HomeMy WebLinkAbout2050 JANIS WAY; ; CB941606; PermitCity of Carlsbad
1635 Faraday Av Carlsbad, CA 92008
01-07-2016 Building Permit Permit No:CB941606
Building Inspection Request Line (760) 602-2725
Job Address: 2050 dANIS WY CBAD
Permit Type: RAD Sub Type:
Parcel No: 2051521300 Lot #: Status: FINAL
Valuation: $90,428.00 Const Type: VN Applied: 12/07/1994
OccGroup: R3 Reference #: Entered By: MDP
Appr/Issued: 01/06/2016
Project Title: 962 SF ADDITION Inspect Area: PD
Applicant:
SOMERS, RICK
2911 STATE ST
CARLSBAD, CA. 92008
619 434-5428
Owner:
LEDESMA ALFONSO&LINDA L
Total Fees: $1,911.00 Payments To Date: $1,911.00 Balance Due:
$0.00
Description , Fee
* ELECTRICAL TOTAL 20.00
* MECHANICAL TOTAL 35.00
* PLUMBING TOTAL 119.00
Building Permit 599.00
Plan Check 389.00
PLDA B 740.00
Strong Motion Fee 9.00
FINAL APPROVAL
InsDector 6t Date: / - 7 Clearance:
t'Jiic Resse take F4ZJflCE that appiud of your prqedir±Jes the Irnxtiorf of fees, dedications, reservations, or other exactions hereMff collectively
refened to "fee adicts' You have 90 days from the the this permt ves issued to protest irrpcbcn of these fe&exadims. .1f you protest therr you rrtst
follow the protest procedures set forth in Gennt Cede Sedion 6020(a), and file the protest and any other required infcmallon wth the City Kftlw for
processing in axcdaite th Carlsbad lvthdpel Code Section a32.030. Failure to timely follow that procedure bar any ss&uent legal action to attedç
re, set aside, void, or annul their irrtion.
You are hereby REfl-ER NZYflA8) that your tight to protest the specified f/eacticnsIXES JLAPftYto.ete and seer connection fees and capaiiy
dwges, r plarrir, za-rr gieding a- other mlar app ionon prccessing a- ser*e fees in antia, wili this preci NCR IXES IT.APftY to any
feecre of vhch you have prWously been qKen a NOTICE niIarto this, or as to which the statute of lirritaliae has ixe'iam otherwise eqired.
Fee's C5i?lected & Credits ' /,
.00
389.00
1,522.00
Ext fee Data ----------------
599.00
389.00
9.00
997.00
20.00 Y
84.00
15.00
119.00
10.00 Y
10.00 Y
20 :oo
15.00 Y
6.50
13.50
35.00
740.00 L
/
Tot .al\TCrë'd-lts 1
olts: \ Bal an, ce'Due:
" \ Units \Fej
efUni —p-_q \ I
!/7.001)
,-
.22
BUILDING PERMIT Permit No: CB941606
Project No: A9402372
Development No: it
07/05/95 13:44
Page 1 o 1
Job Address: 2050 JANIS WY
Permit Type: RESIDENTAL ADD/ALT
Parcel No.: 205-152-13-00
Valuation: 90,428
Construction Type: VN
Occupancy Group: R3
Description: 962 SF ADDITION
Appl/Ownr : SOMERS, RICK
2911 STATE ST
CARLSBAD, CA. 9200
Suite:
Lot#:
2596 07/05/95 0001 01 02
C-PRIIT 1522.00
Reference#: Status: ISSUED
Applied: 12/07/94
Apr/Issue: 07/05/95
Entered By: MDP
619 4345428
*** Fees Required . ----------------------------
Fees:
Adjustments: /.00
Total Fees: 1I,91\00
,,7 '
Fee description
Building Permit .
Plan Check
Strong Motion Fee
* BUILDING TOTAL
. A. Enter "Y" for Plumbing Iss'eFee
Each Plumbing Fixture or Trp
Each Building Sewer\
* PLUMBING TOTAL \ Enter "Y" for Electric Is'sue'Fee %J... Enter Y for Remodel '
* ELECTRICAL TOTAL /7i Enter 'Y' for Mechanical Issue Ree
Each Install Fireplace
Each Install/Beloc Vent
* MECHANICAL TOTAL
PLDAB
0 ~
V L'. MF(/IJUL,
vj4 -
CITY OF CARLSBAD
2075 Las Palmas Dr., Carlsbad, CA 92009 (619) 438-1161
AX
P tATION
City of Carlsbad Building Department
2075 Las Patinas Dr., Carlsbad, CA 92009 (619) 438-1161
From List I (see back) give code of Permit-Type:
---------------------------------------------------------
For Residential Projects Only: From List 2 (see back) give
Code of Structure-Type:
PLAN CHECK NO. (A-
EST. VAL Q( C('tC
PLAN CK DEPOSIT set 0
VALID. BY
DATE
9854 12/07/94 0001 01 02
C-PRMT 389.00
Net Lass/Gain of Dwelling Units
PROJECT INFORMATION FOR OFFICE USE ONLY
Address -2 ,c' r-, WAll Building or Suite No.
