HomeMy WebLinkAbout1911 CALLE BARCELONA; 152; CB041540; PermitJ \w94 City of Carlsbad
1635 Faraday Av Carlsbad, CA 92008
Building Inspection Request Line (760) 602-2725
Commercialllndustrial Permit Perm ): CB0415
Job Address: 191 1 CALLE BARCELONA CBAD St: 152
Permit Type:
Parcel No:
Valuation:
Occupancy Group:
Project Title:
TI Sub Type: COMM
Lot#: 0 Status: ISSUED
$66,240.00 Construction Type: NEW Applied: 05/07/2004
SOLE COMFORT Plan Approved: 06/07/2004
2,208 SF IMPROVEMENT Issued: 06/08/2004
Reference #: Entered By: MDP
Inspect Area :
Plan Check#:
Applicant: Owner:
RUSSELL STOUT & ASSOC
4563 CASS STREET
SAN DIEGO 92109
858 581 -281 2
0
Building Permit
Add'l Building Permit Fee
Plan Check
Add'l Plan Check Fee
Plan Check Discount
Strong Motion Fee
Park Fee
LFM Fee
Bridge Fee
BTD #2 Fee
BTD #3 Fee
Renewal Fee
Add'l Renewal Fee
Other Building Fee
Pot. Water Con. Fee
Meter Size
Add'l Pot. Water Con. Fee
Recl. Water Con. Fee
$419.51 $0.00
$272.68
$0.00
$0.00
$13.91 $0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
Meter Size
Add'l Recl. Water Con. Fee
Meter Fee
SDCWA Fee
CFD Payoff Fee
PFF
PFF (CFD Fund)
License Tax
License Tax (CFD Fund)
Traffic Impact Fee
Traffic Impact (CFD Fund)
PLUMBING TOTAL
ELECTRICAL TOTAL
MECHANICAL TOTAL
Master Drainage Fee
Sewer Fee
Redev Parking Fee
Additional Fees
TOTAL PERMIT FEES
$0.00
$0.00
$0.00
$0.00
$0.00 $0.00
$0.00
$0.00
$0.00
$0.00
$41 .OO
$45.00
$48.50
$0.00
$0.00 $0.00
$0.00
$840.60
Total Fees: $840.60 Total Payments To Date: $272.68 Balance Due: $567.92
Clearance:
processing in accordance with Carlsbad Municipal Code Section 3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack,
review, set aside, void, or annul their imposition.
561.92
PE $& LlCATl ~~\ocl~
CITY OF CARLSBAD BUILDING DEPARTMENT
1635 Faraday Ave., Carlsbad, CA 92008
\a I I
FOR OFFICE USEM , r%
PLAN CHECK NO.
EST. VAL. 66.7 * ' -xu
IPlan Ck. Deposit '7 37- 6%
D
(Sec. 7031.5 Business and Professions Code: Any City or County which requires a permit to construct, alter, improve, demolish or repair any structure, prior to its
issuance, also requires the applicant for such permit to file a signed statement that he is licensed pursuant to the provisions of the Contractor's License Law
[Chapter 9, commending with Section 7000 of Division 3 of the Business and Professions Code1 or that he is exempt therefrom, and the basis for the alleged
4
- i
Designer Name Address city Statelzip Telephone
of perjury one of the f
0 I have and will maintain a certificate of consent to self-insure for workers' compensation as provided by Section 3700 of the Labor Code, for the performance
of the work for which this permit is issued.
0 I have and will maintain workers' compensation, as required by Section 3700 of the Labor Code, for the performance of the work for which this permit is
issued. My worker's compensation insurance carrier and policy number are:
Insurance Company 3- ab Policy No. -ti30 -2-q 'J Expiration Date 0.r
(THIS SECTION NEED NOT BE COMPLETED IF THE PERMIT IS FOR ONE HUNDRED DOLLARS [$lo01 OR LESS)
he performance of the work for which this permit is issued. I shall not employ any person in any manner so as
s of California.
coverage is unlawful, and shall subject an employer to crimina civil fines up to one hundred
compensation, damages as provided for in Section 3706 of the rest and attorney's fees.
I hereby affirm that I am exempt from the Contractor's License Law for the following reason:
0 I, as owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not intended or offered for sale
(Sec. 7044, Business and Professions Code: The Contractor's License Law does not apply to an owner of property who builds or improves thereon, and who does
such work himself or through his own employees, provided that such improvements are not intended or offered for sale. If, however, the building or improvement is sold within one year of completion, the owner-builder will have the burden of proving that he did not build or improve for the purpose of sale).
I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions Code: The
Contractor's License Law does not apply to an owner of property who builds or improves thereon, and contracts for such projects with contractor(s) licensed
pursuant to the Contractor's License Law).
0
1.
2.
3.
I am exempt under Section
I personally plan to provide the major labor and materials for construction of the proposed property improvement. 0 YES ON0
I (have I have not) signed an application for a building permit for the proposed work.
I have contracted with the following person (firm) to provide the proposed construction (include name I address I phone number I contractors license number):
Business and Professions Code for this reason:
4.
number I contractors license number):
5.
of work):
PROPERTY OWNER SIGNATURE DATE
COMPUTE THIS SECTION FOR NON-REsI€NTIAL BUILDING PERMITS ONLY
Is the applicant or future building occupant required to submit a business plan, ac
program under Sections 25505, 25533 or 25534 of the Presley-Tanner Hazardous Substance Account Act? 0 YES 0 NO
Is the applicant or future building occupant required to obtain a permit from the air pollution control district or air quality management district? YES >NO
Is the facility to be constructed within 1,000 feet of the outer boundary of a school site? 0 YES? NO
IF ANY OF THE ANSWERS ARE YES, A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUE
REQUIREMENTS OF THE OFFICE OF EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT.
