HomeMy WebLinkAbout1815 ASTON AVE; 101; CB991441; PermitCity of Carlsbad
05/26/1999
Job Address:
Permit Type:
Parcel No:
Valuation:
Occupancy Group:
Project Title:
05/26/1999
Commekialllndustrial Permit Permit No: CB991441
Building Inspection Request Line (760) 438-31 01
1815 ASTON AV CBAD St: 101
TI Sub Type: COMM
2121201100 Lot #: 0 Status: ISSUED
20 Reference #: Entered By: DT
CENTEX HOMES SAN DlEGO DIV
TI 17,776 OFFICE AND R&D Issued: 05/26/1999
$560,098.00 Construction Type: VN Applied: 04/13/1999
Plan Approved:
lnsPectAre&ji40 05/26/99 0001 01 02
Applicant: C-mT 33321.13 SUTPHIN ROBERT D
1421 PEGASO ST
ENClNlTAS CA 92024
<LF> ROYAL VlLL
760-599-7525
Plan Check Discount
Strong Motion Fee
Park Fee
LFM Fee
Bridge Fee
BTD #2 Fee
BTD #3 Fee
Renewal Fee $1 11.00
Add'l Renewal Fee $160.00
Other Building Fee $0.00 MECHANICAL TOTAL $129.50
Pot. Water Con. Fee $0.00 Master Drainage Fee: $0.00
Meter Size Sewer Fee: $1 3,772.04
Add'l Pot. Water Con. Fee $0.00 TOTAL PERMIT FEES $34,550.66
A/' D::y?AJ,y97'
Inspector: Clearance:
H,
NOTICE: Please take NOTICE that approval of your project includes the 'Imposilon' of fees, dedca8ons. reservations, or other exactions hereafter coileclveiy
referrec to as 'feeslexactmns.' You have 90 days from the date his permlwas issued to pmtest impnsibn of these feeslexactions. If you protest them. you must
follow the protest procedures setforvl in Government Code Section 66020(a), and file the pmtest and any otter required information with the City Manager for
prmsing in accwdance with Callsbad Municipal Code SWn 3.32.030. Failure to lmely foibw that procedure will bar any sutsequent legal action to attack.
review, set aside, void, or annul tteir imposition.
Yware hereby FURTHERNOTIFIED that yourrightto prdestthespec~edfees/exactonsOOESNOTAPPLYtowa~randsewermo~nfeesandcapactiy
changes. nw planning, zoning. gredirg or other similar applicatbn pmcessing or service fees in mnnecticm with ttis pmM NOR DOES IT APPLY to any
feedexacfionr of which you have P(wiouslv been given a NOTICE similar to this, or as to which he statute of limiiauons has previously otherwise expired.
CITY OF CARLSEAD
2075 Las Palmas Dr., Carlsbad, CA 92009 (760) 438-1161
I FOR OFFICE USE ONLY
PERMIT APPLICATION
CITY OF CARLSBAD BUILDING DEPARTMENT
2075 Las Palmas Dr., Carlsbad CA 92009
(760) 438-1161
PLAN CHECK NO&yy/#f
Plan Ck. Deposit
Validated By
Date
'li
(Sec. 7031.5 Business and Profersionr Code: Any City or County which requires B permit to Construct, alter. improve, demolish or repair any structure. prior to it5 issuance. also requires the applicant for Such permit to file B signed statement that he is IicenSsd pwsuant to the provisions of the Contractor's License Law
IChapter 9, commending with Section 7000 Of Division 3 Of the Business and Professions Codel or that he is exempt therefrom, and the basis for the alleged
exemption. Any violation of Section 7031.5 by my Bpplicmt for B permit subjects the applicant to a civil penalty Of not more than five hu drsd dollars 155001).
Name
State License x 57~0~7 License class
Designer Name I Address City
D. Po- 7 4vrPww, A L 1452 PG&50 57- ew& CA szozu~7 $01594 - 7q~ Telephone I ' Address 'City StateIZip -
City Business License x / 20 Sox 1
StatelZip Telephone
--Ex-T..*s IUF+ 0. pt;trr 7 3uWtiiu. nG%dic,
0 of the work for which this permit is issued.
issued. My worker's compensation insurance carrier and policy number are: -r XN5u,i&d& hFn/rJPt Poiicy NO. TU0 hd Flw Cwxpiration Date lc\w %si@ ~nwrance Company %
ITHIS SECTION NEED NOT BE COMPLETED IF THE PERMIT IS FOR ONE HUNDRED DOLLARS I61001 OR LESS)
to become subject to the Workers' Compensation Laws of California.
I have and will maintain a Certificate Of consent to seif-insure for workers' compensation as provided by Section 3700 of the Labor Code. for the performance
I have and will maintain workers' Compensation. as rsquired by Section 3700 of the Labor Code. for ths performance Of the Work for which this permit is a'
CERTIFICATE OF EXEMPTION: I Certify that in the performance Of the work for which this permit is issued, I shall not employ any person in any manner so as
I, as owner of the property or my employees with wages as their 5018 compensation. will do the work and the strwtuie is not intended or offered for 8.18
(Ssc. 7044, Business and Profsssionr Code: The Contractor's License Law does not apply to an owner of property who builds or improves thereon. and who does
such work himself or through his own employees. provided that Such improvements are not intended or offered for sale. If. however. the building or improvement is
sold within one year of completion. the owner-builder will have the burden of proving that he did not build or improve for the purpose of sale).
I, as owner Of the property. am exclusively contracting with licensed Contractors to Construct the project (Sec. 7044. Business and PrOfesSiOnS Code: The
Contractor's License Law does not apply to an owner of property who builds or improves thereon. and COntraCtS for such projects with contractorlr) licensed
pursuant to the Contractor's License Law).
1.
2.
3.
I am exempt under Section
I personally plan to provide the major labor and materials for construction of the proposed property improvement. YES UNO
I (haw I have not) signed an application for a building permit for the proposed work.
I have contracted With the following person (firm) to provide the proposed Construction (include name I address I phons numbsr I Contractors license number):
Business and Professions Code for this mason:
4.
number I contractors license number):
5.
I plan to provide portions of the work, but I ham hired the following person to coordinate, supervise and provide the major work linclude name I address I phone
I will oravide some Of the work. but i have contracted (hired) the following persons to provide the work indicated (include name I address I phone number I type
of work):
is the applicant or future building occupant required to submit a business plan, acutely hazardous materials registration form or risk management and prevention
program under Sections 25505, 25533 or 25534 of the Prssley-Tanner Hazardous Substance Account Act? YES NO
is the applicant or future building occupant required to obtain B permit from the air pollmion control dinrict or air quality management district? YES NO
Is the facility to be constructed within 1,000 feet of the outer boundary of a School site? YES 0 NO
IF ANY OF THE ANSWERS ARE YES. A FINAL CERTIFICATE OF OCCUPANCY MAV NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR IS MEETING THE
REQUIREMENTS OF THE OFFICE OF EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT.
I Certify that I have read the application and state that the above information io correct and that the information on the plans is accurate. I agree to comply with all
City ordinances and State laws relating to building CWStruCtiOn. I hereby authorize representatives of the CitV of Carlsbad to enter upon the above mentioned
property for inspection purpo~es. I ALSO AGREE TO SAVE, INDEMNIFY AND KEEP HARMLESS THE CITY OF CARLSBAD AGAINST ALL LIABILITIES,
JUDGMENTS. COSTS AND EXPENSES WHICH MAY IN ANY WAV ACCRUE AGAINST SAID CITY IN CONSEQUENCE OF THE GRANTING OF THIS PERMIT.
OSHA An OSHA permit is required for excavations over 5'0. deep and demolition or Construction Of StrUCtUreS over 3 st0ries in height.