Nearest Cross Street 7,r4
c 3k7 2- aA4f. 6644 9 1 CHECK BELOW IF SUBMITrED:
)62 Energy Calcs 2 Structural Calcs 02 Soils Report 0 1 Addressed Envelope
ASSESSOR'S PARCEL EXISTING USE PROPOSED USE
DESCRIPTION OF WORK cisV 0,0?, (4&) 1 3 SQ. FT. # OF STORIES # OF BEDROOMS # OF BATHROOMS
(kIN JAG! PhRON (it different trom applicant)
NAME (lastname firsO5t,45 J3. ADDRESS 2.1 IJ -r -T
CITY 'kI) STATE C ZIP CODE DAY TELEPHONE
NAME (last name first) 1atCZ SAS ADDRESS —c
CITY -
:~"skP STATE 45Zk ZIP CODE Z0t1t6 DAY TELEPHONE
PROPERTY UWNEK
NAME (last name first) L1i1A AL.1 '4 L'* ADDRESS jVi ..MU,S 41
CITY STATE j\— ZIP CODE DAY TELEPHONE ap
(DNTRACIOft
NAME (last name first) ADDRESS
CITY STATE ZIP CODE DAY TELEPHONE
STATE UC. # LICENSE CLASS CITY BUSINESS tiC. #
DESIGNER NAME (last name tirst) fZK.. ADDRESS jg F!41;
CITY STATE eq— ZIP CODE DAY TELEPHONE 4341 7-55ATE tiC. #
WORKERS' COMPENSATION
Workers' Compensation Declaration: I hereby attirm that I have a certiticate ot consent to sell-insure issued by the Director ot Industrial
Relations, or a certificate of Workers' Compensation Insurance by an admitted insurer, or an exact copy or duplicate thereof certified
by the Director of the insurer thereof filed with the Building Inspection Department (Section 3800, Lab. C).
INSURANCE COMPANY POLiCY NO. EXPIRATION DATE
Certiticate ot Exemption: I certify that in the performance of the work for which this permit is issued, I shall not employ any person in any manner
so as to become subject to the Workers' Compensation Laws of California.
SIGNATURE DATE
S. OWNER-BUILDER DECLARATION
Owner-Builder Declaration: I hereby attirm that I am exempt from the Contractors License Law for the tollowing reason:
0 I, as owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not intended or
offered for sale (Sec. 7044, Business and Professions Code: The Contractor's License Law does not apply to an owner of property who builds
or improves thereon, and who does such work himself or through his own employees, provided that such improvements are not intended
or offered for sale. If, however, the building or improvement is sold within one year of completion, the owner-builder will have the burden
of proving that he did not build or improve for the purpose of sale.).
0 1, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions
Code: The Contractor's License Law does not apply to an owner of property who builds or improves thereon, and contracts for such projects
with contractor(s) licensed pursuant to the Contractor's License Law).
0 I am exempt under Section Business and Professions Code for this reason:
(Sec. 7031.5 Business and Professions Code: Any City or County which requires a permit to construct, alter, improve, demolish, or repair
any structure, prior to its issuance, also requires the applicant for such permit to file a signed statement that he is licensed pursuant to the
provisions of the Contractor's License Law (Chapter 9, commencing with Section 7000 of Division 3 of the Business and Professions Code)
or that he is exempt therefrom, and the basis for the alleged exemption. Any violation of Section 7031.5 by any applicant for a permit
subjects the applicant to a civil penalty of not more than five hundred dollars [$5001).
SIGNATURE DATE
COMPLETE THIS SECTION FOR NON-RESIDENTIAL BUILDING PERMITS ONLY:
Is the applicant or future building occupant required to submit a business plan, acutely hazardous materials registration form or risk management and
prevention program under Sections 25505, 25533 or 25534 of the Presley-Tanner Hazardous Substance Account Act?
DYES ONO
Is the applicant or future building occupant required to obtain a permit from the air pollution control district or air quality management district?
DYES 0 N
Is the facility to be constructed within 1,000 feet of the outer boundary of a school site?
