HomeMy WebLinkAbout2252 Ivory Pl; ; CBR2017-1449; Permit(city of
Carlsbad
Residential Permit
Print Date: 02/02/2018 Permit No: CBR2017-1449
Job Address:
Permit Type:
Parcel No:
Valuation:
Occupancy Group:
# Dwelling Units:
Bedrooms:
Project Title:
2252 lvory Pl
BLDG-Residential
2132021900
$3,084.90
Work Class:
Lot#:
Reference#:
Construction Type:
Bathrooms:
Orig. Plan Check#:
Plan Check#:
Description: ADDAMO: 182 SF DETACHED PATIO COVER -SOLID ROOF
BUILDING PERMIT FEE $2000+
BUILDING PLAN CHECK FEE (BLDG)
Owner:
TRUST AOOAMO FAMILYTRUST
2252 Ivory Pl
CARLSBAD, CA 92009
ELECTRICAL BLDG RESIDENTIAL NEW/ADDITION/REMODEL
5B1473 BUILDING STANDARDS FEE
STRONG MOTION-RESIDENTIAL
Total Fees: $147.46 Total Payments To Date:
Patio
$147.46
Status:
Applied:
Issued:
Permit
Finaled:
Inspector:
Final
Inspection:
Balance Due:
Please take NOTICE that approval of your project includes the "Imposition" of fees, dedications, reservations, or other exactions hereafter
collectively referred to as "fees/exaction." Y~u have 90 days from the date this permit was issued to protest imposition of these
fees/exactions. If you protest them, you must follow the protest procedures set forth in Government Code Section 66020(a), and file the
protest and any other required information with the City Manager for processing in accordance with Carlsbad Municipal Code Section
3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack, review, set aside, void, or annul their
imposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection
fees and capacity changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this
project. NOR DOES IT APPLY to any fees/exactions of which you have previously been given a NOTICE similar to this, or as to which the
statute of limitation has previously otherwise expired.
Closed -Finaled
06/28/2017
07/19/2017
MColl
2/2/2018 9:00:25AM
$0.00
$61.74
$43.22
$41.00
$1.00
$0.50
1635 Faraday Avenue, Carlsbad, CA 92008-7314 I 760-602-2700 I 760-602-8560 I I www.carlsbadca.gov
,HE FOLLOWING APPROVALS REQUIRED PRIOR TO PERMIT ISSUANCE: 0 PLANNING 0 ENGINEERING □BUILDING □FIRE □HEALTH OHAZMATIAPCD
(city of
Carlsbad
Building Permit Application
1635 Faraday Ave., Carlsbad, CA 92008
Ph: 760-602-2719 Fax: 760-602-8558
email: building@carlsbadca.gov
www.carlsbadca.gov
Plan Check No.Qi)R.z.017-\L\L\C\
Est. Value 3.1'"\; • -
JOB ADDRESS
EXISTING USE
APPLICANT NAME
Primary Contact
ADDRESS
-Z,'2, 5" 2-
CITY
PHONE
"1c.,t:, -
DESIGN PROFESSIONAL
ADDRESS
CITY
PHONE
lPROPOSED USE
VPC..,
I GARAGE (SF)
STATE ZIP
DA--'o/LOCR
STATE ZIP
SUITE#/SPACE#/UNIT#
PATIOS (SF)
1,-
I DECKS (SF)
PROPERTY OWNER
ADDRESS
CITY
PHONE
EMAIL
CONTRACTOR BUS. NAME
ADDRESS
CITY
PHONE
• Plan Ck. Deposit
Date I D-2,\>\-17
FIREPLACE
YES0, IAIR CONDITIONING
No□ YES □No □
STATE ZIP
IFAX
STATE ZIP
I FAX
FIRE SPRINKLERS
YES □No□
I FAX
--------
EMAIL EMAIL
I STATE LIC. # STATE LIC.# I CLASS I CITY BUS. LIC.#
(Sec: 7031.5 Business and P_rofess1ons Code: Any City or Coun_ty which requires a permit to construct, alter, improve, demolish or repair any structure, pnor to its issuance, also requires the applicant for such per_mIt to file a signed statement that he is licensed pursuant to the provisions of the Contractor's License LawJChapter 9, comme_nding with Section 7000 of D1v1sion 3 of the B_usiness and Professions Code} or [hat he Is exempt therefrom, and the basis for the alleged exemption. Any v1olat1on of Section 031.5 by any applicant for a permit subJects the applicant to a
cIvII penalty of not more than five hundred dollars {$500)}.
