HomeMy WebLinkAbout2121 Palomar Airport Rd; ; CBC2017-0021; PermitPrint Date: 08/11/2017
Job Address:
Permit Type:
Parcel No:
Valuation:
Occupancy Group:
# Dwelling Units:
Bedrooms:
Project Title:
2121 Palomar Airport Rd
BLDG-Commercial
2130701300
$48,230.87
City of Carlsbad
1635 Faraday Av Carlsbad, CA 92008
Commercial Permit
www.carlsbadca.gov
Work Class: Tenant Improvement
Lot#:
Reference #:
Construction Type:
Bathrooms:
Orig. Plan Check#:
Plan Check#:
Status:
Applied:
Issued:
Finaled:
Inspector:
Permit No: CBC2017-0021
Closed -Finaled
01/11/2017
02/23/2017
A Krog
Description: BROOKWOOD: RENOVATION OF ELEVATOR LOBBIES// 150 SF AT 1ST, 2ND, AND 3RD FLOOR EACH// RENO 1ST FLOOR
BATHROOM AT 295 SF// 2ND FLOOR AT 292 SF
Applicant: Owner: Contractor:
HURKES HARRIS DESIGN ASSOCIATES
JEFFERY HURKES
BROOKWOOD CARLSBAD EXECUTIVE PLAZA
LLC
SP WHITE CONSTRUCTION INC
619-702-0380
BUILDING PERMIT FEE $2000+
BUILDING PLAN CHECK FEE (BLDG)
72 Cherry Hill Dr
BERVERLY, MA 01915
ELECTRICAL BLDG COMMERCIAL NEW/ADDITION/REMODEL
MECHANICAL BLDG COMMERCIAL NEW/ADDITION/REMODEL
SB1473 BUILDING STANDARDS FEE
STRONG MOTION-COMMERCIAL
Total Fees: $782.82 Total Payments To Date: $782.82
2524 Gateway Rd
Carlsbad, CA 92009-17 42
760-931-1130
Balance Due:
Please take NOTICE that approval of your project includes the "Imposition" of fees, dedications, reservations, or other exactions hereafter
collectively referred to as "fees/exaction." You have 90 days from the date this permit was issued to protest imposition of these
fees/exactions. If you protest them, you must follow the protest procedures set forth in Government Code Section 66020(a), and file the
protest and any other required information with the City Manager for processing in accordance with Carlsbad Municipal Code Section
3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack, review, set aside, void, or annul their
imposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection
fees and capacity changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this
project. NOR DOES IT APPLY to any fees/exactions of which you have previously been given a NOTICE similar to this, or as to which the
statute of limitation has previously otherwise expired.
$0.00
$399.60
$279.72
$43.00
$45.00
$2.00
$13.50
ITHE FOLlp!ilNG APPROVALS REQUIRED PRIOR TO PERMIT ISSUANCE: 0PLANNING 0ENGINEERING 0BUILDING OFIRE OHEALTH OHAZMAT/APCD I
C Cityof Building Permit Application Plan Check ~o. CBc.'2.o\-, -00'.l-(
1635 Faraday Ave., Carlsbad, CA 92008 Est. Value (ff'-f ~ '2-r'-<. \
Carlsbad Ph: 760-602-2719 Fax: 760-602-8558 Plan Ck. Dep9sit email: building@carlsbadca.gov
www.carlsbadca.gov Date \ ( c l / \ -r lswPPP
JOB ADDRESS SUITEt/SPACEt/UNITt ii APN 2121 Palomar Airport Rd, Carlsbad , CA 92011 lby/ Restra 213 -070 -16 -
CT/PROJECT# ILOT# I PHASE# I # OF UNITS I # BEDROOMS # BATHROOMS I TENANT BUSINESS NAME I CONSTR. lYPE I occ. GROUP
Ill-A B
DESCRIPTION OF WORK: Include Square Feet of Affected Area(s)
Renovation of 1st, 2nd, 3rd floor elevator lobbies. New ceiling, lighting, and finishes.
Renovation of 1st & 3rd floor restrooms. New partitions, partial new ceiling , lighting, fixtures and finishes.
',o'!,r ~
EXISTING USE I PROPOSED USE I GARAGE (SF) PATIOS (SF) I DECKS (SF) FIREPLACE I AIR CONDITIONING I FIRE SPRINKLERS
Office Office YES CJit No{ZJ YES [2::JNo D YEs[2] NoD
APPLICANT NAME White Construction, Inc. PROPERTY OWNER NAME Brookwood Management Partners, LLC 3 W ,lY·.&PEU.<In
ADDRESS ADDRESS
2524 Gateway Rd 2131 Palomar Airport Rd, Suite 203
CITY STATE ZIP CITY STATE ZIP
Carlsbad CA 92009 Carlsbad CA 92011
PHONE 'FAX PHONE 'FAX 760-931-1130 760-804-0340
EMAIL EMAIL
shelly@whiteconstructioninc.com svalentino@brookwoodfinancial.com
DESIGN PROFESSIONAL Hurkes Harris Desi1:1n Associates CONTRACTOR BUS. NAME White Construction
ADDRESS ADDRESS
1620 Fifth Ave. Suite 100 2524 Gateway Rd
CITY STATE ZIP CITY STATE ZIP
Sa n Dieao CA 92101 Carlsbad CA 92009
PHONE 'FAX PHONE 'FAX 619-702-0380 (760 ) 93101130 X 118
EMAIL EMAIL
lwise(a)hhdainc.com shelly@whiteconstructioninc.com
ISTATELIC. # 0807 STATE LIC.# ICLASS B I CllY BUS. LIC1#2023880 Jeffery Hurkes 452513
(Sec. 7031.5 Business and Professions Code: Any City or County which requires a permit to construct, alter, improve, demolish or repair an~ structure. prior to its issuance, also requires the applicant for such permit to file a signed statement that he is licensed pursuant to the provisions of the Contractor"s License Law /Chapter 9. commending with Section 7000 of Division 3 of the Business and Professions Code} or that he is exempt therefrom, and the basis for the alleged exemption. Any violation of Section 7031.5 by any applicant for a permit subjects the applicant to a civil penalty of not more than five hundred dollars ($500)).
