HomeMy WebLinkAbout1923 CALLE BARCELONA; 139; CB040539; Permitc.6 33 930 City of Carlsbad
06-1 5-2004
Job Address:
Permit Type:
Parcel No:
Valuation:
Occupancy Group:
Project Title:
Applicant:
1635 Faraday Av Carlsbad, CA 92008
Building Inspection Request Line (760) 602-2725
Commercial/lndustriaI Permit Permit No: CB040539
MCMAHON MARY BETH
2458 DUPONT DRIVE
IRVINE 92612
949 833-1930
1923 CALLE BARCELONA CBAD St: 139
TI Sub Type: COMM
Lot #: 0 Status: ISSUED
$136,500.00 Construction Type: NEW Applied: 02/18/2004
JOS. A. BANK. Plan Approved: 06/15/2004
4,550 SF SHELL TO RETAIL Issued: 0611 512004
Reference #: Entered By: MDP
Inspect Area :
Plan Check#:
Owner:
Building Permit
Add'l Building Permit Fee
Plan Check
Add'l Plan Check Fee
Plan Check Discount
Strong Motion Fee
Park Fee
LFM Fee
Bridge Fee
BTD #2 Fee
BTD #3 Fee
Renewal Fee
Add'l Renewal Fee
Other Building Fee
Pot. Water Con. Fee
Meter Size
Add'l Pot. Water Con. Fee
Recl. Water Con. Fee
$660.52
$0.00
$429.34
$0'00
$0.00
$28.67
$0.00 $0.00 $0.00 $0.00
$0.00
$0.00
$0.00 $0.00
$0.00
$0.00 $0.00
Meter Size
Add'l Recl. Water Con. Fee
Meter Fee
SDCWA Fee
CFD Payoff Fee
PFF
PFF (CFD Fund)
$0.00
$0.00
$0.00
$0.00
$2,484.30
$0.00
4387 06/l!5/0.6 02 License Tax
License Tax (CFD Fund)
Traffic ImPact Fee 3484 47
Traffic Impact (CFD Fund)
PLUMBING TOTAL
ELECTRICAL TOTAL
MECHANICAL TOTAL
Master Drainage Fee
Sewer Fee
Redev Parking Fee
Additional Fees
TOTAL PERMIT FEES
$0.00
$1 04.00
$1 10.00
$102.00
$0.00
$0.00
$0.00
$0.00
$3,918.83
Total Fees: $3,918.83 Total Payments To Date: $429.34 Balance Due: $3,489.49
Inspector: Clearance:
NOTICE: Please take NOTkE that appro21 of your project includes the "Imposition" of fees, dedications, reservations, or other exactions hereafter collectively
referred to as 'fees/exactions." You have 90 days from the date this permit was issued to protest imposition of these feeslexactions. If you protest them, you must
follow the protest procedures set forth in Government Code Section 66020(a), and file the protest and any other required information with the City Manager for
processing in accordance with Carlsbad Municipal Code Section 3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack,
review, set aside, void, or annul their imposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified feeslexactions DOES NOT APPLY to water and sewer connection fees and capacity
changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this project. NOR DOES IT APPLY to any
feesiexactions of which vou have Dreviouslv been aiven a NOTICE sirnilarto this. or as to which the statute o f limitations has Dreviouslv otherwise exDired.
FOR OFFICE USE ONLY
PERMIT APPLlCATlO N
CITY OF CARLSBAD BUILDING DEPARTMENT
1635 Faraday Ave., Carlsbad, CA 92008
SECTION NEED NOT BE COMPLETED IF THE PLRMIT IS FOR ONE HUNDRED DOLLARS 1$1001 OR LESS)
CERTIFICATE OF EXEMPTION: I certify that in the performance of the work for which this permit is issued, I shall not employ any person in any manner so as
s up to one hundred
subject to the Workers' Compensation Laws of California.
the Contractor's License Law for the following reason:
Code: The Contractor's License Law does not apply to an owner of property who builds or improves thereon, and who does
I, as owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not intended or offered for sale
such work himself or through his own employees, provided that such improvements are not intended or offered for sale. If, however, the building or improvement is
I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions Code: The
ontractor's License Law does not apply to an owner of property who builds or improves thereon, and contracts for such projects with contractor(s) licensed
within one year of completion, the owner-builder will have the burden of proving that he did not build or improve for the purpose of sale).
pursuant to the Contractor's License Law).
0 I am exempt under Section Business and Professions Code for this reason:
plan to provide the major labor and materials for construction of the proposed property improvement. WYES ON0
signed an application for a building permit for the proposed work.
with the following person (firm) to provide the proposed construction (include name I address I phone number I contractors license number): 3.
4.
number / co tractors license n bed: . - I plan to provide portions of the work, but I have hired the following person to coordinate, supervise and provide the major work (include name I address / phone
Legal Description Lot No. Subdivision NamdNumber Unit No. Phase No. Total # of units
Proposed Use
T€hrb&T IMpRO 9iSW / $! Assessor's Parcel # Existing Use
Description of Work SQ. FT.
VWCfl 9. /-1
#of>tories # of Bedrooms # of BattGooms
t
Name Address city State/Zip Telephone # Fax #
(Sec. 7031.5 Business and Professions Code: Any City or County which requires a permit to construct, alter, improve, demolish or repair any structure, prior to its
issuance, also requires the applicant for such permit to file a signed statement that he is licensed pursuant to the provisions of the Contractor's License Law
[Chapter 9, Commending with Section 7000 of Division 3 of the Business and Professions Codel or that he is exempt therefrom, and the basis for the alleged
exemption. Any violation of Section 7031.5 by any applicant for a permit subjects the applicant to a civil penalty of not more than five hundred dollars [$5001).
Name Address City State/Zip Telephone # b
State License # License Class City Business License #
Desiqner Name Statelzip Tehone
Workers' Compensation Declaration: I hereby affirm under penalty of perjury one of the following declarations: pa' I have and will maintain a certificate of consent to self-insure for workers' compensation as provided by Section 3700 of the Labor Code, for the performance
of the work for which this permit is issued.
I have and will maintain workers' compensation, as required by Section 3700 of the Labor Code, for the performance of the work for which this permit is
issued. My worker's complensation insurance carrier and policy number are: I <- Insurance Company 'pews a th~~t-r-~w Policy No. 9 (00 4q Expiration Date /v//bfL
Is the applicant or future building occupant required to submit a business plan, acutely hazardous materials registration form or risk management and prevention
program under Sections 25505, 25533 or 25534 of the Presley-Tanner Hazardous Substance Account Act?
Is the applicant or future building occupant required to obtain a permit from the air pollution control district or air quality management district? 0 YES e( NO
Is the facility to be constructed within 1,000 feet of the outer boundary of a school site?
0 YES WNO
0 YES dNO
IF ANY OF THE ANSWERS ARE YES, A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR IS MEETING THE
REQUIREMENTS OF THE OFFICE OF EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT.
LENDERS NAME LENDER'S ADDRESS
CERTWlCAT€O
I certify that I have read the application and state that the above information is correct and that the information on the plans is accurate. I agree to comply with all
City ordinances and State laws relating to building construction. I hereby authorize representatives of the Citb. of Carlsbad to enter upon the above mentioned
property for inspection purposes. I ALSO AGREE TO SAVE, INDEMNIFY AND KEEP HARMLESS THE CITY OF CARLSBAD AGAINST ALL LIABILITIES,
JUDGMENTS, COSTS AND EXPENSES WHICH MAY IN ANY WAY ACCRUE AGAINST SAID CITY IN CONSEQUENCE OF THE GRANTING OF THIS PERMIT.
