B U I L D I N G P E R M I T Permit No: CB951615
Project No: A9502354
Development No:
Job Address: 2233 FARADAY AV
Permit Type: INDUSTRIAL TENANT
Parcel No: 212-061-25-00
IMPROVEMENT
Suite: A
Lot#: 51n 12,112,195 0001 01 02
Valuation: 20,494 >"" •• ;--,r_17 Construction ':eyt,~': ,; 7r-.... , [ .. , VN .,_ ..,._, ... "v
Occupancy Group: B2 Reference#:
Description: CONV WARHS TO OFFICE, SHIP/REC
: UPGRADE WAREHOUSE W/AC/HEAT ETC
Status:
Applied:
Apr/Issue:
Entered By:
619-471-9388
ISSUED
11/06/95
12/11/95
RMA
Appl/Ownr: CSI
135 VALLECITOS DE OSO, #A
SAN MARCOS, CA 92069
--= ··~ ---~ *** Fees Required *** ,,.--*** Feiifs, .. follected & Credi ts *** ---------------------------/~ /-. ' ~---' --, , , --,,, . ..., -",, ..... , -------------------------
1 984 /00 (,~ 1 /: \ , ,,,\ ", I ; • ~ --' : --/ I • --..... // . oo> _, .. · Tdtal/Gredits: . oo
1,.-'984. o·o\ .... •-' Total <P:ayrne'nt~,: 276. 00
Fees:
Adjustments:
Total Fees:
/ /\ '-"·· :,..-·-,:;/7 r· • -~a:1.an._c'~' ~Bt1.e \_ 1 , 7 0 8 . 0 0
Fee description / '"-~·-,. // ,./:-·::,-I -,.>iini t~" . (F~ejurti t Ext fee Data
-------------------/-(-~~-:----_, ,../ ------,-;;_ j',r~•\" -----\\\:.:-'._ _____ --\ ------------------
Building Permit --. ·, c·· 216. O O ;' / // Plan Check 1 140.00
St M t ' F ,, rt -\ : ,:-"1 n 00 rong o ion ee i. • , ; • ,. _;:-.·, ,-':t:.
Enter Number of EJ:?U'\,~:-:-/Water rl:#.~"-'-t. _ ... -~_;. _.).9'_:·1;: \.__ > 456.00
Ent er " Y II to A t · 1 L • ~-m ' ' > ' ; ' / '' · 3 7 3 0 0 Y u. oqa_ c 1c~1:_~-e, __ J if.~ . y·;, 1 { _, .. -\\: / : • •
(Lie '!I'x) C.F\Ei-., \; ::::--..___ \ j;, t ! ,:-·,.,)/ •
\ ( TiF'-,f_unqy'' \';-'./ t;· ' /
\ (TIF CFQ Fund)...:. .:·-.-_ __.->· -
'd \ '--! ' ·Y $ Enter Bri ge Fee \ /::;-..._ --nico::ir-0:,:nJ-1 4.90 * BUILDING TOTAL \ ':· ,; -.,__ wv .. . · ' \ ,... ..,.,,..,,. ' '' ~" \ \ ' Enter "Y" for Plumbi1:'g~Is-s_:9-J?;~e .. :·->·--· .. -
Enter "Y II for Electric l~su~.' f,ee· .. ·, ?.:~ ,--
Remodel/Alter Per AMP '--,,______ '--::: / : ,>: '(1 * ELECTRICAL TOTAL ',-..._ v
Enter 'Y' for Mechanical Issue Feel
Install Furn/Ducts/Heat Pumps >
* MECHANICAL TOTAL
1
344.00
I 124.00
114.00
154.00
1925.00
N
10.00 y
.25 25,00
35.00
15.00 y
9.00 9.00
24.00
APPROVAL
,iNSP. _,~ __ DATE WL-
lcLEARANCE _____ ,
CITY OF CARLSBAD
2075 Las Palmas Dr., Carlsbad, CA 92009 (619) 438-1161
PERMIT APPUCATION PLAN CHECK NO.
City of Carlsbad Building Department
2075 Las Palmas Dr., Carlsbad, CA 92009 (619) 438-1161
1. PERM1'1' 1YPE
From List 1 (see back) give code of Permit-Type: __ -..k ___ J..,...._"J ______ _
For Residential Projects Only: From List 2 (see back) give
Code of Structure-Type: ___________________ _ 4507 11/06/95 0001 01
C-PRMT
Net Loss/Gain of Dwelling Units __________________ _
FOR OFFICE USE ONLY
Bu1ldmg or Smte No. A
mt o.
D 2 Soils Report
CITY s. PROPERTI oWNllll
NAME (last name first)
STATE
(Lo~ C0.
STATE~'
NAME (last name first) C---$ '-=l=-r\ _
CITY s;:-(Y'\ (V}?rcos STATL.4 '
STATE LlC. #0: ~~
DAY TELEPHONE
DOWNER DA.GENT FOR OWNER
ZIP CODE DAY TELEPHONE ct
ADDRESS "Z--Z.. 33 ~ ~Ovf =tt='
ZIP cooll t.(J{)"f DAY TELEPHONE 3-g--+ 1,b:J
ADDREss f3s-VttLLec,~
ZIP CODE Cf 1.D 6 °I DAY TELEPHONE 4'71-°IJ g-l(
LlCENSE CLASS 8 CITY BUSINESS LlC. #
ast name 1rst f"r... ~ 'i
CITY S~f\-'r'~f,\-i~dnE DAY TELEPHONE STATE LlC. #
1. WoRl<ERs' OOMP£NsA1IDN
02
Workers' Compensation Declaration: I hereby affirm that I have a certificate of consent to self-msure issued by the Director of Industnal
Relations, or a certificate of Workers' Compensation Insurance by an admitted insurer, or an exact copy or duplicate thereof certified
by the Director of the insurer thereof filed w· h the Building Inspection Department (Section 3800, Lab. C).
INSURANCE COMPANY ~tot;-e_, POLlCY NO. 04.b-
SIGNATURE DATE s. oWNilt-BUllJJER DEcWtATION
D
D
D
Owner-Bmlder Declaration: I hereby afhrm that I am exempt from the ContractoPs Llcense Law for the foilowmg reason:
I, as owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not intended or
offered for sale (Sec. 7044, Business and Professions Code: The Contractor's License Law does not apply to an owner of property who builds
or improves thereon, and who does such work himself or through his own employees, provided that such improvements are not intended
or offered for sale. If, however, the building or improvement is sold within one year of completion, the owner-builder will have the burden
of proving that he did not build or improve for the purpose of sale.).
I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions
Code: The Contractor's Llcense Law does not apply to an owner of property who builds or improves thereon, and contracts for such projects
with contractor(s) licensed pursuant to the Contractor's License Law).
I am exempt under Section _______ Business and Professions Code for this reason:
(Sec. 7031.5 Business and Professions Code: Any City or County which requires a permit to construct, alter, improve, demolish, or repair
any structure, prior to its issuance, also requires the applicant for such permit to file a signed statement that he is licensed pursuant to the
provisions of the Contractor's License Law (Chapter 9, commencing with Section 7000 of Division 3 of the Business and Professions Code)
or that he is exempt therefrom, and the basis for the alleged exemption. Any violation of Section 7031.5 by any applicant for a permit
subjects the applicant to a civil penalty of not more than five hundred dollars [$500]).
SIGNATURE DATE
COMPLETE THts SECTION FOR NON-RESIDENTIAL BUILDING PERMITS ONLY:
276:100
Is the applicant or future building occupant required to submit a business plan, acutely hazardous materials registration form or risk management and
prevention program under Sections 25505, 25533 or 25534 of the Presley-Tanner Hazardous Substance Account Act?
DYES D NO
Is the applicant or future building occupant required to obtain a permit from the air pollution control district or air quality management district?
DYES D NO
Is the facility to be constructed within 1,000 feet of the outer boundary of a school site?