I plan to provide portions of the work, but I have hired the following person to coordinate, supervise and provide the major work (include name I address I phone
I will provide some of the work, but I have contracted (hired) the following persons to provide the work indicated (include name I address I phone number I type
UNLESS THE APPLICANT HAS MET OR IS MEETING THE
e per
LENDER'S NAME LENDER'S ADDRESS
I certify that I have read the application and state that the above information is correct and that the information on the plans is accurate. I agree to comply with all
City ordinances and State laws relating to building construction. I hereby authorize representatives of the Citt of Carlsbad to enter upon the above mentioned
property for inspection purposes. I ALSO AGREE TO SAVE, INDEMNIFY AND KEEP HARMLESS THE CITY OF CARLSBAD AGAINST ALL LIABILITIES,
OSHA: An OSHA permit is required for excavations over 5'0" deep and demolition or construction of structures over 3 stories in height.
EXPIRATION. Every permit issued by the building Official under the provisions of this Code shall expire by limitation and become null and void if the building or work
authorized by such permit is not commenced within 180 days from the date of such permit or if the building or work authorized by such permit is suspended or abandoned
at any time after the work I
APPLICANT'S SIGNATURE DATE
JUDGMENTS, COSTS AND EXPENSES WHICH MAY IN ANY WAY ACCRUE AGAINST SAID CITY IN CONSEQUENCE OF THE GRANTING OF THIS PERMIT.
YELLOW: Applicant PINK: Finance
City ef Carlsbad
Final Building Inspection
Dept: Building Engineering Planning CMWD St Lite
Plan Check #:
Permit #: CEO41540
Project Name: SOLE COMFORT
2,208 SF IMPROVEMENT
191 1 CALLE BARCELONA #152 Address:
Contact Person: DON HUMPHRIES Phone: 61 92470221
Sewer Dist: Water Dist:
Lot:
Date:
Permit Type:
Sub Type:
0
oa10312004
TI
COMM
By: & Date Inspected: 7bv/ou Approved: Disapproved:
Inspected
Y Inspected Date
By: Inspected: Approved: Disapproved:
Inspected Date
By: Inspected: Approved: Disapproved:
...............................................................................................................................................................
Comments:
City of Carlsbad Bldg
For: 08/05/2004
Permit# CB041540
Title: SOLE COMFORT
Description: 2,208 SF IMPROVEMENT
Type: TI Sub Type: COMM
Job Address: 191 1 CALLE BARCELONA
Suite: 152 Lot 0
Location:
APPLICANT RUSSELL STOUT & ASSOC
Owner:
Remarks: PM PLEASE
Total Time:
Inspection Request
Inspector Assignment: PS
Phone: 6192470221
Requested By:
Entered By:
DON HUMPHRIES
CHRISTINE qomment CD Description
19 Final Structural
~-
Associated PCRs/CVs
CV040459 CLOSED 2- B.4”ER;
Inspection History
Date Description
08/03/2004 89
08/02/2004 89
0711 512004 17
0711 312004 14
07/12/2004 14
07/12/2004 84
07/09/2004 14
06/23/2004 14
06/22/2004 14
06/22/2004 24
06/22/2004 34
06/21/2004 14
06/21/2004 24
0612 1 I2004 34
0611 712004 1 1
0611 712004 14
0611 712004 24
0611 712004 34
06/16/2004 11
0611 512004 21
0611 512004 24
0611 !5/2004 31
Final Combo
Final Combo
Interior LatNDrywall
Frame/Steel/Bolting/Welding
Frame/Steel/BoltinghVelding
Rough Combo
Frame/Steel/Bolting/Welding
Frame/Steel/Boltin@/elding
Frame/Steel/Bolting/Welding
RoughlTopout
Rough Electric
FramelSteeUBoltingNVelding
RoughfTopout
Rough Electric
FtgIFoundatiodPiers
FramelSteellBoltinghVelding
RougWopout
Rough Electric
FtglFoundationlPiers
UndergroundIUnder Floor
RoughlTopout
UndergroundlConduit-W iring
Act lnsp
PA PY
CA PY
AP PS
AP PS
NR PS
NR PS
NR PS
CA PS
AP PS
AP PS
AP PS
NR PS
NR PS
NR PS
CA PY
CA PY
CA PY
CA PY
AP PY
AP PY
AP PY
NR PY
Comments
OK TO STOCK - EMR
NO FIRE
RESET FOR MONDAY-NO FIRE APP
BY DON
WALLS ONLY
ELEC NOT COMPLETE
PLUMB & ELECT TRENCHES
c
City of Carlsbad Building Department
1635 Faraday Avenue Catisbad, CA 92008
Building Inspector Attention:
From: Russ Stout
Re: Sole Comfort - PC # 04-1 540
RUSSELL STOUT & ASSOCIATES, INC. Architecture Planning & interiors
Via: P Fax, Page (s)
0 Team Repro. / CA Overnight P Team Repro. / Fed. Express
0 Team Reprographics
F3 US. Mail
IS Hand Delivery
Q Other:
To Whom It May Concern.
