HomeMy WebLinkAbout1950 SILVERLEAF CIR; ; CB151870; PermitCity of Carlsbad
1635 Faraday Av Carlsbad, CA 92008
11 -05-2015 Cogeneration Permit Permit No:CB151870
Building Inspection Request Line (760) 602-2725
Job Address:1950 SILVERLEAF CR CBAD
Permit Type:COGEN Sub Type: PHOTO Status: ISSUED
Parcel No:2550121600 Lot #:0 Applied: 06/18/2015
Valuation:$342,000.00 Constuction Type: NEW Entered By:SLE
Occupancy Group:Reference #:Plan Approved:11/05/2015
Issued:11/05/2015
Inspect Area: AK
Plan Check #:
Project Title:LA COSTA GLEN: 855 MODULE PV
BALLAST MOUNT, FLUSH/ROOF, 269 KW
Applicant:Owner:
MHD STUDIO CONTINUING LIFE COMMUNITIES LLC
P.O. BOX 10894 1940 LEVANTE ST
TRUCKEE CA 96162 CARLSBAD CA 92009
530-550-9896
Building Permit $1,480.32 PLUMBING TOTAL $0.00
Add'I Building Permit Fee $0.00 ELECTRICAL TOTAL $0.00
Plan Check $1,036.22 MECHANICAL TOTAL $0.00
Add'I Plan Check Fee $0.00 Additional Fees $0.00
Plan Check Discount $0.00 •
Strong Motion Fee $95.76
Green Bldg Stands (SB1473) Fee $12.00
TOTAL PERMIT FEES $2,624.30
Total Fees:$2,624.30 Total Payments To Date:$2,624.30 Balance Due:$0.00
1
FINAL Al ROV L
Inspector:Date:Clearance:
NOTICE:Reese take NOTICE that approval cf yr:krpled indudes the "I rrpcsiticrr cf fees, de:Ica:ions, reservations, or otheroaliors hereafter oollectively
referred to as 'Tees/exalictis."You have 90 days from the date this part was issuedto attestimposition dthese feeektecticrs.If you protest than ycu rust
follow the protest procaine ast forth in Gaierrnent Code Section 66023(a), and file the protest andaryother rectired irforretion with the City Managerfa-
pnamsing in accadarte with Carlsbad Rridpal Cade Section 3.32030.Faille to timelyfdlaythat procedre will bar anyatsequart legal aliento attack,
re/16w, set aside, void,a and their imposition.
Youae hereby FURTHER NOTIFIED that yar right to protest the specified fees/stations DOES NOT'*FLYto miter and saner correction fees and capedty
changes, nor plating,zoning,gazing or other writer applicatiai processing aservice fees in correction with this project.NOR DUES IT APPLY tomy
fees/exactions cf kkrichyou have previously been riven a NOTICE sinter to this.aas toWiththe statute cf lirritaticns has oreviousN cthenkiseached
AW
rTHE FOLLOWING APPROVALS REQUIRED PRIOR TO PERMIT ISSUANCE:OPLANNING DENGINEERING OBUILDING EIFIRE OHEALTH 0 HAZMAT/APCD
irBuilding Permit Application Plan Check No. C...e)15 .I$1 0Clty-of 1635 Faraday Ave., Carlsbad, CA 92008 Est. Value 3 42..,000
Ph: 760-602-2719 Fax: 760-602-8558Carlsbademail: building@carlsbadca.gov Plan Ck. Deposit
www.carlsbadca.gov Date I.D •ISM •IS'SWPPP
JOB ADDRESS SUREVSPACEf/WW0 APR
.
Rso MOO Silverleaf Circle, Carlsbad, CA 92009 255 -012 -016 -00
CT/PROJECT #LOT#PHASE ## OfUNITS # BEDROOMS # BATHROOMS TENANT BUSINESS E CONSTR. TYPE OCC. GROUP
DESCRIPTION OF WORK:Include Square Feet of Affected Area(s)
Installation of PV Solar Panels on Existing Roof b2(Iasi"
11191144 IN--
85-S-7>/9-11--2._Co'l K C%..)
EXISTING USE PROPOSED USE GARAGE (SF)PATIOS (SF)DECKS (SF)FIREPLACE AIR CONDITIONING FIRE SPRINKLERS
YESON NCO YES GNOEl YESO NOO
APPUCANT NAME..PROPERTY OWNER NAMENick Jansing Kevin Ward
ADDRESS ADDRESS
PO Box 10894 1950 Silverleaf Circle
CITY STATE ZIP CITY STATE ZIP
Truckee CA 96162 Calrsbad CA 92009
PHONE FAX PHONE FAX
916-343-3031 760-704-1011
EMAIL EMAIL
nick@centurysunandsolar.com kavin.wardelacostaglen.com
DESIGN PROFESSIONAL CONTRACTOR BUS. NAME MHD Studio
ADDRESS ADDRESS
PO Box 10894
CITY STATE ZIP CITY STATE ZIP
Truckee CA 96162
PHONE FAX PHONE FAX
530-550-9896
EMAIL EMAIL
mike@inbdstudio.com
STATE LIC.#STATE LIC.#CLASS CITY BUS. LIC.#
847538 B 1241033
(Sec.7031.5 Business and Professions Code: Any City or County which requires a permit to construct, alter, improve, demolish or repair any structure, prior to its issuance, also requires the
applicant for such permit to file a signed statement that he is licensed pursuant to the provisions of the Contractor's License Law (Chapter 9, commending with Section 7000 of Division 3 of theBusiness and Professions Code) or that he is exempt therefrom, and the basis for the alleged exemption. Any violation of Section 7031.5 by any applicant for a permit subjects the applicant to acivil penalty of not more than five hundred dollars ($500)).