DYES D NO
IF ANY OF THE ANSWERS ARE YES, A FINAL CERTIFICATE OF CXDJPANCY MAY NOT BE ISSUED AFTER JULY 1, 1989 UNLF.5S THE APPIJCANT
HAS MET OR IS MEETING THE REQUIREMENTS OF THE OFFICE OF EMERGENCY SERVICES AND THE A1R. POLLUTION CONTilOL DISfRICT.
ere 1s a construction en 1s permit 1s issue
LENDER'S NAME LENDE
I certify that I have read the application and state that the above mformation 1s correct. I agree to comply with all City ordinances and State laws
relating to building construction. I hereby authorize representatives of the City of Carlsbad to enter upon the above mentioned property for inspection
purposes. I AI.SO AGREE TO SAVE INDEMNIFY AND KEEP HARMLESS THE CITY OF CARlSBAD AGAINSf ALL IJABILITIF.S, JUDGMENTS, cosrs
AND EXPENSFS WIIlCH MAY IN ANY WAY ACCRUE AGAINSf SAID CITY IN CONSEQUENCE OF THE GRANTING OF TIIlS PERMIT.
OSIIA: An OSHA permit is required for excavations over 5'0" deep and demolition or construction of structures over 3 stories in height.
S E W E R P E R M I T
12/12/95 17:08
Page 1 of 1
Permit No: SE950127
Bldg Planck#: CB951681
Job Address: 2233 FARADAY AV
Permit Type: SEWER -OFFICE/WAREHOUSE
Parcel No: 212-061-25-00
Suite: B-C
3127 1.2/12/95 000.1 o:. 02
Description: WAREHOUSE TO OFFICE-WALLS, ELC
NEW HVAC UNIT,CEILING UPGRADE
S t ii"ffilST: I S S l.EE.Q . (;(.
Perrnitee: CSI 619-471-9388
Applied: 11/29/95
Apr/Issue: 12/12/95
Expired:
***
135 VALLECITOS DE ORO, #A
SAN MARCOS, CA 92069
Prepared By: MAM
Fees Required *** *·*-*··· ·· ....... Fees Collected & Credi ts *** ,,,.,.,.-----
----------------------------,,r_,,,r ,• -------------~ ..... ,----------------------------,-/,' .. ,_
51 0 , 00 / / ' . ..... '•"' /:·oo .. : ,··Tot'a:i'-Credi ts: . 00
5,10. 00.~ . ..., ,/Tot:a'l:''Pdyment-S: . 00
Fees:
Adjustments:
Total Fees:
/ ; J B~'rance-<Due\: 51 0 . 0 0
Fee description / ,'.\ / ,<-<. tjn.:tt~ .. <'. 0;:ee/Oni t Ext fee Data
/ ,,.,. ,\ '..._ / p· / /, ', ""-\ '\ ..,. () \ \
• / ,,::·~~ «,, ~ /.' V './ , , ''. ' '~~ ~ ',\ ~,, -~ ,,,~-....l\ -
Enter Office Square f7?o.:tag~ > " , ·.' 5 2 o \ "'·<.. \ . 2 9
<Enter CREDIT EDUs,> ~·.-··. · .· ~.· ·y .··:.:_·-··.::.,. ... :!,{y '\ · -.10
Total EDUs ' :--. . ··,, 4
-.,., -;~~''.;;~;;;,..:-·~/;:/ • • ,/ ', • 19
Sewer Fee , , , F· · /]. :.:, · 343.00
Enter Sewer EDUs and:~Be.6.efit Arc~~··v ., /> .:· . i,9/;·, / 167. 00 F
* SEWER TOTAL fr\;·1 :, ';;: ~· /_~,..,··.;_°':. · 510.00 ',, ,1,/', \ (1"•• /" {t,.::,j/ :
/.
(' (
,, '\ -i J_~ r .... , ,, : , )J, 1/ /
\;,·,-··· f· .,,, : t}. ',\. . > . _.,,. /
" ' y /
l!JCQM?ORf..'YE.D /,,. ---
105:} \ \',' ~ '-,. .,
i r·-/
~. i ~. !" -~ ' . ·,
\NSP.
CLEARANCE-----\
CITY OF CARLSBAD
2075 Las Palmas Dr., Carlsbad, CA 92009 (619) 438-1161
CITY OF CARLSBAD
INSPECTION REQUEST
PERMIT# CB951615 FOR 05/10/96
DESCRIPTION: CONV WARHS TO OFFICE, SHIP/REC
UPGRADE WAREHOUSE W/AC/HEAT ETC
TYPE: ITI
JOB ADDRESS: 2233
APPLICANT: CSI
CONTRACTOR:
OWNER:
FARADAY AV
PHONE:
PHONE:
PHONE:
INSPECTOR AREA TP
PLANCK# CB951615
OCC GRP B2
CONSTR. TYPE VN
STE: !37'; LOT:
REMARKS: MW/OAVE/471-9388
SPECIAL INSTRUCT:
619-471-u
INSPECTOR ------------
TOTAL TIME:
--RELATED PERMITS--PERMIT#
SE950122
AS950074
FAO96002
TYPE swow
ASTI
FAOO
STATUS
ISSUED
ISSUED
ISSUED
CO LVL DESCRIPTION ACT COMMENTS
19 ST Final Structural
29 PL Final Plumbing
39 EL Final Electrical
49 ME Final Mechanical i--
-----------------------------------------------------------
***** INSPECTION HISTORY *****
DATE DESCRIPTION ACT INSP COMMENTS
011796 Final Combo co TP TITLE 24 ISS.ROOF ACCESS
011196 Final Combo co TP NEED PLANS,JOB CARD
010996 Final Combo NR TP BLOG SUITE LOCKED
122995 Rough Combo co PO ND FIRE APPROVAL
122895 Rough Combo co PD
121995 Interior Lath/Drywall AP TP
121595 Rough Combo PA PK SEE JOB CARO
121495 Rough Combo co TP NO PLANS OR CARO
EQPT
FINAL BUILDING INSPECTION
DEPT: BUILDING ENGINEERING (EIRE~----:,PLANNING U/M WATER
PLAN CHECK#: CB951615
PERMIT#: CB951615
PROJECT NAME: CONV WARHS TO OFFICE, SHIP/REC
DATE: 01/09/96
PERMIT TYPE: ITI
UPGRADE WAREHOUSE W/AC/HEAT ETC
ADDRESS: m,.J.3 FARADJ\Y Ay_§U-ITE.#·--A----:J
CONTACT PERSON/PHONE#: MW/DAVE/471-9388
SEWER DIST: CA WATER DIST: CA
lij~~~~'W~~ ~ JAN 101996 M
INSPECTEDf;
BY: (!, . dl/y
DATE
INSPECTED: /f~/~& APPROVED K DISAPPROVED ( l
INSPECTED
BY:
INSPECTED
BY:
COMMENTS:
DATE
INSPECTED:
DATE
INSPECTED:
APPROVED DISAPPROVED
APPROVED DISAPPROVED
\
\
EsGil Corporation
Professiona{ Pfan !R.f-'lliew 'Engineers
DATE: 11/28/95
JURISDICTION: Carlsbad
PLAN CHECK NO.: 95-1615
PROJECT ADDRESS: 2233 Faraday, Suite A
PROJECT NAME: TI
SET: II
~NT
~ CJ FIRE
CJ PLAN REVIEWER
CJ FILE
• The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
D The plans transmitted· herewith will substantially comply with the jurisdiction's ********** codes
when minor deficiencies identified below are resolved and checked by building department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
D The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
D The applicant's copy of the check list has been sent to:
CSI General
135 Vallecitos De Oro, Suite A, San Marcos, CA 92069
• Esgil Corporation staff did not advise the applicant that the plan check has been completed.
D Esgil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted:
Date contacted: (by: ) Telephone#:
• REMARKS: The designer inked additional information on the plans to satisfy plan corrections.
By: Pete Fischer
Esgil Corporation
0 GA D CM D GP 0 PC 11/27/95
Enclosures:
trnsmtl.dot
EsGil Corporation
Professiona[ Pfan !l{_eview 'Engineers
DATE: 11/14/95
JURISDICTION: Carlsbad
PLAN CHECK NO.: 95-1615
PROJECT ADDRESS: 2233 Faraday, Suite A
PROJECT NAME: TI
SET:I
D ~T
~ D FIRE
D PLAN REVIEWER
D FILE
D The plans transr:nitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's *********** codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's ********** codes
when minor deficiencies identified below are resolved and checked by building department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
• The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
• The applicant's copy of the check list has been sent to:
CSI General
135 Vallecitos De Oro, Suite A, San Marcos, CA 92069
• Esgil Corporation staff did not advise the applicant that the plan check has been completed.
