that is at least 27" high, 30" side and 19" underneath the
sink shall be provided.
f) Hot water and drain shall be insulated.
g) There shall be no sharp or abrasive surfaces under sinks.
7. Please revise the plans to show the showers serving the area of improvement to
provide disabled accessible shower facilities.
To speed up the review process, note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet, note or detail number,
calculation page, etc.
Please indicate here if any changes have been made to the plans that are not a
result of corrections from this list. If there are other changes, please briefly
describe them and where they are located in the plans.
Have changes been made to the plans not resulting from this correction list?
Please indicate:
Yes a No a
The jurisdiction has contracted with Esgil Corporation located at 9320
Chesapeake Drive, Suite 208, San Diego, California 92123; telephone number of
858/560-1468, to perform the plan review for your project. If you have any
questions regarding these plan review items, please contact Doug Moody at
Esgil Corporation. Thank you.
City of Carlsbad PC1O-OO12
3/11/10
[DO NOT PAY- THIS IS NOT AN INVOICE]
VALUATION AND PLAN CHECK FEE
JURISDICTION: City of Carlsbad PLAN CHECK NO.: PC1O-0012
PREPARED BY: Doug Moody DATE: 3/11/1O
BUILDING ADDRESS: 1808 Aston Ave Suite 250 & 270
BUILDING OCCUPANCY: B TYPE OF CONSTRUCTION: VA
BUILDING
PORTION
TI250
TI270
Air Conditioning
Fire Sprinklers
TOTAL VALUE
Jurisdiction Code
AREA
( Sq. Ft.)
11060
2958
cb
Rlrln Pormif FPP hu OrHinanrp ^
Valuation
Multiplier
34.37
34.37
3y Ordinance
Reg.
Mod.
VALUE ($)
380,132
101,666
481,799
$2,036.41
Plan Check Fee by Ordinance
Type of Review:
I I Repetitive FeeRepeats
Complete Review
D Other
r—i Hourly
EsGil Fee
Structural Only
Hr. @
$1,323.67
$1,140.39
Comments:
Sheet 1 of 1
macvalue.doc +
PLANNING/ENGINEERING APPROVALS
PERMIT NUMBER CB t'C /
ADDRESS •i A //X
DATE
RESIDENTIAL TENANT IMPROVEMENT
RESIDENTIAL ADDITION MINOR
(<$17,000.00)
PLAZA CAMINO REAL
CARLSBAD COMPANY STORES
VILLAGE FAIRE
COMPLETE OFFICE BUILDING
OTHER t ft.
PLANNER
ENGINEER
DATE
DATE
Docs/Misforms/Planning Engineering Approvals
/f
/ft
as 292.0
- r/
7
79 /9r3
2
1 j- "i i
.237?c
z
^^^IZM?/
& £
PLANNING DEPARTMENT
BUILDING PLAN CHECK REVIEW CHECKLIST
Plan Check No. PC 10-12 Address 1808 ASTON AV
Planner GINA RUIZ Phone (760) 602- 4675
APN: 212-120-07-00
Type of Project & Use: Tl Net Project Density: DU/AC
Zoning: C-M/OS General Plan: PI/OS Facilities Management Zone: 5
CFD (in/out) #J_Date of participation:5/7/1991 Remaining net dev acres:.
Circle One (For non-residential development: Type of land used created by this permit:
D D
D
D D
D
Legend: |EI Item Complete [ Djltem Incomplete - Needs your action
Environmental Review Required: YES D NO IE] TYPE
DATE OF COMPLETION:
Compliance with conditions of approval? If not, state conditions which require action.
Conditions of Approval:
Discretionary Action Required:
APPROVAL/RESO. NO. DATE .
PROJECT NO.
OTHER RELATED CASES:
YES D NO IEl TYPE
Compliance with conditions or approval? If not, state conditions which require action.
Conditions of Approval:
Coastal Zone Assessment/Compliance
Project site located in Coastal Zone? YES D NO El
CA Coastal Commission Authority? YES Q NO JEl
If California Coastal Commission Authority: Contact them at - 7575 Metropolitan Drive, Suite 103,
San Diego, CA 92108-4402; (619) 767-2370
Determine status (Coastal Permit Required or Exempt):
Habitat Management Plan
Data Entry Completed? YES D NO IE!
If property has Habitat Type identified in Table 11 of HMP, complete HMP Permit application and
assess fees in Permits Plus
(A/P/Ds, Activity Maintenance, enter CB#, toolbar, Screens, HMP Fees, Enter Acres of Habitat Type
impacted/taken, UPDATE!)
Inclusionary Housing Fee required: YES d NO K)
(Effective date of Inclusionary Housing Ordinance - May 21, 1993.)
Data Entry Completed? YES D NO D
(A/P/Ds, Activity Maintenance, enter CB#, toolbar, Screens, Housing Fees, Construct Housing Y/N,
Enter Fee, UPDATE!)
