HomeMy WebLinkAbout2236 RUTHERFORD RD; 105; CB911099; PermitV .. ' ...
"'
B U I L D I N G'i ·I;' E ·R M I T -Permit· N-<Y: 'CB91f099. <.· ' • -'
09/10/91 14:16
Page 1 of 1
· ·Project No: A9101'366 .. ·
Development ·No.,t... -
Fl~ :ste: /tJ.:) · Sob Address: 2236 RUTHERFORD RD
Permit Type: INDUS'I'.RIAL TENANT IMPROVEMENT
·Parc~l No: 212-061-26-00
· Str:
4349 09/10/9l oooi 01 · 02
C-PRMT 261~-00
Valuation: 17,475
Construction -Type.: VN :'C!e-lGol
Occupancy Group: B2 Class CodeH
Description! 1507 SF OFi:'ICE "BLOCK MEDICAL".
··. · ·-· _ . .-· Status:
.Applied:
Apr/Issue!
Validateq By:
4-3.-8-:-3 3 41
ISSUED
07/31/9i.
09/10/91
CD
Appl/Ownr : JM PROPERTIES
2236 RUTHERFORD RD #101
CARLSBAD, CA 92008 · -~---··---:---~-..... " _
./ ,, /'"' .. l ~~-, • , ..... , ,'
. NEW ENGLAND M,U'J'.'UAL LJFE,(lM /} . ;f:1._C.. ,owNER_ . 2236 .· •, ·., ,_ .. ___ ,_//' .. ,\ / '•') ,. _ ~ ·
Fees Required *** /. · ~_<\*** .___ ___ --F~?{,6&1i~.pt'ea & ·credits -
OWNE;R 43_83'341
*** ·*-**' ' / ""\ \(\..,_ .\ ' . --d-~----;;;;~-------;_~/;;_;:;_~-o0 . -· ~,-~~~:----;-=?1''-.~\?~:.;~)-\~---~--~-~--------
A, JUstments: ! -.• O . // v;_;-1;;r~ta Cr\el..l~S: \: . . 00 -
Total Fees: .2,8·6-7 .. 00/'<·;-:-:-:: __ :_·:::-!~a1}:~fi\entt9) \ . 189.00
. . , ·. "-··::-.· , ..... ---,_13a::f-:::ince·Dtle1' , 2 678 00
~¥ • , -... '"-~ -..... , -, ..... • -.-,,...,., r·,.,,,7 } \ / , . , t • · Fee description . ·_ · ,,. __ ,,._::-::::.:,':rJ··:~s rfee-LU..n,it\ Ext fee Data ---------------------._!--_,\ 'r _! ------, --'::~~~/. _z/--~_/2if.}},-1 c-; L-~-----------------. . . . . ' ·,'-. / '::' :f' ./ _,.,. :-i ' '-'¾-:;;,; ; Building Permit ·._. ,~ · ,· :1:. ,,,,..<._ ,::,, lJ / ~--, 1 18.9. O 0
. '', ',. '· j'' ' _:; .,-~.,'-;,,-(,) ' ' Plan Check .. , \ \·,,,;·,,··i ((<i~'\>/':t· ·/· ;J.23·.oo
-tit fl . (,t ,...,."/)'' f Strong Motion Fee .O::'.""-·-lit·· •. ,·' ,_; , ,, . . t' 4 00 ' ' ,,'•-'"'" 11, '0 ';y_// '-.·-Enter 'Y' to Autocalc Lir.::ens,e Tax;')~\-'.?---5 s_',->,;/ / 612.00 Y . / I i '-... .,,,,..,.,_.., -• F.tLF:/G.M.F. and Zone(99) · · ~. :{'--J < ~ / . __ /1 05
Tra£f1c Impact Fee .. :-. •)··"'"'-~"""'140 00 z--......., : -, ~10 oo· . ,, ,--·~i ,c.:r ·z \~"' ::> ;· ':-' · • -Bridge ·Fee _ " '·--~ .. ., __ __:";_j6,2--: oq_.., \\ \(.. -462. oo
Enter Number of EDU' s ·-... . , ~;/ 1 · , •• > ,.~-.,-:5~\~, / . :1.188. 00 * BUILDING TOTAL "·, 'C:: // / -\O~ '.~-' / .. _, 2788. 00
Enter "Y" for Plumbing Issu'e"" __ Fee · ~( .\J'<> ,./" · M
5..00,Y
·so. oo-
55.. 00·
15.00_ Y
9.00
Enter "Y11 for Electric Issue Fee > / ·
Three Phase Per AMP "5"· · _, __ . ·:----[o 0
. * ELE!CTRICAL TOTAL ( $10 Minimum)
Enter 'Y' for Mechanical Issue Fee>
Ins-ball: Furn/Ducts >
* MECHANICAL TOTAL
_ CITY ·OF CARLSBAD
1·
• 50
9.-00
2075 Las Palmas Dr., Carlsbad CA:-92009· (619). 43~1161
2.4 .. 00
<'
,I
' ----'
PERMIT APPLICATION , .
City qf Carlsbad Building Department
207,5 Las Pal mas Dr., Carlsbad, CA 92009 '(619) 438-1161
i. PERMIT TYPE
·····-., ..
~~.
. . .
VAtlD, i!Y-,-'-""'---'--'--"-,...,..-----'-S--"-"'-----
DATE _____ .,,,.,._.....,._....._ __ ---'-...,..-'---
A • COMMERCIAL
B • D INDUSTRIAL
C'. D RESIDENTIAL
TENANT IMPROVEMENT
0 TENANT IMPROVEMENT
0APARTMENT 0CONDO 0SINGLE FAMILY DIIE~LING 0 ADDLTJON/ALTERAT.ION 189-00
D DUPLEX D DEMOLITION
0MECHANICAL 0POOL
0RELOCATION 0MOBILE HOME 0EbECTRICAL [JPLLIMBING
OsPA 0RETAINING IIALL OsoLAR OoT:?':i,....~a....:._,__,,q_,4 _r,1 ti< 1-~~o
2. PROJECT INFORMATION PLAN CHECK N·o·.
A'qdress 2236 Rutherford Road tos
Nearest Cross Stree~s Faraday -
.,.J.EGAL ~CRll'TIPllt Lot NQ. fSubdivision Name/.Nurber · Unit No. Phase No. . .
.P.&,ce.L u tna Portion o Lots F&G according to the part. of. Map of• Rancho Agu Hedidohda.
CHECIC LOW IF SUIIIIITTEO:
nergy Cales 02 Structural Cales 1· Addressed Envelo
ASSESSOR'S PARCEL 212-061-26
DESCRIPTION OF WORK
EXISTING USE Sales of' Med~ SupplJ!~!l§ED USE -Same.
New Walls, Electric, HVAC, Ceiling, Finishes
BLDG .• sc. FTG. Project: 1507 # oF sToR1Es Project: .. I .
3. CONTACT PERSON
NAME Finite Concepts Inc.
cm San Diego
SIGNATURE
STATE CA
ADDRESS
ZIP COOE
'.
1550 Hotel Circle North, Su;i.te 120
921013. DAY TELEPHONE . 296_:6110
4. APPLJCJ.\NT 0CONTRACTOR 0AGENT FOR CONTRACTOR 0DWNER 'fiAGENT FOR OWNER . .
. NAME Finite Concepts Inc. ADDREss 1550 Hotel CY.i;r"cle North, suite 120
my San Diego sTATE CA z1P cooE 9~108 · . :DAY TELEPHONE 296.,.6ilO
5. PROPERTY OWNER OWNER .[]LESSEE 0TENANT
NAME N3i'l Etg]..crtj. M..¢lal Ll£e DH-\ c/o JM ~,ss2236 .Rutherford·. Road~. ·Si.l;i.te, · 101
CITY Carlsbad . STATE CA ZIPCODE -92008 D.AYTELEPH~NE_.438.a.3341
~ CONTRACTOR
NAME JM P.r:operties ADDRESS 2236 n.,-l"'h,._-f _r:d d . , • 1 ·1' . nuw=-i. o · Roa ., SUite O.
cnv Carlsbad STATE CA ZIP CODE 92008 DAY TELEPl{ONE .. 438-'-3341
LICENSE CLASS -~~B~--CITY 'BUSINESS ·L,1¢. #
ADDREss 1550 :Hotel Circl~ ,North, $u.ite .120.