WORKERS' COMPENSATION
Workers' Compensation Declaration: I hereby affirm under penalty of perjury one of the following declarations: D I have and will maintain a certificate of consent to self-insure for workers' compensation as provided by Section 3700 of the Labor Code, for the performance of the work for which this permit is issued D I have and will maintain workers' compensation, as required by Section 3700 of the Labor Code, for the performance of the work for which this permit is issued. My workers' compensation insurance carrier and policy
number are: Insurance Co. ____________________ Policy No. _______________ Expiration Date __________ _
This section need not be completed ~ the permit is for one hundred dollars ($100) or less D Certificate of Exemption: I certify that in the performance of the work for which this permit is issued, I shall not employ any person in any manner so as to become subject to the Workers' Compensation Laws of
California. WARNING: Failure to secure workers' compensation coverage is unlawful, and shall subject an employer to criminal penalties and civil fines up to one hundred thousand dollars (&100,000), ln
addition to the cost of compensation, damages as provided for In Section 3706 of the Labor code, Interest and attorney's fees.
Rf CONTRACTOR SIGNATURE □AGENT DATE -.
OWNER-BUILDEJ? DECLARATION ~-" -
I hereby affirm that I am exempt from Contractor's License Law for the following reason:
I, as owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not intended or offered for sale (Sec. 7044, Business and Professions Ccxle: The Contractor's
License Law does not apply to an owner of property who builds or improves thereon, and who does such work himself or through his own employees, provided that such improvements are not intended or offered for
sale. If, however, the building or improvement is sold within one year of completion, the owner-builder will have the burden of proving that he did not build or improve for the purpose of sale). □
Iii
□
I, as owner of the property, am exclusively contracting with lteensed contractors to construct the project (Sec. 7044, Business and Professions Ccxle: The Contractor's License Law does not apply lo an owner of
property who builds or improves thereon, and contracts for such projects with contractor(s) licensed pursuant to the Contractor's License Law)
I am exempt under Section _____ Business and Professions Code for this reason·
1. I personally plan lo provide the major labor and materials for construction of the proposed property improvement. 0Yes 0No
2. I (have I have not) signed an application for a building permit for the proposed work
3, I have contracted with the following person (firm) to provide the proposed construction (include name address / phone/ contractors' license number):
4. I plan to provide portions of the work, but I have hired the following person to coordinate, supervise and provide the major work (include name I address I phone I contractors' license number):
5. I will provide some of the work, but I have co ed { ired) the following persons to provide the work indicated {include name I address I phone I type of work)
Rf PROPERTY OWNER SIGNATURE □AGENT DATE
/
,COMPLETE THIS SECTIOlll FOR 111~0,lll·RESIDENTIAL BUILDING PERMITS ONLY ~
1 Is the applicant or future building occupant required to submit a business plan, acutely hazardous materials reg1strat1on form or risk management and prevenijon program under Sections 25505, 25533 or 25534 of the
Presley-Tanner Hazardous Substance Account ActJ □ Yes D No
Is the applicant or future building occupant required to obtain a permit from the air pollution control district or air quality management district? 0 Yes □ No
Is the facility to be constructed within 1,000 feet of the outer boundary of a school site? □ Yes □ No
IF ANY OF THE ANSWERS ARE YES, A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR IS MEETING THE REQUIREMENTS OF THE OFFICE OF
EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT.
J certify that I have read the application and state that the above infonnation Is oorrectand that the infonnation on the plans ls accurate. I agree to oomplywlth all Cllyordlnancesand State la~ relating to buildingoonstructlon.
I hereby authorize representative of the City of Carlsbad to enter upon the above mentioned property for inspection purposes. I ALSO AGREE TO SAVE, INDEMNIFY AND KEEP HARMLESS THE CllY OF CARLSBAD
AGAINST ALL LIABILITIES, JUDGMENTS, COSTS AND EXPENSES WHICH MAY IN ANY WAY ACCRUE AGAINST SAID CITY IN CONSEQUENCE OF THE GRANTING OF THIS PERMIT
OSHA: An OSHA permit is required for excavations over 5'0' d and demolition or construction of structures over 3 stories in heght.
EXPIRATION: Every pem1it issued by the Building Official Oer e provisions of this Code shall expire by rimitation and become null and void if the buikling orwori< authorized by such pem1it is not commenced within
180 days from the date of such pennit or if the buildi Olized by such pennit is suspended or abandoned at any time after the worn is commenced for a p of 180 ys (Section 106.4.4 Uniform Building Code)
AS APPLICANT'S SIGNATURE DATE
• STOP: THIS SECTION NOT REQUIRED FOR BUILDING PERMIT ISSUANCE.
Complete the following ONLY if a Certificate of Occupancy will be requested at final inspection.
Fax (760) 602,8560, Email building@carlsbadca,gov or Mail the completed form to City of Carlsbad, Building Division 1635 Faraday Avenue, Cansbad, California 92008.
CO#: (Office Use Only)
CONTACT NAME OCCUPANT NAME
ADDRESS BUILDING ADDRESS
CITY STATE ZIP CITY STATE
Carlsbad CA
PHONE FAX
EMAIL OCCUPANT'S BUS. LIC. No.
DELIVERY OPTIONS
D PICK UP: o CONTACT (Listed above) □ OCCUPANT (Listed above)
o CONTRACTOR (On Pg. 1)
D MAIL TO: □ CONTACT (Listed above) o OCCUPANT (Listed above)
o CONTRACTOR (On Pg. 1)
O MAIL/ FAX TO OTHER: ________________ _
,IS' APPLICANT'S S
□ ASSOCIATED CB#-------------
□ NO CHANGE IN USE/ NO CONSTRUCTION
o CHANGE OF USE/ NO CONSTRUCTION
DATE
ZIP
' ' "'v,s
} PERMIT INSPECTION HISTORY REPORT (CBR2017-1449)
Permit Type: BLOG-Residential Application Dato: 06/2812017 Owner: TRUST ADDAMO FAMILY TRUST
Work Class: Patio Issue Date: 0711912017 Subdivision: CARLSBAD TCT#02-20 LA COSTA
GREENS NEIGHBORHOOD 1.10
Status: Closed -Finaled Expiration Date: 0210712018 Address: 2252 Ivory Pl
Carlsbad, CA 92009-1732
IVR Number: 4675
Scheduled Actual
Date Start Date Inspection Type Inspection No. Inspection Status Primary Inspector Reinspection Complete
07/20/2017 07/20/2017 BLDG-11 029355-2017 Failed Mlchael Collins Reinspection Complete
Foundatlon/Ftg/Pier
s (Rebar)
Checklist Item COMMENTS Passed
BLDG-Building Deficiency No
07/24/2017 07/24/2017 BLDG-11 029538-2017 Passed Michael Collins Complete
Foundatlon/Ftg/Pier
s (Rebar)
Checklist ltem COMMENTS Passed
BLDG-Building Oeficiency Patio only. Yes
08/11/2017 08/11/2017 BLDG-15 031467-2017 Passed Chris Renfro Complete
Roof/ReRoof (Patio)
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Yes
01/26/2018 01/26/2018 BLDG-Final 046970-2018 Failed Tim Frazee Reinspectlon Complete
Inspection
Checklist Item COMMENTS Passed
BLOG-Building Deficiency No
BLDG-Plumbing Final No
BLOG-Mechanical Final No
BLDG-Structural Final No
BLDG-Electrical Final No
02/02/2018 02/02/2018 BLDG-Final 047596-2018 Passed Tim Frazee Complete
Inspection
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Yes
BLDG-Structural Final Yes
February 02, 2018 Page 1 of 1
EsGil Corporation
In <Partners nip witn (jovernment for <Bui{,{ing Safety
DATE: July 19, 2017
JURISDICTION: City of Carlsbad
PLAN CHECK NO.: cbR2017-1449
PROJECT ADDRESS: 2252 Ivory Pl.
SET II
PROJECT NAME: New Patio Cover for Addano Residence
□ APPLICANT
~ JURIS.
□ PLAN REVIEWER
□ FILE
~ The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
D The check list transmitted herewith is for your information. The plans are being held at EsGil
Corporation until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
D The applicant's copy of the check list has been sent to:
~ EsGil Corporation staff did not advise the applicant that the plan check has been completed.
D EsGil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: 0 Telephone#:
Date contacted: (by._J,£ Email:
Mail Telephone Fax In Person
□ REMARKS:
By: Rich Moreno Enclosures:
EsGil Corporation
0 GA 0 EJ 0 MB 0 PC June 13, 2017
9320 Chesapeake Drive, Suite 208 ♦ San Diego, California 92123 ♦ (858) 560-1468 ♦ Fax (858) 560-1576
,
EsGil Corporation
In <Partnersnip witn government for (Bui(aing Safety
DATE: July 7, 2017
JURISDICTION: City of Carlsbad
PLAN CHECK NO.: cbR2017-1449
PROJECT ADDRESS: 2252 Ivory Pl.
SETI
PROJECT NAME: New Patio Cover for Addano Residence
□ _...APPLICANT
_,...el' JURIS.
□ PLAN REVIEWER
□ FILE
D The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
~ The check list transmitted herewith is for your information. The plans are being held at EsGil
Corporation until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
~ The applicant's copy of the check list has been sent to:
Barney Addano
D EsGil Corporation staff did not advise the applicant that the plan check has been completed.
~ EsGil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Barney Addano Telephone#: 760-579-8654
_}late co)1tacted:9i .:J--(by:{)C) Email: barneyA@reylenn.com
t:,Mail ./ ~phon~ Fax In Person
0 RE MAR~ '{y\ .
By: Rich Moreno
EsGil Corporation
D GA D EJ D MB D PC
Enclosures:
June 29, 2017
9320 Chesapeake Drive, Suite 208 ♦ San Diego, California 92123 ♦ (858) 560-1468 ♦ Fax (858) 560-1576
City of Carlsbad cbR201 7-1449
July 7, 2017
PLAN REVIEW CORRECTION LIST
SINGLE FAMILY DWELLINGS AND DUPLEXES
PLAN CHECK NO.: cbR2017-1449
PROJECT ADDRESS: 2252 Ivory Pl.
FLOOR AREA: Patio Cover: 182 sq-ft
REMARKS:
DATE PLANS RECEIVED BY
JURISDICTION: June 28, 2017
DATE INITIAL PLAN REVIEW
COMPLETED: July 7, 2017
FOREWORD (PLEASE READ):
JURISDICTION: City of Carlsbad
STORIES: 1
HEIGHT: 12-ft
DATE PLANS RECEIVED BY
ESGIL CORPORATION: June 29, 2017
PLAN REVIEWER: Rich Moreno
This plan review is limited to the technical requirements contained in the California version of
the International Residential Code, International Building Code, Uniform Plumbing Code,
Uniform Mechanical Code, National Electrical Code and state laws regulating energy
conservation, noise attenuation and access for the disabled. This plan review is based on
regulations enforced by the Building Department. You may have other corrections based on
laws and ordinance by the Planning Department, Engineering Department, Fire Department or
other departments. Clearance from those departments may be required prior to the issuance of
a building permit.
Present California law mandates that construction comply with the 2016 edition of the California
Code of Regulations (Title 24), which adopts the following model codes: 2015 IRC, 2015 IBC,
2015 UPC, 2015 UMC and 2014 NEC.
The above regulations apply, regardless of the code editions adopted by ordinance.
The following items listed need clarification, modification or change. All items must be satisfied
before the plans will be in conformance with the cited codes and regulations. Per Sec. 105.4 of
the 2015 International Building Code, the approval of the plans does not permit the violation of
any state, county or city law.
To speed up the recheck process, please note on this list /or a copy) where each
correction item has been addressed, i.e., plan sheet number, specification section, etc.
Be sure to enclose the marked up list when you submit the revised plans.
City of Carlsbad cbR2017-1449
July 7, 2017
• PLANS
1. Please make all corrections, as requested in the correction list. Submit FOUR new
complete sets of plans for commercial/industrial projects (THREE sets of plans for
residential projects). For expeditious processing, corrected sets can be submitted
in one of two ways:
1. Deliver all corrected sets of plans and calculations/reports directly to the City of
Carlsbad Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760)
602-2700. The City will route the plans to EsGil Corporation and the Carlsbad
Planning, Engineering and Fire Departments.
2. Bring TWO corrected set of plans and calculations/reports to EsGil Corporation,
9320 Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-1468.
Deliver all remaining sets of plans and calculations/reports directly to the City of
Carlsbad Building Department for routing to their Planning, Engineering and Fire
Departments.
NOTE: Plans that are submitted directly to EsGil Corporation only will not be
reviewed by the City Planning, Engineering and Fire Departments until review by
EsGil Corporation is complete.
2. All sheets of plans to once again be signed by the person responsible for their
preparation on re-submittal. (California Business and Professions Code}.
3. Provide a statement on the Title Sheet of the plans stating that this project shall
comply with the 2016 California Residential Code, which adopts the 2015 IRC,
2015 UMC, 2015 UPC and the 2014 NEC. Section R106.1.
4. Exterior walls and projections shall comply with one of the following tables.
Section R302.1. Please review and address the following specific concerns:
a)
Use this table if the building DOES NOT have an automatic fire sprinkler system.
Exterior Wall Element Min. Fire Rating Min. Fire Separation
Distance
Not Allowed N/A <2 feet ~--
Projections (Fire-Resistance Rating) 1-hour on the " 2 feet to 5 feet underside•
~ (Not Fire Rated) 0 hours " 5 feet
5. Specify nail size and spacing for the roof diaphragms on the plans. Table
R602.3(1). Specify plywood and/or particle board thickness, grade and panel
span rating. Table R503.2.1(1)
6. Note roof sheathing proposed on plans.
City of Carlsbad cbR2017-1449
July 7, 2017
• MISCELLANEOUS
7. To speed up the review process, note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet, note or detail number,
calculation page, etc.
8. Please indicate here if any changes have been made to the plans that are not a
result of corrections from this list. If there are other changes, please briefly
describe them and where they are located in the plans.
• Have changes been made to the plans not resulting from this correction list?
Please indicate:
Yes □ No □
9. The jurisdiction has contracted with Esgil Corporation located at 9320
Chesapeake Drive, Suite 208, San Diego, California 92123; telephone number of
858/560-1468, to perform the plan review for your project. If you have any
questions regarding these plan review items, please contact Rich Moreno at
EsGil Corporation. Thank you.
• City of Carlsbad cbR2017-1449
July 7, 2017
[DO NOT PAY -THIS IS NOT AN INVOICE]
VALUATION AND PLAN CHECK FEE
JURISDICTION: City of Carlsbad
PREPARED BY: Rich Moreno
BUILDING ADDRESS: 2252 Ivory Pl.
BUILDING OCCUPANCY: R-3/U
BUILDING AREA Valuation
PORTION (Sq.Ft.) Multiplier
Patio Cover 182 citv est
Air Conditioning
Fire Sprinklers
TOTAL VALUE
Jurisdiction Code cb By Ordinance
Plan Check Fee by Ordinance -----------------~I
Type of Review: Complete Review
D Repetitive Fee --•J Repeats
D Other
0 Hourly
EsGil Fee
Comments:
PLAN CHECK NO.: cbR2017-1449
DATE: July 7, 2017
Reg. VALUE ($)
Mod.
3,084
3,084
$61.371
$39.891
D Structural Only
1-----1,Hr. @ •
$34.371
Sheet 1 of 1
macvalue.doc +
.. ' .
6X6 POST
PER PLANS
cBsa
POST BASE
PER PLANS
...
(fl
II)
II),.._ Wz 2-l) I:
:i~ t-t-
" !::!
TI-IIS ~OJECT SI-IALL COMPL. Y' WITI-I Tl-IE 2016 CALIFOFii!NIA
RESIDENTIAL CODE. ~ICI-I ADOPTS Tl-IE 2015 I~. 201!:i UMC,
2015 UPC ANO Tl-IE 2014 NEC. SECTION Rl0E>.I
• • •
FOOTING PER DTLLU
AT TIE BEAM r::::J® CONDITION OR PER DTL lei
AT ISOLATED FOOTING. -
•4 "U" BAR AT 12"0.C.
w/ ~ TIES AT 8"0.C.
•4 AT 12"0.C. EA. WAY' U.N.O.
POST PEDESTAL CONNECTION
5Cm: NT5 DWG NAMC:TYI' I I I
BARNEY ADDAMO
SHADE STRUCTURE
FRAMING PLAN
NOT TO SCALE