H:\ADMINYTemplate\Building Plancheck Review Checklist.doc Rev 4/08
e Plan:
D
SEE ADDITIONAL COMMENTS BELOW
Policy 44 - Neighborhood Architectural Design Guidelines
1. Applicability: YES D NO [3
2. Project complies: YES D NOQ
D
n
Zoning:
1. Setbacks:
Front:
Interior Side:
Street Side:
Rear:
Top of slope:
Required
Required
Required
Required
Required
D D
2. Accessory structure setbacks:
Front: Required
Interior Side: Required.
Street Side: Required
Rear: Required
Structure separation: Required.
3. Lot Coverage: Required .
Shown
Shown
Shown
Shown
Shown
Shown
Shown
Shown
Shown
Shown
Shown
n n 4. Height:Required Shown
nn
D
Spaces Required Shown5. Parking:
(breakdown by uses for commercial and industrial projects required)
Residential Guest Spaces Required _ Shown _
Additional Comments #1. SHEET E-1 STATES IN THE POWER/DATA KEY NOTES THAT THERE
IS A NEW ROOF-MOUNTED CONDENSING UNIT. ALL ROOF MOUNTED EQUIPMENT NEED
TO BE SCREENED FROM VIEW FROM STREETS WITHIN 500'. PLEASE ADD A SECTION
SHOWING HOW THE NEW UNIT WILL BE SCREENED (SEE ATTACHED HANDOUT FOR
MORE INFORMATION).
OK TO ISSUE AND ENTERED APPROVAL INTO COMPUTER DATE
H:\ADMIN\Template\Building Plancheck Review Checklist.doc Rev 4/08
Carlsbad Fire Department
Plan Review Requirements Category: TI , INDUST
Date of Report: 04-08-20 1 0 Reviewed by: 4:^}if
Name: ROBERTS & BENNETT
Address: 1010 UNIVERSITY AVE
STE C203
SAN DIEGO
C A 92 103
BLr>a. DEFT COPY
Permit #: CB 100369
Job Name: WELLS FARGO: 1 1 ,060SF TI / OFF
Job Address: 1 808 ASTON AV CBAD St: 250
INCOMPLETE The item you[hjiy_e_jubmitted for review is incomplete. At this time, this office cannot
adequately SSfflucilTreview to determine compliance witJLffi^^^le^fe^S^Clci^or stalidardsr Please review
carefully all comments attached. Please jesabmit" trie necessary plans and/or specifications; with changes "clouded",
to this office for review andLjppfiSvaTL
Conditions:
Cond: CON0003957
[NOT MET]
CORRECTIONS
Tl-1 TITLE SHEET -
Project Data
Occupancy - Justify classification of conference room, with an area greater than 750 square feet as
a Group B Occupancy and not as an Assembly Occupancy (CBC 303.1). Address CBC Chapter 5
requirements in a code analysis for mixed use occupancy.
General Notes, and Under Separate Submittals Notes
Note 19 - Revise code section to CFC 505.1
Reflected Ceiling Plan Notes
Remove reference to UFC Section 12.108
Door & Hardware Notes
Note 4. Revise references to CBC Sec. 803, 804 & 806.
Note 5. Revise to 34" minimum and 48" maximum
Fire Protection Notes
Note 6. Revise reference to CFC 712.3.3 to CBC 712.3.3
Under Separate Submittal
Revise hazardous materials table references from UBC Table 3-D & 3E to CBC Tables 307.1(1) and
307.1(2)
Code References (under Sheet Index)
Revise reference to 2006 IEBC to IBC
Add NFPA 13 2002 Edition and NFPA 72 2002 Edition
Page: 2 of 2
Vicinity Map
Provide a north directional arrow
Sign (typical all sheets)
TI-2 SITE ACCESS
Mark this sheet FOR REFERENCE ONLY
Provide a north directional arrow
TI-3 EXIT PLAN
Provide room numbers on plan.
Revise # of occupants and occupant load factor in Conference Room. See Room Legend on sheets TI-5 &
TI-8.
Revise total occupant load
Justify exiting into non-continuous 1-hr rated corridor in path of egress. All interior partitions
and rated per CBC Table 601 for Type VA construction type? Please clarify on plans.
Provide egress analysis for all areas in accordance with CBC Section 1004. Compute the number of
occupants at the rate of one occupant per unit of area as prescribed in CBC Table 1004.1.1.
Determine the use based on a listed use that most resembles the proposed
Provide suite address specifications
Provide a north directional arrow
TI-5 PARTITION PLAN
Add note: rated doors will be equipped with label specifying fire resistive rating.
Add note: All doors are operable without the use of a key, special knowledge or effort.
Denote height of fire extinguisher in accordance with NFPA 10 requirements and denote location.
TI-7 REFLECTED CEILING PLAN
Reflected Ceiling Legend
Provide 90 minutes battery back up for internally lit exit signs
Denote locations of directional exit signs in corridor on plan Condition of recommended approval
Denote location of emergency lighting and reference Sheet E2.
