HomeMy WebLinkAbout2100 COSTA DEL MAR RD; ; CB151045; Permit07-07-2015
City of Carlsbad
1635 Faraday Av Carlsbad, CA 92008
Commercial/Industrial Permit Permit No: CB151045
Building Inspection Request Line (760) 602-2725
Job Address:
Permit Type:
Parcel No:
Valuation:
Occupancy Group:
Project Title:
2100 COSTA DEL MAR RD CBAD
Tl Sub Type: COMM
2165900100 Lot#: 0
$0.00 Construction Type: NEW
Reference #
SD AVIATORS TENNIS- TEMPORARY
BLEACHERS FOR EVENT FROM JULY 12-30TH
Status: ISSUED
Applied: 04/08/2015
Entered By: LSM
Plan Approved: 07/07/2015
Issued: 07/07/2015
Inspect Area
Plan Check #:
Applicant:
DAVE DOUBROFF
Owner:
LC INVESTMENT2010 LLC
1217 PERSHING ST
WENATCHEE WA 98801
310-890-5378
1601 ELM ST
DALLAS TX 75201
Building Permit $0.00 Meter Size
Add1 Building Permit Fee $0.00 Add'l Red. Water Con. Fee $0.00
Plan Check $0.00 Meter Fee $0.00
Add1 Building Permit Fee $413.00 SDCWA Fee $0.00
Plan Check Discount $0.00 CFD Payoff Fee $0.00
Strong Motion Fee $1.00 PFF (3105540) $0.00
Park Fee $0.00 PFF (4305540) $0.00
LFM Fee $0.00 License Tax (3104193) $0.00
Bridge Fee $0.00 License Tax (4304193) $0.00
BTD #2 Fee $0.00 Traffic Impact Fee (3105541) $0.00
BTD #3 Fee $0.00 Traffic Impact Fee (4305541) $0.00
Renewal Fee $0.00 PLUMBING TOTAL $0.00
Add1 Renewal Fee $0.00 ELECTRICAL TOTAL $0.00
Other Building Fee $0.00 MECHANICAL TOTAL $0.00
Pot. Water Con. Fee $0.00 Master Drainage Fee $0.00
Meter Size Sewer Fee $0.00
Add1 Pot. Water Con. Fee $0.00 Redev Parking Fee $0.00
Reel. Water Con. Fee $0.00 Additional Fees $0.00
Green Bldg Stands (SB1473) Fee $1.00 HMP Fee ??
Fire Expedidted Plan Review $0.00 Green Bldg Standards Plan Chk ??
TOTAL PERMIT FEES $415.00
Total Fees: $415.00 Total Payments To Date: $415.00 Balance Due: $0.00
Inspector:
FINAL APPROVAL
Date: I'fvS' Clearance:
NOTICE: Please take NOTICE that approval of your project includes the "Imposition" of fees, dedications, reservations, or other exactions hereafter collectively
refen-ed to as "fees/exactions." You have 90 days from the date this permit was issued to protest imposition of these fees/exadions. If you protest them, you must
follow the protest procedures set forth in Govemment Code Section 66020(a), and file the protest and any other required information with the City Manager for
processing in accordance with Carlsbad Municipal Code Section 3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attacl<,
review, set aside, void, or annul their imposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection fees and capacity
changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this project. NOR DOES IT APPLY to any
fees/exactions of which vou have previouslv been aiven a NOTICE similar to this, or as to which the statute of limitations has previouslv otherwise expired.
THE FOLLOWING APPROVALS REQUIRED PRIOR TO PERMrr ISSUANCE: nPLANNING OENGINEERING IZlBUILDiNG DFIRE nHEALTH IZlHAZMAT/APCD
<L City of
Carlsbad
Building Permit Appiication
1635 Faraday Ave., Carlsbad, CA 92008
Ph: 760-602-2719 Fax:760-602-8558
email: building@carlsbadca.gov
www.carlsbadca.gov
Plan Check No. (2g> / ^5") QV S
Est. Value
Plan Ck. Deposit iOO OO
JOBADDRESS SUITEf/SPACEf/UNIT* APN
CT/PROJECT # LOT# PHASES # OF UNiTS # BEDROOMS # BATHROOMS TENANT BUSINESS NAME
5^ fW\CL>tor3 Tc^ r»v t>
CONSTR. TYPE OCC. GROUP
DESCRIPTION OFWORK: /nc/ude Square Feet of Affected Arears)
TferoHv^ ^&^~r"^ C^*^T^:p— c:t2.oe:^
EXISTING USE PROPOSED USE GARAGE (SF) PATIOS (SF) DECKS (SF) FIREPLACE
YES|~|* NOj I
AIR CONDITIONING
YES QNO I I
FIRESPRINKLERS
YES I |N0| I
APPLICANT NAIME
Primary Contact
PROPERTYOWNER L ^
ADDRESS ADDRESS
CITY STATE ZIP CITY STATE ZIP
PHONE
3\Q • *gfeQ -5^-7 s
FAX PHONE FAX
EMAIL EMAIL
DESIGN PROFESSIONAL CONTRACTOR BUS. NAME CO
ADDRESS ADDRESS
CITY STATE ZIP
Wg|J (VTCK€^, ^6g)QV
PHONE ' jFAX
CITY , STATE
PHONE FAX
e>QA-7<5:z.6?T>v"7
EMAIL
X^^^'/B' ^C>JC?&<L-Dc£=>^ A<s/<01 C-oM.
EMAIL
3'i/v\cfeuYNN;^TB>F<9apifv\fe»/T .COM STATE LIC.# CITY sus. UC.# -
(Sec. 7031.5 Business and Professions Code: Any City or County wtiicti requires a permit to construct alter, improve, demolisti or repair any structure, priorlo its issuance, also requires the applicantfor sucti permitto file a signed statement ttiat tie is licensed pursuantto ttie provisions ofthe Contractor's License Law (Chapter 9, commendingwith Section 7000 of Division 3 ofthe Business and Professions Code) or that he is exempt therefrom, and the basis forthe alleged exemption. Any violation of Section 7031.5 by any applicantfor a permit subjects the applicant to a civil penalty of not more than five hundred dollars ($500)).
'OR KER!' COMPENSATION
Workej;K:ompensation Declaration: / hereby affimi under penaify ofpeijury one ofthe following deciamtions:
Liar have and will maintain a certificate of consent to self-Insure for workers' compensation as provided by Section 3700 of the Labor Code, for the perfomiance of the work tor which this permit is issued.
• I have and will maintain worlters' compensation.ftiiequiied^V Section 3700 ofthe Labor Code, forthe peifonnance of thejfioritfoLwhich this permit is issued. My workers' compensation insurwice earner and policy
number are: Insurance Co, PolicyNo. Expiration Date
Thissectfon need not be completed if the permit is for one hundied dollais ($100) or less.
[•-^Certificate of Exemptian: I ceitify that in the peifonnance of the woh< for which this pennit is issued, I shall not employ any person in any manner so as to beoome subject to the Workers' Compensation Laws of
Califomia. Vi/ARNING: Failure tosecure workers' compensation coverage is unlawful, and shall subject an employer to criminal penalties and civil fines up to one hundred thousand dollars (&100,000), in
addition to the cost of compensatloh. damages as^vlded for In E3MICK3706 ofJbBlalUK code, interest and attomey's fees. I I
.eS" CONTRACTOR SIGNATUR^jJw^^ cl-^^OOC^ QAGENT DATE V»\"^-T? \ * ^
O W N e R • B U l i. O E R OECL A R A T I O N
/ hereby affinn that i am exempt fmm Contractor's License Law for the foiiowing reason:
I I I, as owner of the pioperty or my employees with wages as their sole compensation, will do the woik and the stmcture is not intended or offered for sale (Sec. 7044, Business and Professions Code: The Contractor's
License Law does not apply to an owner of property who builds or improves thereon, and who does such work himself or through his own employees, provided that such improvements are not intended or offered for
sale. If, however, the building or improvement is sold within one year of completion, the owner-builder will have the burden of proving that he did not build or improve for the purpose of sale).
I I I, as owner of the praperty, am exclusively contracting with licensed contractors to constmct the project (Sec. 7044, Business and Professions Code: The Contractor's License Law does not apply to an owner of
property who builds or improves thereon, and contracts for such projects with contractor(s) licensed pursuant to the Contractor's Ucense Law).
I I I am exempt under Section Business and Professions Code for this reason:
1.1 personally plan to provide the major labor and materials for constmction of the proposed praperty improvement L]Yes I iNo
2.1 (have / have not) signed an application for a building pemiit for the praposed work.
3.1 have contracted with the following person (timi) to provide the proposed constmction (include name address / phone / contractore' license number):
4.1 plan to provide portions of the worit, but I have hired the following peison to coordinate, supenfise and provide the major worit (include name / addiess / phone / contractors' license number):
5.1 will provide some of the work, but I have contracted (hired) the following persons to provide the worit indicated (include name / address / phone / type of worit):
/CTPROPERTY OWNER SIGNATURE •AGENT DATE
COMPtETE THfS SECTiON POR NON-RESIDENTIAL BUlLDiNG PERMITS ONLY
Is the applicant or futuie building occupant required to submit a business plan, acutely hazardous materials registration form or risk management and prevention program under Sections 25505,25533 or 25534 of the
Presley-Tanner Hazardous Substance Account Act? Yes No
Is the applicant or future building occupant required to obtain a permit from the air pollution control district or air quality management district? Yes No
Is the facility to be constmcted within 1,000 feet of the outer boundary of a school site? Yes No
IF ANY OF THE ANSWERS ARE YES, A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR IS MEETING THE REQUIREMENTS OF THE OFFICE OF
EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT
CONSTRUCTION LENOING AGENCY
I hereby affinn that there is a constnjction lending agency fbr the perfonnance of the work this pemiit is issued (Sec. 3097 (i) Civil Code).
Lenders Name Lender's Address
APPLICANT CERTIFICATION
I certif that 1 have read ttie application and stats that ttie above information is conectand Uiat the infomiation on the plans is accuiate. I agree to comply witti all Cify ordinances and State laws relating to building constniction.
I heieby authorize representative ofthe City of Caiisbad to enter upon the above mentioned ptoperty fbr inspectbn purposes. I ALSO AGREE TO SAVE, INDEMNIFY AND KEEP HARMLESS THE CffY OF CARLSBAD
AGAINST ALL UABILmES, JUDGMENTS, COSTS AND EXPENSES WHICH MAY IN ANY WAY ACCRUE AGAINST SAID CIPi' IN CONSEQUENCE OF THE GRANTING OF THIS PERMff.