EXPIRATION: Every permit issued by the Building Official under the provisions of this Code shall expire by limitation and become null and void if the building or
work authorized by such
or abandoned at any time
APPLICANT'S SIGNATURE
Uniform Building Code).
DATE
WHITE: File YELLOW: Applicant PINK: Finance
City of Carlsbad Inspection Request
For 7/22/99
Permit# CB991441 Inspector Assignment: DH
Title: CENTEX HOMES SAN DIEGO DIV
Description: TI 17,776 OFFICE AND R&D
Type: TI Sub Type: COMM
Job Address: 1815 ASTON AV
Suite: 101 Lot 0
Location:
APPLICANT SUTPHIN ROBERT D
Owner: JETT&JONES L L C <LF> ROYAL VlLL
Remarks:
Phone: 760931 1754
Inspector: fM
Total Time: Requested By: BUZZ
CD Description Act Comments
Entered By: CHRISTINE
19 Final Structural m + 29 Final Plumbing
39 Final Electrical
49 Final Mechanical
Inspection History
Date Description Act lnsp Comments
7/20/99 89 Final Combo NR DH
7/19/99 89 Final Combo NR DH
7/16/99 89 Final Combo NR DH ELECTRICAL RELEASE OK
7/15/99 84 Rough Combo AP DH T-GRID
7/14/99 84 Rough Combo PA DH
7/13/99 84 Rough Combo PA DH T-BAR MARKED ON CARD
7/12/99 14 Frame/Steel/BoltingNelding AP DH
7/9/99 84 Rough Combo PA RB T-BAR RMS 115-119OK
7/7/99 14 Frame/Steel/BoltingNelding AP DH LOC ON CARD
7/7/99 17 Interior LathIDrywall AP DH
7/6/99 17 Interior Lath/Drywall AP DH LOCONCARD
7/6/99 18 Exterior LathlDrywall AP DH
7/2/99 14 Frame/Steel/BoltingNelding AP DH
7/2/99 17 Interior Lath/Drywail AP DH
7/2/99 18 Exterior Lath/Dlywall AP DH
7/1/99 11 Ftg/Foundation/Piers NR DH
7/1/99 17 Interior Lath/Orywali AP DH LOCONPLANS
6/29/99 17 interior Lath/Drwall AP DH LOCATION ON PLANS
- EsGil Corporation
2n Tartnersfiip witfi Government for 'Buicdng Safety
DATE: May 25, 1999
JURIS DlCTlO N: Carlsbad
PLAN CHECK NO.: 99-1441
0 PLAN REVIEWER
0 FILE
SET iV
PROJECT ADDRESS: 1815 Aston Ave., Suite 101
PROJECT NAME: T. I. for Centex Homes
The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
0 The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
0 The plans transmitted herewith have significant deficiencies identified on the enclosed check list
0 The check list transmitted herewith is for your information. The plans are being held at Esgil
and should be corrected and resubmitted for a complete recheck.
Corporation until corrected plans are submitted for recheck.
[7 The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
0 The applicant's copy of the check list has been sent to:
contact person.
0 Esgil Corporation staff did not advise the applicant that the plan check has been completed.
Esgil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: D. Robert Sutphin Telephone #:
Date contacted: 5/25/99 (by: Abe) Fax #:
H REMARKS: Applicant to carry approved set of plans to the city. Ok'd by Mike Peterson on
5/24/99.
Mail Telephone Fax In Person XX
By: Abe Doliente Enclosures:
Esgil Corporation 0 GA 0 MB EJ 0 PC 5/21/99 trnsrntl.do1
9320 Chesapeake Drive, Suite 208 + San Diego, California 92123 + (619) 560-1468 + Fax (619) 560-1576
c - EsGil - Corporation
ln Partnership witti gouernment for !Building Safety
DATE: May 20, 1999
JU Rl SDl CTl ON : Carlsbad
PLAN CHECK NO.: 99-1441
0 APPLICANT
0 FILE
SET: I11
PROJECT ADDRESS: 1815 Aston Ave., Suite 101
PROJECT NAME: T. I. for Centex Homes
The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
The applicant's copy of the check list has been sent to:
D. Robert Sutphin
1421 Pegaso St., Encinitas, CA 92024
Esgil Corporation staff did not advise the applicant that the plan check has been completed.
Esgil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Telephone #:
Date contacted: (by: 1 Fax #:
REMARKS:
Mail Telephone Fax In Person
By: Abe Doliente Enclosures:
Esgil Corporation 0 GA [XI MB EJ 0 PC 511 9/99 tmsrntl.dot
9320 Chesapeake Drive, Suite 208 + San Diego, California 92123 + (619) 560-1468 + Fax (619) 560-1576
Carlsbad 99-1441 111
May 20, 1999
RECHECK PLAN CORRECTION LIST
PROJECT ADDRESS: 1815 Aston Ave., Suite 101 SET: 111
DATE PLAN RECEIVED BY
ESGlL CORPORATION: 5/19/99
DATE RECHECK COMPLETED:
May 20,1999
I REVIEWED BY: Abe Doliente
FOREWORD (PLEASE READ):
This plan review is limited to the technical requirements contained in the Uniform Building Code,
Uniform Plumbing Code, Uniform Mechanical Code, National Electrical Code and state laws
regulating energy conservation, noise attenuation and disabled access. This plan review is
based on regulations enforced by the Building Department. You may have other corrections
based on laws and ordinances enforced by the Planning Department, Engineering Department
or other departments.
The following items listed need clarification, modification or change. All items must be satisfied
before the plans will be in conformance with the cited codes and regulations. Per Sec. 106.4.3,
1994 Uniform Building Code, the approval of the plans does not permit the violation of any
state, county or city law.
A. Please make all corrections on the original tracings and submit two new sets of prints to:
ESGlL CORPORATION.
B. To facilitate rechecking, please identify, next to each item, the sheet of the plans upon
which each correction on this sheet has been made and return this sheet with the
revised plans.
C. The following items have not been resolved from the previous plan reviews. The original
correction number has been given for your reference. In case you did not keep a copy of
the prior correction list, we have enclosed those pages containing the outstanding
corrections. Please contact me if you have any questions regarding these items.
D. Please indicate here if any changes have been made to the plans that are not a result of
corrections from this list. If there are other changes, please briefly describe them and where
they are located on the plans. Have changes been made not resulting from this list?
QYes ONo
Carlsbad 99-1441 I11
May 20, 1999
2. Plans and calculations shall be signed by the California state licensed engineer
or architect where there are structural changes to existing buildings or structural
additions. Please include the California license number, seal, date of license
expiration and date plans are signed. Business and Professions Code. Check
final sets of plans for signatures.
Specify use of the mezzanine. Check for exit and ventilation requirements.
Complete the window types. Window types A, B.
8.
10.
12. Show the required floor joists for the 20 ft span (1-314“ X 16” Microlam @ 16
0. C.) as called out in the structural calculations. Refer to sheet S-1 of the plans.
Note: Revised floor joists are calculated based on 18 ff span. It appears
that the span is more than that. Please check sheet A-3.1 of the plans.
14. Show FB2 (3-1/4”X9-1/2” TSL) as called out in the revised structural
calculations. Refer to sheet S-1 of the plans.
17. Show the required hold downs (HD5A) al grid line 5 as called out in the structural
calculations. lncorporate this on the original plans. This change was only
inked on the blue prints.
19. Please see the following corrections for electrical, plumbing, mechanical and
energy.