TI.9 DETAIL SHEET
Detail 1
Revise reference from UBC to CBC Table 720 Item #
Details 2 & 3
Provide listed design numbers for rated walls or reference CBC Table 720 item number.
E-2 Lighting Plan
Lighting Legend
Provide 90 minute battery pack for emergency lighting & exit signs.
Lighting Plan
Denote directional exit signs in corridor Condition of recommended approval
RECOMMENDED APPROVAL CONTINGENT UPON EXIT SIGNS IN CORRIDOR
TO BE ADDED BY DESIGNER OVER THE COUNTER
CORRECTIONS
Tl-1 TITLE SHEET -
Project Data
Occupancy - Justify classification of conference room, with an area greater than 750 square feet as
a Group B Occupancy and not as an Assembly Occupancy (CBC 303.1). Address CBC Chapter 5
requirements in a code analysis for mixed use occupancy.
General Notes, and Under Separate Submittals Notes
Note 19 - Revise code section to CFC 505.1
Reflected Ceiling Plan Notes
Remove reference to UFC Section 12.108
Door & Hardware Notes
Note 4. Revise references to CBC Sec. 803, 804 & 806.
Note 5. Revise to 34" minimum and 48" maximum
Fire Protection Notes
Note 6. Revise reference to CFC 712.3.3 to CBC 712.3.3
Under Separate Submittal
Revise hazardous materials table references from UBC Table 3-D & 3E to CBC Tables 307.1(1) and
307.1(2)
Code References (under Sheet Index)
Revise reference to 2006 IEBC to IBC
Add NFPA 13 2002 Edition and NFPA 72 2002 Edition
Page: 2 of 2
Vicinity Map
Provide a north directional arrow
Sign (typical all sheets)
TI-2 SITE ACCESS
Mark' this sheet FOR REFERENCE ONLY
Provide a north directional arrow
TI-3 EXIT PLAN
Provide room numbers on plan.
Revise # of occupants and occupant load factor in Conference Room. See Room Legend on sheets TI-5 &
TI-8.
Revise total occupant load
Justify exiting into non-continuous 1 -hr rated corridor in path of egress. All interior partitions
and rated per CBC Table 601 for Type VA construction type? Please clarify on plans.
Provide egress analysis for all areas in accordance with CBC Section 1004. Compute the number of
occupants at the rate of one occupant per unit of area as prescribed in CBC Table 1004.1.1.
Determine the use based on a listed use that most resembles the proposed
Provide suite address specifications
Provide a north directional arrow
TI-5 PARTITION PLAN
Add note: rated doors will be equipped with label specifying fire resistive rating.
Add note: All doors are operable without the use of a key, special knowledge or effort.
Denote height of fire extinguisher in accordance with NFPA 10 requirements and denote location.
TI-7 REFLECTED CEILING PLAN
Reflected Ceiling Legend
Provide 90 minutes battery back up for internally lit exit signs
Denote locations of directional exit signs in corridor on plan Condition of recommended approval
Denote location of emergency lighting and reference Sheet E2.
TI.9 DETAIL SHEET
Detail 1
Revise reference from UBC to CBC Table 720 Item #
Details 2 & 3
Provide listed design numbers for rated walls or reference CBC Table 720 item number.
E-2 Lighting Plan
Lighting Legend
Provide 90 minute battery pack for emergency lighting & exit signs.
Lighting Plan
Denote directional exit signs in corridor Condition of recommended approval
RECOMMENDED APPROVAL CONTINGENT UPON EXIT SIGNS IN CORRIDOR
TO BE ADDED BY DESIGNER OVER THE COUNTER
CORRECTIONS
Tl-1 TITLE SHEET -
Project Data
Occupancy - Justify classification of conference room, with an area greater than 750 square feet as
a Group B Occupancy and not as an Assembly Occupancy (CBC 303.1). Address CBC Chapter 5
requirements in a code analysis for mixed use occupancy.
General Notes, and Under Separate Submittals Notes
Note 19 - Revise code section to CFC 505.1
Reflected Ceiling Plan Notes
Remove reference to UFC Section 12.108
Door & Hardware Notes
Note 4. Revise references to CBC Sec. 803, 804 & 806.
Note 5. Revise to 34" minimum and 48" maximum
Fire Protection Notes
Note 6. Revise reference to CFC 712.3.3 to CBC 712.3.3
Under Separate Submittal
Revise hazardous materials table references from UBC Table 3-D & 3E to CBC Tables 307.1(1) and
307.1(2)
Code References (under Sheet Index)
Revise reference to 2006 IEBC to ffiC
Add NFPA 13 2002 Edition and NFPA 72 2002 Edition
Page: 2 of 2
Vicinity Map
Provide a north directional arrow
Sign (typical all sheets)
TI-2 SITE ACCESS
Mark this sheet FOR REFERENCE ONLY
Provide a north directional arrow
TI-3 EXIT PLAN
Provide room numbers on plan.
