HomeMy WebLinkAbout1901 CAMINO VIDA ROBLE; 201 | 202; CB940312; PermitBUILDING PERMIT04/06/94 09:26
Page 1 of l
Job Address: 1901 CAMINO VIDA ROBLE
Permit Type: INDUSTRIAL TENANT IMPROVEMENT
Parcel No: 212-092-20-00
Valuation: 241,400
Construction Type: VI
Occupancy Group: B-2 Reference*:
Description: 9656 SF OFFICE TI
Suite
Lot#:
Permit No
Project No
Development No
CB940312
A9400438
Appl/Ownr : WHITE CONSTRUCTION
6351 CORTE DEL ABETO
CARLSBAD, CA 92009
619 931^-1611
Status
Applied
Apr/Issue
Entered By
ISSUED
03/21/94
04/06/94
DC
*** Fees Required ******Fees Collected & Credits ***
Fees: 2,233.00
Adjustments: .00
Total Fees: 2,233,00
Fee description »«*
Total Credits:
^fil Payments:
Balance Due:
Fee/Unit
.00
739.00
1,494.00
Ext fee Data
Building Permit
Plan Check
Strong Motion Fee
* BUILDING TOTAL *
Enter "Y" for Plumbing Issue ;F
Enter "Y" for Electric Isstwfi^
Remodel/Alter Per AMP '•' '*' '**
* ELECTRICAL TOTAL
Enter 'Y' for Mechanical Issue
Install Furn/Ducts/Heat Pumps
Each Exhaust Fan
* MECHANICAL TOTAL
Fee>
>
>
700
11
1
,25
9.00
6. 50
1137.00
739.00
51.00
1927.00
N
10.00 Y
175.00
185.00
15.00 Y
99.00
6. 50
121.00
APPROVAL/ /
DATEiM
CLEARANCE
CITY OF CARLSBAD
2075 Las Palmas Dr., Carlsbad, CA 92009 (619) 438-1161
BUILDING PERMIT05/05/94 15:59
i Page 1 of 1
Job Address: 1901 CAMINO VIDA ROBLE
Permit Type: MISCELLANEOUS
Parcel No: 212-092-20-00
Valuation: 0
Construction Type: NEW
Occupancy Group: Reference*:
Description: SUNDAY INSPECTION
Appl/Ownr : MARSCH, RICHARD
5411 AVENIDA ENCINAS #1ZQ
CARLSBAD, CA. 92008
Suite
Lot#:
Permit No:
Project No:
No:
CB940515
A9400438
619 431-0266
Status:
Applied:
Apr/Issue :
Entered By:
ISSUED
05/05/94
05/05/94
MDP
* **Fees Required ***s *** Fees collated & Credits ***
Fees :
Adjustments:
Total Fees:
Fee description
;o Total Credits:
Total Payments:
Balance Dues
• Fee/Unit
.00
\QQ
60 . 00
Ext fee Data
Miscellaneous Fee #1
* MISCELLANEOUS TOTA&60.60.00 PERMIT
60. 00
iNSP.
CLEARANCE
APPROVAL/ ;
DATE^Ml
CITY OF CARLSBAD
2075 Las Palmas Dr., Carlsbad, CA 92009 (619) 438-1161
pEiwfrr APPLICATION
City of Carlsbad Building Department
2075 Las Palms Dr., Carlsbad, CA 92009 (619) 438-1161
1. PERMIT TYPE
A - [3 Commercial LJ New Building B^Tenant Improvement
B - D Industrial D New Building D Tenant Improvement
C - D Residential D Apartment D Condo D Single Family Dwelling D Addition/Alteration
D Duplex D Demolition D Relocation D Mobile Home D Electrical D Plumbing
D Mechanical DPool D Spa D Retaining Wall D Solar D Other
2. PROJECT INFORMATION Cfjy$ff^j,
Bu.Ung or Mi.te
PLAN CHECK NO.
EST.VAL
PLAN CK DEPOSIT
VALID. BY
DATE
FOR OFFICE USE ONLY
Address /ta^jf
Nearest Cross Street ,.ivision Name/Number Unit No.
i pot_^<
Phase No.
ftyX.
LECAL
CHECK BELOW It bUHMll IhD:
$2 Energy Calcs D 2 Structural Calcs D 2 Soils Report 1 Addressed Envelope
ASSESSOR'S PARCEL EXISTING USE.PROPOSED USE
DESCRIPTION OF WORK
SQ.FT.# OF STORIES
NAME
CITY
W in diiterent irom applicant)
STATE
ADDRESS
ZIP CODE DAY TELEPHONE
4. APPLICANT
NAME
CITY
Q CONTRACTOR UAGENI FOR CON IRACIUK UUWNhR
ADDRESS
ZIP CODE
FUK OWNER
STATE DAY TELEPHONE
5. PROPERTY OWNER
CITY
ADDRESS
ZIP CODE DAY TELEPHONE £>2-&r
6. CONTRACTOR
NAME
CITY STATE
STATE LIC.
ADDRESS
ZIP CODE
LICENSE CLASS
DAY TELEPHONE
CITY BUSINESS LIC. #
7. WO!
Workers' Compensation Declaration: I hereby aiTrnTtriat I have a certiicate ot consent to self-insure issued by the Director ot Industrial
Relations, or a certificate of Workers' Compensation Insurance by an admitted insurer, or an exact copy or duplicate thereof certified
by the Director of the insurer thereof filed with the Building Inspection Department (Section 3800, Lab. C).
INSURANCE COMPANY POLICY NO.EXPIRATION DATE
Certificate ot Exemption: I certify tnat m the pertormance or the work tor which this permit is issued, I shall not employ any person in any manner
so as to become subject to the Workers' Compensation Laws of California.
SIGNATURE DATE
8. OWNER-BUILDER DECLARATION
Owner-Builder Declaration: I hereby aiiirm that I am exempt from the Contractors License Law tor the following reason:
D I, as owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not intended or
offered for sale (Sec. 7044, Business and Professions Code: The Contractor's License Law does not apply to an owner of property who builds
or improves thereon, and who does such work himself or through his own employees, provided that such improvements are not intended
or offered for sale. If, however, the building or improvement is sold within one year of completion, the owner-builder will have the burden
of proving that he did not build or improve for the purpose of sale.).
D I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions
Code: The Contractor's License Law does not apply to an owner of property who builds or improves thereon, and contracts for such projects
with contractor(s) licensed pursuant to the Contractor's License Law).