WORKERS' COMPENSATION
Workers' Compensation Declaration: I hereby affirm under penalty of petjury one of the following declarations:
0 I have and will maintain a certificate of consent to self-insure for workers' compensation as provided by Section 3700 of the Labor Code, for the performance of the work for which this permit is issued. 0 I have and will maintain workers' compensation, as required by Section 3700 of the Labor Code. for the performance of the work for which this permit is issued. My workers' compensation insurance carrier and policy
number are: Insurance Co. Everest National Insurance Com Policy No. 7600014158171 Expiration Date 01.0112011
~section need not be completed if the permit is for one hundred dollars ($100) or less. LJ Certificate of Exemption: I certify that in the performance of the work for which this permit is issued, I shall not employ any person in any manner so as to become subject to the Workers' Compensation Laws of
California. WARNING: Failure to secure wori<ers' compensation coverage is unlawful, and shall subject an employer to criminal penalties and civil fines up to one hundred thousand dollars (&100,000), in
addition to the cost of compensation, damages as provided for in Section 3706 of the Labor code, interest and attorney's fees.
_g CONTRACTORSIGNATIJRE 'f-0AGENT DATE 1/11/17
I hereby affirm that I am exempt from Contractor's License Law for the following reason:
D
D
D
I, as owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not intended or offered for sale (Sec. 7044, Business and Professions Code: The Contractor's
License Law does nol apply lo an owner of property who builds or improves thereon, and who does such work himself or through his own employees, provided that such improvements are not intended or offered fOf
sale. If, however, the building or improvement 1s sold within one year of completion, the owner-builder will have the burden of proving that he did not build or improve for the purpose of sale).
I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions Code: The Contractor's License Law does not apply to an owner of
property who builds or improves thereon, and contracts fOf such projects with contractor(s) licensed pursuant to the Contractor's License Law).
I am exempt under Section Business and Professions Code for this reason:
1. I personally plan to provide the major labor and materials for construction of the proposed property improvement. 0 Yes 0 No
2. I (have I have not) signed an application for a building permit for the proposed work.
3. I have contracted with the following person (firm) to provide the proposed construction (include name address I phone I contractors' license number):
4. I plan to provide portions of the work, but I have hired the following person to coordinate, supervise and provide the major work (include name I address I phone I contractors' license number):
5. I will provide some of the work, but I have contracted (hired) the following persons to provide the work indicated (include name I address I phone I type of work):
_g PROPERTY OWNER SIGNATURE 0AGENT DATE
·-~c O M P L E TE TH I S S E C T I O N F O R N O N • R E S I D E N T I A L 8 U I L D I N G P E R M I TS O N LY
(s the applicoot or future building occupant required to submit a business plan, acutely hazardous materials registration form or risk management and prevention program under Sections 25505, 25533 or 25534 of the
Presley-Tanner Hazardous Substance Account Acf/ Yes ./ No
Is the applicant 01 future building occupant required to obtain a permit from the air pollution control disbict or air quality management disbict? Yes ./ No
Is the facility to be constructed within 1,000 feet of the outer boundary of a school site? Yes ./ No
IF ANY OF THE ANSWERS ARE YES, A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR IS MEETING THE REQUIREMENTS OF THE OFFICE OF
EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT.
I hereby affirm that there is a construction lending agency for the performance of the work this permit is issued (Sec. 3097 (i) Civil Code).
Lender's Name N1A Lender's Address
APPLICANT CERTIFICATION
I certify that I have read the application and state that the above information is correct and that the infonnation on the plans is accurate. I agree to comply with all City ordinances and State laws relating to building construction.
I hereby authorize representative of the City of Carlsbad to enter upon the above mentioned property for inspection purposes. I ALSO AGREE TO SAVE, INDEMNIFY AND KEEP HARMLESS THE CrTY OF CARLSBAD
AGAINST ALL LIABILITIES, JUDGMENTS, COSTS AND EXPENSES WHICH MAY IN ANY WAY ACCRUE AGAINST SAID CrTY IN CONSEQUENCE OF THE GRANTING OF THIS PERMIT.