Revise # of occupants and occupant load factor in Conference Room. See Room Legend on sheets TI-5 &
TI-8.
Revise total occupant load
Justify exiting into non-continuous 1-hr rated corridor in path of egress. All interior partitions
and rated per CBC Table 601 for Type VA construction type? Please clarify on plans.
Provide egress analysis for all areas in accordance with CBC Section 1004. Compute the number of
occupants at the rate of one occupant per unit of area as prescribed in CBC Table 1004.1.1.
Determine the use based on a listed use that most resembles the proposed
Provide suite address specifications
Provide a north directional arrow
TI-5 PARTITION PLAN
Add note: rated doors will be equipped with label specifying fire resistive rating.
Add note: All doors are operable without the use of a key, special knowledge or effort.
Denote height of fire extinguisher in accordance with NFPA 10 requirements and denote location.
TI-7 REFLECTED CEILING PLAN
Reflected Ceiling Legend
Provide 90 minutes battery back up for internally lit exit signs
Denote locations of directional exit signs in corridor on plan Condition of recommended approval
Denote location of emergency lighting and reference Sheet E2.
TI.9 DETAIL SHEET
Detail 1
Revise reference from UBC to CBC Table 720 Item #
Details 2 & 3
Provide listed design numbers for rated walls or reference CBC Table 720 item number.
E-2 Lighting Plan
Lighting Legend
Provide 90 minute battery pack for emergency lighting & exit signs.
Lighting Plan
Denote directional exit signs in corridor Condition of recommended approval
RECOMMENDED APPROVAL CONTINGENT UPON EXIT SIGNS IN CORRIDOR
TO BE ADDED BY DESIGNER OVER THE COUNTER
Entry: 03/08/2010 By: JJK/cw Action: CO
Cond: CON0003958
[MET]
**APPROVED:
THIS PROJECT HAS BEEN REVIEWED AND APPROVED FOR THE PURPOSES OF ISSUEANCE OF A
BUILDING PERMIT.
THIS APPROVAL IS SUBJECT TO FIELD INSPECTIONS, ANY REQUIRED TESTS, FIRE DEPARTMENT
NOTATIONS,
CONDITIONS IN CORRESPONDENCE AND COMPLIANCE WITH ALL APPLICABLE CODES AND
REGULATIONS.
THIS APPROVAL SHALL NOT BE HELD TO PERMIT OR APPROVE ANY VIOLATION OF THE LAW.
Entry: 04/08/2010 By:JJJC7cw Action: AP
Raeffette Abbey
From:
Sent:
To:
Subject:
Daryl [kitfire@sbcglobal.net]
Thursday, April 08, 2010 4:01 PM
Raenette Abbey
Plan Review Charges
Wells Fargo PC100012 Initial Review 1 hr $90. Re-check $45 Total=$135
Perfectly at Home CB100395 Intial & Recheck 1.75 hrs = $157.50
It's a Grind CB100319 Initial Review 1.5 hrs $135. Re-checks 1.25 hrs $112.50
-Total $247.50
Kyss CB 100469 Initial Review 1.5 hrs $135 Re-check .5 hrs $45. = Total =$180
Vcuyl/ Kttjcune*
Daryl K. James & Associates, Inc.
205 Colina Terrace
Vista. CA 92084
760-724-7001
kitfire@sbcalobal.net
CORRECTION LIST Page: 1 of 2
Dvtryl K. James & Associates, Inc. Checked by: Darvl Kit James
205 Colina Terrace Date: March 8, 2010
Vista, CA 92084
T. (760) 724-7001 Email: kitfire@sbcglobal.net 8JLDQ £)pprp pi^x
APPLICANT: Tara Norton JURISDICTION: Carlsbad Fire Department
PROJECT NAME: Wells Fargo PROJECT ADDRESS: 1808 Aston Avenue Ste 250 & 270
PROJECT DESCRIPTION: CB1001369&1370 PC No. PC100012
INSTRUCTIONS
• This plan review has been conducted in order to verify conformance to minimum requirements of codes
adopted by the Carlsbad Fire Department.
• The items below require correction, clarification or additional information before this plan check can be
approved for permit issuance.
• Corrections or modifications to the plans must be clouded and provided with numbered deltas and revision
dates along with a descriptive narrative of corrections addressing all comments.
• Please direct any questions regarding this review to: Daryl Kit James (760) 724-7001 or
kitfire@sbcglobal.net
• Corrected plans and descriptive narrative to be submitted to:
Daryl K. James & Associates, Inc.
205 Colina Terrace
Vista, CA 92084
CORRECTIONS
T1-1 TITLE SHEET -
Project Data
| Occupancy - Justify classification of conference room, with an area greater than 750 square feet as a Group B
Occupancy and not as an Assembly Occupancy (CBC 303.1). Address CBC Chapter 5 requirements in a code
analysis for mixed use occupancy.