DYES 0 N
IF ANY OF THE ANSWERS ARE YES, A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED AFTER JULY 1, 1989 UNLESS THE APPLICANT
HAS MET OR IS MEETING THE REQUIREMENTS OF THE OFFICE OF EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT.
WNSThU(;I1UN LENDING AGENCY
I hereby attirm that there is a construction lending agency tor the performance ot the work for which this permit is issued (Sec 30970) Civil Code).
LENDER'S NAME LENDER'S ADDRESS
AI'PuCANr CFJ(.ICATION
I certify that I have read the application and state that the above inbormation is correct. I agree to comply with all City ordinances and State laws
relating to building construction. I hereby authorize representatives of the City of Carlsbad to enter upon the above mentioned property for inspection
purposes. I ALSO AGREE TO SAVE INDEMNIFY AND KEEP HARMLESS THE CITY OF CARLSBAD AGAINST ALL UABIUTLES, JUDGMENTS, COSTS
AND EXPENSES WHICH MAY IN ANY WAY ACERUE AGAINST SAID CITY IN CONSEQUENCE OF THE GRANTING OF THIS PERMIT.
0511k An OSHA permit is required for excavations over 5,0" deep and demgjjtion or construction of structures over 3 stories in height.
Expiration. Every permit issued :,
Pr,
y the l
building or work authorized by sch
such permit is suspended or abano at
APPUCANT'S SIGNATURE i
Official under th pro ion of this shall expire by limitation and become null and void if the
lot commenced hi ft,V from date of such pemit or if the buildingpr work authorized by
time-after the iê6 nced r a period of 180
>"56'I '/ DATE: f7 ys ($on 303(d) Uniform Building Code). I C7r 9 .-'U '- — fl
CITY OF CARLSBAD
1200 CARLSBAD VILLAGE DRIVE' CARLSBAD, CALIFORNIA 92008
(½# 434-2867
REC'D FRO DATE
ACCOUNT NO. NO. DESCRIPTION AMOUNT
9607/05/95 )0010102
I Vt)
RECEIPT NO. 16420 NOT VALID UNLESS VALIDATED BY TOTAL
Printed on recycled paper. CASH REGISTER
Inspection List
Permit#: CB941606 Type: RAID 962 SF ADDITION
Date Inspection Item Inspector Act Comments
01/07/2016 89 Final Combo - RI
01/0712016 89 Final Combo PD AP
02/12/1997 89 Final Combo PD CO
02/09/1996 89 Final Combo PD CO
02/02/1996 23 Gas/Test/Repairs PY AP
11/14/1995 17 Interior Lath/Drywall PY AP GRG
11/09/1995 17 Interior Lath/Drywall PD NR
11/08/1995 17 Interior Lath/Drywall PD PA NOT GARAGE
11/02/1995 16 Insulation DC AP
10/26/1995 84 Rough Combo PD AP
10/10/1995 14 Frame/Steel/Bolting/Weldin PD CO
10/03/1995 13 Shear Panels/HD's PD AP
10/03/1995 15 Roof/Reroof PD AP
08/16/1995 11 Ftg/Foundation/Piers PD AP
08/15/1995 21 Underground/Under Floor PD AP
12
Thursday January 07, 2016 Page 1 of
01/11/97 INSPECTION HISTORY LISTING
FOR PERNIT# CB941606
.DATE INSPECTION TYPE INSP ACT COMMENTS
02/09/96 Final Combo RI RI MW/AL/434-5602
02/09/96 Final Combo PD CO
02/02/96 Gas/Test/Repairs RI RI MW/AL/434-5602
02/02/96 Gas/Test/Repairs PY AP
11/14/95 Interior Lath/Drywall RI RI MW/AL
11/14/95 Interior Lath/Drywall PY AP GRG
11/09/95 Interior Lath/Drywall RI RI BJN/AL/
11/09/95 Interior Lath/Drywall PD NR
11/08/95 Interior Lath/Drywall RI RI BJN/AL/
11/08/95 Interior Lath/Drywall PD PA NOT GARAGE
11/02/95 Insulation RI RI MW/434-5602
11/02/95 Insulation DC AP
10/26/95 Frame/Steel/Bolting/Wel RI RI MW/AL/434-5602/PM PLEASE
10/26/95 Rough Electric RI RI MW/AL/434-5602/PM PLEASE
10/26/95 Rough Combo PD AP
10/10/95 Frame/Steel/Bolting/Wel RI RI RS/LEDESMA/434-5602
10/10/95 Frame/Steel/Bolting/Wel PD CO
10/03/95 Shear Panels/HD's RI RI MW/AL
10/03/95 Shear Panels/HD's PD AP
10/03/95 Roof/Reroof RI RI MW/AL
10/03/95 Roof/Reroof PD AP
08/16/95 Ftg/Foundation/Piers RI RI MW/AL/PM PLS
08/16/95 Ftg/Foundation/Piers PD AP
08/15/95 Underground/Under Floor RI RI MW/AL
08/15/95 Underground/Under Floor PD AP
HIT <RETURN> TO CONTINUE...
ESGIL CORPORATION
9320 CHESAPEAKE DR., SUITE 208
SAN DIEGO, CA 92123
(619) 560-1468
DATE: March 16, 1995
JURISDICTION: Carlsbad
PLAN CHECK NO.: 94-1606
PROJECT ADDRESS: 2050 Janis Way
SET: II
U APPLICANT
JDICT J
U PLAN REVIEWER
U FILE
PROJECT NAME: SFD Addition & Remodel for Al & Linda Ledesma
J The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
The applicant's copy of the check list has been sent to:
Esgil Corporation staff did not advise the applicant that the plan check has been completed.
Esgil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted:
Date contacted: (by: ) Telephone #:
REMARKS: the City to
place their soil stamp on the plans before issuance of the permit.
By: Abe Doliente Enclosures:
Esgil Corporation
GA fl CM n PC 3/8/95 trnsmtl.dot
ESGIL CORPORATION
9320 CHESAPEAKE DR., SUITE 208
SAN DIEGO, CA 92123
(619) 560-1468
DATE: 12/9/94
JURISDICTION: Carlsbad
PLAN CHECK NO.: 94-1606
PROJECT ADDRESS: 2050 Janis Way
SET:I
O APPLICANT
O PLAN REVIEWER
0 FILE
PROJECT NAME: SFD Addition & Remodel for Al & Linda Ledesma
The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
The applicant's copy of the check list has been sent to:
Rick Somers
2911 State Street, Suite C, Carlsbad, CA 92008
U Esgil Corporation staff did not advise the applicant that the plan check has been completed.
Esgil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted:
Date contacted: (by: ) Telephone #:
• REMARKS: Please see revised valuation.
By: Abe Doliente Enclosures:
Esgil Corporation
GA CM n PC 12/8/94 trnsmtl.dot
Carlsbad 94-1606
12/9/94
PLAN REVIEW CORRECTION LIST
SINGLE FAMILY DWELLINGS AND DUPLEXES
JURISDICTION: Carlsbad PLAN CHECK NO.: 94-1606
PROJECT ADDRESS: 2050 Janis Way
FLOOR AREA: Addition - 962 SF
Remodel - 1450 SF
REMARKS:
DATE PLANS RECEIVED BY
JURISDICTION:
DATE INITIAL PLAN REVIEW
COMPLETED: 12/9/94
STORIES: 1
HEIGHT:
DATE PLANS RECEIVED BY
ESGIL CORPORATION: 12/8/94
PLAN REVIEWER: Abe Doliente
FOREWORD (PLEASE READ):
This plan review is limited to the technical requirements contained in the Uniform Building Code,
Uniform Plumbing Code, Uniform Mechanical Code, National Electrical Code and state laws
regulating energy conservation, noise attenuation and access for the disabled. This plan review
is based on regulations enforced by the Building Department. You may have other corrections
based on laws and ordinance by the Planning Department, Engineering Department, Fire
Department or other departments. Clearance from those departments may be required prior to
the issuance of a building permit.
Present California law mandates that residential construction comply with Title 24 and the
following model codes: 1991 UBC (effective 8/14/92), 1991 UPC (effective 8/14/92), 1991
UMC (effective 8/14/92) and 1990 NEC (effective 7/1/91).
The above regulations apply to residential construction, regardless of the code editions adopted
by ordinance.
The following items listed need clarification, modification or change. All items must be satisfied
before the plans will be in conformance with the cited codes and regulations. Per Sec. 303 (c),
1991 Uniform Building Code, the approval of the plans does not permit the violation of any
state, county or city law.
To speed up the recheck process, please note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet number, specification section. etc.
Be sure to enclose the marked up list when you submit the revised plans.
LIST NO. 1, GENERAL SINGLE FAMILY DWELLINGS AND DUPLEXES WITHOUT SUPPLEMENTS (1991 UBC) r3forw.dot
Carlsbad 94-1606
12/9/94
Please make all corrections on the original tracings and submit two new sets of
prints to:
Esgil Corporation, 9320 Chesapeake Drive, Suite #208, San Diego, California
92123, (619) 560-1468.
Please make, all corrections on the original tracings and submit two new sets of
prints, to:
The jurisdiction's building department.