The jurisdiction has contracted with Esgil Corporation located at 9320
Chesapeake Drive, Suite 208, San Diego, California 92123; telephone number of
619/560-1468, to perform the plan review for your project. If you have any
questions regarding these plan review items, please contact Abe Doliente at
Esgil Corporation. Thank you.
t ELECTRICAL PLAN REVIEW
t 1993 NEC
t PLAN REVIEWER: MORTEZA BEHESHTI
for each Specify size of secondary ground P
transformer secondary ground system .. 2.
NEC 250-26(~).
3. On single line diagram, identify all equipment as new or existing equipment. ON
FOR PANEL “ACI”
SHEET E-3 CORRECT THE PANEL NAME AND VOLTAGE RATING SHOWN
Carlsbad 99-1441 I11
May 20,1999
4. Indicate the total load demand on the existing service. JUSTIFY THE
ADDITIONAL LOAD ON EXISTING SERVICE.
6. Specifically show the location of all panels and transformers. NEC 1 IO-16,240-
HOWEVER FLOOR PLANS SHOW ONLY (1) PANEL AND (1)
TRANSFORMER.
24,300-21. SINGLE LINE SHOWS (3) PANELS AND (2) TRANSFORMERS,
8. Provide overcurrent protection on the primary and secondary side of
transformers. NEC 450-3 PLEASE SHOW LOCATION AND INDICATE SIZES.
Note: If you have any questions regarding this electrical plan review list please contact
Morteza Beheshti at (619) 560-1468. To speed the review process, note on this
list (or a copy) where the corrected items have been addressed on the plans.
PLUMBING, MECHANICAL AND ENERGY CORRECTIONS
PLAN REVIEWER Eric Jensen
PLUMBING (1994 UNIFORM PLUMBING CODE)
The following items had no response from the initial plan check.
1. Provide complete water line sizing calculations, including the water pressure,
pressure losses, water demands, and developed pipe lengths. UPC Section
610.0
2. Correct the water line sizing calculations to show the maximum velocities of 8
feet per second as per the Uniform Plumbina Code Installation Standard “3 for
copper tubing.
3.
4.
Provide drain, waste and vent plans. (Isometrics - floorplans are incorrect)
Show P & T valve on water heater and detail drain line route from P & T valve to
the exterior. UPC Section 608.5
5. Provide combustion air for fuel burning water heaters as described in
accordance with the Uniform Plumbing Code, Section 507.0
6.
7.
Provide a plumbing fixture schedule.
Detail curbs at entry to handicapped showers or show shower drain 48 inches
from entry or door into the shower stall. UPC Section 410.3
Carlsbad 99-1441 I11
May 20,1999
8. Showers and tub-shower combinations, control valves must be pressure balance
or thermostatic mixing valves. UPC Section 410.7
The waste pipe sizing is incorrect on the floorplans at the water closets. 9.
ENERGY CONS E RVATl 0 N
IO. Provide automatic shut-off controls for lighting as per Title 24, Part 6, Section
131 (d).
The signed ENV-1 form must be imprinted on the plans. 11.
Note: If you have any questions regarding this Plumbing, Mechanical, and Energy plan
review list please contact Eric Jensen at (61 9) 560-1468. To speed the review
process, note on this list (or a copy) where the corrected items have been
addressed on the plans.
EmC o r p o ra t i on -
In Tartncrsfiip witfi Fouernmcnt for gui(ding Safety
DATE: April 22, 1999
JURISDICTION: Carlsbad
PLAN CHECK NO.: 99-1441 SET: I
R@NT
REVIEWER
0 FILE
PROJECT ADDRESS: 1815 Aston Ave., Suite 101
PROJECT NAME: T. I. for Centex Homes
0 The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
The plans transmitted herewith have significant deficiencies identified on the enclosed check list
The check list transmitted herewith is for your information. The plans are being held at Esgil
0 The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
The applicant's copy of the check list has been sent to:
and should be corrected and resubmitted for a complete recheck.
Corporation until corrected plans are submitted for recheck.
contact person.
D. Robert Sutphin
1421 Pegaso St., Encinitas, CA 92024
[XI Esgil Corporation staff did not advise the applicant that the.plan check has been completed.
0 Esgil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Telephone #:
Date contacted: (by: ) Fax #:
Mail Telephone Fax In Person 0 REMARKS:
By: Abe Doliente Enclosures:
Esgil Corporation 0 GA MB EJ PC 411 5/99 trnsmtl.dot
9320 Chesapeake Drive, Suite 208 San Diego, California 92123 (619) 560-1468 Fax (619) 560-1576
Carlsbad 99-1441
April 22, 1999
PLAN REVIEW CORRECTION LIST
TENANT IMPROVEMENTS
PLAN CHECK NO.: 99-1441 JURISDICTION: Carlsbad
I/TYPE OF CONSTRUCTION: V-N ACTUAL AREA: 17,776 SF
ALLOWABLE FLOOR AREA: Existing STORIES: 1 (existing) + second story addn
HEIGHT:
SPRINKLERS?: Yes
REMARKS:
DATE PLANS RECEIVED BY
JURISDICTION:
OCCUPANT LOAD: 178 + occ. Load from
Second story.
DATE PLANS RECEIVED BY
ESGlL CORPORATION: 4/15/99
DATE INITIAL PLAN REVIEW
COMPLETED: April 22, 1999
PLAN REVIEWER: Abe Doliente
FOREWORD (PLEASE READ):
This plan review is limited to the technical requirements contained in the Uniform Building Code,
Uniform Plumbing Code, Uniform Mechanical Code, National Electrical Code and state laws
regulating energy conservation. noise attenuation and access for the disabled. This plan review
is based on regulations enforced by the Building Department. You may have other corrections
based on laws and ordinances enforced by the Planning Department, Engineering Department,
Fire Department or other departments. Clearance from those departments may be required
prior to the issuance of a building permit.
Code sections cited are based on the 1994 UBC.
The following items listed need clarification, modification or change. All items must be satisfied
before the plans will be in conformance with the cited codes and regulations. Per Sec. 106.4.3,
1994 Uniform Building Code, the approval of the plans does not permit the violation of any
state, county or city law.
To speed UD the recheck process, please note on this list (or a copvl where each
correction item has been addressed, i.e., plan sheet number. specification section. etc.
Be sure to enclose the marked up list when vou submit the revised plans.
LIST NO. 40, TENANT IMPROVEMENTS WITHOUT SPECIFIC ENERGY DATA OR POLICY SUPPLEMENTS (1994UBC) tifom.dot
Carlsbad 99-1441
April 22, 1999
1.
2.
3.
4.
5.
6.
7.
Please make all corrections on the original tracings and submit two new sets of
prints, to:
Esgil Corporation, 9320 Chesapeake Drive, Suite #208, San Diego, CA 92123,
(619) 560-1468 or to the jurisdiction's building department.
Plans and calculations shall be signed by the California state licensed engineer
or architect where there are structural changes to existing buildings or structural
additions. Please include the California license number, seal, date of license
expiration and date plans are signed. Business and Professions Code.
Indicate the use of all spaces adjacent to the area being remodeled or improved.
This refers to the space east of the T. I.
Identify existing walls to be removed, existing walls to remain and proposed new
walls. Identify bearing walls, non-bearing walls, and shear walls.
The tenant space and new andlor existing facilities serving the remodeled area
must be accessible to and functional for the physically disabled. Are sanitary
facilities existing.This will have to be field verified.
Provide a revised exit analysis Dlan. It appears that the occupant loads of the
research areas are not correct. Please justify.
Corridors serving 30 or more occupants shall have walls and ceilings of one-hour
construction. Show compliance or clearly show on plans which of the following
exceptions has been satisfied:
a) Corridor walls and ceilings need not be of fire-resistive construction within
office spaces having an occupant load of 100 or less when the entire story
in which the space is located is equipped, with an automatic sprinkler
system throughout and an automatic smoke-detection system is installed
within the corridor. The actuation of any detector shall activate alarms
audible in all areas served by the corridor.