General Notes, and Under Separate Submittals Notes
| Note 19 - Revise code section to CFC 505.1
Reflected Ceiling Plan Notes
Remove reference to UFC Section 12.108
Door & Hardware Notes
iNote 4. Revise references to CBC Sec. 803, 804 & 806.
Note 5. Revise to 34" minimum and 48" maximum
Fire Protection Notes
Note 6. Revise reference to CFC 712.3.3 to CBC 712.3.3
Under Separate Submittal
8 Revise hazardous materials table references from UBC Table 3-D & 3E to CBC Tables 307.1(1) and 307.1(2)
Code References (under Sheet Index)IRevise reference to 2006 IEBC to IBC
Add NFPA 13 2002 Edition and NFPA 72 2002 Edition
Page: 2 of 2
Vicinity Map
Provide a north directional arrow
Sign (typical all sheets)
TI-2 SITE ACCESS
E Mark this sheet FOR REFERENCE ONLY
Provide a north directional arrow
TI-3 EXIT PLAN
Provide room numbers on plan.
Revise # of occupants and occupant load factor in Conference Room. See Room Legend on sheets TI-5 & TI-8.
Revise total occupant load
Justify exiting into non-continuous 1-hr rated corridor in path of egress. All interior partitions and rated per CBC
[ Table 601 for Type VA construction type? Please clarify on plans.
Provide egress analysis for all areas in accordance with CBC Section 1004. Compute the number of occupants
at the rate of one occupant per unit of area as prescribed in CBC Table 1004.1.1. Determine the use based on a
listed use that most resembles the proposed
(Provide suite address specifications
Provide a north directional arrow
TI-5 PARTITION PLAN
Add note: rated doors will be equipped with label specifying fire resistive rating.
| Add note: All doors are operable without the use of a key, special knowledge or effort.
Denote height of fire extinguisher in accordance with NFPA 10 requirements and denote location.
TI-7 REFLECTED CEILING PLAN
Reflected Ceiling Legend
I Provide 90 minutes battery back up for internally lit exit signs
Denote locations of directional exit signs in corridor on plan Condition of recommended approval
Denote location of emergency lighting and reference Sheet E2.
TI.9 DETAIL SHEET
Detail 1
Revise reference from UBC to CBC Table 720 Item #
Details 2 & 3
f| Provide listed design numbers for rated walls or reference CBC Table 720 item number.
E-2 Lighting Plan
Lighting Legend
( Provide 90 minute battery pack for emergency lighting & exit signs.
Lighting Plan
Denote directional exit signs in corridor Condition of recommended approval
RECOMMENDED APPROVAL CONTINGENT UPON EXIT SIGNS IN CORRIDOR
TO BE ADDED BY DESIGNER OVER THE COUNTER
Raenette Abbey
From: Daryl [kitfire@sbcglobal.net]
Sent: Thursday, April 08, 2010 4:01 PM
To: Raenette Abbey
Subject: Plan Review Charges
Wells Fargo PC 100012 Initial Review 1 hr $90. Re-check $45 Total=$135
Perfectly at Home CB100395 Intial & Recheck 1.75 hrs = $157.50
It's a Grind CB100319 Initial Review 1.5 hrs $135. Re-checks 1.25 hrs $112.50
=Total $247.50
Kyss CB100469 Initial Review 1.5 hrs $135 Re-check .5 hrs $45. = Total =$180.
Daryl K. James & Associates, Inc.
205 Colina Terrace
Vista. CA 92084
760-724-7001
kitfire(5?sbcq!obal.net
CERTIFICATE OF COMPLIANCE and
FIELD INSPECTION ENERGY CHECKLIST
(Parti of5)MECH-1C
Project Name
Wells Fargo
Date
2/24/2010
Project Address
7808 Aston Avenue Carlsbad
Climate Zone Total Cond. Floor Area
182
Addition Floor Area
0
GENERAL INFORMATION
Building Type:Zl Nonresidential O High-Rise Residential D Hotel/Motel Guest Room
Q Schools (Public School) D Relocatable Public School Bldg. H Conditioned Spaces Unconditioned Spaces
(affidavit)
Phase of Construction:New Construction D Addition Alteration
Approach of Compliance: D Component m Overall Envelope TDV
Energy O Unconditioned (file affidavit)
Front Orientation: N, E, S, W or in Degrees: 0 deg
HVAC SYSTEM DETAILS HELD INSPECTION ENERGY CHECKLIST
Equipment2
Item or System Tags
(i.e. AC-1, RTU-1.HP-1)
Equipment Type4:
Number of Systems
Max Allowed Heating Capacity
Minimum Heating Efficiency
Max Allowed Cooling Capacity
Cooling Efficiency
Duct Location/ R-Value
Duct Leakage Testing - If Yes, a
MECH-4A must be submitted
Economizer
Thermostat
Fan Control
Equipment2
Item or System Tags
(i.e. AC-1. RTU-1.HP-1)
Equipment Type4:
Number of Systems
Max Allowed Heating Capacity
Minimum Heating Efficiency
Max Allowed Cooling Capacity
Cooling Efficiency
Duct Location/ R-Value
Duct Leakage Testing - If Yes, a
MECH-4A must be submitted
Economizer
Thermostat
Fan Control
Meets Criteria or I nents
Inspection Criteria Special Feature1
CU-1
Split DX
1
0 Btu/hr
n/a
24,000 Btu/hr
13.0 SEER/10.0 EER
n/a
No
No Economizer
Setback Required D
Constant Volume
Inspection Criteria
D
D
FIELD INSPECTION ENERGY CHECKLIST
Special Feature1
1. Indicate special feature DETAILS on Page 2 of the Inspection Checklist Form.
2. If the Actual installed equipment performance efficiency and capacity is less than the Proposed (from the energy compliance submirtal or from
the building plans) the responsible party shall resubmil energy compliance to include the new changes.
3. For additional detailed discrepancy use Page 2 of the Inspection Checklist Form.
4. Indicate Equipment Type: Gas (Pkg or, Split), VAV, HP (Pkg or split), Hydronic, PTAC, or other.
EnergyPro 5.0 by EnergySoft Usor Number: 3051 RunCode: 201042-24712:54:58 ID:Page 1o(8
CERTIFICATE OF COMPLIANCE and (Part 2 of 5) MECH-1C
FIELD INSPECTION ENERGY CHECKLIST
Project Name
Wells Fargo
Date
2/24/2010
SPECIAL FEATURES INSPECTION CHECKLIST
The local enforcement agency should pay special attention to the items specified in this checklist. These items require
special written justification and documentation, and special verification. The local enforcement agency determines the
adequacy of the justification, and may reject a building or design that otherwise complies based on the adequacy of the
special justification and documentation submitted.
Discrepancies:
EnergyPro 5.0 by EnergySott User Number: 3051 RunCodo: 2010-02-24712:54:58 ID: Page 2 of 8
II
-
w
y
Iog
I
co1I
D
o
I
cUJ
^in•s
^•en
Q.
H
D
CUJ
o
>.oocUJzUJ
ogUJa.
</>
Q
UJ
E•oc
UJo
Z
rf*f
2
a.e
DJ
D
5J
Z
^^r
JjO
o
1
ev
£aa
9 J3l
i ,*u
: u-
5" "5
<u
iu
<f
3
5
<V
I
i
cv
i
1
\
1
3
s
m
•a<
•!t
\I
i«
"till
~5 rat
Q) O^<5
lit
||2^
UJ
^ ^
1*0^ (DJU c 19 C
!J|;
< 2
-HIio'fS cXU.J2 ao
QQ£
isa
|
i•§ia:
.93
UJ
D
D
a
D
_
13
^5
0
D
a
D
a
a
n
D
n
n
D
o
n
a
n
a
a
n
n
D
a
n
n
a
n
a
n
n
a
a
a
n
n
n
a
a
n
n
a
D
n
a
a
n
D
a
n
n
D
D
a
D
p
D
a
o
a
n
n
a
p
a
a
n
p
p
p
p
p
p
p
p
p
p
p
p
p
p
p
p
p
p
p
p
p
p
p
p
p
p
p
p
p
p
p
p
p
p
p
p
p
p
p
p
p
p
p
p
p
p
p
"~~
p
p
CERTIFICATE OF COMPLIANCE (Part 5 of 5)MECH-1C
Project Name
Wells Fargo
Date
2/24/2010
Documentation Author's Declaration Statement
I certify that this Certificate of Compliance documentation is accurate and complete.
Name Signature
Company Bf^n Cox Mechan/ca, ,nc Date 2/24/2010
Address 12-lSS $20 Ap EA#
CEPE#
City/State/Zip Phone -S-7S-7
The Principal Mechanical Designer's Declaration Statement
• 1 am eligible under Division 3 of the California Business and Professions Code to accept responsibility for the mechanical
design.
• This Certificate of Compliance identifies the mechanical features and performance specifications required for compliance
with Title-24, Parts 1 and 6 of the California Code of Regulations.
• The design features represented on this Certificate of Compliance are consistent with the information provided to document
this design on the other applicable compliance forms, worksheets, calculations, plans and specifications submitted to the
enforcement agency for approval with this buiiding permit application.
Name
Company Brian Cox Mechanical, Inc.
Address 12155 K/rWiam Road
City/State/Zip Poway, Ca 92084 858-679-5757
Mandatory Measures
Indicate location on building plans of Note Block for Mandatary Measures.
MECHANICAL COMPLIANCE FORMS & WORKSHEETS (check box If worksheet Is Included)
For detailed instructions on the use of this and all Energy Efficiency Standards compliance forms, please refer to the 2008 Nonresidential Manual.
