Loading...
HomeMy WebLinkAbout2384 BOTELLA PL; ; CB140392; Permit03-20-2014 Job Address: Permit Type: Parcel No: Valuation: Occupancy Group: Project Title: City of Carlsbad 1635 Faraday Av Carlsbad, CA 92008 Cogeneration Permit Permit No:CB140392 Building Inspection Request Line (760) 602-2725 2384 BOTELLA PL CBAD COGEN Sub Type: PHOTO 2163511200 Lot#: 0 $8,000,00 Constuction Type: NEW Reference #: ABRAMSON RES- INSTALL ROOF MNT PV SYSTEM 20 MODULES NO PANEL UPGRADE Status: ISSUED Applied: 02/20/2014 Entered By: LSM Plan Approved: 03/20/2014 Issued: 03/20/2014 Inspect Area: Plan Check #: Applicant: MARINER MECHANICAL INC DBA ADROIT SOLAR STE 32 1135 GARRET AV SAN DIEGO CA 92109 Owner: ABRAMSON BETH D 2384 BOTELLA PL CARLSBAD CA 92009 858-483-3568 Building Permit $107.27 PLUMBING TOTAL $0.00 Add'l Building Permit Fee $0.00 ELECTRICAL TOTAL $0.00 Plan Check $75.09 MECHANICAL TOTAL $0.00 Add'l Plan Check Fee $74.91 Additionai Fees $0.00 Plan Check Discount Strong Motion Fee Green Bldg Stands (SB1473) Fee $0.00 $1.00 $1.00 TOTAL PERMIT FEES $259.27 Total Fees: $259.27 Total Payments To Date: $259.27 Balance Due: $0.00 Inspector: ^ FINAL APPROVAL ^ Date:>Vf-/y Clearance: NOTICE: Please take NOTICE that approval of your project includes ttie Imposition" of fees, dedications, reservations, or otfier exactions tiereafter collectively referred to as "fees/exactions," You tiave 90 days from the date this pemiit was issued to protest imposition of these fees/exactions. If you protest them, you must follow the protest procedures set forth in Government Code Section 66020(a), and file the protest and any other required infonnabon with the City Manager for processing in accondance with Carisbad Municipal Code Section 3,32.030. Failure to timely follow that procedure wiil t)ar any subsequent legal action to attack, review, set aside, void, or annul their imposition. You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection fees and capacity changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this project, NOR DOES IT APPLY to any fg$?/^x^ption? ipf whiqh vou have orRvinuslv been given a NOTICE similar to this, pr as to which the statute of limitations has previously otherwise expired. THE FOLLOWING APPROVALS REQUIRED PRIOR TO PERMrT ISSUANCE: PUNNING ENGINEERING : BUILDING FIRE HEALTH : HAZMAT/APCt CITY OF CARLSBAD Building Permit Appiication 1635 Faraday Ave., Carlsbad, CA 92008 Ph: 760-602-2719 Fax: 760-602-8558 email: building@car1sbadca.gov www.carlsbadca.gov Plan Check No. Q£) [ g OS^ Zl Est. Value Plan Ck. Deposit (,50 - OO JOB ADDRESS 2384 Botella Place SUrTE«/5PACEf/UNrTf APN " 216 - 351 - 12 - 00 CT/PROJECT # 0200.16 LOT# 60 PHASES ff OF UNITS fl BEDROOMS # BATHROOMS TENANT BUSINESS NAME ' CONSTR. TVPE occ, GROUP DESCRIPTION OF WORK: Indude Square Feet ta Affected Areafs) 5.3kW Roof Mounted Photovoltaic System EXISTING USE PROPOSED USE GARAGE (SF) PATIOS (SF) DECKS (SF) FIREPLACE YESQ#. NOj I AIR CONDmONING YES [ [NO I I RRE SPRINKLERS YES I |N0|~~ APPUCANTNAME (Primary Contact) Sarah Goldstein APPUCANTNAME (Secondary Contact) ADDRESS 1135 Garnet Ave. Suite 32 ADDRESS CITY San Dieao STATE CA ZIP 92109 CITY STATE ZIP PHONE 858-337-6496 FAX 858-492-7772 EMAIL sgoldstein@adroitsolar.com PHONE EMAIL FAX PROPERTY OWNER NAME ADDRESS Beth Abramson CONTRACTOR BUS. NAME Adroit Solar 2384 Botella Place ADDRESS 1135 Garnet Ave. Suite 32 CITY Carlsbad STATE ZIP CA 92009 CITY STATE San Dieao CA ZIP 92109 PHONE 858-245-1196 FAX PHONE 858-483-3568 FAX 858-492-7772 EMAIL babramson@san.rr.com ErvlAIL sgoldsteln@adroitsolar.com ARCH/DESrCNER NAME&ADDRESS STATE LIC. fl STATE LICfl 488255 CLASS C-36 C-46 CITY BUS. LIC.