HomeMy WebLinkAbout2101 COSTA DEL MAR RD; ; CB023231; Permit12-09-2002
City of Carlsbad
1635 Faraday Av Carlsbad, CA 92008
Commercial/Industrial Permit Permit No
Building Inspection Request Line (760) 602-2725
CB023231
Job Address
Permit Type
Parcel No
Valuation
Occupancy Group
Project Title
2101 COSTA DEL MAR RD CBAD
Tl Sub Type
2152101800 Lot*
$71,100 00 Construction Type
Reference #
LACOSTA RESORT 2370SF Tl
MARKET PLACE-ASSEMBLY TO RETAIL STORE AREA
COMM
0
NEW
Applicant
K S L LA COSTA RESORT CORP
50 905 AVENIDA BERMUDA
LA QUINTA CA 92253
Status ISSUED
Applied 10/25/2002
Entered By SB
Plan Approved 12/09/2002
Issued 12/09/2002
Inspect Area
Owner
K S L LA COSTA RESORT CORPJQ3& 12/09/02 0002 01
50 905 AVENIDA BERMUDA
LA QUINTA CA 92253
02
578=69
Total Fees $863 88 Total Payments To Date $285 19 Balance Due $578 69
Building Permit
Add'l Building Permit Fee
Plan Check
Add'l Plan Check Fee
Plan Check Discount
Strong Motion Fee
Park Fee
LFM Fee
Bridge Fee
BTD #2 Fee
BTD #3 Fee
Renewal Fee
Add'l Renewal Fee
Other Building Fee
Pot Water Con Fee
Meter Size
Add'l Pot Water Con Fee
Reel Water Con Fee
$438 76
$000
$28519
$000
$000
$1493
$000
$000
$000
$000
$000
$000
$000
$000
$000
$000
$000
Meter Size
Add'l Reel Water Con Fee
Meter Fee
SDCWA Fee
CFD Payoff Fee
PFF
PFF (CFD Fund)
License Tax
License Tax (CFD Fund)
Traffic Impact Fee
Traffic Impact (CFD Fund)
PLUMBING TOTAL
ELECTRICAL TOTAL
MECHANICAL TOTAL
Master Drainage fee
Sewer Fee
Redev Parking Fee
Additional Fees
TOTAL PERMIT FEES
$000
$000
$000
$000
$000
$000
$000
$000
$000
$000
$41 00
$6000
$2400
$000
$000
$000
$000
$863 88
Inspector
FINAL APPROVAL
Date A~ » - I ?Clearance
NOTICE Please take NOTICE that approval of your project includes the Imposition of fees dedications, reservations or other exactions hereafter collectively
referred to as "fees/exactions You have 90 days from the date this permit was issued to protest imposition of these fees/exactions If you protest them you must
follow the protest procedures set forth in Government Code Section 66020(a) and file the protest and any other required information with the City Manager for
processing in accordance with Carlsbad Municipal Code Section 3 32 030 Failure to timely follow that procedure will bar any subsequent legal action to attack
review set aside void or annul their imposition
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection fees and capacity
changes, nor planning zoning grading or other similar application processing or service fees in connection with this project NOR DOES IT APPLY to any
fees/exactions of which you have previously been given a NOTICE similar to this, or as to which the statute of limitations has previously otherwise expired
PERMIT APPLICATION
CITY OF CARLSBAD BUILDING DEPARTMENT
1635 Faraday Ave , Carlsbad, CA 92008
PROJECT INFORMATION
FOR OFFICE USE ONLY
PLAN CHECK NO
EST VAL ~7I}
Plan Ck Deposit
Validated B;
GF"285.19
ONTACT PERSON (ifWferent from applic
NameJ Address fifty
"3" APPLICANT D Contractor ; QApnt for Contractor Q Owner 10sAgent for Owners**;
State/Zip Telephone ff Pax tt
Name 'Address City State/Zip Telephone tt
(State/Zip Telephone #NamS * Address " " I City
5 "CONTRACTOR COMPANY NAME 17 3" it :4
(Sec 7031 5 Business and Professions Code Any City or County which requires a permit to construct alter improve demolish or repair any structure prior to its
issuance also requires the applicant for such permit to file a signed statement that he is licensed pursuant to the provisions of the Contractor s License Law
[Chapter 9 commending with Section 7000 of Division 3 of the Business and Professions Code] or that he is exempt therefrom and the basis for the alleged
exemption Any violation of Section 7031 5 by any applicant for a permit subjects the applicant to a civil penalty of not more than five hundred dollars [$5001)
