HomeMy WebLinkAbout2200 FARADAY AVE; 205; CB143197; PermitC,ity of Carlsbad
12-24-2014
1635,Faraday Av Carlsbad, CA 92008
Commercial/lnd~strial Permit Permit No: CB143197
Building Inspection Request Line (760) 602-2725
Job Address: 2200 FARADAY AV CBADSt: 205
Permit Type: Tl Sub Type: COMM Status: ISSUED
Applied: 11/18/2014
Entered By: LSM
Parcel No: 2121206000 Lot#: 0
Valuation: $98,120.00 Construction Type: 38
Occupancy Group: Reference# Plan Approved: 12/24/2014
Issued: 12/24/2014
Inspect Area
Plan Check #:
Project Title: REGENTS GYM= CREATE NEW SUITE
FROM EXISTING SUITE 210 2,265 SF OFFICE.TO GYM
Applicant:
JESUS GOMES
STE 290
3900 FIFTH AV
SAN DIEGO CA 92103
619-299-0011 X204
Building Permit
Add'I Building Permit Fee
Plan Check
Add'! Building Permit Fee
Plan Check Discount
Strong Motion Fee
Park Fee
LFM Fee
Bridge Fee
BTD #2 Fee
STD #3 Fee
Renewal Fee
Add'I Renewal Fee
Other Building Fee
Pot. Water Con. Fee
Meter Size
Add'I Pot. Water Con. Fee
Reel. Water Con. Fee
Green Bldg Stands (SB1473) Fee
Fire Expedidted Plan Review
Total Fees:
$621.65
$0.00
$435.16
$0.00
$0.00
$27.47
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$1.00
$0.00
Owner:
·RO F II FARADAY LL C
C/O REGENT PROPERTIES
11990 SAN VICENTE BL VD #200
LOS ANGELES CA 90049
Meter Size
Add'I Reel. Water Con. Fee
Meter Fee
SDCWAFee
CFO Payoff Fee
PFF (3105540)
PFF (4305540)
License Tax (3104193)
License Tax (4304193)
Traffic Impact Fee (3105541)
Traffic Impact Fee (4305541)
PLUMBING TOTAL
ELECTRICAL TOTAL
MECHANICAL TOTAL
Master Drainage Fee
Sewer Fee
Redev Parking Fee
Additional Fees
HMP Fee
Green Bldg Standards Plan Chk
TOTAL PERMIT FEES
$1,376.27 Balance Due:
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$133.00
$78.75
$79.24
$0.00
$0.00
$0.00
$0.00
??
??
$1,376.27
$0.00 ·
Inspector:
FINAL APPROVAL
Date: /.e · tf-I~ Clearance: ------
NOTICE: Please take NOTICE that approval of your project includes the "Imposition" of fees, dedications, reservations, or other exactions hereafter collectively
referred to as "fees/exactions." You have 90 days from the date this permit was issued to protest imposition of these fees/exactions. If you protest them, you must
follow the protest procedwes set forth in Government Code Section 66020(a), and file the protest and any other required information with the City Manager for
processing in accordance with Carlsbad Municipal Code Section 3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack,
review, set aside, void, or annul their imposition. ·
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection fees and capacity
changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this project. NOR DOES IT APPLY to any
fees/exactions of which ou have reviousl been iven a NOTICE similar to this or as to which the statute of limitations has reviousl otherwise ex ired.
«~~ Building Permit Application
Plan Check No. c..BI 4 3 t q-,
Est. Value ~ i, 1 ~ 1635 Faraday Ave., Carlsbad, CA 92008 ~ CITY OF . y-'35"°. l .It> 760-602-2717 / 2718 / 2719 Plan Ck. Deposit CARLSBAD Fax 760-602-8558
www.carlsbadca.gov Date l, I i "1 'Lf lswPPP
JOB ADDRESS SUITE#/.SPACE#/UNII# rPN 2200 FARADAY, CARLSBAD CA 92008 -::ltW-::, N/A -212 -120 -41
CT/PROJECT# ILOT# I PHASE# I# OF UNITS I# BEDROOMS # BATHROOMS 1:;;;;N;SNAME Gtif'\ lcoNSTl~tPE I occ.;ouP
DESCRIPTlo:;r
1
~b~!f!; Square Feet of Affected Area(s) from e>(.\51,rJV" c:P\O c.,r~e., M-<...,,t.:> ~I...U...-l TE..
THIS PROJECT INCLUDES THE BUILD OUT OF NEW BUILDING AMENITY EXERCISE AREA/ROOM (GYM). THE TENANT
IMPROVEMENTS WILL SERVE AS AN ADDITIONAL FREE TENANT'S AMENITY SPACE INCLUDING NON-STRUCTURAL
PARTITIONS, SUSPENDED T-BAR CEILING, LIGHTING, CARPET PER PLAN AND FINISHES PER PLAN.
EXISTING USE
1
PROPOSED USE rARAGE (SF) PATIOS (SF) l DECKS (SF) FIREPLACE I AIR CONDITIONING I FIRE SPRINKLERS
OFFICE EXERCISE ROOM YEsO. No[Z] YES [ljNo D YES[lj NOD
CONTACT NAME (If Different Fom Applicant) APPLICANT NAME JESUS GOMEZ
ADDRESS ADDRESS
3900 FIFTH AVENUE SUITE 290
CITY STATE ZIP CITY STATE ZIP SAN DIEGO CA 92103
PHONE IFAX PHONE
\(~AX 6192990011 6192995544
EMAIL EMAIL
JESUS@DPDESIGNINC.COM
PROPERTY OWNER NAME REGENTS PROPERTIES CONTRACTOR BUS. NAME TRI-VISTA
ADDRESS ADDRESS 116 Market Place Escondido, Ca 92029
CITY STATE ZIP CITY STATE ZIP
ESCONDIDO CA 92025
PHONE tAX PHONE IFAX 17),,;J \0 760-497-0053
EMAIL EMAIL 760-497-0053 / 1 ~b,. f!~f, 00f3
ARCH/OESIGNER NAME & ADDRESS I STATE LIC. # STATE UC.# 'CLASS li't~~l&id--'6°~ 680561
(Sec. 7031.5 Business and Professions Code: Any City or County which requires a permit to construct, alter, improve, demolish or repair any structure, prior to its issuance, also requires the applicant for such permit to file a signed statement that he is licensed pursuant to the provisions of the Contractor's License Law {Chapter 9, commending with Section 7000 of Division 3 of the Business and Professions Code} or that he is exempt therefrom, and the basis for the alleged exemption. Any violation of Section 7031.5 by any applicant for a permit subjects the applicant to a civil penalty of not more than five hundred dollars {$500]).
Workers' Compensation Declaration: / hereby affirm under penalty of perjury one of the following declaraffons:
D I have and will maintain a certificate of consent to self-insure for workers' compensation as provided by Section 3700 of the Labor Code, for the performance of the work for which this permit is issued. !ZI I have and will maintain workers' compensation, as required by Section 3700 of the Labor Code, for the performance of the work for which this permit is issued. My workers' compensation insurance carrier and policy
number are: Insurance Co . STATE FUND COMPENSATION INS. FUND Policy No. 9070945-13 Expiration Date 01/01/2013
]lli§,section need not be completed if the permit is for one hundred dollars ($100) or less. LJ Certificate of Exemption: I certify that in the performance of the work for which this permitis issued, I shall not employ any person in any manner so as to become subject to the Workers' Compensation Laws of
California. WARNING: Failure !~cure ers' compensation coverage is unlawful, and shall subject an employer to criminal penalties and civil fines up to one hundred thousand dollars (&100,000), in
addition to the cost of compensation;!! age ided for in Section 3706 of the Laborcode, interest and attorney's fees •
./i5 CONTRACTORSIGNATURE ' $"-...;:::.:---....~----0AGENT DATE 11 -Jg ..... J
I hereby affirm that I am exempt from Contractor's Ucense Law for the following reason: D I, as owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not intended or offered for sale (Sec. 7044, Business and Professions Code: The Contractor's
License Law does not apply to an owner of property who builds or improves thereon, and who does such work himself or through his own employees, provided that such improvements are not intended or offered for
sale. If, however, the building or improvement is sold within one year of completion, the owner-builder will have the burden of proving that he did not build or improve for the purpose of sale).
0
D
I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions Code: The Contractor's License Law does not apply to an owner of
property who builds or improves thereon, and contracts for such projects with contractor(s) licensed pursuant to the Contractor's License Law).
I am exempt under Section ____ ,Business and Professions Code for this reason:
1.1 personally plan to provide the major labor and materials for construction of the proposed property improvement. 0Yes 0No
2. I (have/ have not) signed an application for a building permit for the proposed work.
3. I have contracted with the following person (firm) to provide the proposed construction (include name address/ phone/ contractors' license number):
4. I plan to provide portions of the work, but I have hired the following person to coordinate, supervise and provide the major work (include name/ address/ phone/ contractors' license number):
5. I will provide some of the work, but I have contracted (hired) the following persons to provide the work indicated (include name/ address/ phone/ type of work):
Ji5 PROPERTY OWNER SIGNATURE AGENT DATE l
Is the applicant or future building occupant required to submit a business~, acutely hazardous materials registration form or risk management and prevention program under Sections 25505, 25533 or 25534 of the
Presley-Tanner Hazardous Substance Account Act? D Yes LL.JNo
Is the applicant or future building occupant required to obtain a permit from the air pollution control district or a!LlJllality management district? 0Yes 0 No
Is the facility to be constructed within 1,000 feet of the outer boundary of a school site? 0Yes L.:LJNo
IF ANY OF THE ANSWERS ARE YES, A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR IS MEETING THE REQUIREMENTS OF THE OFFICE OF
EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT.
I hereby affirm that there is a construction lending agency for the performance of the work this permit is issued (Sec. 3097 (i) Civil Code).
Lender's Name Lender's Address
I certify that I have read the application and state that the above information isoorrectand thatthe information on the plans is accurate. I agree to oomplywith all City ordinances and State laws relating to buildingoonstruction.
I hereby authorize representative of the City of Carlsbad to enter upon the above mentioned property for inspection purposes. I ALSO AGREE TO SAVE, INDEMNIFY AND KEEP HARMLESS THE CITY OF CARLSBAD
AGAINST ALL LIABILITIES, JUDGMENTS, COSTS AND EXPENSES WHICH MAY IN ANY WAY ACCRUE AGAINST SAID CITY IN CONSEQUENCE OF THE GRANTING OF THIS PERMIT.
OSHA: An OSHA permit is required for excavations over 5'0' deep and demolition or oonstruction of structures over 3 stories in height.
EXPIRATION: Every permitissued by the Building Official under the provis· s of this Code shall expire by limitation and become null and void if the building or work authorized by such permitis not commenced within
180 days from the date of such permit or if the b · · o · bysu permit is suspended or abandoned at anytime after the work is commenced fora period of 180 days (Section 106.4.4 Uniform Building Code).
Ji5 APPLICANT'S SIGNATURE DATE \
. •, -..
Inspection List
Permit#: CB143197 Type: Tl
Date Inspection ltein ----------
06/04/2015 89 Final Combo
06/04/2015 89 Final Combo
05/06/2015 89 Final Combo
01/06/2015 17 Interior Lath/Drywall
01/02/2015 21 Underground/Under Floor
12/29/2014 84 Rough Combo
Friday, June 05, 2015
COMM
Inspector Act
RI
PB AP
PB NR
PB NR
PD NR
PB AP
REGENTS GYM= CREATE NEW SUITE
FROM EXISTING SUITE 210 2,265 SF OF
Comments ----
COF
Page 1 of 1
....--~---------~-------· _ ...... -··
,_!·~
I l~it«Ni it,)rjMl',0.RC Wfi ~;.l'.'-mi!!l'l~ _ -,·. I ~-MllBT\l!ltR.EPt1M'fflEJCI; . . l ~=~::::!~~==~~R:~~~~;~N ;_
I ·-$ ~)l:,ll~ -~~!UKimi! •.~·1~1ilClll.•fflil .
--~ . .. ,1
1CBl43Di' · . 22001 fMAIAI AV··tf5/. ,. ··: . _·. _· · :j
ffl;~r ff S G'-~~1 tC~EA lli;; t,J~~t ~Liff~ . . . · -.. ,,;._""' ,.,;.,(.:Ml 'j
!P~;JJl l!tX!J'.Sl'lf~G-~t:fl!'E ~i~ ~?.;::Gt-:i ·:;;r. .Off!c:E I 'I&' '.,.,
11
·:·
n :r;(JM·i~•
llltfJ' .. miSLi5 GC~~es
~It i!i,lffe~lf@'l~!:1,~~lf:;'I; ;• ' . : -,.-1,._,.,..;.,..,,-
EsGil Corporation
In <.Partnersli.ip witli (]overnment for (]3ui(aing Safety
DATE: 12/22/2014
JURISDICTION: Carlsbad
PLAN CHECK NO.: CB14-3197
PROJECT ADDRESS: 2200 Faraday Suite 205
PROJECT NAME: Faraday Gym TI
SET: II
D APPLICANT
D JURIS.
D PLAN REVIEWER
D FILE
~ The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's
codes when minor deficiencies identified below are resolved and checked by building
department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
D The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
D The applicant's copy of the check list has been sent to:
~ EsGil Corporation staff did not advise the applicant that the plan check has been completed.
D EsGil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted:
Date contacted: (by: )
Mail Telephone Fax In Person
D REMARKS:
By: John Le Vey
EsGil Corporation
D GA D EJ D MB D PC
Telephone#:
Email:
Enclosures:
12/16/2014
9320 Chesapeake Drive, Suite 208 + San Diego, California 92123 + (858) 560-1468 + Fax (858) 560-1576
EsGil Corporation
In Q'artnersnip wit/i, qovemment for <Bui{rfing Safety
DATE: 11/26/2014
JURISDICTION: Carlsbad
PLAN CHECK NO.: CB14-3197
PROJECT ADDRESS: 2200 Faraday Suite 250
PROJECT NAME: Faraday Gym TI
SET: I
D APPLICANT
~JURIS.
D PLAN REVIEWER
D FILE
D The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's
codes when minor deficiencies identified below are resolved and checked by building
department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
lZ] The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
D The applicant's copy of the check list has been sent to:
D EsGil Corporation staff did not advise the applicant that the plan check has been completed.
lZ] EsGil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Jesus Gomez Telephone#: 619-299-0011x204
~ pate contacted: rt,} \ (by\fA-Email: jesus@dpdesigninc.com
~ail Telephone Fax In Person
D REMARKS:
By: John Le Vey
EsGil Corporation
D GA D EJ D MB D PC
Enclosures:
11/20/2014
9320 Chesapeake Drive, Suite 208 + San Diego, California 92123 + (858) 560-1468 + Fax (858) 560-1576
Carlsbad CB14-3197
11/26/2014
PLAN REVIEW CORRECTION LIST
TENANT IMPROVEMENTS
PLAN CHECK NO.: CB14-3197
OCCUPANCY: B
TYPE OF CONSTRUCTION: IIIB
ALLOWABLE FLOOR AREA:
SPRINKLERS?: Yes
REMARKS:
DATE PLANS RECEIVED BY
JURISDICTION: 11/18/2014
DATE INITIAL PLAN REVIEW
COMPLETED: 11/26/2014
FOREWORD (PLEASE READ):
JURISDICTION: Carlsbad
USE: Gym
ACTUAL AREA: 2265
STORIES: 2
HEIGHT: unknown
OCCUPANT LOAD: 33
DATE PLANS RECEIVED BY
ESGIL CORPORATION: 11/20/2014
PLAN REVIEWER: John Le Vey
This plan review is limited to the technical requirements contained in the California version of
the International Building Code, Uniform Plumbing Code, Uniform Mechanical Code, National
Electrical Code and state laws regulating energy conservation, noise attenuation and access for
the disabled. This plan review is based on regulations enforced by the Building Department.