Within office spaces occupied by a single tenant, partial'height partitions
which form corridors and which do not exceed 6 feet in height need not be
fire resistive, provided they are constructed in accordance with Section
601.5 and are not more than three fourths of the floor-to-ceiling height.
Section 1005.7.
Corridor walls and ceilings need not be of fire-resistive construction within
office spaces having an occupant load of 100 or less when the building in
which the space is located is equipped with an automatic sprinkler system
throughout. Section 1005.7.
b)
c)
Carlsbad 99-1441
April 22, 1999
CITY OF CARLSBAD SUPPLEMENT
1.
8.
9.
10.
11.
12.
13.
14.
15.
16.
Please make all corrections on the original tracings, as requested in the correction
list.
Submit three sets of plans for commerciallindustrial projects. For expeditious
processing, corrected sets can be submitted in one of two ways:
1. Deliver all corrected sets of plans and calculationslreports directly to the
City of Carlsbad Building Department, 2075 Las Palmas Drive, Carlsbad, CA
92009, (760) 438-1 161. The City will route the plans to EsGil Corporation and the
Carlsbad Planning, Engineering and Fire Departments.
2. Bring one corrected set of plans and calculationslreports to EsGil
Corporation, 9320 Chesapeake Drive, Suite 208, San Diego, CA 92123, (619)
560-1468. Deliver all remaining sets of plans and calculationslreports directly to
the City of Carlsbad Building Department for routing to their Planning, Engineering
and Fire Departments.
NOTE: Plans that are submitted directly to EsGil Corporation only will not
be reviewed by the City Planning, Engineering and Fire Departments until review
by EsGil Corporation is complete.
MISCELLANEOUS
Provide a floor plan of the second floor addition. Specify use of this. Check for
exit and ventilation requirements.
To avoid confusion, make the grid lines on sheet S-I of the plans agree with the
architectural plans.
Complete the window and door types.
Windows or glazing within 24” of the door must be safety glazing.
Show the required floor joists for the 20 ft span (1-3l4” X 16” Microlam @ 16”
0. C.) as called out in the structural calculations. Refer to sheet S-I of the plans.
Show HDR 2 (1-3/4 X 14” Microlam) as called out in the structural calculations.
Refer to sheet S-I of the plans.
Show FB2 (1-314 X 9-112” Microlam as called out in the structural calculations.
Refer to sheet S-I of the plans.
Show the required 22 ft. of shear wall type 2 at grid line C as called out in the
structural calculations. Refer to sheet S-I of the plans.
Show the required 14 ft. of shear wall type 2 at grid line 7 as called out in the
structural calculations. Refer to sheet S-I of the plans.
Carlsbad 99-1441
AprU 22. 1999
17. , -~- Show the required hold downs (HDSA) al grid line 5 as called out in the structural
calculations.
18.
19.
20.
21.
It would be nice if the structural calculations were sequentially numbered for
easy reference.
Please see the following corrections for electrical, plumbing, mechanical and
energy.
To speed up the review process, note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet, note or detail number,
calculation page, etc.
Please indicate here if any changes have been made to the plans that are not a
result of corrections from this list. If there are other changes, please briefly
describe them and where they are located in the plans.
Have changes been made to the plans not resulting from this correction list?
Please indicate:
Yes 0 No 0
The jurisdiction has contracted with Esgil Corporation located at 9320
Chesapeake Drive, Suite 208, San Diego, California 92123; telephone number of
619/560-1468, to perform the plan review for your project. If you have any
questions regarding these plan review items, please contact Abe Doliente at
Esgil Corporation. Thank you.
+ ELECTRICAL PLAN REVIEW + 1993NEC I
+ PLAN REVIEWER: MORTEZA BEHESHTI
1.
2.
Specify the wire type (AL or CU) and insulation (i.e. THWN). NEC 310.
Specify size of secondary ground and the "nearest electrode" used for each
transformer secondary ground system (i.e., building steel, cold water pipe). NEC
250-26(~).
3.
4.
5.
On single line diagram, identify all equipment as new or existing equipment.
Indicate the total load demand on the existing service.
Specify the wiring method you intend to use for this project (i.e., EMT, Metal
Flex, NMC etc.).
Carlsbad 99-1441
April 22, 1999
6. Specifically show the location of all panels and transformers. NEC 1 IO-16,240-
24,300-21.
7.
8.
Provide the required working space about electrical equipment. NEC 110-16.
Provide overcurrent protection on the primary and secondary side of
transformers. NEC 450-3
9. Provide GFI protected receptacle(s) within 25 feet of HVAC equipment. NEC
210-8(b)2 & 210-63
Note: If you have any questions regarding this electrical plan review list please contact
Morteza Beheshti at (619) 560-1468. To speed the review process, note on this
list (or a copy) where the corrected items have been addressed on the plans.
PLUMBING, MECHANICAL AND ENERGY CORRECTIONS
PLAN REVIEWER Eric Jensen
1.
2.
3.
4.
5.
6.
7.
PLUMBING (1994 UNIFORM PLUMBING CODE)
Provide complete water line sizing calculations, including the water pressure,
pressure losses, water demands, and developed pipe lengths. UPC Section
610.0
Correct the water line sizing calculations to show the maximum velocities of 8
feet per second as per the Uniform Plumbing Code Installation Standard "3 for
copper tubing.
Provide drain, waste and vent plans.
Show 1/4 inch per 12 inch slope on drain and waste lines. UPC Section 708.0
Show P & T valve on water heater and detail drain line route from P & T valve to
the exterior. UPC Section 608.5
Provide combustion air for fuel burning water heaters as described in
accordance with the Uniform Plumbing Code, Section 507.0
Provide a plumbing fixture schedule.
Carlsbad 99-1441
April 22. 1999
8.
9.
IO.
11.
12.
13.
14.
15.
Deiail curbs at entry to handicapped showers or show shower drain 48 inches
from entry or door into the shower stall. UPC Section 410.3
Showers and tub-shower combinations, control valves must be pressure balance
or thermostatic mixing valves. UPC Section 410.7
The waste pipe sizing is incorrect on the floorplans at the water closets.
MECHANICAL (1994 UNIFORM MECHANICAL CODE)
Detail the required roof access ladder to roof mounted HVAC equipment. UMC
321.8
HPIO is missing the duct detector symbol.
ENERGY CONSERVATION
On the plans clearly show the wall and roof insulation locations, thickness, and
R-values, as per the energy design.
Provide automatic shut-off controls for lighting as per Title 24, Part 6, Section
131 (d).
The signed ENV-1 form must be imprinted on the plans.
Note: If you have any questions regarding this Plumbing, Mechanical, and Energy plan
review list please contact Eric Jensen at (619) 560-1468. To speed the review
process, note on this list (or a copy) where the corrected items have been
addressed on the plans.
Carlsbad 99-1441
April 22, 1999
Air Conditioning
Fire Sprinklers
TOTAL VALUE
VALUATION AND PLAN CHECK FEE
560,098
JURISDICTION: Carlsbad PLAN CHECK NO.: 99-1441
PREPARED BY: Abe Doliente
BUILDING ADDRESS: 1815 Aston Ave., Suite 101
DATE: April 22, 1999
BUILDING OCCUPANCY: B TYPE OF CONSTRUCTION: V-N
[XI 1994 UBC Building Permit Fee 0 Bldg. Permit Fee by ordinance: $ 2,202.55
[XI 1994 UBC Plan Check Fee 0 Plan Check Fee by ordinance: $ 1,431.66
Type of Review: [XI Complete Review 0 Structural Only 0 Hourly
0 Repetitive Fee Applicable 0 Other:
Esgil Plan Review Fee: $ 1,145.33
Comments:
Sheet 1 of 1
macvalue.dac 5196
Pl.ANNING/ENGINEERING APPROVALS
RESIDENTIAL TENANT IMPROVEMENT
RESIDENTIAL ADDITION MINOR PLAZA CAMtNO REAL (<$lO,WhW)
CARLSBAD COMPANY STORES
VILLAGE FAlRE
COMPLETE OFFICE BUILDING
OTHER
PLANNER DATE
r
ENGINEERING DEPARTMENT
FEE CALCULATION WORKSHEET
stimate based on unconfirmed information from applicant.