Please disregard note on reflected ceiling plan (sheet A2) requiring a scrim sheet be added to the existing insulation. Also, the existing exposed insulation in the stock room is not required to be painted. No work to be
done at insulation - leave as is.
Kevin Renac Russell Stout & Associates
4635 CASS STREET + SAN DIEGO + CALIFORNIA 92109+ VOICE: (858) 581-2812 + FAX: (858) 272-8873
City of Carlsbad Bldg Inspection Request
For: 08/03/2004
Permit# CB041540
Title: SOLE COMFORT
Description: 2,208 SF IMPROVEMENT
Type: TI Sub Type: COMM
Job Address: 191 1 CALLE BARCELONA
Suite: 152 Lot 0
Location:
APPLICANT RUSSELL STOUT 81 ASSOC
Owner:
Remarks: P M PLEASE
Total Time:
CD Description
19 Final Structural
29 Final Plumbing
39 Final Electrical
Inspector Assignment: PS
Phone: 6192470221
Inspector: 9
Requested By: DON HUMPHRIES
Entered By: CHRISTINE
Act Comment .
4 49 Final Mechanical I
Associated PCRs/CVs
CV040459 CLOSED 2- BANNER;
Date
0711 512004
0711 312004
0711 212004
0711 2I2004
07/0912004
06/23/2004
06/22/2004
06/22/2004
06/22/2004
0612 1 I2004
06/21/2004
06/21/2004
0611 712004
0611 712004
0611 712004
0611 712004
Inspection History
Description
17 Interior LathIDrywall
14 FramelSteellBoltingMlelding
14 FrarnelSteellBoltingMlelding
84 Rough Combo
1 4 FramelSteellBoltingMlelding
14 FramelSteellBolting/Welding
14 FrarnelSteellBoltingMlelding
24 RougNTopout
34 Rough Electric
14 FramelSteellBoltingMlelding
24 RougNTopout
34 Rough Electric
11 FtgIFoundatiorVPiers
14 FramelSteellBoltingMlelding
24 Rough/Topout
34 Rough Electric
Act lnsp Comments
AP PS
AP PS
NR PS NOFIRE
NR PS
NR PS RESET FOR MONDAY-NO FIRE APP
CA PS BYDON
AP PS WALLSONLY
AP PS
AP PS
NR PS ELEC NOT COMPLETE
NR PS
NR PS
CA PY
CA PY
CA PY
CA PY
..
\.
CITY OF CARLSBAD NOTICE (7601 602-2700
BUILDING DE.PARTMENT 1635 FARADAV AVENUE
A
FOR INSPECTION CALL (760) 602-2725. RE-INSPECTION FEE DUE? 1 YES
PHONE
CODE ENFORCEMENT OFFICER @
Carlsbad 04- 1540
6/4/04
EsGii CorDoration
DATE: 6/4/04
JURIS D I CTl ON : Carlsbad
PLAN CHECK NO.: 04-1540
0 APPLICANT
P PLANREVIEWER -
0 FILE
SET: II
PROJECT ADDRESS: 1911 Calle Barcelona, Bldg #4, Suite 152
PROJECT NAME: Sole Comfort Retail Store
The plans transmitted herewith have been corrected where necessary and substantially comply
c] The plans transmitted herewith will substantially comply with the jurisdiction’s building codes when
with the jurisdiction’s building codes.
minor deficiencies identified below are resolved and checked by building department staff.
0 The plans transmitted herewith have significant deficien@es identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
The applicant’s copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
0 The applicant’s copy of the check list has been sent to:
Esgil Corporation staff did not advise the applicant that the plan check has been completed.
Esgil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted:
Date contacted: (by: )
Mail Telephone Fax In Person
c] REMARKS:
Telephone #:
Fax #:
By: Chuck Mendenhall Enclosures:
Esgil Corporation
GA MB 0 EJ PC 5/27/04 tmsmtl.dot
.- -4
EsGil Corporation
In Tartnership with Government fm Building Safety
DATE: 5/20/04
J U RIS D l CTl ON : Carlsbad
PLAN CHECK NO.: 04-1540
0 APPLICANT
0 PLAN REVIEWER
0 FILE
&all@=-
SET: I
PROJECT ADDRESS: 1911 Calle Barcelona, Bldg #4, Suite 152
PROJECT NAME: Sole Comfort Retail Store
0 The plans transmitted herewith have been corrected where necessary and substantialJy comply
0 The plans transmitted herewith will substantially comply with the jurisdiction’s building codes
with the jurisdiction’s building codes.
when minor deficiencies identified below are resolved and checked by building department staff.
