HomeMy WebLinkAbout2335 CAMINO VIDA ROBLE; ; CB971326; PermitBUILDING PERMIT
06/09/97 08:08
Page 1 of 1
Job Address: 2335 CAMINO VIDA ROBLE Suite
Permit Type: INDUSTRIAL TENANT IMPROVEMENT
Parcel No: 213-050-27-00 Lot#:
Valuation: . 56,576
Occupancy Group: Reference*:
Description: MOVE WALLS,REMODEL BATHROOMS
: FIRST CLASS MARKETING
Permit No:
Project. No:
.Development No:
5742 06/09/97 0001 01
C-PRHT
Construction Type:
Status;
Applied:
Apr/Issue:
Entered By:
CB97132G
A97C1713
02
628-00
Appl/Ownr : VENTI CONSTRUCTION
1095 MEMORY LN
ESCONDIDO CA 920
*** Fees Required ***
760 747-9590
pileeted & Credits
Fees:
Adjustments :
Total Fees:
91
Fee description
Building Permit
Plan Check
Strong Motion Fee
* BUILDING TOTAL
Enter "Y" for Plu
Each Plumbing Fixt
Each Install/Repai
A PLUMBING TOTAL
Enter "Y" for Electr
Remodel/Alter Per AM
* ELECTRICAL TOTAL
Enter 'Y' for Mechani
Install Furn/Ducts/Heat
* MECHANICAL TOTAL
IIIN
ISSUED
05/21/97
06/09/97
RMA
* * *
.00
230,00
628.00
Ext fee Data
cal
446
290
12
748
20
84
7
111
10
25
35
15
9
24
. 00
.00
.00
.00
. 00
.00
.on
. 00
. 00
.00
.00
. 00
.00
, OQ
y
Y
Y
CITY OF CARLSBAD
Dr., Carlsbad, CA 92009 (619) 438-1161
PERMIT APPLICATION
CITY OF CARLSBAD BUILDING DEPARTMENT
2075 Las Palmas Dr., Carlsbad CA 92009
(760)438-1161
FOR OFFICE USE ONLY
PLAN CHECK NO.
. VAL.j 57
Plan Ck. Deposit
Validated By_
Date
•e
Business Name (at this address)
Assessgj-ex
Name
lUtSUQun
Address j ' City
m^^^^^i^^^Q^fiif^^^^MI^^ 'foriCMivhlH -,
State/Zip Telephone #Fax*
£l^(F fffl02jfa
City State/Zip Telephone #
City State/Zip Telephone #
(Sec. 7031.5 Business and Professions Code: Any City or County which requires a permit to construct, alter, improve, demolish or repair any structure, prior to its
issuance, also requires the applicant for such permit to file a signed statement that he is licensed pursuant to the provisions of the Contractor's License Law
[Chapter 9, commending with Section 7000 of Division 3 of the Business and Professions Code] or that he is exempt therefrom, and the basis for the alleged
exemption. Any yjojation of Section 7031.5 by any applicant for a permit subjects the applicant to a civil penalty of not rpore than five hundred dollars [$500]}.
ffeun L /-
State License #
'Address
License Class ~( cvt*
City State/Zip Telephone #
City Business License # / Cr~& *~[ ^y JT\
Designer Name
State License #
||jTfeli.-Aj£CVV Address 0C.Citv 6. 0,State/Zip Telehone
3MPENSAT10N
Workers' Compensation Declaration: I hereby affirm under penalty of perjury one of the following declarations:
[U I have and will maintain a certificate of consent to self-insure for workers' compensation as provided by Section 3700 of the Labor Code, for the performance
of the work for which this permit is issued.
I have and will maintain workers' compensation, as required by Section 3700 of the Labor Code, for the performance of the work for which this permit is
issued. My worker's compensation insurancecarrier and policy numbar are: j*i_—* * *~ *• I
Insurance Company ^~~>]f*u IE ^\\J r^ *^ Policy No. \(J n£>C.Lc.'~'t"l f Expiration Date Oft
(THIS SECTION NEED NOT BE COMplETED \F THE* PERMIT IS FOR ONE HUNDRED DOLLARS [$100] OR LESS) *
D CERTIFICATE OF KtfiMPTION: I certify that in the/performance of the work for which this permit is issued, I shall not employ any person in any manner so as
to become subject tp^ne Vyorkers' Compensation Law^
WARNING: Fall
thousand doll a
SIGNATURE,
&
ereby af
unlawful, and shall subject an employer to criminal penalpes and/civil fines up to one hundred
, damages as provided for in Section 3706 of the LgbprAode, Merest and attorney's fees.DATE 6727 A7 7
that I am exempt from the Contractor's License Law for the following reason:
I, as owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not intended or offered for sale
(Sec. 7044, Business and Professions Code: The Contractor's License Law does not apply to an owner of property who builds or improves thereon, and who does
such work himself or through his own employees, provided that such improvements are not intended or offered for sale. If, however, the building or improvement is
sold within one year of completion, the owner-builder will have the burden of proving that he did not build or improve for the purpose of sale).
n I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions Code: The
Contractor's License Law does not apply to an owner of property who builds or improves thereon, and contracts for such projects with contractor(s) licensed
pursuant to the Contractor's License Law).
Q I am exempt under Section Business and Professions Code for this reason:
1. I personally plan to provide the major labor and materials for construction of the proposed property improvement. Q YES GNO
2. I (have / have not) signed an application for a building permit for the proposed work.
3. I have contracted with the following person (firm) to provide the proposed construction (include name / address / phone number / contractors license number):
4. I plan to provide portions of the work, but I have hired the following person to coordinate, supervise and provide the major work (include name / address / phone
number / contractors license number):
5, I will provide some of the work, but I have contracted (hired) the following persons to provide the work indicated (include name / address / phone number / type
of work): _____^ . ____
PROPERTY OWNER SIGNATURE DATE
Is the applicant or future building occupant required to submit a business plan, acutely hazardous materials registration form or risk management and prevention
program under Sections 25505, 25533 or 25534 of the Presley-Tanner Hazardous Substance Account Act? Q YES
r-,Is the applicant or future building occupant required to obtain a permit from the air pollution control district or air quality management district? Q YES
Is the facility to be constructed within 1,000 feet of the outer boundary of a school site? Q YES
NO
IF ANY OF THE ANSWERS ARE YES, A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR IS MEETING THE
REQUIREMENTS OF THE OFFICE OF EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT.
I hereby affirm that there iste construction lending agency for the performance of the work for which this permit is issued (Sac. 3097(i) Civil Code).
LENDER'S NAME KJ /A LENDER'S ADDRESS
I certify that I have read the application and state that the above information is correct and that the information on the plans is accurate. I agree to comply with all
City ordinances and State laws relating to building construction, I hereby authorize representatives of the CitV of Carlsbad to enter upon the above mentioned
property for inspection purposes. I ALSO AGREE TO SAVE, INDEMNIFY AND KEEP HARMLESS THE CITY OF CARLSBAD AGAINST ALL LIABILITIES,
JUDGMENTS, COSTS AND EXPENSES WHICH MAY IN ANY WAY ACCRUE AGAINST SAID CITY IN CONSEQUENCE OF THE GRANTING OF THIS PERMIT.
OSHA: An OSHA permit is required for excavations over 5'0" deep and demolition or construction of structures over 3 stories in height.
EXPIRATION: Every permit issue dj»y-*be Building Official under th/ provisions of this Code shall expire by limitation and become null and void if the building or
work authorized by such permitXnot commenced within 365 days' from the date of such permit or if the building or work authorized by fuch permit is suspended
or abandoned at anytime afteOhe work/is commenceoj^br ayperio/l of 1 80 days {Section 1 06.4,4 Uniform Building Code).
APPLICANT'S S1GNATU '{/^4f L SATE
1TE: File YELLOW: Applicant PINK: Finance
07/27/98 • • INSPECTION HISTORY LISTING
FOR PERMIT* CB971326
DATE INSPECTION TYPE INSP ACT COMMENTS
06/30/97 Rough Combo PD NR
06/17/97 Interior Lath/Drywall PD AP
06/13/97 Frame/Steel/Bolting/Wei PD AP
06/12/97 Underground/Under Floor PD AP
HIT <RETURN> TO CONTINUE...