# (Sec. 7031.5 Businessand Professions Code: Any City or County which requires a permitto construct, alter, improve, demolisti or repair any structure, priorto its issuance, also requires the applicantfor such permit to file a signed statement that he is licensed pursuant to the provisions ofthe Contractor's License Law {Chapters, commending with Section 7000 of Division 3 of the Businessand Professions Code} or that he is exempt therefrom, and the basis for the alleged exemption. Any violation of Section 7031.5 t)y any applicant for a permit subjects the applicant to a civil penalty of not more than five hundred dollars {$500}). i^k^RS'; COMP ENSAT I o w Workers' Compensation Declaration: / hereby afRrm under penalty of perjury one of tfie following dedarations: • I have and will maintain a certificate of consent to self-insure for wortters' compensalion as provided by SecUon 3700 of Ihe Labor Code, for the performance of the work for which this pemiit is issued. 0 I have and will maintam workers' compensation, as required by Section 3700 ot the Labor Code, for the perfomwnce of the work for which this pemiit is issued. My workers' compensation insurance earner and policy number are: Insurance Co, California Insurance Co, Policy No. Expiration Date. 3/1/20M This section need not be compleled if the p^mlt Is For one hundred dollars ($100) or less. I I Certificate of Exemption: I certify that in ^e performance of the work tor which this permit is issued, I shall not employ any person in any manner so as to become subject to the Workers' Compensation Laws of Califomia, WARNING: Failure to secure workers' compensalion coverage is unlawful, and shall subject an employer to criminal penalties and civit fines up to one hundred ttiousand dollars {&100,000), in addition tothe cost of compensation, damaga.y provided for inaction 3706 ofthe Labor code. Interest and attomey's fees. -gf CONTRACTOR SIGNATURE v •AGENT DATE ^/iSA ^ I tiereby affirm lhat I am exempt from Contractor's Ucense Law for the Mowing reason: [•] I, as owner of the property or my employees with wages as their sole compensation, will do the work and the structure is nol iniended or offered for sale (Sec 7044, Business and Professions Code: The Contractor's Ucense Law does nol apply to an owner of properly who builds or improves thereon, and who does sucii work himself or through his own empkiyees, provided that such improvements are not intended or offered for sale. If, however, the building or improvement is sold within one year of completion, the owner-builder wiH have Itie burden of proving that he dkl not build w imprave for the purpose of sale), I I I, as owner of the property, am exdusively contracting with licensed contractors to constnjct the project (Sec. 7044, Business and Professions Code: The Contractor's Ucense Law does not apply to an owner of property who buiWs or improves ttwreon, and contracts for such projects with conlractor(s} licensed pursuant lo the Contractor's License Law), I am exempt under Section Business and Professions Code for this reason: • 1.1 personally plan to provide the major labor and materials for construction of the proposed properly improvement. QYes j |NO 2,1 (have / have not) signed an applicalion for a building permii for Ihe proposed work. 3.1 have contracted with the following person (firm) to provide 8ie proposed constaiclkin (include name address / phone / contactors' licHise number): 4,1 plan to provide portions of the work, but I have hired the foBowing person to coordinate, supervise and provide the major work (indude name / address / phone / contractors' license number): 5,1 will provide some of the work, but I have contracted (hired) the following persons to provkle the work indicaled (include name / address / phone / type of work): -S^PROPERTY OWNER SIGNATURE PIAGENT DATE ptETE THIS SECTION FOR N O N - R E S I D E N T I A L BUILDING PERMITS ONLY Is the applicant or fulure building occupant required to submil a business plan, acutely hazardous materials regislralion form or risk managemenl and prevention program under Sections 25505,25533 or 25534 of the Presley-Tanner Hazardous Substance Account Act? • Yes • No Is the applicani or fulure buikiing occupanl required to obtain a permit from the air pollution conlrol district or air quality management district? CT Yes • No Is the facility to be constructed within 1,000feetof the outer boundary of a school site? OYes • No IF ANY OF THE ANSWERS ARE YES, A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR IS MEETING T>IE REQUIREMENTS OF THE OFFICE OF EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTmCT. iSN STRUCTION LENDING AGENCY I hereby affirm ttiat there is a constnjction lerKling agency tor the performance of the woi1( this pemiit is issued {Sec. 3097 (i) Civil Code). Lender's Name Lender's Address A NT CERTIFICATION I cetti^thatl have read ttte application andstatethattheatxive infomiation is conect and that ttie infomiation on the plans is accurate. I agiee to comply vrith all Ci^ ordinances ami State laMsielatine to tMildftigco^^ I hereby aulhonze representative of the City of Carlsbad to enter upon the above mentioned property for inspection purposes. I ALSO AGREE TO SAVE, INDEMNIFY AND KEEP HARMLESS THE CITY OF CARLSBAD AGAINST ALL LIABILITIES, JUDGMENTS, COSTS AND EXPENSES WHICH MAY IN ANY WAY ACCRUE AGAINST SAID CITY IN CONSEQUENCE OF THE GRANTING OF THIS PERMfT. OSMA: An OSHA permit is requred for ^(cavatkxis over S'O' deep and dandition or constnjcSon of structures over 3 sfones n heighL EXRRATION: Every permit issued by the BuiUing Ofiicial under the provisions erf this Code shall expire by imitatkxi and become nui and vokl if ttte bulding orwork authorized by such permit is not commenced within 180 days fiom the date of such pemst or if the buiding or work authorized tiy such pemiit is suspend Building Code). >£^APPLICANT'S SIGNATURE DATE 2 Inspection List PermiW: CB140392 Type: COGEN PHOTO ABRAMSON RES- INSTALL ROOF MNT PV SYSTEM 20 MODULES NO PANEL U Date Inspection item Inspector Act Comments 04/10/2014 35 Photo Voltaic (PV) PB AP 04/10/2014 39 Final Electrical PB AP Friday, April 11. 2014 Page 1 of 1 EsGil Corporation In 'PartnersHip -witH Qovemment for (BuiCding Safety DATE: 03/18/2014 • APPLICANT • JURIS, JURISDICTION: Carlsbad • PLANREVIEWER • FILE PLANCHECKNO.: 14-0392 SET: II PROJECTADDRESS: 2384 Botella Place PROJECT NAME; Abramson 20@215 watt micro inverter rooftop PV system ^ The plans transmitted herewith have been corrected where necessary and substantially comply with the jurisdiction's building codes. I I The plans transmitted herewith will substantially comply with the jurisdiction's codes when minor deficiencies identified below are resolved and checked by building department staff. I I The plans transmitted herewith have significant deficiencies identified on the enclosed check list and should be corrected and resubmitted for a complete recheck. I I The check list transmitted herewith is for your information. The plans are being held at Esgil Corporation until corrected plans are submitted for recheck. I I The applicant's copy of the check list is enclosed for the jurisdiction to fonward to the applicant contact person. I I The applicant's copy of the check list has been sent to: Ixl EsGil Corporation staff did not advise the applicant that the plan check has been completed. I I EsGil Corporation staff did advise the applicant that the plan check has been completed. Person contacted: Telephone #: Date contacted: (by: ) Email: Fax #: Mail Telephone Fax In Person • REMARKS: By: John Le Vey Enclosures: EsGil Corporation • GA • EJ • MB • PC 03/12/2014 9320 Chesapeake Drive, Suite 208 • San Diego, Califomia 92123 • {858)560-1468 • Fax (858) 560-1576 EsGil Corporation In (PartnersHip with government for (BuiCding Safety DATE: 3/3/2014 • APPLICANT ^.^a^URIS. JURISDICTION: Carlsbad • PLAN REVIEWER • FILE PLANCHECKNO.: 14-0392 SET; I PROJECTADDRESS: 2384 Botella Place PROJECT NAME: Abramson 20 microinverter rooftop PV system I I The plans transmitted herewith have been corrected where necessary and substantially comply with the jurisdiction's codes. I I The plans transmitted herewith will substantially comply with the jurisdiction's codes when minor deficiencies identified below are resolved and checked by building department staff. I I The plans transmitted herewith have significant deficiencies identified on the enclosed check list and should be corrected and resubmitted for a complete recheck. 