The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
0 The applicant’s copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
The applicant’s copy of the check list has been sent to:
Russell Stout & Assoc. , Att’n: Kevin Renic
4635 Cass St., San Diego, CA 92109
0 Esgil Corporation staff did not advise the applicant that the plan check has been completed.
Esgil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Kevin Renic
Date contacted:51%[o-t (by:% )
Telephone #: 581 -281 2
Fax #: s%. 2qL- Bey3
MailJTelephone J’ Fax4 In Person 0 REMARKS:
By: Chuck Mendenhall Enclosures:
Esgil Corporation
GA [7 MB [7 EJ PC 5/10/04 tmsmtl.dot
9320 Chesapeake Drive, Suite 208 + San Diego, California 92123 + (858) 560-1468 + Fax (858) 560-1576
Carlsbad 04-1540
5/20/04
PLAN REVIEW CORRECTION LIST
TENANT IMPROVEMENTS
PLAN CHECK NO.: 04-1540
OCCUPANCY: M USE: Retail Store
TYPE OF CONSTRUCTION: V N
ALLOWABLE FLOOR AREA: no change
J U RIS D I CTl ON : Carlsbad
ACTUAL AREA: 2208 'I7 Only
STORIES: no change
HEIGHT: no change
SPRINKLERS?: Yes OCCUPANT LOAD: 45
REMARKS:
DATE PLANS RECEIVED BY
JURISDICTION: ESGIL CORPORATION: 5/10/04
DATE INITIAL PLAN REVIEW
COMPLETED: 5/20/04
FOREWORD (PLEASE READ):
This plan review is limited to the technical requirements contained in the Uniform Building Code,
Uniform Plumbing Code, Uniform Mechanical Code, National Electrical Code and state laws
regulating energy conservation, noise attenuation and access for the disabled. This plan review
is based on regulations enforced by the Building Department. You may have other corrections
based on laws and ordinances enforced by the Planning Department, Engineering Department,
Fire Department or other departments. Clearance from those departments may be required
prior to the issuance of a building permit.
DATE PLANS RECEIVED BY
PLAN REVIEWER: Chuck Mendenhall
Code sections cited are based on the 1997 UBC.
The following items listed need clarification, modification or change. All items must be satisfied
before the plans will be in conformance with the cited codes and regulations. Per Sec. 106.4.3,
1997 Uniform Building Code, the approval of the plans does not permit the violation of any
state, county or city law.
To speed up the recheck process, please note on this list (or a copy) where each
correction item has been addressed, Le., plan sheet number, specification section, etc.
Be sure to enclose the marked up list when vou submit the revised plans.
TENANT IMPROVEMENTS WITHOUT SPECIFIC ENERGY DATA OR POLICY SUPPLEMENTS (1997UBC) tifowdot
Carlsbad 04- 1540
5/20/04
Please make all corrections on the original tracings, as requested in the correction
list. Submit three sets of plans for commercial/industriaI projects (two sets of plans for residential projects). For expeditious processing, corrected sets can be
submitted in one of two ways:
1. Deliver all corrected sets of plans and calculations/reports directly to the City of
Carlsbad Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760)
602-2700. The City will route the plans to EsGil Corporation and the Carlsbad
Planning, Engineering and Fire Departments.
2. Bring one corrected set of plans and calculationdreports to EsGil Corporation,
9320 Chesapeake Drive, Suite 208, San Diego, CA 921 23, (858) 560-1 468.
Deliver all remaining sets of plans and calculationdreports directly to the City of
Carlsbad Building Department for routing to their Planning, Engineering and Fire
Departments.
NOTE: Plans that are submitted directly to EsGil Corporation only will not be
reviewed by the City Planning, Engineering and Fire Departments until review by
EsGil Corporation is complete.
1. The occupant load information and egress diagram on sheet CSI indicates two
exits are required based on an occupant load of 50. this is the code requirement.
However, you are showing that the 2"d exit is accessed through the storage
room. Exits may pass through adjacent rooms but not kitchens or store rooms.
UBC 1004.2.2. The occupant load that I determine based on the uses and
eliminating the area of the rest room is only 45 occupants and requires only one
exit. Revise the plans to show only one exit is required or extend the one hour
rated exit corridor through the store room.
2. Show in detail 19/A5.1 lateral support for the top of the wall that supports the
glass store front.
3. Specify on sheet A5.1 the thickness and type of store front glass you intend to
install.
4. The ENV-1 and MECH-1 section of the energy form PERF-1 imprinted on sheet
M-2 must be signed by the professionals assuming design responsibility for the
sections of the energy design.
DISABLED ACCESS REVIEW LIST
DEPARTMENT OF STATE ARCHITECT
TITLE 24
a SITE PLAN REQUIREMENTS
5. Clearly show that the site development is designed to provide access from the
disabled accessible parking the entrance of the tenant space. Section 1 127B.1.
Carlsbad 04-1540
~ 5120104
Where necessary to provide access, shall incorporate pedestrian ramps, curb
ramps, stairways and handrails, etc.
6. Show on the site plan the required number of accessible parking spaces for new
facilities. Per Table 11 B-7 the minimum number of spaces is:
a) 1 for each 25 spaces up to 100 total spaces.
7. Show that accessible parking spaces comply with Section 1 1298.4.1 as follows:
a) Single spaces shall be 14' wide and outlined to provide a 9' parking area and a 5' loading and unloading area on the passenqer side of the vehicle.
b) When more than one space is provided, in lieu of providing a 14' space for each space, two spaces can be provided within a 23' area with a 5' loading
zone between each 9'0" wide space.
Each space is to be a minimum of 18 in depth. c)
At least one in every 8 accessible parking spaces shall be served by an access
aisle 296" in width and designated as VAN ACCESSIBLE, per Section 11296.4.2.
The words "NO PARKING" shall be painted on the ground within each loading and
unloading access aisle (in white letters no less than 12' high and located so that it
is visible to traffic enforcement officials). Section 1 129B.4.2.
Ramps shall not encroach into any accessible parking space or the adiacent
access aisle. Section 1 129B.4.3.