You may have other corrections based on laws and ordinances enforced by the Planning
Department, Engineering Department, Fire Department or other departments. Clearance from
those departments may be required prior to the issuance of a building permit.
Code sections cited are based on the 2013 CBC, which adopts the 2012 IBC.
The following items listed need clarification, modification or change. All items must be satisfied
before the plans will be in conformance with the cited codes and regulations. Per Sec. 105.4 of
the 2012 International Building Code, the approval of the plans does not permit the violation of
any state, county or city law.
To speed up the recheck process, please note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet number, specification section, etc.
Be sure to enclose the marked up list when you submit the revised plans.
Carlsbad CB14-3197
11/26/2014
Please make all corrections, as requested in the correction list. Submit FOUR new
complete sets of plans for commercial/industrial projects (THREE sets of plans for
residential projects). For expeditious processing, corrected sets can be submitted
in one of two ways:
1. Deliver all corrected sets of plans and calculations/reports directly to the City of
Carlsbad Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760)
602-2700. The City will route the plans to EsGil Corporation and the Carlsbad
Planning, Engineering and Fire Departments.
2. Bring one corrected set of plans and calculations/reports to EsGil Corporation,
9320 Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-1468.
Deliver all remaining sets of plans and calculations/reports directly to the City of
Carlsbad Building Department for routing to their Planning, Engineering and Fire
Departments.
NOTE: Plans that are submitted directly to EsGil Corporation only will not be
reviewed by the City Planning, Engineering and Fire Departments until review by
EsGil Corporation is complete.
1. Please correct the plans to show the suite # 250
2. Please provide a door schedule; indicate the type of hardware and reference the
doors on the floor plan.
3. Please clearly show the location of the new transformer is it mounted on the floor ,
ceiling please specify
4. Please provide plans and calculations signed by the California State licensed
engineer or architect for the structural support of the 993# rooftop air handler
units. Include all calculations and finding on the plans. Please include the
California license number, seal, date of license expiration and date plans are
signed. Business and Professions Code. Correct the scope of work on the cover
sheet, it states no new mechanical equipment
5. Please complete the L Tl-02-E forms 1 of 5 and 2 of 3
6. Please complete the LTl-01-E 2 of 5
7. Voltage drop is limited to 2% on feeders and 3% on branch circuits. Provide
worst case voltage drop calculations (feeders<2% and branch circuits<3%) per
ES 130.5(c). For the new electrical panel EL-A-G
8. Please show the trap primers on the equipment schedule
9. Please correct the venting for the plumbing it does not meet the required
aggregated area of the building sewer.
Carlsbad CB14-3197
11/26/2014
Advisory Note : When alterations, structural repairs or additions are made to an
existing building, that building, or portion of the building affected, is required to
comply with all of the following requirements, per Section 11 B-202.4:
• The area of specific alteration, repair or addition must comply as "new"
construction.
• Existing toilet and bathing facilities that serve the remodeled area must be
shown to comply with all accessibility features.
• Please address the following comments that are the result of the alterations.
10. Please correct the standard shower measurements per the CBC 118608,
measurements and locations are not correct, and the details do not match the
plans
11. Show that the minimum strike edge distances are provided at the level area on the
side to which a door (or a gate) swings, per Section 11 B-404.2.4:
a) ~18" at interior conditions.
12. Show a level area, or landing, per Section 11 B-404.2.4:
~60" in the direction of door swing
13. It is unclear from the plans if the restrooms servicing the tenant improvement are
disabled accessible, please provide a dimensioned restroom plans showing the
restroom to be accessible compliant.
14. For water closet compartments having side-opening doors, compliance with the
following figure must be shown on the plans. The door shall be in the partition
farthest from the water closet and shall be 4" maximum from the front partition.
15. At least one side partition at the accessible water closet(s) must have a toe
clearance of at least 9" (unless the stall width is increased to 66"). Section 11 B-
604.8.1.4. you show 5 feet 5 inches.
16. Hot water supplied to a public use lavatory is limited to a maximum temperature
potential of 120 degrees by a device that conforms to ASSE 1070 or CSA
8125.3; please provide the manufacturer's listing showing compliance. Detail
how this temperature limitation is achieved. The water heater thermostat may not
be used for compliance with this Code section. UPC 413.1 & UPC 414.
17. Plans shall indicate that drinking fountains comply with Section 11 B-602.9 as
either:
a) Located completely in an alcove, ~32" in width and ~18" in depth.
b) Positioned completely between wing walls.
Carlsbad CB14-3197
11/26/2014
c) Positioned to not encroach into accessible pedestrian ways.
To speed up the review process, note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet, note or detail number,
calculation page, etc.
Please indicate here if any changes have been made to the plans that are not a
result of corrections from this list. If there are other changes, please briefly
describe them and where they are located in the plans.
Have changes been made to the plans not resulting from this correction
list? Please indicate: D Yes D No
The jurisdiction has contracted with Esgil Corporation located at 9320
Chesapeake Drive, Suite 208, San Diego, California 92123; telephone number of
858/560-1468, to perform the plan review for your project. If you have any
questions regarding these plan review items, please contact John Le Vey at
Esgil Corporation. Thank you.
I( I ' '
Carlsbad CB14-3197
11/26/2014
[DO NOT PAY -THIS IS NOT AN INVOICE]
VALUATION AND PLAN CHECK FEE
JURISDICTION: Carlsbad
PREPARED BY: John Le Vey
PLAN CHECK NO.: CB14-3197
DATE: 11/26/2014
BUILDING ADDRESS: 2200 Faraday Suite 250
BUILDING OCCUPANCY: B
BUILDING AREA Valuation Reg.
PORTION ( Sq. Ft.) Multiplier Mod.
Tl per city
Air Conditioning
Fire Sprinklers
TOTAL VALUE
Jurisdiction Code cb By Ordinance
Bldg. Permit Fee by Ordinance
Plan Check Fee by Ordinance
Type of Review: El Complete Review
VALUE
D Structural Only
D Repetitive Fee 3 Repeats
D Other
D Hourly
EsGil Fee
1--------11 Hr. @ •
Comments:
($)
98,120
98,120
$618.171
$401.81 I
$346.181
Sheet 1 of 1
macvalue.doc +
/
. 4-
/41 ~-.
~-~·}··' ~ CITY OF
CARLSBAD
PLAN CHECK
REVIEW
TRANSMITTAL
Community & Economic
Development Department
1635 Faraday Avenue
Carlsbad CA 92008
www.carlsbadca.gov
DATE: 12/05/14 PROJECT NAME: FARADAY AVE GYM PROJECT ID: CB143197
PLAN CHECK NO: 1 SET#: ADDRESS: 2200 FARADAY AVE STE #205 APN:
VALUATION: $98,120 CONVERT OFFICE TO.GYM PER APPLICANT JUST FOR THE TENANTS ONLY
This plan check review is complete and has been APPROVED by the ENGINEERING
Division.
By: KATHLEEN LAWRENCE 12/05/14
A Final Inspection by the Division is required Yes I No
. This plan check review is NOT COMPLETE. Items missing or incorrect are listed on
the attached checklist. Please resubmit amended plans as required.
Plan Check Comments have been sent to: JESUS@DPDESIGNINC.COM
You may also have corrections from one or more of the divisions listed below. Approval
from these divisions may be required prior to the issuance of a building permit.
Resubmitted plans should include corrections from all divisions.
For questions or clarifications on the attached checklist please contact the following reviewer as marked:
PLANNING· ENGINEERl'N'G FIR·E:· PREVENTION
760-602-46l0 760-ij02-2750 760-602-4695
Chris Sexton ,I Kathleen Lawrence
7G0-602-"'!,62~l-760-602-27 41 -;· 'O('-GtJ:?-~t~:,;13_::~
Chris.Sexton@carlsbadca.gov Kathleen.Lawrence@carlsbadca.gov Gregory.Ryan@carlsbadca.gov
Gina Ruiz u Onti11En-os (~ f"t \/ \,\l f) .... p ';,~ _'I. ~ ~ "" J i ,:;.
760-802-4675 760-602-2773 ?60-6Cn-·-:6G?
Gina.Ruiz@carlsbadca.gov Linda.Ontiveros@carlsbadca.gov Cynthia.Wong@carlsbadca.gov
,,
Domini•: Fled
7 60-602~4664
Dominic.Fieri@carlsbadca.gov
Remarks:
PER APPLICANT GYM JUSTFORTHETENANTS NOT OPEN TO THE PUBLIC SEE ATTACHED EMAIL
~~ « .. ( ·.
~ CITY OF
CARLSBAD
BUILDING PLANCHECK
CHECKLIST
QUICK-CHECK/APPROVAL
Development Services
Land Development Engineering
1635 Faraday Avenue
760-602-2750
www.carlsbadca.gov
ENGINEERING Plan Check for C8143197 Date: 12/05/14
Project Address: 2200 FARADAY AVE STE #205 APN:
CONVERT OFFICE TO GYM PER APPLICANT
Project Description: JUST FOR THE TENANTS ONLY Valuation: $98,120
ENGINEERING Contact : Kathleen Lawrence
Phone: 760-602-27 41
Email: kathleen.lawrence@carlsbadca.gov
Fax: 760-602-1052
[] RESIDENTIAL INTERIOR
C] RESIDENTIAL ADDITION
<$20,000>
i--] CARLSBAD PREMIER OUTLETS
0 OTHER: --LEGOLAND
IZJ TENANT IMPROVEMENT
CJ PLAZA CAMINO REAL
[] COMPLETE OFFICE BUILDING
r··-··-··-··-··-··-··-··-··-··-··-··-··-··-··-··-··-··-··, OFFICIAL USE ONLY
E-36
ENGINEERING AUTHORIZATION TO ISSUE BUILDING PERMIT
BY: KATHLEEN LAWRENCE
REMARKS: NO NEW ENG FEES
DATE: 12/05/14
Notification of Engineering APPROVAL has been sent to JESUS@DPDESIGNINC.COM
via EMAIL on 12/05/14
Page 1 of 1 REV 4/30/11
Kathleen Lawrence
From:
Sent:
To:
Jesus Gomez <jesus@dpdesigninc.com>
Friday, December 05, 2014 1:51 PM
Kathleen Lawrence
Subject: Re: CB 14-3197
That is absolutely correct. Not for public access
Sent from my iPhone
On Dec 5, 2014, at 12: 36 PM, Kathleen Lawrence
< Kathleen.Lawrence@carlsbadca.gov> wrote:
<imageOO 1. gif->
Jesus,
Is the gym proposed at 2200 Faraday Avenue planck no. CB 14-3197 just
for the tenants and not for the public? ·
Thank you.
Kathleen
Eng. Counter
<image002.gif>
KATHLEEN LAWRENCE
ENGINEERING TECHNICIAN II
LAND DEVELOPMENT ENGINEERING
1635 FARADAY AVE
760.602.2741
760-602.1052
1
«~t> ~ CITY OF
CARLSBAD
PLANNING DIVISION
BUILDING PLAN CHECK
APPROVAL
P-29
DATE: 11-20-14 PROJECT NAME: PROJECT ID:
Development Services
Planning Division
1635 Faraday Avenue
(760) 602-4610
www.carlsbadca.eov
PLAN CHECK NO: CB 14-3197 SET#: 1 ADDRESS: 2200 Faraday Av APN: 212-120-41-00
C8J This plan check review is complete and has been APPROVED by the Planning
Division.
By: Chris Sexton
A Final Inspection by the Planning Division is required D Yes [ZI No
You may also have corrections from one or.more of the divisions listed below. Approval
from these divisions may be required prior to the issuance of a building permit.
Resubmitted plans should include corrections from all divisions.
D This plan check review is NOT COMPLETE. Items missing or incorrect are listed on
the attached checklist. Please resubmit amended plans as required.
Plan Check APPROVAL has been sent to:
For questions or clarifications on the attached checklist please contact the following reviewer as marked:
PLANN·ING ENGINEERING FIRE PREVENTION
760-602-4610 760-602-2750 760-602-4665
~ Chris Sexton D Kathleen Lawrence D Greg Ryan
760-602-4624 760-602-27 41 760-602-4663
Chris.Sexton@carlsbadca.gov Kathleen.Lawrence@carlsbadca.gov Gregory.Ryan@carlsbadca.gov
D Gina Ruiz D Linda Ontiveros D Cindy Wong
760-602-4675 760-602-2773 760-602-4662
Gina.Ruiz@carlsbadca.gov Linda.Ontiveros@carlsbadca.gov Cynthia.Wong@carlsbadca.gov
D D D Dominic Fieri
760-602-4664
Dominic.Fieri@carlsbadca.gov
Remarks: convert office to amenity exercise area only for building tenants
& ~ CITY OF
CAR·LSBAD
PLAN CHECK
REVIEW
TRANSMITTAL
DATE: 12/8/14 PROJECT NAME: regents gym PROJECT ID:
Community & Economic
Development Department
1635 Faraday Avenue
Carlsbad CA 92008
www.carlsbadca.gov
PLAN CHECK NO: cb143197 SET#: I -ADDRESS: 2200 faraday #210 AP~
~co~
!ZI This plan check review is complete and has been ~FtRYliED by the fire Division. ~y'O.
By: cwong v
A Final Inspection by the Division is required [8'] Yes D No
D This plan check review is NOT COMPLETE. Items missing or incorrect are listed on
the attached checklist. Please resubmit amended plans as required.
Plan Check Comments have been sent to jesus@dp-designinc.com
You may also have corrections from one or more of the divisions listed below. Approval
from these divisions may be required prior to the issuance of a building permit.
Resubmitted plans should include corrections from all divisions.
For questions or clarifications on the attached checklist please contact the following reviewer as marked:
-
PLANNING
760-602-4610
D Chris Sexton
760-602-4624
Chris.Sexton@carlsbadca.gov
D Gina Ruiz
760-602-4675
Gina.Ruiz@carlsbadca.gov
D
Remarks:
12/8/14
**APPROVED:
ENGINEERING
760-602-2750
D Kathleen Lawrence
760-602-27 41
Kathleen.Lawrence@carlsbadca.gov
D Linda Ontiveros
760-602-2773
Linda.Ontiveros@carlsbadca.gov
D
Page 1 of2
FIRE PREVENTION
760-602-4665
D Greg Ryan
760-602-4663
Gregory.Ryan@carlsbadca.gov
~ Cindy Wong
760-602-4662
Cynthia.Wong@carlsbadca.gov
D Dominic Fieri
760-602-4664
Dominic.Fieri@carlsbadca.gov
~THIS PROJECT HAS BEEN REVIEWED AND APPROVED FOR THE PURPOSES OF ISSUEANCE
· OF A BUILDING PERMIT.