3 The check list transmitted herewith is for your information. The plans are being held at Esgil Corporation until corrected plans are submitted for recheck. I I The applicant's copy of the check list is enclosed for the jurisdiction to fonward to the applicant contact person. I I The applicant's copy ofthe check list has been sent to: I I EsGil Corporation staff did not advise the applicant that the plan check has been completed. I I EsGil Corporation staff did advise the applicant that the plan check has been completed. Person contacted: Sarah Goldstein Telephone*: 858.337.6496 Date contacted: ^ ^ ^^^^^^ ^ Email: sgoldstein@adroitsolar.com Fax #: Mail^ Telephone )^ Fax In Person • REMARKS: By: Morteza Beheshti Enclosures: EsGil Corporation • GA • EJ • MB • PC 2/21 9320 Chesapeake Drive, Suite 208 • San Diego, Califomia 92123 • (858)560-1468 • Fax (858) 560-1576 Carlsbad 14-0392 3/3/2014 GENERAL PLAN CORRECTION LIST JURISDICTION: Carlsbad PLANCHECKNO.: 14-0392 PROJECTADDRESS: 2384 Botella Place DATE PLAN RECEIVED BY DATE REVIEW COMPLETED: ESGIL CORPORATION: 2/21 3/3/2014 REVIEWED BY: Morteza Beheshti FOREWORD (PLEASE READ): This plan review is limited to the technical requirements contained in the International Building Code, Uniform Plumbing Code, Uniform Mechanical Code, National Electrical Code and state laws regulating energy conservation, noise attenuation and disabled access. This plan review is based on regulations enforced by the Building Department. You may have other corrections based on laws and ordinances enforced by the Planning Department, Engineering Department or other departments. The following items listed need clarification, modification or change. All items must be satisfied before the plans will be in conformance with the cited codes and regulations. The approval of the plans does not permit the violation of any state, county or city law. • Please make all corrections and submit two new complete sets of prints to: ESGIL CORPORATION. • To facilitate rechecking, please identify, next to each item, the sheet of the plans upon which each correction on this sheet has been made and return this sheet with the revised plans. • Please indicate here if any changes have been made to the plans that are not a result of corrections from this list. If there are other changes, please briefly describe them and where they are located on the plans. Have changes been made not resulting from this list? • Yes • No Carlsbad 14-0392 3/3/2014 ELECTRICAL and ENERGY COMMENTS PLAN REVIEWER: Morteza Beheshti ELECTRICAL (2013 CALIFORNIA ELECTRICAL CODE) 1. Please revise the section numbers and notes on the plans such as single line to match the 2013 CBC and 2010 CEC, as adopted by California. 2. The following design loads shall be clearly indicated on the construction documents. Wind load. The following information should be provided: *Basic Wind speed (3-second gust), 110 mph *Wind exposure shall be determined by the engineer. 3. Please demonstrate compliance with the fire access and pathways setback requirements under section 3111.4 ofthe 2013 residential CBC. Show setback dimensions on plans. There should be a minimum of 36" clear from the roof ridge. Also, a minimum of 36" clear from at least one side of the edge down. There should be at least 18" from edge of the modules to any roof edge/ valley or hip. When there is modules on both sides of the valley then 18" clear should be provided on both sides of the valley to the edge of the nearest module. Do not install junction boxes or any obstacles in the above clear fire department passageways. 