D I am exempt under Section Business and Professions Code for this reason:
(Sec. 7031.5 Business and Professions Code: Any City or County which requires a permit to construct, alter, improve, demolish, or repair
any structure, prior to its issuance, also requires the applicant for such permit to file a signed statement that he is licensed pursuant to the
provisions of the Contractor's License Law (Chapter 9, commencing with Section 7000 of Division 3 of the Business and Professions Code)
or that he is exempt therefrom, and the basis for the alleged exemption. Any violation of Section 7031.5 by any applicant for a permit
subjects the applicant to a civil penalty of not more than five hundred dollars [$500]).
SIGNATURE DATE
COMPLETE THIS SECTION FOR NQN-RESIDENTIAL BUILDING PERMITS ONLY:
Is the applicant or future building occupant required to submit a business plan, acutely hazardous materials registration form or risk management and
prevention program under Sections 25505, 25533 or 25534 of the Presley-Tanner Hazardous Substance Account Act?
D YES D NO
Is the applicant or future building occupant required to obtain a permit from the air pollution control district or air quality management district?
D YES D NO
Is the facility to be constructed within 1,000 feet of the outer boundary of a school site?
D YES D NO
IF ANY OF THE ANSWERS ARE YES, A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED AFTER JULY 1,1989 UNLESS THE APPLICANT
HAS MET OR IS MEETING THE REQUIREMENTS OF THE OFFICE OF EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT,
g. UUNbTKUL'llUN^LENDlNG ACJfeNCY
I hereby attirm that there is a construction lending agency lor the performance of the work tor which this permit is issued (Sec 3097U) CivTTCodeJ.
LENDER'S NAME LENDER'S ADDRESS
10. APPLICANT (CERTIFICATION
I certify that I have read the application ana state that the above information is correct. I agree to comply with all City ordinances and State laws
relating to building construction. I hereby authorize representatives of the City of Carlsbad to enter upon the above mentioned property for inspection
purposes. I ALSO AGREE TO SAVE INDEMNIFY AND KEEP HARMLESS THE CITY OF CARLSBAD AGAINST ALL LIABIUTTES, JUDGMENTS, COSTS
AND EXPENSES WHICH MAY IN ANY WAY ACCRUE AGAINST SATO OTY IN CONSEQUENCE OF THE GRANTING OF THIS PERMIT.
OSIIA: An OSHA permit is required for excavations over 5'0" deep and demolition or construction of structures over 3 stories in height.
Expiration. Every permit issued by the Building Official under the provisions of this Code shall expire by limitation and become null and void if the
building or work authorized by such permit is not commenced within 365 days from the date of such permit or if the building or work authorized by
such permit is suspended or abandoned at any time after the work is commenced for a period of 180 days (Section 303(d) Uniform Building Code).
JCANTS SIGNATURE DATC:
WHITE: File YELLOW: Applicant PINK: Finance
PERMIT! CB940312
DESCRIPTION: 9656 SF OFFICE TI
CITY OF CARLSBAD
INSPECTION REQUEST
FOR 06/08/94
TYPE: ITI
JOB ADDRESS
APPLICANT:
CONTRACTOR:
OWNER:
1901 CAMINO VIDA ROBLE
WHITE CONSTRUCTION PHONE
PHONE
PHONE
INSPECTOR AREA PY
PLANCK# CB940312
OCC GRP B-2
CONSTR. TYPE VI
STE: 201&202 LOT:
619 931-1611
REMARKS: BJN/TRAVIS/931-1130
SPECIAL INSTRUCT:
INSPECTOR
TOTAL TIME:
—RELATED PERMITS—PERMITS TYPE
AS940019 ASC
CB940515 MISC
FA940006 FALARM
STATUS
ISSUED
ISSUED
ISSUED
CD
19
29
39
49
LVL DESCRIPTION ACT COMMENTS
ST Final
PL Final
EL Final
ME Final
Structural
Plumbing
Electrical
Mechanical
A ^
/ \ / '
"Ob ^~~\
'
***** INSPECTION HISTORY *****
DATE DESCRIPTION
060294 Final Combo
051894 Frame/Steel/Bolting/Welding
051894 Rough Electric
051894 Rough/Ducts/Dampers
051794 Frame/Steel/Bolting/Welding
051794 Rough Electric
051794 Rough/Ducts/Dampers
051694 Frame/Steel/Bolting/Welding
051694 Rough/Topout
051694 Rough Electric
051694 Rough/Ducts/Dampers
050994 Rough Electric
042794 Interior Lath/Drywall
042694 Frame/Steel/Bolting/Welding
042594 Interior Lath/Drywall
042294 Interior Lath/Drywall
042094 Frame/Steel/Bolting/Welding
042094 Rough Electric
042094 Interior Lath/Drywall p^
041994 Interior Lath/Drywall
041994 Rough Electric
041894 Interior Lath/Drywall
041594 Rough Electric
041194 Frame/Steel/Bolting/Welding
ACT
NR
AP
AP
AP
PI
CO
CO
PA
PI
PI
PI
NR
AP
AP
PA
PA
AP
AP
XP">
AP
CO
PA
AP
PA
INSP
PPY
TP
TP
TP
TP
TP
TP
TP
TP
TP
TP
PY
PY
PY
PY
PK
PY
PY
PY
TP
TP
PY
PY
PY
COMMENTS
T-BAR
CEILING
DUCT,UNITS
T-BAR (SCREWS & WIRES)
DISCONNECTS
DISCS,DUCTS,SUPP,SECONDARY
T-BAR
CEILING
CEILING
DUCTS,UNITS
SEE NOTES
SIDE B
DEMISING WALL
ND CORRIDOR CORRECTIONS
SEE NOTES
SIDE A
SUB PANELS TO BE RMV/CORR WAL
PARTIAL SIDE A
SIDE A
PERMIT* CB940312
DESCRIPTION: 9656 SF OFFICE TI
CITY OF CARLSBAD
INSPECTION REQUEST
FOR 06/08/94
TYPE: ITI
JOB ADDRESS:1901 CAMINO VIDA ROBLE
INSPECTOR AREA PY
PLANCK* CB940312
OCC GRP B-2
CONSTR. TYPE VI
STE: 201&202 LOT:
***** INSPECTION HISTORY *****
DATE DESCRIPTION
041194 Rough/Topout
041194 Rough Electric
041194 Rough/Ducts/Dampers
ACT INSP
AP PY
AP PY
NR PY
COMMENTS
ESGIL, CORPORATION
9320 CHESAPEAKE DR., SUITE 203
SAN DIEGO, CA 92123
(619)560-1^68
DATE:
JURISDICTION: __
PLAN CHECK NO:
PROJECT ADDRESS
PROJECT NAME:
- <3 4
,~
t£=>SET:
Pi APPLICANT
^
QFILE COPY
QUPS
FjDESIGNER
The plans transmitted herewith have been corrected where
necessary and substantially comply with the jurisdiction's
building codes.
The plans transmitted herewith will substantially comply
with the jurisdiction's building codes when minor deficien-
cies identified are resolved and
checked by building department staff.
The plans transmitted herewith have significant deficiencies
identified on the enclosed check list and should be corrected
and resubmitted for a complete recheck.
The check list, transmitted herewith is for your information.
The plans are being held at Esgil Corp. until corrected
plans are submitted for recheck.
The applicant's copy of the check list is enclosed for the
jurisdiction to return to the applicant contact person.
The applicant's copy of the check list has been sent to:
Esgil staff did not advise the applicant contact person that
plan check has been completed.
Esgil staff did advise applicant that the plan check has
been completed. Person contacted:
Date contacted:
REMARKS:"
Telephone
By:C(Enclosures
ESGIL CORPORATION
DGA DCM
ESGIL CORPORATION
9320 CHESAPEAKE DR., SUITE 208
SAN DIEGO, CA 92 123
(619) 560-1*68
DATE: ^/^U~"^ -
JURISDICTION: C fa eft (TArteb/vd. _ n^jFLAN CHECKER'
I y QFILE COPY
PLAN CHECK NO: Ct=> ^ 4 - j /A _ SET: r _ DUPS
QDESIGN'ER
PROJECT ADDRESS: f
PROJECT NAME: -T, 1 .
The plans transmitted herewith have been corrected where
necessary and substantially comply with the jurisdiction's
building codes.
The plans transmitted herewith will substantially comply
with the jurisdiction's building codes when minor deficien-
cies identified _ are resolved and
checked by building department staff.
The plans transmitted herewith have significant deficiencies
identified on the enclosed check list and should be corrected
and resubmitted for a complete recheck.
The check list transmitted herewith is for your information.
The plans are being held at Esgil Corp. until corrected
plans are submitted for recheck.
The applicant's copy of the check list is enclosed for the
jurisdiction to return to the applicant contact person.
The applicant's copy of the check list has been sent'to:
Esgil staff did not advise the applicant contact person that
plan check has been completed.
] Esgil staff did advise applicant that the plan check has
been completed. Person contacted:
Date contacted: Telephone §
REMARKS:
By: Cv \ * ^? CiA**- Enclosures :
ESGIL CORPORATION
PLAN CHECK NO.:.
JURISDICTION:
*"/ — -5 f.4
FLAK CORRECTION SHEET
TENANT IMPROVEMENT
^ _ Date plans received by jurisdiction:
TO:
PROJECT DATA
OCCUPANCY:
BUILDING USE: 0
TYPE OF COHSTKUCTIOH:- I Hfc- /
ACTUAL AREA: ^>t;TTZ«»
ALLOWABLE AREA:yf
STORIES
HEIGHT:
SPRINKLERS V
OCCUPANT LOAD:1 5*7 ~
REMARKS:
Date plans received by Esgil Corporation:
Date initial plan check completed:
Bv:
Applicant contact person:
Tel.
FOREWORD: PLEASE READ
Plan check is limited to technical requirements
contained in the Uniform Building Code, Uniform
Plumbing Code, Uniform Mechanical Code, National
Electrical Code and state laws regulating energy
conservation, noise attenuation and access for the
handicapped. The plan check is based on
regulations enforced by the Building Inspection
Department. You may have other corrections based
on laws and ordinances enforced by the Planning
Department, Engineering Department, Fire Department
or other departments. Code sections cited are
based on the 1991 UBC. Clearance from those
departments may be required prior to the issuance
of a building permit.
The circled items listed need clarification,
modification or change. All items must be
satisfied before the plans will be in conformance
with the cited codes and regulations. Per Sec.
303(c), 1991 Uniform Building Code, the approval of
the plans does not permit the violation of any
state, county or city law.
To speed-up the recheck process, note on this list
(or a CODV^ where each correction item has been
addressed. i.e.. Plan sheet, specification. etc.
Be sure to enclose the marked UP list when you
submit the revised plans.
NOTE: PAGE NUMBERS ARE NOT IN SEQUENCE AS PAGES HAVING NO PEEKS NEEDING CORRECTIONS WERE DELETED.
LIST NO. i.0 TENANT IMPROVEMENT WITHOUT SPECIFIC ENERGY ZONE DATA OR POLICY SUPPLEMENTS, 1991 UBC
Please make all corrections on the original
tracings and submit two new sets of prints, to:
Esgil Corporation, 9320 Chesapeake Drive,
Suite #208, San Diego, CA 92123,
(619) 560-1468.
Please make all corrections on the original
tracings and submit tvo new sets of prints, to:
The jurisdiction's building department.
Indicate on the Title Sheet of the plans, the
name of the legal owner and name of person
responsible for the preparation of the plans.
Section 302(d).
Each sheet of the plans must be signed by the
person responsible for their preparation, even
though there are no structural changes.
Business and Professions Code.
Plans and calculations shall be signed by the
California state licensed engineer or architect
where there are structural changes to existing
buildings or structural additions. Please
include the California license number, seal,
date of license expiration and date plans are
signed. Business and Professions Code.
Provide the correct address and suite number of
tenant space on the plans. Section 302(d).
Provide a note on the site plan indicating the
previous use of the tenant space or building
being remodeled. Section 302.
When the character of the occupancy or use
changes within a building, the building must be
made to comply with current Building Code
requirements for the new occupancy. Please
provide complete details to show the building
with comply. Section 502.
UBC Section 304 requires the Building Official
to determine the total value of all
construction work proposed under this permit.
The value shall include all finish work,
painting, roofing, electrical, plumbing,
heating, air conditioning, elevator, fire
extinguishing systems and any other permanent
equipment. Please provide a signed copy of the
designer' s or contractor' s construction cost
estimate of all work proposed.
Provide a plot plan showing the distance from
the building to the property lines and the
location of tenant space (or remodel) within
the building.
On the first sheet of the plans indicate:
Type of construction of the existing building,
present and proposed occupancy classifications
of the remodel area and the occupant load of
the renodel areas and the floor where the
tenant inprovement is located.
Provide a note on the plans indicating if any
hazardous materials will be stored and/or used
within the building which exceed the
quantities listed in UBC Tables 9-A and 9-8.
A complete description of the activities and
processes that will occur in this tenant space
should be provided. A listing of all
hazardous materials should be included. The
materials listing should be stated in a form
that would make classification in Tables 9-A
and 9-B possible. The building official nay
require a technical report to identify and
develop methods of protection from hazardous
materials. Section 901(f).
If control areas are used for exceeding the
exempt amounts of hazardous materials from
Tables 9-A and 9-B, they shall be constructed
of not less that required for a one-hour
occupancy separation. Section 404.
The number of control areas within a building
used for retail/wholesale stores shall not
exceed two; the number of control areas in
buildings with other uses shall not exceed
four. Footnote 1, Tables 9-A and 9-B.
The aggregate quantity of any hazardous
materials "in use" and "in storage" shall not
exceed the quantity listed in Tables 9-A and
9-B for "storage". Footnotes 2 and 3, Tables
9-A and 9-B.
17. ) Provide a statement on the Title Sheet of the
plans that this project shall comply with
Title 24 and 1991 UBC, UMC and UPC and 1990
NEC.
Provide a fully dimensioned floor plan showing
the size and use of all rooms or areas within
the space being improved or altered. Draw the
plans to scale and indicate the scale on the
plan. Section 302(d).
Indicate the use of all spaces adjacent to the
area being remodeled or improved.
Show any existing fire rated area separation
walls, occupancy separation walls, demising
wal Is , shafts or rated corridors . Identify
and provide construction details for proposed
new fire rated walls.
Specify on the plans the fire ratings of
assemblies to protect penetrations or proposed
openings in existing or new fire walls, floor-
ceiling assemblies or roof-ceiling assemblies.
8/4/92
Identify existing walls to be removed,
existing walls to remain and proposed new
walls. Identify bearing walls, non-bearing
walls, and shear walls. s_..TA.& 'efr"<t°n.,Cexf£Z-
Snow safety glazing in the f ollowing
cations, per Section 5406(d):
Where the nearest edge of glazing is
within a 24-inch arc of either side of a
door in a closed postion (unless there is
an intervening wall between the door and
the glazing or if the glazing is S'-O'^or^.
higher above the walking surface). _rg*j c'•*"
Glazing greater than 9 square feet with
the bottom edge less than 18" above the
floor and the top edge greater than 36"
above the floor (unless the glazing is
more than 36" horizontally away from
walking surfaces or if a complying
protective bar is installed).
Glazing in shower and tub enclosures
(including windows within 5 feet of tub
or shower floor).
Provide a section view of all new interior
partitions. Show:
(a) Type, size and spacing of studs. Indicate
gauge for metal studs. Specify
manufacturer and approval number or
indicate "to be ICBO approved".
(b) Method of attaching top and bottom plates
to structure. (NOTE: Top of partition
must be secured to roof or floor framing,
unless suspended ceiling has been designed
for partition lateral load).
(c) Wall sheathing material and details of
attachment (size and spacing of
fasteners).
(d) Show height of partition and suspended
ceiling, and height from floor to roof
framing or floor framing.
Provide notes and/or details to show that the
floor and wall finish in toilet rooms are
surfaced with a smooth hard non-absorbent
material extending five inches up the wall.
Similar surfacing shall be provided on the
walls from the floor to a height of 4 feet
around urinals and within water closet
compartments. Section 510(b).
Note on the plans: "All interior finishes must
comply with Chapter 42 of the UBC". Specify
"Class flame spread rating (minimum)
for ."
Note on plan that suspended ceilings shall
comply with UBC Tables 47-A and 23-P.
In buildings having floors and roofs of wood
frame construction, other than dwelling or
hotel occupancies, draft stop the area between
the celling and floor above so that no
concealed space exceeds 1,000 s.f. and no
horizontal dimension exceeds 60 L.F. (if space
has sprinklers, then 3,000 s.f. and 100 L.F.).
Section 2516(f).
In buildings having floors and roofs of wood
frame construction, other than dwelling or
hotel occupancies, draft stop the area between
the ceiling and roof above so that no
^..concealed space exceeds 3,000 s.f. and no
"^""horizontal dimension exceeds 60 L.F. (if space
_ has sprinklers, then 9,000 s.f. and 100 L.F.).
Section 2516(f).
I. Storage areas exceeding 1000 sq. ft. in
connection with wholesale or retail sales
shall be separated from the public area by a
one-hour occupancy separation. If the entire
i£"Jrs. __ building has an automatic sprinkler system,
-then the occupancy separation need not be
3*.
provided. Section 702(c).
3^. An automatic sprinkler system shall be
' installed in rooms used by the occupants for
the consumption of alcohol and in accessory
uses where the total area of such unseparated
rooms and assembly uses exceeds 5000 square
feet. Section 3802(c).
The tenant space and new and/or existing
facilities serving the remodeled area must be
accessible to and functional for the
physically disabled. See the attached
correction sheet. Title 24, Part 2.
The width of the required level area on the
side into which doors swing shall extend 24
inches past the strike edge for exterior doors
and 18 inches past the strike edge for
interior doors. Section 2-3304, Title 24.
Specify lever-type hardware for passage doors
on floors accessible to the disabled. Section
2-3304, Title
a. II drs . Ht,_Tf Both SeXey wfll Ufe employed and the number
of employees exceeds four, provide separate
toilet facilities for men and women. If "both
sexes will be employed and the total number of
employees will not exceed four", and only one
restroom is provided, note the words in
quotation above on the floor plan. Section
705(c).
A -hour occupancy separation is
required between «««..— -»...« =^^
the
W
.occupancy and
_occupancy. Table 5-B.
Ducts penetrating occupancy or area separation
walls must have fire dampers. Section 4306
(j).
In areas where the occupant load exceeds
two exits are required. See
. Table 33-A.
Provide an exit analysis plan (may be 8 1/2" x
11" or any convenient size).
Exits should have a minimum separation of one-
half the maximum overall diagonal dimension of
the building or area served. Section 3303(c).
7/8/92
i-
The maxinmra number of required exits and their
required separation must be maintained until
egress is provided from the structure. Section
3303(a).
Rooms with more than 10 occupants may have one
exit through one adjoining room. Revise exits
to comply. Section 3303(e).
Exit signs are required whenever two exits are
required. Show all required exit sign
locations. Section 3314 (a).
Show that exits are lighted with at least one
foot candle at floor level. Section 3313(a).
Show the locations of existing exits from the
building and show the path of travel from the
remodel area to the existing exits. «~L«A \ae\t•&
Note on the plans: "All exits are to be
openable from inside without the use of a key
or special knowledge". In lieu of the above,
in a Group B occupancy, you may note "Provide a
sign on or near the exit doors reading THIS
DOOR TO REMAIN UNLOCKED DURING BUSINESS HOURS".
This signage is only allowed at the main exit.
Section 3304(c).
Exit doors should be a minimum size of 3 feet
by 6 feet 8 inches with a minimum door swing of
90 degrees. Maximum leaf width is 4 feet.
Section 3304(f).
Exit doors should swing in the direction of
egress when serving an occupant load of 50 or
more or when serving any hazardous area.
Section 3304(b). Applies to door(s)
Regardless of occupant load, a floor or landing
not more than 1/2 inch below the threshold is
required on each side of an exit door used for
disabled access (may be 1" maximum where not
used for disabled access). Section 3304(i).
Doors should not project more than 7 inches
into the required corridor width when fully
opened, nor more than one-half of the required
corridor width when in any position. Section
3305(d).