8.
9.
10.
a DOORS
11. Show or note that the lower IO'' of all doors comply with Section 11338.2.6, as
follows: See detail 20/A5.1. The bottom edge finish of the door must be a min.
of 10".
a) To be smooth and uninterrupted, to allow the door to be opened by a wheelchair footrest, without creating a trap or hazardous condition.
b) Narrow frame doors may use a 10" high smooth panel on the push side of the door.
12. Note that the doorways leading to sanitary facilities shall be identified, per Section
1 1 15B.5, as follows:
a)
b)
c)
d)
An equilateral triangle Vi" thick with edges 12" long and a vortex pointing
upward at men's rest rooms.
A circle Vi" thick, 12" in diameter at women's rest rooms.
A 12" diameter circle with a triangle superimposed on the circle and within
the 12" diameter at unisex rest rooms.
The required symbols shall be centered on the door at a height of 60".
Carlsbad 04-1540
5120104
e) Braille signage shall also be located on the wall adiacent to the latch
outside of the doorways leading to the sanitary facilities, per Section
1 1 17B.5.7.
COUNTERS
13. show or note on the plans that the service counters shall be 28 to 34" from the
floor. The disabled accessible srvice area shall be located at a section of counter
that is at least 36 long and no more than 28 to 34 high. Section 1122B.4.
To speed up the review process, note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet, note or detail number,
calculation page, etc.
The jurisdiction has contracted with Esgil Corporation located at 9320
Chesapeake Drive, Suite 208, San Diego, California 921 23; telephone number of
858/560-1468, to perform the plan review for your project. If you have any
questions regarding these plan review items, please contact Chuck Mendenhall
at Esgil Corporation. Thank you.
'
TOTAL VALUE
Carlsbad 04-1540
. 5/20/04
66,240
[VALUATION AND PLAN CHECK FEE
Bldg. Permit Fee by Ordinance
JURIS D lCTl ON: Carlsbad PLAN CHECK NO.: 04-1540
V
PREPARED BY: Chuck Mendenhall DATE: 5/20/04
Plan Check Fee by Ordinance
BUILDING ADDRESS: 1911 Calle Barcelona, Bldg #4, Suite 152
7
BUILDING OCCUPANCY: M TYPE OF CONSTRUCTION: V N
I I I I I I I I I I I
Air Conditioning
Fire Sprinklers
Jurisdiction Code I cb ley Ordinance I I $41 0.51 I
I $266.831
Type of Review: Complete Review 0 Structural Only
0 Repetitive Fee Repeats
0 Other
0 Hourly I] Hour
Esgil Plan Review Fee
Comments:
Sheet 1 of 1
macvalue.doc
PLANNINC/ENGINEERING APPROVALS
--
PERM^ NUMBER CB -1540 DATE
RESIDENTIAL ADDmON MINOR PLAZA CAMlNO REAL (< $lrO,WO.OO)
CARLSBAD COMPANV STORES
VILLAGE FAIRE
COMPLEl'E OFFlCE BUILDING
OTHER
PLANNER DATE
,Carlsbad Fire Department 04 1 546
1635 Faraday Ave.
Carlsbad, CA 92008
Fire Prevention
(760) 602-4660
Plan Review Requirements Category: Building Plan ,n
Date of Report: 05/17/2004 Reviewed by:
Name: Russell Stout
Address: 4635 Cass Street
City, State: San Diego CA 92109
Job #: 041546 Plan Checker:
Job Name: Sole Comfort Bldg #: CB041540
Job Address: 191 1 Calle Barcelona Ste. or Bldg. No. 152
0 Approved The item you have submitted for review has been approved. The approval is
based on plans, information and / or specifications provided in your submittal;
therefore any changes to these items after this date, including field
modifications, must be reviewed by this office to insure continued conformance
with applicable codes and standards. Please review carefully all comments
attached as failure to comply with instructions in this report can result in
suspension of permit to construct or install improvements.
Approved
Subject to
The item you have submitted for review has been approved subject to the
attached conditions. The approval is based on plans, information and/or
specifications provided in your submittal. Please review carefully all comments
attached, as failure to comply with instructions in this report can result in
suspension of permit to construct or install improvements. Please resubmit to
this office the necessary plans and / or specifications required to indicate
compliance with applicable codes and standards.
0 Incomplete The item you have submitted for review is incomplete. At this time, this office
cannot adequately conduct a review to determine compliance with the
applicable codes and / or standards. Please review carefully all comments
attached. Please resubmit the necessary plans and / or specifications to this
office for review and approval.
Review 1 st 2nd 3rd Other Agency ID
FD Job # 041546 FD File #
Requirements Category: Building Plan
Requirement: Pending 05.22 Exit Door Hardware
Exit doors shall be openable from the inside without the use of a key or any special knowledge or
effort.
Exception: In group B occupancies, key locking hardware may be used on the Main Exit when the
main exit consists of a single door or pair of doors if there is a readily visible, durable sign on or
adjacent to the door stating, "This door to remain unlocked during business hours."
For State Fire Marshal, sign shall read, "This door to remain unlocked whenever the building is
occupied."
See item 32 for additional exit door hardware requirements.
Thumbturn locks are not permitted for use in retail businesses in Carlsbad. CFD requires that a
Double cylinder (key) lock be installed. Additionally, if owners lockset is replced then occupant shall
be required to provide CFD with a key to the front door for emergency access.
Requirement: Pending 05.29 High Piled Combustible Storage
Storage in closely packed piles shall not exceed 15 feet in height, 12 feet on pallets or in racks and 6
feet for tires, plastics and some flammable liquids. If high piled stock piling is to be done, submit a
complete storage plan and description of the commodoties to be stored. Show compliance with
Article 81 of the Uniform Fire Code.
PLANS FOR STORAGE ROOM SHELVING/RACKS ARE REQUIRED TO BE SUBMITTED
REQUIRED.
SEPERATELY. AN APPLICATION FOR PERMIT TO INSTALL HI-PILED STORAGE SHALL BE
Page 1 0511 7/04
t -
City of Carlsbad
Building Department
1635 Faraday Avenue
Carlsbad, CA 92008
Raenette Abbey Attention:
From: Kevin Renac
Re: Sole Comfort - PC ## 04-1 540
RUSSELL STOUT & ASSOCIATES, INC.
Architecture Planning & interiors
Via: 0 Fax, page (s) El Team Repro. / CA Overnight
0 Team Repro. / Fed. Express
Team Reprographics
P U.S. Mail
P Hand Delivery 0 Other:
Raenette,
Please find the attached (2) sets of drawings along with calculationdreportdspecifications for re-submittal.
One corrected set with calculations/repwts has been sent to EsGil Corporation. Thank you Raenette.
Kevin Renac
Russell Stout & Associates
4635 CASS STREET + SAN DIEGO + CALIFORNIA 92109+ VOICE: (858) 581-2812 + FAX: (858) 272-8813
.- Carlsbad 04- 1540
5120104
Please make all corrections on the original tracings, as requested in the correction
list. Submit three sets of plans for commercial/industrial projects (two sets of plans
for residential projects). For expeditious processing, corrected sets can be
submitted in one of two ways:
1. Deliver all corrected sets of plans and calculations/reports directly to the City of
Carlsbad Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760)
602-2700. The City will route the plans to EsGil Corporation and the Carlsbad
Planning, Engineering and Fire Departments.
2. Bring one corrected set of plans and calculations/reports to EsGil Corporation,
9320 Chesapeake Drive, Suite 208, San Diego, CA 921 23, (858) 560-1468.
Deliver all remaining sets of plans and calculations/reports directly to the City of
Carlsbad Building Department for routing to their Planning, Engineering and Fire
Departments.
NOTE: Plans that are submitted directly to EsGil Corporation only will not be
reviewed by the City Planning, Engineering and Fire Departments until review by
EsGil Corporation is complete.
1. The occupant load information and egress diagram on sheet CSI indicates two
exits are required based on an occupant load of 50. this is the code requirement.
However, you are showing that the 2nd exit is accessed through the storage
room. Exits may pass through adjacent rooms but not kitchens or store rooms.
UBC 1004.2.2. The occupant load that I determine based on the uses and
eliminating the area of the rest room is only 45 occupants and requires only one
exit. Revise the plans to show only one exit is required or extend the one hour
rated exit corridor through the store room.
ucdypqh(c: s, flEvlf@, &$kQi%S 014cjrRA-4 REModGO r/hfC6 OAE Ex/'- R-3
2. Show in detail 19/A5.1 lateral support for the top of the wall that supports the
3. Specify on sheet A5.1 the thickness and type of store front glass you intend to install. ~~DS'ROAO- /VO~%S A OOW
4. The ENV-1 and MECH-I section oi the energy form PERF-1 imprinted on sheet
M-2 must be signed by the professionals assuming design responsibility for the
sections of the energy design. 5 I4NA TUG5 AmW
DISABLED ACCESS REVIEW LIST
DEPARTMENT OF STATE ARCHITECT
TITLE 24
e SITE PLAN REQUIREMENTS
5. Clearly show that the site development is designed to provide access from the
disabled accessible parking the entrance of the tenant space. Section 1 1276.1.
Carlsbad 04-1540
5/20/04
Where necessary to provide access, shall incorporate pedestrian ramps, curb
ramps, stairways and handrails, etc. MCESSI~LE PARU- rt/~u- ON EXtIwtrZj ExtSc PA)-+
Show on the site plan the required number of accessible parking spaces for new
facilities. Per Table 1 1 B-7 the minimum number of spaces is:
a)
Show that accessible parking spaces comply with Section 1129B.4.1 as follows:
a) Single spaces shall be 14' wide and outlined to provide a 9' parking area and a 5' loading and unloading area on the passenaer side of the vehicle.
b) When more than one space is provided, in lieu of providing a 14' space for each space, two spaces can be provided within a 23' area with a 5' loading
zone between each 9'0" wide space.
c) Each space is to be a minimum of 18' in depth. SEE 5/4% I
8. At least one in every 8 accessible parking spaces shall be served by an access
aisle 296" in width and desi as VAN ACCESSIBLE, er Section 1129B.4.2.
9. The words "NO ARKING"
unloading access aisle (in white letters no less than 12" high and located so that it
is visible to traffic enforcement officials). Section 1129B.4.2.
access aisle. Section 1 129B.4.3.
bc TRAVE L l-0 EdrrCY 6.
1 for each 25 spaces up to 100 total spaces.
PARCI~)~, CALCS. AOO EP FOR bzs?srtdf 5 frE codpirio+d E%- f 7.
ALL aulCss/ LE P~RJC t~ AN 4tt SS-/~LC -SEG .P~CKI 2- on t cc e ground within each loading an umAc.I) 2
10. Ramps shall not encroach into any accessible parking
U=-FO OW EX./ mq ,~x/jr/~4 RAI\.~~ DO &or EEJLROAIC/J
e
11. Show or note that the lower 10" of all doors comply with Section 11 338.2.6, as
follows: See detail 20/A5.1. The bottom edge finish of the door must be a min.
a) To be smooth and uninterrupted, to allow the door to be opened by a wheelchair footrest, without creating a trap or hazardous condition.
b) Narrow frame doors may use a 10" high smooth panel on the push side of
the door.
of1oyY- SEg DETAIL zo/As,/ - Ell//$&&
12. Note that the doorways leading to sanitary facilities shall be identified, per Section
1 1 158.5, as follows:
a)
b)
c)
d)
An equilateral triangle %" thick with edges 12" long and a vortex pointing
upward at men's rest rooms.
A circle %" thick, 12" in diameter at women's rest rooms.
A 12" diameter circle with a triangle superimposed on the circle and within
the 12" diameter at unisex rest rooms.
The required symbols shall be centered on the door at a height of 60".
3/A5--
Carlsbad 04-1540
5/20/04
e) Braille signage shall also be located on the wall adjacent to the latch
outside of the doorways leading to the sanitary facilities, per Section
1 1 176.5.7.
COUNTERS
13. show or note on the plans that the service counters shall be 28” to 34” from the
floor. The disabled accessible srvice area shall be located at a section of counter
that is at least 36” long and no more than 28” to 34 high. Section 1122B.4.
To speed up the review process, note on this list (or a copy) where each
correction item has been addressed, Le., plan sheet, note or detail number,
calculation page, etc.
AOOEO - S+tG&r A\
The jurisdiction has contracted with Esgil Corporation located at 9320
Chesapeake Drive, Suite 208, San Diego, California 921 23; telephone number of
858/560-1468, to perform the plan review for your project. If you have any
questions regarding these plan review items, please contact Chuck Mendenhall
at Esgil Corporation. Thank you.
16 GAUGE 1-1/2" COLD
ROLLED 4TE€L @ 48"
0.C.
1905 CALLE €3 G 4 - SUITE 152
ATTACH TO EX.
BEAM MB $8
TEK 5CREH5,
TYP.
HAT CHANNELS @
16'I 9°C.
2 #& T€K
5CSREW5 AT HAT
CMANNEL AN13
VAULTED STEEL
/
8 GAUeE HIRE @ 4'-0' ON
CENTER, ATTACH W/ EYE HOOK5
-
50FFIT @r BARREL ARCH
/
16 6A. ENT TRACK A/2 IOd
DES16NER PRPtHINi55
EXISTIN6 2xb DEM15lNC
471133 WALL
LOM 5OFF. @ MET. 5TUD %ale: N.T.3. @
1905 CALLE B G 4 - SUITE! 152
4 -I-
PARTITION HALL
SOL-T Irluss&1 m1 bt AS5661Arn m
CARLSBAD, CA 92009 85&mm21119 PH
wm !YA”lm !mmm TENANT IMPROVEMENT om* -
46%cAss~ wmamm 1905 CALLE BARCELONA - BUILDING 4 - SUMX 152
OMIT INSULATION
FULL HEIGHT PARTITION
SaE Cm AUmmT&ASS6CUtES,K
w%Tm
A#&mEmE pwmme HTEWCYIS TENANT IMPROVEMENT B*B - 1905 CALLE BARCELONA - BUILDING 4 - SUITE 152 CARLSBAD, CA 92009
COW. TOP 7
0-
HARD-CE 1 L I Ne FRAMI NG
4 - SUITE 152
--
3-3/&" 29 CA. 4TWD
4 - SUITE 152
5-W" 20 6A. BTUD-
0 IS" Q.G., w/ 5W' 67'P. 131pD. TUP AND
mTTQM
5-9/15'' 20 @A. STUD-
@ 16" U.G., W 518" 6YP. bRP. TOP AND
BOTTOM
7 3-5/&" 20 6A. WX
WAM STUD
u) FEILINe FRAMING PLAN
5TOCK ROOM
/
ir
.I E5 AKEA
CE 1 L I NG FKAMI Ne PLAN 5~~lrr~: N.T.5.
ci d
STOREFRONT 5Y5. NOTE5 %ale: N.T.5. (lo)
1905 CALLE BARCELONA - BUILDING 4 - SUITE 152 CARLSBAD. CA 92009
I
NORTH
SOLE COMYURT TENANT IMPROVEMENT 1905 CALLE BARCELONA - BUILDING 4 - SUITE 152 CARLSBAD, CA 92009
5HEET 2
SCALE: 1/2"= I '-0"
RussELLsrouT&ASSOCUTES,K ARc"RE PWIUIG MEmts
m.8 -
4656wsTRElET ynDE8o.cAiao 85am.Bl2 PH
I\ I
SOLE COMPORT TENANT IMPROVEMENT 1905 CALLE BARCELONA - BUILDING 4 - SUITE 152 CARLSBAD, CA 92009
,
RUSSEUSTOUTa~Es,n MlEcNa pw11)(6 llllIlwRs
m.8 -
4#cAssm SAMMEcAcA.921
Mbs1.2612
DET. 'XE WT. 3 31M.
NORTH 1
\
\
\
\
\
PI
I
I
SHEET
SALE: 1/2"=I'-C
P 9 4
SOLE COMFORT TENANT IMPROVEMENT 1905 CALLE BARCELONA - BUILDING 4 - SUITE 152 CARLSBAD, CA 92009
M I.-. .-
Russel SrOOfbr ASSOCUTES, INC.
WiPam
ARa#lEmRE pumr(6 tlTERKlRs m.. -
858.w.2812 PH
4 I
or
FULL HE
-20 6A. TOP TPZACK UNPUNCHED
3-5/8" 20 6A. 4TUP
0 16" O.C.
5/8" 6RfEN 00ARD ON 4ALE5 51DE
OMIT INSJLATION
I/2" PIN5 69 32" O.C. /-------
20 6A. BOTTOM
TRACK
UNWGttED
A d d
0
d A -ENSTIN6 CONCRETE 4LA8
SHEET
%ALE: N.T.5.
GHT 5TUD HALL
BOTTOM TO JOIST '
5/8" 'TYPE "X" 6YP.
50FF T DETAIL 5H€ET 5
SCALE: N.T.5.
SOLE c$
ARQIrnM RNIWG I1mats - aaa TENANT IMPROVEMENT
4855CASSSTRoET YSI DEW CA, WlOD 1905 CALLE BARCELONA - BUILDING 4 - SUITE 152 CARLSBAD, CA 92009 858561.2n12 PH
pESlCPN ASSUMPTIONS:
CONCRETE STRENGTH AT NVENTY EKSWT DAYS:
MASONRY:
MORTAR: TYPES 1806PSI
GROUT: 2000 PSI
REiNFORClNG STEEL: A415 GRADE 40: #6 AND LESS
- - GRADE "N" CONCRETE BLOCK F I M =
I GRAbE 60: #8 AND L4RG STRUCTURAL STEEL: A-36
LUMBER: DOUGLAS F;IR-LARCH
JOtSfS $ . am BEAMSANP OSTS STUDS . - STUD OR BETTER'
SEISMIC FORCE: REPORTBY I------
WINDFORCE: ,7c1 MM H? F+ REPORTNO.:. "I SOIL PRESSURE: -
BWF L IVE LOAD
SLOPING INTERIOR 40 PSF FLAT
These calculstione are limited only to the items included herein, selected by tha cilent and do not Imply approval of any other portion of the structure by thjs office. These calculations are not valid if attered in any way, or not accompanied by a wet stamp and signature of the Engineer of Record.
FtOQ&k&@ L OAD
BALCoNY 60 PSF (U.O.N.) EXITWALKWAY , 100 PSF
P
w 1'
Horowitz Taylor Kushkaki
Structural Engineers
3914 Murphy Canyon Road, Suite A100
San Diego, CA 921 23
.
(858) 560-4383
Title : Dsgnr: Description :
Scope :
Job #
Date: 258PM, 6MAY04
Description
1 General Information C
Center Span 27.00 ft Moment of Inertia 1,000.000 in4
Left Cantilever ft Elastic Modulus 460 ksi
Right Cantilever ft Beam End Fixity Pin-Pin
On Center Span ... On Left Cantilever ... On Right Cantilever. ..
#1 0.045 wn #1 wft #1 wn
Magnitude 0.085 k
Location 23.000 ft
k
ft
k
ft
k
ft
k n
Center Location \ 0.000 ft Left Cant 0.000 ft Rlght Cant 0.000 ft
Moment 0.00 k-ft 0.00 k-ft 0.00 k-ft
Shear 0.62 k 0.00 k 0.00 k
Deflection 0.00000 in 0.00000 in 0.00000 in
Moments ...
Max + Q Center
Max - @ Center
@ Left Cant
@ Right Cant
Maximum =
I
Shears ... Reactions ...
4.27 k-ft at 13.80ft 63 Left 0.62 k Q Left 0.62 k
0.00 k-ft at o.oon @ Right 0.68 k @ Right 0.68 k
0.00 k-ft
0.00 k-ft Deflections ...
Maximum 0.68 k
Q Center -1.226 in at 13.58ft
@ Left Cant. 0.000 in at 0.OOft
@ Rightcant 0.000 in at 0.00 ft
4.27 k-ft
, --
may u'/ u4 Ur?:49a Tom Harinton 909 506-0123 P. 1
r 1 TITLE 24 REPORT
Title 24 Report for:
SOLE COMFORT
CARLSBAD, GA 92009
1905 CALLE BARCELONA - BLDG. 4 - SUITE A 52
Project Designer:
RUSSELL STOUT & ASSQC
4635 CASS ST. SAN DIEGQ, CA 92109
Report Prepared By:
TOM HARINTQN WARINTON MECHANICAL DEStCN INC.
45750 Jeronimo Street Temecula, CA 92592
(909) 506-01 22
Job Number:
Date:
5/6/20 04
' The EnergyPrc computer program has been UsEd to perform the calcutations summarized in this compliance report. This program has approval and is authwked by the California Energy Commission for use with both the Residential and Nonresidential 2M)l BuiMing Energy Efficiency Standards.
This program developed by EnergySoR. LLC (415) 883-5900,
-I_____ -- -~__ ~ __ - UserNumber d945 __ --. - EnergyPro 3.1 By Energ$?iof! I Job Number:-_
Y 1