D Esgil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted:
Date contacted: (by: ) Telephone #:
D REMARKS:
By: Pete Fischer Enclosures:
Esgil Corporation
IX] GA 0 CM D GP IX] PC 11/7/95 trnsmtl.dot
9320 Chesapeake Drive, Suite 208 + San Diego, California 92123 + (619) 560-1468 + Fax (619) 560-1576
Carlsbad 95-1615
11/14/95
PLAN REVIEW CORRECTION LIST
TENANT IMPROVEMENTS
PLAN CHECK NO.: 95-1615
OCCUPANCY: B2
TYPE OF CONSTRUCTION: VN SPR
ALLOWABLE FLOOR AREA: NO CHANGE
SPRINKLERS?: YES
REMARKS:
DATE PLANS RECEIVED BY
JURISDICTION:
DATE INITIAL PLAN REVIEW
COMPLETED: 11/14/95
FOREWORD {PLEASE READ):
JURISDICTION: Carlsbad
USE: OFFICE/WAREHOUSE
ACTUAL AREA: TI = 1440
STORIES: 1
HEIGHT: NO CHANGE
OCCUPANT LOAD: TI = 14
DATE PLANS RECEIVED BY
ESGIL CORPORATION: 11/7/95
PLAN REVIEWER: Pete Fischer
This plan review is limited to the technical requirements contained in the Uniform Building Code,
Uniform Plumbing Code, Uniform Mechanical Code, National Electrical Code and state laws
regulating energy conservation, noise attenuation and access for the disabled. This plan review
is based on regulations enforced by the Building Department. You may have other corrections
based on laws and ordinances enforced by the Planning Department, Engineering Department,
Fire Department or other departments. Clearance from those departments may be required
prior to the issuance of a building permit.
Code sections cited are based on the 1991 UBC.
The following items listed need clarification, modification or change. All items must be satisfied
before the plans will be in conformance with the cited codes and regulations. Per Sec. 303 (c),
1991 Uniform Building Code, the approval of the plans does not permit the violation of any
state, county or city law.
To speed up the recheck process, please note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet number, specification section, etc.
Be sure to enclose the marked up list when you submit the revised plans.
LIST NO. 40, TENANT IMPROVEMENTS WITHOUT SPECIFIC ENERGY DATA OR POLICY SUPPLEMENTS (1991UBC) tiforw.dot
Carlsbad 95-1615
11/14/95
1. Please make all corrections on the original tracings and submit two new sets of
prints, to:
Esgil Corporation, 9320 Chesapeake Drive, Suite #208, San Diego, CA 92123,
(619) 560-1468.
OR
The jurisdiction's building department.
2. Each sheet of the plans must be signed by the person responsible for their
preparation. Business and Professions Code.
3. Indicate the use of all spaces adjacent to the area being remodeled or improved.
4. Show any existing fire rated area separation walls and occupancy separation
walls. Provide a note on the plans stating "Penetrations of fire-resistive walls
shall be protected as required in UBC Sections 4304 ."
5. Identify on the plans which doors are new and which are existing. Show safety
glazing per 5406 adjacent to all new doors.
6. If both sexes will be employed and the number of employees exceeds four,
provide separate toilet facilities for men and women. If "both sexes will be
employed and the total number of employees will not exceed four", and only one
restroom is provided, note the words in quotation above on the floor plan.
Section 705(c).
7. Indicate the weight of the new roof mounted equipment. Verify the existing roof
framing is adequate to support the new equipment.
8. The tenant space and new and/or existing facilities serving the remodeled area
must be accessible to and functional for the physically disabled. See the
attached correction sheet. Title 24, Part 2.
• CITY OF CARLSBAD SUPPLEMENT
9. No wiring is permitted on the roof of a building and wiring on the exterior of a
building requires approval by the Building Official. (City Policy)
10. All roof-mounted equipment shall be concealed from view. Provide structural
detailing for the screening. (City Policy 80-6).
• MISCELLANEOUS
11. See the attached for all plumbing, mechanical, energy and electrical corrections.
Carlsbad 95-1615
11/14/95
12. To speed up the review process, note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet, note or detail number,
calculation page, etc.
13. Please indicate here if any changes have been made to the plans that are not a
result of corrections from this list. If there are other changes, please briefly
describe them and where they are located in the plans.
• Have changes been made to the plans not resulting from this correction list? Please
indicate:
Yes D No D
14. The jurisdiction has contracted with Esgil Corporation located at 9320
Chesapeake Drive, Suite 208, San Diego, California..92123; telephone number of
619/560-1468, to perform the plan review for your project. If you have any
questions regarding these plan review items, please contact Pete Fischer at
Esgil Corporation. Thank you.
+ PLUMBING, MECHANICAL AND ENERGY CORRECTIONS
+ PLAN REVIEWER: Glen Adamek
• PLUMBING (UNIFORM PLUMBING CODE)
15. Show the existing water heater size, type, and location.
• MECHANICAL (UNIFORM MECHANICAL CODE)
16. Detail ladder access to roof mounted HVAC equipment.
17. Detail disposal of main condensate drainage from air conditioning units. (UMC
Section 510)
• ENERGY CONSERVATION
18. Show the daylit areas and required daylit area lighting controls for lighting in
daylit areas. Title 24, Part 6, Section 131(c).
19. The corrected, completed and signed ENV-1, L TG-1, and MECH-1 forms must
be imprinted on the plans.
Carlsbad 95-1615
11/14/95
20. The energy design does not match the plans.
a) The energy design shows only Office occupancy. The plans show only
about 190 square feet of Office, 220 square feet of Restroom, Corridor &
Support Area, 570 square feet of Storage (warehouse), and 460 square
feet of General Commercial and Industrial Work (shipping/receiving).
Please correct the LTG-2 form. ·
b) The plans do not show the wattages of the light fixtures and number of
tubes per fixture, as per the energy design. Please correct.
c) Light fixture in the newly conditioned restroom is not shown on the plans
and in the energy design.
Note: If you have any questions regarding this plan review list please contact
Glen Adamek at (619) 560-1468. To speed the review process, note on this list
(or a copy) where the corrected items have been addressed on the plans.
DISABLED ACCESS REQUIREMENTS FOR REMODELS1
(alterations. structural repairs. additions. tenant improvements and occupancy changes}
A GENERAL
Full access compliance is required for remodels, including:
1. The specific area being remodeled, (i.e., the "new" work).
2. Existing elements in the path of travel to the remodeled area.
{a)Parking, (b)Walks, (c)Hazards, (d)Curb Ramps, (e) Ramps, (f)Elevators, (g) Stairs.
Show the complying path of travel from the disabled parking to the
remodeled area on the site plan.
3. Entrance to the remodeled area.
(a)Entrance doors, (b)Exit doors.
4. Existing sanitary facilities serving the remodeled area.
5. Existing drinking fountains and telephones serving the remodeled area.
1 Based on the provisions in Title 24, Part 2 of the California Building Code, Effective April 1, 1994
2Note: In determining the value of a remodel, the total costs of all improvements over the last 3 years along the same
path of travel must be included (even if the previous remodels were done by other tenants). The 20-percent provisions
for determining if upgrade costs are disproportionate and for determining the amount to spend on upgrades shall be
based on this total value. Please complete the attached declaration form (Form HA-1).
Specify lever-type hardware for passage doors on floors accessible to the disabled.
Section 2-3304, Title 24.
Carlsbad 95-1615
11/14/95
VALUATION AND PLAN CHECK FEE
JURISDICTION: Carlsbad PLAN CHECK NO.: 95-1615
PREPARED BY: Pete Fischer DATE: 11/14/95
BUILDING ADDRESS: 2233 Faraday, Suite A BUILDING OCCUPANCY: B2
BUILDING PORTION BUILDING AREA
(sq. ft.)
Tl VALUE PER CITY
Air Conditioning
Fire Sprinklers
TOTAL VALUE
UBC Building Permit Fee:
UBC Plan Check Fee:
Comments:
TYPE OF CONSTRUCTION: VN SPR
VALUATION
MULTIPLIER
APPLICATION
VALUE
51,840
51,840
$ 423.50
$ 275.28
($)
Sheet 1 of 1
valuefee.dot
. ·' 1· City of Carlsbad
M § ei• 11 ,f§§ I I ei• I •24 •El I•• ,f§ h I
/~ BUILDING PLANCHECK CHECKLIST ,,.,-,
DATE: '6/4£ PLANCHECK NO. CB :Z.J /6 /.6-
BUILDING'AORESS: cJ)-f) 3 3 P /f /e.4 o d Y ~ .
