HomeMy WebLinkAbout1945 PALOMAR OAKS WAY; ; CB073181; PermitCity of Carlsbad
1635 Faraday Av Carlsbad, CA 92008
01-31-2008 Mechanical Permit Permit No: CB073181
Building Inspection Request Line (760) 602-2725
Job Address: 1945 PALOMAR OAKS WY CBAD
Permit Type: MECH Status: ISSUED
Parcel No: 2130910200 Lot #: 0 Applied' 12/24/2007
Valuation: $0.00 Entered By: JMA
Reference #' Plan Approved 01/31/2008
Issued 01/31/2008
Project Title: SENDEX: INSTALL DUCTLESS SPLIT Inspect Area:
NC SYSTEM IN SERVER ROOM
Applicant: Owner:
XNERGY ARDEN REALTY LTD PTNSHP
STE100
2237 FARADAY AV 11601 WILSHIRE BLVD 4TH FL
CARLSBAD CA 92008 LOS ANGELES CA 90025
438-7676
Mechanical Issue Fee $1500
Install/Furn/Ducts/Heat Pumps Fee I $900
Fireplace Installation Fee 0 $000
Exhaust Fan Fee 0 $0.00
Installation/Relocation Vent Fee 0 $0.00
Hood Fee 0 $0.00
Boiler/Compressor to 15HP Fee 0 $000
Other $200.00
Additional Fees $0.00
TOTAL PERMIT FEES $22400
Total Fees: $224.00 Total Payments To Date: $224.00 Balance Due: $0.00
FINAL APPRQVAL
Inspector: L44 lc2t4 Date: b'hI
f
V5/o '3. Clearance:
NOTICE. Please take NOTICE that approval of your project includes the imposition of fees, dedications, reservations, or other exactions hereafter collectively
referred to as fees/exactions. You have 90 days from the date this permit was issued to protest imposition of these fees/exactions. If you protest them, you must
follow the protest procedures set forth in Government Code Section 66020(a), and file the protest and any other required information with the City Manager for
processing in accordance with Carlsbad Municipal Code Section 3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack,
review, set aside, void, or annul their imposition.
'You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection fees and capacity
changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this project NOR DOES IT APPLY to any
fees/exactions of which you have oreviouslv been given a NOTICE similar to this, or as to which the statute of limitations has oreviously otherwise expired.
City of Carlsbad
1635 Faraday Ave., Carlsbad, CA 92008
760-602-2717 / 2718 / 2719
Fax: 70-602-8558
Building Permit Application
Plan Check No.C27 07 3(9-/
Est. Value
Plan Ck. Deposit
Date 12,
JOB ADDRESS
CTCY
SUITE#/SPACE#/UNiTA I APN
-
1T C
PHASE C OF UNITS C BEDROOMS A BATHROOMS TENANT BUSINESS NAME CONSTR PE 0CC GROUP
DESCRIPTION OF WORK:
_
i./L ccAA.J - z;1 ,'c M / clui
EXISTING USE PROPOSED USE GARAGE (SF) PATIOS (SF) DECKS (SF) I FIREPLACE
YES 0 #_ NO 0
AIR CONDITIONING
YE-921W NO 0
I FIRE SPRINKLERS
YES 0 NOD
CONTACT lE (If Different Fom APPIIcant4_t
— Aj —
APPLICANT NAPE
14 ADDRESS
kr- .4
ADDRESS
CITY STATE ZIP
cdc1L
CITY STATE ZIP
PHONE 7 p - 6
- FAX PHONE
/
FAX
EMAIL EMAIL
PROPERTY OWNER NAME
- bJ
N., CON
__
ACTOR BUS. NAME
ADDRESS J
CITY STATE ZIP CITY STATE ZIP
PHONE . FAX PHONE FAX
EMAIL EMAIL
ARCH/DESIGNER NAME & ADDRESS STATE LIC C hSTATE LIC C CLASS l iTY BUS LIC C
tZ2-72-O
Sec ISiS I S Business and Professions Code Any City or County which requires a permit to construct alter improve. demolish or repair any structure prior to its Issuance, also requires the applicant for such permit to file a signed statement that he is icenitd pursuant to the provinioni of the Contractors license Law {(hapter 9. commending with Section 1000 of Division 3 of the Business and Preeasions Code) or that he is exempt therefrom, and the basis for the alleged exemption. Any violation of Section 10315 by any applicant for a permit subjects the applicant to a civil penalty of not more than live hundred dollars {$500})
4j
Workers' Compensation Declaration I hereby,affirm under penalty of perjury one of the following declarations IJ I have and will maintain a certificate of consent to self-insure for workers' compensation as provided by Section 3700 of the Labor Code, for the performance of the work for which this permit is issued
have and will maintain workers' compe s ti on, as required by Section 3700 of the Labor Code, for the performance of the work hich t is erm i issued My workers' compensation insurance cam ad policy
number are Insurance Co ' Policy No 'j / 0 Expiration Date J 0 0
This section need not be completed if the permit is for one hundred dollars ($100) or less J Certificate of Exemption: I certify that in the performance of the work for which this permit is issued, I shall not employ any person in any manner so as to become subject to the Workers' Compensation Laws of
California WARNING: Failure to secure workers' compens ion coverage is unlawful, and shall subject an employer to criminal penalties and civil fines up to one hundred thousand dollars (&100,000), in
addition to the cost of compensation, damages as provid o n 3706 of the Labor code, interest and attorney's fees.
CONTRACTOR SIGNATURE DATE 41—() 7
thereby affirm that lam exempt from Contractor's License Law for the following reason
0 I, as owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not intended or offered for sale (Sec. 7044, Business and Professions Code The Contractor's
License Law does not apply to an owner of property who builds or improves thereon, and who does such work himself or through his own employees, provided that such improvements are not intended or offered for
sale If, however, the building or improvement is sold within one year of completion, the owner-builder will have the burden of proving that he did not build or improve for the purpose of sale)
0 I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec 7044, Business and Professions Code The Contractors License Law does not apply to an owner of
property who builds or improves thereon, and contracts for such projects with contractor(s) licensed pursuant to the Contractor's License Law)
0 I am exempt under Section ______________Business and Professions Code for this reason
1 I personally plan to provide the major labor and materials for construction of the proposed property improvement 0 Yes 0 No
2 I (have / have not) signed an application for a building permit for the proposed work
3 I have contracted with the following person (firm) to provide the proposed construction (include name address I phone / contractors' license number)
4 I plan to provide portions of the work, but I have hired the following person to coordinate, supervise and provide the major work (include name! address / phone contractors' license number)
5 I will provide some of the work, but I have contracted (hired) the following persons to provide the work indicated (include name! address / phone I type of work)
ii PROPERTY OWNER SIGNATURE DATE
Is the applicant or future building occupant required to submit a business plan, acutely hazardous materials registration form or risk management and prevention program under Sections 25505, 25533 or 25534 of the
Presley-Tanner Hazardous Substance Account Act? 0 Yes ulo
Is the applicant or future building occupant required to obtain a permit from the air pollution control district or air quality management district? 0 Yes CISQo Is the facility to be constructed within 1,000 feet of the outer boundary of a school site? 0 Yes 'No
IF ANY OF THE ANSWERS ARE YES, A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR IS MEETING THE REQUIREMENTS OF THE OFFICE OF
EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT.
' :1v unrty'-'ui "K 7riFj ,4 J tt!Jt°j uxiv k'u. 0€ —
I hereby affirm that there is a construction lending agency for the performance of the work this permit is issued (Sec. 3097 (i) Civil Code),
Lender's Name Lender's Address
_F3Tf
I certify that I have read the application and state that the above information is correct and that the information on the plans is accurate. I agree to complywith all City ordinances and State laws relating to building construction.
L,hereby authorize representative of the City of Carlsbad to enter upon the above mentioned property for inspection purposes I ALSO AGREE TO SAVE, INDEMNIFY AND KEEP HARMLESS THE CITY OF CARLSBAD
AGAINST ALL LIABILITIES, JUDGMENTS, COSTS AND EXPENSES WHICH MAY IN ANYWAY ACCRUE AGAINST SAID Cfl) INCONSEQUENCE OF THE GRANTING OF THIS PERMIT
OSHA An OSHA permit is required for excavations over 50' deep and demolition or construction of structures over 3 stones in height
EXPIRATION Every permit issued by the Building Official under the provisions of this Code shall expire by limitation and become null and void if the building or work authorized by such permit is not commenced within
180 days from the date of such permit or if the building or a zed by such permit is suspended or abandoned at any time after the work is commenced for a period of 180 days (Section 106.44 Uniform Building Code)
.'APPLICANT'S SIGNATURE DATE /2 c21' —
City of Carlsbad Bldg Inspection Request
For 06/20/2008
Permit# CB073181 Inspector Assignment: RB
Title: SENDEX: INSTALL DUCTLESS SPLIT
Description: NC SYSTEM IN SERVER ROOM
Type: MECH Sub Type:
Phone: 7606033425
Job Address. 1945 PALOMAR OAKS WY
Suite: Lot 0
Location: inspector:
APPLICANT XNERGY
Owner: ARDEN REALTY LTD PTNSHP
Remarks:
Total Time. Requested By: BARRY
Entered By: JANEAN
CD Description Act Comment
49 Final Mechanical I. ''SIP .._1O tA& $
Comments/Notices/Holds
Associated PCRs/CVs Original PC#
Inspection History ,S. La6 _ t cf Date Description Act Insp Comments
02/01/2008 44 Rough/Ducts/Dampers CO RB SEE NOTIC
02/01/2008 49 Final Mechanical CO RB
t1-'44.
J
EsGil Corporation
In Partnership with government for Bui(tfing Safety
DATE: January 23, 2008
JURISDICTION: Carlsbad
PLAN CHECK NO.: 07-3181
PROJECT ADDRESS: 1945 Palomar Oaks Way
PROJECT NAME: Sendx Server room AC Unit
SET: II
U APPLICANT
U PLAN REVIEWER
U FILE
The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
Lii The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
The applicant's copy of the check list has been sent to:
Esgil Corporation staff did not advise the applicant that the plan check has been completed.
Esgil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Telephone #:
Date contacted: (by: ) Fax #:
Mall Telephone Fax In Person
LII REMARKS:
By: Bryan Zuppiger Enclosures:
Esgil Corporation
El GA 0 MB [] EJ El pc 01/14/2008
trnsmtl dot
9320 Chesapeake Drive, Suite 208 • San Diego, California 92123 • (858) 560-1468 • Fax (858) 560-1576
EsGil Corporation
In (Partners/lip with government for Bui(iing Safety
DATE: January 8, 2008
JURISDICTION: Carlsbad
PLAN CHECK NO.: 07-3181 SET: I
PROJECT ADDRESS: 1945 Palomar Oaks Way
PROJECT NAME: Sendx Server room AC Unit
çP
22LJANT
(yj )
U PLAN REVIEWER
U FILE
LII The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected-plans are submitted for recheck.
LII The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
The applicant's copy of the check list has been sent to:
Allan Lehr
2721 Loker Avenue West
Carlsbad, CA 92010
LI Esgil Corporation staff did not advise the applicant that the plan check has been completed.
Esgil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted All n,ehr Telephone #: 760 576 7851
Date cojacted p-v Fax #: - '.4!' 70 '1
Mail y4elephone " Fax In Person
LI REMARKS: Co")
By: Bryan Zuppiger Enclosures:
Esgil Corporation
LI GA LI MB LI EJ LI Pc 12/26/2007
tmsmtl.dot
9320 Chesapeake Drive, Suite 208 • San Diego, California 92123 • (858) 560-1468 • Fax(858)560-1576
Carlsbad 07-3181
January 8, 2008.
PLAN REVIEW CORRECTION LIST
TENANT IMPROVEMENTS
PLAN CHECK NO.: 07-3181
DATE PLANS RECEIVED BY
JURISDICTION:
DATE INITIAL PLAN REVIEW
COMPLETED: January 8, 2008
FOREWORD (PLEASE READ):
JURISDICTION: Carlsbad
DATE PLANS RECEIVED BY
ESGIL CORPORATION: 12/26/2007
PLAN REVIEWER: Bryan Zuppiger
This plan review is limited to the technical requirements contained in the Uniform Building Code,
Uniform Plumbing Code, Uniform Mechanical Code, National Electrical Code and state laws
regulating energy conservation, noise attenuation and access for the disabled. This plan review is
based on regulations enforced by the Building Department. You may have other corrections based
on laws and ordinances enforced by the Planning Department, Engineering Department, Fire
Department or other departments. Clearance from those departments maybe required prior to the
issuance of a building permit.
Code sections cited are based on the 2001 CBC that adopts the 1997 UBC..
The following items listed need clarification, modification or change. All items must be satisfied
before the plans will be in conformance with the cited codes and regulations. Per Sec. 106.4.3, 1997
Uniform Building Code, the approval of the plans does not permit the violation of any state, county or
city law.
To speed up the recheck process, please note on this list (or a copy) where each correction
item has been addressed, i.e., plan sheet number, specification section, etc. Be sure to
enclose the marked up list when you submit the revised plans.
TENANT IMPROVEMENTS WITHOUT SPECIFIC ENERGY DATA OR POLICY SUPPLEMENTS (1997UBC) tiforw.dot
Carlsbad 07-3181
January 8, 2008
. PLANS
Please make all corrections on the originals and submit two new complete sets of prints to
Esgil Corporation, 9320 Chesapeake Drive, Suite 208, San Diego, California 92123, (858)
560-1468.
Provide a statement on the Title Sheet of the plans stating that this project shall comply with
the 2001 editions of the California Building/Plumbing/Mechanical Codes and the 2004 edition
of the California Electrical Code that adopt the 1997 UBC, 2000 UMC, 2000 UPC and the
2002 NEC.
Roof mounted equipment must be screened and roof penetrations should be minimized. City
Policy 80-6. Please imprint the attached.
Indicate wiring method, i.e. EMT, metal flex and conductor sizes on the plans.
The City requires the following notes on the plans:
WIRING METHODS: AC Cable is not allowed in A, B, E, H and I occupancies.-NM cable is
restricted (without City approval) to one and two family dwellings. Note on plans that an
equipment ground conductor is to be installed in all flexible conduits.
The use of flexible metal conduit as a grounding means must comply with City Policy 84-36.
No wiring is permitted on the roof of a building and wiring on the exterior of a building requires
approval by the Building Official. City Policy.
The person responsible for their preparation must sign all final sheets of plans. (California
Business and Professions Code).
To speed up the review process, note on this list (or a copy) where each correction item has
been addressed, i.e., plan sheet, note or detail number, calculation page, etc.
The jurisdiction has contracted with Esgil Corporation located at 9320 Chesapeake Drive,
Suite 208, San Diego, California 92123; telephone number of 858/560-1468, to perform the
plan review for your project. If you have any questions regarding these plan review items,
please contact Bryan Zuppiger at Esgil Corporation. Thank you.
Carlsbad 07-3181
January8, 2008
VALUATION AND PLAN CHECK FEE
JURISDICTION: Carlsbad PLAN CHECK NO.: 07-3181
PREPARED BY: Bryan Zuppiger DATE: January 8, 2008
BUILDING ADDRESS: 1945 Palomar Oaks Way
BUILDING
PORTION
AREA
(Sq. Ft.)
Valuation
Multiplier
Reg.
Mod.
VALUE ($)
Air Conditioning
Fire Sprinklers
TOTAL VALUE
Jurisdiction Code JCb jBy Ordinance
vj
Plan Check Fee by Ordinance
Type of Review: El Complete Review El Structural Only
El Repetitive Fee El Other Repeats Hourly 1 1.51 Hours *
Esgil Plan Review Fee
* Based on hourly rate
Comments:
I $144.00]
macvalue.doc\
PLANNING/ENGINEERING APPROVALS
PERMIT NUMBER CB - /i / DATE
ADDRESS
RESIDENTIAL TENANT IMPROVEMENT
RESIDENTIAL ADDITION MINOR INO REAL
(<$17,000.00)
COMPLETE OFFICE BUILDING
OTHER
PLANNER
ENGINEER
I
DATE
DATE
CARLSBAD COMPANY STORES
VILLAGE FAIRE
oocslMisformslPlannlng Engineering Approvals
PLANNING DEPARTMENT
BUILDING PLAN CHECK REVIEW CHECKLIST
Plan Check No. CB0731 81 Address 1945 Palomar Oaks Way
Planner Deborah Milam Phone (760) 602-4619
APN:
co co M Type of Project & Use: Net Project Density: DU/AC
Zoning: _____ General Plan: Facilities Management Zone:
CFD (in/out) #_Date of participation:_____ Remaining net dev acres:_____
. (For non development: Type of land used created by this permit: Circle One
Legend: Z Item Complete LI Item Incomplete - Needs your action
LI LI Environmental Review Required: YES LI NO Z TYPE
DATE OF COMPLETION:
Compliance with conditions of approval? If not, state conditions which require action.
Conditions of Approval:
0 LI . Discretionary Action Required: YES LI NO 0 TYPE
APPROVAL/RESO. NO. DATE
PROJECT NO.
OTHER RELATED CASES:
Compliance with conditions or approval? If not, state conditions which require action.
Conditions of Approval:
LI 0 Coastal Zone Assessment/Compliance
Project site located in Coastal Zone? YES D NO D
CA Coastal Commission Authority? YES D NO 0
If California Coastal Commission Authority: Contact them at - 7575 Metropolitan Drive, Suite 103,
San Diego CA 92108-4402; (619) 767-2370
Determine status (Coastal Permit Required or Exempt):
0 LI Habitat Management Plan NA
Data Entry Completed? YES LI NO LI
If property has Habitat Type identified in Table 11 of HMP, complete HMP Permit application and
assess fees in Permits Plus
(AJP/Ds, Activity Maintenance, enter CB#, toolbar, Screens, HMP Fees, Enter Acres of Habitat Type
impacted/taken, UPDATE!)
LI LI Inclusionary Housing Fee required: YES El NO
(Effective date of Inclusionary Housing Ordinance - May 21, 1993.)
Data Entry Completed? YES LI NO LI
(NP/Ds, Activity Maintenance, enter CB#, toolbar, Screens, Housing Fees, Construct Housing Y/N,
Enter Fee, UPDATE!)
F:\Plan checks\cB073181 .doc Rev 3/06
Site Plan:
Provide a fully dimensional site plan drawn to scale. Show: North arrow, property lines, easements,
existing and proposed structures, streets, existing street improvements, right-of-way width,
dimensional setbacks and existing topographical lines (including all side and rear yard slopes).
Provide legal description of property and assessor's parcel number.
Policy 44 - Neighborhood Architectural Design Guidelines
El El 1. Applicability: YES II] NO
2. Project complies: YES 0 NOD
Zoning:
0 0 1. Setbacks:
Front: Required Shown
Interior Side: Required Shown
Street Side: Required Shown
Rear: Required Shown
Top of slope: Required Shown
0 0 2. Accessory structure setbacks:
Front: Required Shown
Interior Side: Required Shown
Street Side: Required Shown
Rear: Required Shown
Structure separation: Required Shown
0 0 Lot Coverage: Required Shown
0 0 Height: Required Shown
0 0 Parking: Spaces Required Shown
(breakdown by uses for commercial and industrial projects required)
El
Residential Guest Spaces Required Shown
Additional Comments: Correction #1: Please include APN and legal description on the title page.
Correction #2: Please include at least three building elevations to demonstrate how the proposed
equipment is shielded from street level.
OK TO ISSUE AND ENTERED APPROVAL INTO COMPUTER DATE
//f (a r
F:\Plan Checks\CB073181 .doc Rev 3106
Carlsbad Fire Department 3ULLII EII,V
COPY
Plan Review Requirements Category: MECH, APPROVED A S SUMMED
Date of Report: 12-31-2007 Reviewed by:
CAILSIz
Name:
ENT
Address:
Permit #: CB073181
Job Name: SENDEX: INTALL DUCTLESS SPLIT
Job Address: 1945 PALOMAR OAKS WY CBAD
submitted for review is incomplete. At this time, this office cannot
adequately conduct compliance with the applicable codes and/or standards. Please review a review to
carefully all comments attached. Please resubmit the necessary plans and/or specifications, with changes "clouded",
to this office for review and approval.
Conditions:
Cond: C0N0002529
[NOT MET]
Cond: C0N0002530
THIS PROJECT HAS BEEN REVIEWED AND APPROVED FOR THE PURPOSES OF ISSUANCE OF
BUILDING PERMIT.
THIS APPROVAL IS SUBJECT TO FIELD INSPECTION AND REQUIRED TEST, NOTATIONS HEREON,
CONDITIONS IN
CORRESPONDENCE AND CONFORMANCE WITH ALL APPLICABLE REGULATIONS.
THIS APPROVAL SHALL NOT BE HELD TO PERMIT OR APPROVE THE VIOLATION OF ANY LAW.
Entry: 12/31/2007 By: GR Action: AP