Note: The Enforcement Agency may require all forms to be incorporated onto the building plans.
El MECH-1C Certificate of Compliance. Required on plans for all submittals.
MECH-2C Mechanical Equipment Summary is required for all submittals.
El MECH-3C Mechanical Ventilation and Reheat is required for ail submittals with mechanical ventilation.
El MECH-4C Fan Power Consumption is required for all prescriptive submittals.
ZnergyPro 5.0 by EnergySoft User Number: 3051 RunCode: 201042-24712:54:5 ID:Page 5 of B
AIR SYSTEM REQUIREMENTS (Part 1 of 2) MECH-2C
Project Name Date
Wells Fargo 2/24/2010
Item or System Tags
(i.e.AC-1,RTU-1.HP-1)
Number of Systems
MANDATORY MEASURES
Heating Equipment Efficiency
Cooling Equipment Efficiency
HVAC Heat Pump Thermostat
Furnace Controls/Thermostat
Natural Ventilation
Mechanical Ventilation
VAV Minimum Position Control
Demand Control Ventilation
Time Control
Setback and Setup Control
Outdoor Damper Control
Isolation Zones
Pipe Insulation
Duct Insulation
PRESCRIPTIVE MEASURES
Calculated Design Heating Load
Proposed Heating Capacity
Calculated Design Cooling Load
Proposed Cooling Capacity
Fan Control
DP Sensor Location
Supply Pressure Reset (DDC only)
Simultaneous Heat/Cool
Economizer
Heat and Cool Air Supply Reset
Electric Resistance Heating'
Air Cooled Chiller Limitation
Duct Leakage Sealing. If Yes, a
MECH-4-A must be submitted
I Indicate Air Systems Type (Central, Single Zone, Packa?
U^lUftUUJUMQEHSI
BBB
J CU-1
I 1
e, VAV, or etc...)
Indicate Page Reference on Plans or Schedule and Indicate the applicable exceptlon(s)
T-24 Sections
112(a)
112(8)
112(b), 112(c)
I12(c). 115(a)
121(b)
121(b)
121 (c)
121(c)
122(e)
122(e)
122fl)
122(Q)
123
124
nto
13.0 SEER n 0.0 EER
n/a
n/a
Ocfm
No
No
Programmable Switch
Setback Required
Auto
n/a
Refrigerant Piping
n/a
144(a & b)
I44(a&b)
144(a&b)
144(a & b)
144(0
144(c)
144(c)
144{d)
144(e)
144(f)
144(g)
144fi)
144(k)
495 Btu/hr
0 Btu/hr
23,497 Btutor
. 21,958 Btufltr
Constant Volume
No
No Economizer
Constant Temp
Constant Temp
No
1 . Total installed capacity (MBtu/hr) of all electric heat on this project exclusive of electric auxiliary heat for heat pumps. If electric heat Is used
explain which exception(s) to §l44(g) apply.
EnergyPro 5.0 by EnergySofi User Number: 3051 RunCode: 201 0-02-24T1 2:54:5 ID: Page 6 of 8
U
o
o
P
L
2C
e
>
<u.REHEAw
2
MECJ2
$m<u
§
o
m
O
os e5
j
UJ
!3S
oi
m
~°m
fl»l
^N.
I
ra5
CD
S
•5
III
0
f>
£
Q
3
S
*
I
i |£
\Jo\i
aCO
is
£Q'DVI5
o<i
o
x"a
£•>
S
o
o
X
S
3
i
§
5
1
H
FAN POWER CONSUMPTION MECH-4C
Project Name Date
Wells Fargo 2/24/2010
NOTE: Provide one copy of this worksheet for each fan system with a total fan system horsepower greater than 25 hp for Constant A
Fan Systems or Variable Air Volume (VAV) Systems when using the Prescriptive Approach. See Power Consumption of fan §1 44(c
A
Fan Description
Supply Fan
B
Design Brake
HP
0.100
C D
Efficiency
Motor
49.0%
Drive
100.0%
E
Number of
Fans
1.0
r Volume (CAV)
i.
F
Peak Watts
BXEX746/
(CXD)
152
TOTALS AND ADJUSTMENTS
FILTER PRESSURE ADJUSTMENT Equation 144-A In §144(c) 1 , TOTA|_ pAN SYSTEM poWER WAm SUM CQ^M p]
2) SUPPLY DESIGN AIRFLOW (CFM)
A) "^!!^^^TliTlTST1Th2?'&<ir 3) TOTAL FAN SYSTEM POWER INDEX (Row I/ Row 2)
pressure drop across the fan (SP() on Line 5. 4) SP.
5) SP,
B) Calculate Fan Adjustment and enter on line 6. 6) Fan Adjustment = 1 -( SP. - 1 ) / SP,
C) Calculate Adjusted Fan Power Index and enter on Row 7 7) ADJUSTED FAN POWER INDEX (Line 3 x Line 6}'
152
710
W/CFM
0.214 W/CFM
1 . TOTAL FAN SYSTEM POWER INDEX or ADJUSTED FAN POWER INDEX must not exceed 0.8 W/CFM for Constant Volume systems or 1 .25
W/CFM for VAV systems.
EnergyPro 5.0 by EnergySoft User Number: 3051 RunCode: 201 0-02-24712:54:5 ID: Page 8 of 8
SAN DIEGO REGIONAL
HAZARDOUS MATERIALS QUESTIONNAIRE
OFFICE USE ONLY
UPFP#
HW
BP DATE
The following questions represent trie facility's activities, NOT the specific project description.
PART I: FIRE DEPARTMENT - HAZARDOUS MATERIALS DIVISION: OCCUPANCY CLASSIFICATION: Indicate by circling the item, whether your business
will use, process, or store any of the following hazardous materials. If any of the items are circled, applicant must contact the Fire Protection Agency with
jurisdiction prior to plan submittal.
5. Organic Peroxides 9.
6. Oxidizers 10.
7. Pyrophorics 1 1 .
8. Unstable Reactives 12.
1. Explosive or Blasting Agents
2. Compressed Gases
3. Flammable/Combustible Liquids
4. Flammable Solids
Water Reactives
Cryogenics
Highly Toxic or Toxic Material
Radioactives
13.Corrosives
Other Health Hazards
me of These.
PART II: SAN DIEGO COUNTY DEPARTMENT OF ENVIRONMENTAL HEALTH - HAZARDOUS MATERIALS DIVISIONS (HMD): If the answer to any of the
questions is yes, applicant must contact the County of San Diego Hazardous Materials Division, 1255 Imperial Avenue, 3™ floor. San Diego, CA 92101.
Call (619)338-2222 prior to the issuance of a building permit. ' ' *-*
FEES ARE REQUIRED.
YES
1. D
2. D
3. D
Expected Date of Occupancy:
D
D
D
ls your business listed on the reverse side of this form? (check all that apply).
Will your business dispose of Hazardous Substances or Medical Waste in any amount?
Will your business store or handle Hazardous Substances in quantities equal to or greater than
55 gallons, 500 pounds, 200 cubic feet, or carcinogens/reproductive toxins in any quantity?
Will your business use an existing or install an underground storage tank?
Will your business store or handle Regulated Substances (CalARP)?
Will your business use or install a Hazardous Waste Tank System (Title 22, Article 10)?
D CalARP Exempt
Date Initials
D CalARP Required
Date Initials
D CalARP Complete
Date Initials
PART III: SAN DIEGO COUNTY AIR POLLUTION CONTROL DISTRICT: If the answer to any of the questions below is yes, applicant must contact the Air
Pollution Control District (APCD), 10124 Old Grove Road, San Diego, CA 92131-1649, telephone (858) 586-2600 prior to the issuance of a building or demolition
permit. Note: if the answer to questions 3 or 4 is yes, applicant must also submit an asbestos notification form to the APCD at least 10 working days prior to
commencing demolition or renovation, except demolition or renovation of residential structures of four units or less. Contact the APCD for more information.
YES
1. D
2. D
3. D
4. D
Will the subject facility or construction activities include operations or equipment that emit or are capable of emitting an air contaminant? (See the
APCD factsheet at http://www.sdapcd.orq/info/facts/permits.pdf. and the list of typical equipment requiring an APCD permit on the reverse side
of this from. Contact APCD if you have any questions).
D (ANSWER ONLY IF QUESTION 1 IS YES) Will the subject facility be located within 1,000 feet of the outer boundary of a school (K through 12)?
. (Public and private schools may be found after search of the California School Directory at http://www.cde.ca.aov/re/sd/: or contact the
f appropriate school district).
D Will there be renovation that involves handling of any friable asbestos materials, or disturbing any material that contains non-friable asbestos?
n Will there be demolition involving the removal of a load supporting structural member?
Briefly describe proposed proje
erein are_true and correct. /
Briefly describe businessactivities:
neriurv thai to the best of my knowledge an
Nam
FOR OFFICIAL USE ONLY:FIRE DEPARTMENT OCCUPANCY CLASSIFICATION:,
BY:DATE:
EXEMPT OR NO FURTHER INFORMATION REQUIRED
COUNTY-HMD APCD
RELEASED FOR BUILDING PERMIT BUT NOT FOR OCCUPANCY
COUNTY-HMD APCD
RELEASED FOR OCCUPANCY
COUNTY-HMD APCD
HM-9171(04/07)County of San Diego - DEH - Hazardous Materials Division
V o
y§ 2o m O
"n 3} fc*O O t&
5 z
0^ g
HBO
•s
If0 n1 I1 S
Dao3n>
i
CM
O O-
0»
O
0
O
:<^
b91
ff