PROJECT DESCRIPTION~ffto sc 111/aQF ;:6 OPi 5tcC. 5/t::t'r ;;l:z;--6; q-ffi-0
ASSESSOR's PARCEL NOMBER: ' EST. VALUE 57,/'L/f
ENGINEERING DEPARTMENT
APPROVAL
The item you have submitted for review has been
approved. The approval is based on plans, information
and/or specifications provided in your submittal; therefore
any changes to these items after this date, Including field
modifications, must be reviewed by this office to insure
continued conformance with applicable codes. Please
review qarefully all comments attached, as failure to
comply with instructions in this report can result in
suspension of permit to build.
DENIAL
Please see the attached report of deficiencies marked
with O Make necessary corrections to plans or
specifications for compliance with applicable codes and
standards. Submit corrected plans and/or specifications
to this office for review.
By: _________ Date: ___ _
D By: D~ A Right-of-Way permit is required prior to construction -------------
of the following improvements:
ATTACHMENTS
D Dedication Application
D Dedication Checklist
D Improvement Application
D Improvement Checklist
D Future Improvement Agreement
D Grading Permit Application
D Grading Submittal Checklist
D Right of Way Permit Application
D Right of Way Permit Submittal Checklist
and Information Sheet
D Sewer Fee Information Sheet
By: _________ Date: ___ _
ENGINEERING DEPT. CONTACT PERSON
NAME: _____________ _
City of Carlsbad
ADDRESS: 2075 Las Palmas Dr., Carlsbad, CA 92009
PHONE : (619) 438-1161, Ext.
A-4
P:\DOCS\CHKLS1\BP0001.FRM REV 05/11/94
2075 Las Palmas Dr.• Carlsbad, CA 92009-1576 • (619) 438-1161 • FAX (619) 438-0894
r1
' '
BUILDING PLANCHECK CHECKLIST
SITE PLAN
-,/ 3rd,/ .
D D · 1. Provide a fully dimensioned site plan drawn to scale. Show:
D
A. North Arrow D. Property Lines Easements
B. Existing & Proposed Structures E. Easements
C. Existing Street Improvements F. Right-of-Way Width & Adjacent Streets
2. Show on site plan:
A. Drainage Patterns C. Existing Topography
8. Existing & Proposed Slopes
3. Include note: "Surface water to be directed away from the building foundation at a 2%
gradient for no less than 5' or 2/3 the distance to the property line (whichever is less)."
[Per 1985 USC 2907(d)5].
On graded sites, the top of any exterior foundation shall extend above the elevation
of the street gutter at point of discharge or the inlet of an approved drainage device ·
a minimum of 12 inches plus two percent'' (per 1990 USC 2907(d)5.).
4. Include on title sheet
A. Site address
B. Assessor's Parcel Number
C. Legal Description
For commercial/industrial buildings and tenant improvement projects, include: Total
building square footage with the square footage for each different use, existing sewer
permits showing square footage of different uses (manufacturing, warehouse, office,
etc.) previously approved.
EXISTING PERMIT NUMBER DESCRIPTION
P:\DOCS\CHKLST\BP0001.FRM Page 1 of 4 REV 05/11/94
/
' "
BUILDING PLANCHECK CHECKLIST
DISCRETIONARY APPROVAL COMPLIANCE uz1~~ 2ndv' 3rdv' ,, 0 0 5 Project does not comply with the following Engineering Conditions of approval for
Project No. _______________________ _
~o o
Conditions were complied with by: ______ _ Date: -------
DEDICATION REQUIREMENTS
6. Dedication for all street Rights-of-Way adjacent to the building site and any storm
drain or utility easements on the building site is required for all new buildings and for
remodels with a value at or exceeding $ ______ -pursuant to Cod~ Section
18.40.030.
Dedication required as follows: ________________ _
Attached please find an application form and submittal checklist for the dedication
process. Provide the completed application form and the requirements on the
checklist at the time of resubmittal.
Dedication completed by ___________ _ Date: ___ _
IMPROVEMENT REQUIREMENTS
D D D 7a. All needed public improvements upon and adjacent to the building site must be
constructed at time of building construction whenever the value of the construction
exceeds $ -pursuant to Code Section 18.40.040.
Public improvements required as follows: _____________ _
Please have a registered Civil Engineer prepare appropriate improvement plans and
submit them together with the requirements on the attached checklist for a separate
plancheck process through the Engineering Department. Improvement plans must be-
approved, appropriate securities posted and fees paid prior to issuance of permit.
Attached please find an application form and submittal checklist for the public
improvements requirements. Provide the completed application form and the
requirements on the checklist at the time of resubmittal.
Improvement Plans signed by: __________ _ Date: __ _
P:\DOCS\CHKLST\BP0001.FRM Page 2 of 4 REV 05/11 /94
1 stv' 2ndv' 3rdv' DD D
BUILDING PLANCHECK CHECKLIST
7b. Construction of the public improvements may be deferred pursuant to code Section
18.40. Please submit a recent property title report or current grant deed on the
property and processing fee of $ ________ so we may prepare the
necessary Future Improvement Agreement. This agreement must be signed, notarized
and approved by the City prior to issuance of a Building Permit.
Future public improvements required as follows: ___________ _
Improvement Plans signed by: __________ _ Date: ----
D D D 7c. Enclosed please find your Future Improvement Agreement. Please return signed and
notarized Agreement to the Engineering Department.
D D
D D
lo
D
D
D
Future Improvement Agreement completed by: ___________ _
Date: _______ _
7d. No Public Improvements required. SPECIAL NOTE: Damaged or defective
improvements found adjacent to building site must be repaired to the satisfaction of
the City Inspector prior to occupancy.
GRADING PERMIT REQUIREMENTS
The conditions that invoke the need for a grading permit are found in Section 11.06.030
of the Municipal Code.
8a. Inadequate information available on Site Plan to make a determination on grading
requirements. Include accurate grading quantities (cut, fill import, export).
Sb. Grading Permit required. A separate grading plan prepared by a registered Civil
Engineer must be Submitted together with the completed application form attached.
NOTE: The Grading Permit must be issued and rough grading approval obtained prior
to issuance of a Building Permit.
Grading Inspector sign off by: Date:
SC. No Grading Permit required.
P:\DOCS\CHKLST\BP0001.FRM Page3<:A4 REV 05/11/94
' l
·r
BUl'LDING PLANCHECK CHECKLIST
MISCELLANEOUS PERMITS
~ 2ndv' 3rdv' 'Jlr D D s. A RIGHT-OF-WAY PERMIT is required to do work in City Right-of-Way and/or
private work adjacent to the public Right-of-Way. Types of work include, but are not
limited to: street improvements, trees, driveways, tieing into public storm drain, sewer
and water utilities.
Right-of-Way permit required for ________________ _
A separate Right-of-Way permit issued by the Engineering Department is required for
the following: ______________________ _
1 O. A SEWER PERM.IT is required co·ncurrent with the building permit issuance. The fee
is noted in the fees section on the following page.
11. INDUSTRIAL WASTE PERMIT is required. Applicant must complete Industrial·
Waste Permit Application Form and submit for City approval prior to issuance of a
Permit.
Industrial waste permit accepted by: _______ Date: ___ _
P:\DOCS\CHKLS1\BP0001.FRM Page 4 of 4 REVOS/11/94
:-p.~-------------------------------------· ENGINEERING DEPARTMENT ENGINEERING REVIEW SECTION
FEE CALCULATION WORKSHEET
D Estimate based on unconfirmed information from applicant.
XCalculation based on building plancheck plan submittal.
Address: ~ 2, :, 3 Y.41:/t,l>dl . Bldg. Permit No. Ct:3 q 5/ 6 / .!:i_.
Prepared by: /k,.--Date: %/9s Checked by: _____ Date: _______ _
EDU CALCULATIONS: List types and square footages for all uses.
. 5.1~ .. ~
Types of Use:_,__tft;:::hfl c Sq. Ft./Un~ /(JI} EDU's: __ ~~----=-
e,, ~ 6' I>,: T' tAhf s-E -1--f-bto ·:' 57) p (}
S-/C, Total EDU's:. __ ~-""'---A--~~
ADT C~LCULATIONS: List types and square footages for an;:t,e;· ""ZA/ ~~, /
Types of Use: t:2/Ht' e Sq. Ft/Units~ ,,... ~ ADTs: I t)
C~' / a// _r,f' . -1!;-JJ,.',-3 Total ADr:
7
3
FEES REQUIRED:
PUBLIC FACILITIES FEE REQUIRED O YES ~NO (See Building Department for amount)
WITHIN CFD: DYES (no bridge & thorougae
1
fee, _'ANO
reduced Traffic Impact Fee) $ 1.PARK-IN-UEU FEE PARK AREA: ___ _
FEE/UNIT:_____ X NO. UNITS: __ _
~ 2.TRAFFIC IMPACT FEE 1 ADT's~NITS: ~ X FEE/ADT: ..3'f:
~ 3. BRIDGE AND THOROUGHFARE FEE ? .
ADT's/UNITS: ~ X FEE/ADT: cX, ;:i.._ !Ji, 4. FACILITIES MANAGEM,;;.T FEE ZONE: ___ _
SQ.FT.:___ X FEE/SQ.FT.: ___ _
~ 5. SEWER FEE
PERMIT No.. · .,;ff?'~tf'/_Zt;L,
EDU's:. ,--&: 11 q X FEE/EDU: /Pl
BENEFIT AR;.: --s DRAINAGE BASIN: SB
11
1, EDU's: ~q X FEE/EDU: JC? 1
/~6 .. DRAINAGE FEES PLDA.____ HIGH ___ /LOW __ _
ACRES:--------,. X FEE/AC: __ _ $ 7. SEWER LATERAL ($2,500 DEPOSl"D
~ 8. WATER FEE
EDU's: ,x; f 1
/
X FEE/EDU: ;;2._7tJ(}
=$-~-=----
=$
=$-~ 31/:J
=$ ~/b/ ..,c:
=$ ~ .,
=$ ~
TOTAL OF ABOVE FEES*:$~
*NOTE: This calculatlon sheet la NOT a complete 11st of all fees which may be due.
Dedications and Improvements may also be required with Building Permits.
P:\DOCS\MISFORMS\BP0002.FRM REV 01 /04/95
\,..
iS'---
\
(j-
l
u u ., • .. .. • • Q Q Q
~ I I ~-~ .
.!' .!' .!'
; ~ ;
"' "' "' \,I \,I ~ u .,
~ ~ ~ <.J <.J <.J
i i i ---Cl. Cl. Cl.
~DD
PlMOO:NG Q-IECKUST
Plan Check No. tJt;-/61( Address __ 22..........::;..3~5_h_a __ r_~J_0c+-t~&~~--__
J Planner DAVID RICK
(Name)
Phone 438-1161 ext. _4_3_2_8 ___ _
APN: --------------------------
Type of Project and Use _---1,-.-.:;.~ _:r._. ------~---
Zone Of\ Facilities Management Zone f'
crD (~ 1(tf property ut, complete SPECIAL TAX CALCULATION
WORKSHEET provided by Building Department.)
[tern Complete
(9 [tem [ncomplete. Needs your action
1, 2, 3 Number in circle indicates plancheck number where deficiency was
identified
Environmental Review Required: YES
DATE OF COMPLETION:
NO ~E __ _
Compliance with conditions of approval? If not, state conditions which require action. Conditions of Approval _____________________ _
~ 0 Discmionary htion Required: YES_ NO ~E __ _
APPROVAL/RESO. NO. __ _ DATE: _____ _
PROJECT NO. ___ _
OTHER RELATED CASES: ___________________ _
Compliance with conditions of approval? If not, state conditions which require action.
Conditions of Approval _____________________ _
I /
ci' 0 0 Califomia Coastal c.ommisslcm Permit Required: YES _ NO 7
DATE OF APPROVAL:
San Diego Coast District, 3111 Camino Del Rio North, Suite 200, San Diego, CA. 92108-1725
(619) 521-8036
Compliance with conditions of approval? If not, state conditions which require action. Conditions of Approval _____________________ _
~. lnclusjoiwy Ho~ Fee~ YES~ NO . ~
(Effective date-of ·tn6h,1sionary HQusi,ng brclinance ·• M~y 21, 1993.)
Site Plan:·
CH{c1 : ,. L
2.
1.
.2.
3.
4.
:Provi4e a fully dimensioned site .--p:lan drawn to scale. · Show: North
arrow, property lihe,s, ¢asetnents, ~xisting and proposed struc-t~~s,
$tteets, existing street improvements, right-of~way width, dimensioned
__ $et~acks and e~StinJ topo~aphic:al lines,
Provid,e.1eg~ d·escription. of prqp~rty, .and assessors parcel number.
Setbacks·:
:Fr,orit: Required Shown
Int . .Side: .Required Shown
Street Side: Required. Shown
Rear:· Required Shown
Lot coverage: . Required-Shown,
H~ight: R!(luited Shown-·
l~arking: Spaces :~equired (,..)Q.l' C.\J.U ~SJ~,=(, . . hown
Guest Spaces Required Shown
0 D D Additional Comin~n.ts ____________ ___,. __ .,.......,.,.,...... ___ ....-------------------,------,
O.K TO ISSUE ~. EmER£I) APPROVAL (NrO COMPUTER i)d0
. . . ~ ' . '
DATE
-i
PLN~FRM
City of Carlsbad 95253
Fire Department • Bureau of Prevention
Plan Review: Requirements Category: Building Plan Check
Date of Report: Monday, December 11, 1995 Reviewed by: ~
Contac~ Name C.S.I. General Inc
Address 145 Vallecitos De Oro #F
City, State San Marcos CA 92069
Bldg. Dept. No. 95-1615 Planning No.
Job Name International Cosmet
Job Address _2_23_3_F_a_ra_da ..... Y ____________ _ Ste. or Bldg. No. _A ____ _
.~ Approved -The item you have submitted for review has been approved. The approval is
based on plans; information and/or specifications provided in your submittal;
therefore any changes to these items after this date, including field modifica-
tions, must be reviewed by this office to insure continued conformance with
applicable codes. Please review carefully all comments attached, as failure
to comply with instructions in this report can result in suspension of permit to
construct or install improvements.
D Disapproved -Please see the attached report of deficiencies. Please make corrections to
plans or specifications necessary to indicate compliance with applicable
codes and standards. Submit corrected plans and/or specifications to this
office for review.
For Fire Department Use Only
Review 1st ___ _ 2nd._-'--_ 3rd __ _
Other Agency ID
CFD Job# __ 95_2_5_3 __ File# ___ _
2560 Orion Way • Carlsbad, California 92008 • (619) 931-2121
City of Carlsbad 95253
Fire Department • Bureau of Prevention
Plan Review: Requirements Category: Building Plan Check
Date of Report: Monday, November 13, 1995 Reviewed by: ~
Contact Name C.S.I. General Inc
Address 145 Vallecitos De Oro #F
City, State San Marcos CA 92069
Bldg. Dept. No. 95-1615 Planning No.
Job Name Unknown IA ----------------------
Job Address _2_23 __ 3_F_a_ra_d~ay.___ ____________ _ Ste. or Bldg. No. _A ____ _
D Approved -The item you have submitted for review has been approved. The approval is
based on plans; information and/or specifications provided in your submittal;
therefore any changes to these items after this date, including field modifica-
tions, must be reviewed by this office to insure continued conformance with
applicable codes. Please review carefully all comments attached, as failure
to comply with instructions in this report can result in suspension of permit to
construct or install improvements.
jg! Disapproved -Please see the attached report of deficiencies. Please make corrections to
plans or specifications necessary to indicate compliance with applicable
codes and standards. Stlbrnit corrected plans and/or specificatieAs te this
office for revieW:-
For Fire Department Use Only
Review 1st. __ _ 2nd __ _ 3rd. __ _
Other Agency ID
CFD Job# __ 95_2---'-5---3 __ File# ___ _
2560 Orion Way • Carlsbad, California 92008 • ( 619) 931-2121
From: Fax: 8:32:57 11/27/95 Page 1 of 21 Log:295
To: Qave C.8.1. Fax: 471-0149
TITLE 24 REPORT FOR:
2233 Faraday Ave., Suite A
2233 Faraday Ave., Suite A
Carlsbad, CA 92008
PROJECT DESIGNER:
C.S.I.
145 Los Vallecitos De Oro, Suite F
San Marcos, CA 92069
(619)471-9388
REPORT PREPARED BY:
Steve Balderrama
E!aynal & Co., Inc.
425 West Fifth Street
Escondido, CA 92025
(619) 743-5408
Job Number:
Date: ll/27/1995
The COMPLY 24 computer program has been used to perform the calculations
summarized in this compliance report. This program has approval and is
authorized by the california Energy Commission for use with both the
Residential and Nonresidential Building Energy Efficiency Standards.
This program developed by Gabel Dodd Associates (510) 428-0803.
From: Fax:
To: Qave C.8.1. Fax: 471-0149
Table Of Contents for Title 24 Report
Cover Page --
Table of Contents
1
2
Form ENV-1 Envelope Certificate of Compliance
Form PERF-1 Performance Compliance Summary ------· 5
Form ENV-2 Envelope Summary ......................................... 6
Form ENV-3 Construction Assemblies ------9
3
Form LTG-1 Lighting Certificate of Compliance .... _................. 12
Form LTG-2 Lighting Compliance Summary .............................. 14
Form MECH-1 Mechanical Certificate of Compliance ---15
Form MECH-2 Mechanical Summary ...................................... 18
Form MECH-3 Mechanical Equipment Summary ............................ 19
Form MECH-4 Mechanical Ventilation .................................. 20
8:32:57 11/27/95 Page 2 of 21 Log:295
From: Fax: 8:32:57 11/27/95 Page 3 of 21 Log:295
To: Qave C.S.I. Fax: 471-0149
CERTIFICATE OF COMPLIANCE (part 1 of 2) ENV-1 page 3 of 20
Project Name: 2233 Faraday Ave., Suite A
Address: 2233 Faraday Ave., Suite A
Carlsbad, CA 92008
Envelope
Designer: c.s.r.
!Date: ll/'ZJ/1995
!Building Permit No
!Checked by / Date
I Documentation: Haynal & Co., Inc. !COMPLY 24 User 2875
GENERAL INFORMATION
Date of Plans:
Building Type: Nonresidential
Building Conditioned Floor Area:
climate Zone:
1440 sf
7
Phase of Construction: O New Construction X Addition 0 Alteration
Method of Envelope Compliance: Performance -COMPLY 24 v 4.ll
STATEMENT OF COMPLIANCE
This Certificate of Compliance lists the building features and performance
specifications needed to comply with Title 24, Part 6, Chapter 1 and Title
20, Chapter 2, Subchapter 4, Article 1 of the California Code of Regula-
tions. This certificate applies only to building envelope requirements.
The Principal Envelope Designer hereby certifies that the proposed build-
ing design represented in this set of construction documents is consistent
with the other compliance forms and worksheets, with the specifications,
and with any other calculations submitted with this permit application.
The proposed building has been designed to meet the envelope requirements
contained in sections no, ll6 through ll8, and 143 or 149 of Title 24,
Part 6, Chapter L
Please check one:
0 I hereby affirm that I am eligible under the provisions of Division 3
of the Business and Professions Code to sign this document as the
person responsible for its preparation; and that I am a civil engineer
or architect.
-~affirm that I am eligible under the exemption to Division 3 of the r ~~iness and Professions Code by Section 5537.2 of the Business and
Professions Code to sign this document as the person responsible for
its preparation; and that I am a licensed contractor preparing docu-
ments for work that I have contracted to perform.
0 I affirm that I am eligible under the exemption to Di vision 3 of the
Business and Professions Code by Section ____ of the
Code to sign this document as person responsible for its
preparation; and for the following re7 __ "ir--=l!-+-,~-----------
PRINCIPAL ENVELOPE DESIGNER
C.S.I.
(619)471-9388
ENVELOPE MANDATORY MEASURES
Indicate location on plans of Note Block for Mandatory Measures:
From: Fax:
To: D.ave C.S.I. Fax: 471-0149
CERTIFICATE OF COMPLIANCE (part 2 of 2)
Project Name: 2233 Faraday Ave., Suite A
Documentation: Haynal & Co., Inc.
Const
8:32:57 11/27/95 Page 4 of 21 Log:295
ENV-1 page 4 of 20
JDate: ll/ZJ/1995
I
JCOMPLY 24 User 2875
OPAQUE SURFACES
Assembly Name Type Location/Comments
Note to
Field
6" Concrete Wall None
R-19 Roof(R.19 on Tile) Wood
Roll-Up Door None
FENESTRATION Frame
Orient Panes Type Exterior Shade OH Glazing Type
Right (NW) l Metal None N Single Tinted
From: Fax:
To: Dave C.S.I. Fax: 471-0149
PERFORMANCE COMPLIANCE SUMMARY
Project Name: 2233 Faraday Ave., Suite A
Documentation: Haynal & Co., Inc.
ANNUAL SOURCE ENERGY USE (KBtu/sgft-yr)
Energy Component
Space Heating
Space Cooling
HVAC Fans & Pumps
Domestic Hot Water
Lighting
Receptacle
Process
TOTALS
Cale: DOE-24
Standard
Design
15.38
9.27
10.44
0.00
29.13
10.65
0.00
74.85
*** BUILDING COMPLIES ***
8:32:57 11/27/95 Page 5 of 21 Log:295
PERF-1 page 5 of 20
jDate: 11/27/1995
I
jCOMPLY 24 User 2ff75
(COMPLIANCE)
Proposed Compliance
Design Margin
13.10 2.27
8.98 0.29
10.29 0.15
0.00 0.00
30.69 -L56
10.65 0.00
0.00 0.00
73.71 1.15
OPTIONAL CAPABILITES AND SPECIAL COMPLIANCE INFORMATION
From: Fax:
To: Qave C.8.1. Fax: 471-0149
PERFORMANCE ENVELOPE SUMMARY Part 1 of 3
Project Name: 2233 Faraday Ave., Suite A
Documentation: Haynal & Co., Inc.
GENERAL INFORMATION BY SPACE
Space Name Occupancy
Office Area Office
Restroom/Hall Corridor/Restroom
Shipping/Receiving Industrial Work
Warehouse Industrial Storage
8:32:57 11/27/95 Page 6 of 21 Log:295
ENV-2 page 6 of 20
jDate: ll/Z?/1995
I
jCOMPLY 24 User 2875
Flr Floor Display
No Area Volume Perim.
1 190 1710 0
1 220 1980 0
1 460 4140 0
1 570 5130 0
Total 1440
From: Fax:
To: Qave C.8.1. Fax: 471-0149
PERFORMANCE ENVELOPE SUMMARY Part 2 of 3
Project Name: 2233 Faraday Ave., Suite A
Documentation: Haynal & Co., Inc.
OPAQUE SURFACES Act Solar
Type Area U-Val Azm Tilt Gains Form 3 Reference
Wall 108 0.752 225 90 Yes 6" Concrete Wall
Wall 5 0.752 315 90 Yes 6" Concrete Wall
Roof 190 0.043 0 22 Yes R-19 Roof(R.19 on Tile)
Roof 220 0.043 0 22 Yes R-19 Roof(R.19 on Tile)
Wall 144 0.752 225 90 Yes 6" Concrete Wall
Roof 460 0.043 0 22 Yes R-19 Roof(R.19 on Tile)
Wall 185 0.752 135 90 Yes 6'' Concrete Wall
Wall 144 0.752 225 90 Yes 6" Concrete Wall
Wall 5 0.752 315 90 Yes 6" Concrete Wall
Roof 570 0.043 0 22 Yes R-19 Roof(R.19 on Tile)
8:32:57 11/27/95 Page 7 of 21 Log:295
ENV-2 page 7 of 20
!Date: 11/27/1995
I jCOMPLY 24 User 2Z75
Location/Comments
Office Area
Office Area
Office Area
Restroom/Hall
Shipping/Receiving
Shipping/Receiving
Warehouse
Warehouse
Warehouse
Warehouse
From: Fax: 8:32:57 11/27/95 Page 8 of 21 Log:295
To: Dave C.S.I. Fax: 471-0149
PERFORMANCE ENVELOPE SUMMARY Part 3 of 3 ENV-2 page 8 of 20
Project Name: 2233 Faraday Ave., Suite A
Documentation: Haynal & Co., Inc.
FENESTRATION SURFACES
!Date: JJ./ZJ/1995
I !COMPLY 24 User 2Z75
SC
Act Glass
# Type Area Frame Div U-Val Azrn Tilt Only Location/Comments
----------------------
1 Wdw Right (NW) 40.0 Metal No 1.10 315 90 0.69 Office Area
0.69 Warehouse 2 Wdw Right (NW) 40.0 Metal No 1.10 315 90
OVERHANGS/SIDE FJNS
-Window--
# Type Ht Wd
NONE
----Overhang-----Left Fin--Right Fin-
Len Ht LExt RExt Dist Len Ht Dist Len Ht
From: Fax: 8:32:57 11/27/95 Page 9 of 21 Log:295
To: Qave C.8.1. Fax: 471-0149
PROPOSED CONSTRUCTION ASSEMBLY ENV-3 page 9 of 20
Project Name: 2233 Faraday Ave., Suite A
Documentation: Haynal & Co., Inc.
jDate: ll/Z7/J995
I
jCOMPLY 24 User 2Z75
COMPONENT DESCRIPTION
Sketch of Construction Assembly
ASSEMBLY U-VALUE
Construction Components
Outside Air Film
1. Concrete, 140 lb, Not Dried
2.
3.
4.
5.
6.
7.
8.
9.
Inside Air Film
ADJUSTMENT FOR FRAMING
Assembly Name: fl' Concrete Wall
Assembly Type: Wall
Assembly Tilt: 90 deg (Vertical)
Framing Material: None
Framing Spacing: " O.C.
Framing Percent: 0.0 %
Absorptivity: 0.70
Roughness: Concrete, Asph. shingles
Th R-Value
Fr (in) Cavity Frame
6.000 0.48
Unadjusted R-Values
0.17 0.17
0.48
0.68
1.33
0.68
1.33
(1 / 1.33) x (LOO) + (1 / 1.33) X (0.00) 0.752
Weight:
Heat capacity:
70.0 lb/sq.Et
15.40
TOTAL U-VALUE = 0.752
TOTAL R-VALUE 1.33
From: Fax:
To: gave C.S.I. Fax: 471-0149
8:32:57 11/27/95 Page 10 of 21 Log:295
ENV-3 page 10 of 20 PROPOSED CONSTRUCTION ASSEMBLY
Project Name: 2233 Faraday Ave., Suite A
Documentation: Haynal & Co., Inc.
!Date: ll/ZJ/l995
I !COMPLY 24 User ms
COMPONENT DESCRIPTION
Sketch of Construction Assembly
ASSEMBLY U-VALUE
Construction Components
outside Air Film
1. Roofing, Built-Up
2. Membrane, Vapor-Permeable Felt
3. Plywood
4. Air Space
5. Insulation, Mineral Fiber, R-19
6. Acoustical Tile, Interior Finish
7.
8.
9.
Inside Air Film
ADJUSTMENT FOR FRAMING
(1 /231)2) X (0.90) + (1 /23.02) X (0.10)
Assembly Name: R-19 Roof(R.19 on Tile)
Assembly Type: Roof
Assembly Tilt: 22 deg (Tilted Up)
Framing Material: Wood
Framing Spacing: " o.c.
Framing Percent: 10.0 %
Absorptivity: 0.70
Roughness: Concrete, Asph. Shingles
Th R-Value
Fr (in) Cavity Frame
0.17 0.17
0.375 0.33
0.010 0.06
0.500 0.62
0.33
0.06
0.62
0.80 12.000
6.000 19.00
0.500 1.43
0.80
19.00
1.43
0.61 0.61
Unadjusted R-Values 23.02 23.02
0.043
TOTAL U-VALUE 0.043
TOTAL R-VALUE 23.02
Weight:
Heat Capacity:
4.6 lb/sqft
1.45
From: Fax:
To: Dave C.S.I. Fax: 471-0149
8:32:57 11/27/95 Page 11 of 21 Log:295
ENV-3 page ll of 20 PROPOSED CONSTRUCTION ASSEMBLY
Project Name: 2233 Faraday Ave., Suite A
Documentation: Haynal & Co., Inc.
!Date: JJ./Z?/1995
I
!COMPLY 24 User 2875
COMPONENT DESCRIPTION Assembly Name: Roll-Up Door
Assembly Type: Door
Assembly Tilt: 90 deg (Vertical)
Framing Material: None
Framing Spacing: " O.C.
Framing Percent: o.o %
Absorptivity: 0.70
Sketch of Construction Assembly Roughness: Smooth Plaster, Metal
ASSEMBLY U-VALUE
Construction Components
Outside Air Film
1. Steel
2.
3.
4.
5.
6.
7.
8.
9.
Inside Air Film
Th R-Value
Fr (in) Cavity Frame
0.17 0.17
0.001 0.00 0.00
0.68 0.68
Unadjusted R-Values 0.85 0.85
ADJUSTMENT FOR FRAMING
(1 / 0,85) X (1.00) + (1 / 0.85) X (0.00) 1.176
Weight:
Heat Capacity:
0.0 lb/sgft o.oo
TOTAL U-VALUE = 1.176
TOTAL R-VALUE 0.85
From: Fax:
To: Dave C.S.I. Fax: 471-0149
CERTIFICATE OF COMPLIANCE (part l of 2)
Project Name: 2233 Faraday Ave., Suite A
Address: 2233 Faraday Ave., suite A
Carlsbad, CA 92008
Lighting
Designer:
Documentation: Haynal & Co., Inc.
8:32:57 11/27/95 Page 12 of 21 Log:295
LTG-1 page 12 of 20
!Date: ll/Zl/1995
!Building Fermi t No
jChecked by / Date
I jCOMPLY 24 User ms
GENERAL INFORMATION
Date of Plans: Building Conditioned Floor Area: 1440 sf
Building Type: Nonresidential climate Zone: 7
Phase of Construction: o New Construction X Addition O Alteration
Method of Lighting Compliance: Performance -COMPLY 24 v 4.ll
STATEMENT OF COMPLIANCE
This Certificate of Compliance lists the building features and performance
specifications needed to comply with Title 24, Part 6, Chapter l and Title
20, Chapter 2, Subchapter 4, Article l of the California Code of Regula-
tions. This certificate applies only to building lighting requirements.
The Principal Lighting Designer hereby certifies that the proposed build-
ing design represented in this set of construction documents is consistent
with the other compliance forms and worksheets, with the specifications,
and with any other calculations submitted with this permit application.
The proposed building has been designed to meet the lighting requirements
contained in sections ll0, 119, 130 through 132 and 146 or 149.
Please check one:
0
0
I hereby affirm that I am eligible under the provisions of Division 3
of the Business and Professions Code to sign this document as the
person responsible for its preparation; and that I am a civil engineer
electrical engineer or architect.
I affirm that I am eligible under the exemption to Division 3 of the
Business and Professions Code by Section 5537.2 of the Business and
Professions Code to sign this document as the person responsible for
its preparation; and that I am a licensed contractor preparing docu-
ments for work that I have contracted to perform.
I affirm that I am eligible under the exemption to Division 3 of the
Business and Professions Code by Section ____ of the
Code to sign this document as the person responsible for its
preparation; and for the following reason: __ 1----------------
PRINCIPAL LIGHTING DESIGNER
LIGHTING MANDATORY MEASURES
Indicate location on plans of Note Block for Mandatory Measures:
From: Fax: 8:32:57 11/27/95 Page 13 of 21 Log:295
To: Qave C.8.1. Fax: 471-0149
CERTIFICATE: OF COMPLIANCE: (part 2 of 2) LTG-1 page 13 of 20
JDate: ll/ZJ/JSJ95
I
Project Name: 2233 Faraday Ave., Suite A
Documentation: Haynal & Co., Inc. JCOMPLY 24 User '2Z75
INSTALLED LIGHTING SCHEDULE:
No of
Name Lamp Type Lamps
Fluorescent 2
MANDATORY AUTOMATIC CONTROLS
Control
Watts/
Lamp
32
Ballast
Type
Standard
Ballasts/ No of
Luminaire Fixt.
1.0 22
Control Location m Control Type Space Controlled
CONTROLS FOR CREDIT
Control
Control Location m Control Type Space Controlled
Note to
Field
Note to
Field
Note to
Field
From: Fax: 8:32:5711/27/95 Page 14 of 21 Log:295
To: Qave C.S.I. Fax: 471-0149
LIGHTING COMPLIANCE SUMMARY
Project Name: 2233 Faraday Ave., Suite A
Documentation: Haynal & Co., Inc.
ACTUAL LIGHTING POWER
Name Description
48" T-8 Straight /2 Lamp
LTG-2 page 14 of 20
JDate: 11/ZJ /1995
I
JCOMPLY 24 User ms
No of
Lumin
Watts
per Default
Total
Watts
22 68.0 _Y_ 1496
SubTotal
Less Control Credi ts (LTG-3)
Total Proposed Watts
1496
0
1496
* If not CEC Default value, please provide supporting documentation.
MODELLED LIGHTING POWER BY SPACE
Space Name
Office Area
Restroom/Hall,
shipping/Receiving
Warehouse
Occupancy
Office
Corridor/Restroom
Industrial Work
Industrial Storage
TOTALS
Modelled
Floor LPD Total Tailored
Area (w/sf:'} (watts) (watts)
190
220
460
570
1.074
0.9ZJ
1.035
1.074
1440 1.039
204
204
476
612
1496
0
0
0
0
0
* Note: Tailored Allotment requires supporting documentation on form LTG-4.
From: Fax: 8:32:57 11/27/95 Page 15 of 21 Log:295
To: Oave C.S.I. Fax: 471-0149
CERTIFICATE OF COMPLIANCE (part 1 of 3)
Project Name: 2233 Faraday Ave., Suite A
Address: 2233 Faraday Ave., Suite A
Carlsbad, CA 92008
Mechanical
Designer:
Documentation: Haynal & Co., Inc.
MECH-1 page 15 of 20
jDate: ll/Z?/1995
jBuilding Permit No
!Checked by / Date
I jCOMPLY 24 User 2Z75
GENERAL INFORMATION
Date of Plans: Building Conditioned Floor Area: 1440 sf
Building Type: Nonresidential Climate Zone: 7
Phase of Construction: 0 New Construction X Addition 0 Alteration
Method of Mechanical Compliance: Performance -COMPLY 24 v 4.11
Proof of Envelope Compliance: 0 Previous Permit X Compliance Attached
STATEMENT OF COMPLIANCE
This Certificate of Compliance lists the building features and performance
specifications needed to comply with Title 24, Part 6, Chapter 1 and Title
20, Chapter 2, Subchapter 4, Article 1 of the California Code of Regula-
tions. This certificate applies only to building mechanical requirements.
The Principal Mechanical Designer hereby certifies that the proposed build-
ing design represented in this set of construction documents is consistent
with the other compliance forms and worksheets, with the specifications,
and with any other calculations submitted with this permit application.
The proposed building has been designed to meet the mechanical requirements
contained in sections 110 through 115, 120 through 124, 140 through 142,144
and 145.
Please check one:
0 I hereby affirm that I am eligible under the provJ..S1ons of Division 3
of the Business and Professions Code to sign this document as the
person responsible for its preparation; and that I am a civil engineer
mechanical engineer or architect.
y'I affirm that I am eligible under the exemption to Division 3 of the
Business and Professions Code by Section 55372 of the Business and
Professions Code to sign this document as the person responsible for
its preparation; and that I am a licensed contractor preparing docu-
ments for work that I have contracted to perform.
0 I affirm that I am eligible under the exemption to Division 3 of the
Business and Professions Code by Section ____ of the
Code to sign this document the person responsible for its
preparation; and for the following
PRINCIPAL MECHANICAL DESIGNER
(Date)
MECHANICAL MANDATORY MEASURES
Indicate location on plans of Note Block for Mandatory Measures:
~m: F~
To: Qave C.S.I. Fax: 471-0149
CERTIFICATE OF COMPLIANCE (part 2 of 3)
Project Name: 2233 Faraday Ave., Suite A
Documentation: Haynal & Co., Inc.
SYSTEM FEATURES
Zone Name New Area
Time Control __ s __
Setback Control None
# of Isolation Zonesn/a
HP Thermostat Yes
Electric Heat 0.0 KW
Fan Control Constant Volume
VAV Min Position n/a
simul. Heat/Cool n/a
Heat Supply Reset Constant Temp
Cool Supply Reset Constant Temp
Ventilation __ B __
OA Damper Control A
Economizer Type No Economizer
Outdoor Air CFM 216
Heat Equip Type Heat Pump
Make & Model No. Rheem RQKA-A030JK
Cool Equip Type DX
Make and Model
Code Tables
Time Control
S:Prog switch
O:Occ Sensor
M:Man Timer
Ventilation
B:Air Balance
C:OA Cert.
M:OA Measure
D:Demand Cont
N:Natural
OA Damper
A:Auto
G:Gravity
8:32:57 11/27/95 Page 16 of 21 Log:295
MECH-1 page 16 of 20
!Date: ll/27/1995
I
!COMPLY 24 User ms
Note to
Field
From: Fax:
To: Oave C.S.I. Fax: 471-0149
CERTIFICATE OF COMPLIANCE (part 3 of 3)
Project Name: 2233 Faraday Ave., Suite A
Docum~tation: Haynal & Co., Inc.
DUCT INSULATION
System Name
Rheem RQKA-A030JK
PIPE INSULATION
System Name
Domestic Hot Water
Type Duct Location
Heating Ducts in Attic
Cooling Ducts in Attic
Pipe Type
Insul
Required
y / N
NOTES TO FIELD -For Building Department Use Only
8:32:57 11/27/95 Page 17 of 21 Log:295
MECH-1 page 17 of 20
JDate: ll/ZJ/1995
I
JCOMPLY 24 User ms
Duct Tape Insul Note to
Allowed R-Val Field
y / N
y / N
4.2 I
4.2
Note to
Field
From: Fax:
To: Dave C.S.I. Fax: 471-0149
MECHANICAL EQUIPMENT ZONING SUMMARY
Project Name: 2233 Faraday Ave., Suite A
Documentation: Haynal & Co., Inc.
SYSTEM/ZONING SUMMARY
Zone/Spaces Served
New Area
Office Area
Restroom/Hall
Shipping/Receiving
Warehouse
Central/Zonal System
Rheem RQKA-A030JK
8:32:57 11/27 /95 Page 18 of 21 Log:295
MECH-2 page 18 of 20
!Date: JJ./ZJ /1995
I
jCOMPLY 24 User WS
No
System Type Sys
Packaged Heat Pump l
From: Fax: 8:32:57 11/27/95 Page 19 of 21 Log:295
To: Dave C.S.I. Fax: 471-0149
MECHANICAL EQUIPMENT SUMMARY MECH-3 page 19 of 20
JDate: 11/27/1995
I
Project Name: 2233 Faraday Ave., Suite A
Documentation: Haynal & Co., Inc. JCOMPLY 24 User '2Z75
CENTRAL SYSTEM SUMMARY
Sys
No System Name
1 Rheem RQKA-A030JK
CENTRAL SYSTEM RATINGS
No
System Type Sys Economizer Type
Packaged Heat Pu 1 No Economizer
Sys ---Heating ---------------Cooling
No Type Output Aux KW EFF Type Output Sensible EER SEER ----------------
1 Heat Pump 29000 0.0 6.80 DX 29000 19000 9.05 10.00
CENTRAL FAN SUMMARY -----Supply Fan-------Return Fan -
Sys Mtr Drv Mtr Drv
No Fan Type Motor Location CFM BHP Eff Eff CFM BHP Eff Eff --------------------------
1 Constant Volume Draw-Through
ZONAL FAN SUMMARY
1000 0.20 60 100
Zonal Fan -----
Mtr Drv
None
Exhaust Fan --
Mtr Drv
Space Name No CFM BHP Eff Eff No CFM BHP Eff Eff
None
From: Fax:
To: pave C.S.I. Fax: 471-0149
MECHANICAL VENTILATION
Project Name: 2233 Faraday Ave., suite A
Documentation: Haynal & Co., Inc.
VENTILATION SUMMARY BY SPACE
Space Name
Office Area
Restroom/Hall
Shipping/Receiving
Warehouse
T Occupancy
Office
Corridor/Restr
Industrial Wor
Industrial Sto
8:32:57 11/27/95 Page 20 of 21 Log:295
MECH-4 page 20 of 20
!Date: ll/ZJ/l995
I
jCOMPLY 24 User 2875
Tran
Floor sqft CFM Min Design sfer
Area /Occ /Occ CFM CFM CFM
190
220
460
570
143
200
100
500
2L5 29
30.0 33
15.0 69
75.0 86
TOTALS
29
33
69
86 -----
216 216
Note: If Tailored (T=*), user must document sg:ft/Occ and/or CFM/Occ values.
From: Fax: 8:32:57 11/27/95 Page 21 of 21 Log:295
To: Dave C.8.1. Fax: 471-0149 ,,