HomeMy WebLinkAbout1935 CALLE BARCELONA; 176; CB030742; PermitI I T >- --a' :
City of Carlsbad
1635 Faraday Av Carlsbad, CA 92008
Building Inspection Request Line (760) 602-2725
CommerciaI/lndustrial Permit Permit No: CB030742
Job Address:
Permit Type:
Parcel No:
Valuation:
Occupancy Group:
Project Title:
Applicant:
KRASTMANHANK
1935 CALLE BARCELONA CBAD St: 176
TI Sub Type: COMM
Lot #: 0 Status: ISSUED
$43,530.00 Construction Type: NEW Applied: 0311 212003
THE COFFEE BEAN & TEA LEAF Plan Approved: 08/19/2003
1,451 SF IMPROVEMENT Issued: 08/19/2003
Reference #: Entered By: MDP
Inspect Area:
Plan Check#:
Owner:
20610 ROMAR ST
CHATSWORTH 9131 1
Building Permit
Add'l Building Permit Fee
Plan Check
Add'l Plan Check Fee
Plan Check Discount
Strong Motion Fee
Park Fee
LFM Fee
Bridge Fee
BTD #2 Fee
BTD #3 Fee
Renewal Fee
Add'l Renewal Fee
Other Building Fee
Pot. Water Con. Fee
Meter Size
Add'l Pot. Water Con. Fee
Recl. Water Con. Fee
$320.83
$0.00 $208.54
$0.00
$0.00
$9.14
$0.00
$0.00
$0.00 $0.00
$0.00
$0.00 $0.00 $0.00
$0.00
$0.00 $0.00
Meter Size
Add'l Recl. Water Con. Fee
Meter Fee
SDCWA Fee
CFD Payoff Fee
PFF
PFF (CFD Fund)
License Tax
License Tax (CFD Fund)
Traffic Impact Fee
Traffic Impact (CFD Fund)
PLUMBING TOTAL
ELECTRICAL TOTAL
MECHANICAL TOTAL
Master Drainage Fee
Sewer Fee
Redev Parking Fee
Additional Fees
TOTAL PERMIT FEES
$0.00
$0.00
$0.00
$0.00
$0.00 $0.00
$0.00
$0.00 $0.00 $0.00
$139.00
$1 10.00
$47.00 $0.00
$0.00
$0.00
$0.00
$834.51
Total Fees: $834.51 Total Payments To Date: $208.48 Balance Due: $626.03
follow the protest procedures set forth in Government Code Section 66020(a), and file the protest and any other required information with the City Manager for
processing in accordance with Carlsbad Municipal Code Section 3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack,
review, set aside, void, or annul their imposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified feedexactions DOES NOT APPLY to water and sewer connection fees and capacity
changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this project. NOR DOES IT APPLY to any
mxact ions of wh ich vou have D reviouslv been aiven a NO TlCF similar to this. o r as to which the rev iouslv mtw ise exdred. .. .
526 03
I FOR OFFICE USE ONLY A
PERMIT APPLICATION
CITY OF CARLSBAD BUILDING DEPARTMENT
?635 Faraday Ave., Carlsbad CA 92008
Plan Ck. Deposit
Validated By
Date
Legal Description Lot No. Subdivision NamelNumber Unit No. Phase No. Tdal #of units
Assessor's Pam1 # Exlstulg use Proposed Use
Desaiption of Work #of Stones #of Bedmoms #ofsathrwms
9
Name Address statemp Telephone #
sis for the alleged exemption Any violation of Sectton 7031 5 by
State License # --
w@uuilm-w
Workers Compensabon Declaratron 1 hereby
0
Tor which this permit is issued
worker's compensation inswance canier and
Insurance Company5- P . Es. f%d!2- Policy No 1 bq -0 3 Expiration Date 7/17/h
(THIS SECTION NEED NOT BE COMPLETED IF THE PERMIT IS FOR ONE HUNDRED WLLARS [$IO01 OR LESS)
0
become subject to the Workem' Compensation Laws of California
I have and wlll maintain a certificate of cansent to selfinsure for workers' ampensatton as prmded by Sectton 3700 of the Labor Code, for the performance of the work
I have and 41 maintain worker's compensation, as required by %&on 3700 of the labor Code, for Ihe performance d the work for whch this pennit is tssued My
'cy number are
CERTKlCATE OF EXEMPTION: I certify that in the performance of the work for which this permit is issued, I shall not employ any persal in any manner 90 as to
one hundred thouaand salon coverage Is unlawful, and shall subject an employer to crlmlnal pe
satlon. dammges are pmvlded for in Section 3?06 ofthe Labor Code, lnte
I herebyafrirm that I am exempt from the Contractor's License Law for the folfowtng reason
CI 1, as owner of the properly or my employees with wages as their sole compensation, will d the work and the structure is not intended or offered for sale (Sec 7044,
Business and Professions Code The Contractor's License Law does not apply to an Owner of property who builds or improves tbeon, and who does such work himself or
through his own employees. provided that such improvements are not miended or *red for sale kf, however, the building or improvement is sold within one year of
completion. the owner-builder will have the burden of pmg that he did not bulfd or impm tw the purpose of sate)
0 I, as Owner of the property, am exdusively mntracting wth bcensed contraciors to mnslrucf the prcljecl @ec 7044, Business and Professions Code The ConlracWs
License Law does not appiy to an owner of property who builds or improves thereon, and wntracls for such prop& with wntraaOr(s) licensed pursuant to the Contractor's
License Law)
0
1
2
3
4.
5.
1 am exempt under S&n
I personally pian ta provide the major labor and materials for construction of the proposed property improvement 0 YES 0 NO
I (havehave not) stgned an applicatton for a building permit for the proposed work
I have contracted with the follomng person (firm) to provlde the proposed construd~on (indude name / address / phone number I contractors llcefise number)
I plan to prowde portions of the work, but I have hired the fdlowtng perm to wordinate, supervise and provide the major work (lndude name / address I phone number /
lontractors license number)
I will provide me of the work, but I have contracted (hired) the foilowhg persons to provMe the wcrk idicated (include name / address / phone number / type of work)
Business and Professions Code for this reason
PROPERTY OWNER SIGNATURE DATE
WHITE: File YELLOW: ADplicanl PINK: Finance
ctw OF CARLSBAD Buttwe DEPARTMENT
1635 Faraday Ave., Cartsbad CA 92008
Page 2 of 2
C~~~~~fQJtWCW&WMW
Is he applicant or future building occupant required lo s
Sections 25505 25533 or 25534 of the Presley-Tanner Hazardous Substance Account Act7 CI YES
Is the appllcanl or future Mng occwpanl reqwed to oblatn a permit from I
Is the facility to be constructed wthm 1 ,OOO feel of the ouler boundary of a school site? YES p( NO
IF ANY OF THE ANSWERS ARE YES, A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR IS MEETING THE
REQUIREMENTS OF THE OFFICE OF EMERGENCY SERVICES AND THE AtR POLLUTION CONTROL DISTRICT.