OSHA: An OSHA permit is required for excavations over 5'0" deep and demolition or construction of structures over 3 stories in height.
EXPIRATION: Every permit issued by the building Official under the provisions of this Code shall expire by limitation and become null and void if the building or work
authorized by such permit is not commenced within 180 days from the date of such permit or if the building or work authorized by such permit is suspended or abandoned
at any time after the work is commenced for
APPLICANT'S SIGNATURE DATE \m& (Section 106.4.4 Uniform Building Code)
WHITE: File YELLOW: Applicant PINK: Finance
Inspection List
Permit#: CB040539 Type: TI
Date Inspection Item
08/02/2004 89
08/02/2004 89
07/30/2004 89
07/29/2004 84
07/29/2004 84
07/28/2004 84
07/28/2004 84
07/27/2004 84
07/27/2004 84
07/27/2004 84
07/26/2004 84
07/26/2004 84
0711 612004 17
0711 312004 17
07/09/2004 14
07/09/2004 24
07/09/2004 34
07/09/2004 44
07/07/2004 84
07/06/2004 14
07/06/2004 14
07/06/2004 34
07/06/2004 34
07/06/2004 44
07/06/2004 44
06/28/2004 21
06/28/2004 31
06/24/2004 44
06/23/2004 34
06/23/2004 44
Final Combo
Final Combo
Final Combo
Rough Combo
Rough Combo
Rough Combo
Rough Combo
Rough Combo
Rough Combo
Rough Combo
Rough Combo
Rough Combo
Interior LathIDrywall
Interior LathIDrywall
FramelSteellBoltingNeldin
Roughflopout
Rough Electric
Roug h/Ducts/Dampers
Rough Combo
FramelSteellBoltingNVeldin
FramelSteellBoltingNeldin
Rough Electric
Rough Electric
Roug h/Ducts/Dampers
RoughIDuctslDampers
UndergroundIUnder Floor
UndergroundIConduit-W irin
Roug h/Ducts/Dampers
Rough Electric
Roug h/Ducts/Dampers
COMM JOS. A. BANK.
4,550 SF SHELL TO RETAIL
Inspector Act Comments
MP
PS
PS
PS
PD
PS
PS
PS
RB
RB
RB
RB
PS
PS
PS
PS
PS
PS
PS
PS
PS
PS
PS
PS
RI
AP
co
co
RI
RI
co
RI
RI
co
RI
NR
AP
PA
AP
AP
PA
CA
co
NR
NR
NR
NR
NR
NR
AP
AP
CA
PA
co
MAY BE DONE ON FRIDAY
OK TO TILE, LEAVE SOME TILE OUT
CEILING REINSPECTION
T-BAR CEILING
OPEN CEILING INSPECTION
NEED FIREINOT COMPLETE BUT OK TO
STOCK WHEN FIRE APPROVES AND
OK TO INSTALL BORDER AND
SPRINKLER DROP TILES
PM INSP PLEASE
ABOVE l2FEET IN SALES AREA
TO 12FT ABOVE FLR SALES AREA
WALL
NEED TO GROUND BOXES-OK TO
DRYWALL
BY JEFF-MECH CONTRACTOR
DEMISING WALLS
NOT PER PLANS
Monday, August 02,2004 Page 1 of 1
City of Carlsbad Bldg Inspection Request
For: 08/02/2004
Permit# CB040539
Title: JOS. A. BANK.
Description: 4,550 SF SHELL TO RETAIL
Type: TI Sub Type: COMM
Job Address: 1923 CALLE BARCELONA
Suite: 139 Lot 0
Location:
APPLICANT MCMAHON MARY BETH
Owner:
Remarks: MAY BE DONE ON FRIDAY
Inspector Assignment: PS
Phone: 7144126528 P
Inspector:
Total Time: Requested By: RANDY
CD Description omment
Entered By: CHRISTINE
19 Final Structural
29 Final Plumbing
39 Final Electrical
49 Final Mechanical I
Associated PCRs/CVs
InsDection History
Date Description
Q7/3Q/2QQ4 89
0712912QQ4 84
Q7l28l2QQ4 84
Q7127120Q4 84
0712612QQ4 84
0711 612004 17
0711 312004 17
07IQ9/2004 14
Q7lQ9/2QQ4 24
07/09/2004 34
07/09/2Q04 44
Q7/Q7l2QQ4 84
07/06/2004 14
07/06/2004 14
Final Combo
Rough Combo
Rough Combo
Rough Combo
Rough Combo
Interior LathIDrywall
Interior LathfDrywall
Frame/Steel/BoltingWelding
Roughhopout
Rough Electric
RoughIDuctslDarnpers
Rough Combo
FramelSteeVBoltingMlelding
Frame/Steel/BoltingWelding
Act lnsp
co PS co PS
co PS
CO PD
NR PS
AP PS
PA PS
AP RB
AP RB
PA RB
CA RB co PS
NR PS
NR PS
Comments
OK TO TILE, LEAVE SOME TILE OUT
NEED FIRWNOT COMPLETE BUT OK TO STOCK WHEN FIRE
APPROVES AND OK TO INSTALL BORDER AND SPRINKLER DROP
TILES
ABOVE 12FEET IN SALES AREA
TO 12FT ABOVE FLR SALES AREA
WALL
NEED TO GROUND BOXES-OK TO DRYWALL
UNSCHEDULED BUILDING INSPECTION
INSPECTOR 7s
PLAN CHECK,#
DESCRIPTION
CODE DESCRIPTION ACT COMMENTS
... .- - c A$
"-bL?
(760) 602-2700
1635 FARADAY AVENUE
I PERMITNO- F
1 FOR INSPECTION CALL (760) 602-2725. RE-INSPECTION FEE DUE? YES
;z, .. NOTICE ne01 602-2700
, . ** I I_'
CITY OF CARLSBAD 1 BUILDING DEPARTMENT 163s FAFU~DAY AVENUE
FOR INSPECTION CALL (760) 602-2725. RE-INSPECTION FEE DUE? YES I
ORMATION, CONTACT
PHONE
CODE ENFORCEMENT OFFICER @ -1-
City of Carlsbad Bldg
For: 07/09/2004
Permit# CB040539
Title: JOS. A. BANK.
Description: 4,550 SF SHELL TO RETAIL
Type: TI Sub Type: COMM
Job Address: 1923 CALLE BARCELONA
Suite: 139 Lot 0
Location:
APPLICANT MCMAHON MARY BETH
Owner:
Remarks: E
c-
Total Time:
Inspection Request
Inspector Assignment: PS
KP Inspector:
Requested By:
Entered By: CHRISTINE *wornmu CD Description
i- 14 Frame/SteeUBoltingMIelding
24 Roughnopout
34 Rough Electric
44 Rough/Ducts/Dampers
Associated PCRs/CVs
Inspection History
Date Description Act lnsp
07/07/2004 84
07/06/2004 14
07/06/2004 34
07/06/2004 44
06/28/2004 21
06/28/2004 31
06/24/2004 44
06/23/2004 34
06/23/2004 44
Rough Combo
Frarne/SteellBoltingNVelding
Rough Electric
RougNDuctslDampers
UndergroundIUnder Floor
Undergroundlconduit-Wiring
RoughIDuctslDarnpers
Rough Electric
RoughtDuctsIDarnpers
co PS
NR PS
NR PS
NR PS
AP PS
AP PS
CA PS
PA PS
co PS
Comments
BY JEFF-MECH CONTRACTOR
DEMISING WALLS
NOT PER PLANS
BUILDING DEPARTMENT OTICE (760) 602-2700
1635 FARADAi AVENUE
DATE 7-?-0* TIME
PERMIT NO.
ec I
FOR INSPECTION CALL (760) 602-2725. RE-INSPECTION FEE DUE? L 1 YES
FOR FURTHER INFORMATI
PHONE
I @ BUILDING INSPECT~R CODE ENFORCEMENT OFFICER
City of Carlsbad Bldg Inspection Request
For: 07/07/2004
Permit# CB040539
Title: JOS. A. BANK.