Revolving, sliding and overhead doors are not
permitted as exit doors if the occupant load
exceeds 9 or the exit door serves a hazardous
area. Section 3304(h).
Provide panic hardware in Group A,E,H-l,H-2,H-3
and I occupancies. Chapter 33.
Double acting doors are not allowed when
serving a tributary occupant load of more than
100, or when part of a fire assembly, or part
of smoke and draft control assemblies or when
equipped with panic hardware. Section
3304(b).
?*•
Corridors must provide continuous protection
to the exterior of the building.
Interruptions by an intervening room is not
permitted. Foyers, lobbies or reception rooms
constructed as required for corridors are not
considered intervening rooms. Section 3305.
Corridors and exterior exit balconies serving
10 or more occupants must be a minimum 44
inches wide and 7 feet high to the lowest
projection. Corridors serving less than 50
occupants may be a minimum of 36 inches in
width. Section 3305(b).
When two exits are required, dead end
corridors and exit balconies are limited to 20
feet. Section 3305(e).
Corridors serving 30 or more occupants shall
have walls and ceilings of one-hour
construction. Show compliance or clearly show
on plans which of the following exceptions has
been satisfied: -
a. Corridors greater than 30 feet wide when
the occupants have an exit independent
from the corridor.
b. Exterior sides of exterior exit
balconies.
c. Corridor walls and ceilings need not be
of fire-resistive construction within
office spaces having an occupant load of
100 or less when the entire story in
which the space is located is equipped
with an automatic sprinkler system
throughout and smoke detectors are
installed within the corridor in
accordance with their listing.
d. Within office spaces occupied by a single
tenant, partial height partitions which
form corridors and which do not exceed 6
feet in height need not be fire
resistive, provided they are constructed
in accordance with Section 1705 and are
. not more than three fourths of the floor-
to-ceiling height. Section 3305 (g).
Section 3305(g), Exception 5, cannot be used
for non-rated corridors in a fully sprinklered
office space if the occupant load in the space
exceeds 100.
Section 3305(g), Exception 5 does not apply to
common corridors where the corridor serves as
an exit for non-office areas (manufacturing,
warehouse, etc.).
Section 3305(g) , Exception 5 is applicable
only for corridors on one floor; the corridors
on the lower level(s) must be rated if these
lower corridors have openings into them from
other levels.
of
'"*-
t>u<.L "Chr^x
5/28/92
61.
T
f-
f-
If non-rated corridors are used per Section
3305 (g), Exc. 5, provide a reference to the
corridors on the floor plan, noting:
1.
2.
3.
Corridors are non- rated per Section
3305(g), Exception 5.
Smoke detectors shall be maximum 30' on
center.
Power supply shall be dedicated branch
circuit. Circuit disconnecting means
shall be accessible only to authorized
personnel and shall be clearly marked FIRE
ALARM CIRCUIT CONTROL, with a lock-on
device. _
"I? a tenant space utilizes Section 3305(g),
Exception 5 , then that tenant space shal 1 be
separated from adjacent spaces by a demising
wall constructed as for a one-hour corridor
wall.
Clearly show where the non-rated corridor
system terminates and a rated corridor system
commences .
One-hour fire-rated corridors shall have
interior door openings protected by tight-
fitting smoke and draft control assemblies
rated 20 minutes, except openings in interior
walls of exterior exit balconies. Doors shall
be maintained self-closing or be automatic-
closing by action of a smoke detector per
Section 4306(b). Doors shall be gasketed to
provide a smoke and draft seal where the door
meets the stop on sides and top. Section
3305(h).
Total area of all openings, except doors, in
any portion of an interior corridor, shall not
exceed 25 percent of the area of the corridor
wall of the room which it is separating from
the corridor. Such openings shall be protected
by fixed glazing listed and labeled for a fire-
protection rating of at least 3/4-hour.
Section 3305(h).
Show rated corridors , lobbies , reception or
foyers cross-hatched on the floor plans.
Provide a complete architectural section of
the corridor .or exterior exit balcony.
showing all fire-resistive materials and
details of construction for all floors, walls,
ceiling and all penetrations. Section
3305(g)-
Show the location of fire dampers. Provide
fire dampers at duct penetrations of fire-
rated occupancy and area separations , shafts
and corridor ceilings. Combination fire/smoke
dampers are required at duct penetrations of
rated corridor walls. Section 4306(j).
If a room with an exhaust fan has a door
opening into a rated corridor, show how make-
up air will be provided to the room. The door
cannot be undercut, nor can a louver in the
door be provided. Section 3305(h)l.
If building exceeds two stories and has an
elevator opening into a rated corridor, show
how the smoke and draft control provision of
Section 3305(h) will be met. Either provide a
separated elevator lobby or a second door at
the elevator entry meeting the provision.
Section 3305(j).
If a second door is provided at the elevator
entry, note that it will be readily openable
from the car side without a key, tool or
special knowledge or effort. Section 5106.
New provisions in Chapter 43 of the 1991 UBC
require special treatment of penetrations at
fire-resistive assemblies. Provide typical
details on the plans showing how the fire-
resistive integrity will be maintained at the
following conditions (Include the
manufacturers1 names and ICBO numbers (or
equal) for any sealant):
A. THROUGH-PENETRATIONS (through the entire
assembly):
1. Fire-resistive bearing walls and/or
walls requiring protected openings shall
have penetrations protected with through-
penetration fire stops having an F-
rating, T-rating or complying with UBC
Standard 43-1, depending on their
locations, sizes and combustibility.
2. Fire resistive floor/ceiling assemblies
shall have penetrations protected with
through-penetration fire stops having and
F-rating, T-rating or complying with UBC
Standard 43-1, depending on their sizes,
combustibility and whether the
penetrations are in walls above.
B. MEMBRANE-PENETRATIONS (through only one
side of an assembly):
1. Fire-resistive walls (whether bearing or
not and whether requiring fire protected
openings or not) shall have penetrations
protected with membrane-penetration fire
s tops having an F-rating or complying
with UBC Standard 43-1, depending on
their size and combustibility. Limited
steel electrical outlet boxes (not
exceeding 16 sq. in., nor more than 100
sq. in. for any 100 sq. ft. of wall)
require no protection.
2. Fire-resistive ceilings shall have no
penetrations, except for noncombustible
sprinkler pipes and steel electrical
outlet boxes as described above.
NOTE: The plans should indicate the various
fire-stop ratings required for ^al^.
penetrations.,hT.
73.\ Provide ^ note on the plans stating
I } "Penetrations of fire-resistive walls, floor-
^-—^ ceilings and roof-ceilings shall be protected
as required in UBC Sections 4304 and 430511.