I hereby affirm that lhere is a constructton lending agency for the performance of the work for which this permil is issued (Sec 3097(1)
LENDERS NAME LENDERS ADDRESS
I certify that I
ordmances and State laws relating to buildtng wstruclton I hereby authorize representabves of the City of Carlsbad to enter upon the above menboned properly for inspecbon
purposes I ALSO AGREE TO SAM. INDEMNIFY AND KEEP HARMLESS THE CITY OF CARLSBAD AGAINST ALL LIABILITIES, JUDGEMENTS, COSTS AND
EXPENSES WHICH MAY IN ANY WAY ACCRUE AGAINST SAID CITY IN CONSEQUENCE OF THE GRANTING OF THIS PERMIT.
OSHA An OSHA permit is required for excavations of 5'0" deep and demolibon or conslrudion of structures over 3 stories in height
EXPIRATION: Every permit issued by he building ORiaal under he pmwsions of this Code shall expire by limitation and beaxne null and void d he building or work authorized by such permit is not commenced mlhtn 180 days from the dale of such permit or fl he budding or work author& by such permit is suspended or abandaned at any time afier
8. -L*m
RAPPW:
DATE 3 - /O - 0.1
WHITE: File YELLOW: Applicant PINK: Finance
PERMIT APPLICATION
CITY OF CARLSBAD BUILDING DEPARTMENT
1635 Faraday Ave., Carlsbad, CA 92008
Assessor's Parcel # Existing Use Proposed Use
FOR OFFICE USE ONLY
PLAN CHECK NO.
EST. VAL.
Plan Ck. Deposit
Validated By
Date
#of Stories Y of Bedrooms Y of Bathrooms Description of Work SO. FT.
Name Address City Statelzip Telephone # Fax #
Name Address City Statelzip Telephone #
Name Address City Statelzip Telephone #
issuance, also requires the applicant for such permit to file a signed statement that he is licensed pursuant to the provisions of the Contractor's License Law
[Chapter 9, commending with Section 7000 of Division 3 of the Business and Professions Codel or that he is exempt therefrom, and the basis for the alleged
the applicant to a civil penalty of not more than five hundred dollars [$5001).
City Statelzip
0 c.7
Address
State License # 70 73 7d License Class 6 City Business License Y
Designer Name Address city Statelzip Telephone
Workers' Compensation Declaration: I hereby affirm under penalty of perjury one of the following declarations:
0
of the work for which this permit is issued.
0
I have and will maintain a certificate of consent to self-insure for workers' compensation as provided by Section 3700 of the Labor Code, for the performance
I have and will maintain workers' compensation, as required by Section 3700 of the Labor Code, for the performance of the work for which this permit IS - issued. My worker's compensation insurance carrier and policy number are:
t Insurance Company X~ZT~ ~n4,4 Policy NO. /SY59y7 2003 Expiration Date /- D/ .- y
(THIS SECTION NEED NOT BE COMPLETED IF THE PERMIT IS FOR ONE HUNDRED DOLLARS 161001 OR LESS1
0 to become subject to the Workers' Compensation Laws of California.
CERTIFICATE OF EXEMPTION: I certify that in the performance of the work for which this permit is issued, I shell not employ any person in any manner so as
a up to one hundred I. unlawful, and shall subject an employ
ation, damages as provided for In Section
0 I, as owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not intended or offered for sale
(Sec. 7044, Business end Professions Code: The Contractor's License Law does not apply to an owner of property who builds or improves thereon, and who does
such work himself or through his own employees, provided that such improvements are not intended or offered for sale. If, however, the building or improvement is sold within one year of completion, the owner-builder will have the burden of proving that he did not build or improve for the purpose of sale).
0 I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions Code: The
Contractor's License Law does not apply to an owner of property who builds or improves thereon, and contracts for such projects with contractor(s1 licensed
pursuant to the Contractor's License Law).
0
1.
2.
3.
4.
number I contractors license number):
5.
of work):
*
I am exempt under Section
I personally plan to provide the major labor and materials for construction of the proposed property improvement. 0 YES UNO
I (have I have not) signed an application for a building permit for the proposed work.
I have contracted with the following person (firm) to provide the proposed construction (include name I address I phone number I contractors license number):
I plan to provide portions of the work, but I have hired the following person to coordinate, supervise and provide the major work (include name I address I phone
I will provide some of the work, but I have contracted (hired) the following persons to provide the work indicated (include name I address I phone number I type
Business and Professions Code for this reason:
program under Sections 25505, 25533 or 25534 of the Presley-Tanner Hazardous Substance Account Act? 0 YES 0 NO
Is the applicant or future building occupant required to obtain a permit from the air pollution control district or air quality management district?
Is the facility to be constructed within 1,000 feet of the outer boundary of a school site?
IF ANY OF THE ANSWERS ARE YES, A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR IS MEETING THE
0 YES 0 NO
0 YES 0 NO
I certify that I have reed the application and state that the above information is correct and that the information on the plans is accurate. I agree to comply with all City ordinances and State laws relating to building construction. I hereby authorize representatives of the City of Carlsbad to enter upon the above mentioned property for inspection purposes. I ALSO AGREE TO SAVE, INDEMNIFY AND KEEP HARMLESS THE CITY OF CARLSBAD AGAINST ALL LIABILITIES,
JUDGMENTS, COSTS AND EXPENSES WHICH MAY IN ANY WAY ACCRUE AGAINST SAID CITY IN CONSEQUENCE OF THE GRANTING OF THIS PERMIT.
OSHA An OSHA permit is required for excavations over 5'0" deep and demolition or construction of structures over 3 stories in height.
EXPIRATION: Every permit issued by the building Official under the provisions of this Code shall expire by limitation and become null and void if the building or work
authorized by such permit is not commenced within 180 days from the date of such permit or if the building or work authorized by such permit is suspended or abandoned
at any time after the work is commenced for a period of 180 days (Section 106.4.4 Uniform Building Code).
APPLICANT'S SIGNATURE DATE
WHITE: File YELLOW: Applicant PINK: Finance
City of Carlsbad
Final Building
Dept: Building Engineering Planning
Plan Check #:
Permit #: CB030742
Project Name: THE COFFEE BEAN & TEA LEAF
1,451 SF IMPROVEMENT
Address: 1935 CALLE BARCELONA #176
CMWD St Lite
Date:
Permit Type:
Sub Type:
Lot: 0
1 1 /19/2003
TI
COMM
Contact Person: HOWARD Phone: 9097123288
Sewer Dist: Water Dist:
4sapproved:
Date
Inspected: Approved:
Date Y Inspected
By: Inspected: Approved: Disapproved:
Inspected Date
By: Inspected: Approved: Disapproved:
Comments:
...........................................................................................................................................................
City of Carlsbad Bldg Inspection Request
For: 1 1/25/2003
Permit# C BO30742
Title: THE COFFEE BEAN & TEA LEAF
Description: 1,451 SF IMPROVEMENT
Type: TI Sub Type: COMM
Job Address: 1935 CALLE BARCELONA
Suite: 176 Lot 0
Location:
APPLICANT KRASTMAN HANK
Owner:
inspector Assignment: PS
Phone: 9097123288
Inspector: KY
Remarks:
Total Time: Requested By: HOWARD
CD Description Act Comment
Entered By: CHRISTINE
19 Final Structural
29 Final Plumbing
39 Final Electrical
I 49 Final Mechanical
Associated PCRsCVs
PCR03193 ISSUED COFFEE BEAN &TEA LEAF, REVISE PLUNBING &ELECTRICAL
Date
11/21/2003
1 1 I1 912003
1 111 712003
11/17/2003
1 111 412003
1 1 /13/2003
1 111 2/2003
11/12/2003
11/12/2003
11/10/2003
1 111 012003
11/10/2003
10/02/2003
10/02/2003
09/26/2003
09/25/2003
InsDection History
Description
89 Final Combo
89 Final Combo
29 Final Plumbing
84 Rough Combo
84 Rough Combo
84 Rough Combo
23 Gas/Test/Repairs
34 Rough Electric
44 RougMDuctsIDampers
14 FrarnelSteellBoltingWelding
34 Rough Electric
44 RougNDuctslDampers
17 Interior LatNDrywall
44 RougNDuctsIDampers
11 FtgIFoundatiordPiers
24 Rougwopout
Act lnsp Comments
CO PS NOFIREAPP
CO PS EMR AND GAS METER RELEASE co PS co PS
PA PS ON T BAR PRIM ONLY
co Pst
AP PS
NR PS
AP PS ROUGH
NS TP
NS TP
NS TP
AP PS
CO PS NOTPERPLAN
AP FS POURBACK
AP PS
Inspection List
Permit#: CB030742 Type: TI COMM THE COFFEE BEAN & TEA LEAF
1,451 SF IMPROVEMENT
Date Inspection Item Inspector Act Comments
11/26/2003 89
11/25/2003 89
11/25/2003 89
11/24/2003 89
1 1 /24/2003 89
1 1 /2 112003 89
1 112 112003 89
1111 912003 89
1 111 912003 89
1 111 712003 29
1 111 712003 29
1 111 712003 84
1 111 712003 84
1 111 412003 84
1 111 412003 84
1 111 312003 84
1 111 312003 84
1 111 212003 23
1 111 212003 23
1 111 212003 34
1 1 /12/2003 34
11/12/2003 44
1 111 212003 44
1 111 012003 14
1111 0/2003 34
1 111 012003 44
10/02/2003 17
10/02/2003 44
09/26/2003 11
09/25/2003 24
09/25/2003 44
09/04/2003 14
09/04/2003 24
09/04/2003 34
08/29/2003 84
08/28/2003 84
08/26/2003 34
08/22/2003 34
08/21/2003 24
08/21 12003 34
Final Combo
Final Combo
Final Combo
Final Combo
Final Combo
Final Combo
Final Combo
Final Combo
Final Combo
Final Plumbing
Final Plumbing
Rough Combo
Rough Combo
Rough Combo
Rough Combo
Rough Combo
Rough Combo
GasllestlRepairs
GasllesVRepairs
Rough Electric
Rough Electric
Roug h/Ducts/Dampers
Rough/Ducts/Dampers
FrarnelSteeVBoltingNVeldin
Rough Electric
Roug h/Ducts/Dampers
Interior Lath/Drywall
Rough/Ducts/Dampers
Ftg/Foundation/Piers
Roug hllopout
Roug h/Ducts/Dampers
Frame/SteeVBoltingNVeldin
Roughllopout
Rough Electric
Rough Combo
Rough Combo
Rough Electric
Rough Electric
Roughllopout
Rough Electric
PS
PS
PS
PS
PS
PS
PS
PS
PS
PS
PS
TP
TP
TP
PS
PS
PS
PS
PS
TP
TP
TP
PS
PS
PS
PS
PS
PS
RI
RI
AP
RI
NR
RI
co co
RI
co
RI
co
RI
PA
RI
RI
co
RI
AP
RI
NR
RI
AP
NS
NS
NS
AP
co
AP
AP
co
PA
co
AP
co
CA
NR
co
co
co
NO FIRE APP
EMR AND GAS METER RELEASE
NEEDS UTILITIES RELEASED
WANTS GAS METER
ON T BAR PRIM ONLY
T-BAR
ROUGH
NOT PER PLAN
POUR BACK
NOT PER PLAN
NON PLUMB WALLS
NPP
WALLS, PNLS @ WALL
NOT PER PLAN
BY DAVD
SEE ATTAHED NOTICE
CONSULTATION
Wednesday, November 26,2003 Page 1 of 1
City of Carlsbad Bldg Inspection Request
For: 1 1/19/2003
Permit# CB030742 Inspector Assignment: PS
Title: THE COFFEE BEAN & TEA LEAF
Description: 1,451 SF IMPROVEMENT
Type: TI Sub Type: COMM
Job Address: 1935 CALLE BARCELONA
Suite: 176 Lot 0
Location:
APPLICANT KRASTMAN HANK
Owner:
Remarks: NEEDS UTILITIES RELEASED
Phone: 9097123288
Inspector: 3r
Total Time: Requested By: HOWARD
CD Description
19 Final Structural
29 Final Plumbing
39 Final Electrical
49 Final Mechanical
Entered By: KAREN 4% Comment EA fl-
Associated PCRs/CVs
PCR03193 ISSUED COFFEE BEAN &TEA LEAF; REVISE PLUNBING & ELECTRICAL
Inspection History
Date Description
1 1 /I 712003 29
1 111 712003 84
1 111 412003 84
1 111 312003 84
11/12/2003 23
11/12/2003 34
11/12/2003 44
1 111 012003 14
11/10/2003 34
1 111 012003 44
10/02/2003 17
10/02/2003 44
09/26/2003 11
09/25/2003 24
09/25/2003 44
09/04/2003 14
Final Plumbing
Rough Combo
Rough Combo
Rough Combo
Gas/Test/ Repairs
Rough Electric
RoughlDuctsIDampers
Frame/Steel/BoltinglWelding
Rough Electric
RougNDuctsIDampers
Interior LatNDrywall
Roug NDuctslDampers
FtglFoundationlPiers
Roug NDuctsIDampers
Frame/Steel/BoltinglWelding
RoughlTopout
Act lnsp Comments
GO PS co PS
PA PS ON T BAR PRIM ONLY
co PS
AP PS
NR PS
AP PS ROUGH
NS TP
NS TP
NS TP
AP PS
CO PS NOTPERPLAN
AP PS POURBACK
AP PS
CO PS NOTPERPLAN
PA TP NONPLUMBWALLS
EsGil Corporation
In Partnership with Government for Qcuifding Sufety
DATE: 7/ 16/03
JURISDICTION: City of Carlsbad
PLAN CHECK NO.: 03-742 SET: I11
0 FILE
PROJECT ADDRESS: 1935 Calle Barcelona Sutie 176
PROJECT NAME: Coffee Bean 8~ Tea Leaf - TI
0 The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified in the remarks below are resolved and checked by building
department staff.
0 The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
The check list transmitted herewith is for your information. The plans are being held at Esgil
The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
Corporation until corrected plans are submitted for recheck.
contact person.
0 The applicant's copy of the check list has been sent to:
Ix] Esgil Corporation staff did not advise the applicant that the plan check has been completed.
0 Esgil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Telephone #:
Dj#e contacted: (by: ) Fax #:
REMARKS: Applicant to provide truss calculations stamped and signed be a California licensed
engineer or architect and attach structural plans to city held sets. *
By: Doug Moody Enclosures:
Mail Telephone Fax In Person
Esgil Corporation 0 GA 0 MB 0 EJ 0 PC 7/8/03 trnsmtl.dot
9320 Chesapeake Drive, Suite 208 4 San Diego, California 92123 (858) 560-1468 4 Fax (858) 560-1576
EsGi t Corporation
In Partnersfiip witfi Government for Quilding safety
DATE: 5/ 15/03
JURISDICTION: City of Carlsbad
PLAN CHECK NO.: 03-742 SET: I1
PROJECT ADDRESS: 1935 Calle Barcelona Suite 176
PROJECT NAME: Coffee Bean & Tea Leaf - TI
c] The plans transmitted herewith have been corrected where ne
with the jurisdiction’s building codes.
-
a FILE
ssary and substantially comply
u The plans transmitted herewith will substantially comply with the jurisdiction’s building codes
when minor deficiencies identified below are resolved and checked by building department staff.
The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
The applicant’s copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
The applicant’s copy of the check list has been sent to:
Hank Krastman
20610 Romar Street, Chatsworth, CA 9131 I
0 Esgil Corporation staff did not advise the applicant that the plan check has been completed.
Esgil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Hank Krastman
Date contacted: 5 3 .(by: k- ) -i .
Mail /Telephone Fax/ In Person 0 REMARKS:
By: Doug Moody Enclosures:
Esgil Corporation 0 GA c] MB [7 EJ PC 5/8/03
Telephone #: 81 8-727-1 723
Fax #: ala-727-1149
trnsrntl.dot
9320 Chesapeake Drive, Suite 208 + San Diego, California 92123 + (858) 560-1468 + Fax (858) 560-1576
0 ',
REVIEWED BY: Doug Moody
City of Carlsbad 03-742
5 f 15/03
RECHECK PLAN CORRECTION LIST
1 JURISDICTION: City of Carlsbad PLAN CHECK NO.: 03-742
PROJECT ADDRESS: 1935 Calle Barcelona Suite 176 SET: I1
DATE PLAN RECEIVED BY
E SG I L COR P 0 RAT I 0 N : 5/8/03
DATE RECHECK COMPLETED:
5/ 15/03
FOREWORD (PLEASE READ):
This plan review is limited to the technical requirements contained in the Uniform Building Code,
Uniform Plumbing Code, Uniform Mechanical Code, National Electrical Code and state laws
regulating energy conservation, noise attenuation and disabled access. This plan review is
based on regulations enforced by the Building Department. You may have other corrections
based on laws and ordinances enforced by the Planning Department, Engineering Department
or other departments.
The following items listed need clarification, modification or change. All items must be satisfied
before the plans will be in conformance with the cited codes and regulations. Per Sec. 106.4.3,
1997 Uniform Building Code, the approval of the plans does not permit the violation of any
state, county or city law.
A. Please make all corrections on the original tracings and submit three new sets of prints to:
ESGIL CORPORATION.
B. To facilitate rechecking, please identify, next to each item, the sheet of the plans upon
which each correction on this sheet has been made and return this sheet with the
revised plans.
C. The following items have not been resolved from the previous plan reviews. The original
correction number has been given for your reference. In case you did not keep a copy of
the prior correction list, we have enclosed those pages containing the outstanding
corrections. Please contact me if you have any questions regarding these items.
D. Please indicate here if any changes have been made to the plans that are not a result of
corrections from this list. If there are other changes, please briefly describe them and where
they are located on the plans. Have changes been made not resulting from this list?
OYes ONo
City of Carlsbad 03-742
5/ 15/03
Please make all corrections on the origina tracings, as requested in the correction
list. Submit three sets of plans for commerciallindustrial projects (two sets of plans
for residential projects). For expeditious processing, corrected sets can be
submitted in one of two ways:
1. Deliver all corrected sets of plans and calculations/reports directly to the City of
Carlsbad Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760)
602-2700. The City will route the plans to EsGil Corporation and the Carlsbad
Planning, Engineering and Fire Departments.
2. Bring one corrected set of plans and calculations/reports to EsGil Corporation,
9320 Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-1468.
Deliver all remaining sets of plans and calculations/reports directly to the City of
Carlsbad Building Department for routing to their Planning, Engineering and Fire
Departments.
NOTE: Plans that are submitted directly to EsGil Corporation only will not be
reviewed by the City Planning, Engineering and Fire Departments until review by
EsGil Corporation is complete.
These corrections are in response to items not fully addressed or as the
result of information provided, the text in bold print indicates the
unresolved issue.
2. Please provide plans and calculations signed by the California State licensed
engineer or architect for the structural support of the 1376# rooftop air handler
unit. Include all calculations and finding on the plans. Please include the
California license number, seal, date of license expiration and date plans are
signed. Business and Professions Code. Please provide plans and details
clearly showing the additional framing for the support of the new HVAC
equipment as shown in the calculations. Each sheet of the plans must be
stamped and signed. Please clarify the calculations to indicate why the
live load of the roof structure may be removed from the calculations?
Please provide calculations to show the TJl’s adequate.
EsGil Corporation
In cPurtnership with Government for Building Sufety
DATE: 3/24/03
JURISDICTION: City of Carlsbad
PLAN CHECK NO.: 03-742
0 FILE
SET: I
PROJECT ADDRESS: 1935 Calle Barcelona Suite 176
PROJECT NAME: Coffee Bean & Tea Leaf - TI
0
0
0
w
0
w
0 w
0
The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction’s building codes.
The plans transmitted herewith will substantially comply with the jurisdiction’s building codes
when minor deficiencies identified below are resolved and checked by building department staff.
The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
The applicant’s copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
The applicant’s copy of the check list has been sent to:
Hank Krastman
20610 Romar Street, Chatsworth, CA 9131 1
Esgil Corporation staff did not advise the applicant that the plan check has been completed.