Name
State License #
Address
License Class
City State/Zip
City Business License #
Telephone
Designer Name Address City State/Zip Telephone
State License #
6 WORKERS COMPENSATION , , .,, ™?" 3*4.- "':::"": :i:.:*W ""•-•' ~" 5y; '""
Workers Compensation Declaration I hereby affirm under penalty of perjury one of the following declarations
l~l I have and will maintain a certificate of consent to self insure for workers compensation as provided by Section 3700 of the Labor Code for the performance
of the work for which this permit is issued
Q I have and will maintain workers compensation as required by Section 3700 of the Labor Codf for the performance of the work for which this permit is
issued My worker s compensation insurance earner and policy number are
Insurance Company Policy No Expiration Date
(THIS SECTION NEED NOT BE COMPLETED IF THE PERMIT IS FOR ONE HUNDRED DOLLARS [$1001 OR LESS)
l~l CERTIFICATE OF EXEMPTION I certify that in the performance of the work for which this permit is issued I shall not employ any person in any manner so as
to become subject to the Workers Compensation Laws of California
WARNING Failure to secure workers compensation coverage is unlawful and shall subject an employer to criminal penalties and civil fines up to one hundred
thousand dollars ($100 000) in addition to the cost of compensation damages as provided for in Section 3706 of the Labor code interest and attorney s fees
SIGNATURE DATE
7 OWNER BUILDER:DECLARAf JON
I hereby affirm that I am exempt from the Contractor s License Law for the following reason
l~l I as owner of the property or my employees with wages as their sole compensation will do th< work and the structure is not intended or offered for sale
(Sec 7044 Business and Professions Code The Contractor s License Law does not apply to an ownei of property who builds or improves thereon and who does
such work himself or through his own employees provided that such improvements are not intended or offered for sale If however the building or improvement is
sold within one year of completion the owner builder will have the burden of proving that he did not build or improve for the purpose of sale)
JKJ I as owner of the property am exclusively contracting with licensed contractors to construct the project (Sec 7044 Business and Professions Code The
Contractor s License Law does not apply to an owner of property who builds or improves thereon and contracts for such projects with contractor(s) licensed
pursuant to the Contractor s License Law)
l~l I am exempt under Section Business and Professions Code for this reason
isally plan to provide the major labor and materials for construction of the proposed property improvement
(I (have/ have not) signed an application for a building permit for the proposed work
YES NO
3 rfiave contracted with the following person (firm) to provide the proposed construction (include name / address / phone number / contractors license number)
4 I plan to provide portions of the work but I have hired the following person to coordinate supervi e and provide the major work (include name / address / phone
number / contractors license numbejl—
5 I will provide some of the/work but I have contrasted (hired) the following persons to provide the work indicatEcTTtoclude name / address / phone number / type
of work)zz
Rty
DATEPROPERTY OWNER SIGNAT
COMPLETE THIS SECTION IfORNpN^ESIDENT/AL BUILDING PERMITS I
Is the applicant or future b\jilding occupant required to submit a business plan acutely hazardous materials registration form or risk management and prevention
program under Sections 255O5 25533 or 25534 of the Presley Tanner Hazardous Substance Account Act' O YES J8s No
Is the applicant or future building occupant required to obtain a permit from the air pollution control district or air quality management district? Q YES JS NO
Is the facility to be constructed within 1 000 feet of the outer boundary of a school site? L~3 YES HiS NO
IF ANY OF THE ANSWERS ARE YES A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR IS MEETING THE
REQUIREMENTS OF THE OFFICE OF EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT
8 CONSTRUCTION LENDING AGENCY »N M
I hereby affirm that there is a construction lending agency for the performance of the work for which this permit is issued (Sec 3097(0 Civil Code)
LENDER S NAME LENDER S ADDRESS
9 'APPLICANT CERTIFICATION ::""-:" "!K ,^:'-1L*;' • '::: -•• .*J W
I certify that I have read the application and state that the above information is correct and that the information on the plans is accurate I agree to comply with all
City ordinances and State laws relating to building construction I hereby authorize representatives of the CitV of Carlsbad to enter upon the above mentioned
property for inspection purposes I ALSO AGREE TO SAVE INDEMNIFY AND KEEP HARMLESS THE CITY OF CARLSBAD AGAINST ALL LIABILITIES
JUDGMENTS COSTS AND EXPENSES WHICH MAY IN ANY WAY ACCRUE AGAINST SAID CITY IN CONSEQUENCE OF THE GRANTING OF THIS PERMIT
OSHA An OSHA permit is reqLm£d_toi excavations over 5 0 deep and demolition or construction of structures over 3 stories in height
EXPIRATION Every peprrrfissuea bytj^ bdilding pflttial under the provisions of this Code shall expire by limitation and become null and void if the building or work
authorized by such permit is not corinife/ce/ within /aojdays/om the date of such permit or if the building or work authorized by such permit is suspended or abandoned
at any time after the/faork is comrr^n/jp j/r f pgr\ljra/180/jjj^l (Section 106 4 4 Uniform Building Code)
APPLICANT S SIGN DATE
WHITE File YELLOW Applicant PINK Finance
City of Carlsbad
Final Building Inspection
Dept Building Engineering Planning CMWD St Lite (Firef
Plan Check #
Permit #
Project Name
Address
Contact Person
Sewer Dist
Inspected-^
Bv /ft >
Inspected
By
Inspected
Bv
Comments
CB023231
LACOSTA RESORT 2370SF Tl
MARKET PLACE ASSEMBLY TO RETAIL STORE
2101 COSTA DEL MAR RD
JEFF ROBERT SO Phone 7609296319
LC Water Dist CA
x, „ Date //?/«.// . n . t . '/4/t\i—(/^&j<L?sU^ Inspected / ^tO
(/ Date
Inspected
Date
Inspected
Date
Permit Type
Sub Type
AREA
Lot 0
Approved
Approved
Approved
.... .
01/03/2003
Tl
COMM
,»•*•
Disapproved
Disapproved
Disapproved
City of Carlsbad Bldg Inspection Request
For 01/03/2003
Permits CB023231
Title LACOSTA RESORT 2370SF Tl
Description MARKET PLACE-ASSEMBLY TO RETAIL STORE AREA
Inspector Assignment
2101 COSTA DEL MAR RD
Lot 0
Type Tl Sub Type COMM
Job Address
Suite
Location
APPLICANT K S L LA COSTA RESORT CORP
Owner K S L LA COSTA RESORT CORP
Remarks
Phone 7609296319
Inspector/
Total Time
CD Description
19 Final Structural
29 Final Plumbing
39 Final Electrical
4 Final/Mechanical(IMr.ft
Comment
Requested By JEFF ROBERTSON
Entered By CHRISTINE
Date
Associated PCRs/gVs
CV020692 CLOSED H MOLD AND ILLEGAL CONST (ROOF
PCR02289 ISSUED LA COSTA RESORT/MOVED WALLS & REVISE LIGHTING @ CLUBHOUSE FITNESS
Inspection History
Description Act Insp Comments
EsGil Corporation
In Partnership with Government for Building Safety
DATE 12/6/O2 a APPLICANTa JURIS
JURISDICTION City of Carlsbad a PLAN REVIEWER
a FILE
PLAN CHECK NO 02-3231 SET III
PROJECT ADDRESS 2101 Costa Del Mar
PROJECT NAME La Costa Market Place -TI
The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes
The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff
The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete lecheck
The check list transmitted herewith is for your information The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck
[""I The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person
LJ The applicant's copy of the check list has been sent to
A] Esgil Corporation staff did not advise the applicant that the plan check has been completed
Esgil Corporation staff did advise the applicant that the plan check has been completed
Person contacted Telephone #
Date contacted (by ) Fax #
Mail Telephone Fax In Person
REMARKS Applicant to sign all sheets
By Doug Moody Enclosures
Esgil Corporation
D GA D MB D EJ D PC H/27/02 tmsnidot
9320 Chesapeake Drive, Suite 208 + San Diego, California 92123 4> (858)560-1468 + Fax (85*) 560-1576
EsGil Corporation
In Partnership with Government for Building Safety
DATE 11/22/O2 a
a
JURISDICTION City of Carlsbad acAN REVIEWER
Q FILE
PLAN CHECK NO 02-3231 SET II
PROJECT ADDRESS 2101 Costa Del Mar
PROJECT NAME La Costa Market Place- TI
The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes
I | The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff
I | The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck
[Xj The check list transmitted herewith is for your information The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck
The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person
XI The applicant's copy of the check list has been sent to
Tom McCabe
1909 State Street, San Diego, CA 92101
Esgil Corporation staff did not advise the applicant that the plan check has been completed
Esgil Corporation staff did advise the applicant that the plan check has been completed
Person contacted Tom McCabe Telephone # 619-233-8740
Date contacted t c///^/CE (by fv) Fax # 619-233-8741
Mail ^-^Telephone Fa*-' In Person
REMARKS
By Doug Moody Enclosures
Esgil Corporation
D GA D MB D EJ D PC 11/15/02 trnsmtldot
9320 Chesapeake Drive, Suite 208 * San Diego, California 92123 * (858)560-1468 + Fax (858) 560-1576
City of Carlsbad O2-3231
11/22/02
RECHECK PLAN CORRECTION LIST
JURISDICTION City of Carlsbad PLAN CHECK NO 02-3231
PROJECT ADDRESS 2101 Costa Del Mar SET II
DATE PLAN RECEIVED BY DATE RECHECK COMPLETED
ESGIL CORPORATION 11/15/02 11/22/02
REVIEWED BY Doug Moody
FOREWORD (PLEASE READ)
This plan review is limited to the technical requirements contained in the Uniform Building Code,
Uniform Plumbing Code, Uniform Mechanical Code, National Electrical Code and state laws
regulating energy conservation, noise attenuation and disabled access This plan review is
based on regulations enforced by the Building Department You may have other corrections
based on laws and ordinances enforced by the Planning Department, Engineering Department
or other departments
The following items listed need clarification, modification or change All items must be satisfied
before the plans will be in conformance with the cited codes and regulations Per Sec 106 4 3,
1997 Uniform Building Code, the approval of the plans does not permit the violation of any
state, county or city law
A Please make all corrections on the original tracings and submit two new sets of prints to
ESGIL CORPORATION
B To facilitate rechecking, please identify, next to each item, the sheet of the plans upon
which each correction on this sheet has been made and return this sheet with the
revised plans
C The following items have not been resolved from the previous plan reviews The original
correction number has been given for your reference In case you did not keep a copy of
the prior correction list, we have enclosed those pages containing the outstanding
corrections Please contact me if you have any questions regarding these items
D Please indicate here if any changes have been made to the plans that are not a result of
corrections from this list If there are other changes, please briefly describe them and where
they are located on the plans Have changes been made not resulting from this list?
QYes QNo
City of Carlsbad O2-3231
11/22/O2
Please make all corrections on the original tracings, as requested in the correction list
Submit three sets of plans for commercial/industrial projects (two sets of plans for
residential projects) For expeditious processing, corrected sets can be submitted in one of
two ways
1 Deliver all corrected sets of plans and calculations/reports directly to the City of
Carlsbad Building Department, 1635 Faraday Ave , Carlsbad, CA 92008, (760) 602-2700
The City will route the plans to EsGil Corporation and the Carlsbad Planning, Engineering
and Fire Departments
2 Bring one corrected set of plans and calculations/reports to EsGil Corporation, 9320
Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-1468 Deliver all
remaining sets of plans and calculations/reports directly to the City of Carlsbad Building
Department for routing to their Planning, Engineering and Fire Departments
NOTE Plans that are submitted directly to EsGil Corporation only will not be reviewed by
the City Planning, Engineering and Fire Departments until review by EsGil Corporation is
complete
These corrections are in response to items not fully addressed or as the result of
information provided, the text in bold print indicates the unresolved issue
1 Plans and calculations shall be signed by the California State licensed engineer or
architect where there are structural changes to existing buildings or structural additions
Please include the California license number, seal, date of license expiration and date
plans are signed Business and Professions Code Not clearly indicated on the plans
2 Exit signs are required whenever two exits are required Show all required exit sign
locations Section 1003 282 Not clearly indicated on the plans
7 Please provide complete electrical plans Not provided
8 Provide mechanical plans, showing existing and proposed HVAC equipment, ducts and
access to equipment Not provided
9 Provide complete plumbing plans, including Not provided
1 Complete dram, waste and vent plans
2 Provide gas line plans and calculations, showing pipe lengths and gas demands
UPC Section 12170
3 Provide complete water line sizing calculations, including the water pressure,
pressure losses, water demands, and developed pipe lengths UPC Section 610 0
4 Show water heater size, type and location on plans UPC, Section 501 0
10 Provide complete energy designs for the proposed changes in envelope, lighting, and
mechanical systems Provide the completed ENV-, LTG-, and MECH- forms showing
energy compliance Not provided
City of Carlsbad 02-3231
11/22/O2
11 The completed and signed ENV-1, LTG-1, and MECH-1 forms must be imprinted on the
plans Not provided
12 Show or note that the proposed general sales, display and office areas are accessible, per
Section 111 OB 1, as follows Not clearly indicated on the plans
1 Work stations are located on accessible levels
2 The customer side of sales or checkout stations are accessible
3 Employee work areas are sized and arranged to provide access to employees in
wheelchairs
4 Checkstands shall provide
5 A 36" aisle on the customer side of the checkstand
6 Where quick checkstands are provided, >1 shall be accessible
7 Where regular checkstands are provided, the number of accessible checkstands
shall be as follows, per table 11B-2
8 >1 but 4 regular total = 1 accessible
9 >5 but 8 regular total = 2 accessible
10 >9 but 15 regular total = 3 accessible
11 >15 regular total = 3, + an additional 20%, accessible
12 Accessible checkstands shall provide a clear check-out aisle width of 36" with an
adjoining counter 38" above finished floor Note that they will always be open
and be identified by a sign clearly visible to those in wheelchairs
13 All circulation aisles and pedestrian ways shall be sized according to functional
requirements and >36" in clear width
13 Show that dining, banquet and bar facilities are accessible, per Section 1104B 5, as
follows Not clearly indicated on the plans
1 Fixed seating, counters and/or tables shall comply with Section 1104B 5 4 as follows
2 Access to these seats shall be by mam aisles >36" in clear width
3 Accessible seats are integrated with the general seating to allow a reasonable selection
of seating area and to avoid having one area specifically highlighted
4 Food service aisles shall be a >36" clear width, with a preferred width of 42", where
passage of stopped wheelchairs by pedestrians is desired
5 Restrooms shall be accessible
EsGil Corporation
In Partnership with Government for Building Safety
DATE 11/4/02 0_AEELJ£ANT
JURISDICTION City of Carlsbad a PLAN REVIEWER
a FILE
PLAN CHECK NO O2-3231 SET I
PROJECT ADDRESS 21O1 Costa Del Mar
PROJECT NAME La Costa Market Place- TI
J The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes
|~] The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff
The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck
The check list transmitted herewith is for your information The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck
The applicant's copy of the check list is enclosed for the jui isdiction to forward to the applicant
contact person
XI The applicant's copy of the check list has been sent to
Tom McCabe
1909 State Street, San Diego, CA 92101
Esgil Corporation staff did not advise the applicant that the plan check has been completed
Xj Esgil Corporation staff did advise the applicant that the plan check has been completed
Person contacted Tom McCabe Telephone # 619-233-8740
Date contacted//-4^2- (by &u_) Fax # 619-233-8741
Mail Telephone-^ Fax—" In Person
1 REMARKS
By Doug Moody Enclosures
Esgil Corporation
D GA D MB D EJ D PC 10/29/02 trnsmtldot
9320 Chesapeake Drive, Suite 208 4> San Diego, California 92123 4 (858)560-1468 + Fax (858) 560-1576
City of Carlsbad 02-3231
11/4/02
PLAN REVIEW CORRECTION LIST
TENANT IMPROVEMENTS
PLAN CHECK NO O2-3231
OCCUPANCY A3
TYPE OF CONSTRUCTION III 1H
ALLOWABLE FLOOR AREA
SPRINKLERS'? YES
REMARKS
DATE PLANS RECEIVED BY
JURISDICTION 10/25/02
DATE INITIAL PLAN REVIEW
COMPLETED 11/4/02
JURISDICTION City of Carlsbad
USE Retail
ACTUAL AREA 2370 sf
STORIES 1
HEIGHT
OCCUPANT LOAD 158
DATE PLANS RECEIVED BY
ESGIL CORPORATION 10/29/02
PLAN REVIEWER Doug Moody
FOREWORD (PLEASE READ)
This plan review is limited to the technical requirements contained in the Uniform Building Code,
Uniform Plumbing Code, Uniform Mechanical Code, National Electrical Code and state laws
regulating energy conservation, noise attenuation and access for the disabled This plan review
is based on regulations enforced by the Building Department You may have other corrections
based on laws and ordinances enforced by the Planning Department, Engineering Department,
Fire Department or other departments Clearance from those departments may be required
prior to the issuance of a building permit
Code sections cited are based on the 1997 UBC
The following items listed need clarification, modification or change All items must be satisfied
before the plans will be in conformance with the cited codes and regulations Per Sec 106 4 3,
1997 Uniform Building Code, the approval of the plans does not permit the violation of any
state, county or city law
To speed up the recheck process, please note on this list (or a copy) where each
correction item has been addressed, i e. plan sheet number, specification section, etc
Be sure to enclose the marked up list when you submit the revised plans
TENANT IMPROVEMENTS WITHOUT SPECIFIC ENERGY DATA OR POLICY SUPPLEMENTS (1997UBC)tiforw dot
City of Carlsbad 02-3231
11/4/02
Please make all corrections on the original tracings, as requested in the correction
list Submit three sets of plans for commercial/industrial projects (two sets of plans
for residential projects) For expeditious processing, corrected sets can be
submitted in one of two ways
1 Deliver all corrected sets of plans and calculations/reports directly to the City of
Carlsbad Building Department, 1635 Faraday Ave , Carlsbad, CA 92008, (760)
602-2700 The City will route the plans to EsGil Corporation and the Carlsbad
Planning, Engineering and Fire Departments
2 Bring one conected set of plans and calculations/reports to EsGil Corporation,
9320 Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-1468
Deliver all remaining sets of plans and calculations/reports directly to the City of
Carlsbad Building Department for routing to their Planning, Engineering and Fire
Departments
NOTE Plans that are submitted directly to EsGil Corporation only will not be
reviewed by the City Planning, Engineering and F ire Departments until review by
EsGil Corporation is complete
1 Plans and calculations shall be signed by the California state licensed engineer
or architect where there are structural changes 1o existing buildings or structural
additions Please include the California license number, seal, date of license
expiration and date plans are signed Business and Professions Code
2 Provide a section view of the new soffits Show
a) Type, size and spacing of studs Indicate gauge for metal studs Specify
manufacturer and approval number or indicate "to be ICBO approved"
b) Method of attaching top to the structure and lateral bracing
c) Wall sheathing material and details of attachment (size and spacing of
fasteners)
d) Show height of the soffit from floor, soffit to roof framing or floor framing
3 Note on plan that suspended ceilings shall comply with UBC Tables 25-A, 16-O
and 16-B
4 If exit signs are required, provide the following notes on the plans, per Section
1003282
a) Exit signs shall be located as necessary to clearly indicate the direction of
egress travel No point shall be more than 100 feet from the nearest
visible sign
b) Exit signs shall be readily visible from any direction of approach
5 Exit signs are required whenever two exits are required Show all required exit
sign locations Section 1003 282
6 Specify on the plans the following information for the roof materials, per Section
10633
a) Manufacturer's name
b) Product name/number
City of Carlsbad O2-3231
11/4/O2
c) ICBO approval number, or equal
7 Please provide complete electrical plans
8 Provide mechanical plans, showing existing and proposed HVAC equipment,
ducts and access to equipment
9 Provide complete plumbing plans, including
a) Complete dram, waste and vent plans
b) Provide gas line plans and calculations, showing pipe lengths and gas
demands UPC Section 1217 0
c) Provide complete water line sizing calculations, including the water
pressure, pressure losses, water demands, and developed pipe lengths
UPC Section 6100
d) Show water heater size, type and location on plans UPC, Section 501 0
10 Provide complete energy designs for the proposed changes in envelope, lighting,
and mechanical systems Provide the completed ENV-, LTG-, and MECH- forms
showing energy compliance
11 The completed and signed ENV-1, LTG-1, and MECH-1 forms must be imprinted
on the plans
12 Show or note that the proposed general sales, display and office areas are
accessible, per Section 1110B 1, as follows
a) Work stations are located on accessible levels
b) The customer side of sales or checkout stations are accessible
c) Employee work areas are sized and arranged to provide access to
employees in wheelchairs
d) Checkstands shall provide
i) A 36" aisle on the customer side of the checkstand
n) Where quick checkstands are provided, >1 shall be accessible
in) Where regular checkstands are provided, the number of accessible
checkstands shall be as follows, per table 11B-2
a) >1 but 4 regular total = 1 accessible
b) >5 but 8 regular total = 2 accessible
c) >9 but 15 regular total = 3 accessible
d) >15 regular total = 3, + an additional 20%, accessible
e) Accessible checkstands shall provide a clear check-out aisle width of 36"
with an adjoining counter 38" above finished floor Note that they will
always be open and be identified by a sign clearly visible to those in
wheelchairs
City of Carlsbad O2-3231
11/4/02
f) All circulation aisles and pedestrian ways shall be sized according to
functional requirements and >36" in clear width
13 Show that dining, banquet and bar facilities are accessible, per Section 1104B 5,
as follows
a) Access is provided at primary entrances and exits as required by Chapter
10
b) Fixed seating, counters and/or tables shall comply with Section 1104B 5 4
as follows
i) Wheelchair access is required to all areas where each type of
functional activity occurs