8/4/92
I
SO'.
i-
1-
t
Provide evidence of Health Department approval
(for restaurants or for tenants us ing X- ray
equipment).
If nonflarciable supply cylinders for medical
gas systens are located inside buildings, show
how they comply with UBC Section 702(c)4.
FT.BTTPTfUL
Submit plan showing location of all panels.
Submit panels schedules.
Submit electrical load calculations
Indicate existing main service size.
Indicate existing total main service load.
Indicate new additional loads.
Indicate wiring method, i.e. EMT, metal flex.
Show exit signs on the electrical lighting
plan(s). As per Section 3313 and 3314. of the
1991 UBC, provide two sources of power to exit
signs and exit illumination.
Provide receptacle(s) within 25' of HVAC
units. UMC Section 509.
Provide multiple switch lighting controls per
Title 2k, Part 6.
MECHANICAL
Provide mechanical ventilation in all rooms
capable of supplying a minimum of 5 cubic feet
per minute of outside air with a total
circulation of not less than 15 cubic feet per
minute per occupant. Section 605 and 705,
UBC.
Provide mechanical plans showing existing and
proposed HVAC equipment, ducts and access to
equipment.
Detail access and working clearances to HVAC
equipment.
Detail disposal of main condensate drainage
from air conditioning units. (UMC Section
510)
Detail overflow (secondary) condensate
discharge from air conditioning units that are
in a ceiling space. (UMC Section 1205)
Fire rated corridors are not to be used to
convey air to or from rooms. UMC Section
1002.
FUMBUJG
Provide gas line plans and calculations,
showing pipe lengths and gas demands. UPC
Section 1219.
S3. Provide drain, waste and vent plans.
9X. Provide water line sizing calculations. UPC
' Section 1009.
96.
/
9fe.
97.
Detail how floor drain trap seal is to be
maintained. UPC Section 707 (floor drain trap
priming).
Show P & T valve on water heater and detail
drain line route from P & T valve to the
exterior. UPC Section 1007(e).
Show l/^" per 12" slope on drain and waste
lines. UPC Section 407.
'8 .
49.
Provide a drinking fountain at each floor
level in assembly occupancies (except drinking
and dining establishments). UBC Section 605.
Note on the plans that new water closets and
associated flushometer valves, if any, shall
use no more than 1.6 gallons per flush and
shall meet performance standards established
by the American National Standards Institute
Standard A112.19.2, and urinals and associated
flushometer valves, if any, shall use no more
than one gallon per flush and shall meet
performance standards established by the
American National Standards Institute Standard
A112.19.2. H & S Code, Section 17921.3(b).
EHERGY
'0. Provide complete energy design calculations,
including all existing design and new energy
design for this building. See attached non-
residential energy design checklist.
.01. For remodels in an existing conditioned space,
/ show that the remodeled space will not use
more energy than the existing space or show
the remodeled space will conform to latest
energy design standards.
10,
10Z.
MISCELLANEOUS
10Z. Please see additional corrections or remarks
that follow.
103.)To speed up the recheck process, note on this
V J list (or a copy) whee each correction item has
— been addressed, i.e., plan sheet, note or
detail number, calculation page, etc.
Please indicate here if any changes have been
made to the plans that are not a result of
corrections from this list. If there are
other changes, please briefly describe them
and where they are located in the plans.
Have changes been made to the plans not
resulting from this correction list? Please
check.
Yes No
8/4/92
The jurisdiction has contracted with Esgil
Corporation located at 9320 Chesapeake Drive, Suite
208, San Diego, California 92123; telephone number
of 619/560-1468, to perform the plan check for your
project. If you have any questions regarding these
plan check items, please contact
at Esgil Corporation
Thank you.
Enclosures:
l._
2-_
3.
8/4/92
Datei Jurisdiction
Prepared byi Q Bldg. Dept
VALUATION AND PLAN CHECK FEE
PLAN CHECK NO.
BUILDING ADDRESS
APPLICANT/CONTACT
BUILDING OCCUPANCY _
TYPE OF CONSTRUCTION
- 312- (
PHONE NO.
DESIGNER PHONE
CONTRACTOR PHONE
BUILDING PORTION
n~: i .
Air Conditionine
Commercial
Residential
Res. or Comm.
Fire Surinklers
Total Value
BUILDING AREA
^56 't
VALUATION
MULTIPLIER
3$^
@
@
@
VALUE
^4) M^ —^
J>H\ ^od"^
Building Permit Fee $
Plan Check Fee $
COMMENTS:
SHEET CD
12/87
PLANNING/ENGINEERING APPROVALS
PERMIT NUMBER CB DATE
ADDRESS
RESIDENTIAL
RESIDENTIAL ADDITION MINOR
« $10,000.00)
TENANT IMPROVEMENT
PLAZA CAMINO REAL
VILLAGE FAIRE
OTHER
COMPLETE OFFICE BUILDING
r
PLANNER DATE
ENGINEER DATE
C:\WP51 \FILES\BLDG.FRM Rev 11/15/90
Plan Check No. 9*-
PLANNING CHECKLIST
Address
Planner VAN LYNCH Phone 438-1161 ext. 4325
(Name)
« *» 4>
APN:
Type of Project and Use (O &*?&&' V&
Zone K AI Facilities Management Zone ^___
CFD (in/otitj # "^
citcle' at property in, complete SPECIAL TAX CALCULATION
WORKSHEET provided by Building Department.)
*>
Legend
s s s _
Ob a. a. V J
Item Complete
Item Incomplete - Needs your action
1, 2, 3 Number in circle indicates plancheck number where deficiency was
identified
D Environmental Review Required: YES NOX TYPE
DATE OF COMPLETION:
Compliance with conditions of approval? If not, state conditions which require action.
Conditions of Approval
D Discretionary Action Required: YES NO X TYPE
DATE: ^___APPROVAVRESO. NO.
PROJECT NO.
OTHER RELATED CASES:
Compliance with conditions of approval? If not, state conditions which require action.
Conditions of Approval
California Coastal Commission Permit Required: YES _ NO A*
DATE OF APPROVAL:
San Diego Coast District, 3111 Camino Del Rio North, Suite 200, San Diego, CA. 92108-1725
(619) 521-8036
Compliance with conditions of approval? If not, state conditions which require action.
Conditions of Approval _ _
era D Inclusionary Housing Fee required: YES NO
(Effective date of Inclusionary Housing Ordinance - May 21, 19930
D
or:D
D
Q^JD
Site Plan:
Zoning:
1. Provide a fully dimensioned site plan drawn to scale. Show: North
arrow, property lines, easements, existing and proposed structures,
streets, existing street improvements, right-of-way width, dimensioned
setbacks and existing topographical lines.