CITY OF CARLSBAD
INSPECTION REQUEST
PERMIT* CB971326 FOR 06/30/97
DESCRIPTION: MOVE WALLS,REMODEL BATHROOMS
FIRST CLASS MARKETING
TYPE: ITI
JOB ADDRESS
APPLICANT:
; 2335 CAMINO VIDA ROBLE
VENTI CONSTRUCTION
CONTRACTOR:
OWNER:
REMARKS: R/ARNIE/735-0562
SPECIAL INSTRUCT:
PHONE:
PHONE:
PHONE:
INSPECTOR AREA PD
PLANCK# CB971326
OCC GRP
CONSTR. TYPE IIIN
STE: LOT:
760 747-9590
INSPECTO
TOTAL TIME:
—RELATED PERMITS-PERMIT* TYPE
CB911015 MISC
AS940057 ASTI
CO940099 COFO
STATUS
EXPIRED
ISSUED
ISSUED
CD
14
24
34
44
LVL DESCRIPTION
ST Frame/Steel/Bolting/Welding
PL Rough/Topout
EL Rough Electric
ME Rough/Ducts/Dampers
ACT COMMENTS
***** INSPECTION HISTORY *****
DATE DESCRIPTION ACT INSP
061797 Interior Lath/Drywall AP PD
061397 Frame/Steel/Bolting/Welding AP PD
061297 Underground/Under Floor AP PD
COMMENTS
EsGil Corporation
Professional!Pfan !%ez>ieztJ "Engineers
DATE: 6/6/97 O^APPtt^ANT
JURISDICTION: Carlsbad ^Q-TCXl
Q FILE
PLAN CHECK NO.: 97-1326 SET: II
PROJECT ADDRESS: 2335 Camino Vida Roble
PROJECT NAME: 1st Class Marketing TI
• The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
The applicant's copy of the check list has been sent to:
Esgil Corporation staff did not advise the applicant that the plan check has been completed.
Esgil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Telephone #:
Date contacted: (by: ) Fax #:
Mail Telephone Fax In Person
REMARKS:
By: Chuck Mendenhall Enclosures:
Esgil Corporation
D GA D CM D EJ D PC Walk in trnsmtl.dot
9320 Chesapeake Drive, Suite 208 + San Diego, California 92123 + (619)560-1468 + Fax (619) 560-1576
EsGil Corporation
ProfessionalTfon Review) 'Engineers
DATE: 5/30/97 Q APPLICANT
JURISDICTION: Carlsbad a-FtANREVIEWER
a FILE
PLAN CHECK NO.: 97-1326 SET: I
PROJECT ADDRESS: 2335 Camino Vida Roble
PROJECT NAME: 1st Class Marketing TI
The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
The remarks below are transmitted herewith for your information. The plans are being held at
Esgil Corporation until corrected plans are submitted for recheck. Submit 3 sets of plans to the
city or 2 sets to the city and one directly to EsGil Corp. for recheck.
The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
The applicant's copy of the check list has been sent to:
Arnold Venti
1095 Memory Ln., Escondido, CA 92026
Esgil Corporation staff did not advise the applicant (except by mail) that the plan check has been
completed.
Esgil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Telephone #:
REMARKS: 1. Show on the site plan the location of the disabled accessible parking and the
disabled access path of travel to the remodeled area. 2. Note on the plans that there is not
change to the HVAC equipment and no change to the lighting load. If this is not the case then
energy compliance documentation is required. 3. Provide DWV plumbing plans for the new
plumbing system. 4. Show on the plans the required exhaust ventilation for the new bath rms. 5.
Show on the plans the location of the supply & return air registers in the new Galley and note
the outside fresh air will equal 15 CFM per occupant per the '94 UBC.
By: Chuck Mendenhall Enclosures:
Esgil Corporation
D GA D CM D EJ D PC 5/22/97 tmsmtl.dot
9320 Chesapeake Drive, Suite 208 + San Diego, California 92123 4- (619)560-1468 4 Fax (619) 560-1576
VALUATION AND PLAN CHECK FEE
JURISDICTION: Carlsbad
PREPARED BY: CM
BUILDING ADDRESS: 2335 Camino Vida Roble
BUILDING OCCUPANCY: B
PLANCHECKNO.: 97-1326
DATE: 5/30/97
TYPE OF CONSTRUCTION: III
BUILDING PORTION
Tl
Air Conditioning
Fire Sprinklers
TOTAL VALUE
BUILDING AREA
(ft-2)
2176
VALUATION
MULTIPLIER
26
VALUE
($)
56,576
56,576
• 1991 UBC Building Permit Fee D Bldg. Permit Fee by ordinance: $446.00
• 1991 UBC Plan Check Fee D Plan Check Fee by ordinance: $ 289.90
Type of Review: • Complete Review tH Structural Only [H Hourly
D Repetitive Fee Applicable D Other:
Esgil Plan Review Fee: $ 231.92
Comments:
Sheet 1 of 1
macvalue.doc 5196
PLANNING/ENGINEERING APPROVALS
PERMIT NUMBER DATE / 7
ADDRESS
RESIDENTIAL TENANT IMPROVEMENT
RESIDENTIAL ADDITION MINOR
« $10,000.00)
PLAZA CAMINO REAL
VILLAGE FAIRE
COMPLETE OFFICE BUILDING
OTHER sW-
d
PLANNER DATE
ENGINEE DATE
C;\WP5 1 \FILES\BLDG.FRM Rev 1 1 /1 5/90
PLANNING DEPARTMENT
BUILDING PLAN CHECK REVIEW CHECKLIST
Plan Check No. CB Address
Planner _Greg Fisher
APN:
Phone (619) 438-1 1 61 , extension 4328
Type of Project and Use:
Zone:Facilities Management Zone:
CFD <in/ojj# #
Circle One (If property in, complete SPECIAL TAX CALCULATION WORKSHEET provided bv Building
Department.)
i i Legend
Item Complete
Item Incomplete - Needs your action
D Environmental Review Required: YES
DATE OF COMPLETION:
NO TYPE
Compliance with conditions of approval? If not, state conditions which require action.
Conditions of Approval
Discretionary Action Required:
APPROVAL/RESO. NO. ._
PROJECT NO. _^____^_
YES NO TYPE
DATE
OTHER RELATED CASES:
Compliance with conditions or approval? If not, state conditions which require action.
Conditions of Approval
Coastal Zone Assessment/Compliance
Project site located in Coastal Zone? YES
CA Coastal Commission Authority? YES
NO
NO
If California Coastal Commission Authority: Contact them at - 3111 Camino Del Rio North, Suite
200, San Diego CA 92108-1725; (619) 521-8036
Determine status (Coastal Permit Required or Exempt):
Coastal Permit Determination Form already completed? YES NO
If NO, complete Coastal Permit Determination Form now.
Coastal Permit Determination Log #:
Follow-Up Actions:
1) Stamp Building Plans as "Exempt" or "Coastal Permit Required" {at minimum
Floor Plans).
2) Complete Coastal Permit Determination Log as needed.
SD
COMPENSATION
INSURANCE
FUND
P.O. BOX 807, SAN FRANCISCO,CA 94101-0807
CERTIFICATE OF WORKERS' COMPENSATION INSURANCE
ISSUE DATE: 05-01-97
POLICY NUMBER: 1076222 - 97
CERTIFICATE EXPIRES: 05-01-98
CONTRACTORS STATE LICENSE BOARD
ATTN: WORKERS' COMP. UNIT
BOX 26000
SACRAMENTO CA 95826
JOB: LIC #326755
INCEPTION DATE: 05-01-97
D.O.: SAN DIEGO
This is to certify that we have issued a valid Workers' Compensation insurance policy in a form approved by the
California Insurance Commissioner to the employer named below for the policy period indicated.
This policy is not subject to cancellation by the Fund except upon 30 days' advance written notice to the employer.
We will also give you 30 days' advance notice should this policy be cancelled prior to its normal expiration.
This certificate of Insurance is not an insurance policy and does not amend, extend or alter the coverage afforded
by the policies listed herein. Notwithstanding any requirement term, or condition of any contract or other document
with respect to which this certificate of insurance may be issued or may pertain, the insurance afforded by the
policies described herein is subject to all the terms, exclusions and conditions of such polrcies.
. .PRESIDENT
EMPLOYER'S LIABILITY LIMIT INCLUDING DEFENSE COSTS: $1 ,000*000. OO PER OCCURRENCE.
STANDARD EXCLUSION: INDIVIDUAL EMPLOYERS AND HUSBAND AND WIFE EMPLOYERS ARE NOT ELIGIBLE
FOR BENEFITS AS EMPLOYEES UNDER THIS POLICY.
ENDORSEMENT 12065 ENTITLED CERTIFICATE HOLDERS' NOTICE EFFECTIVE O5/O1/97 IS ATTACHED TO AND
FORMS A PART OF THIS POLICY.
EMPLOYER LEGAL NAME
VENT I CONSTRUCTION
1095 MEMORY LN
ESCONDIDO CA 92026
VENTI, ARNOLD L.
PRINTED- 04-18-97 POdfiQ
SCIF 10265 (REV. 2-95)
D
D
Inclusionary Housing Fee required: YES NO
(Effective date of Inclusionary Housing Ordinance - May 21, 1993.)
Date Entry Completed? YES NO
Site Plan:
1. Provide a fully dimensional site plan drawn to scale. Show: North arrow,
property lines, easements, existing and proposed structures, streets, existing
street improvements, right-of-way width, dimensional setbacks and existing
topographical lines.
2. Provide legal description of property and assessor's parcel number.
Zoning:
1. Setbacks:
Front:
Int. Side:
Street Side:
Rear:
Required
Required
Required
Required
2. Accessory Structure Setbacks:
Front: Required
Int. Side: Required
Street Side: Required
Rear: Required
| 3. Lot Coverage:Required
Shown
Shown
Shown
Shown
Shown
Shown
Shown
Shown
Shown
D 4. Height:Required Shown
5. Parking: Spaces Required
Guest Spaces Required
Additional Comments ~~
Shown
Shown
OK TO ISSUE AND ENTERED APPROVAL INTO COMPUTER DATE
This is a Patch T type separator she
i
asi Portrait Feed
a
0-
(0to
New Document Follows;
Printed on 5/25/00 at 10:08.
• - CopyrigUCKofaxliMge Products 1994-1999
(ft
Q)
•o0)
0>u.s
(Q
OCO
•O
C
CO
£cument -0
Q
fc.
^
w» •
si
Ion 5/25/00 at 10Kotax lm«8« Product**^ scs 2c £•C 90. §.aoO
05-24-2004
City of Carlsbad
1635 Faraday Av Carlsbad, CA 92008
Commercial/Industrial Permit Permit No: CB033121
Building Inspection Request Line (760) 602-2725
Job Address:
Permit Type:
Parcel No:
Valuation:
Occupancy Group:
Project Title:
2335 CAMINO VIDA ROBLE CBAD
Tl Sub Type: COMM
2130502700 Lot #: 0
$15,090.00 Construction Type: NEW
Reference #:
ONE SOURCE DATA 503 SF Tl
OFFICE TO OFFICE ADD PARTION WALLS
Applicant:
RICHARD AND RICHARD
4305 VIA TERCERO
OCEANSIDE, CA 92056
Status:
Applied:
Entered By:
Plan Approved:
Issued:
Inspect Area:
Plan Check*:
ISSUED
11/17/2003
SB
12/18/2003
12/18/2003
TP
Owner:
WELLS FARGO BANK TR
P O BOX 63700
SAN FRANCISCO CA 94163
Building Permit
Add'l Building Permit Fee
Plan Check
Add'l Plan Check Fee
Plan Check Discount
Strong Motion Fee
Park Fee
LFM Fee
Bridge Fee
BTD #2 Fee
BTD #3 Fee
Renewal Fee
Add'l Renewal Fee
Other Building Fee
Pot. Water Con. Fee
Meter Size
Add'l Pot. Water Con. Fee
Reel. Water Con. Fee
$145.89 Meter Size
$0.00 Add'l Reel. Water Con. Fee
$94.83 Meter Fee
$0.00 SDCWA Fee
$0.00 CFD Payoff Fee
$3.17 PFF
$0.00 PFF (CFD Fund)
$0.00 License Tax
$0.00 License Tax {CFD Fund)
$0.00 Traffic Impact Fee
$0.00 Traffic Impact (CFD Fund)
$0.00 PLUMBING TOTAL
$0.00 ELECTRICAL TOTAL
$0.00 MECHANICAL TOTAL
$0.00 Master Drainage Fee
Sewer Fee
$0.00 Redev Parking Fee
$0.00 Additional Fees
TOTAL PERMIT FEES
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$20.00
$0.00
$0.00
$0.00
$0.00
$0.00
$263.89
Total Fees:$263.89 Total Payments To Date:$263.89 Balance Due:$0.00
Inspector:
FINAL APPROVAL
Date: _5 Clearance:
NOTICE: Please take NOTICE that approval of your project includes the "Imposition" of fees, dedications, reservations, or other exactions hereafter collectively
referred to as fees/exactions." You have 90 days from the date this permit was issued to protest imposition of these fees/exactions. If you protest them, you must
follow the protest procedures set forth in Government Code Section 66020(a), and file the protest and any other required information with the City Manager for
processing in accordance with Carlsbad Municipal Code Section 3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack,
review, set aside, void, or annul their imposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection fees and capacity
changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this project. NOR DOES IT APPLY to any
fees/exactions of which you have previously been given a NOTICE similar to this, or as to which the statute of limitations has previously otherwise,expired.
PERMIT APPLICATION
CITY OF CARLSBAD BUILDING DEPARTMENT
1635 Faraday Ave., Carlsbad, CA 92008
FOR OFFICE USE ONLY
PLAN CHECK
EST. VAL.
Plan Ck. Deposit
ValidatedDate/
Address (include Bldg/Suite Business Name (at this address)23 11/17/03 0002 01 02
Legal Description Lot No.Subdivision Name/Number Unit No.Phase NeJOPTotal # of uni34~-~33
Assessor's Parcel #Existing Use Proposed Use
Fax #
Address City State/Zip Telephone #
Address City State/Zip Telephone #
(Sec. 7031.5 Business and Professions Code: Any City or County which requires a permit to construct, alter, improve, demolish or repair any structure, prior to its
issuance, also requires the applicant for such permit to file a signed statement that he is licensed pursuant to the provisions of the Contractor's License Law
[Chapter 9, commending with Section 7000 of Division 3 of the Business and Professions Code] or that he is exempt therefrom, and the basis for the alleged
exemptiflp. Any violation of Section 7031.5 bv any applicant for ax>ermit subjects the. applicant to a civil pepaity of notfrnore than five Mndred dollars ($500)).
f*frkt ' ~~
Name e Address
State License It (">£/ QO-S-5 License Class
fDesigner Name Address
State License #
City State/Zip * .- Telep'hone 3T •""J^V") "/CS
Citv Business License # / f^ > ~>O5 •?•
City State/Zip Telephone
leer*'' comrjMisatiiVcoverage is unlawful, and shall subject an employer to criminal penalties and civil fines up to one hundred
In addition tp^tfe costlofo^mpensation, damages as provided for in Section 3706 of the Labo/code,/nterest and attorney's fees.
DATE /<?//^/£^»
Workers' Compensation Declaration: I hereby affirm under penalty of perjury one of the following declarations:
Q I have and will maintain a certificate of consent to self-insure for workers' compensation as provided by Section 3700 of the Labor Code, for the performance
of the work for which this permit is issued.
GT—-•! have and will maintain workers' compensation, as required by Section 3700 of the Labor Code, for the performance of the work for which this permit is
issued. My worker's compensation insurance carrier and policy number are:
Insurance Company <~z* HUfH"T Rff yQ ^6^54^5^ Policy No. | lg>\^ \ \ £>Q ^a - Expiration Date /
{THIS SECTION NEED NOT BE COMPLETED IF THE PERMIT IS FOR ONE HUNDRED DOLLARS [$100] OR LESS)
Q CERTIFICATE OF EXEMPTION: I certify that Jn the performance of the work for which this permit is issued, 1 shall not employ any person in any manner so as
to become subject to the Workers' Cqrqoensation Qfews of California.
WARNING: Fajji
thousand dollars ($1
SIGNATURE_
7>,!
I hereby affirm thatTUm exempt frorV-ttletontractor's License Law for the following reason:
n I, as owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not intended or offered for sale
(Sec. 7044, Business and Professions Code: The Contractor's License Law does not apply to an owner of property who builds or improves thereon, and who does
such work himself or through his own employees, provided that such improvements are not intended or offered for sale. If, however, the building or improvement is
sold within one year of completion, the owner-builder will have the burden of proving that he did not build or improve for the purpose of sale).
O I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions Code: The
Contractor's License Law does not apply to an owner of property who builds or improves thereon, and contracts for such projects with contractor(s) licensed
pursuant to the Contractor's License Law).
d I am exempt under Section Business and Professions Code for this reason:
1. I personally plan to provide the major labor and materials for construction of the proposed property improvement. Q YES ONO
2. I (have / have not) signed an application for a building permit for the proposed work.
3. I have contracted with the following person (firm) to provide the proposed construction (include name / address / phone number / contractors license number):
4. I plan to provide portions of the work, but I have hired the following person to coordinate, supervise and provide the major work (include name / address / phone
number / contractors license number):
5. I will provide some of the work, but I have contracted (hired) the following persons to provide the work indicated (include name / address / phone number / type
of work): _^_____ .