Description: 4,550 SF SHELL TO RETAIL
Type: TI Sub Type: COMM
Job Address: 1923 CALLE BARCELONA
Suite: 139 Lot 0
Location:
APPLICANT MCMAHON MARY BETH
Owner:
Remarks:
Total Time:
Inspector Assignment: PS
Phone: 7606259093
Inspector. %
Requested By: RANDY
Entered By: CHRISTINE
CD Description Act Comment
14 Frame/SteeUBolting/Welding e& f 24 Roughflopout
34 Rough Electric
44 Rough/Ducts/Dampers
Associated PCRsKVs
Date
07/06/2004
07/06/2004
07/06/2004
06/28/2004
06/28/2004
06/24/2004
06/23/2004
06/23/2004
Inspection Historv
Description
14 FramelSteellBoltingMelding
34 Rough Electric
44 RoughtDuctslDampers
21 UndergroundIUnder Floor
31 Underground/Conduit-Wiring
44 RoughlDuctslDampers
34 Rough Electric
44 RougWDuctsIDarnpers
Act lnsp Comments
NR PS
NR PS
NR PS
AP PS
AP PS
CA PS BY JEFF-MECH CONTRACTOR
PA PS DEMISING WALLS
CO PS NOTPERPLANS
L
BUILDING DEPARTMENT
OTICE (760) 602-2700
1635 FARADAY AVENUE
TIME
LOCATION /G 7-3
PERMITNO. 4/95 3 c.
~~ ~
FOR INSPECTION CALL (760) 602-2725. RE-INSPECTION FEE DUE? YES
PHONE
@ CODE ENFORCEMENT OFFICER
23441 Canyon Lake Dr. N. - Canyon Lake, CA. 92587 - PA (909) 24.4-9730 - Fax (909) 246-1266
To Whom It May Concern, This letter is provided to serve as evidence that Diversified Electric has appropriately
Torqued all electrical connections associated with the electrical construction of the Jos A.
Bank location at 1923 Calle Barcelona, in the City of Carlsbad CA. All electrical
connections were Torqued as Follows:
All #3/0 Copper Connections: 300 inch-pounds
All #6 Copper Connections: 45 inch-pounds
All #8 Copper Connections: 40 inch-pounds
All #14-10 Copper Connections: 25 inch-pounds
Please feel flee to contact our office should you have any questions or concerns,
Sincerely,
Gordon Hyland
.
EsGil 7 Corporation
In Partnership with Government for SuiGfing Safety
DATE: 5/20/04 APPLICANT
JURISDICTION: City of Carlsbad
PLAN CHECK NO.: 04-0539 SET I11
PROJECT ADDRESS: 1923 Calle Barcelona Suite 141
PROJECT NAME: JoS. A. Bank - TI
p LAN REVIEWER
R FILE
w
0
0
0
0
w
0
The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction’s building codes.
The plans transmitted herewith will substantially comply with the jurisdiction’s building codes
when minor deficiencies identified below are resolved and checked by building department staff.
The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
The applicant‘s copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
The applicant’s copy of the check list has been sent to:
Esgil Corporation staff did not advise the applicant that the plan check has been completed.
Esgil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Telephone #:
Date contacted: (by: ) Fax #:
REMARKS:
Mail Telephone Fax In Person
By: Doug Moody Enclosures:
Esgil Corporation
GA [7 MB 0 EJ 0 PC 5/13/04 trnsmtl .dot
. 9320 Chesapeake Drive, Suite 208 4 San Diego, California 92123 4 (858) 560-1468 4 Fax (858) 560-1576
EsGil Corporation
In Partnership with <jovemment for Buitiiing Safety
DATE: 3/ 19/04
JURISDICTION: City of Carlsbad
PLAN CHECK NO.: 04-0539 SET: I1
PROJECT ADDRESS: 1923 Calle Barcelona Suite 141
PROJECT NAME: JoS. A. Bank - TI
0 The plans transmitted herewith have been corrected where n
with the jurisdiction’s building codes.
ce
a PLAN REVIEWER a FILE
ary and substantially comply
u The plans transmitted herewith will substantially comply with the jurisdiction’s building codes
when minor deficiencies identified below are resolved and checked by building department staff,
0 The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
The applicant’s copy of the check list is enclosed for the jurisdiction to forward to the applicant
w The applicant’s copy of the check list has been sent to:
Carlile Coatsworth Architects/ Mary Beth McMahon
2458 Dupont Drive, Irvine, CA 92612
contact person.
0 Esgil Corporation staff did not advise the applicant that the plan check has been completed. w Esgil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Mary Beth McMahon
Date contacted: 3 If 9 kscP Xby: &c)
Telephone #: 949-833-1 930
Fax #: 949-833-1 140
Mail eephone Fax- InPerson
REMARKS:
By: Doug Moody Enclosures:
Esgil Corporation 0 GA 0 MB 0 EJ PC 3/16/04 trnsrntl.dot
9320 Chesapeake Drive, Suite 208 San Diego, California 92123 (858) 560-1468 + Fax (858) 560-1576
City of Carlsbad 04-0539 31 19/04
RECHECK PLAN CORRECTION LIST
JURISDICTION: City of Carlsbad PLAN CHECK NO.: 04-0539 1
PROJECT ADDRESS: 1923 Calle Barcelona Suite 141 SET: I1
DATE PLAN RECEIVED BY
ESGIL CORPORATION: 3/16/04
DATE RECHECK COMPLETED:
3/ 19/04
REVIEWED BY: Doug Moody
FOREWORD (PLEASE READ):
This plan review is limited to the technical requirements contained in the Uniform Building Code,
Uniform Plumbing Code, Uniform Mechanical Code, National Electrical Code and state' laws
regulating energy conservation, noise attenuation and disabled access. This plan review is
based on regulations enforced by the Building Department. You may have other corrections
based on laws and ordinances enforced by the Planning Department, Engineering Department
or other departments.
The following items listed need clarification, modification or change. All items must be satisfied
before the plans will be in conformance with the cited codes and regulations. Per Sec. 106.4.3,
1997 Uniform Building Code, the approval of the plans does not permit the violation of any
state, county or city law.
A. Please make all corrections on the original tracings and submit two new sets of prints to:
ESGIL CORPORATION.
B. To facilitate rechecking, please identify, next to each item, the sheet of the plans upon
which each correction on this sheet has been made and return this sheet with the
revised plans.
C. The following items have not been resolved from the previous plan reviews. The original
correction number has been given for your reference. In case you did not keep a copy of
the prior correction list, we have enclosed those pages containing the outstanding
corrections. Please contact me if you have any questions regarding these items.
D. Please indicate here if any changes have been made to the plans that are not a result of
corrections from this list. If there are other changes, please briefly describe them and where
they are located on the plans. Have changes been made not resulting from this list?
OYes ONo
.
City of Carlsbad 04-0539
3/ 19/04
Please make all corrections on the original tracings, as requested in the correction
list. Submit three sets of plans for commerciaVindustria1 projects (two sets of plans
for residential projects). For expeditious processing, corrected sets can be
submitted in one of two ways:
I. Deliver all corrected sets of plans and calculationslreports directly to the City of
Carlsbad Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760)
602-2700. The City will route the plans to EsGil Corporation and the Carlsbad
Planning, Engineering and Fire Departments.
2. Bring one corrected set of plans and calculations/reports to EsGil Corporation,
9320 Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-1468.
Deliver all remaining sets of plans and calculations/reports directly to the City of
Carlsbad Building Department for routing to their Planning, Engineering and Fire
Departments.
NOTE: Plans that are submitted directly to EsGil Corporation only will not be
reviewed by the City Planning, Engineering and Fire Departments until review by
EsGil Corporation is complete.
These corrections are in response to items not fully addressed or as the
result of information provided, the text in bold print indicates the
unresolved issue.
1. Please provide plans and calculations signed by the California State licensed
engineer or architect for the alteration to the exterior of the building as shown on
sheet A201, the structural support of the 1414# roof top air handler unit and the
IO’ high stockroom shelving. Include all calculations and finding on the plans.
Please include the California license number, seal, date of license expiration and
date plans are signed. Business and Professions Code. The only information
provided was for the stockroom shelving and this information was not
included in the plans. Please incorporate the details from the structural
calculations for the stockroom shelving into the plans and have the
engineer sign and stamp the plans. Please provide evidence the structural
alteration to the storefront are being performed under a separate permit
such as permit # of plan check #. Please have the engineer address the
structural support of the roof top HVAC units.
2. On the mechanical plans clearly show the limits of ceiling space used as duct or
plenum. Please provide the MECH 4 form for this project.
a) Clearly show that all material exposed within the plenum complies with
UMC Section 604.2. “Materials shall have a mold-, humidity-, and
erosion-resistant face that meets the requirements of UL 181 .”
Please revise the plans to show 21 fitting room or dressing room for the customers shall
be provided as follows: Please revise the plans to show the bench 48” in
length.
Entry doors shall provide:
48” clear on the push side of the door.
. f
City of Carlsbad 04-0539
3/19/04
The jurisdiction has contracted with Esgil Corporation located at 9320
Chesapeake Drive, Suite 208, San Diego, California 92123; telephone number of
858/560-1468, to perform the plan review for your project. If you have any
questions regarding these plan review items, please contact Doug Moody at
Esgil Corporation. Thank you.
EsGil Corporation
In Partnership with Government for QuiC&ng Sufety
DATE: 3/2/04
JURISDICTION: City of Carlsbad n PLAN REVIEWER
0 FILE PLAN CHECK NO.: 04-0539 SET: I
PROJECT ADDRESS: 1923 Calle Barcelona Suite 141
PROJECT NAME: JoS. A. Bank - TI
The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction’s building codes.
0 The plans transmitted herewith will substantially comply with the jurisdiction’s building codes
when minor deficiencies identified below are resolved and checked by building department staff.
The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
0 The applicant’s copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
The applicant’s copy of the check list has been sent to:
Carlile Coatsworth Architects/ Mary Beth McMahon
2458 Dupont Drive, Irvine, CA 92612
0 Esgil Corporation staff did not advise the applicant that the plan check has been completed.
Esgil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Mary Beth McMahon
Date contacted:3/Z/oy (by: kp)
Telephone #: 949-833-1 930
Fax #: 949-833-1 140
Mail LTelephone FaxJ In Person 0 REMARKS:
By: Doug Moody Enclosures:
Esgil Corporation
GA c] MB EJ PC 2/20104 tmsmtl.dot
9320 Chesapeake Drive, Suite 208 San Diego, California 92123 + (858) 560-1468 Fax (858) 560-1576
-~
City of Carlsbad 04-0539
3/2/04
PLAN REVIEW CORRECTION LIST
TENANT IMPROVEMENTS
PLAN CHECK NO.: 04-0539
OCCUPANCY: M USE: Retail
TYPE OF CONSTRUCTION: VN ACTUAL AREA: 4550sf
ALLOWABLE FLOOR AREA: STORIES: 1
JURISDICTION: City of Carlsbad
HE I G HT:
SPRINKLERS?: YES
REMARKS:
DATE PLANS RECEIVED BY
JURISDICTION: 2/18/04
OCCUPANT LOAD: 131
DATE PLANS RECEIVED BY
ESGIL CORPORATION: 2/20/04
DATE INITIAL PLAN REVIEW
COMPLETED: 3/2/04
FOREWORD (PLEASE READ):
PLAN REVIEWER: Doug Moody
This plan review is limited to the technical requirements contained in the Uniform Building Code,
Uniform Plumbing Code, Uniform Mechanical Code, National Electrical Code and state laws
regulating energy conservation, noise attenuation and access for the disabled. This plan review
is based on regulations enforced by the Building Department. You may have other corrections
based on laws and ordinances enforced by the Planning Department, Engineering Department,
Fire Department or other departments. Clearance from those departments may be required
prior to the issuance of a building permit.
Code sections cited are based on the 1997 UBC.
The following items listed need clarification, modification or change. All items must be satisfied
before the plans will be in conformance with the cited codes and regulations. Per Sec. 106.4.3,
1997 Uniform Building Code, the approval of the plans does not permit the violation of any
state, county or city law.
To speed up the recheck process, please note on this list (or a COPY) where each
correction item has been addressed, i.e., plan sheet number, specification section, etc.
Be sure to enclose the marked up list when YOU submit the revised plans.
TENANT IMPROVEMENTS WITHOUT SPECIFIC ENERGY DATA OR POLICY SUPPLEMENTS (1997UBC) tiforw.dot
City of Carlsbad 04-0539
3/2/04
Please make all corrections on the original tracings, as requested in the correction
list. Submit three sets of plans for commerciaVindustria1 projects (two sets of plans
for residential projects). For expeditious processing, corrected sets can be
submitted in one of two ways:
1. Deliver all corrected sets of plans and calculations/reports directly to the City of
Carlsbad Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760)
602-2700. The City will route the plans to EsGil Corporation and the Carlsbad
Planning, Engineering and Fire Departments.
2. Bring one corrected set of plans and calculationsheports to EsGil Corporation,
9320 Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-1468.
Deliver all remaining sets of plans and calculations/reports directly to the City of
Carlsbad Building Department for routing to their Planning, Engineering and Fire
Departments.
NOTE: Plans that are submitted directly to EsGil Corporation only will not be
reviewed by the City Planning, Engineering and Fire Departments until review by
EsGil Corporation is complete.
1. Please provide plans and calculations signed by the- California State licensed
engineer or architect for the alteration to the exterior of the building as shown on
sheet A201 , the structural support of the 1414# roof top air handler unit and the
IO’ high stockroom shelving. Include all calculations and finding on the plans.
Please include the California license number, seal, date of license expiration and
date plans are signed. Business and Professions Code.
2. Please note on the plans “AC Cable is not allowed in A, B, E, H, and I
occupancies. NM cable is restricted (without City approval) to one and two
family dwellings. Note on plans that an equipment ground conductor is to be
installed in all flexible conduits”.
3. Please imprint on the plans the City of Carlsbad Policies and Procedures for
Roof Mounted Equipment to the plans.
4. On the mechanical plans clearly show the limits of ceiling space used as duct or
plenum.
a) Clearly show that all material exposed within the plenum complies with
UMC Section 604.2. “Materials shall have a mold-, humidity-, and
erosion-resistant face that meets the requirements of UL 181 .’I
Combustibles within the plenum space must comply with UMC Section
601.3. Flame-spread index of not more than 25 and a smoke-developed
rating of not more than 50.
Environmental duct systems shall not extend into or through ducts or
plenums. UMC Section 504.1.
b)
c)
City of Carlsbad 04-0539
3/2/04
5. Show that water heater is adequately braced to resist seismic forces. Provide
two straps (one strap at top 1/3 of the tank and one strap at bottom 1/3 of the
tank). UPC, Section 510.5.
6. Please revise the plans to show 21 fitting room or dressing room for the customers
shall be provided as follows:
a)
i) Entry doors shall provide:
48” clear on the push side of the door.
7. Please dimension to plans to show the hallway to the disabled dressing room to
be a minimum of 44”.
To speed up the review process, note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet, note or detail number,
calculation page, etc.
Please indicate here if any changes have been made to the plans that are not a
result of corrections from this list. If there are other changes, please briefly
describe them and where they are located in the plans.
Have changes been made to the plans not resulting from this correction list?
Please indicate:
Yes 0 No 0
The jurisdiction has contracted with Esgil Corporation located at 9320
Chesapeake Drive, Suite 208, San Diego, California 92123; telephone number of
858/560-1468, to perform the plan review for your project. If you have any
questions regarding these plan review items, please contact Doug Moody at
Esgil Corporation. Thank you.
CITY OF CARLSBAD
POLICIES AND PROCEDURE
EFFECTIVE: 5/1/92
SUPERSEDES: 80-6(9/10/80)
80-6(5/01/s1)
I
SECTION: BU [LO lNG DEPARTMENT
'r'UM8ER: 80-6 SUBJECT: ROOF MOUNTEO EQUIPMENT
INTENT: A. Maintain roof integrity.
B.
C.
1.
2.
3.'
Prevent'hazardous condition to firemen who must fight fire on the roof.
Provide an installation that is aesthetically sensitive to the building and the
adjoining properties: .
. All equipment shall be concealed from view and the design+ shall mest the
approval of the Planning Department.
All equipment shall be speciiicglly designed and approved for exterior use 2nd
shall be approved by the City of Carlsbad Building Department.
All roof mounted equipmen: shell be on a platform which shall be sn integral
part of the roof--flashed and kvzierproofed. When a screen is'appioved, ii shall
have 2s few roof connections 2s possible and be structurally stiequate.
All electrical, plumbing, mechanical duct work and related piping shall be inside
the building'and not on the roof. All connections related to equipment shall be '
made in the same roof openin9 on the platform or have the prior epproval from
the building official. Sewer vents shall be brought to one main vent below the roof 2nd have one
POLICY:
4.
5. penetration where resirooms or other plumbing fixtures are back to back or in
the general proximity.
Air exhaust fans and other equipment shall be within the building and use the
same roof opening where restrooms and other equipment are back to bzck or in - general proximity.
'6. Existing buildings and equipment, remodel or replacement, shall meet the above
.. _. regulations or shall have the prior.approva1 from the building official,
. 7. ' . .Where new equipment is installed, unused'or abandoned equipment, including ..
. all roof mounted piping, elektrical, mechanical, duct, an.d other. related
appurtenances shall be removed from roof and unused openings p.roperly sealed
$0 maintain roof integrity. ..
..
.. *
they are on the roof or elsewhere. .
e
initiated By: Approved 8
__
' City of Carlsbad 04-0539
3/2/04
bALUATION AND PLAN CHECK FEE
JURISDICTION: City of Carlsbad PLAN CHECK NO.: 04-0539
PREPARED BY: Doug Moody
BUILDING ADDRESS: 1923 Calle Barcelona Suite 141
BUILDING OCCUPANCY: M TYPE OF CONSTRUCTION: VN
DATE: 3/2/04
1994 UBC Building Permit Fee V
1994 UBC Plan Check Fee '(I
Type of Review: El Complete Review
0 Repetitive Fee Repeats
:: ~
I $429.341
0 Structural Only
0 Other
Hourly -1 Hour *
Esgll Plan Review Fee 0 I $369.89 I
Comments:
Sheet1 of 1
macvalue.dcc
PLANNINC/ENGINEERINC APPROVALS
PERMIT NUMBER CB 04 4s3 7 DATE 3 -5-09
RESIDENTIAL
RESIDENTIAL ADDITION MINOR
(< $10,000.00)
PLAZA CAMINO REAL
CARLSBAD COMPANY STORES
VILLAGE FAIRE
COMPLETE OFFICE BUILDING
OTHER
PLANNER DATE
ENGINEE DATE *5’-&
DOCYMiSformYPlanning Engineering Approvals
PLANNING DEPARTMENT
BUILDING PLAN CHECK REVIEW CHECKLIST
Plan Check No. cb04 5m Address H6?? fL~kQw [T Planner Christer Westman Phone (760) 602-461 4
APN:
Type of Project & Use: Net Project Density: DUiAC
Zoning: General Plan: Facilities Management Zone:
CFD (inlout) # Date of participation: Remaining net dev acres:
Circle One
(For non-residential development: Type of land used created by
this permit: 1
Legend: Item Complete Item incomplete - Needs your action
Environmental Review Required: YES - NO TYPE
DATE OF COMPLETION:
Compliance with conditions of approval? If not, state conditions which require action.
Conditions of Approval:
Discretionary Action Required: YES NO TYPE
APPROVAL/RESO. NO. DATE
PROJECT NO.
OTHER RELATED CASES:
Compliance with conditions or approval? If not, state conditions which require action.
Conditions of Approval:
Coastal Zone Assessment/Compliance
Project site located in Coastal Zone? YES - NO-
CA Coastal Commission Authority? YES- NO
If California Coastal Commission Authority: Contact them at - 3111 Camino Del Rio North, Suite
200, San Diego CA 92108-1725; (619) 521-8036
Determine status (Coastal Permit Required or Exempt) :
Coastal Permit Determination Form already completed?
If NO, complete Coastal Permit Determination Form now.
Coastal Permit Determination Log #:
YES- NO
Follow-Up Actions:
1) Stamp Building Plans as "Exempt" or "Coastal Permit Required" (at minimum
Floor Plans).
2) Complete Coastal Permit Determination Log as needed.
H:\ADMIN\COUNTER\BldgPlnchkRevChklst
.~
lnclusionary Housing Fee required: YES NO- ~ ~- (Effective date of lnclusionary Housing Ordinance - May 21, 1993.)
NO Data Entry Completed? YES - (AIPIDs, Activity Maintenance, enter CB#, toolbar, Screens, Housing Fees, Construct Housing YIN. Enter Fee UPDATE')
Site Plan:
1. Provide a fully dimensional site plan drawn to scale. 0 Show: North arrow,
property lines, easements, existing and proposed structures, streets, existing
street improvements, right-of-way width, dimensional setbacks and existing
topographical fines.
0 2. Provide legal description of property and assessor's parcel number.
Zoning: 0 1. Setbacks:
Front: Required Shown
Interior Side: Required Shown
Street Side: Required Shown
Rear: Required Shown
0 0 2. Accessory structure setbacks:
Front: Required Shown
Interior Side: Required Shown
Street Side: Required Shown
Rear: Required Shown
Structure separation: Required Shown
0 0 0 3. Lot Coverage: Required Shown
(7 (7 0 4. Height: Required Shown
5. Parking: Spaces Required Shown
Guest Spaces Required Shown
OK TO ISSUE AND ENTERED APPROVAL INTO COMPUTE ATE 7-\4+64
H:\ADMIN\COUNTER\BldgPlnchkRevChklst
Carlsbad Fire Department 040539
1635 Faraday Ave.
Carlsbad, CA 92008 Fire Prevention
(760) 602-4660
Plan Review Requirements Category: Building Plan
Date of Report: 02/23/2004 Reviewed by:
Name: Carlile Coatsworth
Address: 2458 Dupont Drive
City, State: lrvine CA 92612
Plan Checker: Job#: 040539
Job Name: Jos. A. Bank Bldg #: CB040539
Job Address: 1923 Calle Barcelona Ste. or Bldg. No. 141
Approved The item you have submitted for review has been approved. The approval is
based on plans, information and / or specifications provided in your submittal;
therefore any changes to these items after this date, including field
modifications, must be reviewed by this office to insure continued conformance
with applicable codes and standards. Please review carefully all comments
attached as failure to comply with instructions in this report can result in
suspension of permit to construct or install improvements.
0 Approved
Subject to
The item you have submitted for review has been approved subject to the
attached conditions. The approval is based on plans, information and/or
specifications provided in your submittal. Please review carefully all comments
attached, as failure to comply with instructions in this report can result in
suspension of permit to construct or install improvements. Please resubmit to
this office the necessary plans and / or specifications required to indicate
compliance with applicable codes and standards.
0 Incomplete The item you have submitted for review is incomplete. At this time, this office
cannot adequately conduct a review to determine compliance with the
applicable codes and / or standards. Please review carefully all comments
attached. Please resubmit the necessary plans and / or specifications to this
office for review and approval.
Review 1 st 2nd 3rd Other Agency ID
FD Job# 040539 FD File #
CANFIELD CONSULTING
STRUCTURAL ENGINEERS
STRUCTURAL CALCULATIONS
FOR
JOS A BANK
Mechanical unit support
Job# 04-057
March 11,2004
f
CA)IFIELD CONSULTING project& p
location STRUCTURAL ENGINEERS
205 North Main Street
Santa Ana, CA 92701
Phone 714.647.9848
Fax 714.647.9645
sheet no by &?L
client job no.
project G4 m~
location m5c373 CANFIELD CONSULTING
STRUCTURAL ENGINEERS
205 North Main Street Phone 714.647.9848 ''lent r%f/- Santa Ana, CA 92701 Fax 71 4.647.9645
9, L'
sheet no by 3z
date s-//--& z
&'a"7 job no
t I CL, FhWo
w'
Title :
Dsgnr:
Description :
Job #
Date:
Scope :
Page 1 Rev: 510300 i- IC1 User: 1983-99 Kw.0503761. ENERCALC Ver 5.1.3.22.Jun-1999. win32 General Timber Beam
Description Jos A Bank
LGenerai information Calculations are designed to 1997 NDS and 1997 UBC Requirements
Section Name 6.75x24.0 Center Span 32.00ft . . . . .Lu 2.00 ft Beam Width 6.750 in Left Cantilever ft . . . . .Lu 0.00 ft Beam Depth 24.000 in Right Cantilever ft . . . . .Lu 0.00 ft
Member Type GluLam Douglas Fir, 24F - V8
Bm Wt. Added to Loads Fb Base Allow 2,400.0 psi Load Our. Factor 1.000 Fv Allow 165.0 psi Beam End Fixity Pin-Pin Fc Allow 560.0 psi Wood Density 35.000 pcf E 1,800.0 ksi
I Full Lenah Uniform Loads C
Center DL 288.00 ~ft LL 288.00 #/ft Left Cantilever DL Right Cantilever DL #/ft LL #/ft
#/ft LL #/R
Point Loads c Dead Load 1,414.0 Ibs Ibs Ibs Ibs Ibs Ibs Ibs Live Load Ibs Ibs Ibs Ibs Ibs IbS Ibs ... distance 16.000 ft 0.000 ft 0.000 ft 0.000 ft 0.000ft 0.000 ft 0.000ft
Beam Design OK
Span= 32.00ft, Beam Width = 6.750in x Depth = 24.in, Ends are Pin-Pin
Max Stress Ratio 0.801 : 1
Maximum Moment 90.1 k-ft Maximum Shear * 1.5
Allowable 112.5 k-ft Allowable
Max. Positive Moment 90.08 k-ft at 16.000 ft Shear: Q Left Max. Negative Moment 0.00 k-ft at 0.000 ft Q Right
Max Q Left Support 0.00 k-ft Camber: Q Left
Max Q Right Support 0.00 k-ft Q Center
Max. M allow 1 12.49 Q Right Reactions ...
fb 1.668.15 psi fv 97.71 psi Left DL 5.94 k Max
Fb 2,083.17 psi Fv 165.00psi Right DL 5.94 k Max
15.8 k
26.7 k
10.55 k 10.55 k
0.000 in 1.006 in 0.000 in
10.55 k
10.55k
I Deflections ~ ~~ ~~
Center Span ... Dead Load Total Load Left Cantilever ... Dead Load Total Load
Deflection -0.671 in -1.156 in Deflection 0.000 in 0.000 in ... Location 16.000 ft 16.000 ft .. . LengthlDefl 0.0 0.0
. .. LengthlDefl 0.0 0.0
. . . LengthlDefl 572.3 332.06 Right Canti lever.. . Deflection 0.000 in 0.000 in
I Stress Caics h
Bending Analysis Ck 22.210 Le cv 0.870 Rb
Q Center
Q Left Support
Q Right Support
Shear Analysis
Design Shear Area Required
Fv: Allowable
Bearing @ Supports
Max. Left Reaction
Max. Right Reaction
4.118 R 5.103
Max Moment
90.08 k-ft
0.00 k-ft
0.00 k-ft
Q Left Support
15.83 k
95.936 in2
165.00 psi
10.55 k
10.55 k
Sxx 648.000 in3 Area 162.000 in2 CI 0.997 Sxx Rea'd Allowable tb
518.90 in3 2,083.17 psi
0.00 in3 2,088.59 psi
0.00 in3 2,088.59 psi
Q Right Support
15.83 k
95.936 in2
165.00 psi
2.792 in Bearing Length Req'd
Bearing Length Req'd 2.792 in
Title :
Dsgnr: Description :
scope :
Job #
Date:
user: W.0603761, Ver 5.1.3. 22.Jun-1999. Win32 General Timber Beam
Description Jos A Bank
I Quew Values c
CANFIELD CONSULTING
STRUCTURAL EN GIN EERS
205 North Main Street Phone 714.647 9848 Fax 71 4.647 9645 Santa Ana, CA 92701
A project \Ti, w\t bY sheet no
location rmy3 dates’ I1-4 3
‘’lent job no 0+57
. ,
CANFIELD CONSULTING
STRUCTURAL ENGINEERS
STRUCTURAL CALCULATIONS
FOR
STEEL STORAGE RACKS
JOS A BANK
Job# 04-057
March 9,2004
proiect JO 3 /TANK
location
CAihFIELD CONSULTING
STRUCTURAL ENGINEERS
sheet no by ,9 I
date 3-8 -& 9 /
205 North Main Street
Santa Ana, CA 92701
Phone 714.647.9848 Fax 714.647.9645
job no. c''ent
proiect 50 S .A /.?AN K
I ocat I on
CANFIELD CONSULTlNG
STRUCTURAL ENGINEERS
sheet no by 37
date 3-8-m
205 North Main Street
Santa Ana, CA 92701 Phone 714.647.9848 Fax 714.647.9645
job no 'lien'
sheet no
-? project 30 5 /+ ?&A)/*' IbY ST GANFIELD CONSULTING I
205 North Main Street Santa Ana, CA 92701
Phone 714.647.9848 Fax 714.647.9645
1 1 location 1 date 7 - @ a$ I STRUCTURAL EN GIN EERS
job no. c"ent I"iY-C)v
!,
,,
-> 4 EA$jA< CANFIELD CONSULTING . pro'ect Jtp
STRUCTURAL ENGINEERS location
job no. 205 North Main Street
Santa Ana, CA 92701
Phone 714.647.9848 Fax 714.647.9645
sheet no by ST
date 3- 8 -oc/
I
I
-> --+
-4
-3 -> ->
-2
---?
4
'= 7- 76 I,,
-
proiect ~$25 A ~:dft~lt)
local I on CANFIELD CONSULTING
STRUCTURAL ENGINEERS
sheet no by 3 -7
date3- 8-w c5
- li'
I
I i
205 North Main Street
Santa Ana, CA 92701
Phone 714.647.9848
Fax 714.647.9645
job no o+! --os7 "lent
CANFIELD CONSULTING --- 1 by s"T project s& # Em K
STRUCTURAL ENGl N EERS
205 North Main Street
Santa Ana, CA 92701
Phone 714.647.9848 Fax 714.647.9645
sheet no. -
location
client
date 3' -8-09 1 6
iob no
I/' 04-os7
''I Compariy : Designer :
SEC?
SEC2 SEC3
March 9,2004
TSI .5X.75X.054 STL .231 1.2 1.2 .022 .067 1 .051
TSl.SX.75X,OM STL ,231 1.2 1.2 .022 .067 I .051
TS1.5X.75X.054 STL ,231 1.2 1.2 .022 .067 1 .051
Job hmber : Checked By.
SEC4 ,TS1.5X.75X.054, STL I .231 1.2 1.2 .022 , .067 ,051
RISA-3D Version 4 [C:\Storage Rack Sheetkteel posts.r3d] Page 1
'1 1
\
f
J 1 i
f
e
\ 3
i 3
i
!
c
c
J J i
c
J
J \
F 2
; i
b
CANflELD CO1AISULTING
STRUCTURAL ENGINEERS
205 horth Mm >tree[
Smta Ana, CA 92701
jeff@can~e~dcoilsu~lin~.net
Ph 714.647.9848 Fax: 711.647.9645
PROJECT BACK BRACE DET.
LOCATION JOS. k BANK CARLBAD. CA
SHEa NO. BY x
DATE 3/10/04 SK-1
CLIENT CCA
STOCK U" ELEVATION
JOB NO. CHECKEO X
DATE 3/\O/M
c
17 GAUGE TUBE SlEEL 60!3T 1 '/2'%3/4'
-'/2' WW SHELF
GALVANIED Srm WST
SIDE ELEVATION m
1
8 0 I i.,
m
CLIENT CCA 205 North Main Street Santa Ana, CA 92701
jeff@canfieldconsulting.nel
Ph: 7 14.647.Y848 Fax: 714.647.9645
F-
JOB NO. CHECKED X
DATE 3/10/04
/--
POST BASE DETAL m
205 North Miun Street
Sam Ana, CA 92701
jeff@canfieldconsulting.net
Ph: 714,647,9848
Fax: 714.647.9645
POST BASE DETAIL
Ecrs
JOB NO. CLIENT CCA CHECKECI X
DATE 3/10/04
r.
L
X- BRACINQ CONNECTION
NTS
1
GENERAL SEISMIC NOTES:
UGHT WTY STORAGE FIXCURE DESIGNED PER CHWrcR 22.1 DMSlON 6 OF THE 1994 U.B.C. 2 STOW WACilY: 50 LBS. PER SHELF LEVEL ASTU A570 FOR WE R- 330M) PSI GbE 33.3 Ur-BOLTS A307 UNLESS KTEO 4 -k%S SkL BE INSTAUOD WlTH A WMUM TOLElUNCE OF 5. 1 IN / 10 Fl.
X-BRACING R€WRED ON MRY OMER UNIT IN A RUN
X - BRACNQ DETAIL
HIS
CANFIELD CONSULTING
STRUCTURAL ENGINEERS
STRUCTURAL CALCULATIONS
FOR
JOS A BANK
Mechanical unit support
Job# 04-057
n
March 11,2004
3
CANFIELD CONSULTING
STRUCTURAL ENGl NEERS
sheet no wect- B W+ by rL
I ocat I on date5-//- 4 1
-A
5
205 North Main Street Sank Ana, CA 92701
Phone 714.647.9848 Fax 724.647.9645
r
job no. 'Iieni (%&
@---
4
P
CANFIELD CONSULllNG
STR U CTU R AL E N GI NE
205 North Main Street
Santa Ana, CA 92701 Phone 714.647.9848 Fax 714.647.9645
I
project &5 /I, h~ sheet no.
client job no.
4 ?= 4&
w'
, Title :
Dsgnr:
Description :
Job #
Date:
scope :
Page 1 Rev: 510300
(CI 1983-99 ENERCALC User: KW.0603761. Ver 5.1.3. 22.Jun.1999. Win32 General Timber Beam
Description Jos A Bank
I General Information Calculations are desianed to 1997 NDS and 1997 UBC Requirements h
Section Name 6.75x24.0 Beam Width 6.750 in Beam Depth 24.000 in Member Type GluLam
Bm Wt. Added to Loads
Load Dur. Factor 1.000
Beam End Fbtity Pin-Pin
Wood Density 35.000 pcf
Center Span Left Cantilever Right Cantilever Douglas Fir, 24F -
Fb Base Allow
Fv Allow
Fc Allow
E
32.00ft . . . . .Lu 2.00 ft ft . . . . .Lu 0.00 ft ft ..... Lu 0.00 ft
.V8
2,400.0 psi
165.0 psi 560.0 psi 1,800.0 ksi
LFUII Lengh Uniform Loads f
Center DL 288.00 #/ft LL 288.00 #/ft Left Cantilever DL #/ft LL #/ft Right Cantilever DL #/ft LL #Iff
I Point Loads c Dead Load 1,414.0 Ibs Ibs Ibs Ibs Ibs Ibs Ibs
Live Load Ibs Ibs Ibs Ibs IbS Ibs Ibs ... distance 16.000 ft 0.000 ft 0.000 ft 0.000 R 0.000 ft 0.000 ft 0.oooft
Beam Design OK
Span= 32.0Oft, Beam Width = 6.750in x Depth = 24.in, Ends are Pin-Pin Max Stress Ratio 0.801 1
Maximum Moment 90.1 k-ft Maximum Shear * 1.5
Allowable Allowable 112.5 k-ft
Max. Positive Moment 90.08 k-ft at 16.000 ft Shear: Q Left Max. Negative Moment 0.00 k-ft at 0.000 ft Q Right
Max Q Left Support 0.00 k-ft Camber: Q Left Max Q Right Support 0.00 k-ft Q Center
Max. M allow 112.49
fb 1,668.1 5 psi fv 97.71 psi Left DL 5.94 k Max
Fb 2.083.17 Psi Fv 165.00psi Right DL 5.94 k Max
Q Right Reactions ...
15.8 k
26.7 k
10.55 k 10.55 k
0.000 in
1.006 in 0.000 in
10.55 k
10.55 k
LDeflections
Total Load Left Canti lever.. . Dead Load Total Load Center Span ... Dead Load
Deflection -0.671 in -1.156 in Deflection 0.000 in 0.000 in ... Location 16.000 ft 16.000 ft . . . LengthlDefl 0.0 0.0
... LengthlDefl 0.0 0.0
. . . LengthlDefl 572.3 332.06 Right Cantilever ... Deflection 0.000 in 0.000 in
[ Stress Calcs
Bending Analysis Ck 22.210 Le cv 0.870 Rb
Q Center
Q Left Support Q Right Support
Shear Analysis Design Shear
Area Required Fv: Allowable
Bearing @ Supports
Max. Left Reaction
Max. Right Reaction
4.118 ft 5.103
Max Moment
90.08 k-ft
0.00 k-ft
0.00 k-ft
Q Left Support
15.83 k
95.936 in2
165.00 psi
10.55 k
10.55 k
SXX 648.000 in3 Area 162.000 in2 CI 0.997
Sxx Rea'd Allowable fb
518.90 in3 2,083.17 psi
0.00 in3 2,088.59 psi
0.00 in3 2,088.59 psi
Q Right Support
15.83 k
95.936 in2
165.00 psi
Bearing Length Req'd 2.792 in
Bearing Length Req'd 2.792 in
Title :
Dsgnr:
Description :
Scope :
Job #
Date:
Page 2 Rev: 510300
IC) 1983.99 ENERCALC User: KW-0603761. Ver 5.1.3. ZZ.Jun.1999. Win32 General Timber Beam
Description Jos A Bank
I Query Values C
M, V, 8 D @ Specified Locations Moment Shear Deflection
@ Center Span Location = 0.00 ft 0.00 k-ft 10.55 k 0.0000 in
@ Right Cant. Location = 0.00 ft 0.00 k-ft 0.00 k 0.0000 in
@ Left Cant. Location = 0.00 fl 0.00 k-ft 0.00 k 0.0000 in
Sketch & Diagram
t t
wAu( = 9O.lk-ft omu - 4.156in
!.W
Rmax = 10.6k
vmax @ left = 10.6k
Rmu -
Vmu @
104k
rt - io
Lwl 'y' Deflection (in) Lastion Along Member IW
CANFIELD CONSULTING
STRUCTURAL ENGINEERS
205 North Main Street
Santa Ana, CA 92701
Phone 714.647.9848
Fax 71 4 647.9645
4. sheet no project JIB WL- by
location dates' 11-4 3
job no client 04757
CANFIELD CONSULTING
STRUCTURAL ENGINEERS
STRUCTURAL CALCULATIONS
FOR
STEEL STORAGE RACKS
JOS A BANK
Job# 04-057
March 9,2004
Y ;s G
CAAFIELD CONSULTING
STRUCTURAL EN GIN EERS
205 North Main Street
Santa Ana, CA 92701
Phone 714.647.9848
Fax 714.647.9645
client I iob no. 0” - (25-7
b
7
0 9
I-
project .To A EAru I<
location
GANFIELD CONSULTING
STRUCTURAL ENGINEERS
sheet no by 37
date 3-8- &
205 North Main Street
Santa Ana, CA 92701
Phone 714.647.9848
Fax 714.647.9645
job no. .
project 305 A fYfhl/\'
location
OANFIELD CONSULTING
STRUCTURAL ENGINEERS
job no 205 North Main Street Santa Ana, CA 92701
Phone 714.647.9848 Fax 714.647.9645 04-057
__ __ _____ll-.l--_l.-----
sheet no by 3 ?
date 7 - 3 59 L5.
111-51
\
1%
project qxO_S 4 $,-+/J,<'
location
GANFIELD CONSULTING
STRUCTURAL ENGINEERS -
sheet no by 57
date 3-B -cr/
2 0; h'; i= I
205 North Main Street
Santa Ana, CA 92701
Phone 714.647.9848
Fax 714.647.9645
-3
-> --9
--3
-7
-3
-2 c --+
job no c''ent BY- 0-5 7
= 7.76 I,
proiect 3)s A- ~;MJ,+)
location
CARFIELD CONSULTING
STRUCTURAL ENGINEERS
sheet no
date3 - 5 -Ly k5
by 37
c
-
205 North Main Street
Sank Ana, CA 92701
Phone 714.647.9848
Fax 714.647.9645
job no. 'Iient
proiect ZG& A
location
- Ew K GARFIELD CONSULTING
STRUCTURAL ENGINEERS
sheet no by 37
date 3 -8-09 6
LOAD -
205 North Main Street
Santa Ana, CA 92701
Phone 714.647.9848
Fax 714.647.9645
50 lbs
job no. 'lien' 04- 05 7
Eornpa'ny : Dehigner : Job Number :
SECl TS1 SX.75X.054 STL 1 .231 1.2 I 1.2 ,022 SEC2 TSlSX.75X,OM STL I .231 "' 1.2 1.2 .022 SEC3 TS1 SX.75X.054 STL I ,231 1.2 1.2 .022 SEC4 TS1.5X.75&054 STt I ' .231 1.2 1.2 .022
March 9,2004
Checked By:
.067 .051
.067 .051 .067 .051 .067 f ,055 i
RISA3D Version 4 [C:\Storage Rack Sheetkteel posts.r3d] Page 1
-L 0
3
b
A
3
b
- y," x 17 GAUGE STRAP (X - WING REQD ON EMRY OMEf? UNIT IN A RUN)
STOCK UNIT ELEVATION
HIS
-
. 0
*?
*I
s 0 I -*?
n *I
c
- 8 n -
SIDE ELEVATION
NTS
CLIENT CCA 205 North Main Street
Sam Ana, CA 92701
jeCf@canfreldconsultina.net
Ph: 7 I4.647.’)848 Fax: 714.647.9645 r, c
JOB NO. CHECKED X
DATE 3/10/04
SECTlON A-A
SHELF
I I I 1 I
I I I I I
I I
I I
I
1
I
J
. h(
. r
POST BASE DETAIL
NTS
.CANFIE ID CONSULTt MG
S~RUCTURAL ENGINEERS
205 North Man Street Ph: 7 14.647.9848
Santa Ana, CA 92701 Fax: 714.647.7.%45
jeff@canfieldconsulting.net
POST BASE DETAL m
SHEET NO. By x SK-3 PRQECT BACK B~CE DEL
LNA~ON JOS. BANK ww. a DATE 3/10/04
CLIENT CCA CHECKED X JOB NO.
DATE 3/10/04
1
20.5 Nocth Main Street
Sanu Ana. CA 92701 jeff~canfieldconsul~~~.~
Ph: 7 14.647.YXUL
Fax: 714.647.9645
JOB NO. CLIENT CCA CHECKEO JC
DATE 3/10/M
3/; x 17 GAUGE
X- BRACINQ CONNECTION
NTS
L
G&MCIELD C~~SUL~~G
S-fRUCTURAL ENGINEERS
205 No& Main Street Ph: 714.647.9848
Saou Ana, CA 92701 Fax: 714.647.9645
jeff~can~eeldconsulting.net
GENERAL SEISMIC NOTES:
LIGHT DUTY STWE FlXNRE DESIGNED PER CHAPTER 22.1 DMSlON 6 OF ME 1994 U.B.C. 2 STORAGE WMIIY: 50 LBS. PER SHELF LEVEL &TU A570 FOR WE Fy- 33000 PSI GRADE 33.3 AU BOLTS A307 UNLESS NOTED 4 RACKS SW BE INSTALLED WlTH A WYUM TOLERANCE OF 5. I IN / 10 FT.
SHEET NO. BY x SK-5 PROJECT BRACE DEL
mnON Jos. A. WLRQ a DATE 3/10/04
CLIENT CCA CHECKED X JOB NO.
DATE 3/10/04
// END. M AT’CENTER.
X - BRACING =AIL m
TITLE 24 REPORT
Title 24 Report for:
Jos. A. Bank 1905 Calle Barcelona, Suite 141
Carlsbad, CA 92009
Project Designer:
Carlile Coatsworth Architects, Inc.
2458 Dupont Drive Imine, CA 92612
(949) 833-1 930
Report Prepared By:
Gregory Schnackel
Dale Schnackel Company
3035 South 72nd Street
Omaha, NE 68124-3583 (402) 391 -7680
Job Number:
040137
Date:
511 112004
The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is authorized by the California Energy Commission for use with both the Residential and Nonresidential 2001 Building Energy Efficiency Standards.
This program developed by EnergySoft, LLC (415) 883-5900.
EnergyPro 3.1 By EnergySofi Job Number: 040137 User Number: 4094
r
A