HomeMy WebLinkAbout1923 Calle Barcelona; 147; CBC2017-0411; PermitPrint Date: 12/08/2017
Job Address:
Permit Type:
Parcel No:
Valuation:
Occupancy Group:
# Dwelling Units:
Bedrooms:
Project Title:
1923 Calle Barcelona, 147
BLDG-Commercial
2550120400
$47,021.61
City of Carlsbad
1635 Faraday Av Carlsbad, CA 92008
Commercial Permit
www.carlsbadca.gov
Work Class: Tenant Improvement
Lot#:
Reference #:
Construction Type:
Bathrooms:
Orig. Plan Check #:
Plan Check#:
Description: EVERYTHING BUT WATER: 1,011 SF T.I. RETAIL TO RETAIL
Owner:
T-C FORUM AT CARLSBAD LLC
4675 Macarthur Ct Tiaa-Cref, 110
NEWPORT BEACH, CA 92660
BUILDING PERMIT FEE ($2000+)
BUILDING PLAN CHECK FEE (BLDG)
ELECTRICAL BLDG COMMERCIAL NEW/ADDITION/REMODEL
MANUAL BUILDING PLAN CHECK FEE
MECHANICAL BLDG COMMERCIAL NEW/ADDITION/REMODEL
PLUMBING BLDG COMMERCIAL NEW/ADDITION/REMODEL
581473 GREEN BUILDING STATE STANDARDS FEE
STRONG MOTION-COMMERCIAL
Total Fees: $834.63 Total Payments To Date: $834.63
Status:
Applied:
Issued:
Fina led:
Inspector:
Balance Due:
Please take NOTICE that approval of your project includes the "Imposition" of fees, dedications, reservations, or other exactions hereafter
collectively referred to as "fees/exaction." You have 90 days from the date this permit was issued to protest imposition of these
fees/exactions. If you protest them, you must follow the protest procedures set forth in Government Code Section 66020(a), and file the
protest and any other required information with the City Manager for processing in accordance with Carlsbad Municipal Code Section
3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack, review, set aside, void, or annul their
imposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection
fees and capacity changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this
project. NOR DOES IT APPLY to any fees/exactions of which you have previously been given a NOTICE similar to this, or as to which the
statute of limitation has previously otherwise expired.
Permit No: CBC2017-0411
Closed -Finaled
08/01/2017
10/10/2017
TFraz
$0.00
$393.20
$266.28
$43.00
$8.98
$45.00
$63.00
$2.00
$13.17
THE FOLLOWING APPROVALS REQUIRED PRIOR TO PERMIT ISSUANCE: 0PLANNING 0ENGINEERING 0BUILD1NG OFIRE OHEALTH OHAZMAT/APCD
. C cityof
Carlsbad
Building Permit Application 1-P_la_n_C_h_e_ck_No_.~,......_~..L..;_.;_~µ-+-
1635 Faraday Ave., Carlsbad, CA 92008 Est. Value
Ph: 760-602-2719 Fax: 760-602-8558 1---------.::!~--L:-i-.1..~~-¥-~+-=
email: building@carlsbadca.gov
www.carlsbadca.gov Date
JOB ADDRESS \ (\ 2,.. ~ IIIIIJI/SPACH/UNITII 14 1
CT/P JE 11 II BATHROOM
PATIOS(SF) DECKS (SF) AIR CONDITIONING FIRE SPRINKLERS FIREPLACE
YES[]#. N<O vES ONoO vESO NoO
DESIGN PROFESSIONAL ~ ~'<C..: CONTRACTOR BUS. NAME -\ L f!..cµ~
ADDRESS \2_j ~s+ '2.Lf
CITY Zif LOO\\
PHONE FAX '2 \ 1.. 61 '5 . '2.'2. Be;
EMAIL
Worilen' Compensation Decllfltion: I hereby aff,m under penalty of perjury one of the following declarations: D I have and will rnaintlin a certificate of consent to self-Insure for workers' compensation as provided by Sec1ion 3700 of the Labor Code, for lhe performance of the work for which this permit is issued.
D I have and will rnalntlin worilers' CO\J11>8nlation, as reQuired by Section 3700 of the Labor Code. for the performance of the wOII( for whr this pennft is issued. My wori<ers' compensation i7r'ill1~µ and policy
number are: Insurance CO. C 1 ~ Policy No., {I'/ }CO Expiration Date J 2-1-'9-
~seclion need not be completed WIile permit is for one hundred dollars ($100) or less. LJ Certificate of Exemption: I certify that in the performance of the worlt for which this permft is issued, I shall not employ 'ill1Y person in any manner so as to become subject to the W0111ers' Compensation Laws of
California. WARNING: Failure to secure workers' compensation coverage Is unlawful, and shall subject an employer to criminal penalties and civil fines up to one hundred thousand dollars (&100,000), In
addition to the cost of compensation, daT ~vi for '.n~'?:13f6 of the Labor ~terest and attorney's fees .
.8$ CONTRACTOR SIGNATURE 'f.7"'" ~ ~
I hereby aff,m that I am exempt from Contractors License Law for the following reason: D I, as owner of the property or my employees wfth wages as their sole compensation, will do the wOl1I and the structure is not intended or offered for sale (Sec. 7044, Business and Professions Code: The COntractor's
License Law does not apply to an owner of property who builds or improves thereon, 'iJlld who does such worlt himseW or through his own employees, provided that such improvements are not intended or offered for
sale. If, however. the building or improvement is sold within one year of completion. the owner-builder will have the burden of proving that he did not build or i111>rove for the purpose of sale). D I, as owner of the property, am exclusively contra:Ung with licensed contr.K:tors to construct the project (Sec. 7044, Business 'iJi1d Professions Code: The COntra:tor's License Law does not apply to an owner of
property who buikls or improves thereon, and contracts for such projects with contractor(s) licensed pursuant to the COntractor's License Law).
D I am exempt under Section Business and Professions Code for this reason:
1. I personally plan to provide the major labor 'iJi1d materials for construction of the proposed property improvement. D Y es O o
2. I (have I have not) signed an application for a Mding permft for the proposed worlt.
3. I have controcted with the following person (firm) to provide the proposed construction (include name address I phone I contractors' license number):
4. I pl'iJll to provide portions of the work, but I have hired the following person to coordinate, supervise and provide the major work (include name I address I phone I contractors' license number):
5. I wiU provide some of the work, but I have controcted (hired) the following persons to provide the worlt indicated ~nclude name I address I phone I type of worlt):
.a5 PROPERTY OWNER SIGNATURE 0AGENT DATE
Is lhe awllcanl or lu\lire bo.ild ng OOCt/panl required lo submlt a business plan, ac\Jlcly hazcrdoos materi,ts regtsua!ion form or rlslt man.igerrenl and prevcnfion program under Secbls 25505, 25533 or 25534 ol the
l'lcsley-TaMer liazatcbus Substarce Accounl AGI? Yes No
Is Iha epp.icanl 01 lutu;e bu'ding occupanl rcqu<Jlld to obtain a permit r,om the air pol'.UIJon con~ol d!sll'rc1 or air qua'Jty management cjslricl? Yes No
Is Ole facility to bo ccnslructed wilh!n 1,000 feet of the ou:er boundary o/ a school site? Yes No
IF Am OF THE ANSWERS ARE YES, A FINAL CERTIF1CATE OF OCCUPANCY MAY NOT~ ISSUED UNLESS TltE APPLICANT HAS MEl O.~ IS MEEltNG TIIE REOOtREIAENTS OF THE OFFICE OF
EMERGENCY ~RVICES A!.D TIIE AIR POU.UTION CONTROL DiSTRICT.
I Cl3f1lfy that 11\a-.o road lho illlPllcatlon end state that the abo'ielnlonnationiscotreetond tl'at lllelnlomlation en t!ic pl.:ins Is oa:uratc. I agree to Q?mplyl'.ith all Cll)'Olt'inances and Slate laws relating to bulldlngconstM:tiOO.
I heretly au1JoriZ9 reinsentative of tho a:y of Carlsbad lo Clllerupoo lhe alx>Yo mentioned proi;erty i:lr lnspectai pullXlSl!S. I AL.SO AGREE TO SAVE, NDEMNL::Y /.ND KEEP HARMLESS THE CrTY OF CARLSBAD
' AOOIST ALL L.IAl31LfTIES. JUDGMENTS, COSTS Ai'O EXPENSES WHICH MAY IN Affr WAY ACCRUE AG.AJNST SAID CITY IN CONSEQUENCE OF THE GRANTlNG OF THIS PERMIT
OSHA: An OSHA pemil ls lll(JJ~'OO i:w"excavaL'onscwr SfJ deep anddem:llliJn or<Xll\Slrudiono/structlleSovoc Jstorics il hci;ht .
EXPlRA TION: ~,y pennl MUed by L'lO eu~:ng Oli::ia! ul'lOO' lhe ~ens or l1is Code sha1 exiiJe 11)' r.nlcafDn cm txxx:rre ~ .m ';!lid ~ tr.o bul1.og or v.ak aulhorilf.'d by sucti p;nrit s not canmenced v.ihii
100days tom Iha da'.ocl sud1 pcm,iorrt thebula:ngorv.ak auihori21:d 11)' such JBTllil is s~or ati.r1d:looo at arff tine after Ille \\Qi\( is ClllTVTlerced for a peoodol 100days (Sediln 100.4.4 Un·oon 9Jl:ling Code).
Ji5 APPLICANT'S SIGNATURE DATE
STOP: THIS SECTION NOT REQUIRED FOR BUILDING PERMIT ISSUANCE.
Complete the following ONLY if a Certificate of Occupancy will be requested at final inspection.
C E R T I F O C A T I:: 0 6' 0 C C U P A N C V I C O m n, c r c I ii I I' r O J C C t S O 11 I lf J
Fax (760) 602-8560. Email building@carlsbadca.gov or Mail the completed lorm to City ol Carlsbad, Building Division 1635 Faraday Avenuo, Carlsbad, Cafilornia 92008.
DELIVERY OPTIONS
PICK UP: CONTACT {Listed above)
CONTRACTOR (On PC:. 1)
CONTACT (Listed above)
CONTRACTOR (On P/!-l l
MAIL/ FAX TO OTHER:----
,65 APPLICANT'S SIGNATURE
OCCUPANT (Listed above)
OCCUPANT (Listed above)
CO#: (Olllce U1e Only)
occ PANT NAME JOH rv rv WA s 1.tvl-·
Cm' STATE ZIP
Carlsbad CA C, 3. 0 0
OCCUPANT'S BUS. LIC. No.
ASSOCIATEDCB# Cf3C,.:2_or7-o'fll
NO CHANGE IN USE/ NO CONSTRUCTION
CHANGE OF USE / NO CONSTRUCTION
DATE
PERMIT INSPECTION HISTORY REPORT (CBC2017-0411)
Permit Type: BLDG-Commercial Application Date: 08/01/2017 Owner:
Work Class: Tenant Improvement Issue Dato: 10/10/2017 Subdivision:
Status: Closed -Finaled Expiration Date: 06/04/2018 Address:
IVR Number: 5389
Actual Scheduled
Date Start Date Inspection Type Inspection No. Inspection Status Primary Inspector
12/08/2017 12/08/2017
December 08, 2017
BLDG-Fina I
Inspection
Checklist Item
BLDG-Building Deficiency
BLDG-Plumbing Final
BLDG-Mechanical Final
BLDG-Structural Final
BLDG-Electrical Final
042813-2017
Checklist Item
BLDG-Building Deficiency
BLDG-Plumbing Final
BLDG-Mechanical Final
BLDG-Structural Final
BLDG-Electrical Final
COMMENTS
Waiting for Fire Final Inspection
Passed Tlm Frazee
COMMENTS
Waiting for Fire Final Inspection
T-C FORUM AT CARLSBAD LLC
CARLSBAD TCT#92-08 GREEN
VALLEY
1923 Calle Barcelona , 147
Carlsbad, CA 92009-8458
Reinspection Complete
Passed
No
No
No
No
No
Complete
Passed
Yes
Yes
Yes
Yes
Yes
Page 2 of 2
" ' ;, ~ ~ .
, ~ERMIT,INSPECTION HISTORY REPORT (CBC2017-0411)
Permit Type: BLDG-Commercial Application Date: 08/01/2017 Owner: T-C FORUM AT CARLSBAD LLC
Work Class: Tenant Improvement Issue Date: 10/10/2017 Subdivision: CARLSBAD TCT#92-08 GREEN
VALLEY
Status: Closed -Finaled Expiration Date: 06/04/2018 Address: 1923 Calle Barcelona, 147
Carlsbad, CA 92009-8458
IVR Number: 5389
Scheduled Actual Inspection Status Primary Inspector Complete
Date Start Date Inspection Type Inspection No. Reinspection
11/06/2017 11/06/2017 BLDG-81 039648-2017 Passed Tim Frazee Complete
Underground
Combo(11,12,21,31)
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Yes
BLDG-21 Yes
Underground-Underfloor
Plumbing
BLDG-84 Rough 039649-2017 Partial Pass Tim Frazee Reinspection Incomplete
Combo(14,24,34,44)
Checklist Item COMMENTS Passed
BLDG-14 Yes
Frame-Steel-Bolting-Welding
(Decks)
BLDG-24 Rough-Topout Underground OK, not finished top out yet No
BLDG-34 Rough Electrical Yes
BLDG-44 Yes
Rough-Ducts-Dampers
11/07/2017 11/07/2017 BLDG-24 039759-2017 Passed Tim Frazee Complete
Rough/Topout
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Yes
11/14/2017 11/14/2017 BLDG-82 Drywall, 040274-2017 Passed Tim Frazee Complete
Exterior Lath, Gas
Test, Hot Mop
Checklist Item COMMENTS Passed
BLDG-1 7 Interior Lath-Drywall Yes
11/17/2017 11/17/2017 BLDG-17 Interior 040793-2017 Passed Tim Frazee Complete
Lath/Drywall
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Yes
12/05/2017 12/05/2017 BLDG-49 042268-2017 Passed Tim Frazee Complete
Mechanical Final
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Yes
BLDG-Final 042301-2017 Failed Tim Frazee Reinspection Complete
Inspection
December 08, 2017 Page 1 of 2
EsGil Corporation
In iPartnersli.ip witfi. government for (}Jui{aing Safety
DATE: 9/11/17
JURISDICTION: City of Carlsbad
PLAN CHECK NO.: CBC2017-0411 SET: II
PROJECT ADDRESS: 1923 Calle Barcelona Suite 147
PROJECT NAME: Everything But Water -TI
D APPLICANT
~URIS.
D PLAN REVIEWER
D FILE
cg] The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's
codes when minor deficiencies identified below are resolved and checked by building
department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
D The check list transmitted herewith is for your information. The plans are being held at EsGil
Corporation until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
D The applicant's copy of the check list has been sent to:
cg] EsGil Corporation staff did not advise the applicant that the plan check has been completed.
D EsGil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Telephone#:
Date contacted: 4,-(by: "ivf Email:
Mail Telephone Fax In Person
D REMARKS:
By: Morteza Beheshti Enclosures:
EsGil Corporation
0 GA D EJ D MB D PC 8/31
9320 Chesapeake Drive, Suite 208 + San Diego, California 92123 + (858) 560-1468 + Fax (858) 560-1576
EsGil Corporation
In (}'artnersliip wit Ii (jovernment for (}Juiftfing Safety
DATE: 8/14/17
JURISDICTION: City of Carlsbad
PLAN CHECK NO.: CBC2017-0411 SET: I
PROJECT ADDRESS: 1923 Calle Barcelona Suite 147
PROJECT NAME: Everything But Water -TI
q,..,APPLICANT
...0 JURIS.
CJ PLAN REVIEWER
CJ FILE
D The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's
codes when minor deficiencies identified below are resolved and checked by building
department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
~ The check list transmitted herewith is for your information. The plans are being held at EsGil
Corporation until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
D The applicant's copy of the check list has been sent to:
D EsGil Corporation staff did not advise the applicant that the plan check has been completed.
~ EsGil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Permit Resources/ Mary Ryan Telephone#: 949-582-3735
))ate contacted: 0/ ( 4-(by:~ Email: mary@permitresources.com
~ail ~gleph~ Fax In Person
D ~~'f\"-,,
REMAR :
By: Doug Moody
EsGil Corporation
D GA D EJ D MB D PC
Enclosures:
8/3/17
9320 Chesapeake Drive, Suite 208 + San Diego, California 92123 + (858) 560-1468 + Fax (858) 560-1576
City of Carlsbad CBC2017-0411
's/14/17
PLAN REVIEW CORRECTION LIST
TENANT IMPROVEMENTS
PLAN CHECK NO.: CBC2017-0411
OCCUPANCY: M
TYPE OF CONSTRUCTION: VB
ALLOWABLE FLOOR AREA:
SPRINKLERS?: YES
REMARKS:
DATE PLANS RECEIVED BY
JURISDICTION: 8/1/17
DATE INITIAL PLAN REVIEW
COMPLETED: 8/ 14/ 17
FOREWORD (PLEASE READ):
JURISDICTION: City of Carlsbad
USE: Retail
ACTUAL AREA: 1011 sf
STORIES: 2
HEIGHT:
OCCUPANT LOAD: 18
DATE PLANS RECEIVED BY
ESGIL CORPORATION: 8/3/17
PLAN REVIEWER: Doug Moody
This plan review is limited to the technical requirements contained in the California version of
the International Building Code, Uniform Plumbing Code, Uniform Mechanical Code, National
Electrical Code and state laws regulating energy conservation, noise attenuation and access for
the disabled. This plan review is based on regulations enforced by the Building Department.
You may have other corrections based on laws and ordinances enforced by the Planning
Department, Engineering Department, Fire Department or other departments. Clearance from
those departments may be required prior to the issuance of a building permit.
Code sections cited are based on the 2016 CBC, which adopts the 2015 IBC.
The following items listed need clarification, modification or change. All items must be satisfied
before the plans will be in conformance with the cited codes and regulations. Per Sec. 105.4 of
the 2015 International Building Code, the approval of the plans does not permit the violation of
any state, county or city law.
To speed up the recheck process, please note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet number, specification section, etc.
Be sure to enclose the marked up list when you submit the revised plans.
City of Carlsbad CBC2017-0411
8/14/17
Please niake all corrections on the original tracings, as requested in the correction
list. Submit three sets of plans for commercial/industrial projects (two sets of plans
for residential projects). For expeditious processing, corrected sets can be
submitted in one of two ways:
1. Deliver all corrected sets of plans and calculations/reports directly to the City of
Carlsbad Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760)
602-2700. The City will route the plans to EsGil Corporation and the Carlsbad
Planning, Engineering and Fire Departments.
2. Bring two corrected sets of plans and calculations/reports to EsGil Corporation,
9320 Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-1468.
Deliver all remaining sets of plans and calculations/reports directly to the City of
Carlsbad Building Department for routing to their Planning, Engineering and Fire
Departments.
NOTE: Plans that are submitted directly to EsGil Corporation only will not be
reviewed by the City Planning, Engineering and Fire Departments until review by
EsGil Corporation is complete.
1. Please provide plans and calculations signed by the California State licensed
engineer or architect for the structural support and lateral bracing of the new
785# roof mounted HVAC equipment. Include all calculations and finding on the
plans. Please include the California license number, seal, date of license
expiration and date plans are signed. Business and Professions Code.
2. Please review the requirements, revise the plans appropriately and imprint on
the plans the City of Carlsbad Policies and Procedures for Roof Mounted
Equipment to the plans.
3. Please provide the required L Tl -02 forms showing the mandatory lighting control
measures.
4. Please provide the compete L Tl -05 forms and correct the L Tl-01 part 5 of 6
forms to show the correct installed wattage.
5. Hot water supplied to a public use lavatory is limited to a maximum temperature
potential of 120 degrees by a device that conforms to ASSE 1070 or CSA
B125.3; please provide the manufacturer's listing showing compliance. Detail
how this temperature limitation is achieved. The water heater thermostat may not
be used for compliance with this Code section. UPC 413.1 & UPC 414.
Advisory Note : When alterations, structural repairs or additions are made to an
existing building, that building, or portion of the building affected, is required to
comply with all of the following requirements, per Section 11 B-202.4:
• The area of specific alteration, repair or addition must comply as "new"
construction.
City of Carlsbad CBC201 7-0411
8/14/17
• A primary entrance to the building and the primary path of travel to the
altered area, must be shown to comply with all accessibility features.
• The path of travel shall include the existing parking.
• Existing toilet and bathing facilities that serve the remodeled area must be
shown to comply with all accessibility features.
• Please address the following comments that are the result of the alterations.
6. Show that at least one water closet fixture shall provide the following, per Section
118-604:
a) One side of the water closet shall provide 17" -18" from the centerline of
the water closet to the adjacent wall.
7. Sales and service counters shall have a portion of the counter which is at least 36"
in length with a maximum height of 34 inches. Section 118-904.4.1.
8. Please revise the plans to show ?::1 fitting room or dressing room for the customers
shall be provided as follows:
i) The room dimension shall be ~60" in width and length and no door
shall encroach into the required space.
ii) Show a 24" x 48" bench:
a) Fixed along the wall at the 48" dimension.
b) Mounted ~17" but :::;19"_
c) A clear floor space complying with 118-305 provided
positioned at the end of the bench and parallel to the short
axis of the bench.
To speed up the review process, note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet, note or detail number,
calculation page, etc.
Please indicate here if any changes have been made to the plans that are not a
result of corrections from this list. If there are other changes, please briefly
describe them and where they are located in the plans.
Have changes been made to the plans not resulting from this correction list?
Please indicate:
Yes D No D
The jurisdiction has contracted with Esgil Corporation located at 9320
Chesapeake Drive, Suite 208, San Diego, California 92123; telephone number of
858/560-1468, to perform the plan review for your project. If you have any
City of Carlsbad CBC201 7-0411
8/14/17
questions regarding these plan review items, please contact Doug Moody at
Esgil Corporation. Thank you.
~ity of Carlsbad CBC201 7-0411
8/14/17
[DO NOT PAY -THIS IS NOT AN INVOICE]
VALUATION AND PLAN CHECK FEE
JURISDICTION: City of Carlsbad PLAN CHECK NO.: CBC2017-0411
PREPARED BY: Doug Moody DATE: 8/14/17
BUILDING ADDRESS: 1923 Calle Barcelona Suite 147
BUILDING OCCUPANCY: M
BUILDING AREA Valuation
PORTION ( Sq. Ft.) Multiplier
Tl 1011 46.51
Air Conditioning
Fire Sprinklers
TOTAL VALUE
Jurisdiction Code cb By Ordinance ---·~-·~--·-~--3
Bldg. Permit Fee by Ordinance -.: ~---~-~~-----~·
Plan Check Fee by Ordinanc~e ~-•~I
Type of Review: Q Complete Review
D Repetitive Fee -· , ,.. J Repeats
Comments:
D Other
D Hourly
EsGil Fee
Reg. VALUE
Mod.
D Structural Only
1----IHr@•
($)
47,022
47,022
$393.691
$255.901
$224.401
Sheet 1 of 1
macvalue.doc +
P.JF PAULJ.FORD
& COMPANY
& REV.
08 f 2. '+/ ~,,
I SSIJt DA'T':-
Columbus
250 E Broad St, Suite 600
Columbus, OH 43215
Phone 614.221 .6679
Founded in 1965
The Forum Carlsbad
Everything But Water
Carlsbad, CA
PJF Comm. Number A98117-0003
August 22, 2017
RECEIVED
AUG 3 0 2017
CITY OF CARLSBAD
BUJLDING DIVISION
,F) Orlando ~ 1801 Lee Rd, Suite 230
Winter Park, FL 32789
Phone 407.898.9039
www.PaulJFord~ .21)' '1 :-n•Ltf 1
P.JF PAUL J. FORD
&COMPANY
-, www.pjfweb.com
Page Of ____ _
By PR.c Date f>B 1~ 'I-! '2AJ\]
• I
Project J"E, ~'JM (&Q.L<;BA.D -t ew
Client _____ Comm.No.Aq~!ll-oooJ
---L... -+--T-------~-~ i . ·-··
-J -
I
-,. -·-'
...J
I
I I -T t r----___ ... -
I
--~ --· ------_L
~ .. ___ --
--i -
I . .
r -
--
I I
+ -----.----------....---.---1---_..,_I --
1 I --· ·-----+------1--:..--______:.._
--,_ --.. -------1-----1--;.__l______:..i -
I I
--+ 4--
' I
' --'-----4--L---l-----
+ -... ------'''--I-__;____:_-+----
--t---___ ,_
I
I ./foa-·.----:--'t--i--l __c.., -+---:----+-_;__' --+-_.'._' ---+-----1---.'....__~1-!-_!.__
'~(i. l '
---+--l •.. t -
' I
-~ --~----!-----+-..:____;_
-
--~-T"' ---+-+
I
J._ .. +
------+------+--+ ------------+-----
1 : I -._... -+----+--_,____...__ --!---1' -"1" '--I
I I I I I I
---! _ --'. l -I ~+--f-1-_1
--I~ -, f-f
l -! _ !
I I I
1
-
I I
I + -
i
I I
-
.. I -. -
I
I I
l
-l-. + •
I I
·1 I
I
l L +-
.. I
-
•
I -l
t
-1 --~ ; ~ -~ +-;
I -. ---__ I l I I -1 ·1 r ~ --· 1-
I '. --, ~ jf [ , . _:_ ~ _._, ----~
.j I I l -~. -~ ---~-Ll~+I I I • I
: -I -1· --_' !I, ~ --+ !I -l -I --·-· --------: __ [ _ _J_ .
i --'-· ----~--C---------'-----'--'-1 __!l~__,__~1----'--___J__~'-__L_~'-_____!___'
ROOF FRAMING NOTES:
1. CONTROLLING BUILDING CODE: 2016 CALIFORNIA BUILDING CODE (2015 IBC)
w/ LOCAL AMENDMEN TS PER CITY OF CARLSBAD, CA
SEISMIC DESIGN CATEGORY: D
S05 = 0.77 S01 = 0.44
DESIGN ROOF LIVE LOAD = 20 PSF
NOMINAL DESIGN HIND SPEED = 85 MP!-j (3-SEC GUST)
ULTIMATE DESIGN HIND SPEED = 110 MPl-1
HIND EXPOSURE CATEGORY: B (PER CITY OF CARLSBAD, CA)
2. EXISTI NG ROOF CONSTRUCTION: PLYHOOD DECK ON HOOD I-JOISTS AND GLULAM BEAMS .
3. l>:<I INDICATES ROOF OPENING. DETERMINE EXACT SIZE AND LOCATION FROM MEC!-jANICAL
DRAHINGS
4. IT IS T!-jE CONTRACTOR'S SOLE RESPONSIBILITY TO DETERMINE ERECTION PROCEDURE AND
SEQUENCE TO INSURE Tl-1E SAFETY OF Tl-1E BUILDING AND ITS COMPONENT PARTS DURING
ERECTION. T!-jlS INCLUDES, BUT IS NOT LIMITED TO, T!-jE ADDITION OF H!-jATEVER TEMPORARY
BRACING, GUYS OR TIE -DOHNS T!-jAT MAY BE NECESSARY. sue~ MATERIAL S!-jALL BE REMOVED
AND S~ALL REMAIN T~E PROPERTY OF T!-jE CONTRACTOR AFTER COMPLETION OF T!-jE PROJECT.
5. FIELD VERIFY ALL DIMENSIONS PRIOR TO FABRiCATION. MEC~. UNIT DIM ENSIONS S~ALL BE
COORDINATED HIT!-j APPROVED MECl-1. UNIT MANUFACTUR ER DRAHINGS.
6. SUPPORT FRAMING Sl-10HN IS FOR Tl-1E MECl-1. UNIT SPECIFIED ON MEC!-jANICAL DRAH INGS. IF
DIFFERENT UNI T IS TO BE USED, CONTACT STRUCTURAL ENGINEER BEFORE PROCEEDING.
7. IF EXISTING STRUCTUR E IS DIFFERENT Tl-1AN Sl-10HN, CONTACT STRUCTURAL ENGINEER BEFORE
PROCEEDING HIT!-j ANY HORK IN T!-jAT AREA.
PA€.~ 3
GL\11.At'\8~) 6l~ ~ ~\\t(/1_:
t~ fik)Sr\!At ~\~(1., ~,/\vc.i\)QAL .B-vl(J)\~ DRWG-i
!:)(lST' 6,. Gl\) L,\11\ ~ I G-1/lVP.. o,J ~ID ® J
IS D~l,Nlrf) T0 .li_JffQ/(lj' fQv1~MM u:iAf)
of j ~00 l,BS " ( NfMJ I ,~o lAl M~H WT
• ·,1 G-\'..U~ ~ G:Jl~D/fl ok ./ .
~-ll'l,1 ::,.
1!1-11'
1 1 1
1 1
' oosro 11.aJS' ssi """ 1-.JOtST J -~ --------------------------------------~S __ -----------ex,sro11.aJS'ssi,2r1x 1--"'ST : ·3 -00---------------------·3 .... /:-_ _________ --------------------~ ~ r . --00--,
" NE>< ROOFT<lP '-"IT ct I
a\ oo MAX WT • 1,IOO LBS, ,_ I
{ llt:UJOOI(; EXIST1NO CURB :'::: J I ;;ii ANO ~EH aJR& AOAPTER•:A • OO I .,. SEE MECM C)l.olGS FOR I ~ OO \...IWIJF..CTURER I .-OOEL a I § ~ 00 I ~u i
r-I
-'I.----< 10
OO '• i I X ]X i / ~-:=-~:~:LTU OO i --'-----~--'j.-~r----___!j.!.i ,~-v BIS-20! MCLO DOHN 0£TAJL. 00 i
_oo ____ ~=i ____ _ij!:~~,~: _______ ~oo ___ ____L:
I 111 I
oo ex,sr, ... MECM '-"IT /: : : .+.J-------=1:""""° ~---I oo :
r EXl5TINCi OEMISING I
00 HAU. SELOH, TYP. I
·oo ________________ ?: ________ :::·-----------------:--::-·:·:::·::·:j
00
I
I
ex,sro 11.aJS' ssi ,,,,. '·-"'ST :
@MECl-l SUPPORT FRAMING PLAN " -20 ..... 3/0'•1'-<l'
.S: S: 1 } '2t'I\ x I -1\, ~ l.MJ) C)\W.:
N'i,\,J I
1
lo~ \&.L ~ WT. --Y 1,;__ WT, b\Jif.~\I' s;u~ at.I 0\1~ 4'.ll!t!IM f§J(\/6 M 1
~vtiv'& l(L WI, 1o ~ svr.p~ Br 4-0(\S~ S~I 1-J\tSV>~
\/-i__~)\o~ l~S 1.vTJ{,~ ~ 13 i lBS, wt/ f ~ J 11£ff J , 1-:1\ 1sii__
~nvw' 5~ u,,, NCr}J) w T, o N '1\0 ~ :t -T ~tJT
~:;-S SI j '2.M X I <J11 ts-r S ok f,y' IN Sf £<:.;Tt~ /
--.._..
CHECK SEISMIC OVERTURNING SUPPORT OF ROOFTOP MECHANICAL UNIT(S}
Controlling Building Code: 2..ti \ C:. C.A,L\fo .R.N IA &v1ll)ltJ6-Co/£. W /Joe L
r-<.o Is ::t89 (!ft.. crrY of afi.UW>J t~
Determine Lateral Seismic Load: Sos = 0.113 {See Page _.:l_)
0.4 ap Sos Wp ----------""7 where: ap = 2.5, Sos = 0,113, Rp = 6.0,
Fp = [ 1 + 2 {z/h) ] Ip = 1.0, {z/h) ~ 1.0 for mech unit{s)
{ Rp I Ip) located on roof
o.4(2.sH o:rt3) wp
Fp = [ 1 + 2 (1.0) ]
( 6.0 I 1.0)
Fp = 0.'3~7wP ----7 Also check Fp range limits:
Fp :5 Fp(max) = 1.6 Sos Ip WP = 1.6( 0,1,3 )(1.0) WP= j. i~7 Wp {OK) V
Fp 2! FptmrnJ = 0.3SoslpWp = 0.3(0.T73)(1.0)Wp=0.1.3'l Wp (0 1:::_)V
• ·., use Fp = 0.'381 WP (factored)
Convert factored Fp seismic value Into working stress Fp seismic value:
Fp = (0.70) 0,3 8] WP = O. Q.11 WP (working stress)
Seismic value at each rooftop mech unit(_ different mech unit weights): ~ Q 0 Case 1}. Wp1 = V 00 lbs. ---7 : ., Fp1 = 0. 271 ( tl \ 00 ) lbs. =_ c.._ 10_ lbs. (working stress)
of = lbs. ---·""7 ••• , Fp2 = '
Case3) Wp3 = __ lbs.
Case 4) Wp4 =
lbs.
A
Mech unit weight 0.6WJ2 Wp/2
-/+ +
.:..:M.:..::e~ch:..:....s:::.::e:.:,,is::.:.m!!.'ic::..!lo::c.:a::.o:d,.._ _____ __,_Fv11_{.=B/....,C::.i..l ____ __,_Fl!..(B/C)
Combined total =0.6Wp/2 -Fp(B/C) = Wp/2 + Fp(B/C}
wt./ load (max. uplift) (max. down)
or [ 0.6Wp/2 -Fp(B/C)] I 2
{max. uplift each corner)
or [ Wp/2 + Fp (B/C)] I 2
(max. down each corner)
. I D esign Maps Summary Report https://earthquake.usgs.gov/cn2/designmaps/us/summary.php?templ. ..
1 of 1
~USGS Design Maps Summary Report
2-01 b CAU~,4 B.Ultllltd W.e
w/ (})~l, /<M~{'/IOJ-rs Lb),s l8c'
_,)
User-Specified Input
Report Title A98117-0003 The Forum Carlsbad-EBW
Fri August 18, 2017 13 :07: 18 I.JfC
P~ 01-ry of (AR.LS8AP J (A J
Building Code Reference Document 2012/2015 International Building Code
(which utilizes USGS hazard data available in 2008)
Site Coordinates 33.07123°N, 117.26578°W
Site Soil Classification Site Class D -"Stiff Soil"
Risk Category I/II/III
USGS-Providecl. Output
Ss = 1.090 g
S1 = 0.420 g
Solima Su ch~
SMs = 1.160 g
SM1 = 0.664 g
Gos = ~ .--YALU(
501 = 0.443 g
FAG-E.. S
For information on how the SS and 51 values above have been calculated from probabilistic (risk-targeted) and
deterministic ground motions in the direction of maximum horizontal response, please return to the application and
select the "2009 NEHRP" building code reference document.
c..w
l.::J) o.~
,_;,e ,1-:-:::'.:
Y,:.?,j Q.~
,;ul' C..!b
~ a•i
(J (LOO "'
~ (1.£,!
<l O.~J <,,,
1l'-!' a.~
'1.~ 11::4
~=.t 0. !(
Q,)O 4-->---+--1--+----l--+---l--+----1----<
C..:?"'..! =1.}.: C..:0 i:lt.'".: ~!X~ :..,:~:. l.:O i.¥.J ',W t :r..~ .Z.'X' •:i.tJJ O,,_-:i 11 :..0 0.!-0 ,,ts:, lf..rJ \.:.V.,1 't;(Q' • ~:~.i 1.&J .:..ex;:
P~"•6~ r (1i~::)
Although this information is a product of the U.S. Geological Survey, we provide no warranty, expressed or implied, as to the accuracy of
the data contained therein. This tool is not a substitute for technical subject-matter knowledge.
8/18/2017 9:08 AM
Case 1) Wpl = t, \C)O lbs., Fpl = 2-tts lbs., A1 = 38 11, 81 = 4-1 11, C1 = Lf--?_ II
. 0.6WpJ2 -Fp1(B1/C1) (), Co ~~\OO LB~Y2. -(~ 8 I.M.~l~~")
Uplift each corner = = ___ ..... _____ .....;_..;,_~
.. J
2 2
IMS\ C-~\f\ctiJl"
Uplift each corner = :J1L 1bs. ( V?L\Fi value)
1tJs1Gif1c:A!oll uplift due to seismic loading (OK) V
___ lbs., Fp2 = ___ lbs., A2 = __ 11,
0.6Wpi/2 -Fp2(BJC2)
·ft each corner --------------------------------------------------------
2
ch corner = + __ lbs. (positive value)
ift due to seismic loading (OK) V
Case 3) Wp3 = _ _,,,,__lbs., Fp3 = __ _
0.6Wp4
Uplift each corner = ---------------------------------------------------------------------
Uplift each corner = +
. · ., no uplift due to ,sei
2
II
Case 5) Wps = __ _ ., As= __ 11, Bs = __ 11, Cs= __ 11
2
\ ------------------~-;-----------------------
orner = + __ lbs. (positive
ift due to seismic loading (OK) V
1'-r\r' .• , for all cases, \t-l~ uplift due to seismic loading (OK) V
CHECK SLIDING OF ROOFTOP MECHANICAL UNIT(S) DUE TO SEISMIC LOADING :
From all _l_ cases, max. sliding force = max Fp = Fpj__ = 1J..B_ lbs. (Case j_)
• Use hold-down clip "A" at (3) locations each side of each mech unit -(12) clips I unit (See
Detail~ Page~).
• Use hold-down clip "S" at (3) locations each side of each mech unit -(12) clips I unit (See Detail
~ Page ..&...J.
• Use 3/8" dia. x 2 Yz'' long lag bolts (provide min. 1 Yz" embed.) @ 12" o.c. all around perimeter
for roof curb connection to roof (See Detail ~ Page ..l_) .
• · ., connections of existing roof curb-to-roof, new curb adapter-to-existing roof curb, and rooftop
mechanical unit-to-new curb adapter are each ok by inspection for adequate resistance to sliding forces
due to seismic loading (OK) t/
(3)-1112 WOOD
SCREWS ----......
'HOLD-DOWN'
CLIP 'A'-
CONT 2X4 WOOD BLOCKING
(BY CURB ADAPTER
SUPPLIER)------~
'5' CLIPS BY CURB ADAPTER
MANUFACTURER (3 PER SIDE).
SEE MANUFACTURER'S DWG FOR ATTACHMENT. ______ _,,.
EXISTING WOOD
SUPPORT FRAMING
(n\
RTU
2" r-14 GA GALV PLATE
1112 SCREW, TYP
NEW CURB
ADAPTER
~OLD-DOHN CLIP 11A 11
(BY CURBS PLUS, INC) NOTE:
CONTRACTOR SHALL VERIFY
'HOLD-DOWN" CLIP DIMENSIONS ARE
COMPATIBLE HITH SIZE OF RTU
SPECIFIED.
MINIMUM CONNECTION REQUIRED:
3/5"~ LAG BOLT @ 12" O.C. ALL
AROUND (PROVIDE MIN. I 112'
EMBED INTO EXIST WOOD
FRAMING.)
NOTE: PROVIDE ADDITIONAL
FASTENERS TO EXISTING
CONNECTIONS AS REQUIRED TO
ACHIEVE EQUIVALENT OVERALL
CONNECTION STRENGTH.
'5' CLIPS BY CURB
ADAPTER MANUFACTURER
(3)-LOCATIONS EACH SIDE
EXIST'G ROOF
'HOLD-DOWN'
CLIP 'A' AT
(3)-LOCATIONS
EACH SIDE
NEW CURB ADAPTER, SEE
MANUFACTURER'S DWG FOR
ATTACHMENT TO EXISTING CURB
ATTAC~MENT TO CURB ADAPTER
ROOFTOP ~VAC UNITS
(o\
~
~ r
Oo