HomeMy WebLinkAbout2005 Cordoba Pl; ; CBR2018-1485; Permit(City of
Carlsbad
Print Date: 07/26/2019
Job Address:
Permit Type:
Parcel No:
Valuation:
Occupancy Group:
# Dwelling Units:
Bedrooms:
Project Title:
2005 Cordoba Pl
BLDG-Residential
2072401300
$21,627.15
Residential Permit
Work Class: Alteration
Lot#:
Reference #:
Construction Type:
Bathrooms:
Orig. Plan Check#:
Plan Check#:
Status:
Applied:
Issued:
Permit
Finaled:
Inspector:
Final
Inspection:
Permit No: CBR2018-1485
Closed -Finaled
06/21/2018
08/21/2018
PBurn
4/4/2019 1:53:45PM
Description: COWELL: 465 SF REMODEL FOR KITCHEN// ADDING NEW SLIDING DOOR AND WINDOW// PANEL UPGRADE TO 200A
Applicant: Owner:
LARRY LIPKIN
13607 Powers Rd
Poway, CA 92064-3615
858-774-1957
COOWNER COWELL JONATHAN D AND
MELISSAJ
BUI LOI NG PERMIT FEE ($2000+)
BUILDING PLAN CHECK FEE (BLOG)
2005 Cordoba Pl
CARLSBAD, CA 92008
ELECTRICAL BLDG RESIDENTIAL NEW/ADDITION/REMODEL
PLUMBING BLDG RESIDENTIAL NEW/ADDITION/REMODEL
SB1473 GREEN BUILDING STATE STANDARDS FEE
STRONG MOTION-RESIDENTIAL
Total Fees: $470.19 Total Payments To Date: $470.19 Balance Due:
Please take NOTICE that approval of your project includes the "Imposition" of fees, dedications, reservations, or other exactions hereafter
collectively referred to as "fees/exaction." You have 90 days from the date this permit was issued to protest imposition of these
fees/exactions. If you protest them, you must follow the protest procedures set forth in Government Code Section 66020(a), and file the
protest and any other required information with the City Manager for processing in accordance with Carlsbad Municipal Code Section
3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack, review, set aside, void, or annul their
imposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection
fees and capacity changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this
project. NOR DOES IT APPLY to any fees/exactions of which you have previously been given a NOTICE similar to this, or as to which the
statute of limitation has previously otherwise expired.
$0.00
1635 Faraday Avenue, Carlsbad, CA 92008-7314 I 760-602-2700 I 760-602-8560 f I www.carlsbadca.gov
$221.40
$154.98
$41.00
$49.00
$1.00
$2.81
THE FOLLOWING APPROVALS REQUIRED PRIOR TO PERMIT ISSUANCE: □PLANNING 0 ENGINEERING □BUILDING []FIRE □HEALTH D HAZMATIAPCD
( City of Building Permit Application Plan Check No.(P,f<:Jt')/8'-/Lf~ ?S
1635 Faraday Ave., Carlsbad, CA 92008 Est. Value tt _')/ t,:J7. /r...
Carlsbad Ph: 760-602-2719 Fax: 760-602-8558 Plan Ck. Deposit . I
email: building@carlsbadca.gov .
www.carlsbadca.gov Date fnl:Jl II~
JOB ADDRESS SUITEt/SPACEt/U•••, .. ,
2005 CORDOBA PLANE \"' 207 -240 -13 -00
'cl7PR6jECT# /LOT# I PHASE# I# oF ~N1rs j # sEoR;~-Er # BATHROOMS 'TENANT SUilNW NAME I coNS~bTYPE · 1 occ~;uP 48 2
DESCRIPTION OF WORK: Include Square Feet of Affected Area(•)
REMODEL EXISTING KITCHEN (465 SQ FT) AND INSTALL NEW SLIDING DOOR AND WINDOW
EXISTING USE I PROPOSED USE I GARAGE (SF) PATIOS (SF) I DECKS (SF) FIREPLACE I AIR CONDITIONING I ARE SPRINKLERS
SFD SFD YES@ NcCJ YES0No0 YES0N00
APPLICANT NAME LARRY LIPKIN PROPERTY OWNER NAME JON AND MELISSA COWELL p
ADDRESS ADDRESS
13607 POWERS ROAD 2005 CORDOOBA PLACE
CITY STATE ZIP CITY STATE ZIP
POWAY CA 92064 CARLSBAD CA 92008
PHONE IFAX PHONE I FAX 858.774.1957 925.200.6857
EMAIL EMAIL
llipkin61@gmail.com joncowell@cbmsconsulting.com
DESIGN PROFESSIONAL LARRY LIPKIN CONTRACTOR BUS, NAME
ADDRESS ADDRESS 13607 POWERS ROAD ·-CITY STATE ZIP CITY STATE ZIP
POWAY CA 92064 ··-PHONE l'AX PHONE l'AX 858. 77 4.1957 ·--~
EMAIL EMAIL llipkin61@gmail.com I STATE UC.# STATE UC.# I ClASS I c1rv aus. uC.#
(Sec. 7031.5 Business and Professions Code: Any City or County which requires a permit to construct, alter, improve, demolish or repair any structure, prior to Its issuance, also requires the
applicant for such permit to file a signed statement that he Is licensed pursuant to the provisions of the Contractor's License Law {Chapter 9, commending with Section 7000 of Division 3 of the Business and Professions Code) or that he is exempt therefrom, and the basis for the alleged exemption. Any violation of Section 1031.5 by any applicant for a permit subjects the applicant to a
civil penalty of not more than five hundred dollars {$500)).
"f O R K E R S ' CO M PIE N S A T I O N I I ! i !
Workars' Compensation Declaration: I hereby affirm under penalty of perjury one of the following declarations:
BI have and will maintain a ctrtlftcata of consent to sett-insure for workers' compensation as provided by Section 3700 of the Labor Code, for the performance of the work for which this permit is issued.
I have and will maintain workers' compensation, as required bv Section 3700 of the Labor Code, for the performance of the wor1t for which this oennit is issued. My workers' compensation insurance carrier and poicy
number are: Insurance Co. ---------------~ Policy No. _____________ Expiration Date ________ _
J]u§.seclion need not be completed iflhe permit IS for one hundred dollars ($100} or less. LJ Certificate of Exemptfon: I certify that in the performance of the work for which this permit is iS$1J8d, I shall not employ any person in any manner so as to become subject lo lhe WITTers' Compensation laws of
Califomia. WARNING: Failure to secure wotk&n' compensation coverage ia unlawful, and shall aubject an employer to crfmlnal panaltiea and cfvll fines up to one hundred thousand dollars (&100,000), in
addition to the cost of ccmpensatlon, damages as provided for In Section 3706 of the Labor code, interest and attorney's fees.
A5 CONTRACTOR SIGNATURE □AGENT DATE
~ W N E R , 8 U I L D l!ltl D E C LARA TI ON ; I , : j j
I hereby affirm that I am exempt from Contractor's License Law for the following reason: D I, as owner of the property or my employees with wages as their sole compensation, wiU do the wor1t and the structure is no! intended or offered for sale (Sec. 7044, Business and Professions Code: The Contracto~s
license Law does not appyto an O'M'ler of property who builds or improves thereon, and who does StJch work himself or through h'1s own employees, provided that such improvements are not intended or offered for
sale. If, however, lhe building or improvement Is sold within one year of completion, the owner-builder wil have the burden of proving that he did not bu~d or improve for the purpose of sale).
~
□
I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions Code: The Contractor's License Law does not apply to an owner of
property who builds or improves thereon, and contracts for such projects with contractor(s) licensed pursuant to the Contractor's License Law).
I am exempt under Section ____ ,Business and Professions Code for this reason:
1. J personaOy plan to provide the major labor and materials for construction of the proposed property improvement 0Yes Do
2. I (have/ have not) signed an application for a building permit for the proposed wonc
3. I have contracted with the following person {firm) to provide the proposed construction (include name address/ phone/ contractors' license number):
4. I plan to provide portions of the wor1t, but l have hired the following person to coordinate, supervise and provide the major work {indude name I address/ phone I contractors' license number):
5. I wiA provide some of the work, but I have contracted (hired) the following persons to provide the work indicated (il'ICiude name I address/ phone/ type of work):
,15 PROPERTY OWNER SIGNATURE □AGENT DATE
co MI' LET 11 T K IS Is E c TI o N F o R t,,1o N. RE s IDEN TI Ai L Bu, L D, NG P 11 I'M IT s o NL v 1
Is the applicant or future bt.i1dl"ng occupant required to submit a business plan, acutely hazardous materials registration form or risk management and prevention program under Sections 25505, 25533 or 25534 of the
Presley-Tanner Hazardous Substance ~ount Act.? □ Yes □ No
Is the applicant or future building occupant required to obtain a permit from the air pollution control district or air quality management disbict? □ Yes □ No
ls the faciity to be constructed within 1,000 feet of the outer boundary of a school site? □ Yes □ No
IF ANY OF THE ANSWERS ARE YES, A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR IS MEETING THE REQUIREMENTS OF THE OFFICE OF
EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT.
.. ciof4STRUCH9111 ~ENDING AGEl\'{Y
I hereby affirm that there 1s a construction lending agency for the performance of the work this permit 1s issued (Sec. 3097 (1) Ci'lll Code).
Lender's Name lender's Address
I cef1lt, that I tuwe read die application and state that the above lntormatfon Is correct and that the infonnatlon on the plans Is accurate. I agree to complyMth all Ctt:yonflnances and State laws ~to btlldlngconsll'\lctlon.
I hef8by aulho!inl n,prasenlalNe of tho City of Cai1sbad ID enter upon tho above rrentioned property for ilspedion purposes. I ALSO AGREE TO SAVE, INDEMNIFY AND KEEP HARMLESS THE CITY Of CARLSBAD
AGAINST All LIABILmES, JUDGMENTS, COSTS 1W EXPENSES WHICH MAY IN ANYWAY ACCRUE AGAINST SAID CITY IN CONSEQUENCE OF THE GRANTING Of THIS PERMIT.
OSHA: AA OSHA permit is requied t,r excavations fN8f 5'0' deep and demolitoo or construction of strucil.lres (J-/8f 3 sbies in height
EXPIRATION: Every pemilt issued by the lding Official under the ~ions of this Code shal expire by tnitation and becomEl nul and void if lhe lxJiding or 'NOfk authorized by sudl permt Is not commenced wilhil
180 da)o lorn Ile date of sudl pem;t or, b · · by sudl pennlt • suspended or abandoned at any liro allorlho -is oommenced for a period of 180 days(Sedion 106.4A Unifoml Buikl;,g Coda).
~ APPLICANT'S SIGNATURE DATE
PERMIT INSPECTION HISTORY REPORT (CBR2018-1485)
Permit Type: BLDG-Residential Application Date: 06/21/2018 Owner:
Work Class: Alteration Issue Date: 08/21/2018 Subdivision:
Status: Closed -Finaled Expiration Date; 10/01/2019 Address:
IVR Number: 12089
Scheduled
Date
Actual
Start Date Inspection Type Inspection No.
10/11/2018 10111/2018
11/12/2018 12/12/2018
02/26/2019 02/26/2019
04/0412019 04/04/2019
July 26, 2019
BLOG-17 Interior
Lath/Drywall
072689-2018
Checklist Item
BLDG-Building Deficiency
BLDG-33 Service
Change/Upgrade
078733-2018
Checklist Item
BLDG-Building Deficiency
BLDG-18 Exterior
Lath/Drywall
084652-2019
BLDG.Final
Inspection
Checklist Item
BLDG•Building Deficiency
087802·2019
Checklist Item
BLDG•Building Deficiency
BLDG·Plumbing Final
BLDG·Mechanical Final
BLDG•Structural Final
BLDG·Electrical Final
Inspection Status Primary Inspector
Passed Chris Renfro
COMMENTS
Partial Pass Paul Burnette
COMMENTS
Passed Michael Collins
COMMENTS
Passed Paul Burnette
COMMENTS
Completed by P. Burnette 4/3/2019
according to contractor
COOWNER COWELL JONATHAN
D AND MELISSA J
LAGUNA RIVIERA UNIT #2
2005 Cordoba Pl
Carlsbad, CA 92008-3711
Relnspection Complete
Complete
Passed
Yes
Reinspectlon Incomplete
Passed
No
Complete
Passed
Yes
Complete
Passed
Yes
Yes
Yes
Yes
Yes
Page 2 of2
PERMIT INSPECTION HISTORY REPORT (CBR2018-1485)
Permit Type: BLDG-Residential Application Date: 06/21/2018 Owner: COOWNER COWELL JONATHAN
D AND MELISSA J
Work Class: Alteration Issue Date: 08/21/2018 Subdivision: LAGUNA RIVIERA UNIT #2
Status: Closed -Finaled Expiration Date: 10/01/2019 Address: 2005 Cordoba Pl
Carlsbad, CA 92008-3711
IVR Number: 12089
Scheduled Actual
Date Start Date Inspection Type Inspection No. Inspection Status Primary Inspector Relnspectlon Complete
09/20/2018 BLDG-21 070759-2018 Passed Paul Burnette Complete
Underground/Underf
loor Plumbing
Checklist Item COMMENTS Passed
BLDG-Building Deficiency No
BLDG-31 070760-2018 Passed Paul Burnette Complete
Underground/Condu
it-Wiring
Checklist Item COMMENTS Passed
BLDG-Building Deficiency No
09/20/2018 09/20/2018 BLDG-84 Rough 070526-2018 Partial Pass Paul Burnette Reinspection Incomplete
Combo(14.24,34,44)
Checklist Item COMMENTS Passed
BLDG-Building Deficiency No
BLDG-14 No
Frame-Steel-Bolting-Welding
(Decks)
BLDG-24 Rough-Topout No
BLDG-34 Rough Electrical No
BLDG-44 No
Rough-Ducts-Dampers
10/0612018 10/06/2018 BLDG..£14 Rough 072146-2018 Failed Paul Burnette Reinspection Complete
Combo(14,24,34,44)
Checklist Item COMMENTS Passed
BLDG-Building Deficiency No
BLDG-14 No
Frame-Steel-Bolting-Welding
(Decks)
BLDG-24 Rough-Topout No
BLDG-34 Rough Electrical No
BLDG-44 No
Rough-Ducts-Dampers
10/09/:2018 10/09/2018 BLDG-34 Rough 072383-2018 Passed Andy Krogh Complete
Electrical
BLDG-84 Rough 072536-2018 Passed Andy Krogh Complete
Combo(14,24,34,44)
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Yes
BLDG-14 Yes
Frame-Steel-Bolting-Welding
(Decks)
BLDG-24 Rough-Topout Yes
BLDG-34 Rough Electrical Yes
BLDG-44 Yes
Rough-Ducts-Dampers
July 26, 2019 Page 1 of2
~ ~ CITY 0 1
CARLSBAD
Building Division INSPECTION RECOR
61J INSPECTION RECORD CARD WITH APPROVED
PLANS MUST BE KEPT ON THE JOB
@ CALL BEFORE 3:00 pm FOR NEXT WORK DAY INSPECTIO
@ FOR BUILDING INSPECTION CALL: 760-602-2725
OR GOTO:
"Request Inspection"
DATE:
CBR2018-1485
2005 CORDOBA PL
00\NEU. 465 SF REMODEL FOR KITCHEN// ADDING
NEW SLIDING DOOR AND WINDOW // PANEL UPGRADE
TO 200A
2072401300
12/11/2018
CBR2018-1485
IF MARl<ED "YES", IT IS REQUIRED PRIOR TO ANY CONSTRUCTION
STORM WATER PRECON MEETING REQUIRED 760-602•2725 Allow 24 houn
IF MARKED "YES", APPROVAl REQUIRED PRIOR TO REQUESTING BUILDING ANAL ••••••••·••·
76<>-602-4660 Allow 48 hours
760-944-8463 Allow 48 hours
CM&I I£nglnttfing t,up«tlons) 760-438-3891 CaH before 2 pm
Type of Inspection
C0U > BUILDING Inspector
#11 FOUNDATION
112 RONFOICED fflD. #34 ROUGH WffllC £YCIWIGEI
fH MASONRY Pit£ GIOUT #33 0 WC SEIVICE #320TDIPOIIAIY
□ GIOUT □ WALL DltAIIS #35 PHOTO VOLTAIC
110 TilTPANO.S #38 SIGNS
,u POUISTll'S :..=.:=..::'---------4-------1-----11.DG-ANAI.
111 COUIIINFOOllHS
114 SUlflAME □ R.GOI □ C£IUIIG
115 IOOFSllfA11IUIIG
113 EXT. SHfAII flANO.S
Ill UISUWlON
Ill EXTEIIOI LATH
117 ll10IOll LATH Ii DIYWAll
121
124 TOP OUT D WASlt □ WIii
127 1VI a SIIOWEI PAIi
123 D USTESI' DUI .....
ILDI FIIAL
, . POOLS
NI
112 -..
ruor , MECHANICAL
Ml UNDEIIROUND DUCl'S Ii 191"8
144 0 DUCT Ii PLENUM O IEF. PfflNI
143 HEAT-All COND. SYS1tMS
.,..
COf"YOf
REOUIIIE
(City of
Carlsbad
SPECIAL INSPECTION
AGREEMENT
B-45
Development Services
Building Division
1635 Faraday Avenue
760-602-2719
www.carlsbadca.gov
In accordance with Chapter 17 of the California Building Code the following must be completed when work being performed
requires special inspection, structural observation and construction material testing.
Project/Permit: -~=R'--"Jo"-"'"'----'{ 3c..__-___,(_,Y___,,KS=---Project Address~~_,,_,_,_=D_,___ _ __,_fu.,_,_ii_,_d,=lxc=~-----
A. THIS SECTION MUST BE COMPLETED BY THE PROPERTY OWNER/AUTHORIZED AGENT. Please check if you are Owner-Builder
□. (If you checked as owner-builder you must also complete Section B of this agreement.)
Name: (Please print~ ___ J_l>_"'l_..,_~ _________ \) __ • __________ ~_o_u.>_e.-_l_l ___ _
{First) (M.I.) (Last)
Mailing Address '2-0 0S Cord.I> b..... e !. c ..... Is ~ .... d I C¥l "'z_ooi
Email· joY\.d ~o...v-4! /( "2. YA,,k.#0 · C6.,..,, Phone '1 'l.S--U>O -G.&'~t
I am: o/l"operty Owner □Property Owner's Agent of Record □Architect of Record □Engineer of Record
State of California Registration Numbe~·-------------Expiration Date: ________ _
AGREEMENT: I, the undersigned, declare under penalty of perjury under the laws of the State of California, that I have read,
understand, acknowledge and promise to comply with the City of Carlsbad requirements for special inspections, structural
observations, construction materials testing and off-site fabrication of building components, as prescribed in the statement of
special insp~ons n:teJ-,°n the approved plans and, as required by the California Buil1ing
1
Cfde.
Signature~~ Date: _i_i,_-z..,_+~-/~f>~-----
B. CONTRACTOR'S STATEMENT OF RESPONSIBILITY (07 CBC, Ch 17, Section 1706). This section must be completed by the
contractor / builde~e~der)
Contractor's Company Name: ___________________ Please check if you are Owner-Builder □
Name: (Please print) __________________________________ _
(First) (M.I) (Last)
Mailing Address: ___________________________________ _
Email: _________________________ Phone_· ___________ _
State of California Contractor's License Number: __________ Expiration Date: _______ _
• I acknowledge and, am aware, of special requirements contained in the statement of special inspections noted on
the approved plans;
• I acknowledge that control will be exercised to obtain conformance with the construction documents approved by the
building official;
• I will have in-place procedures for exercising control within our (the contractor's) organization, for the method and
frequency of reporting and the distribution of the reports; and
• I certify that I will have a qualified person within our (the contractor's) organization to exercise such control.
• I will provide a final report I letter in compliance with CBC Section 1704.1.2 prior to requesting final
ins~n.v{,tz_
Signature· L Date: 6(-z I/,(
B-45 Page 1 of 1 Rev. 08111
Q QUALLS I
STRUCTURAL
ENGINEERING
E N G I N E ER I NG SERVICES
Project: COWELL REMODEL
Engineer: ANDREWLEUA
(N) 2xlO CEILING JOIST
SISTERED TO (E) TRUSS
BOTTOM CHORD VV
¼"x3" SDS SCREV'iS
@ 8" O.C., STAGGERED
Sheet:
Job#:
Date:
SSK1
18096
08-02-18
SECTION: A-A RECEIVED
(E) ROOF SHT'G ~ ,
AUG I 7 2018
CITY OF CARLSBAD
BUILDING DIVISION
)-::::~::::---... I(E) ROOF TRUSS ~(E) GAL-FIL \E) ROOF SHT'G ,.,,.---4/ ,..,._......... FRAMING ----// ,, --__ ,,,..,,. __ // ,, __ ......... _
.., --/ / '' --~------·--------n---.. v------r'!'!'------// ,, ___ , -,,,_,_.--// '-'---..._,, a D C ffi ----// ,, __ ...... ,.,,,,... -"\\Is: / / , , 7/1.--..._ Ill
_. • .--\ // '•' I __ .... , \\ // ,, if __ , ....
\\ // A ,, Ir ...... _ .... ....,,
// ,, --.... \\ // ,, // .... N __ ..........
/ ' -=----
---~__:,.~ ---------· --------------':.:::✓..:..i_ ----. . . . . . . . . . . .
(NJ 2'10 CEILING JOIST/
SISTERED TO (E) ROOF TRUSS
BOTTOM GHORD VV ¼"x3" SDS
SGREV'iS@ 8" O.G., STAGGERED
A
(E) GUT SEGTION OF
TRUSS BOTTOM GHORD
VV 2x FILLER BLOGK
~ G\,,.,L~<, '""'-<,t\A,;;1.--n..,V\.~ vV'A> loV\TIZ-'\-C.Tl::"v) ...., q-r, n-/c CL/cNT c,J
A,,.) IVl.\)IVI\)~ \l.11'> IS1 ':>eVH.(.,4,12 F\.l-0.,,_,._ T\t(' (..o"\.TI-l.+Ln,>L 4"10
i)ESl~NtV<.__/,41'1.C.lc/ll'F(f. 0._u.l,LLS E\Al)l"'-(:i;K11,1.f1 ,,__.,+s lfllZt'"Q 7D VIS II
TTft Clt0\.T0l ~Aovnt-,._.,-A+->\) k€°Vl0,,,v T1-t6' \:)(l~/7'1~ t-1.ocp f~ln~.
Tue Cl U::V\. T ru-o..v-c-ST1:() Lvt pi,1._.ov I OF A Fl/( Pr'-.. A ~ cT C p
~s'>cs, ""r-11c.H ..,,.,.1) Rt.eY\. _;,. .. 7cyz.co 11'1. i--rtG v-4ST: --nJ-1s h 01ttl
THH.£ q 5 CV P-Fl X: fC fliG C. L 1-eV'-n S n=t--v c. 7V>-IAL :r: 5 5 v e. .
(N) SIMPSON
"HU28-2" HGR.
(E) GIRDER TRUSS
DATE: August 16, 2018
JURISDICTION: Carlsbad
✓• EsG1I
A S1Uf.built Company
PLAN CHECK#.: CBR2018-1485
PROJECT ADDRESS: 2005 Cordoba Place
SET: III
PROJECT NAME: Remodel for Cowell Residence
0 APPLICANT
0 JURIS.
~ The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
0 The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
0 The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
0 The check list transmitted herewith is for your information. The plans are being held at EsGil
until corrected plans are submitted for recheck.
0 The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
0 The applicant's copy of the check list has been sent to:
Larry Lipkin
~ EsGil staff did not advise the applicant that the plan check has been completed.
□ EsGil staff did advise th
Person contacted:
Date contacted:
Mail Telephone Fax
applicant that the plan check has been completed.
Lipi. Telephone#: (858) 774-1957
(b ) Email: llipkin61@gmail.com
rson
0 REMARKS:
By: Chris Shaver (for JS)
EsGil
08/9/18
Enclosures:
9320 Chesapeake Drive, Suite 208 ♦ San Diego, California 92123 ♦ (858) 560-1468 ♦ Fax (858) 560-1576
'
DATE: 07/30/18
JURISDICTION: Carlsbad
✓• EsG1I
A SAFEbuilt Company
PLAN CHECK#.: CBR2018-1485
PROJECT ADDRESS: 2005 Cordoba Place
SET: Ilr
PROJECT NAME: Remodel for Cowell Residence
□ APPLICANT ;zr JURIS.
D The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
[gj The check list transmitted herewith is for your information. The plans are being held at EsGil
until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
[gj The applicant's copy of the check list has been sent to:
Larry Lipkin
D EsGil staff did not advise the applicant that the plan check has been completed.
[gj EsGil staff did advise the applicant that the plan check has been completed.
Person contacted: Larry Lipkin o...P Telephone#: (858) 774-1957
Date contacted: '7 I ?,1 \I&' (by.:./4 IJ) Email: llipkin61@gmail.com
Telephone Fax In Person
RKS:
By: Chris Shaver (for JS)
EsGil
07/30/18
Enclosures:
9320 Chesapeake Drive, Suite 208 ♦ San Diego, California 92123 ♦ (858) 560-1468 ♦ Fax (858) 560-1576
Carlsbad CBR2018-1485
07/30/18
NOTE: The items listed below are from the previous correction list. These
remaining items have not been adequately addressed. The numbers of the items
are from the previous check list and may not necessarily be in sequence. The
notes in bold font are current.
PLANS
Please make all corrections, as requested in the correction list. Submit FOUR new
complete sets of plans for commercial/industrial projects (THREE sets of plans for
residential projects). For expeditious processing, corrected sets can be submitted in one
of two ways:
1. Deliver all corrected sets of plans and calculations/reports directly to the City of
Carlsbad Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760) 602-
2700. The City will route the plans to EsGil and the Carlsbad Planning, Engineering and
Fire Departments.
2. Bring mQ corrected set of plans and calculations/reports to EsGil, 9320 Chesapeake
Drive, Suite 208, San Diego, CA 92123, (858) 560-1468. Deliver all remaining sets of
plans and calculations/reports directly to the City of Carlsbad Building Department for
routing to their Planning, Engineering and Fire Departments.
1. All sheets of plans must be signed by the person responsible for their
preparation. (California Business and Professions Code).
MISCELLANEOUS
Per conversation with structural engineer, truss detail can be removed
from plans. If included with plans, provide a legible version.
Please provide note clearly describing proposed modifications/repairs to
truss.
8. To speed up the review process, note on this list (or a copy) where each correction item
has been addressed, i.e., plan sheet, note or detail number, calculation page, etc.
9. Please indicate here if any changes have been made to the plans that are not a result of
corrections from this list. If there are other changes, please briefly describe them and
where they are located in the plans.
• Have changes been made to the plans not resulting from this correction list? Please
indicate:
,Yes □ No □
1 0. The jurisdiction has contracted with EsGil, located at 9320 Chesapeake Drive, Suite
208, San Diego, California 92123; telephone number of 858/560-1468, to perform the
plan review for your project. If you have any questions regarding these plan review
items, please contact Chris Shaver (for JS) at EsGil. Thank you.
Carlsbad CBR2018-1485
07/30/18
~CITY OF
CARLSBAD
SPECIAL INSPECTION
AGREEMENT
B-45
Development Services
Building Division
1635 Faraday Avenue
760-602-2719
www.carlsbadca.gov
In accordance with Chapter 17 of the California Building Code the folloWing must be completed when work being performed
requires special inspection, structural observation and construction material testing.
roject/Permit: __________ Project Address_·------------------
\. THIS SECTION MUST BE COMPLETED BY THE PROPERTY OWNER/AUTHORIZED AGENT. Please check if you are Owner-Builder
□. (lf you checked as owner-builder you must also complete Section 8 of this agreement.)
Name: (Pleaseprint~--------------------------------
(F1rsti (MI) (La.st)
Mailing Addres,~· ---------------------------------
Email_· _______________________ Phone· __________ _
I am: □Property Owner □Property Owner's Agent of Record □Architect of Record □Engineer of Record
State of California Registration Numbe · Expiration Date: _______ _
AGREEMENT: I, the undersigned, declare under penalty of perjury under the laws of the state of California, that I have read,
understand, acknowledge and promise to comply with the City of Carlsbad requirements for special inspections, structural
observations, construction materials testing and off-site fabrication of building components, as prescribed in the statement o1
special inspections noted on the approved plans and, as required by the California Building Code.
Signatur~-----------------------Date: __________ _
!. CONTRACTOR'S STATEMENT OF RESPONSIBILITY (07 CBC, Ch 17, Section 1706). This section must be completed by the
contractor / builder / owner-builder.
Contractor's Company Name: _________________ ~ Please check if yoo are OWner-Builder D
Name: (Pleaseprint) ____ -cc-~----------c=-----------,----c--------
(F,rstJ (MI I llast)
Mailing Address: ________________________________ _
Email: _______________________ Phone_· __________ _
State of California Contractor's License Number: _________ Expiration Date: ______ _
• I acknowledge and, am aware, of special requirements contained in the statement of special inspections noted on
the approved plans;
• I acknowledge that control will be exercised to obtain conformance with the construction documents approved by the
building official;
• I will have in-place procedures for exercising control within our (the contractor's) organization, for the method and
frequency of reporting and the distribution of the reports; and
• I certify that I will have a qualified person within our (the contractor's) organization to exercise such control.
• I wilt provide a final report (letter In comp/lance with CBC Section 1704.1.2 prior to reguestlna tins/
Inspection.
Signature~: ______________________ Date: __________ _
B-45 Page 1 of 1 Rev. 06/11
DATE: 07/26/18
JURISDICTION: Carlsbad
✓• EsG1I
A. SAf-Eburlt Company
PLAN CHECK#.: CBR2018-1485
PROJECT ADDRESS: 2005 Cordoba Place
SET II
PROJECT NAME: Remodel for Cowell Residence
D APPLICANT ,,¢ JURIS.
D The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
[SJ The check list transmitted herewith is for your information. The plans are being held at EsGil
until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
[SJ The applicant's copy of the check list has been sent to:
Larry Lipkin
D EsGil staff did not advise the applicant that the plan check has been completed.
[SJ EsGil staff did advise the applicant that the plan check has been completed.
Person contacted: Larry Lipkin Telephone#: (858) 774-1957
Date contacted: 7(i6(,JY (b~) Email: llipkin61@gmail.com
~Telephone Fax In Person
0 REMARKS:
By: Chris Shaver (for JS)
EsGil
07/20/18
Enclosures:
9320 Chesapeake Drive, Suite 208 ♦ San Diego, California 92123 ♦ (858) 560-1468 ♦ Fax (858) 560-1576
, Carlsbad CBR2018-1485
07/26/18
NOTE: The items listed below are from the previous correction list. These
remaining items have not been adequately addressed. The numbers of the items
are from the previous check list and may not necessarily be in sequence. The
notes in bold font are current.
PLANS
Please make all corrections, as requested in the correction list. Submit FOUR new
complete sets of plans for commercial/industrial projects (THREE sets of plans for
residential projects). For expeditious processing, corrected sets can be submitted in one
of two ways:
1. Deliver all corrected sets of plans and calculations/reports directly to the City of
Carlsbad Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760) 602-
2700. The City will route the plans to EsGil and the Carlsbad Planning, Engineering and
Fire Departments.
2. Bring IlOlQ corrected set of plans and calculations/reports to EsGil, 9320 Chesapeake
Drive, Suite 208, San Diego, CA 92123, (858) 560-1468. Deliver all remaining sets of
plans and calculations/reports directly to the City of Carlsbad Building Department for
routing to their Planning, Engineering and Fire Departments.
1. All sheets of plans must be signed by the person responsible for their
preparation. (California Business and Professions Code).
MISCELLANEOUS
Plans note that changes are being made from last plan check. Please
clearly show what modifications are being proposed to existing truss
system. Modifications of trusses require calculations approved by an
engineer.
Truss detail is not legible, please provide a clearer drawing. Also,
engineers stamp does not have an expiration date, which is required.
a. To speed up the review process, note on this list (or a copy) where each correction item
has been addressed, i.e., plan sheet, note or detail number, calculation page, etc.
9. Please indicate here if any changes have been made to the plans that are not a result of
corrections from this list. If there are other changes, please briefly describe them and
where they are located in the plans.
• Have changes been made to the plans not resulting from this correction list? Please
indicate:
Yes □ No □
10. The jurisdiction has contracted with EsGil, located at 9320 Chesapeake Drive, Suite
208, San Diego, California 92123; telephone number of 858/560-1468, to perform the
plan review for your project. If you have any questions regarding these plan review
items, please contact Chris Shaver (for JS) at EsGil. Thank you.
Carlsbad CBR2018-1485
07/26/18
♦CITY OF
CARLSBAD
SPECIAL INSPECTION
AGREEMENT
B-45
Development Services
Building Division
1635 Faraday Avenue
760-602-2719
www.carlsbadca.gov
In accordance with Chapter 17 of the California Building Code the following must be completed when work being performed
requires special inspection, structural observation and constnJction material testing.
roject/Permit: ___________ Project Address· _________________ _
t THIS SECTION MUST BE COMPLETED BY THE PROPERTY OWNER/AUTHORIZED AGENT. Please check if you are Owner-Builder
□. (If you checked as owner-builder you must also complete Section B of this agreement)
Name: (Pleaseprint----~~-------------------~-------
lFirst) (MI ) (Lest)
Mailing Addres.~·---------------------------------
Email_· _______________________ Phone· __________ _
I am: □Property owner □Property owner's Agent of Record □Archrtect of Record □Engineer of Record
state of California Registration Numbe · Expiration Date: _______ _
AGREEMENT: I, the undersigned, declare under penalty of perjury under the laws of the state of California, that I have read,
understand, acknowledge and promise to comply with the City of Carlsbad requirements for special inspections, structural
observations, construction materials testing and off-site fabrication of building components, as prescribed in the statement o1
special inspections noted on the approved plans and, as required by the California Building Code.
Signatursc·----------------------Date: ___________ _
3. CONTRACTOR'S STATEMENT OF RESPONSIBILITY (07 CBC, Ch 17, Section 1706). This section must be completed by the
contractor I builder/ owner-builder.
Contractor's Company Name:. __________________ Please check if you are OWner-Bullder o
·Name: (Please print) ________________________________ _
(F1rst1 (MI) (Last)
Mailing Address: _________________________________ _
Email· _______________________ Phone· __________ _
state of Galifornia Contractor's License Number_· _________ Expiration Date: ______ _
• I acknowledge and, am aware, of special requirements contained in the statement of special inspections noted on
the approved plans;
• I acknowledge that control will be exercised to obtain conformance with the construction documents approved by the
building official;
• I will have in-place procedures for exercising control within our (the contractor's) organization, for the method and
frequency of reporting and the distribution of the reports; and
• I certify that I will have a qualified person within our (the contractor's) organization to exercise such control.
• I w/11 provkle a final report/letter In comp/lance with CBC Section 1704.1.2 prior to requesting final
inspection.
Signature~: ______________________ Date: __________ _
B-45 Page 1 of 1 Rev. 08/11
•
DATE: 07/02/18
JURISDICTION: Carlsbad
✓• EsG1I
A SAf.~built Cc1mp,w,y
PLAN CHECK#.: CBR2018-1485
PROJECT ADDRESS: 2005 Cordoba Place
SET: I
PROJECT NAME: Remodel for Cowell Residence
□ APPLICANT
□ JURIS.
D The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
IZJ The check list transmitted herewith is for your information. The plans are being held at EsGil
until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
IZJ The applicant's copy of the check list has been sent to:
D EsGil staff did not advise the applicant that the plan check has been completed.
IZJ EsGil staff did advise the applicant that the plan check has been completed.
Person contacted: ~ ~ Telephone#:
Date contacted: (b~) Email: ~o CQ.J(1'Cl W\'t'tt ~Ml
Mail Telephone
0 REMARKS:
By: Javier Snider
EsGil
Fax In Person
Enclosures:
06/25/18
9320 Chesapeake Drive, Suite 208 ♦ San Diego, California 92123 ♦ (858) 560-1468 ♦ Fax (858) 560-1576
Carlsbad CBR2018-1485
07/02/18
PLAN REVIEW CORRECTION LIST
SINGLE FAMILY DWELLINGS AND DUPLEXES
PLAN CHECK#.: CBR2018-1485 JURISDICTION: Carlsbad
PROJECT ADDRESS: 2005 Cordoba Place
FLOOR AREA: Residence=2 l OOsf
Garaga=465sf
REMARKS:
DATE PLANS RECEIVED BY
JURISDICTION:
DATE INITIAL PLAN REVIEW
COMPLETED: 07 /02/ 18
FOREWORD (PLEASE READ):
STORIES: 1
HEIGHT:
DATE PLANS RECEIVED BY
ESGIL CORPORATION: 06/25/18
PLAN REVIEWER: Javier Snider
This plan review is limited to the technical requirements contained in the California version of
the International Residential Code, International Building Code, Uniform Plumbing Code,
Uniform Mechanical Code, National Electrical Code and state laws regulating energy
conservation, noise attenuation and access for the disabled. This plan review is based on
regulations enforced by the Building Department. You may have other corrections based on
laws and ordinance by the Planning Department, Engineering Department, Fire Department or
other departments. Clearance from those departments may be required prior to the issuance of
a building permit.
Present California law mandates that construction comply with the 2016 edition of the California
Code of Regulations (Title 24), which adopts the following model codes: 2015 IRC, 2015 IBC,
2015 UPC, 2015 UMC and 2014 NEC.
The above regulations apply, regardless of the code editions adopted by ordinance.
The following items listed need clarification, modification or change. All items must be satisfied
before the plans will be in conformance with the cited codes and regulations. Per Sec. 105.4 of
the 2015 International Building Code, the approval of the plans does not permit the violation of
any state, county or city law.
To speed up the recheck process, please note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet number, specification section, etc.
Be sure to enclose the marked up list when you submit the revised plans.
Carlsbad CBR2018-1485
07/02/18
PLANS
Please make all corrections, as requested in the correction list. Submit FOUR new
complete sets of plans for commercial/industrial projects (THREE sets of plans for
residential projects). For expeditious processing, corrected sets can be submitted in one
of two ways:
1. Deliver all corrected sets of plans and calculations/reports directly to the City of
Carlsbad Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760) 602-
2700. The City will route the plans to EsGil and the Carlsbad Planning, Engineering and
Fire Departments.
2. Bring TWO corrected set of plans and calculations/reports to EsGil, 9320 Chesapeake
Drive, Suite 208, San Diego, CA 92123, (858) 560-1468. Deliver all remaining sets of
plans and calculations/reports directly to the City of Carlsbad Building Department for
routing to their Planning, Engineering and Fire Departments.
1. All sheets of plans must be signed by the person responsible for their
preparation. (California Business and Professions Code).
FOUNDATION REQUIREMENTS
2. Foundation anchorage in Seismic Design Categories C, Do, D1 and D2. In
addition to the requirements of Section R403.1.6, the following requirements
shall apply to wood light-frame structures in Seismic Design Categories Do, D1
and D2 and wood light-frame townhouses in Seismic Design Category C.
R403.1.6.1
1. Plate washers conforming to Section R602.11.1, 0.229"x3"x3", shall be
provided for all anchor bolts over the full length of required braced wall lines.
Properly sized cut washer shall be permitted for anchor bolts in wall lines not
containing braced wall panels.
2. Interior braced wall plates shall have anchor bolts spaced at not more than 6
feet on center and located within 12 inches of the ends of each plate section
when supported on a continuous foundation.
3. Interior bearing wall sole plates shall have anchor bolts spaced at not more
than 6 feet on center and located within 12 inches of the ends of each plate
section when supported on a continuous foundation.
3. Show holdowns to show compliance with conventional framing per
CRC602.10.2.2.1 and figure 602.10. 7 condition #2.
ELECTRICAL
4. Note on the plans that receptacle outlet locations will comply with CEC Article
210.52.
Carlsbad CBR2018-1485
07/02/18
PLUMBING
5. Specify on the plans whether the existing house was built before or after 1994.
For additions or improvements to a residence built before 1994, note on the
plans that existing "noncompliant" fixtures (toilets that use more than 1.6 gallons
of water per flush, urinals that use more than one gallon of water per flush,
showerheads that have a flow capacity of more than 2.5 gallons of water per
minute, and interior faucets that emit more than 2.2 gallons of water per minute)
shall be replaced. Certification of compliance shall be given to the building
inspector prior to final permit approval. California SB407.
ENERGY CONSERVATION
6. Include on the Title Sheet of the plans the following statement: "Compliance with
the documentation requirements of the 2016 Energy Efficiency Standards is
necessary for this project. Registered, signed, and dated copies of the
appropriate CF 1 R, CF2R, and CF3R forms shall be made available at necessary
intervals for Building Inspector review. Final completed forms will be available for
the building owner."
MISCELLANEOUS
7. Please show an existing floor plan and a proposed. I am unable to to determine
what work is being done in kitchen aside from the door and window. If there is no
other work, or there is going to be a substitution of like items please state so.
8. To speed up the review process, note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet, note or detail number,
calculation page, etc.
9. Please indicate here if any changes have been made to the plans that are not a
result of corrections from this list. If there are other changes, please briefly
describe them and where they are located in the plans.
• Have changes been made to the plans not resulting from this correction list?
Please indicate:
Yes □ No □
10. The jurisdiction has contracted with EsGil, located at 9320 Chesapeake Drive,
Suite 208, San Diego, California 92123; telephone number of 858/560-1468, to
perform the plan review for your project. If you have any questions regarding
these plan review items, please contact Javier Snider at EsGil. Thank you.
Carlsbad CBR2018-1485
07/02/18
~~,_,,
'~ CITY OF
CARLSBAD
SPECIAL INSPECTION
AGREEMENT
B-45
Development Services
Building Division
163S Faraday Avenue
760-602-2719
www.carlsbadca.gov
In accordance with Chapter 17 of the California Building Code the following must be completed when work being performed
requires special Inspection, structural observation and construction material testing.
roject/Permlt: _________ _ Project Address_· ________________ _
\. THIS SECTION MUST BE COMPLETED BY THE PROPERTY OWNER/AUTHORIZED AGENT. Please check if you are Qv.mer-Builder
□. (If you checked as owner-builder you must also complete Section 8 of this agreement.)
Name: (Please print~----------------------------------
(First) (Ml) ILastJ
Mailing Addres. ___________________________________ _
Emai-• _________________________ Phone· __________ _
I am: □Property Owner □Property Owner's Agent of Record □Architect of Record □Engineer of Reoord
State of California Registration Numbe · Expiration Date: ________ _
AGREEMENT: I, the undersigned, declare under penalty of perjury under the laws of the State of California, that I have read,
understand, acknowledge and promise to comply with the City of Carlsbad requirements for special inspections, structural
observations, construction materials testing and off-site fabrication of building components, as prescribed in the statement 01
special inspections noted on the approved plans and, as required by the California Building Code.
Signatur~----------------------Date: ___________ _
3. CONTRACTOR'S STATEMENT OF RESPONSIBILITY (07 CBC, Ch 17, Section 1706). This section must be completed by the
contractor I builder/ owner-builder.
Contractor's Company Name: ___________________ Please check if you are Owner-Buflder O
Name: (Please print) __________________________________ _
(First) (M.I) [Last)
Mailing Address: _________________________________ _
Email: _________________________ Phone: ___________ _
state of California Contractor's License Number_· __________ Expiration Date: _______ _
• I acknowledge and, am aware, of special requirements contained in the statement of special inspections noted on
the approved plans;
• I acknowledge that control will be exercised to obtain conformance with the construction documents approved by the
bUilding official;
• I will have in~place procedures for exercising control within our (the contractor's) organization, for the method and
frequency of reporting and the distribution of the reports; and
• I certify that I will have a qualified person within our (the contractor's) organization to exercise such control.
• I will provide a final report I letter In comp/lance with CBC Section 1704.1.2 prfor to requesting final
inspection.
Signature~: ________________________ ,Date: ___________ _
B-45 Page 1 of 1 Rev. 08/11
Carlsbad CBR2018-1485
07/02/18
[DO NOT PAY -THIS IS NOT AN INVOICE]
VALUATION AND PLAN CHECK FEE
JURISDICTION: Carlsbad PLAN CHECK#.: CBR2018-1485
PREPARED BY: Javier Snider
BUILDING ADDRESS: 2005 Cordoba Place
BUILDING OCCUPANCY: R-3/U-1
BUILDING AREA Valuation
PORTION ( Sq. Ft.) Multiplier
Remodel 465 46.51
Air Conditioning
Fire Sprinklers
TOTAL VALUE
Jurisdiction Code cb By Ordinance
-------------
1997 UBC Buildin Permit Fee .... g ___ --;_]
1997 UBC Plan Check Fee ,.. j
Type of Review: Complete Review
□ Repetitive Fee __3 Repeats
□ Other
0 Hourly
EsGil Fee
DATE: 07/02/18
Reg. VALUE
Mod.
□ Structural Only
1------11 Hr. @ *
Comments: In addition to the above fee, an additional fee of$
$ /hr.) for the CalGreen review.
($)
21,627
21,627
$125.991
is due ( hour@
Sheet of