4. Provide the required separate grounding electrode for the "photovoltaic rack assembly" per 690.47 (C)(1). Sized per 250.166, not smaller than #8. This is in addition to the required equipment grounding conductor; both are required. Note: If you have any questions regarding this Electrical and Energy plan review list please contact Morteza Beheshti at (858) 560-1468. To speed the review process, note on this list (or a copy) where the corrected items have been addressed on the plans. Carlsbad 14-0392 3/3/2014 [DO NOT PAY- THIS IS NOT AN INVOICE] VALUATION AND PLAN CHECK FEE JURISDICTION: Carlsbad PLANCHECKNO.: 14-0392 PREPARED BY: Morteza Beheshti DATE: 3/3/2014 BUILDING ADDRESS: 2384 Botella Place BUILDING OCCUPANCY: TYPE OF CONSTRUCTION: BUILDING PORTION AREA ( Sq. Ft.) Valuation Multiplier Reg. Mod. VALUE ($) Air Conditioning Fire Sprinklers TOTAL VALUE Jurisdiction Code Cb By Ordinance Bldg. Permit Fee by Ordinance W | Plan Check Fee by Ordinance Type of Review: • Complete Review I I Repetitive Fee ^"j Repeats • Other [7] Hourly EsGil Fee • Structural Only 1.5 Hrs. Based on tiourly rate Comments: 1.5 hour solar PV system review. Sheet 1 of 1 macvalue.doc + EsGil Corporation In (PartnersHip with government for (BuiCding Safety DATE: 3/3/2014 • APPLICANT ^,a<IURIS. JURISDICTION: Carlsbad • PLANREVIEWER • FILE PLANCHECKNO.: 14-0392 SET: I PROJECTADDRESS: 2384 BoteUa Place PROJECT NAME: Abramson 20 microinverter rooftop PV system I I The plans transmitted herewith have been corrected where necessary and substantially comply with the jurisdiction's codes. I I The plans transmitted herewith will substantially comply with the jurisdiction's codes when minor deficiencies identified below are resolved and checked by building department staff. I I The plans transmitted herewith have significant deficiencies identified on the enclosed check list and should be corrected and resubmitted for a complete recheck. ^ The check list transmitted herewith is for your information. The plans are being held at Esgil Corporation until corrected plans are submitted for recheck. I I The applicant's copy of the check list is enclosed for the jurisdiction to fon/vard to the applicant contact person. I I The applicant's copy ofthe check list has been sent to: I I EsGil Corporation staff did not advise the applicant that the plan check has been completed. I I EsGil Corporation staff did advise the applicant that the plan check has been completed. Person contacted: Sarah Goldstein Telephone #: 858.337.6496 Date contacted: (by: Email: sgoldstein@adroitsolar.com Fax #: Mail Tetephone Fax In Person • REMARKS: By: Morteza Beheshti Enclosures: EsGil Corporation • GA • EJ • MB • PC 2/21 9320 Chesapeake Drive, Suite 208 • SanDiego, Califomia 92123 • (858)560-1468 • Fax (858) 560-1576 Carlsbad 14-0392 3/3/2014 GENERAL PLAN CORRECTION LIST JURISDICTION: Carlsbad PLANCHECKNO.: 14-0392 PROJECTADDRESS: 2384 BoteUa Place DATE PLAN RECEIVED BY DATE REVIEW COMPLETED: ESGIL CORPORATION: 2/21 3/3/2014 REVIEWED BY: Morteza Beheshti FOREWORD (PLEASE READ): This plan review is limited to the technical requirements contained in the International Building Code, Uniform Plumbing Code, Uniform Mechanical Code, National Electrical Code and state laws regulating energy conservation, noise attenuation and disabled access. This plan review is based on regulations enforced by the Building Department. You may have other corrections based on laws and ordinances enforced by the Planning Department, Engineering Department or other departments. The following items listed need clarification, modification or change. All items must be satisfied before the plans wiil be in conformance with the cited codes and regulations. The approval of the plans does not permit the violation of any state, county or city law. • Please make all corrections and submit two new complete sets of prints to: ESGIL CORPORATION. • To facilitate rechecking, please identify, next to each item, the sheet of the plans upon which each correction on this sheet has been made and return this sheet with the revised plans. • Please indicate here if any changes have been made to the plans that are not a result of corrections from this list. If