:=--....;:.cccIT::'.Y~~=--:."7"'~~::-:::'."'."'.".:::-::-=':'7:-:------...;:.;-"'-''-'---'....C::i;:.;.c...:.:.:.::..._....::L"'--'-UJ'-'=-----'---__:D::;A::;Y_;T;::·E::;LE::.R:::H:::oN;:;E"-.,;-.:·~l,O;=-tU..U.'----'-·s::,:Tc::A~T.E~-:::::t·.:.:IC::,:'.:...:.#.:3,l;!k¼,J:.!.3
~b.
llorkers' Corrpe,:,sation Declaration: I hereby affirm that I have a certi-ficate o.f consent to-self·insuce' issued by the Director of °industri'al Re.Lat.io~s-~·
or a certificate of \lorkers' Corrpensation rnsurance by an acinitted insurer, or an exact copy ·or duplicate ·thereof certif.ied by th.e 'Director-of' the
insurer thereof filed with the Building Inspection Department (Section 3800, La,b. ·C). ·
JNsURANcE cOMPANY State Fund Ins. Co POLICY NO.
Certificate of Exerrption: I certify that in the performance of the work for which this permit is issued,
so as t come subject to the \lorkers• Corrpensation Laws of California.
1
8.
am exempt from· the Contract?,"'~ Li~ense ·t.aw for the 'fotlowing reason:·
as owner of the property or my errployees with wages as their sole compensation, will do the work and the 'structure is' nbt intended or o.ffered fo.r sal·e
(Sec. 7044, .Bus.iness and ·Professions code: The Contractor's License Law does not apply to an owner of proper-w who builds or improves ther~o'n,, and' whg
does such worlc himself or through his own errptoyees, provided that such irilpr.ovement~ are not intended or offered for sale. If, however, 'the building,
or improvement is sold within one year of coo-pletion, the owner-builder wi,l l have the burden o? proving, that lie c;Iid no~ build or improve for the purpose
of sale.).
0 I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions. Code:
The Contractor's License Law does not apply to an owner of property who builds or. improves thereon, and contracts ·for such. projects ·witli contrador(s)
licensed pursyant to the Contractor's License Law). ' · ·
0 I am exempt under Section __________ Business and Professions Code for this' reason:
.(Sec. 7031.5 Business and Professions Code: Any City or County which requires ~.permit to construct, alter, improye., demolish, or repair any.str)Jcture,
prior to its issuance, also requires the awl i cant for such permit to file a signed· statement that he 1 s .. H censed pl.irsuaht to the prov-is ions 'of the
Contractor's Lkense Law (Chapter 9, conmenci'ng with Section 7000 of Division 3 of the B<1siness a119· Professi9ns ,Code) or that he is· e_xelnpt :therefrOIT),
·and the basis for the aUeged exerrption. Any·v.iolation of Section 7031.5 by any applicant for a·permit .subjects the applicant to a civil.penal:t_y of .no.t
more than five hundred dollars [$5001).
SIG~ATURE 0,AtE .
~ffid_~@t_:@Jt FOR NON·RESIDENTIAL BUILDING PE~MITS ONLY:
Is the applicant or future building occupant required to submit a business plan, acutely hazardous materials regi~tration f.orm·o~ risk management a~ prevention
program under Sections 25505, 25533 or 2~534 of the Presley-Tanner Hazardous Substance Acco~nt Act? -
DYES .E:l'No . .
Is the applicant or future building occupant required to obtain a permit from the a1r p9l lut\'on control district or. ~.ir· quality management distr_ict?
DYES 0'No ,.
Is the fac,i l i ty to be constructed within 1,000 feet' of the outer boundary of a schoo.t site?
Om ,0No
IF ANY OF THE ANSWERS ARE YES,, A FINAL CERTIFICATE OF OCClJPANCY IIAY NOT BE ISSUED AHER JULY 1, 1989 UNLESS THE APPLICANT° HAS MET OR IS MEETING -THE REQUIREMENTS
OF THE OFF.ICE OF EMERGENCY SERVICES All> T~ ,AIR. POLLUTION CONTROL DISTRICT.
9. CONSTRUCTION LENDING AGENCY
I hereby affirm that there is a construction lending agency for the performance .pf the work for which this permi.t is issued (Sec 3097(i) Civi'l Cooe).
LENDER IS NAME LENDER_1S ADDRESS
10. APPLICANT'S SIGNATUR~
I ce·rtify that I have· read the application and state that the above information· is correct.. 'I agree to comply'with' all C-ity ·ordinances and· State··l'aws ·relating
to building construction. I hereby authorize representatives of the City of Carlsbad to· enter upon, the· apove .ment·i oned property for irispect.i ori ·purpos~~. .I ALSO
AGREE TO SAVE INDEMNIFY AND KEEP HARMLESS THE CHY OF CARLSBAD AGAINST ALL LIAB!tlTIES; JWGIIENTS, COSTS AND EXPEN~ES IIHtCH MAY IN ANY IIAY ACCRLIE 'AGA\NST· Si\lD
CITY IN CONSEQUENCE OF THE GRANTING OF THIS PERMIT. .
Expiration. Every permit issued by the Bui.lding Official under the provisions of tni·s i;ode shall expire by limitation ahd become riull .and voic! if the building
or· work authorized by such permit is not conmenced within 180 days from the date of such permit or if th~ building or· work euthori zed by such permit 'is suspended
or abandoned at any time after the work is conmenced for a period of 180 days (section 303(d) Unfform Bllilding Code.).
0 OWNER ~ CONTRACTOR OBY PHONE
HITE: File YELLOW: Appiiqant PINK: Finance
S E W E R P B R M I T
r O~l/ 10/':H l 'l: 37
Pag,::> 1 of 1
',J,>b Address: 2236 RlJ'rHERf'ORD RD
Permit Type.: SEWER -OFFICE/WAREHOUSE
P,:trci:l He•: ;~12-061-26:-oo
Vescription: J. 507 SF OF'PICE BLOCK MEDICAL
1507 SF WARBHOIJSE 'TO OFFICE
Penni tE·e: JM PROPERTIES
2·:36 RUTHERFORD RD JH01
CARLSBJ.s.D, CA 9200-8
***
619 438-3341
Permit Nu: :3E91ooe,1_1
4349 09/10/91 0001 01 02
C-P.RMT 1343.66
(P /1 ';(1 ... I"-..... (C , I
St.;1tus: ISSUE!)
Applied: Od/12/91
Apr/I:i'lsue~ 09/10/91
Expired:
Prepared By: MCL
-------~-----------------~--Fees: .1,343.66
~00
------~~--7------~~(---~----------------~---( /', ' ''-, '-..
.l\djustrnl:!nts:
'I'otal F,~e;;:: . 1,.343.66:, ,, . ',
> , ,. ,,_ " ~
· s: : <'. 1:0t,,:1.;:·~1t::ed its : . o u
-'!'ot,:i'i '--Pavments 't, . . oo .