Calculation based on building plancheck plan submittal.
Address: /63 &e /O/ Bldg. Permit No. c8 ?93/S/y/
Prepared by: Date: y/&/SS Checked by: Date:
I.
Sq. Ft./Units: EDU's: 4. 7/
Types of Use: Sq. Ft./Units: EDU's:
for all uses.
Sq. Ft./Units: ADT's: &!D
Types of Use: Sq. Ft./Units: ADT's:
FEES REQUIRED:
WITHIN CFD: dbridge & thoroughfare fee in District #1, reduced Traffic Impact Fee) 0 NO fi 1. PARK-IN-LIEU FEE PARK AREA & #:
FEEIUNIT: X NO. UNITS:
&TRAFFIC IMPACT FEE
2 FEEIADT: do I
kec do( X-'f OlS? #2 - DIST. #3 __
ADT'sNNITS:
&. BRIDGE AND
ADT'slUNITS: X FEE/ADT: =s ,pf
UNITISQ.FT.: X FEE/SQ.FT./UNIT: =$ {m.
EDU's: 4- 7/ X FEEIEDU: /gs't/ - -$ R733d.3Y
k4. FACILITIES MANAGEMENT FEE ZONE:
Id SEWER FEE
PERMIT No.
BENEFIT AREA f DRAINAGE BASIN:
€Duns: 4. ?/ X FEEIEDU:/O 7 0 =$ -5n.?9.7
&6. SEWER LATERAL 1$2,500) =$ ,& & 7. DRAINAGE FEES PLDA HIGH /LOW
ACRES: X FEE/AC: =$ ,kf
TOTAL OF ABOVE FEES*: $ *w *NOTE: This calculation sheet is NOT a complete list of all fees which may be due.
Dedications and Improvements may also be required with Building Permits.
P:UIOCSUIISFORMS\N CMCUUnON WORKSHEET REV 7/13/98
.s 2 ; 0 4
0 Coastal Zone AssessmentlCompliance d
Type of Project & Use: 1. Net Project Density: DU/AC
Zoning: General Plan: Facilities Management Zone:
CFD lin/niit\ # Date of participation: Remaining net dev acres: Circle One -
Project site located in Coastal Zone? YES- NOY
CA Coastal Commission Authority?
If California Coastal Commission Authority: Contact them at - 31 11 Carnino Del Rio North, Suite
200, San Diego CA 92108-1725; (619) 521-8036
Determine status (Coastal Permit Required or Exempt):
Coastal Permit Determination Form already completed?
If NO, complete Coastal Permit Determination Form now.
Coastal Permit Determination Log #:
YES- NO-
YES- NO
Follow-Up Actions:
1) Stamp Building Plans as "Exempt" or "Coastal Permit Required" (at minimum
Floor Plans).
2) Complete Coastal Permit Determination Log as needed.
- lnclusionary Housing Fee required: YES __ NO
(Effective date of lnclusionary Housing Ordinance . May 21, 1993.)
- NO Data Entry Completed? YES - (AIPlDs, Activity Maintenance, enter CB#, toolbar, Screens, Housing Fees, Construct Housing YIN, Enter Fee. UPDATE11
Site Plan: 0 0 1. Provide a fully dimensional site plan drawn to scale. Show: North arrow,
property lines, easements, existing and proposed structures, streets, existing
street improvements, right-of-way width, dimensional setbacks and existing
topographical lines.
2. Provide legal description of property and assessor's parcel number.
Zoning: - ,@ 0 0 1. Setbacks:
Front:
Interior Side:
Street Side:
Rear:
Required Shown
Required Shown
Required Shown
Required Shown
$n 2. Accessory structure setbacks:
Front: Required Shown
Interior Side: Required Shown
Street Side: Required Shown
Rear: Required Shown
Structure separation: Required Shown
Fo 3. Lot Coverage: Required Shown
p'm 0 4. Height: Required Shown a@ 5. Parking: Spaces Required Shown
Guest Spaces Required Shown
shoo &$;at tt OF spces. ?au;&c pdbnI\s SUM- 4- wan sCce.
@ 0 Additional Comments ?mu; de a in& o\an ~hn w:n7 *, b,& 30
I-, -F 001, eeu~~~. I &[ OF 'e4"., *a. VlUCh l.rc sdee-h
SUJ a x
"
E--. i)l il
OK TO ISSUE AND ENTERED APPROVAL INTO COMPUTER $. I
Carlsbad Fire Department 990151
2560 Orion Way Fire Prevention
Carlsbad, CA 92008 (760) 931-2121 + Plan Review Requirements Category: Building Plan
Date of Report: 04/22/1999 Reviewed by:
Name: Sutphin, Robert
Address: 1421 Pegaso St
City, State: Encinitas CA 92024
Job#: 990151 Plan Checker:
Job Name: Centex Homes CB991441
Job Address: 1815 Aston Av Ste. or Bldg. No. 101
Approved The item you have submitted for review has been approved. The approval is
based on plans, information and l or specifications provided in your submittal;
therefore any changes to these items after this date, including field
modifications, must be reviewed by this office to insure continued conformance
with applicable codes and standards. Please review carefully all comments
attached as failure to comply with instructions in this report can result in
suspension of permit to construct or install improvements.
!8
0 Approved
Subject to
The item you have submitted for review has been approved subject to the
attached conditions. The approval is based on plans, information andlor
specifications provided in your submittal. Please review carefully all comments
attached, as failure to comply with instructions in this report can result in
suspension of permit to construct or install improvements. Please resubmit to
this office the necessary plans and I or specifications required to indicate
compliance with applicable codes and standards.
0 Incomplete The item you have submitted for review is incomplete. At this time, this office
cannot adequately conduct a review to determine compliance with the
applicable codes and I or standards. Please review carefully all comments
attached. Please resubmit the necessary plans and l or specifications to this
office for review and approval.
Review 1 st 2nd 3rd Other Agency ID
FD Job # 990151 FD File #
STRUCTURAL CALCULATIONS
FOR
Centex Homes, MczLanine
1815 Astoo Avq Suite 101, Carlsbad, Cali.
CLIENT:
DATE ISSUED: ADril 10. 1999
D. Robert Sutphin. Desian GrouD
DESIGN LOADS
FLOOR
DEAD LOAD:
FLOORING 2.0 SHEATHING 2.0
JOISTS .................................................................................................... 3.5
DRYWALL 2.5
TOTAL DEAD LOAD 15.0PSF
LIVE LOAD (LT. STORAGE USE PER UBC 1994 CHAPTER 16) 125.0 PSF
LIVE LOAD (EXTERIOR DECK -WHERE INDICATED - 60 PSF)
............................................................................................... .............................................................................................
............................................................................................... OTHER (ELEC.,ME~,MISC.) ................................................................. 5.0
TOTALLOAD 140 PSF
INTERIOR WALL
STLJDS 2.0 PSF
DRYWALL 6.5 PSF
TOTALLOAD 10.0 PSF
.......................................................................................... ................................................................................... OTHER wc., MEW., MISC.) ..................................................... 1.5 PSF
FLOOR JOIST DESIGN
W = 15 PSF+ 125 = 14OPSF= 140X 1.33 = 186PLF USE TJJl%X11% @16"O.C.