TIDS APPROVAL IS SUBJECT TO FIELD INSPECTIONS, ANY REQUIRED TESTS, FIRE
DEPARTMENT NOTATIONS, CONDITIONS IN CORRESPONDENCE AND COMPLIANCE WITH
ALL APPLICABLE CODES AND REGULATIONS.
TIDS APPROVAL SHALL NOT BE HELD TO PERMIT OR APPROVE ANY VIOLATION OF THE
LAW.
Page2 of2
··Carlsbad Fire Department
Plan Review Requirements Category: TI , COMM
Date of Report: 12-08-2014-
Name:
Address:
Permit#: CB143197
TRIVISTA CONTRACTORS INC
STE423
970WVALLEYPARKWAY
ESCONDIDO CA
92025
Job Name: REGENTS GYM= CREATE NEW SUITE
Job Address: 2200 FARADAY AV CBAD St: 205
Conditions:
Cond: CON0007904
[MET]
**APPROVED:
Reviewed by:_~~,---~---,
THIS PROJECT HAS BEEN REVIEWED AND APPROVED FOR THE PURPOSES OF ISSUEANCE OF A
BUILDING PERMIT.
THIS APPROVAL IS SUBJECT TO FIELD INSPECTIONS, ANY REQUIRED TESTS, FIRE DEPARTMENT
NOTATIONS,
CONDITIONS IN· CORRESPONDENCE AND COMPLIANCE WITH ALL APPLICABLE CODES AND
REGULATIONS.
THIS APPROVAL SHALL NOT BE HELD TO PERMIT OR APPROVE ANY VIOLATION OF THE LAW.
Entry: 12/08/2014 By: cwong Action: AP
.( SR CT l C LCUl NS
F y y
TIEN 1 E r? it IENTS
CARLSBAD, CA
Prepared For:
REGENTS PROPERTIES
MEC Project No.; 1461.
Date Issued: __ l2ll2ll4
Revision Dates:
Prepared By:
C EFF !CNGINEERING
& CONSULTING
A P R O F l: S $ l O x A l. C O R P O R A f f (_> N
1991 VILLAGE PARK WAY SUITE 115
ENCINITAS, CA 92024
T (760) 479-9838 F (760) 479-9837
www.mcneffengineering.com
'
McNEFF ENGINEERING
& CONSULTING
A ?f:OHSSIONAL COIU'ORATH)N
1991 Village Park Way, Suite 'l 15
Enclnilas, CA 92024
Tei: (760} 47!Ml838 .. fax: (760) 479~9837 . .
JOf.l \q(:?l
SHZEfNO.
CALCUl.ATED BY
Cl-lE!::KEo av
~r~i. fi::i~ I\ 'C I ' 7
OF tf
\v\AJ\J\ DATF. 10/tdl4
OATI:
i
' 1 '--+----1 --·-t ·-
w<•~ ,: u--L-Wl
' ' -;.. -··t." ; 'l
, j -r----r----r-
.......... 1 __ ~~ ~--->---· ~!----~_j,,..,-~ .. ~
i i : ~ I
< i ~ {
i r·-·
l j -,----+--~-~_,..,._,_.,..,........,..,.,,.,
!
··tt·r-::"h,w-j
McNEFf ENGINEERING JCB \L\ lo\
& CONSULTING 2. SH=TNO. OF
J A PnOHSS!ONAL CORPO!tAllON
i991 Village Park Way, Suite 115 CAtCULA TEO $Y. PATE
Encinitas, CA 92024 CHECKEOaY DATE
Tel: (760) 479--9838 .. Fax: {760) 47!;M1837
SCALE
! ! --+----i'~-!-.-l ---J.--i.l ______ ,_ 1, .. ,<--. I ,
•l---+--1----i.._-'i-....
t ... -------· .. --r
j
McNEFf ENGINEERING
& CONSULTING
A f'l<OfESS!ONAt CORPORAilON
i991 Village Park Way, Suito 115
Encinitas, CA 92024
Te!: (760} 479·9838 • Fax: {160) 479~9837
l
i
JOS \4 {ol
?; SHEE'fNO. __ .._:::;;;._ ____ _ Or ____ .,_ ____ _
CALCULATEPSY __________ _ OA'tE: ________ _
CHECKEO SY ___________ _ DATE ________ _
I _ _,..;,._-, ____ , ... , ... _.
--4---1---... ,_ .. , ·--
; I ' . ---~ -----.----;---t---1 t _4-_...,l _-!-__,,j!-,--~~~--·-~
! 'i i l
'
---~ ; .. l_,_J ... J __ .. i L .... L. .. L ..... ' \ ' . . ' ! '
........ J .. L.. _; .. J .... 1.J ___ , .. ~ ... .J ! ~ ~ l> ; i 1---~
-~~~~~~"'*"--4---4_..,1__;__-4-_,~_J--l--!-_;.!_..j_-J' __ , i ! ! i r ..... ,---------1
' i f "-"f '"""' 1--.;-......... -· ......... , __ _
! ( ! i -+-;...----,......,.....+,--+--+=r:-i-.--+--+--+-~;---·-
'
·--....---+-----
---l---~---i---1---+ ....... j------·---
' l --r----
l
.I
McNEFF ENGINEERING
& CONSULTING
A PROJ'ES:.IONAL CORP·ORAT!ON
1991 vmage Park Way, Suite 115
Encinitas, CA 92024
Tel: (760} 479--9838 ,.. Fax: (760} 47fH}837
JOB_,..:....4..:....f.c>c.-l,__ __________ _
SHEITTNO. _____ .__ ______ _
CALCl.ll.ATEO SY.-----------
CHIECKED RY·------------
I
--i----i..:....-L
D OF----4-+-------
DATE _________ _
DATE _________ _
l ___ L
i
,J __ _
i l
..__ ' S1~TE OF CALIFORNIA
MECHANICAL SYSTEMS
CEC-NRCC-MCH-01-E (Revised 06/14 i CALIFORNIA ENERGY COMMISSIOt.."·
CERTIFICATE OF COMPLIANCE NRCC-MCH-01-E
Mechanical Systems (Page 1 of 3)
Project Name: Faraday Gym Date Prepared: 11/5/2014
MECHANICAL COMPLIANCE FORMS & WORKSHEETS (check box if worksheet is included)
For detailed instructions on the use of this and all Energy Efficiency Standards compliance forms, refer to the 2013 Nonresidential Manual
Note: The Enforcement Agency may require all forms to be incorporated onto the building plans.
YES NO Form/Worksheet# Title
Ill D NRCC-MCH-01-E (Part 1 of 3) Certificate of Compliance, Declaration. Required on plans for all submittals.
l!'.'.I D NRCC-MCH-01-E (Part 2 of 3) Certificate of Compliance, Required Acceptance Tests (MCH-02A to 11A). Required on plans for all submittals.
Ill D NRCC-MCH-01-E (Part 3 of 3) Certificate of Compliance, Required Acceptance Tests (MCH-12A to 18A). Required on plans where applicable.
Ill D NRCC-MCH-02-E (Part 1 of 2) Mechanical Dry Equipment Summary is required for all submittals with Central Air Systems. It is optional on plans.
Ill D NRCC-MCH-02-E (Part 2 of 2) Mechanical Wet Equipment Summary is required for all submittals with chilled water, hot water or condenser water
systems. It is optional on plans.
Ill D NRCC-MCH-03-E Mechanical Ventilation and Reheat is required for all submittals with multiple zone heating and cooling systems. It is
optional on plans.
MECHANICAL HVAC ACCEPTANCE FORMS (check box for required forms) 11111
Designer:
11
This form is to be used by the designer and attached to the plans. Listed below are all the acceptance tests for HVAC systems. The designer is required to check the applicable boxes for all
acceptance tests that apply and list all equipment that requires an acceptance test. All equipment of the same type that requires a test, list the equipment description and the number of systems.
·~ 1--
Installing Contractor:
The contractor who inst.ailed t~e equipment is responsible to either conduct the acceptance test them self or have a qualified entity run the test for them. If more than one person has
responsibility for the acceptance testing, each person shall sign and submit the Certificate of Acceptance applicable to the portion of the construction or installation for which they are responsible.
--tj
Enforcement Agency:
Plan check-The NRCC-MCH-01-E form is not considered a completed form and is not to be accepted by the building department unless the correct boxes are checked.
Inspector-Before occupancy permit is granted all newly installed process systems must be tested to ensure proper operations.
Test Description MCH-02A MCH-03A MCH-04A MCH-0SA MCH-06A MCH-07A MCH-08A MCH-09A MCH-lOA MCH-llA
Equipment #of Outdoor Single Zone Air Economizer Demand Supply Fan Valve Leakage Supply Water Hydronic Automatic
Requiring Testing units Air Unitary Distribution Controls Control VAV Test Temp. Reset System Demand Shed
or Verification Ducts Ventilation Variable Flow Control
(DCV) Control
Trane WSC090 1 Ill IZI D IZI Ii'.) D D D D D
D D D D D D D D D D
D D D D D D D D D D
D D D D D D D D D D
D D D D D D D D D D
D D D D D D D D D D
CA Building Energy Efficiency Standards -2013 Nonresidential Compliance ca,c+,,?>l?i',
ST/\TE OF CALIFORNIA
MECHANICAL.SYSTEMS
CEC-NRCC-MCH-01-E (Revised 06/14 CALIFORNIA ENERGY COMMISSIOI\
CERTIFICATE OF COMPLIANCE NRCC-MCH-01-E
Mechanical Systems (Page 2 of 3)
Project Name: Faraday Gym Date Prepared: 11/5/2014
MECHANICAL HVAC ACCEPTANCE FORMS (check box for required forms)
Designer:
This form is to be used by the designer and attached to the plans. Listed below are all the acceptance tests for HVAC systems. The designer is required to check the applicable boxes for all
acceptance tests that apply and list all equipment that requires an acceptance test. Alf equipment of the same type that requires a test, list the equipment description and the number of systems.
Installing Contractor:
The contractor who installed the equipment is responsible to either conduct the acceptance test them self. or have a qualified entity run the test for them. If more than one person has
responsibility for the acceptance testing, each person shall sign and submit the Certificate of Acceptance applicable to the portion of the construction or installation for which they are responsible.
The following tests require a
Enforcement Agency:
Plan check-The NRCC-MCH-01-E form is not considered a completed form and is not to be accepted by the building department unless the correct boxes are checked.
Inspector -Before occupancy permit is granted all newly installed process systems must be tested to ensure proper operations.
Test Description MCH-12A MCH-13A MCH-14A MCH-lSA MCH-16A MCH-17A MCH-18A
Equipment #of Fault Detection & Automatic Fault Distributed Energy Thermal Energy Supply Air Condenser Water ECMS
Requiring Testing units Diagnostics for DX Detection & Storage DX AC Storage (TES) Temperature Reset Reset Controls
or Verification Units Diagnostics for Air & Systems Systems Controls
Zone
Trane WSC0901 1 IZl D D D D D D
D D D D D D D
D D D D D D D
D D D D D D D
D D D D D D D
D D D D D D D
D D D D D D D
D D D D D D D
D D D D D D D
D D D D D D D
CA Building Energy Efficiency Standards -2013 Nonresidential Compliance . June 2014
(!
STATE OF CALIFORNIA.
MECHANICAL SYSTEMS
CEC-NRCC-MCH-01-E (Revised 06/14 ~4 CALIFORNIA ENERGY COMMISSIOI\~'
CERTIFICATE OF COMPLIANCE NRCC-MCH-01-E
Mechanical Systems (Page 3 of 3)
ProjectName: Faraday Gym DatePrepared: 11/5/2014
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT rYJ ~ 1. I certify that this Certificate of Compliance documentation is accurate and complete.
Documentation Author Name: Mark Gallant, CEPE Documentation Author Signature:
Company: Gallant Energy Consulting Signature Date: 111512014
Address: 508 W Mission Ave Ste 201 CEA/ HERS Certification Identification (if applicable):
City/State/Zip: Escondido, CA 92025 Phone: 760-743-5408
RESPONSIBLE PERSON'S DECLARATION STATEMENT
I certify the following under penalty of perjury, under the laws of the State of California:
1. The information provided on this Certificate of Compliance is true and correct.
2. I am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design or system design identified on this Certificate of Compliance (responsible
designer).
3. The energy features and performance specifications, materials, components, and manufactured devices for the building design or system design identified on this Certificate of Compliance
conform to the requirements ofTitle 24, Part 1 and Part 6 of the California Code of Regulations.
4. The building design features or system design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance documents,
worksheets, calculations, plans and specifications submitted to the enforcement agency for approval with this building permit application.
5. I will ensure that a completed signed copy of this Certificate of Compliance shall be made available with the building permit(s) issued for the building, and made available to the enforcement
agency for all applicable inspections. I understand that a completed signed copy of this Certificate of Compliance is required to be included with the documentation the builder provides to the
building owner at occupancy.
Responsible Designer Name: Mike Mayer Responsible Designer Signature:
Company: REM Mechanical Date Signed:
Address: 1075 Linda Vista Drive, Ste A License:
City/State/Zip: San Marcos, CA 92078 Phone: 760-471-1755
CA Building Energy Efficiency Standards -2013 Nonresidential Compliance June 2014
STATE OF CALIFORNIA
HVAC SYSTEM REQUIREMENTS
CEC-NRCC-MCH-02-E Revised 06/14 CALIFORNIA ENERGY COMMISSION ~-
CERTIFICATE OF COMPLIANCE NRCC-MCH-02-E
HVAC Dry System Requirements (Page 1 of 3)
ProjectName: Faraday Gym Date Prepared: 11/5/2014
Equipment Tags and System Description1 Retail Mech. Syst,
MANDATORY MEASURES T-24 Sections Reference to the Requirements in the Contract Documents2
Heating Equipment Efficiency3 110.1 or 110.2(a) Sheet M-1
Cooling Equipment Efficiency3 110.1 or 110.2(a) Sheet M-1
HVAC or Heat Pump Thermostats 110.2(b), 110.2(c) Sheet M-1
Furnace Standby Loss Control 110.2(d) Sheet M-1
Low leakage AH Us. 110.2(f) Sheet M-1
Ventilation4 120.l(b) Sheet M-1
Demand Control Ventilation5 120.l(c)4 Sheet M-1
Occupant Sensor Ventilation Control6 120.l(c)S, 120.2(e)3 Sheet M-1
Shutoff and Reset Controls7 120.2(e) Sheet M-1
Outdoor Air and Exhaust Damper Control 120.2(f) Sheet M-1
Isolation Zones 120.2(g) Sheet M-1
Automatic Demand Shed Controls 120.2(h) Sheet M-1
Economizer FDD 120.2(i) Sheet M-1
Duct Insulation 120.4 Sheet M-1
PRESCRIPTIVE MEASURES
Equipment is sized in conformance with 140.4(a & b) y
140.4 (a & b)
Supply Fan Pressure Control 140.4(c) Sheet M-1
Simultaneous Heat/Cool8 140.4(d) Sheet M-1
Economizer 140.4(e) Sheet M-1
Heat and Cool Air Supply Reset 140.4(f) Sheet M-1
Electric Resistance Heating9 140.4(g) Sheet M-1
Duct Leakage Sealing and Testing.10 140.4(1) Sheet M-1
Notes:
1. Provide equipment tags (e.g. AHU 1 to 10) and system description (e.g. Single Duct VAV reheat) as appropriate. Multiple units
with common requirements can be grouped together.
2. Provide references to plans (i.e. Drawing Sheet Numbers) and/or specifications (including Section name/number and relevant
paragraphs) where each requirement is specified. Enter "NIA" if the requirement is not applicable to this system.
3. The referenced plans and specifications must include all of the following information: equipment tag, equipment nominal
capacity, Title 24 minimum efficiency requirements, and actual rated equipment efficiencies. Where multiple efficiency
requirements are applicable (e.g. full-and part-load) include all. Where appliance standards apply (110.1), identify where
equipment is required to be listed per Title 20 1601 et seq.
4. Identify where the ventilation requirements are documented for each central HVAC system. Include references to both central
unit schedules and sequences of operation. If one or more space is naturally ventilated identify where this is documented in the
plans and specifications. Multiple zone central air systems must also provide a MCH-03-E form.
5. If one or more space has demand controlled ventilation identify where it is specified including the sensor specifications and the
sequence of operation.
6. If one or more space has occupant sensor ventilation control identify where it is specified including the sensor specifications and
the sequence of operation
7. If the system is DOC identify the sequences for the system start/stop, optimal start, setback (if required) and setup (if required).
For all systems identify the specification for the thermostats and time clocks (if applicable).
8. Identify where the heating, cooling and deadband airflows are scheduled for this system. Include a reference to the
specification of the zone controls. Provide a MCH-03-Eform.
9. Enter N/A if there is no electric heating. If the system has electric heating indicate which exception to 140.4(g) applies.
10. If duct leakage sealing and testing is required, a MCH-04-Aform must be submitted.
CA Building Energy Efficiency Standards -2013 Nonresidential Compliance June 2014
STATE OF CALIFORNIA
HVAC SYSTEM REQUIREMENTS • CEC-NRCC-MCH-02-E (Revised 06/13) CALIFORNIA ENERGY COMMISSION -
CERTIFICATE OF COMPLIANCE NRCC-MCH-02-E
HVAC Wet System Requirements (Page 3 of 3)
Project Name: Faraday Gym I Date Prepared: 11/5/2014
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT FY/ ~ 1. I certify that this Certificate of Compliance documentation is accurate and complete.
Documentation Author Name: Mark Gallant, CEPE Documentation Author Signature:
Company: Gallant Energy Consulting Signature Date: 11/5/2014
Address: 508 W Mission Ave Ste 201 CEA/ HERS Certification Identification (if applicable):
City/State/Zip: Escondido, CA 92025 Phone: 760-7 43-5408
RESPONSIBLE PERSON'S DECLARATION STATEMENT
I certify the following under penalty of perjury, under the laws of the State of California:
1. The information provided on this Certificate of Compliance is true and correct.
2. I.am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design or system design
identified on this Certificate of Compliance (responsible designer).
3. The energy features and performance specifications, materials, components, and manufactured devices for the building design or system
design identified on this Certificate of Compliance conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of
Regulations.
4. The building design features or system design features identified on this Certificate of Compliance are consistent with the information
provided on other applicable compliance documents, worksheets, calculations, plans and specifications submitted to the enforcement
agency for approval with this building permit application.
5. I will ensure that a completed signed copy of this Certificate of Compliance shall be made available with the building permit(s) issued for the
building, and made available to the enforcement agency for all applicable inspections. I understand that a completed signed copy of this
Certificate of Compliance is required to be included with the documentation the builder provides to the building owner at occupancy.
Responsible Designer Name: Mike Mayer Responsible Designer Signature:
Company: REM Mechanical Date Signed:
Address: 1075 Linda Vista Drive, Ste A License:
City/State/Zip: San Marcos, CA 92078 Phone: 760-471-1755
CA Building Energy Efficiency Standards -2013 Nonresidential Compliance June 2014
STATE OF CALIFORNIA
MECHANICAL VENTILATION AND REHEAT
CEC-NRCC-MCH-03-E (Revised 06/14 CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE NRCC-MCH-03-E
Mechanical Ventilation & Reheat (Page 1 of2)
Project Name: Faraday Gym DatePrepared: 11/5/2014
ACTUAL DESIGN INFO (FROM EQUIPMENT
SCHEDULES, ETCl AREA BASIS OCCUPANCY BASIS MINIMUM
VAV Reheated Primary Air
CFM
VAV Deadband
Primary Air CFM
A
< ~ ~~ ,,,---. ~~ ~ rri Gl s:
----
Gym
Locker
B
8~ 0 V> t: G) -Zz Q G) " s: ,:: 22 -~~
~::!
C
> ~ ~ ~ ffi r:,, z ~ ~ ;g n~~ ~o~ --<
D
il; Cl ~ rn -zGi Q G) z s: > "0 -:;i5 2:! -n s: r:,, 0 ::0 ~ -<
~ ~~ z "0 -m
Cl Cl n
n -n .§
~ z V> ril ::0
G
8 z > Cl SN~~ -:,,o z m Cl
s: z n -n s:
"0 m ::0 > ::0 ~
H
s: z n -n s:
~ > ::0 ~
1,475 I o.50 I 738
684 I 0.15 I 103
z C ~
0 -n
"0 m 0 ;!! m
98.8
13.7
n -n s:
"0 m ::0
"0 m ~ 0 z
K
7.5
7.5
s: z n ~~ ~ ~
0 R c;:
738
103
M N
~ ::c n l>)>m 0 -x;;;.q_ S: n O 'Tl O I "Tl -n r < "'O S:-om t: -~~~ rn
C
738 y
103 y
Total I 840
Yellow shaded cells require user input. Remaining cells are protected and automatic
B. The largest amount of primary air supplied by the terminal unit when it's operating in the cooling mode.
C. The smallest amount of primary air supplied by the terminal unit in the deadband mode.
D. The largest amount of primary air supplied by the terminal unit when it's operating in the heating mode.
0
"0 ::0
2~ ~ -0·~ ::;,;, n z o l> -< ~CJg;c8~ -8~ ~ ~ 2 Gl
E. A terminal unit can be controlled with DDC controls, or non-DDC controls. Each control category has different reheat limitations in code.
F. Transfer Air must be provided where Required Ventilation Airflow (Column M) is greater than the Design Primary Deadband Airflow (Column C).
H. Minimum ventilation rate per Section §120.1. Table 120.1-A.
p
s: n:,, -n X s: --s: 0 S: C
::0 > s: .9;~
-n :,:
s: E
Q
8 s: ;!!
m
R
.::; zO Q~; s::60 -o.r> Dz )>
s T
Q) z~ n )> (0 0 no0 a,~ ~ "Tl -, -+, -c S.Dzs; C -0 m z Q V)
':;,:;
J. Based on number of fixed seats where applicable or the greater of the expected number of occupants and 50% of the CBC occupant load for egress purposes for spaces without fixed seating.
M. Required Ventilation Airflow (Req'd Ventilation Airflow) is the larger of the ventilation rates calculated on an AREA BASIS or OCCUPANCY BASIS (Column I or L)
N. This column identifies whether or not the Design Primary Dead band Airflow complies or not. It compares the value in column M to the value in column C and column F.
0. Design Primary Cooling Airflow * 0.50 for DDC, Design Primary Cooling Airflow* 0.30 for Non-DOC. If the Design Primary Cooling Airflow is less than 300 cfm, then this is not applicable.
P. Maximum of Column Mand Column 0. If the Design Primary Cooling Airflow is 300 cfm or less, then this is not applicable.
Q. This column identifies whether or not the Design Primary Reheat Airflow at the zone level, complies or not. It compares the value in column P to the value in column D.
R. Design Primary Cooling Airflow * 0.20 for DOC. Not applicable for Non-DOC zones or zones where Design Primary Cooling Airflow is is 300 cfm or less.
S. Maximum of Column M and Column R. Not applicable if the Design Primary Cooling Airflow is 300 cfm or less.
T. This column identifies whether or not the Design Primary Dea_dband Airflow at the zone level, complies or not. It compares the value in column S to the value in column C.
CA Building Energy Efficiency Standards -2013 Nonresidential Compliance June 2014
STATE OF CALIFORNIA
MECHANICAL VENTILATION AND REHEAT xar . ...., "'-·~" .. .. ······· ..... . ...... . ..
CERTIFICATE OF COMPLIANCE NRCC-MCH-03-E
Mechanical Ventilation & Reheat (Page 2 of 2)
Project Name: Faraday Gym I DatePrepared: 11/5/2014
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT ~ 1. I certify that this Certificate of Compliance documentation is accurate and complete. /11 Documentation Author Name: Mark Gallant, CEPE Documentation Author Signature:
Company: Gallant Energy Consulting Signature Date: 111512014
Address: 508 W Mission Ave Ste 201 CEA/ HERS Certification Identification (if applicable):
City/State/Zip: Escondido, CA 92025 Phone: 760-7 43-5408
RESPONSIBLE PERSON'S DECLARATION STATEMENT
I certify the following under penalty of perjury, under the laws of the State of California:
1. The information provided on this Certificate of Compliance is true and correct.
2. I am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design or system design identified on this Certificate of Compliance (responsible
designer).
3. The energy features and performance specifications, materials, components, and manufactured devices for the building design or system design identified on this Certificate of Compliance
conform to the requirements ofTitle 24, Part 1 and Part-6 of the California Code of Regulations.
4. The building design features or system design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance documents,
worksheets, calculations, plans and specifications submitted to the enforcement agency for approval with this building permit application.
5. I will ensure that a completed signed copy of this Certificate of Compliance shall be made available with the building permit(s) issued for the building, and made available to the enforcement
agency for all applicable inspections. 1 understand that a completed signed copy of this Certificate of Compliance is required to be included with the documentation the builder provides to the
building owner at occupancy.
Responsible Designer Name: Mike Mayer Responsible Designer Signature:
Company: REM Mechanical Date Signed:
Address: 1075 Linda Vista Drive, Ste A License:
City/State/Zip: San Marcos, CA 92078 Phone: 760-471-1755
CA Building Energy Efficiency Standards -2013 Nonresidential Compliance June 2014
STATE OF CALIFORNIA
REQUIRED ACCEPTANCE TESTS
.... ---· . ----. . . ...
CERTIFICATE OF COMPLIANCE NRCC-MCH-04-E
Required Acceptance Tests (Page 1 of 3)
Project Name: Faraday Gym I Date Prepared: 11/5/2014
MECHANICAL COMPLIANCE FORMS & ~ORKSHEETS (indicate if worksheet is included)
For detailed instructions on the use of this and all Energy Efficiency Standards compliance forms, refer to the 2013 Nonresidential Manual Note: The Enforcement Agency may
require al/forms to be incorporated onto the building plans. Forms NRCC-MCH-04-E and NRCC-MECH-05-E are alternative forms to NRCC-MCH-01-E, NRCC-MCH-02-E and NRCC-
MCH-03-Efor projects using only single zone packaged HVAC systems.
YES NO Form Title
,/ NRCC-MCH-04-E (1 of 2) Certificate of Compliance. Required on plans when used.
,/ NRCC-MCH-04-E (2 of 2) Mechanical Acceptance Tests. Required on plans when used.
,/ NRCC-MCH-05-E (1 of 2) HVAC Prescriptive Requirements. It is required on plans when used.
,/ NRCC-MCH-05-E (2 of 2) Mechanical SWH Equipment Summary is required for all submittals with service water heating, pools or spas. It is
required on plans where applicable.
CA Building Energy Efficiency Standards -2013 Nonresidential Compliance June 2014
STATE OF CALIFORNIA
REQUIRED ACCEPTANCE TESTS
--... ·--···-·. -. -. ·-··-----· .. -·. .. . ........... -....... . ..
CERTIFICATE OF COMPLIANCE NRCC-MCH-04-E
Required Acceptance Tests (Page 2 of 3)
Project Name: Faraday Gym I DatePrepared: 11/5/2014
Designer:
This form is to be used by the designer and attached to the plans. Listed below are all the acceptance tests for mechanical systems. The designer is required to check the
applicable boxes by all acceptance tests that apply and list all equipment that requires an acceptance test. If all equipment of a certain type requires a test, list the equipment
description and the number of systems. The NA number designates the Section in the Appendix of the Nonresidential Reference Appendices Manual that describes the test.
Since this form will be part of the plans, completion of this section will allow the responsible party to budget for the scope of work appropriately.
Enforcement Agency:
Systems Acceptance. Before occupancy permit is granted for a newly constructed building or space, or a new space-conditioning system serving a building or space is operated
for normal use, all control devices serving the building or space shall be certified as meeting the Acceptance Requirements for Code Compliance.
Systems Acceptance. Before occupancy permit is granted. All newly installed HVAC equipment must be tested using the Acceptance Requirements ..
The NRCC-MCH-04-E form is not considered a completed form and is not to be accepted by the building department unless the correct boxes are checked. The equipment
requiring testing, person performing the test (Example: HVAC installer, TAB contractor, controls contractor, PE in charge of project) and what Acceptance test must be
conducted. The following checked-off forms are required for ALL newly installed and replaced equipment. In addition a Certificate of Acceptance forms shall be submitted to
the building department that certifies plans, specifications, installation certificates, and operating and maintenance information meet the requirements of Section 10-103(b)
and Title 24 Part 6. The building inspector must receive the properly filled out and signed forms before the building can receive final occupancy.
Test Description MCH-02-A MCH-03-A MCH-04-A MCH-05-A MCH-06-A MCH-07-A MCH-11-A MCH-12-A MCH-14-A MCH-18-A Test Performed By:
Equipment #of Outdoor Single Zone Air Economizer Demand Supply Automatic FDD for Distribute Energy
Requiring units Air Unitary Distribution Controls Control FanVAV Demand Packaged d Energy Managem
Testing or Ducts Ventilation Shed DX Units Storage ent
Verification (DCV) Control DXAC Control
Systems System
Trane WSC 1 ,/ ,/ ,/ ,/ ,/
CA Building Energy Efficiency Standards -2013 Nonresidential Compliance June 2014
STATE OF CALIFORNIA
REQUIRED ACCEPTANCE TESTS
---... ·--···-·. -. . ,-··-----· .. .. ·---..... -.. . ......
CERTIFICATE OF COMPLIANCE NRCC-MCH-04-E
Required Acceptance Tests (Page 3 of 3)
Project Name: Faraday Gym I Date Prepared: 11/5/2014
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT ~ 1. I certify that this Certificate of Compliance documentation is accurate and complete. rYJ Documentation Author Name: Mark Gallant, CEPE Documentation Author Signature:
Company: Gallant Energy Consulting Signature Date: 111512014
Address: 508 W Mission Ave Ste 201 CEA/ HERS Certification Identification (if applicable):
City/State/Zip: Escondido, CA 92025 Phone: 760-743-5408
RESPONSIBLE PERSON'S DECLARATION STATEMENT
I certify the following under penalty of perjury, under the laws of the State of California:
1. The information provided on this Certificate of Compliance is true and correct.
2. I am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design or system design identified on this Certificate of Compliance (responsible
designer).
3. The energy features and performance specifications, materials, components, and manufactured devices for the building design or system design identified on this Certificate of Compliance
conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of Regulations.
4. The building design features or system design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance documents,
worksheets, calculations, plans and specifications submitted to the enforcement agency for approval with this building permit application.
5. I will ensure that a completed signed copy of this Certificate of Compliance shall be made available with the building permit(s) issued for the building, and made available to the enforcement
agency for all applicable inspections. I understand that a completed signed copy of this Certificate of Compliance is required to be included with the documentation the builder provides to the
building owner at occupancy.
Responsible Designer Name: Mike Mayer Responsible Designer Signature:
Company: REM Mechanical Date Signed:
Address: 1075 Linda Vista Drive, Ste A License:
City/State/Zip: San Marcos, CA 92078 Phone: 760-471-1755
CA Building Energy Efficiency Standards -2013 Nonresidential Compliance June 2014
STATE OF CALIFORNIA
REQUIREMENTS FOR PACKAGED SINGLE ZONE UNITS
CEC-NRCC-MCH-05-E (Revised 06/14 CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE N RCC-MCH-05-E
Requirements for Packaged Single-Zone Units (Page 1 of 2)
Project Name: Faraday Gym Date Prepared: 11/5/2014
Equipment Tag(s)1 Retail Mech. System
MANDATORY MEASURES T-24 Sections Requirement As Schedulecf Requirement3 As Schedulecf Requirement As Schedulecf
Heating Equipment Efficiency4 110.1 or 110.2(a) 3.30 COP 2.20 COP
Cooling Equipment Efficiency4 110.1 or 110.2(a) 11.0 EER 11.0 EER
Thermostats5 110.2(b), 110.2(c) Setback Setback
Furnace Standby Loss Control6 110.2(d) n/a
Low Leakage AHU 110.2(f) NR none
Ventilation7 120.l(b) 840 840
Demand Control Ventilations 120.l(c)4 Req Yes
Occupant Sensor Ventilation Controls 120.l(c)S, 120.2(e)3
Shutoff and Reset Controls9 120.2(e) Req Programmable
Outdoor Air and Exhaust Damper Control 120.2(f) Req Gravity
Automatic Demand Shed Controls 120.2(h) NR none
Economizer FDD 120.2(i) Req
Duct Insulation 120.4 n/a none
PRESCRIPTIVE MEASURES
Equipment is sized in conformance with 140.4(a & b) 76,233 Btu/hr 68,084 Btu/hr
140.4 (a & b) 109,193 Btu/h 48 273 Btu/hr
Economizer 140.4(e) Req Diff. Temo (lntE
Electric Resistance Heating10 140.4(g) No No
Duct Leakage Sealing and Testing.11 140.4(1) NR No
Notes:
1. Provide equipment tags (e.g. AC1 or AC1 to 10}. Multiple units of the same make and model with the same application and accessories can be grouped together.
2. Enter the following information as appropriate: Unit Manufacturer; Unit Model Number (including all accessories); Description of the unit (e.g. gas-pack or heat pump; rated heating capacity
(enter "NIA" if no heating); and, rated cooling capacity (enter "NIA" if no cooling). For unit capacities include the units (e.g. kBtuh or tons).
3. For each requirement, enter the minimum requirement from the Standard In the left column (under "Standard Requirement"). In the right column (under "As Scheduled") enter the value for
the units as specified.
4. Where there is more than one requirement (e.g. full and part load efficiency) enter both with the appropriate labels (e.g. COP and JEER).
5. In the left column identify the thermostatic requirements from the standard (e.g. programmable setback thermostat or heatpump with electric heat), . In the right column indicate the
capabilities of the thermostat as scheduled.
6. If the unit has a furnace which is rated at >=225,000 Btuh of capacity, indicate the rated standby loss and ignition source (e.g. /ID). If there is no furnace or the unit is rated for <225,000 Btuh
indicate "NIA".
7. In the left column, enter both the required ventilation value from Table 120.1A and for the number of occupants times 15 cf ml person. In the right column enter the actual minimum
ventilation as scheduled. If the space is naturally ventilated enter "NIA" in the left column and "the space is naturally ventilated" in the right column.
8. If the space is required to have either DCVor Occupant Sensor Ventilation Control indicate "required" in the left column (otherwise indicate "NIA" in the left column). If either DCVor Occupant
Sensor Ventilation Control is provided indicate "provided" in the right column (otherwise indicate "NIA" in the right column)
9. In the left column indicate the required time controls from the standard. In the right column identify the device that provides this functionality (e.g. EMCS or programmable timeclock).
10. Enter NIA if there is no electric heating. If the system has electric heating indicate which exception to 140.4{g) applies.
11. If duct leakage sealing and testing is required, a MCH-04-A form must be submitted.
CA Building Energy Efficiency Standards -2013 Nonresidential Compliance June 2014
STATE OF CALIFORNIA
REQUIREMENTS FOR PACKAGED SINGLE ZONE UNITS • -----... ·--........ ' --..... "'·"'··-----· . ' -··-·· .......... ,_,,_,, .............. ,, ______
CERTIFICATE OF COMPLIANCE NRCC-MCH-05-E
Requirements for Packaged Single-Zone Units {Page 2 of 2)
Project Name: Faraday Gym I Date Prepared: 11/5/2014
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT ~ 1. I certify that this Certificate of Compliance documentation is accurate and complete.
Documentation Author Name: Mark Gallant, CEPE Documentation Author Signature:
Company: Gallant Energy Consulting Signature Date: 11/5/2014
Address: 508 W Mission Ave Ste 201 CEA/ HERS Certification Identification (if applicable):
City/State/Zip: Escondido, CA 92025 Phone: 760-743-5408
RESPONSIBLE PERSON'S DECLARATION STATEMENT
I certify the following under penalty of perjury, under the laws of the State of California:
1. The information provided on this Certificate of Compliance is true and correct.
2. I am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design or system design identified on this Certificate of Compliance (responsible
designer).
3. The energy features and performance specifications, materials, components, and manufactured devices for the building design or system design identified on this Certificate of Compliance
conform to the requirements ofTitle 24, Part 1 and Part 6 of the California Code of Regulations.
4. The building design features or system design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance documents,
worksheets, calculations, plans and specifications submitted to the enforcement agency for approval with this building permit application.
5. I will ensure that a completed signed copy of this Certificate of Compliance shall be made available with the building permit(s) issued for the building, and made available to the enforcement
agency for all applicable inspections. I understand that a completed signed copy of this Certificate of Compliance is required to be included with the documentation the builder provides to the
building owner at occupancy.
Responsible Designer Name: Mike Mayer Responsible Designer Signature:
Company: REM Mechanical Date Signed:
Address: 1075 Linda Vista Drive, Ste A License:
City/State/Zip: San Marcos, CA 92078 Phone: 760-471-1755
CA Building Energy Efficiency Standards -2013 Nonresidential Compliance June 2014
STATE OF CALIFORNIA
FAN POWER CONSUMPTION
CEC-NRCC-MCH-07-E Revised 07/14 CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE NRCC-MCH-07-E
Power Consumption of Fans Requirements (Page 1 of 2)
ProjectName: Faraday Gym Date Prepared: 11/5/2014
Constant Volume Fans Systems
NOTE: Provide one copy of this worksheet for each fan system with a total fan system horsepower greater than 25 hp of Constant Volume Fan
Systems when using the Prescriptive Approach. See Power Consumption of fans §140.4(c).
A B C D E F
FAN DESCRIPTION DESIGN EFFICIENCY NUMBER OF PEAK WATTS
BxEx746/ BRAKE HP MOTOR DRIVE FANS (CxD)
Retail Mech. System -Supply Fan 1.440 86.5% 97.0% 1.0 1,280
Variable Air Volume Fans Systems
NOTE: Provide one copy of this worksheet for each fan system with a total fan system horsepower greater than 25 hp of Variable Air Volume
(VAV) Systems when using the Prescriptive Approach. See Power Consumption of fans §140.4(c).
A B C D E F
FAN DESCRIPTION DESIGN EFFICIENCY NUMBER OF PEAK WATTS
BRAKE HP FANS BxEx746/
MOTOR DRIVE (Cx D)
Totals and Adjustments
FILTER PRESSURE ADJUSTMENT Equation 140.4-A 1) TOTAL FAN SYSTEM POWER (WATTS, SUM 1,280 w
in §140.4(c) of the Building Energy Efficiency COLUMN F)
Standards. 2) SUPPLY DESIGN AIRFLOW CFM 3,000
A) lffilter pressure drop (SP al is greater than 1 inch 3) TOTAL FAN SYSTEM POWER INDEX (Row 1 / Row 2) 1 W/CFM W. C. or 245 Pascal then enter SP. on line 4. Enter
Total Fan pressure drop across the fan (SPt) on Line
4) SP a inW.C
5. or Pa
5) SPt inW.C
B) Calculate Fan Adjustment and enter on line 6. or Pa
C) Calculate Adjusted Fan Power Index and enter 6) Fan Adjustment= 1-(SP. -1)/SPt
on Row7
7) ADJUSTED FAN POWER INDEX (Line 3 x Line 6) 1 0.427 W/CFM
1. TOTAL FAN SYSTEM POWER INDEX or ADJUSTED FAN POWER /Nf?EX must not exceed 0.8 w/cfm for Constant Volume systems or 1.25 w/cfm
for VAV systems.
CA Building Energy Efficiency Standards -2013 Nonresidential Compliance July 2014
STATE OF CALIFORNIA
FAN POWER CONSUMPTION • CEC-NRCC-MCH-07-E /Revised 07/14)" CALIFORNIA ENERGY COMMISSION "'
CERTIFICATE OF COMPLIANCE NRCC-MCH-07-E
Power Consumption of Fans Requirements (Page 2of 2)
ProjectName: Faraday Gym I DatePrepared: 11/5/2014
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT
_Jlr. -1. I certify that this Certificate of Compliance documentation is accurate and complete. rY/ -" Documentation Author Name: Mark Gallant, CEPE Documentation Author Signature: 11
V7-r
Company: Gallant Energy Consulting Signature Date: 111512014
Address: 508 W Mission Ave Ste 201 CEA/ HERS Certification Identification (if applicable):
City/State/Zip: Escondido, CA 92025 Phone: 760-743-5408
RESPONSIBLE PERSON'S DECLARATION STATEMENT
I certify the following under penalty of perjury, under the laws of the State of California:
1. The information provid!=!d on this Certificate of Compliance is true and correct.
2. I am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design or system design
identified on this Certificate of Compliance (responsible designer).
3. The energy features and performance specifications, materials, components, and manufactured devices for the building design or system
design identified on this Certificate of Compliance conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of
Regulations.
4. The building design features or system design features identified on this Certificate of Compliance are consistent with the information
provided on other applicable compliance documents, worksheets, calculations, plans and specifications submitted to the enforcement
agency for approval with this buil_ding permit application.
5. I will ensure that a completed signed copy of this Certificate of Compliance shall be made available with the building permit(s) issued for the
building, and made available to the enforcement agency for all applicable inspections. I understand that a completed signed copy of this
Certificate of Compliance is required to be included with the documentation the builder provides to the building owner at occupancy.
Responsible Designer Name: Mike Mayer Responsible Designer Signature:
Company: REM Mechanical Date Signed:
Address: 1075 Linda Vista Drive, Ste A License:
City /State/Zip: San Marcos, CA 92078 Phone: 760-471-1755
.. CA Building Energy Efficiency Standards -2013 Nonresidential Compliance July 2014
•
e TRAIii!'
Customer : REM MECHANICAL
Project:
Name: FARADAY GYM
Unit function DX cooling
Airflow application Downflow
Elevation 0.00
Model Number WSC090E3R0A **K00000000000B00000000000000
7.5 TON HP RTU
Airflow Convertible
Design Airflow 3000
Evaporator rows 4.00
Fresh air selection Low Leak Econ-dry bulb 0-100%/bar Evaporator fin spacing 192
rel 3p
Evaporator face area 12.36 Tonnage 7.5Ton
Evaporator face velocity 243 Max unit operating weight 993.0
Cooling EDB 80.00 Min. unit operating weight 804.0
Cooling EWB 67.00 Ent Air relative humidity 0.00
ASHRAE 90.1 Yes Ambient Temperature 95.00
Rated capacity (AHRI) 89.00 Heating EAT 70.00
Heating ambient temp 47.00 Heating ambient WB 42.60
Heating ambient relative humidity 70.00 Voltage 208-230/60/3
Design ESP 0.500
~
··-' '
Tonnage 7.5Ton Cooling EDB
Cooling EWB 67.00 Ent Air relative humidity
Ambient Temperature 95.00 Gross Total Capacity 94.00
Gross Sensible Capacity 69.29 Gross Latent Capacity 24.71
Evap Coil Leaving Air Temp (DB) 58.61 Evap Coil Leaving Air Temp (WB) 56.86
Cooling LOB 59.85 Cooling LWB 57.34
Dew Point Temp 55.73 Fan motor heat 2.96
Net total capacity 91.04 Net sensible capacity 66.33
Net sensible heat ratio 0.73 Refrig charge (HFC-410A) -ckt 1 13.8
Saturated Discharge Temp 1 118.16 Saturated Suction Temp 1 50.06
Saturated Discharge Temp 2 0.00 Saturated Suction Temp 2 0.00
Saturated Discharge Temp Circuit 1 -105.69 Saturated Suction Temp Circuit 1 -HP 26.67
HP
Saturated Discharge Temp Circuit 2 -0.00 Saturated Suction Temp Circuit 2 -HP 0.00
HP
Output htg capacity 83.21 Output htg capacity w/fan 86.17
Heating EAT 70.00 Heating ambient temp 47.00
Heating ambient WB 42.60 Heating ambient relative humidity 70.00
Heating LAT 96.59 · Heating delta T
Page 1
LaSan_11 ~ SPECIFICATION SHEET
LOSONE SELECT®
CEILING MOUNT VENTILATORS
L 100 SERIES ~ERIES p1,,
Incredibly reliable. Unbelievably quiet. Offering the CFM
choices you needatthe lowest sound levels in the industry.