OSHA: An OSHA permit is required for excavations over 5'0' deep and demolition or construction of structures over 3 stories in height
EXPIRATION: Every permit issued by the Building Official under the provisions of this Code shall expre by imitation and beoome nul and void ~ the buildi,g or won< authorized by such permit is not commenced within
180 days from the date of such permit or/' building or won< authorized by such permit is suspended or abandoned at any time after the won< is commenced for a perod of 180 days (Section 106.4.4 Uniform Building Code) .
..@S° APPLICANT'S SIGNATURE r-DATE 1/11/2017
STOP: THIS SECTION NOT REQUIRED FOR BUILDING PERMIT ISSUANCE.
Complete the following ONLY if a Certificate of Occupancy will be requested at final inspection.
Fax (760) 602-8560, Email building@carlsbadca.gov or Mail the completed form to City of Carlsbad, Building Division 1635 Faraday Avenue, Carlsbad, California 92008.
CO#; (Office Use Only)
CONTACT NAME OCCUPANT NAME
ADDRESS BUILDING ADDRESS
CITY STATE ZIP CITY STATE
Carlsbad CA
PHONE FAX
EMAIL OCCUPANT'S BUS. LIC. No.
DELIVERY OPTIONS
PICK UP: CONTACT (Listed above) OCCUPANT (Listed above)
CONTRACTOR (On Pg. 1)
MAIL TO: CONTACT (Listed above)
CONTRACTOR (On Pg. 1)
OCCUPANT (Listed above)
MAIL/FAXTOOTHER: ________________ ~
,IS APPLICANT'S SIGNATURE
ASSOCIATED CB#------------
NO CHANGE IN USE / NO CONSTRUCTION
CHANGE OF USE / NO CONSTRUCTION
DATE
ZIP
:·'." ·, . . PERMIT INSPECTION HISTORY REPORT (CBC2017-0021)
Permit Typo BLDG-Commercial Application Date: 01/11/201 7 Owner:
Work Class: Tenant Improvement Issue Date: 02/23/201 7 Subdivision:
Status Closed -Finaled Expiration Date: 12/13/2017 Address:
IVR Number: 1408
Actual Scheduled
Date Start Date Inspection Type Inspection No. Inspection Status Primary Inspector
08/07/2017 08/07/2017 BLOG-Final
Inspection
08/11/2017 08/11/2017 BLOG-Final
Inspection
August 11, 2017
Checklist Item
BLDG-Building Deficiency
030823-2017
Checklist Item
BLDG-Building Deficiency
BLDG-Plumbing Final
BLDG-Mechanical Final
BLDG-Structural Final
BLDG-Electrical Final
031472-2017
Checklist Item
BLDG-Plumbing Final
BLDG-Mechanical Final
BLDG-Structural Final
BLDG-Electrical Final
COMMENTS
3rd floor restroom. additional screws to
base track in women's restroom as noted
Partial Pass Andy Krogh
COMMENTS
3rd floor restroom ok to occupy
Passed Andy Krogh
COMMENTS
BROOKWOOD CARLSBAD
EXECUTIVE PLAZA LLC
CARLSBAD TCT#83-10
2121 Palomar Airport Rd
Carlsbad, CA 92011
Reinspection Complete
Passed
Yes
Reinspection Incomplete
Passed
Yes
No
No
No
No
Complete
Passed
Yes
Yes
Yes
Yes
Page 3 of 3
r~~~ .-,
1~--_ PERMIT INSPECTION HISTORY REPORT (CBC2017-0021)
Permit Type: BLDG-Commercial Application Date: 01/11/2017 Owner: BROOKWOOD CARLSBAD
EXECUTIVE PLAZA LLC
Work Class: Tenant Improvement Issue Date: 02/23/2017 Subdivision: CARLSBAD TCT#83-10
Status: Closed -Finaled Expiration Date: 12/13/2017 Address: 2121 Palomar Airport Rd
Carlsbad, CA 92011
IVR Number; 1408
-----
Scheduled Actual Inspection Type Inspection No. Inspection Status Primary Inspector Date Start Date Reinspection Complete
05/11/2017 05/11/2017 BLDG-Final 023049-2017 Partial Pass Andy Krogh Reinspection Incomplete
Inspection
Checklist Item COMMENTS Passed
BLDG-Building Deficiency First floor restroom ok to occupy Yes
BLDG-Plumbing Final No
BLDG-Mechanical Final No
BLDG-Structural Final No
BLDG-Electrical Final No
06/06/2017 06/06/2017 BLDG-24 025371-2017 Passed Andy Krogh Complete
Rough/Topout
Checklist Item COMMENTS Passed
BLDG-Building Deficiency 3rd floor restrooms Yes
BLDG-85 T-Bar, 025370-2017 Partial Pass Andy Krogh Relnspection Incomplete
Ceiling Grids,
Overhead
Checklist Item COMMENTS Passed
BLDG-Building Deficiency 3rd floor lobby Yes
BLDG-14 Yes
Frame-Steel-Bolting-Welding
(Decks)
BLDG-24 Rough-Topout Yes
BLDG-34 Rough Electrical Yes
BLDG-44 Yes
Rough-Ducts-Dampers
06/08/2017 06/08/2017 BLDG-85 T-Bar, 025822-2017 Passed Andy Krogh Complete
Ceiling Grids,
Overhead
Checklist Item COMMENTS Passed
BLDG-Building Deficiency 1st floor lobby Yes
BLDG-14 Yes
Frame-Steel-Bolting-Welding
(Decks)
BLDG-24 Rough-Topout Yes
BLDG-34 Rough Electrical Yes
BLDG-44 Yes
Rough-Ducts-Dampers
06/12/2017 06/12/2017 BLDG-24 025906-2017 Passed Andy Krogh Complete
Rough/Topout
Checklist Item COMMENTS Passed
BLDG-Building Deficiency 3rd floor restroom Yes
06/16/2017 06/16/2017 BLDG-18 Exterior 026461-2017 Passed Andy Krogh Complete
Lath/Drywall
August 11, 2017 Page 2 of 3
~( t\'
;, -PERMIT INSPECTION HISTORY REPORT (CBC2017-0021)
Permit type BLDG-Commercial Application Date: 01/11/2017 Owner: BROOKWOOD CARLSBAD
EXECUTIVE PLAZA LLC
Work Class Tenant Improvement Issue Date: 02/23/2017 Subdivision: CARLSBAD TCT#83-10
Status· Closed -Finaled Expiration Date: 12/13/2017 Address: 2121 Palomar Airport Rd
Carlsbad, CA 9201 1
IVR Number: 1408
Scheduled Actual
Date Start Date Inspection Type Inspection No. Inspection Status Primary Inspector Reinspect.ion Complete
03/16/2017 03/1612017 BLDG-24 016769-2017 Failed Paul Burnette Relnspection Complete
Rough/Topout
Checklist Item COMMENTS Passed
BLDG-Building Deficiency No
03117/2017 03/17/2017 BLDG-24 016905-2017 Passed Paul Burnette Complete
Rough/Topout
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Yes
03/20/2017 03/20/2017 BLDG-14 017000-2017 Passed Paul Burnette Complete
Frame/Steel/Bolting/
Welding (Decks)
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Yes
03/24/2017 03/24/2017 BLDG-17 Interior 017589-2017 Passed Peter Dreibelbis Complete
Lath/Drywall
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Yes
03/30/2017 03/30/2017 BLDG-85 T-Bar, 018258-2017 Failed Paul Burnette Relnspection Complete
Ceiling Grids,
Overhead
Checklist Item COMMENTS Passed
BLDG-Building Deficiency No
BLDG-14 No
Frame-Steel-Bolting-Welding
(Decks)
BLDG-24 Rough-Topout No
BLDG-34 Rough Electrical No
BLDG-44 No
Rough-Ducts-Dampers
04/04/2017 04/04/2017 BLDG-85 T-Bar, 018710-2017 Passed Peter Dreibelbis Complete
Ceiling Grids,
Overhead
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Yes
BLDG-14 Yes
Frame-Steel-Bolting-Welding
(Decks)
BLDG-24 Rough-Topout Yes
BLDG-34 Rough Electrical Yes
BLDG-44 Yes
Rough-Ducts-Dampers
August 11, 2017 Page 1 of 3
EsGil Corporation
Jn <Partnersliip witli qovernment for (}Jui{aing Safety
DATE: 2/21/17
JURISDICTION: City of Carlsbad
PLAN CHECK NO.: C2017-0021
PROJECT ADDRESS: 2121 Palomar Airport Rd
SET: II
D APPLICANT
..,.13-"j UR IS.
D PLAN REVIEWER
D FILE
PROJECT NAME: Carlsbad Eixecutive Plaza Lobby and Restroom Renovation -TI
~ The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's
codes when minor deficiencies identified below are resolved and checked by building
department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
D The check list transmitted herewith is for your information. The plans are being held at EsGil
Corporation until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
D The applicant's copy of the check list has been sent to:
~ EsGil Corporation staff did not advise the applicant that the plan check has been completed.
D EsGil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: -()(j Telephone#:
Date contacted: -(by:~) Email:
Mail Telephone Fax In Person
D REMARKS:
By: Doug Moody Enclosures:
EsGil Corporation
D GA D EJ D MB 0 PC 2/14/17
9320 Chesapeake Drive, Suite 208 + San Diego, California 92123 + (858) 560-1468 + Fax (858) 560-1576
EsGil Corporation
Jn (J?artnersfi.ip witli. government for c.Bui(aing Safety
DATE: 1/26/17
JURISDICTION: City of Carlsbad
PLAN CHECK NO.: C2017-0I021
PROJECT ADDRESS: 2121 Palomar Airport Rd
SET: I
E PLICANT
RIS.
D PLAN REVIEWER
D FILE
PROJECT NAME: Carlsbad E:xecutive Plaza Lobby and Restroom Renovation -TI
D The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's
codes when minor deficiencies identified below are resolved and checked by building
department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
l2{i The check list transmitted herewith is for your information. The plans are being held at EsGil
Corporation until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
D The applicant's copy of the check list has been sent to:
D EsGil Corporation staff did not advise the applicant that the plan check has been completed.
D EsGil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted:. White Construction. Telephone#: 760-931-1130 ext. 118
,~ate coit t.e· d: I }2,~·-(by~ Email: shelly@whiteconstructioninc.com
{:::::tMail el phonS\ Fax In Person
D REMAR :'-\l'\v
By: Doug Moody
EsGil Corporation
D GA D EJ D MB D PC
Enclosures:
1/17/17
9320 Chesapeake Drive, Suite 208 + San Diego, California 92123 + (858) 560-1468 + Fax (858) 560-1576
City of Carlsbad C201 rl-0021
1/26/17
PLAN REVIEW CORRECTION LIST
TENANT IMPROVEMENTS
PLAN CHECK NO.: C20ll 7-0021
OCCUPANCY: B
TYPE OF CONSTRUCTION: IIIA
ALLOWABLE FLOOR AREA:
SPRINKLERS?: YES
REMARKS:
DATE PLANS RECEIVED BY
JURISDICTION: 1/10/17
DATE INITIAL PLAN REVIEW
COMPLETED: 1/26/ 17
FOREWORD (PLEASE READ):
JURISDICTION: City of Carlsbad
USE: Elevator Lobby Restrooms
ACTUAL AREA: 1037sf
STORIES: 3
HEIGHT:
OCCUPANT LOAD: N/A
DATE PLANS RECEIVED BY
ESGIL CORPORATION: 1/17/17
PLAN REVIEWER: Doug Moody
This plan review is limited to the technical requirements contained in the California version of
the International Building Code, Uniform Plumbing Code, Uniform Mechanical Code, National
Electrical Code and state laws regulating energy conservation, noise attenuation and access for
the disabled. This plan review is based on regulations enforced by the Building Department.
You may have other corrections based on laws and ordinances enforced by the Planning
Department, Engineering Department, Fire Department or other departments. Clearance from
those departments may be required prior to the issuance of a building permit.
Code sections cited are based on the 2013 CBC, which adopts the 2012 IBC.
The following items listed need clarification, modification or change. All items must be satisfied
before the plans will be in conformance with the cited codes and regulations. Per Sec. 105.4 of
the 2012 International Building Code, the approval of the plans does not permit the violation of
any state, county or city law.
To speed up the recheck process, please note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet number, specification section, etc.
Be sure to enclose the marked up list when you submit the revised plans.
City of Carlsbad C201 7-0021
1/26/17
Please make all corrections on the original tracings, as requested in the correction
list. Submit three sets of plans for commercial/industrial projects (two sets of plans
for residential projects). For expeditious processing, corrected sets can be
submitted in one of two ways:
1. Deliver all corrected sets of plans and calculations/reports directly to the City of
Carlsbad Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760)
602-2700. The City will route the plans to EsGil Corporation and the Carlsbad
Planning, Engineering and Fire Departments.
2. Bring two corrected sets of plans and calculations/reports to EsGil Corporation,
9320 Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-1468.
Deliver all remaining sets of plans and calculations/reports directly to the City of
Carlsbad Building Department for routing to their Planning, Engineering and Fire
Departments.
NOTE: Plans that are submitted directly to EsGil Corporation only will not be
reviewed by the City Planning, Engineering and Fire Departments until review by
EsGil Corporation is complete.
1. Please clarify the plans to show the hard lid ceiling that is to be removed to not
be a 1 hour rated ceiling assembly as part of the elevator lobby. Section 107.2.
2. Please correct the plumbing fixture schedule to show the urinals to use .125 GPF
and not the .5 GPF shown.
3. Please clarify the plumbing plans to show floor drains in the following locations,
as per UPC. Section 411.2:
a) Toilet rooms containing two or more water closet or a combination of 1
water doset and 1 urinal.
Advisory NotE~ : When alterations, structural repairs or additions are made to an
existing building, that building, or portion of the building affected, is required to
comply with all of the following requirements, per Section 11 B-202.4:
• A primary entrance to the building and the primary path of travel to the
altered are~ must be shown to comply with all accessibility features.
• The path of travel shall include the existing parking.
• Please address the following comments that are the result of the alterations.
4. Show on the site plan the complying disabled accessible path of travel from the
disabled accessible parking spaces to the primary entrance of the tenant space.
Please provide detailed plans of the path of travel, indicate slope and width, any
pedestrian ramps, curb ramps, walks, handrails, provide dimensioned parking
stall details etc.
City of Carlsbad C2017-0021
1/26/17
To speed up the review process, note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet, note or detail number,
calculation page, etc.
Please indicate here if any changes have been made to the plans that are not a
result of corrections from this list. If there are other changes, please briefly
describe them and where they are located in the plans.
Have changes been made to the plans not resulting from this correction list?
Please indicate:
Yes 0 No 0
The jurisdiction has contracted with Esgil Corporation located at 9320
Chesapeake Drive, Suite 208, San Diego, California 92123; telephone number of
858/560-146B, to perform the plan review for your project. If you have any
questions regarding these plan review items, please contact Doug Moody at
Esgil Corporation. Thank you.
' City of Carlsbad C201 7-0021
. 1/26/17
[DO NOT PAY -THIS IS NOT AN INVOICE]
VALUATION AND PLAN CHECK FEE
JURISDICTION: City of Carlsbad PLAN CHECK NO.: C2017-0021
PREPARED BY: Doug M<J•ody DATE: 1/26/17
BUILDING ADDRESS: 2121 Palomar Airport Rd
BUILDING OCCUPANCY:
BUILDING AREA~ Valuation
PORTION ( Sq. Ft) Multiplier
Tl 1037 46.51
Air Conditioning
Fire Sprinklers
TOTAL VALUE
Jurisdiction Code cb By Ordinance
Bldg. Permit Fee by Ordinance ~1
-Pla-n -Ch;-ck-Fe-e-by-0-rd-in-an--ce~~,..-J
Type of Review: GJ Complete Review
D Repetitive Fee
--~ Repeats
Comments:
D Other
D Hourly
EsGil Fee
Reg. VALUE
Mod.
D Structural Only
1---------11 Hr @ '
($)
48,231
48,231
$400.09!
$260.061
$224.051
Sheet 1 of 1
macvalue.doc +
STORM WATER
COMPLIANCE
ASSESSMENT
8-24
Development Services
Building Division
1635 Faraday Avenue
760-602-2719
www .carlsbadca.gov
I am applying to the City of Carlsbad for the following type(s) of construction permit:
!XI Building Permit D Right-of-Way Permit
D My project is categorically EXEMPT from
the requirement to prepare a storm water
pollution prevention plan (SVVPPP) because it
only requires issuance of one or more of the
following permit types:
Patio/Deck
Photo Voltaic
Re-Roofing
Sign
Spa-Factory
Sprinkler
Electrical
Fire Additional
Fire Alarm
Fixed Systems
Mechanical
Mobile Home
Plumbing Water Discharge
Project Sto1rm Water Threat Assessment Criteria*
No Threat Assessment Criteria
IJI My project qualifies as NO THREAT and is exempt from the requirement to prepare a storm water pollution prevention plan (SWPPP) because
it meets the "no threat" assessmenl criteria on the City's Project Threat Assessment Worksheet for Determination of Construction SWPPP Tier
Level. My project does not meet any of the High, Moderate or Low Threat criteria described below.
Tier 1 -Low Threat Assessment Criteria
D My project does not meet any of the Significant or Moderate Threat criteria, is not an exempt permit type (See list above) and the project
meets one or more of the following criteria:
• Results in some soil disturbance; and/or
• Includes outdoor construction activities (such as saw cutting, equipment washing, material stockpiling, vehicle fueling, waste stockpiling).
Tier 2 -Moderate Threat Assessmen1t Criteria
D My project does not meet any of the Significant Threat assessment Criteria described below and meets one or more of the following criteria:
• Project requires a grading plan pursuant to the Carlsbad Grading Ordinance (Chapter 15.16 of the Carlsbad Municipal Code); or,
• Project will result in 2,500 square feet or more of soils disturbance including any associated construction staging, stockpiling, pavement
removal, equipment storage, refueling and maintenance areas and project meets one or more of the additional following criteria:
• Located within 200 feet of an environmentally sensitive area or the Pacific Ocean, and/or
• Disturbed area is located on a slope with a grade at or exceeding 5 horizontal to 1 vertical, and/or
• Disturbed area is located along or within 30 feet of a storm drain inlet, an open drainage channel or watercourse, and/or
• Construction will be initiaited during the rainy season or will extend into the rainy season (Oct. 1 through April 30).
Tier 3 -Significant Threat Assessme,nt Criteria
D My project includes clearing, grading or other disturbances to the ground resulting in soil disturbance totaling one or more acres including any
associated construction staging, equipment storage, stockpiling, pavement removal, refueling and maintenance areas: and/or
D My project is part of a phased development plan that will cumulatively result in soil disturbance totaling one or more acres including any
associated construction staging, equipment storage, refueling and maintenance areas: or,
D My project is located inside or within 200 feet of an environmentally sensitive area (see City ESA Proximity map) and has a significant
potential for contributing pollutants !o nearby receiving waters by way of storm water runoff or non-storm water discharge(s).
I certify to the best of my knowledge that the above
checked statements are true and correct. I understand
and acknowledge that even though this project does
not require preparation of a construction SWPP, I must
still adhere to, and at all times during construction
activities for the permit type(s) check above comply
with the storm water best management practices
pursuant to Title 15 of the Carlsbad Municipal Code
and to Citv Standards.
Project Address: Assessor Parcel No.
'The City Engineer may authorize minor variances from the Storm
Water Threat Assessment Criteria in special circumstances where it
can be shown that a lesser or higher Construction SWPPP Tier Level is
warranted.
B-24
2121 Palomar Airport Rd, Carlsbad, CA 92011
Owner/Owner's Authorized Agent Name:
Steve White, CEO
Owner/Owner's Authorized Agent Signature: r
City Concurrence: By: Date:
0 YES ONO
Page 1 of 1
213-070-16
Title:
C.E.O.
Date:
1/11/2017
Project ID:
Rev.03/09
INDUSTRIAL WASTEWATER DISCHARGE PERMIT
SCREENING SURVEY
Date 0111112017
Business Name Brookwood Management Partners, LLC
Street Address 2121 Palomar Airport Rd, Carlsbad, CA 92011
Email Address svalentino@brookwoodfinancial.com
PLEASE CHECK HERE IF YOUR BUSINESS IS EXEMPT: (ON REVERSE SIDE CHECK TYPE OF BUSINESS) 0
Check all below that are presient at your facility: None
Acid Cleaning Ink Manufacturing Nutritional Supplement I
Assembly Laboratory Vitamin Manufacturing
Automotive Repair Machining I Milling Painting I Finishing
Battery Manufacturing Manufacturing Paint Manufacturing
Biofuel Manufacturing Membrane Manufacturing Personal Care Products
Biotech Laboratory (i.e. water filter membranes} Manufacturing
Bulk Chemical Storage Metal Casting I Forming Pesticide Manufacturing I
Car Wash Metal Fabrication Packaging
Chemical Manufacturing Metal Finishing Pharmaceutical Manufacturing
Chemical Purification Electroplating {including precursors}
Dry Cleaning Electroless plating Porcelain Enameling
Electrical Component Anodizing Power Generation
Manufacturing Coating (i.e. phosphating) Print Shop
Fertilizer Manufacturing Chemical Etching I Milling Research and Development
Film I X-ray Processing Printed Circuit Board Rubber Manufacturing
Food Processing Manufacturing Semiconductor Manufacturing
Glass Manufacturing Metal Powders Forming Soap I Detergent Manufacturing
Industrial Laundry Waste Treatment/ Storage
SIC Code(s) (if known):
Brief description of business activities (Production I Manufacturing Operations): _____ _
Business Office
Description of operations geinerating wastewater (discharged to sewer, hauled or evaporated):
None other than sanitary waste from restrooms.
Estimated volume of industria1I wastewater to be discharged (gal I day): ___ NI_A ____ _
List hazardous wastes generated (type I volume): ___ N_I_A ___________ _
Date operation began/or will begin at this location:----------------
Have you applied for a Wastewater Discharge Permit from the Encina Wastewater Authority?
Yes No If yes, when: _N_o ___________________ _
Site Contact Sunny Valentino Title Property Manager
Signature Phone No. 760-804-0340 ·------------ENCINA WASTEWATER AUTHORITY, 6200 Avenida Encinas Carlsbad, CA 92011 (760) 438-3941
FAX: (760) 476-9852
Business Name
SAN DIEGO REGIONAL
HAZARDOUS MATERIALS
QUESTIONNAIRE
Brookwood Management Partners, LLC
Business Contact
Sunny Valentino
Project Address
2121 Palomar Airport Rd
Mailing Address
2131 Palomar Airport Rd
City
Carlsbad
City
Carlsbad
OFFICE USE ONLY
RECORD ID# __________________ _
PLAN CHECK# _________________ _
State
CA
State
CA
Telephone#
760-804-0340
Zip Code
92011
Zip Code
92011
BP DATE
APN#
213-070-16
Plan File#
Project Contact Shelly Edwards Applicant E-mail shelly@whiteconstructioninc.com Tele~hone # 760-931-1130
The following questions represent the facility's activities, NOT the specific project description.
PART I: FIRE DEPARTMENT -HAZARDOUS MATERIALS DIVISION: OCCUPANCY CLASSIFICATION: (not required for projects within the City of San
Diego): Indicate by circling the item, whether your business will use, process, or store any of the following hazardous materials. If any of the items are circled,
applicant must contact the Fire Protection Agency with jurisdiction prior to plan submittal. None.
Occupancy Rating: Facility's Square Footage (including proposed project):
1. Explosive or Blasting Agents 5. Organic Peroxides 9. Water Reactives 13. Corrosives
2. Compressed Gases 6. Oxidizers 10. Cryogenics 14. Other Health Hazards
3. Flammable/Combustible Liquids 7. Pyrophorics 11. Highly Toxic or Toxic Materials 15. None of These.
4. Flammable Solids 8. Unstable Reactives 12. Radioactives
PART II: SAN DIEGO COUNTY DEPARTMENT OF ENVIRONMENTAL HEAL TH -HAZARDOUS MATERIALS DIVISION (HMD): If the answer to any of the
questions is yes, applicant must contact the County of San Diego Hazardous Materials Division, 5500 Overland Avenue, Suite 110, San Diego, CA 92123.
Call (858) 505-6700 prior to the issuance of a building permit.
FEES ARE REQUIRED Project Completion Date: Expected Date of Occupancy: 0 CalARP Exempt
I
1.
2.
3.
4.
5.
6.
7.
8.
YES NO (for new construction or remodeling projects)
Is your business listed on the reverse side of this form? (check all that apply). D [xJ
D IXI D !XI
Will your business dispose of Hazardous Substances or Medical Waste in any amount?
Will your business store or handle Hazardous Substances in quantities greater than or equal to 55 gallons, 500
pounds and/or 200 cubic feet?
D
D
D D
D
!XI Will your business store or handle carcinogens/reproductive toxins in any quantity?
[xJ Will your business use an existing or install an underground storage tank?
[xi Will your business store or handle Regulated Substances (CalARP)?
!XI Will your business use or install a Hazardous Waste Tank System (Title 22, Article 10)?
~ Will your business store petroleum in tanks or containers at your facility with a total facility storage capacity equal to
or greater than 1,320 gallons? (California's Aboveground Petroleum Storage Act .
Date Initials
0 CalARP Required
I
Date Initials
0 CalARP Complete
I
Date Initials
PART Ill: SAN DIEGO COUNTY AIR POLLUTION CONTROL DISTRICT (APCD): Any YES* answer requires a stamp from APCD 10124 Old Grove Road, San
Diego, CA 92131 apcdcomp@sdcounty.ca.gov (858) 586-2650). [*No stamp required if Q1 Yes and Q3 Yes and Q4-Q6 No]. The following questions are intended
to identify the majority of air pollution issues at the planning stage. Projects may require additional measures not identified by these questions. For comprehensive
requirements contact APCD. Residences are typically exempt, except -those with more than one building+ on the property; single buildings with more than four
dwelling units; townhomes; condos; mixed-commercial use; deliberate burns; residences forming part of a larger project. ['Excludes garages & small outbuildings.]
1.
2.
3.
4.
5.
6.
YES NO
!XI D D !XI IBl D
Will the project disturb 160 square feet or more of existing building materials?
Will any load supporting structural members be removed? Notification may be required 10 working days prior to commencing demolition.
(ANSWER ONLY IF QUESTION 1 or 2 IS YES) Has an asbestos survey been performed by a Certified Asbestos Consultant or Site Surveillance
Technician?
D
D
D
!XI (ANSWER ONLY IF QUESTION 3 IS YES) Based on the survey results, will the project disturb any asbestos containing material? Notification
may be required 1 O working days prior to commencing asbestos removal.
!xi Will the project or associated construction equipment emit air contaminants? See the reverse side of this form or APCD factsheet
(www.sdapcd.org/info/facts/permits.pdf) for typical equipment requiring an APCD permit.
D (ANSWER ONLY IF QUESTION 5 IS YES) Will the project or associated construction equipment be located within 1,000 feet of a school
bounda
Briefly describe business activities: Lobby & Restrooms of Commercial Office Briefly describe proposed project:
Replace ceiling tile, lighting, finishes
I declare under p~nal!l! of perjury that to the best of my knowledge and belief ttie responses made herein are true .~~d correct. Steve White G.E.O. . ·
Name of Owner or Authorized Agent Signature of Owner or Authorized Agent /r.-----.._ 01/ 11 /2017
Date
FOR OFFICAL USE ONLY:
FIREDEPARTMENTOCCUPANCYCLASSIFICATION:~---------------------------------
BY:~~~~~~~~~~~~~~~~~--~~~~~~~~~~~~ DATE:--~'--'~--
EXEMPT OR NO FURTHER INFORMATION REQUIRED RELEASED FOR BUILDING PERMIT BUT NOT FOR OCCUPANCY RELEASED FOR OCCUPANCY
COUNTY-HMO* APCD COUNTY-HMO APCD COUNTY-HMO APCD
. . *A stamp 1n this box only exempts businesses from completing or updating a Hazardous Materials Business Plan. Other perm1tt1ng requirements may still apply .
HM-9171 /08/15) Countv of San Dieao -DEH -Hazardous Materials Division
.
· {_ City of
Carlsbad
l.llVASTE MANAGEMENT
PLAN
8-59
Development Services
Building Division
1635 Faraday Avenue
760-602-2719
www.carlsbadca.gov
Brookwood Management Partners, LLC
Contractor: White Construction, Inc. Owner:
2121 Palomar Airport Rd, Carlsbad, CA 92011 760-931-1130 Job Address: _______________ _ Phone Number; _________________ _
Permit#:
85,000
Estimated Cost of Project: $ _____________ _
Type of Project: O New Construction [)§ Remodel or T.I. O Residential 1ZJ Commercial ODemolition
(check all that apply) D Other
Non-hazardous construction waste generated during the course of this project shall be recycled and/or salvaged for re-use at a
minimum of 50% per CALGreen Sec. 5.408.1. Failure to comply may result in a penalty fee up to $1,000. For projects which
consist of mainly equipment and/or racking, that have a combined weight of new construction disposal that does not exceed 2
lbs per square foot of building area a1'fected by this permit, may be deemed to meet the 50% minimum requirement upon
approval of Building Department.
ALTERNATIVE FORMS OF COMPLIANCE: (If selected, do not complete Tables 1 & 2 below)
0 Construction waste shall not exceed 2 lbs. per sf. of area. All receipts shall be provided to the Building Official prior to
final. (This option not applicable for most construction projects.)
Square feet of construction area X 2 lbs.= lbs. of allowable waste.
i:) I plan on using a WASTE MANAGEMENT roll-off bin. All receipts shall be provided to the Building Official prior to final.
Table 1-Estimated Waste (To be filled out prior to permit issuance refer to example on Page 2.)
MATERIALS lbs. of waste to be ta ken to lbs. of waste to be Waste Hauling Company or Re-Use Method LANDFILL RE-USED or RECYCLED
Asphalt/ Concrete 1\1/ A
Brick/ Masonry N/A
Cardboard 1 () lhc-i::I"'\('{''\
Drywall i:;n lhc:
Landscape Debris N/A
Lumber/ Wood N/A Millwork sub will recvcle at shnn
Metals 20 EDCO
Mixed Waste 2251bs EDCO
Trash I Garbage 251bs
Other:
TOTAL lbs: 75 2551bs
60 Estimated Percentage to be Re-Used or Recycled ______ %
I certify that the information provided herein, to the best of my knowledge, is true and correct. Steve White
Contractor or Owner (print namer1
Contractor or Owner (signature)
Official Use Only
D Plan Approved O Plan Denied O Project Valuation Approved
Reviewed/ Approved by: _____ , ____________ _
Page 1of 2
Date
01/11/2017