SPAN=12'-0".
SPAN= 18'-0" /
W = 15 PSF+ 125 PSF= 140
USE 140 X 1.33 = 186F'I.F MICRO LAM 1 'A X 14" @ 16 0.c
I
FLOOR BEAM DESIGN
HDR 1 SPAN = 10' - 0"
W = 140 PSFX 12'X !4 = 84OpLF
USE 3 %" X 11" TSL
HDR 2 SPAN = 3'0" Ww= 140 PSF X 21' X %= 1470 PLF
USE3WX 9%"TSL
HDR 3 SPAN = 8' -0"
W = 140PSFX 1.33 X 1.2 = 93 PZF
USE 3 %" X 9 %" TSL
F.B. 1 sPAN=lT-O" 2.5 k FROM F.B.2
M = 2.SK X 7 X 10 + 17 = 10.3 'x
USE 3 %" X 14" TSL Mu= 12.13 lX
F.B. 2 SPAN = 7'4" W = 14s PSFX S ' X%= 362,s PZF
USE 3 %" X9 Vi'' TSL Wu= 695 PLF
LATEW ANAYLSIS
SEISMIC LOAD
SEISMIC ZQNE 4 Z = 0.4
1 = I.O(STANDAFUJ OCCUPANY) C = 2.75
W = TOTAL SEISMIC DEAD LOAD RW =
FLOORWEIGHT
DIAPHRAGM = 1 = (15.0 F‘SF + .25 X 125) (12’ X 42’) = 23.3 K WALLWEIGHT(TRTBUTARYToDIApHRAGM)=(1OF’S~(4.5’X42.0’)= 1.9K TOTAL WEIGH TRIBUTARY TO DIAPHRAGM = 25.2 K
FLOOR WEIGHT
DIAPHRAGM = 2 = 15.0 PSF + .25 X 125) (21.0’ X 44.0’) = 42.7K
WALL WEIGHT (TRIBUTARY TO DIAPHRAGM) = (10 PSF) (4.5’X44’) = 2.OK 44.7 K
TOTAL. DEAD LOAD
SEISMICBASESHEARV=O,183W= DIAPH 1=.183X25.2K=4.61K DIApH2 = ,183 X44.7 = 8.2 K
LATERAL ANAYLSIS
SEISMIC LOAD
SEISMIC ZONE 4 Z = 0.4 I = 1.0 (STANDM OCCUPANCY) C = 2.75 W = TOTAL SEISMIC DEAD LOAD
RW=
SEISMIC DEAD LOAD
FLOOR WEIGHT
DIAPHRAGM = 3 = (I5 PSF + .25 X 125) (12’ X 5’) = 8.8 K WALL WEIGHT (TRIBUTARY TO DIAPHRAGM) = (10 PSQ(4.5’ X 16.0’) = .72K
TOTAL WEIGH TRIBUTARY TO DIAPHRAGM = 9.6 K
FLOOR WEIGHT
DIAPHRAGM =
WALL WEIGHT (TRIBUTARY TO DIAPHRAGM ) = TOTAL WEIGHT TRIBUTARY TO DIAPHRAGM =
TOTAL DEAD LOAD
SEISMICBASESHEARV=O.l83W= DIAPH3=.183X9,6K= 1.8K
LArrrW ANAYLSIS COW.
DAIPH. 1
LONG DIRECTION
W = 4.61K + 12 = 384 PLF
384 #/1
A I L . c'
Rf=2304 ' 12'4" 2304
V DIAPH = 2304 + 42 = 55 PSF llOx/l
[A A L1 TRANS. DIRECTION ,
W=4.61K+ 42=110PLF R= 242W 42'0"
VDJAFW = 2420 + 12 = 201
USE % " P.W. W/10 a @ 6.647
DIAPH. 2 44x21
LO". DIRECTTON
W = 8.2 +21= 390PLF
VDIAPH= 4095+44=99PSF
TRAMSV. DIRECTION
W = 8.6 K + 44 = 195 PLF
VDJAFW= 429O+ 21 =204PsF
1105 3"P.W. W/lOa@6.6.12
L L I R= 4095 21'
19s
T -L I R=4590# 21'
LATERAL CONT.
DIM. 3 12' X 16'
LONG DIFECTION
W=1.8K+12=15OPLF
VDIAPH= 900+ 16= 56PSF
TRANS. DIRECTION
W = 1.8K+ 16- 112PL.F
150 #/1 [. A
R= 900
12.c
112 #/1 l.t------4' R=8% 16'4"
VDIAF" = 8% + 12 = 74 F'SF
USE " P.W. Wl 10 a tiJ 6.6.12
SHEAR WW DESIGN
LINEA8rB DIAPH3
L = 810”
V=900+8=112 #/I USE S. W 1 318- P.W W/
8d @ 6.6.12 GOOD FOR 230 #/1
UES 1
NO UPLIFT
LINE A DIAF” 2 L= 24’ - 0”
V = 4095 + 24‘ = 170 #/1 NO UPLIFT
LINE c
DIAPH1&2
L=44
V = (2420 + 4095) + 22’ = 2% # NO UPLIFT
LINE D DIAPH 1
V = 2420 + 12 = 201 #I1 USE 1
USE 2
CK UPLIFT h& = 2420 X 9 = 21780 ’‘
MRBs = (10x9 + 1.33 + 2 X 140)X 12X6= 13176
UPL.IFT = (21780 - 13176) + 12 = 719#
SHEAR WALL DESIGN CONT.
DIAPH. 1852
L = 42’
V= (2304 + 195 X 17) +42 = 134 #1
NO UPLIFT
LINE 7
DIAF” 2
L=14’-0”
V=195 X (23 X %) + 14 = 160 #/1
& = 2242 X 9 = 20178
Mm = (10 X 9 + 140 X 1.33 X 5)X 14 X7 = 17943
UPLIFT = (20178 - 17943) + 14’ = 159 #
USE A
USE A
SHEAR WALL DESIGN COW.
LINElBt2
DIAPH. 3 L=8'
V= 8% + 8'
= 112 #/1 NO UPLlFT
LINE 3 DIAPH 2
L=8'
V= 195 w/1 X4/2 +8= 50 #/1
LINE 4
DlAF"2
L=10'
V= 195 XU2 + 10 = 78 #/1
LINE 5
DIAPHlB2
L= 12' TWO C' SkCTIONS
V= (2304 + 8 X 185) + 12 = 322 #/1
USE
USE
USE
USE S.W 4 3/8" P.W W/ 8d 4.4.12 GOOD FOR 360 #/1
CHECKUPLIFT
h& = 3864 X 9 = 34776'4
MRas = (140 X6 + 10 X 9) X 6 X 3 = 16740
uPLlFT~(34776-16740)+6'~3006#
USE HD5
~ - ... -.
Design Data - Allwable Stresses __
-: 5.50 in fc: PariIlil 11 kain : 'ZOO xi G5 psi
I?ae Owatiw Factor : 1.00
: :130000 Dsi :;a*::: !4:d31us
ioial loiuin Ht : 9.00 it !e far X-l !xis Axial Leads 2.00 it ~e i:r i-7 :xis Axial Leaas 0.00 it
:i far X-Y 3inding : ?.OD it
Deaa Live Short ieri
0.00 in (along "depth" axis)
Co'lunn !isih
::'urn* dI$th : 3.58 :n :¶; denojng _. . .
Applied loads
Lxial Load ;iso.o t 3000.0 I 2.; # ... Eccentricity iransverse Holnent 3 in4 8 in-# 0 in-#
Ec:eniric Side toad : 01 01 01
. . . .E::entric::y 0.30 in 0.00 in 0.130 in .... Distance above Base : 0.00 it 0.00 it 0.00 in Calculated loments
Eouivaient Load 1 Hid-He?ght 01 Ot Ot
Side Load bent 0 in-# 0 in4 8 in4
tax. Design noment : 0 in4 0 in4 0 in-t
Actual Lxial Stress : 493.5 psi 4l5.S psi 77.9 psi Ailowable " " 793.: psi 193.3 psi !93.3 Dsi
Lctual Bending Stress : 0.0 csi 8.0 psi 0.0 psi
Allonable " " 920.4 DSI 810.4 Psi 820.4 psi
Stress Interaction Value 0.62i -OK- 0.622 -OK- 0.0?8 -0X-
Design Swiary DL+LL SLtLLtSI DLtSi
Axial isad .. .L;centri:jty Transverse t4onent
Ec:eniric Sibe Loa6 : .... F:c+niricitf . , , .Disrance above Sase :
Ewivalent totd @ Hid-deiakt
Side toad konent Max. Orsian Moment
.. :'Ye . .. O€dO
.X.J U ::3.0 il 0.33 in iajm? ":ioih' axis'i J in-d 0 in-1 01 01
...
3.83 in 1.30 in 0.00 it 0.00 !i Calculated llorents 18 !# 0 in-li 0 in-# 0 in-U 0 in-k
30 0 in4 0 in4
Tile 24 Report for:
CentexHomes -TI 1815Aston Cadsbad, CA 92008
Project Designer:
D. Robert Sutphin Design Group 3252 Holiday Court ste 101 La Jolla, CA 92030 61 9.297.8066
Report Prepared By:
Brian Bannock-GM PACIFIC COAST DESIGNS 161 1 So. Rancho Santa Fe Rd., Suite F2 SAN MARCOS, CA 9206S5157 (760) 47 1 -9000
Job Number:
PCD #99170
Date:
411 2/99
4
City of Carlsbad
09/10/1999 Plan Check Revision Permit No:PCR99168 Building Inspection Request Line (760) 438-31 01
Job Address: 1815ASTONAVCBADSt: 101
Permit Type: PCR Status: ISSUED
Parcel No: 2121201100 Lot #: 0 Applied: 07/08/1999
Valuation: $0.00 Construction Type: NEW Entered By: MDP
Reference #: CB99-1441 Plan Approved: 07/26/1999
Issued: 09/10/1999
Project Title: CENTEX HOMES Inspect Area: STRUCTURAL REVISIONS FOR FOLDING PARTIONS
Applicant:
SUTPHIN ROBERT > ROYAL VlLL
1421 PEGASO ST
ENClNlTAS CA 92009
760-599-7525
Plan Check Revision Fee
FINAL APPROVAL
Inspector: Date: Clearance:
NOTICE Please take NOTICE that approval of your project includes the'lmpilon' of fees, dedcations, reservations, or other exacfions hereafler collectively referred to as "feedexadmns: You have 90 days from the date this perml was issued to protest imposition of these feeslexactions. If you protest them, you must
follow the protest procedures set forth in Government Code Secljon 66020(a), and file the protest and any other required inforrnaBon with the City Manager for
processing in amordance wlh Callsbad Municipal Code Seaon 3.32.030. Failure to lmelyfollow that pmcedure will bar any subsequent legal action to attack
review, set aside, void, or annul their imposilon.
You are hereby FURTHER NOTIFIED that your right to protest the speck fedexadions DOES NOT APPLY to water and sewer wnnection fees and capactiy
changes, nor planning, zoning, grading or other similar applicakn pmcessing or service fees in connection with this project NOR DOES IT APPLY to any feedexadons of which you have previously been given a NOTICE similar to this, or as to which the statute of iimitations has previously othewise expired.
CITY OF CARLSBAD
2075 Las Palmas Dr., Carlsbad, CA 92009 (760) 438-1161
PERMIT APPLICATION
CITY OF CARLSBAD BUILDING DEPARTMENT
2075 Las Palmas Dr., Carlsbad CA 92009
(760) 438-1161 a?-
FOR OFFICE USE OF cr
PLAN CHECK NO. kcI -@
EST. VAL.
Pian Ck. Deposit
Validated By
Date
L' 1. PROJECT INFORMATION
Address linclude BldgISuits XI
I
($15 A'X60 A08 Sue I&\ Business Name (at thm address1
Legal Description Lot No Subdwirton NamslNumbar Unit No Phase NO TODI X of ""lrr
%I?AJLTWL wAd&G +I& F~~DII&, PA ,u<i Tr d ASSBSSOI'I Parcel X Existing Use Ropoied Use
Description of Work SO FT #Of Storla X at Bedrooms I of Bathrooms
0. lzpeem 5dPW 14 , AY 2/ rn &so 5T (760) 549-7525' v 2. CONTACT PERSON IH dmmm tmm appliurnl E&U&?34 ,c#
Statslzlp ' Name Addrsrr CltV 1
3. APPLICANT &ranor Agent for Comnnor Owner 17 Agent lor Owner
Name Address City StatelZip Telephone X
4. PROPERTY OWNER
Name Address city StataIZip Telephone X
6. CONTRACTOR. COMPANY NAME
fsec. 7031.5 Business and Professions Coda: Any City or County Which requires I permit to COnltrUCt. alter, improve. demolish or repair any strunure, prior to its
ISSY~C~. also requires the epplicmt for such permit to file a signed statement that ha is licensed pursuant to the provisions of the COntraROr'S License Law
(Chapter 9. commendmg Wlth Section 7000 of Division 3 of the BUSIMSJ and Rofarrions Codel Or that he is exempt therefrom. and the barfs for tho alleged
exemption. Any violation ot Section 7031.5 by any applicant for a permit SubjeRS the applicant to a civil penalty of not mors than five hundred dollars l850011.
Name Addieis City StatelZip Telephone X
state LIC*".B t License C:larr City Burinerr License X
Designer Name Address City StatelZip Telephone
state LIceme t
6. WORKERS' COMPENSATION
Workers' Compensation Declaration: I hereby affirm under penalty of perjury one of the following declarations:
0
of the work for Which this permit I$ issued.
wued. My worker's compensation insurance carrrer and po11cy number are:
Insurance Company Policv NO. Expiration Date
(THIS SECTION NEED NOT BE COMPLETED IF THE PERMIT IS FOR ONE HUNDRED DOLLARS l8lOOl OR LESS1
CERTIFICATE OF EXEMPTION: I Certify that in the performance of the work for which this Permit is issued. I shall not emplw my person on any manner so as
10 become SubpR to the Workers' Companaatlon Laws Of Cslitarnla.
WARNING: Failure IO secure workers' Compe1uation coverage is mhwhd. and shall subion an employer 10 criminal pnahies and civil finer up lo OM hundred
Ihouimd dollars f8100.0001. in addition Io the cost of comp.(uation. darn-. u pmv*d for in Saclion 3706 of the hbor coda. inl.ns1 and amnmy's fns.
SiGNATURE DATE
7. OWNER-BUILDER DECLARATION
i hereby affirm that I am exempt from the COnmROr's License Law for the tollowing reason:
0 I, as owner Of the property or my employees With wages as their sole compensation. will do the work and tho structure is not intended or offemd for sale
1Ses. 7044, B~siness and Profasrianr Code: The Contractor's LIC~IISO Law does not apply to an owner of PIOPenv who builds 01 Improver thereon. and who doer
such work himself or through his awn employees. provided that such improvements are not intended or offered for sale. If. however. the building or improvement is
sold within one year Of Completion. the Owner-builder will have the burden of proving that he did not build 01 improve for the purpose of salei.
