HomeMy WebLinkAbout2285 Cameo Rd; ; CBR2018-2774; Permit(city of
Carlsbad
Residential Permit
Print Date: 02/01/2019 Permit No: CBR2018-2774
Job Address:
Permit Type:
Parcel No;
Valuation:
Occupancy Group:
# Dwelling Units:
Bedrooms:
Project Title:
2285 Cameo Rd
BLDG-Residential
1670802000
$18,604.00
Work Class:
Lot#:
Reference#:
Construction Type:
Bathrooms:
Orig. Plan Check#:
Plan Check#:
Alteration Status:
Applied:
Issued:
Permit
Finaled:
Inspector:
Final
Inspection:
Description: FRAIJO: 400 SF REMODEL OF BEDROOM TO ADD KITCHENETTE// ADD SIDE ENTRY DOOR (NOT INTENDED TO BE
ACCESSORY DWELLING UNIT -NO COOKING)
Owner:
TRUSTFRAIJO FAMILY TRUST 09-18-95
2285 Cameo Rd
BUILDING PERMIT FEE ($2000+)
BUILDING PLAN CHECK FEE (BLDG)
CARLSBAD, CA 92008
ELECTRICAL BLDG RESIDENTIAL NEW/ADDITION/REMODEL
PLUMBING BLDG RESIDENTIAL NEW/ADDITION/REMODEL
SB1473 GREEN BUILDING STATE STANDARDS FEE
STRONG MOTION-RESIDENTIAL
Total Fees: $424.56 Total Payments To Date: $424.56 Balance Due:
Please take NOTICE that approval of your project includes the "Imposition" of fees, dedications, reservations, or other exactions hereafter
collectively referred to as "fees/exaction." You have 90 days from the date this permit was issued to protest imposition of these
fees/exactions. If you protest them, you must follow the protest procedures set forth in Government Code Section 66020(a), and file the
protest and any other required information with the City Manager for processing in accordance with Carlsbad Municipal Code Section
3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack, review, set aside, void, or annul their
imposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection
fees and capacity changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this
project. NOR DOES IT APPLY to any fees/exactions of which you have previously been given a NOTICE similar to this, or as to which the
statute of limitation has previously otherwise expired.
Closed -Finaled
10/11/2018
11/26/2018
Tfraz
2/1/2019 11:30:36AM
$0.00
$194.79
$136.35
$41.00
$49.00
$1.00
$2.42
1635 Faraday Avenue, Carlsbad, CA 92008-7314 I 760-602-2700 I 760-602-8560 f I www.carlsbadca.gov
( City of
Carlsbad
RESIDENTIAL
BUILDING PERMIT
APPLICATION
8-1
Plan Check C$QP..2.0\fo-2774
Est. Value
PC Deposit ----------
Date \0-\\-lf)
Job Address _2-._2-_&::5 _______ .------'~~.........CC..~"""--'-to-~_-+/Tz-,:;;, ..... f---Suitf_Cf:J __ ~ __ APN: ________ _
CT /Project#: __________ Lot#: ____ Fire Sprinklers: yes/ no Air Conditioning: yes/ no
BRIEF DE cR PT10N oF woRK: /LZr/4/LP dre 1"c-,
/M tJ ~ C o 'J
tvlw/)t /Jy-&I f"M. k,fe~"/r I ~ I
0 Addition/New: _____ New SF, ____ Deck SF, ____ Patio SF, ____ Garage SF
Is this to create an Accessory Dwelling Unit? Yes/ No New Fireplace? Yes/ No, if yes how many? __
~emodel: ~ SF of affected area Is the area a conversion or change of use? YesE)
D Pool/Spa: ____ SF Additional Gas or Electrical Features? ____________ _
0 Solar: ___ KW, __ Modules, ___ Mounted, Tilt: Yes/ No, RMA: Yes/ No, Panel Upgrade: Yes/ No,
Battery Yes/ No
D Reroof: ---------------------------------------
Plumbing/Mechanical/Electrical Only: _________________________ _
D Other: ----------------------------------------
DESIGN PROFESSIONAL CONTRACTOR BUSINESS
Name: _________________ _ Name: ____________________ _
Address: _________________ _ Address: __________________ _
City: ________ State: ___ Zip: ____ _ City: ________ State: ___ Zip: ______ _
Phone: _________________ _ Phone: ___________________ _
Email: _________________ _ Email: ____________________ _
Architect State License: ___________ _ State License: ______ Bus. License: ______ _
(Sec. 7031.5 Business and Professions Code: Any City or County which requires a permit to construct, alter, improve, demolish or repair any structure, prior to its
issuance, also requires the applicant for such permit to file a signed statement that he/she is licensed pursuant to the provisions of the Contractor's License Law
{Chapter 9, commending with Section 7000 of Division 3 of the Business and Professions Code} or that he/she is exempt therefrom, and the basis for the alleged
exemption. Any violation of Section 7031.5 by any applicant for a permit subjects the applicant to a civil penalty of not more than five hundred dollars ($500}).
1635 Faraday Ave Carlsbad, CA 92008 Ph: 760-602-2719 Fax: 760-602-8558 Em ail: Building@carlsbadca.gov
B-1 Page 1 of 2 Rev. 06/18
( OPTION A): WORKERS'COMPENSATION DECLARATION:
I hearby affirm under penalty of perjury one of the following declarations:
0 I have and will maintain a certificate of consent to self-insure for workers' compensation provided by Section 3700 of the Labor Code, for the performance of the
work which this permit is issued.
0 I have and will maintain worker's compensation, as required by Section 3700 of the Labor Code, for the performance of the work for which this permit is issued.
My workers' compensation insurance carrier and policy number are: Insurance Company Name: _____________________ _
Policy No. _______________ Expiration Date: __________ _
0 Certificate of Exemption: I certify that in the performance of the work for which this permit is issued, I shall not employ any person in any manner so as to be come
subject to the workers' compensation Laws of California. WARNING: Failure to secure workers compensation coverage is unlawful, and shall subject an employer to
criminal penalties and civil fines up to $100,000.00, in addition the to the cost of compensation, damages as provided for in Section 3706 of the Labor Code,
interest and attorney's fees.
CONTRACTOR SIGNATURE: □AGENT DATE: -----------------------------------
( OPTION B ): OWNER-BUILDER DECLARATION:
I hereby affirm that I am exempt from Contractor's License Law for the following reason:
0 I, as owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not intended or offered for sale (Sec.
7044, Business and Professions Code: The Contractor's License Law does not apply to an owner of property who builds or improves thereon, and who does such work
himself or through his own employees, provided that such improvements are not intended or offered for sale. If, however, the building or improvement is sold within
one year of completion, the owner-builder will have the burden of proving that he did not build or improve for the purpose of sale).
/
0 I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions Code: The
Contractor's License Law does not apply to an owner of property who builds or improves thereon, and contracts for such projects with contractor(s) licensed
pursuant to the Contractor's License Law).
0 I am exempt under Section ________ Business and Professions Code for this reason:
1. I personally plan to provide the major labor and materials for construction of the proposed property improvement. 0 Yes O No
2. I (have/ have not) signed an application for a building permit for the proposed work.
3. I have contracted with the following person (firm) to provide the proposed construction (include name address/ phone/ contractors' license number):
4. I plan to provide portions of the work, but I have hired the following person to coordinate, supervise and provide the major work (include name/ address/ phone/
contractors' license number):
5. I will provide some of the work, but I h4 ntracted (hir e following persons to provide the work indicated (include name/ address/ phone/ type of work):
OWNER SIGNATURE: _/ __ •~------.4--------□AGENT DATE: //~6 -/f
CONSTRUCTION LENDING AGENCY, IF ANY:
I hereby affirm that there is a construction lending agency for the performance of the work this permit is issued (Sec. 3097 (i) Civil Code).
Lender's Name: _____________________ _ Lender's Address: _____________________ _
ONLY COMPLETE THE FOLLOWING SECTION FOR NON-RESIDENTIAL BUILDING PERMITS ONLY:
Is the applicant or future building occupant required to submit a business plan, acutely hazardous materials registration form or risk management and prevention
program under Sections 25505, 25533 or 25534 of the Presley-Tanner Hazardous Substance Account Act? 0 Yes O No
Is the applicant or future building occupant required to obtain a permit from the air pollution control district or air quality management district? 0 Yes O No
Is the facility to be constructed within 1,000 feet of the outer boundary of a school site? 0 Yes O No
IF ANY OF THE ANSWERS ARE YES, A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR IS MEETING THE
REQUIREMENTS OF THE OFFICE OF EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT.
APPLICANT CERTIFICATION:
I certify that I have read the application and state that the above information is correct and that the information on the plans is accurate. I agree to comply with all
City ordinances and State laws relating to building construction.
I hereby authorize representative of the City of carlsbad to enter upon the above mentioned property for inspection purposes. I ALSO AGREE TO SAVE, INDEMNIFY AND KEEP
HARMLESS THE CITY OF CARLSBAD AGAINST ALL LIABILITIES, JUDGMENTS, COSTS AND EXPENSES WHICH MAY IN ANY WAY ACCRUE AGAINST SAID CITY IN CONSEQUENCE OF
THE GRANTING OF THIS PERMIT.OSHA: An OSHA permit is required for excavations over 5'0' deep and demolition or construction of structures over 3 stories in height.
EXPIRATION: Every permit issued by the Building Official under the provisions of this Code shall expire by limitation and become null and void if the building or work authorized
by such permit is not commenced within 180 days from the date of such permit or if the building or work authorized by such permit is suspended or abandoned at any time
APPLICANT SIGNATURE:
after the work is commenced for a period of 180 days (Section 106.4.4 Unif uilding Code).
_:3 DATE: //--<,Z-c;_-/£' ---'=------'------,,,.<----,'--,1--------------
1635 Faraday Ave Carlsbad, CA 92008
B-1
Ph : 760-602-2719 Fax: 760-602-8558
Page 2 of 2
Email: Building@carlsbadca.gov
Rev. 06/18
I • ' ( '
. PERMIT INSPECTION HISTORY REPORT (CBR2018-2774)
Permit Typo: BLDG-Residential Application Date: 10/1 1/2018 Owner: TRUST FRAIJO FAMILY TRUST
09-18-95
Work Class. Alteration Issue Date: 11/26/2018 Subdivision: CHESTNUT HEIGHTS
Status. Closed -Finaled Expiration Date: 07/29/2019 Address: 2285 Cameo Rd
Carlsbad, CA 92008-2759
IVR Number: 14551
Scheduled Actual
Date Start Date Inspection Type Inspection No. Inspection Status Primary Inspector Reinspection Complete
12/04/2018 12/04/2018 BLDG-24 077743-2018 Passed Tim Frazee Complete
Rough/Topout
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Yes
01 /15/2019 01/15/2019 BLDG-84 Rough 08127 5-2019 Passed Tim Frazee Complete
Combo(14,24,34,44)
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Yes
BLDG-14 Yes
Frame-Steel-Bolting-Welding
(Decks)
BLDG-24 Rough-Topout Yes
BLDG-34 Rough Electrical Yes
BLDG-44 Yes
Rough-Ducts-Dampers
01/29/2019 01/29/2019 BLDG-Final 082406-2019 Failed Tim Frazee Reinspection Complete
Inspection
Checklist Item COMMENTS Passed
BLDG-Building Deficiency No
BLDG-Plumbing Final Sink not hooked up, functioning No
BLDG-Structural Final No
BLDG-Electrical Final No
02/01/2019 02/01/2019 BLDG-Final 082938-2019 Passed Tim Frazee Complete
Inspection
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Yes
BLDG-Plumbing Final Sink not hooked up, functioning Yes
BLDG-Structural Final Yes
BLDG-Electrical Final Yes
February 01, 2019 Page 1 of 1
DATE: November 20, 2018
JURISDICTION: Carlsbad
PLAN CHECK#.: CBR2018-2774
PROJECT ADDRESS: 2285 Cameo Dr.
✓• EsG1I
SET: Ill
PROJECT NAME: Interior Remodel for Fraijo Residence
D APPLICANT
D JURIS.
~ The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
0 The plans transmitted herewith will substantially comply with the jurisdiction's
codes when minor deficiencies identified below are resolved and checked by building
department staff.
0 The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
0 The check list transmitted herewith is for your information. The plans are being held at EsGil
until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
0 The applicant's copy of the check list has been sent to:
Mike Fraijo
~ EsGil staff did not advise the applicant that the plan check has been completed.
0 EsGil staff did advise the applicant that the plan check has been completed.
Person contact~d: Mik Fraij¾\\ Telephone#: 760-720-5400
Date contacted: (by~ Email: mikefraijo@gmail.com
Mail Telepho Fax In Person
0 REMARKS:
By: Kat Frankowski
EsGil
Enclosures:
11/14/2018
9320 Chesapeake Drive, Suite 208 ♦ San Diego, California 92123 ♦ (858) 560-1468 ♦ Fax (858) 560-1576
•
DATE: November 7, 2018
JURISDICTION: Carlsbad
PLAN CHECK#.: CBR2018-2774
PROJECT ADDRESS: 2285 Cameo Dr.
✓• EsG1I
A SAFEbuilt Company
SET: II
PROJECT NAME: Interior Remodel for Fraijo Residence
□~LICANT
?'JURIS.
D The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's
codes when minor deficiencies identified below are resolved and checked by building
department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
i;gj The check list transmitted herewith is for your information. The plans are being held at EsGil
until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
i;gj The applicant's copy of the check list has been sent to:
Mike Fraijo
D EsGil staff did not advise the applicant that the plan check has been completed.
i;gj EsGil staff did advise the applicant that the plan check has been completed.
Person contacted: Mike Fraijo Telephone#: 760-720-5400
Date contacted: \ [ -q--(by~ ) Email: mikefraijo@gmail.com
Q.JlllailY Telephone j.. Fax In Person
0 REMARKS:
By: Kat Frankowski
EsGil
11/1/2018
Enclosures:
9320 Chesapeake Drive, Suite 208 ♦ San Diego, California 92123 ♦ (858) 560-1468 ♦ Fax (858) 560-1576
Carlsbad CBR2018-2774
November 7, 2018
PLANS
1. Please make all corrections, as requested in the correction list. Submit FOUR new complete
sets of plans for commercial/industrial projects (THREE sets of plans for residential projects).
For expeditious processing, corrected sets can be submitted in one of two ways:
1. Deliver all corrected sets of plans and calculations/reports directly to the City of Carlsbad
Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760) 602-2700. The City will
route the plans to EsGil and the Carlsbad Planning, Engineering and Fire Departments.
2. Bring TWO corrected set of plans and calculations/reports to EsGil, 9320 Chesapeake Drive,
Suite 208, San Diego, CA 92123, (858) 560-1468. Deliver all remaining sets of plans and
calculations/reports directly to the City of Carlsbad Building Department for routing to their
Planning, Engineering and Fire Departments.
NOTE: Plans that are submitted directly to EsGil only will not be reviewed by the City Planning,
Engineering and Fire Departments until review by EsGil is complete.
2. All sheets of plans must be signed by the person responsible for their preparation. (California
Business and Professions Code).
Will be checked on final
4. Specify on the Title Sheet of the plans the gross floor area of each element of this project,
including dwelling, garage etc. Section R106.2.
Not addressed
5. Provide a scale for each page.
Correct scale is 1/2"=1', please correct on plans.
6. Clearly dimension building setbacks from property lines, street centerlines, and from all
adjacent buildings and structures on the site plan. Section R106.2.
Not addressed
STRUCTURAL
13. Show header size for new exterior door.
Header is undersized per table R602.7(1)
ELECTRICAL
14. Note on the plans that receptacle outlet locations will comply with CEC Article 210.52.
Not addressed
15. Include on the plans the following specifications for electrical devices installed in dwellings:
CEC Article 210 & 406
a) Weather resistant type for receptacles installed in damp or wet locations (outside).
Not addressed
16. A balcony, deck, or porch that is accessible from the interior of the dwelling will require a
minimum of one receptacle outlet. CEC 210.52(E) (3). This receptacle must be GFCI
Carlsbad CBR2018-2774
November 7, 2018
protected.
Not addressed
Residential Energy Lighting Requirements: ES 150.0(k)
18. All installed luminaires shall be high-efficacy in accordance with ES TABLE 150.0-A. Light
sources that are not marked "JA8-2016-E" shall not be installed in enclosed luminaires. ES
150.0(k)
Not addressed
19. In bathrooms, garages, laundry rooms, and utility rooms at least one luminaire shall be
controlled by a vacancy sensor.
Not addressed
20. Dimmers or vacancy sensors shall control all LED style luminaires. Two exceptions: Fixtures
installed in hallways or (closets under 70 square feet).
Not addressed
21. Recessed can light fixtures shall be IC listed, air-tight labeled, and not be equipped with a
standard medium base screw shell lamp holder. ES 150.0(k)
Not addressed
22. SFD outdoor lighting fixtures that are attached to a building are required to be high efficacy, be
manually on/off switch controlled, and have both motion sensor and photocell control. See ES
150.0(k) 3 for additional control options.
Not addressed
PLUMBING
23. Specify on the plans: Water conserving fixtures: New water closets shall use no more than
1.28 gallons of water per flush, kitchen faucets may not exceed 1.8 GPM, lavatories are
limited to 1.2 GPM, and showerheads may not exceed 1.8 GPM of flow. CPC Sections 407,
408,411,412.
Not addressed
24. Specify on the plans whether the existing house was built before or after 1994. For additions
or improvements to a residence built before 1994, note on the plans that existing
"noncompliant" fixtures (toilets that use more than 1.6 gallons of water per flush, urinals that
use more than one gallon of water per flush, showerheads that have a flow capacity of more
than 2.5 gallons of water per minute, and interior faucets that emit more than 2.2 gallons of
water per minute) shall be replaced. Certification of compliance shall be given to the building
inspector prior to final permit approval. California SB407.
Not addressed
25. All domestic hot water piping to have the following minimum insulation installed: ½" pipe (1/2"
insulation);¾" pipe (1" insulation): 1" to 1-½" pipe (1-½" insulation). CPC 609.11 & ES 150.0U)
a) Additionally, the ½" hot water pipe to the kitchen sink, and the cold water pipe within 5'
of the water heater both require 1" minimum insulation. ES 150.OU)
Not addressed
Carlsbad CBR2018-2774
November 7, 2018
MISCELLANEOUS
26. To speed up the review process, note on this list (or a copy) where each correction item has
been addressed, i.e., plan sheet, note or detail number, calculation page, etc.
27. Please indicate here if any changes have been made to the plans that are not a result of
corrections from this list. If there are other changes, please briefly describe them and where
they are located in the plans.
• Have changes been made to the plans not resulting from this correction list? Please
indicate:
Yes □ No □
28. The jurisdiction has contracted with EsGil, located at 9320 Chesapeake Drive, Suite 208, San
Diego, California 92123; telephone number of 858/560-1468, to perform the plan review for
your project. If you have any questions regarding these plan review items, please contact Kat
Frankowski at EsGil. Thank you.
DATE: October 22, 2018
JURISDICTION: Carlsbad
PLAN CHECK#.: CBR2018-2774
PROJECT ADDRESS: 2285 Cameo Dr.
✓• EsG1I
A SAFEbwlt Company
SETI
PROJECT NAME: Interior Remodel for Fraijo Residence
J;J APPLICANT
½t"JURIS.
D The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's codes.
0 The plans transmitted herewith will substantially comply with the jurisdiction's
codes when minor deficiencies identified below are resolved and checked by building
department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
[8'.I The check list transmitted herewith is for your information. The plans are being held at EsGil
until corrected plans are submitted for recheck.
0 The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
[8'.I The applicant's copy of the check list has been sent to:
Mike Fraijo
D EsGil staff did not advise the applicant that the plan check has been completed.
[8'.I EsGil staff did advise the applicant that the plan check has been completed.
□
Person contacted: Mike Fraij<: ~
Date contacted: lo/.;id-l1l( (byt)A ) Email:
eMail ✓Telephone/ Fax In Person
REMARKS:
By: Kat Frankowski
EsGil
10/15/2018
Telephone#: 760-720-5400
mikefraijo@gmail.com
Enclosures:
9320 Chesapeake Drive, Suite 208 ♦ San Diego, California 92123 ♦ (858) 560-1468 ♦ Fax (858) 560-1576
Carlsbad CBR2018-2774
October 22, 2018
PLAN REVIEW CORRECTION LIST
SINGLE FAMILY DWELLINGS AND DUPLEXES
PLAN CHECK#.: CBR2018-2774
PROJECT ADDRESS: 2285 Cameo Dr.
FLOOR AREA:
REMARKS:
DATE PLANS RECEIVED BY
JURISDICTION: 10/11/2018
DATE INITIAL PLAN REVIEW
COMPLETED: October 22, 2018
FOREWORD (PLEASE READ):
JURISDICTION: Carlsbad
STORIES:
HEIGHT:
DATE PLANS RECEIVED BY
ESGIL CORPORATION: 10/15/2018
PLAN REVIEWER: Kat Frankowski
This plan review is limited to the technical requirements contained in the California version of
the International Residential Code, International Building Code, Uniform Plumbing Code,
Uniform Mechanical Code, National Electrical Code and state laws regulating energy
conservation, noise attenuation and access for the disabled. This plan review is based on
regulations enforced by the Building Department. You may have other corrections based on
laws and ordinance by the Planning Department, Engineering Department, Fire Department or
other departments. Clearance from those departments may be required prior to the issuance of
a building permit.
Present California law mandates that construction comply with the 2016 edition of the California
Code of Regulations (Title 24), which adopts the following model codes: 2015 IRC, 2015 IBC,
2015 UPC, 2015 UMC and 2014 NEC.
The above regulations apply, regardless of the code editions adopted by ordinance.
The following items listed need clarification, modification or change. All items must be satisfied
before the plans will be in conformance with the cited codes and regulations. Per Sec. 105.4 of
the 2015 International Building Code, the approval of the plans does not permit the violation of
any state, county or city law.
To speed up the recheck process, please note on this list (or a copy} where each
correction item has been addressed, i.e., plan sheet number, specification section, etc.
Be sure to enclose the marked up list when you submit the revised plans.
Carlsbad CBR2018-2774
October 22, 2018
PLANS
1. Please make all corrections, as requested in the correction list. Submit FOUR new
complete sets of plans for commercial/industrial projects (THREE sets of plans for
residential projects). For expeditious processing, corrected sets can be submitted in one of
two ways:
1. Deliver all corrected sets of plans and calculations/reports directly to the City of
Carlsbad Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760) 602-2700.
The City will route the plans to EsGil and the Carlsbad Planning, Engineering and Fire
Departments.
2. Bring TWO corrected set of plans and calculations/reports to EsGil, 9320 Chesapeake
Drive, Suite 208, San Diego, CA 92123, (858) 560-1468. Deliver all remaining sets of
plans and calculations/reports directly to the City of Carlsbad Building Department for
routing to their Planning, Engineering and Fire Departments.
NOTE: Plans that are submitted directly to EsGil only will not be reviewed by the City
Planning, Engineering and Fire Departments until review by EsGil is complete.
2. All sheets of plans must be signed by the person responsible for their preparation.
(California Business and Professions Code).
3. Indicate on the Title Sheet of the plans the name of the legal owner and name of the
person responsible for the preparation of the plans. Section R106.1.1.
4. Specify on the Title Sheet of the plans the gross floor area of each element of this
project, including dwelling, garage etc. Section R106.2.
5. Provide a scale for each page.
6. Clearly dimension building setbacks from property lines, street centerlines, and from all
adjacent buildings and structures on the site plan. Section R106.2.
7. Provide a legend for all symbols shown on plans.
FIRE PROTECTION
8. Show locations of permanently wired smoke alarms with battery backup, per Section
R314:
a) Inside each bedroom.
b) Outside each separate sleeping area in the immediate vicinity of the bedrooms.
c) On each story, including basements.
d) Such smoke alarm locations shall comply with the following:
i) They shall be not less than 3' from the door opening of a bathroom.
ii) They shall be at least 20' from a cooking appliance.
iii) They shall be at least 3' from supply registers of heating/cooling systems.
iv) They shall be at least 3' from the tip of the blade of a ceiling-mounted fan.
Carlsbad CBR2018-2774
October 22, 2018
• NOTE: When more than one smoke alarm is required to be installed, the alarm
devices shall be interconnected in such a manner that the actuation of one alarm will
activate all of the alarms in the unit.
9. In existing buildings, when alterations, repairs or additions requiring a permit occur (or
when one or more sleeping rooms are added), the dwelling unit shall be provided with
smoke alarms located as required for new dwellings; the smoke alarms shall be
interconnected and hard wired. Exception: Smoke alarms in existing areas need not be
interconnected and hard wired where the alterations or repairs do not result in the
removal of interior wall or ceiling finishes exposing the structure, unless there is an attic,
crawl space, or basement available which could provide access for hard wiring and
interconnection without the removal of interior finishes. Section R314.8.1.
10. In dwelling units within which fuel-burning appliances are installed (and in dwelling units
having attached garages), show the locations of permanently wired carbon monoxide
alarms with battery backup, per Section R315:
a) Outside each separate sleeping area in the immediate vicinity of the bedrooms.
b) On each story, including basements.
• NOTE: When more than one carbon monoxide alarm is required to be installed, the
alarm devices shall be interconnected in such a manner that the actuation of one
alarm will activate all of the alarms in the unit.
11. When alterations, repairs or additions are proposed for dwelling units within which fuel-
burning appliances are installed (and in dwelling units having attached garages), the
dwelling unit shall be provided with carbon monoxide alarms located as required for
new dwellings; the carbon monoxide alarms shall be interconnected and hard wired.
Exception: Carbon monoxide alarms in existing areas need not be interconnected and
hard wired where the alterations or repairs do not result in the removal of interior wall or
ceiling finishes exposing the structure, unless there is an attic, crawl space, or basement
available which could provide access for hard wiring and interconnection without the
removal of interior finishes. Section R315.2.
EXITS, STAIRWAYS, AND RAILINGS
12. Show landings at exterior doors. There shall be a landing or floor on each side of each
exterior door. The width of each landing shall not be less than the door served and have
a minimum or 36-inches measured in the direction of travel. Exterior landings shall be
permitted to have a slope not to exceed ¼-inch per foot. Landings or finished floors shall
not be more than 1.5 inches lower than the top of the threshold for outward swinging
exterior doors or 7.75" for doors that do not swing outwards. R311.3.
STRUCTURAL
13. Show header size for new exterior door.
Carlsbad CBR2018-2774
October 22, 2018
ELECTRICAL
14. Note on the plans that receptacle outlet locations will comply with CEC Article 210.52.
15. Include on the plans the following specifications for electrical devices installed in
dwellings: CEC Article 210 & 406
a)
b)
c)
d)
Tamper resistant receptacles for all locations described in 210.52 (i.e., all
receptacles in a dwelling).
Weather resistant type for receptacles installed in damp or wet locations (outside).
Arc-fault protection for all outlets (not just receptacles) located in rooms described
in NEC 210.12(A): Kitchens, laundry areas, family, living, bedrooms, dining,
halls, etc.
GFCI protected outlets for locations described in NEC 210.8(A): Laundry areas,
kitchen dishwashers, kitchens, garages, bathrooms, outdoors, within 6' of a sink,
etc.
16. A balcony, deck, or porch that is accessible from the interior of the dwelling will require a
minimum of one receptacle outlet. CEC 210.52(E) (3). This receptacle must be GFCI
protected.
17. Show at least one wall switch-controlled lighting outlet to be installed in every habitable
room; in bathrooms, hallways, stairways, attached garages, and detached garages with
electric power; and at the exterior side of outdoor entrances or exits. At interior
stairways show 3-way switching for lighting outlets at each floor level where there are six
or more steps. CEC Article 210.70(A).
Residential Energy Lighting Requirements: ES 150.0(k)
18. All installed luminaires shall be high-efficacy in accordance with ES TABLE 150.0-A.
Light sources that are not marked "JAB-2016-E" shall not be installed in enclosed
luminaires. ES 150.0(k)
19. In bathrooms, garages, laundry rooms, and utility rooms at least one luminaire shall be
controlled by a vacancy sensor.
20. Dimmers or vacancy sensors shall control all LED style luminaires. Two exceptions:
Fixtures installed in hallways or (closets under 70 square feet).
21. Recessed can light fixtures shall be IC listed, air-tight labeled, and not be equipped with
a standard medium base screw shell lamp holder. ES 150.0(k)
22. SFD outdoor lighting fixtures that are attached to a building are required to be high
efficacy, be manually on/off switch controlled, and have both motion sensor and
photocell control. See ES 150.0(k) 3 for additional control options.
PLUMBING
23. Specify on the plans: Water conserving fixtures: New water closets shall use no more
than 1.28 gallons of water per flush, kitchen faucets may not exceed 1.8 GPM, lavatories
·Carlsbad CBR2018-2774
October 22, 2018
are limited to 1.2 GPM, and showerheads may not exceed 1.8 GPM of flow. CPC
Sections 407,408,411,412.
24. Specify on the plans whether the existing house was built before or after 1994. For
additions or improvements to a residence built before 1994, note on the plans that
existing "noncompliant" fixtures (toilets that use more than 1.6 gallons of water per flush,
urinals that use more than one gallon of water per flush, showerheads that have a flow
capacity of more than 2.5 gallons of water per minute, and interior faucets that emit more
than 2.2 gallons of water per minute) shall be replaced. Certification of compliance shall
be given to the building inspector prior to final permit approval. California SB407.
25. All domestic hot water piping to have the following minimum insulation installed: ½" pipe
(1/2" insulation);¾" pipe (1" insulation); 1" to 1-½" pipe (1-½" insulation). CPC 609.11 &
ES 150.00)
a) Additionally, the ½" hot water pipe to the kitchen sink, and the cold water pipe
within 5' of the water heater both require 1" minimum insulation. ES 150.00)
MISCELLANEOUS
26. To speed up the review process, note on this list (or a copy) where each correction item
has been addressed, i.e., plan sheet, note or detail number, calculation page, etc.
27. Please indicate here if any changes have been made to the plans that are not a result of
corrections from this list. If there are other changes, please briefly describe them and
where they are located in the plans.
• Have changes been made to the plans not resulting from this correction list? Please
indicate:
Yes □ No □
28. The jurisdiction has contracted with EsGil, located at 9320 Chesapeake Drive, Suite 208,
San Diego, California 92123; telephone number of 858/560-1468, to perform the plan
review for your project. If you have any questions regarding these plan review items,
please contact Kat Frankowski at EsGil. Thank you.
. (!arl:sbad CBR2018-2774
October 22, 2018
[DO NOT PAY -THIS IS NOT AN INVOICE]
VALUATION AND PLAN CHECK FEE
JURISDICTION: Carlsbad
PREPARED BY: Kat Frankowski
BUILDING ADDRESS: 2285 Cameo Dr.
BUILDING OCCUPANCY: R-3
BUILDING AREA Valuation
PORTION ( Sq. Ft.) Multiplier
Air Conditioning
Fire Sprinklers
TOTAL VALUE
Jurisdiction Code #N/A
1997 UBC Buildin Permit Fee g •
1997 UBC Plan Check Fee
Type of Review:
D Repetitive Fee
.. ~ Repeats
* Based on hourly rate
Comments:
□ Complete Review
□ Other
Hourly □ EsGII Fee
PLAN CHECK#.: CBR2018-2774
DATE: October 22, 2018
Reg. VALUE ($)
Mod.
D Structural Only
11Hr.@•
~=====$=9=0-=0~0 $90.001
Sheet 1 of 1