FEATURES
GRILLE:
• Conceals interior
• Low profile styling blends with any decor
• White polymeric ("MG" models -metal, finished with
white painted enamel)
BLOWER:
• Low RPM for quiet operation
• Resilient anti-vibration mounts
• Dynamically-balanced, polymeric, centrifugal blower
wheel for quiet, efficient performance
• Permanently lubricated, thermally protected motor
• Plug-in motor rated at 120 VAC
• Designed for continuous operation
HOUSING:
Rugged, 20 gauge galvanized steel
• 6" round duct connector
• 1/2" acoustic insulation inside
• May be installed in ceiling or wall (size permitting)
• 8-position mounting brackets for easy installation and
greater adaptability to various mounting requirements
• Automatic backdraft damper located within duct connector
• Factory-shipped in horizontal discharge position -easily
converted to vertical discharge
• May be installed as an in-line ventilator with addition of
accessory kit Model 961 L (see "Accessories")
ACCESSORIES (purchase all separately):
• Model 57V (Ivory)/ 57W (White) Electronic Variable Speed
Control
• Model 59V (Ivory)/ 59W (White) 60-Minute Time Control
• Model 61V (Ivory)/ 61W (White) 15-Minute Time Control
• Model 71V (Ivory)/ 71W (White) 12-Hour Time Control
• Electronic Variable Speed Controls -Model 72V (120 VAC)
• Model 961 L In-line Adapter Plate
• Model RD1 Radiation Damper
• Model SOL Electronic Speed Control (Internal)
TYPICAL SPECIFICATION
Ventilator shall be Brean Model L 100, (1:.1 00MG), (L 150),
(L150MG).
Ventilator shall have galvanized steel housing insulated with
at least 1/2" of acoustic insulation. Housing to have adjustable
mounting brackets.
Automatic backdraft damper to be located within duct
connector. Duct connector, blower assembly and wiring plate
shall be adjustable for either horizontal or vertical installation.
Blower unit shall be removable from housing and will have a
polymeric, dynamically balanced centrifugal-type blower
wheel. Motor to be permanently lubricated and mounted with
resilient anti-vibration mounts. RPM not to exceed number
listed for each model.
Air delivery shall be no less and sound levels no greater than
listed for each model. All air and sound ratings shall be
certified by AMCA. Units to be UL and cUL listed.
"Broan-NuTone LLC certifies that the models shown herein are
licensed to bear the AMGA Seal.
The ratings shown are based on
tests and procedures performed
in accordance with AMGA
Publication 211 (and AMGA
Publication 311 If sound Is also
certified) and comply with the
requirements of the AMGA
Certified Ratings Program"
Models L100 and L150 are
UL listed for use over
bathtubs and showers when
connected to a GFCl-
·protected branch circuit.
Broan-NuTone LLC, 926 West State Street, Hartford, Wisconsin 53027 (1-800-637-1453)
Broan-NuTone Canada, 1140 Tristar Drive, Mississauga, Ontario, L5T 1 H9 (1-888-882-7626)
REFERENCE QTY. REMARKS Project
Location
Architect
Engineer
Contractor
Submitted by Date
50J 99042731G
PERFORMANCE RATINGS -LOSONE SELECT®
CEILING MOUNT VENTILATORS
L 100 SERIES & L 150 SERIES
AMCA LICENSED PERFORMANCE
CFM /SONES· AT STATIC PRESSURES (Ps • inches of H20)
MODEL NOMINAL 0.0" .10" .125" .250" .375" .50" .625" .750" .875" 1.0" NOMINAL AMPS WATTS
NO. VOLTAGE Ps Ps Ps Ps Ps Ps Ps Ps Ps Ps RPM @SO Hz
L100 120 VAC CFM Hor. 136 115 109 93 80 65 44 12 640 1.1 87
SONES Hor. 0.5 0.8 0.9 1.3 1.8 2.3 3.0 3.2
CFMVer. 138 117 112 94 80 67 46 13 650 1.1 87
SONES Ver. 0.7 0.9 1.0 1.3 1.8 2.2 2.8 3.0
L100MG 120 VAC CFM Hor. 144 121 115 97 83 68 46 12 630 1.1 87
SONES Hor. 0.5 0.8 0.9 1.2 1.8 2.4 3.0 3.3
CFMVer. 142 119 115 95 80 67 45 13 640 1.1 87
SONES Ver. 0.5 0.8 0.9 1.4 1.8 2.3 2.9 3.1
L150 120 VAC CFM Hor. 181 161 157 141 132 124 114 94 62 710 1.3 100
SONES Hor. 1.3 1.4 1.5 2.2 2.6 3.1 3.6 4.1 4.6
CFMVer. 179 163 160 149 142 133 122 105 73 23 750 1.3 100
SONES Ver. 1.4 1.6 1.6 2.0 2.5 3.0 3.3 3.6 3.9 4.2
L150MG 120 VAC CFM Hor. 184 165 161 148 141 135 126 108 74 19 710 1.3 100
SONES Hor. 1.1 1.4 1.4 1.9 2.3 2.8 3.2 3.8 4.1 4.5
CFM Ver. 183 165 162 151 143 135 124 107 76 26 725 1.3 100
SONES Ver. 1.4 1.6 1.6 2.0 2.5 3.0 3.3 3.6 4.0 4.4
Performance ratings include the effects of inlet grille and backdraft damper in the airstream. Speed (RPM) shown is nominal. Performance is based on actual speed of test. The
sound ratings shown are loudness values in fan sones at 5' (1.5m) in a hemispherical free field calculated per AMCA Std. 301. Values shown are for Installation Type B: Free inlet
fan sone levels. Performance shown is for Installation Type B: Free inlet, Ducted outlet.
"Broan-NuTone LLC certifies that
the models shown herein are Ii·
censed to bear the AMCA Seal.
The ratings shown are based on
tests and procedures performed in
accordance with AMCA Publica-
tion 211 (and AMCA Publication
311 if sound is also certified) and
comply with the requirements of
the AMCA Certified Ratings Pro-
gram.'
1.00
0 .90
~ 0.80 CJ
~ 0.70
~
r,:i 0 .60 p::; p 050 C/l
C/l
r,:i 0 .40 p::;
0..
µ 0 30 8 ,:i:: 8 020 C/l
0 J.O
0 .00
........ , I
\
.. ,.(7~J
~v&
\ K "~-<Sl,s, c--Oo ' ,& \'s,.,,. \ /(S)
\ iS'
\ \
\ ' \ \
I\ \
~ '\
0 20 40 60 80 100 120 140 160 180 200
AJR FLOW RATE (CFM)
WEIGHT----
MODEL NO. SHIPPING WT.
L100 22.8 lbs.
L100MG 23.7 lbs.
L150 23.1 lbs.
L150MG 23.7 lbs.
BRGJ\N® Broan-NuTone LLC, 926 West State Street, Hartford, Wisconsin 53027 (1-800-637-1453)
Broan-NuTone Canada, 1140 Tristar Drive, Mississauga, Ontario, L5T 1H9 (1-888-882-7626)
LaSa~ sPEc1F1cAT10N sHEET
LOSONE SELECT® iF~~ -~r(U)~~
E LING MOUNT VENTILATORS
L20 , L250, L300 SERIES, L300KMG
dibly reliable. Unbelievably quiet. Offering the CFM
choices you need at the lowest sound levels in the
industry.
FEATURES
GRILLE:
• Conceals interior
• Low profile styling blends with any decor
• White polymeric ("MG" models -metal, finished with white
painted enamel)
BLOWER:
• Low RPM for quiet operation
• Resilient anti-vibration mounts
• Dynamically-balanced, polymeric, centrifugal blower
wheel for quiet, efficient performance (Model L300KMG-
metal wheel)
• Permanently lubricated, thermally protected motor
• Plug-in motor rated at 120 VAC
• Designed for continuous operation
HOUSING:
• Rugged, 20 gauge galvanized steel
• 8" round duct connector
• 1/2" acoustic insulation inside (Model L300KMG -no
insulation -for kitchen applications)
• May be installed in ceiling or wall (size permitting)
• a-position mounting brackets for easy installation and
greater adaptability to various mounting requirements
• Automatic backdraft damper located within duct connector
• Factory-shipped in horizontal discharge position -easily
converted to vertical discharge
• May be installed as an in-line ventilator with addition of
accessory kit Model 981 L (purchase separately)
ACCESSORIES (purchase all separately):
• Model 57V (Ivory)/ 57W (White) 3-Amp, Electronic Variable
Speed Control
• Model 59V (Ivory)/ 59W (White) 60-Minute Time Control
• Model 61V (Ivory)/ 61W (White) 15-Minute Time Control
• Model 71V (Ivory) /71W (White) 12-HourTime Control
• 6-Amp, Electronic Variable Speed Controls
Model 72V/72W (120 VAC)
• Model 981L In-line Adapter Kit
• Model RD1 Radiation Damper
• Model LAF1 Grease Filter (for Model L300KMG)
• Model SOL Electronic Speed Control (Internal)
TYPICAL SPECIFICATION
Ventilator shall be Broan Model L200, (L200MG), (L250),
(L250MG), (L300), (L300KMG).
Ventilator shall have galvanized steel housing insulated with
at least 1/2" of acoustic insulation (with no insulation -Model
L300KMG). Housing to have adjustable mounting brackets.
Automatic backdraft damper to be located within duct
connector. Duct connector, blower assembly, and wiring
plate shall be adjustable for either horizontal or vertical
installation.
Blower unit shall be removable from housing and will have a
polymeric, dynamically balanced centrifugal-type blower
wheel. Motor to be permanently lubricated and mounted with
resilient anti-vibration mounts. RPM not to exceed number
listed for each model.
Air delivery shall be no less and sound levels no greater than
listed for each model. All air and sound ratings shall be
certified by AMCA. Units to be UL and cUL listed.
/CUDD
I"¾ riiR ~
"Broan-NuTone LLC certifies that
the models shown herein are
licensed to bear the AMOA Seat.
The ratings shown are based on
tests and procedures perfonmed
in accordance with AMOA
Publication 211 (and AMOA
Publication 311 If sound is also
certified) and comply with the
requirements or the AMOA
Certified Ratings Program"
Models L200, L250, and
L300 are UL listed for use
over bathtubs and showers
when connected to a GFCl-
protected branch circuit.
Broan-NuTone LLC, 926 West State Street, Hartford, Wisconsin 53027 (1-800-637-1453)
Broan-NuTone Canada, 1140 Tristar Drive, Mississauga, Ontario, L5T 1H9 (1-888-882-7626)
REFERENCE QTY. REMARKS Project
Location
Architect
Engineer
Contractor
Submitted by Date
60J 99042732J
\
PERFORMANCE RATINGS -LOSONE SELECT®
CEILING MOUNT VENTILATORS
AMCA LICENSED PERFORMANCE
L200, L250, L300 SERIES~ L300KMG
MODEL NOMINAL 0.0"
NO. VOLTAGE Ps
L200 120 VAC CFM Hor. 231
SONES Hor. 1.6
CFM Ver. 224
SONES Ver. 1.5
L200MG 120 VAC CFM Hor. 237
SONES Hor. 1.4
CFMVer. 228
SONES Ver. 1.5
L250 120 VAC CFM Hor. 272
SONES Hor. 2. 1
CFMVer. 269
SONES Ver. 2.3
L250MG 120 VAC CFM Hor. 280
SONES Hor. 2.1
CFMVer. 275
SONES Ver. 2.2
L300 120 VAC CFM Hor. 312
SONES Hor. 2.8
CFM Ver. 319
SONES Ver. 2.6
L300MG 120 VAC CFM Hor. 323
SONES Hor. 3.0
CFMVer. 322
SONES Ver. 2.4
L300KMG 120 VAC CFM Hor. 286
SONES Hor. 2.8
CFMVer. 287
SONES Ver. 3.3
CFM / SONES-AT STATIC PRESSURES (Ps -inches of H2O)
.10" .125" .250" .375" .50"
Ps Ps Ps Ps Ps
214 210 196 186 177
1.8 1.7 2.3 2.9 3.5
210 207 197 187 179
1.8 2.0 2.3 2.7 3.4
218 215 199 190 180 1.8 1.9 2.4 3.0 3.6
213 209 198 190 182
1.7 1.8 2.3 2.8 3.4
261 259 250 242 233
2.3 2.2 2.9 3.3 3.9
261 259 253 248 239
2.6 2.7 3.0 3.3 3.7
267 265 254 246 238
2.5 2.5 2.9 3.4 3.9
263 262 255 250 241
2.6 2.7 3.0 3.4 3.8
309 308 303 296 287
2.9 2.9 3.3 3.5 3.9
314 313 306 299 288
2.9 3.0 3.4 3.6 3.9
317. 316 312 305 298 2.8 3.0 3.2 3.5 3.9
315 314 308 302 292
2.7 2.8 3.3 3.5 3.9
279 277 272 268 261
3.0 3.1 3.4 3.8 4.4
280 277 273 266 259
3.6 3.7 4.1 4.7 5.2
.625" .750"
Ps Ps
165 144
4.1 4.9
167 144
4.0 4.5
167 144 4.2 5.1
168 145
4.1 4.6
218 201
4.4 4.8
224 203
4.2 4.7
224 209
4.3 4.6
229 210
4.3 4.8
273 254
4.3 4.7
274 251
4.4 4.7
283 266 4.:3 4.8
278 259
4.3 4.7
253 241
4.8 5.1
247 231
5.6 6.3
1.00
0 0.90
~ 0.80
Z-:::::, 0.70
llJ a: 0.60
:::J ~ 0.50
~ 0.40
Q. O 0.30
~ 0.20
~ 0.10
0.00
0
.875" 1.0" NOMINAL AMPS WATTS
Ps Ps RPM @60Hz
113 51 740 1.8 127
5.3 5.3
99 41 760 1.8 127
5.1 5.2
108 47 715 1.8 127
5.6 5.5
105 56 730 1.8 127
5.1 5.2
165 99 830 2.1 166
5.5 5.8
171 101 860 2.1 166
5.4 5.6
172 105 805 2.1 166
5.6 5.9
178 105 830 2.1 166
5.5 5.8
219 125 905 2.6 212
5.1 5.6
219 120 940 2.6 212
5.0 5.5
235 153 860 2.6 212
5.2 5.7
227 119 885 2.6 212
5.1 5.5
222 173 790 2.6 212
5.5 6.1
208 164 815 2.6 212
6.8 6.9
40 80 120 160 200 240 280 320
AIR FLOW RATE (CFM)
WEIGHT--------POLYMERIC GRILLE
MODELS
L200, L250,
L300
METAL GRILLE
MODELS
L200MG, L250MG,
L300MG, L300KMG
MODEL NO. SHIPPING WT.
L200 ...................................................................... 23.0 lbs.
L250, L300 .......................................................... 23.1 lbs.
L200MG ................................................................ 23.9 lbs.
L250MG, L300MG ................................................ 24.0 lbs.
L300KMG ............................................................. 25.2 libs. ·
@c(~i)
BRG.'\N® Broan-NuTone LLC, 926 West State Street, Hartford, Wisconsin 53027 (1-800-637-1453)
Broan-NuTone Canada, 1140 Tristar Drive, Mississauga, Ontario, L5T 1H9 (1-888-882-7626)
MODEL 670
CEILING/WALL FANS
Simple installation and dependability make this
odor and moisture removing fan a real value.
FEATURES
GRILLE:
• White polymeric -blends well with any decor
• Torsion spring grille mounting -no tools required
• Metal grille kit available -(purchase separately)
MOTOR:
• Plug-in, permanently lubricated
• Brean-designed polymeric blower wheel
• Snap in/out motor assembly for easy cleaning-no screws
to drive or drop
HOUSING:
• Compact, 25 gage galvanized steel -attaches easily to
wall or ceiling joists
• Double strength mounting flanges with keyhole slots .
• Removable wiring cover -make connections away from
tight corners
• No electrical knockout to remove
• Polymeric duct fitting with tapered sleeve for easy, positive
duct connection
• Quiet polymeric damper prevents cold backdrafts -no
metallic clatter
Model 1667H: Rough-in housing for 1670Ffinish assemblies
(packed 6 per carton).
• U.L. listed for tub or shower enclosure with GFCI branch
wiring
CONTROLS: Designed by Broan for use with this product
(purchase separately)
• Model 57V (lvory)/57W(White) electronic variable speed
control
• Model 59V (lvory)/59W(White) 60-Minute Time Control
• Model 61V/61W 15-Minute Time Control
SPECIFICATION SHEET
TYPICAL SPECIFICATION
Ventilator shall be Brean Model 670.
Ventilator shall have galvzanized steel housing with double-
strength mounting flanges. It shall be ducted vertically
(hoirizontally) to a roof cap (wall cap).
Motor assembly shall be removable and permanently
lubricated.
Air delivery shall be no less and sound levels no greater than
listed. All air and sound ratings shall be certified by AMCA
and/or HVI. Units shall be U.L. listed.
"Broan-NuTone LLC certifies thatthe models
shown herein are licensed to bear the AMCA
Seal. The ratings shown are based on tests
and procedures performed in accordance with
AMCA Publication 211 (and AMCA Publica-
tion 311 if sound is also certified) and comply
with the requirements of the AMCA Certified
Ratings Program."
® ~,.,, .....
MVI
CERTIFIED
Broan-NuTone LLC, 926 West State Street, Hartford, WI 53027 (1-800-637-1453)
REFERENCE QTY. REMARKS Project
Location
Architect
Engineer
Contractor
Submitted by Date
50G 99041842E
PERFORMANCE RATINGS -MODEL 670
AMCA LICENSED PERFORMANCE---------------
Model Sones@ CFM @ Static Pressure (Ps -Inches of H20) Total Duct
No. 0.0"S.P. o.o I 0.1 I .125 I .250 I .a15 I .500 Volts Watts RPM Size
670 3.4 56 I 51 I 50 I 46 I 41 I 32 120 55 1700 3" Round
The performances shown are with inlet grille, backdraft damper and outlet duct. RPM shown is nominal and the performance is based on actual speed of test.
The sound ratings shown are loudness values in fan sones at 5' (1.5m) in a hemispherical free field calculated per AMCA Std. 301. Values shown are for
installation Type B: free inlet fan sone levels.
SONES --------AMPS
Model HVI Sones AMCASones
Number @0.1" S.P.** @0.0" S.P.**
670 3.5 3.4
** There is difference between sone values certified by HVI for
residential use and by AMCA for commercial/industrial use. Exact
comparison of these values is not possible. This difference is
mainly due to procedures used to convert measured sound to
perceived sound. ANSI S3.4, used by both HVI and AMCA,
MODEL
NUMBER AMPS*
670 0.8
*Total Connected Load
"Broan-NuTone LLC certifies that the
models shown herein are licensed to
bear the AMCA Seal. The ratings shown
are based on tests and procedures per-
formed in accordance with AMCA Pub-
lication 211 (and AMCA Publication 311
if sound is also certified) and comply
with the requirements of the AMCA
Certified Ratings Program."
specifies a procedure for calculating loudness as perceived by a -:scf,----,,------;T"---,------'-......----,
typical listener under specific conditions. HVI establishes values
at a distance of 5feetfrom the fan in a "spherical free field"; AMCA
establishes values at a distance of 5 feet in a "hemispherical free
field". HVI and AMCA have different rules for rounding sane
values.
HVI PERFORMANCE----
MODEL NUMBER SONES
670 3.5
HVI·2100CERTIFIEDRATINGScomplywith
new testing technologies and procedures
prescribed by the Home Ventilating Institute,
for off-the-shelf products, as they are available
to consumers. Product performance is rated
at 0.1 in. static pressure, based on tests
conducted in AMCA's state-of-the-art test
laboratory. Sones are a measure of humanly-
perceived loudness, based on laboratory
measurements.
CFM@0.1" Ps
50 ~,,.,., ...
MVI
CERTIFIED
WEIGHT-------
MODEL NUMBER SHIPPING WT.
670 4.2 LBS. ®
in !!:. w IC :,
II)
II) w a: a.
0 ~ I-II)
.40
.30
.20
.10
0 o!--~15=-----a~o=----4*5=--....,.-:st::o--~75
CFM
r1¾t~!l
~it
Broan-NuTone LLC, 926 West State Street, Hartford, WI 53027 (1-800-637-1453)
JOB NAME fft<url>fttf tfVl>J SUBMITTAL SHEET
ARCHITECT
ENGINEER
Form NumberGS0007.1 Effective Date 1/99
Replaces Form GS0007
CONTRACTOR _________ _
LOCATION I ~~J!!!!&r~!
880 SERIES S1J>e-W1tL-l SuPPr 'l>lfffl~ 6€-S
Double Deflection Adjustable Grille
'2{))(/0
1-3/4"
(45) DUCT SIZE + 1-3/4(45)
...., --...., 9/16" VER CAL ...., (14) DUCT ...., SIZE
PLUS
.... 7 .....
-=-1-3/4"
VERTICAL (45) .... DUCT L SIZE
-= ...., 1-3/4"
(45)
.... MINUS
3/4"(19) D FRAME 22 --.... J (SURFACE MOUNT) .... __,, -=-
HORIZONTAL DUCT SIZE PLUS 1-3/4"(45) PANEL SIZE -1/4(6)
880H¥ D880V FRAME
3/4"(19) X
1-1/4"(32)
ANGLE
-t---.==..--j_J_
3-1/4"(83)
-J r-3/4"(19)
Y V V V V EXISTING
DUCT
#8 SCREW
HORIZ. DUCT SIZE MINUS 1/4"(6) CONCEALED SCREW
880HOBD D D880VOBD HOLE DETAIL
1-3/4"
(45)
t 1/4"(6)
D FRAME 23
(LAY IN TEE BAR)
NOTES: (NOT AVAILABLE WITH OBD)
1. Frame 22 shown. See frame style detail for frame dimensions. FASTEN METHOD
2. All steel construction D 1. No Screw Holes
3. Designation: 880H -Horizontal deflectors with Vertical rear deflectors D 2. STD Screw Fastener
880V -Vertical deflectors with Horizontal rear deflectors. (Shown Above)
4. Standard finish 44 British white. D 3. Concealed Screw Holes
5. Dimensions are in inches (See Detail)
6. Dimensions in parenthesis are in mm.
OPTIONAL ACCESSORIES:
D Opposed blade damper -Model OBD
D Steel OBD (22 GA CRS)
D Painted OBD
D Aluminum OBD D Plaster Frame
D Square to Round Adapter
Product Information is Subject to Change Without Notice
JOB NAME
ARCHITECT
ENGINEER
SUBMITTAL SHEET
Form Number GS0004.8 Effective Date 5/13
CONTRACTOR _________ _ Replaces Form GS0004.7
l1(g]ll!!Q¥,~£:~ LOCATION
SSOH V or HZ VZ SERIES S 1Pe-t,,1All-f2.w-T1A-IZN G12-1 t...1..s-
' ' 3/4" Spaced Fixed Blade Steel Return Grille 3o)C.z.o Page 1 of 2
35° HORIZONTAL BLADES 3/4" (19) O.C. 35° VERTICAL BLADES 3/4" (19) O.C.
"' / l ' l .... 9/16" .... (14) .... TYP-I / 7 DUCT .... SIZE / .... + LLL + PLUS DUCT / .... 1-3/4" LESS .... (45) 3/4" (19)
J J ....
~ SS0H I/ "' L1"(25)
0 ssov
I DUCT SIZE PLUS 1-3/4" (45) • I --l
-J 1--3/4" (19) _j_
I lJ2;j t5(;t:5~ I 2(i~r 0 SS0H-OBD 0 SS0V-OBD
I DUCT LESS 1/4" (6) .. 1t
0° HORIZONTAL BLADES 3/4" (19)·O.C. 0° VERTICAL BLADES 3/4" (19) O.C.
~ "" / l ~l l ,-
,-
....
.... / / DUCT -~ L'.( SIZE -+ + PLUS C DUCT
,-1-3/4" LESS .... (45) 3/4" (19) -J J ----' / "" L1"(25) 0 SS0HZ I .. 1 --l 0 ssovz
DUCT SIZE PLUS 1-3/4" (45)
-J 1--3/4" (19) _l
I lJ2;j ~[ I
21/2"
0 SS0HZ-OBD
(64) 0 SS0VZ-OBD
I DUCT LESS 1/4" (6) .. 1t
Product Information is Subject to Change Without Notice
JOB NAME
ARCHITECT
ENGINEER CONTRACTOR _________ _
LOCATION
SERIES 180
SUBMITTAL SHEET
Form Number GS0010.4 Effective Date 09/12
Replaces GS0010.3
IUalll!!Y§. !!~~
CURVED BLADE, MUL Tl -DEFLECTION STEEL DIFFUSER
o 180 OBD
r 1 1/4"
{32)
~
I/
+ /
'
'
/ / / / / I' I' " ' '
'-'-'-'-' ' 1., 1., ,,
,.
+_J_ ~
9/16" (14) TYP__J
"UCT SIZE PLUS 1-3/4" {45
FACE VIEW· FRAME 22-PATTERN '4'
SEE CHART BELOW FOR OTHER BLOW
PATTERN OPTIONS r 1 1/4"
(32)
------\-PANEL LESS 1/4" {6}
1/4"(6}
DL
SIZ
CT
E s /4"
}
PLU
1-3
{45
#8 SCREW
3/4" X 1 1/4" (19 X 32) ANGLE
0
0
0
0
0
0 D CT
LESS 0 3/4" (19}
~,-,J
(32)
D 180
EXISTING
DUCT
FRAME 22 DETAIL FRAME 23 DETAIL CONCEALED FASTENING
NOTES:
1. 180 CONSTRUCTION IS 22 GA. STEEL
2. EACH BLADE IS INDIVIDUALLY ADJUSTABLE.
3. STANDARD FINISH IS 44 WHITE
OPTIONS:
D NO SCREW HOLES
D CONCEALED FASTENING
ACCESSORIES :
D 080 STEEL OPPOSED BLADE DAMPER
D SPF STEEL PLASTER FRAME
D SRAC325 STEEL SQUARE TO ROUND ADAPTER
DIMENSIONS ARE SHOWN AS
INCHES(MM)
1-WAY 2-WAY 3-WAY 4-WAY
~ ffim mm
1 2 2C 3 4 ••nna 1S 2S 2CR 3C 4S ~mu 1L 2L 2CL
Product Information is Sub· ect to Chan e Without Notice
Honeywell
VisionPRO® 8000 with RedLINK™
.. ~'l, -~:-~ 1
·IIEJSEl
i .,,:·· (1.l
I 12' \il \ .Js~ -~_._1 __ .,_
APPLICATION
The VisionPRO® 8000 with RedLINK™ features an effortless,
7-Day programmable touchscreen thermostat that provides
control of temperature, humidification, dehumidification, and
ventilation for up to 4 Hea-V2 Cool heat pump systems or up to
3 Hea-V2 Cool conventional systems for residential and
commercial applications.
FEATURES
• RedLINK™ Compatible
Increase your content and profit per job by including ·
RedLINK™ accessories that meet your customers comfort
and convenience needs. RedLINK accessories include the
Wireless Outdoor Sensor, Portable Comfort Control (PCC),
Equipment Interface Module (EIM), RedLINK Internet
Gateway, Wireless Indoor Sensor, TrueSTEAM™ humidi-
fier with Wireless Adapter, TrueZONE™ zoning panel with
Wireless Adapter, Vent Boost Remote and Entry/Exit
Remote.
. .
PRODUCT DATA
• Customizable Service Reminders
Set up to 1 o service reminders. Choose from the pre-set
options or customize your own. Reminders can be based
on date or the outdoor temperature.
• Universal Inputs
Thermostat -S1
EIM -S1, S2, S3, S4
Assignable inputs allow you to setup Indoor and Outdoor
Temperature Sensors, Discharge and Return Air Sensors
or Dry Contact Devices. Dry Contact Devices can be used
to trip pre-set or customized alerts on the thermostat home
screen. Note: Dry Contact Alerts require an Equipment
Interface Module (EIM).
• User Interaction Log
The interaction log stores history of thermostat setting
changes including temperature, system and installer setup.
You can use the interaction log to save time by determining
if the issue is a system error or an accidental user error.
The Interaction Log is only viewable on a computer after
you download·it from the thermostat to a microSD card.
• Selectable for Residential and Light Commercial
Applications
One thermostat does it all to meet the needs of Residential
and Light Commercial applications. Simply select Residen-
tial or Commercial during the installer setup. If Commercial
is selected, the thermostat will use commercial language,
meet building codes and offer 365 day holiday scheduling.
• MicroSD Card Port for Quick Installer Setup
Save time by using a microSD card to upload installer set-
tings and service reminders in one simple step.
• Selectable Sensors
When paired with a Wireless Indoor Sensor(s) you have
the ability to choose which sensor(s) to use for tempera-
ture, humidification and dehumidification. They can be
used in combination for temperature averaging-or individ-
ually-to condition humidity levels in separate spaces.
SPECIFICATIONS
Thermostat Description:
Feature Description
Powering method • Common wire or battery
System types (up to • Gas, oil or electric heat with air
4 heat/2 cool heat conditioning
pump and up to 3 • Warm air, hot water, high-efficiency
heat/2 cool furnaces, heat pumps, steam and
conventional) gravity
• Cool only
Changeover Manual or Auto changeover selectable
System setting Em Heat-Heat-Off-Cool-Auto
Fan setting Auto-On-Gire-Follow Schedule
Electrical Ratings for: the Equipment Interface Module and
VisionPRO Thermostats
NOTE: To find what terminals are available on the Equip-
ment Interface Module and the VisionPRO Thermo-
stats, see "Terminal Designations" below the table.
Voltage Max. Current
Terminal (50/60 Hz) Rating
W-O/B 18 to 30 VAC and 1.00A
750 mVDC
Y (cooling) 18to30VAC 1.00A
G (fan) 18to30 VAC 0.50A
W2 -Aux 1 (heating) 18to 30 VAC 0.60A
W3 -Aux 2 (heating) 18to30 VAC 0.60A
Y2 (cooling) 18to 30 VAC 0.60A
A-UA (Output) 18to 30 VAC 1.00A
U1, U1 30VAC max. 0.50A
U2,U2
U3,U3
Terminal Designations:
-Equipment Interface Module: R, RC, RH, C, W-O/B,
W2-AUX 1, W3-AUX 2, Y, Y2, G, A-UA, U1 U1, U2 U2,
U3 U3, S1 S1, S2 S2, S3 S3, S4 S4, A, B, C, D
-TH8321 Thermostat: R, RC, C, W-O/B, W2-AUX/E, Y, Y2,
G, A-UA, K, U1 U1, S1 S1
-TH8320 Thermostat: R, RC, C, W-O/8, W2-AUX/E, Y, Y2,
G, A-UA, K, S1 S1
-TH811 O Thermostat: R, RC, C, W-O/B, Y, G, K, S1 S1
Power Consumption of TH8321ITH8320ITH811 O:
Backlight on: 1.44 VA
Backlight off: 1.32 VA
RedLINK Communication:
Frequency: 900 Mhz frequency range
Re-Sync Time: RedLINK devices re-establish communication
within 6 minutes after AC power resumes.
· Temperature Setting Range:
Heating: 40 to 90 °F (4.5 to 32 °C).
Cooling: 50 to 99 °F (10 to 37 °C).
Temperature Sensor Accuracy:
± 1.5 Fat 70 F (0.75 C at 21.0 C)
3
VJSIONPRO® 8000 WITH REDLINK™
Humidification Setting Range:
10% to 60% RH.
Dehumidification Setting Range:
40% to 80% RH.
Humidity Display Range:
0%to99%.
Humidity Sensor Accuracy:
± 5% RH from 30% to 50% RH at 75 F.
Cool Indication:
VisionPRO® 8000 with RedLINK™ displays "Cool On" when
the thermostat turns the cooling on.
Heat Indication:
VisionPRO® 8000 with RedLINK™ displays "Heat On" when
the thermostat turns the heating on.
Auxiliary Heat Indication:
VisionPRO® 8000 with RedLINK™ displays "Aux Heat On"
when the thermostat turns the auxiliary heat on.
Interstage Differential:
Comfort: The thermostat keeps the indoor temperature within 1
degree of the setpoint (droop less control). The thermostat
turns on stage 2 when the capacity on stage 1 reaches 90%.
When the interstage differential is set to 1.0 or higher, the ther-
mostat stages the equipment based on how far the Indoor
temperature is from the setpoint (ISU 303 to 309). See
page 27 for more information.
Clock Accuracy: 1 minute per month at 77 °F (25 °C). ± 2
minutes per month over the operating ambient temperature
range.
Mounting Means:
Thermostat mounts directly on the wall in the living space
using mounting screws and anchors provided. Fits a hori-
zontal 2 x 4 in. junction box.
Equipment Interface Module (EIM) mounts on HVAC equip-
ment or on a wall in the equipment room.
4-5/
J
4•15/16 (126)
Inf -.
10--01
I (5 I I (5 I
i 0 0~ : Cv j
-3·5/1684-() M34521
Fig. 1. Dimensions of thermostat in in. (mm).
68-0312-02
INDUSTRIAL WASTEWATER DISCHARGE PERMIT
SCREENING SURVEY
Date UI tel·~
Business Name· Rf_c; f>.71.:-, C:i:::CM ...
StreetAddress 2-'Z...oo '.fhAAJ?Aj STE. "2..oS: C¥.t>tJA-b CA 4,z..008
EmailAddn;}SS ~p J~5=>"S B J)f Pf-2l'71Jl,YC. . Cdot::t
PLEASE CHECK HERE IF YOUR BUSINESS IS EXEMPT: (ON REVERSE SIDE CHECK TYPE OF BUSINESS) D
Check all below that are present at your facility:
Acid Cleaning Ink Manufacturing Nutritional Supplement/
Assembly Laboratory Vitamin Manufacturing
Automotive Repak ' Machining /Milling Painting/ Finishing
Battery Manufacturing Manufacturing Paint Manufacturing
Biofuel Manufacturing Membr~me Manufacturing Personal Care Products
Biotech Laboratory (Le. water filter membranes). Manufacturing
Bulk Chemical Storage Metal Casting/ Forming· Pesticide Manufacturing /
CarWash Metal Fabrication Packaging.
Chemical Manufacturing Metal Finishing Pharmaceutical Marn;tfacturing
Chemical Purification Electroplating (including precursors)
Dry Cleaning Electroless plating Porcelain Enameling
Electrical Component Anodizing Power Generation
Manufacturing Coating (i.e. phosphating) Print Shop
Fertilizer Manufacturing Chemical Etching / Milling Research and Development
i=ilm /X-ray Processing Printed Circuit Board Rubber Manufacturing
Food Processing Manufacturing Semiconductor Manufacturing
Glass Manl!facturing Metal Powders Forming Soap/ Detergent Manuf~cturing
Industrial Laundry Waste Treatment/ Storage
SIC Code(s) (if known): ______________________ _
Brief description of business activities (Production/ Manufacturing Operations): f2<€.f?.(.(S.[__ . p..oo,.,, · -~"' 1:rr :to f:,Loc, CQC1.1M> .M-'A.
Description of operations generating wastewater (djschar_ged to sewer, hauled or evaporated):
Estimated volume of industrial wastewater to be discharged (gal I day): --=-tJ-~ __ C.. ___ _
List hazardous wastes generated (type I volume): _ _,}-J~{;)J~u:,,,f.J'i __________ _
Date operation began/or will begin at this location: 0 ( l ;A\ \ 5=
Have you ap~d for a Wastewater Discharge Permit from the Encina Wastewater Authority?
Yes ~ If yes, when: ,
Site Contact . N ~·" Title f /l!>~ u__i; J.JvwA.,~~
Signature · Phone No. (7 t,o i 'I Cf] .. 00 5:,
EN CINA WASTEW A . ER AUTHORITY, 6200 Avenida Encinas Carlsb~d, CA92011 (760) 438-3941
FAX: {760) 476-9852
SAN DIEGO REGIONALThV f(pl/Li2LL{
HAZARDOUS MATERIALS QUESTIONNAIRE
OFFICE USE ONLY
UPFP# ______ _
HV# ________ _
BP DATE __ _,_ _ _._ __ _
;PN1!-z. '? .. r2.o -41
Plan File#
1-=-,.---,-,,--,--,--------------------------------------'------.. -· .. ,-, ___ ----· Project Contact \ C--. Telephone# _ "" OJ 0'6 I l /-,, A <,1 -l~P o~t?_ v~, 1 x \J'
"The:followln9.quostlons ropre~tacilit'f's.actlvllles, NOT the specific project description.
PART I: FIRE DEPARTMENT-HAZARDOUS MATERIALS DIVISION: OCCUPANCY CLASSIFICATION: Indicate by circling the item, whether your business
will use, process, or store any of the following hazardous materials. If any of the items are circled, applicant must contact lhe Fire Protection Agency with
Jurlsdlctlon prior to plan submittal. ·
1. Explosive or Blasting Agenls 5. Qrganic Peroxides 9. Water Reactives 13. Corrosives
2. Compressed Gases 6. Oxidizers 10. Cryogenics 14. Other Health Hazards
3. Flammable/Combustible Liquids 7. Pyrophorics 11. Highly Toxic or Toxic Materials 15. None of These.
4. Flammable Solids 8. Unstable Reactives 12. Radioactives
PART II: SAN DIEG·o COUNTY DEPART ENT OF ENVIRONMENTAL HE LT -HAZA 00 S A ERIA OIV S!ONS. HMO,k lfth1< answer lo any of the
questions ls yes. llppllcnnt musl conla.cUhe County-ul San Q1ego Mawrdous Materials Div mon. 1255 lrrfperial vemIe. 3 lloo,, Sao Di<;1go, CA 92101. can (619) .338,2222: prior to the Issuance of a building permit.
FEES ARE REQUIRED. Expected Date of Occupancy: 12 I / "3 0 I 1 S'
YES NO
1. 0 ,tl. Is your business listed on the reverse side of this form? (check all lhat apply).
2. 0 · ~ Will your business dlspose·of Hazardous Substances or Medical Waste in any amount?
3. 0 ~ Will your business slore or handle Hazardous Substances In quanUlies equal to or greater than
· 55 gallons, 500 pounds, 200 cubic feet, or carcinogens/reproductive toxins in any quantity?
4,
5
6,
0
D D
~ Will your business use an existing or install an underground storage tank?
6( Will your business.store or handle Regulated $ubstances (CalARP}?
fi{' Will your business use or install a Hazardous Waste Tank System (Title 22, Article 10)?
0 CalARP Exempt
I
Date Initials
D CalARP Required
I
Date Initials
D GalARP Complete
Date lnltials
PART Ill: SAN DIEGO COUNTY AIR POLLUTION CONTROL DISTRICT: If the answer to any of the quesllons below is yes, applicant must contact lhe Air
Pollutlon Control District (APCD), 10124 Old Grove Road, San Diego, CA 92131-1649, telephone (858) 586-2600 prior to the Issuance of a bulldfng or demolition
permit. Note: if the answer lo questions 3 or 4 is yes, applicant must also -submit' an asbestos notification form to the APCD at least 10 working days prior to commencing demolition or renovation, except demolltjon or renovation of residential structures offour units or less. Contact the APCD for more information.
1 YfjS ~ Will the subject facllU ,::,r co activities lt1ciude operations or equipment that emit or are capable of emitting an air contaminant? (See the APCD factsheet a .QUlllnmlli!W,~P,ill!!llk'i.,J,!;lf., and the list or typical equipment requiring an APCD permit on the reverse side
of this from. Con you have any questions).
2. 0
D
0
0 (ANSWER ONLY IF QUESTION 1 IS YES) Will the subject facilily be located within 1,000 feet of the outer boundary of a school (K through 12)?
(Pubfic and private schools may be found after search of the California School Directory at http://www.cde.ca.gov/re/sd/; or contact the
appropriate school district).
3
4.
Wtli lhere be renovation that involves handling of any friable asbestos materials, or dislurbing any material that contains non-friable asbestos?
Will there be demolition involving the removal of a load supporting structural member? ·
Bt1e!ly describe business activities: 1) oC.C{Jf~(,."( Briefly describe proposed proj,;n;J.
AM wt T'i fOJL. iws, T~) l'"~IJ!MJrJ M t-"' t.JZ..q ~ .c...
I declare under i:ienalty of perjury that to !he best of my knowledge an fZJ .. C., ~'J· ~ti'k:rt,t.;> ~&;;;;;:;;;: Authorized Agent
FOR OFFICIAL USE ONLY: FIRE DEPARTMENT OCCUPANCY CLASSIFICATION; ______________________________ _
BY:~-_______________________ _ DATE: __ ,_/ __ ,_/ __
EXEMPT OR NO FURTHER INFORMATION REQUIRED RELEASED FOR BUILDING PERMIT l!UT NOT FOR OCCUPANCY RELEASED FOR OCCUPANCY
.. APCD COUNTY-HMO APCO COUNTY-HMO APCD
'. ·, ;.,.-/ ,.
:~ ,, ',
t ..... ~i~·--~t, ..... ~;~ ~~ < :,,.'J'-~ ,. {-~, 1, n fo wrwa?l, ti "ti·. W:!+':.:."· ··"'· i.\ , • ·1 .... ">, -ri .·<:t1lj i ........... /rt .. ,.-,.~}·
' .. •'(,l ... ~-~ ''., : J";V
Ji,\,\ ,et.,,.~
HM-9171 (0-1/07) County of San Diego DEH Hazardous Materials Division
«~ ~ CITY OF
PLUMBING,
ELECTRICAL,
MECHANICAL
WORKSHEET
Development Services
Building Department
1635 Faraday Avenue
760-602-2719
www.carlsbadca.gov CARLSBA B-18
Project Address: Permit No.: CB1 Lf-3\97
Information provided below refers to worl:l being done on the above mentioned permit only.
This form must be completed and returned to the Building Department before the permit can be issued.
B-18
Building Dept. Fax: (760) 602-8558
Number of new or relocated fixtures, traps, or floor drains....................................................... 13
New building sewer line? ......................................................................................... Yes __ No -.../
Number of new roof drains?............................................................................................................... N/A
Install/alter water line?......................................................................................................................... ~
Number of new water heaters? ........................................................................................................ . 1
Number of new, relocated or replaced gas outlets?.................................................................... N/A
Number of new hose bibs?.................................................................................................................. N/A
Upgrade existing panel? ......................................................................................... Yes __ No _L
From NIA Amps to NIA Amps
Number of new panels or subpanels? .............................................................................................. __NL.A_
Single Phase ............................................................................................ Number of new amperes_NLA_
Three Phase .............................................................................................. Number of new amperes-12.5A.
Three Phase 480 .: ................................................................................... Number of new amperes....N./.A...._
Remodel (relocate existing outlets/switches or add outlets/switches)?
Yes ~ No __
Number of new furnaces, A/C, or heat pumps? ....................................................................... J... 1
New or relocated duct wor~? .......................................................................... Yes -.../ No_-_-_-_-
Number of new fireplaces? ................................................................................................................. 0
Number of new exhaust fans?............................................................................................................ 5
Relocate/install vent?............................................................................................................................ 0
Number of new exhaust hoods?........................................................................................................ 0
Number of new boilers or compressors? ........... , ............................................... Number of HP O
Page 1 of 1 Rev. 03/09
0
0
CB143197 2200 FARADAY AV 205
REGENTS GYM= CREATE NEW SUITE
FROM EXISTING SUITE 210 2,265 SF OFFICE TO GYM
tt\l~!Ly 'ID p l.-FYl.J ) 81\&--, r ,!2.6 .._ B§--1 L w I en~ .J l'.9 ')
i\ ( 20/ lL-f p,i-.~ ""\b
10-J s),Lf ~ @.-ft2.-
/z,/-z--~/ rt;-P--n/ 10
1-z__(zef (1c+ ~ ----_L.
~
1 -'"', •V~ ,., >¢Hi '*0 ~-:%~' .. '.~*"':,.::.tv.:,*: ~J-~:~:_N~t _:~ .... ~
_ .. _,.. ____________ ... ____ ..,. .. _________ ~·-----------
Final Inspection required by:
CJ Plan O CM&I CJ Fire a
SW OISSUED I l:JCV.
Approved Date By
BUILDING 1-z__/z,.,~/t..J , JLIJ
PlANNING 1 / /2P(f'-( I r.,.,c;.
ENGINEERING -/:)..} '6")1'-f /::...L
FIRE Expedite? vtG} l.:>-f ~ ''i ~
DIGITAL FILES Reauired7 y N
HazMat
APCD
Health
Forms/Fees Sent Rec'd Due? By
Encina 11 lf'iS' 1'r y NI p'-,o-v
Fire ,· I y N
HazHealthAPCD 1, \l'?, 114-~,1r. /!!I y N
PE&M (\.,l4<ll'-+' /IY"7n/1c../ y N
School y N
Sewer y N
Stormwater y N
Special Inspection y N
CFD: y N
LandUse: Density: lmpArea: FY: Annex: Factor:
PFF: y N
Comments Date Date Date Date
Building t//v.d(Lf
Planning
Engineering
Fire
Need?
DDone
DDone
DDone
DDone