I. as owner of the propeny, am exdusiveIy contracting with licensed ContraCtDls to Cm6trUCt the PrOleCt ISec. 7044. Business and Professions Code: The
Contractor's L~cense Law doer not apply to an owner of pmperty who builds or improver thereon. and Contracts for such projeRs with contraRor(il licensed
pursuant to the Contractor's License Lawl.
1.
2.
3.
I haw and will maintain B certificate of consent to self-insure for workers' comPsnration as provided by Saction 3700 of the Labor Code. for the performance
I have and will maintain workers' compensation. as required by Section 3700 of the Labor Code. tor the PerlormancB of the work for which this permit IO
I am exempt under Sscrion
I ~srronallv plan to provide the malor labor and materials for Construction of the ProPosad Prapenv tmprovemant. YES QNO
I (have I have not1 signed an application for a building permit for the proposed work.
I have contracted with the folloivlng person lfirml to provide the proposed construction ImcIYde name I address I phons number I EOntraROrs license numbarl:
Business and Profssrionr Code for this reason:
4.
number I cOntraCtorr license numberl:
5.
of workl:
I plan to provide portions of the work. but I have hired the following person to coordinat8. wpewise and provide the major work (induds name I address I phons
I will provide some of the work. but I have canrractsd Ihlredl the following persons to provide the work indicated (include name I address I phone number I type
PROPERTY OWNER SIGNATURE DATE
COMPLETE THIS SECTION FOR IYDIY-RESIDWML BUILDING PERMITS ONLY
1s the applicant or future building OCoUpant required to submit a business plan. acutely hazardour materials regirtration form or risk management and prevention
program under Sections 25505, 25533 01 25534 of the Piaslay-Tanner HPZ~I~S Substance Account AR? 0 YES NO
1s the applicant or future building Occupant required to obtain 8 permit from the air pollution Cantroi dinrin of air quality management district? 0 YES 0 NO
Is the facility to be Constructed within 1,000 feet of the omer boundary of a school Sit07 YES NO
IF ANY OF THE ANSWERS ARE YES. A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR IS MEETING THE
REOUIREMENTS OF THE OFFICE OF EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT.
8. CONSTRUCTION LENDING AGENCY
I hereby affirm that there is a COnstruRion lending agency for the performance of the work tor which this psrmit is issued (Sac. 3097(il Civil Codel.
LENDER'S NAME LENDER'S ADDRESS
9. APPLICAW CERTIFICATION
I Canifv lhat I have read the application and state that the above information is correct and that the information on the Plans is accurate. I agree to comply woth ali
City ordinances and State laws relating to building Construction. I hereby authorize raprsrsntativss of thn CitV of Carlsbad to enter upon the above mentioned
Propany for insPBRion purposes. I ALSO AGREE TO SAVE, INDEMNIFY AND KEEP HARMLESS THE CITY DF CARLSBAD AGAINST ALL LIABILITIES.
OSHA: An OSHA permit is raquirad 101 axcsvatiens over 5'0' deep and demdition M ConStNCtion of StrUctUIeL wef 3 stones in hsighi.
EXPIRATION: Every permit issued
work amhorized by such permit
or abandoned at any time aft the w rk io
JUDGMENTS. COSTS AND EXPENSES WHICH MAY IN ANY WAY ACCRUE AGAINST SAID CITY IN CDNSEDUENCE OF THE GRANTING OF THIS PERMIT.
uilding Official und the provisions of this Code shall expire by limitation and become null and void if the buildmg or
' hin 385 ays from the date Of such Permit or if the building 01 work authorized by Such permit is suspended not com e ed
me sd for riod of 180 days Isaction 108.4.4 Uniform Building Cadcl.
APPLICANT'S SIGNATURE qfL&W- DATE 7 /8/40/
WHITE: File YELLOW: Applicant PINK: Finance
~ ~~
~~
- EsGil - Corporation
In 'Partnersfiip witfi ~ouernmcnt for liuicdng Safety
DATE: July 23, 1999
JURISDICTION: Carlsbad
0 FILE
PLAN CHECK NO.: 99-1441 (PCR99168)
PROJECT ADDRESS: 1815 Aston Ave, Suite 101
PROJECT NAME: Structural Changes for Folding Partition
E The plans transmitted herewith have been corrected where necessary and substantially comply
0 The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff
0 The plans transmitted herewith have significant deficiencies identified on the enclosed check list
0 The check list transmitted herewith is for your information. The plans are being held at Esgil
0 The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
0 The applicant's copy of the check list has been sent to:
SET I
with the jurisdiction's building codes.
and should be corrected and resubmitted for a complete recheck.
Corporation until corrected plans are submitted for recheck.
contact person.
Esgil Corporation staff did not advise the applicant that the plan check has been completed.
0 Esgil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Telephone #:
Date contacted: (by: 1 Fax #:
Mail Telephone Fax In Person E REMARKS: Revision No. 1.
By: Abe Doliente Enclosures:
Esgil Corporation
GA 0 MB 0 EJ 0 PC 7/9/99 tmsmtl.dot
9320 Chesapeake Drive, Suite 208 + San Diego, California 92123 + (858) 560-1468 + Fax (858) 560-1576
Carlsbad 99-1441 (PCR99168)
July 23, 1999
VALUATION AND PLAN CHECK FEE
JU Rl SDl CTI ON: Carlsbad
(PCR99168)
PLAN CHECK NO.: 99-1441
PREPARED BY: Abe Doliente
BUILDING ADDRESS: 1815 Aston Ave, Suite 101
DATE: July 23, 1999
BUILDING OCCUPANCY: B TYPE OF CONSTRUCTION: V-N
REVISION NO. I I TO THE ORIGINAL I SET OFAPPROVED I PLANS
Air Conditioning
Fire Sprinklers
TOTAL VALUE
0 199 UBC Building Permit Fee
0 199 UBC Plan Check Fee
Type of Review: 0 Complete Review 0 Structural Only Hourly
0 Repetitive Fee Applicable
0 Bldg. Permit Fee by ordinance: $
0 Plan Check Fee by ordinance: $
0 Other:
Esgil Plan Review Fee: $ 87.15
Comments: 1 HOUR @ 87.15
Sheet 1 of 1
SX6' 1/4" STEEL TUBE Srm TUBE
4'X4. SEEL TUBE
DOWEL m DisrC SLAB
W/ #3 REBAR 16' O/C
4'-
>*. ..
FOOTING AND STEEL COLUMN SCALE: N.S. 1
I ,EXIST& CONCCRETE SLAB
ALUM. TRACK (BY
STEEL NBE
MANUFACTURER)
BEAM/ CLEAT SECTION 0 SCALE N.S.
.. - .. . . . . . ._ -...
FLAG POLE DESIGN
W,v.ll = 23x8~14 = 2576 ‘
Pbh, = (23x5~14)/4 =402 ’
M=PxL
=402x14’
= 5.6
using 36 KSI TS
Change
Change = PL3/3EI
.84” = (402~14~xl728)/(3x29xlO~xI)
I Req‘d = 26 It$
Use 6x6~114
5x5~12
= ,005 H = .005xl4’x12” = .84”
.~ .. . .. ~. .. .’.~. ..
FLAG POLE FOOTING DESIGN
P = 2576’
A Rq’d = 2576 I 100
= 2.5
Use 18”xlS”Footing
Po= 1610/4=402’
D2 = 4.25 PWS,B ’
D2 = 4.25 (4@2~14)/(lfSOdx2.%)
D3= 5.7 -i
I
?
BEAM DESIGN
2576 #
23’4” ,, +--- a =PL3/48EI
.A .,,=L/240= 1.15”
I .15 = (2576~14~~1728)/(48X5~10~x1)
I Rcq.d = 8.36 Lbf
Use TS 5x3x1/4
or
4x4~5116