2. Provide legal description of property, and assessor's parcel number.
Setbacks:
ODD
,A/tf6 Front:
ti^ tat. Side:
Street Side:
Rear:
2. Lot coverage:
3. Height:
f^i*0&' ' 4. Parking:
tt**^
Additional Comments
Required
Required
Required
Required
Required
Required
Spaces Required
Guest Spaces Required
Shown
Shown
Shown
Shown
Shown
Shown
Shown
Shown
OK TO ISSUE AND ENTERED APPROVAL INTO COMPUTER DATE
PLNOCFRM
City of Carlsbad 94075
Fire Department • Bureau of Prevention
Plan Review: Requirements Category: Building Plan Check
Date of Report: Tuesday. April 5.1994 Reviewed by:
Contact Name Richard Marsch
Address 6351 Corte Del Abeto #113
City, State Carlsbad CA 92009
Bldg. Dept. No. 94-312 Planning No. t
Job Name Crystal/203/6/8
Job Address 1901 Camino Vida Roble Ste. or Bldg. No. 2Q3'
E3 Approved - The item you have submitted for review has been approved. The approval is
based on plans; information and/or specifications provided in your submtttal;
therefore any changes to these items after this date, including field modifica-
tions, must be reviewed by this office to insure continued conformance with
applicable codes. Please review carefully all comments attached, as failure
to comply with instructions in this report can result in suspension of permit to
construct or install improvements.
D Disapproved - Please see the attached report of deficiencies. Please make corrections to
plans or specifications necessary to indicate compliance with applicable
codes and standards. Submit corrected plans and/or specifications to this
office for review.
For Fire Department Use Only
Review 1 st 2nd 3rd
Other Agency ID
CFD Job# 94075 File#
2560 Orion Way * Carlsbad, California 92008 * (619) 931-2121
City of Carlsbad 94075
Fire Department • Bureau of Prevention
Plan Review: Requirements Category: Building Plan Check
Date of Report: Wednesday, March 30.1994 Reviewed by:
Contact Name Richard Marsch __^__
Address 6351 Corte Del Abeto #113
City, State Carlsbad CA 92009
Bldg. Dept. No. 94-312 Planning No.
Job Name Crystal/203/6/8
Job Address 1901 Camino Vida Roble Ste. or Bldg. No. 2Q3/
Approved - The item you have submitted for review has been approved. The approval is
based on plans; information and/or specifications provided in your submittal;
therefore any changes to these items after this date, including field modifica-
tions, must be reviewed by this office to insure continued conformance with
applicable codes. Please review carefully all comments attached, as failure
to comply with instructions in this report can result in suspension of permit to
construct or install improvements.
Disapproved - Please see the attached report of deficiencies. Please make corrections to
plans or specifications necessary to indicate compliance with applicable
codes and standards. Submit corrected plans and/or specifications to this
office for review.
For Fire Department Use Only
Review 1 st 2nd 3rd
Other Agency ID
CFD Job# 94075 File#
2560 Orion Way • Carlsbad, California 92008 • (619) 931-2121
L
BUILDING PERMIT
05/05/94 10:45
Page 1 of 1
Job Address: 1901 CAMINO VIDA ROBLE Suite:
Permit Type: PLAN CHECK REVISION
Parcel No: 212-092-20-00 Lot#:
Valuation: 0
Construction Type: NEW
Occupancy Group: Referenced: 94-312
Description: REMOVE 1030 SF OFFICE
PCR No:
Project No:
Development No:
/,
PCR94012
A9400438
Status:
Applied:
Apr/Issue:
Entered By:
ISSUED
04/21/94
05/05/94
MDP
Appl/Ownr : MARSCH, RICHARD
5411 AVENIDA ENCINAS #120
CARLSBAD, CA. 92008
*** Fees Required ******
619 431-0266
Fees Collected & Credits ** *
Fees: 109^430
Adjustments: *t*^0
Total Fees: l^l^pO
Fee description
Plan Check Revision Fee
Total Credits:
Total Payments:
Units
109.00
.00
.00
109.00
Ext fee Data
109.00
CITY OF CARLSBAD
2075 Las Palmas Dr., Carlsbad, CA 92009 (619) 438-1161
PERMIT APPLICATION
**-
City of Carlsbad Building Department
2075 Las Palnas Dr., Carlsbad, CA 92009 (619) 438-1161
I. PERMIT TYPE
From List 1 (see back) give code of Permit-Type:
For Residential Projects Only: From List 2 (see back) give
Code of Structure-Type:
Net Loss/Gain of Dwelling Units
PLAN CHECK NO.
PLAN CK DEPOSIT
VALID. BY
DATE
2. PROJECT INFORMATION FOR OFFICE USE ONLY
Address
Nearest Cross Street
J%£^£Buildmg or Suite No.
LEGAL DESCRIPTION Lot No.Subdivision Name/Number Unit No.Phase No.
CHECK BELOW IF SUBMITTED:
D 2 Energy Calcs D 2 Structural Calcs D 2 Soils Report D 1 Addressed Envelope
ASSESSOR'S PARCEL
DESCRIPTION OF WORK
'Z. 1*2.
SQ. FT.# OF STORIES # OF BEDROOMS # OF BATHROOMS
3. (JUNTACT FtKbuw (a airierenl trom applicant;
NAME (last name first)
CITY STATE
ADDRESS
ZIP CODE DAY TELEPHONE
I. APPLICANT UCONTRACTOR U AGLNTFOR CONIKACTOR DOWNER EJAGENI rOR OWNER
NAME (last name first)
CITY/STATE ZIP CODE DAY TELEPHONE
5TPHOPERTY OWNERT
NAME (last name first)
CITY
ADDRESS
STATE ZIP CODE DAY TELEPHONE
6. CONTRACTOR
NAME (last name first)
CITY TATE
ADDRESS
ZIP CODE DAY TELEPHONE
STATE IJC. #LICENSE CLASS CITY BUSINESS LIC. #
L3ESIGNERNAME (last name lirstj
CITY
ADDRESS
STATE ZIP CODE DAY TELEPHONE STATE LIC. #
7. WORKERS^ COMPENSATION
Workers Compensation Declaration: I hereby arrinn that I have a certificate or consent to sell-insure issued by the Director of Industrial
Relations, or a certificate of Workers' Compensation Insurance by an admitted insurer, or an exact copy or duplicate thereof certified
by the Director of the insurer thereof filed with the Building Inspection Department (Section 3800, Lab. C).
INSURANCE COMPANY POLICY NO.EXPIRATION DATE
Certificate of Exemption: I certify that in the performance of the work lor which this permit is issued, I snail not employ any person in any manner
so as to become subject to the Workers' Compensation Laws of California.