Ba:lahte' ,6Li:e l ', 1 , ~: 4 3 , 6 6 ·'"" /'' Fee description l.'.fp.--it.s ', F~$./f.Jtti\t Ext fee Data -----------------.----...... ,:""_:__, ..... _...; __ -:-_.;,...:,,:.; ..... _t~\"'!"'::".:.::.:...---~.:..\.:...';..._-·.:.. ___ :._ ________ '. ________ _
Er.tter Off ic,::-Square ·Foota,ge >· . ,-.,.j..507,. :-, 84 ~~!:! ~~~s :_::. /:_~-=::,~J;x, . , , . , , , 13 5 i: ;~~
'~Sewer Credit> ··;,, ,:r48-3".00 .· -·, -483.r)O
Ent~r Sewer EDU:;; and Benet it Are-:11 ','> _,,· .. ,,"'~ :· ,S,:lf.'. • ,_.,.". 474. 66 P
' > • • ...... J ,,,. , ' : / • // , ,. :";-; ----• : f ,'. * SEWER TO'I'AL '•, '·.: ',,·\IA f -~;,·,· ' 1343.66
I
/
CITY OF CARLSBAD
2075 Las Palm~ Dr., Carlsbad·CA-920<)9 (619) 438-1161
,: '_, , t I•'
I. UNSCHEDULED INSPECTION !1/1~ __...,
DATE_-'-/_o)...,__,1/_~t:f~/___ INSPECTOR ~
PERMIT #. CIJ'}J/011 --p-;;.n-t--C-K---t#t--. -----
JOB ADDRESS_.,,...2_2,, ____ ~-'c,_...r.;J?t.1:;._.;...,,Zc..:.~'---~-"~--.,;;::. =-------...;..._ ______ _
MJtt'ffi Io<
TIME ARRIVE: _________ TIME LEAVE: _____ _
CD LVL D~SCR~PTION
PERMITS
6/15/89
ACT COMMENTS
PERMIT# CB911099
DESCRIPTION: 1507 SF OFFICE
CITY OF CARLSBAD
INSPECTION REQUEST
FOR 09/30/91
"BLOCK MEDICAL"
INSPECTOR AREA MC
PLANCK# CB911099
OCC GRP B2
CONSTR. TYPE VN TYPE: !TI
JOB ADDRESS:
APPLICANT: JM
CONTRACTOR:
2236 RUTHERFORD RD
PROPERTIES
STR:** FL:**** STE: 105
PHONE: 619 438-3341
PHONE:
OWNER: NEW ENGLAND MUTUAL LIFE/JM PHONE: 4383341
REMARKS:. MH/JERRY/438-3341
SPECIAL INSTRUCT: INSPECTOR --+A/vf:-=--1--~------7
TOTAL TIME:
--RELATED PERMITS--
CD LVL DESCRIPTION
PERMIT# TYPE
SE910080 SWOW
STATUS
ISSUED
ACT COMMENTS I
19 ST Final Structural CD !!(~17F~~~Ud. 6/c;:--29 PL Final Plumbing --i...;;c..~~2-____
39 EL Final Electrical __ (32 D!f!t~µ..b ll.}.,B1.,t"1\71, ~
49 ME Final Mechanical c..e,,,,_1'/~G«-,,,., ~ (~~
== = ============ ~. ~ oE -------,---------------
***** INSPECTION HISTORY*****
DATE
092491
092491
092491
092491
092391
092391
092091
0.91891
091791
091791
091791
091791
DESCRIPTION
Frame/Steel/Bolting/Welding
Rough Electric
Rough/Ducts/Dampers
Rough/Ducts/Dampers
Frame/Steel/Bolting/Welding
Rough/Ducts/Dampers
Rough Combo
lnterior Lath/Drywall
Frame/Steel/Bolting/Welding
Rough/Topout
Rough Electric
Rough/Ducts/Dampers
ACT INSP
AP MPC
AP MPC
AP MPC
CO MPC
NR MPC
NR MPC
NR MPC
AP MPC
PA MPC
NR MPC
PA MPC
NR MPC
COMMENTS
CEILING GRID
LIGHT FIXTURES
A/C REGSTRS HOR DUCTS
SEE INSP NOTES
CEILING GRID SYSTEM
CEILING GRIDS ETC
WALLS
IN WALLS
IN WALLS
CITY OF CARLSBAD
INSPECTION REQUEST
PERMI~# CB911099 . FOR 09/24/91
DESCRIPTION: 1507 SF OFFICE "BLOCK MEDICAL"
INSPECTOR AREA MC
PLANCK# CB911099
OCC GRP B2
CONSTR. TYPE VN TYPE: ITI
JOB ADDRESS:
APPLICANT: JM
CONTRACTOR:
2236 RUTHERFORD RD
PROPERTIES
STR:** FL:**** STE: 105
PHONE: 619 438-3341
PHONE:
OWNER: NEW ENGLAND MUTUAL LIFE/JM PHONE: 4383341
REMAR,KS: MH/JERRY/438-3341
SPECIAL INSTRUCT:
INSPECTOR ~t:_--7--------=--if--
TOTAL TIME:
--RELATED PERMITS--PERMIT# TYPE
SE910080 SWOW
STATUS
ISSUED
CD LVL DESCRIPTION ACT COMMENTS
----__________ __._ ___ ___
-------------------
***** INSPECTION HISTORY*****
DATE
091891
091791
091791
091791
091791
DESCRIPTION
Interior Lath/Drywall
Frame/Steel/Bolting/Welding
Rough/Topout
Rough Electric
Rough/Ducts/Dampers
ACT INSP
AP MPC
PA MPC
NR MPC
PA MPC
NR MPC
COMMENTS
WALLS
IN WALLS
IN WALLS
DEPT: BUILDING
RECErVF.11 nrr O 2 1991
FINAL BUILDING INSPECTION
ENGINEERING ~ PLANNING U/M WA ER
PLAN CHECK#: CB911099
PERMIT#: CB911099
PROJECT NAME: 1507 SF OFFICE "BLOCK MEDICAL"
ADDRESS: 2236 RUTHERFORD RD SUITE# 105
CONTACT PE~SON/PHONE#: MH/JERRY/438-3341
SEWER DIST: CA WATER DIST: CA
~~7PEff~
INSPECTED
BY:
INSPECTED
BY:
COMMENTS:
DATE
INSPECTED:
DATE
INSPECTED:
DATE
INSPECTED:
10/z/2_/
I I
DATE: 09/30/91
PERMIT TYPE: ITI
APPROVED cµ. DISAPPROVED
APPROVED DI'S APPROVED
APPROVED DISAPPROVED
:t'. ~~~~,,~~ ·, t!S'2~'.'~~{~"::?~~i,'.,,-½f ,>, f· .~ ,,A ,oe,c '· · -· . _ _ ~~~~~92'ft~~~'J;"(';
~tt'·;tff1~.:f,1t~-.i'};rt·:tf1~;._~/:.:e?-~~9JP .. 9QJlJ~!Q.~T~p~~-~i-----~::;\·:~~t:_··:~-~-----_. · ··: -:--~-· _ _. -·
_(1 ~,:,{_·,::·~_'·:~4-t~_::~,, .. ~.·--=, ._;·.... -.~32O_~HESA;~~~KB_~R~·;_~UI!~2O8-_:,:.~-. .
. ·· SAN DIEGO, .CA 92123
(619) 560-i4-68 . .
DATE:
JURISD.ICTION: CARLSBAD
PLAN CHECK NO: 91-(Qqq SET: JJT.
PROJECT ADDRESS: ____ 2~z=--=3~G--~R-D_t-h~e_y_-C.~·~o~r~d-~R_d_
PROJECT NAME: __ R=L=o~C~K--~iY:l ....... E~D~/~C~A_L_~_# __ l_o_S __ _
D
·--0
:0
-o
The plans transmitted herewith have been corrected where
necessary and substantially comply with the .jurisdiction's
building codes.
The plans transmitted herewith will substantially comply
with ·the jurisdiction's building codes when minor deficien-
cies identified b..e/ot,,) -are resolved and
checked by building department staff.
The plans tr~nsmitted herewith have sigriificant deficiencies
identified on the enciosed check list and should be corrected
and resubmitted for a complete recheck •
...
The check list transmitted herewith is for your information.
The plans are being held at E~gil Corp. until corrected
plans are submitted for recheck.
The applicant's copy of the check list is enclosed for the
jurisdiction to return to.the applicant·contact person.
ffl] Th_e applicant'·s copy of the check list -has been sent to:
Fib,+e C0nce·o+.s · Inc J
1s-.ro Hofe l c1rcfe north -#1-<-0 s:o q2.lt?cf.-
ffll Esgil staff did not advise the applicant contact person that
plan check has been completed.
O Esgil staff did advise applicant that the plan check has
been completed. Person contacted: -------------
Date contacted: Telephone ---------11 REMARKS: ....l.:Z:2::'.-~~~€!-~.ec:l!:U:l::l.L---'Lr,_.5::;..1.=-=...l..E:!.--1.:::ru:.~__J_~~~~
By:· DAVID . 1/jO Enclosures:
ESGIL CORPORATION ,.,,, ,'~ ~-d -----------
0 GA DAA ORN ODM
'
_,
DATE:
ESGIL CORPORATION
9320 CHESAPEAKE DR., SUITE 208
SAN DIEGO,.CA 92123
(619) 560-1468
JURISDICTION:
8 I 2t I q1
CARL~ BAO
QAPPLICANT
<t]JURISDICT:(QN> 0 PLAN CHECKER
QFILE COPY
CUPS
,:DESIGNER
PJ:.AN CHECK NO: SET: :r[
PROJECT ADDRESS:_· __ 2_Z_3_,__,6,___i.;R~u~r~h~e~t'---£....;...;..o~~~d"----'-R=c-l_
__ ..
PROJECT NAME:_~B~L=o"----c~K~·-~M~,~E~D~I_C-A~.~l ___ #_._,_to~5:"=----
D
D
D
D
The plans transmitted herewith have been corrected where
necessary and substantially comply with the jurisdiction's
building codes.
The plans transmitted herewith will substantially comply
with the jurisdiction's building codes when minor deficien-
cies identified...,..._ ______________ are resolved and
checked by building department staff.
The plans transmitted herewith have significant deficiencies
identifi~d on the enciosed check list and should be corrected
and resubmitted for a complete recheck.
The check list transmitted herewith is for your information.
The plans are being held at Esgil Corp. until corrected
plans are submitted for recheck.
The applicant's copy of the check list is enclosed fo~ the
jurisdiction to return to the applicant contact person.
fi\) Th_e applicant's copy of the check ~ist
f fb:+e Can ceo+~ lti C
has been sent to:
j
IS t12 d" +e I . Ctrcl..t;> J1oyf/2 I '
sP
.!lll lj Esgil staff did not advise the applicant contact person that
plan check has been completed.
O Esgil staff did advise applicant that the plan check has
been completed. Person contacted: ' ------------
Date c.ontacted: _________ Telephone # _______ _
D REMARKS=-----------"---------------
By: [)AVID YAD
ESGIL CORPORATION ~/1.r:-
Enclosures: -----------
lDGA DAA ORN ODM
,,
" "
. •' ~··. "
.JORISD1cr1m1 __ ---.:e...:.:;A...i.:;.~:..:'-=--iS..::~.-.:-.!4~"';:;,_-----
Pl.Alf aD!XX ltlm!R: _ _.9i;,_/;..__-_/ 0___,_9 ___ 9 ____ 2_/._
8
I. I
DA.1:£: a -2 , -9, !ITGLnf AD.WX
PI.AX QW3CER: 0 GARr IJQl.
D-----·-···-·-·-· --~ ··--·"
DATE:
ESGIL C.ORPORATION
9320 CHESAPEAKE DR., SUITE 208
SAN DIEGO, CA 92123
(619) 560-1468
R-I I
JURISDICTION: CARLSBAD LAN CHECKER
OFILE COPY
QUPS
QDESIGNER
PLAN CHECK NO: q/-1011 SE.T: .I_
PROJECT ADDRESS: ___ 2~2 .......... :3,_b~-,---· ~f<~«~tb ........... er....__,-h.~o--~~J~__._R~d
PROJECT NAME: _ ..... B......__f... ...... o_...c .... l~....__· ___ M ____ E ____ b ___ t c ___ A __ --=L-__,..# ___ ro __ s=--__ oFF I CE
D
D
D
The plans transmitted herewith have been corrected where
necessary and substantially compiy with the .jurisdiction's
building codes.
The plans transmitted herewith-will Substantially comply
with the jurisdiction's building codes when minor deficien-
cies identified-,--'---=-------...,....,,.---are resolved and
checked by building department staff.
The plans transmitted herewith have significant deficiencies
identified on the enclosed check list and should be corrected
and resubmitted for a complete recheck.
fflli The check list·transmitted herewith is for your information.
The plans are.being held at Esgil Corp. until corrected
plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the
jurisdiction to return to the applicant·contact person. . .
ffli The applicant's copy of the check list has been sent to:
°FI '71 fe f'/n"l Cf' ,rt:-:-f 11 C J
( I y,/.p SJ)
Im Esgil staff did not advise the applicant contact person that
plan check has been completed.
O Esgil staff did advise applicant that the plan check has
been completed. Person contacted: ------------
Date contacted: Telephone # ------------------0 REMARKS: _____________________________ _
By:· ~-Al/(D ~o ESGL C0RPORATI N Pf;
OGA DAA D R~l ODM
Enclosures: -----------
,,
• <.
PI.Alf aIECK BO. :. __ ---'9-'-f-_,:._/ 0__,_1__._9_--,--_
JDRISDicrION:.--'CARLSBAD===:;..._-----------
1'0: 1=-;n ,+e CoYI C:e r2+s /11 (.
I
is-ro Hot I Cwc.fe North 4, i.-o
~() CA C/Z/of-
OCCUPAHCT: _____ ~R __ -___ < ________ ~
BUILDIHGUSE: ___ o~{~'_{_,_{e _____ _
TYPE oF coHSIRUC'I'IoH: __ ""'"v_-_N _________ _
AcmAL ARY.A:. ______ ·_/ S:_()_7 __ ._s_._F ___ _
ALLOWABLE ARY.A: ______________ _
SIORIES: _______ __,;; _________ --,-
HEIGHI: ____________________ _
SPRINICLERS: _____ --;,c..;:P~..__ ________ _
OCCOPAN.r LOAD: ______ __,_/_-________ _
REMARKS:. _____________________ _
Date plans received by jurisdiction:
Date plans received by Esgil Corporation:
e/r /q/
Date initial plan check completed:
-~---By:___.i>.t:..LA-'-l:V~l~D_Yi,1-J.'lt~v~ I
Applicant contact person:
FORE.WRD: PLF.ASE READ
Plan check is limited to technical requirements
contained in the Uniform Building Code, Uniform
Plumbing Code, Uniform Mechanical Code, National
Electrical Code and state laws regulating energy
conservation, noise-attenuation and access for the
handicapped. The plan check is based on
regulations enforced by the Building Inspection
Department. You may have other corrections based
on laws and ordinances enforced by the Planning
Department, Engineering Department, Fire Department
or other departments. Code sections cited are
based on the 198~ UBC.
The circled items listed
modification or change.
need clarification,
Ali items must be
satisfied before the plans will be in conformance
with the cited codes and regulations. Per Sec.
303(c),·1988 Uniform Building Code, the approval of
the plans does not permit the violation of any
state, county or city law.
To speed up the recheck process, note on this list
(or a copy) where each correction item has been
addressed, i.e .• plan sheet, ·specification, etc.
Be sure to enclose the marked up list when you
submit the revised plans.
NOTE: PAGE NUMBERS ARE NO'.[ IN SEQUENGE AS PAGES_ HAVING BO I:nMS HEEDING CORREC'.I;WHS WERE DELEnD.
LIST NO. 56 CARLSBAD TENANT IMPROVEMENT-WITIIOUT SPECIFIC ENERGY ZONE DATA OR POLICY SUPPLEMENTS, 1988 UBC
f·
!·
0
f-
l·
{
Please make all corrections on the original
tracings and submit two new sets of prints, and
any original plan sets that may have been
returned to you by the jurisdiction, to:
Esgil Corporation, 9320 Chesapeake Drive,
Suite #208, San Diego, CA 92123,
(619) 560-1468.
Please make all corrections on the original
tracings and· submit two new sets of prints, and
any original plan sets that may have been
returned to you by the jurisdiction, to:
The jurisdiction's building department.
Indicate on the Title Sheet of the plans, the
name of the legal owner and name of person
responsible for the preparation of the plans. Section 302(d). -
Each sheet of the plans must be signed by the
person responsible for their preparation, even
though there are no structural changes.
Business and Professions Code.
Plans and calculations shall be signed by the
California state licensed engineer or architect
where there are structural changes to existing
buildings or structural additions. Please
include the California' license· number, seal,
date of license expiration and date plans are
signed. Business and Professions Code.
Provide the correct addre~s and suite number of
tenant space on the plans. Section 302(d).
Provide a note on the site plan indicating the
previous use of the tenant space or building
being remodeled. Section 302.
· When the character of the occupancy or use
changes within a building, the building must be
made to comply with current Building Code
requirements for the new occupancy. Please
provide complete details to show the building
-with comply. Section 502.
UBC Section $04 requires the Building Official
to determine the total value of all
construction work proposed under this permit.
The value shall include 'a!l finish work,
painting, roofing, electrical, plumbing,
heating, air conditioning, elevator, fire
extinguishing systems and any_ o.ther permanent
equipment. Please provide a signed copy of the
designer's or contractor's construction cost
estimate of all work proposed.
Provide a plot plan showing the .distance from
the building to the property lines and .the
location of tenant space (or remodel) within
the building.
u.s.e c +
d 6r-'-•r <
I
f·
r·
r·
r·
fa·
On the first sheet of the plans indicate:
Type of construction of the existing building,
present and proposed occupancy classifications
-of the remodel area and the occupant load of
the remodel areas and the floor where the
tenant improvement is located.
Provide a note on the plans indicating if any
hazardous materials will be stored and/or used
within the building which exceed the
quantities list~d in UBC Tables 9-A and 9-B.
A complete description of the activities and
processes that will occur in this tenant space
~hould be provided. A listing of all
hazardous materials should be included. The
materials listing should be stated in a form
that would make classification in Tables 9-A
and 9-B possible. The building official may
require a technical report to identify and
develop methods of protection from hazardous
materials. Section 90l(f).
If control areas are used for exceeding the
exempt amounts of hazardous materials from
Tables 9-A and 9-B, they shall be constructed
of not less that required for a one-hour
occupancy separation. Section 404.
The number of control areas within a building
used for retail/wholesale stores shall·not
exceed two; the number of control areas in
buildings with other uses shall not exceed
four. Footnote l, Tables 9-A and 9-B.
The aggregate quantity of any hazardous
materials "in use" and "in storage" shall not
exceed the quantity listed in Tables 9-A and
9-B for "storage11• Footnotes 2 and 3, Tables
9-A and 9-B.
Provide a statement on the Title Sheet of the
plans that this project shall comply with
Title 24 and 1988 UBC, UMC and UPC and 1990
NEC. ==-
Provide a fully dimensioned floor plan showing
the size and use of all rooms or areas within
the--·space ·being improved or· altered.· Draw the
plans to scale and indicate the scale on the
plan. Section 302(d).
Indicate the use of all spaces adjacent to the
area being remodeled or improved.
Show any existing fire rated area separation
walls, occupancy separation walls, demising
walls, .shafts or rated corridors. Identify
and provide construction details for proposed
new fire rated walls.
Specify on the plans the fire ratings of
assemblies to protect proposed openings in
existing or new fire walls.
/"-,---
e,./ .c ,' ( p ? ?.)
f
)9.
Section 330S(g), -Exception 5 is applicable. only
for corridors on one floor; .the corridors on
the lower level(s) must be rated if these lower
corridors have openings into them from other
levels.
If non-rated corridors are used per Sec½ion
3305(g), Exe. s, provide a reference to the
corridors on the floor plan, noting:
1, Corridors are non-rated per Section
3305(g), Exception 5.
2. Smo~e detection system must be listed by
the State Fire Marshall and be a
supervised low v~ltage system •.
3. Smoke detectors shall be maximum 30 1 on
center.
4. Power supply shall be dedicated branch
·circuit. Circuit disconnecting means
shall be accessible only to authorized
personnel and shall be clearly marked FIRE
ALARM CIRCUIT CONTROL, with a lock-on
device.
If a tenant space utilizes Section 3305(g),
Exception 5., then · that tenant space shall be
separated from adjacent spaces by a demising
wall constructed as for a one-hour corridor
wall.
·ciearly show where the non-rated corridor
system terminates and a rated corridor system
co1111Dences.
One-hour fire-rated corridors shall have door
openings protected by tight-fitting smoke and
draft control assemblies rated 20 minutes,
except openings in interior walls of exterior
exit balconies. Doors shall be maintained
self-ciosing or be automatic-closing by action
of a smoke detector per Section 4306(b). Doors
shall be gasketed to provide-a smoke and draft
seal where the door meets the stop on sides and
top. Section 3305{h,).
Show rated corridors,' lobbies, reception or
foyers cross-hatched on the floor plans.
Total area of all openings, except doors, in
any portion of an interior corridor, shall not
excee9 25 percent of the area of the corridor
wall of the ~oom which it is separating from
the corridor. Such openings shall be protected
by fixed, approved 1/4 inch thick wired glass
installed in steel frames. Section 3305(h),
6/13/90
i
r·
f·
~-
0
0
Provide a complete architectural section of
the corridor, or exterior exit balcony,
showing all fire-resistive materials and
details of construction for all floors, walls,
ceiling and all penetrations. Section
3305(g).
Show 'the location of fire dampers. Provide
fire dampers at duct penetrations of fire-
rated occupancy and area separations, shafts
and corridor walls and ceilings. Section
4306(j).
If a room with an exhaust fan has a door
opening into a rated corridor, show how make-
up air will be provided to the room. The door
cannot be undercut, nor · can a louver in the
door be provided. Section 3305(h)l,
If building exceeds two stories and has an
elevator opening into.a rated corridor, show
how ·the smoke and draft control provision of
Section 3305{h) will be met. Either provide a
separated elevator lobby or a second door at
the elevator entry meeting the provisi?n·
If a second door is provided
entry, note that it will be
from the car side without
special knowledge or effort.
at the elevator
readily openable
a key, tool or
Section SJ,06.
Provide evidence of Health Department approval
(for restaurants or for tenants us1ing X-ray
equipment). :r.f o.pp /, Cq.l, e,
When nonflammable supply cylinders for medical
gas systems are located inside buildings, they
shall .be in a separate room or enclosure
separated from the rest of the building by not
less than one-hour fire-resistive
construction. Doors to the room or enclosure
shall be self-closing.smoke-and draft-control
assemblies having a fire-protection rating of
not less than one hour. Rooms shall have at
least one exterior wall in which there are not
less than two vents of no~ less than 36 square
inches in area. One vent shall be within 6
inches of the floor and one shall be within 6
inches of the ceiling. When an exterior wall
cannot be provided for the room, automatic
sprinklers shall be installed within the room
and the room shall be vented to the exterior
through ducting contained within a one-hour-
rated shaft enclosure, Approved mechanical
ventilatio~ shall provide six air changes per
hour for the room. Section 702(b)4/
-.z:_ 1-0. ppn (nJ, -e_.
5
~
71·
Submit plan showing location of all panels.
Submit panels schedules. Rc>v1~e'f'"1?el sdrPdl.(/e
Submit electrical load calculations
Indicate existing main service size. /4· .J!_. Indicate existing total main service load.
@ Indicate new additional loads.
<!!.J Indicate wiring method, i.e. EMT, metal flex.
7~ Show exit signs on the electricai,lighting I plan(s). As per Section 3313 and 3314 of the·
1988 UBC, provide two sources of power to exit
0
@
sf.
J.
L. !
(s.
f·
@
signs and exit illumination.
Provide receptacle{s) within 25 1 of HVAC units.
UMC Section 509.
Provide multiple swi;ch lighting controls per
Title 24, 5319. dH>.fhn<:9-ro011"\.. ;
Provide an electrical.plan for the alarm system
showing compliance with criteria described
under earlier correction number 58.
Provide mechanical ventilation in all rooms
capable of ·supplying a minimum of 5 cubic feet
per minute of outside air with a total
circulation of not less than 15 cubic feet per
minute per occupant. Section 605 and 705, UBC.
Provide mechanical plans showing existing and
proposed HVAC equipment, ducts and access to
equipment.
Detail access and working clearances to HVAC
equipment.
Cooling coils or cooling units located in attic
or furr~d· space, where damage ·may result from
condensate overflow, shall -be·· provided with an
additional water tight pan of corrosion
resistant -material to catch overflow if primary
condensate drain becomes clogged. Section 1205, UMC. .
One-hour corridors shall not be used as an
integral part of a duct system. This includes
the space above a dropped ceiling within the
one-hour corridor. UMC Section 706(b).
PLDHBING
~as line plans and
pipe lengths and gas
Provide
showing
S~ftion v,ec<.>e..
1~1~~r/y ,shoiv W~e>re
,1 .. a I
calculations,
demands. UPC
t-he.. C-ondfr ... ;o.:¼_
7/10/91
9/·
. f.
Provide drain, waste and vent plans.
Provide water line sizing calculations. UPC
· Section 1009.
Detail how floor drain trap seal is to be
maintained. UPC Section 707 (floor drain trap
priming) .•
Show P & T valve on water heater and detail
drain line route from P & T valve.to the
exterior. UPC.Section 1007(e).
Show 1/411 per 1211 slope on drain and waste
lines. UPC Section 407.
Provide a drinking fountain at each floor
level in assembly occupancies (except drinking
and-dining establishments). UBC Section 605.
Provide complete energy design calculations,
including all existing design and new energy
design for this building. See attached non-
residential energy design checklist •
For remodels in an existing conditioned space,
show· that ·the remodeled space will not use
more energy than the existing space or show
the remodeled space will conform to -latest
energy design standards.
CITY OF CARLSBAD SUPPUmXr
Floor drains must have auto-prime (City
Policy).
A grease interceptor is required. Show
details complying with City Policy 83-34.
Roof mounted equipment must be screened and
roof penetrations should be minimized (City
Policy 80-6) •
Condensate drains must connect to a wet trap
(dry traps are not permitted). (Memo
1/14/83).
fo. Show fans are duct type; City Policy does not
permit ductless fans.
~Romex is not permitted in industrial or V commercial buildings. (City Policy)
fioz\ No wiring is permitted on the roof of a V building and wiring on the exterior of a
building requires approval by the Building
Official. (City Policy)
~ All roof-mounted equipment shall be concealed V from view. Provide structural detailing for
the screening.
clff.!,,,_ --h, ? vJh1ch re c~p,.~c/e ?
J
..,l.h_.
D,lrr
7
All panel boards -shall have a minimum 100 amp rating or approved by the Building.Official.
The min:imi.lm rating of a service disconnect is
100 amperes.
The minimum size conductor to receptacles and
lighting fixtures in commercial and industrial
buildings shall be #12 Cu.
~ AC(BX) cable is not allowed in group A, B, E, H V and I occupancies. (see Ord. for exception)
MISCELLAMmJS
Please see additional
that follow.
corrections or remarks
~ To speed up the · .. recheck process, note on this V list (or a copy) where each correction item has
been addressed, i.e., plan sheet, note or
detail number, calculation page, etc.
t:')Please indicate here if any changes have been V made to the plans that are not a result of
corrections from this list. If there are other
changes, please briefly describe 'them and where
they are located in the plans.
NO'IE:
Have changes been made to the plans not
resulting from this correction list? Please
check.
____ Yes ______ ... No
The following provisions are contained in Title 24,
Part 2, California Building Code, as adopted and
enforced by the State Fire Marshal. They are
provided pere as a courtesy to assist designers in
developing· the project documents. All applicable
provisions may not necessarily be included. Please
direct any questions i:egarding interpretations of
these provisions to the local Fire DepartEnt.
S-1. Walls of corridors and exterior exit balconies
in Groups A,E,I.,R-1 a,nd C Occupancies having an
occupant load of more than!!! persons and in
all other occupancies having an occupant load
of 30 or more shall be not less than one-hour
fire-resistive construction. Section 3305(g)l.
S-2. Note on the plans that approved floor-level
S-3. Area separation walls shall not be considered
to create separate buildings for the purpose
·of automatic fire-sprinkler system
requirements as set forth in Chapter 38.
Section SOS(e)6. .
EXCEP'IION: Buildings separated by continuous
area separation walls of four-hour fire-
resistive construction without openings.
Buildings required to have automatic fire-
sprinkler prot~ction as set forth in Section
13113 of the Health and Safety Code (homes for
children or the aged) are prohibite4 from
using area separation walls in lieu of
automatic fire-sprinkler protection.
S-4. In educational occupancies, storage and
janitor closets shall be of one-hour fire-
resistive construction with openings protected
by assemblies having at least a three-fourths-
hour fire-resistive rating. Section 802(c)-.
S-5. Section 1807 should be reviewed for all high-
rise·buildings.
S-6. The exception in Section 3318 of the UBC has
been revised· so.as -to allow the omission of
panic hardware at 'the main exit in churches
(by using signage), only when the occupant
load of the church is less than 300.
S-7. If emergency warning systems are required,
they shall activate a means of warning the
h~ing impaired. Flashing visual warnings
shall have a frequency of not more than 60
flashes per minute.
The jurisdiction has contracted with Esgil Corporation located at 9320 Chesapeake Drive, Suite
208, San Diego, California 92123; telephone number
of 619/560-1468, to perform the plan check for your
project. If you have any ·questions regarding these plan check items, please contact. _______ _
]>AV ID
at Esgil Corporation
Thank you.
Enclosures:
YA-o I .
!. ______________________ _
exit signs shall be proy-ided. This applies to 2 • _____________________ _
A, E and I occupancies.
3. _____________________ _
rl ?
I I
7/8/91 7
.•·
Dates Jurisdic~ion GARLSBAD
_Prepared by,
k'AWD y1w VALUATION AND PLAN CHECK· FEE·
CJ Bldg. Dept.
O Esgil
PLAN CHECK NO •. q I-ID qq
BUILDING-ADDRESS 2Z.;3£ t?ufhn::Gcd 12d.
APPLICANT/CONTACT r(n l fe U7t.(11pf.s PHONE NO. ~ fib -6 / / o
BUILDING OCCUPANCY f>--< _ DESIGNER PHONE -----,----TYPE OF CONSTRUCTION V-N ~Pk CONTRACTOR PHONE . -----
BUILDING PORTION BUILDING AREA 'VALUATION VALUE
·MULTIPLIER
-r: 7-J 1.-0 7 2. I 3 /, 64 -r!!_
, .
..
Air Conditionine:
Commercial .. @ ..
Residential @ ..
Res. or Comm.
Fire· Snrinklers @
•,•
Total Value ~/, c47.2.1L
Building Perm it fee $ _________ -______ _,_ __ ___,$"--_--.;;;.;2._q...r...J,..7_J_-:-tJ __
l a>~ P Ian Che c~ f" ee--'$---------------------------$ __ __,_...;..7::;.._;, __ _
COMMENTS_,:---------------------------
SHEET __ OF __
12/87
,,., Cl:> 99-00lq \lqqa ai=FICE
v ZL\'1 olil WAR.E !tdJU.SE.
,, Ji
..J
BUILDING PLANCHECK
ENGINEERING CHECKLIST
DATE: _...a;B;;....-_____ , 2=---9--"-t _______ _ \)
< [if ITE.M COMPLETE
~ PLANCHECK NO. C~ 9 I -16 9 9 ITEM INCOMPLETE
NEEDS YOUR ACTION t <(
1 2 3 ITEM SELECTED
s N R
T D D
C C C PR0JEGT ID: APt-J 212-O6 t -2 b
H H H
E E E LEGAL REQUIREMENTS
K K K Site Plan
5ZJDD 1.