there are other changes, please briefly describe them and where they are located on the plans. Have changes been made not resulting from this list? • Yes • No Carlsbad 14-0392 3/3/2014 [DO NOT PAY- THIS IS NOT AN INVOICE] VALUATION AND PLAN CHECK FEE JURISDICTION: Carlsbad PLAN CHECK NO.: 14-0392 PREPARED BY: Morteza Beheshti DATE: 3/3/2014 BUILDING ADDRESS: 2384 Botella Place BUILDING OCCUPANCY: TYPE OF CONSTRUCTION: BUILDING PORTION AREA ( Sq. Ft.) Valuation Multiplier Reg. Mod. VALUE ($) Air Conditioning Fire Sprinklers TOTAL VALUE Jurisdiction Code cb By Ordinance Bldg. Permit Fee by Ordinance • [ Plan Check Fee by Ordinance • | Type of Review: I I Repetitive Fee ~| Repeats Based on houriy rate • Complete Review • Other [7] Hourly EsGll Fee $187.50 • Structural Only 1.5 $100.00 Hrs. @ $150.00 Comments: 1.5 hour solar PV system review. Sheet 1 of 1 macvalue.doc + Carlsbad 14-0392 3/3/2014 ELECTRICAL and ENERGY COMMENTS PLAN REVIEWER: Morteza Beheshti ELECTRICAL (2013 CALIFORNIA ELECTRICAL CODE) 1. Please revise the section numbers and notes on the plans such as single line to match the 2013 CBC and 2010 CEC, as adopted by California. 2. The following design loads shall be clearly indicated on the construction documents. Wind load. The following information should be provided: *Basic Wind speed (3-second gust), 110 mph *Wind exposure shall be determined by the engineer. 3. Please demonstrate compliance with the fire access and pathways setback requirements under section 3111.4 of the 2013 residential CBC. Show setback dimensions on plans. There should be a minimum of 36" clear from the roof ridge. Also, a minimum of 36" clear from at least one side of the edge down. There should be at least 18" from edge of the modules to any roof edge/ valley or hip. When there is modules on both sides of the valley then 18" clear should be provided on both sides of the valley to the edge of the nearest module. Do not install junction boxes or any obstacles in the above clear fire department passageways. 4. Provide the required separate grounding electrode for the "photovoltaic rack assembly" per 690.47 (C)(1). Sized per 250.166, not smaller than #8. This is in addition to the required equipment grounding conductor; both are required. Note: If you have any questions regarding this Electrical and Energy plan review list please contact Morteza Beheshti at (858) 560-1468. To speed the review process, note on this list (or a copy) where the corrected items have been addressed on the plans. \ " ^ CITY Of CARLSBAD PLANNING DIVISION BUILDING PLAN CHECK APPROVAL P-29 Development Services Planning Division 1635 Faraday Avenue (760) 602-4610 www. carlsbadca.eov DATE: 2/20/14 PROJECT NAME: SOLAR PANELS PROJECT ID: PLAN CHECK NO: C6140392 SET#: ADDRESS: 2384 BOTELLA PL APN: ^ This plan check review is compiete and has been APPROVED by the PLANNING Division. By: GINARUIZ A Final Inspection by the PLANNING Division is required • Yes ^ No You may aiso have corrections from one or more ofthe divisions listed below. Approval from these divisions may be required prior to the issuance of a buiiding permit Resubmitted plans should include corrections from ali divisions. Q This plan check review is NOT COIVIPLETE. Items missing or incorrect are listed on the attached checklist. Please resubmit amended plans as required. Plan Check APPROVAL has been sent to: For questions or clarifications on the attached checklist please contact the following reviewer as marked: PLANNING 760-602-4610 ENGINEERiNG 760-602-2750 FIRE PREVENTION 760-602-4665 1 1 Chris Sexton 760-602-4624 Chris.Sexton@carlsbadca.eov f~| Kathieen Lawrence 760-602-2741 Kathleen.Lawrence@carlsbadca.fiov 1 1 Greg Ryan 760-602-4663 G reeorv. Rva n@ca rlsbadca.gov 1 Gina Ruiz 760-602-4675 Gina. Ru iz@carlsbad ca. ;So v Q Linda Ontiveros 760-602-2773 Li nda.Ontiveros@ca risbadca. fiov Q Cindy Wong 760-602-4662 Cvnth]a.Wonfi@carlsbadca,fiov • • 1 1 1 Dominic Fieri 760-602-4664 Dominic.Fieri@carlsbadca.gov Remarks: