HomeMy WebLinkAbout2290 COSMOS CT; ; CB050917; Permit03-23-2006
City of Carlsbad
1635 Faraday Av Carlsbad, CA 92008
Commercial/Industrial Permit Permit No
Building Inspection Request Line (760) 602-2725
CB050917
Job Address
Permit Type
Parcel No
Valuation
Occupancy Group
Project Title
2290 COSMOS CT CBAD
Tl Sub Type COMM
2130504400 Lot# 0
$21,390 00 Construction Type NEW
Reference #
SIERRA WIRELESS 690 SF Tl
Applicant
MONTELLO GEORGE
471560THST
SAN DIEGO CA 92115
619229-0642
Status (EXPIRE
Applied ^53/18/2005
Entered By SB
Plan Approved
Issued
Inspect Area
Plan Check#
Owner
GRANDONA INVESTMENT ASSOCIATES L P
2610HARRISBURGAVE
FREMONT CA 94536
Building Permit
Add'l Building Permit Fee
Plan Check
Add'l Plan Check Fee
Plan Check Discount
Strong Motion Fee
Park Fee
LFM Fee
Bridge Fee
BTD #2 Fee
BTD #3 Fee
Renewal Fee
Add'l Renewal Fee
Other Building Fee
Pot Water Con Fee
Meter Size
Add'l Pot Water Con Fee
Reel Water Con Fee
$19209 Meter Size
$0 00 Add'l Reel Water Con Fee
$12486 Meter Fee
SO 00 SDCWA Fee
$0 00 CFD Payoff Fee
$449 PFF (3105540)
$0 00 PFF (4305540)
$0 00 License Tax (3104193)
$0 00 License Tax (4304193)
$0 00 Traffic Impact Fee (3105541)
$0 00 Traffic Impact Fee (4305541)
$0 00 PLUMBING TOTAL
$0 00 ELECTRICAL TOTAL
$0 00 MECHANICAL TOTAL
$0 00 Master Drainage Fee
Sewer Fee
$0 00 Redev Parking Fee
$0 00 Additional Fees
HMP Fee
TOTAL PERMIT FEES
$000
$000
$000
$000
$000
$000
$000
$000
$000
$000
$000
$000
$000
$000
$000
$000
$000
7?
$321 44
Total Fees $321 44 Total Payments To Date $12486 Balance Due $19658
Inspector
FINAL APPROVAL
Date Clearance
NOTICE Please take NOTICE that approval of your project includes the "Imposition" of fees, dedications, reservations, or other exactions hereafter collectively
referred to as "fees/exactions" You have 90 days from the date this permit was issued to protest imposition of these fees/exactions If you protest them, you must
follow the protest procedures set forth in Government Code Section 66020(a), and file the protest and any other required information with the City Manager for
processing in accordance with Carlsbad Municipal Code Section 3 32 030 Failure to timely follow that procedure will bar any subsequent legal action to attack,
review, set aside, void, or annul their imposition
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection fees and capacity
changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this project NOR DOES IT APPLY to any
fees/exactions of which you have previously been given a NOTICE similar to this, or as to which the statute of limitations has previously otherwise expired
PERMIT APPLICATION
CITY OF CARLSBAD BUILDING DEPARTMENT
1635 Faraday Ave , Carlsbad, CA 92008
PROJECT INFORMATION;;
FOR OFFICE USE QIMLY
PLAN CHECK
EST VAL
Plan Ck Deposit<£
Validated By „
/Date +
Address (include Bldg/Suite #)Business Name (at this address)
03/1SK&S No'002 Q&>tal#CoT unitsLegal Description Lot No Subdivision Name/Number
Assessor's Parcel #-TO
Existing Use Proposed Use
Description of Work
2 'CONTACT PERSON
1\ ' 'WOWM
Name
4 PROPERTY OWNER
sa FT #of Stories # of Bedrooms # of Bathrooms
toith fr -r>
Address City State/Zip Telephone #
Name Address City State/Zip Telephone #
5"" "CONTRACTOR - COMPANY NAME it;!-' """" - - """ ;':f: ~iif""" "i-.-
(Sec 7031 5 Business and Professions Code Any City or County which requires a permit to construct alter, improve, demolish or repair any structure, prior to its
issuance, also requires the applicant for such permit to file a signed statement that he is licensed pursuant to the provisions of the Contractor's License Law
[Chapter 9, commending with Section 7000 of Division 3 of the Business and Professions Code] or that he is exempt therefrom, and the basis for the alleged
exemption Any violation of Section 7031 5 by any applicant for a permit subjects the applicant to a civil penalty of not more than five hundred dollars [$500])
Name
State License #
Address
License Class
City State/Zip
City Business License #
Telephone #
Designer Name Address City State/Zip Telephone
State License #
6 WORKERS', COMPENSATION """ ' ../:"•'• ^F" *;^ ...;•?*:
Workers Compensation Declaration I hereby affirm under penalty of perjury one of the following declarations
l~1 I have and will maintain a certificate of consent to self-insure for workers compensation as provided by Section 3700 of the Labor Code for the performance
of the work for which this permit is issued
l~l I have and will maintain workers' compensation, as required by Section 3700 of the Labor Code for the performance of the work for which this permit is
issued My worker's compensation insurance carrier and policy number are
Insurance Company Policy No Expiration Date
(THIS SECTION NEED NOT BE COMPLETED IF THE PERMIT IS FOR ONE HUNDRED DOLLARS [$100] OR LESS)
l~l CERTIFICATE OF EXEMPTION I certify that in the performance of the work for which this permit is issued, I shall not employ any person in any manner so as
to become subject to the Workers' Compensation Laws of California
WARNING Failure to secure workers compensation coverage is unlawful and shall subject an employer to criminal penalties and civil fines up to one hundred
thousand dollars ($100 000) in addition to the cost of compensation damages as provided for in Section 3706 of the Labor code interest and attorney s fees
SIGNATURE DATE
7 ;;;OWNER-BUILbER DECLARATION '"" '" ™ • ;M 1 V:lf:""
I hereby affirm that I am exempt from the Contractor's License Law for the following reason
Cl I, as owner of the property or my employees with wages as their sole compensation will do the work and the structure is not intended or offered for sale
(Sec 7044, Business and Professions Code The Contractor's License Law does not apply to an owner of property who builds or improves thereon, and who does
such work himself or through his own employees, provided that such improvements are not intended or offered for sale If however the building or improvement is
sold within one year of completion, the owner-builder will have the burden of proving that he did not build or improve for the purpose of sale)
l~l I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec 7044 Business and Professions Code The
Contractor's License Law does not apply to an owner of property who builds or improves thereon, and contracts for such projects with contractor(s) licensed
pursuant to the Contractor s License Law)
1~1 I am exempt under Section Business and Professions Code for this reason
1 I personally plan to provide the major labor and materials for construction of the proposed property improvement l~l YES PINO
2 I (have / have not) signed an application for a building permit for the proposed work
3 I have contracted with the following person (firm) to provide the proposed construction (include name / address / phone number / contractors license number)
4 I plan to provide portions of the work, but I have hired the following person to coordinate, supervise and provide the major work (include name / address / phone
number / contractors license number) __^
5 I will provide some of the work, but I have contracted (hired) the following persons to provide the work indicated (include name / address / phone number / type
of work)
PROPERTY OWNER SIGNATURE DATE
COMPLETE THIS SECTION FOR NON-RES/DENTIALiBUILbHiG PERMITS ONLY S5 11= ,
Is the applicant or future building occupant required to submit a business plan acutely hazardous materials registration form or risk management and prevention
program under Sections 25505, 25533 or 25534 of the Presley-Tanner Hazardous Substance Account Act? d YES d NO
Is the applicant or future building occupant required to obtain a permit from the air pollution control district or air quality management district' l~l YES l~l NO
Is the facility to be constructed within 1,000 feet of the outer boundary of a school site? l~l YES l~l NO
IF ANY OF THE ANSWERS ARE YES A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR IS MEETING THE
REQUIREMENTS OF THE OFFICE OF EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT
8.,i: CONSTRUCTION LENDING AGENCYB ,s™r • ,"" • .. '-• " : " ,;. :1 ;'...,,..
I hereby affirm that there is a construction lending agency for the performance of the work for which this permit is issued (Sec 3097(0 Civil Code)
LENDER'S NAME LENDER S ADDRESS __________
9 APPUCANrCERTIFiCATIpNl; „,.;...-... . ,. li''';. .. Hr" ;SJ:i;r'" *•' _,..... "E-"'
I certify that I have read the application and state that the above information is correct and that the information on the plans is accurate I agree to comply with all
City ordinances and State laws relating to building construction I hereby authorize representatives of the CitV of Carlsbad to enter upon the above mentioned
property for inspection purposes I ALSO AGREE TO SAVE INDEMNIFY AND KEEP HARMLESS THE CITY OF CARLSBAD AGAINST ALL LIABILITIES
JUDGMENTS, COSTS AND EXPENSES WHICH MAY IN ANY WAY ACCRUE AGAINST SAID CITY IN CONSEQUENCE OF THE GRANTING OF THIS PERMIT
OSHA An OSHA permit is required for excavations over 5'0" deep and demolition or construction of structures over 3 stories in height
EXPIRATION Every permit issued by the building Official under the provisions of this Code shall expire by limitation and become null and void if the building or work
authorized by such permit is not commenced within 180 days from the date of such permit or if the building or work authorized by such permit is suspended or abandoned
at any time after the work is commenced fon^tpsftodflj^O^lay^Section 106 4 4 Uniform Building Code)
APPLICANT'S SIGNATURE /\ V^-^y/VV/Z DATE
YELLOW Applicant PINK Finance
City of Carlsbad
Building Department
December 14, 2005
GEORGE MONTELLO
4715 60™ ST
SAN DIEGO CA 92115
RE:
APPLICATION DATE 03/18/2005
PLAN CHECK # CB050917
ADDRESS 2290 COSMOS CT
EXPIRATION DATE 03/18/2006
PERMIT TYPE TI
DESCRIPTION SIERRA WIRELESS 690SF TI
You applied to have your plans checked on the date noted above To date, the related building
permit has not been obtained The original plan review application will expire as no building
permit has been issued
Plans submitted and not retrieved from the building department prior to the plan check
expiration date noted above will be destroyed
The provisions of sections 304 (d) of the Uniform Building Code state
"Section 304 9d) Expiration of Plan Review
Applications for which no permit is issued within one year following the date of
application shall expire by limitation, and plans and other data submitted for review
may thereafter be returned to the applicant or destroyed by the Building Official
In order to renew action on an application after expiration, the applicant shall resubmit
plans and pay a new plan review fee "
In order to provide better service, please indicate your handling choice for the plans originally
submitted and return this letter to the Building Department
Project Abandoned -1 will pick up the plans within 10 days
Project Abandoned - Plans may be destroyed
If you have any questions, please contact the Building Department at (760) 602-2719
Building Department
1635 Faraday Avenue • Carlsbad, CA 92008-7314 • (760) 602-2700 • FAX (760) 602-856O
EsGii Corporation
In (Partnership with government for (Bui fifing Safety
DATE 4/28/05
jg JURIS^
JURISDICTION City of Carlsbad a PLAN REVIEWER
a FILE
PLAN CHECK NO 05-0917 SET II
PROJECT ADDRESS 2290 Cosmos court
PROJECT NAME Sierra Wireless Chamber Room - TI
The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes
The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff
The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck
The check list transmitted herewith is for your information The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck
The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person
XI The applicant's copy of the check list has been sent to
Terry Montello
4715 60th Street, San Diego, CA 92115
Esgil Corporation staff did not advise the applicant that the plan check has been completed
XI Esgil Corporation staff did advise the applicant that the plan check has been completed
Person contacted Terry Montello Telephones 619-994-5557
Date contacted c/M^(by fa) Fax # 619-229-0642
Mal^^^Telephone Fax •'""'in Person
REMARKS
By Steve Sanders for Doug Moody Enclosures
Esgil Corporation
D GA D MB D EJ D PC 4/22/05 trnsmtldot
9320 Chesapeake Drive, Suite 208 + San Diego, California 92123 + (858)560-1468 + Fax (858) 560-1576
City of Carlsbad O5-0917
4/28/05
RECHECK PLAN CORRECTION LIST
JURISDICTION City of Carlsbad PLAN CHECK NO 05-0917
PROJECT ADDRESS 2290 Cosmos court SET II
DATE PLAN RECEIVED BY DATE RECHECK COMPLETED
ESGIL CORPORATION 4/22/05 4/28/05
REVIEWED BY Steve Sanders for Doug Moody
FOREWORD (PLEASE READ):
This plan review is limited to the technical requirements contained in the Uniform Building Code,
Uniform Plumbing Code, Uniform Mechanical Code, National Electrical Code and state laws
regulating energy conservation, noise attenuation and disabled access This plan review is
based on regulations enforced by the Building Department You may have other corrections
based on laws and ordinances enforced by the Planning Department, Engineering Department
or other departments
The following items listed need clarification, modification or change All items must be satisfied
before the plans will be in conformance with the cited codes and regulations Per Sec 106 4 3,
1997 Uniform Building Code, the approval of the plans does not permit the violation of any
state, county or city law
A Please make all corrections on the original tracings and submit two new complete sets of
prints to ESGIL CORPORATION
B To facilitate rechecking, please identify, next to each item, the sheet of the plans upon
which each correction on this sheet has been made and return this sheet with the
revised plans
C The following items have not been resolved from the previous plan reviews The original
correction number has been given for your reference In case you did not keep a copy of
the prior correction list, we have enclosed those pages containing the outstanding
corrections Please contact me if you have any questions regarding these items
D Please indicate here if any changes have been made to the plans that are not a result of
corrections from this list If there are other changes, please briefly describe them and where
they are located on the plans Have changes been made not resulting from this list?
GYes aNo
City of Carlsbad 05-0917
4/28/05
Please make all corrections on the original tracings, as requested in the correction
list Submit three sets of plans for commercial/industrial projects (two sets of plans
for residential projects) For expeditious processing, corrected sets can be
submitted in one of two ways
1 Deliver all corrected sets of plans and calculations/reports directly to the City of
Carlsbad Building Department, 1635 Faraday Ave , Carlsbad, CA 92008, (760)
602-2700 The City will route the plans to EsGil Corporation and the Carlsbad
Planning, Engineering and Fire Departments
2 Bring one corrected set of plans and calculations/reports to EsGil Corporation,
9320 Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-1468
Deliver all remaining sets of plans and calculations/reports directly to the City of
Carlsbad Building Department for routing to their Planning, Engineering and Fire
Departments
NOTE Plans that are submitted directly to EsGil Corporation only will not be
reviewed by the City Planning, Engineering and Fire Departments until review by
EsGil Corporation is complete
4 Please provide complete construction plans and details for the new chamber If
an assembly please provide the listing and installation information Please
provide Listing number from a recognized testing laboratory or provide
structural calculations from a California State licensed Architect or
Engineer for the RF Chamber to be assembled on site. Provide mechanical
ventilation for the RF Chamber capable of supplying outside air at a
minimum rate of 15 cubic feet per minute per occupant. UBC, Section
12022.1
5 Please provide a door schedule, indicate the type of hardware and reference the
doors on the floor plan Note D1 sheet AO.2 does not indicate door hardware
for all doors. Please provide a door schedule as requested
6 Specify lever-type hardware for passage doors on floors accessible to the
disabled Title 24 Note D1 sheet AO.2 does not specify lever type hardware
for all passage doors. Please show lever type hardware on the door
schedule.
9 Please provide panel schedules, indicate new and existing loads Please show
branch circuit serving the 30 amp. filter on the new R. F. Shielded Room as
specified on the Installation Manuel supplied by Raymond EMC.
City of Carlsbad O5-0917
4/28/O5
To speed up the review process, note on this list (or a copy) where each
correction item has been addressed, i e , plan sheet, note or detail number,
calculation page, etc
Please indicate here if any changes have been made to the plans that are not a
result of corrections from this list If there are other changes, please briefly
describe them and where they are located in the plans
Have changes been made to the plans not resulting from this correction list?
Please indicate
Yes Q No a
The jurisdiction has contracted with Esgil Corporation located at 9320 Chesapeake
Drive, Suite 208, San Diego, California 92123, telephone number of
858/560-1468, to perform the plan review for your project If you have any
questions regarding these plan review items, please contact Steve Sanders for
Doug Moody at Esgil Corporation Thank you
-I ...-—.!_.._-
EsGil Corporation
In (Partnership with government for (BmCtfing Safety
DATE 3/30/O5
JURISDICTION City of Carlsbad O~TO\NREVIEWER
a FILE
PLAN CHECK NO 05-0917 SET I
PROJECT ADDRESS 2290 Cosmos court
PROJECT NAME Sierra Wireless Chamber Room - TI
The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes
The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff
The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck
XI The check list transmitted herewith is for your information The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck
I The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person
X] The applicant's copy of the check list has been sent to
Terry Montello
4715 60th Street, San Diego, CA 92115
I Esgil Corporation staff did not advise the applicant that the plan check has been completed
XI Esgil Corporation staff did advise the applicant that the plan check has been completed
Person contacted Terry Montello Telephone # 619-994-5557
Date contacted 3/3//D5(by/^v>) Fax # 619-229-0642
Mail ^-Telephone Fax---' In Person
REMARKS
By Doug Moody Enclosures
Esgil Corporation
D GA D MB D EJ D PC 3/21/05 trnsmtldot
9320 Chesapeake Drive, Suite 208 4 San Diego, California 92123 •* (858)560-1468 + Fax (858) 560-1576
City of Carlsbad O5-O917
3/30/05
PLAN REVIEW CORRECTION LIST
TENANT IMPROVEMENTS
PLAN CHECK NO O5-0917
OCCUPANCY B
TYPE OF CONSTRUCTION VN
ALLOWABLE FLOOR AREA
SPRINKLERS'? YES
REMARKS
DATE PLANS RECEIVED BY
JURISDICTION 3/18/05
DATE INITIAL PLAN REVIEW
COMPLETED 3/30/05
JURISDICTION City of Carlsbad
USE Testing?
ACTUAL AREA 690sf
STORIES 1
HEIGHT
OCCUPANT LOAD 6
DATE PLANS RECEIVED BY
ESGIL CORPORATION 3/21/05
PLAN REVIEWER Doug Moody
FOREWORD (PLEASE READ)-
This plan review is limited to the technical requirements contained in the Uniform Building Code,
Uniform Plumbing Code, Uniform Mechanical Code, National Electrical Code and state laws
regulating energy conservation, noise attenuation and access for the disabled This plan review
is based on regulations enforced by the Building Department You may have other corrections
based on laws and ordinances enforced by the Planning Department, Engineering Department,
Fire Department or other departments Clearance from those departments may be required
prior to the issuance of a building permit
Code sections cited are based on the 1997 UBC
The following items listed need clarification, modification or change All items must be satisfied
before the plans will be in conformance with the cited codes and regulations Per Sec 106 4 3,
1997 Uniform Building Code, the approval of the plans does not permit the violation of any
state, county or city law
To speed up the recheck process, please note on this list (or a copy) where each
correction item has been addressed, i.e.. plan sheet number, specification section, etc.
Be sure to enclose the marked up list when you submit the revised plans.
TENANT IMPROVEMENTS WITHOUT SPECIFIC ENERGY DATA OR POLICY SUPPLEMENTS (1997UBC)tiforw dot
City of Carlsbad O5-O917
3/30/05
Please make all corrections on the original tracings, as requested in the correction
list Submit three sets of plans for commercial/industrial projects (two sets of plans
for residential projects) For expeditious processing, corrected sets can be
submitted in one of two ways
1 Deliver all corrected sets of plans and calculations/reports directly to the City of
Carlsbad Building Department, 1635 Faraday Ave , Carlsbad, CA 92008, (760)
602-2700 The City will route the plans to EsGil Corporation and the Carlsbad
Planning, Engineering and Fire Departments
2 Bring one corrected set of plans and calculations/reports to EsGil Corporation,
9320 Chesapeake Dnve, Suite 208, San Diego, CA 92123, (858) 560-1468
Deliver all remaining sets of plans and calculations/reports directly to the City of
Carlsbad Building Department for routing to their Planning, Engineering and Fire
Departments
NOTE Plans that are submitted directly to EsGil Corporation only will not be
reviewed by the City Planning, Engineering and Fire Departments until review by
EsGil Corporation is complete
1 Each sheet of the plans must be signed by the person responsible for their
preparation, even though there are no structural changes Business and
Professions Code
2 Provide a statement on the Title Sheet of the plans stating that this project shall
comply with the 2001 edition of the California Building Code (Title 24), which
adopts the 1997 UBC, 2000 UMC, 2000 UPC and the 1999 NEC
3 A complete description of the activities and processes that will occur in this
tenant space should be provided A listing of all hazardous materials should be
included The materials listing should be stated in a form that would make
classification in Tables 3-D and 3-E possible The building official may require a
technical report to identify and develop methods of protection from hazardous
materials Section 307 1 6
4 Please provide complete construction plans and details for the new chamber If
an assembly please provide the listing and installation information
5 Please provide a door schedule, indicate the type of hardware and reference the
doors on the floor plan
6 Specify lever-type hardware for passage doors on floors accessible to the
disabled Title 24
7 Please note on the plans "AC Cable is not allowed in A, B, E, H, and I
occupancies NM cable is restricted (without City approval) to one and two
family dwellings Note on plans that an equipment ground conductor is to be
installed in all flexible conduits"
City of Carlsbad 05-O917
3/3O/O5
8 It appears the lighting system is to be altered, if so please provide complete
plans Please provide the required energy compliance forms The LTG forms
shall be signed and imprinted on the plans
9 Please provide panel schedules, indicate new and existing loads
10 Please provide an equipment schedule of the equipment to be installed as part
of the chamber
11 When new rooms or spaces are constructed and the existing mechanical system
is not to be altered other than relocation of existing duct work, please note or
show mechanical ventilation will be provided capable of supplying outside air at a
minimum rate of 15 cubic feet per minute per occupant UBC, Section 1202 2 1
To speed up the review process, note on this list (or a copy) where each
correction item has been addressed, i e , plan sheet, note or detail number,
calculation page, etc
Please indicate here if any changes have been made to the plans that are not a
result of corrections, from this list If there are other changes, please briefly
describe them and where they are located in the plans
Have changes been made to the plans not resulting from this correction list?
Please indicate
Yes Q No a
The jurisdiction has contracted with Esgil Corporation located at 9320
Chesapeake Drive, Suite 208, San Diego, California 92123, telephone number of
858/560-1468, to perform the plan review for your project If you have any
questions regarding these plan review items, please contact Doug Moody at
Esgil Corporation Thank you
City of Carlsbad O5-0917
3/3O/O5
VALUATION AND PLAN CHECK FEE
JURISDICTION City of Carlsbad
PREPARED BY Doug Moody
BUILDING ADDRESS 2290 Cosmos court
PLAN CHECK NO 05-0917
DATE 3/30/05
BUILDING OCCUPANCY B TYPE OF CONSTRUCTION VN
BUILDING
PORTION
Tl
Air Conditioning
Fire Sprinklers
TOTAL VALUE
Jurisdiction Code
AREA
(Sq Ft)
690
cb
Valuation
Multiplier
City Valuation
-
By Ordinance
Reg
Mod
VALUE ($)
21,390
21,390
1994 UBC Building Permit Fee
1994 UBC Plan Check Fee
Type of Review
D Repetitive Fee
Repeats
Complete Review
D Other
r—1 Hourly
Structural Only
Hour*
Esgil Plan Review Fee
$19209
$12486
$10757
Comments
Sheet 1 of 1
macvalue doc
PLANNING/ENGINEERING APPROVALS
PERMIT NUMBER CB
ADDRESS
DATE
RESIDENTIAL
RESIDENTIAL ADDITION MINOR
« $1O.OOO.OO)
PLAZA CAMINO REAL
CARLSBAD COMPANY STORES
VILLAGE FAIRE
COMPLETE OFFICE BUILDING
OTHER
PLANNER DATE
ENGINEER DATE
Carlsbad Fire Department 050917
1635 Faraday Ave
Carlsbad, CA 92008
Plan Review
Date of Report
Fire Prevention
(760} 602-4660
Requirements Category:
03/22/2005
Building Plan
Reviewed by
Name
Address
City, State
Terry Montello
4715 60th Street
San Diego CA 92115
Plan Checker
Job Name
Job Address
JTTI Approved
Job# 050917
Sierra Wireless
2290 Cosmos Ct
Bldg# CB050917
Ste orBldg No
The item you have submitted for review has been approved The approval is
based on plans, information and / or specifications provided in your submittal,
therefore any changes to these items after this date, including field
modifications, must be reviewed by this office to insure continued conformance
with applicable codes and standards Please review carefully all comments
attached as failure to comply with instructions in this report can result in
suspension of permit to construct or install improvements
D Approved
Subject to
The item you have submitted for review has been approved subject to the
attached conditions The approval is based on plans, information and/or
specifications provided in your submittal Please review carefully all comments
attached, as failure to comply with instructions in this report can result in
suspension of permit to construct or install improvements Please resubmit to
this office the necessary plans and / or specifications required to indicate
compliance with applicable codes and standards
D Incomplete The item you have submitted for review is incomplete At this time, this office
cannot adequately conduct a review to determine compliance with the
applicable codes and / or standards Please review carefully all comments
attached Please resubmit the necessary plans and / or specifications to this
office for review and approval
Review
FDJob#
1st 9n<1 3rd
050917 FDFile#
Other Agenry ID
Carlsbad Fire Department _ °50917
less Faraday Ave Fire Prevention
j- Carlsbad, CA 92008 (760) 602-4660
Plan Review
Date of Report Q3/22/2005 _ Reviewed by _
Name Terry Montello
Address 4715 60th Street
City, State San Diego CA 92115
Plan Checker £!££1Z
Job Name Sierra Wireless
Job Address 2290 Cosmos ct Ste or Bldg No
Fire Department shall require a plan indicating fire sprinkler coverage or improvements to existing
Q
8
S oin po <°U V)
o <f>0> LLJ
01
UJoo