Plans, specifications and calculations shall be signed and sealed by the
California state licensed engineer or architect responsible for their preparation,
for plans deviating from conventional wood frame construction. Specify
expiration date of license. (California Business and Professions Code).
If required, show size, embedment and location of hold down anchors on
foundation plan. Section 302 (d).
If hold downs are required, note on plan that hold down anchors must be tied in
place prior to foundation inspection. Section 305 (e) I.
Provide calculations for main vertical and horizontal framing members and
footings. Section 302 (b).
Provide calculations for lateral loads, shear panels, shear transfer and related.
Section 302 (b).
Show the size, location and type of all heating and cooling appliances or
systems.
Note on the plans that the FAU closet or alcove must be 12 inches wider than
the furnace or furnaces being installed. UMC Section 704.
Show minimum 30" deep unobstructed working space in front of furnace. Section
505, UMC.
1,1. Show access to the attic containing equipment to be minimum 30 inches by 30
inches. The opening may be 22 inches by 30 inches if the equipment can be
removed through such opening. Section 708, UMC.
Note that passageway to the attic furnace shall be unobstructed and have
continuous solid flooring not less than 24 inches wide, not more than 20 feet in
length through the attic. Section 708, UMC.
Show permanent electrical outlet and lighting fixture controlled by a switch for
furnace located in attic or underfloor space. Section 708 & 709, UMC.
Carlsbad 94-1606
12/9/94
Show I.C.B.O. approval number for prefab fireplace. Show height of chimney
above roof per I.C.B.O. approval or Table 37-13. ICBO approval number 3195 is
no longer valid.
Note on the plans that approved spark arrestors shall be installed on all
chimneys. UBC, Section 3703(h).
Show on the plan the amperage of the electrical service, the location of the
service panel and the location of any sub-panels. If service is over 200 amps,
submit single line diagram, panel schedule and load calculations.
Note on the plans that receptacle outlet locations will comply with 1990 NEC Art.
210-52(a).
Provide adequate barrier to protect water heater from vehicle damage. An 18"
platform for the water heater does not satisfy this requirement. UPC, Section
1310.
Show T and P valve on water heater and show route of discharge line to exterior.
UPC, Section 1007 (e).
Show that water heater is adequately braced to resist seismic forces. UPC,
Section 1310.
New water closets and associated. flushometer valves, if any, shall use no more
than 1.6 gallons per flush and shall meet performance standards established by
the American National Standards Institute Standard Al 12.19.2, and urinals and
associated flushometer valves, if any, shall use no more than one gallon per
flush and shall meet performance standards established by the American
National Standards Institute Standard A112.19.2. H & S Code, Section
17921.3(b).
The regulations require a properly completed and properly signed Form CF-lR to
be either imprinted on the plans, taped to the plans or "sticky backed" on the
plans, to allow the building inspector to readily compare the actual construction
with the requirements of the approved energy design.
Provide fluorescent general lighting (40 lumens per watt minimum) in kitchen(s)
and bathrooms.
. CARLSBAD S.F.D. & DUPLEX SUPPLEMENT
For 'gas piping under slabs that serve kitchen island cooktops, see the attached
Policy 91-46 for special sleeve and clean-out requirements.
rz
Carlsbad 94-1606
12/9/94
MISCELLANEOUS
Complete floor plan notes.
Clearly cross reference the truss drawings with the roof framing plan. The truss
roof framing reference must agree also with the roof framing plan.
City to place their soils stamp on the plans before issuance of the permit.
To speed up the review process, note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet, note or detail number,
calculation page, etc.
Please indicate here if any changes have been made to the plans that are not a
result of corrections frbm this list. If there are other changes, please briefly
describe them and where they are located in the plans.
Have changes been made to the plans not resulting from this correction list? Please
indicate:
El Yes El No
30. The jurisdiction has contracted with Esgil Corporation located at 9320
Chesapeake Drive, Suite 208, San Diego, California 92123; telephone number of
619/560-1468, to perform the plan review for your project. If you have any
questions regarding these plan review items, please contact Abe Doliente at
Esgil Corporation. Thank you.
Carlsbad 94-1606
12/9/94
VALUATION AND PLAN CHECK FEE
JURISDICTION: Carlsbad PLAN CHECK NO.: 94-1606
PREPARED BY: Abe Doliente DATE: 12/9/94
BUILDING ADDRESS: 2050 Janis Way BUILDING OCCUPANCY: R.3
TYPE OF CONSTRUCTION: V-N
BUILDING PORTION BUILDING AREA
(sq. ft.)
