HomeMy WebLinkAbout2100 PALOMAR AIRPORT RD; ; CB080846; Permit06-27-2008
City of Carlsbad
1635 Faraday Av Carlsbad, CA 92008
Commercial/Industrial Permit Permit No
Building Inspection Request Line (760) 602-2725
CB080846
Job Address
Permit Type
Parcel No
Valuation
Occupancy Group
Project Title
Applicant
2100 PALOMAR AIRPORT RD CBAD
Tl Sub Type INDUST
2130201800 Lot# 0 Status
$20,47500 Construction Type 3A Applied
Reference # Entered By
PALOMAR AIRPORT-HANGER #7- Plan Approved
585 SF TI-(335 SF MEZZANINE TO OFFICE.250 SF 1ST FLR Issued
Inspect Area
Plan Check*
Owner
ISSUED
05/08/2008
RMA
06/27/2008
06/27/2008
KELCHLIN CONSTRUCTION COUNTY OF SAN DIEGO
12225 WORLD TRADE DR 92128
858618-2785
PUBLIC AGENCY 00000
Building Permit
Add'l Building Permit Fee
Plan Check
Add'l Plan Check Fee
Plan Check Discount
Strong Motion Fee
Park Fee
LFM Fee
Bridge Fee
BTD #2 Fee
BTD #3 Fee
Renewal Fee
Add'l Renewal Fee
Other Building Fee
Pot Water Con Fee
Meter Size
Add'l Pot Water Con Fee
Reel Water Con Fee
$201 15 Meter Size
$0 00 Add'l Reel Water Con Fee
$13075 Meter Fee
$0 00 SDCWA Fee
$0 00 CFD Payoff Fee
$430 PFF (3105540)
$0 00 PFF (4305540)
$0 00 License Tax (3104193)
$0 00 License Tax (4304193)
$000 Traffic Impact Fee (3105541)
$000 Traffic Impact Fee (4305541)
$0 00 PLUMBING TOTAL
$0 00 ELECTRICAL TOTAL
$0 00 MECHANICAL TOTAL
$0 00 Master Drainage Fee
Sewer Fee
$0 00 Redev Parking Fee
$0 00 Additional Fees
HMP Fee
TOTAL PERMIT FEES
$000
$000
$000
$000
$372 65
$343 98
$000
$000
$296 40
$273 60
$4800
$2000
$3750
$000
$531 45
$000
$000
77
$2,259 78
Total Fees $2,259 78 Total Payments To Date $2,259 78 Balance Due $000
:.;DJNG PLANS
IN STORAGE
ATTACHED
Inspector —>
FINAL APPROVAL
Date _Clearance
NOTiCE Please take NOTICE that approval of your project includes the "Imposition" of fees, dedications, reservations, or other exactions hereafter collectively
referred to as lees/exactions" You have 90 days from the date this permit was issued to protest imposition of these fees'exactions if you protest them, you must
follow the protest procedures set forth in Government Code Section 66020(a), and file the protest and any other required information with the City Manager for
processing in accordance with Carlsbad Municipal Code Section 3 32 030 Failure to timely follow that procedure will bpi any subsequent legal action to attack,
review, set aside, void, or annul their imposition
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection fees and capacity
changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this project NOR DOES IT APPLY to any
fees/exactions of which you have previously been given a NOTICE similar to this, or as to which the statute of limitations has previously otherwise expired
City of Carlsbad
1635 Faraday Ave , Carlsbad, CA 92008
760-602-2717 / 2718 / 2719
Fax 760-602-8558
Plan Check No.
Plan Ck. Deposit
Building Permit Application
JOB ADDRESS2-100 -020 -
CONSTR TYPE I OCC GROUPPHASE # # OF UNITS I # BEDROOMS # BATHROOMS TENANT BUSINESS NAME
DESCRIPTION OF WORK Include Square Feet of Affected Area(s)
\
FIRE SPRINKLERS
YES/fi NOD
E (ff Different Fom
ADDRESS-p-ioo
ARCH/DESIGNER NAME & ADDRESS
(Sec. 70315 Business and Professions Code Any City or County which requires a permit to construct, alter, improve, demolish or repair any structure, prior to its issuance, also requires the applicant for such permit to fjfe~a//ifried statement that Ae a
licensed pursuant to the provisions of the Contractor's License Law (Chapter 9, commending with Section 7000 ol Division 3 of the Business and Professions Code) or that he is exempt therefrom, and the basis lor the jftegn exemption Any violation of
Section 71)31 S by any applicant for a permit subjects the applicant to a mil penalty of not more than five hundred dollars {$500}) | "
Workers' Compensation Declaration / hereby affirm under penalty of perjury one of the following declarations
D I have and will maintain a certificate of consent to self insure for workers compensation as provided by Section 3700 of the Labor Code for the performance of the work for which this permit is issued
J& I have and will maintain workers' compensation as required by Section 3700 of the Labor Code, for the performance of the work for which this permit is issued My workers compensation insurance carrier and policy
number are InsuranceCo I ^t^goVy^ /^uvt»A/-rfi \ IA^> Policy No g^uJCLQO L| gr«T<5 Cs Expiration Date O[ [ 8 I ( 7JD<3 <?
This section need not be completed if the permit is for one hundred dollars ($100) or less
O Certificate of Exemption I certify that in the performance of the work for which this permit is issued I shall not employ any person in any manner so as to become subject to the Workers Compensation Laws of
California WARNING Failure to secure workers' compensation coverage is unlawful, and shall subject an employer to criminal penalties and civil fines up to one hundred thousand dollars (4100,000), in
addition to the cost of compensation, damages as orovided for injeettoin706 of the Labor code, Interest and attorney's fees
I hereby affirm that I am exempt from Contractor s License Law for the following reason
O I as owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not intended or offered for sale (Sec 7044 Business and Professions Code The Contractor's
License Law does not apply to an owner of property who builds or improves thereon and who does such work himself or through his own employees provided that such improvements are not intended or offered for
sale If however, the building or improvement is sold within one year of completion, the owner builder will have the burden of proving that he did not build or improve for the purpose of sale)
O I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec 7044, Business and Professions Code The Contractor's License Law does not apply to an owner of