SIGNATURE DATE
8. OWNER-BUILDER Dl TION
LJwner-Builoer Declaration^ hereby atiinn that 1 am exempt from the contractors License Law lor the following reason:
D I, as owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not intended or
offered for sale (Sec. 7044, Business and Professions Code: The Contractor's License Law does not apply to an owner of property who builds
or improves thereon, and who does such work himself or through his own employees, provided that such improvements are not intended
or offered for sale. If, however, the building or improvement is sold within one year of completion, the owner-builder will have the burden
of proving that he did not build or improve for the purpose of sale.).
D I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions
Code: The Contractor's License Law does not apply to an owner of property who builds or improves thereon, and contracts for such projects
with contractor(s) licensed pursuant to the Contractor's License Law).
D I am exempt under Section _ Business and Professions Code for this reason:
(Sec. 7031.5 Business and Professions Code: Any City or County which requires a permit to construct, after, improve, demolish, or repair
any structure, prior to its issuance, also requires the applicant for such permit to file a signed statement that he is licensed pursuant to the
provisions of the Contractor's License Law (Chapter 9, commencing with Section 7000 of Division 3 of the Business and Professions Code)
or that he is exempt therefrom, and the basis for the alleged exemption. Any violation of Section 7031.5 by any applicant for a permit
subjects the applicant to a civil penalty of not more than five hundred dollars [$500]).
SIGNATURE DATE
COMPLETE THIS SECTION FOR NQN -RESIDENTIAL BUILDING PERMITS ONLY:
Is the applicant or future building occupant required to submit a business plan, acutely hazardous materials registration form or risk management and
prevention program under Sections 25505, 25533 or 25534 of the Presley-Tanner Hazardous Substance Account Act?
D YES D NO
Is the applicant or future building occupant required to obtain a permit from the air pollution control district or air quality management district?
D YES D NO
Is the facility to be constructed within 1,000 feet of the outer boundary of a school site?
D YES D NO
IF ANY OF THE ANSWERS ARE YES, A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED AFim JULY 1, 1989 UNLESS THE APPLICANT
HAS MET OR IS MEETING THE REQUIREMENTS OF THE OFFICE OF EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT.
9. UJNSTHmJTloN LENDING AGENCY '
l hereby attirm that there is a construction lending agency tor the pertormance ot the work tor which this permit is issued 3097UJ Civil CodeJ.
LENDER'S NAME LENDER'S ADDRESS
10. AFFUCANI
I certify that 1 nave read the application and state that the above information is correct. T agree to comply with all City ordinances and State laws
relating to building construction. I hereby authorize representatives of the City of Carlsbad to enter upon the above mentioned property for inspection
purposes. I ALSO AGREE TO SAVE INDEMNIFY AND KEEP HARMLESS THE CITY OF CARLSBAD AGAmST ALL UABIUTIES, JUDGMENTS, COSTS
AND EXPENSES WHICH MAY IN ANY WAY ACCRUE AGAINST SATO CITY IN CONSEQUENCE OF THE GRANTING OF THIS PERMIT.
OSHA: An OSHA permit is required for excavations over 5'0" deep and demolition or construction of structures over 3 stories in height.
Expiration. Every permit issued by die Building Official under the provisions of this Code shall expire by limitation and become null and void if the
building or work authorized by such permit is not commenced within 365 days from the date of such permit or if the building or work authorized by
such permit is suspended or abandoned at any time after the work is commenced for a period of 180 days (Section 303(d) Uniform Building Code).
--- DATE: •/-£/*M
WHITE: File YELLOW: Applicant PINK: Finance
ESGIL CORPORATION
9320 CHESAPEAKE DR.. SUITE 208
SAN DIEGO. CA 92123
(619)560-1468
DATE:
JURISDICTION:
PLAN CHECK NO:
PROJECT ADDRESS: \r\Q\
PROJECT NAME:
Z.
The plans transmitted herewith have been corrected where
necessary and substantially comply with the jurisdiction,' s
building codes.
The plans transmitted herewith will substantially comply
with the jurisdiction's building codes when minor deficien-
cies identified are resolved and
checked by building department staff.
The plans transmitted herewith have significant deficiencies
identified on the enclosed check list and should be corrected
and resubmitted for a complete recheck.
The check list transmitted herewith is for your information.
The plans are being held at Esgil Corp. until corrected
plans are submitted for recheck.
The applicant's copy of the check list is enclosed for the
jurisdiction to return to the applicant contact person.
The applicant's copy of the check list has been sent to:
Esgil staff did not advise the applicant contact person that
plan check has been completed.
Esgil staff did advise applicant that the plan check has
been comoleted. Person contacted:
Date contacted:
REMARKS:
Teleohone £
By •>'' o
ESGIL CORPORATION
Enclosures
DGA DCM
L>ate Jurisdiction
Prepared byi
VALUATION AND PLAN CHECK FEE
Bldg. Dept
Esgil
PLAN CHECK NO.
BUILDING ADDRESS
APPLICANT/CONTACT
BUILDING OCCUPANCY
\M
H._.PHONE NO.
DESIGNER PHONE .—
TYPE 0? CONSTRUCTIQN CCNTRACTO?, PHONE
.,TTnTrp .„ , , MM- ... . ba . .
*<1?*%"S/*« TT
1/17, ,0K ^^T^i
Air Conditionine
Commercial
Residential
Res. or Comm.
Fire S-orir.klers
IW,
i
Total Value
VALUATION
MULTIPLIER
Zl.lrfn^
'
@
@
@
VALUE
^7"*7 1 ^^^ / t- * \ J(
^
Building Permit Fee $_
Plan Check Fee $
COM M E N I S:
SHEET (S) OF (Tj
12/87
City of Carlsbad 94075
Fire Department * Bureau of Prevention
Plan Review: Requirements Category: Building Plan Check
Date of Report: Friday. April 29, 1994 _ Reviewed bv:
Contact Name Richard Marsch
Address 6351 Cone Del Abeto #113
City, State Carlsbad CA 92009
Bldg. Dept. No. 94-312 Planning No.
Job Name Crystal/203/6/8
Job Address 1901 Camino Vida Robie Ste. or Bldg. No. 203/
Approved - The item you have submitted for review has been approved. The approval is
based on plans; information and/or specifications provided in your submittal;
therefore any changes to these items after this date, including field modifica-
tions, must be reviewed by this office to insure continued conformance with
applicable codes. Please review carefully all comments attached, as failure
to comply with instructions in this report can result in suspension of permit to
construct or install improvements.
Disapproved - Please see the attached report of deficiencies. Please make corrections to
plans or specifications necessary to indicate compliance with applicable
codes and standards. Submit corrected plans and/or specifications to this
office for review.
For Fire Department Use Only
Review 1 st 2nd 3rd
Other Agency ID
CFD Job# 94075 File*
2560 Orion Way • Carlsbad, California 92008 • (619) 931-2121