DOD 2.
ODD 3 •
Provide a fully dimensioned site plan drawn to scale.
Show: north arrow, property lines, easements, existing and
proposed structures, streets, existing street improvements,
right-of-way width and dimension setbacks.
Show on site plan: Finish floor elevations, pad
elevations, elevations of finish grade adjacent to
building, existing topographical lines, existing and
proposed slopes, driveway with percent ( % ) grade and
drainage patterns.
Provide legal description and Assessors Parcel Number.
I . Discretionary Approval Compliance
[1]00 4. No Discretionary approvals were required.
ODD 5. Project complies with all Engineering Conditions of Approval for Project No. ________ _
DOD 6. Project does not compiy with the following Engineering
Conditions of Approval for Project No. _________ _
Conditions complied with by: ________ Date: ___ _
Field Review
DOD 7. Field review completed. No issues raised.
DOD a. Field review completed. The following issues or
discrepancies with the site plan were found:
DOD A. Site lacks adequate public improvements
DOD B. Existing drainage improvements. not shown or in
conflict with s·ite plan.
DOD c. Site is served by overhead power lines.
P:\DOC$\MISF0RMS\FRM0010.DH REV. 02/27/91
DODD. Grading is required to access site, create p,.
provide for ultimate street improvement.
DODE. Site access visibility prc;>bleins 'exist. Provide onsitt.
turnaround or engineered solution to problem.
DOD F. Other: _______________________ _
Dedication Requirements
I 5ZJDD
DOD
9.
10.
No dedication required.
Dedication required. Please have a registered civil
Engineer or Land Surveyor prepare the appropriate legal
description together with an 8\11 x. 11" plat map and submi4 with a title report and the reqg.ired processing fee •. All
easement documents must pe approved and signed by owner(s)
prior to issuance of Building Permit. The description of
the dedication is as follows: ______________ _
Dedication completed, Da.te _________ _ By: __ _
~ Improvement Requirements .
\/ DD 11. No public improvements required. SPECIAL NOTE: Damaged or
defective improvements found adjacent to building site must
be repaired to the satisfaction of the City inspector prior
DD 0 12 •
to occupancy. ·
Public improvements required. This project :c:equires
construction of public improvements pursuant to Section
18. 40 of the City Code. Please have a registered Civil
Engineer prepare appropriate improvement plans and submit
for· separate plancheck process through the Engineering
Department. Improvement plans must be approved,
appropriate securities posted and fees paid prior to
issuance of permit. The required improvements are: __ _
Improvement plans signed, Date: ________ by: ___ _
P:\DOCS\MI$FORMS\FRM0010.DH REV. 02/27/91
><ODD 13.
DD D 13a.
I fiZJDD 14.
Improvements are required. Construction of the public
improvements may be deferred in accordance with Section
18.40 of the City Code. Please submit a letter requesting
def err al of the required improvements together with a
recent title report on the property and the appropriate
processing fee so we may prepare the necessary Future
Improvement Agreement. The Future Improvement Agreement
must be signed, nqtarized and approved by the City prior to
issuance of a Building Permit ..
Future Improvement Agreement completed, Date: _____ _
By: __________ _
,,
Inadequate information avaiiable on site plan to make a
determination on grading requirements. Please provide more
detailed proposed and existing elevations and contours.
Include accurate.estimates of the grading quantities (cut,
fill, import, export).
No grading required ~s determined by the
provided on the site plan .•
information
D D D 15. Grading Permit required. A separate grading plan prepared
by a registered civil Engineer must be submitted for
separate plan check and approval through the Engineering
Department. NOTE: The Grading Permit must be issued and
grading substantially complete and !ound acceptable to the
City Inspector prior to issuance of Building Permits.
Grading Inspector sign otf. Date: ______ by: ____ _
Miscellaneous Permits
~DD
DOD
ODD
l&IDD
5rloo
16.
i7.
18.
19.
20.
Right-of-Way Permit not required.
Right-of-Way ~ermit required. A separate Right-of-Way
Permit issued by the Engineering Department is required for the following: ____ -________________ _
Sewer Permit is not required.
Sewer Permit is required. A sewer Fermi t is required
concurrent wi t;.h Building Perin:i,. t issuance. The fee required
is noted below in the fees section.
Industrial Waste Permit is not required.
P:\DOCS\MISFORMS\FRMD010.DH REV. 02/27/91
lg)
]21
~I
g'
D
21. Industrial Waste Permit is required. Applicant must
complete Industrial Waste Permit Application Form and
submit for city approval prior to issuance of a Building
Permits. Permits must be issued prior to occupancy.
-Industrial Waster Permit accepted -
Date: _________ By: __ -___________ _
Fees Required rso'1 ltl OFFICE ADT::. 2.l.
27. Park-in-Lieu Fee
23.
24.
25.
26-
27.
Quadrant: ____ Fee per Unit: ______ _
Total Fees: __ _
Traffic Impact Fee
Fee Per Unit: . IQ/ AD1 • j
Bridge and Thorough fare Fee
Fee Per Unit: 72 / ADT
Public Facilities Fee required.
Zt A 00 Total Fee:---"____._~1..1 __ _
Total Fee: '-4 b Z oo
Facilities Management Fee Zone:_~ ______ Fee: NO t,JE..
sewer Fees Permit No. SE.·Q\~6 ~h EDU's ,54 X 1~10-=-Bl:.9,YO
Benefit Area: I=°-::. 879 X , sL.f-=-47'/ ,,,Fee: I :3 Y ~ . b b
~Cb D 28. sewer Lateral Required: ___ tJ_.1.._.A ____________ _
Fee: _________ _
0 29. RE~KS : ______________________ _
At>T-=-
zo-(:. Al>T t2i
\000 czi X \S01 =
21.\C>
ENGINEERING AUTHORIZATION TO ISSUE PERMIT
BY:~~ z;>
DATE: ____ ·~_-""""'/_2-_-9_/ __ _
E'DtJs Xe;oom x. tso1 i-4 =-c,BL-1
1/ooooRlx 1so7rA = o. ~ox lblO = LI 83.oo sewe,,r crc:.d,t
P:\DOCS\MISFORMS\FRM0010.DH REV. 02/27/91
Qj Qj .., ..,
(0 (0
C C
j I
~ ~ ... N ,., ,.,
.,,,_ .,,,_
u ·u Qj Qj .t: .t: u u
C: C:
(0 IQ .., ..,
Q. Q.
Qj ..,
(0
C
~
~ .,,,_
u Qj .t: u
C: IQ ..,
Q.
PLANNING CHECKUSf
Plan Check No. q/_..(Ot/1 Address ~'2.36-~f?u~7H......_&R-"--"-"@"--'W,....___ ______ _
Planner V-CyN~ Phone 438-1161 ext. q3c:..J
(Name)
APN: £L «-06(-c:/:,
Type ofProject and Use I/J/JUJ.'7f?ll!tv z:z;;._
Zone C6v:": Facilities Management Zone __ ,&._..... __ _
Legend
[l] Item Complete
D Hem Incomplete -Needs your action
1, 2, 3 Numper in circle indicates planclaeck number-where deficiency was
identified
.. ~ 0 E:nvironmental Review Required: YES _ NO _){_ TYPE ---,---
DATE OF COMPLETION:
Compliance with conditions of approval? If not, state conditions which require action.
Conditions of Approval _______________________ _
Discretionary Action Required: YES _ NoK TYPE __ _
APPROVAL/RESO. NO. __ _ DATE: -------PROJECT NO. ___ _
OTHER RELATED CASES: -------------------------------
Compliance with conditions of approval? If not, state conditions which require action.
Conditions of Approval--------------------------
California Coastal Commission Permit Required: YES _ NO~
DATE OF APPROVAL:
San Diego Coast District, 3111 Camino Del Rio South, Suite 200, San Diego, CA. 92108-1725
(619) 521-8036
Compliance with conditions of approval? If not, state conditions which require action.
Conditions of Approval----------------------------
Landscape Plan Required: YES _ NO _
See attached submittal requirements for landscape. plans
Site Plan:
Zoning:
~o /L
I 11rtf"U!; & t11 r--cOP
1.
2.
3.
4.
1.
2.
3.
D D O o .. t I ~ 4. v3~J
Provide a fully dimensioned site plan dr~wn to scale. Show: ~or::h
arrow, property lines, easements, existing and proposed structures,
streets, existing street improvements, right-of-way width ar.d.
dimensioned setbacks.
Show on Site Plan: Finish floor elevations, elevations of finish grade
adjacent to building, existing topographical lines, existing and proposed.
slopes and driveway.
Provide legal description of property.
Provide assessors parcel number.
Setbacks:
Front: Required
rnt. ~ide: Required
Street Side: Required
Rear: Required
Lot coverage: Required
Height: Required
Parking: Spaces Required
Guest Spaces Required
Shown
Shown
Shown
Shown
Shown
Shown
Shown
Shown
D O O Additional Comments ___________________ _
OK TO [SSUE AND ENTERED APPROVAL INTO COMPUTER V ~ ).____ DATE z-::,1.,-f t:
PLNCK.FR.M
-. -C'()
' r
COMMERCIAL/INDUSTRIAL
APPLICATION FORM FOR INDUSTRIAL WASTE DISCHARGE PERMIT
CITY or CARLSBAD
APPLICATION: NEW _____ X....__ __ _
(CHECK ONE) REVISED ---------
BUILDING P.C. NO.: q ;-.){) 91
APPLICATION NO.: 8(o4-
INDUSTRIAL CLASS: 3/ / 80
DATE: 7•3/· jf
APPLICATION FOR INDUSTRIAL WASTE DISCHARGE PERMIT
B~ WAST~AND PROCESSING: (Check where applicable)
lz( Domestic Waste Only 1-1 Industrial Waste 1-1 Industrial Waste NOT
--Discharged to Sewer -Discharged to Sewer
GENERAL DESCRIPTION Of WASTE (Chemical and Physical Characteristics of
proposed waste): . /4£11/~ <2rf"'//e' ;=t2L t?JelJ/fftC-t::;4?V;.,e'IWAff ~Le.'5
• . . • J /eoz¢:
GENERAL DESCRIPTION Of PROCESS (If Applicable): _________ _
C. WASTES TO BE DISCHARGED TO SEWER:
WASTE:
(Check One)
TREATED: ~
UNTREAT~ --
QUANTITY: AVERAGE ____ GPO (Daily) MAXIMUM ____ GPO
(Gallons Per Day)
\
. " , -, '. •';. I t
City of Carlsbad Ai•h II I ,iU. ,I; N •ZM§ ,., ., I ,i§" I
INDUSTRIAL WASTE PERMIT
You are applying for a building permit that requires an Industrial
Waste Application per City Sewer Ordinance 13. 16.
The attached application should be completed and returned to the
Development Processing Services Division as soon as possible.
This permit will be reviewed and forwa.rded to the Encina Water
Pollution Control facility or San Diego County Department of Public
Works for. investigation of capacity and usage.
' I • \ \ '~ '., • ! •
If this is not returned before planchecking·' is _completed, yoyr building
permit could be delayed.
2075 Las Palmas Drlve•Carlsbad, California 92009-4859•(619) 438-1161
' '
·,
' ' . , '
2560'ORION WAY
CARLSBAD, 'CA 92008
·. €:itp -of <ltarl~bab
FIRE DEPARTMENT
PAGE' 1 OF _j_
TELEPHONE
(619) 931-212,1 APPROVED "1< · ..... .,,,,
' DISAPPROVED ,., ....
PLAN CHECK REPORT PLAN CHECK#
:<)1-1n?1
., PROJECT ''Et: QL K M 8\,c AL ADDRESS ]d3C.0 i<M11-lt::l( fuR l\ StE IDS-
,, ARCHITECT £1 N 11'1= Co"-..1 C E:?T .S ADDRESS 'S fVJ i) tE GD PHONE "J9to-fc.~11 o
OWNER Nt:..-u) 016( Avub IU 1-11UAI.. Ltf € ADDRESS & Al2LS3Ai) PHONE L\ 3R-.'.53 '-I I
occuPAN.QY BZ · CONST. --:::'-..l."'-'-'Ai"--_ _.... .. To,:ALSO. FT. ----~ STORIES '
;&SPRINKLERED '¥1-JENANT IMP. _.l-"S:=..c0=--1..__,~'""""'+-->,t--------'-----,-:,.-----------
__ 1.
_._2.
--. _3.
~ 4. r,
_·_5_
"-1-__ 6.
::;£,....1.
APPROVAL OF PLANS IS PREDICATED ON CONFORMING
TO THE FOLLOWING CQNDITIONS AND/OR MAKING
. THE FOl.LO'f'IN~ CORRECTIONS:
PLANS, S_PECIF.ICATIONS, AND PERMITS
Provide one copy of: floor plan(s); site plan; sheets
Provide two site plans showing th~ location of al! existing fire hydrants within 200 feet of the project.
Provide specifications for th~ .following: .~------,------~----'-----'---------
Permits are required for the installation of all fire protection system~, stand pipE:ls, dry chemical, halon,
CO2, alarms, hydrants). Plan must be approved by th~ fire·department prior to, installatiori.
The business owner shall complete a bu ii.ding information l~tter and return it to ·the fire department.
FIRE PROTl:CTION SYSTEMS AN·D ,EQUIPMENT
Tfle following fire protection systems are required:
if..Autornatic fi're sprinklers (Desi~n Crite[ia: ---i:A-=£..,_. -~.>.-:~=_. _:,_.....1.&""l--'-f_-p.,_·;4_~-=tc.::.3=-----------~---
D Dry Chemical, Halon, CO2 (Location: ---'----,---~----''--'-------"------------
. D Stand Pipes (Type: -,-. --,--·. ---~----~------'--'----------'----~-,
D Fire Alarm (Type/Location: ------------:'----------------~--
Fire Extinguisher Requirements: . · . . · .
~One 2A rated ABC extinguisher for each. WDD D sq. ft. or portion thereof with a travel distance to the nearest
extinguisher not to exceed 75 feet of travel.
D An extinguisher with a minimum rating of . . to be located:
D ,Other:----,-------------~~----'-----------,--~------
--. 8. Additional fire hydrant(s) shall be p_rovided -----"-',--------,--~~------..,,......----,--
EXITS
~-9. Exit doors shall be openable fro"'. the inside withdut the llSe of a .key or any special knowledge ?r effort.
__ .16. · A sign stating, " This door to remain unlocked :during business hours" ·shall be pl.aced above the main exit and
doors--~----',-----~----~----~----------~--
· __ . 11 .. EXIT signs (6" x ¾" l~tters) shall be placed over all req~irep exilts and directional signs located as necessary to
cleariy indicate the location of exi.t doors.: ·
Gl:NERAI,.
_._12. Storage, dispensing or use of any flammable or combustible liqqids, ffamma'ble liquids, flammable gases and
hazardous chemicals shall comply. with Uniform Fire Code.
__ 13. Building(s) not approved for hi~h piled combustible stock. Storage in clos.ely:packed piles shall not exceed:15 feet
.in height, 12 feet on pa,llets or in racks and 6 feet,for tires., plastics and some flammable liquids. If high stock pil-
ing is· to be done, comply wi.th Uniform Fire Code, 'Article 81. · ·
__ 14. Add.itional Requirements. -.,----,--'-----'--------~-,-------------
--15. Comply with regulations on attached sheet(s).
Plan Examiner'----,_·, (1 __ ~,L...,,, -------L Date---"~"'-'/'--z--'/_9'-f/ ___ _
Report mailed to architect ___ Met with -----------''---__ Attach to Plaas
l