n) Each dining, banquet and bar area shall have one wheelchair
seating space for each 20 seats, with >1 space per functional area
c) Access to these seats shall be by mam aisles >36" in clear width
d) Accessible seats are integrated with the general seating to allow a
reasonable selection of seating area and to avoid having one area
specifically highlighted
e) Food service aisles shall be a >36" clear width, with a preferred width of
42", where passage of stopped wheelchairs by pedestrians is desired
f) Restrooms shall be accessible
To speed up the review process, note on this list (or a copy) where each
correction item has been addressed, i e , plan sheet, note or detail number,
calculation page, etc
Please indicate here if any changes have been made to the plans that are not a
result of corrections from this list If there are olher changes, please briefly
describe them and where they are located in the plans
Have changes been made to the plans not resulting from this correction list7
Please indicate
Yes G No a
The jurisdiction has contracted with Esgil Corporation located at 9320
Chesapeake Drive, Suite 208, San Diego, California 92123, telephone number of
858/560-1468, to perform the plan review for your project If you have any
questions regarding these plan review items, please contact Doug Moody at
Esgil Corporation Thank you
City of Carlsbad 02-3231
11/4/02
VALUATION AND PLAN CHECK FEE
JURISDICTION City of Carlsbad PLAN CHECK NO 02-3231
PREPARED BY Doug Moody DATE 11/4/02
BUILDING ADDRESS 21O1 Costa Del Mar
BUILDING OCCUPANCY A3 TYPE OF CONSTRUCTION III1H
BUILDING
PORTION
Tl
Air Conditioning
Fire Sprinklers
TOTAL VALUE
Jurisdiction Code
AREA II Valuation
( Sq Ft ) Multiplier
2370
cb
:1QQ/1 I IRT RinlHinn Pormif Poo : V
City Valuation
By Ordinance
Reg
Mod
VALUE ($)
71,100
71,100
$429 76
1994 UBC Plan Check Fee
Type of Review
I I Repetitive Fee
Repeats
Complete Review
D Other
n Hourly
Structural Only
Hour
Esgil Plan Review Fee
Comments
$279 34
$240 67
Sheet 1 of 1
macvalue doc
PLANNING/ENGINEERING APPROVALS
PERMIT NUMBER CB 02-DATE
AODRESS
RESIDENTIAL TENANT IMPROVEMENT
RESIDENTIAL ADDITION MINOR
« $10,000.00)
PLAZA CAMINO REAL
CARLSBAD COMPANY STORES
VILLAGE FAIRE
COMPLETE OFFICE BUILDING
OTHER cot 73-SpA-
PLANNER
ENGINEER
DATE
DATE
Doci/Misforms/Planning Engineering Approvals
Carlsbad Fire Department 023231
1635 Faraday Ave
Carlsbad CA 92008
Plan Review
Date of Report
Fire Prevention
(760) 602-4660
Requirements Category
10/31/2002
Building Plan
Reviewed by
Me Cabe Harris, Inc
1909 State Street
Name
Address
City, State San Diego CA 92101
Plan Checker
Job Name Market Place
Job Address 2101 Costa Del Mar
Job # 023231
Bldg # CB023231
Ste or Bldg No
Approved The item you have submitted for review has been approved The approval is
based on plans, information and / or specifications provided in your submittal,
therefore any changes to these items after this date, including field
modifications, must be reviewed by this office to insure continued conformance
with applicable codes and standards Please review carefully all comments
attached as failure to comply with instructions in this report can result in
suspension of permit to construct or install improvements
D Approved
Subject to
The item you have submitted for review has been approved subject to the
attached conditions The approval is based on plans, information and/or
specifications provided in your submittal Please review carefully all comments
attached, as failure to comply with instructions in this report can result in
suspension of permit to construct or install improvements Please resubmit to
this office the necessary plans and / or specifications required to indicate
compliance with applicable codes and standards
D Incomplete The item you have submitted for review is incomplete At this time, this office
cannot adequately conduct a review to determine compliance with the
applicable codes and / or standards Please review carefully all comments
attached Please resubmit the necessary plans and / or specifications to this
office for review and approval
Review
FD Job#
1st 2M 3rd
023231 FDFile#
Other Agenr.y ID