property who builds or improves thereon and contracts for such projects with contractor(s) licensed pursuant to the Contractor s License Law)
n I am exempt under Section Business and Professions Code for this reason
1 I personally plan to provide the major labor and materials for construction of the proposed property improvement CJ Yes a No
2 I (have / have not) signed an application for a building permit for the proposed work
3 I have contracted with the following person (firm) to provide the proposed construction (include name address / phone / contractors license number)
4 I plan to provide portions of the work but I have hired the following person to coordinate supervise and provide the major work (include name / address / phone / contractors license number)
5 I will provide some of the work but I have contracted (hired) the following persons to provide the work indicated (include name / address / phone / type of work)
^PROPERTY OWNER SIGNATURE DATE
Is (he applicant or future building occupant required to submit a business plan acutely hazardous matenals registration form or nsk management and prevention program under Sections 25505 25533 or 25534 of the
Presley Tanner Hazardous Substance Account Act' O Yes D No
Is the applicant or future building occupant required to obtain a permit from the air pollution control distnct or air quality management district' a Yes O No
Is the facility to be constructed within 1,000 feet of the outer boundary of a school site? a Yes a No
IF ANY OF THE ANSWERS ARE YES, /
EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT
I hereby affirm that there is a construction lending agency for the performance of the work this permit is issued (Sec 3097 (i) Civil Code)
Lender's Name Lender's Address
Irertjfythatlhavereadtheapplic^onandstatethattheabcweinfb^^ I agree to comply with all Crty ordinances and State laws relatmgto building construction
I hereby auftionze representative of the City of Carlsbad to enter upon ttie above mentioned property for inspection purposes I ALSO AGREE TO SAVE, INDEMNIFY AND KEEP HARMLESS THE CITY OF CARLSBAD
AGAINST ALL LIABILITIES, JUDGMENTS, COSTS AND EXPENSES WHICH MAY IN ANY WAY ACCRUE AGAINST SAID CITY IN CONSEQUENCE OF THE GRANTING OF THIS PERMIT
OSHA An OSHA permit is required for excavations over 5'0' deep and demolition or construction of structures over 3 stones in height
EXPIRATION Every permit issued by the Building Official under the provisions of this Code shall expire by limitation and become null and void if Ihe building or work authonzed by such permit is not commenced within
180 days from the date of such permit or if the builaWbr work auttaaecTBft such perrat is suspended or abandoned at any feme after the work is commenced for a penod of 180 days (Secton 106 4 4 Unifoim Building Code)
, ^APPLICANT'SSIGNATURE C^^sC^Pf ^J-^-^f ' DATE
\f
ip^ai City of cansbad iTti^IIEfEj^
Final Building Inspection u^^
Dept Building Engineering Planning CMWD St Lite NEn-e^ 1 v)
Plan Check* Date 09/30/2008
Permit* CB080846 Permit Type Tl
Project Name PALOMAR AIRPORT-HANGER #7- Sub Type INDUST
585 SF TI-(335 SF MEZZANINE TO OFFICE.250 SF 1ST F
Address 2100 PALOMAR AIRPORT RD Lot 0
Contact Person JOE
Sewer Dist CA
Inspected /) / j
Bv /. (j[J<8s4A0i
Inspected
Bv
Inspected
Bv
Phone 6197783994
Water Dist CA
Date a / // f/ XInspected i rZ/o^ % Approved £s Disapproved
Date
Inspected Approved Disapproved
Date
Inspected Approved Disapproved
Comments
Inspection List
Permit* CB080846 Type Tl
Date Inspection Item
09/30/2008 89
09/30/2008 89
09/15/2008 14
09/15/200834
09/15/2008 44
09/12/2008 14
09/12/200824
09/12/2008 34
09/12/2008 44
09/04/2008 17
08/29/2008 17
08/29/2008 24
08/11/2008 14
08/11/200824
08/08/2008 34
07/16/2008 11
Final Combo
Final Combo
Frame/Steel/BoltmgA/Veldin
Rough Electric
Rough/Ducts/Dampers
Frame/Steel/Boltmg/Weldin
Rough/Topout
Rough Electric
Rough/Ducts/Dampers
Interior Lath/Drywall
Interior Lath/Drywall
Rough/Topout
Frame/Steel/Boltmg/Weldin
Rough/Topout
Rough Electric
Ftg/Foundation/Piers
INDUST PALOMAR AIRPORT-HANGER #7-
585 SF TI-{335 SF MEZZANINE TO OFFICE
Inspector Act Comments
TP
-
TP
TP
TP
MC
MC
MC
MC
TP
MC
MC
TP
TP
TP
PD
AP
Rl
AP
AP
AP
CO SEE NOTICE
CO
CO
CO
AP
CO NOTICE, OK TO TAPE LOWER RM
AP EXT GATE CODE 2 & 4
SIMULTANEOUSLY AND THEN 3
AP NEED ENG REV FOR TJIs, L90 SPEC &
NEED WELD REPORT
CO NEED TES T
AP
AP
Wednesday, October 01, 2008 Page 1 of 1
City of Carlsbad Bldg Inspection Request
For 09/30/2008
Permit* CB080846
Title PALOMAR AIRPORT-HANGER #7-
Inspector Assignment TP
Description 585 SF TI-(335 SF MEZZANINE TO OFFICE.250 SF 1ST FLR
OFFICE)
Type Tl Sub Type INDUST
Job Address 2100 PALOMAR AIRPORT RD
Suite Lot 0
Location
OWNER COUNTY OF SAN DIEGO
Phone 6197783994
Inspector
Owner WESTERN SERVICE CONTRACT CORP <LF> PALOMAR AIPOR
Remarks
Total Time Requested By JOE
Entered By CHRISTINE
CD Description
19 Final Structural
29 Final Plumbing
39 Final Electrical
49 Final Mechanical
Act Comments
AP .
Comments/Notices/Holds
Associated PCRs/CVs Original PC#
PCR05031 WITHDRAW PALOMAR AIRPORT BLDG 1 RLVISF 1RI NCI I DRAINS
PCR05043 ISSUED AIKI'OR I HANGAR BLDG-1, PLUMBING REVISIONS
PCR05095 ISSUED PALOMAR AIRPOR P HANGER BLDG 1 MISC REVISIONS DPI TA 5
PCR05119 ISSUED PALOMAR AIRPORFCNIR DkPERRCD STAIR SUBMITTIAL BLDG I
PCR05180 ISSUED BLDCi I DELTA 8 S> PAIR SUBMI H AL
PCR05189 ISSUED PALOMAR AIRPORT BLDG I DELTA 7 RHVISIONS
PCR05227 ISSUED PALOMAR AIRPORT CENTER CHANGE DIRIXTIVr II-I DOOR ADD HKhLl I b \VINL
PCR06035 ISSUED PALOMAR AIRPORT BLDG 1 WALl GLAZING
Inspection History
CommentsDate Description Act
09/15/2008 14 Frame/Steel/Bolting/Weldmg AP
09/15/2008 34 Rough Electric AP
09/15/2008 44 Rough/Ducts/Dampers AP
09/12/2008 14 Frame/Steel/Bolting/Weldmg CO
09/12/2008 24 Rough/Topout CO
Insp
TP
TP
TP
MC SEE NOTICE
MC
City of Carlsbad Bldg Inspection Request
For 09/12/2008
Permit* CB080846
Title PALOMAR AIRPORT-HANGER #7-
Inspector Assignment TP
Description 585 SF TI-(335 SF MEZZANINE TO OFFICE.250 SF 1ST FLR
OFFICE)
Type Tl Sub Type INDUST
Job Address 2100 PALOMAR AIRPORT RD
Suite Lot 0
Location
OWNER COUNTY OF SAN DIEGO
Owner RELATIONAL PALOMAR LLC <LF> PALOMAR AIRPORT CENT
Remarks CEILING IN HANGER #7
Phone 6194954148
Inspector
Total Time Requested By JESUS
Entered By CHRISTINE
CD Description Act Comments
14 Frame/Steel/Boltmg/Welding
24 Rough/Topout
34 Rough Electric
44 Rough/Ducts/Dampers
Comments/Notices/Holds
Associated PCRs/CVs Original PC#
PCR05031 WITHDRAW I'ALOMAR AIRPORT BLDG 1 REVISE TRENCH DRAINS
PCR05043 ISSUED AIRPORI HANGAR BLDG-I PLUMBING REVISIONS
PCR05095 ISSUED PALOMAR AIRPORT HANGER BLDG I, M1SC REVISIONS DPLTA 5
PCR05119 ISSUED PALOMAR AIRPORT CNIR DrTERRED STAIR SUBMITT1AL BLDG I
Bl DO I DELTA 8 STAIR SUBMITTAL,
PALOMAR AIRPORT BLDG I I3FLTA 7 REVISIONS
PALOMAK AIRPORT CENI ER , CHANGE D1REC1IVL 11-1 DOOR ADD HRELI1C W1NC
PALOMAR AIRPORT BLDG I, WALL GLAZING
PCRoSlSO ISSUED
PCR05189 ISSUED
PCt«iJ5227 ISSUED
PCR06035 ISSUED
Inspection History
Date Description Act Insp
09/04/2008 17 Interior Lath/Drywall AP TP
08/29/2008 17 Interior Lath/Drywall CO MC
08/29/2008 24 Rough/Topout AP MC
08/11/2008 14 Frame/Steel/Bolting/Welding AP TP
08/11/2008 24 Rough/Topout CO TP
Comments
NOTICE OK TO TAPE LOWER RM
EXT GATE CODE 2 & 4 SIMULTANEOUSLY AND THEN 3
NEED ENG REV FOR TJIs, L90 SPEC & NEED WELD REPORT
NEED TEST
NOTICECITY OF CARLSBAD (760) 602-2700
BUILDING DEPARTMENT 1635 FARADAY AVENUE
PERMIT NO
DATE Y** **Z*f\ ^^ .' TIME
*'
LOCATION ° ~ "' ' ~
^ u
6
fe.rU ^; I
I • V
U i^ I
FOR INSPECTION CALL (760) 602-2725 RE-INSPECTION FEE DUE? . YES
L
FOR FURTHER INFORMATION, CONTACT _ ^
JA\PHONE
BUILDING INSPECTOR CODE ENFORCEMENT OFFICER
City of Carlsbad Bldg Inspection Request
For 08/29/2008
Permit* CB080846
Title PALOMAR AIRPORT-HANGER #7-
Description 585 SF TI-(335 SF MEZZANINE TO OFFICE.250 SF 1ST FLR
OFFICE)
Sub Type INDUST
Inspector Assignment TP
Type Tl
Job Address 2100 PALOMAR AIRPORT RD
Suite Lot 0
Location
OWNER COUNTY OF SAN DIEGO
Owner OPEN RANGE INC <LF> PALOMAR AIRPORT CENTER LLC
Remarks
Phone 6197783995
Inspector
Total Time
CD Description
17 Interior Lath/Drywall
24 Rough/Topout
Act Comments
Requested By MANNY
Entered By CHRISTINE
&V-a L&i^&tL
Comments/Notices/Holds
Associated PCRs/CVs Original PC#
PCR05031 WITHDRAW PALOMAR AIRPORT BI DC I REVISE TRCNCIf DRAINS
AIRPORT I IANGAR BLDG-1 PLUMBING REVISIONS
HALOMAR AIRPORT HANGER B! DO I M1SC REVISIONS DO 1 A S
PALOMAR AIRPORT CN I R DEFERRED S I AIR SUBMI I I IAL BI DC I
HI DG I DELTA 8 S 1 AIR SUBMITTAL
PAIOMARAIRPORFBIDG I DELIA? REVISIONS
PALOMAR A1RPORI CENTER CHANGE DIRECTIVE 1 1- 1 DOOR ADD HRR 1TP WINL
PALOMAR AIRPORT BLDG I, WALL 01 A7ING
Inspection History
Act Insp Comments
TP NEED ENG REV FOR TJIs L90 SPEC & NEED WELD REPORT
CO TP NEED TEST
TP
PD -
PCR05043 ISSUED
PCR05095 ISSUED
PCR05119 ISSUED
PCR05180 ISSUED
PCR05189 ISSUED
PCR05227 ISSUED
PCR06035 ISSUED
Date *. Description
08/11/2008 14 Frame/Steel/BoltingA/Veldmg AP
08/11/2008 24 Rough/Topout
08/08/2008 34 Rough Electric
07/16/2008 11 Ftg/Foundation/Piers
AP
AP
NOTICE
CITY OF CARLSBAD (760) 602-2700
BUILDING DEPARTMENT *'" " , 1635 FARADAY AVENUE
DATE Z»7 A\Jfr7 7^-"^ TIME
LOCATION -2[oo -p^uoKA^ AigJ^^T tz-t> 4-lfeig.
PERMIT NO
^S>^
FOR INSPECTION CALL (760) 602-2725 RE-INSPECTION FEE DUE? ' ' YES
FOR FURTHER INFORMATION, CONTACT _
PHONE
BUILDING INSPECTOR CODE ENFORCEMENT OFFICER
"A Quality Assurance Firm"
TESTING SERVICES
&• INSPECTION INC.
3030 Main Street
San Diego, CA 92113
(619) 234-9904
(619) 234-4931 Fax
VISUAL INSPECTION REPORT
Ll Name HVSGbRft? PALOMAR AIRPOKI
Projicl *\ddrii,i 2100 A 21SO P \LOMAR VIRPORTWAl HViS(,rRft7 Approv.il Numhir C B08-II846
Arduleu N/A HOKOWIIZ IAYI Projcu Number VV
Genera/ Contractor M.LC11L li\ C ON.VTKl'C J ION
Contrinor Doing Reported Work \\ I ION \L IKON tt ORkS
lull V\
Olliu \/\
lab Ru.c.ivinp&TLsnngCQiisU1 Mai I Samples N/\Other N/V
1VSPECIION MM L SAMPLING On iUAI'l OESCRIPIIOiN I^S1•L( I ION CHECK I 1ST
Field Shop CnnircteCMiiidirs PI ll
C oiKri.lt i ii S n Com Mix PM Clt. i
Stuiunnl Slid Grout S^imp Com Mix/PM Pl.KltlOMS
i \M.iM'iir\ Pnsnii All l SIA.S
M isoinv I31ot.k Groin Mix/l'Sl
Pile Morlii
Roofing H s Uohs 7/S 1 UK)III. A|J|<llCll
Specullx Aaph lit i Tuisum Applied
Soil-,Rnnfini!Skil
Boll Pull Oul Steel Fiii.pnii'1 Dnllul Hol>.»
PiC'.tres., Lomriie i SliLiiglli Bull i BKxk e AIIIUII
WaleipMuhni!OlIlLl I nil Hii
OS H I'D Ollii-i Mel il Deck
ObA Ollk.1 (.oiretiioii'.Cftniplele
OlIlLl I |HI\>
i. il Other Oilici
Li uch Plant Olhu
Inspection Date 07-21-08
INSPECT ED THE INSTALLA 1 ION OF AS TIM A325 HIGH STRENGTH BOL FS, INCI UDING BOI f HOLES AND F AYING
SURFACES FOR FRICTIOM TYPE CONNECTIONS AS NOTFD ON THF APPROVfD DRAWINGS
VERIFIED FASTENER TENSION BY TWIST OFF 'I YPE TENSION CONTROI METHOD
W16 v 26 BEAM TO TS 5 \ 5 \ ',* POS1 S- TOTAL OF 8-7/8' BOLTS
CERflUCVriOS Ol COMPIHNtE Ml of ilii. iipwiid iimk unkas oihLiu^L HUI«| cranphi-s wiih ijipintnl pi u
report only i-Overt ihe lonlions ot the milk nibpLi.ii.d inJ dues nul i-oiibiiiiiie einjiiiiDiiL opinion
laiioiii mil ifiplii il>L M.L>it>iiM.'li!ic!>iiil(liii(.<.ntks Thii
SI VM T\ L SCHLVGTR
CFR1 HIC \PFMIMBtR
INSI'I 'S SIGN \UIRf
£29 0 ^P /'rfrffiML.*,,^7f
NOTE Inspections based on A 4-hour minimum, actual tmu niter 4 hours 2 hour show up minimum lor jut) cancellations
double time on Sunda\
1 "V^-y^ve
(A 11 turn efleffeitivc on Saturda>s
SUBMII PhD 10 THE C11Y Of CARI SBAD/ NAIIONAI IRON WORKS
"A Quality Assurance Firm"
TESTING SERVICES
&• INSPECTION INC.