Esgil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Hank Krastman (\. t-j]
Date contacted: 3 I/ 2Y 03 (by: It, )
REMARKS:
Telephone #: 81 8-727-1 723
Fax #: 818-727-1 149
Mail 4elephone J Fax J In Person
By: Doug Moody Enclosures:
Esgil Corporation 0 GA 0 MB 0 EJ 0 PC 311 3/03 tmsmtl .dot
9320 Chesapeake Drive, Suite 208 + San Diego, California 92123 (858) 560-1468 + Fax (858) 560-1576
City of Carlsbad 03-742
3/24/03
PLAN REVIEW CORRECTION LIST
TENANT IMPROVEMENTS
PLAN CHECK NO.: 03-742
OCCUPANCY: B
TYPE OF CONSTRUCTION: VN
ALLOWABLE FLOOR AREA:
SPRINKLERS?: YES
REMARKS:
DATE PLANS RECEIVED BY
JURISDICTION : Unknown
DATE INITIAL PLAN REVIEW
COMPLETED: 3/24/03
JURISDICTION: City of Carlsbad
USE: Restaurant
ACTUAL AREA: 1381sf
STORIES: 1
H El GHT:
OCCUPANT LOAD: 44
DATE PLANS RECEIVED BY
ESGIL CORPORATION: 3/13/03
PLAN REVIEWER: Doug Moody
FOREWORD (PLEASE READ):
This plan review is limited to the technical requirements contained in the Uniform Building Code,
Uniform Plumbing Code, Uniform Mechanical Code, National Electrical Code and state laws
regulating energy conservation, noise attenuation and access for the disabled. This plan review
is based on regulations enforced by the Building Department. You may have other corrections
based on laws and ordinances enforced by the Planning Department, Engineering Department,
Fire Department or other departments. Clearance from those departments may be required
prior to the issuance of a building permit.
Code sections cited are based on the 1997 UBC.
The following items listed need clarification, modification or change. All items must be satisfied
before the plans will be in conformance with the cited codes and regulations. Per Sec. 106.4.3,
1997 Uniform Building Code, the approval of the plans does not permit the violation of any
state, county or city law.
To speed up the recheck process, please note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet number, specification section, etc.
Be sure to enclose the marked up list when vou submit the revised plans.
TENANT IMPROVEMENTS WITHOUT SPECIFIC ENERGY DATA OR POLICY SUPPLEMENTS (1997UBC) tifowdot
City of Carlsbad 03-742
3/24/03
Please make all corrections on the original tracings, as requested in the correction
list. Submit three sets of plans forcommerciaI/industrial projects (two sets of plans
for residential projects). For expeditious processing, corrected sets can be
submitted in one of two ways:
1. Deliver all corrected sets of plans and calculations/reports directly to the City of
Carlsbad Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760)
602-2700. The City will route the plans to EsGil Corporation and the Carlsbad
Planning, Engineering and Fire Departments.
2. Bring one corrected set of plans and calculationsheports to EsGil Corporation,
9320 Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-1468.
Deliver all remaining sets of plans and calculationsheports directly to the City of
Carlsbad Building Department for routing to their Planning, Engineering and Fire
Departments.
NOTE: Plans that are submitted directly to EsGil Corporation only will not be
reviewed by the City Planning, Engineering and Fire Departments until review by
EsGil Corporation is complete.
I. Provide evidence of Health Department approval (for restaurants), where
regulated by the local Health Department.
2. Please provide plans and calculations signed by the California State licensed
engineer or architect for the structural support of the 1376# rooftop air handler
unit. Include all calculations and finding on the plans. Please include the
California license number, seal, date of license expiration and date plans are
signed. Business and Professions Code.
3. Please note on the plans "AC Cable is not allowed in A, 9, E, H, and I
occupancies. NM cable is restricted (without City approval) to one and two
family dwellings. Note on plans that an equipment ground conductor is to be
installed in all flexible conduits".
4. Please attach the City of Carlsbad Policies and Procedures for Roof Mounted
Equipment to the plans.
5. Show a level area, or landing at the restroom door, per Section 1133B.2.4.2:
a)
b)
260" in the direction of door swing.
248" in the direction opposite the door swing (or 44" if doors don't have
latches or closers).
To speed up the review process, note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet, note or detail number,
calculation page, etc.
Please indicate here if any changes have been made to the plans that are not a
result of corrections from this list. If there are other changes, please briefly
describe them and where they are located in the plans.
City of Carlsbad 03-742
3/24/03
VALUATION
JURISDICTION: City of Carlsbad
PREPARED BY: Doug Moody
AND PLAN CHECK FEE
PLAN CHECK NO.: 03-742
DATE: 3/24/03
BUILDING ADDRESS: 1935 Calle Barcelona Suite 176
BUILDING OCCUPANCY: B TYPE OF CONSTRUCTION: VN
1994 UBC Building Permit Fee
1994 UBC Plan Check Fee -7
Type of Review:
0 Repetitive Fee 71 Repeats
Complete Review 0 Structural Only
0 Other
I $320.831
I $208.541
Hourly I I Hour *
Esgil Plan Review Fee 0
Comments:
Sheet 1 of I
rnacvalue.doc
PLANNINC/ENGINEERING APPROVALS
PERMIT NUMBER CB 03 O7Lt.a- DATE
RESIDENTIAL (TENANT IMPROVEMENT )
RESIDENTIAL ADDITION MINOR PLAZA CAMINO REAL
( < $10,000,00)
CARLSBAD COMPANY STORES
VILLAGE FAIRE
COMPLETE OFFICE BUILDING
OTHER
PLANNER DATE t I7103 L
ENGfNEER
Carlsbad Fire Department 030742
1635 Faraday Ave.
Carlsbad, CA 92008 Fire Prevention / (760) 602-4660 ,&/ Plan Review Requirements Category: Building Plan
Date of Report: 3.17.03 Reviewed by: ,&/ Plan Review Requirements Category: Building Plan
Date of Report: 3.17.03 Reviewed by:
Name: Hank Krastman JI
Address: 20610 Romar Street
City, State: Chatsworth CA 9131 1
Job#: 030742 Plan Checker:
Job Name: Coffee Bean & Tea Bldq #: CB030742
Job Address: 1935 Calle Barcelona Ste. or Bldg. No.
Approved The item you have submitted for review has been approved. The approval is
based on plans, information and / or specifications provided in your submittal;
therefore any changes to these items after this date, including field
modifications, must be reviewed by this office to insure continued conformance
with applicable codes and standards. Please review carefully all comments
attached as failure to comply with instructions in this report can result in
suspension of permit to construct or install improvements.
0 Approved
Subject to
The item you have submitted for review has been approved subject to the
attached conditions. The approval is based on plans, information and/or
specifications provided in your submittal. Please review carefully all comments
attached, as failure to comply with instructions in this report can result in
suspension of permit to construct or install improvements. Please resubmit to
this office the necessary plans and / or specifications required to indicate
compliance with applicable codes and standards.
0 Incomplete The item you have submitted for review is incomplete. At this time, this office
cannot adequately conduct a review to determine compliance with the
applicable codes and / or standards. Please review carefully all comments
attached. Please resubmit the necessary plans and / or specifications to this
office for review and approval.
Review 1 st 2nd 3 rd Other Agency ID
I FD Job # 030742 FD File #
CITY OF CARLSBAD POLICIES AND PROCEDURE
S ECTI 0 N ; BU 1 LD I NG DEP ARTM E NT
'URPOSE: PROVIDE INSTALLATION STANDARDS FOR ALL ROOF MOUNTED EQUIPMENT AND
PENETRATIONS ON COMMERCIAL AND INDUSTRIAL BUILDINGS,
NTENT: A.
6, C.
POLICY: 'I.
2.
3.'
4,
ti.
6.
7.
Maintain roof integrity. ,
Prevent hazardous condition to firemen who must fight ilre on the roof. Provide an Installation that is aesthetically sensltfve to the building and the ad joining pro pe rt ie 8,
All equipment shall be concealed from view and the design' shall meet the
approval of the Planning Department,
All equipment shall be specifically designed and approved for exterior use and shall be approved by the City of Caflsbad Suilding Department.
All roof mounted equipment shall be on a platform whlch shall be an lntegral
part of the roof--flashed and waterproofed. When a screen is'approved, it shall have 8s few root connections as possible and be structurally adequate.
All electrical, plumbing, mechanical duct work and related piping shall be inside
the buitding'and not an the roof. All connections retated to equipment shall be
made in the same roof opening on the platform or have the prior approval from
the building official. Sewer vents shall be brought to one main vent below the roof and have one
penetration where resttooms or other plumbing fixtures are back ta back or In the general proximity.
Air exhaust fans and other equipment shall be within the building and use the
8ams roof opsning where restrooms and other equipment are back to back or In
general proximity,
Existing buildings and equipment, remodel or replacement, shall meet the above
regulations or shall have the prior approval from the building official,
Whcrc ncw squtprncnt is installed, unused or ebendonsd equipment, including
all roof mounted piping, electrical, mechenical, duct, and other related
appurtenances shall be removed from roof end unused dpenings properly sealed .to maintain roof integrity,
*The architect should, through desfgn, conceal the heatlng/AC unlt and Oth8r equipment whether they are gn the roof or d$ewhere,
tnitiatod Ey:
1 O/ 14/03
City of Carlsbad
Building Department
1635 Faraday Ave.
Carlsbad, CA 92008
Re! Coffee Bean & Tea Leaf #8S
The Forum at Cartsbad
1935 Calle Barcelona, Suite #176
Carlsbad, CA 92009
To whom it may concern:
Our client has approved the use of rigid spiral ductwork with flex duct
in place of the rigid rectangular ductwork with flex duct shown on the permit plans. We have no problem with this substitution.
Sincerely ,
/Michael R. Btack, AIA
California License # : C26839
VENDOR llsT
MK
w.a
u1.0 U.0
U4.0
I DRAW
ARCHfl
M. 1 M.2
M.3 a1.1
A2.1 h3.1 a.2
CJJ
M. 1
45.1 Ah1
A7.1 A72
A7.3
h7.4 M.1
A8.2 w
a4
INVOICE FOR PROFESSIONAL SERVICES
WESRI ENGI"G
2180 GARNET AVE, SUITE 2B
SAN DIEGO, CALLwRloL4 92109 IPI 858 273 6701, [FJ 868 273 6758
[ormil] MIKEMESRI@AOL.COM
DATE! April 16,2003
CLIENT: PDMS, CARE OFMR. BRAD DEZKACH
PROJECT: EQUIP. SWPORT @ COFFEE BEAN;ANP TEA LEAP
JOB NO.: 0321.
TOTAL FHR: s(j00
AMOUNT PAID: S300CMANK YOU)
AMOIINT DUE S300
MESRl ENGINEXRING INC.
STRUCTURAL CONSULTING
2f 80 GAR!!T A\%., SUITE 2E SAY DI&Go, CALIFORNU 92109 IP1858 273 8701, [F] 858 273 6758 urnall: ralkcmri@aol.com
03q
0 I 'I 0
a
I
r. UI
F ACS I MI LE TRANS MI T TAL
Trammission Date:
# Of Pages Including Cover:
20 39Vd SWad EGIbEESLT8 80 :80 E002/02/90
I. YL
mil
Pwl Y0d.r
Phano : Wl et0 lB00
E0 33Vd SWad
bO 39Wd SWad ESTbEE9LI8 80 :80 E002/02/90
#!&?LW3lISSIW VERIFXCATION REPORT
1
TIME : 06/17/2003 13:00
MODE
86/17 12:59 185827367586666 00: 01 : 44 03 OK STQNDnRD
50 39Vd SWad
July 16,2003
Mesri Engineering, Inc.
2180 Garnet Ave., ste 2E
San Diego, CA 92109
Attn: Michael Mesri
Re: The forum at Carlsbad.
Dear Mr. Mesri:
In accordance with your request, please find attached specialty joist calculations for the above referenced
project. Based on the information provided, the product specified in the attached calculations meets or
exceeds code accepted design values for the application, span and loads listed.
It should be noted that project construction documents were not reviewed by Trus Joist (TJ) Engineering
and the application, span and loads listed on the attached calculations were provided by others. The
Professional Engineer’s seal on this letter solely indicates that the allowable product values shown are in
accordance with current TJ materials and code accepted design values.
Thank you for your interest in our products. Please contact us at (949) 616-1600 if we may be of further
assistance.
Sincerely,
Mark A. Lowe
Product Engineer
Attachments: (1) TJBeamTM Calculation(s) for Type “N’- 14“ TJIWL65 roof joists.
tj
Western Regionol Office A 27042 Towne Centre Owe, Suite 200 A Foothill Ranch, Californio 92610 A Phone 949 616 1600 A Fox 949 616 161
Type "N"
Load Case #I
User 4 6/17/03 11 20 17 AM 14" TJI@/L65 @ 32" o/c - Page 1 Engine Version 1 6 44 THIS PRODUCT MEETS OR EXCEEDS THE SET DESIGN
CONTROLS FOR THE APPLICATION AND LOADS LISTED
Member Slope: -.#VI2 Roof Slope-.49fl2 1
a: :o
I I 9 21' 8" 0
All dimensions are horizontal. Product Diagram is Conceptual.
LOADS:
Analysis is for a Joist Member.
Primary Load Group - Roof (psf): 20.0 Live at 125 % duration, 15.0 Dead
Vertical Loads:
Type Class Live Dead Location Application Comment
Point(plf) Roof(l.25) 72.0 161 .O 6' 6" Tower Wall Perpendicular
Point(1bs) Roof(1.25) 0 182 11'6' 1450# MU over 4 joists
Point(lbs) Roof(1.25) 0 182 16'6 145W MU over 4 joists
SUP PORTS :
Input Bearing Vertical Reactions (Ibs) Ply Depth Nailing Detail Other
Width Length LivelDeadlUplifUTotaI Depth
1 Glulam or solid sawn lumber beam 2.50" Hanger 710 I 861 IO / 1571 1 14.01" NIA Top Mount Hanger None
2 Glularn or solid sawn lumber beam 3.50" Hanger 637 I 800 IO I 1437 1 14.01" NIA Top Mount Hanger None
-Web stiffeners are required at support(s): 1, 2. See TJI JOIST INSTALLATION INFORMATION for nailing requirements
HANGERS: Simpson Strong-Ti& Connectors
support Model Slope Skew Reverse
Flanges
1 Top Mount Hanger LBV314XD2 -.49/12 0 NIA
2 Top Mount Hanger LBV314XU2 -.49112 0 NIA
-Nailing for Support 1 : Face: 2-N10 , Top 4-N10 , Member: 2-N10
-Nailing for Support 2: Face: 2-N10 , Top 4-N10 , Member: 2-N10
DESIGN CONTROLS:
Maximum Design Control Control
Shear (Ibs) 1552 1552 2656 Passed (58%)
Vertical Reaction (Ibs) 1552 1552 2656 Passed (58%)
Moment (Ft-Lbs) 8544 8544 9569 Passed (89%)
Live Load Defl (in) 0.479 1.059 Passed (LI530)
Total Load Defl (in) 1.131 1.412 Passed (U225)
-Deflection Criteria: MINIMUM(LL:LI240,TL:U180).
Top Flange Top Flange Support Wood
Offset Slope Species
No 0 Douglas Fir
No 0 Douglas Fir
Location
Lt. end Span 1 under Roof loading
Bearing 1 under Roof loading
MID Span 1 under Roof loading
MID Span 1 under Roof loading
MID Span 1 under Roof loading
-Bracing(Lu): All compression edges (top and bottom) must be braced at 3' 8" olc unless detailed otherwise. Proper attachment and positioning of
lateral bracing is required to achieve member stability.
PROJECT INFORMATION:
The Forum at Carlsbad
Building 8 Roof
Carlsbad, CA
SC02E02064
OPERATOR INFORMATION:
Paul Yoder
Phone : 949 616 1600
Copyright 01 2003 by TIUS Joist, a Weyerhaeuser Business
TJ10 and TJ-BeamM are registered trademarks of TTCS Joist. e-I Joistw,Prow and TJ-Pro- are trademarks of TLUS Joist. Simpson Strong-Trem Connectors is a registered trademark of Simpson Strong-Tie Company, Inc.
G:\TJCADD\J0S\SC02EOZD64\Des~gns\Sizing\PavBldg~\TypeN~l.sms
Type "N"
Load Case #I +?g!&!&@L* TJ-Beam(TM) 6.06 Serial du%~?%$%%2!
User: 4 6/17/03 ll:20:1BAM 14" TJI@/L65 @ 32" o/c
THIS PRODUCT MEETS OR EXCEEDS THE SET DESIGN
CONTROLS FOR THE APPLICATION AND LOADS LISTED
Page 2 Engine Version 1.6.44
AkDMTt01(tkl;TWTES:
-IMPORTANT! The analysis presented is output from software developed by Trus Joist (TJ). Allowable product values shown are in accordance with
current TJ materials and code accepted design values. TJ Engineering has verified the analysis. The input loads and dimensions have been provided
by others ( ) and must be verified and approved for the specific application by the design professional for
the project.
-Allowable Stress Design methodology was used for Building Code UBC analyzing the TJ Custom product listed above.
-(Minimum cut length) = (Overall horizontal length) x 1.001 + 9/16'
-THIS ANALYSIS FOR TRUS JOIST PRODUCTS ONLY! PRODUCT SUBSTITUTION VOIDS THIS ANALYSIS.
PROJECT INFORMATION:
The Forum at Carlsbad
Building 8 Roof
Carlsbad, CA
SC02E02064
OPERATOR INFORMATION:
Paul Yoder
Phone : 949 616 1600
Copyright E2 2003 by Trus Joist, a Weyerhaeuser Business
TJIW and TJ-Beam are regisrered trademarks of Trus Joist. e-I JolStn,Pro" and TJ-Pro- are trademarks of Trus Joist. Simpson Strong-Tie(* Connectors is a registered trademark of Simpson Strong-Tie Company, Inc.
G:\TJCADD\JOB\SCO2EOZO64\Desigl'.s\Slz~n~\PavBldg~\TypeNLl.sms
s
J
3 ps
3 4 +- 3 s’
09-23-2003
Job Address:
Permit Type:
Parcel No:
Valuation: Reference #:
Project Title:
Applicant: FERGUSON DAVID
909 534-4 18 1
City of Carlsbad
1635 Faraday Av Carlsbad, CA 92008
Plan Check Revision
Building Inspection Request Line (760) 602-2725
Permit No: PCR03193
1935 CALLE BARCELONA CBAD St: 176
PCR Status: ISSUED
Lot#: 0 Applied: 09/09/2003
$0.00 Construction Type: NEW Entered By: MDP
CB03 742 Plan Approved: 09/23/2003 Issued: 09/23/2003
COFFEE BEAN & TEA LEAF
REVISE PLUNBING & ELECTRICAL
Inspect Area:
Owner:
Plan Check Revision Fee
Additional Fees
$90.00
$0.00
Total Fees: $90.00 Total Payments To Date: $0.00 Balance Due: $90.00
4825 09/23/03 0002 01 02
CGP 90.00
PERMIT -APPLICATION PLAN CHECK NO.
CITY OF CARLSBAD BUILDING DEPARTMENT
Legal Description Lot No. Subdivision NamelNumber Unit No. Phase No. Total # of units
Proposed Use
# of Bedrooms # of Bathrooms
Existing Use E
SO. FT. #of Stories
Name Address City Statelzip Telephone #
(Sac. 7031.5 Business and Professions Code: Any City or County which requires a permit to construct, alter, improve, demolish or repair any structure, prior to its
issuance, also requires the applicant for such permit to file a signed statement that he is licensed pursuant to the provisions of the Contractor's License Law
[Chapter 9, commending with Section 7000 of Division 3 of the Business and Professions Code1 or that he is exempt therefrom, and the basis for the alleged
exemption. Any violation of Section 7031.5 by any applicant for a permit subjects the applicant to a civil penalty of not more than five hundred dollars [$5001).
Name Address City Statelzip Telephone #
State License # License Class City Business License #
Designer Name Address city Statelzip Telephone
State License #
8. WORKERS' COMPENSATION
Workers' Compensation Declaration: I hereby affirm under penalty of perjury one of the following declarations:
0 of the work for which this permit is issued.
0 issued. My worker's compensation insurance carrier and policy number are:
Insurance Company Policy No. Expiration Date
(THIS SECTION NEED NOT BE COMPLETED IF THE PERMIT IS FOR ONE HUNDRED DOLLARS IS1001 OR LESS)
0 CERTIFICATE OF EXEMPTION: I certify that in the performance of the work for which this permit is issued, I shall not employ any person in any manner so as
to become subject to the Workers' Compensation Laws of California.
WARNING: Fallure to aecure worked compenaation covarage la unlawful, and ahall subject an employer to criminal penalties and civil finea up to one hundred
thousand dollara (8100,000~. in addition to the cost of compensation, damages at provided for in Section 3706 of the Labor code, interest and attorney's fees.
I have and will maintain a certificate of consent to self-insure for workers' compensation as provided by Section 3700 of the Labor Code, for the performance
I have and will maintain workers' compensation, as required by Section 3700 of the Labor Code, for the performance of the work for which this permit is
SIGNATURE DATE
OWNER-BU~DEW,D~CWRATION- c-
I hereby affirm that I am exempt from the Contractor's License Law for the following reason:
0 I, as owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not intended or offered for sale
(Sec. 7044, Business and Professions Code: The Contractor's License Law does not apply to an owner of property who builds or improves thereon, and who does
such work himself or through his own employees, provided that such improvements are not intended or offered for sale. If, however, the building or improvement is
sold within one year of completion, the owner-builder will have the burden of proving that he did not build or improve for the purpose of sale).
0 I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions Code: The
Contractor's License Law does not apply to an owner of property who builds or improves thereon, and contracts for such projects with contractor(s1 licensed
pursuant to the Contractor's License Law).
0
1.
2.
3.
I am exempt under Section
I personally plan to provide the major labor and materials for construction of the proposed property improvement. 0 YES UNO
I (have I have not) signed an application for a building permit for the proposed work.
I have contracted with the following person (firm) to provide the proposed construction (include name / address I phone number I contractors license number):
Business and Professions Code for this reason:
4.
number I contractors license number):
5.
of work):
I plan to provide portions of the work, but I have hired the following person to coordinate, supervise and provide the major work (include name / address I phone
I will provide some of the work, but I have contracted (hired) the following persons to provide the work indicated (include name / address / phone number I type
PROPERTY OWNER SIGNATURE DATE
&l
Is the applicant or future building occupant required to submit a business plan, acutely hazardous materials registration form or risk management and prevention
program under Sections 25505, 25533 or 25534 of the Presley-Tanner Hazardous Substance Account Act? 0 YES 0 NO
Is the applicant or future building occupant required to obtain a permit from the air pollution control district or air quality management district7
Is the facility to be constructed within 1,000 feet of the outer boundary of a school site? 0 YES 0 NO
IF ANY OF THE ANSWERS ARE YES, A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR IS MEETING THE
REQUIREMENTS OF THE OFFICE OF EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT.
0 YES 0 NO
LENDERS ADDRESS
I certify that I have read the application and state that the above information is correct and that the information on the plans IS accurate. I agree to comply with all City ordinances and State laws relating to building construction. I hereby authorize representatives of the Citt of Carlsbad to enter upon the above mentioned property for inspection purposes. I ALSO AGREE TO SAVE, INDEMNIFY AND KEEP HARMLESS THE CITY OF CARLSBAD AGAINST ALL LIABILITIES,
JUDGMENTS, COSTS AND EXPENSES WHICH MAY IN ANY WAY ACCRUE AGAINST SAID CITY IN CONSEQUENCE OF THE GRANTING OF THIS PERMIT.
OSHA: An OSHA permit is required for excavations over 5'0" deep and demolition or construction of structures over 3 stories in height.
EXPIRATION: Every permit issued by the building Official under the provisions of this Code shall expire by limitation and become null and void if the building or work
authorized by such permit is not commenced within 180 days from the date of such permit or if the building or work authorized by such permit is suspended or abandoned
at any time after the work is commenced for a period of 180 days (Section 106.4.4 Uniform Building Code).
APPLlCl T'S SIGNATURE DATE
WHITE: File YELLOW: Applicant PINK: Finance
EsGil Corporation
In Partnership with Gwemment for QuiUing safety
DATE: 9/23/03
JURISDICTION: Carlsbad 0 PLANREVIEWER
0 FILE PLAN CHECK NO.: 03-742 (PCRO3-193) SET:- 1, Set I1
PROJECT ADDRESS: 1935 Calle Barcelona, Suite 176
PROJECT NAME: Coffee Bean & Tea Leaf TI, Plumbing Revisions
0
rn
0
0
0
0
0
rn
The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
The remarks listed below are transmitted herewith for your information. The plans are being
held at Esgil Corporation until corrected plans are submitted for recheck. Submit responses
and revisions to the City of Carlsbad or directly to EsGil Corp. for recheck
The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
The applicant's copy of the check list has been sent to:
Esgil Corporation staff did not advise the applicant that the plan check has been completed.
Esgil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Guy
Date contacted:
Mail Telephone Fax In Person
rn REMARKS: The attached
of plans to make a 2nd set
incorporated into the city set
in red on the plans from
EsGil.
By: Chuck Mendenhall Enclosures:
Esgil Corporation 0 GA 0 MB 0 EJ 0 PC FAX In tmsmtl.dot
EsGil Corporation
In %rtnersfiip with Government for Building Sufety
DATE: 9/17/03
J U Rl SD l CTl ON : Carlsbad 0 PLAN REVIEWER
0 FILE
PLAN CHECK NO.: 03-742 (PCRO3-193) SET:REV 1, Set I
PROJECT ADDRESS: 1935 Calle Barcelona, Suite 176
PROJECT NAME: Coffee Bean & Tea Leaf TI, Plumbing Revisions
0
0
0
The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction’s building codes.
The plans transmitted herewith will substantially comply with the jurisdiction’s building codes
when minor deficiencies identified below are resolved and checked by building department staff.
The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
The remarks listed below are transmitted herewith for your information. The plans are being
held at Esgil Corporation until corrected plans are submitted for recheck. Submit responses
and revisions to the City of Carlsbad or directly to EsGil Corp. for recheck
The applicant’s copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
The applicant’s copy of the check list has been sent to:
mHAwd oc LUCY 3 (~,Lf)890-LbkS
Esgil Corporation staff did not advise the applicant that the plan check has been completed.
Esgil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: David Ferguson
Date contacted: ?//?b3 (by: ) Fax #:
Telephone #: (909) 534-4181
Mail Telephone4 Fax/ In Person
REMARKS: 1. The revised sanitary waste riser diagram shown on sheet P2.0 for the bath room
showing a water closet, FD and sink on combination waste and vent line does not comply with
the code. Provide a separate vertical vent for the water closet. All other revisions are OK
By: Chuck Mendenhall
Esgil Corporation
Enclosures:
0 GA 0 MB EJ 0 PC 9/11/03 tmsrntl.dot
9320 Chesapeake Drive, Suite 208 + San Diego, California 92123 + (858) 560-1468 Fax (858) 560-1576
c=_-
~
VALUATION AND PLAN CHECK FEE
Plan Check Fee bv Ordinance
JURISDICTION: Carlsbad PLAN CHECK NO.: 03-742 (PCR03-193)
7
PREPARED BY: Chuck Mendenhall DATE: 9/17/03
BUILDING ADDRESS: 1935 Calle Barcelona, Suite 176
BUILDING OCCUPANCY: B TYPE OF CONSTRUCTION: VN
Type of Review: 0 Complete Review
Repetitive Fee Repeats
0 Structural Only
Cl Other
Hourly 10.751 Hour*
Esgil Plan Review Fee
I $90.001
I $72.001
* Based on hourly rate
Comments:
Sheet 1 of 1