WORKERS'COMPENSATION
Workers' Compensation Declaration:I hereby affirm under penallyofperjury one of the following declarations:
FiI
have and will maintain a certificate of consent to self-insure for workers' compensation as provided by Section 3700 of the Labor Code, for the performance ofthe work for which this permit is issued.
I have and will maintain workers' compensation, as required by Section 3700 of the Labor Code, for the performance of the work for which this permit is issued. My workers' compensation insurance carrier and policy
number are: Insurance Co.State Compensation Insurance Fund Policy No.1979466 Expiration Date 1241.2015
Thi section need not be completed if the permit is for one hundred dollars ($100) or less.
Certificate of Exemption:I certify that in the performance of the work for which this permit is issued,I shall not employ any person in any manner so as to become subject to the Workers' Compensation Laws of
California.WARNING: Failure to secure workers'-...'coverage is unlawful, and s i I subject an employer to criminal penalties and civil fines up to one hundred thousand dollars (&100,000), in
addition to the cost of compensation, damages provided /in Section 3706 ii -iF .-.interest and attorney's fees.,.---
)1N..ESCONTRACTOR SIGNATURE A 0 AGENT DATE li9 /Ei I
OWNER -BUILDER DECLI.RATION
I hereby affirm that I am exempt from Contractor's License Law for the following reason:
ElI,as owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not intended or offered for sale (Sec. 7044, Businessaid Professions Code: The Contractor's
License Law does not apply to an owner of property who builds or improves thereon, and who does such work himself or through his own employees, provided that such improvements are not intended or offered for
sale. If, however, the building or improvement is sold within one year of completion, the owner-builder will have the burden of proving that he did not build or improve for the purpose of sale).0 I,as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions Code: The Contractor's Licenselaw does not apply to an owner of
property who builds or improves thereon, and contracts for such projects with contractor(s) licensed pursuant to the Contractor's License Law).
ElI am exempt under Section Business and Professions Code for this reason:
1.I personally plan to provide the major labor and materials for construction of the proposed property improvement.ElYes psio
2.I (have /have not) signed an application for a building permit for the proposed work.
3.I have contracted with the following person (firm) to provide the proposed construction (include name address /phone / contractors' license number):
4.I plan to provide portions of the work, butI have hired the following person to coordinate, supervise and provide the major work (include name/address /phone /contractors' license number):
5.I will provide some of the work, but I have contracted (hired) the following persons to provide the work indicated (include name /address/phone /typeof work):
itSPROPERTYOWNER SIGNATURE DAGENT DATE
COMP -LETS THIS SECTION FOR NON -RESIDENTIAL BUILDING PERMITS ONLY
Is the applicant or future building occupant required to submit a business plan, acutely hazardous materials registration form or risk management and prevention program under Sections 25505, 25533 or 25534 of the
Presfey-Tanner Hazardous Substance Account Act?Yes No
Is the applicant or future building occupant required to obtain a permit from the air pollution control district or air quality management district?Yes No
Is the facility to be constructed within 1,000 feet of the outer boundary of a school site?Yes No
IF ANY OF THE ANSWERS ARE YES, A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR IS MEETING THE REQUIREMENTS OF THE OFFICE OF
EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT.
CONSTRUCTION LENDING AGENCY
I hereby affirm that there is a construction lending agency for the performance of the work this permit is issued (Sec. 3097 (i) Civil Code).
Lender's Name N/A Lender's Address
#0: it art ile2NT CEFtTIFICATION
Icertifythat'have mad the application and state that the above information is conect and that the'donationon the plans is accurate.Iagreeto comply with all City ordinances and State laws relating to building construction.
I hereby authorize representative of the City of Carlsbad to enter upon the above mentioned property for inspection purposes.IALSO AGREE TO SAVE, INDEMNIFY AND KEEP HARMLESS THE CITY OF CARLSBAD
AGAINST ALL LIABILITIES, JUDGMENTS, COSTS AND EXPENSES WHICH MAYIN ANY WAY ACCRUE AGAINST SAID CITY IN CONSEQUENCE OF THE GRANTING OF THIS PERMIT.
OSHA: An OSHA permit is required for excavations over 60' deep an••olition or construction of structures over 3 stories in height.
EXPIRATION: Every permit issued by the Budding Official under the ••••ns ofthis ('Mn shall expire by limitation and become null and void if the building or work authorized by such permit is not commenced within
180 days from the date of such permit or if the txfildin work a I •'Y •by suchlioor'''.spended or abandoned at any time after the work is commenced fora period of1180 days (Section 1064.4 Uniform Budding Code).
ic APPLICANT'S SIGNATURE DATE 61/ g/Lc
STOP
STOP:THIS SECTION NOT REQUIRED FOR BUILDING PERMIT ISSUANCE.
Complete the following ONLY if a Certificate of Occupancy will be requested at final inspection.
Fax (760) 602-8560, Email buildingOcarisbadca.gov or Mail the completed form to City of Carlsbad, Building Division 1635 Faraday Avenue, Carlsbad, California 92008.
CO#:(Office Use Only)
CONTACT NAME OCCUPANT NAME
ADDRESS BUILDING ADDRESS
CITY STATE ZIP CITY STATE ZIP
Carlsbad CA
PHONE FAX
EMAIL OCCUPANT'S BUS. LIC. No.
DELIVERY OPTIONS
PICK UP:CONTACT (Listed above)OCCUPANT (Listed above)
CONTRACTOR (On P.1)
ASSOCIATED CB#MAIL TO:CONTACT (Listed above)OCCUPANT (Listed above)
CONTRACTOR (On Pg.1.)NO CHANGE IN USE /NO CONSTRUCTION
MAIL /FAX TO OTHER:CHANGE OF USE /NO CONSTRUCTION
„eAPPLICANT'S SIGNATURE DATE
Inspection List
Permit#:CB151870 Type:COGEN PHOTO LA COSTA GLEN: 855 MODULE PV
BALLAST MOUNT, FLUSH/ROOF, 269 KW
Date Inspection Item Inspector Act Comments
11/12/2015 35 Photo Voltaic (PV)RI PM PLEASE/ FIRE IN AM
11/12/2015 35 Photo Voltaic (PV)AEK AP
11/12/2015 39 Final Electrical RI PM PLEASE/ FIRE IN AM
11/12/2015 39 Final Electrical AEK Fl
Friday, November 13, 2015 Page 1 of 1
CR151870 1950 SILVERLEAF CR.{co.•LA COSTA GLEN: 855 MODULE PV-...\/.CITY CiF•
CARLSBAD INSPECTION RECORD BALLAST MOUNT,FLUSH/ROOF 269 KW
COGEN PHOTOBuilding Division Lot#:MHD STUDIO
El INSPECTION RECORD CARD WITH APPROVED
PLANS MUST BE KEPT ON THE JOB
El CALL BEFORE 3:30 pm FOR NEXT WORK DAY INSPECTION
21 FOR BUILDING INSPECTION CALL:760-602-2725
OR GO TO: www.Carlsbacica.gov/Buildigg AND CLICK ON
"Request Inspection"t.../VV.IL..N.).Yr ‘1.1...
DATE:is -iv -
1
IF "YES"IS CHECKED BELOW THAT DIVISION'S APPROVAL IS REQUIRED PRIOR TO REQUESTING A FINAL BUILDING INSPECTION.
IF YOU HAVE ANY QUESTIONS PLEASE CALL THE APPLICABLE DIVISIONS AT THE PHONE NUMBERS PROVIDED BELOW.AFTER
ALL REQUIRED APPROVALS ARE SIGNED OFF—FAX TO 760-602-8560,EMAIL TO BLDGINSPECTIONS@CARLSBADCA.GOV OR
BRING IN A COPY OF THIS CARD TO:1635 FARADAY AVE., CARLSBAD, CA 92008.BUILDING INSPECTORS CAN BE REACHED
AT 760-602-2700 BETWEEN 7:30 AM —8:00 AM THE DAY OF YOUR INSPECTION.
NO YES Required Prior to Requesting Building Final If Checked YES Date Inspector Notes,
‘..›(".Planning/Landscape 760-944-8463 Allow48 hours
XCM&I (Engineering Inspections)760-438-3891 Call before 2 pm ..
X Fire Prevention 760-6024660 Allow 48 hours /07/14/1
Type of Inspection Type of Inspection
coos a BUILDING Date Inspector Coos a ELECTRICAL Date Inspector
#11 FOUNDATION
I
#31 0 ELECTRIC UNDERGROUND 0 UFER
#12 REINFORCED STEEL #34 ROUGH ELECTRIC
#66 MASONRY PRE GROUT
1 .#33 0 ELECTRIC SERVICE El TEMPORARY
0 GROUT 0 WALL DRAINS #35 PHOTO VOLTAIC I
#10 TILT PANELS #39 FINAL
#11 POUR STRIPS
#11 COLUMN FOOTINGS #41 UNDERGROUND DUCTS &PIPING
#14 SUBFRAME 0 FLOOR 0 CEILING
y
#44 0 DUCT & PLENUM 0 REF. PIPING
#15 ROOF SHEATHING I #43 HEAT-AIR COND. SYSTEMS
#13 DM SHEAR PANELS #49 FINAL-
#16 INSULATION cobs #COMBO INSPECTION
#18 EXTERIOR LATH #81 UNDERGROUND (11,12,21,31)
#17 INTERIOR LATH &DRYWALL #82 DRYWALL,EXT LATH, GAS TES (17,18,23)
#51 POOL.EXCA/STEEL/BOND/ FENCE #83 ROOF SHEATING, EXT SHEAR (13,15)
#55 PREPLASTER/FINAL #84 FRAME ROUGH COMBO (14,24,34,44)
#19 FINAL #85 T-Bar (14,24,34,44)
Date Ins ector #89 FINAL OCCUPANCY (19,29,39,49)
#22 0 SEWER & BL/C0 0 PL/CO Date Ins ector
#21 UNDERGROUND OWASTE 0 WTR ,
#24 TOP OUT 0 WASTE 0 WTR A/S UNDERGROUND VISUAL\\
#27 TUB &SHOWER PAN A/S UNDERGROUND HYDRO \\\
#23 0 GAS TEST 0 GAS PIPING A/S UNDERGROUND FLUSH \\
#25 WATER HEATER A/S OVERHEAD VISUAL \\N\
#28 SOLAR WATER A/S OVERHEAD HYDROSTATIC \\\
#29 FINAL A/S FINAL \\
cope #STORM WATER F/AROUGH-IN \
#600 PRE-CONSTRUCTION MEETING F/AFINAL \
#603 FOLLOW UP INSPECTION FIXED EXTINGUISHING SYSTEM ROUGH-IN \-
#605 NOTICE TO CLEAN FIXED ELTING SYSTEM HYDROSTATIC TEST-
#607 WRITTEN WARNING FIXED EXTINGUISHING SYSTEM FINAL \\
#609 NOTICE OF VIOLATION MEDICAL GAS PRESSURE TEST
#610 VERBAL WARNING MEDICAL GAS FINAL \1
REV 10/2012 SEE BACK FOR SPECIAL NOTES
EsGil Corporation
In Partnership with governmentfor Budding Safety
DATE:11/02/2015 APPLICANT
JURIS.
JURISDICTION:Carlsbad PLAN REVIEWER
O FILE
PLAN CHECK NO.:C1315-1870 SET:IV
PROJECT ADDRESS:1950 Silver Glen
PROJECT NAME:Lacosta Glen 269 KW Solar Photovoltaic System
Z The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
The plans transmitted herewith will substantially comply with the jurisdiction's
codes when minor deficiencies identified below are resolved and checked by building
department staff.
The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
The check list transmitted herewith is for your information.The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
7 The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
The applicant's copy of the check list has been sent to:
Esgil Corporation staff did not advise the applicant that the plan check has been completed.
Esgil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted:Telephone #:
Date contacted:(by:)Fax #:
Mail Telephone Fax In Person E-mail:
REMARKS:
By:John Le Vey Enclosures:
EsGil Corporation
GA EJ PC 10/26/2015
9320 Chesapeake Drive, Suite 208 San Diego, California 92123 (858) 560-1468 Fax (858) 560-1576
,.
,EsGil Corporation
In Tartnersfiip witfi Governmentfor (Budding Safety
DATE:10/21/2015
yeAPPLICANTJURIS.
JURISDICTION:Carlsbad PLAN REVIEWER
FILE
PLAN CHECK NO.:CB15-1870 SET:III
PROJECT ADDRESS:1950 Silver Glen
PROJECT NAME:Lacosta Glen 269 KW Solar Photovoltaic System
F-7 The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's codes.
The plans transmitted herewith will substantially comply with the jurisdiction's
codes when minor deficiencies identified below are resolved and checked by building
department staff.
ri The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
N The check list transmitted herewith is for your information.The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
ri The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
1 ____The applicant's copy of the check list has been sent to:
1
ri Esgil Corporation staff did not advise the applicant that the plan check has been completed.
X1 Esgil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted:Nick Jansing Telephone #: 916-343-3031
to contacted:1.0rM (by:Y4)-
ail Telephone Fax In Person4 Fax #:
E-mail: nick@centurysunandsolar.com
E REMARKS:
By:John Le Vey Enclosures:
EsGil Corporation
GA EJ PC 10/15/2015
9320 Chesapeake Drive, Suite 208 San Diego, California 92123 (858) 560-1468 Fax (858) 560-1576
Carlsbad CB15-1870
10/21/2015
ELECTRICAL and ENERGY COMMENTS
PLAN REVIEWER: John Le Vey
ELECTRICAL (2013 CALIFORNIA ELECTRICAL CODE)
Please make all corrections, as requested in the correction list.Submit FOUR new complete sets
of plans for commercial/industrial projects (THREE sets of plans for residential projects).For
expeditious processing, corrected sets can be submitted in one of two ways:
1.Deliver all corrected sets of plans and calculations/reports directly to the City of Carlsbad
Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760) 602-2700.The City will
route the plans to EsGil Corporation and the Carlsbad Planning, Engineering and Fire
Departments.
2.Bring one corrected set of plans and calculations/reports to EsGil Corporation, 9320
Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-1468.Deliver all remaining sets
of plans and calculations/reports directly to the City of Carlsbad Building Department for routing to
their Planning, Engineering and Fire Departments.
NOTE:Plans that are submitted directly to EsGil Corporation only will not be reviewed by the City
Planning, Engineering and Fire Departments until review by These corrections are in response
to items not fully addressed or as the result of information provided, the text in bold
underlined print indicates the unresolved issue.
1.The plans do not meet the required code compliance, please submit new set's of
plans with an electrical engineer design, stamped and signed for the electrical
system. The 3000 amp bus is exceeding the 120 percent rule per the CEC
705.12(D)(2)
Previous comments not addressed:
A.Provide the required special inspection on the cover sheet of the plans for
the ballast system
B.Sign all sheets
C.The typical placard for the building must match the actual building
D.Separation is not clear for the access of 150 feet per the CBC 3111.2.2.1
E.Show the required access per the CBC 3111.2.3.1
F.Provide the mechanical ventilation for the room for the transformers
New comment:
G.Now it appears for the most point the conduits will be sufficient, however the
conduit from the 3000 amp service to the transformer is overfilled for 3 inch flex
To speed up the review process, note on this list (or a copy) where each correction item
has been addressed, i.e., plan sheet, note or detail number, calculation page, etc.
Please indicate here if any changes have been made to the plans that are not a result of
corrections from this list.If there are other changes, please briefly describe them and
where they are located in the plans. Have changes been made to the plans not
Carlsbad CB15-1870
10/21/2015
resulting from this correction list?Please indicate: Yes No The jurisdiction has
contracted with Esgil Corporation located at 9320 Chesapeake Drive, Suite 208, San
Diego, California 92123; telephone number of 858/560-1468, to perform the plan review
for your project. If you have any questions regarding these plan review items, please
contact John Le Vey at Esgil Corporation.Thank you. Note: If you have any questions
regarding this Electrical and Energy plan review list please contact John Le Vey at
(858) 560-1468. To speed the review process, note on this list (or a copy) where the
corrected items have been addressed on the plans.
.,,
,.._.„
EsGil Corporation
In (Partnership with governmentfor Ouilifing Safety
DATE:08/31/2015 CIAPPLICANT
JURIS.
JURISDICTION:Carlsbad 0 PLAN REVIEWER
0 FILE
PLAN CHECK NO.:CB15-1870 SET:II
PROJECT ADDRESS:1950 EMI/V*131otq:LIvt.r ka Ce
PROJECT NAME:Lacosta Glen 269 KW Solar Photovoltaic System
IT The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's codes.
The plans transmitted herewith will substantially comply with the jurisdiction's
codes when minor deficiencies identified below are resolved and checked by building
department staff.
The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
RI The check list transmitted herewith is for your information.The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
n The applicant's copy of the check list has been sent to:
El Esgil Corporation staff did not advise the applicant that the plan check has been completed.
X Esgil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted:ick JansingN Telephone #: 916-343-3031
I3ate contacted:8 01 (by:Fax Fax #:
.?ail v‘lephone Fax In Person E-mail: nick@centurysunandsolar.com
REMARKS:
By:John Le Vey Enclosures:
EsGil Corporation
0 GA I::EJ El PC 08/25/2015
9320 Chesapeake Drive, Suite 208 •San Diego, California 92123 •(858) 560-1468 •Fax (858) 560-1576
•Carlsbad CB15-1870
08/31/2015
ELECTRICAL and ENERGY COMMENTS
PLAN REVIEWER:John Le Vey
ELECTRICAL (2013 CALIFORNIA ELECTRICAL CODE)
Please make all corrections, as requested in the correction list.Submit FOUR new complete sets
of plans for commercial/industrial projects (THREE sets of plans for residential projects).For
expeditious processing, corrected sets can be submitted in one of two ways:
1.Deliver all corrected sets of plans and calculations/reports directly to the City of Carlsbad
Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760) 602-2700.The City will
route the plans to EsGil Corporation and the Carlsbad Planning, Engineering and Fire
Departments.
2.Bring one corrected set of plans and calculations/reports to EsGil Corporation, 9320
Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-1468.Deliver all remaining sets
of plans and calculations/reports directly to the City of Carlsbad Building Department for routing to
their Planning, Engineering and Fire Departments.
NOTE:Plans that are submitted directly to EsGil Corporation only will not be reviewed by the City
Planning, Engineering and Fire Departments until review by These corrections are in response
to items not fully addressed or as the result of information provided, the text in bold print
indicates the unresolved issue.
1.The plans do not meet the required code compliance. please submit new set's of
plans with an electrical engineer design, stamped and signed for the electrical
system.
To speed up the review process, note on this list (or a copy) where each correction item
has been addressed, i.e., plan sheet, note or detail number, calculation page, etc.Please
indicate here if any changes have been made to the plans that are not a result of
corrections from this list.If there are other changes, please briefly describe them and
where they are located in the plans. Have changes been made to the plans not
resulting from this correction list?Please indicate: Yes No The jurisdiction has
contracted with Esgil Corporation located at 9320 Chesapeake Drive, Suite 208, San
Diego, California 92123; telephone number of 858/560-1468, to perform the plan review
for your project. If you have any questions regarding these plan review items, please
contact John Le Vey at Esgil Corporation.Thank you. Note: If you have any questions
regarding this Electrical and Energy plan review list please contact John Le Vey at
(858) 560-1468. To speed the review process, note on this list (or a copy) where the
corrected items have been addressed on the plans.
EsGil Corporation
In (Partnership with governmentfor(Budding Safety
DATE:06/30/2015
yfDPLICANTJURIS.
JURISDICTION:Carlsbad 0 PLAN REVIEWER
GI FILE
PLAN CHECK NO.:CB15-1870 SET:I
PROJECT ADDRESS:1950 Silver4liCe1/41
PROJECT NAME:Lacosta Glen 269 KW Solar Photovoltaic System
ri The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's codes.
ri The plans transmitted herewith will substantially comply with the jurisdiction's
codes when minor deficiencies identified below are resolved and checked by building
department staff.
ri The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
M The check list transmitted herewith is for your information.The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
ri The applicant's copy of the check list has been sent to:
Esgil Corporation staff did not advise the applicant that the plan check has been completed.
Esgil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted:Nick Jansing Telephone #: 916-343-3031
late con)acted: ‘4947)0 (bylgS-)-Fax #:
41.4 lielephone Fax In Person E-mail: nick@centrysunandsolar.com
REMARKS:
By:John Le Vey Enclosures:
EsGil Corporation
1:1 GA EJ PC 06/22/2015
9320 Chesapeake Drive, Suite 208 •San Diego, California 92123 •(858) 560-1468 •Fax (858) 560-1576
r Cailsbad CB15-1870
•06/30/2015
ELECTRICAL and ENERGY COMMENTS
PLAN REVIEWER: John Le Vey
ELECTRICAL (2013 CALIFORNIA ELECTRICAL CODE)
1.Please make all corrections, as requested in the correction list.Submit FOUR new
complete sets of plans for commercial/industrial projects (THREE sets of plans for
residential projects).For expeditious processing, corrected sets can be submitted in one of
two ways:
1.Deliver all corrected sets of plans and calculations/reports directly to the City of
Carlsbad Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760) 602-2700.
The City will route the plans to EsGil Corporation and the Carlsbad Planning, Engineering
and Fire Departments.
2.Bring one corrected set of plans and calculations/reports to EsGil Corporation, 9320
Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-1468.Deliver all
remaining sets of plans and calculations/reports directly to the City of Carlsbad Building
Department for routing to their Planning, Engineering and Fire Departments.
NOTE:Plans that are submitted directly to EsGil Corporation only will not be reviewed by
the City Planning, Engineering and Fire Departments until review by
2.Please provide a statement on the Title Sheet of the plans to show compliance with the
current Codes. The following are the correct current Codes:
a)The 2013 edition of the California Building Code (CBC) adopts the 2012
International Building Code (IBC) and the 2012 California Amendments.
b)The 2013 edition of the California Electrical Code (CEC) adopts the 2011 National
Electrical Code (NEC) and the 2012 California Amendments.
3.Please provide an engineer design for the ballast system stamped and signed
4.Please provide on the cover sheet that the ballast system will have the required special
inspection
5.Please specify which module will be used for the system
6.Please provide a sample of the placards per the CEC section 690 and the locations
7.Please show the locations of all equipment associated with the PV system, more precise,
show the existing equipment and the new PV layout
8.Please show the combiner boxes on the roof
9.Please review the #10 conductors from the combiner box to the inverters and correct
10.Please provide the worst case voltage drop scenario for the combiner box to the inverter
branch
CaAlsbad CB15-1870
06/30/2015
11.Please correct the #10 conductor from the distribution to the A/C disconnect
12.Please explain the arrangement in the red box on sheet El,why two transformers to one
panel ,why #10 branch circuits from the panel to the transformer, how many new
breakers at the existing service
13.Please show the room where the PV system will be located show all the required
clearance.
14.Please show compliance with the CEC section 450.14 for the transformer
15.Please show the required grounding for the secondary side for the transformer
16.Please show the required ventilation for the transformer per the CEC section 450.9
17.Please show the conductors to have the required 1,000 volt listing
18.Please show the required fusing in the combiner this must also correspond with the
module series fusing, include the fusing for both polarities.
19.Indicate on the Title Sheet of the plans the name of the legal owner and name of the
person responsible for the preparation of the plans. CBC 107.1.
20.Utility-interactive inverters shall be permitted to be mounted on roofs or other exterior
areas that are not readily accessible; however, these installations shall comply with CEC
690.14(c)1 though 5.Please show compliance on the plans.
21.Show on the plans that when direct-current output circuits of a utility-interactive inverter
from a building-integrated or other photovoltaic system are run inside a building or
structure; they shall be contained in metal (EMT, FMC, or LFMC) raceways. 690.31 (E).
You state EMT however show the locations
22.Please add the following note to the plans: "Roof coverings shall be designed, installed
and maintained in accordance with this code and the approved manufacturer's
instructions such that the roof covering shall serve to protect the building or structure.
CBC 1503."
To speed up the review process, note on this list (or a copy) where each correction item
has been addressed, i.e., plan sheet, note or detail number, calculation page, etc.Please
indicate here if any changes have been made to the plans that are not a result of
corrections from this list.If there are other changes, please briefly describe them and
where they are located in the plans. Have changes been made to the plans not
resulting from this correction list?Please indicate: Yes No The jurisdiction has
contracted with Esgil Corporation located at 9320 Chesapeake Drive, Suite 208, San
Diego, California 92123; telephone number of 858/560-1468, to perform the plan review
for your project. If you have any questions regarding these plan review items, please
contact John Le Vey at Esgil Corporation.Thank you. Note: If you have any questions
regarding this Electrical and Energy plan review list please contact John Le Vey at
(858) 560-1468. To speed the review process, note on this list (or a copy) where the
corrected items have been addressed on the plans.
Cailsbad CB15-1870
•06/30/2015
(DO NOT PAY -THIS IS NOT AN INVOICE]
VALUATION AND PLAN CHECK FEE
JURISDICTION:Carlsbad PLAN CHECK NO.:CB15-1870
PREPARED BY:John Le Vey DATE:06/30/2015
BUILDING ADDRESS:1950 Silver Glen
BUILDING OCCUPANCY:TYPE OF CONSTRUCTION:
BUILDING AREA Valuation Reg.VALUE ($)
PORTION (Sq.Ft.)Multiplier Mod.
PV commerical 342,000
Air Conditioning
Fire Sprinklers
TOTAL VALUE 342,000
Jurisdiction Code cb By Ordinance
Bldg.Permit Fee by Ordinance
$1,526.81
Plan Check Fee by Ordinance $992.43
Type of Review:CI Complete Review Structural Only
Repetitive Fee D Other
Repeats Hourly Hr. @ *
EsGil Fee $855.01
•
PLANNING DIVISIONBUILDINGDevelopment ServicesPLAN CHECK Planning Division
\-/CITY OF APPROVAL 1635 Faraday Avenue
CARLSBAD P-29 (760) 602-4610
www.carlsbadca.eov
DATE:6-18-15 PROJECT NAME:PROJECT ID:
PLAN CHECK NO: CB 15-1870 SET#:1 ADDRESS:1950 Silverleaf Cr APN:255-012-16-00
This plan check review is complete and has been APPROVED by the Planning
Division.
By: Chris Sexton
-A Final Inspection by the Planning Division is required Yes E No
You may also have corrections from one or more of the divisions listed below. Approval
from these divisions may be required prior to the issuance of a building permit.
Resubmitted plans should include corrections from all divisions.
This plan check review is NOT COMPLETE. Items missing or incorrect are listed on
the attached checklist. Please resubmit amended plans as required.
Plan Check APPROVAL has been sent to:
For questions or clarifications on the attached checklist please contact the following reviewer as marked:
PLANNING ENGINEERING FIRE PREVENTION
760-602-4610 760-602-2750 760.602-4665
X Chris Sexton Chris Glassen Greg Ryan
760-602-4624 760-602-2784 760-602-4663
Chris.Sexton@carlsbadca.gov Christophes.Glassen@carlsbadca.gov Gregory.Ryan@carisbadca.gov
Gina Ruiz ValRay Marshall Cindy Wong
760-602-4675 760-602-2741 760-602-4662
Gina.Ruiz@carlsbadca.gov VaiRay.Marshall@carlsbadca.gov Cynthia.Wong@carlsbadca.gov
Linda Ontiveros Dominic Fieri
760-602-2773 760-602-4664
Linda.Ontiveros@carlsbadca.gov Dominic.Fieri@carlsbadca.gov
Remarks:
BUILDING DEPT.
PLAN CHECK oefit ity&Economic
REVIEW Development Department
N.77 CITY OF 1635 Faraday Avenue
CARLSBAD TRANSMITTAL Carlsbad CA 92008
www.carlsbadca.gov
DATE:10/15/2015 PROJECT NAME: LA COSTA GLEN -PV ARRAY PROJECT ID:CB151870
PLAN CK NO: SET#:2/1 ADDRESS:1950 SILVERLEAF CIRCLE
Z This plan check review is complete and has been APPROVED by the FIRE Division.
By: GR
A Final Inspection by the FIRE Division is required Z Yes D No
This plan check review is NOT COMPLETE. Items missing or incorrect are listed on
the attached checklist. Please resubmit amended plans as required.
Plan check comments have been sent to:nick@centurysunandsolar.com
You may also have corrections from one or more of the divisions listed below. Approval
from these divisions may be required prior to the issuance of a building permit.
Resubmitted plans should include corrections from all divisions.
For questions or clarifications on the attached checklist please contact the following reviewer as marked:
PLANNING ENGINEERING FIRE PREVENTION
760-602-4610 760-602-2750 760-602-4665
Chris Sexton X Greg Ryan
760-602-4624 760-602-4663
Chris.Sexton@carlsbadca.gov Gregory.Ryan@carlsbadca.gov
Gina Ruiz Linda Ontiveros Cindy Wong
760-602-4675 760-602-2773 760-602-4662
Gina.Ruiz@carlsbadca.gov Linda.Ontiveros@carlsbadca.gov Cynthia.Wong@carlsbadca.gov
Dominic Fieri
760-602-4664
Dominic.Fieri@carlsbadca.gov
C114.o <
'uWin
e44;Fcge'Carlsbad Fire Department SUILDING DEPT.
COPY
Plan Review Requirements Category:COGEN ,PHOTO
Date of Report:10-15-2015 Reviewed by:RrUt
Name:MHD STUDIO
Address:P.O.BOX 10894
TRUCKEE CA
96162
Permit #:CB151870
Job Name:LA COSTA GLEN:855 MODULE PV
Job Address:1950 SILVERLEAF CR CBAD
Please review carefully all comments attached.
CITY OF CARLSBAD FIRE DEPARTMENT -APPROVED:
THIS PROJECT HAS BEEN REVIEWED AND APPROVED FOR THE PURPOSES OF ISSUANCE OF BUILDING PERMIT.
THIS APPROVAL IS SUBJECT TO FIELD INSPECTION AND REQUIRED TEST, NOTATIONS HEREON, CONDITIONS IN
CORRESPONDENCE AND CONFORMANCE WITH ALL APPLICABLE REGULATIONS.
THIS APPROVAL SHALL NOT BE HELD TO PERMIT OR APPROVE THE VIOLATION OF ANY LAW.
Entry:06/30/2015 By: GR Action: CO Entry:10/15/2015 By: GR Action: AP
BUILDING DEPT.
Af"°>PLAN CHECK CommAcilvonomic
N/4 P4 REVIEW Development Department
CITY OF 1635 Faraday Avenue
CARLSBAD TRANSMITTAL Carlsbad CA 92008
www.carlsbadca.gov
DATE:06/30/2015 PROJECT NAME:LA COSTA GLEN PROJECT ID:CB151870
PLAN CK NO: SET*: 1 /1 ADDRESS:1950 SILVERLEAF CIRCLE APN:255-012-16-00
E This plan check review is complete and has been APPROVED by the FIRE Division.
By: GR
A Final Inspection by the FIRE Division is required Z Yes No
Z This plan check review is NOT COMPLETE.Items missing or incorrect are listed on
the attached checklist. Please resubmit amended plans as required.
Plan Check Comments have been sent to: nick@centurysunandsolar.com
You may also have corrections from one or more of the divisions listed below. Approval
from these divisions may be required prior to the issuance of a building permit.
Resubmitted plans should include corrections from all divisions.
For questions or clarifications on the attached checklist please contact the following reviewer as marked:
PLANNING ENGINEERING FIRE PREVENTION
760602-461.0 760-602-2750 760-602-4665
Chris Sexton Kathleen Lawrence X Greg Ryan
760-602-4624 760-602-2741 760-602-4663
Chris.Sexton@carlsbadca.gov Kathleen.Lawrence@carlsbadca.gov Gregory.Ryan@carlsbadca.gov
Gina Ruiz Linda Ontiveros Cindy Wong
760-602-4675 760-602-2773 760-602-4662
Gina.Ruiz@carlsbadca.gov Linda.Ontiveros@carlsbadca.gov Cynthia.Wong@carlsbadca.gov
Dominic Fieri
760-602-4664
Dominic.Fieri@carlsbadca.gov
itiliell
0 \C40 ''›BUILDING DEPT.C:
-i,--0'Carlsbad Fire Department COPY
Plan Review Requirements Category:COGEN ,PHOTO
Date of Report:06-30-2015 Reviewed by:Rovair
Name:MHD STUDIO
Address:P.O.BOX 10894
TRUCKEE CA
96162
Permit #:CB151870
Job Name:LA COSTA GLEN: 855 MODULE PV
Job Address:1950 SILVERLEAF CR CBAD
INCOMPLETE The item you have submitted for review is incomplete.At this time, this office cannot
adequately conduct a review to determine compliance with the applicable codes and/or standards.Please review
carefully all comments attached.Please resubmit the necessary plans and/or specifications, with changes "clouded",
to this office for review and approval.
Conditions:
Cond: CON0008366 oygr]
Provide a larger sheet for the PV panel layout, submittal to small to make determinations.
This plan shall provide a scale to measure from.
You shall demonstrate compliance with 605.11 of the 2013 CFC
Access
There should be a minimum six foot (6') wide clear perimeter around the edges ofthe roof.
Exception:If either axis of the building is 250 feet or less, there should be a minimum four feet
(4') wide clear perimeter around the edges of the roof.
Pathways
Pathways should be established in the design of the solar installation. Pathways should meet the following
requirements:
a.Should be over structural members
b. Centerline axis pathways should be provided in both axis of the roof. Centerline axis pathways should run on
structural members or over the next closest structural member nearest to the center lines ofthe roof
c.Should be straight line not less than 4 feet (4') clear to skylights and/or ventilation hatches.
d. Should be straight line not less than 4 feet (4') clear to roof standpipes.
e.Should provide not less than 4 feet (4') clear around roof access hatch with at least one not less than 4 feet (4') clear
pathway to parapet or roof edge
Smoke Ventilation
.•.0.
a.Arrays should be no greater than 150 by 150 feet in distance in either axis
,b. Ventilation options between array sections should be either:
1.A pathway 8 feet (8') or greater in width
2.4 feet (4') or greater in width pathway and bordering on existing roof skylights or ventilation hatches
.3.4 feet (4') or greater in width pathway and bordering four feet (4') x 8 feet 8' "venting cutouts" every 20 feet (20')
on alternating sides of the pathway
For commercial application, the marking should be placed adjacent to the main service disconnect in a location
clearly visible from the location where the lever is operated.
Marking Content and Format
o MARKING CONTENT: CAUTION: SOLAR ELECTRIC SYSTEM
o RED BACKGROUND
o WHITE LETTERING
o MINIMUM 3/8" LETTER HEIGHT
o ALL CAPITAL LETTERS
o ARIAL OR SIMILAR FONT, NON-BOLD
o REFLECTIVE, WEATHER RESISTANT MATERIAL SUITABLE FOR THE ENVIRONMENT (durable
adhesive materials may meet this requirement)
Marking for Direct Current Conduit, Raceways, Enclosures, Cable Assemblies, and Junction Boxes
Marking is required on all interior and exterior DC conduit, raceways, enclosures, cable assemblies, and junction
boxes to alert the Fire Service to avoid cutting them. Marking should be placed on all interior and exterior DC
conduit, raceways, enclosures, and cable assemblies, every 10 feet, at turns and above and/or below penetrations and
all DC combiner and junction boxes.
Marking Content and Format
o MARKING CONTENT: CAUTION: SOLAR CIRCUIT
o RED BACKGROUND
o WHITE LETTERING
o MINIMUM 3/8" LETTER HEIGHT
o ALL CAPITAL LETTERS
o ARIAL OR SIMILAR FONT, NON-BOLD
o REFLECTIVE, WEATHER RESISTANT MATERIAL SUITABLE FOR THE ENVIRONMENT (durable
adhesive materials meet this requirement)
Entry:06/30/2015 By: GR Action:AP—ac.