HomeMy WebLinkAbout2285 RUTHERFORD RD; ; CB013136; Permit\
... -. .,,-._
City of Carlsbad
1635 Faraday Av Carlsbad, CA 92008
Commercial/Industrial Permit Permit No: CB013136
Building Inspection Request Line (76_0) 602-2725
Job Address: 2285 RUTHERFORD RD CBAD
Permit Type: Tl Sub Type: COMM
0
NEW
Parcel No: 2120620800 Lot#: Status: ISSUED
Valuation: $22,350.00 Construction Type: Applied: 10/01/2001
Occupancy Group: Reference #: Entered By: JM
Project Title: CALLAWAY GOLF-Tl 745 Plan Approved: 11/01/2001
Applicant:
SMITH CONS.ULT .,
12220 EL CAMINO REAL
SAN DIEGO CA 92130
858-793-4787
Total Fees: $461.34
Building Permit
Add'I Building Permit Fee
Plan Check
Add'I Plan Check Fee
Plan Check Discount
Strong Motion Fee
Park Fee
LFM Fee
Bridge Fee
BTD#2 Fee
BTD #3 Fee
Renewal Fee
Add'I Renewal Fee
Other Building Fee
Pot. Water Con. Fee
Meter Size
Add'I Pot. Water Con. Fee
Reel. Water Con; Fee
Issued: 11/02/2001
Owner:
Inspect Ar9Jb06 11/02/01 0002 Ol.
CALLAWAY GOLF CO
2285 RUTHERFORD RD
CARLSBAD CA 92008
CGP
TotarPayments To Date: $129.86 Bal9-nce Due: $331.48
$199.79
$0.00
$129.86
$0.00
$0.00
$4.69
$0.00
$0.0d
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
Meter Size
Add'I Reel. Water Con. Fee
Meter Fee
SDCWAFee
CFO Payoff Fee
PFF
PFF (CFO ·Fund)
License Tax
License Tax (CFD Fund)
Traffic Impact Fee
Traffic Impact (CFD Fund)
PLUMBING TOTAL
ELECTRICAL TOTAL
MECHANICAL TOTAL
Master Drainage Fee
$ewer Fee
Redev Parking Fee
Additional Fees
TOTAL PERMIT FEES
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$34.00
$60.00
$33.00
$0.00
$0.00
$0.00
$0.00
$461.34
FINAL APPROVAL
Date: /:i./i~ I Clearance: _____ _
NOTICE: Please take NOTICE that approval of your project includes the "Imposition" of fees, dedications, reservations, or other exactions hereafter collectively
referred to as "fees/exactions.• You have 90 days from the date this permit was issued to protest imposition of these fees/exactions. If you protest them, you must
follow the protest procedures set forth in Government Code Section 66020(a), and file the protest and any other required information with the City Manager for
processing in accordance with Carlsbad Municipal Code Section 3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack,
review, set aside, void, or annul their imposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection fees and capactiy
changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this project. NOR DOES IT APPLY to any
fees/exactions of which ou have reviousl beer\ iven a NOTICE similar to this or as to which the statute of limitations has reviousl otherwise ex ired.
33.1-48
: ; \\ io \~ C bS A ~hi-kds, Inc._ .
· PERMIT APPLICATION . '
CITY OF CARLSBAD BUILDING DEPARTMENT
1635 Faraday Ave., Carlsbad, CA 92008
FOR OFFICE USE O~~
PLAN CHECK No.U::x:J/3!3t
·EST. VAL. ~ 5, 5" 0 .
Plan Ck. Depos / 2). ,
Validated By ___ ,-s.--=-~---,,,,._---,---
Date __ -'--____ ...J.£!.IQ!:..-~~-+---
1228 10/()1/01 0002 01 02. CGP 129-86
Lot No. Subdivision Name/Number Phase No. TotaJ # of units
· Name ....,,..,...,.,._,......, Address City State/Zip, Telephone # Fax #
!3:,';:.. ABPLICAf,i't /;P,·,contractcir '. r, Agent .for-Contrar.tor. -:-:l'."""'f'io.wniir"7'~-4jlent•forQwnilr · ,-': -.·""·.7 S:::·TRT'~'..)";~-::._yr;f:,::Th~)~l:IJ.'< i ':f}J-:~_;z-,,IJ"} .-~--... ·""-·"""' ·--i.:4 ......... --.. ., .... ,1,;/J .. " ........... ,.,. .......... 1:.-J_\...."""""";(!!,f'~~,=-··· """'""'"-•• -··=· .. --1-·----"=--···"-· ·rr "1177' 17~'-'l"rvr
Name · Address State/Zi './ 7J
!~'?eRQRER:tr;owNat .. • •. :·. •· ':'· ·: •. , ..... •· ·
Name -=== Address
[~e;:_01tnmQI9-~.\:::..G9J'-:'le~NX J\IAilJl:~.-.. : .,::_:;.:::.~:;~::·.~:~·: :. :: · ·
City S.tate/;!:ip Telephone#
(Sec. 7031.5 Business and Professions Code: Any City or County which requires a permino construct, alter, impr9ve, demolish or repair any structure, prior to its
issuance, also requires the applicant for such permit to file a signed statement that 'he is licensed· pursuant to the provisions of the Contractor's License Law
[Chapter 9, commending with Section 7000 of Division 3 of the Business and Professions Code) or that he is exempt therefrom, and the basis for the alleged
ex~,ptioh. ny ~lation of Section 7031.5 by any aP,plicant for a permit subjects the applicant to a civilJ)elialty of not more than five hundred dollars [$5001).
6 0 -{ t:::d. ----. • ,L . . f; 9t..~ J' s-, -
Telephone Designer Name '/I ( S~Zip
_sta~~nse #_, __ (}d!J}{.~~ '"" .---· -·--· -,c· •. -·--~·-----,.-,-~~---~ '"""~--r~.-· tJtJ, ... 7:"t~{~"7ZI/J. ,;:{tll~, L6 ... WJ)RK§UV>COMlfENS'A'l"ION4 · · : ,. • · .... ~ .... __ . · . , . · _ · .. : · ... _.;, ~· , .• · . · .• ··•· _.-. · · .. · ·Y:>" 1_:;_,.,..,, L..:. ,. ·Ks .. -::::t· -, y· · · <b:<: .. '--" ·1...:,, · ,, .... J
Workers' Compensation Declaration: I ·hereby affirm under penalty of perjury one of the following declarations:
0 I have and will maintain a certificate of consent to self-insure for workers' compensation as provided by Section 3700 of the Labor Code, for the performance
of the work for which this permit is issued.
0 I have and· will maintain workers' compensation, as required by Section 3700 of the L11bor Code, for the performance of the work for which this permit is
issued. My worker's compensation insurance carrier and policy number are:
Insurance Company ______ ~--~----------Policy No.____________ Expiration Date _______ _
(THIS SECTION NEED NOT BE COMPLETED IF THE PERMIT IS FOR ONE HUNDRED DOLLARS ($100) OR LESS)
0 CERTIFICATE OF EXEMPTION: I certify that in the performance of the work for which this permit is issued, J. shall not employ any person in any manner so as
tg become subject·to the Workers' Compensation Laws of California.
WARNING: Failure to secure workers' compensation coverage is unlawful, and shall subject an employer' 10 criminal penalties and civil fjnes up to one hundred
thousand dollars '($100,000), in addition to the cost of compensation, damages as provided for in Section 3706 of the Labor code, interest and atton,~y's fees.
SIGNATURE·------------------------..,,-,-----DATE ___ __,--~--iJ·~: ::ow111eR::su1i?oeiG.olfut:AeAtioN'~ ... :.;· . : , , _: . . . .. ,. ·.:7 ~: -::·.~ ... · .• :c··,. :::: '~ ' .. ·; ' :::,~;;:y;,~.~,§:: ·::·:z~~ · .::~::>.--::yy ;:i',"'sl:.::':5~':f::: ": :1;;:{ \f : : ~i
I hereby affirm that I am exempt from the Contractor's License Law for the following reason:
0 I, as· owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not intended or offered for sale
(Sec. 7044, Business and Professions Code: The Contractor's License Law does not apply to an owner of property who builds ,or improves thereon, and who does
such work himself or through his own employees, provided that such improvements are not intended or of.fared for sale. If, however, the building or improvement is
sold within·one year of completion, the owner-builder will have the burden of proving that he did not build or improve for, the purpose of sale).
0 I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions Code: The
Contractor's License Law does not apply to an owner of property who builds or improves thereon, and contracts for such projects with contractor(s) licensed
pursuant to the·Contractor's License Law).
0 I am exempt under Section ______ Business and Professions Code for this reason:
1. I personally plan to provide the major labor and materials for construction of the proposed property improvement. 0 YES ONO
2. I (have / have not) signed an application for a building permit for the proposed work.
· 3. I have contracted with the following person (firm) to provide the proposed construction (include name I address / phone number / contractors license .number):
4.· I plan to provide portions of the work, but I have hired the following person to coordinate, supervise.and provide the major work (include name /address/ phone
number/ contractors license number): _________________ --'-----------------------------
5. I will provide some of the work, but I have contracted (hired) the following persons to provide the work indicated (include name / address / phone number / type
of work): _____________________________________ --'-------------------
PROPERTY OWNER SIGNATURE _______________ --,-,--------,---.DATE~· ________ _
igm;ie!;.;!Jf;it1is'.se_q[(Q~fQfi'..tYQ&'i€S}p~M~-'lt·Awi1.01NQJ{~RNlli~:'.:qt{Ci:t::~·-;~ '.:.::~=~::;:'.:::::~"";:sX~::.::::::r2'!:2I::::~·tt:~?::(::~~:-~::2::-::·:~iit}
Is the applicant or future building occupant required to submit a business plan, acutely hazardous materials registration form or risk management and prevention
program under Sections 25505, 25533 or 25534 of the Presley-Tanner Hazardous Substance Account Act? 0 YES O NO
: Is the applicant or future building occupant required to obtain a permit from the air pollution. control district or air quality management district? 0 YES O NO
Is the facility to be constructed within 1,000 feet of the outer boundary of a school site? tJ YES O NO
IF ANY OF THE ANSWERS ARE YES, A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR IS MEETING THE
REQUIREMENTS-OF THE ,C>FFICE OF EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRl<:;T.
:s1;>s<tQNS;TRUCT:iON;feNDJNG-AGl:NC,Y _;, '.-:· •.• · ·,,·. ·--·~·· · •. --:·c,--.,,,-""''7:'.'.'f"'""'""".'.-·-,,,.,.,.~,_,,"'~"''V7'J:''"""":"'"'7"':7'7'7;\C"";"';-,"':7;rw:,:z""":··"7'""\""."''.,,,,..:,,:·
I hereby affirm that there is a construction lending agency for the performance of the work for which this permit is issued (Sec. 3097(i) Civil Code).
I certify that I have read the· application and i;tate that the above information is ,correct and that the information on the plans is accurate. I agree to comply with all
City ordinances and State laws relating. tb building construction. I hereby authorize representatives of the Citt of Carlsbad to .enter upon the above mentioned
property for inspection .purposes. I ALSO AGREE TO SAVE, INDEMNIFY AND KEEP HARMLESS THE CITY OF CARLSBAD AGAINST ALL LIABILITIES,
JUDGMENTS, COSTS AND EXPENSES WHICH MAY IN ANY WAY ACCRUE AGAINST SAID CITY IN CONSEQUENCE OF THE GRANTING OF THIS PERMIT.
OSHA: An OSHA permit is required for excavations over 5'0" deep and demolition or construction of structures over 3 stories in height.
EXPIRATION: Every permit is by the building Officia under the provisions of this Code shall expire by limitation and become null an<:l void if the building or work
authorized by such permit is n c ithin from the date of uch permit or if the building or work authorized by such i:?ermit is suspended or abandoned
at any time after the work is , Sectio 06.4.4 Uniform Building Code). DATE ~) k. ~ ?J
APPLICANT'S SIGNATURE f--lM:.HP'l:~~.,,_,~~Y,fbl~'-F-------------~--,..,.'tfl/.---~r--i'/~--------
WHITE F YELLOW: Applicant PINK: Finance
City of Carlsbad Bldg Inspection Request
Permit# CB013136
Title: CALLAWAY GOLF -Tl 745
Description:
For: 12/06/2001
Type: Tl Sub Type: COMM
Job Address: 2285 RUTHERFORD RD
Suite: Lot
Location:
APPLICANT SMITH CONSULT
owner: CALLAWAY GOLF co
Remarks:
Total Time:
Cb Description
0
Act Comment
lnsp·ector Assignment: TP ---
Phone: 7608012426
Inspector. g
Requested By: KURT
Entered By: KAREN
19 Final Structural .H!__ __ ~------
29 Final Plumbing
39 Final Electrical
49 Final Mechanical
t---"----------'-----'---
--Associated PCRs
lns12ection Histo[Y
Date Description Act lnsp Comments
11/19/2001 89 Fi11al Combo NR TP NEED PLNS, CARD, FIRE APPVL
11/19/2001 89 Final Combo NR TP
11/07/2001 17 Interior Lath/Drywall AP TP
11/07/2001 24 Rough/Topout AP TP
11/05/2001 14 Frame/Steel/Bolting/Welding AP TP
11/05/2001 34 Rough Electric AP TP
CIIY or Carlsbad
· Flnal Bulldlng Inspection
Dept: Building Engineering Planning CMWD St Lite {FifO
Plan Check #:
Permit#: CB013136
Project Name: CALLAWAY GOLF -Tl 745
Address: 2285 RUTHERFORD RD
Contact Person: KURT Phone: 7608012426
Water Dist: CA Sewer Dist: CA
Date: 11/19/2001
Permit Type: Tl
Sub Type: COMM
Lot: 0
~~:~:~~~~;; ... :;;~ ......... ~:;: ........ .._ .. ;i:·1 .................................................................... ..
By: ~ V_d _ Inspected: ¼:J-1/11/ Approved: ~isapproved: __
Inspected Date
By: Inspected: Approved: Disapproved: __
Inspected Date
By: Inspected: Approved:_ Disapproved: __
...
••••II I I~ I I I I II Ill II 1111 ':I I I I I I II I II Ill II II I I II I I I II II 11111 II I I II II 11 I I I~ II 111111 I JI II IJ 11111111111I1111 I I I 111111 I 111 I I I 11 I I I I I Ill 11 I I I II I I I I I I I I I I 11II11111
Comments: __________________________________ _
EsGil Corporation
·'
In Partnership with Government for Buil<,ling Safety
DATE: 10/31/01
JURISDICTION: City of Carlsbad
PLAN CHECK NO.: 01-3136
PROJECT ADDRESS: 2285 Rutherford Rd
SET: II
PROJECT NAME: Callaway Golf Building 1-UV and Vibe Room
D~ANT
~ d PLAN REVIEWER
D FILE
[8J The plans transmitted herewith have been corrected. where necessary and substantially comply
with the jurisdiction's building codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checke.d by building department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected ·and resubmitted for a complete recheck.
D The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
D The applicant's copy·of the check list has been sent to:
~ Esgil Corporation staff did not advise the applicant that the plan check has been completed.
D Esgil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Telephone#:
Date contacted: (by: ) ·Fax#:
Mail Telephone Fax In Person
D REMARKS:
By: Doug Moody Enclosures:
Esgil Corporation
D GA D MB D EJ D PC LOG trnsmtl.dot
9320 Chesapeake Drive, Suite 208 + San Diego, California 92123 + (858) 560-1468 + Fax (858) 560-1576
r EsGil Corporation
In Partnership with Government for Building Safety
DATE: 10/15/01
JURISDICTION: City of Carlsbad
PLAN CHECK NO.: 0.1-3136 SET:I
PROJECT ADDRESS: 2285 Rutherford Rd
PROJECT NAME: Callaway Golf Building 1 -UV and Vibe Room
D The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checke.d by building department staff.
D The plans transmitted herewith have .significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
~ The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
~ The applicant's copy of the check list has been sent to:
Andrew Tarango
12·220 El Camino Real Suite 200, San Diego, CA 92130
D Esgil Corporation staff did not advise the applicant that the plan check has been completed.
k8:I Esgil Corporation staff did advise the applicant that the plan check has be7h completed.
Person contacted: Andrew Tarango Telephone#: 858-793-4777
Date contacted: Io f, {p /o r(by: f-A;x) Fax #: 858-793-4787
Mail ~elephone
D REMARKS:
Fax./ In Person
By: D9ug Moody
Esgil Corporation· -
D GA O MB D EJ D PC
Enclosures:
10/4/01 trnsmtl.dot
9320 Chesapeake Drive, Suite 208 + San Diego, California 92123 + (858) 560-1468 + Fax (858) 560-1576
r ~ City of Carlsbad 01-3136
,. 10/15/01
PLAN REVIEW CORRECTION-LIST
TENANT IMPROVEMENTS
· PLAN CHECK NO.: 01-3136
OCCUPANCY: F2?
TYPE OF CONSTRUCTION: Unknown
ALLOWABLE FLOOR AREA:
SPRINKLERS?: Unknown
REMARKS:
DATE PLANS RECEIVED BY
JURISDICTION: 10/1/01
DATE INITIAL PLAN REVIEW
COMPLETED: 10/ 15/01
FOREWORD (PLEASE READ):
JURISDICTION: City of Carlsbad
USE:Unknown
ACTUAL AREA: 7 45
STORIES:
HEIGHT:
OCCUPANTLOAD:Unknown
DATE PLANS RECEIVED BY
ESGIL CORPORATION: 10/4/01
PLAN REVIEWER: Doug Moody
This plan review is limited to the technical requirements contained in the Uniform Building Code,
Uniform Plumbing Code, Uniform Mechanical Code, National Electrical Code and state laws
regulating energy conservation, noise attenuation and access for the disabled. This plan review
is based on regulations enforced by the Building Department. You may have other corrections
based on laws and ordinances enforced by the Planning Department, Engineering Department,
Fire Department or other departments. Clearance from those -departments may be required
prior to the issuance of a building permit.
Code sections cited are based on the 1997 UBC.
The following items listed need clarification, modification or change. All items must be satisfied
before the plans will be in conformance with the cited codes and regulations. Per Sec. 106.4.3,
1997 Uniform Building Code, the approval of the plans does not permit the violation of any
state, county or city law.
To speed up the recheck process, please note on .this list (or a copy) where each
·correction item has been addressed, i.e., plan sheet number, specification section, etc.
Be sure to enclose the marked_up list when you submit the revised plans.
TENANT IMPROVEMENTS WITHOUT SPECIFIC ENERGY DATA OR POLICY SUPPLEMENTS (1997UBC) tiforw.dot
City of Carlsbad 01-3136
10/15/01
Please make all corrections on the original tracings, as requested in the correction
list. Submit three sets of plans for commercial/industrial projects (two sets of plans
for residential projects). For expeditious processing, corrected sets can be
submitted in one of two ways:
1. Deliver all corrected sets of plans and calculations/reports directly to the City of
Carlsbad Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760)
602-2700. The City will route the plans to EsGil Corporation and the Carlsbad
Planning, Engineering and Fire Departments.
2. Bring one corrected set of plans and calculations/reports to EsGil Corporation,
9320 Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-1468.
Deliver all remaining sets of plans and calculations/reports directly to the City of
Carlsbad Building Department for routing to their Planning, Engineering and Fire
Departments.
NOTE: Plans that are submitted directly to EsGil Corporation only will not be
reviewed by the City Planning, Engineering and Fire Departments until review by
EsGil Corporation is complete. ·
1. Please revise the Title Sheet of the plans to state that this project shall comply
with the 1998 edition of the California Building Code (Title 24 ), which adopts the
1997 UBC, UMC and UPC and the 1996 NEC.
2. A complete description of the activities and processes that will occur in this
tenant space should be provided. A listing of all hazardous materials should be
included. The materials listing should be stated in a form thafwould make
classification in Tables 3-0 and 3-E possible. The building official may require a
technical report to identify and develop methods of protection from hazardous
materials. Section 307.1.6. It appears the UV room contains a paint cabinet?
Clearly indicate all hazardous materials.
3. In Groups B, F, M, and S Occupancies, or portions thereof, where Class I, II, or
Ill-A liquids are used (in any amount), mechanical exhaust shall be provided
sufficient to produce six air changes per hour. Such mechanical exhaust shall be
taken from a point at or near the floor. UBC, Section 1202.2.2.
4. Please specify on the plans the following information for the pre-fab UV room per
Section 106.3.3
a) Manufacturers name
b) Product name/number
c) ICBO approval number, or equal,
·5. Please provide the manufacturers insta.llation recommendation for the UV room
and Vibe room equipment.
6. Please revise the plans to show the method of providing outside air to the
occupants of the UV room.
7. Please provide a panel schedule and load calculations for panel PE9A.
,~ ' . City of Carlsbad 01~3136
10/15/01·
8. Please -revise the panel schedules to show the lighting for the UV and Vibe
rooms.
9. Please provide the required energy compliance forms for the new lighting in the
UV and Vibe rooms.
10. · Please revise the panel schedules to show power for the automatic door.
11. Please provide the required energy compliance forms for the new HVAC system
to be used in both rooms.
12. Please note on the plans "AC.Cable is not allowed. NM cable is restricted
(without City approval) to one and two family dwellings. Note on plans that an
equipment ground conductor 'is to be installed in all flexible conduits". Per City of
Carlsbad.
To speed up the review process, note on this list (or a copy) where each
correction item has been addre$sed, i.e., plan sheet, note or detail number,
calculation page, etc.
Please indicate here if any changes have been. made to the plans that are not a
result of corrections from this list. If there are other changes, please briefly
describe them and where they are located in the plans.
Have changes been made to the plans not resulting from this correction list?
Please indicate:
Yes D No D
The jurisdiction has contracted with Esgil Corporation located at 9320
Chesapeake Drive, Suite 208, San Diego, California 92123; telephone number of
858/560-1468, to perform the plan review for your project. If you have any
questions regarding these plan review items, please contact Doug Moody at
Esgil Corporation. Thank you.
, City of Carlsbad 01-3136
f.0/15/01
VALUATION AND PLAN CHECK FEE
JURISDICTION: City of Carlsbad
PREPARED BY: l>oug Moody
PLAN CHECK NO.: 01.-3136
DATE: 10/15/_0l
BUILDING ADDRESS: 2285 Rutherford Rd
BUILDING OCCUPANCY: F2? TYPE OP CONSTRUCTION: Unknown
-BUILDING AREA Valuation Reg. VALUE
PORTION ( Sq. Ft.) Multiplier Mod.
Tl 745 City Valuation
Air Conditioning
Fire Sprinklers
TOTAL VALUE
Jurisdiction Code cb By Ordinance
1994 UBC Building Permit Fee / •-!
1994 UBC Plan Check Fee I ,.. I
Type of Review: 0 Complete Revfow D Structural Only
D Repetitive Fee ~ Repeats-
Comments:
D Other
D Hourly _· I Hour *
Esgil Plan Review Fee
($)
22,350
22,350
$199.79!
$129.861
$111.881
Sheet 1 of 1
macvalue.doc
.,
PLANNING/ENGINEERING APPROVALS
PERMIT NUMBER CB O l )./) ~ DATE /0 5 -0/
ADDRESS ;J~ 5 dL kH
"RESIDENTIAL
RESIDENTIAL ADDITION MINOR
( < $10,000.00}
OTHER
CARLSBAD COMPANY STO~ES
VILLACE. FAIRE
COMPLETE OFFICE BUILDING
-------------------
PLANNER DATE /0., J---0/
------
DATE ;o/4,z/ 2e9q
Docs/Mlsfonns/Planning Engineering ApprovalS
Carlsbad Fire Department 013136
· 1635 Faraday Ave.
CarlsbacJ,· CA 92008
Plan Review Requirements Category:
Fire Prevention
(760) 602-4660
Date of Report: _10_1_10_12_0_0_1 _______ _
Building Plan
Reviewed by:
Name: SMITH CONSULT ARCH
Address: 12220 EL CAMINO REAL STE 200
City, State: SAN DIEGO CA 92130
Plan Checker: Job#: 013136 -------
Job Name: Callaway Golf Bldg#: CB0f31.3"6-:) -----,--------,,----------------
Job Address: 2285 Rutherford Road Ste. or Bldg. No.
IZI Approved
LJ Approved
Subject to
LJ Incomplete
Review
FD Job#
The item you have submitted for review has been approved. The approval is _
based on plans, information and/ or specifications provided in your submittal;
therefore any changes to these items after this date, including field
modifications, must be reviewed by this office to insure continued conformance
with applicable codes and standards. Please review carefully all comments
attached as failure to comply with instructions in this report can result in
suspension of permit to construct or install improvements.
The item you have submitted for review has peen approved subject to the
attached conditions. The approval is based on plans, information and/or
specifications provided in your submittal. Please review carefully all comments
attached, as failure to comply with instructions in this report can result in
suspension of permit to construct or install improvements. Please resubmit to
this office the necessary plans and I or specifications required to indicate
compl_iance with applicable codes and standards.
-The item you have submitted for review is incomplete. At this time, this office
cannot adequately conduct a review to determine compliance with the
applicable codes and / or standards. Please review carefully all comments
attached. Please resubmit the necessary plans and / or specifications to this
office for review and approval.
1st
013136
2nd
FD File#
3rd Other Agency ID
Bruce M. Kerl & Assoc1A1Es, INC.
Fire Prevention Contract Services
October 30, 2001
Mr:Doug Moody
EsGil Corporation
9320 Chesapeake Drive, Suite 208
San Diego, CA 92123
Re: NUTRO U.V. Spray Booth Conveyor,. Callaway Building 1;
Subject:
a) Requirement for Ducting to Exhaust Directly to the Exterior & Requirement
Exception
b) NUTRO U.V. Spray Booth Conveyor & ExplosionproofElectrical
Fire Protection Technical Opinion & Report
OVERVIEW
Callaway Golf Company is in the process of making internal changes in Building 1 at 2285
Rutherford Road, to make room for an additional production cell. As a part of this process, a
fully automated, U.V. spray booth conveyor (used for golf club repair) must be moved to a new
location within Building 1. I have conducted research with regard to this component and offer
the following explanation and opinions.
ISSUES & REGULATION
Requirement for Ducting Exhaust Directly to the Exterior & Requirement Exception
Uniform Mechanical Code Section 505.1 requires that ducts conveying explosives or flammable
vapors, fumes or dusts shall extend directly to the exterior of the building without entering other
spaces. The exception for this requirement allows that if the ducts conveying vapor or fumes
having flammable constituents less than 25 percent of their lower flammability limit may pass
through other spaces.
After a review of the Material Safety Data Sheet (MSDS) revealed no flammable range for Nano
Cure U.V. Coating, I contacted American Synthetics Company & Magna Coatings the maker of
Nano Cure. I spoke with Brian Zelek, President of the Company on 10/24/01 at (480) 951-8400.
He explained that Nano Cure is a mixture of mainly monomer & oligomer (plastic) solids. He
further stated that about 1 to 1 ½ percent of the total mixture is solvent (isopropyl alcohol) to
cause the plastics mix together in liquid form. It is this small amount of solvent that gives Nano
Cure Coating its III-B Combustible rating. Mr.-Zelek stated that testing to establish flammable
limits for Nano Cure were never conducted due to its low combustibility. He also verified that
Callaway only buys a few gallons of the product per year.
P.O. Box 1861 Alpine, CA 91903-1861, Phone: 619-659•8562, Fax: 619-659-8734, Cell: 619-742·1472
E•mall: bmkandassoc@scltl.com
Bruce M. Kerl & Assoc1ATES, INe.
Fire Prevention Contract Services
Callaway Golf, NUTRO U. V. Spray Booth Conveyor
Doug Moody, EsGil Corporation
Page2
Without exact chemical characteristics it is difficult to apply appropriate code sections. The
MSDS for Nano Cure indicates a flash point of 250+ degrees Fahrenheit, giving it the lowest fire
hazard combustible rating ofIII-B.
The classification of flammable and combustible liquids has been widely established and is
published in the California Building Code, California Fire Code and NFP A 30. Within these
definitions it is anticipated that, in most areas, the indoor temperature could reach 100 degrees
Fahrenheit at some time during the year. Therefore all liquids with flash points below 100
degrees are called Class I (flammable) liquids. With their low flashpoints, these liquids give off
ignitable vapor in ambient temperatures. These liquids must be used with extreme care. Liquids
with flash points above 100 degrees are considered less hazardous and are classified as
. combustible liquids. These liquids require preheating before they will give off vapor that will
ignite. The least hazardous of the combustible liquids are classified as III-B liquids having flash
points greater than 200 degrees.
While determining the flammable ( or explosive) range is important when dealing with a
flammable liquid, it is less important to determine the flammable range of a combustible liquid.
Under ordinary conditions of a plant or factory the preheating required necessary for the liquid to
give off ignitable vapor is inconceivable.
Section 502 of the Mechanical Code defines flammable vapor or fumes as the concentration of
flammable constituents in air that exceeds 10 percent of its lower flammability limit. Most spray
finishes are flammable liquids giving off vapors that will ignite in ambient temperatures. Based
on my research and the material collected, it is my opinion that Section 505 of the Uniform
Mechanical Code applies to flammable vapors and materials and does not apply in this instance
because Nano Cure U.V. Coating is not a flammable material.
NUTRO U. V. Spray Booth Conveyor & Explosion proof Electrical
After some analysis it appears that the NUTRO Spray Booth Conveyor is not equipped with
explosionproof electrical components. There is speculation among us as to why this is the case.
In a typical spray operation the material used is a flammable liquid, a material giving off vapor
that can ignite in ambient temperatures. In this case, the Nano Cure U.V. Coating must be
preheated to over 250 degrees Fahrenheit before it will give off vapor that can ignite.
National Electrical Code (NEC) Article 516-1 states that the article covers the regular or
frequent application of flammable liquids, combustible liquids, and combustible powders by
spray operations and the application of flammable liquids, or combustible liquids at
temperatures above their flashpoint by dipping, coating, or other means.
Additionally, NEC Article 516-2 States that the classification of hazard locations for
explosionproof electrical is based on dangerous quantities of flammable vapors, combustible
mists, residues, dusts, or deposits
P.O. Box 1861 Alpine, CA 91903-1861, Phone: 619-659-8562, Fax: 619-659-8734, Cell: 619-742-1472
I-mall: bmkandassoc@scltl.com
Bruce M. Kerl & AssotlA'FES, INe.
Fire Prevention Contract Services
Callaway Golf, NU1RO U. V. Spray Booth Conveyor
Doug Moody, EsGil Corporation
Page3
I offer the following considerations in evaluating the requirement for explosionproof electrical. . .
1) Nano Cure U.V. Coating is the only material used in the NUTRO Spray Booth
Conveyor, a material with a flash point of over 250 degrees Fahrenheit.
2) The spray operation is used infrequently. Only a few gallons of the Nano Cure
product are purchased and used annually. NEC 516-1 covers regular and frequent
application & NEC 516-2 classifies hazard locations based on dangerous quantities of
vapors or mists. Based on the type and quantity of material, these do not seem to apply.
3) Ventilation for the Spray Booth Conveyor is interlocked with the spray operations.
4) The Spray Booth Conveyor is protected throughout by the automatic fire sprinkler
system installed in the structure.
Based on my research and the material collected, it is my opinion that the regulations for
explosionproof electrical in the NEC address the typical spray operation with materials having a
much greater fire hazard than Nano Cure U.V. Coating. Code professionals maybe reluctant to
reduce requirements or address specific less hazardous operations like the one listed above.
Much of the spray finishing industry is moving toward waterbased or waterborne paints and
coatings. While this move is to meet environmental regulations, the increased level of fire safety
is evident. These changes have been occurring over the last five years or so the code
requirements are the same for these products as for petroleum based finishes.
I hope this information will assist you. If you have any questions, or if I can be of any assistance
to you, please do not hesitate to contact me at 619-659-8562.
Respectfully submitted,
'~wt~
Bruce M. Kerl
President
Attachments
P.O. Box 1861 Alplne, CA 91903-1861, Phone: 619-659•8562, Fax: 619-659•8734, Cell: 619-742·1472
E•mall: bmkandassoc@scltl.com
504.6
506.1
I. hTh~ terminhation poinhtfor ehnv11ir~mmben1tal a1h·r du3c~ exh(a9u1s4ts dis)-c argmg to-t e atmpsp ere s a not e esst an ~eet mm
from a property line or from openings into a building.
SECTION 505 -PRODUCT-CONVEYING SYSTEMS
505.1 General. A mechanical ventilation or exhaust system
shall be installed to control, capture and remove emissions gener~
·ated from product use or handling·when required by the Bl;lilding .
Code or Fire Code and when ·such emissions result in.a hazard to; ..
life or property. The ·design of the system shall be such that the .
emissions are .confined to the area in which they are generated by
air currents, hoods or enclosures and shall be exhausted by a duct
system to a safe location or treated by re111oving contaminants.
Ducts conveying explosives or flamµiable vapors, fumes-or dusts
shall extend directly to the-exterior of the building without enter-
ing other spaces. Exhaust ducts shall not extend into or through
ducts and plentims.
EXCEPTION: ·Ducts conveying vapor or fumes having·flammabie
constituents less·than 25 percent of their' lower flammability limit may
pass through other spaces. •
505.2 Incompatible Materials. Separate and distinct systems
shall be provided for incompatible materials.
505.3 Recirculaijon. Contaminated air shall not be recirculated
to occupied areas. unless contaminants have been removed. Air·
contaminated with explosive or flammable vapors, fumes or.
dusts; flammable or toxic gases, or radioactive material shall not
be recirculated;
505.4 Minimum Velocities and Circulation. The velocity and
circulation of ai,r in work areas shall be such that contaminants are
captured by an airstream at the area where the emissions are gener-
ated and conveyed into a product-conveying duct sys~em. Mix-
tures within work areas where contaminants are generated shall be
diluted below 25 percent oftheir lower explosive limit or lower
flammability limit with air which does not contain other contami-
nants. The velocity of air within the duct shall not be less than set
forth in Table 5-A.
505.5 Design, Systems for removal of vapors, gases and smoke
shall be designed by the constant velocity or equal friction meth-
ods. Syst~ms conveying particulate matter shall be designed em-
ploying the constant velocity method. Systems conveying
explosive or radioactive materials shall be prebalanced through
duct sizing. Other systems may be designed with balancing de-
vices such as dampers. Dampers provided to balance air flow shall
be provided with securely fixed minimum-position blocking de-
vices to prevent restricting flow below the required volume or ve-
locity.
505.6 Makeup Air. Makeup air shall be provided to replenish
air exhausted by the ventilation system. Mak;eup-air intakes shall
be located so as to avoid recirculation of contaminated air within
enclosures. ·
505. 7 Hoods and Enclosures. Hoods and enclosures shall be
used wheQ contaminants originate ill a concentrated area. The de-
sign of the hood or enclosure shall be such that air currents Cfeated
by the exhaust systegis. ~ill capture the ~ontaminants and trans-
port them directly t9 the exhaust duct. The volume-of air shall be
sufficient to dilute explosive or flammable vapors, fumes or dusts
as·serforth in Section 505.4:Hoods of steel-shall have a base metal
thickness not less than 0.027 inch.(0.68 mm) (22 gage) for,class 1
and Class 5 metal _duct systems; 0.033 irich (0.84 mm) (20 gage)
for hoods serving a ~lass ;2 quct system;_.0.044 inch (1.12 mm)
(18 gage) for hoods serving a Class 3 duct system; and 0.068 inch
(1.73 mm) (14 gage)-for hoods serving a Class 4 duct system. Ap-,
28
... , ., ,'
1997 UNIFORM MECHANICAL CODE
. proved nonmetallic hoods and duct systems may be used for Class
·5 corrosive systems when the corrosive mixture is nonflammable.
Metal hoods used with Class 5 duct systems shall be protected
with suitable corrosion-resistant material. Edges of hoods shall be
rounded. The minimum clearance between hoods and combus-
tible construction.shall be the clearance required by the duct sys-
tem.
505.8 Small Hobby Kiln Exhaust Systems. The provisions of
.this·section.apply to kilns used forfiring ceramics, having a maxi-
. mum interior volume of 20 cubic feet (0.57 m3), used for hobby
and other noncommercial purposes.
505.8.1 'Hoods. A canopy-type hood shall be installed directly
above each kiln. The face opening area of the hood shall be equal
to or greater than the top horizontal surface area of the kiln. The
hood shall be constructed of not less than 0.024-inch (0.61 mm)
.(No. 24 U.S. -gage) ·galvanized. steel or equivalent and be sup-
ported at a.height of between 12 inches and 30 inches (j05 mm and
762 mm) above the 'kiln by noncombustible supports.
EXCEPTION: Electric kilns installed with listed exhaust blowers
may be used when marked as being suitable for the kiln and installed
in accordance with manufacturer's instructions.
505.8.2 Gravity ventilation ducts. Each kiln hood shall be con-
nected to a gravity ventilation duct extending in a vertical direc-
tion to ·outside the building. This duct shall be of the same
· construction as the hood and shall have a minimum cross-section-
al area-of.not less than-one fifteenth of the face opening area of the
bood. The-duct shall terminate a.minimum of 12 inches (305 mm)
above any portion of a building within 4 feet (1219 mm) and termi-
nate no less:than 4 feet (1219 mm) from any openable windows or
other openings into the building or adjacent property line. The
duct opening to the outside shall be shielded, without reduction of
duct area, to prevent entrance of rain into the duct. The duct shall
be supported at each section by noncombustible supports.
505.9 Exhaust Outlets. Outlets for exhausts that exceed 600°F
(315°C) shall comply with Table 8-D.
The termi.Qation point for exhaust ducts discharging to the
atmosphere shall not be less than the following:
1. Ducts conveying explosive or flamQtable vapors, fumes or
dusts: 30 feet (9144 mm) from property line, 10 feet (3048 mm)
from openings into the building, 6 feet (1829 mm) from exterior
walls or roofs, 30 feet (9144 mm) from combustible walls or open-
ings into a building which are in the direction of the exhaust dis-
charge, and 10 feet (3048 mm) above adjoining grade.
2. Other product-conveying outlets: 10 feet (3048 mm) from
property line, 3 feet (914 mm) from exterior wall or roof, 10 feet
(3048 mm) from openings into the building, and 10 feet (3048
mm) above adjoining grade.
SECTION 506 -PRODUCT-CONVEYING DUCT
SYSTEMS
506,1 Cl!)ssificatio11. Product-conveying ducts shall be classi-
fied according to their use, as follows: -
Class 1. Ducts conveying nonabrasives, such as smoke, spray,
mists, fogs, noncorrosive fumes and gases, light fine dusts or pow-
ders.
Class ·2. Ducts conveying moderately abrasive particulate in
light concentratiqns, such as sawdust and grain dust, buffing and
polishing dust. .
Class 3. Ducts conveying Class 2 materials in high concentra-
tions and-bigbly abrasive materials in lqw concentrations, such as
manganese, steel chips ,and coke.
' 'f997 UNIFORM MECHANICAL CODE · 501
504.6
.~
Chapters
EXHAUST SYSTEMS
' '
Part I-Product-conveying
and Environmental Air Systems
• ~ SECTION 501-SCOPE OF PART I
: ' .Part I of.this chapter. applies to-environmental air-ventilation sys-
. terns ,that are not a.part of a heating or cooling system and to prod-
uct-conveying duct systems. For commercial hood and kitchen
ventilation systems, see Part II of this chapter.
""· SECTION 502 -DEFINITIONS
For the purposes of Part I, the following definitions apply:
ENVIRONMENTAL AIR DUCT is ducting used for convey-
ing air at temperatures not exceeding 250°F (121 °C) to or from oc-
cupied areas of any occupancy through other than heating or
air-conditioning systems, such as ventilation for human usage,
domestic kitchen range exhaust, bathroom exhaust ducts, and
doine~tic,type. clothes dryer exhaust ducts. ·
FLAMMABLE VAPOR OR FUMES is the concentration of
flammable constituents in air that exceeds 10 percent of its lower
flammability limit (LFL).
PRODUCT-CONVEYING DUCT is ducting used for con-
veying solid particulates, such as refuse, dust, fumes and:smoke;
,.--.. liquid particulate matter, such as spray residue, mists and fogs; va-
pors, such as vapors from flammable or corrosive liquids; noxious.
and·.toxic gases; and air at temperatures exceeding 250°F (12l°C).
SECTION 503 -MOTORS AND FANS
503.1 General. Motors and fans shall be sized to provide the re-
quired air movement. Motors in areas which contain flammable
vapors or dusts shall be of a type approved for such environments.
A-manually operated remote control installed at an approved loca-
tion shall be provided to shut off fans or blowers in flammable va-
por or dust systems. Electrical equipment used in operations that
generate explosive or flammable vapors, fumes or dusts shall be
interlocked with the ventilation system so that the equipment can-
not be operated unless the ventilation fans are in operation. Motors
,,..---:--.., ·_rorrans.us.e_q ,to ~9.n.vey ~m-~pl~ :'{llPO~ qr d_usts shall~locati:d -
) · outside the duct or shall be protected with approved shields and
dustproofing. Motors and fans s~all be accessible for servicing
and maintenance.
503.2 Fans. Parts of fans-in contact with explosive or flammable
vapors, fumes.or dusts shall be of nonferrous or nonsparking mate-
.,,-..__ rials or their casing shall be lined or constructed of such material.
. When· the size and hardness of materials passing through a fan
could produce a spark, both the fan and the casing shall be of non-
sparking materials. When fans are required to be spark resistant,
their bearings shall n9t be within the airstream, and all parts of the
fan ~hall be grounded. Fans in sys~ms handling materials that are
·likely to clog the blades, and fans in buffing or· woodworking ex-
~,: ha~f ~~s~~m~, ~~~1~._bep_f_t~~~~-a\~?l.a,?e}~r t~~:-axial,tY:~·-
, ... · ~·-. ,:!\:-. :---··-.. · '-"\...'· ... .-~·::::·~-·--''·'···· ., ... ·~~ .....
· · 503.2r1 .Equipment id,n.tific~tion" plate. Equipment used to
exhati.st-explol!ive Of, flaiµ~~ble vapors, _fumes or dusts shall bear.
an identification plate stating the-ventilation rate for which the
sy~tem was desi$ned.
;
503.2.2 Corrosion-resistant fans. Fans located in systems con-
veying corrosives shall be of material~ that a~e resistant t? the cor-
rosive or shall be coated with corros1on-res1stant matenals .
-S.ECTION 504 -ENVIRONMENTAL AIR DUCTS
504.1 Makeup and Exhaust Air Ducts. Environmental air ducts
not .regulated by other provisions of this code shall comply with
this section. Ducts·shall be su!:>stantially airtight and shall comply
with the provisions of Chapter 6. Exhaust ducts shall terminate
. outside the ·building and shall be equipped with backdraft damp-
ers. Environmental air ducts which· have an alternate function as a
part of an approved smoke-control system do not require design as
Class I product-conveying ducts.
504.2 Domestic Range Vents. Ducts used for domestic kitchen
range ventilation shail be of metal and shall have smooth interior
surfaces.
EXCEPTION: Ducts for domestic kitchen downdraft grill-range
ventilation installed under a concrete slab floor may be of approved
~chedule 40 PVC provided:
I, The under-floor-trench in which the duct is installed shall be com-
pletely backfi!led with sand or gravel.
2. Not more than I inch (25 mm) of 6-inch-diameter ( 152 mm).PVC
. coupling may protrude above the concrete floor surface.
3. PVC.pipe joints shall be solvent cemented to provide an air-and
grease-tight duct.
4. The duct shall tenninate above grade outside the building and
shall be equipped with a backdraft damper.
504:3 Domestic Dryer Vent. Domestic clothes dryer moisture
exhaust ducts ~hall be of metal and shall have smooth interior
surfaces.
EXCEPTION: Approved flexible duct connectors not more than
6 feet (1829 mm) in length may be used in connection with domestic
dryer exhausts. Flexible duct connectors shall not be concealed within
construction.
·s04.3.1 Moisture-exhaust ducts. Moisture-exhaust ducts for
domestic clothes dryers shall terminate on the outside of the build-
ing and shall be equipped with a back-draft damper. Screens shall
not be installed at the duct termination. Ducts for exhausting
clothes dryers sh!lll not be connected or installed with sheet metal
screws or other fasteners which will obstruct the flqw.
Clo~es-dryer ~oisture-exhau~t ducts shal! nq~·be connected to a gas vent' connector, ·gas· venf or chimney. Clothes-dryer moisture-
exhaust ducts shall not extend into or through ducts or plenums.
504.3.2 Leµgtb limitation. Unless otherwise permitted or re-
q1,1ired by the dryer manufacturer's installation instructions and
approved by the building official, domestic dryer moisture-
exhaust ducts shall not exceed a total combined horizontal and
ve~ical length.9f 14 feet (4267 mm), including two 90-degree
elbows. Two feet (610 mm) shall be deducted for each 90-degree
elbow in excess of two. 1
504.4 Commerciai Dryer Exhaust Systems. Commercial dry-
er moistu~-exha1:1st. ~c~s sha!,l be installed in accordance with
their listing. 1; . --4·
504.5 Gypsqaµ,-:Wall~oai;.(-D,ctil'.Bathroom .and laundry--toom
exhaust ducts may be-of gypsuµi wallboard subject to the limita-
tions of Section.601.1.3.
504.6 Exhaust Outlets. Outlets for exhausts that exceed 600°F I
(315°C) shall comply with Table 8-D.
27
,.,
1.7.3.1 Combustible Liquid.
Any liquid that b.as a closed-cup flash point at or above 100°F (37 .8°C), as determined by the test
procedures and apparatus set forth in 1. 7.4. Combustible liquids are classified as Class II or Class
III as follows: ( a) Class 11 Liquid-any liquid that has a :flash point at or above 100°F (37 .8°C)
and below 140°F ( 60°C); (b) Class II/A -. 811Y liquid that has a flash point at or above 140°F
( 60°C), but below 200°F (93 °C); ( c) Class /JIB -any liquid that has a flash point at or above
200°F (93°C).
1. 7.3.2 Flammable Liquid.
Any liquid that has a closed-cup flash point below 100°F (37.8°C), as determined by the test
procedures and apparatus set forth in 1. 7.4. Flammable µquids are classified as Class I as follows:
(a) Class I Liquid-any ]jquid that has a closed-cup :flashpoint below 100°F (37.8°C) and a Reid
vapor pressure not exceeding 40 psia (2068.6 mm Hg) at 100°F (37.8°C), as determined by
ASTM D 323, Standard Method of Test for Vapor Pressure of Petroleum Products (Reid
Method). Class I liquids are further classified as follows: (1) Class IA liquids -those liquids that
have :flash points below 73°F (22.8°C) and boiling points below 100°F (37.8°C); (2) Class IB
liquids -. those liquids that have flash porn.ts below 73 °F (22. 8°C) and boiling points at or above
100°F (37.8°C); (3) Class IC liquids-those liquids that have :flash points at or above 73°F
(22.8°C), but below 100°F (37.8°C).
1. 7 .4 Determination of Flash Point.
The flash point of a liquid shall be determined according to the methods specified in this
subsection.
1.7.4.1
The :flash point of a liquid having a viscosity below 5.5 centiStokes at 104 °F ( 40°C) or below 9.5
centiStokes at 77°F (25°C) shall be determined in accordance with ASTM D 56, Standard
Method.of Test for Flash Point by the Tag Closed Cup Tester.
Exception: Cut-back asphalts, liquids that tend to form a surface film, and liquids that contain
suspended solids shall not _be tested in accordance with ASTM D 56, even if they otherwise meet
the viscosity criteria.
1.7.4.2
The :flashpoint of a liquid having a viscosity of 5.5 centiStokes or more at 104°F (40°C) or 9.5
centiStokes or more at 77°F (25°C) or a :flash point of200°F (93.4°C) or higher shall be
deterniined m accordance with ASTM D 93, Standard Test Methods for Flash Point by the
Pensky-Martens Closed Tester.
1.7.4.3
As an alternative, ASTM D 3278, Standard Method of Tests for Flash Point of Liquids by
Setajlash Closed Tester, shall be permitted to be used for paints, enamels, lacquers, varnishes, and
r~lated products and their components that have :flash points between 32°F (0°C) and 230°F
Copyright NFP A
, 1.pdf· -> .,
FAX tll, May. 05 ~ 09!36f:'tl P2
-
MATERIAL SAFETY DATA SHEET
:«-"3\0i
'{V'"
~ ~ 1111 II. Bifan Z8lell
24 HOUR EMERGENCY AIIIITANCI! I AM!IUCAN SYNTHETICS co. & MAG~COATINOS
C~REC: 80M24-eSOO 774'JEast.EYant Scottsd;n,AZ.meo [k1-&,oo
,IQRS~ffll -171 ~ LEAST• 0 SI.GltT • 1 MOOER,t.TE • 2 HIGM • 1 ~-· 1 JIIATlNIII
SECTIONI NAME
flllODUCTIWIIS .-NANO cuae u.v. c .. a., Bati:h: Clear or Pigmented
Ctl!MICAl..l'AML't MDCII)~ & OUCJ0lll!IIS
... _sec_TION __ n_-A _________ PRODUCT ___ ,IN_GRED __ IE_NT ___ _,, ______ __.l ~>
11-... i-,-
Nlilllbe-~
• ,. P'l'Odlllct • 8111GU! CO.PONl!NT, 100% eouae
I ~MY CHElol$TR't FOMUATIOH
2 OIIGOMIIIS
3 MOMCIIIERS
4 •CIILUPffll
! INITIATOAS
I IECTIONH
Numblr
~
15-28
3()-.U%
$.8%
'SPE<ilFICOSIIC>.LaarnTYNI/OICRl'IIOPOlm0!IOflMISC()IIIP(IICIITIHlilNGIICI.D.&$'11llCGSICRSTlll'QRIIATt)N.
TO,lC&CfrY DATA
P NO DATAAVNt.N!iU;
1
2
3
'4
6
I SECTIONII HEALTH I~ INFOIWA110N
. EV! CONTACT
.f"'YCWJ8l!BelEIIIEl'IRfTAllON.~GOOOLESANP/ORff<a:SHIELD.W.\IEMWASHUNTAVM.NAJ:. ...
8IQN CONTACT
• /0 11/J'-J If
(VI ,-e,.Ji..,-
At. ( 'f 5,-00 x...~ ft.t,. if-I-\ '
'w,y~ $MRE CK1N IRRITATION: WEM PROTECTI\IE CLOTHING AND GLOVES. SUGHTSl<IN A8SORP110N 1-NMD
NW.ATION
' ,,diCl&O~MA.YCAU81!1RTAT10NTORESl'lftATORY$\'STEM,SUSf'EOTRESPIRATORYTR,eCTIRRfTATIONMA!AR[).
~
SIGNS/ SYMPTOMS
ontl!ltl!l'Pl!CTa
ll.TRA \/IOLET-CMEIMSTRY18 ClAS&IFIEOAS UN$TAIII.E UPON llEPLET10N OF INHtelTOR$..
•.-:-.., ,·
• 1.pdf,
FROM : May. 05 2000 09:36F'C1 P3 -
11RODUCT NAMI ~ NANO CURE u.v. Coating Batch, (:lflr ot PlgMenbtd PAGE2
I -·'-----------------------------------~---~ I I SECTION IV. OCCUPATIONAL EXPOSURE UMTS :
Nlltffl
P NONEEST~
2
s
4
5
TLV1t11it. OTHiR
•TilE a11UK11'ATIOll 1iDICATiSlHl!SUISTANCI! IMYIEAIISOIWOTltl!OUQll \'141!-, MIJCO!l .• -tO!' ll'U, 11V RCT OR AIRIOlliE EllPOGUAE,AND SUGGEffl
tl4A.T--1Elil&l,SUfB IE TAllill TI> PIIE'IBITSUCIIMSCIIPTIOlf. I 8ECTIQNV !ll!RGENCY AND FIRST AID PRC)CEOURES ]
eYl!CONTACT
INMB».TELYFLUSHEY!SWITH PLEN'fY Of'WA'TSt l"ORAT LEAST 15 MNUTESWHU! HOLDNG E'IEJDS OPEH. RINS£
CCWJWuOIJSLYWITH WATER YIIHIL!: ON WAYTOGE:r MEDICALA1TENT10tl.
MCINCONTACT
IMIEPII\TB.YREMO\/EpcJNTAl!fi\TEOOI.01111NGORSHOU,Wl'l:EXCESSFROM81<1N'ANDl'WSHWITHPISffYQFWATl!ftl'OR
ATI.EAST1$MINUTl!t,USl!~H'l'llll'lllLYAVMNJli,ORFQU.OWBVTHOROUCH.YWASHIIIGWITHSCW>.ANDWATffl.OONOT
,eJIIE()I..Q"MNG UNTIL THOAOUGHLY OE<:ONl"MMHIITED,
INIW.A1'1Dft
~'\IICTIMTOl'RESHNANIDPR<MDEOX'roENFIIREATIINGIS.DFl'ICULT.CET~AT'!ENTIONIFNEC~
t INCll!SIION
DONOTINDUCEVOMITM,IGPATRl:$'!'.ANDCONT.ter~.
SEC.TIONYI 8UPPLE~AL HEALTH INFQRMATION
IECTJONYII
IIOIUN8PClff' O.W900o.ai-F.
.... ,..PCIIII' Nat~
1!¥.IIORAlDI RATI!
NNAIIANCII· Mabi191iquidwilhmlllyodor
..
. PtfftlCM.OATA
8PECIFIO.GRAVfJY
aouaul'Y(ln_,,
VAPOltP'IIAIUM
YAJICR llEIISffY
. FIRE AND EXPLOSION HAZARDS
l'UIHPOINT li#J laTIIOD
PMCC OVER 2!!0F
~ IIBIA
UEWA'Tl!RFOG, RWl,DRVCH!MICH.,002arDRYCHEMICN-j _,........ ___ _
FUMMMU! LN'l'S-'JI.Vcumlnlllt
NODA.TAAVAIL
0o1111t.-MW..,.._,,_~0acon..-., Prclillldsnpollll*.Fful'llh~$G~.11PllllllCtldlOcallen.t-i.lllllor
~fflll'lncnNe~ adb!Atinntn.,-lllllftlPllllrl.daNCICCllllllnn. W*IIIIYN~lll~Pblaw
llCM:&lly. lhe..,_,fqJforOCXllif(I. NOll'y~IUc,idtnS-f !lldo'Mlln,
UIIUIU,\L n.NJD~ ~
·CONTAtlE'RSEJCPOSED TO NT'ENSEHEATFOAMFIRESSHOUI.DBEc;:o0l.EDwmtWATERTOPIUiVENTVfll'CIP. ~
·IMJILDIJl"WHICH OOUl.0 l'QiU.T INCOHT'AINl!Rl'lUl"TURE.
FRCl'I: FAX NO. May. 05 2000 09:·37AM P4 -l'llODUCTIIAMI! .... NANO CURE U.V. Coating Batch: Clear or Pigmented PAGE:3
STABLE
' . \ CCINDfflONI MIO MATl!!IIMU TO 11.YO/lJ
A\IOIDHE'AT,FUIME.STOAEATROOM'TDPl;;RA.TURE,Al.WA'IS~SJF.OONTAINeRCI..OSEDWHliNNOTINUSE.DonCll:med!Um
or__.,_..,AYdCl~~lllllllgM.ullll'llolltrllCNlon,an:ltnertgas~
IIAZANIOUS DECOMl'oalilOfl l'll0IIUln'I
NIIRC$;N O,XIDU, ~ ~.-ND ........ lll'lll>~<X>MPOUND8""YlliifO!'W&D CIUAINGOON8U8TION.
I IECTIONX EMPLOYEE PROTECTION
IIIIPIVffllRY MOTK110N
DO NOT IIA!ATHV,¥0M 01\MISTS. ·~ WIVOR ooessaeo OCCUPATIONl,i. EXPOSURe UMIT$USE,\ NIOSH-
APPROVED RESPIRIITOR TO PAIM:NT ~.
IMX> HATI-INGVN'CRS'WHICH tlAVIEl'ROllllCEI) UNDER 801ECONDITIONt llUCH M Hl!ATINO ORAPPUCA'!'IONS Oil
tMCLNDUATIRW..INLARGEtt#AC&N'IJEM.AVODIIRliA'TlalGMISTSWHICHW.YIEFORMEDBYV~METHODSOF N'PUCATION.
l'IIIOTl!ICTM! CUJl1INB
PO NOTO&T Nli'YliS,·WliARCl,e,ICA&, 80GGUiS IFTHEN:.18 P01fflfW. CONTACTWl1HEYE8. DO NOTGET ONlll<IH, ON
CLO'MNQ, WEAR 0HEIICM. IGISTANT PAOlliCTlYE CLO,nllNGsuc.f ~OLOYU. OUTER CLO!llNG ORN'RON. OVERSHOES
)tfl)AFACE-8MIELDSUl'r"81.&TOPQTMW.E)llQSURC.
allll,l.QltJ,.eM~
• .t,RONJ....._ WITH~ Mlt.THIAL (DRYSNIJ OR liARTM) TH&N PUliCI! INACHEIIICM. WASTiiCONTAINER. FWSH PW:A wrl'H
,WA.TIA TO RIIDIE TRACE RESIDUE.
I .SECTION XII . SPECIAL PRECAUl'ION8
'(:ONTAINMC, EWNTHCll!THAT HA.\IEBEEN BIPT1E0, CAN CONTAIN HUAROOUS PRODl,CT RESIDUES. WASH WITH sa,,p NiD
~T&Rllli'F0fliEATINQ,DRJNICINQ,SMCICING,Al'PLVIN0009NETIC8.0R~TOILET 1-ACI.ITliS,
I, tECTION XIII
;, DEIWffllENTOF11WMPORTA'l'IOII CUUIIICATIDN:
' NOT FIEOUIA'il!O
DAT.flRCIIIR..,.NAMI!
NOT~
UNINACOlle NotAvallatlle
..............
{ftf1-
' /0.,l~Q I ·
JO -'i, ,,<) I
4-;_-. ~ --
lo l ~.(. l Ol
... ', ' . '
.•, ··>
,' .
• I' <
.. :.;'·,
··:._
~\ ~ ,::, .
I • • •
. ,. ·-,·.
: . .:,. .
·-.:·-. ;', ~ .
. ,
/
CB013136 2285 RUTHERFORD RD CBAD
C,~LLAWAY GOLF -Tl 745 ' -----Tl . r.niv1M: .
L ' I ~1· ~ t:v1 e-, (/, / IJ/~
GLW[
~ f:C ..
~r uJ~t I~
pc."-> @) re
\
~--______ ..,.__ , .. _.,, _ __.,
,,
' '