3030 Mam Street
San Diego, CA 92113
(619) 234-9904
(619) 234-4931 Fax
VISUAL INSPECTION REPORT
Project Name HANGLR #7 McCELLAN- PALOMAR AIRPORT
Project Address 2100 & 2150 PALOMAR AIRPORT WAV Approval Number CB08-0846
Archilid N/A Engineer HTK Project Number N/A
General Contractor KELCIILIN CONSTRUCTION1 Job Number N/A
Contractor Doing Reported Woik NATIONAL IRON WOUUS Other IN/A
Lab Receiving & 'I esling Conslr Mat I Samples N/A Other \/A
INSPECTION IMAT'L SAMPLING Q'l V MVPLDESCRIFHON INSPECTION CHECK LIST
held \ Shop Concrete Cylinders Reinforcinj. Steel Pl.in/Sp<:i.s
Concrete Mortar Samples Cone Mit/PSl Clearances
Structural Steel Grout Samples Cone Mix/PSl Positions
Ma^onrv Masonry Prisms All Thread Bolts Sizes
Fireproofin^Mdsonrv Block Grout Mix/PSI L.ips
Pile Driving Reinforcing Steel Morcar Ivpe/PSI Consolidation
Roofing Fireprootini;US Bolts Torque Applied
Specially Asphalt Concrete Electrode E-70T Tuiuun Applied
Soils Technician Roofing Sled A-500 Lpoxy
Bolt Pull-Out Steel Fireproof Drilled Holei
Prestress Concrete High Strength Bolts Units Block Corrective Action
Waterproofing Other Unit Brick
OSHPD Other Metal Deck
OSA Other Remf Tendons Corrections Complete
Mcclnnical Other Cpox)
Eli.cmcil Other aher
BdlJi Plant Other Other
Inspection Date 07-08-08
INSPECTED THE WELDING OF BEN F P[ ATE TOPE SADDLER ON (5) SQUARE TUBE 5 \ 5 \ V, COLUMNS PER DETAIL 8/ S-3 AND
I WO COLUMNS WITH ADDITIONAL SHEAR PL A I E CONNECTIONS PER DETAIL 3/ S-3 AND 13/ S-3 COMPLEI ED WELDS ARF IN
CONFORMANCE WITH DESIGN DRAWING AND ACCEPTED TO INCLUDE WELDING OF 5/8 ROUND WELDED STUDS ON EACH
COLUMN PCR DETAII 20/ S-3
CERl If1 IC'A'I ION OF COMF1 IANCE All of the reported work unless otherwise noted, complies \vitli apprjx^drflaas, specifications and ipplicable sections ot the building codes This
report onl\ coxcrs the locations of the work inspected and does not constitute engineering opinion or proiccl control / \
INSPLC TOR NAME Jt ^N DIAZ
CERl IFICATE NUMBER 190
NOTE Inspections based on a 4-hour minimum, actual time after 4 hours, 2 hour show up minimum for job cancellations Overtime effective on Saturdays,
double time on Sunday
SUBM11 rbD TO THF CITY Of CARLSBAD/ NATIONAI IRON WORKS
EsGil Corporation
In Partnership with government for (Building Safety
DATE June 26, 2008
JURISDICTION Carlsbad
PLAN CHECK NO 080846 SET III
PROJECT ADDRESS 2100 Palomar Airport Way
PROJECT NAME Office T.I. (Hangar # 7)
The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes
XI The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff
The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck
The check list transmitted herewith is for your information The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck
The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person
The applicant's copy of the check list has been sent to
Esgil Corporation staff did not advise the applicant that the plan check has been completed
Esgil Corporation staff did advise the applicant that the plan check has been completed
Person contacted Kris Telephone # 858/273-3889
Date contacted 6/26/08 (by Abe) Fax #
Mail Telephone Fax In Person .
Xi REMARKS Engineer of Record must/sign both sets of structural plans Applicant to carry the
approved set of plans to the city /Tfrf
By Abe Doliente Enclosures
Esgil Corporation
D GA D MB D EJ n PC 6/26/08
9320 Chesapeake Drive, Suite 208 ^ San Diego, California 92123 <fr (858)560-1468 ^ Fax (858) 560-1576
EsGil Corporation^ ••••.
In (Partnership with government for <Sui[ifing Safety
DATE June 24, 2O08 OAPPLICANT
JURISDICTION Carlsbad a PLAN REVIEWER
a FILE
PLAN CHECK NO 080846 SET II
PROJECT ADDRESS 2100 Palomar Airport Way
PROJECT NAME Office T.I. (Hangar # 7)
The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes
The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff
The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck
The check list transmitted herewith is for your information The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck
The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person
The applicant's copy of the check list has been sent to
Akropolys Interiors
3660 Clairemont Dr , Suite 10, San Diego, CA 92117
Esgil Corporation staff did not advise the applicant that the plan check has been completed
A! Esgil Corporation staff did advise the applicant that the plan check has been completed
Person contacted Akropolys -— C-H/U^1 Telephone # 858/273-3889
Date contacted £/x^/V/(by/^ Fax # - 3866
MB\V Telephone Fax y^ In Person
REMARKS
By Abe Doliente Enclosures
Esgil Corporation
D GA D MB [X] EJ D PC 6/17/08
9320 Chesapeake Drive, Suite 208 + San Diego. California 92123 * (858)560-1468 + Fax (858) 560-1576
Carlsbad 08O846
June 24, 2008
RECHECK CORRECTION LIST
JURISDICTION Carlsbad PLAN CHECK NO 080846
PROJECT ADDRESS 2100 Palomar Airport Way SET II
DATE PLAN RECEIVED BY DATE RECHECK COMPLETED
ESGIL CORPORATION 6/17/08 June 24, 2008
REVIEWED BY Abe Doliente
FOREWORD (PLEASE READ):
This plan review is limited to the technical requirements contained in the Building Code,
Plumbing Code, Mechanical Code, Electrical Code and state laws regulating energy
conservation, noise attenuation and disabled access This plan review is based on regulations
enforced by the Building Department You may have other corrections based on laws and
ordinances enforced by the Planning Department, Engineering Department or other
departments
The following items listed need clarification, modification or change All items must be satisfied
before the plans will be in conformance with the cited codes and regulations The approval of
the plans does not permit the violation of any state, county or city law
A Please make all corrections on the original tracings and submit two new complete sets of
prints to Esgil Corp ortothebldg dept of the juris
B To facilitate recheckmg, please identify, next to each item, the sheet of the plans upon
which each correction on this sheet has been made and return this sheet with the
revised plans
C The following items have not been resolved from the previous plan reviews The original
correction number has been given for your reference In case you did not keep a copy of
the prior correction list, we have enclosed those pages containing the outstanding
corrections Please contact me if you have any questions regarding these items
D Please indicate here if any changes have been made to the plans that are not a result of
corrections from this list If there are other changes, please briefly describe them and where
they are located on the plans Have changes been made not resulting from this list?
QYes QNo
Carlsbad 080846
June 24, 2008
Please make all corrections, as requested in the correction list Submit three new
complete sets of plans for commercial/industrial projects For expeditious processing,
corrected sets can be submitted in one of two ways
1 Deliver all corrected sets of plans and calculations/reports directly to the City of
Carlsbad Building Department, 1635 Faraday Ave , Carlsbad, CA 92008, (760) 602-2700
The City will route the plans to EsGil Corporation and the Carlsbad Planning, Engineering
and Fire Departments
2 Bring one corrected set of plans and calculations/reports to EsGil Corporation, 9320
Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-1468 Deliver all
remaining sets of plans and calculations/reports directly to the City of Carlsbad Building
Department for routing to their Planning, Engineering and Fire Departments
NOTE Plans that are submitted directly to EsGil Corporation only will not be reviewed by
the City Planning, Engineering and Fire Departments until review by EsGil Corporation is
complete
1 Each sheet of the plans must be signed by the person responsible for their preparation,
even though there are no structural changes California Business and Professions Code
2 Plans and calculations shall be signed by the California state licensed engineer or
architect where there are structural changes to existing buildings or structural additions
Please include the California license number, seal, date of license expiration and date
plans are signed California Business and Professions Code
7 Revise the sheet index sheet to show the drawings submitted There are two sheet M-2
shown
PLUMBING, MECHANICAL, ELECTRICAL, and ENERGY CORRECTIONS
PLAN REVIEWER: Eric Jensen
ELECTRICAL (2005 NATIONAL ELECTRICAL CODE)
PLUMBING (2006 UNIFORM PLUMBING CODE)
MECHANICAL (2006 UNIFORM MECHANICAL CODE)
ENERGY CONSERVATION
1 Include compliance with CBC 412 2 4 for the heating equipment Caution This Code
section is stringent, a careful review is warranted Provide a complying mechanical
design Design unchanged, applicant is discussing a waiver from this Code requirement
with the City
Note If you have any questions regarding this Electrical, Plumbing, Mechanical, and Energy
plan review list please contact Eric Jensen at (858) 560-1468 To speed the review process,
note on this list (or a copy) where the corrected items have been addressed on the plans
EsGil Corporation
In (Partnership with government for <Buifd*ing Safety
DATE May 20, 2008 alAEEUCANT
JURISDICTION Carlsbad O~PEANREVIEWER
a FILE
PLAN CHECK NO 080846 SET I
PROJECT ADDRESS 2100 Palomar Airport Way
PROJECT NAME Office T.I. (Hangar # 7)
The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes
The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff
The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck
XI The check list transmitted herewith is for your information The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck
The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person
XI The applicant's copy of the check list has been sent to
Akropolys Interiors
3660 Clairemont Dr, Suite 10, San Diego, CA 92117
Esgil Corporation staff did not advise the applicant that the plan check has been completed
XI Esgil Corporation staff did advise the applicant that the plan check has been completed
Person contacted/ Akrppolys 0n/U^ Telephone # 858/273-3889
Date contactec^/^V^b Fax # - 3866
vMail Telephone v Fa*v \^1n Person
REMARKS {CckJMfj
By Abe Doliente Enclosures
Esgil Corporation
D GA D MB [X] EJ D PC 5/12/08
9320 Chesapeake Dme, Suite 208 4 San Diego, California 92123 + (858)560-1468 + Fax (858) 560-1576
Carlsbad O80846
May 2O, 2008
PLAN REVIEW CORRECTION LIST
TENANT IMPROVEMENTS
PLAN CHECK NO O80846
OCCUPANCY B
TYPE OF CONSTRUCTION II-1HR
ALLOWABLE FLOOR AREA
SPRINKLERS'?
REMARKS
DATE PLANS RECEIVED BY
JURISDICTION
DATE INITIAL PLAN REVIEW
COMPLETED May 20, 20O8
JURISDICTION Carlsbad
USE Offices
ACTUAL AREA 658 SF (T I only)
STORIES 2
HEIGHT
OCCUPANT LOAD 7
DATE PLANS RECEIVED BY
ESGIL CORPORATION 5/12/08
PLAN REVIEWER Abe Doliente
FOREWORD (PLEASE READ)-
This plan review is limited to the technical requirements contained in the International Building
Code, Uniform Plumbing Code, Uniform Mechanical Code, National Electrical Code and state
laws regulating energy conservation, noise attenuation and access for the disabled This plan
review is based on regulations enforced by the Building Department You may have other
corrections based on laws and ordinances enforced by the Planning Department, Engineering
Department, Fire Department or other departments Clearance from those departments may be
required prior to the issuance of a building permit
Code sections cited are based on the 2007 CBC, which adopts the 2006 IBC
The following items listed need clarification, modification or change All items must be satisfied
before the plans will be in conformance with the cited codes and regulations Per Sec 105 4 of
the 2006 International Building Code, the approval of the plans does not permit the violation of
any state, county or city law
To speed up the recheck process, please note on this list (or a copy) where each
correction item has been addressed, i.e . plan sheet number, specification section, etc.
Be sure to enclose the marked up list when you submit the revised plans
Carlsbad O8O846
May 20, 2O08
Please make all corrections, as requested in the correction list Submit three new
complete sets of plans for commercial/industrial projects For expeditious
processing, corrected sets can be submitted in one of two ways
1 Deliver all corrected sets of plans and calculations/reports directly to the City of
Carlsbad Building Department, 1635 Faraday Ave , Carlsbad, CA 92008, (760)
602-2700 The City will route the plans to EsGil Corporation and the Carlsbad
Planning, Engineering and Fire Departments
2 Bring one corrected set of plans and calculations/reports to EsGil Corporation,
9320 Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-1468
Deliver all remaining sets of plans and calculations/reports directly to the City of
Carlsbad Building Department for routing to their Planning, Engineering and Fire
Departments
NOTE Plans that are submitted directly to EsGil Corporation only will not be
reviewed by the City Planning, Engineering and Fire Departments until review by
EsGil Corporation is complete
• PLANS
1 Each sheet of the plans must be signed by the person responsible for their
preparation, even though there are no structural changes California Business
and Professions Code
2 Plans and calculations shall be signed by the California state licensed engineer
or architect where there are structural changes to existing buildings or structural
additions Please include the California license number, seal, date of license
expiration and date plans are signed California Business and Professions
Code
3 Provide a Building Code Data Legend on the Title Sheet Include the following
code information for each building proposed
4 Occupancy Classification(s) B/S-2
4 For Mixed Occupancy Buildings, state whether the "nonseparated" or
"separated" option was chosen from Section 508 3
* Description of Use Offices (T I portion only)
4 Type of Construction II-A
* Sprinklers Yes
* Stories 1 + M
4 Height
* Floor Area 674 SF, T I only
4 Occupant Load. 7 (T I only)
4 Provide a statement on the Title Sheet of the plans, stating that this project shall
comply with the 2007 California Building Code, which adopts the 2006 IBC, 2006
UMC, 2006 UPC and the 2005 NEC
Carlsbad O80846
May 2O, 2008
• STAIRWAYS
5 Handrails (Sections 1012 and 1009 10)
a) Handrails are required on each side of stairways
b) Handrails and extensions shall be 34" to 38" above nosing of treads and
be continuous Additionally, the open sides of stairs shall be
provided with 42" high guards, per Section 1013
c) The handgrip portion of all handrails shall be not less than 1-1/4 inches
nor more than 2 inches in cross-sectional dimension If the handrail is not
circular, it shall have a perimeter dimension of at least 4" and not greater
than Q 25" with a maximum cross-section dimension of 2 25 inches
d) Handrails shall be continuous, without interruption by newel posts or other
obstructions
e) Handrails shall extend 12" beyond the top riser and continue to slope for
the depth of one tread beyond the bottom riser
f) Ends of handrails shall be returned to a wall, guard or the walking surface
• ACCESSIBILITY
Q Provide notes and details on the plans to show compliance with the enclosed
"Disabled Access" Review List
• ADDITIONAL
7 Revise the sheet index sheet to show the drawings submitted
8 Please see the following corrections for electrical, energy, plumbing and
mechanical
9 To speed up the review process, note on this list (or a copy) where each
correction item has been addressed, i e , plan sheet, note or detail number,
calculation page, etc
10 Please indicate here if any changes have been made to the plans that are not a
result of corrections from this list If there are other changes, please briefly
describe them and where they are located in the plans
Have changes been made to the plans not resulting from this correction
list? Please indicate
Q Yes a No
- Carlsbad 080846
May 20, 2O08
11 The jurisdiction has contracted with Esgil Corporation located at 9320
Chesapeake Drive, Suite 208, San Diego, California 92123, telephone number of
858/560-1468, to perform the plan review for your project If you have any
questions regarding these plan review items, please contact Abe Doliente at
Esgil Corporation Thank you
PLUMBING, MECHANICAL, ELECTRICAL, and ENERGY CORRECTIONS
PLAN REVIEWER: Eric Jensen
ELECTRICAL (2005 NATIONAL ELECTRICAL CODE)
PLUMBING (2006 UNIFORM PLUMBING CODE)
MECHANICAL (2006 UNIFORM MECHANICAL CODE)
ENERGY CONSERVATION
1 Provide electrical plans
2 Detail the indirect receptor location for the condensate waste design
3 Include compliance with CBC 412 2 4 for the heating equipment Caution This
Code section is stringent, a careful review is warranted Provide a complying
mechanical design
4 Provide plans, calculations and worksheets to show compliance with current
energy standards (The LTG is missing, the submitted energy plans do not
describe the correct square footage)
5 On the plans clearly show the wall and roof insulation locations, thickness, and
R-values, as per the energy design (Include both existing and new areas
6 Provide automatic shut-off controls for lighting as per Title 24, Part 6, Section
131 (d)
7 Provide the bi-level lighting controls as per Title 24, Part 6, Section 131 (b)
Note If you have any questions regarding this Electrical, Plumbing, Mechanical, and
Energy plan review list please contact Eric Jensen at (858) 560-1468 To speed the
review process, note on this list (or a copy) where the corrected items have been
addressed on the plans
Carlsbad O8O846
May 20, 2008
DISABLED ACCESS REVIEW LIST
DEPARTMENT OF STATE ARCHITECT
TITLE 24
The following disabled access items are taken from the 2007 edition of California Building
Code, Title 24 Per Section 1091, all publicly and privately funded public
accommodations and commercial facilities shall be accessible to persons with disabilities
NOTE All Figures and Tables referenced in this checklist are printed in the California
Building Code, Title 24
• REMODELS. ADDITIONS AND REPAIRS
When alterations, structural repairs or modifications or additions are made to an
existing building, that building, or portion of the building affected, is required to
comply with all of the requirements for new buildings, per Section 1134B 2 These
requirements apply as follows
a) The area of specific alteration, repair or addition must comply as "new"
construction
b) A primary entrance to the building and the primary path of travel to the
altered area, must be shown to comply with all accessibility features
c) Existing sanitary facilities that serve the remodeled area must be shown to
comply with all accessibility features
d) Existing drinking fountains (if any) must be shown to comply with all
accessibility features
e) Existing public telephones (if any) must be shown to comply with all
accessibility features
•Carlsbad O8O846
May 20, 2O08
VALUATION AND PLAN CHECK FEE
JURISDICTION Carlsbad PLAN CHECK NO 080846
PREPARED BY Abe Doliente DATE May 20, 2008
BUILDING ADDRESS 2100 Palomar Airport Way
BUILDING OCCUPANCY B TYPE OF CONSTRUCTION II-A
BUILDING
PORTION
Office T 1
Air Conditioning
Fire Sprinklers
TOTAL VALUE
Jurisdiction Code
Rlrin Pprmir FPP hv Ordina
AREA
( Sq Ft )
674
cb
Valuation
Multiplier
3437
By Ordinance
..... i
nrp ^ !
Reg
Mod
VALUE ($)
23,165
23,165
$226 35
Plan Check Fee by Ordinance
Type of Review \^
] Repetitive Fee
~^Tj Repeats
Comments
Complete Review
D Other
r-1 Hourly
Structural Only
Hour*
Esgil Plan Review Fee
$147 13
$12676
Sheet 1 of 1
macvalue doc
Carlsbad Fire Department BUILDING DEFT
Plan Review Requirements Category TI, INDUS!
Date of Report 05-16-2008 Reviewed by
Name
Address
KELCHLIN CONSTRUCTION
12225 WORLD TRADE DR
SAN DIEGO CA 92128
Permit # CB080846
Job Name PALOMAR AIRPORT-HANGER #7-ADD
Job Address 2100 PALOMAR AIRPORT RD CBAD
IWWMM'I'lS'ETU"1'"' Ilfe^i11ffi^6inta?e*subrnitted for review is incomplete At this time, this office cannot
adequately conduct a review to determine compliance with the applicable codes and/or standards Please review
carefully all comments attached Please resubmit the necessary plans and/or specifications, with changes "clouded",
to this office for review and approval
Conditions:
roNoooi
IET] APPROVED^
THIS PROJECT HAS BEEN REVIEWED AND APPROVED FOR THE PURPOSES OF ISSUANCE OF
BUILDING PERMIT
THIS APPROVAL IS SUBJECT TO FIELD INSPECTION AND REQUIRED TEST, NOTATIONS HEREON,
CONDITIONS IN
CORRESPONDENCE AND CONFORMANCE WITH ALL APPLICABLE REGULATIONS
THIS APPROVAL SHALL NOT BE HELD TO PERMIT OR APPROVE THE VIOLATION OF ANY LAW
Entry 05/16/2008 By GR Action AP
PLANNING/ENGINEERING APPROVALS
PERMIT NUMBER CB DATE 5- / a- o <e>
ADDRESS
RESIDENTIAL
RESIDENTIAL ADDITION MINOR
« $10.000.00)
IMPROVEMENT
PLAZA CAMINO REAL
CARLSBAD COMPANY STORES
VILLAGE FAIRE
COMPLETE OFFICE BUILDING
OTHER
PLANNER
ENGINES
DATES
DATE S
DOcs/MlsformVPIannmg Engineering Approvals
ENGINEERING DEPARTMENT
FEE CALCULATION WORKSHEET
n Estimate based on unconfirmed information from applicant / >D Calculation based on building plancheck plan submittal • ' -. ' ... \
1
Address
Prepared by
Bldg Permit No
Checked by Date
EDU CALCULATIONS List types and square footages-for all uses
•* IX ——**- N ' -. '' . " r '
Types of Use
Types of Use Sq Ft /Units
EDU's
EDU's
APT CALCULATIONS tList types and square footages for all uses
Types of Use
Types of Use
ADT's \
ADT's
FEES REQUIRED
WITHIN CFD D YES (no bridge & thoroughfare fee in District #1, reduced Traffic Impact Fee) D NO
D 1 PARK-IN-LIEU FEE
FEE/UNIT
PARK AREA & #
NO UNITS
D 2 TRAFFIC IMPACT FEE
ADT's/UNITS / /
D 3 BRIDGE AND THOROUGHFARE FEE (DIST #1
ADT's/UNITS X " FEE/ADT
DIST #2
D 4 FACILITIES MANAGEMENT FEE
UNIT/SQ FT
D 5 SEWER FEE
EDU's .
BENEFIT AREA
EDU's
ZONE./
X FEE/SO. FT /UNIT
D 6 SEWER LATERAL ($2,500)
D 7 DRAINAGE FEES PLDA_
ACRES
X FEE/EDU
HIGH
= $
/LOW
X FEE/AC -$
D 8 POTABLE WATER FEES
UNITS CODE CONNECTION FEE METER FEE SDCWA FEE IRRIGATION
WordVDocs\Mlsforms\Fee Calculation Worksheet
1 of 2
X
.7/
7£ O^L^J-
. I Ul \lflll il_w iiv «. „
3PERABLE
ATING BARS.
WARE
>ENING HARDWARE.h252)
^S (762 mm)
VIDE A CLEAR.
)NED AT AN ANGLE
ICHNG SHALL HAVE
WHEELCHAIR
FRAME DOORS ARE
ISH SIDE
RVING AN OCCUPANT
ING DOORS WITHOUT
NGING, SLIDING AND
15-
) A 30-POUND
IECTED TO A 15-POUNO
ING AND UNLOADING
12 INCHES (305MM)
JACENT ACCESS ABLE.
CT, I HAVE
M(S) SERVING
£QUIREMENTS
5) IS/ARE NOT
. REQUIRE
ELEVATIONS TOR
HE/SHE SHALL REQUIRE' COMPLETE, DETAILED PLANS CLEARLY SHOWING ALL EXISITNG NON COMPLYING CONDITION
AND THE PROPOSED MODIFICATIONS TO MEET CURRENT ACCESSIBILITY PROVISIONS AFFECTED BY THE REMODEL
(including site plan, floor plans, details, etc) THE PLANS MUST BE STAMPED BY THE FIELD INSPECTOR AND
RESUBMITTED TO THE BUILDING DEVELOPMENT REVIEW DIVISION
TYPE OF CONS'
TENANT BUILDII
SCOPE OF '
BUILDING 1
TYPE OF CONSTRUCTION. TYPE II ONE-HOUR
HANGAR GROUP.
NET GROUP S, DIVISION 5 HANGAR AREA:
NET TOP LEVEL OFFICE AREA: GROUP B
JET CENTER GROUND LEVEL AREA. GROUP B
JET CENTER TOP LEVEL AREA. GROUP B
STAIRS/CORRIDORS. ELEVATOR MACHINE & ELECTRICAL
ROOMS:
BUILDING I TOTAL AREA-
SUB TOTAL S
SUB TOTAL B
TOTAL BUILDING -
505.2 UNLIMITED AREA.
THE AREA OF ANY ONE-OR TWO-STORY BUILDING OF
GROUPS B; F, DIVISION 1 OR 2; M; S, DIVISION 1,2,3,4 OR
5; AND H, DIVISION 5 OCCUPANCIES SHALL NOT BE
LIMITED IF THE BUILDING IS PROVIDED WITH AN APPROVED
AUTOMATIC SPRINKLER SYSTEM THROUGHOUT AS
SPECIFIED IN CHAPTER 9, AND ENTIRELY SURROUNDED
AND AJOINED BY PUBLIC WAYS OR YARDS NOT LESS
THAN 60 FEET (18 288 MM) IN WIDTH.
504.3 ALLOWABLE FLOOR AREA MIXED OCCUPANCIES.
WHEN A BUILDING HOUSES MORE THAN ONE OCCUPANCY,
THE AREA OF THE BUILDING SHALL BE SUCH THAT THE
SUM OF THE RATIOS OF THE ACTUAL AREA FOR EACH
SEPERATE OCCUPANCY DIVIDED BY THE TOTAL ALLOWABLE
AREA FOR EACH SEPERATE OCCUPANCY SHALL NOT
EXCEED ONE.
STORIES ALLOWABLE TABLE 58, CBC
TYPE II - 1 HOUR - 18,000 SQ. FT. ALLOWABLE
505.2 UNLIMITED AREA
THE AREA OF ANY ONE-OR TWO-STORY BUILDING
5 OCCUPANCIES
AUTOM^ SPR.NKLER SYSTB
N CHAPTER 9, AND ENTIRELY SURROUNDED Af
PUBLIC WAYS OR YARDS NOT LESS THAN 60 FEET (18 288 I
HANGAR AREA: 108,328 S.F.
OFFICE, SUPPORT AREA: 62,172 S.F.
108.328 , 62.172 < -,
INFINITY INFINITY
NOTE-
A.YARDS USED FOR AREA INCREASES SHALL BE
PERMANENTLY MAINTAINED
THEY ARE FAA DEDICATED TAXI LANES ON 3 SIDES AND
RAMP AREA ON FOURTH SIDE.
THERE ARE NO CLASS I, II OR III-A LIQUIDS USED IN HANGAR F
THEREFOR MECHANICAL EXHAUST IS NOT REQUIRED
County of San Oiego Airports
Tenant Improvement Plan Approval
Approved for planning purposes only. All applicable regulatory requirements must
be met at lessee's expense by lessee including, but not limited to, building permits
required by the permitting authority. All uses must be consistent with Federal
Aviation Administration (FAA) rules, regulations and guidance documents. There
will be no residential units, including crew quarters or caretaker residences,
without prior written approval of the FAA
Airport Manager
Airport Engineer.
Approved urpons/DiBfecTor
\J
WO SCALE
14268 Dantelaon Street
Suite 200
Poway, CA 92064
Phone 868^79-8989
Fax 858-678-8969
n 2350 So Jones, #101
Las Vegas. NV 89146
Phone 702-506-8225
fax. 702-215-5801
,
'
HOROWITZ
KUSHKAI
STRUCTURAL ENGINEFUS
FACSIMILE TRANSMITTAL SHEET
T°
COMPANY DATE:
PHONE NUMBER TOTAL NO 'OF PAGES INCLUDING COVER-
^ENCEPAX NUMBER.SENDER'S REFERENCE NUMBER
RE />fr/P-fo^T
REFERENCE NUMBER:
O URGENT a FOR REVIEW D PLHASE COMMENT D PLEASE REPLY D PLEASE RECYCLE
NOTES/COMMENTS,
/
Structural Engineering
tvid WdTT £T 8002 62 6S686i98S8- ON Xdd Sd33NiaN3 n.X1H1
05/19/2flO« 09:26 FAX 760 434 3373 TRUS JOIST @001/003
Southwest Residential Office
eve
by Weyerhaeuser
2424 Vteta Way, Suite 315, Ooaanslde.CA 92054 trt: 760-434-3374 fax. 760-434-3373
Tr*n*ml3*loa
Number of pages (including cover): 3 Date <>-V\'
From:
o.
\t
Name
\\i\tA
Company Fax Number
Message-
This facsimile may contain certain confidential Information that is not intended for distribution to anyone
other than the intended recipient listed above. In the event the intended recipient or an employee
responsible for delivering this facsimile to the intended recipient Is unavailable, pJeaee do not distribute
this facsimile, notify us immediately by telephone, and return this facsimile by mail. Thank you
t'/Sd WdTT'ZI 8002 62 ',6ny 6S686i98S8' 'ON Xttd n.ionais XLH-
05^19/2008 09.26 KA1 760 434 3373 TRUS JOIST.
eve
fey WgyirhMuttl
il 002/003
Specified pat
11 7/8" TJH8/L90 @ 16" o/c
PRODUCT MEETS OR EXCEEDS THE SET DESIGN
CONTROLS FOR THE APPLICATION AND LOADS LISTED
-w-Pro0u« 0*flram )• conceptual.
Analysis later a Jett Member
Primary Load Group -Offtea BUgs • Offices (psf). SO 0 Live* 100 % duration, 15.0 Dead, 20 0 Partition
SUPPORTS:
Input Bearing Vertical Reaotbna (Ibs)
Width Ungth UvWDwrf/Upim/Total
piy
1
2
HAtu
1
2
Plata on steal beam $.80* Hanger 667/467/0/1143 . »
Prate on steal beam 3.50- Hanger 067/467/0/1133'
NdER$: $lmD8on Strano-TleA Connectora
ipport Model
Top Mount Hanger ITT41 1 88
Top Mount Hanger ITT41 1 .66
Slope Skew Reverse
0/12 0 N/A
0/12 0 N/A
Depth Naflng
Depth
11.86" 1-50'
DvtMl Other
Tcp Mount Harder Mono
Top Mount Hangar None
Top Flange Top Range Support wood
Ottoi 8Jop» SpeekM
No 0 Douglas Fir
No 0 Dowojaa Fir
-N*D9 Tor Support 1 Faca2-N10, Top 4-N10. Member 2HM10
-NaHnp for Support 2 F«c« 2*110, Top 4-N10, Member. 2-N10
DESIGN CONTROLS;
Maximum Contral Meault
Shew (los) HOO
Vertical Reaction (»») 1100
Moment (Ft-Lba) 6341
UvaUMdDefl(ln)
Tofel Load Daft (In)
TJPro
-1100
1100 180S
S341 9606
0-380 0X00
0596 0071
42 30
Peesed($7%) Rt end Span 1 under Floor loading
Pas«ed(6B%) Bearing 2 under Floor loading
Passed (56%) MID $pm 1 under Floor loading
Passed (L/668) MID Span 1 under Floor reading
Passed (L/392) MID Scan 1 under Floor Bating
pawed Spani
-Deflection Criteria STANDARD(LL'0 400*,TL:U240).
-Detection analyoie le based on eompoelte action with single layer Of ift02* Panels (20" Span Rating) GLUED & NAILED wood decking
-Bracingtlu) All compression adgm (top and bottom) must be braced at ffB" ote unlees detalod otherwls& Proper attaortmem and poetttonlng of lateral bracing
to required to acwew member siri>ity
•2000 (bs concentrated toad rtiquremerrts for standard riOJWWldarrtW ftoora haw been ooneWered lor reaction and anear.
frfrfre RATING 8YSTBM , :
•The TJ-Pro RBHPg System value pronldee addtttonal ftoor performanoa Information and IB based on a GLUED A NAILED 1B/32" Panda (20° Span Rating)
decking The controlling span is supported by beams, Additional consUaratlons for this rating Include: Ceding - Mono. A structured anriyslB of the deck has not
been panrarned by the program. Comparison Value. 2.24 | • , ' :
PROJECT INFORMATION:
Pakmar Akport Hanger #7
Carlsbad, Ca
QP6RATOR INFORMATION:
|aykM I
ILevel
Ste.216
Phone 760-434-3374
Fax 7604344373
. <t iOOl by lL«vcl», rgdaral Nay,
T.TTD ma i^-Bt*aa> AC* «gi«t<u
«•* +ii*V,t*^ uv> rj-I>i.i« n
3tronj-Iid* Connectors »8 •Credgwrk at Slnpiua Stroiu|-fl>
8002 6SS86A98S8- 'ON Xbd
OS/19/2008 09-2? FAX 760 434 3373 TRTTS JOIST Bl 003/00 J
eve SubBbtutadjorst
117/80TJ»5eO@16"o/c
THIS PRODUCT MEETS OR EXCEEDS THE SET DESIGN
CONTROLS FOR THE APPLICATION AND LOADS LISTED
-w-
LOADS;
Analysis to for a Jabrt Member
Primary 1^ Group-Offtoe Bides-OW«w(p8i) SO OUwst 100% duration, 180 Dead, 20 OPartlbon
SUPPORTS;
Input
Width Length
1 Plate on steel beta* 350" Hanger
2 Plaieon tttel beam 300" Hanger
Verticil Reactions (Ibo)
UvefltoadAJpUftrTotal
667/407/0/1133
607/467/0/1133
pty Depot
Depth
1 11-88" 1.50"
1 11.68" 1BO"
Other
Top Mount Hanger Nona
Top Mount Hanger None
MANGBR9: Sir i Stte I.TI4BC
Support
1
2
Modal
tgnntstftfa;
Slop*
Top Mount Hanger nT411 96 0/1?
Top Mount Hanger ITT411.8B 0/12
0
0
Reverse Tep Flange Top Flange Support Wood
Ftangaa Offset Slope Spades
N/A No 0 DougtosFfr
N/A No 0 ' Dough* Fir
-NrtUng for Support 1 Face. 2-N10, Top-WHO .Member 2-N10
^Idllnc for Support 2- Paoa-2-N10, Top 4»N10 .Member 2-N10
PBaifiN COKTTRQL8.
Shear <M)
vertical Reaction (Da)
MomaK(Fl-U»)
Uv» Load Deft (In)
TOW Load Dtfl (In)
TJPro
MMbnum Dnlgn
1100 -1100
1100 1100 '
6341 0941
0.345
0588
42
Central Reauft
20SO Passed (64%)
1725 Passed (64%)
9500 Passed (86%)
0.400 Pae$ed(U67ti)
0571 Pawed (L/338)
30 Passed
Location
Rt end Span 1 under Floor loading
Bearing 2 under Ptoor loading
MID Span 1 under Floor loading
MID Span 1 under Floor loading
MID Span 1 under Floor loading
Spanl
-Deflection Criteria 5TANOARD{U.:0.400",TL:U240).
-Deflection analysis n based on composite action with slnpje layer of 19/32" Panels (20* Span Rating) GLUED A NAILED wood decking
-Biaolng(U): All compression aogea (top and bottom) must be braced at ff 6" ofc unless deWW otherwise. Proper attachment and positioning of lateral bracing
a required to achieve member stability
-20Wibsc<weernr8tedloadi^uremartef<*rt
TJ-Pro RATING SYSTEM
-The TJ-Pro Rating System value provides additional floor performance Information and b based on a GLUED & NAILED 1B/32* Panels (20' Span Rating)
decking The controlling span Is siaaported by beams Addttana) conakterauon* for this rating Include, Ceiling -None A structural analysis ortrw deck ru» not
been performed by the program. Comparison Value 2.2
PROJECT INFORMATION:
Patomar Airport Hanger #7
Can«bad,C« ;
OPERATOR fNFQRjMf TfON:
jaylove j
tt-BWEj |
300 carisead village dr
Ste.216 :
cartebad, CA 92006 j
Phona. 760-434^374
Fax . 760-434-3373
jay.lovBQweyBrrHBuaer.com
CoiwitfDt » 2007 by ll«v»l», fodorol Nay, Ml.
TJIO (aid TJ-t)ooa» m reoiaund uadmrkn at ILovoi*
• T Joiot™, Pro- and M-Hu- aia tzad<B&Tkii at
nn?ctoro is A rc Itnnq-Tla
t'/t'd WdTT'ST 8002 62 6S686i98S8' ON XUJ
STRUCTURAL CALCULATIONS
PROJECT 7Aiovi Kg, At mtrtf KUSHKAKI
STRUCTURAL ENG|NEERS
DESIGM ASSUMPTIONS
CONCR.ETE STRENGTH AT TWENTY EIGHT DAYS
MASON RV GRADE "N" CONCRETE BLOCK F ' M =
MORTAR TYPES 1,800 PSI
GROUT: 2000 PSI
REIN FORCING STEEL A-615
STRUCTURAL STEEL A-36
LUMBER DOUGLAS FIR-LARCH
JOISTS
BEAMS AND POSTS
STUDS
SEISMIC FORCE
GRADE 40
GRADE 60
#4 AND LESS (U O N )
#5 AND LARGER
.PSI
PSI
#2
#2
STUD OR BETTER
REPORT BY
WIND FORCE
DESIGN LOADS
ROOF DEAD LOAD
SLOPING
ROOFING
PLYWOOD
JOISTS
INSUL &CLG
MISC
TOTAL =
ROOF LIVE LOAD
SLOPING
FLAT
REPORT NO SOIL PRESSURE
FLAT
FLOOR DEAD LOAD
INT
FLOORING
PLYWOOD
JOISTS
INSUL &CLG
MISC
TOTAL =/•r
FLOOR LIVE LOAD
INTERIOR
BALCONY
EXIT WALKWAY
EXT
WALL DEAD LOAD
INTERIOR
EXTERIOR
10PSF
16PSF
PSF
'60 PSF (U ON)
100 PSF
These calculations are limited only to the items included herein, selected by the client and do not imply approval of any other portion
of the structure by this office These calculations are not valid if altered in any way, or not accompanied by a wet stamp and
signature of the Engineer of Record
Job No Designed By
(&
Date
S// //) 9i
- (\
IP-
--. Z is
Conterminous 48 States
2006 International Building Code
Latitude = 33 1
Longitude = -11 7 25
Spectral Response Accelerations Ss and S1
Ss and S1 = Mapped Spectral Acceleration Values
Site Class B - Fa = 1 0 ,Fv = 1 0
Data are based on a 0 01 deg grid spacing
Period Sa
(sec) (g)
02 1 1 17 (Ss, Site Class B)
10 0421(81 .Site Class B)
Conterminous 48 States
2006 International Building Code
Latitude = 33 1
Longitude = -11 7 25
Spectral Response Accelerations SMs and SM1
SMs = FaSs and SM1 = FvS1
Site Class D - Fa = 1 053 ,Fv = 1 579
Period Sa
(sec) (g)
02 1 1 76 (SMs, Site Class D)
10 0 665 (SM1, Site Class D)
Conterminous 48 States
2006 International Building Code
Latitude = 33 1
Longitude = -117 25
SDs = 2/3 x SMs and SD1 = 2/3 x SM1
Site Class D - Fa = 1 053 ,Fv = 1 579
Period Sa
(sec) (g)
02 0 784 (SDs, Site Class D)
10 0 443 (SD1, Site Class D)
TS -
TS
< 3
*f&vr-} fj^