Loading...
HomeMy WebLinkAbout2035 CALETA CT; ; CB150401; PermitCity of Carlsbad 1635 Faraday Av Carlsbad, CA 92008 03-06-2015 Residential Permit Permit No: CB150401 Building Inspection Request Line (760) 602-2725 Job Address: Permit Type: Parcel No: Valuation: 2035 CALETA CT CBAD RESDNTL Sub Type: RAD Lot#: 0 Constuction Type: 58 Reference#: 2151107900 $464,807.00 Status: ISSUED Applied: 02/06/2015 Entered By: JMA Occupancy Group: # Dwelling Units: 0 0 Structure Type: Plan Approved: 03/06/2015 Issued: 03/06/2015 Bedrooms: Bathrooms: 0 Inspect Area: Orig PC#: Plan Check #: Project Title: GILLEY: 1,909 SF ADDITION// 2,369 SF REMODEL././72 SF COVERED PATIO// 17 SF GARAGE CONVERSION Applicant: Owner: JAMIE GILLEY GILLEY CASEN J & JAMIE L 2035 CALETA CT 2035 CALETA CT CARLSBAD CA 92009 CARLSBAD CA 92009 619-890-0695 Building Permit $1,914.51 Meter Size Add'l Building Permit Fee $0.00 Add'l Reel. Water Con. Fee Plan Check $1,340.16 Meter Fee Add'l Plan Check Fee $0.00 SDCWA Fee Plan Check Discount $0.00 CFD Payoff Fee Strong Motion Fee $60.42 PFF (3105540) Park in Lieu Fee $0.00 PFF (4305540) Park Fee $0.00 License Tax (31 04193) LFM Fee $0.00 License Tax ( 4304193) Bridge Fee $0.00 Traffic Impact Fee (31 05541) Other Bridge Fee $0.00 Traffic Impact Fee (4305541) BTD #2 Fee $0.00 Sidewalk Fee BTD #3 Fee $0.00 PLUMBING TOTAL Renewal Fee $0.00 ELECTRICAL TOTAL Add'l Renewal Fee $0.00 MECHANICAL TOTAL Other Building Fee $0.00 Housing Impact Fee HMP Fee $0.00 Housing lnlieu Fee Pot. Water Con. Fee $5,604.00 Housing Credit Fee Meter Size D3/4 Master Drainage Fee Add'l Pot. Water Con. Fee $0.00 Sewer Fee Reel. Water Con. Fee $0.00 Additional Fees Green Bldg Stands (SB1473) Fee $19.00 Fire Sprinkler Fees Green Bldg Stands Plan Chk Fee $0.00 TOTAL PERMIT FEES I Total Fees: $6,310.67 Total Payments to Date: $6,310.67 Balance Due: I ' rA / FINAL ArP~~~tL Inspector: Date: l J1 7P {., Clearance: D3/4 $0.00 $301.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $238.00 $45.00 $70.18 $0.00 $0.00 $0.00 $917.40 $0.00 ($4, 199.00) $0.00 $6,310.67 $0.00 NOTICE: Please take NOTI~ .t~ t approval of your project includes the "lmpohion" of fees, dedications, reservations, or other exactions hereafter collectively referred to as "fees/exactions. You have 90 days from the date this permit was issued to protest imposition of these fees/exactions. If you protest them, you must follow the protest procedures set forth in Government Code Section 66020(a), and file the protest and any other required information with the City Manager for processing in accordance with Carlsbad Municipal Code Section 3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack, review, set aside, void, or annul their imposition. You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection fees and capacity changes, nor planning, zoning. grading or other similar application processing or service fees in connection with this project. NOR DOES IT APPLY to any fees/exactions of which vou have oreviouslv been aiven a NOTICE similar to this or as to which the statute of limitations has oreviouslv otherwise exoired. THE FOLLOWING APPROVALS REQUIRED PRIOR TO PERMIT ISSUANCE: [i!'PLANNING CltNGINEERING (2BUILDING []FIRE []HEALTH [] HAZMATIAPCDJ (City of Building Permit Application Plan Check No. Cf3 \ S. Ot.JOf 1635 Faraday Ave., Carlsbad, CA 92008 Est. Value p lf(o<f. ff>? ov Ph: 760-602-2719 Fax: 760-602-8558 Plan Ck. Deposit , Carlsbad email: building@carlsbadca.gov Date '2J b { 1~ [swPPPJ!'~ j(/ ] www.carlsbadca.gov JOB ADDRESS 203 5 Cale-l-t"i SUITE#/SPACEf/UNIT# IAPN , C'nut'"'+ -d}15" -/10 -7'1 - CT/PROJECT # I LOT# I PHASEll I# OF UNITS I# BEDROOMS #BATHROOMS I TENANT BUSINESS NAME I CONSTR. TYPE I occ. GROUP DESCRIPTION OF WORK: Include Square Feet of Affected Area(s) ~c\chti ... l of lc.?TGq<;( of ii"') vtrC"Or1 ·~·dehen, c...JfA (.'('/ C:Iuf's!--brz-"'?J<)'Y\ ·-IV ("')<i~ -h~ ~-f-Y\OI"N'. o.( u::m-.~err r7tb /2el)ovCihOn D~ ·z~ .-s{ GO\Ia.re.e ~~u 1:t.ti:l PYJ.s~) hofY)p_ g~e..4o lw·~ EXISTING USE FIREPLACE _._t-\o_l'nc I PROPOSED USE J-6 f'I"'J c:. 1 GARAGE (SF) PATIOS (SF) J DECKS (SF) YEsO I AIR CONDITIONING I FIRE SPRINKLERS NoD YES0No0 YESONoO APPLICANT NAME _b , Prlnarv Contact "' I"() I e i ~c."\1 Mllllr-L/ PROPERTY OWNER NAME ~ \.., -( I it' ~ {/.i., ··..J 6hrtlcv ADDRESS 2035 c..., I~}?-; I Ct. I ADDRESS 2o3s C0 k-hl c+-! ( CITY STATE ZIP CITY ZIP C(;f/o 6b~ .. d CA q20()?1 Ci1rlsbf"cl STATE A c 02txJ"'] PHONE I FAX PHONE . r-I FAX (.R ~r ~qo,. OV> ct ':)' lr?t<ir&c1of Ol'Yi ~ EMAIL . • f\ I (' \ \ \ ce.> rp+rYJ.cJJ), C 0 iY"\ EMAIL .cr!rJ j 1 c 0 h.o~~e1t'/· (~o~ DESIGN PROFESSIONAL ;._t r:_~. De~\U!'\ CONTRACTOR BUS. NAME o.. . .ew ADDRESS ~ol~p ~~t>I0 .ucr c'Y1 tr Pw. ADDRESS CITY Q j S/-\E ZIP CITY STATE ZIP ~()ibb4 c ct'ZDIO .- PHONE . siFAX [(;O-till -I Sn PHONE .I FAX EMAIL EMAIL I STATE LIC. # STATE LIC.# I CLASS I CITY BUS. LIC.# (Sec. 7031.5 Busmess and Professions Code: Any C1ty or County WhiCh reqwres a permit to construct, alter, 1mprove, demoliSh or repa1r any structure, pnor to 1ts 1ssuance, also reqwres the applicant for such permit to file a signed statement that he is licensed pursuant to the provisions of the Contractor's License Law (Chapter 9, commending w1th Section 7000 of Division 3 of the Business and Professions Code) or fhat he is exempt therefrom, and the basis for the alleged exemption. Any violation of Section 7031.5 by any applicant for a permit subjects the applicant to a civil penalty of not more than five hundred dollars ($500)). Workers' Compensation Declaration: I hereby affirm under penalty of perjury one of the following declarations: 0 I have and will maintain a certificate of consent to self·insure for workers' compensalion as provided by Section 3700 of the Labor Code, for the performance of the work for which this permil is issued. 0 I have and will maintain workers' compensation, as required by Seclion 3700 of lhe Labor Code. for the performance of the work for which this permil is issued. My workers' compensation insurance carrier and policy number are: Insurance Co Policy No. Expiralion Dale _________ _ This section need nol be completed if the permit is for one hundred dollars ($1 00) or less. 0 Certificate of Exemption: I certify lhat in lhe performance of lhe work for which this permil is issued, I shall not employ any person in any manner so as to become subject to lhe Workers' Compensalion Laws of California. WARNING: Failure to secure workers' compensation coverage is unlawful, and shall subject an employer to criminal penalties and civil fines up to one hundred thousand dollars (&100,000), in addition to the cost of compensation, damages as provided for in Section 3706 of the Labor code, interest and attorney's fees. ~CONTRACTOR SIGNATURE I hereby affirm that I am exempt from Contractor's License Law for the following reason: ~I, as owner of the property or my employees wilh wages as their sole compensalion, will do lhe work and the slructure is not inlended or offered for sale (Sec. 7044, Business and Professions Code: The Conlraclor's License Law does nol apply Ia an owner of property who builds or improves thereon, and who does such work himself or lhrough his own employees, provided that such improvements are nol inlended or offered for sale. If, however, lhe building or improvemenl is sold wilhin one year of completion, lhe owner-builder will have the burden of proving that he did no I build or improve for lhe purpose of sale). I, as owner of lhe property, am exclusively conlracling wilh licensed contraclors to construe! the project (Sec. 7044, Business and Professions Code: The Contraclor's License Law does not apply loan owner of property who builds or improves !hereon, and contracls for such projects with contraclor(s) licensed pursuant to the Contractor's License Law). I am exempt under Section Business and Professions Code for !his reason: 1. I personally plan to provide the major labor and materials for construclion of lhe proposed property improvement. DYes ~o 2. I (have I have not) signed an applicalion for a building permil for the proposed work. 3. I have conlracled wilh the following person (firm) to provide the proposed construclion (include name address I phone I contraclors' license number): 4. I plan Ia provide portions of lhe work, but I have hired the following person to coordinate, supervise and provide lhe major work (include name I address I phone 1 contraclors' license number): 5. I will provide some of the work, but_l have contract~d (hired) the following persons lo provide lhe work indica led (include name 1 address I phone I type of work): / -0AGENT DATE /) I certify thatl have read the application and state that the above infunnation is correct and that the infunnation on the plans is accurate. I agree to comply with all City on:li nances and State laws relating to building construction. I hereby authorize representative of the City of Cartsbad to enter upon the above mentioned property for inspection purposes.! ALSO AGREE TO SAVE, INDEMNIFY AND KEEP HARMLESS THE CITY OF CARLSBAD AGAINST ALL LIABILITIES, JUDGMENTS, COSTS AND EXPENSES WHICH MAY IN ANY WAY ACCRUE AGAINST SAID CITY IN CONSEQUENCE OF THE GRANTING OF THIS PERMIT OSHA: An OSHA penni! is required for excavations over 5'0' deep and demol~ion or construction of structures over 3 stories in height. EXPIRATION: Every permit issued by the Building Official under the provisions of this Code shall expire by flmitation and become null and void if the building or VYOrk authorized by such permit is not commenced within 180 days from the date of such buildin~ orVYOrk authorized by such perm~ is suspended or abandoned at any time after the VYOrk is commenced for a period of 180 days (Section 106.4.4 Uniform Building Code). DATE Inspection List Permit#: CB150401 Type: RESDNTL RAD GILLEY: 1,909 SF ADDITION// 2,369 SF REMODEL/./ 72 SF COVERED P Date _Inspection Item Inspector Act Comments 01/07/2016 89 Final Combo Rl 01/07/2016 89 Final Combo PY AP 01/07/2016 89 Final Combo PY AP 08/19/2015 23 Gas/T esURepairs PY AP 07/28/2015 17 Interior Lath/Drywall py AP 07/20/2015 16 Insulation PO AP 07/15/2015 84 Rough Combo py AP 06/26/2015 21 Underground/Under Floor PB PA 06/19/2015 13 Shear Panels/HD's py AP 06/15/2015 15 Roof/Reroof py NR 06/12/2015 15 Roof/Reroof MC co COMPLETE WORK 05/06/2015 11 Ftg/Foundation/Piers py AP 05/05/2015 11 Ftg/Foundation/Piers py PA 05/04/2015 11 Ftg/Foundation/Piers py co 04/22/2015 21 Underground/Under Floor PY AP Monday, January 11, 2016 Page 1 of 1 /;#~ ~~ ~ CITY OF CARLSBAD SPECIAL INSPECTION AGREEMENT 8-45 Development Services Building Division 1635 Faraday Avenue 760-602-2719 www.carlsbadca.gov In accordance with Chapter 17 of the California Building Code the following must be completed when work being performed requires special inspection, structural observation and construction material testing. Project/Permit: C. B l '5-=-Ju \ Project Address: 203 5 C 6\ I c-k LDviA A. THIS SECTION MUST BE COMPLETED BY THE PROPERTY OWNER/AUTHORIZED AGENT. Please check if you are Owner-Builder ~(If you checked as owner-builder you must also complete Section B of this agreement.) Name: (Please print) "'-)ao"'J\C L:;J'""~ oe. (F~rst) ( I.) C:::m") I e.f (Last) Mailing Address: Zo ~'5 Citl e·-\n Email· .. 51 C\; \C@) hobYv,~\ · ( O,Y\ Phone: lt' jc\ -~C"jO -Q{/t:;- 1 am: Froperty Owner DProperty Owner's Agent of Record DArchitect of Record DEngineer of Record State of California Registration Numbe · Expiration Date:.~~~~~~~- AGREEMENT: I, the undersigned, declare under penalty of perjury under the laws of the State of California, that I have read, understand, acknowledge and promise to comply with the City of Carlsbad requirements for special inspections, structural observations, construction materials testing and off-site fabrication of building components, as prescribed in the statement of special inspections noted on the approved plans and, as required by the California Building Code. 0 '7·7-f)-Signatur · Date: __:'7=------,_L~__:-~~~~~~- / ( 8. CONTRACTd 'S STATEMENT OF RESPONSIBILITY (07 CBC, Ch 17, Section 1706). This section must be completed by the contractor I builder I owner-builder. Contractor's Company Name:_~~~~~~~~~~~~~-----Please check if you are Owner-Builde')r£ Name: (Please print) __J~\"Y'lt' e L. G,) I fV (First) (M.I) (Last) T MailingAddffi~: ~3~.-~c_·~~\~C-~~-~~C~~~----------------------- Email: g;,-\j \ C B hut 1'0 C"l.\ I l Cu0C'\ State of California Contractor's License Number: _____ ~~---Expiration Date: -~~~~~~- • I acknowledge and, am aware, of special requirements contained in the statement of special inspections noted on the approved plans; • I acknowledge that control will be exercised to obtain conformance with the construction documents approved by the building official; • I will have in-place procedures for exercising control within our (the contractor's) organization, for the method and frequency of reporting and the distribution of the reports; and • I certify that I will have a qualified person within our (the contractor's) organization to exercise such control. • I will provide a final report I Jetter in compliance with CBC Section 1704.1.2 prior to requesting final ins ~ ) Date: .3~ Z -)S-Signature: ? 0( ( / B-45 Page 1 of 1 Rev. 08/11 ~~ 6 40/ SPECIAL INSPECTION DAILY REPORT I HAVE FROIJIIED CN SITE 0 CXNCRE'IE 0 STEEL ASSEMBLY /WELDJN3 0 DATEto .\I. I c-.::; SPEX::IAL INSPEX::TICN SERVICES 0 MASCNRY <"'0 EroxY AN<:::H:R>/In'IELS 0 TESTJN3/Sl'MP.LIN3: FOR THE FO~ ITEMS: 0 FIREFRCDFING 0 SHEAR WALL FRAM:IN; SYSTEM 0 Ol'HER: PROJECI':) ~\1"1 lf $: · 'J\'.:. t'l 1::-l llll 'I \-UL,lcC\ BLDG J:'EHI1IT: eGIS 0'401 PLAN FTIE: ADrnESS:'2 0 3 S C l\ 1.. ~ It\ CT a-mER: (OR REPRESEN'm'I'IVE CITY/AHJl: 1-\12\..SI?i.-\0 ARG!ITECI: TIME lli: I our: I I MilES: I ENGINEER: t '£.Sit\ I'! 'BLDf:.-"DES\ E:;..l'-.1 MA'IERIAL(·( li'-11··( .... ()1~ C...:,~ T Xi; trc.>~Y CCNI'RPCIDR: --1-10 NJ\. c.. _!: .. ~ l LfTI:_ SUEO:NI'RACIOR: ~ \N E>~r-t Tc....:: t \{_, y ,, J\.1 'l+ 1 c s1" e: s~t:. '-'.~.-\ L I t---4£.0t.L.11G ~~ Pt:\Jit\...Jt::-1~ ../'--1~1.:. )(.....-....) E.J _:) i=\...J\ 1"-1 s 5£'2 'Dt_ IJ\ I L 14/ SOl ( ~) HDLIC?"::;> t lui.\) 1)0Wt'-!S. l(.(:P.. TE 1) 'a t;.J\ST 11 '-'-1\.L. L LIIJ 11"--.1<.:. \2. 601 ....... 1 , 'I \)E.-N .-='il \ 'i: 1\ 12. \;oJ.!..\L L ( ~) •S/e_ ', ~ \u I i)q~ f...f\ \.. \J.£.\f'J I ZE \~ e J\l L Tl-\tL~E...!\0 ~GDS \II t IL I 'F I t \ ) tv\\ N ~1'-"\l::,t 1.) t>t..'P'Ttl '1" IN I 0 ( \'I C., T l NC:... 1. :C\1'\.\CILt=: .. n:: f"oc:n ''-'?:-- t~OLi.. S \.A...It;.\4:;. D•..t 1 LL t: 1::J Z/1..\.. 1' e ~ C L~...l'o..Nt';:. 1.:) \''E;,.IL 1'-lA 1'-.J vi=" L\<. I L. \ tL t. 12.;;:;. 1 \i s·r 1.{ \..~c.. no" .s tsf.2 2 Suf_, ( "E-.:6 t: \.2. \.1 E. 0 1 \-\ t IN1EC\iGN Ot='" t 1::::Ux ""·/ ..i\.1) 1--\ f:C., I \J b (. bt \'V'I~S()N <:;; t I XP B.t\i c...t-t :t\ 011 U (c,::loT E~\' 1"2Lila IN!() -\-\(H-f. <;;, \;-.1 IT H _c.. 'S, I\""" 0SCJ 1"-1 \) 1<:; i'f._l\lS II"'-!~ E u I''J '* M\ Y. I 1\..J~ "-CZ2l ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ -pr:\\D CI\G\\ Q.\~-~h1(\5 ~(~ INSPECTOR: tl11 ~<::_ 1 S, 1\ N OE I<Z S 1 siGNATURE: -yr---v-:~>-./__ ./ ,/ CERTIFICATION: SP '101 lCC 51(>'-\-{}-1-{o I DATE: (b. I I. I 5 I HEARBY AKNCWLErGE THAT SPEX::IAL INSPEX::TICN !XES NO!' RELIEVE ME THE a-mER, CXNffillCI'CR, BUilDER CR REFRESENI'ITIVE OF MY RESPCNSIDILITY 'ID ASSURE THAT ALL WCRK IS ~D FER THE APProVED PLANS, SPEX::IFICATICNS AND APPLICABlE BUILDJN3 CDDE. FOR ANY ITEMS PlEASE SCHEIUIE FOR RE-lliSPECIICN. ALL WCRK PERFrnMED IS BILlED IN 4 Ha.JR :rn:::REMENI'S SEE aJR aJRRENI' RA'IES. I HEARBY AGREE 'ID INIEMUEY AND OOW HARMLESS THE INSPECICR llliN3 WTIH ANY AND f\LL ASSQSIA'IED ENI'ITIES FCR ANY AND ALL ClAIMS OF /FCR ~S WHETHER 1\CCIDENrAL OR INI'ENI'ICNAL. I HFARBY RElEASE THE lNSPECI'CR ALCNG WTIH ANY AND ALL ASSXIATED ENTITIES EROIM ANY AND ALL ClAIMS ~ CR UNKNCWN THAT MAY HAVE ARISEN, CR MAY ARISE FRCM THE lliSPECIICN OF THE N5JVE ITEMS. I HFARBY AGREE 'ID PAY FCR ANY AND ALL ATTORNEY AND CXXJRT CCSTS REGAROLEsS OF FINDINGS. I WIU. ~ FOR ANY AND ALL JUIXMENl'S BROOGHI' AGAINsr THE lliSPECICR AND/OR ANY REIA'IED ENI'ITIES IXJE TO 1\NYTHING RE:INIED TO TUIS OJECI WHATSCEVER. a-mER: CCNI'RACIOR: / / /;t::~ L(r ' i .r" i Sic:NA'IURE: I DATE: I SI~'IURE:1 I DA'IE: I GeoTek, Inc. 710 E. Park ridge Avenue. Suite I 05. Corona. C~liforn1a 92879-1 097 (951) 710-1 160 Office 1951) 710-1167 Fax wv.rw.g·cotekusuorn Mr. & Mrs. Gilley 2532 Luciernaga Str·eec Carlsbad, California 92009 Subject: Geotechnical Review of Foundation Plans Proposed Addition 2035 Caleta Court Carlsbad, San Diego County, California March 3, 20 I 5 Project No. 1287-CR3 Reference: Geo Tek, Inc.. 2014, "Limited Geotechnical Evaluation, 2035 Caleta Court, Carlsbad, San Diego County, California," Project No. 1287-CRJ, dated February 12, 2015 Dear Mr. & Mrs. Gilley: As requested, Geo Tek, Inc. (Geo Tek) has reviewed the foundation plans for the subject project. The plans were reviewed from a geotechnical perspective. Specifically. Geo T ek reviewed Sheets I; SO I; SD2; 3; 4; and 5 of the undated plans pr·epared by Deskin Building Design, 1/4" = 1.0' scale where applicable. Based on our review of these plans, we conclude that the plans incorporate the recommendations pr·esented in the referenced report. Please contact the undersigned if you have any questions. MR. & MRS. GILLEY Geotechnical Review of Foundations Plans 2035 Caleta Court, Carlsbad, San Diego County. California Respectfully submitted, GeoTek, Inc. Edward H. LaMont CEG 1892, Exp. 7/31/16 Principal Geologist cc: (I) Client (e-mail) GEOTEK Project No. 1287-CR3 March 3, 2015 Page 2 Edmund Vardeh RGE 2381, Exp. 09/30/15 Project Engineer ~-·FJ. ( IJ( ... J'> {JiE !1 A I IV 5 {:;-;/( & I [{;; (City of Carlsbad CIRCUIT CARD B-36 ~'-~?X~?~_CI__Q/!!_~~?1__ Service~ Building Division 1635 Faraday Avenue 760-602-2719 www.carlsbadca.gov TillS CARD MUST BE FILLED OUT AND AVAILABLE AT THE SERVICE EQUIPMENT FOR THE ROUGH INSPECTION Address: r::J. 0 3 c; C/1[13 TA C T--Cl1f11 c; 1\AO /L'1-Permit Number: C 8 /\.~/Ji./0 I ~---- LOCATION CKT BKR WIRE MISC SIZE SIZE TYPE IUD iF i 1 j<;" I.J ftC I'"(, !.{ MA ~Tr;./1 3 !Iff I. 1{.·:"1 t:.t I? Pdf/· l 5 l'D I ·? /( (?11 t J-1, f3-A 1}{ 7 'J {' 1'2 D 8· a ""'I _5 _fj£ 9 '(' i ') M·"' i§ e l'f ~J i{~ ::--11 I c...-/t..J (Z(;;'"j ID -I 11:::.£:/J~# '7 13 I_,-~ .. ,';. £, LA (<W_fiK 15 1/ I -•/'1 f.") k -./-f J 17 ..&.-v 19 21 23 25 27 29 31 33 35 37 39 41 MAIN: 0 ~ 0 Q AMP BRKJFUSE 0 MLO BUS: 1 ,2 c> AMP Service enlrantir'or feeder c,onductors: ..,../ A) Size: No. !4-. 1<.2 B) Type: 0 CU lli AL C) Insulation: · D) Conduit Size: ~ Service ground/bond: ,.-,-,/. ~ ' A) Size: No. ~-B) Type: ~ CU 0 AL C) Clamp location s): 0 UFER 250-50( c) ,Bt Water Pipe 250 -104 ~ Ground Rod . 250 -52 "0 ${iLQfA2 !1/tilll GFCIIocations 210-8, 680-70: 0 Bathroom{s) 0 Garage(s) 0 Outdoors AFCI Protected Circ. 210-12 0 Bedroom(s) B-36 D Kitchen []Hydromassage Tub o ______ _ 0 REC REC LTG MISC WIRE BKR SIZE TYPE SIZE CKT JL.j AO('i /<:;--2 /u /!!. (,·:'1 J ~.;.-4 f !7 BlJMJ '_/'} 6 I ' 1:1' P--o 1"\~ lt; 8 'I RoM· 1 ~-10 v i •' J ~ -."-'\. 20 12 _j~ A vj£" 14 II~ "'"' (....~ 16 J. I") .-vt. ·.-I ~ 7 ' I v 18 20 22 24 26 28 30 32 34 36 38 40 42 Computed Load ------c------,,--.,...-c-----AMPS See Calculation Worksheet on back Branch circuits required: A) Lighting Circuits 220-3(b), 4(d) B) Two Small Appliance Circuits 210-11(e) C) Laundry Circuit 220 -16(b) D) Central Heating Equipment 422-12 E) Bathroom 210-52(d) Remarks: / 00 /1 c~ f' s; S <-t IJ. I' It ..vEL t,u,.JH f;/0 J:, rz C. A 1: C~'l a r e~ WIRE LOCATION 13f:b.:# L. kJAC i , F> ft. Til -7~ Fl"l0 E,-rJTttq I If]( /\l 7 .-L' {. IJOv 1 U !" /-A f.:.#• C: l. ~ I certify that all terminations have been torqued in accordance with manufacturer's instructions and that the work shown on this circuit card represents the full extent of the work performed under this permit. 0 Owner "dt LL E 'j 0 Contractor Q vv ,v Z: r . 0 Signed ,~; -.'-'> /-Date 7·-/§: /z:; y' ;;/. <...--c--<·<.rF ..,.;;_ _./ Page 1 of2 Rev. 03/09 CIRCUIT CARD 8-36 Development Services Building Division 1635 Faraday Avenue 760-602-2719 www. carlsbadca .gov THIS CARD MUST BE FILLED OUT AND AVAILABLE AT THE SERVICE EQUIPMENT FOR THE ROUGH INSPECTION Address: , C) ··;;; c:; ('A L£7A· Permit Number: C' 13 A J q 0 L/ U j Owner: r;; /t l ; ;;: U\ Phone: /' / q ) s? Q /~ ,.., r c ,. -Area in Sq. Ft. 1 Contractor: t!) r_· /A 1 /1 'f) •7£ /::::St t"'3 ,';(), ~)Phone: , ·'rc l ,_, '1 (' '.-, ., ';> PANEL: ( ... w. I_ A.!.. 7 , "'' 7 VOLTS 0 WIRE LOCATION I CKT BKR WiRE LTG MISC WIRE BKR I CKT LOCATION MISC REC REC SIZE SIZE SIZE TYPE SIZE TYPE kt7rJI 1 lg,a; I.J .> 'E ~ D i.rEII.J. I iA '~ Rot1-'~() 2 f)i/1/j/I,J{l" k/T,'/1, 3 ~-l~ /1..0!'1' D /,:,) J i .• /-") IJ r•i"-1 "'} /) 4 11 .·.~~:· r A/ ·-) () /,-'7r II 5 ,,., j 1 fl()(/'t J1 i( i l /SJ. A.l).£-t 'f.l) 6 ~ fSit'-H I 7 <.... I ,p,:.:; J::: I I •71 Dt1M 11) 8 r: II 'Til /i 1< ' Tt' IJ 4) /') { y?! ,p ,,..., i 1 k hrtl '-" '""~ ·1 h1111 .Ill pfl. LJ' 1 II/' -10 I ~'"' 9 I "'} ,.,_ ."} 1lnM .., ,.., A ;( { .;: ·o •~ ~ 1\ I A-{J /1. ~ ,,. 1.' 11 ,,..,!~ /.I I j :;~v it::i A o_J-1 1 ,-12 uAr~ I 13 ';) :. ' ·-If ... b / .. ., o/ 14 ~--.-il r"A<Mt·· jJ i D .,f'1, i..l .vi ;r .-;'- 1 l l 7 ~-~ . ~· 16 iT i.n ATfi'/D~.i.T 15 I ).--!u ; A.tl'M 2 t..l _o IV'-1. Jr n -; Jl. -t:l ,::;-I 17 / I I I •1 I I. R•·M 18 k1 TrNCV '" 19 I • j ,:1 (.") ·'"' 20 I 1. /IVl I I I 21 Tf"' i: ' ~ .,.-1-t-/1 ~ 22 I'IUt'l./(' I I 23 I i 25 I I I I I I J I i i 27 I I ! I i I l 29 i I I I 31 I I 33 35 I 37 I 39 I I 41 I I MAIN: 0 AMP BRK/FUSE 0 MLO ! BUS: AMP 1 Service entrance or feeder conductors: A) Size: No. ____ _ 8) Type: 0 CU 0 AL D) Conduit Size: __ _ C) Insulation:--:--- Service ground/bond: A) Size: No. ____ _ B) Type: 0 CU 0 AL C) Clamp location(s): ;:] UFER 0 Water Pipe i.J Ground Rod 25C-50( c) 250-104 250-52 0--~---::-::-:c---::-::--GFCIIocations 210-&, 680-70: D Bathroom(s) 0 Garage(s) 0 Outdoors AFCI Protected Circ. 210-12 0 Bedroom(s) B-36 0 Kitchen OHydromassage Tub o _____ _ ! i I i i i '7 /7 24 26 28 I 30 32 34 36 38 40 42 I Computed Load ---=.........,::-:---:-.-:---:-:":-~-:---=----:--AMPS See Calculation Worksheet on back Branch circuits required: A) Ughting Circuits B) Two Small Appliance Circuits 220-3{b), 4{d) 210-11{e) 220 -16(b) 422-12 C) Laundry Circuit D) Central Heating Equipment E) Bathroom Remarks: C:' U {3 ;;>' 210-52( d) 19 All) IE L ( o/J~> C ) ;,_ ,;/ I I I I i I certify that all terminations have been torqued in accordance with manufacturer's instructions and that the work shown on this circuit card represents the full extent of the work petformed under this permit. 0 Owner __ """'71,....,.. __ ~-~s......._.._.,_ __ _ 0 Contractor---E(!.;J..?'7.4c4.6&1~M~~;,.;,,:i.-<::d:«:~:e;,;:!:::!>dt~4=-:--· :--- 0 Signed--------Date 7 ·-o;--Is- Page 1 of2 Rev. 03/09 I ) ~ ~,,,~,, . .,:·,~·:;::"';-11~~1:::~~:~~ ·:~ ~· ~ ................ _______________________ __ 203S CALET/1-GT /5D~ .GeoTek, Inc. -t;o/ Field Observation Report CLIENT: PROJECT: LOCATION: CONTRACTOR: 0.!4 20 a ,;: WORK IN PROGRESS ( ) GRADING ( ) STREET: SG · __ B __ AC __ ( ) SIDEWALK: SG B WO:/ d.' / C, _.(. __ DATE:5-~ I y' Jl ) DAY: t-f''"j!w TH F 5 5 HOURS: UJ ) UTILITY 8/F: S __ W __ JT __ SO__ OTHER __ _ ( ) CURB & GUTTER: SG __ B __ 1 ) WALL ( ) FOUNDATION OTHERUN4ft:<,. .t...R b /.!X.:.~r.,;;,;a · EQUIPMENT;_=------------------------------------------------------------------ TEST RESULTS TEST LOCATION ELEV/ MOISTURE DRY SOIL MAXD TEST RELCOIIP NO. DEPTH CONTENT DENSI1) TYPE TYPE ., / ' \ / // / / v L / \ /' / L '\ / / v / _//j_ ,./ /t /' /' \__ / v ......._,__, / / ~ / /,/ / . -"""'"'"" .. ,,;? ';;>~!;,, sY: y ,_..,1 My r; / .J L,::;r;p: r J > 1 P~. / t ;1"72-;;v t-' PRINT NAME COPIES TO: OFFICE CLIENT/REP ' (WHITE) (YELLOW) __ _ 2.o~S CALET7f GeoTek, 'fife~ a/ CLIENT: 1A:~,\~ {Cpfkl (~; (}{_,( PROJECT: ? .. t ">S' C t\ L~<:l ~ ( 0\.J ,;.::_\ LOCATION: (_~:Qt~\)1\c\ (f.._ q J.C:-(./1 CONTRACTOR: b: I J e j SUPERINTENDENT: ·-;,.._,.~,~<./(A' ~1 FOREMAN: Field Observation Report WO: I Z6f-(' 1Z ~ DATE: .(j I ZC• I 15· DAY:~T W TH F S S HOURS: M .. ,.J I VA m WQRK IN PROGRESS ( ) GRADING ) UTILITY 8/F: S __ W __ JT __ SD__ OTHER ___ ··-,~ ( ) STREET: SG __ B __ AC __ · ( ) CURB & GUTTER: SG __ B ( ) SIDEWALK: SG B ) WALL k' FOUNDATION OTHER EQUIPMENT: COMMENTS I DISCUSSION ~( '·~. \ \. ·.~ . '··' TEST RESULTS TEST LOCATION EL£Vl NO. DEPTH ~.---~~ ~\.-.,,c. i 11. i -· · rt \I~ t \ MOISTURE CONTENT --------~-- DRY DENSITY ---- SOIL TEST RELCOMP TYPE MAXD TYPE .. -. -. ~----·--''" // ~- ,/ _ _.. / / ' .. .. ' •. .. / .... BY: i ~:l l \)v~\ c SIGNATURE: l \_LL (_ r1:3(L. --- '< ' PRINT NAME COPIES TO: OFFICE CLIENT/REP AGENCY CONTRACTOR FIELD FILE (WHITE) __ _ (YELLOW) __ _ (PINK)___ (GOLDENROD)___ (GREEN)--.,---, 1 ATTACHAODITIONALSHEETSASNEEDED. THIS IS SHEET _JOF _!_ . EsGil Corporation In Cl'artnersliip witli qovernment for (]3ui{aing Safety DATE: MARCH 02, 2015 JURISDICTION: CARLSBAD PLAN CHECK NO.: 15-0401 PROJECT ADDRESS: 2035 CALETA COURT PROJECT NAME: SFR ADDITION FOR GILLEY SET: II D APPLICANT D JURIS. D PLAN REVIEWER D FILE D The plans transmitted herewith have been corrected where necessary and substantially comply with the jurisdiction's codes. ~ The plans transmitted herewith will substantially comply with the jurisdiction's building codes when minor deficiencies identified below are resolved and checked by building department staff. D The plans transmitted herewith have significant deficiencies identified on the enclosed check list and should be corrected and resubmitted for a complete recheck. D The check list transmitted herewith is for your information. The plans are being held at Esgil Corporation until corrected plans are submitted for recheck. D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant contact person. D The applicant's copy of the check list has been sent to: JAMIE GILLEY ~ EsGil Corporation staff did not advise the applicant that the plan check has been completed. D EsGil Corporation staff did advise the applicant that the plan check has been completed. Person contacted: JAMIE Telephone#: 619-890-0695 Date contacted: (by: ) Email: girljlc@hotmail.com Mail Telephone Fax In Person ~ REMARKS: 1tl}: The applicant to complete the City Special Inspection Form for Epoxy Anchors; tm: Submit a letter from the soils engineer to the City confirming that the foundation plans have been reviewed & it's been determined that the report recommendations are properly incorporated into the plans. By: ALI SADRE, S.E. Enclosures: EsGil Corporation 0 GA 0 EJ 0 MB 0 PC 2/24 9320 Chesapeake Drive, Suite 208 + San Diego, California 92123 + (858) 560-1468 + Fax (858) 560-1576 EsGil Corporation In CFartnersfiip witli government for CBui{ding Safety DATE: FEB. 12, 2015 JURISDICTION: CARLSBAD PLAN CHECK NO.: 15-0401 PROJECT ADDRESS: 2035 CALETA COURT PROJECT NAME: SFR ADDITION FOR GILLEY SET: I 0 ~PLICANT ~JURIS. 0 PLAN REVIEWER 0 FILE D The plans transmitted herewith have been corrected where necessary and substantially comply with the jurisdiction's codes. D The plans transmitted herewith will substantially comply with the jurisdiction's codes when minor deficiencies identified below are resolved and checked by building department staff. D The plans transmitted herewith have significant deficiencies identified on the enclosed check list and should be corrected and resubmitted for a complete recheck. ~ The check list transmitted herewith is for your information. The plans are being held at Esgil Corporation until corrected plans are submitted for recheck. D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant contact person. ~ The applicant's copy of the check list has been sent to: JAMIE GILLEY D EsGil Corporation staff did not advise the applicant that the plan check has been completed. ~ EsGil Corporation staff did advise the applicant that the plan check has been completed. Person contacted: JAMIE Telephone#: 619-890-0695 ;Date contacted:P/1_3 (by:~mail: girljlc@hotmail.com ~ail ~eje~.~~ Fax In Person ~ REMAR~o}·t~e purpose of fire sprinklers, this is considered a new building (due to extensive remodel and addition) & requires automatic fire sprinklers. By: ALI SADRE, S.E. Enclosures: EsGil Corporation D GA D EJ D MB D PC 2/9 9320 Chesapeake Drive, Suite 208 + San Diego, California 92123 + (858) 560-1468 + Fax (858) 560-1576 CARLSBAD 15-0401 FEB. 12,2015 GENERAL PLAN CORRECTION LIST JURISDICTION: CARLSBAD PROJECT ADDRESS: 2035 CALETA COURT DATE PLAN RECEIVED BY ESGIL CORPORATION: 2/9 REVIEWED BY: ALI SADRE, S.E. FOREWORD (PLEASE READ): PLAN CHECK NO.: 15-0401 DATE REVIEW COMPLETED: FEB. 12,2015 This plan review is limited to the technical requirements contained in the International Building Code, Uniform Plumbing Code, Uniform Mechanical Code, National Electrical Code and state laws regulating energy conservation, noise attenuation and disabled access. This plan review is based on regulations enforced by the Building Department. You may have other corrections based on laws and ordinances enforced by the Planning Department, Engineering Department or other departments. The following items listed need clarification, modification or change. All items must be satisfied before the plans will be in conformance with the cited codes and regulations. The approval of the plans does not permit the violation of any state, county or city law. • Please make all corrections, as requested in the correction list. Submit FOUR new complete sets of plans for commercial/industrial projects (THREE sets of plans for residential projects). For expeditious processing, corrected sets can be submitted in one of two ways: 1. Deliver all corrected sets of plans and calculations/reports directly to the City of Carlsbad Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760) 602-2700. The City will route the plans to EsGil Corporation and the Carlsbad Planning, Engineering and Fire Departments. 2. Bring one corrected set of plans and calculations/reports to EsGil Corporation, 9320 Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-1468. Deliver all remaining sets of plans and calculations/reports directly to the City of Carlsbad Building Department for routing to their Planning, Engineering and Fire Departments. NOTE: Plans that are submitted directly to EsGil Corporation only will not be reviewed by the City Planning, Engineering and Fire Departments until review by EsGil Corporation is complete. • To facilitate rechecking, please identify, next to each item, the sheet of the plans upon which each correction on this sheet has been made and return this sheet with the revised plans. 1. An automatic residential fire sprinkler system shall be installed in single- family dwelling. Please clearly note this on plans. Sec. R313.2. 2. Show the location of permanently wired carbon monoxide alarms with battery backup, per Section R315: a) Outside BR #5 on Sheets #4 & #9. CARLSBAD 15-0401 FEB. 12,2015 3. Openable windows shall be located a minimum of 1 0' from any plumbing vents, chimneys, etc. Section R303.5. 4. Provide a copy of the project soil report. The report shall include foundation design recommendations based on the engineer's findings and shall comply with Section R401.4. The City Policy requires a soils report for this project. 5. Provide a letter from the soils engineer confirming that the foundation/ grading plan and specifications have been reviewed and that it has been determined that the recommendations in the soils report are properly incorporated into the plans. 6. Note on plans that surface water will drain away from building. The grade shall fall a minimum of 6" within the first 1 0'. Sec. R401.3. This applies to the addition. 7. A reminder that as per Figure 1609A, the wind loads must use an ultimate wind speed of 110 mph. 8. Please provide the following information for this project on plans (Section 1603.1): • Roof live load. Each roof live load used should be indicated. • Floor live load. Uniformly distributed, concentrated, and impact live load, including any live load reductions used, should be indicated. • Wind load. The following information should be provided, (Section 1603.1.4) o Ultimate Wind speed (3-second gust), mph, and nominal design wind speed o Risk category o Wind exposure o Applicable internal pressure coefficient o Components and cladding (the design wind pressure in terms of psf to be used for the design of exterior component and cladding materials not specifically designed by the registered design professional) • Seismic design data. The following information should be provided. (Section 1603.1.5) o Risk category o Seismic importance factor, le o Mapped spectral response accelerations S8 and S1 o Site Class o Design spectral response coefficients S08 and S01 o Seismic design category o Basic seismic-force-resisting system(s) o Design base shear o Seismic response coefficient(s), Cs o Response modification factor(s), R, i.e., as per Table 15.4-1, etc. o Analysis procedure used. • Geotechnical information-This applies to the floor support for vertical loads. CARLSBAD 15-0401 FEB. 12,2015 9. The City requires that their Special Inspection Form be completed. This form is available at the building department. 10. The plans shall indicate that special inspection will be provided for the following work. (Section 1 07.2): Please add epoxy anchors to the list of Special Inspections on the cover sheet of the plans: a) Epoxy Anchors. Periodic special inspection should be provided for anchors installed in hardened concrete. Section 1705.3. 11. Show minimum underfloor access of 16" x 24". Section R408.4. 12. Show minimum underfloor ventilation equal to 1 sq. ft. for each 150 sq. ft. of underfloor area. One such opening shall be within 3' of each corner of the building. Section R408.1. 13. Where is detail A/SD1, as referenced on foundation & framing plans? 14. The jurisdiction has contracted with EsGil Corporation located at 9320 Chesapeake Dr., #208, S.D., CA 92123; Tel: 858/560-1468, to perform the plan review for your project. If you have any questions regarding these plan review items, please contact ALI SADRE, S.E. at EsGil Corp. Thank you. CARLSBAD 15-0401 FEB. 12,2015 [DO NOT PAY-THIS IS NOT AN INVOICE] VALUATION AND PLAN CHECK FEE JURISDICTION: CARLSBAD PLAN CHECK NO.: 15-0401 PREPARED BY: ALI SADRE, S.E. DATE: FEB. 12, 2015 BUILDING ADDRESS: 2035 CALETA COURT BUILDING OCCUPANCY: R31U; V-B/SPR. BUILDING AREA Valuation Reg. VALUE PORTION (Sq. Ft.) Multiplier Mod. LIVING ADD & 1909 REMODEL 2369 COVERED 72 PATIO GARAGE 17 CONVERSION Air Conditioning Fire Sprinklers TOTAL VALUE Jurisdiction Code CB By Ordinance Bldg. Permit Fee by Ordinance Plan Check Fee by Ordinance Type of Review: Complete Review D Structural Only D Repetitive Fee ' Repeats ... I - -J D Other 0 Hourly EsGil Fee t------11 H r @ • Comments: Please add $116 for green building code review. ($) 464,807 $1,921.811 $1,249.181 $1,076.211 Sheet 1 of 1 macvalue.doc + PLAN CHECK REVIEW TRANSMITTAL DATE:OJ-02-2015 PROJECT NAME: GillEY RESIDENCE PLAN CHECK NO: 2 SET#: ADDRESS: 2035 CAlETA CT. VALUATION: Community & Economic Development Department 1635 Faraday Avenue Carlsbad CA 92008 www.carlsbadca.gov PROJECT ID: CB15-0401 APN: 215-110-79-00 This plan check review is complete and has been APPROVED by the ENGINEERING Division. By: CG A Final Inspection by the ENGINEERING Division is required Yes No This plan check review is NOT COMPLETE. Items missing or incorrect are listed on the attached checklist. Please resubmit amended plans as required. Plan Check Comments have been sent to: GIRUlC®HOTMAILCOM For questions or clarifications on the attached checklist please contact the following reviewer as marked: PLANNING ENGINEERING FIRE PREVENTION 760-602-4610 760-602-2750 760-602-4665 Chris Glassen 760-602-2784 _ctris.Sexton@carlsbadca . .@.Y. Christogher.Giassen@carlsbadca.gov Gregory.Ryan@carlsbadca.gov Gina.Ruiz@carlsbadca.gov Linda.Ontiveros@carlsbadca.gov Cynthia.Wong@carlsbadca.gov Dominic.Eieri_@_c:!'lrlsb_\:l_Q_cS!,gQy Remarks: RlM 0 2 E-36 Set# issue.\ will be marked with . Make the ncce.>mrv correeliom· codes and 'il;milurds . .')uhmi/ corrected~ division /(>r re·.Hihmillollo the to j1ermil ure 1. SITE PLAN Provide a fully dimensioned site plan drawn to scale. Show: North arrow Existing & proposed structures Existing street improvements Property lines (show all dimensions) Easements Right-of-way width & adjacent streets Show on site plan: Drainage patterns Driveway widths Existing or proposed sewer lateral Existing or proposed water service Submit on signed approved plans DWG No. Building pad surface drainage must maintain a minimum slope of one percent towards an adjoining street or an approved drainage course. ADD THE FOLLOWING NOTE "Finish grade will provide a minimum positive drainage of 2% to swale 5' away from building". Existing & proposed slopes and topography Size, location, alignment of existing or proposed sewer and water service(s) that serves the project Each unit requires a separate service; however, second dwelling units and apartment complexes are an exception. Sewer and water laterals should not be located within proposed driveways, per standards. Include on title sheet: Site address Assessor's parcel number Legal description/lot number For commercial/industrial buildings and tenant improvement projects, include: total building square footage with the square footage for each different use, existing sewer permits showing square footage of different uses (manufacturing, warehouse, office, etc.) previously approved. Show all existing use of SF and new proposed use of SF. Example: Tenant improvement for 3500 SF of warehouse to 3500 SF of office. Lot/Map No.: I MAP #5434 Subdivision/Tract: LA COSTA VAllEY UNTI #1 Reference No(s): Page 2 of 6 REV 6/01112 N/A E-36 Set# 2. DISCRETIONARY APPROVAL COMPLIANCE Project does not comply with the following engineering conditions of approval for project no.: 3. DEDICATION REQUIREMENTS Dedication for all street rights-of-way adjacent to the building site and any storm drain or utility easements on the building site is required for all new buildings and for remodels with a value at or exceeding $ 24,000 , pursuant to Carlsbad Municipal Code Section 18.40.030. For single family residence, easement dedication will be completed by the City of Carlsbad, cost $115.00. Dedication required as follows: 4. IMPROVEMENT REQUIREMENTS All needed public improvements upon and adjacent to the building site must be constructed at time of building construction whenever the value of the construction exceeds $124,000 00, pursuant to Carlsbad Municipal Code Section 18.40 040. Public improvements required as follows sidewalk. Construction of the public improvements must be deferred pursuant to Carlsbad Municipal Code Section 18.40. Please submit a recent property title report or current grant deed on the property and processing fee of $ 444-QG-so we may prepare the necessary Neighborhood Improvement Agreement. This agreement must be signed, notarized and approved by the city prior to issuance of a building permit. Processing fee $157.00. Future public improvements required as follows: Page 3 of 6 CURB, GUTTER, SIDEWALK UNDERGROUND UTILITIES REV6/30/10 E-36 Set# 5. GRADING PERMIT REQUIREMENTS The conditions that require a grading permit are found in Section 15.16 of the Municipal Code. Inadequate information available on site plan to make a determination on grading requirements. Include accurate grading quantities in cubic yards (cut, fill, import, export and remedial). This information must be included on the plans. If no grading is proposed write: "NO GRADING" Grading Permit required. NOTE: The grading permit must be issued and rough grading approval obtained prior to issuance of a building permit Graded Pad Certification required. (Note: Pad certification may be required even if a grading permit is not required.) All required documentation must be provided to your Engineering Construction Inspector The inspector will then provide the engineering counter with a release for the building permit. No grading permit required Minor Grading Permit required. See attached marked-up submittal checklist for project- specific requirements. 6. MISCELLANEOUS PERMITS RIGHT -OF-WAY PERMIT is required to do work in city right-of-way and/or private work adjacent to the public right-of-way. Types of work include, but are not limited to: street improvements, tree trimming, driveway construction, tying into public storm drain, sewer and water utilities. Right-of-way permit required for: Driveway Page 4 of 6 REV 6/01/12 E-36 Set# 7. STORM WATER Construction Compliance Project Threat Assessment Form complete. Enclosed Project Threat Assessment Form incomplete. Requires Tier 1 Storm Water Pollution Prevention Plan. Please complete attached form and return (SW ) Requires Tier 2 Storm Water Pollution Prevention Plan. Requires submittal of Tier 2 SWPPP, payment of processing fee and review by city. Post-Development (SUSMP) Compliance Storm Water Standards Questionnaire complete. Storm Water Standards Questionnaire incomplete. Please make the corrections, re-sign the questionnaire and resubmit with next submittal. Project is subject to Standard Storm Water Requirements. See city Standard Urban Storm Water Management Plan (SUSMP) for reference. http •I /www. carl sbadca. g ov /bus i ness/bu 1id i ng/Docurn ents/E ng Stands w-s tds-vo 14-ch2. pdf Project needs to incorporate low impact development strategies throughout in one or more of the following ways: Rainwater harvesting (rain barrels or cistern) Vegetated Roof Bio-retentions cell/rain garden Pervious pavement/pavers Flow-through planter/vegetated or rock drip line Vegetated swales or rock infiltration swales Downspouts disconnect and discharge over landscape Other Page 5 of 6 REV 6/01/12 Set# 9. WATER METER REVIEW UPGRADE TO METER. 5/8" CREDIT WILL BE GIVEN 8. FEES Domestic (potable) Use FYI FYI What size meter is required? Where a residential unit is required to have an automatic fire extinguishing system, the minimum meter size shall be a 1" meter. NOTE: the connection fee, SDCWA system capacity charge and the water treatment capacity charge will be based on the size of the meter necessary to meet the water use requirements. For residential units the minimum size meter shall be 5/8", except where the residential unit is larger than 3,500 square feet or on a lot larger than one quarter (1/4) acre where the meter size shall be%". I Required fees have been entered in building permit. Drainage fee applicable Added square feet Added square footage in last two years? Permit No. Permit No. Project built after 1980 Impervious surface> 50% Impact unconstructed facility yes yes yes yes no no no no Fire sprinklers required Upgrade No fees required yes yes no (is addition over 150' from center line) no 10. Additional Comments Attachments: Engineering Application Storm Water Form Right-of-Way Application/Info. Reference Documents c E-36 Page 6 of 6 REV 6/01/12 5·1 Fee Calculation Worksheet ENGINEERING DIVISION Prepared by: 02-18-2015 Date: 5 GEO DATA: LFMZ: I B&T: Address: Bldg. Permit#: 5-0401 Fees Update by: Date: 5 Fees Update by: Date: EDU CALCULATIONS: List types and square footages for all uses. Types of Use: Sq.Ft./Units EDU's: Types of Use: Types of Use: Types of Use: Sq .Ft./Units Sq.Ft./Units Sq.Ft./Units ADT CALCULATIONS: List types and square footages for all uses. EDU's: EDU's: EDU's: Types of Use: Sq.Ft./Units ADT's: Types of Use: Sq.Ft./Units ADT's: Types of Use: Types of Use: FEES REQUIRED: Sq.Ft./Units Sq.Ft./Units ADT's: ADT's: Within CFD: YES (no bridge & thoroughfare fee in District #1, reduces Traffic Impact Fee) NO 1. PARK-IN-LIEU FEE: NW QUADRANT NE QUADRANT SE QUADARANT SW QUADRANT ADT'S/UNITS: I X FEE/ADT: I =$ D 2.TRAFFIC IMPACT FEE: ADT'S/UNin X FEE/ADT: I=$ D 3. BRIDGE & THOROUGHFARE FEE: DIST. #1 DIST.#2 DIST.#3 ADT' S/U NITS: ~ FEE/ADT: 1=$ D 4. FACILITIES MANAGEMENT FEE ZONE: ADT'S/UNITS: X FEE/SQ.FT./UNIT: I=$ D 5. SEWER FEE EDU's IX FEE/EDU: I=$ D BENEFIT AREA: EDU's IX FEE/EDU: I=$ D 6. DRAINAGE FEES: PLDA: HIGH MEDIUM LOW ACRES: IX FEE/AC: I=$ D ' 7. POTABLE WATER FEES: UNITS CODE CONN. FEE METER FEE SDCWA FEE TOTAL u $1 ... PLAN CHECK REVIEW TRANSMITTAL Community & Economic Development Department 1635 Faraday Avenue Carlsbad CA 92008 www.carlsbadca.gov DATE:02-18-2015 PROJECT NAME: GillEY RESIDENCE PROJECT ID: CB15-0401 APN: 215-110-79-00 PLAN CHECK NO: SET#: ADDRESS: 2035 CALETA CT. VALUATION: This plan check review is complete and has been APPROVED by the ENGINEERING Division. By: A Final Inspection by the Division is required Yes No This plan check review is NOT COMPLETE. Items missing or incorrect are listed on the attached checklist. Please resubmit amended plans as required. Plan Check Comments have been sent to: For questions or clarifications on the attached checklist please contact the following reviewer as marked: PLANNING ENGINEERING FIRE PREVENTION 760-602-4610 760-602-2750 760-602-4665 Chris Glassen 760-602-2784 _QluJs.Sexton@carl.sbadca.gov _Q.I:lristoQher.GI<;Jssen@carl~l:>adca,ggv Gregory.Ryan@carlsbadca.gov gina.Ruiz@carlsbadca.gov J,.jnda.Ontiveros@carlsbadca.gov Cynthia. Wong@carlsbadca .gov Q.omlni cJ=Jerl@_ga rl~_!;@gcf!gQ_y Remarks: E-36 Set# Any outstandin{J issues will be marked with . i"fake I he necessary corrections complhmce wiiiJ applicaf?le codes ami Sul1mil corrected phms and/or speci(icalions /o the Buildinq division for re-submitlal ro 111e J.nyineeriny division. llerm llwl con(orm to permit are marked wit/1 1. SITE PLAN Provide a fully dimensioned site plan drawn to scale. Show: North arrow Existing & proposed structures Existing street improvements Property lines (show all dimensions) Easements Right-of-way width & adjacent streets Show on site plan: Drainage patterns Driveway widths Existing or proposed sewer lateral Existing or proposed water service Submit on signed approved plans DWG No. Building pad surface drainage must maintain a minimum slope of one percent towards an adjoining street or an approved drainage course. ADD THE FOLLOWING NOTE: "Finish grade will provide a minimum positive drainage of 2% to swale 5' away from building". Existing & proposed slopes and topography Size, location, alignment of existing or proposed sewer and water service(s) that serves the project Each unit requires a separate service; however, second dwelling units and apartment complexes are an exception. Sewer and water laterals should not be located within proposed driveways, per standards. Include on title sheet: Site address Assessor's parcel number Legal description/lot number For commercial/industrial buildings and tenant improvement projects, include: total building square footage with the square footage for each different use, existing sewer permits showing square footage of different uses (manufacturing, warehouse, office, etc.) previously approved. Show all existing use of SF and new proposed use of SF. Example: Tenant improvement for 3500 SF of warehouse to 3500 SF of office. Lot/Map No.: LOT #62/ MAP #5434 Subdivision/Tract: LA COSTA VALLEY UNTI #1 Reference No(s): Page 2 of 6 REV 6/01/12 NIA NEIGHBORHOOD AGREEMENT E-36 Set# 2. DISCRETIONARY APPROVAL COMPLIANCE Project does not comply with the following engineering conditions of approval for project no.: 3. DEDICATION REQUIREMENTS Dedication for all street rights-of-way adjacent to the building site and any storm drain or utility easements on the building site is required for all new buildings and for remodels with a value at or exceeding $ 24,000 , pursuant to Carlsbad Municipal Code Section 18.40.030. For single family residence, easement dedication will be completed by the City of Carlsbad, cost $115.00. Dedication required as follows: 4. IMPROVEMENT REQUIREMENTS All needed public improvements upon and adjacent to the building site must be constructed at time of building construction whenever the value of the construction exceeds $124,000 00, pursuant to Carlsbad Municipal Code Section 18.40.040. Public improvements required as follows: Construction of the public improvements must be deferred pursuant to Carlsbad Municipal Code Section 18.40. Please submit a recent property title report or current grant deed on the property and processing fee of $ 444-Q.Q-so we may prepare the necessary Neighborhood Improvement Agreement. This agreement must be signed, notarized and approved by the city prior to issuance of a building permit. Processing fee $157.00. Future public improvements required as follows: Page 3 of 6 CURB, GUTTER, SIDEWALK UNDERGROUND UTILITIES REV 6/30/10 SEE ADDITIONAl E-36 Set# 5. GRADING PERMIT REQUIREMENTS The conditions that require a grading permit are found in Section 15.16 of the Municipal Code. Inadequate information available on site plan to make a determination on grading requirements. Include accurate grading quantities in cubic yards (cut, fill, import, export and remedial). This information must be included on the plans. If no grading is proposed write: "NO GRADING" Grading Permit required. NOTE: The grading permit must be issued and rough grading approval obtained prior to issuance of a building permit. Graded Pad Certification required. (Note: Pad certification may be required even if a grading permit is not required.) All required documentation must be provided to your Engineering Construction Inspector The inspector will then provide the engineering counter with a release for the building permit. No grading permit required. Minor Grading Permit required. See attached marked-up submittal checklist for project- specific requirements. 6. MISCELLANEOUS PERMITS RIGHT -OF-WAY PERMIT is required to do work in city right-of-way and/or private work adjacent to the public right-of-way. Types of work include, but are not limited to: street improvements, tree trimming, driveway construction, tying into public storm drain, sewer and water utilities. Right-of-way permit required for: Driveway Page 4 of 6 REV 6/01/12 Set# 7. STORM WATER REQUIRES TIER 2 PER E-36 Construction Compliance Project Threat Assessment Form complete. Enclosed Project Threat Assessment Form incomplete. Requires Tier 1 Storm Water Pollution Prevention Plan. Please complete attached form and return (SW ) Requires Tier 2 Storm Water Pollution Prevention Plan. Requires submittal of Tier 2 SWPPP, payment of processing fee and review by city. Post-Development (SUSMP) Compliance Storm Water Standards Questionnaire complete. Storm Water Standards Questionnaire incomplete. Please make the corrections, re-sign the questionnaire and resubmit with next submittal. Project is subject to Standard Storm Water Requirements. See city Standard Urban Storm Water Management Plan (SUSMP) for reference. httpi lwww carlsbadca govlbusiness/buildi ng/Documents/EngStandsw-stds-vol4-ch2 QQf Project needs to incorporate low impact development strategies throughout in one or more of the following ways: Rainwater harvesting (rain barrels or cistern) Vegetated Roof Bio-retentions cell/rain garden Pervious pavement/pavers Flow-through planter/vegetated or rock drip line Vegetated swales or rock infiltration swales Downspouts disconnect and discharge over landscape Other: Page 5 of 6 REV 6/01112 Set# 9. WATER METER REVIEW MUST UPGRADE TO METER. CREDIT WILL BE GIVEN 8. FEES Domestic (potable) Use FYI What size meter is required? Where a residential unit is required to have an automatic fire extinguishing system, the minimum meter size shall be a 1" meter. NOTE: the connection fee, SDCWA system capacity charge and the water treatment capacity charge will be based on the size of the meter necessary to meet the water use requirements. For residential units the minimum size meter shall be 5/8", except where the residential unit is larger than 3,500 square feet or on a lot larger than one quarter (1/4) acre where the meter size shall be%". Required fees have been entered in building permit. Drainage fee applicable Added square feet Added square footage in last two years? Permit No. Permit No. Project built after 1980 Impervious surface > 50% Impact unconstructed facility yes yes 1 yes yes no no no no Fire sprinklers required Upgrade No fees required yes yes no (is addition over 150' from center line) no 10. Additional Comments PLEASE SUBMIT COPY OF GRANT DEED TO DRAFT N.I.A. INOR GRADING PER CARLSBAD MUNICIPAL CODE 15.16.050. PlEASE SEE ATTACHED CHECKLIST. Attachments: Engineering Application Storm Water Form Right-of-Way Application/Info. Reference Documents c E-36 Page 6 of 6 REV 6/01112 215-110-79-00 Fee Calculation Worksheet ENGINEERING DIVISION Prepared by: 02-18-2015 Date: 02-1 5 GEO DATA: LFMZ: I B&T: Address: Bldg. Permit#: CB15-0401 Fees Update by: Date: 5 Fees Update by: Date: EDU CALCULATIONS: List types and square footages for all uses. Types of Use: Sq.Ft./Units EDU's: Types of Use: Sq.Ft./Units EDU's: Types of Use: Sq.Ft./Units EDU's: Types of Use: Sq.Ft./Units EDU's: ADT CALCULATIONS: List types and square footages for all uses. Types of Use: Sq. Ft./Units ADT's: Types of Use: Sq.Ft./Units ADT's: Types of Use: Types of Use: FEES REQUIRED: Sq.Ft./Units Sq.Ft./Units ADT's: ADT's: Within CFD: YES (no bridge & thoroughfare fee in District #1, reduces Traffic Impact Fee) NO 1. PARK-IN-LIEU FEE: NW QUADRANT NE QUADRANT SE QUADARANT SW QUADRANT ADT'S/UNITS: I X FEE/ADT: I =$ D 2.TRAFFIC IMPACT FEE: ADT'S/UNIT~ X FEE/ADT: I=$ D 3. BRIDGE & THOROUGHFARE FEE: DIST. #1 DIST.#2 DIST.#3 ADT'S/UNITS: FEE/ADT: 1=$ D 4. FACILITIES MANAGEMENT FEE ZONE: ADT'S/UNITS: X FEE/SQ. FT./UNIT: I=$ D 5. SEWER FEE EDU's IX FEE/EDU: I=$ D BENEFIT AREA: EDU's IX FEE/EDU: I=$ D 6. DRAINAGE FEES: D PLDA: HIGH MEDIUM LOW ACRES: jx FEE/AC: I=$ GZJ 7. POTABLE WATER FEES: UNITS CODE CONN. FEE METER FEE SDCWA FEE TOTAL 03/4 (city of· GRADING PLAN Develoement Services INITIAL SUBMITTAL Carlsbad Land Development Engineering CHECKLIST 1635 Faraday Avenue 760-602-2 750 E-8 www.carlsbadca.gov THIS SECTION TO BE COMPLETED BY CITY PERSON:-JEL Project ID Project Name DWG No. GR No. Project Engineer • Submittals may be rejected if the submittal package is incomplete or current forms are not used. • Items marked with an asterisk(*) must be completed by an appropriately licensed engineer. THE FOLLOWING ITEMS MUST BE INCLUDED IN THE INITIAL SUBMITTAL: All items must be submitted unless an item is marked "N/A" and initialed by city engineering personnel. __ 0) This submittal checklist __ (2) Transmittal from engineer of work listing all items being submitted __ @) Completed and signed city Engineering Plancheck Application 4. a) Digital submittal of plans, b) Completed digital submittal checklist. and c) Layer description -see engineering standards on city website for digital submittal requirements and checklist __ 5. Copy of environmental clearance or completed E.I.A. form, Part 1, with copy of grading plans attached, if no prior CEQA approval --® ·~sets of prints of the grading plans folded to 9" X 12'~~re..e.. ~~) __ 7. *Two sets of bound drainage report __ @ *Two sets of bound soils report __ ® *Two copies of earthwork quantity calculations --·~ *Two copies of engineer's cost estimate __ \D) Two sets of preliminary title report (issued within six months of application) __ 12. Three copies of all signed conditions of approval (if applicable) __ 13. Three sets of prints of approved site plan or tentative map signed by planner and project engineer (if applicable) · __ 14. Three copies of Notice of Intent to Issue Coastal Development Permit, when applicable --15. Concurrent submittal required (as applicable): finalfparcel map, improvement plans, easement documents, temporary construction easement for off-site grading, etc. --@ Original and one copy of completed and signed Storm Water Compliance form per the completed Project Threat Assessment worksheet. Check type of compliance form required : 0Tier 2 0Tier 3 --G:.D One Storm Water Pollution Prevention Plan .(S.WPPP). ··Check type of SWPPP required using the Project Threat Assessment worksheet: 0Tier 2 UTier 3 --® Originai and one copy of completed and signed Storm Water Standards Questionnaire --19. *Two sets of Storm Water Management Plan (SWMP) (required if project is defined as a priority project per the Storm Water Standards Questionnaire or if conditioned with project) __ 20. SWPPP/SWMP review fee(s). if applicable --@ Grading plancheck fee 22. Other: ________________________________ _ COMMENTS _____________________________________________________________ ___ !suBMITTAL COMPLETE. CHECKED BY DATE E-8 Page 1 of 3 REV 01/15 '~ "' •: ~ CITY OF CARLSBAD STORM WATER COMPLIANCE ASSESSMENT B-24 Development Services Building Division 1635 Faraday Avenue 760-602-2719 www .carlsbadca .gov I am applying to the City of Carlsbad for the following type(s) of construction permit: ·-Q.-Building Permit I 0 My project is categorically EXEMPT from the requirement to prepare a storm water pollution prevention plan (SWPPP) because it only requires issuance of one or more of the following permit types: D Right-of-Way Permit Patio/Deck Photo Voltaic Re-Roofing Sign Spa-Factory Sprinkler Electrical Fire Additional Fire Alarm Fixed Systems Mechanical Mobile Home Plumbing Water Discharge Project Storm Water Threat Assessment Criteria* No Threat Assessment Criteria 0 My project qualifies as NO THREAT and is exempt from the requirement to prepare a stonm water pollution prevention plan (SWPPP) because it meets the 'no threaf' assessment criteria on the City's Project Threat Assessment Worksheet for Determination of Construction SWPPP Tier Level. My project does not meet any of the High, Moderate or Low Threat criteria described below. Tier 1 · Low Threat Assessment Criteria ¢ ~-My project does not meet any of the Significant or Moderate Threat criteria, is not an exempt penmit type (See list above) and the project meets one or more of the following criteria: • Results in some soil disturbance; and/or II i / • Includes outdoor construction activities (such as saw cutting, equipment washing, material stockpiling, vehicle fueling, waste stockpiling). \:ier.{_) Moderate Threat Assessment Criteria · · _;-. My project does not meet any of the Significant Threat assessment Criteria described below and meets one or more of the following criteria: • Project requires a grading plan pursuant to the Carlsbad Grading Ordinance (Chapter 15.16 of the Carlsbad Municipal Code); or, • Project will result in 2,500 square feet or more of soils disturbance including any associated construction staging, stockpiling, pavement removal, equipment storage, refueling and maintenance areas and project meets one or more of the additional following criteria: • Located within 200 feet of an environmentally sensitive area or the Pacific Ocean, and/or • Disturbed area is located on a slope with a grade at or exceeding 5 horizontal to 1 vertical, and/or • Disturbed area is located along or within 30 feet of a storm drain inlet, an open drainage channel or watercourse, and/or • Construction will be initiated during the rainy season or will extend into the rainy season (Oct 1 through April 30). Tier 3 · Significant Threat Assessment Criteria CJ My project includes clearing, grading or other disturbances to the ground resutting in soil disturbance totaling one or more acres including any associated construction staging, equipment storage, stockpiling, pavement removal, refueling and maintenance areas: and/or 0 My project is part of a phased development plan that will cumulatively result in soil disturbance totaling one or more acres including any associated construction staging, equipment storage, refueling and maintenance areas: or, 0 My project is located inside or within 200 feet of an environmentally sensitive area (see City ESA Proximity map) and has a significant potential for contributing pollutants to nearby receiving waters by way of storm water runoff or non-stonm water discharge(s). I certify to the best of my knowledge that the above checked statements are true and correct. I understand and acknowledge that even though this project does not require preparation of a construction SWPP, I must still adhere to, and at all times during construction activities for the permit type{s) check above comply with the storm water best management practices pursuant to Title 15 of the Carlsbad Municipal Code and to City Standards. Project Address: Assessor Parcel No. 'The City Engineer may authorize minor variances from the Storm Water Threat Assessment Criteria in special circumstances where it can be shown that a lesser or higher Construction SWPPP Tier Level is warranted. B-24 --,_,s ~ ;::>..-(t<il e lt1 C+ Owner/Owner's Authorized Agent Name: J1rn~ ( ~ eel><~-, f:::>,:\t'/ Owner/Owner:S Authprized Agent gignature: )''l . { .': L·( ' c:-~·\ \.City Concurrence: By: Date: 'jYES Q NO c (r s l-IS Page 1 of 1 Title: Ow~ Date: :?--/ 3/15 Project 10: ( () ,~--'f 0 I Rev.03/09 Construction SWPPPTier Level Tier 3 Tier 2 Tier 1 Exempt CONSTRUCTION THREAT ASSESSMENT WORKSHEET FOR DETERMINATION OF PROJECT'S PERCEIVED THREAT TO STORM WATER QUALITY E-33 Development Services land Development Engineering 1635 Faraday Avenue 760-602-2750 www.carlsbadca.gov Perceived Construction Threat Assessment Criteria* Threat to Storm Water Quality Tier 3 -High Construction Threat Assessment Criteria 0 Project site is 50 acres or more and grading will occur during the rainy season 0 Project site is 1 acre or more in size and is located within the Buena Vista or Agua Hedionda Lagoon watershed, inside or within 200 feet of an environmentally sensitive area (ESA) or discharges directly to an ESA High 0 Soil at site is moderately to highly erosive (defined as having a predominance of soils with 0 USDA-NRCS Erosion factors kt greater than or equal to 0.4) Site slope is 5 to 1 or steeper 0 Construction is initiated during the rainy season or will extend into the rainy season (Oct. 1 0 through April 30). Owner/contractor received a Storm Water Notice of Violation within past two years Tier 3 -Medium Construction Threat Assessment Criteria Medium 0 All projects not meeting Tier 3 High Construction Threat Assessment Criteria Tier 2 High Construction Threat Assessment Criteria 0 Project is located within the Buena Vista or Agua Hedionda Lagoon watershed, inside or within 200 feet of an environmentally sensitive area (ESA) or discharges directly to an ESA 0 Soil at site is moderately to highly erosive (defined as having a predominance of soils with USDA-NRCS Erosion factors kr greater than or equal to 0.4) High 0 Site slope is 5 to 1 or steeper r:: Construction is initiated during the rainy season or will extend into the rainy season (Oct. 1 through April 30). Owner/contractor received a Storm Water Notice of Violation within past two years 0 Site results in one half acre or more of soil disturbance Tier 2 -Medium Construction Threat Assessment Criteria Medium 0 All projects not meeting Tier 2 High Construction Threat Assessment Criteria Tier 1 -Medium lnsQection Threat Assessment Criteria 0 Project is located within the Buena Vista or Agua Hedionda Lagoon watershed, within or \ directly adjacent to an environmentally sensitive area (ESA) or discharges directly to an ESA 0 Soil at site is moderately to highly erosive (defined as having a predominance of soils with USDA-NRCS Erosion factors kr greater than or equal to 0.4) Medium li Site slope is 5 to 1 or steeper Construction is initiated during the rainy season or will extend into the rainy season (Oct. 1 through April 30). 0 Owner/contractor received a Storm Water Notice of Violation within past two years 0 Site results in one half acre or more of soil disturbance Tier 1 -Low lnsQection Threat Assessment Criteria Low 0 All projects not meeting Tier 1 Medium Construction Threat Assessment Criteria -Not Applicable -Exempt *The c1ty eng1neer may authonze mmor vanances from the construction threat assessment cntena 1n special Circumstances where it can be shown that a lesser or higher amount of storm water compliance inspection is warranted in the opinion of the city engineer E-33 Page 1 of 1 REV 4/30/10 ',,,,,. ~ CITY OF C RLSB STORM WATER STANDARDS QUESTIONNAIRE E-34 Development Services Land Development Engineering 1635 Faraday Avenue 760-602-2750 www.carlsbadca.gov To address post-development pollutants that may be generated from development projects, the City requires that new development and significant redevelopment priority projects incorporate Permanent Storm Water Best Management Practices (BMP's) into the project design per the City's Standard Urban Stormwater Management Plan (SUSMP). To view the SUSMP, refer to the Engineering Standards (Volume 4, Chapter 2) at www,carlsbadca.gov/standards. Initially this questionnaire must be completed by the applicant in advance of submitting for a development application (subdivision, discretionary permits and/or construction permits). The results of the questionnaire determine the level of storm water standards that must be applied to a proposed development or redevelopment project. Depending on the outcome, your project will either be subject to 'Standard Stormwater Requirements' or be subject to additional criteria called 'Priority Development Project Requirements'. Many aspects of project site design are dependent upon the storm water standards applied to a project. Your responses to the questionnaire represent an initial assessment of the proposed project conditions and impacts. City staff has responsibility for making the final assessment after submission of the development application. If staff determines that the questionnaire was incorrectly filled out and is subject to more stringent storm water standards than initially assessed by you, this will result in the return of the development application as incomplete. In this case, please make the changes to the questionnaire and resubmit to the City. If you are unsure about the meaning of a question or need help in determining how to respond to one or more of the questions, please seek assistance from Land Development Engineering staff. A separate completed and signed questionnaire must be submitted for each new development application submission. Only one completed and signed questionnaire is required when multiple development applications for the same project are submitted concurrently. In addition to this questionnaire, you must also complete, sign and submit a Project Threat Assessment Form with construction permits for the project. Please start by completing Step 1 and follow the instructions. When completed, sign the form at the end and submit this with your application to the city. 1. Is your project LIMITED TO constructing new or retrofitting paved sidewalks, bicycle lanes or trails that meet the following criteria: (1) Designed and constructed to direct storm water runoff to adjacent vegetated areas, or other non-erodible permeable areas; OR (2) designed and constructed to be hydraulically disconnected from paved streets or roads; OR (3) designed and constructed with permeable pavements or surfaces in accordance with USEPA Green Streets uidance? 2. Is your project LIMITED TO retrofitting or redeveloping existing paved alleys, streets, or roads that are designed and constructed in accordance with the USEPA Green Streets guidance? YES NO If you answered "yes" to one or more of the above questions, then your project is NOT a priority development project and therefore is NOT subject to the storm water criteria required for priority development projects. Go to step 4, mark the last box stating "my project does not meet PDP requirements" and complete applicant information. If you answered "no" to both questions, then go to Step 2. E-34 Page 1 of 3 Effective 6/27113 /{~'\:,, .,, '-..:~ f· . ·-~ CITY OF CARLSBAD STORM WATER STANDARDS QUESTIONNAIRE E-34 Development Services Land Development Engineering 1635 Faraday Avenue 760-602-2750 www.carlsbadca.gov To determine if your project is a priority development project, please answer the following questions: 1. Is your project a new development that creates 10,000 square feet or more of impervious surfaces collectively over the entire project site? This includes commercial, industrial, residential, mixed-use, and public develo ment ro ·eels on ublic or rivate land. 2. Is your project creating or replacing 5,000 square feet or more of impervious surface collectively over the entire project site on an existing site of 10,000 square feet or more of impervious surface? This includes commercial, industrial, residential, mixed-use, and ublic develo ment ro ·eels on ublic or rivate land. 3. Is your project a new or redevelopment project that creates 5,000 square feet or more of impervious surface collectively over the entire project site and supports a restaurant? A restaurant is a facility that sells prepared foods and drinks for consumption, including stationary lunch counters and refreshment stands selling prepared foods and drinks for immediate consum lion. 4. Is your project a new or redevelopment project that creates 5,000 square feet or more of impervious surface collectively over the entire project site and supports a hillside development project? A hillside development project includes development on any natural slope that is twenty-five percent or greater. 5. Is your project a new or redevelopment project that creates 5,000 square feet or more of impervious surface collectively over the entire project site and supports a parking lot. A parking lot is a land area or facility for the tempora parking or storage of motor vehicles used personally for business or for commerce. 6. Is your project a new or redevelopment project that creates 5,000 square feet or more of impervious surface collectively over the entire project site and supports a street, road, highway freeway or driveway? A street, road, highway, freeway or driveway is any paved impervious surface used for the transportation of automobiles, trucks, motorc cles, and other vehicles. 7. Is your project a new or redevelopment project that creates or replaces 2,500 square feet or more of impervious surface collectively over the entire site, and discharges directly to an Environmentally Sensitive Area (ESA)? "Discharging Directly to" includes flow that is conveyed overland a distance of 200 feet or less from the project to the ESA, or conveyed in a pipe or open channel any distance as an isolated flow from the ro·ect to the ESA i.e. not commin les with flows from ad·acent lands.* 8. Is your project a new development that supports an automotive repair shop? An automotive repair shop is a facility that is categorized in any one of the following Standard Industrial Classification (SIC) codes: 5013, 5014, 5541, 7532-7534, or 7536-7539. 9. Is your project a new development that supports a retail gasoline outlet (RGO)? This category includes RGO's that meet the following criteria: (a) 5,000 square feet or more or (b) a project Average Daily Traffic (ADT) of 100 or more vehicles erda . 1 O.ls your project a new or redevelopment project that results in the disturbance of one or more acres of land and are expected to generate pollutants post construction? 11.1s your project located within 200 feet of the Pacific Ocean and (1) creates 2,500 square feet or more of impervious surface or (2) increases impervious surface on the property by more than 10%? YES NO X X )< X .X: )( X .X )( X If you answered "yes" to one or more of the above questions, you ARE a priority development project and are therefore subject to implementing structural Best Management Practices (BMP's) in addition to implementing Standard Storm Water Requirements such as source control and low impact development BMP's. A Storm Water Management Plan (SWMP) must be submitted with your application(s) for development. Go to step 3 for redevelopment projects. For new projects, go to step 4 at the end of this questionnaire, check the "my project meets PDP requirements" box and complete applicant information. If you answered "no" to all of the above questions, you ARE NOT a priority development project and are therefore subject to implementing only Standard Storm Water Requirements such as source control and low impact development BMP's required for all development projects. A Storm Water Management Plan (SWMP) is not required with your application(s) for development. Go to step 4 at the end of this questionnaire, check the "my project does not meet PDP requirements" box and complete applicant information. E-34 Page 2 of 3 Effective 6/27113 \ ~ ... .... ~ CITY OF STORM WATER COMPLIANCE FORM TIER 1 CONSTRUCTION SWPPP CARLSBAD STORM WATER COMPLIANCE CERTIFICATE -./ My project is not in a category of permit types exempt from the Construction SWPPP requirements -./ My project is not located inside or within 200 feet of an environmentally sensitive area with a significant potential for contributing pollutants to nearby receiving waters by way of storm water runoff or non-storm water discharge(s). -./ My project does not require a grading plan pursuant to the Carlsbad Grading Ordinance (Chapter 15.16 of the Carlsbad Municipal Code) -./ My project will not result in 2,500 square feet or more of soils disturbance including any associated construction staging, stockpiling, pavement removal, equipment storage, refueling and maintenance areas that meets one or more of the additional following criteria: located within 200 feet of an environmentally sensitive area or the Pacific Ocean; and/or, disturbed area is located on a slope with a grade at or exceeding 5 horizontal to 1 vertical; and/or • disturbed area is located along or within 30 feet of a storm drain inlet, an open drainage channel or watercourse; and/or • construction will be initiated during the rainy season or will extend into the rainy season (Oct. 1 through April 30). I CERTIFY TO THE BEST OF MY KNOWLEDGE THAT ALL OF THE ABOVE CHECKED STATEMENTS ARE TRUE AND CORRECT. I AM SUBMITTING FOR CITY APPROVAL A TIER 1 CONSTRUCTION SWPPP PREPARED IN ACCORDANCE WITH THE REQUIREMENTS OF CITY STANDARDS. I UNDERSTAND AND ACKNOWLEDGE THAT I MUST: (1) IMPLEMENT BEST MANAGEMENT PRACTICES (BMPS) DURING CONSTRUCTION ACTIVITIES TO THE MAXIMUM EXTENT PRACTICABLE TO MINIMIZE THE MOBILIZATION OF POLLUTANTS SUCH AS SEDIMENT AND TO MINIMIZE THE EXPOSURE OF STORM WATER TO CONSTRUCTION RELATED POLLUTANTS; AND, (2) ADHERE TO, AND AT ALL TIMES, COMPLY WITH THIS CITY APPROVED TIER 1 CONSTRUCTION SWPPP THROUGHOUT THE DURATION OF THE CONSTRUCTION ACTIVITIES UNTIL THE CONSTRUCTION WORK IS COMPLETE AND APPROVED BY THE CITY OF CARLSBAD. AME (PRINT) 2/&i!) 1AME (SIGNATURE) DATE E-29 E-29 ~' ~ '\ I I STORM WATER POLLUTION PREVENTION NOTES 1. ALL NECESSARY EQUIPMENT AND MATERIALS SHALL BE AVAILABLE ON SITE TO FACILITATE RAPID INSTALLATION OF EROSION AND SEDIMENT CONTROL BMPS WHEN RAIN IS EMINENT. 2. THE OWNER/CONTRACTOR SHALL RESTORE ALL EROSION CONTROL DEVICES TO WORKING ORDER TO THE SATISFACTION OF THE CITY ENGINEER AFTER EACH RUN-OFF PRODUCING RAINFALL. 3. THE OWNER/CONTRACTOR SHALL INSTALL ADDITIONAL EROSION CONTROL MEASURES AS MAY BE REQUIRED BY THE CITY ENGINEERING OR BUILDING INSPECTOR DUE TO UNCOMPLETED GRADING OPERATIONS OR UNFORESEEN CIRCUMSTANCES WHICH MAY ARISE. 4. ALL REMOVABLE PROTECTIVE DEVICES SHALL BE IN PLACE AT THE END OF EACH WORKING DAY WHEN THE FIVE (5) DAY RAIN PROBABILITY FORECAST EXCEEDS FORTY PERCENT (40%). SILT AND OTHER DEBRIS SHALL BE REMOVED AFTER EACH RAINFALL. 5. ALL GRAVEL BAGS SHALL BE BURLAP TYPE WITH 3/4 INCH MINIMUM AGGREGATE. 6. ADEQUATE EROSION AND SEDIMENT CONTROL AND PERIMETER PROTECTION BEST MANAGEMENT PRACTICE MEASURES MUST BE INSTALLED AND MAINTAINED. SPECIAL NOTES Page 1 of 3 Development Services Land Development Engineering 1635 Faraday Avenue 760-602-2750 www.carlsbadca.gov PROJECT INFORMATION .site Address: .).(:;"'"22 Cctl e tv; Ot . Assessor's Parcel Number:------- Project ID: 3W I S-7 Y Construction Permit No.:CBf Sol{ oJ Estimated Construction Start Date ____ _ Project Duration Months • Emergency Contact: • Name: ~IY)Ie &i I \ev I • 24 hour Phone: LQ \C\-0C\ 0-ex oC.\CS Perceived Threat to Storm Water Quality f;iJ Medium O Low If medium box is checked, must attach a site plan sheet showing proposed work area and location of proposed structural BMPs For City Use Only CITY OF CARLSBAD STANDARD TIER 1 SWPPP Approved By: C. G- Date: 5 ' J -I ') REV 4/30/10 ~- -~ CITY OF CARLSBAD STORM WATER STANDARDS QUESTIONNAIRE E-34 Development Services Land Development Engineering 1635 Faraday Avenue 760-602-2750 www.carlsbadca.gov Does the redevelopment ent of impervious surface in an amount of less than 50% of the surface area If you answered "yes," the structural BMP's required for Priority Development Projects apply only to the creation or replacement of impervious surface and not the entire development. Go to step 4, check the "my project meets PDP requirements" box and complete applicant information. If you answered "no," the structural BMP's required for Priority Development Projects apply to the entire development. Go to step 4, check the " meets PDP irements" box and com nt information. D My project meets PRIORITY DEVELOPMENT PROJECT (PDP) requirements and must comply with additional stormwater criteria per the SUSMP and I understand I must prepare a Storm Water Management Plan for submittal at time of application. I understand flow control (hydromodification) requirements may apply to my project. Refer to SUSMP for details. My project does not meet PDP requirements and must only comply with STANDARD STORMWATER REQUIREMENTS per the SUSMP. As part of these requirements, I will incorporate low impact development strategies throughout my project. Applicant Information and Signature Box Address:•. . _ cii\'J i( g1 \i r ; Accessor's Parcel Number(s): Applic..rnt l)tl~,;.....-- 1' -- Applicant Signature: Date: This Box for City Use Only City Concurrence: I YES I NO L K l By: cc,. Date: ~ --~-IS Project ID: c&(5-'-IC\ *Environmentally Sensitive Areas include but are not limited to all Clean Water Act Section 303(d) impaired water bodies; areas designated as Areas of Special Biological Significance by the State Water Resources Control Board (Water Quality Control Plan for the San Diego Basin (1994) and amendments); water bodies designated with the RARE beneficial use by the State Water Resources Control Board (Water Quality Control Plan for the San Diego Basin (1994) and amendments); areas designated as preserves or their quivalent under the Multi Species Conservation Program within the Cities and County of San Diego; and any other equivalent environmentally sensitive areas which have been identified by the Copermittees. E-34 Page 3 of 3 Effective 6/27113 Erosion Control Tracking Non-Storm Water Waste Management and Materials Sediment Control BMPs Control BMPs BMPs Management BMPs Pollution Control BMPs c: c: c: "E "E 0 0 0 "0 u u Ol ~ Ql "0 Ql c: c: E c: E "0 Ul 0 c: Ol ro c: -ro ro 2 2 '6 .E Q. Ql ro Ql Ul § Ol Qj a; iii Ul iii ~ c: ·:; ~ Ol iii Ql :2 Ol "0 Ql ro c: c:-Q. Ql c: c c: ('5 ';::: C" Ql ro iii Best Management Practice c: ro ro ·a. .E c: Ul c: UJ > c: .Q s ~ :c Ul ~ m -0 Ql 0 Ql i ro ro-(BMP) Description -7 Ul :;: c: E Ql ro c: u ~ u Ul "0 Qi Ql "E Ql s ~ Ul 0 Ql(f) ·~ 1-Ul Ol Q)Ol m ·ro c -g~ c: "0 c: Ul :2 Ql iii Ul Ql "3 ~Ql Ql "E ro ro 3:£ "0:-, ~~ c: ~ g 0 :::> > ::::> Ql E 0 0 0 m Ol ~ 0 ro Ql ro 0 ~ :2 OOl 0 c: Ql (f)E ro 0+:: Ql ro Ql )J (ij i~ s -a; 0:: N Ul ~:;: Ol ·a. "E Ql c: Ql ro Ql E "" Qi -::::> .c E al :.= UJ :0 ~ -~ $ "0 .<:: c: Ql u. 0 Qj > Ql ::::> "0 :0~ ·-"0 c: "" "0 ro tl ~ 0 0 t•-Q. '6 Ql Ql 0 c: 00 .c ro 2~ ·s: ro 0 ~~ Ql ~ ro ~ 0 Ql .<:: .c ~ .=-ro ro &5£ .!!! 0 ~a: ~( 0 ~t ro 0 0 c: <t -~ 8::2 CJ UJO 1i5 Ui (/) u i.L CJ (/)> (/) (f) D. (/)0:: 0. :2 U5 (/) .. CASQA Designation -7 r-... co CJ) ~ ('") "<t L() <0 r-... co 0 N ~ ('") r-... co N ('") "<t L() <0 co c.) c.) c.) uJ uJ uJ uJ uJ uJ uJ ~ cY cY rh rh rh rh ~ ~ ~ ~ ~ ~ ~ UJ UJ UJ c.) (/) (/) (/) (/) (/) (/) (/) uJ 1-1-z z z z s s s s s s s Construction Activity UJ (/) ~ Grading/Soil Disturbance X X X X Trenching/Excavation ")( Stockpiling Drilling/Boring Concrete/Asphalt Saw culling )( Concrete flatwork X Paving ConduiUPipe Installation Stucco/Mortar Work 'X Waste Disposal y Staging/Lay Down Area ' Equipment Maintenance and Fueling Hazardous Substance Use/Storage Dewatering Site Access Across Dirt Other (list): -L_ ---------L .. -----,_ -· --· - Instructions: Begin by reviewing the list of construction activities and checking the box to the left of any activity that will occur during the proposed construction. Add any other activity descriptions in the blank activity description boxes provided for that purpose and place a check in the box immediately to the left of the added activity description. For each activity descrribed, pick one or more best management practices (BMPs) from the list located along the top of the form. Then place an X in the box at the place where the activity row intersects with the BMP column. Do this for each activity that was checked off and for each of the selected BMPs selected from the list. For Example -If the project includes site access across dirt, then check the box to the left of "Site Access Across Dirt". Then review the list for something that applies such as "Stabilized Construction Ingress/Egress" under Tracking Control. Follow along the "Site Access Across Dirt" row until you get to the "Stabilized Construction Ingress/Egress" column and place an X in the box where the two meet. As another example say the project included a stockpile that you intend to cover with a plastic sheet. Since plastic sheeting is not on the list of BMPs, then write in "Cover with Plastic" in the blank column under the heading Erosion Control BMPs. Then place an X in the box where the "Stockpiling" row intersects the new "Cover with Plastic" column. To learn more about what each BMP description means, you may wish to review the BMP Reference Handout prepared to assist applicants in the selection of appropriate Best Management Practice measures. The reference also explains the California Stormwater Quality Association (CASQA) designation and how to apply the various selected BMPs to a project. E-29 Page 2 of 3 REV 4/30/10 PLANNING DIVISION BUILDING PLAN CHECK o 1 REVIEW CHECKLIST CARLSBAD P-28 DATE: 2-9-15PROJECT NAME: PROJECT ID: Development Services Planning Division 1635 Faraday Avenue (760) 602-4610 www.carlsbadca.eov PLAN CHECK NO: CB 15-0401 SET#: 1 ADDRESS: 2035 Caleta Ct APN: 215-110-79-00 ~ This plan check review is complete and has been APPROVED by the Planning Division. By: Chris Sexton A Final Inspection by the Planning Division is required 0 Yes ~No You may also have corrections from one or more of the divisions listed below. Approval from these divisions may be required prior to the issuance of a building permit. Resubmitted plans should include corrections from all divisions. D This plan check review is NOT COMPLETE. Items missing or incorrect are listed on the attached checklist. Please resubmit amended plans as required. Plan Check Comments have been sent to: girljlc@hotmail.com For questions or clarifications on the attached checklist please contact the following reviewer as marked: PLANNING ENGINEERING FIRE PREVENTION 760-602-4610 760-602-2750 760-602-4665 [gJ Chris Sexton D Kathleen Lawrence D Greg Ryan 760-602-4624 760-602-2741 760-602-4663 Chris.Sexton@carlsbadca.gov Kathleen.Lawrence@carlsbadca.gov Grego!}'.Ryan@carlsbadca.gov D Gina Ruiz D Linda Ontiveros D Cindy Wong 760-602-4675 760-602-2773 760-602-4662 Gina.Ruiz@carlsbadca.gov Linda.Ontiveros@carlsbadca.gov Cynthia.Wong@carlsbadca.gov D D Dominic Fieri 760-602-4664 Dominic.Fieri@carlsbadca.gov Remarks: REVIEW#: 1 2 3 [8]00 [8]00 [8]00 [8]00 rgJOO [8]00 P-28 Plan Check No. CB 15-0401 Address 2035 Caleta Ct Date 2-9-15 Review# 1 Planner Chris Sexton Phone (760) 602-4624 APN: 215-110-79-00 Type of Project & Use: addition Net Project Density:1.5 DU/AC Zoning: R-1 General Plan: RLM Facilities Management Zone:§. CFD (in/out) #_Date of participation: __ Remaining net dev acres: __ (For non-residential development: Type of land use created by this permit: __ ) Legend: [8] Item Complete 0 Item Incomplete-Needs your action Environmental Review Required: YES 0 NO 0 TYPE DATE OF COMPLETION: Compliance with conditions of approval? If not, state conditions which require action. Conditions of Approval: Discretionary Action Required: YES 0 NO 0 TYPE __ APPROVAL/RESO. NO. DATE PROJECT NO. OTHER RELATED CASES: Compliance with conditions or approval? If not, state conditions which require action. Conditions of Approval: __ Coastal Zone Assessment/Compliance Project site located in Coastal Zone? YES 0 NO .[8], CA Coastal Commission Authority? YES 0 NO .[8], If California Coastal Commission Authority: Contact them at -7575 Metropolitan Drive, Suite 103, San Diego, CA 92108-4402; (619) 767-2370 Determine status (Coastal Permit Required or Exempt): Habitat Management Plan Data Entry Completed? YES 0 NO 0 If property has Habitat Type identified in Table 11 of HMP, complete HMP Permit application and assess fees in Permits Plus (A/P/Ds, Activity Maintenance, enter CB#, toolbar, Screens, HMP Fees, Enter Acres of Habitat Type impacted/taken, UPDATE!) lnclusionary Housing Fee required: YES D NO D (Effective date of lnclusionary Housing Ordinance-May 21, 1993.) Data Entry Completed? YES 0 NO D (A/P/Ds, Activity Maintenance, enter CB#, toolbar, Screens, Housing Fees, Construct Housing Y/N, Enter Fee, UPDATE!) Housing Tracking Form (form P-20) completed: YES 0 NO 0 N/A 0 Page 2 of 3 07111 Site Plan: DOD [g]DD [g]DD [g]DD [g]DD [g]00 [g]DD ODD Provide a fully dimensional site plan drawn to scale. Show: North arrow, property lines, easements, existing and proposed structures, streets, existing street improvements, right-of- way width, dimensional setbacks and existing topographical lines (including all side and rear yard slopes). Provide legal description of property and assessor's parcel number. City Council Policy 44-Neighborhood Architectural Design Guidelines 1. Applicability: YES D NO D 2. Project complies: YES D NOD Zoning: 1. Setbacks: Front: Required 20' Shown 26'6 13/16" Interior Side: Required 9.2' Shown 9.2' Street Side: Required __ Shown __ Rear: Required 18.4' Shown 18.4' Top of slope: slope is less than 10% on lot Required __ Shown __ 2. Accessory structure setbacks: N/A Front: Required __ Shown __ Interior Side: Required __ Shown __ Street Side: Required __ Shown __ Rear: Required __ Shown __ Structure separation: Required __ Shown __ 3. Lot Coverage: Required <40% Shown 23.14% 4. Height: Required <30' with min. 3:12 roof pitch Shown 20'11 5/8" 5. Parking: Spaces Required~ Shown 1 current garage configuration does not have 20'x 20' interior dimensions (breakdown by uses for commercial and industrial projects required) Residential Guest Spaces Required __ Shown __ Additional Comments OK TO ISSUE AND ENTERED APPROVAL INTO COMPUTER Chris Sexton DATE 2-9-15 P-28 Page 3 of 3 07/11 ('city of Carlsbad CERTIFICATION OF SCHOOL FEES PAID B-34 Development Services Building Department 1635 Faraday Avenue 760-602-2719 www.carlsbadca.gov This form must be completed by the City, the applicant, and the appropriate school districts and returned to the City prior to issuing a building permit. The City will not issue any building permit without a completed school fee form. Project Name GILLEY RESIDENCE Building Permit Plan Check Number: _C::::;;B:.1.:.::5::.;::0:..:.4.:..01,:.__ ___________________ _ Project Address: ~20...,3..,.5~C~A;:.=:L::.:.E~T.!;;lA~C~T~------------------ A.P.N __.,.21.!.l5L..-1..w1L>!0~-7~9~-0!:.!!<0 __________________ _ Project Applicant (Owner Name): JAMIE & CASEY GILLEY Project Description: RESIDENTIAL ADDITION Building Type Residential: NEW DWELLING UNIT(S) Square Feet of Living Area in New Dwelling/s Second Dwelling Unit: Square Feet of Living Area in SOU ------~------------~----------------------------------- Residential Additions: 1,909 Net Square Feet New Area --~----------~----------------------------------------- Commercial/Industrial: Net Square Feet New Area City Certification of _sd' . Applicant Information: ~ ~ Date 02/18/2014 SCHOOL DISTRICTS WITHIN THE CITY OF CARLSBAD ~ Carlsbad Unified School District 6225 El Camino Real 0 Vista Unified School District 0 San Marcos Unified School District Carlsbad CA 92009 (760-331-5000) 0 Encinitas Union School District 1 01 South Rancho Santa Fe Rd Encinitas, CA 92024 (760-944-4300 x1166) 1234 Arcadia Drive 2 5 5 P i c o A v e S t e . 1 0 0 Vista CA 92083 (760-726-2170) xt San Marcos, CA 92069 (760-290-2649) 2222 Contact: Nancy Dolce (By Appt. Only) 0 San Dieguito Union High School District-By Appointment Only 684 Requeza Dr. Encinitas, CA 92024 (760-753-6491 X 5514) Certification of Applicant/Owners. The person executing this declaration ("Owner") certifies under penalty of pe~ury that (1) the information provided above is correct and true to the best of the Owner's knowledge, and that the Owner will file an amended certification of payment and pay the additional fee if Owner requests an increase in the number of dwelling units or square footage after the building permit is issued or if the initial determination of units or square footage is found to be incorrect, and that (2) the Owner is the owner/developer of the above described project(s), or that the person executing this declaration is authorized to sign on behalf of the Owner . Signature: . /n~r .C{l[t1fv{ lli/ , Date: +,4,~~~~~~\~------------- ! I : ; Page 1 of2 <,J Rev. 03/09 B-34 SCHOOL DISTRICT SCHOOL FEE CERTIFICATION (To be completed by the school district(s)) *************************************************************************************************** THIS FORM INDICATES THAT THE SCHOOL DISTRICT REQUIREMENTS FOR THE PROJECT HAVE BEEN OR WILL BE SATISFIED. SCHOOL DISTRICT: The undersigned, being duly authorized by the applicable School District, certifies that the developer, builder, or owner has satisfied the obligation for school facilities. This is to certify that the applicant listed on page 1 has paid all amounts or completed other applicable school mitigation determined by the School District. The City may issue building permits for this project. SIGNATURE OF AUTHORIZED SCHOOL DISTRICT OFFICIAL TITLE NAME OF SCHOOL DISTRICT DATE PHONE NUMBER +b. S '"?o±l:o N~~ Cc , (~ '-·'''""~-\ vY\C.~) s\4\MA \U~/IY/\f:d\1\ CARLSBAD UNIFIED SCHOOL DISTRICT 6225 EL CAMINO RE"At CARLSBAD, CA 92009 ---;. I )c.-J--l.!>-_J B-34 Page 2 of 2 Rev. 03/09 City of Carlsbad 1635 Faraday Av Carlsbad, CA 92008 06-17-2015 Plan Check Revision Permit No:PCR15043 Job Address: Permit Type: Parcel No: Valuation: Reference #: PC#: Project Title: Applicant: JAMIE GILLEY 619-890-0695 Building Inspection Request Line (760) 602-2725 2035 CALETA CT CBAD PCR Lot#: 0 2151107900 $0.00 Construction Type: 58 Status: Applied: Entered By: Plan Approved: GILLEY: REVISIONS TO CB150401 Owner: GILLEY 2035 CALETA CT CARLSBAD CA 92009 Issued: Inspect Area: Plan Check Revision Fee Fire Expedited Plan Review Additional Fees $187.50 $0.00 $0.00 Total Fees: $187.50 Total Payments To Date: $187.50 Balance Due: FINAL APPROVAL Inspector: Date: Clearance: ISSUED 06/09/2015 JMA 06/17/2015 06/17/2015 $0.00 NOTICE: Please take NOTICE that approval of your project includes the "Imposition" of fees, dedications, reservations, or other exactions hereafter collectively referred to as "fees/exactions." You have 90 days from the date this permit was issued to protest imposition of these fees/exactions. If you protest them, you must follow the protest procedures set forth in Government Code Section 66020(a), and file the protest and any other required information with the City Manager for processing in accordance with Carlsbad Municipal Code Section 3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack, review, set aside, void, or annul their imposition. You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection fees and capacity changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this project. NOR DOES IT APPLY to any fees/exactions of which vou have previously been aiven a NOTICE similar to this or as to which the statute of limitations has previously otherwise ex_l2ired. (City of Carlsbad PLAN CHECK REVISION APPLICATION B-15 Development Services Building Division 1635 Faraday Avenue 760-602-2719 www.carlsbadca.gov Plan Checl< Revision No. PC r<.. (~-Lf? Original Plan Check No. Cf::; I~ 0 l/:0 ( Project Address :r.:.;-x?'2 5 Cc1 \e 1z1 c~ Date _,f.J~n~-C1__J1l--.C-r_S.,.___ ___ _ Contact~ I c-(?i)\cu Ph ((7\ur'CP\o-c::lJ('\S Fax ________ _ Email ,ji<ljlc@bo:\ ~"" 1\ Cb~ Contact Address 2o?S Ca lew C-\ , City Givl.sb0d Zip g2o Cf1 GeneraiScopeof~orl<~----------------------------------------------------~ Original plans prepared by an architect or engineer, revisions must be signed & stamped by that person. 1 . Elements revised: t;lJ. Plans 0 Calculations 0 Soils 0 Energy 0 Other~~~~~~----~~~~ 2. Describe revisions in detail 5. Does this revision, in any way, alter the exterior of the project? 6. Does this revision add ANY new floor area(s)? D Yes 7. Does this revision affect any fire related issues? D Yes 3. List page(s) where each revision is shown ~Yes ~ No [] No 4. List revised sheets that replace existin sheets D No 8. Is this a complete ~et? ~ ~ Yes 'E7ll No £$'Signature (--bn,lvl ~~- 1635 Faraday Avenu~rlsbad, CA 92008 Ph: 760-602-2719 Fax: 760-602-8558 Email: building@carlsbadca.gov www.carlsbadca.gov EsGil Corporation In fPartnersliip witli (]overnment for (]3ui{aing Safety DATE: 6/12/15 JURISDICTION: CARLSBAD PLAN CHECK NO.: 15-0401 REV PROJECT ADDRESS: 2035 CALETA COURT PROJECT NAME: SFR ADDITION FOR GILLEY SET: I REVISION CJ APPLICANT CJ JURIS. CJ PLAN REVIEWER CJ FILE [g) The plans transmitted herewith have been corrected where necessary and substantially comply with the jurisdiction's building codes. 0 The plans transmitted herewith will substantially comply with the jurisdiction's codes when minor deficiencies identified below are resolved and checked by building department staff. D The plans transmitted herewith have significant deficiencies identified on the enclosed check list and should be corrected and resubmitted for a complete recheck. 0 The check list transmitted herewith is for your information. The plans are being held at Esgil Corporation until corrected plans are submitted for recheck. 0 The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant contact person. D The applicant's copy of the check list has been sent to: ~ EsGil Corporation staff did not advise the applicant that the plan check has been completed. D EsGil Corporation staff did advise the applicant that the plan check has been completed. Person contacted: Telephone#: Date contacted: (by: ) Email: Mail Telephone Fax In Person D REMARKS: By: Kurt Culver (for AS) EsGil Corporation 0 GA 0 EJ 0 MB 0 PC 6/11/15 Enclosures: Previously-approved plans 9320 Chesapeake Drive, Suite 208 + San Diego, California 92123 + (858) 560-1468 + Fax (858) 560-1576 CARLSBAD 15-0401 REV .... 6/12/15 [DO NOT PAY-THIS IS NOT AN INVOICE) VALUATION AND PLAN CHECK FEE JURISDICTION: CARLSBAD PLAN CHECK NO.: 15-0401 REV PREPARED BY: Kurt Culver (for AS) DATE: 6/12/15 BUILDING ADDRESS: 2035 CALETA COURT BUILDING OCCUPANCY: R31U; V-B/SPR. BUILDING AREA Valuation Reg. VALUE {$) PORTION (Sq. Ft.) Multiplier Mod. Air Conditioning Fire Sprinklers TOTAL VALUE Jurisdiction Code cb By Ordinance Bldg. Permit Fee by Ordinance C:!J Plan Check Fee by Ordinance $187.501 Type of Review: 0 Complete Review o Structural Only 0 Repetitive Fee : · , •I Repeats 0 Other 0 Hourly EsGil Fee ,__ ___ 1_.5--tl Hrs. @ * $100.00_ $150.001 • Based on hourly rate Comments: Sheet 1 of 1 macvalue.doc + PLANNING DIVISION BUILDING PLAN CHECK cITy 0 F APPROVAL CARLSBAD P-29 DATE: 6-9-15 PROJECT NAME: PROJECT ID: Development Services Planning Division 1635 Faraday Avenue (760) 602-4610 www.carlsbadca.eov PLAN CHECK NO: PCR 15-43 SET#: 1 ADDRESS: 2035 Caleta Ct APN: ~ This plan check review is complete and has been APPROVED by the Planning Division. By: Chris Sexton A Final Inspection by the Planning Division is required 0 Yes [8:1 No You may a/so have corrections from one or more of the divisions listed below. Approval from these divisions may be required prior to the issuance of a building permit. Resubmitted plans should include corrections from all divisions. 0 This plan check review is NOT COMPLETE. Items missing or incorrect are listed on the attached checklist. Please resubmit amended plans as required. Plan Check APPROVAL has been sent to: girljlc@hotmail.com For questions or clarifications on the attached checklist please contact the following reviewer as marked: PLANNING 760-602-4610 L8J Chris Sexton 760-602-4624 Chris.Sexton@carlsbadca.gov D Gina Ruiz 760-602-4675 Gina.Ruiz@carlsbadca.gov D Remarks: ENGINEERING 760-602-2750 FIRE PREVENTION 760-602-4665