OSHA An (DSHA pemiit is required fbr excavations over 5'0' deep and demolitbn or consttuctton of stnjctunes over 3 stoties in height.
EXPIRATION: Every pemiit issued by the Building Oflfcial under the provisbns of this Code shall expiie by limltatbn and become null and vob if the building or wortt aulhorized by such permit is not commenced wilhin
180 days from the date of such pemiit or if the buikJing or viorit authorized by such pennit is suspended or abandoned at any time alter the vrortt is comnnenced for a period of 180 days (Sectbn 106.4.4 Unifomi Building Ctxle).
I APPLICANT'S SIGNATUI DATE
STOP: THIS SECTION NOT REQUIRED FOR BUILDING PERMIT ISSUANCE.
Complete the following ONLY If a Certificate of Occupancy will be requested at final Inspection.
Fax (760) 602-8560, Email buildinQ@carisbadca.qov or Mall the completed form to City of Carlsbad, Building Division 1635 Faraday Avenue, Carlsbad, Califomia 92008.
C0#: (Office Use Only)
CONTACT NAIVIE OCCUPANT NAME
ADDRESS BUILDING ADDRESS
CITY STATE ZIP CITY STATE ZIP
Carlsbad CA
PHONE FAX
EIVIAIL OCCUPANT'S BUS. LIC. No.
DELIVERY OPTIONS
PICK UP: CONTACT (Listed above) OCCUPANT (Listed above)
CONTRACTOR (On Pg. 1)
MAILTO: CONTACT (Listed above) OCCUPANT (Listed above)
CONTRACTOR (On Pg. i)
MAIL/FAX TO OTHER:
ASSOCIATED CB#
NO CHANGE IN USE / NO CONSTRUCTION
CHANGE OF USE / NO CONSTRUCTION
ASSOCIATED CB#
NO CHANGE IN USE / NO CONSTRUCTION
CHANGE OF USE / NO CONSTRUCTION
jeSAPPLICANT'S SIGNATURE DATE
Inspection List
Permit*: CB151045 Type: Tl COMM SD AVIATORS TENNIS-TEMPORARY
BLEACHERS FOR EVENT FROM JULY 12-
Date Inspection Item Inspector Act Comments
07/09/2015 19 Final Structural - Rl PM PLEASE/FIRE SIGNS OFF IN AM/
EMAILING CARD
07/09/2015 19 Final Structural PB AP
Monday, July 13, 2015 Page 1 of 1
Car
\-l C
t Re
iS -
^ef f
/Rep'
; CB
tt:
Toti
oriag
BTD;
BTD
Rene
Add1
Othet
Pot\
Metet
Add'!
Rec^.
Gree
Fire f
jlF6i
CB151045 2100 COSTA DEL MAR
INSPECTION RECORD
SD AVIATORS TENNIS
Rl FACHFRS FOR FVFrJ
TEMP'ORARY
FROM .1.-11 Y 12-30TH
Tl OMM
DAVE DOUBROFF
CARLSBAD
Building Divlsfon
a INSPICTION RECORD CARD WITH APPROVED
PLANS MUST BE KEPT ON THE JOB
SCAU. BEFORE liaa^ni FOR NEXT WORK DAY INSPECTION nCf^ODr^ f^OPV
0 FOR BUILDING INSPECTION CALL: 760-602-2725 ItCWV/IXL-' Kj'KJr I
OR GO TOJ www.Carlsbadca.aov/Buiidinq AND CUCK ON
"Request inspection"
DATE:
NO YIS Required Prior to Requesting Building Final If Checked YES Date Insi^tor Notes
2 Planrring/Larxtscape 760-944-8463 Allow 48 hours
CM&I {Enginccrir^ In^jcctiorwl 760-438-3891 Call before 2 pm
X Pre Prewntion 760-602-4660 AUow 48 hours
type Of inspection T^e of Inspection
Date Inspector coDE# ELECTRICAL Date Inspi
#11 iltlMO«»ll #31 OaECTRiCUNDERSROUMO OUFER
«12 REINFORCED STEEL #34 ROUGH ELECTRIC
#66 MASONRY PRE CROUT #33 • ELECTRIC SERVICE • TEMPORARY
• OROIir aWMLORAIKS #35 PHOTOVOLTAIC
*10 BLT PANELS #39 FlHiU.
«li POUR STRIPS CODE* MECHANICAL
#11 coioMMroomHss #41 UNDERGROUND DUCTS & PIPING
#14 SUBFRAME OnOOR •CHUN6 #44 C»UCT*I»IEHUM OREF.HPING
#15 R00FSHEATHHI8 »43 HEXr-AIRCOiO. SYSTEMS
#13 OCT. SHEim PANELS #49 FINAL
#1S INSmAmN CODES COMBO INSPECTION
#18 OCnERIORlAIM #81 UNDERSR0B»B(n,lM1.31)
#17 IN1ERMRIA1K& DRYWAU #82 ORYWAILEWTLATH, GASTES(1?,1W3)
#51 WOlBHWSim/BONO/FOICE #83 ROOFSHEATWG, EXTSHEAR|13,1S)
#5S ramJ^TER/FINAL #84 FRAME ROUGH C0M80( 14,24,34,44)
#19 FINAL , #85 T'Bar(14,a4,34,44J
1 coo« « PLUMBING Oate lns|>ector #89 RNAL OCCOFANCY {19,29.39.49)
#22 omm&WGQ OM/CO FIRE Osite
#21 UNDEBGROUNO CWASTE • WTR
#24 TOPOUT DWASTE DWTR A/S UNDroGROUNO VISUAl
#27 TUB a SHOWER PAN A/SUNOinQROUNDHYMO::
#23 OGAS TEST OCAS PIPING A/S uNOERGRouKi mm.:
•25 WATER NEATER S/sbWRHEWVraUAl ^^:v
#28 SOLAR WATER VSOWRHEAOIOTROSTATIC ~"
#29 ONAl viniiAL
COOES STORMWATER F/AROUGMIN
#600 PRE-CONSTRUCnON MEETINO
#603 FOLLOW UP INSPECTION FIXED EXTINOUISHINQ SSOlW ROWM-w""^
#605 NOnCCro CLEAN ...J FIXED EXTING SYSIIM fRlMSm i@T
•607 WRITTEN WARNING FIXED EXnNGUISHING niill FMAL ^'™^'"*—
#609 NOTICE OFVIOUTION MEDKAL GAS PRESSUREtiir
#610 VERBAL WARNINC MiuicAl GAS HNAL
NO'
nHc
folic
pmx
revv
VOL
cha
REV 100017 S66;B*CK FOR SPECIAL NOTI
Jbh
RECORD OF CONSTRUCTION OBSERVATION
TO: CITT OF CARLSBAD DATE: JULT 1, 2015-
COmUNITY 4 ECONOMIC DEVELOPMENT
1635 FARADAY AVE.
CARLSSAD, CALIFORNIA ^2006
ATTN: MICHAEL PETERSON
BBS JOB NO.
RE: SAN DIE30 AVIATOR TENNIS
LA COSTA RESORT ANP SPA
LOCATION: CARLSBAD, CA ^200°!
OBSERVATION DATE:
LUEDNESDAY
JULY 1, 2015
ARCHITECTURAL REPRESENTATIVE:
N/A
CONTRACTOR:
r iB EQUIPMENT CO., INC.
LOCATION OF OBSERVATION:
2/Al 12' X =1 ADA SEATING FLOOR
OBSERVER:
JOE P. HILL, P. E.
LABORATORY REPRESENTATIVE:
N/A
SUPERINTENDENT:
JIM MCCSLYNN
DESCRIPTION OF CONSTRUCTION OBSERVED:
CONFORMANCE TO PLANS
COMMENTS AND RECOMMENDATIONS:
BASIC STRUCTURE: l^Vjg:tfe#7
2, STAIRS 4 HANDRAILS:
JOE P. HILL, P.E.
CONSULTING STRUCTURAL ENGINEERING
1801 NORTH HAMPTON ROAD, SUITE NO. 440
DE SOTO, TEXAS 75115
MAIN : (972) - 283-5111
FAX : (972) - 283-5113
Job
RECORD OF CONSTRUCTION OBSERVATION
TO: CITY OF CARLSBAD
COMMUNITY 4 ECONOMIC DEVELOPMENT
Ifc35 FARADAY AVE.
CARLSBAD, CALIFORNIA °l200g
ATTN: MICHAEL PETERSON
DATE: JULY 1, 20IB>
lE-lSB JOB NO.
RE: SAN DIEOO AVIATOR TENNIS
LA COSTA RESORT AND SPA
LOCATION: CARLSBAD, CA =1200=1
OBSERVATION DATE:
LUEDNESDAY JULY 1, 2015
ARCHITECTURAL REPRESENTATIVE:
N/A
CONTRACTOR:
T 4 B EQUIPMENT CO., INC.
LOCATION OF OBSERVATION:
&/A1 120' X 4 ROLU BLEACHER
OBSERVER:
JOE P. HILL, P. E.
LABORATORY REPRESENTATIVE:
N/A
SUPERINTENDENT:
JIM MCGfLYNN
DESCRIPTION OF CONSTRUCTION OBSERVED:
CONFORMANCE TO PLANS
COMMENTS AND RECOMMENDATIONS:
1. BASIC STRUCTURE: CXl:^ ^^e0^^m^ j ^T- , ^n^^.'RZ^Vyt
2. STAIRS 4 HANDRAILS:
BY:
CC: JIM MCGLYNN HILL, P. E. - PRESIDENT
HE P. HILL, P.E.
CONSULTING STRUCTURAL ENGINEERING
1801 NORTH HAMPTON ROAD, SUITE NO. 440
DE SOTO, TEXAS 75115
MAIN : (972) - 283-5111
FAX : (972) - 283-5113
RECORD OF CONSTRUCTION OBSERVATION
TO: CITY OF CARLSBAD DATE: JULY 1, 20I5
COMMUNITY 4 ECONOMIC DEVELOPMENT
Ife35 FARADAY AVE.
CARLSBAD, CALIFORNIA =12003
ATTN: MICHAEL PETERSON
JOB NO. B\33
RE: SAN DIEGO AVIATOR TENNIS
LA COSTA RESORT AND SPA
LOCATION: CARLSBAD, CA =12001
OBSERVATION DATE:
LUEDNESDAY
JULY I, 2015
ARCHITECTURAL REPRESENTATIVE:
N/A
CONTRACTOR:
T 4 B EQUIPMENT CO., INC.
LOCATION OF OBSERVATION:
I/A2 IS'x 4 ROLU BLEACHER
OBSERVER:
JOE P. HILL, P. E.
LABORATORY REPRESENTATIVE:
N/A
SUPERINTENDENT:
JIM MCGtLYNN
DESCRIPTION OF CONSTRUCTION OBSERVED:
CONFORMANCE TO PLANS
COMMENTS AND RECOMMENDATIONS:
BASIC STRUCTURE:
2. STAIRS 4 HANDRAILS:
BY:
CC: JIM MCGLYNN HILL, P. E. - PRESIDENT
J0E P. HILL, P.E.
CONSULTING STRUCTURAL ENGINEERING
1801 NORTH HAMPTON ROAD, SUITE NO. 440
DE SOTO, TEXAS 75115
MAIN : (972) - 283-5111
FAX : (972) - 283-5113
Jbh
RECORD OF CONSTRUCTION OBSERVATION
TO: CITY OF CARLSBAD
COMMUNITY 4 ECONOMIC DEVELOPMENT
Ife 35 FARADAY AVE.
CARLSBAD, CALIFORNIA =12008
ATTN: MICHAEL PETERSON
DATE: JULY 1, 2015-
JOB NO. 15)33
RE: SAN DIEGO AVIATOR TENNIS
LA COSTA RESORT AND SPA
LOCATION: CARLSBAD, CA =I200=I
OBSERVATION DATE:
LUEDNESDAY
JULY 1, 2015
ARCHITECTURAL REPRESENTATIVE:
N/A
CONTRACTOR:
T 4 B EQUIPMENT CO., INC.
LOCATION OF OBSERVATION:
4/A2 144'X IO ROLU BLEACHER
OBSERVER:
JOE P. HILL, P. E.
LABORATORY REPRESENTATIVE:
N/A
SUPERINTENDENT:
JIM MCGLYNN
DESCRIPTION OF CONSTRUCTION OBSERVED:
CONFORMANCE TO PLANS
COMMENTS AND RECOMMENDATIONS:
BASIC STRUCTURE: O^C^
2. STAIRS 4 HANDRAILS:
CC: JIM MCGLYNN
I
HILL, P. E. - PRESIDENT
IOE P. HILL, P.E.
CONSULTiDd STRUCTURAL ENGINEERiNG
1801 NORTH HAMPTON ROAD, SUITE NO. 440
DE SOTO, TEXAS 75115
MAIN : (972) - 283-5111
FAX : (972) - 283-5113
EsGil Corporation
In (Partnersliip witfi government for (Building Safety
DATE: 7/6/15 • APPLICANT
• JURIS.
JURISDICTION: Carlsbad • PLAN REVIEWER
• FiLE
PLANCHECKNO.: 15-1045 SET.V
PROJECT ADDRESS: 2100 Costa Del Mar
PROJECT NAME: Temporary Outdoor Bleacher Seating
I I The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's codes.
^ The plans transmitted herewith wiil substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department
staff.
I I The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
I I The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
I I The applicant's copy of the check list is enclosed for the jurisdiction to fonward to the applicant
contact person.
I I The applicant's copy of the check list has been sent to:
I I EsGil Corporation staff did not advise the applicant that the plan check has been completed.
3 EsGil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Jim McGlynn Telephone #: In Person
Date contacted: 7/6/15 (by: CM) Email:
^ REMARKS: A. Enaroseols-one set of approved plans. The clouded revisions on the approved
plans from EsGiLdffsheet A1 must be made to the City set of plans to make a 2"*^ set of
approved plans/B, Ciry B.O. must approved the number of total rest room fixtures and total
C number of ADA Veetloom fixtures for compliance with the code.
By: Chuck Mendenhall Enclosures:
EsGil Corporation
• GA • EJ • PC Walk In , , jn
EsGil Corporation
In (PartnersHip -witli government for (Building Safety
DATE: 7/6/15 • APPLICANT
• JURIS.
JURISDICTION: Carlsbad • PLAN REVIEWER
• FILE
PLANCHECKNO.: 15-1045 SET:V
PROJECT ADDRESS: 2100 Costa Del Mar
PROJECT NAME: Temporary Outdoor Bleacher Seating
I I The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's codes.
^ The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department
staff.
I I The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
I I The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
0 The applicant's copy of the check list is enclosed for the jurisdiction to fonA/ard to the applicant
contact person.
1 I The applicant's copy of the check list has been sent to:
I I EsGil Corporation staff did not advise the applicant that the plan check has been completed.
XI EsGil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Jim McGlynn Telephone #: In Person
Date contacted: 7/6/15 (by: CM) Email:
X REMARKS: A. EnMsteols-one set of approved plans. The clouded revisions on the approved
plans from EsGiLefffiheet A1 must be made to the City set of plans to make a 2"'^ set of
approved plans/ B. <Cny B.O. must approved the number of total rest room fixtures and total
number of ADAVeetfoom fixtures for compliance with the code.
By: Chuck Mendenhall \\ Enclosures:
EsGil Corporation \j
• GA • EJ • PC Walk In
EsGil Corporation
In (Partnersfiip -witfi government for (BuiUing Safety
DATE: 6/29/15 QAPPLICANT
JURIS.
JURISDICTION: Carlsbad • PLAN REVIEWER
• FILE
PLANCHECKNO.: 15-1045 SET: IV
PROJECT ADDRESS: 2100 Costa Del Mar
PROJECT NAME: Temporary Outdoor Bleacher Seating
I I The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's codes.
I I The plans transmitted herewith will substantially comply with the jurisdiction's codes
when minor deficiencies identified below are resolved and checked by building department staff.
I I The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
Kl The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
I I The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
X The applicant's copy of the check list has been sent to:
T&B Equipment Co., Att'n: Jim McGlynn
11065 Leadbetter Rd., Ashland, VA 23005
I I EsGil Corporation staff did not advise the applicant that the plan check has been completed.
EsGil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Jim McGlynn ^^^1 elephone #: (623) 293-7404
Date contacted: (byV^ ) Email: imcqlvnn@tbequipment.com
• REMARKS:
By: Chuck Mendenhall Enclosures:
EsGil Corporation
• GA • EJ • PC 6/24/15
9320 Chesapeake Drive, Suite 208 • San Diego, Califomia 92123 • (858) 560-1468 • Fax (858) 560-1576
Carlsbad 15-1045
6/29/15
NOTE: The items listed below are from the previous correction list These remaining items
have not been adequately addressed. The numbers ofthe items are from the previous check
list and may not necessarily be in sequence. The notes in bold font AND CAPS are current.
1. Please provide an exit analysis plan Show in this analysis the occupant load of each area, the
general exit flow patterns (by using arrows), accumulated occupant loads and required exit
widths. Section 107.2.3. Also, include in the exit analysis a site exit analysis showing the exit
flow from the seating area to public way. Occupants must have exit access to a public way.
There was no exit analysis provided as discussed by phone on 6/16/15. The exit
analysis would consist of the arrows pointing to the exits and the number of people
assigned to that exit. Specify on the exist analysis the required width of the exit based
on the occupant load and the actual width of the exit per CBC Section 1005.2. THE EXIT
ANALYSIS AND OCCUPANT LOADS HAVE BEEN PROVIDED ON 8-1/2x11 SHEETS.
BASED ON THE OCCUPANT LOAD THE AISLE BETWEEN THE TEMP BLEACHER
SEATING ( DETAIL 4/A2) AND FIXED SEATS MUST BE DIMENSIONED AS 72" WIDE.
THE AISLE DIMENSION BETWEEN TEMP BLEACHER SEATING ( DETAIL 5/a1) AND THE
EXISTING FIXED SEATING MUST BE 48". THESE DIMENSIONS ARE NOT SHOWN ON
THE PLANS. CBC SECTION 1028.6.3.
3. Provide calculations to show compliance with CPC Section 412.0 & Table 4-1, (Minimum
Plumbing Facilities forthis event) As per our phone conversation 6/16/15 the City will
review the total number of required temporary rest room and hand washing facilities
DISABLED ACCESS SEATING
6. Specify the slope of the disabled access ramp that serves the 72'X9' ADA seating area. The
max slope without handrail is 1:20. Section 11 B-402.2. The e-mail with site slope shown
from the disabled seating area to the lower level is less than 5% and need not have
handrails. The correction also applies to the ramps that access the raised seating area
for the disabled as shown in detail 2 on sheet Al. The following corrections apply to the
ramps at the raised seating area. THE CURRENT 8-1/2x11 PLAN SHEETS BY T&B
EQUIP CO. SHOW THAT YOU INTEND TO ELIMINATE THE DISABLED ACCESS
SEATING AREA. THIS SEATING IS STILL SHOWN ON THE PLANS BY J.P. HILL
ENGINEERING. ALSO. PROVIDE JUSTIFI8CATI0N FOR THE ELIMINATION OF THE
DISABLED SEATING.
7. The allowable slope for an accessible ramp is ^1:12 (8.33%), per Section 11B-405.2.
8. Show or note that ramp surfaces will be slip resistant. Section 11 B-302.1.
9. Where the ramp surface is not bounded by a wall, the ramp shall comply with one of the
following requirements, per Section 11B-405.9.2:
• A guide curb a minimum of 2" in height shall be provided at each side of the ramp; or
• A wheel guide rail shall be provided that prevents the passage of a 4" sphere where the sphere
is within 4" of the finish floor.
Carlsbad 15-1045
6/29/15
1? MIN,
12' MIN.
(b)GUC3ER4ilL
HAhjR,41L
R3
JT
3-J. r -ic-H
/iVHsiL GUIDE
n GUiDz R4IL
CENTESED 4T
J." HIGH
IF sues RAI DETAI
(clVfl-EELOJCt WHEBLGUDEDETAJL
THESE DSAKWJUS (LLUSTTMTE ThE Sf^lFIC REQUR£f.€NT5
CF THESE REGSJLATJONS AW3 ARE INTENDED CR.Y AS AN AID
rm BUtONG DESGN AhB COSSTSLCTIOK.
FIGURE tlB^T—RAMPS AKD SIDEWALKS
10. Show on the plans that the max rise of the ramp between landings is 30
DISABLED ACCESS SANITARY FACILITIES
13. As per our phone conversation 6/16/15 you have spoken to Will Foss BO for the City has
agreed to accept portable ADA complying rest rooms in lieu of fixed rest rooms. The
number of ADA portable rest rooms must be reviewed and approved by City Staff.
END OF PLAN RECHECK
The jurisdiction has contracted with Esgil Corporation located at 9320 Chesapeake Drive,
Suite 208, San Diego, California 92123; telephone number of 858/560-1468, to perform the
plan review for your project. If you have any questions regarding these plan review items,
please contact Chuck Mendenhall at Esgil Corporation. Thank you.
EsGil Corporation
In (Partnersfiip witfi government for (BuiCding Safety
DATE: 6/18/15 •APPLICANT
/efjURIS.
JURISDICTION: Carlsbad • PLAN REVIEWER
• FILE
PLANCHECKNO.: 15-1045 SET: III
PROJECT ADDRESS: 2100 Costa Del Mar
PROJECT NAME: Temporary Outdoor Bleacher Seating
I I The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's codes.
I I The plans transmitted herewith will substantially comply with the jurisdiction's codes
when minor deficiencies identified below are resolved and checked by building department staff.
I I The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
X The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
I I The applicant's copy of the check list is enclosed for the jurisdiction to fonward to the applicant
contact person.
X The applicant's copy of the check list has been sent to:
T&B Equipment Co., Att'n: Jim McGlynn
11065 Leadbetter Rd., Ashland, VA 23005
I I EsGil Corporation staff did not advise the applicant that the plan check has been completed.
EsGil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Jim McGlynn X Telephone #: (623) 293-7404
Date contacted: (^['^ {by.^f^^^ EmaiK imcqlvnn(q^tbequipment.com
• REMARKS:
By: Chuck Mendenhall Enclosures:
EsGil Corporation
• GA • EJ • PC 6/17/15 (e-mail)
9320 Chesapeake Drive, Suite 208 • San Diego, Califomia 92123 • (858) 560-1468 • Fax (858) 560-1576
Carlsbad 15-1045
6/18/15
Please make all corrections, as requested in the correction list. Submit FOUR new complete
sets of plans for commercial/industrial projects (THREE sets of plans for residential projects).
For expeditious processing, corrected sets can be submitted in one of two ways:
1. Deliver all corrected sets of plans and calculations/reports directly to the City of Carlsbad
Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760) 602-2700. The City will
route the plans to EsGil Corporation and the Carlsbad Planning, Engineering and Fire
Departments.
2. Bring one corrected set of plans and calculations/reports to EsGil Corporation, 9320
Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-1468. Deliver all remaining
sets of plans and calculations/reports directly to the City of Carlsbad Building Department for
routing to their Planning, Engineering and Fire Departments.
NOTE: Plans that are submitted directly to EsGil Corporation only will not be reviewed by the
City Planning, Engineering and Fire Departments until review by EsGil Corporation is complete.
NOTE: The items listed below are from the previous correction list. These remaining items
have not been adequately addressed. The numbers ofthe items are from the previous check
list and may not necessarily be in sequence. The notes in bold font are current. A number of
corrections were not addressed
1. Please provide an exit analysis plan Show in this analysis the occupant load of each area, the
general exit flow patterns (by using arrows), accumulated occupant loads and required exit
widths. Section 107.2.3. Also, include in the exit analysis a site exit analysis showing the exit
flow from the seating area to public way. Occupants must have exit access to a public way.
There was no exit analysis provided as discussed by phone on 6/16/15. The exit
analysis would consist of the arrows pointing to the exits and the number of people
assigned to that exit Specify on the exist analysis the required width of the exit based
on the occupant load and the actual width ofthe exit per CBC Section 1005.2
3. Provide calculations to show compliance with CPC Section 412.0 & Table 4-1, (Minimum
Plumbing Facilities for this event) As per our phone conversation 6/16/15 the City will
review the total number of required temporary rest room and hand washing facilities
DISABLED ACCESS SEATING
6. Specify the slope of the disabled access ramp that serves the 72'X9' ADA seating area. The
max slope without handrail is 1:20. Section 11 B-402.2. The e-mail with site slope shown
from the disabled seating area to the lower level is less than 5% and need not have
handrails. The correction also applies to the ramps that access the raised seating area
for the disabled as shown in detail 2 on sheet Al. The following corrections apply to the
ramps at the raised seating area.
7. The allowable slope for an accessible ramp is <1:12 (8.33%), per Section 11 B-405.2.
8. Show or note that ramp surfaces will be slip resistant. Section 11 B-302.1.
9. Where the ramp surface is not bounded by a wall, the ramp shall comply with one of the
following requirements, per Section 11B-405.9.2:
• A guide curb a minimum of 2" in height shall be provided at each side of the ramp; or
Carlsbad 15-1045
6/18/15
• A wheel guide rail shall be provided that prevents the passage of a 4" sphere where the sphere
is within 4" of the finish floor.
12" MIN.
(bjOiCeiMIL
12- MIN.
1 e
C-U DE RAIL
CEMESED 4-
;•• A" HiGH
aUtX liALDET.«L
WHEEL "G¥IDE
(cjWVCEL>3LICC WHEEL GUDE tout
THESE iUJUSTRATE THE SPECIFIC REQuaEf/ENTS
OF THESE REGULATiONS AKO ARE INTENDED CHJr AS AN .AID
FOR BU .DING DeS<3>J AND CONSTHLtt^lOK.
FIGURE 11 B-27—RAMPS Am SIDEWALKS
10. Show on the plans that the max rise of the ramp between landings is 30
DISABLED ACCESS SANITARY FACILITIES
13. As per our phone conversation 6/16/15 you have spoken to Will Foss BO for the City has
agreed to accept portable ADA complying rest rooms in lieu of fixed rest rooms. The
number of ADA portable rest rooms must be reviewed and approved by City Staff.
END OF PLAN RECHECK
The jurisdiction has contracted with Esgil Corporation located at 9320 Chesapeake Drive,
Suite 208, San Diego, California 92123; telephone number of 858/560-1468, to perform the
plan review for your project. Ifyou have any questions regarding these plan review items,
please contact Chuck Mendenhall at Esgil Corporation. Thank you.
EsGil Corporation
In (Partnersliip -witfi government for (Building Safety
DATE: 5/13/15 • APPLICANT
• JURIS.
JURISDICTION: Carlsbad • PLANREVIEWER
• FILE
PLANCHECKNO.: 15-1045 SET: II
PROJECT ADDRESS: 2100 Costa Del Mar
PROJECT NAME: Temporary Outdoor Bleacher Seating
I I The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's codes.
I I The plans transmitted herewith will substantially comply with the jurisdiction's codes
when minor deficiencies identified below are resolved and checked by building department staff.
I I The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
I I The applicant's copy of the check list is enclosed for the jurisdiction to fonward to the applicant
contact person.
^ The applicant's copy of the check list has been sent to:
T&B Equipment Co., Att'n: Jim McGlynn
11065 Leadbetter Rd., Ashland, VA 23005
I I EsGil Corporation staff did not advise the applicant that the plan check has been completed.
EsGil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Jim McGlynn Telephone #: (623) 293-7404
Date contacted: (by: ) Email: imcqlvnn(S)tbequipment.com
• REMARKS:
By: Chuck Mendenhall Enclosures:
EsGil Corporation
• GA • EJ • PC 5/12/15
9320 Chesapeake Drive, Suite 208 • San Diego, Califomia 92123 • (858) 560-1468 • Fax (858) 560-1576
Carlsbad 15-1045
5/13/15
Please make ail corrections, as requested in the correction list. Submit FOUR new complete
sets of plans for commercial/industrial projects (THREE sets of plans for residential projects).
For expeditious processing, corrected sets can be submitted in one of two ways:
1. Deliver all corrected sets of plans and calculations/reports directly to the City of Carlsbad
Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760) 602-2700. The City will
route the plans to EsGil Corporation and the Carlsbad Planning, Engineering and Fire
Departments.
2. Bring one corrected set of plans and calculations/reports to EsGil Corporation, 9320
Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-1468. Deliver all remaining
sets of plans and calculations/reports directly to the City of Carlsbad Building Department for
routing to their Planning, Engineering and Fire Departments.
NOTE: Plans that are submitted directly to EsGil Corporation only will not be reviewed by the
City Planning, Engineering and Fire Departments until review by EsGil Corporation is complete.
NOTE: The items listed below are from the previous correction list These remaining items
have not been adequately addressed. The numbers of the items are from the previous check
list and may not necessarily be in sequence. The notes in bold font are current. A number of
corrections were not addressed
1. Please provide an exit analysis plan Show in this analysis the occupant load of each area, the
general exit flow patterns (by using arrows), accumulated occupant loads and required exit
widths. Section 107.2.3. Also, include in the exit analysis a site exit analysis showing the exit
flow from the seating area to public way. Occupants must have exit access to a public way.
No response and no plan change
3. Provide calculations to show compliance with CPC Section 412.0 & Table 4-1, (Minimum
Plumbing Facilities for this event) No response and no plan change
DISABLED ACCESS SEATING
6. Specify the slope of the disabled access ramp that serves the 72'X9' ADA seating area. The
max slope without handrail is 1:20. Section 11 B-402.2. No response and no plan change
7. The allowable slope for an accessible ramp is ^1:12 (8.33%), per Section 11 B-405.2. No
response and no plan change
8. Show or note that ramp surfaces will be slip resistant. Section 11 B-302.1. No response and no
plan change
9. Where the ramp surface is not bounded by a wall, the ramp shall comply with one of the
following requirements, per Section 11B-405.9.2: No response and no plan change
• A guide curb a minimum of 2" in height shall be provided at each side of the ramp; or
• A wheel guide rail shall be provided that prevents the passage of a 4" sphere where the sphere
is within 4" ofthe finish floor.
Carlsbad 15-1045
5/13/15
"1
(bjOJCt RAIL
C-U DS SAIL
CESTSSED «-
r .tV HiGH
GUCtHALDETAL
h4NgRa,::L
r ^ 1' -ISM
WHEEL' Gu ioi
lc)WI-CELaLIDe WHEB.aUDE DETAIL
THEEE D^rSRMilS ILLLBTRATE THE SPECIFIC RECJiiSSEI^NTS
CF THESE REGaLAT50NS AKD ARE SiTENDEO CWLV AS AN AID
FC« SULOIMG DESSN ANS COfjSmkSTIOIV.
FIGUKE ttB-27-«AMPS AND SfflEWAUCS
10. Show on the plans that the max rise ofthe ramp between landings is 30". No response and
no plan change
DISABLED ACCESS SANITARY FACILITIES
13. Show on the plans the location and number of disabled accessible rest room facilities. Where
separate facilities are provided for persons of each sex, these facilities shall be accessible to
persons with disabilities. Where unisex facilities are provided, these facilities shall be
accessible to persons with disabilities, per Section 1115B.2. No response and no plan
change
• Show that passageways leading to sanitary facilities have required clear access widths, per
Section 1115B.5. Show that all doonways have: No response and no plan change
• >32" clear opening.
• A clear area:
• >60" in the direction of the door swing.
• >44" away from the direction of door swing.
• All strike edge clearance dimensions are required to be met (i.e. 18" strike edge distance).
15. Note that the doorways leading to sanitary facilities shall be identified, per Section 1115B.6, as
follows: No response and no plan change
• An equilateral triangle %" thick with edges 12" long and a vortex pointing upward at men's rest
rooms.
Carlsbad 15-1045
5/13/15
• A circle %" thick, 12" in diameter at women's rest rooms.
• A 12" diameter circle with a triangle superimposed on the circle and within the 12" diameter at
unisex rest rooms.
• The required symbols shall be centered on the door at a height of 60".
• Braille signage shall also be located on the wall adjacent to the latch outside of the doonways
leading to the sanitary facilities, per Section 1117B.5.1.
16. Show a sufficient space in the toilet room for a wheelchair to enter the room and close the door,
per Section 1115B.3.2. The space is required to be: No response and no plan change
• >60" diameter.
• A T-shaped space as shown in Figure 11 B-12(a) and (b).
• Doors are not permitted to encroach into this space by more than 12 inches.
17. Show that the water closet is located in a space, per Section 1115B.3.2.3, which provides: No
response and no plan change
• A clear space in front of the water closet measuring 60" wide by 48" in front. Section
1115B.4.1.2. See the following figures:
m'wn.
Carlsbad 15-1045
5/13/15
ooonmiifnsD
(UTO^B} PORTION
tafOBMUNCESATWATeRClOSir
18. Doors shall not swing into the clear floor space required for any fixture but may swing into that
portion of the maneuvering space which does not overlap the required clear floor space.
Maintain the required clearances at the lavatory/water closet without the entry door swinging into
those areas. Section 1115B.3.2.2. No response and no plan change
19. Show, or note, on the plans that the accessible water closets meet the following requirements,
per Section 1115B.4.1: No response and no plan change
• The seat is to be >17" but <19" in height.
• The controls for flush valves shall be:
• Mounted on the side of the toilet area.
• Be ^44" above the floor.
20. Show, or note, on the plans that accessible urinals meet the following requirements, per Section
1115B.4.2: No response and no plan change
• The rim of at least one urinal shall:
• Project at least 14" from the wall.
• Be ^17" above the floor.
• The control mechanism is to be located <44" above the floor.
• >30" X 48" clear floor space is provided in front of the accessible urinal. Section 1115B.4.2.
21. Show that accessible lavatories comply with the following, per Sections 1115B.4.3: No
response and no plan change
• >30" X 48" clear space is provided in front for fonA/ard approach. The clear space may include
knee and toe space beneath the fixture.
• When lavatories are adjacent to a side wall or partition, there shall be a minimum of 18" to the
center line of the fixture to the wall.
• The counter top is ^34" maximum above the floor.
• >29" high, reducing to 27" at a point located 8" back from the front edge.
• >9" high x 30" wide and 17" deep at the bottom.
• Hot water pipes and drain lines are insulated.
Carlsbad 15-1045
5/13/15
22. Show that grab bars comply with the following, per Section 1115B.4: No response and no plan
change
Grab bars shall be located on each side or one side and the back of the water closet stall or
compartment.
They shall be securely attached 33" above the floor, and parallel.
NOTE: Where a tank-type toilet is used which obstructs placement at 33", the grab bar may be
installed as high as 36".
Grab bars at the side shall be located:
15" to 1672" (±1") from the center line ofthe water closet stool.
Be >42" long with the front end positioned 24" in front of the stool.
Total length of bars at the back shall be >36".
The diameter, or width, of the grab bar gripping surface is >1 %" but ^1 V-i', or the shape shall
provide an equivalent gripping surface.
If mounted adjacent to a wall, the space between the wall and the grab bar shall be V/z.
END OF PLAN RECHECK
The jurisdiction has contracted with Esgil Corporation located at 9320 Chesapeake Drive,
Suite 208, San Diego, California 92123; telephone number of 858/560-1468, to perform the
plan review for your project. Ifyou have any questions regarding these plan review items,
please contact Chuck Mendenhall at Esgil Corporation. Thank you.
EsGil Corporation
In (Partnersfiip witfi government for (Building Safety
DATE: 4/16/15 • APl^lCANT
JURIS.
JURISDICTION: Carlsbad / • PLAN REVIEWER
• FILE
PLANCHECKNO.: 15-1045 SET: I
PROJECT ADDRESS: 2100 Costa Del Mar
PROJECT NAME: Temporary Outdoor Bleacher Seating
I I The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's codes.
I I The plans transmitted herewith will substantially comply with the jurisdiction's codes
when minor deficiencies identified below are resolved and checked by building department staff.
I I The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
^ The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
I I The applicant's copy of the check list is enclosed for the jurisdiction to fonA/ard to the applicant
contact person.
^ The applicant's copy of the check list has been sent to:
T&B Equipment Co., Att'n: Jim McGlynn
11065 Leadbetter Rd., Ashland, VA 23005
I I EsGil Corporation staff did not advise the applicant that the plan check has been completed.
IXI EsGil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Jim McGlynn Telephone #: (623) 293-7404
Date contacted:-^-^ {^ {by.Q^A Email: imcqlvnn(5^tbequipment.com
• REMARKS: ^(^ai (
By: Chuck Mendenhall Enclosures:
EsGil Corporation
• GA • EJ • PC 4/9/15
9320 Chesapeake Drive, Suite 208 • San Diego, Califomia 92123 • (858) 560-1468 • Fax (858) 560-1576
Carlsbad 15-1045
4/16/15
PLAN REVIEW CORRECTION LIST
COMMERCIAL
PLANCHECKNO.: 15-1045 JURISDICTION: Carlsbad
OCCUPANCY: A-5 USE: Bleachers for Outdoor viewing
TYPE OF CONSTRUCTION: VB ACTUAL AREA: 4,950 sq ft Approx.
ALLOWABLE FLOOR AREA: UL STORIES: NA
HEIGHT: 16 ft approx.
SPRINKLERS?: NA OCCUPANT LOAD: 1270 Approx.
REMARKS:
DATE PLANS RECEIVED BY
JURISDICTION:
DATE PLANS RECEIVED BY
ESGIL CORPORATION: 4/9/15
DATE INITIAL PLAN REVIEW
COMPLETED: 4/16/15
PLAN REVIEWER: Chuck Mendenhall
FOREWORD (PLEASE READ):
This plan review is limited to the technical requirements contained in the California version of
the International Building Code, Uniform Plumbing Code, Uniform Mechanical Code, National
Electrical Code and state laws regulating energy conservation, noise attenuation and access for
the disabled. This plan review is based on regulations enforced by the Building Department.
You may have other corrections based on laws and ordinances enforced by the Planning
Department, Engineering Department, Fire Department or other departments. Clearance from
those departments may be required prior to the issuance of a building permit.
Code sections cited are based on the 2010 CBC, which adopts the 2009 IBC.
The following items listed need clarification, modification or change. All items must be satisfied
before the plans will be in conformance with the cited codes and regulations. Per Sec. 105.4 of
the 2009 International Building Code, the approval of the plans does not permit the violation of
any state, county or city law.
To speed UD the recheck Drocess. please note on this list (or a copv) where each
correction item has been addressed, i.e.. plan sheet number. sDecification section, etc.
Be sure to enclose the marked up list when vou submit the revised plans.
Carlsbad 15-1045
4/16/15
Please make all corrections, as requested in the correction list. Submit FOUR new complete
sets of plans for commercial/industrial projects (THREE sets of plans for residential projects).
For expeditious processing, corrected sets can be submitted in one of two ways:
1. Deliver all corrected sets of plans and calculations/reports directly to the City of Carlsbad
Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760) 602-2700. The City will
route the plans to EsGil Corporation and the Carlsbad Planning, Engineering and Fire
Departments.
2. Bring one corrected set of plans and calculations/reports to EsGil Corporation, 9320
Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-1468. Deliver all remaining
sets of plans and calculations/reports directly to the City of Carlsbad Building Department for
routing to their Planning, Engineering and Fire Departments.
NOTE: Plans that are submitted directly to EsGil Corporation only will not be reviewed by the
City Planning, Engineering and Fire Departments until review by EsGil Corporation is complete.
1. Please provide an exit analysis plan Show in this analysis the occupant load of each area, the
general exit flow patterns (by using arrows), accumulated occupant loads and required exit
widths. Section 107.2.3. Also, include in the exit analysis a site exit analysis showing the exit
flow from the seating area to public way. Occupants must have exit access to a public way.
2. Show or note on the plans that the aisle center discontinuous handrails shall have gaps at
least 22" but no more than 36". CBC Section 1028.13.1
3. Provide calculations to show compliance with CPC Section 412.0 & Table 4-1, (Minimum
Plumbing Facilities for this event)
. STRUCTURAL
4. Note on the plans that the design engineer of record must provide special inspection of the
completed structural system and notify the Building Official in writing that the construction was
inspected by him and found to comply with the design and the code prior to final approval for
use bythe City. CBC Section 1705.1.1. NOTE: the City of Carlsbad special inspection
agreement form must be completed and returned to the city prior to permit issuance. See the
attached.
5. Where in the design calc's did you show that the /4" bolted connections are adequate for the
most critical shear loads? See bolted L- clip detail on sheet Bl.
• DISABLED ACCESS SEATING
6. Specify the slope of the disabled access ramp that serves the 72'X9' ADA seating area. The
max slope without handrail is 1:20. Section 11 B-402.2.
7. The allowable slope for an accessible ramp is ^1:12 (8.33%), per Section 11 B-405.2.
8. Show or note that ramp surfaces will be slip resistant. Section 11B-302.1.
9. Where the ramp surface is not bounded by a wall, the ramp shall comply with one of the
following requirements, per Section 11B-405.9.2:
Carlsbad 15-1045
4/16/15
a) A guide curb a minimum of 2" in height shall be provided at each side ofthe ramp; or
b) A wheel guide rail shall be provided that prevents the passage of a 4" sphere where the
sphere is within 4" of the finish floor.
1? MIN.
(biiaiCC RAJL
12' MIN.
GUiDE SAIL
CEIHTESED AT
J" HIGH
GUCe II .AL PETAL
(c)yvKELajcc WHEaOUDEOCTAIL
THESE DIAG=MMS ILLUSTRATE TtC SraCIFtC REQUSEMENTS
OF THESE RE&JLATKNS AMD ARE INTEHDH) 0(*.Y AS AN AID
FOR BLittHNS DESGN AND COHSTRIXTIOK
FIGURE 11B-27—RAMPS AMD SIDEWALKS
10. Show on the plans that the max rise of the ramp between landings is 30".
11. Note on the plans that stainA/ays occurring outside a building comply with Section 11 B-504.4.1
as follows:
a) The upper approach and all treads shall be marked with a strip of contrasting color as
follows:
i) >2" in width.
ii) Placed parallel to and ^1" from the nose of the step or landing.
iii) The strip is required to be as slip resistant as the treads of the stairs.
iv) A painted stripe will be acceptable, but grooves shall not be used to satisfy this
requirement.
DISABLED ACCESS SANITARY FACILITIES
13. Show on the plans the location and number of disabled accessible rest room facilities. Where
separate facilities are provided for persons of each sex, these facilities shall be accessible to
persons with disabilities. Where unisex facilities are provided, these facilities shall be
accessible to persons with disabilities, per Section 1115B.2.
Carlsbad 15-1045
4/16/15
14. Show that passageways leading to sanitary facilities have required clear access widths, per
Section 1115B.5. Show that all dooHA/ays have:
a) >32" clear opening.
b) A clear area:
i) >60" in the direction of the door swing.
ii) >44" away from the direction of door swing.
c) All strike edge clearance dimensions are required to be met (i.e. 18" strike edge
distance).
15. Note that the doonA/ays leading to sanitary facilities shall be identified, per Section 1115B.6, as
follows:
a) An equilateral triangle thick with edges 12" long and a vortex pointing upward at men's
rest rooms.
b) A circle %" thick, 12" in diameter at women's rest rooms.
c) A 12" diameter circle with a triangle superimposed on the circle and within the 12"
diameter at unisex rest rooms.
d) The required symbols shall be centered on the door at a height of 60".
e) Braille signage shall also be located on the wall adiacent to the latch outside of the
doonA/ays leading to the sanitary facilities, per Section 1117B.5.1.
16. Show a sufficient space in the toilet room for a wheelchair to enter the room and close the door,
per Section 1115B.3.2. The space is required to be:
a) >60" diameter.
b) A T-shaped space as shown in Figure 11 B-12(a) and (b).
c) Doors are not permitted to encroach into this space by more than 12 inches.
17. Show that the water closet is located in a space, per Section 1115B.3.2.3, which provides:
a) A clear space in front of the water closet measuring 60" wide by 48" in front. Section
1115B.4.1.2. See the following figures:
Carlsbad 15-1045
4/16/15
60'MIN
CENTERLINE
OF
FIXTURE
in
FLUSH
ACTIVATOR
ON WIDE
SIDE
gjEAftlHtOOftSWCE f
4rm
CIEAR FIOOR SLUICE
ooi»mmm
(i4 CLEARANCES AT WhTBt Of^ET
18. Doors shall not swing into the clear floor space required for any fixture but may swing into that
portion of the maneuvering space which does not overlap the required clear floor space.
Maintain the required clearances at the lavatory/water closet without the entry door swinging into
those areas. Section 1115B.3.2.2.
19. Show, or note, on the plans that the accessible water closets meet the following requirements,
per Section 1115B.4.1:
a) The seat is to be >17" but <19" in height.
b) The controls for flush valves shall be:
i) Mounted on the side of the toilet area.
Carlsbad 15-1045
4/16/15
ii) Be ^44" above the floor.
20. Show, or note, on the plans that accessible urinals meet the following requirements, per Section
1115B.4.2:
a) The rim of at least one urinal shall:
i) Project at least 14" from the wall.
ii) Be <17" above the floor.
b) The control mechanism is to be located ^44" above the floor.
c) >30" X 48" clear floor space is provided in front of the accessible urinal. Section
1115B.4.2.
21. Show that accessible lavatories comply with the following, per Sections 111 5B.4.3:
a) >30" X 48" clear space is provided in front for fonA/ard approach. The clear space may
include knee and toe space beneath the fixture.
b) When lavatories are adjacent to a side wall or partition, there shall be a minimum of 18" to
the center line of the fixture to the wall.
c) The counter top is ^34" maximum above the floor.
d) >29" high, reducing to 27" at a point located 8" back from the front edge.
e) >9" high x 30" wide and 17" deep at the bottom.
f) Hot water pipes and drain lines are insulated.
22. Show that grab bars comply with the following, per Section 1115B.4:
a) Grab bars shall be located on each side or one side and the back of the water closet stall
or compartment.
b) They shall be securely attached 33" above the floor, and parallel.
NOTE: Where a tank-type toilet is used which obstructs placement at 33", the grab bar may be
installed as high as 36".
c) Grab bars at the side shall be located:
i) 15" to 16!^" (±1") from the center line of the water closet stool.
ii) Be >42" long with the front end positioned 24" in front of the stool.
iii) Total length of bars at the back shall be >36".
d) The diameter, or width, of the grab bar gripping surface is >1 but ^114", or the shape
shall provide an equivalent gripping surface.
e) If mounted adjacent to a wall, the space between the wall and the grab bar shall be 114".
END OF PLAN REVIEW
The jurisdiction has contracted with Esgil Corporation located at 9320 Chesapeake Drive,
Suite 208, San Diego, California 92123; telephone number of 858/560-1468, to perform the
plan review for your project. If you have any questions regarding these plan review items,
please contact Chuck Mendenhall at Esgil Corporation. Thank you.
•J^^x Development Services
<^ SPECIAL INSPECTION Building D..isi«.
^ CITY OF AGREEMENT 1635 Faraday Avenue
r^ADl CD An B-45 760 602 2719
JD/AL-/ www.carlsbadca.gov
in accordance with Chapter 17 ofthe Califomia Building Code the following must be completed when work being performed
requires special inspection, structural observation and construction material testing.
*roject/Permlt: Project Address:
A. THIS SECTION MUST BE COMPLETED BY THE PROPERTY OWNER/AUTHORIZED AGENT. Please check if you are ChMner-Builder
•. (If you checked as owner-builder you must also complete Section B of this agreement)
Name: (Please print)
(First) (Ml.) (Last)
Mailing Address:
Email: Flione;
lam: QProperty Owner •Property Owner's Agent of Recorcl QArchitect of Record QEngineer of Record
State of Califomia Registration Numtjec: Expiration Date:
AGREEMENT: I, the undersigned, declare under penalty of perjury under the laws of the State of Califomia, that I have read,
understand, acknowledge and promise to comply with the City of Carisbad requirements for special inspections, structural
observations, construction materials testing and off-site fabrication of building components, as prescribed in the statement of
special inspections noted on the approved plans and, as required t>y the Califomia Buiiding Code.
Signature: Date:
B. CONTRACTOR'S STATEMENT OF RESPONSIBIUTY (07 CBC, Ch 17, Section 1706/ This section must be completed by the
contractor / builder / owner-txjilder.
Contractor's Company Name: Please check if you are Ovmer-Bullder •
Name: (Please print)
(Firat) (M.I.) (Ust)
Mailing Address:
Email: Phone;
State of Califomia Contractor's License Number: Expiration Date:.
• I acknowledge and, am aware, of special requirements contained in the statement of special inspections noted on
the approved plans;
• I acknowledge that control will be exercised to obtain confomnance witti the construction documents approved by the
building official;
• I will have in-place procedures for exercising control within our (the contractor's) organization, for the method and
frequency of reporting and the distribution of the reports; and
• I certify that I will have a qualified person within our (the contractor's) organization to exercise such control.
• / will orovide a ffiraaf reoort/letter in cowp/Zance with CBC Section 1704.1.2 priorto reauestina ffna/
//ispectfoifi.
Signature; Date:
B-45 Pagelofi Rev. 08/11
Carlsbad 15-1045
4/16/15
[DO NOT PAY- THIS IS NOT AN INVOICE]
VALUATION AND PLAN CHECK FEE
JURISDICTION: Carlsbad PLANCHECKNO.: 15-1045
PREPARED BY: Chuck Mendenhall DATE: 4/16/15
BUILDING ADDRESS: 2100 Costa Del Mar
BUILDING OCCUPANCY: A-5 TYPE OF CONSTRUCTION: VB
BUILDING
PORTION
AREA
( Sq. Ft.)
Valuation
Multiplier
Reg.
Mod.
VALUE ($)
Outdoor Seating 4950 Hrly
Air Conditioning
Fire Sprinklers
TOTAL VALUE
Jurisdiction Code cb By Ordinance
Bldg. Permit Fee by Ordinance
Plan Check Fee by Ordinance •
Type of Review: • Complete Review
EHRepetitive Fee ^ Repeats
Based on hourly rate
• Other
[7] Hourly
EsGil Fee
• Structural Only
Hrs.
$348.00
Comments:
Sheet 1 of 1
macvalue.doc +
PLAN CHECK PLAN CHECK Community & Economic
^ CITY OF REVIEW Development Department
1635 Faraday Avenue
CARLSBAD TRANSMITTAL Carlsbad CA 92008
ww/w.carlsbadca.gov
DATE:04-14-2015 PROJECT NAME: LA COSTA RESORTTEMPORARY BLEACHERS
PLANCHECKNO: 1 SET#: 1 ADDRESS: 2100 COSTA DEL MAR RD.
VALUATION: $
PROJECT ID: CB15-1045
APN:
/ This plan check review is complete and has been APPROVED by the ENGINEERING
Division.
By: CG 4/14/15
A Final Inspection by the Division is required Yes / No
This plan check review is NOT COMPLETE. Items missing or incorrect are listed on
the attached checklist. Please resubmit amended plans as required.
Plan Check Comments have been sent to: DAVE@UNDERDOGPLANNIN6.COIVI
You may also have corrections from one or more ofthe divisions listed below. Approval
from these divisions may be required prior to the issuance of a building permit.
Resubmitted plans should include corrections from all divisions.
For questions or clarifications on the attached checklist please contact the following reviewer as mari<ed:
PLANNING
760-602-4610
ENGINEERING
760-602-2750
FllEfRiVENTIQN
760-602-4665 i
Chris Sexton
760-602-4624
Chris.Sexton@carlsbadca.^ov
/ Chris Glassen
760-602-2784
Christopher.Glassen@carlsbadca.gov
Greg Ryan
760-602-4663
Gregorv.Rvan@carlsbadca.gov
Gina Ruiz
760-602-4675
Gina.Ruiz@carlsbadca.gov
Linda Ontiveros
760-602-2773
Linda.Ontiveros@carlsbadca.gov
Cindy Wong
760-602-4662
Cynthia.Wong@carlsbadca.gov
Dominic Fieri
760-602-4664
Dominic.Fieri@carlsbadca.gov
Remarks:
CITY OF
CARLSBAD
BUILDING PLANCHECK
CHECKLIST
QUICK-CHECK/APPROVAL
Development Services
Land Development Engineering
1635 Faraday Avenue
760-602-2750
www.carlsbadca.gov
ENGINEERING Plan Check for CB15-1045 Date: 04-14-2015
Project Address: 2100 COSTA DEL MAR RD. APN:
^ . ... BLEACHER SEATING FOR 1,270 TOTAL SEATS FOR „ , * Project Description: wjj jENNIS EVENT AT CENTER COURT JULY 12-30. Valuation: 3,
ENGINEERING Contact: CHRIS GLASSEN
Phone: 760-602-2784
Email: Christopher.Glassen@carlsbadca.gov
Fax: 760-602-1052
RESIDENTIAL INTERIOR TENANT IMPROVEMENT
RESIDENTIAL ADDITION MINOR
(<$20,000.00)
PLAZA CAMINO REAL
CARLSBAD PREMIER OUTLETS COMPLETE OFFICE BUILDING
/ OTHER: LA COSTA RESORT
OFFICIAL USE ONLY
ENGINEERING AUTHORIZATION TO ISSUE BUILDING PERMIT
BY: CG 4/14/15
REMARKS: NO ADDITIONAL ENGINEERING FEE
DATE: 04-14-2015
I
Notification of Engineering APPROVAL has been sent to DAVE@UNDERD0GPLANNING.COM |
via EMAIL on 04-14-2015 j
E-36 1 of 1 REV 4/30/11
^ CITY O F
CARLSBAD
STORM WATER
COMPUANCE
ASSESSMENT
B-24
Development Services
Building Division
1635 Faraday Avenue
760-602-2719
www.carlsbadca.eov
I am applying to the City of Carlsbad for the following type(s) of construction permit:
Building Permit • Right-of-Way Permit
'My project is categorically EXEMPT from
the requirement to prepare a storm water
pollution prevention plan (SWPPP) because it
only requires issuance of one or more of the
following permit types:
Electrical
Fire Additional
Fire Alarm
Fixed Systems
Meciianical
Mobile Home
Plumbing
Patio/Deck
Photo Voltaic
Re-Roofing
Sign
Spa-Factory
Sprinlder
Water Discharge
Project Storm Water Threat Assessment Criteria*
No Threat Assessment Criteria
• My projed qualifies as NO THREAT and is exempt from the requirement to prepare a stonn water pollution prevention plan (SWPPP) because
it meets the "no threaf assessment criteria on the Cit/s Project Threat Assessment Worksheet for Determination of Constniction SWPPP Tier
Level. My project does not meet any of the High, Moderate or Low Threat criteria described below.
Tierl - Low Titreat Assessment Criteria
• My project does not meet any of the Significant or Moderate Threat criteria, is not an exempt pennit type (See list above) and the project
meets one or more of the following criteria:
• Results in some soil disturbance; and/or
• Includes outdoor constnjction activities (such as saw cutting, equipment washing, material stockpiling, vehicle fueling, waste stockpiling).
T/er2 • Moderate Threat Assessment Criteria
• My project does not meet any of the Significant Threat assessment Criteria described below and meets one or more of the following criteria:
• Project requires a grading plan pursuant to the Carisbad Grading Ordinance (Chapter 15.16 of the Carisbad Municipal Code); or,
• Project will result in 2,500 square feet or more of soils disturbance including any associated construction staging, stockpiling, pavement
removal, equipment storage, refueling and maintenance areas and project meets one or more of the additional following criteria:
• Located within 200 feet of an environmentally sensitive area or the Pacific Ocean, and/or
• Disturbed area is located on a slope with a grade at or exceeding 5 horizontal to 1 vertical, and/or
• Disturbed area is located along or within 30 feet of a storm drain inlet an open drainage channel or watercourse, and/or
• Construction wil! be initiated during the rainy season or will extend into the rainy season (Oct. 1 through April 30).
T/ef3 -
•
a
Significant Threat Assessment Criteria
My project includes clearing, grading or other disturbances to the ground resulting in soil disturbance totaling one or more acres Including any
associated construction staging, equipment storage, stockpiling, pavement removal, refueling and maintenance areas: and/or
My project Is part of a phased development plan that will cumulatively result in soil disturbance totaling one or more acres including any
associated construction staging, equipment storage, refueling and maintenance areas: or,
My project is located inside or within 200 feet of an environmentally sensitive area (see City ESA Proximity map) and has a significant
potential for contributing pollutants to nearby receiving waters by way of storm water runoff or non-storm water discharge(s).
/ cerfify to the best of my knowledge that the above
checJted statements are true and correct I understand
and acknowledge that even though this project does
not requ/re preparation of a construction SWPP, I must
still adhere to, and at all times during construction
actlvJOes for the permit type(s) check above comply
with the storm water best management practices
pursuant to Title 15 of the Carlsbad Municipal Code
and to Citv Standards.
•The City Engineer may authorize minor variances from the Storm
Water Threat Assessment Criteria in special circumstances where it
can be shown that a lesser or higher Construction SWPPP Tier Level is
wan-arited.
Project Address; Assessor Parcel No.
2-\oo CTc^fvv -^i^i^ MAR. "Po
Owner/Owner's Authorized Agent Name:
Owner/Owner's Authorized Agent Signature:
City Concun'ence:
I^YES QNO
By; Date:
Title; •CPvPiec.rjz,*-
Date;
Project ID:
B-24 Page 1 of 1 Rev.03/09
CITY OF
CARLSBAD
CONSTRUCTION THREAT
ASSESSMENT WORKSHEET FOR
DETERMINATION OF PROJECT'S
PERCEIVED THREAT TO
STORM WATER QUALITY
E-33
Development Services
Land Development Engineering
1635 Faraday Avenue
760-602-2750
www.carlsbadca.gov
Construction
SWPPP Tier
Level
Construction Threat Assessment Criteria*
Perceived
Threat to
Storm Water
Quality
Tier 3
Tier 3 - Hiah Construction Threat Assessment Criteria
U Project site is 50 acres or more and grading will occur during the rainy season
• Project site is 1 acre or more in size and is located within the Buena Vista or Agua Hedionda
Lagoon watershed, inside or within 200 feet of an environmentally sensitive area (ESA) or
discharges directly to an ESA
• Soil at site is moderately to highly erosive (defined as having a predominance of soils with
USDA-NRCS Erosion factors kf greater than or equal to 0.4)
• Site slope is 5 to 1 or steeper
• Construction is initiated during the rainy season or will extend into the rainy season (Oct. 1
through April 30).
• Owner/contractor received a Stomn Water Notice of Violation within past two years
High
Tier 3
Tier 3 - Medium Constaiction Threat Assessment Criteria Medium
Tier 3
• All projects not meeting Tier 3 High Construction Threat Assessment Criteria Medium
Tier 2
Tier 2 Hiah Constnjction Threat Assessment Criteria
• Project is located within the Buena Vista or Agua Hedionda Lagoon watershed, inside or
within 200 feet of an environmentally sensitive area (ESA) or discharges directly to an ESA
• Soil at site is moderately to highly erosive (defined as having a predominance of soils with
USDA-NRCS Erosion factors kf greater than or equal to 0.4)
• Site slope Is 5 to 1 or steeper
• Construction is initiated during the rainy season or will extend into the rainy season (Oct. 1
through April 30).
• Owner/contractor received a Storm Water Notice of Violation within past two years
• Site results in one half acre or more of soil disturbance
High
Tier 2
Tier 2 - Medium Construction Threat Assessment Criteria Medium
Tier 2
• All projects not meeting Tier 2 High Construction Threat Assessment Criteria Medium
Tierl
Tier 1 - Medium Inspection Threat Assessment Criteria
Medium
Tierl
• Project is located within the Buena Vista or Agua Hedionda Lagoon watershed, within or
directly adjacent to an environmentally sensitive area (ESA) or discharges directly to an ESA
• Soil at site is moderately to highly erosive (defined as having a predominance of soils with
USDA-NRCS Erosion factors kf greater than or equal to 0.4)
• Site slope is 5 to 1 or steeper
• Construction is initiated during the rainy season or will extend into the rainy season (Oct. 1
through April 30).
• Owner/contractor received a Storm Water Notice of Violation within past two years
• Site results in one half acre or more of soil disturbance
Medium
Tierl
Tier 1 - Low Inspection Threat Assessment Criteria Low
Tierl
• All projects not meeting Tier 1 Medium Construction Threat Assessment Criteria Low
Exempt - Not Applicable -Exempt
*The city engineer may authorize minor variances from the constnjction threat assessment criteria in special circumstances
where it can be shown that a lesser or higher amount of storm water compliance inspection is warranted in the opinion of
the city engineer
E-33 Page 1 of 1 REV 4/30/10
^ CITY OF-
CARLSBAD
PLANNING DIVISION
BUILDING PLAN CHECK
APPROVAL
P-29
Development Services
Planning Division
1635 Faraday Avenue
(760) 602-4610
www.carlsbadca.eov
DATE: 4/9/15 PROJECT NAME: TEMP. BLEACHERS PROJECT ID:
PLAN CHECK NO: CB151045 SET#: ADDRESS: 2100 COSTA DEL MAR RD APN:
^ This plan check review is complete and has been APPROVED by the PLANNING
Division.
By: GINA RUIZ
A Final Inspection by the PLANNING Division is required • Yes ^ No
You may also have corrections from one or more of the divisions listed below. Approval
from these divisions may be required prior to the issuance of a building permit
Resubmitted plans should include corrections from all divisions.
[]] This plan check review is NOT COMPLETE. Items missing or incorrect are listed on
the attached checklist. Please resubmit amended plans as required.
Plan Check APPROVAL has been sent to: DAVE@UNDERD0GPLANNING.COM
For questions or clarifications on the attached checklist please contact the following reviewer as marked:
PLANNING
760-602-4610
ENGINEERING
760-602-2750
FIRE PREVENTION
760-602-4665
1 1 Chris Sexton
760-602-4624
Chris.Sexton@carlsbadca.eov Ct
Chris Glassen
760-602-2784
ristopher.Glassen@carlsbadca.gov
Greg Ryan
760-602-4663
Gregorv.Rvan@carlsbadca.gov
1 1 Gina Ruiz
760-602-4675
Gina.Ruiz@carlsbadca.iSov
ValRay Marshall
760-602-2741
ValRaxJyiarshall@carlsbadca.gov
[~~] Cindy Wong
760-602-4662
Cvnthia.Wong@carlsbadca.gov
• Linda Ontiveros
760-602-2773
.-inda.OntiverosQcarlstedca^oy
[ I Dominic Fieri
760-602-4664
Dommic.Fieri@carlsbadca.gov
Remarks: TEIVIP. BLEACHERS PREVIOUSLY APPROVED BY VL PER CB121161
^ CITY OF
CARLSBAD
PLAN CHECK
REVIEW
TRANSMITTAL
Community & Economic
Development Department
1635 FaradayAvenue
Carlsbad CA 92008
www.carlsbadca.gov
DATE: 4/29/15 PROJECT NAME: bleachers sd aviators tennis
PLAN CHECK NO: cbl41045 SET#: I
PROJECT ID:
ADDRESS: 2100 costa del mar APN:
•
This plan check review is complete and has been APPROVED ^ the flre Division.
By: cwong
A Final Inspection by the Division is required
1
IYes DNo
This plan check review is NOT COMPLETE. Items missing or incorrec&j;e listed on
the attached checklist. Please resubmit amended plans as required.
Plan Check Comments have been sent to dave@,underdogplanning.com & USPS
You may also have corrections from one or more of the divisions listed below. Approvai
from these divisions may be required prior to the issuance of a buiiding permit.
Resubmitted plans shouid include corrections from ail divisions.
For questions or clarifications on the attached checklist please contact the following reviewer as marked:
1 1 Chris Sexton
760-602-4624
Chris.Sexton@carlsbadca.gov
1 1 Kathleen Lawrence
760-602-2741
Kathleen.Lawrence@carlsbadca.gov
1 1 Greg Ryan
760-602-4663
Gre£ory.Rya n@carlsbadca.gov
1 1 Gina Ruiz
760-602^675
Gina.Ruiz@carlsbadca.^ov
1 1 Linda Ontiveros
760-602-2773
Linda.Ontiveros@carlsbadca.gov
X Cindy Wong
760-602-4662
Cvnthia.Wong@carlsbadca.gov
• • 1 1 Dominic Fieri
760-602-4664
Dominic.Fieri@carlsbadca.gov
Remarks:
4/29/15
**APPROVED:
Page 1 of 2
THIS PROJECT HAS BEEN REVIEWED AND APPROVED FOR THE PURPOSES OF ISSUEANCE
OF A BUILDING PERMIT.
THIS APPROVAL IS SUBJECT TO FIELD INSPECTIONS, ANY REQUIRED TESTS, FIRE
DEPARTMENT NOTATIONS, CONDITIONS IN CORRESPONDENCE AND COMPLIANCE WITH
ALL APPLICABLE CODES AND REGULATIONS.
THIS APPROVAL SHALL NOT BE HELD TO PERMIT OR APPROVE ANY VIOLATION OF THE
LAW.
4/23/15
***Bubble All Changes***
1. Second floor viewing balcony is greyed out and is not shown in details. Please confirm
that this area will not be built this year. If it will be built, add to front,rear and side
elevations. Include means of egress. Be sure to show unobstructed egress the entire way
to public way.
Page 2 of2
Carlsbad Fire Department
Plan Review Reguirements Category: COGEN , PHOTO
Date of Report: 04-29-2015 Reviewed by:
Name:
Address:
KYLE STEPHENS
UNIT 701
1350 COLUMBIA ST
SAN DIEGO CA
92101-3456
Permit #: CBI50696
Job Name: SCROOSCOOPS: 14 ROOF MOUNT PV
Job Address: 2180 LAS PALMAS DR CBAD
INCOMPLETE Thei! aye submitted for review is iiicomplete. A^^ time, this office CMmot
adequately conduct a review to Hpitffrmlj^'g"|i iiiii|iiMi| | |]^
^or specifications, with changes "clouded", carefully all i niiimi iill min il I'll i i resubmit the necess
to this office for review and approval.
Conditions;
Cond: CON0008124
[NOT MET]
Please identify on sheet A-l the roofs centeriine structural supports. Per CFC 605.11.3.3.2
Entry: 03/25/2015 By: df Action: CO
Cond: CON0008237
[MET]
**APPROVED:
THIS PROJECT HAS BEEN REVIEWED AND APPROVED FOR THE PURPOSES OF ISSUEANCE OF A
BUILDING PERMIT.
THIS APPROVAL IS SUBJECT TO FIELD INSPECTIONS, ANY REQUIRED TESTS, FIRE DEPARTMENT
NOTATIONS,
CONDITIONS IN CORRESPONDENCE AND COMPLIANCE WITH ALL APPLICABLE CODES AND
REGULATIONS.
THIS APPROVAL SHALL NOT BE HELD TO PERMIT OR APPROVE ANY VIOLATION OF THE LAW.
Entry: 04/29/2015 By: cwong Action: AP
^^^^
^ CITY OF
CARLSBAD
PLAN CHECK
REVIEW
TRANSMITTAL
Community & Economic
Development Department
1635 FaradayAvenue
Carlsbad CA 92008
www.carlsbadca.gov
DATE: 4/23/15 PROJECTNAME: PROJECTID:
PLAN CHECK NO: cbl41045 SET#: I ADDRESS: 2100 costa del mar
7^
APli^
[]] This plan check review is complete and has been APPROVED by the fire Division.
By: cwong
A Final Inspection by the Division is required |^ Yes • No
^ This plan check review is NOT COMPLETE. Items missing or incorrect are listed on
the attached checklist. Please resubmit amended plans as required.
Plan Check Comments have been sent to dave@,underdogplanning.com & USPS
You may also have corrections from one or more of the divisions listed beiow. Approval
from these divisions may be required prior to the issuance of a building permit.
Resubmitted plans should include corrections from aii divisions.
For questions or clarifications on the attached checklist please contact the following reviewer as marked:
• f—rr—I V _ «—• :T» <
• 1 1 Chris Sexton
760-602-4624
Chris.Sexton@carlsbadca.gov
1 1 Kathleen Lawrence
760-602-2741
Kathleen.Lawrence@carlsbadca.gov
1 1 Greg Ryan
760-602-4663
GregorY.Rvan@carlsbadca.gov
1 1 Gina Ruiz
760-602-4675
Gina.Rulz@carlsbadca.gov
1 1 Linda Ontiveros
760-602-2773
Linda.Ontiveros@carlsbadca.gov
X Cindy Wong
760-602-4662
Cynthia.Wong@carlsbadca.gov
• • 1 1 Dominic Fieri
760-602-4664
Dominic.Fieri@carlsbadca.gov
Remarks:
4/23/15
Page 1 of 2
***Bubble All Changes***
1. Second floor viewing balcony is greyed out and is not shown in details. Please confirm
that this area will not be built this year. If it will be built, add to front,rear and side
elevations. Include means of egress. Be sure to show unobstructed egress the entire way
to public way.
Page 2 of 2
Carlsbad Fire Department
Plan Review Requirements Category: TI, COMM
Date of Report: 04-23-2015
DAVE DOUBROFF
Reviewed by:
Name:
Address:
1217 PERSHING ST
WENATCHEE WA
98801
Permit #: CBI51045
Job Name: SD AVIATORS TENNIS- TEMPORARY
Job Address: 2100 COSTA DEL MAR RD CBAD
INCOMPLETE The item you have submitted for review is incomplete. At this time, this office cannot
adequately conduct a review to determine compliance with the applicable codes and/or standards. Please review
carefully all comments attached. Please resubmit the necessary plans and/or specifications, with changes "clouded",
to this office for review and approval.
Conditions:
Cond: CON0008220
[NOT MET]
***Bubble All Changes*
1. Second floor viewing balcony is greyed out and is not shown in details. Please confirm that this
area will not be built this year. If it will be built, add to fi'ont,rear and side elevations.
Include means of egress. Besure to show unobstructed egress to public way.
Entry: 04/23/2015 By: cwong Action: CO
h
May 7, 2015
EsGil Corporation
9320 Chesapeake Dr., Suite 208
San Dlego, CA 92123
Re: Temporary Outdoor Bleacher Seating
Project Location: 2100 Costa Del Mar
Plan Check No.: 15-1045
Jurisdiction: Carlsbad
Mr. Chuck Mendenhall
In regards to your structural review comments from April 16, 2015; we offer
the following response.
Note Comment
2. Provided dimension to show the discontinuous handrails on sheet 4/A2 of the
plans.
Structural Comments
4. Provided note on sheet A1 of the plans that the design engineer of record
must provide special inspection ofthe completed structural system.
5. Provided calculations for the critical shear load on the threaded stud
connection L-clip.
Disabled Access Seating Comment
11. Provided note on sheet B1 of the plans that stainways occurring outside a
building complywith Section 11B-504.4.1.
Should you have any questions or concerns, please contact us directly at 972-283-
5111.
Sincerely,
3def. Hill, P. E.
President
JPH:cd
JOE P. HILL, P.E.
CONSULTING STRUCTURAL ENGINEERING
1801 N. Hampton Rd., Suite 440
DeSoto.TX 75115-2399
972-283-5111
Joh
Vl K. CALCULATIONS
L- CLiP
Ostr^G iz. -T\{^eA£>E^ ST\IO
JOB: DATE:, ^
BY:
JOE P. HILL, P.E.
CONSULTING STRUCTURAL ENGINEERING SHEET OF.
CB151045 2100 COSTA DEL IVIAR RD
SD AVIATORS TENNIS- TEMPORARY
Rl PAr.HFR.<; pnp C\/PMT PRnu ii ii v i9-^nTM
^|.:ir|rb <^t=C
-7. (JJIULS OkL. on cSCriU cBrr^^ '
7?4t£>L (^CJXXJ^ Dr^^&)
7"'/IS" H^'^HKd
Final Inspection required by: