HomeMy WebLinkAbout1923 CALLE BARCELONA; 142; CB133105; Permit04-04-2014
City of Carlsbad
1635 Faraday Av Carlsbad, CA 92008
Commercial/Industrial Permit Permit No: CB133105
Building Inspection Request Line (760) 602-2725
Job Address:
Permit Type:
Parcel No:
Valuation:
Occupancy Group:
Project Title:
1923 CALLE BARCELONA CBADSt: 142
Tl Sub Type: COMM
2550120400 Lot#: 0
$50,000.00 Construction Type: 5B
Reference #
MADEWELL: INSTALLATION OF
RACKS
Status: ISSUED
Applied: 12/16/2013
Entered By: JMA
Plan Approved: 04/04/2014
Issued: 04/04/2014
Inspect Area
Plan Check #:
Applicant:
TASIA KALLIES
STE 450
111 W WASHINGTON ST
CHICAGO IL 60602-2817
312-260-7090
Owner:
T-C FORUM AT CARLSBAD LLC
C/O TIAA-CREF
4675 MACARTHUR CT #1100
NEWPORT BEACH CA 92660
Building Permit $450.62 Meter Size
Add'l Building Permit Fee $0.00 Add'l Red. Water Con. Fee $0.00
Plan Check $315.43 Meter Fee $0.00
Add'l Building Permit Fee $0,00 SDCWA Fee $0.00
Plan Check Discount $0.00 CFD Payoff Fee $0.00
Strong Motion Fee $10.50 PFF (3105540) $0.00
Park Fee $0.00 PFF (4305540) $0.00
LFM Fee $0.00 License Tax (3104193) $0.00
Bridge Fee $0.00 License Tax (4304193) $0.00
BTD #2 Fee $0.00 Traffic Impact Fee (3105541) $0.00
BTD #3 Fee $0,00 Traffic Impact Fee (4305541) $0.00
Renewal Fee $0.00 PLUMBING TOTAL $0.00
Add'l Renewal Fee $0.00 ELECTRICAL TOTAL $0.00
Other Building Fee $0.00 MECHANICAL TOTAL $0.00
Pot. Water Con. Fee $0.00 Master Drainage Fee $0.00
Meter Size Sewer Fee $0.00
Add'l Pot. Water Con. Fee $0.00 Redev Parking Fee $0.00
Reel. Water Con. Fee $0.00 Additional Fees $0.00
Green Bldg Stands (SB1473) Fee $1.00 HMP Fee ??
Fire Expedidted Plan Review $0.00 Green Bldg Standards Plan Chk ??
TOTAL PERMIT FEES $777.55
Total Fees: $777,55 Total Payments To Date: $777.55 Balance Due: $0.00
Inspector.*
FINAL
Date:
. APPROVAI/
Clearance:
NOTICE: Please take NOTICE that approvai of your project includes the "Imposition" of fees, dedications, reservations, or other exactions hereafter collectively
referred to as "fees/exactions," You have 90 days from the date this permit was issued to protest imposition of these fees/exactions. If you protest them, you must
follow the protest procedures set forth in Govemment Code Section 66020(a), and fiie the protest and any other required information with the City Manager for
processing in accordance with Carlsbad Municipal Code Section 3.32,030, Failure to timely follow that procedure will bar any subsequent legal action to attack,
review, set aside, void, or annul their imposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection fees and capacity
changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this project, NOR DOES IT APPLY to any
fRfts/exactions of which vou have previousiv been given a NOTICE similar to this, or as to which the statute of limitations has previously othenwi.se expired,
Cifcy of Carlsbad
1635 Faraday Ave., Carlsbad, CA 92008
760-602-2717 / 2718 / 2719
Fax: 760-602-8558
Building Permit Application
Plan Check No. -3^0^
Est. Value 50,OOd
Plan Ck. Deposit ^3
JOB ADDRESS 1923 Calle Barcelona SUITE#/SPACE#/UNIT#
142
CT/PROJECT # # OF UNITS # BEDROOMS # BATHROOMS TENANT BUSINESS NAME CONSTR, TYPE
IB
occ, GROUP
M
DESCRIPTION OF WORK: /nclude Square Feet of Affected Areafs)
Installation of shelving at Madewell retail store at Forum at Carlsbad. No high pile storage.
EXISTING USE
retail
PROPOSED USE
retail
GARAGE (SF) PATIOS (SF) DECKS (SF) FIREPLACE
YES|~|# NoTTI
AIR CONDITIONING
YES I INO I I
FIRE SPRINKLERS
YES|~|N0r71
CONTACT NAME (If Different Fom Applicant) Tasia Kallles APPLICANT NAIME Madewell
ADDRESS 111 West Washington Street, Suite 450 ADDRESS
770 Broadwav, 10th floor
CITY Chicago STATE
IL
ZIP
60602
CITY New York STATE NY 10003
PHONE 312-260-7090 FAX
312-407-7915
PHONE 212-647-0011 212-647-0022
EMAIL TKallies@Bumhamnationwide.com ElVIAIL
nuraldiins@hbcarch.com
PROPERTY OWNER NAME L.A. Forum Carlsbad, LLC CONTRACTOR BUS. NAME 0 . 0. <lDmfhP.(^^.,a
ADDRESS 1905 Calle Barcelona, Suite 200 ADDRESS P 0 BQ/ a '^l^^
CITY
Carlsbad
STATE
CA
ZIP
92009
CITY STATE . ZIP
PHONE /I, ,_ , [ I FAX PHONE
760-613-3783
FAX
EMAIL EMAIL
ARCH/DESIGNER NAME & ADDRESS
EcliDse Enaineerina Inc
STATE LIC, #
C61726
CLASS
Jl
CITY BUS, LIC.#
(Sec. 7031.5 Business and Professions Code: Any City or County wtiich requires a permit to construct, alter, improve, demolish or repair any structure, prior to its issuance, also requires the applicantfor such permit to file a signed statement that he is licensed pursuant to the provisions ofthe Contractor's License Law (Chapter 9, commending with Section 7000 of Division 3 of the Business and Professions Code) or that he is exempt therefrom, and the basis for the alleged exemption. Any violation of Section 7031.5 by any applicantfor a permit subjects the applicant to a civil penalty of not more than five hundred dollars ($500)),
WORKERS' COMPENSATION
Workers'Compensation Dec\antion: I hereby aflirm under penalty of perjury one of the following declarations:
ave and will maintain a certificate of consent to self-insure for workers' coinpensation as provided by Section 3700 of the Labor Code, for the performance of the work for which this pemnit Is issued. Ol*avi
Hlhav, it is issued. My wor1<ers' compensation insurance carrier and policy
Expiration Date ^— / / ^
I have and wiil maintain workers' compensation, as reauired by Section 3700 of the Labor Code, for the perfomiance of the work for which thjs
numberare: InsuranceCo ^^/"d /i:ai>\^p,^ i/)^.^ (^'f- ^ i/\ T*T5l(H^*j^" ^ C) ^ \ /'S
Bsection need not be completed if the permit is for one hundred dollars ($100) or less, f'lA-
Certificate of Exemption: I certify that in the perfomiance of the work for which this perniit is Issued, I sn^ll not employ any person in any manner so as to become subject to the Workers' Compensation Laws of
Califomia, WARNING: Failure to secure wortters'cfimpensption coverage Is unlawful, and shall subject an employer to criminal penalties and civil fines up to one hundred thousand dollars (&100,000), in
addition to the cost of compensation, damages iyfrimt^or in Section 3706 of the Labor code, Interest and attomey's fees. .\ .
>eS" CONTRACTOR SIGNATURE ^^1^/y^ ""^ ^
OWNER-BUILDER DECLARATION
.irj
I hereby affinn that I am exempt fmm (^tractor's License Law for the following reason:
I I I, as owner of the property or my employees with wages as their sole compensation, will do the wori( and the stnicture is not intended or offered for sale (Sec, 7044, Business and Professions Code: The Contractor's
License Law does not apply to an owner of property wtio buikis or improves thereon, and who does such work himself or through his own emptoyees, provided that such improvements are not intended or offered for
sale. If, however, the building or improvement is sold within one year of completion, the owner-builder will have the bunten of proving that he did not build or improve for the purpose of sale),
I I I, as owner of the property, am exclusively contracting with licensed contractors to constnict the project (Sec, 7044, Businessand Professions Code: The Contrxtors License Lawdoes not apply to an owner of
property who builds or improves thereon, and contracts for such projects with contractor(s) licensed pursuant to the Contractor's License Law),
I I I am exempt under Section Business and Professions Code for this reason:
1,1 personally plan to provide the major labor and materials for construction of the proposed property improvement. •Yes I INO
2,1 (have / have not) signed an application for a building pemiit for the proposed work.
3,1 have contracted with the following person (fimn) to provide the praposed constmction (include name address / phone / contractors' license number):
4.1 plan to provide portions of the work, but I have hired the following person to coordinate, supen/ise and provide the major work (include name / address / phone / contractors' license number):
5.1 will provide some of the work, but I have contracted (hired) the following persons to provide the worl< indicated (include name / address / phone / type of work):
>8rPR0PERTY OWNER SIGNATURE DATE
COMPLETE THIS SECTION FOR N O N - R E S I D E N T I A L BUILDING PERMITS ONLY
Is the applicant or futuro building occupant required to submit a businesiuto, acutely hazardous materials registration fomi or risk management and prevention program under Sections 25505,25533 or 25534 of the
Presiey-Tanner HazanJous Substance Account Act? I I Yes >l2^No
Is the applteant or future building occupant required to obtain a permit from the air pollution contral district or air qualitv management district? LjYes "^^3 No
Is the facility to be constmcted within 1,000 feet of the outer boundary of a school site? LjYes "^3)10
IF ANY OF THE ANSWERS ARE YES, A FiNAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR IS MEETING THE REQUIREMENTS OF THE OFFICE OF
EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT.
CONSTRUCTION LENDING AGENCY
I hereby affirm that there is a construction lending agency for the performance ot the work ttiis permit is issued {Sec 3097 (i) Civil Code),
Lender's Name Lender's Address
APPLICANT CERTIFICATION
i ceitify thati have read ttie applicaflon and state that the aboveinforrnation is conect and that ttieinfbnriation on the p^
I hereby authorize representative ofthe City of Carisbad to enter upon the above mentbned pnjperty for inspecton purposes, I ALSO AGREE TO SAVE, INDEMNIFY AND KEEP HARMLESS THE CITY OF CARLSBAD
AGAINST ALL LIABILITIES, JUDGMENTS COSTS AND EXPENSES WHICH MAY IN ANY WAY ACCRUE AGAINST SAID CITY IN CONSEQUENCE OF THE GRANTING OF THIS PERMIT,
OSHA: An OSHA pennit is required for excavations over 50 deep and demolitk)n or constmcta of stmctures over 3 stories in height
EXPIRATION: Every pennit issued by the Building Offidal underibfifliDviskjns ofthis Coda«Mll expire by limitatton and become null and voki if the building or work authorized by such pemnit is not commenced vwthin
180 days from the date of such pemiit or if the buiidingfflAJWflTaiihaized by such permills^spended or abandoned at any time after the work is commenced for a period of 180 days (Sectk)n 106,4,4 Unifonn Buikiing Oxie),
^APPLICANT'S SIGNATURE DATE
Inspection List
Permit#: CB133105 Type: Tl COMM MADEWELL: INSTALLATION OF
RACKS
Date Inspection Item Inspector Act Comments
04/15/2014 14 Frame/Steel/Bolting/Weldin PD AP
04/15/2014 19 Final Structural PD AP
Wednesday, April 16, 2014 Page 1 of 1
INSPECTION RECORI
•<:<?*
CARISBAD
Building Dlui^lon
K! INSPECTION RECORD CARD WITH APPROVED
PLANS MUST BE KEPT ON THE JOB
'•1 CALL BEFORE 3;30pm FOR NEXT WORK DAY INSPECTIOI
:0 FOR BUILDING INSPECTION CALL: 760-602-2725>('
OH GO TO: wwwJCariUaSw.aovj^BtUWinfl AND CLICK ON
"Request/—
DATE:
CB133105 1923 CALLE BARCELONA
MADEWELL INSTALLA riOfJ
RACKS
T! COMM
I ol# TASIA KALLiti'S
RtooRD COPV
IF • Yfci." IS CHECKED BELOW THAT DiViSiON'S APPROVAL SS REQUIRED PR!OR.TO...nOQlJESB.NG A >-IWrt.. L.
IF YCU HAVE ANY QUESTIONS PLEASE CALL THE APPLSCABLE OiViSlOMS AT THE PHONE NUMBERS PRC
ALL REQUrREO APPHCVALZ APE SIGNED OFF- P,.^X TO 760-602"e560. EMAIL TO BLDGlNSPECn.Q
OR BRlNrt m A COPY OE THiS CAF30 TO: 1635 FARADAY AVE,. CARL,SBAD. CA 92008. BulLOifK
REACHED AT 760-S02-2700 BETWEEN 7:30 AM ~ 8:00 AM THE DAV OF YOUR INSPECTION.
simo, A FiESAL BUILDING iNSPECTioN.
-"".....»=.,« oooviDBO BELOW. AFTER
NO
7
YES
2
Required Prior to Requeiting Building Final If Checlted YES
760 944 13463
Date I inspector Notes
Pianning/Landscsipe
CM&i iLngiiweiInq Iriipn-t o">< 760 433 1091
Allow AH hours
CnN bcforv Z (iffl
Fire Prewnbon Allow 48 hours
—
Type of Inspection
CODE »• BU.ILDIMG
#11
«12
#66
type of Inspection
Date Inspector
HO
#11
"#tl
»M
#1S
#13
»16
»lg
#17^
Jf55~
#19
FOUNDATION
REINFORCED STEEL _
MASONRY PRE GROUT'
• GROUT • WAaPRAIHS
TILTPANELS
POUR STRIPS
COIUMH fOOTWOS ^
SUBIHAME • FLOOR pciPLMO
ROOFSHEATHINB "
OT.SBEftR PANELS
INSULWiON^
EXTERIOR UTH
CODE » ELECTRICAL
ti31 •ELECimC UNDERGROUND 13 UFER
~«34 ROUGHELECTRiC _ .
*33 r ELECTRIC SERVICE „ TEMPORARY
Inspector
#35
i«39
PHOTO VOLTAIC
nHAL
CODE MECHANICAL
#41 UNDERGROUND DUCrea PIPING
#44 • DUCT & PLENUM PREP. PIWNO^
#43 HEAT-AIR COND. SYSTEMS
#49 FINAL
••au,. r. COf*4BO INSPECTiOf^
#81 UNDERGROUND (11,12.11.31)
1
j^NTERIOR LATH tt DRYVyALL
POOL EXCA/STEEL/BOND/FENCE
PREPLASTER/FINAL
FINAL W'lS'Cf Ji*fk *8S T'Baf<i4,aw«.Mr
#82 PRVWALl,EXTlATH,0ASTESt«,18.a3)
#83 ROOF SHEATING, EXTSHEAR (13,15)
#S4 FRAME ROUGH COMBO 114 24.34 44) |
CODE PLUMBING
m aSBWER* BL/CO D PL/CO
#21 UNPEROROUNO DWASTE DWra
#24 TOPOUT DWASTE OWrR
Date I inspector ' «S9 RNAL OCCUPANCV (19,29.39,49)
#27 TUB ft SHOWER PAH
"m DGASTEST aGASPIPINQ
A/SUNDERGROUND HYDRO
VS UNDERGROUND FLUSH
m WATER HEATER
#28 SOUR WATBI
"#29 FINAL
CLc* -t STORM WATER
#BBO PKE-CplCTtMCnOWWEEnNO
#eW WlXOWUPINSPECnOH
#805 NOTICETO CLEAN
A/S OVERHEAD VISUAL
A/5 OVERHEAp HYDROSTATIC
A/S FINAL
F/AROUGH-IN
2/AFINAL
FIXED EXTINGUISHING SYSTEM ROUGH-IN
CS07 WRITTEN WARNING -r
FIXED EXTING SYSTEM HYDROSTATICTEST a L
t
—I—
#80£ NOTICE OF VIOUTION
FKED EXnNOUISHINQ SYSTEM RNAL
MEDICAl OAS PRESSURETEST
#610 ifERBALWARNING [ MEDICAl OAS RNAL
SEC SACK COR SPeCMI.« •ies
Field Daily Report
Projecl#
/ /
Projecl#
/ /
rnhAHHr...- CjkUutL tf3^4f/eL^l*A^_^^c:vVS L .' 7^^^^
Projecl#
/ /
Report Date: / "S-jT// "Y
.^T" 7
License # jkJ^KL^^ Exp Date: f 7^ /'Z<^Co
License Required for tn.spection;
Contractor:
Contact at Site: -i
Penmit # C 31 ^ Jurisdiction " >-'^ •
Offsite? • Yes • No Offsite Location:
TYPE OF WORK: (check one) ^^einforced Concrete • Prestressed Concrete • Masonry • Welding
• Other :
Description of Work;
)ATE TASK# REGUL.\R
Inspector Nanie: l<J]^Xc^ •^'^Aol(
O.T.
.•\pproved by:
(Print Name)
TIME IN
Sio:nature:
Signature:
MARS INSPECTION INC.
"A Special Inspection Company "
1423 Savoy Circle, Point Loma, CA 92107
_^^^^^^^_^^^^jCeUPh^l9^33^33^Err^^
Project Name
Project Acldress
Architect: triSC
Engineer:_
Contractor:
of 1 nspection Report
Page:
Permit#:
File #:
DSA#:
Other:
Report #:
INSPECTION MATERIAL SAMPLING QTY MATERIAL DESCRIPTION INSPECTION CHECKLIST
><Structural Steel
Masonry
Concrete
Fireproofing .
J<.Other:^./|,Ffe,
Other: «
Other:
Other:
Other:
H.S. Bolts
Prisms
Mortar/Grout
Cone. Cylinders
Fireproof
Other:
Other:
Other:
Other:
H.S. Bolts
Cone. PSI
Grout PSI
Mortar PSI
Steel A'.5'di<a
Elect./Wire
Fireproof . ,
X Other: EH T-Y (Bed/Jc
X Other: ^< M" - 7z /n ct^ /?|7
f>C Plans/Specs
-^Clearances
Positions
^ Sizes
Laps
Consolidation
Xjorque Ft. Lbs.
Other:
Other:
/^Visual WeW • Ultra Sonic Test
, 1. Observed Welding By Certified Welders
2. All Welds i^dSingle Pass Fillets
• Epoxy Anchors • Concrete Placement
.^^Id
Vf
• Full Pen Groove Welds • Shop
• Continuous /^^feeriodic
• SMAW 3. Process Used Z^CAW nSMAW ^ , I f i
CERTIFICATION OF COMPLIANCE: All reported work, unless othenwise noted, complies with approved plans, specifications and
applicable sections of the building codes. This report covers the locations of the work inspected and does not constitute opinion or
project control. ^ j y^/^
Inspector: x ^ .^Z
T Date
Insp. Date: Day1: c»^tcbl4 Daya: ^^hUi Day 3: Day 4: Day 5:
Time Start:
Time Stop:
Copies of report submitted to:
EsGil Corporation
In (Partnersfiip witfi government for (BuiCding Safety
DATE: 12/27/2013 • APPLICANT
a^juRis.
JURISDICTION: City of Carlsbad • PLANREVIEWER
• FILE
PLANCHECKNO.: 13-3105 SET: I
PROJECTADDRESS: 1923 Calle Barcelona
PROJECT NAME: Shelving for Madewell
I I The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's codes.
^ The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
[ I The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
I I The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
I I The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
I I The applicant's copy of the check list has been sent to:
EsGil Corporation staff did not advise the applicant that the plan check has been completed.
I I EsGll Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Telephone #:
Date contacted: (by: ) Email: Fax #:
Mail Telephone Fax In Person
^ REMARKS: Fire Department approval is required.
By: David Yao Enclosures:
EsGil Corporation
• GA • EJ • MB • PC 12/17
9320 Chesapeake Drive, Suite 208 • San Diego, Califomia 92123 • (858) 560-1468 • Fax (858) 560-1576
City of Carlsbad 13-3105
12/27/2013
[DO NOT PAY- THIS IS NOT AN INVOICE]
VALUATION AND PLAN CHECK FEE
JURISDICTION: City of Carlsbad PLANCHECKNO.: 13-3105
PREPARED BY: David Yao DATE: 12/27/2013
BUILDING ADDRESS: 1923 Calle Barcelona
BUILDING OCCUPANCY: TYPE OF CONSTRUCTION:
BUILDING
PORTION
AREA
( Sq. FL)
Valuation
Multiplier
Reg.
Mod.
VALUE ($)
shelving per city 50,000
Air Conditioning
Fire Spnnklers
TOTAL VALUE 50,000
Jurisdiction Code cb By Ordinance
Bidg. Permit Fee by Ordinance
Plan Check Fee by Ordinance
Type of Review: IZI Complete Review • Structural Only
$450.62
$292.90
n Repetitive Fee
^1 Repeats
• Other
J—j Hourly
EsGil Fee
Hr. @ *
$252.35
Comments:
Sheet 1 of 1
macvaiue.doc +
PLAN CHECK PLAN CHECK Community & Economic
^ CITY OF REVIEW Development Department
1635 Faraday Avenue
CARLSBAD TRANSMITTAL Carlsbaci CA 92008
w/ww.carlsbadca.gov
DATE: 12/24/13 PROJECT NAME: Madewell _ shelving tenant imp PROJECT ID:
PLAN CHECK N0:CBi33iO5 SET#:I ADDRESS: ^923 Calle Barcelona APN:255-012-04
VALUATION: $5,000 APPLICANT CONTACT: tkallies@bumhamnationwide.eom
X Ths plan check review transmittal is to notify you of clearance by:
LAND DEVELOPMENT ENGINEERING DIVISION
Final Inspe ction by the Construction & Inspection Division is required: Yes
fif For status from a division not marked below, please call 760-602-2719
No X
This plan check review is NOTCOMPLETE Items missing or incorrect are listed
on the attached checklist. Please resubmit amended plans as required.
LAND DEVELOPMENT ENG.
760-602-2750
760^602^-4624 ;
Ch ris.Sf?xtonfic;ir lsbadca.gov ;
760^602-274.1 ^
KathleNini..av¥rence®'caiisbadca.gov :
760-602-4663
Gregory.Ryan@carlsbadca.gov
- Gtna Ryiz ' ;
760-602-4675 I
Gina.Ruizi/carSsbadca.gov
\/ linda Ontiveros
760-602-2773
Linda.Ontiveros@carlsbadca.gov
Cindy Wong j
760^602-4662 ^
Cyntliia.Woiig@cartebadca.gov |
Dominic Fieri I
760-602-4664 :
Dominic. Fieri;§carlsbadca.gGv i
Remarks:
PLANNING DIVISION Development Services
Planning Division BUILDING PLAN CHECK Development Services
Planning Division
^ CITY OF APPROVAL 1635 Faraday Avenue
CARLSBAD P-29 (760) 602-4610
www.carlsbadca.eov
DATE: 12/19/13 PROJECT NAME: T.I. PROJECTID:
PLAN CHECK NO: CB133105 SET#: ADDRESS: 1923 CALLE BARCELONA APN:
^ This plan check review is complete and has been APPROVED by the PLANNING
Division.
By: GINA RUIZ
A Final Inspection by the PLANNING Division is required • Yes ^ No
You may also have corrections from one or more ofthe divisions Usted below. Approval
from these divisions may be required prior to the issuance of a building permit.
Resubmitted plans should include corrections from all divisions.
[J This plan check review is NOT COMPLETE. Items missing or incorrect are listed on
the attached checklist. Please resubmit amended plans as required.
Plan Check APPROVAL has been sent to: tkallies@burnhamnationwide.com
For questions or clarifications on the attached checklist please contact the following reviewer as marked:
PUNNING
760-602-4610
ENGINEERING
760-602-2750
FIRE PREVENTION
760-602-4665
Chris Sexton
760-602-4624
Chris.Sexton@carlsbadca.gov
1 1 Kathleen Lawrence
760-602-2741
Kathleen.Lawrence@carlsbadca.fiov
r~| Greg Ryan
760-602-4663
Gregorv.Rvan@carlsbadca.gov
1 I Gina Ruiz
760-602-4675
Gina.Ruiz@carlsbadca.gov
1 1 Linda Ontiveros
760-602-2773
Llnda.Ontlveros@carlsbadca.gov
Cindy Wong
760-602-4662
Cvnthla.Wong@carlsbadca.gov
• • 1 1 Dominic Fieri
760-602-4664
Dominlc.Fieri@carlsbadca.gov
Remarks:
PLAN CHECK PLAN CHECK Community & Economic
CITY OF REVIEW Development Department
1635 Faraday Avenue
CARLSBAD TRANSMITTAL Carlsbad CA 92008
www.carlsbadca.gov
DATE: 04/03/14 PROJECT NAME: madewell PRO^CT ID:
PLAN CHECK NO: cbiaSlOS SET#: III ADDRESS: 1923 cafto/^i^elona APN:
This plan check review is complete and has been APPROVED by (^^re Division.
By: cwong
A Final Inspection by the Division is required ^ Yes • No
• This plan check review is NOT COIVIPLETE. Items missing or incorrect are listed on
the attached checklist. Please resubmit amended plans as required.
Plan Check Comments have been sent to: tkallies@burnhamnationwide.com
(and via usps)
You may also have corrections from one or more ofthe divisions listed below. Approval
from these divisions may be required prior to the issuance of a building permit.
Resubmitted plans should include corrections from all divisions.
For questions or clarifications on the attached checklist please contact the following reviewer as marked:
1 1 Chris Sexton
760-602-4624
Chris.Sexton@carlsbadca.^ov
1 1 Kathleen Lawrence
760-602-2741
Kathleen.Lawrence@carlsbadca.gov
1 1 Greg Ryan
760-602-4663
Gregorv.Ryan@carlsbadca.gov
1 1 Gina Ruiz
760-602-4675
Gina.Ruiz@carlsbadca.gov
1 1 Linda Ontiveros
760-602-2773
Linda.Ontiveros@carlsbadca.gov
X Cindy Wong
760-602-4662
Cvnthla.Wong@carlsbadca.gov
• • 1 1 Dominic Fieri
760-602-4664
Dominic.Fieri@carlsbadca.gov
Remarks:
4/3/14
**No hi pile permit required. Top of shelf per letter dated March 25, 2014, at 9' from Nuraldim Singh, HBC
Architects. Walls marked with height limit as shown on plans. ***
Page 1 of 2
APPROVED:
THIS PROJECT HAS BEEN REVIEWED AND APPROVED FOR THE PURPOSES OF ISSUEANCE OF A BUILDING PERMIT.
THIS APPROVAL IS SUBJECT TO FIELD INSPECTIONS, ANY REQUIRED TESTS, FIRE DEPARTMENT NOTATIONS,
CONDITIONS IN CORRESPONDENCE AND COMPLIANCE WITH ALL APPLICABLE CODES AND REGULATIONS.
THIS APPROVAL SHALL NOT BE HELD TO PERMIT OR APPROVE ANY VIOLATION OF THE LAW.
3/6/14
***Bubble All Changes***
1. Numbers 1 and 4 from comments dated 1/9/14 have yet to be addressed.
2. This will be considered high pile storage with top of shelf at 10'. To avoid, the top shelf shall be removed.
3. Annual Fire Use application and permit shall be required. The application will be sent via USPS. Provide an 8.5
X14 sheet showing all shelving, elevations and commodity classification per NFPA 13,
**Bubble All Changes**
1. Provide statement that addresses/specifies classification of commodities to be stored.
2. Bumpers that provide transverse flue spaces as shown on partial floor plan is not listed or referenced in the
materials list.
3. Sheet A-1.2: Note that specifies wire shelving appears to be "white out" from plans. Is this intentional? If so,
specify type of shelving and NFPA 13 section that speaks to design density required for commodity in this mobile
storage type if shelves are solid instead of wire type.
4. Provide note saying that maximum top of storage and delineating line will be painted on walls.
Page 2 of2
Carlsbad Fire Department
Plan Review Requirements Category: TI, COMM
Date of Report: 04-03-2014 Reviewed by:
Name:
Address:
TASIA KALLIES
STE 450
111 W WASHINGTON ST
CHICAGO IL
60602-2817
Permit #: CBI33105
Job Name: MADEWELL: INSTALLATION OF
Job Address: 1923 CALLE BARCELONA CBAD St: 142
ITSL'UMFLEIE ine item you have submitted for review'islnic8IH^Cte*'AUlais-lime. this office cannot^
adequately conduct a review to Hptprtnipp f> i'f*^it«llk» Ik^ appiiVdhip nr.H<»o Qr.H/r.r ot^7ffrnTni..i P|j»aoA r^^^^i^i^
carefully all i iiiiiiin iil,| iillix In ll I'll i i resubmit the necessary plans and/or specifications, with changes "clouded",
to this iiljii M Illl ll II and approval.
Conditions:
Cond: CON0006922
[NOT MET]
**Bubble All Changes**
1. Provide statement that addresses/specifies classification of commodities to be stored.
2. Bumpers that provide transverse flue spaces as shown on partial floor plan is not listed or
referenced in the materials list.
3. Sheet A-1.2: Note that specifies wire shelving appears to be "white out" from plans. Is this
intentional? If so, specify type of shelving and NFPA 13 section that speaks to design density
required for commodity in this mobile storage type if shelves are solid instead of wire type.
4. Provide note saying that maximum top of storage and delineating line will be painted on walls.
Cond: CON0007089
[NOT MET]
***Bubble All Changes***
1. Numbers 1 and 4 have yet to be addressed.
2. This will be considered high pile storage with top of shelf at 10'. To avoid, the top shelf
shall be removed.
3. Annud Fire Use application and permit shall be required. The application will be sent vis USPS.
Provide an 8.5 X14 sheet showing all shelving, elevations and commodity classification per NFPA 13,
Entry: 03/06/2014 By: cwong Action: CO
Cond: CON0007173
[MET]
**No hi pile permit required. Top of shelf per letter dated March 25, 2014, at 9' from Nuraldim
Singh, HBC Architects. Walls marked with height limit as shown on plans. ***
**APPROVED:
THIS PROJECT HAS BEEN REVIEWED AND APPROVED FOR THE PURPOSES OF ISSUEANCE OF A
BUILDING PERMIT.
THIS APPROVAL IS SUBJECT TO FIELD INSPECTIONS, ANY REQUIRED TESTS, FIRE DEPARTMENT
NOTATIONS,
CONDITIONS IN CORRESPONDENCE AND COMPLIANCE WITH ALL APPLICABLE CODES AND
REGULATIONS.
THIS APPROVAL SHALL NOT BE HELD TO PERMIT OR APPROVE ANY VIOLATION OF THE LAW.
Entry: 04/03/2014 By: cwong Action: AP
^ CITY OF
CARLSBAD
PLAN CHECK
REVIEW
TRANSMITTAL
Community & Economic
Development Department
1635 Faraday Avenue
Carlsbad CA 92008
www.carlsbadca.gov
DATE: 03/06/13 PROJECT NAME: madewell PROJECT ID:
PLAN CHECK NO: cbl33105 SET#: II ADDRESS: 1923 calle barcelona APN:
• This plan check review is complete and has been APPROVED by the fire Division.
By: cwong
A Final Inspection by the Division is required |3 Yes • No
^ This plan check review is NOT COIVIPLETE. Items missing or incorrect are listed on
the attached checklist. Please resubmit amended plans as required.
Plan Check Comments have been sent to: tkallies@burnhamnationwide.com
(and via usps)
You may also have corrections from one or more of the divisions listed below. Approval
from these divisions may be required prior to the issuance of a building permit
Resubmitted plans should include corrections from all divisions.
For questions or clarifications on the attached checklist please contact the following reviewer as marked:
PLANNING
760«02-4610
ENGINEERING
76&€02-2750
FIRE PREVENTION
76&602-4665
1 1 Chris Sexton
760-602-4624
Ch ris.Sexton@carisbadca.gov
1 1 Kathleen Lawrence
760-602-2741
Kathleen.Lawrence@carlsbadca.gov
Q Greg Ryan
760-602-4663
Gregorv.Rvan@carlsbadca.gov
1 1 Gina Ruiz
760-602-4675
Gina.Ruiz@carisbadca.gov
1 1 Linda Ontiveros
760-602-2773
Linda.Ontlveros@carisbadca.gov
X Cindy Wong
760-602-4662
Cvnthia.Wong@carlsbadca.gov
• • 1 1 Dominic Fieri
760-602-4664
Dominic.Fieri@carlsbadca.gov
Remarks:
3/6/14
***Bubble All Changes***
Page 1 of2
1. Numbers 1 and 4 from comments dated 1/9/14 have yet to be addressed.
2. This will be considered high pile storage with top of shelf at 10'. To avoid, the top shelf shall be removed.
3. Annual Fire Use appiication and permit shall be required. The application will be sent via USPS. Provide an 8.5
Xi4 sheet showing all shelving, elevations and commodity classification per NFPA 13,
**Bubble All Changes**
1. Provide statement that addresses/specifies classification of commodities to be stored.
2. Bumpers that provide transverse flue spaces as shown on partial floor plan is not listed or referenced in the
materials list.
3. Sheet A-1.2: Note that specifies wire shelving appears to be "white out" from plans. Is this intentional? If so,
specify type of shelving and NFPA 13 section that speaks to design density required for commodity in this mobile
storage type if shelves are solid instead of wire type.
4. Provide note saying that maximum top of storage and delineating line wiil be painted on walls.
Page 2 of2
Carlsbad Fire Department
Plan Review Requirements Category: TI, COMM
Date of Report: 01 -09-2014 Reviewed by:
Name:
Address:
TASIA KALLIES
STE 450
111 W WASHINGTON ST
CHICAGO IL
60602-2817
Permit #: CBI33105
Job Name: MADEWELL: INSTALLATION OF
JobAddress: 1923 CALLE BARCELONA CBAD St: 142 "
INCOMPLETE The item you have submitted for review is incorjiplete. At this time, this office cannot
adequately conduct a review to determine compliance with the applicable codes and/or standards. Please review
carefully all comments attached. Please resubmit the necessary plans and/or specifications, with changes "clouded",
to this office for review and approval.
Conditions:
Cond: CON0006922
[NOT MET]
**Bubble All Changes**
1. Provide statement that addresses/specifies classification of commodities to be stored.
2. Bumpers that provide transverse flue spaces as shovra on partial flbor plan is not listed or
referenced in the materials list.
3. Sheet A-1.2: Note that specifies wire shelving appears to be "whit6 out" fi-om plans. Is this
intentional? If so, specify type of shelving and NFPA 13 section that speaks to design density
required for commodity in this mobile storage type if shelves are solid instead of wire type.
4. Provide note saying that maximum top of storage and delineating line will be painted on walls.
Entry: 01/09/2014 By: cwong Action: CO
Carlsbad Fire Department
Plan Review Requirements Category: Tl, COMM
Date of Report: 01-09-2014 Reviewed by: QA^AJI
Name:
Address:
TASIA KALLIES
STE 450
111 W WASHINGTON ST
CHICAGO IL
60602-2817
Permit #: CB133105 ' Cn
Job Name: MADEWELL: INSTALLATION OF
JobAddress: 1923 CALLE BARCELONA CBAD St: 142
INCOMPLETE The item you have submitted for review is incomplete. At this time, this office cannot
adequately conduct a review to determine compliance with the applicable codes and/or standards. Please review
carefully all comments attached. Please resubmit the necessary plans and/or specifications, with changes "clouded",
to this office for review and approval.
Conditions:
Cond: CON0006922
[NOT MET]
**Bubble All Changes**
1. Provide statement that addresses/specifies classification of commodities to be stored.'y^-^
2. Bumpers that provide transverse flue spaces as shown on partial floor plan is not Hsted or
referenced in the materials list.
3. Sheet A-1.2: Note that specifies wire shelving appears to be "white out" from plans. Is this
intentional? If so, specify type of shelving and NFPA 13 section that speaks to design density
required for commodity in this mobile storage type if shelves are solid instead of wire type.
4. Provide note saying that maximum top of storage and delineating line will be painted on walls.
Entry: 01/09/2014 By: cwong Action: CO
HOWELL BELANGER CASTELLI ARCHITECTS
122 West 27th Street
4tti Floor
New York, New York 10001
212,647.001 1
tax,547,0022
HBC ARCH,COm
March 25,2014
Attn: Cindy Wong
Fire Department Plans Examiner
Re: 1923 CaUe Barcelona rCB13-3031)
Madewell Retail Store
The Forum At Carlsbad
1923 Calle Barcelona
Carlsbad, CA 92009
HBC Project No. 13070
Dear Cindy,
In response to your objections/comments regarding the High Shelving and Declaration of Commodities, please find the
following responses fi'om our office. We have revised our drawings as per Revision No.4 dated 03.25.14.
Fire Department Plan Review:
Comment; 1. Provide statement tfiat addresses/specified classification of commodities to be stored.
Response: Note has been added to the Cover Sheet as required under NFPA 13 as IV.
Commetit: 2. Considered high pile storage with top of shelf at 10 '-0 ". To avoid, the top shelf shall be removed.
Response; Shelves have been modified within the BOH to a maximum height AFF of 9'-0" as per code and your
request.
Please contact me if you have any questions or comments, thank you.
HOWELL BELANGER CASTELLI ARCHITECTS, PC
Nuraldim Singh, HBC Architects
cc: Matthew Dresser, HBC Architects
D. Shane Harvey, J. Crew
^ CITY OF
CARLSBAD
PLAN CHECK
REVIEW ^>
TRANSMITTAL
Community & Economic
Development Department
1635 Faraday Avenue
IQ Carlsbad CA 92008
' j/\ www.carlsbadca.gov
^
DATE: 01/08/13 PROJECT NAME: madewell
PUN CHECK NO: cbl33105 SET#: I
PROJECT ID:
ADDRESS: 1923 calle barcelona ipN:
Q This plan check review is complete and has been APPROVED by the fire Division.
By: cwong
A Final Inspection by the Division Is required |^ Yes • No
^ This plan check review Is NOT COIVIPLETE. Items missing or Incorrect are listed on
the attached checklist. Please resubmit amended plans as required.
Plan Check Comments have been sent to: tkallies@burnhamnationwlde.com
(and via usps)
You may also have corrections from one or more of the divisions listed below. Approval
from these divisions may be required prior to the issuance of a building permit.
Resubmitted plans should include corrections from all divisions.
For questions or clarifications on the attached checklist please contact the following reviewer as marked:
1 1 Chris Sexton
760-602-4624
Chris.Sexton@carlsbadca.gov
1 1 Kathleen Lawrence
760-602-2741
Kathleen.Lawrence@carlsbadca.gov
Q Greg Ryan
760-602-4663
GregorY.RYan@carlsbadca.gov
1 1 Gina Ruiz
760-602-4675
Gina.Ruiz@carlsbadca.gov
1 1 Linda Ontiveros
760-602-2773
Linda.Ontiveros@carlsbadca.gov
X Cindy Wong
760-602-4662
Cynthia.Wong@carlsbadca.gov
• • 1 1 Dominic Fieri
760-602-4664
Dominic.Fieri@carlsbadca.gov
Remarks:
**Bubble All Changes**
1. Provide statement that addresses/specifies classification of commodities to be stored. <v^-e^
Page 1 of 2
2. Bumpers that provide transverse flue spaces as shown on partial floor plan Is not listed or referenced In the
materials list.
3. Sheet A-i.2: Note that specifies wire shelving appears to be "white out" from pians. Is this Intentional? If so,
specify type of shelving and NFPA 13 section that speaks to design density required for commodity in this mobile
storage type if shelves are solid instead of wire type.
4. Provide note saying that maximum top of storage and delineating line will be painted on walls.
Page 2 of 2
Carlsbad Fire Department
Plan Review Requirements Category: TI, COMM
Date of Report: 01 -09-2014 Reviewed by:
Name: TASIA KALLIES
Address: STE 450
111 W WASHINGTON ST
CHICAGO IL
60602-2817
Permit #: CBI33105
JobName: MADEWELL: INSTALLATION OF
Job Address: 1923 CALLE BARCELONA CBAD St: 142
INCOMPLETE The item you have submitted for review is incomplete. At this time, this office cannot
adequately conduct a review to determine compliance vdth the applicable codes and/or standards. Please review
carefully all comments attached. Please resubmit the necessary plans and/or specifications, with changes "clouded",
to this office for review and approval.
Conditions:
Cond: CON0006922
[NOT MET]
* *Bubble All Changes * *
1. Provide statement that addresses/specifies classification of conunqdities to be stored, ^ j
2. Bumpers that provide transverse flue spaces as shown on partial floor plan is not listed or
referenced in the materials list.
3. Sheet A-1.2: Note that specifies wire shelving appears to be "white out" firom plans. Is this
intentional? If so, specify type of shelving and NFPA 13 section that speaks to design density
required for commodity in this mobile storage type if shelves are solid instead of wire type.
4. Provide note saying that maximum top of storage and delineating lline will be painted on walls.
Entry: 01/09/2014 By: cwong Action: CO
^ECLIPSE
ENGINEERING
ECLIP5E-ENGINEERING.COM
January 22,2014
City of Carlsbad, Fire Department
Attn: Cindy Wong
2560 Orion Way
Carisbad, CA 92010
Re: Madewall #295 - The Forum at Carlsbad - Space #142
1923 Calle Barcelona
Carlsbad, CA 92009
EEI Project Number: 13-11-138
Carlsbad Permit No. = CB133105
To Ms. Wong:
^AN Z 12014
•QFCAUJ
This letter was prepared in an effort to assist your review of our responses to the comments generated by the City of
Carlsbad Fire Department. Please note that Eclipse Engineering, Inc. is only re-submitting structural details for the shelving
racl<s. All other submittal requirements shall be provided by the project architect or their consultants.
Comments:
1. Provide sfafemenf (hat addresses/specifies (dassification of commodities to be stored.
A. This item shall be handled by others.
2. Bumpers that provide transverse pue spaces as shown on partial floor plan is not listed or referenced in the materials
list.
A. Duly noted - please reference plan sheet 1.
3. Sheef A-1.2; Note fhaf specifles wire shelmg appears to be Vh/(e ouf" from plans. Is this intentional? If so, specify
type of shelving and NFPA 13 section that speaks to design density required for commodity in this mobile storage
type if shelves are solid instead of wire type.
A. This item shall be handled by others.
4. Prow'de note saying that maximum top of storage and delineating line will be painted on walls.
A. Duly noted - please reference plan sheet 1.
Eclipse Engineering, Inc. has only reviewed the structural components within our scope of services, and we do nottal<e any
responsibility for any other portion of the project or plan submittal. Please feel free contact us with any questions on this
portion of the project - (541) 389-9659.
Sincerely,
Eclipse Engineering, Inc.
Matt Gaivin
Staff Engineer
Bend, OR
541-389-9659
Enclosed: shelving calculations, detail sheet
MISSOULA
U3 VMU Mah, Sl* S. Mnoia. MT 5980?
Hwm: (we) TZtem • Fax (wn 721-«»e
WHlfEFISH
lOOS EWear/M., 5ut> E. WHWWl. Mree837
PlmiK («») m'37IS • Fax taMffi^TlS
ECU PSE
ENGINEERING
ECLIPSE-ENGINEERING.COM
Structural Calculations
steel Storage Racks
By Pipp Mobile Storage Systems, Inc.
PIPP PO #107613 SO #328277
JAN 2 2 2014
m 3o20ff
Madewell #295
The Forum at Carlsbad
1923 Calle Barcelona - Space #142
Carlsbad, California 92009
Prepared For:
Pipp Mobile Storage Systems, Inc.
2966 Wilson Drive NW
Walker, Ml 49544
Please note: The calculations contained within justify the seismic resistance of the shelving racks, the fixed
and mobile base supports, and the connection to the existing partition walls for both lateral and overturning
forces as required by the 2010 California Building Code. These storage racks are not accessible to the
general public.
MISSOULA
113 West Main, Siie B, Mssoub. MT 58602
Phone: (406) m-em • Fax (W6) 721-4988
WHITEFISH
1005 Batef Ava, Sute E, Whieflsli, MT 58837
Phone: (406) 862-3715 • Fax: 406662^
^j|MU0lhAHMfHra.OR 87702
•Hnne: (541) 38»«669 • Fax: (541) 312^
Eclipse Engineering, Inc. MADEWELL #295 11/11/2013
Consulting Engineers CARLSBAD, CA Rolf Armstrong, PE
Pipp Mobile STEEL STORAGE RACK DESIGN
2009 IBC & 2010 CBC - 2208 & ASCE 7-05 - 15.5.3
Design Vertical Steel Posts at Each Comer: pit := ib tr ^
Shelving Dimensions: psf:=ib fi"^
Total Height of Sfielving Unit - ht := 10.00 ft pcf := ib-ft" ^
Width of Shelving Unit - w := 3.00 ft l<si := lOOO Ib in" ^
Depth of Shelving Unit - d := 2.50 ft Idps := 1000-Ib
Number of Shelves - N .= 10
Vertical Shelf Spacing - S := 13.33 in
Shelving Loads:
Maximum Live Load on each shelf is 100 Ibs:
Weight per shelf - Wt) ;= 100 • Ib Wq = 100 Ib
^^'"P^^- LLj:=^ L^= 13.3333.psf
^ wd ^ ^
Design Live Load on Shelf - LL := LLj LL = 13.3333• psf
Dead Load on Shelf - DL := 2.50 psf
Section Properties of Double Rivet 'L' Post:
Modulus of Basticity of Steel - E := 29000 • ksi b:= 1.5in
h:= l.Sin
Steel Yield Stress - Fv := 33 ksi
y ry:=0.47in
Section Modulus in x and y - Sx := 0.04 in^ TX := 0.47 in
Moment of Inertia in x and y - Ix := 0.06 in^ t := 0.075 in
Full Cross Sectional Area - Ap := 0.22- in :„2 he := 1.42in
be := 1.42in
Length of Unbraced Post - W< := S = 13.33 in Ly := S = 13.33 in Lt:= S = 13.33 in
Effective Length Factor - Kx := 1.0 Ky := 1.0 Kt := 1.0
Section Properties Continued:
Density of Steel - psteel := 490 pcf
Weight of Post - Wp := psteel Ap ht Wp = 7.491b
Vertical DL on Post - P^ := DL-w-.25d N -H Wp Pj = 54.361b
Vertical LL on Post- P, := LL-w-.25d-N P|= 2501b
Total Vertical Load on Post - Pp := Pj -i- p, Pp = 304.36 • Ib
Eclipse Engineering, Inc.
Consulting Engineers
MADEWELL #295
CARLSBAD, CA
11/11/2013
Rolf Armstrong, PE
Floor Load Calculations
Weight of Mobile Carriage:
Total Load on Each Unit:
Area of Each Shelf Unit:
Floor Load under Shelf:
Wc := 901b
W:= 4 Pp-i-Wc
Ay := (w -I- 9 in)-(d-H 4 in)
W
PSF:
W= 1307.441b
Au= 10.625 ft^
PSF= 123 psf
NOTE: SHELVING LIVE LOAD IS CONSISTENT WITH 125 psf REQ'D FOR RETAIL FLOOR LOADING
Find the Seismic Load using Full Design Live Load :
ASCE-7 Seismic Design Procedure:
Importance Factor -
Determine Sg and S^ from maps
Determine tfie Site Class -
Determine Fg and F^ -
Determine S^^s -
Determine S^g and S^j.
IE := 1.0
Ss:= 1.222
Class D
Fa:= 1.011
SMS:= f^a-Ss
SMS= 1.2354
SDS:= 3'^MS
SDS =0.824
Structural System - Section 15.5.3 ASCE-7:
4. Steel Storage Racks R := 4.0
Rp:=R
Total Vertical LL Load on Shelf - W| := UL w d
no:= 2
ap := 2.5
Total Vertical DL Load on Shelf •
W
WH := DL-w d + 4—-° N
Seismic Analysis Procedure per ASCE-7 Section 13.3.1:
Average Roof Height -
Height of Rack Attachment -
hr := 20.0 ft
Seismic Base Shear Factor - Vt :=
z:= Oft
0.4apSDs
Shear Factor Boundaries Vtmin := 0.3 SDS-Ip
Vtmax:= 1.6SDsIp
Vt:= if(Vt>Vt,nax.Vtmax.Vt)
Vt:= if(Vt<Vt„,|n,Vt^in,Vt)
Sl := 0.458
Fv := 1.542
SMI := Fy Si
SMI = 0.7062
% := 3 SMI
SDI = 0.471
Cd := 3.5
Ip := 1.0
W|= 100 Ib
Wd = 21.741b
(O'-O" For Ground floor)
Vt= 0.206
Vtmin = 0.247
Vtmax= 1.318
Vt= 0.247
Eclipse Engineering, Inc. MADEWELL #295 11/11/2013
Consulting Engineers CARLSBAD, CA Rolf Amistrong, PE
Seismic Loads Continued :
Vt
For ASD, Shear may be reduced - Vn := — = 0.176
^ 1.4
Seismic DL Base Shear - Vjd := Vp Wd N = 38.381b
DL Force per Shelf: Fd := Vp Wd = 3.841b
Seismic LL Base Shear - V^ := Vp W| N = 176.49 Ib
U. Force per Shelf: F, := Vp Wi = 17.65 Ib
0.67 * LL Force per Shelf: Fie? •= 0.67 Vp • W| = 11.82 Ib
Force Distribution per ASCE-7 Section 15.5.3.3:
Operating Weight is one of Two Loading Conditions :
Condition #1: Each Shelf Loaded to 67% of Uve Weight
Cumulative Heights of Shelves -
Hi := O.O S + 1.0 S + 2.0 S + 3.0 S + 4.0 S + 5.0 S + 6.0 S + 7.0 S + S.O S + 9.0 S
H2:=0 H:=HI-HH2 H = 49.99ft
Total Moment at Shelf Base - Mt .= H Wd + H 0.67 W| Mt = 4436.11 ft ib
Vertical Distribution Factors for Each Shelf -
Total Base Shear - Vtotai := Vtd + 0.67 Vti Vtotai = 156.63 Ib
Wd-O.O S-i-W| 0.67 0.0 S Wd-l.O S-f W| 0.671.0 S
Cl := = 0 C, := = 0.022
^ Mt Mt
Fl := Ci{Vtotal) = 0 F2 := C2(Vtotal) = 3.48 Ib
Wd 2.0 S + W| 0.67 2.0 s Wd 3.0 s + W| 0.67-3.0 S
C3 := = 0.044 C4 := = 0.067
Mt Mt
F3 := C3(Vtotai) = 6.96 Ib F4 := C4(Vtotai) = 10.441b
Wd-4.0 S -I- W| 0.67-4.0 S Wd-5.0 S + W| 0.67-5.0 S
C5:= = 0.089 C6:= = 0.111
Mt ^ Mt
F5 := C5(Vtotal) = 13.921b Fg := C6(V,„tal) = 17.41b
Wd-6.0 S + W| 0.67 6.0 S WH 7.0 S + W| 0.67-7.0 S
C7 := = 0.133 Cg := 0.156
Mt " Mt
Fy := C7-(V,„tal) = 20.881b Fg := C8(Vtotai) = 24.361b
Wd-8.0 S -I- W| 0.67 8.0 S Wd-9.0 S + Wi 0.67 9.0 S
Cg := = 0.178 Cio := 0.2
Mt Mt
F9 := C9 (V,otal) = 27.841b Fio := Cio (Vtotai) = 31.331b
Cl -(- C2 + C3 -H C4 -t- C5 -I- Ce + C7 -I- Cs + Cg -h Cio = 1 Coefficients Should total 1.0
Eclipse Engineering, Inc. MADEWELL #295 11/11/2013
Consulting Engineers CARLSBAD, CA Rolf Armstrong, PE
Force Distribution Continued :
Condition #2: Top Shelf Only Loaded to 100% of Uve Weight
Total Moment at Base of Shelf - Mta := (N - 1) S Wd + (N - 1) S Wi = 1217ft lb
Total Base Shear - Vtotac := Vtd + F| ^totaa = 56.03 Ib
Wd-O.O S-i-O W| O.O S Wd (N- l) S-i-W|-(N- 1) S
Cia:= = 0 Ctea:= -; = 1
Mta Mta
Fla := Cia (Vtota.2) = 0 ^^.^ C^iV^^) = 56.031b
Condition #1 Controls for Total Base Shear
By Inspection, Force Distribution for intermediate shelves witfx)Ut LL are negligible.
Moment calculation for each column is based on total seismic base shear.
Column at center of rack is the worst case for this shelving rack system.
1 S
Column Design in Short Direction : Mj := - •- (Vtd + Vu) = 29.84ft lb
Bending Stress on Column - fi,x := Mj Sx" ^ = 8.95 ksi
Allowable Bending Stress - Fb := 0.6 Fy = 19.8 ksi
Bending at the Base of Each Column is Adequate
Deflection of Shelving Bays - worst case is at the bottom bay
(Vtri + Vtij-S^ S
A := -i^ = 0.0244 in — = 546.8859
12E-Ix A
At:= A-(N - 1) = 0.2194 in Aa:= 0.05 ht= 6 in
if (At < Ag, "Deflection is Adequate", "No Good") = "Deflection is Adequate"
Moment at Rivet Connection:
Shear on each rivet - -j
Ms d/-3.14 ,
dr := 0.25in Vf := 238.68 lb Ar := = 0.0491 in^
1.5in 4
Vr
Steel Stress on Rivet - f^ := — = 4.86 ksi A,
Allowable Stress on Rivet - F^ := 0.4-80 ksi = 32 ksi
RIVET CONNECTION IS ADEQUATE FOR MOMENT CONNECTION FROM BEAM TO POST
Eclipse Engineering, Inc. MADEWELL #295 11/11 /2013
Consulting Engineers CARLSBAD, CA Rolf Armstrong, PE
Seismic Uplift on Shelves :
Seismic Vertical Component: Ev := 0.2-SDS (DL -I- LL) w d Ev = 19.5612 Ib
Vertical Dead Load of Shelf: D := (DL -f LL) w d D = 118.75 Ib
Note: since the shelf LL is used to generate the seismic uplift force, it may also be used to
calculate the net uplift load. For an empty shelf, only the DL would be used, but the ratio
of seismic uplift will be the same.
Net Uplift Load on Shelf: Fu := Ev - 0.6-D Fu = -51.6888 Ib
Note: This uplift load is for the full shelf. Each shelf will be connected at each corner.
Number of Shelf Connections: Nc := 4
Fu
Uplift Force per Corner: Fuc := — Fuc = -12.9222 Ib
Nc
MOTE: Since the uplift force is negative, a mechanical connection is not requiredr
Eclipse Engineering, Inc.
Consulting Engineers
MADEWELL #295
CARLSBAD, CA
11/11/2013
Rolf Armstrong, PE
Find Allowable Axial Load for Column :
Allowable Buckling Stresses -
^ex.x •" ( Kx-k^l
= 355.82 ksi
V 'X ;
Distance fi'om Shear Center
to CL of Web via X-axis er:=
t-hcW
4L
Distance From CL Web to Centroid - Xc := 0.649-in - 0.5 t
Distance From Shear Center
to Centroid -
Polar Radius of Gyration -
Torsion Constant -
Warping Constant -
Shear Modulus -
Xo:= Xc+ ec
r~2 2 2
J:=l.(2.b.t3 + h.t3)
3 '
^ex-= '^ex.x = 355.82-ksi
ec= 1.2706ln
Xc = 0.6115in
Xo= 1.8821 in
ro= 1.996in
J = 0.00063 In^
t b^ h^ (3 bX+ 2 h t
12 V 6 b t-Hh t
G:= 11300 ksi
CTt:=
Ap fo
G-J-H
TT^ECw
(Kfk)^
Cw= 0.0339 in"
crt= 70.4601 ksi
Fet := [(^ex + ^t) - V (*^ex + o^t)^ " 4 P orex <Tt]
Elastic Flexural Buckling Stress Fe := if (Fet < o'ex- Fet. '''ex)
Fn := if Allowable Compressive Stress -
Factor of Safety for Axial Comp. - := 1.92
Fe>Y.Fy
3 = 0.1109
.Fe
Fet = 59.7422 ksi
Fe= 59.7422 ksi
Fn = 28.4429 ksi
Eclipse Engineering, Inc.
Consulting Engineers
MADEWELL #295
CARLSBAD, CA
11/11/2013
Rolf Amistrong, PE
Find Effective Area -
Determine the Effective Width of Flange
Flat width of Flange -
Flange Plate Buckling Coefficient •
Flange Slenderness Factor -
Wf := b - 0.5 t
kf := 0.43
Xf:
1.052 Wf fF^
Pf := 0.22
Effective Flange Width -
Determine Effective Width of Web •
Flat width of Web-
Web Plate Buckling Coefficient -
Web Slenderness Factor -
be := if (Xf > 0.673, Pf Wf, Wf)
w„ := h - t
kv,:= 0.43
_ 1.052 Wy,
Pw- 1-
0.22^
Xy^
_1_
Xyv
Wf = 1.4625 in
Xf = 0.9797
Pf = 0.7915
be= 1.1576in
w„= 1.425-in
X„= 0.9546
Pw = 0.8061
Effective Web Width -
Effective Column Area -
Nominal Column Capacity -
Allowable Column Capacity -
Check Combined Stresses
he := \f{\i > 0.673, p„ Ww,w„) hg = 1.1487 i in
Ae:= t(he+ be)
Pn '•- Ae'Fn
Pn
fio
Ae= 0.173in''
Pn = 49201b
Pa = 25621b
TT^EIx
P -
(Kx-l^)^
P — P "^cr •- "^crx
Magnification Factor
Combined Stress:
Prry=9.66x 10^ lb
Per = 96647.071b
a:= 1-
P.
^»oPp^
^ + £21:^.0:505
Pa Fbtt
a = 0.994 Cn, := 0.85
MUST BE LESS THAN 1.0
Final Design: 'L' POSTS WITH BEAM BRACKET ARE ADEQUATE FOR
REQD COMBINED AXIAL AND BENDING LOADS
NOTE: Pp is the total vertical load on post, not 67% live load, so the design is conservative
Eclipse Engineering, Inc.
Consulting Engineers
MADEWELL #295
CARLSBAD, CA
11/11/2013
Rolf Armstrong, PE
STEEL STORAGE RACK DESIGN - cont'd
Rnd Overturning Forces
Total Height of Shelving Unit -
Depth of Shelving Unit -
Number of Shelves -
Height to Top Shelf Center of G -
Height to Shelf Center of G -
Ht:= ht= 10ft
d= 2.5ft
N= 10
htop := Ht
IV:.^S
Width of Shelving Unit - w = 3 ft
WORST CASE
Vertical Shelf Spacing - S = 13.33 in
htop= 10ft
he = 6.1096-ft
From Vertical Distribution of Seismic Force previously calculated -
Controlling Load Cases -
Weight of Rack and 67% of LL - W := (Wd + 0.67-W|) • N W = 887.44 Ib
Seismic Rack and 67% of LL - V := V,d + 0.67 Vti V = 156.63 Ib
Ma:= Fi-O.O S+ F2 1.0 S+ F3 2.0 S-h F4-3.0 S-f F5 4.0 S-H Fg 5.0 S + F7-6.0 S + Fg 7.0 S
Mb := Fg-B.OS + Fio-9.0S
Overturning Rack and 67% of LL -
Weight of Rack and 100% Top Shelf - Wa := Wd • N -H W|
Seismic Rack and 100% Top Shelf - Va := V,d + F|
Overturning Raci< and 100% Top Shelf - Ma := Vtd -he + Fphtop
Controlling Weight -
ConfroUing Shear -
ConfroUing Moment -
Tension Force on Column Anchor
per side of shelving unit
Wc := lf(W>Wa,W,Wa)
Vc:= if(V>Va,V.Va)
Mot:= if(M>Ma,M,Ma)
M:= Ma+ Mb= 1101.91ftlb
Wa= 317.441b
Va= 56.031b
Ma = 410.%ftlb
Wc= 887.441b
Vc= 156.631b
Mot= 1101.91ft lb
Shear Force on Column Anchor
Allowable Tension Force
Allowable Shear Force -
T:=
T:=
V:=
0.60
d 2
T = 174.53 lb
T = 174.53 lb
V= 78.311b
if(T<Olb,Olb,T)
Vc
2
USE: HILTI KWIK BOLT TZ ANCHOR (or equivalent) -
USE 3/8"<|> X 2" embed installed per the requirements of Hilti
Ta := 1006-lb For 2500psi Concrete
Va := 999 lb Per ASCE 13.4.2 p := 1.3
Combined Loading MUST BE I^S
THAN 1.00
Eclipse Engineering, Inc.
Consulting Engineers
MADEWELL #295
CARLSBAD, CA
11/11/2013
Rolf Armstrong, PE
STEEL ANTI-TIP CLIP AND ANTI-TIP TRACK DESIGN
Tension (Uplift) Force on each side - T = 174.51b
Connection fi-om Shelf to Carriage = 1/4" diameter bolt through 14 ga. steel:
Capacity of #12 screw (smaller tiian 1/4" diam. bolt) _ _ ..
in 16 ga. steel (tiiinner tiian 14 ga. posts and clips) - A: •- •
if (T < 2-Zc, "(2) 1/4" Bolts are Adequate", "No Good") = "(2) 1/4" Bolts are Adequate"
Use 3/16" Diameter anti-tip device for connection of carriage to frack
Yield Sfress of Angle Steel - Fy := 36- ksi
Thickness of Anti-tip Head - tg := 0.090- in
Widtii of Anti-tip Rod + Radius - br := 0.25-in
Widtii of Anti-tip Head-
Widtii of Anti-tip Flange -
Tension Force per Flange leg
Bending Moment on Leg -
Section Modulus of Leg -
Bending Sfress on Leg -
ba:= 0.490-in
ba-br
2
T| := 0.5 T
T|L^
M|:= —
baV
f.:=^
La = 0.12-in
T|= 87.271b
M|= 0.44ftlb
S| = 0.001-in^
fb = 7.92ksi
Ratio of Allowable Loads -
Widtii of Anti-Tip frack -
Thickness of Aluminum Track •
Spacing of Bolts -
Section Modulus of Track -
Design Moment on Track -
for continuous frack section
Bending Sfress on Track -
Allowable Sfress of Aluminum
Ratio of Allowable Loads -
0.75-Fv = 0.293
L:= 5.1 in
tt:= 0.33-in
Stb:= 22.5in
St:=
M:=
LV
6
T-Stb
8
f - ^
Fb := 21ksi
fbFb"^ = 0.2525
MUST BE LESS THAN 1.0
Average Thickness
St = 0.0926-in^
M = 40.91ft-lb
fb = 5.3-ksi
MUST BE LESS THAN 1.0
ANTI-TIP CLIP STEEL CONNECTION AND TRACK ARE ADEQUATE
Eclipse Engineering, Inc. MADEWELL #295 11/11/2013
Consulting Engineers CARLSBAD, CA Rolf Amistrong, PE
FIXED BEAM DESIGN: Double Rivet Low Profile Beam
Design criteria:
steel Yield Sfress - Fy = 36 ksi B^dty^^ E = 2.9 x lo'^-ksi
Widtii of _„ Deptii of ^
Rack- « = 3ft Rack- ^ = "ft
Uve Ijoad ^ti npr «:hPif := j-— = 16.6667 plf Uve Load on LL = 13.3333 psf persneir 2-max(w,d) Shelves-
Dead Load on DLmin(w,d) , ,^ Minimum Dist „
Shelves- ^d'^= i = 3.125-plf ^oaj Req'd- Wdi + w„ = 19.7917-plf
Wt)
Total Point Load @ Center - p := —i = 50 Ib 2 Moments for Each Load -
wti-max(w,d)^ Wdimax(w,d)^ rP-max(w,d)^
M„: = 14.844ft-lb Mp := + ^ ' ^ = 21.094ft-lb 12 12 y 8 y
Maximum Design Moment - M := max(Mp, M„) = 21.094ft-lb
Lateral Moment from Post - Mj = 29.8354ft-lb page 4 of original calcs
Shear fbr Wt|-max(w,d) Wdi max(w,d) p
Each Load - := ^ = 29.6875 Ib Vp := ^ + - = 29.6875 Ib
Maximum Design Shear - V := max(Vp, V„) = 29.6875 Ib
Allowable Shear Sfress - Fv := 0.4-Fy = 14.4-ksi
Allowable Bending Sfress - Fb := 0.66-Fy = 23.76-ksi
Section Properties: Double Rivet Low Profile Beam
A := 0.250-in^ S := 0.098-in^ I := 0.072-^^*
Actual Shear Sfress - Actual Bending Sfress -
V fy M -h Mc fb f := - = 0.119-ksi — = 0.008 OK fb := = 6.236-ksi — = 0.262 OK A Fv " S Fb
Deflections for Each -
4 4
Wti-max(w,d) Wdi-max(w,d)
A„ := = 0.003-in AD := +
384-EI " 384-E-I
P-max(w,d)''
i—= 0.006-in
192-E-I )
Total Load Deflection - A := max(Ap, Aw) = 0.006-in "'^^^"'^^ = 5656 OK
Double Rivet Low Profile Beam is Adequate
10
Eclipse Engineering, Inc.
Consulting Engineers
MADEWELL #295
CARLSBAD, CA
11/11/2013
Rolf Amistrong, PE
Connection from Steel Racks to Wall
Seismic Analysis Procedure per ASCE-7 Section 13.3.1:
Average Roof Height - hr = 20 ft
Height of Rack Attachments - Zb := z + ht = 10 ft At Top for fixed racks connected to walls
Seismic Base Shear Factor
Shear Factor Boundaries
Vt:=
0.4-ap-SDs C
1-H 2-
Seismic Coefficient -
Number of Shelves -
Weight per Shelf -
Total Weigfit on Rack -
Seismic Force at top and bottom
Connection at Top:
standard Stud Spacing -
Widtii of Rack-
Number of Connection Points -
on each rack
Force on each connection point -
Capacity per inch of embedment •
Required Embedment -
For Steel Sbids:
Vtmin := 0.3 SDs Ip
Vtmax := 1.6-SDsIp
Vt:= if(Vt>Vt„«x.V,n,ax,Vt)
Vt:=if(Vt<Vt„,in,Vtn,in,Vt)
Vt= 0.412
N= 10
Wtj= 100 Ib
WT:= 0.667-4-Pp
0.7VtWT
Tv:=
Sstud := 16 in
w = 3ft
C w
Nr := floor
Sstud,
]b
in Ws:= 135—
T20 := 84-lb
Vt= 0.412
Vtmin = 0.247
V,^ax= 1.318
Vt= 0.412
WT= 812.041b
117.041b
Nn=2
Fe= 58.521b
dc= 0.433-in
For #10 Screw - per Scafco Puilout Capacity in 20 ga
studs - per Scafco
MIN #10 SCREW ATTACHED TO EXISTING WALL STUD IS
ADEQUATE TO RESIST SEISMIC FORCES ON SHELVING UNITS.
EXPANSION BOLT IS ADEQUATE BY INSPECTION AT THE BASE
11
Eclipse Engineering, Inc. MADEWELL #295 11/11/2013
Consulting Engineers CARLSBAD.CA Rolf Armstrong, PE
Pipp Mobile STEEL STORAGE RACK DESIGN
2009 IBC & 2010 CBC - 2208 & ASCE 7-05 - 15.5.3
Design Vertical Steel Posts at Each Comer: pif := ib ft~ ^
Shelving Dimensions: psf:=ib ft"^
Total Height of Shelving Unit - ht := lO.OO-ft pcf := Ib-ft" ^
Widtii of Shelving Unit - w := 3.00-ft ksi := lOOO-lb in" ^
Deptii of Shelving Unit - d := 2.50-ft kips := lOOO Ib
Number of Shelves - N := 3
Vertical Shelf Spacing - S := 60.00-in
Shelving Loads:
Maximum Uve Load on each shelf is 150 Ibs:
Weight per shelf - Wti := 150- Ib Wq = 150 Ib
in psf- ,. ^fl ,, o«
LLj := LL = 20-psf
' w-d
Design Uve Load on Shelf - LL := LLj LL = 20 psf
Dead Load on Shelf - DL := 2.50-psf
Section Properties of Double Rivet 'L' Post:
Modulus of Basticity of Steel - E := 29000 ksi !"
h:= 1.5-in
Steel Yield Sfress - Fv := 33-ksi
y ry:=0.47-in
Section Modulus in x and y - Sx := 0.04-in^ TX := 0.47-in
Moment of Inertia in x and y - Ix := 0.06-in^ t := 0.075-in
Full Cross Sectional Area - Ap := 0.22-in^ ^'^
be:= 1.42-in
Lengtti of Unbraced Post - k := S = 60-in Ly := S = 60-in ^ := S = 60-in
Eflective Lengtii Factor - Kx := 1.0 Ky := 1.0 Kt:= 1.0
Section Properties Continued:
Density of Steel - psteel := 490- pcf
Weight of Post - Wp := psteel - Ap - ht Wp = 7.49- Ib
Vertical DLon Post- Pd := DL-w-.25d-N -H Wp Pj = 21.551b
Vertical U.on Post- P|:= LL-w-.25-d N P|= 112.51b
Total Vertical Load on Post - Pp := Pj -i- P| Pp = 134.05-lb
12
Eclipse Engineering, Inc.
Consulting Engineers
MADEWELL #295
CARLSBAD, CA
11/11/2013
Rolf Armstrong, PE
Floor Load Calculations
Weight of Mobile Carriage:
Total Load on Each Unit:
Area of Each Shelf Unit:
Floor Load under Shelf:
We := 901b
W := 4Pp + Wc
Au := W-d
W
PSF:^
Au
W = 626.191b
Au = 7.5ft^
PSF = 83 psf
NOTE: SHELVING LIVE LOAD IS CONSISTENT WITH 125 psf REQ'D FOR RETAIL FLOOR LOADING
Find the Seismic Load using Full Design Live Load :
ASCE-7 Seismic Design Procedure:
Importance Factor -
Determine Ss and Si from maps -
Determine the Site Class -
Determine Fg and Fv -
Determine S^g and S^i.
Determine S^g and S^i.
IE := 1.0
Ss:= 1.222
Class D
Fa:= 1.011
SMS:= Fa'Ss
SMS= 1.2354
SDS:= "^'^MS
SDS =0.824
Sfructural System - Section 15.5.3 ASCE-7:
4. Steel Storage Racks flo:=2
ap := 2.5
Total Vertical LL Load on Shelf -
Total Vertical DL Load on Shelf •
R := 4.0
Rp:=R
W| := LL-w-d
W
WH := DL-w-d -i- 4-— N
Seismic Analysis Procedure per ASCE-7 Section 13.3.1:
Average Roof Height -
Height of Rack Attachment -
hr := 20.0 ft
Seismic Base Shear Factor
z:= 0-ft
^0.4-ap-S.sr ^.I
Sl := 0.458
Fv := 1.542
SMI '•= FySi
SMI = 0.7062
SDI := "^SMI
SDI = 0.471
Cd := 3.5
Ip := 1.0
W|= 1501b
Wd = 28.731b
(O'-O" For Ground floor)
Vt= 0.206
Shear Factor Boundaries Vtmin := 0.3-SDS-Ip
Vtmax:= 1.6-SDsIp
Vt:= if(Vt>Vtn,ax,Vt„«x.Vt)
Vt:= if(Vt<Vt„,|n,Vt„„n,Vt)
Vtmin = 0.247
Vtmax= 1.318
Vt = 0.247
13
Eclipse Engineering, Inc.
Consulting Engineers
MADEWELL #295
CARLSBAD, CA
11/11/2013
Rolf Armstrong, PE
Seismic Loads Continued :
For ASD, Shear may be reduced
Seismic DL Base Shear -
DL Force per Shelf:
Seismic LL Base Shear -
LL Force per Shelf:
0.67 * LL Force per Shelf:
Vo := — = 0.176 " 1.4
Vtd:=Vp-WdN = 15.211b
Fd := Vp-Wd = 5.071b
Vt|:=VpW|N = 79.421b
F|:= Vp-W|= 26.471b
F|.67:= 0.67 Vp-W|= 17.741b
Force Distribution per ASCE-7 Section 15.5.3.3:
Operating Weight is one of Two Loading Conditions :
Condition #1: Each Shelf Loaded to 67% of Uve Weight
Cumulative Heights of Shelves -
Hi:= 0.0-S+ 1.0 S-H 2.0 S
H2-O H:=Hi+H2
Total Moment at Shelf Base - Mt:= H -Wd + H 0.67-W|
Vertical Disfribution Factors for Each Shelf -
Total Base Shear - Vtotai := Vtd + 0.67-Vti
Wd-O.O-S-H W| 0.67 0.0 S
H = 15ft
Mt= 1938.47 ft lb
C,:= Mt
Fi:= Ci-(Vtotai) = 0
= 0
Wd 2.0 S-H W| 0.67 2.0-S
C3:= = 0.667
Mt
F3:=C3-(V,„tal) = 45.621b
Cl -I- C2 + C3 = 1
Vtotai = 68.421b
Wd-1.0-S+W|0.67-1.0S
M;
F2:=C2(Vtotai) = 22.811b
= 0.333
Coefficients Should total 1.0
14
Eclipse Engineering. Inc. MADEWELL #295 11/11/2013
Consulting Engineers CARLSBAD, CA Rolf Amistrong, PE
Force Distribution Continued :
Condition #2: Top Shelf Only Loaded to 100% of Uve Weight
Total Moment at Base of Shelf - Mta := (N - 1) S-Wd + (N - 1) S W, = 1787ft lb
Total Base Shear - Vtotai2 := Vtd + F| Vtotai2 = 41.69 Ib
Wd-O.O-S-i-0-W|-0.0-S Wd-(N- l)-S-i-W| (N- 1)-S
Cia: = 0 Ctsa:= 1
Mta Mta
Fla := Cia (Vtotal2) = 0 C,sa (Vtotal2) = 41.691b
Condition #1 Confrols for Total Base Shear
By Inspection, Force Disfribution for intermediate shelves without LL are negligible.
Moment calculation fbr each column is based on total seismic base shear.
Column at center of rack is the worst case for this shelving rack system.
1 S
Column Design in Short Direction : ^s '= - - (Vtd + Vti) = 59.15ft-lb
Bending Sfress on Column - fbx:= Mj-Sx" ^ = 17.74-ksi
Allowable Bending Sfress - Fb .= 0.6-Fy = 19.8-ksi
Bending at tiie Base of Each Column is Adequate
Deflection of Shelving Bays - worst case is at tiie bottom bay
(Vtd + Vt,)s3 S A := -^^ — = 0.979 in — = 61.2888
12EIx A
At := A-(N - 1) = 1.9579-in Aa := 0.05-ht = 6-in
if (At < Aa, "Deflection is Adequate", "No Good") = "Deflection is Adequate"
Moment at Rivet Connection:
Shear on each rivet -
Mc ,
dr := 0.25in Vf := = 473.171b Ar := = 0.0491-in'^
' 1.5-in ' 4
Steel Sfress on Rivet - f^ = — = 9.64 ksi Vr
A,
Allowable Sfress on Rivet - Fyr := 0.4-80-ksi = 32-ksi
RIVET CONNECTION IS ADEQUATE FOR MOMENT CONNECTION FROM BEAM TO POST
15
Eclipse Engineering, Inc.
Consulting Engineers
MADEWELL #295
CARLSBAD, CA
11/11/2013
Rolf Amistrong, PE
Seismic Uplift on Shelves :
Seismic Vertical Component: Ev := 0.2-SDS (DL + LL) w-d Ey = 27.7974 Ib
Vertical Dead Load of Shelf: D := (DL + LL) -w-d D = 168.75 Ib
Note: since the shelf LL is used to generate ttie seismic uplift force, it may also be used to
calculate the net uplift load. For an empty shelf, only ttie DL would be used, but the ratio
of seismic uplift will be the same.
Net Uplift Load on Shelf: Fu := Ev - 0.6-D Fu = -73.4526 Ib
Note: This uplift load is for tiie full shelf. Each shelf will be connected at each corner.
Number of Shelf Connections:
Uplift Force per Corner:
Nc := 4
Fuc-Fuc =-18.36311b
NOTE: Since the uplift force is negative, a mechanical connection is not required.
16
Eclipse Engineering, Inc.
Consulting Engineers
MADEWELL #295
CARLSBAD, CA
11/11/2013
Rolf Amistrong, PE
Find Allowable Axial Load for Column :
Allowable Buckling Sfresses -
Kxi-x^
= 17.56-ksi CTexCTex.x = 17.56-ksi
V '•x J
Distance from Shear Center
to CL of Web via X-axis
thc^bc^
4Ix
Distance From CL Web to Cenfroid - Xc := 0.649-in - 0.5-t
Distance From Shear Center XQ := Xc + ec
to Cenfroid -
Polar Radius of Gyration
Torsion Constant -
Warping Constant -
Shear Modulus -
r~2 2 2
To-'y/rx +ry +Xo
J:=^-(2-b-t3 + h-t^) 3 ^ '
t-b^ h^ f 3 b-t-H2-h-t^
~ 12 V 6-b-t-i-h-t
G := 11300 ksi
ec= 1.2706-in
Xc = 0.6115-in
Xo= 1.8821-in
ro= 1.996-in
J = 0.00063-in''
Cw= 0.0339 in^
(Tt:=
Ap-rg
G J + TT^-E Cw
CTt= 11.2335-ksi
P:= 1-3= 0.1109
Fet := [(o-ex + o^t) " >/('^ex + o^t)^ - 4-p-(Tex-(Tt] 2-3
Elastic Flexural Buckling Sfress
Allowable Compressive Sfress
Fe := if (Fet < ^ex. Fet. '''ex)
Fn := if
Factor of Safety for Axial Comp. - := i,92
Fe > —, Fv e 2 ' y 1-
4Fe .Fe
Fet = 7.0423-ksi
Fe= 7.0423-ksi
Fn = 7.0423 ksi
17
Eclipse Engineering, Inc.
Consulting Engineers
MADEWELL #295
CARLSBAD, CA
11/11/2013
Rolf Armstrong, PE
Find Effective Area -
Determine ttie Effective Widtii of Flange
Flat width of Flange -
Flange Plate Buckling Coefficient -
Flange Slenderness Factor -
Wf := b - 0.5-t
kf := 0.43
1.052 Wf [F^
0.22\ 1
Wf = 1.4625 in
Xf = 0.4875
Pf = 1.1256
Effective Flange Width -
Determine Effective Width of Web
Flat widtii of Web-
Web Plate Buckling Coefficient -
Web Slenderness Factor -
{ Xf j Xf
be:= if(Xf> 0.673, pfWf.Wf) be= 1.4625in
Ww := h - t
kw:= 0.43
_ 1.052 Ww pii"
Xw
Ww= 1.425-in
Xw = 0.475
Pw= 1.1302
-Vw
Eflective Web Widtii -
Effective Column Area -
Nominal Column Capacity -
Allowable Column Capacity -
Check Combined Stresses
he := if(Xw > 0.673, Pw-Ww, Ww) hg = 1.425-
Ae := t(he + bg)
Pn := Ag-Fn
in
Ae= 0.2166-in''
Pn = 15251b
Pa = 7941b
TT^E-L
(KX-L*)^
Pcrx= 4770.31 lb
Pcr:=Pa
Magnification Factor
Combined Sfress:
Pcr= 4770.311b
a:= 1-
\ Par J
a =0.946 Cm := 0.85
» 0.974 MUST BE L£SS THAN 1.0
Pa iPb«*
Final Design: 'L' POSTS WITH BEAM BRACKET ARE ADEQUATE FOR
REQD COMBINED AXIAL AND BENDING LOADS
NOTE: Pp is the total vertical load on post, not 67% live load, so the design is conservative
18
Eclipse Engineering, Inc.
Consulting Engineers
MADEWELL #295
CARLSBAD, CA
11/11/2013
Rolf Armstrong, PE
STEEL STORAGE RACK DESIGN - cont'd
Ht:= ht= 10ft
d= 2.5ft
N = 3
htop -•= Ht
Find Overturning Forces
Total Height of Shelving Unit -
Deptii of Shelving Unit -
Number of Shelves -
Height to Top Shelf Center of G -
Height to Shelf Center of G -
From Vertical Disfribution of Seismic Force previously calculated
ConfroUing Load Cases -
Weight of Rack and 67% of LL -
Seismic Rack and 67% of LL -
Ma:= F1-O.O-S+ F2-l.O-SH-F3-2.O-S
Mb :=0
Overturning Rack and 67% of LL -
Weight of Rack and 100% Top Shelf
Seismic Rack and 100% Top Shelf -
Widtii of Shelving Unit - w = 3ft
WORST CASE
Vertical Shelf Spacing - S = 60-in
htop = 10ft
he = 10-ft
W:= (Wd + 0.67 W|)-N
V := Vtd + 0.67-Vti
Wa := Wd-N-H W|
Va:=Vtd+F|
Overturning Rack and 100% Top Shelf - Ma := Vtd-hc + F|-htop
ConfroUing Weight -
ConfroUing Shear -
ConfroUing Moment -
Tension Force on Column Anchor
per side of shelving unit
Shear Force on Column Anchor -
Wc:= if(W>Wa,W,Wa)
Ve:= if(V>Va,V,Va)
Mot:=if(M>Ma,M,Ma)
Mot Wc T:= 0.60 d 2
T:= if(T<Olb,Olb,T)
2
W = 387.691b
V= 68.421b
M:= MaMb = 570.21 ft-lb
Wa= 236.191b
Va= 41.691b
Ma = 416.86 ft-lb
Wc = 387.691b
Vc = 68.421b
Mot = 570.21 ft-lb
T= 111.771b
T= 111.771b
V= 34.211b
USE: HILTI KWIK BOLT TZ ANCHOR (or equivalent) -
USE 3/8"(|> X 2" embed installed per the requirements of Hilti
Allowable Tension Force - Ta:= 1006-lb For 2500psi Concrete
Allowable Shear Force - V;. := 999-lb Per ASCE 13.4.2 p := 1.3
Combined Loading
Va := 999-lb
p.V = 0.189 MUST BE 1^
THAN 1.00
19
Eclipse Engineering, Inc.
Consulting Engineers
MADEWELL #295
CARLSBAD, CA
11/11/2013
Rolf Armstrong, PE
STEEL ANTI-TIP CLIP AND ANTI-TIP TRACK DESIGN
Tension (Uplift) Force on each side - T = 111.81b
Connection ft-om Shelf to Carriage = 1/4" diameter bolt ttirough 14 ga. steel:
Capacity of #12 screw (smaller than 1/4" diam. bolt) _ ..
in 16 ga. steel (thinner than 14 ga. posts and dips) - A: -- •
if(T < 2-Zc, "(2) 1/4" Bolts are Adequate", "No Good") = "(2) 1/4" Bolts are Adequate"
Use 3/16" Diameter anti-tip device for connection of carriage to frack
Yield Sfress of Angle Steel - Fy := 36-ksi
Thickness of Anti-tip Head - tg := 0.090-in
br:= 0.25-in Widtti of Anti-tip Rod + Radius
Widtii of Anti-tip Head-
Widtii of Anti-tip Flange -
Tension Force per Flange leg -
Bending Moment on Leg -
Section Modulus of Leg -
Bending Sfress on Leg -
Ratio of Allowable Loads -
Width of Anti-Tip frack -
Thickness of Aluminum Track -
Spacing of Bolts -
Section Modulus of Track -
Design Moment on Track -
for continuous frack section
Bending Sfress on Track -
Allowable Sfress of Aluminum
Ratio of Allowable Loads -
0.490-in
ba-br
T| := 0.5 T
TrU
2
2
M,:=
S|:= baV
f • ^
0.75-Fv = 0.188
L:= 5.1-in
tt:= 0.33-in
Stb := 22.5-in
St:=
M:=
6
T-Stb
8
f - !^
Fb:= 21-ksi
fbFb"^ = 0.1617
L^= 0.12-in
T|= 55.891b
M| = 0.28-ft-lb
S| = 0.001-in-^
fb = 5.07-ksi
MUST BE l£SS THAN 1.0
Average Thickness
St = 0.0926-in^
M = 26.2ftlb
fb = 3.4-ksi
MUST BE LESS THAN 1.0
ANTI-TIP CLIP STEEL CONNECTION AND TRACK ARE ADEQUATE
20
Eclipse Engineering, Inc.
Consulting Engineers
MADEWELL #295
CARLSBAD, CA
11/11/2013
Rolf Armstrong, PE
FIXED BEAM DESIGN: Double Hanger Bar Beam
Design criteria:
y
w = 3ft
Steel Yield Sfress - Fv = 36-ksi Modulus of
Elasticity -
Widtii of
Rack-
Depth of
Rack-
Uve Load
per shelf -
Dead Load on
Shelves -
W|| :=
2-max(w,d)
Wdl := 0.80-plf
E= 2.9x 10^-ksi
d = 2.5ft
LL= 20-psf
Wa := Wdl + W|| = 25.8-plf
Point Loads on Beam -
Moments for Each Load
v2
Mw:=
Wti-max(w,d)
8 = 29.025 ft-lb
Maximum Design Moment -
= 25 plf Uve Load on
Shelves -
Minimum Dist
Load Req'd -
Wq
P:= —= 75lb 2
Wdi-max(w,d) fp.max(w,d)^, Mp := -I-1 ^ I = 57.15ft-lb
M:= max(Mp,Mw) = 57.15ftlb
Shear for Each
Load -
Maximum Design
Shear-
Vw:=
wtimax(w,d)
= 38.71b
Allowable Shear
Sfress -
Wdi-max(w,d) p
Vp := + - = 38.71b
^ 2 2
Allowable Bending
Sfress -
V := max(Vp, Vw) = 38.71b Fv := 0.4-Fy = 14.4-ksi Fb := 0.66-Fy = 23.76 ksi
Section Properties: Hanger Bar Beam
.3 A:= 0.233 in^
Actual Shear Sfress -
S:= 0.066-in
Acbjal Bending Sfress
I:= 0.041-in'*
V fy fv := - = 0.166-ksi — = 0.012 OK
Deflections for Each
Aw:=
5-Wt|-max(w,d)
= 0.04 in Ap:=
M fb fb := — = 10.391-ksi — = 0.437 S Fb
5wdimax(w,d)'' f p.max(w,d)^'
OK
384-E-I " 384 E-I
Total Load Deflection - A := max(Ap, Aw) = 0.063-in
V 48-E-I
max(w, d)
0.063-in
= 576 OK
Hanger Bar Beam is Adequate
21
Eclipse Engineering, Inc. MADEWELL #295 11/11/2013
Consulting Engineers CARLSBAD, CA Rolf Armstrong, PE
FIXED BEAM DESIGN: Double Rivet Std. Profile Beam
Design criteria:
steel Yield Sfress - Fy = 36 ksi El^dtyE = 2.9 x lo"* - ksi
Widtti of Deptii of . _ Rack- ^ = 3ft Rgj.,^. d = 2.5ft
Total U)ad Pj, := v = 38.7ft plf Uve Load on LL=20 psf
P®"^ ^^"^ • Shelves -
Dead Load on DLmax(w,d) Distance ft-om End min(w,d)
Shelves- ^<"== i 3.75.Plf of Shelf to Point ^f- i = ^-^^ft
Load -
Wdimin(w,d)^ TPu-ati^
Total Moments - M: -i- = 18.078ft-lb 12 { 2 )
Lateral Moment ft-om Post - Mg = 59.1462 ft - Ib page 4 of original calcs
Wdi-min(w,d) 2-Pti
Total Shear - V := + = 43.3875 Ib
2 2
Allowable Shear Sfress - Allowable Bending Sfress -
Fv= 14.4-ksi Fb = 23.76-ksi
Section Properties: Double Rivet Standard Profile Beam
A := 0.264 in^ S := 0.126-in^ I := 0.211 in^
Actual Shear Sfress - Actual Bending Sfress -
fv:=^ = 0.164-ksi ^ = 0.011 OK ^ !!U!!f ^ 7.355.^, 1^0.31 OK
" S Fb
Total Load Deflection
4
Wdimin(w,d)
A:= -I-
384-EI
Pti-ati-[3-(min(w,d)^)-4-ati^]
96 -E I
= 0.002-in ^^^^^ = 18484 OK
Double Rivet Standard Profile Beam is Adequate
22
ECLIPSE ENGINEERING INC. MADEVVELL#295 11/11/2013
CONSULTING ENGINEERS CARLSBAD, CA NICK BURNAM, PE
Conterminous 48 States
2009 International Building Code
Latitude = 33.071745
Longitude = -117.265227
Spectral Response Accelerations Ss and SI
Ss and 81 = Mapped Spectral Acceleration Values
Site Class B - Fa = 1.0 ,Fv = 1.0
Data are based on a 0.01 deg grid spacing
Period Sa
(sec) (g)
0.2 1.222 (Ss, Site Class B)
1.0 0.458 (SI, Site Class B)
Contemiinous 48 States
2009 Intemational Building Code
Latitude = 33.071745
Longitude = -117.265227
Spectral Response Accelerations SMs and SMI
SMs = Fa X Ss and SMI = Fv x SI
Site Class D - Fa = 1.011 ,Fv = 1.542
Period Sa
(sec) (g)
0.2 1.236 (SMs, Site Class D)
1.0 0.707 (SM1, Site Class D)
Conterminous 48 States
2009 Intemational Building Code
Latitude = 33.071745
Longitude = -117.265227
Design Spectral Response Accelerations SDs and SDI
SDs = 2/3 X SMs and SD1 = 2/3 x SMI
Site Class D - Fa = 1.011 ,Fv = 1.542
Period Sa
(sec) (g)
0.2 0.824 (SDs, Site Class D)
ECLIPSE ENGINEERING INC.
CONSULTING ENGINEERS
MADEWELL #295
CARLSBAD, CA
11/11/2013
NICK BURNAM. PE
Fasteners (Screws and Wglds) iSlsmFm
Screw Table Notes
1. Scmw pacing and edge distence shtall m be less tiian 3 x D. (D = Nominal sGnew diamnier}
2. Tti8i|llow8*te screw values are basod tw flw a^
E4.
3. Whert cormecHng materials of dmarant metal tiiicknesses or ^ strenp^, the lowest applimtile values i^ould be
4. The nominal strengtii of the screw must be at least 3.75 times ttie alkȴabte loads.
5. Vahiss indude a 3.0 factor of ^fety.
6. Ap|30«l loads may be multiplied by 0.7S for sej«mtic or wind leading, per AISI A 5.1.3.
7. Pwiiatretlon of soews ttirough joined mmW» shOMkJ not be less than 3 Sixffflsed ttireadS- Screw® should be
installesd and tightened in accofdantie vMi mm manufa<^rer*s recommehdafions.
Allowable Loads Screw Connections (lbs/screw)
1.
2.
3.
4.
5.
6.
Weld Table Notes
m{mMB» tms0 AiSi, section EE
When dinnecting itiliteriptB of diffBrent m^l tttickti^ or tensile slm^ (Fu), lhe lowe^ applicable vialu^
should be lised.
Valu% In^ucte a 2.5 Isictor of safety.
Based Oh tttH minimum allowance load for flilet or flare groove wdds, l^gMnal or transvarm loacte.
Allo)Ma^;Meili b^siid on E6(hoi etodraies
For matiftate* than areqiwrtto .1t4a*lWck, drawirigs i^Wwnomlhal weW sim For sut* material, ttie effeoi^
tiiroatof^e wdld shidlniot .be 1^ ttian U» thickness of ttie ttilnne^ connected part.
Allowable Loads For Fillet Welds And Flare Groove Welds
0
43
54 04066
33 46
33 46 764
66 ^ Jlffiff'* 13 46.
*' .lh-.'' -'46.
. 4 i' 663
r; 1373 118 0.1242 33 45 1677
54 0^1666
68 OJ0713
SQ es
60 BS
1104
1390
97 0.1017 •
118 o.'iswa
do 65
SO 65
> 1983
2422
48
ECLIPSE ENGINEERING INC.
CONSULTING ENGINEERS
MADEWELL #295
CARLSBAD, CA
11/11/2013
NICK BURNAM, PE
Page 11 of 14 ESR-1917
TABLE 9—KB-TZ CARBON AND STAINLESS STEEL ALLOWABLE SEISMIC TENSION (ASD), NORMAL-WBGHT
CRACKED CONCRETE. CONOmON B (pounds)^-^'
Nominal
Anchor
Diameter
Embedment
Depth hri
(In.)
Conorete Compraastve Strength'
Nominal
Anchor
Diameter
Embedment
Depth hri
(In.)
rcs2.500psl fc s 3,000 psI rcc 4,000 psi fc B 6,000 pel Nominal
Anchor
Diameter
Embedment
Depth hri
(In.) Cariian
steel
Stainless
steel
Carbon
steel
Stainless
eteel
Carbon
stael
stainless
steel
Caibon
steel
Stainless
steel
3^ 2 1,006 1,037 1,102 1,136 1,273 1,312 1,559 1,607
1/2 2 1,065 1,212 1,167 1,328 1,348 1,533 1.651 1,878 1/2 31/4 2,178 2,207 2.386 2,418 2.755 2.792 3.375 3.419
5/8 31/B 2,081 2,081 2,280 2.280 2,632 2,632 3.224 3,224 5/8 4 3,014 2,588 3.301 2.83S 3.812 3,274 4.669 4,010
3/4 3 3/4 2,736 3,594 2,997 3,937 3,460 4,546 4,238 5,568 3/4 4 3/4 3,900 3,900 4,272 4,272 4,933 4,933 6,042 6,042
For SI: 11bf» 4.45 N, 1 psi = 0.00689 MPa For pound-Inch units: 1 mm » 0.03937 inches
Values are for single anchors «Ah no edge dislance or spacing reduction. For other cases, calculation of Rd as per ACI 318-05 and conversion
to ASD In accordance wMi Section 4.2.1 Eq. (5) is required.
Values are for normal weight concrete. FOrsand-tlghtwelght concrete, multiply values by 0.60.
^Condition B applies where supplementary reinforeement in conformance with AQI318-05 Section D.4.4 is not provided, or where puilout or
pryout strengtti govems. FOr cases where the presence of supplementary relnfoicement can be verified, the strength reduction factors
assodated witti Condlflon A may bs used.
TABLE 10—KB-TZ CARBON AND STAINLESS
STEEL ALLOWABLE SEISMIC SHEAR LOAD (ASD),
(pounds^
Nomlnel
Anchor
Diameter
Allowable Sted Capacity, Seismic Sheer Nomlnel
Anchor
Diameter Carbon Steel Stainless Steel
3/8 999 1,252
1/2 2,639 3,049
6/8 4,678 5,245
3/4 6,313 6,477
Values are for singla anchors wth no edge distance or
spacing reduction due to concrete falure.
^ CD
W W l-» O tfl
(O ISS
w
>
o m
o
o
ST n
a p
2
-<
El
3
SI
•