PROPERTY OWNER SIGNATURE DATE
Kn M -rii ¥•:'-:;' %yi -4 1 Iff, v j.:>: -.h;.; j : ;.' r ;J & - ? ; =f • -'->i •>. •' '•:,' ..-:., .- = =,-... -, -.A:
Is the applicant or future building occupant required to submit a business plan, acutely hazardous materials registration form or risk management and prevention
program under Sections 25505, 25533 or 25534 of the Presley-Tanner Hazardous Substance Account Act? Q YES Q NO
Is the applicant or future building occupant required to obtain a permit from the air pollution control district or air quality management district? O YES Q NO
Is the facility to be constructed within 1 ,000 feet of the outer boundary of a school site? n YES Q NO
IF ANY OF THE ANSWERS ARE YES, A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR IS MEETING THE
REQUIREMENTS OF THE OFFICE OF EMERGENCY SERVICES AMD THE AIR POLLUTION CONTROL DISTRICT.
I hereby affirm that there is a construction lending agency for the performance of the work for which this permit is issued (Sec. 3097(i) Civil Code),
LENDER'S ADDRESS
I certify that I have read the application and state that the above information is correct and that the information on the plans is accurate. I agree to comply with all
City ordinances and State laws relating to building construction. I hereby authorize representatives of the Citf* of Carlsbad to enter upon the above mentioned
property for inspection purposes. I ALSO AGREE TO SAVE, INDEMNIFY AND KEEP HARMLESS THE CITY OF CARLSBAD AGAINST ALL LIABILITIES,
JUDGMENTS. COSTS AND EXPENSES WHICH MAY IN ANY WAY ACCRUE AGAINST SAID CITY IN CONSEQUENCE OF THE GRANTING OF THIS PERMIT.
OSHA: An OSHA permit is required for excavations over 5'0" deep and demolition or construction of structures over 3 stories in height.
EXPIRATION: Every permit issueaby/the huMw^crticial under the provisions of this Code shall expire by limitation and become null and void if the building or work
Authorized by such permit is not copfrfence^withjn 180 days from the date o( such permit or if the building or work authorized by such permit is suspended or abandoned
it any time alter the work is cgrnr
'APPLICANT'S SIGNATURE*
80 days (Section 106.4.4 Unrform Building Code).
DATE "//7/Q3
WHITE: File YELLOW: Applicant PINK: Finance
City of Carlsbad Bldg Inspection Request
For: 01/16/2004
Permit* CB033121
Title: ONE SOURCE DATA 503 SF Tl
Description: OFFICE TO OFFICE ADD PARTION WALLS
Sub Type: COMM
Inspector Assignment: TP
2335 CAMINO VIDA ROBLE
Lot 0
Type: Tl
Job Address:
Suite:
Location:
APPLICANT RICHARD AND RICHARD
Owner:
Remarks:
Phone: 7605353280
Inspector:
Total Time:
CD Description
19 Final Structural
29 Final Plumbing
39 Final Electrical
49 Final Mechanical
Requested By: PABLO
Entered By: CHRISTINE
Act Comment
Associated PCRs/CVs
Inspection History
Date Description Act Insp Comments
12/31/2003 17 Interior Lath/Drywall AP TP
12/29/2003 18 Exterior Lath/Drywall NR TP BLDG LOCKED
12/22/2003 14 Frame/Steel/Bolting/Welding AP TP
EsGil Corporation
In (Partnership witfi government for <Buitifing Safety
DATE: December 10, 2003
JURIS,
JURISDICTION: Carlsbad a>tANREVlEWER
a FILE
PLAN CHECK NO.: O3-3121 SET: II
PROJECT ADDRESS: 2335 Camino Vida Roble
PROJECT NAME: One Source Data TI
H The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
The applicant's copy of the check list has been sent to:
Esgil Corporation staff did not advise the applicant that the plan check has been completed.
Esgil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Telephone #:
Date contacted: (by: ) Fax #:
Mail Telephone Fax In Person
REMARKS:
By: Bryan Zuppiger Enclosures:
Esgil Corporation
D GA D MB D EJ D PC 12/05/03 tmsmtl.dot
9320 Chesapeake Drive, Suite 208 ^ San Diego, California 92123 + (858)560-1468 4 Fax (858) 560-1576
EsGil Corporation
In (Partnership witR government for <BuihRng Safety
DATE: November 26, 2003 Q
JURISDICTION: Carlsbad a PLAN REVIEWER
Q FILE
PLAN CHECK NO.: 03-3121 SET: I
PROJECT ADDRESS: 2335 Camino Vida Roble
PROJECT NAME: One Source Data TI
The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
The applicant's copy of the check list has been sent to:
Gary Seward
234 Venture Street Suite 100 San Marcos CA ?????
Esgil Corporation staff did not advise the applicant that the plan check has been completed.
Esgil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Gary Seward Telephone #: 760 759 2260
Date contacted: | zJ.f e>3 (by: (^) Fax #: 760 759 2269
Mail (/Telephone Faxt/ In Person
REMARKS:
By: Bryan Zuppiger Enclosures:
Esgil Corporation
D GA D MB D EJ D PC 11/18/03 trnsmtl.dot
9320 Chesapeake Drive, Suite 208 + San Diego, California 92123 * (858)560-1468 * Fax (858) 560-1576
Carlsbad 03-3121
November 26, 2003
PLAN REVIEW CORRECTION LIST
TENANT IMPROVEMENTS
PLAN CHECK NO.: 03-3121 JURISDICTION: Carlsbad
OCCUPANCY: B USE: Office
TYPE OF CONSTRUCTION: VN ACTUAL AREA: 5867
ALLOWABLE FLOOR AREA: 8000 STORIES: 1
HEIGHT: n/a
SPRINKLERS?: unknown OCCUPANT LOAD: 100
REMARKS:
DATE PLANS RECEIVED BY DATE PLANS RECEIVED BY
JURISDICTION: ESGIL CORPORATION: 11/18/03
DATE INITIAL PLAN REVIEW PLAN REVIEWER: Bryan Zuppiger
COMPLETED: November 26, 2003
FOREWORD (PLEASE READ):
This plan review is limited to the technical requirements contained in the Uniform Building Code,
Uniform Plumbing Code, Uniform Mechanical Code, National Electrical Code and state laws
regulating energy conservation, noise attenuation and access for the disabled. This plan review
is based on regulations enforced by the Building Department. You may have other corrections
based on laws and ordinances enforced by the Planning Department, Engineering Department,
Fire Department or other departments. Clearance from those departments may be required
prior to the issuance of a building permit.
Code sections cited are based on the 1997 UBC.
The following items listed need clarification, modification or change. All items must be satisfied
before the plans will be in conformance with the cited codes and regulations. Per Sec. 106.4.3,
1997 Uniform Building Code, the approval of the plans does not permit the violation of any
state, county or city law.
To speed up the recheck process, please note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet number, specification section, etc.
Be sure to enclose the marked up list when you submit the revised plans.
TENANT IMPROVEMENTS WITHOUT SPECIFIC ENERGY DATA OR POLICY SUPPLEMENTS (1997UBC) tiforw.dot
Carlsbad 03-3121
November 26, 2003
• PLANS
1. Please make all corrections on the original tracings, as requested in the correction
list. Submit three sets of plans for commercial/industrial projects (two sets of plans
for residential projects). For expeditious processing, corrected sets can be
submitted in one of two ways:
a) Deliver all corrected sets of plans and calculations/reports directly to the
City of Carlsbad Building Department, 1635 Faraday Ave., Carlsbad, CA
92008, and (760) 602-2700. The City will route the plans to EsGil
Corporation and the Carlsbad Planning, Engineering and Fire Departments.
b) Bring one corrected set of plans and calculations/reports to EsGil
Corporation, 9320 Chesapeake Drive, Suite 208, San Diego, CA 92123,
and (858) 560-1468. Deliver all remaining sets of plans and
calculations/reports directly to the City of Carlsbad Building Department for
routing to their Planning, Engineering and Fire Departments.
NOTE: Plans that are submitted directly to EsGil Corporation only will not
be reviewed by the City Planning, Engineering and Fire Departments until
review by EsGil Corporation is complete.
2. Indicate on the Title Sheet of the plans, the name of the legal owner and name
of person responsible for the preparation of the plans. Section 106.3.3.
3. Each sheet of the plans must be signed by the person responsible for their
preparation, even though there are no structural changes. Business and
Professions Code.
4. Plans and calculations shall be signed by an engineer or architect licensed by
the State of California where there are structural changes to existing buildings or
structural additions. Please include the California license number, seal, date of
license expiration and date plans are signed. Business and Professions Code.
5. Provide a statement on the Title Sheet of the plans stating that this project shall
comply with the 2001 edition of the California Building Code (Title 24), which
adopts the 1997 UBC, 2000 UMC, 2000 UPC and the 1999 NEC.
6. On the first sheet of the plans indicate, differs from the application:
• The floor area of the remodeled area,
• Type of construction of the existing building,
• Sprinklers: Yes or No
• Present and proposed occupancy classifications of the remodel area,
• The story where the tenant improvement is located,
• The occupant load of the remodel area(s).
Carlsbad 03-3121
November 26, 2003
7. Show any existing fire rated area separation walls, occupancy separation walls,
demising walls, shafts or rated corridors. Identify and provide construction details
for proposed new fire rated walls.
8. Provide a note on the plans indicating if any hazardous materials will be stored
and/or used within the building which exceed the quantities listed in UBC Tables
3-D and 3-E.
9. Glazing in the following locations should be of safety glazing material in
accordance with Section 2406.4 (see exceptions):
a) Fixed and sliding panels of sliding door assemblies and panels in swinging
doors other than wardrobe doors.
b) Fixed or operable panels adjacent to a door where the nearest exposed
edge of the glazing is within a 24-inch arc of either vertical edge of the door
in a closed position.
10. Provide an exit analysis plan (may be 8 1/2" x 11" or any convenient size). Show -
in this analysis the occupant load of each area, the general exit flow patterns (by
using arrows), accumulated occupant loads and required exit widths.
11. Exits should have a minimum separation of one-half the maximum overall
diagonal dimension of the building or area served. Section 1004.2.4.
12. Exits shall not pass through kitchens, store rooms, or spaces used for similar
purposes. Section 1004.2.2.
13. Exit signs are required whenever two exits are required. Show all required exit
sign locations. Section 1003.2.8.2.
14. If exit signs are required, provide the following notes on the plans, per Section
1003.2.8.2:
a) Exit signs shall be located as necessary to clearly indicate the direction of
egress travel. No point shall be more than 100 feet from the nearest
visible sign.
b) Exit signs shall be readily visible from any direction of approach.
15. Note on the plans: "All exits are to be operable from inside without the use of a
key or special knowledge." In lieu of the above, in a Group B, F, M or S
occupancies, you may note "Provide a sign on or near the exit door, reading
THIS DOOR TO REMAIN UNLOCKED DURING BUSINESS HOURS." This
signage is only allowed at the main exit. Section 1003.3.1.8.
Carlsbad O3-3121
November 26, 2003
• ELECTRICAL
16. Submit plan showing location of all panels.
17. Submit panels schedules.
18. Submit electrical load calculations.
19. Indicate existing main service size.
20. Indicate existing total main service load.
21. Indicate new additional loads.
22. Indicate wiring method, i.e. EMT, metal flex.
23. Show exit signs on the electrical lighting plan(s). As per Section 1003.2.8,
provide two sources of power to exit signs and exit illumination.
24. Provide multiple switch lighting controls per Title 24, Part 6.
25. WIRING METHODS: AC Cable is not allowed in A, B, E, H, and I occupancies.
NM cable is restricted (without City approval) to one and two family dwellings.
Note on plans that an equipment ground conductor is to be installed in all flexible
conduits.
26. The use of flexible metal conduit as a grounding means must comply with City
Policy 84-36.
• MECHANICAL
27. Show the location, type and size (BTU's) of all heating and cooling appliances or
systems.
28. Provide mechanical ventilation in all rooms, capable of supplying outside air at a
minimum rate of 15 cubic feet per minute per occupant. UBC, Section 1202.2.1.
29. Provide mechanical plans, showing existing and proposed HVAC equipment,
ducts and access to equipment.
30. Detail access and working clearances to HVAC equipment.
31. Detail ladder access to roof mounted HVAC equipment.
32. Detail disposal of main condensate drainage from air conditioning units. (UMC
Section 309)
33. Detail overflow (secondary) condensate discharge from air conditioning units that
are in a ceiling space, to a readily observable location. (UMC Section 1105.12)
Carlsbad 03-3121
November 26, 2O03
• ENERGY
34. Provide plans, calculations and worksheets to show compliance with current
energy standards.
35. Provide complete energy designs for the proposed changes in envelope, lighting,
and mechanical systems. Provide the completed ENV-, LTG-, and MECH- forms
showing energy compliance.
36. On the plans clearly show the wall and roof insulation locations, thickness, and
R-values, as per the energy design.
37. The completed and signed ENV-1, LTG-1, and MECH-1 forms must be imprinted
on the plans.
• MISCELLANEOUS
38. Please comply with the attached disabled access list.
To speed up the review process, note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet, note or detail number,
calculation page, etc.
The jurisdiction has contracted with Esgil Corporation located at 9320
Chesapeake Drive, Suite 208, San Diego, California 92123; telephone number of
858/560-1468, to perform the plan review for your project. If you have any
questions regarding these plan review items, please contact Bryan Zuppiger at
Esgil Corporation. Thank you.
Carlsbad 03-3121
November 26, 2003
DISABLED ACCESS REVIEW LIST
DEPARTMENT OF STATE ARCHITECT
TITLE 24
The following disabled access items are taken from the 2001 edition of California Building
Code, Title 24. Per Section 101.17.11, all publicly and privately funded public
accommodations and commercial facilities shall be accessible to persons with disabilities.
NOTE: All Figures and Tables referenced in this checklist are printed in the California
Building Code, Title 24.
• REMODELS. ADDITIONS AND REPAIRS
1. When alterations, structural repairs or modifications or additions are made to an
existing building, that building, or portion of the building affected, is required to
comply with all of the requirements for new buildings, per Section 1134B.2. These
requirements apply as follows:
a) The area of specific alteration, repair or addition must comply as "new"
construction.
b) A primary entrance to the building and the primary path of travel to the
altered area, must be shown to comply with all accessibility features.
c) Existing sanitary facilities that serve the remodeled area must be shown to
comply with all accessibility features.
d) Existing drinking fountains (if any) must be shown to comply with all
accessibility features.
e) Existing public telephones (if any) must be shown to comply with all
accessibility features.
2. If an unreasonable hardship finding is granted, priority should be given to those
elements that will provide the greatest access, per Section 1134B.2.1 Exception
#1. The order of priority shown below should be followed:
a) An accessible entrance.
b) An accessible route of travel.
c) At least one accessible restroom for each sex.
d) Accessible telephones.
e) Accessible drinking fountains.
f) When possible, additional accessible elements such as parking, storage
and alarms.
Carlsbad 03-3121
November 26, 2003
• SITE PLAN REQUIREMENTS
3. Clearly show that the site development and grading are designed to provide
access to all entrances and exterior ground floor exits, as well as access to normal
paths of travel, per Section 1127B.1. Where necessary to provide access, shall
incorporate pedestrian ramps, curb ramps, stairways and handrails, etc.
4. Show, or note that at every primary public entrance, and at every major function
area along, or leading to, an accessible route of travel, there is to be a sign
displaying the international symbol of accessibility. Signs are required to indicate
the direction to accessible building entrances and facilities, per Sections 1117B.5.7
and1127B.3.
WALKS AND SIDEWALKS
5. If any proposed walks slope >1:20 (5%) they must comply with ramp requirements,
per Section 1133B.5.1.
6. Walks along an accessible route of travel are required to be >48" minimum in width
and have slip resistant surfaces, per Section 1133B.7.
7. The maximum permitted cross slope shall be VT per ft., per Section 1133B.7.1.3.
8. Show or note that any abrupt level changes will be ^" along any accessible route
of travel. When changes do occur, they shall be beveled with a slope of ^:2.
Level changes of ^" may be vertical.
NOTE: If level changes >Yz\ they must comply with the requirements of curb
ramps.
9. Show that a 60" x 60" level area is provided at areas where a door (or gate) swings
toward the walk in the accessible route of travel, per Section 1133B.7.5. Show that
the walk extends >24" beyond the strike edge of the strike edge of any door (or
gate) that swings toward the walk.
10. Show or note that >80" headroom is to be provided from all walkway surfaces to
obstructions, per Section 1133B.8.2.
11. Show that walks with continuous gradients are provided with level areas >5'0" long
at intervals of 400'0" maximum, per Section 1133B.7.6.
12. If grated openings are to be provided in the path of travel, they are to be limited to
:£" in the direction of travel, per Section 1133B.7.2. Revise plans to show, or
note, compliance.
13. Show that a 36" wide detectable warning material is provided at boundaries
between walkways and vehicular ways. Material shall comply with criteria of
Sections 1133B.8.3 through 1133B.8.5, per Section 1133B.8.5.
14. Plans indicate that more than one route of travel is to be provided. Revise plans to
show that all routes are to be made accessible, per Section 1127B.1.
Carlsbad 03-3121
November 26, 2003
• PEDESTRIAN RAMPS
15. Show that any path of travel with a slope >1:20 (5%) complies with pedestrian
ramp requirements, per Section 1133B.5.
16. The allowable slope for an accessible ramp is ^:12 (8.33%), per Section
1133B.5.3. Revise plans to show the least possible slope is being provided for all
ramps, per Section 1133B.5.1.
17. The allowable cross slope at pedestrian ramps shall be 3A" per ft (2%), per
Section 1133B.5.3.1.
18. Show or note that ramp surfaces will be slip resistant.
19. Ramps shall have a minimum width of 48 inches, per Section 1133B.5.2.2. Where
a ramp serves a building having an occupant load of 300 or more, the minimum
clear width shall be 60 inches.
20. Revise plans to show required landings at the top and bottom of ramps, per
Section 1133B.5.4.
a) The bottom landing shall be >72" in the direction of travel.
b) The top landing shall be a >60" x 60".
21. Show that the required intermediate landing is provided, per Section 1133B.5.4 as
follows:
a) >60" long where the elevation change is >30".
b) >72" long at direction changes >30°.
22. Revise plans to show the minimum required depth of landing where a door swings
over the top landing. The minimum depth of the landing is required to be equal to
the door width, plus 42", per Section 1003.3.4.4.
23. Plans shall show that the strike edge distances at doors comply with the
requirements of Section 1133B.5.4.4, as follows:
a) >24" at exterior ramps.
b) >18" at interior ramps.
24. Show handrails at each side of ramp(s) which are shown to be >1:20 (5%) in
slope, per Section 1133B.5.5.
25. Show that handrails are >W but ^%" in any cross sectional dimension.
Additionally, show that the handrails are placed a >11/2H from any wall, per Section
1133B.5.5.
26. Show or note that handrails meet the following requirements, per Section
1133B.5.5:
a) Are continuous.
b) Are to be located >34" but ^8" above the ramp surface.
c) Extend >12" beyond both the top and bottom landings.
d) Ends are to be returned.
Carlsbad 03-3121
November 26, 2003
27. Where the ramp surface is not bounded by a wall or fence and the ramp exceeds
10' in length, the ramp shall comply with one of the following requirements, per
Section 1133B.5.6:
a) A guide curb a minimum of 2" in height shall be provided at each side of the
ramp; or
b) Awheel guide rail shall be provided, centered 3" ± 1" above the surface of
the ramp.
28. Note that all wall surfaces, adjacent to handrails, will be free of sharp or abrasive
elements, per Section 1133B.5.5.1 (i.e., no stucco).
• DOORS
29. Revise plans, or door schedules, to show that every required passage door has
>32" clear width, per Section 1133B.2.
30. Show, or note, that there is a level floor or landing on each side of all doors. The
floor or landing is to be &•? lower than the doorway threshold, per Section
1133.2.4.1.
31. Show a level area, or landing, per Section 1133B.2.4.2:
a) >60" in the direction of door swing.
b) >48" in the direction opposite the door swing (or 44" if doors don't have
latches or closers).
MULTIPLE ACCOMMODATION SANITARY FACILITIES
32. Show that the accessible rest room is to be provided with either:
a) A 60" minimum diameter clear space measured from the floor to a height of
27"
b) A clear space 56" x 63" in size.
NOTE: Doors (other than the door to the accessible toilet compartment) in
any position may encroach into this space by not more than 12 inches, per Section
1115B.7.1.1.
33. Show that at least one water closet fixture, located in a compartment, shall provide
the following, per Section 1115B.7.1.3:
a) >28" clear space from a fixture (or >32" clear space from a wall) at one side.
b) The other side of the water closet shall provide 18" from the centerline of
the water closet to the wall.
c) The stall shall be a minimum of 60" wide.
d) Clear space in front of the water closet shall be:
i) >48" if the compartment has a end opening door,
ii) >60" is required for side opening doors.
e) Grab bars shall not project more than 3" into the clear spaces indicated.
Carlsbad O3-3121
November 26, 20O3
34. Show or note, per Section 1115B.7.1.3 that the doors to the accessible water
closet compartment will be equipped with a self closing device with:
a) >32" clearance when located at the end of the compartment.
b) >34" clearance when located at the side of the compartment.
35. Note that if standard compartment doors are used, that the following will be
provided, per Section 1115B.7.1.4:
a) £9" clearance forfootrests underneath.
b) A self closing device.
If non-standard compartment doors are used, clearance at the strike edge as
specified in Section 1133B.2.4.3 is required.
36. When more than 6 water closets are provided, show the additional requirements
given in Section 1115B.7.1.5.
RESTROOM FIXTURES AND ACCESSORIES
37. Show, or note, on the plans that the accessible water closets meet the following
requirements, per Section 1115B.2.1:
a) The seat is to be >17" but ^9" in height.
b) The controls for flush valves shall be:
i) Mounted on the side of the toilet area,
ii) Be ^4" above the floor.
38. Show, or note, on the plans that accessible urinals meet the following
requirements, per Section 1115B.2.1.1:
a) The rim of at least one urinal shall:
i) Project at least 14" from the wall,
ii) Be ^ 7" above the floor.
b) The control mechanism is be located ^4" above the floor.
c) >30" x 48" clear floor space is provided in front of the accessible urinal.
39. Show that accessible lavatories comply with the following, per Sections
1115B.2.1.2:
a) >30" x 48" clear space is provided in front for forward approach. The clear
space may include knee and toe space beneath the fixture.
b) When lavatories are adjacent to a side wall or partition, there shall be a
minimum of 18" to the center line of the fixture to the wall.
c) The counter top is ^4" maximum above the floor.
d) >29" high, reducing to 27" at a point located 8" back from the front edge.
e) >9" high x 30" wide and 17" deep at the bottom.
Carlsbad 03-3121
November 26, 2003
f) Hot water pipes and drain lines are insulated.
40. Show that grab bars comply with the following, per Section 1115B.8:
a) Grab bars shall be located on each side or one side and the back of the
water closet stall or compartment.
b) They shall be securely attached 33" above the floor, and parallel.
NOTE: Where a tank-type toilet is used which obstructs placement at 33", the grab
bar may be installed as high as 36".
c) Grab bars at the side shall be located:
i) 15" to 161/£" (±1") from the center line of the water closet stool,
ii) Be >42" long with the front end positioned 24" in front of the stool,
iii) Total length of bars at the back shall be >36".
d) The diameter, or width, of the grab bar gripping surface is >1%" but ^%",
or the shape shall provide an equivalent gripping surface.
e) If mounted adjacent to a wall, the space between the wall and the grab bar
shall be 11/2".
f) Be designed to support 250#.
41. Show on the plans ^0" height for:
a) The operable parts of at least 1;
i) Paper towel dispenser.
ii) Sanitary napkin dispenser.
iii) Waste paper disposal.
iv) Other similar dispensing and/or disposal fixtures.
b) The bottom edge of mirrors.
Carlsbad 03-3121
November 26, 2003
VALUATION AND PLAN CHECK FEE
JURISDICTION: Carlsbad PLAN CHECK NO.: 03-3121
PREPARED BY: Bryan Zuppiger DATE: November 26, 2003
BUILDING ADDRESS: 2335 Camino Vida Roble
BUILDING OCCUPANCY: B TYPE OF CONSTRUCTION: VN
BUILDING
PORTION
Tl
Air Conditioning
Fire Sprinklers
TOTAL VALUE
Jurisdiction Code
AREA
(Sq.Ft.)
s^ -sser
s
cb
US?;
Valuation
Multiplier
City Estimate
By Ordinance
Reg.
Mod.
VALUE ($)
15,090
15,090
$145.89
Plan Check Fee by Ordinance
Type of Review:
Q Repetitive Fee
Repeats
Comments:
Complete Review
D
Other
Hourly
Esgll Plan Review Fee
Structural Only
Hour*
$94.83
$81.70
Sheet of
macvalue.doc
BUILDING PLANCHECK CHECKLIST
DATE:
BUILDING ADDRESS: j? 33J?
PROJECT DESCRIPTION:
PLANCHECK NO.: CB
\ltdta
ASSESSOR'S PARCEL NUMBER:$O -3*7 EST. VALUE:
ENGINEERING DEPARTMENT
APPROVAL
The item you have submitted for review has been
approved. The approval is based on plans,
information and/or specifications provided in your
submittal; therefore any changes to these items after
this date, including field modifications, must be
reviewed by this office to insure continued
conformance with applicable codes. Please review
carefully all comments attached, as failure to comply
with instructions in this report can result in
suspension of permit to build.
A Right-of-Way permit is required prior to
construction of the following improvements:
DENIAL
Please see\ thax attached report of deficiencies
marked wither Make necessary corrections to plans
or specifications for compliance with applicable
codes and standards. Submit corrected plans and/or
specifications to this office for review.
Date:
Date:
Date:By:
ENGINEERING lfHpRIZ#T*QNWSSUE BUIUJING PERMIti
, -':"'.. Date:
Dedication Application
Dedication Checklist
Improvement Application
Improvement Checklist
Future Improvement Agreement
Grading Permit Application
Grading Submittal Checklist
Right-of-Way Permit Application
Right-of-Way Permit Submittal Checklist
and Information Sheet
Sewer Fee Information Sheet
ENGINEERING DEPT. CONTACT PERSON
Name: JOANNE JUCHNIEWICZ
City of Carlsbad
Address: 1635 Faraday Avenue, Carlsbad. CA 92008
Phone: (760) 602-2775
CFD INFORMATION
Parcel Map No:
Lots:
Recordation:
Carlsbad Tract:
A-4
H:\WORDTOCS\CHKLST\euftJto Planch** Ckbl Form (GeneriC).doc
BUILDING PLANCHECK CHECKLIST
SITE PLAN
* ST 2NO 3RD
CI D D 1- Provide a fully dimensioned site plan drawn to scale. Show:
A. North Arrow F. Right-of-Way Width & Adjacent Streets
B. Existing & Proposed Structures G. Driveway widths
C. Existing Street Improvements H. Existing or proposed sewer lateral
D. Property Lines I. Existing or proposed water service
E. Easements J. Existing or proposed irrigation service
ODD2- Show on site plan:
A. Drainage Patterns
1. Building pad surface drainage must maintain a minimum slope of one
percent towards an adjoining street or an approved drainage course.
2. ADD THE FOLLOWING NOTE: "Finish grade will provide a minimum positive
drainage of 2% to swale 5' away from building."
B. Existing & Proposed Slopes and Topography
C. Size, type, location, alignment of existing or proposed sewer and water service
(s) that serves the project. Each unit requires a separate service, however,
second dwelling units and apartment complexes are an exception.
D. Sewer and water laterals should not be located within proposed driveways, per
standards.
D D D 3- Include on title sheet:
A. Site address
B. Assessor's Parcel Number
C. Legal Description
For commercial/industrial buildings and tenant improvement projects, include:
total building square footage with the square footage for each different use,
existing sewer permits showing square footage of different uses (manufacturing,
warehouse, office, etc.) previously approved.
EXISTING PERMIT NUMBER DESCRIPTION
mwORD\DOCS\CHKLSTOuMlng PtenchecK CWst Form fGwwftc).doc
BUILDING PLANCHECK CHECKLIST
1ST 2ND 3* DISCRETIONARY APPROVAL COMPLIANCE
D D D 4a. Project does not comply with the following Engineering Conditions of approval for
Project No.
D D D 4b. All conditions are in compliance. Date:
DEDICATION REQUIREMENTS
D D D 5. Dedication for all street Rights-of-Way adjacent to the building site and any storm
drain or utility easements on the building site is required for all new buildings and
for remodels with a value at or exceeding $15.000. pursuant to Carlsbad
Municipal Code Section 18.40.030.
Dedication required as follows:
Dedication required. Please have a registered Civil Engineer or Land Surveyor
prepare the appropriate legal description together with an 8 14" x 11" plat map
and submit with a title report. All easement documents must be approved and
signed by owner(s) prior to issuance of Building Permit. Attached please find an
application form and submittal checklist for the dedication process. Submit the
completed application form with the required checklist items and fees to the
Engineering Department in person. Applications will not be accept by mail or fax.
Dedication completed by: Date:
IMPROVEMENT REQUIREMENTS
6a. All needed public improvements upon and adjacent to the building site must be
constructed at time of building construction whenever the value of the
construction exceeds $75.000. pursuant to Carlsbad Municipal Code Section
18.40.040.
Public improvements required as follows:
Attached please find an application form and submittal checklist for the public
improvement requirements. A registered Civil Engineer must prepare the
appropriate improvement plans and submit them together with the requirements
on the attached checklist to the Engineering Department through a separate plan
check process. The completed application form and the requirements on the
H:\WOflD\DOCS\CHKLST\BuUdino PlandMCk GUI Form (RIDDLE • HARVEY 7-12-00).<Joe
sr
BUILDING PLANCHECK CHECKLIST
checklist must be submitted in person. Applications by mail or fax are not
accepted. Improvement plans must be approved, appropriate securities posted
and fees paid prior to issuance of building permit.
Improvement Plans signed by: Date:
D D D 6b. Construction of the public improvements may be deferred pursuant to Carlsbad
Municipal Code Section 18,40. Please submit a recent property title report or
current grant deed on the property and processing fee of $310 so we may
prepare the necessary Future Improvement Agreement. This agreement must be
signed, notarized and approved by the City prior to issuance of a Building permit.
- ':..<
Future public improvements required as follows:
D D D 6c- Enclosed please find your Future Improvement Agreement. Please return
agreement signed and notarized to the Engineering Department.
Future Improvement Agreement completed by:
Date:
D D D 6d-No Public Improvements required. SPECIAL NOTE: Damaged or defective
improvements found adjacent to building site must be repaired to the satisfaction
of the City Inspector prior to occupancy.
GRADING PERMIT REQUIREMENTS
The conditions that invoke the need for a grading permit are found in Section
11.06.030 of the Municipal Code.
D D D 7a- Inadequate information available on Site Plan to make a determination on grading
requirements. Include accurate grading quantities (cut, fill import, export).
D D D 7t)- Grading Permit required. A separate grading plan prepared by a registered Civil
Engineer must be submitted together with the completed application form
attached. NOTE: The Grading Permit must be issued and rough grading
approval obtained prior to issuance of a Building Permit.
Grading Inspector sign off by: ' Date:
D D D 7c. Graded Pad Certification required. (Note: Pad certification may be required even
if a grading permit is not required.)
H:\WOflD\DOCS\CHKLST\Bulldlnj Planch** Chl«l Forni [Generic 7-14-OOJ.doc
BUILDING PLANCHECK CHECKLIST
*ST 2ND 3RD
D D D 7d -No Grading Permit required.
D D D 7e- ^ grading is not required, write "No Grading" on plot plan.
MISCELLANEOUS PERMITS
D D D 8- A RIGHT-OF-WAY PERMIT is required to do work in City Right-of-Way and/or
private work adjacent to the public Right-of-Way. Types of work include, but are
not limited to: street improvements, tree trimming, driveway construction, tying
into public storm drain, sewer and water utilities.
Right-of-Way permit required for:
D D EH 9- INDUSTRIAL WASTE PERMIT If your facility is located in the City of Carlsbad
sewer service area, you need to contact the Carlsbad Municipal Water District,
located at 5950 El Camino Real, Carlsbad, CA 92008. District personnel can
provide forms and assistance, and will check to see if your business enterprise is
on the EWA Exempt List. You may telephone (760) 438-2722, extension 7153,
for assistance.
Industrial Waste permit accepted by:
Date:
D D D 10.NPDES PERMIT
Complies with the City's requirements of the National Pollutant Discharge
Elimination System (NPDES) permit. The applicant shall provide best
management practices to reduce surface pollutants to an acceptable level prior to
discharge to sensitive areas. Plans for such improvements shall be approved by
the City Engineer prior to issuance of grading or building permit, whichever
occurs first.
D D CD 11- Q Required fees are attached
Q No fees required
WATER METER REVIEW
D D D 12a. Domestic (potable) Use
Ensure that the meter proposed by the owner/developer is not oversized.
Oversized meters are inaccurate during low-flow conditions. If it is oversized, for
the life of the meter, the City will not accurately bill the owner for the water used.
• All single family dwelling units received "standard" 1" service with 5/8" service.
H:\WORD\DOCS\CHKLSTOuldlnD Plancheck CUst Forni (Genertc).doc
BUILDING PLANCHECK CHECKLIST
1ST )ND IRQ
n n
• If owner/developer proposes a size other than the "standard", then
owner/developer must provide potable water demand calculations,
which include total fixture counts and maximum water demand in gallons
per minute (gpm). A typical fixture count and water demand worksheet is
attached. Once the gpm is provided, check against the "meter sizing
schedule" to verily the anticipated meter size for the unit.
• Maximum service and meter size is a 2" service with a 2" meter.
• If a developer is proposing a meter greater than 2", suggest the
installation of multiple 2" services as needed to provide the anticipated
demand, (manifolds are considered on case by case basis to limit
multiple trenching into the street).
12b. Irrigation Use (where recycled water is not available)
All irrigation meters must be sized via irrigation calculations (in gpm) prior
to approval. The developer must provide these calculations. Please follow
these guidelines:
1. If the project is a newer development (newer than 1998), check the recent
improvement plans and observe if the new irrigation service is reflected on
the improvement sheets. If so, at the water meter station, the demand in
gpm may be listed there. Irrigation services are listed with a circled "I",
and potable water is typically a circled "W". The irrigation service should
look like:
STA 1+00 Install 2" service and
2.
3.
1.5: meter (estimated 100 gpm)
If the improvement plans do not list the irrigation meter and the
service/meter will be installed via another instrument such as the building
plans or grading plans (w/ a right of way permit of course), then the
applicant must provide irrigation calculations for estimated worst-case
irrigation demand (largest zone with the farthest reach). Typically, Larry
Black has already reviewed this if landscape plans have been prepared,
but the applicant must provide the calculations to you for your use. Once
you have received a good example of irrigation calculations, keep a set for
your reference. In general the calculations will include:
• Hydraulic grade line
• Elevation at point of connection (POC)
• Pressure at POC in pounds per square inch (PS!)
• Worse case zone (largest, farthest away from valve
• Total Sprinkler heads listed (with gpm use per head)
• Include a 10% residual pressure at point of connection
In general, all major sloped areas of a subdivision/project are to be
irrigated via separate irrigation meters (unless the project is only SFD with
no HOA), As long as the project is located within the City recycled water
H:\WORD\DOC5VCHKLST\BulUlng PttncMck Octet Forni [G«Wffc).doc
1ST OND oRD
BUILDING PLANCHECK CHECKLIST
service boundary, the City intends on switching
services/meters to a new recycled water line in the future.
these irrigation
D D 12c. Irrigation Use (where recycled water is available)
n
1. Recycled water meters are sized the same as the irrigation meter above.
2. If a project fronts a street with recycled water, then they should be
connecting to this line to irrigate slopes within the development. For
subdivisions, this should have been identified, and implemented on the
improvement plans. Installing recycled water meters is a benefit for the
applicant since they are exempt from paying the San Diego County Water
Capacity fees. However, if they front a street which the recycled water is
there, but is not live (sometimes they are charged with potable water until
recycled water is available), then the applicant must pay the San Diego
Water Capacity Charge. If within three years, the recycled water line is
charged with recycled water by CMWD, then the applicant can apply for a
refund to the San Diego County Water Authority (SDCWA) for a refund.
However, let the applicant know that we cannot guarantee the refund, and
they must deal with the SDCWA for this.
13. Additional Comments
H:\wORO\DOCS\CHKLSTfluliding Pbncheck Ckl« Foon (Genertc) Joe
PLANNING/ENGINEERING APPROVALS
PERMIT NUMBER £6.
ADDRESS
RESIDENTIAL
RESIDENTIAL ADDITION MINOR
« $1O,OOO.OO>
DATE
'to U>
TENANT IMPROVEMENT
PLAZA CAMINO REAL
CARLSBAD COMPANY STORES
VILLAGE FAIRE
COMPLETE OFRCE BUILDING
OTHER
PLANNER DATE
ENGINEER DATE
Docs/Mtsforms/ptannins Engineering Approvals
Carlsbad Fire Department 033121
1635 Faraday Ave.
Carlsbad, CA 92008
Plan Review Requirements Category:
Date of Report: 12/17/2003
Building Plan
Reviewed by:
Fire Prevention
(760) 602-4660
(L
Name:
Address:
Richard & Richard Co
234 Venture St.Suite A
City, State: San Marcos CA 92078
Plan Checker:
Job Name: Spec building
Job#: 033121
Job Address: 2335 Camino Vida Roble
Bldg #: CB033121
Ste. or Bldg. No.
Approved The item you have submitted for review has been approved. The approval is
based on plans, information and / or specifications provided in your submittal;
therefore any changes to these items after this date, including field
modifications, must be reviewed by this office to insure continued conformance
with applicable codes and standards. Please review carefully all comments
attached as failure to comply with instructions in this report can result in
suspension of permit to construct or install improvements.
Approved The item you have submitted for review has been approved subject to the
Subject to attached conditions. The approval is based on plans, information and/or
specifications provided in your submittal. Please review carefully all comments
attached, as failure to comply with instructions in this report can result in
suspension of permit to construct or install improvements. Please resubmit to
this office the necessary plans and / or specifications required to indicate
compliance with applicable codes and standards.
Incomplete The item you have submitted for review is incomplete. At this time, this office
cannot adequately conduct a review to determine compliance with the
applicable codes and / or standards. Please review carefully all comments
attached. Please resubmit the necessary plans and / or specifications to this
office for review and approval.
Review
FD Job #
1 st ?nH 3rd
033121 FDFile#
Other Agpnny in
ACORD. CERTII
PRODUCER
Driver Alliant Insur
1620 Fifth Avenue
" San Diego, CA 921
Jim Castle
FICATE OF LIABILITY INSURANCE
619-699-0539
ance
01
INSURED
Richard & Richard
Construction, Inc.
4751 Oceanside Blvd.
Oceanside CA 92056
DATE (MM/DD/YY) *'•
3/27/03 |
THIS CERTIFICATE IS ISSUED AS A MATTER OF INFORMATION
ONLY AND CONFERS NO RIGHTS UPON THE CERTIFICATE
HOLDER. THIS CERTIFICATE DOES NOT AMEND, EXTEND OR
ALTER THE COVERAGE AFFORDED BY THE POLICIES BELOW
COMPANIES AFFORDING COVERAGE
COMPANY
A MT. HAWLEY INSURANCE CO.
COMPANY
B HARTFORD CASUALTY INSURANCE CO
COMPANY
c STATE COMPENSATION FUND
COMPANY
D
COVERAGES ' * r ,* '^ *'''•*" C'* « '>'--"' ' , " *\ ^ '' v , V' =- '
THIS IS TO CERTIFY THAT THE POLICIES OF INSURANCE LISTED BELOW HAVE BEEN ISSUED TO THE INSURED NAMED ABOVE FOR THE POLICY PERIOD
INDICATED. NOTWITHSTANDING ANY REQUIREMENT. TERM OR CONDITION OF ANY CONTRACT OR OTHER DOCUMENT WITH RESPECT TO WHICH THIS
CERTIFICATE MAY BE ISSUED OR MAY PERTAIN. THE INSURANCE AFFORDED BY THE POLICIES DESCRIBED HEREIN IS SUBJECT TO ALL THE TERMS
EXCLUSIONS AND CONDITIONS OF SUCH POLICIES. LIMITS SHOWN MAY HAVE BEEN REDUCED BY PAID CLAIMS.
CO
LTR
A
C
B
TYPE OF INSURANCE
GENERAL UABIUTY
X COMMERCIAL GENERAL LIABILITY
1 CLAIMS MADE |_Xj OCCUR
X OWNER'S & CONTRACTOR'S PROT
AUTOMOBILE UABIUTY
ANY AUTO
ALL OWNED AUTOS
SCHEDULED AUTOS
HIRED AUTOS
NON-OWNED AUTOS
OARAGE UABIUTY
ANY AUTO
EXCESS UABIUTY
UMBRELLA FORM
OTHER THAN UMBRELLA FORM
WORKERS COMPENSATION AND
EMPLOYERS' UABIUTY
THE PROPRIETOR/ INCL
OFFICERS ARE: EXCL
OTHER
LEASED/RENTED
EQUIPMENT
POUCY NUMBER
MGL0 135539
PER PROJECT
AGGREGATE
161511503
72SBAAA5710,
POUCY EFFECTIVE
DATE IMM/DD/YYI
3/26/03
01/01/03
03/26/03
POUCY EXPIRATION
DATE IMM/DO/YY)
3/26/04
01/01/04
03/26/04
LIMITS
GENERAL AGGREGATE
PRODUCTS - COMP/OP AGO
PERSONAL & AOV INJURY
EACH OCCURRENCE
FIRE DAMAGE (Any on* fire)
MED EXP [Any ana perun)
COMBINED SINGLE LIMIT
BODILY INJURY
(Pw perionl
BODILY INJURY(Per «cid«ni]
PROPERTY DAMAGE
AUTO ONLY - EA ACCIDENT
OTHER THAN AUTO ONLY:
EACH ACCIDENT
AGGREGATE
EACH OCCURRENCE
AGGREGATE
v I WC STATU-* (TORY LIMITS OTH-ER
EL EACH ACCIDENT
EL DISEASE • POUCY LIMIT
EL DISEASE - EA EMPLOYEE
« 2000000
» 1000000
* 1000000
* 1000QOQ
* 50000
* 5000
*
t
1
*
*
4
*1
t
*
t 1000000
1 1000000
t 1000000
$50,000 LIMIT
$500 DEDUCTIBLE
SPECIAL FORM PERILS
DESCRIPTION OF OPERATIONS/LOCATIONS/VEHICLES/SPECIAL ITEMS
•10 DAYS NOTICE FOR NON-PAYMENT OF PREMIUM.
^W)l&TEHptOERv"' «<T,<f>"y^\, ^O?^/? ^\§'£t J'","^,-
INFORMATION PURPOSES ONLY SHOULD ANY OF THE ABOVE DESCRIBED POUCIES BE CANCELLED BEFORE THE