VALUATION
MULTIPLIER
VALUE
($)
Addition 962 SF 94.00 90,428
Remodel 1450 SF 26.00 37,960
Air Conditioning
Fire Sprinklers
TOTAL VALUE 128,388
Building Permit Fee:
Plan Check Fee:
Comments:
$ 741.00
$ 481.65
Sheet 1 of I
valuefee.dot
City of Ca'rlsbad-
BUILDING PLANCHECK CHECKLIST
DATE:____ PLANCHECK NO. CB 9
BUILDIN'GAD6RESS ca2.SZ' JJ;s a,W
PROJECT DESCRIPTION: ____
ASSESSORs PARCEL NUMBER: c? s-/ -," j/ 7 EST. VALUE T 4'P
ENGINEERING
APPROVAL
The item you have submitted for review has been
approved, The approval Is based on plans, information
and/or specifications provided In your submittal; therefore
any changes to these items after this date, Including field.
modifications, must be reviewed by this office to insure
continued conformance with applicable codes. Please
review careft.illy all comments attached, as failure to
comply with Instructions In this report can result in
suspension of permit to build.
0 A Right-of-Way permit is required prior to construction
of the following improvements:
DEPARTMENT
DENIAL
Please see the attached report of deficiencies marked
with Make necessary corrections to plans or
speifications for compliance with applicable codes and standards. Submit corrected plans and/or specifications '
to this office for review. /1
1z A/eels t?
By: _ t4L Date:______
By: Date:________ -
By: Date:_________
ATTACHMENTS . ENGINEERING DEPT. CONTACT PERSON
0 Dedication Application. . . .
0 Dedication Checklist
0 Improvement Application
0 Improvement Checklist: NAME: .
El Future Improvement Agreement. . . City of Carlsbad
0 Grading Permit Application ADDRESS: 2075 Las Palmas Dr., Carlsbad, CA 92009
0 Grading Submittal Checklist PHONE:(619) 438..1161, Ext.
O Right of Way Permit Application .
El Right of Way Permit Submittal Checklist
and Information Sheet . El Sewer Fee Information Sheet . A-4
P:\D0CS\CHKLSt\6P000I.FRM - REV 05/11/94
2075 Las Palmas Dr. • Carlsbad, CA 92009-1576 • (619) 438-1161. FAX (619) 438-0894
BUILDING PLANCHECK CHECKLIST
ols46 3rdv'
0•.
SITE PLAN
1. Provide a fully dimensioned site plan drawn to scale. Show:
North Arrow D. Property Lines Easements
Existing & Proposed Structures E. Easements
Existing Street Improvements F. Right-of-Way Width & Adjacent Streets
O 2. Show on site plan:
Drainage Patterns C.' Existing Topography
Existing & Proposed Slopes
o 3. include note: "Surface water to be directed away from the building foundation at a 2%
gradient for no less than 5' or 2/3 the distance to the property line (whichever is less).*
[Per 1985 UBC 2907(d)5].
On graded sites, the top of any exterior foundation shall extend above the elevation -
of the street gutter at point of discharge or the inlet of an approved drainage device -
a minimum of 12 inches plus two percenr (per 1990 UBC 2907(d)5.).
0 4. Include on title sheet•
Site address
Assessor's Parcel Number
Legal Description
For commërcial/industnal buildings and tenant improvement projects, include: Total
building square footage with the square footage for each different use, existing sewer
permits showing square footage of different uses (manufacturing, warehouse, office,
etc.) previously approved.
EXISTING PERMIT NUMBER DESCRIPTION
P:\D0CS\CHKLST\8P0001.FRU " Page 1 of 4 REV oa/ii/a
I'
BUILDING PL NCHECK CHECKLIST
DISCRETIONARY APPROVAL COMPLIANCE
..i,/ 2fldv1 3rd'
V7 0 0 5. Project does not comply with the following Engineering Conditions of approval for
Project No.
Conditions were complied with by:— Date:
DEDICATION REQUIREMENTS
6. Dedication for all street Rights-of-Way adjacent to the building site and any storm
drain or Utility easements on the building site is required for all new buildings and for
remodels with a value at or exceeding $_Jo ID,, pursuant to Code Section
18.40.030.
Dedication required as follows:
Attached please find an application form and submittal checklist forthe dedication
process. Provide the completed 'application form and the requirements on the
checklist at the time of resubmittal.
Dedication completed by Date:__________
IMPROVEMENT REQUIREMENTS
7a. All needed public improvements upon and adjacent to, the building site must be
constructed at time of building construction whenever the value of the construction
exceeds $ £Z', ,rv1 ' -pursuant to Code Section 18.40.040.
Public improvements required as follows: 5iE&'Jà/i'S ~77Z/,97
Please have a registered Civil Engineer prepare appropriate improvement plans and
submit them together with the requirements on the attached checklist for a separate
plancheck process through the Engineering Department. Improvement plans must be
approved, appropriate securities posted and fees paid prior to issuance of permit.
Attached please find an application form and submittal checklist for the public
improvements requirements. Provide the* completed application form and the
requirements on the checklist at the time of resubmittal.
Improvement Plans signed by:
, Date:
P:\DOCS\CHKLSTBP0001.FRM ' Page 2 of 4 ' REV 05/11/94
BUILDING PLANCHECK CHECKLIST
X2nd,/ 3rd,/ . 0 0 7b. Construction of the public improvements may be deferred pursuant to code Section
18.40. Please submit a recent property e report or current grant deed on the
A property and processing fee of $_ - so we may prepare the.
/ necessary Future Improvement Agreement. This agreement must be signed, notarized
4 ' . . and approved by the City prior to issuance of a Building Permit.
Future public improvements required as follows:5,D5t'J-4fk2 seeríJ 117---
•
/ . Improvement Plans signed by: Date:___________
76. . Enclosed please find your Future Improvement Agreement. Please return signed and
notarized Agreement to the Engineering Department.
. Future Improvement Agreement completed by: _•
0
Date:
0 0 0 7d. No Public mprovements required. SPECIAL _NOTE:. Damaged ordefective
improvementsfoundadiacenttobuildingsitemustberepairedtothesatisfactionof - the City_ Inspector priortooccupancy.
GRADINGPERMITREQUIREMENTS
The conditions that invoke the need for a grading permit are found in Section 11.06.030
of the Municipal Code.
0. 0 0 8a. Inadequate information available on Site Plan to' make a determination on grading
requirements. Include accurate grading quantities (cut, fill import, export).
O 0 0 8b. Grading Permit required. A separate grading plan prepared by a registered Civil
Engineer must be Submitted together with the completed application form attached.
NOTE: The Grading Permit must be issued and rough grading approval obtained prior
toissuanceofaBuildingPermit.
Grading Inspector sign off by: Date: eO 0 8c. No Grading Permit required.
P:\DOCS\CHKLSI\BP0001.FRM • Page 3 d 4 • 0 • REV osiiiies
BUILDING PLANCHECK CHECKLIST
MISCELLANEOUS PERMITS
1 st/ 2nd' 3rd' kil/ 0 9. A RIGHT-OF-WAY PERMIT is required to do work in City Right-of-Way and/or
private work adjacent to the public Right-of-Way.-Types of work include, but are not
limited to: street improvements, trees, driveways, tieing into public storm drain, sewer
and water utilities.
Right-of-Way permit required for S
S
A separate Right-of-Way permit issued by the Engineering Department is required for
the following:
J/D 0 10. A SEWER PERMIT is required concurrent with the building permit issuance. The fee
S is noted in the.fees section on the following page.
O 0 ii. INDUSTRIAL WASTE PERMIT is required. Applicant mutt complete Industrial-
Waste Permit Application Form and submit for City approval prior to issuance of a
Permit. S S
Industrial waste permit accepted by: Date:
4
/
P:\DOcS\CHKLST\BP0001.FRU S Page 4 of 4 REV 05/11/14
e
ENGINEERING DEPARTMENT ENGINEERING REVIEW SECTION
FEE CALCULATION WORKSHEET
Cl Esumare bMed on =w*mW Womisuon from appOcanL
Cacutation bassi on buIdIng pancheck plan submittaL
Address: _co s3 J', T tJ4 permit NO. _(8 9
Prepared by:/4> Dat.f Chocked by: Oar.:______________
EDU CALCULATIONS: Liar types and square foctages for ON uses.
Types of Us.:£ es. 6, Sq. FL: EDU's: _6
Tcasi EDU's: -
AOT CALCULATIONS: List typm and square footageii for all us's.
Types of Use: /f i ' ,J Sq. FL: ADTs__________________
Total ADVa__________________
FEES REWIRED:
PUBLIC FACILITIES FEE REQUIRED C YES 0 NO (Ss Building Oepaztmer* for amount)
WITHIN CFO: 0 YES (no bridge & thoroughfare fee, 0 NO
reduced Trallc Impact Fe.)
1.PARK4N-UEU FEE PARK AREA:
FEEAJNrr: X NO. UNITS: 4 or
43 2.TRAFF1C IMPACT FEE
IA
A ADTs. X
3. BRIDGE AND THOROUGHFARE FEE (Il
ADVs X
FACILITIES MANAGEMENT FEE
.1/41
SO.FT: • X
SEWER FEE
M PRMITNO.______
EDU's X
FEE/ADT: :- -
FEADT:___
ZONE________
FEE/SO.F:____
4
BENEFIT AREA: DRAINAGE BASIN:_______
EDU's: X FEEIEDU: 4
& SEWER LATERAL ($2OO DEPOSIT) 4
7 P/ I)
7. WATER FEE .
EDU's: • X FEE!EDU:_______ • 4
TOTAL OF ABOVE FEES $______________
No
Plan Check No. q • )eo
Address
Planner DAVID RICK Phone 438-1161 ext. 4328
(Name)
APN: 2O5- IS 15 -
Type of Project and Use EM).
Zone Facilities Management Zone
CFD (in/out) #________________ circle (If property in, complete SPECIAL TAX CALCULATION
WORKSHEET provided by Building Department.)
2d
[tern Complete
[tern Incomplete . Needs your action
1,2,3 Number in circle indicates plancheck number where deficiency was
identified
13/c 0 Environvn,ntal Review Required: 'YES - NO TYPE
DATE OF COMPLETION:
Compliance with conditions of approval? If not, state conditions which require action.
Conditions of Approval
0 Discretionary Action Required: YES NO zYPE
APPROVALJRESO. NO. DATE:
PROJECT NO.
OTHER RELATED CASES:
Compliance with conditions of approval? If not, state conditions which require action.
Conditions of Approval
California Coastal Commission Penuit Req9ir YES - NO
DATE OF APPROVAL:
San Diego Coast District, 3111 Camino Del Rio North, Suite 200, San Diego, CA. 92108-1725
(619) 521-8036
Compliance with conditions of approval? If not, state conditions which require action.
Conditions of Approval
C3 [ndusionaiy Housing Fee rquired: YES NO (Effective date of [nclusionaxy Housing Ordinance May 21, 1993.)
Site Plan
0 Provide a hWy dimensioned site plan drawn' ra to scale Show: Noh
arrow, property lines, easements, existing and proposed structures,
streets, existing street improvements, right-of-way width, dimensioned
/ setbacks and existing topographical lines.
0 0 Provide legal description of property, and assessor's parcel number.
Zoning S
0 1. Setbacks:
Front: Required 30'
--Shown
• mt. Side: . Required 7' Shown 7'
Street Side: Required Ak Shown '
• Rear: Required ' Shown ?'
0 . 2. Lot coverage: Required 9 Ob Shown 1-31)6
]'1( 0
Height:
,.
Required 30 / Shown
Parking: Spaces Required Shown 2- C
Guest Spaces Required Shown
00 0 Additional Comments
OK TO ISSUE AND ENTERED APPROVAL INTO COMPUTER IIL) a- DATE
PLNCK.FRM
CERTIFICATION OF COMPLIANCE ty /
CITY OF CARLSBA.D Plan Check No. /__! (6 08
DEVELOPMENT PROCESSING SERVICES DIVISION
2075 LAS PALMAS DR., CARLSBAD, CA 92009
(619) 438-1161
This form shall be used to determine the amount of school fees for a project and to verify
that the project applicant has complied with the school fee requirements. No building
permits for the projects shall be issued until the certification is signed by the appropriate
school district and returned to the City of Carlsbad Building Department.
SCHOOL DISTRICT:
_Carlsbad Unified San Marcos Unified _____
801 Pine Avenue 1290 West San Marcos Blvd.
Carlsbad, CA 92009 (434-0610) San Marcos, CA 92024 (744-4776)
Encinitas Union San Dieguito Union High School
101 South Rancho Santa Fe Rd. 710 Encinitas Boulevard
Encinitas, .CA 92024 (619) 994-430a Encinitas, CA 92024 (753-6491)
Project Applicant: APN:-\c -(.3
Project Address: 1OcO
RESIDENTIAL: SQ. FT. of living area __ number of dwelling units (
SQ. FT. of covered area________ SQ. FT. of garage area_____________
COMMERCIAL/ INDUSTRIAL: SQ. F . AREA______
Prepared by Date ~~Zc
FEE CERTIFICATION
(To be completed by the School District)
JAppIicant has complied with fee requirement under Government Code 53080
Project is subject to an existing fee agreement
Project is exempt from Government Code 53080
_____Final Map approval, and construction started before September 1,
(other school fees paid)
Other
Residential Fee Levied: $/(5 427" based on ?2 sq. ft. @
nØi L.stFee Levied:$ based on sq. ft. @________________
District /Official e te
AB 2926 e
crped
201 fees are capped, at $1'. 72 per square foot for residential.
AB 2926 is at .28- per square foot for commercial /industrial.
1986.