Loading...
HomeMy WebLinkAbout2501 EL CAMINO REAL; 220; CB143015; PermitCity of Carlsbad 1635 Faraday Av Carlsbad, CA 92008 02-02-2015 Commercial/Industrial Permit Permit No: CB143015 Building Inspection Request Line (760) 602-2725 Job Address: 2501 EL CAMINO REAL CBADSt: 220 Permit Type: Tl Sub Type: COMM Status: ISSUED Applied: 11/04/2014 Entered By: LSM Parcel No: 1563020800 Lot#: 0 Valuation: $217,044.00 Construction Type: 3B Occupancy Group: Reference# Project Title: PANERA-3,600 SF Tl SHELL TO RESTAURANT Applicant: NIKKI STOUT 4635 CASS ST SAN DIEGO CA 92109 858-243-3240 Building Permit Add'l Building Permit Fee Plan Check Add'l Building Permit Fee Plan Check Discount Strong Motion Fee Park Fee LFM Fee Bridge Fee BTD #2 Fee BTD #3 Fee Renewal Fee Add'l Renewal Fee Other Building Fee Pot. Water Con. Fee Meter Size Add'l Pot. Water Con. Fee Reel. Water Con. Fee Green Bldg Stands (SB1473) Fee Fire Expedidted Plan Review $1,042.60 $0.00 $729.82 $35.40 $0.00 $60.77 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $0.00 $8.00 $385.00 Total Fees: $11,318.22 Total Payments To Date: Inspector: Owner: CMF PCR L L C Plan Approved: 02/02/2015 Issued: 02/02/2015 Inspect Area Plan Check#: C/0 WESTFIELD PROPERTY TAX DEPT PO BOX 130940 DEPT WFLD CARLSBAD, CA 92013 Meter Size Add'l Reel. Water Con. Fee Meter Fee SDCWA Fee CFD Payoff Fee PFF (3105540) PFF (4305540) License Tax (31 04193) License Tax (4304193) Traffic Impact Fee (31 05541) Traffic Impact Fee (4305541) PLUMBING TOTAL ELECTRICAL TOTAL MECHANICAL TOTAL Master Drainage Fee Sewer Fee Redev Parking Fee Additional Fees HMP Fee Green Bldg Standards Plan Chk TOTAL PERMIT FEES $11,318.22 Balance Due: Clearance: -- $0.00 $0.00 $0.00 $0.00 $3,950.20 $3,646.34 $0.00 $0.00 $0.00 $0.00 $250.00 $1,044.50 $165.59 $0.00 $0.00 $0.00 $0.00 ?? ?? $11,318.22 $0.00 NOTICE: Please take NOTICE that approval of your project includes the "Imposition" of fees, dedications, reservations, or other exactions hereafter collectively referred to as "fees/exactions." You have 90 days from the date this permit was issued to protest imposition of these fees/exactions. If you protest them, you must follow the protest procedures set forth in Government Code Section 66020(a), and file the protest and any other required information with the City Manager for processing in accordance with Carlsbad Municipal Code Section 3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack, review, set aside, void, or annul their imposition. You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection fees and capacity changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this project. NOR DOES IT APPLY to any fees/exactions of which ou have reviousl been iven a NOTICE similar to this or as to which the statute of limitations has reviousl otherwise ex ired. OHAZMAT/APCD Est. Value Building Permit Application 1635 Faraday Ave., Carlsbad, CA 92008 Ph: 760-602-2719 Fax: 760-602-8558 email: building@carlsbadca.gov www.carlsbadca.gov PlanCk. Deposit "7:/l.O. .i'~ t liS. JOB ADDRESS CT/PROJECT # LOT# #BEDROOMS TENANT BUSINESS NAME OCC. GROUP DESCRIPTION OF WORK: Include Square Feet of Affected Area(s) PW\tllvt Bv.evvt 1 ~t 3 I CPO 0 Sf. EXISTING USE GARAGE (SF) NE:W ADDRESS 4-lP -a ~ crt-ss ZIP 011-\0 CITY ?P\N STACA- PHONE qj?~ -':t-1-? -?;2-'1-0 FAX DESIGN PROFESSIONAL R \) ?S t?\V [A_ T CITY STATE CA ZIP PHONE<()c;~ _ 0~ \ ..-2.'0 !2 FAX EMAIL R-usse «-vssELL.STO LA-1 A:-65o POl.ol\ue..-~r€U~ PATIOS (SF) ADDRESS 2.-0 CITY Ctvl PHONE lp\Cj EMAIL ADDRESS ;Ls3 ~ FIREPLACE YEsO ll i"'- CITY., ,. , 1 [ vV'C I <A./ 1 '>'-14 s· AIR CONDITIONING NoD YES0No0 STATE ,1J e_,r:r-ZIP FIRE SPRINKLERS YESONoD (Sec. 7031.5 Business and Professions Code: Any City or County which requires a permit to construct, alter, improve, demolish or repair any structure, prior to its issuance, also requires the applicant for such permit to file a signed statement that he is licensed pursuant to the provisions of the Contractor's License Law {Chapter 9, commending with Section 7000 of Division 3 of the Business and Professions Code) or that he is exempt therefrom, and the basis for the alleged exemption. Any violation of Section 7031.5 by any applicant for a permit subjects the applicant to a civil penalty of not more than five hundred dollars {$500)). Workers' C~nsation Declaration: I hereby affirm under penalty of perjury one of the following declarations: ~£and will maintain a certificate of consent to self-insure for workers' compensation as provided by Section 3700 of the Labor Code, for the performance of the work for which this permit is issued. ~ I have and will maintain workers' c~m~ensation, as re u·re,~ by Se,.ction 370~e Labor Code, for the performance of the work for wp!ch t~s permit is issuef-Mf workers' , number are: Insurance Co. J' 0 0 u..J i/ tl uJ A) Policy No. 7 fo 0 V 0 eJ ] 7 )_ tf I / f Exptration Date --''+----''-.L~c.___t_-"£...... This section need not be completed if the permit is for one hundred dollars ($1 00) or less. 0 Certificate of Exemption: I certify that in the performance of the work for which this permit is issued, I shall not employ any person in any manner so as to become subject to the Workers' Compensation Laws of California. WARNING: Failure to secure workers' compensation coverage is unlawful, and shall subject an employer to criminal penalties and civil fines up to one hundred thousand dollars (&100,000), in addition to the cost of compensation, damages as pro·fided for in of the Labor interest and attorney's fees. ...---- 2$ CONTRACTOR SIGNATURE ~ . I hereby affirm that I am exempt from Contractor's License Law for the following reason: D D D I, as owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not intended or offered for sale (Sec. 7044, Business and Professions Code: The Contractor's License Law does not apply to an owner of property who builds or improves thereon, and who does such work himself or through his own employees, provided that such improvements are not intended or offered for sale, If, however, the building or improvement is sold within one year of completion, the owner-builder will have the burden of proving that he did not build or improve fm the purpose of sale). I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions Code: The Contractor's License Law does not apply t9,,an owner of property who builds or improves thereon, and contracts for such projects with contractor(s) licensed pursuant to the Contractor's License Law). I arn exempt under Section Business and Professions Code for this reason: 1. I personally plan to provide the major labor and materials for construction of the proposed property improvement DYes 0No 2. I (have I have not) signed an application for a building permit for the proposed work. 3. I have contracted with the following person (firm) to provide the proposed construction (include name address I phone I contractors' license number): 4. I plan to provide portions of the work, but I have hired the following person to coordinate, supervise and provide the major work (include name I address I phone I contractors' license number): 5. I will provide some of the work, but I have contracted (hired) the following persons to provide the work indicated (include name I address I phone I type of work): 2$ PROPERTY OWNER SIGNATURE 0AGENT DATE I certify that I have read the application and state that the above information is correct and thatthe information on the plans is accurate. I agree to comply with all City ordinances and State laws relating to building construction. I hereby authorize representative ofthe City of Carlsbad to enter upon the above mentioned property for inspection purposes. I ALSO AGREE TO SAVE, INDEMNIFY AND KEEP HARMLESS THE CITY OF CARLSBAD AGAINST ALL LIABILITIES, JUDGMENTS, COSTS AND EXPENSES I MAY IN ANY WAY ACCRUE AGAINST SAID CITY IN CONSEQUENCE OF THE GRANTING OF THIS PERMIT. OSHA: An OSHA permtt is required for excavations over 5'0' deep and or construction of structures over 3 stories in height. EXPIRATION: Every permit issued by the Building Official under the Code shall expire by limitation and become null and void if the building or work authorized by such permit is not commenced within 180 days from the date of such permit or if the permit is suspended or abandoned at anytime after the work is commenced for a period of 180 days (Section 106.4.4 Uniform Building Code). ~APPLICANT'S SIGNATURE DATE \\·4·\4- STOP: THIS SECTION NOT REQUIRED FOR BUILDING PERMIT ISSUANGE. Complete the following ONLY if a Certificate of Occupancy will be requested at final inspection. Cl!i'l:'fif!CA'TE OF OCCUPANCY IC:e~mmen:iai Projects Only! Fax (760) 602-8560, Email building@carlsbadca.gov or Mail the completed form to City of Carlsbad, Building Division 1635 Faraday Avenue, Carlsbad, California 92008. I CO#: (Office Use Only) CONTACT NAME OCCUPANT NAME ADDRESS BUILDING ADDRESS CITY STATE ZIP CITY STATE ZIP Carlsbad CA PHONE I FAX EMAIL OCCUPANT'S BUS. LIC. No. DELIVERY OPTIONS PICKUP: CONTACT (Listed above) OCCUPANT (Listed above) CONTRACTOR (On Pg. 1) ASSOCIATED CB# MAIL TO: CONTACT (Listed above) OCCUPANT (Listed above) CONTRACTOR (On Pg. 1) NO CHANGE IN USE/ NO CONSTRUCTION MAIL/ FAX TO OTHER: CHANGE OF USE/ NO CONSTRUCTION .2S APPLICANT'S SIGNATURE DATE I pecti n ist Permit#: CB143015 Type: Tl Date __ __lr!!>_e_ecti~!'_l~m --· 04/21/2015 89 Final Combo 04/21/2015 89 Final Combo 04/20/2015 89 Final Combo 04/20/2015 89 Final Combo 04/06/2015 33 Service Change/Upgrade 04/01/2015 85 T-Bar 03/30/2015 23 Gas/Test/Repairs 03/30/2015 85 T-Bar 03/17/2015 18 Exterior Lath/Drywall 03/17/2015 23 Gas/Test/Repairs 03/10/2015 17 Interior Lath/Drywall 03/04/2015 14 Frame/Steei/Bolting!Weldin 03/04/2015 24 Roug hiT opout 03/04/2015 34 Rough Electric 03/03/2015 24 Rough/Topout Monday, April 27, 2015 COMM Inspector Act Rl py AP Rl py NR py AP py PA PO PA PO PA py AP py AP PY AP py AP py AP PY AP py NR PANERA-3,600 SF Tl SHELL TO RESTAURANT Comments ---·------·----- FIRE SIGNS OFF IN EARLY AM PANERA BREAD/PM PLEASE/ FIRE SIGNS OFF IN PM Page 1 of 1 EsGil Corporation In Partners!iip witli qowrnment for (}3ui(aing Safety DATE: 1/21/15 Cl APPLICANT Cl JURIS. JURISDICTION: City of Carlsbad Cl PLAN REVIEWER Cl FILE PLAN CHECK NO.: 1~3.0 015 SET: II ·~-t)l PROJECT ADDRESS: ~525-El Camino Real Suite 220 PROJECT NAME: Panera Bread Restaurant-TI D D D D D The plans transmitted herewith have been corrected where necessary and substantially comply with the jurisdiction's codes. The plans transmitted herewith will substantially comply with the jurisdiction's building codes when minor deficiencies identified below are resolved and checked by building department staff. The plans transmitted herewith have significant deficiencies identified on the enclosed check list and should be corrected and resubmitted for a complete recheck. The check list transmitted herewith is for your information. The plans are bl3ing held at Esgil Corporation until corrected plans are submitted for recheck. The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant contact person. , The applicant's copy of the check list has been sent to: EsGil Corporation staff did not advise the applicant that the plan check has been completed. EsGil Corporation staff did advise the applicant that the plan check has been completed. Person contacted: Telephone#: Date contacted: (by: ) ~~il: \\S~ Mail Telephone Fax In Person O ~ \\4-1\... REMARKS: Per Mike Peterson, the plans are to be r~ned and City Staff will resolve the remaining item. By: Doug Moody EsGil Corporation D GA D EJ D MB D PC Enclosures: LOG 9320 Chesapeake Drive, Suite 208 + San Diego, California 92123 + (858) 560-1468 + Fax (858) 560-1576 r;:::' ' :;! EsGil Corporation In CJ!artnersliip witli government for (}3uiftfing Safety DATE: 1/13/15 JURISDICTION: City of Carlsbad PLAN CHECK NO.: 14-3015 ol SET: II PROJECT ADDRESS: 252'S""El Camino Real Suite 220 PROJECT NAME: Panera Bread Restaurant-TI V,PPLICANT /n ~URIS. D PLAN REVIEWER D FILE D The plans transmitted herewith have been corrected where necessary and substantially comply with the jurisdiction's codes. D The plans transmitted herewith will substantially comply with the jurisdiction's codes when minor deficiencies identified below are resolved and checked by building department staff. D The plans transmitted herewith have significant deficiencies identified on the enclosed check list and should be corrected and resubmitted for a complete recheck. ~ The check list transmitted herewith is for your information. The plans are being held at Esgil Corporation until corrected plans are submitted for recheck. D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant contact person. 0 The applicant's copy of the check list has been sent to: D EsGil Corporation staff did not advise the applicant that the plan check ha8 been completed. ~ EsGil Corporation staff did advise the applicant that the plan check has been completed. Person contacted: Nikki Stout Telephone#: 858-243-3240 ;Date contacted: \ ( !'~(by: ~Email: russ@russellstoutassoc.com Jfl Mail Telephone Fax In Person D REMARKS: By: Doug Moody EsGil Corporation 0 GA 0 EJ 0 MB 0 PC Enclosures: 1/7/15 9320 Chesapeake Drive, Suite 208 + San Diego, California 92123 + (858) 560-1468 + Fax (858) 560-1576 C'ity of Carlsbad 14-3015 1/13/15 Please make all corrections on the original tracings, as requested in the correction list. Submit three sets of plans for commercial/industrial projects (two sets of plans for residential projects). For expeditious processing, corrected sets can be submitted in one of two ways: 1. Deliver all corrected sets of plans and calculations/reports directly to the City of Carlsbad Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760) 602-2700. The City will route the plans to EsGil Corporation and the Carlsbad Planning, Engineering and Fire Departments. 2. Bring one corrected set of plans and calculations/reports to EsGil Corporation, 9320 Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-1468. Deliver all remaining sets of plans and calculations/reports directly to the City of Carlsbad Building Department for routing to their Planning, Engineering and Fire Departments. NOTE: Plans that are submitted directly to EsGil Corporation only will not be reviewed by the City Planning, Engineering and Fire Departments until review by EsGil Corporation is complete. These corrections are in response to items not fully addressed or as the result of information provided, the text in bold print indicates the unresolved issue. 2. Please review the requirements, revise the plans appropriately (sheet M-1.2) and imprint on the plans the City of Carlsbad Policies and Procedures for Roof Mounted Equipment to the plans. The sheet M-1.2 stills shows the make-up air duct work being run across the roof this is not permitted. Please correct the plans. To speed up the review process, note on this list (or a copy) wh~~re each correction item has been addressed, i.e., plan sheet, note or detail number, calculation page, etc. Please indicate here if any changes have been made to the plans that are not a result of corrections from this list. If there are other changes, please briefly describe them and where they are located in the plans. Have changes been made to the plans not resulting from this correction list? Please indicate: Yes D No D The jurisdiction has contracted with Esgil Corporation located at 9320 Chesapeake Drive, Suite 208, San Diego, California 92123; telephone number of 858/560-1468, to perform the plan review for your project. If you have any questions regarding these plan review items, please contact Doug Moody at Esgil Corporation. Thank you. EsGil Corporation In a>artnersliip witli government for CJ3ui(aing Safety DATE: 11/14/14 JURISDICTION: City of Carlsbad PLAN CHECK NO.: 14-3015 SET: I PROJECT ADDRESS: 2525 El Camino Real Suite 220 PROJECT NAME: Panera Bread Restaurant-TI D APPLICANT ~URIS. D PLAN REVIEWER D FILE D The plans transmitted herewith have been corrected where necessary and substantially comply with the jurisdiction's codes. D The plans transmitted herewith will substantially comply with the jurisdiction's codes when minor deficiencies identified below are resolved and checked by building department staff. D The plans transmitted herewith have significant deficiencies identified on the enclosed check list and should be corrected and resubmitted for a complete recheck. [g) The check list transmitted herewith is for your information. The plans are being held at Esgil Corporation until corrected plans are submitted for recheck. D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant contact person. D The applicant's copy of the check list has been sent to: D EsGil Corporation staff did not advise the applicant that the plan check has been completed. [g) EsGil Corporation staff did advise the applicant that the plan check has been completed. Person contacted: Nikki Stout Telephone#: 858-243-3240 ~ate contacted: II) 14--(b>1(~~ Email: russ@russellstoutassoc.com 4JMail Telephone Fax In Person D REMARKS: By: Doug Moody EsGil Corporation D GA D EJ D MB D PC Enclosures: 11/6/14 9320 Chesapeake Drive, Suite 208 + San Diego, California 92123 + (858) 560-1468 + Fax (858) 560-1576 City of Carlsbad 14-3015 11/14/14 PLAN REVIEW CORRECTION LIST TENANT IMPROVEMENTS PLAN CHECK NO.: 14-3015 OCCUPANCY: A2 TYPE OF CONSTRUCTION: liB ALLOWABLE FLOOR AREA: SPRINKLERS?: Yes REMARKS: DATE PLANS RECEIVED BY JURISDICTION: 11/4/14 DATE INITIAL PLAN REVIEW COMPLETED: 11/14/14 FOREWORD (PLEASE READ): JURISDICTION: City of Carlsbad USE: Restaurant ACTUAL AREA: 3600sf STORIES: 1 HEIGHT: OCCUPANT LOAD: 87 DATE PLANS RECEIVED BY ESGIL CORPORATION: 11/6/14 PLAN REVIEWER: Doug Moody This plan review is limited to the technical requirements contained in the California version of the International Building Code, Uniform Plumbing Code, Uniform Mechanical Code, National Electrical Code and state laws regulating energy conservation, noise attenuation and access for the disabled. This plan review is based on regulations enforced by the Building Department. You may have other corrections based on laws and ordinances enforced by the Planning Department, Engineering Department, Fire Department or other departments. Clearance from those departments may be required prior to the issuance of a building permi1t. Code sections cited are based on the 2013 CBC, which adopts the 2012 IBC. The following items listed need clarification, modification or change. All items must be satisfied before the plans will be in conformance with the cited codes and regulations. Per Sec. 105.4 of the 2012 International Building Code, the approval of the plans does not permit the violation of any state, county or city law. To speed up the recheck process, please note on this list (or a copy) where each correction item has been addressed, i.e., plan sheet number, specification section, etc. Be sure to enclose the marked up list when you submit the revised plans. City of Carlsbad 14-3015 11/14/14 Please make all corrections on the original tracings, as requested in the correction list. Submit three sets of plans for commercial/industrial projects (two sets of plans for residential projects). For expeditious processing, corrected sets can be submitted in one of two ways: 1. Deliver all corrected sets of plans and calculations/reports directly to the City of Carlsbad Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760) 602-2700. The City will route the plans to EsGil Corporation and the Carlsbad Planning, Engineering and Fire Departments. 2. Bring one corrected set of plans and calculations/reports to EsGil Corporation, 9320 Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-1468. Deliver all remaining sets of plans and calculations/reports directly to the City of Carlsbad Building Department for routing to their Planning, Engineering and Fire Departments. NOTE: Plans that are submitted directly to EsGil Corporation only will not be reviewed by the City Planning, Engineering and Fire Departments until review by EsGil Corporation is complete. 1. Please provide plans and calculations signed by the California State licensed engineer or architect for the structural design of the exterior alterations to the building shown on sheet A-5.1. Include all calculations and finding on the plans. Please include the California license number, seal, date of license expiration and date plans are signed. Business and Professions Code. 2. Please review the requirements, revise the plans appropriately (sheet M-1.2) and imprint on the plans the City of Carlsbad Policies and Procedures for Roof Mounted Equipment to the plans. • NON-RESIDENTIAL GREEN BUILDING STANDARDS (Additions and Alterations) The California Building Standards Commission (BSC) has adopted the Green Building Standards Code which became effective January 1, 2011, and must be enforced by the local building official. The Green Building Standards apply to nonresidential additions or tenant improvements throughout California. These standards apply to nonresidential additions of 1,000 sq. ft. or larger or alterations (tenant improvements) with a value of $200,000 or more. CGC Section 301.3. Provide a sheet on the plans labeled "Green Building Code Requirements" and include the following notes as applicable. 3. Light pollution reduction. Note on the plans that exterior light pollution must comply with CGC section 5.1 06.8. 4. Waste management. Note on the plans that the contractor must submit to the Engineering Department or other Agency that regulates construction waste management a Waste Management Plan that outlines the items listed in CGC Section 5.408.1.1. City of Carlsbad 14-3015 11/14/14 5. Recycling. Note on the plans that a minimum of 50% of construction waste is to be recycled. CGC 5.408.1. Documentation shall be provided to the enforcing agency which demonstrates compliance. CGC Section 5.408.1.4. 6. Recycling. Note on the plans that an identified, readily accessible area shall be provided that serves the entire building for collecting recycling, such as paper, cardboard, glass, plastics, metals, etc. CGC Section 5.41 0.1. 7. Documentation. Note on the plans that a building "Systems Manual" as listed in CGC Section 5.41 0.2.5 shall be delivered to the building owner or representative and the facilities operator. Further, note on the plans that the "Systems Manual" shall contain the required features listed in CGC Section 5.41 02.5.1. 8. Pollutant control. Note on the plans that during construction, ends of duct openings are to be sealed, and mechanical equipment is to be covered. CGC 5.504.3. 9. Pollutant control. Note on the plans that VOC's must comply with the limitations listed in Section 5.504.4 and Tables 4.504.1, 5.504.4.1 5.504.4.2, 5.504.4.3 and 5.504.4.5 for: Adhesives, Sealants, Paints and Coatings, Carpet and Composition Wood Products. CGC 5.504.4. 10. Pollutant control. Note on the plans that mechanically ventilated buildings shall provide regularly occupied areas with air filtration media for outside and return air that provides at least a Minimum Efficiency Reporting Value (MERV) of 8. MERV 8 filters shall be installed prior to occupancy. CGC Section 5.504.5.3. 11. Environmental comfort. Wall and roof assemblies exposed to noise sources shall have an STC rating of at least 50, with exterior windows having a minimum STC of 40 in the following locations, per CGC Section 5.507.4.1: a) Within the 65 CNEL noise contour of a freeway, railroad or industrial source, as determined by the jurisdiction's Noise Element of the General Plan. b) Within the 65 CNEL noise contour of an airport. c) Note on the plans whether or not this addition or tenant improvement is located within the areas listed above. 12. Outdoor air quality. Note on the plans that installations of HVAC, refrigeration and fire suppression systems will not contain CFC's or Halons, per CGC 5.508.1. 13. Note on the plans that prior to final inspection the licensed contractor, architect or engineer in responsible charge of the overall construction must provide to the building department official written verification that all applicable provisions from the Green Building Standards Code have been implemented as part of the construction. CGC 1 02.3. City of Carlsbad 14-3015 11/14/14 To speed up the review process, note on this list (or a copy) where each correction item has been addressed, i.e., plan sheet, note or detail number, calculation page, etc. Please indicate here if any changes have been made to the plans that are not a result of corrections from this list. If there are other changes, please briefly describe them and where they are located in the plans. Have changes been made to the plans not resulting from this correction list? Please indicate: Yes D No D The jurisdiction has contracted with Esgil Corporation located at 9320 Chesapeake Drive, Suite 208, San Diego, California 92123; telephone number of 858/560-1468, to perform the plan review for your project. If you have any questions regarding these plan review items, please contact Doug Moody at Esgil Corporation. Thank you. City of Carlsbad 14-3015 11/14/14 [DO NOT PAY-THIS IS NOT AN INVOICE] VALUATION AND PLAN CHECK FEE JURISDICTION: City of Carlsbad PREPARED BY: Doug Moody PLAN CHECK NO.: 14-3015 DATE: 11/14/14 BUILDING ADDRESS: 2525 El Camino Real Suite 220 BUILDING OCCUPANCY: A2 BUILDING AREA Valuation PORTION (Sq. Ft.) Multiplier Tl 3600 City Valuation Air Conditioning Fire Sprinklers TOTAL VALUE Jurisdiction Code cb By Ordinance Bldg. Permit Fee by Ordinance Pian Check Fee by Ordina nee Type of Review: [!] Complete Review 0Repetitive Fee .,... Repeats D Other D Hourly EsGil Fee Reg. VALUE Mod. D Structural Only 1------11 H r @ • ($) 217,044 217,044 $1,044.961 $679.221 $585.181 Comments: In addition to the above fee, an additional fee of $86.00 is due (1 hours@ $86.00/hr.) for. the CaiGreen review. Sheet 1 of 1 macvalue.doc + DATE: PLAN CHECK REVIEW TRANSMITTAL PROJECT NAME: WestField Community & Economic Development Department 1635 Faraday Avenue Carlsbad CA 92008 www .carlsbadca.gov PROJECT ID: PLAN CHECK NO: 1 SET#: 1 ADDRESS: El Real APN: VALUATION: This plan check review is complete and has been APPROVED by the Division. By: A Final Inspection by the Division is required Yes No This plan check review is NOT COMPLETE. Items missing or incorrect are listed on the attached checklist. Please resubmit amended plans as required. Plan Check Comments have been sent to: For questions or clarifications on the attached checklist please contact the following reviewer as marked: Chris Sexton 760-602-4624 Gina Ruiz 760-602-4675 Remarks: VaiRay Marshall 760-602-2773 VaiRay.Marshall@carlsbadca.gov Linda Ontiveros 760-602-2773 Cindy Wong 760-602-4662 Dominic Fieri 7 60-602-4664 Dominic.Fieri@carlsbadca.gQY. BUILDING PLANCHECK CHECKLIST QUICK-CHECK/APPROVAL Land Development Engineering 1635 Faraday Avenue 760-602-2750 www.carlsbadca.gov ENGINEERING Plan Check for Date: 1 Project Address: P . t D . t' Tl roJec escnp 1on: SF ENGINEERING Contact : Phone: ·RESIDENTIAL INTERIOR RESIDENTIAL ADDITION MINOR (<$20,000.00) APN: Valuation: Email: Fax: TENANT IMPROVEMENT PLAZA CAMINO REAL CARLSBAD PREMIER OUTLETS COMPLETE OFFICE BUILDING OTHER: GYM r··-··-··-··-··-··-··-··-··-··-··-··-··-··-··-··-··-··-.. , OFFICIAL USE ONLY ENGINEERING AUTHORIZATION TO ISSUE BUILDING PERMIT BY: DATE: 4 REMARKS: Notification of Engineering APPROVAL has been sent to via on 1 4 F-36 PaQe 1 of 1 REV 4/30/11 PLANNING DIVISION BUILDING PLAN CHECK APPROVAL P-29 Development Services Planning Division 1635 Faraday Avenue (760) 602-4610 www.carlsbadca.2ov DATE: 11/13/2014 PROJECT NAME: Panera Bread PROJECT ID: EIR 09-02/SDP 09-04 PLAN CHECK NO: CB143015 SET#: 1 ADDRESS: 2501 ECR, Suite #220 APN: 156-302-08 ~ This plan check review is complete and has been APPROVED by the Planning Division. By: Jason Goff, Associate Planner (1.1>- A Final Inspection by the Planning Division is required DYes ~~No You may also have corrections from one or more of the divisions listed below. Approval from these divisions may be required prior to the issuance of a building permit. Resubmitted plans should include corrections from all divisions. D This plan check review is NOT COMPLETE. Items missing or incorrect are listed on the attached checklist. Please resubmit amended plans as required. Plan Check APPROVAL has been sent to: russ@russellstoutassoc.com ~ For questions or clarifications on the attached checklist please contact the following reviewer as marked: PLANNING ENGINEERING FIRE PREVENTION 760-602-4610 760-602-2750 760-602-4665 D Chris Sexton D Kathleen Lawrence D Greg Ryan 760-602-4624 760-602-27 41 760-602-4663 Chris.Sexton@carlsbadca.gov Kathleen. Lawrence@carlsbadca.gov Gregory.R:tan@carlsbadca.gov D Gina Ruiz D Linda Ontiveros D Cindy Wong 760-602-467 5 760-602-2773 760--602-4662 Gina.Ruiz@carlsbadca.gov Linda.Ontiveros@carlsbadca.gov C:tnthia. W<ong@carlsbadca.gov ~ Jason Goff cJfr D D Dominic Fieri 760-602-4643 760-602-4664 Jason.Goff@carlsbadca.gov Dominic.Fieri@carlsbadca,gov Remarks: '£ «'~ ~ CITY OF CARLSBAD PLAN CHECK REVIEW TRANSMITTAL DATE: 1/27/14 PROJECT NAME: panera bread PROJECT ID: Community & Economic Development Department 1635 Faraday Avenue Carlsbad CA 92008 www.carlsbadca.gov PLAN CHECK NO: cb143015 SET#: I ADDRESS: 2501 ecr ste 220 APN: !ZI This plan check review is complete and has been APPROVED by the fire Division. By: cwong A Final Inspection by the Division is required [gJ Yes D No D This plan check review is NOT COMPLETE. Items missing or incorrect are listed on the attached checklist. Please resubmit amended plans as required. Plan Check Comments have been sent to You may also have corrections from one or more of the divisions listed below. Approval from these divisions may be required prior to the issuance of a building permit. Resubmitted plans should include corrections from all divisions. For questions or clarifications on the attached checklist please contact the following reviewer as marked: 0 Chris Sexton 760-602-4624 Ch ris.Sexton@carlsbadca.gov 0 Gina Ruiz 760-602-4675 Gina.Ruiz@carlsbadca.gov D Remarks: D Kathleen Lawrence 760-602-27 41 Kathleen.Lawrence@carlsbadca.gov D D Linda Ontiveros 760-602-2773 Linda.Ontiveros@carlsbadca.gov 0 Greg Ryan 760-602-4663 Gregory.Ryan@carlsbadca.gov ~ CindyWong 760-602-4662 Cynthia. Wong@carlsbadca.gov 0 Dominic Fieri 760-602-4664 Dominic.Fieri@carlsbadca.gov . );_ ***The following note shall be added to Sheet A-2.1A in order for Fire Approval to be rr valid*** Page 1 of2 Item #D42B-Bulk C02: Bulk C02 storage shall meet requirements of Section 5307, CFC, ~2013 edition, including referenced sections (e.g. 5004.3:1 cu ftjmin/ft2) c I' \*APPROVED: THIS PROJECT HAS BEEN REVIEWED AND APPROVED FOR THE PURPOSES OF ISSUEANCE OF A BUILDING PERMIT. THIS APPROVAL IS SUBJECT TO FIELD INSPECTIONS, ANY REQUIRED TESTS, FIRE DEPARTMENT NOTATIONS, CONDITIONS IN CORRESPONDENCE AND COMPLIANCE WITH ALL APPLICABLE CODES AND REGULATIONS. THIS APPROVAL SHALL NOT BE HELD TO PERMIT OR APPROVE ANY VIOLATION OF THE LAW. Page 2 of2 Iii Carlsbad Fire Department Plan Review Requirements Category: TI , COMM Date ofReport:Ol-27-2015 Reviewed by: _v_,;:{-"'c-""{"""';_n_~_)_'Lf__,\,:-T--/ __ l /1 LJ Name: Address: Permit#: CB143015 NIKKI STOUT 4635 CASS ST SANDIEGO CA 92109 Job Name: PANERA-3,600 SF TI SHELL TO Job Address: 2501 EL CAMINO REAL CBAD St: 220 INCOMPLETE The item you have submitted for review is incomplete. At this time, this office cannot ~~nductaL~~i~~!Q_<letermine compliance with the applicable codes and/or standards. Please review carefully all comments attached.~P1e-ase-~~~!l12mit.too-neeessacyp!ans-·anarorsifec1ficat1ollS;wlf1:lcnangeSTrcrouCled", to this office for revie~_@dappr<5VaT:''---·------·--___ _ ~-~-· .. , .. __ Conditions: Cond: CON0008005 [MET] ***The following note shall be added to Sheet A-2.1A in order for Fire Approval to be valid*** Item #D42B -Bulk C02: Bulk C02 storage shall meet requirements of Section 5307, CFC,2013 edition, including referenced sections (e.g. 5004.3: 1 cu ft/min/ft2) Entry: 0 1127/2015 By: cwong Action: AP Daryl K. James & Associates, Inc. APPLICANT: Nikki Stout PROJECT NAME: Panera Bread BI~DCt DEPT COPY RECOMMENDEDFORAPPROVAL Checked by: ROBERT SCOTT Date: January 20, 2015 JURISDICTION: Carlsbad Fire Department PROJECT ADDRESS: 2501 El Camino Re~al #220 PROJECT DESCRIPTION: CB14-3015-Tenant Improvement of 3,600 1!1 in existing Sprinklered, 2 story shell building. Work includes install Type-11 exhaust Hood, HVAC, electrical and plumbing, cooking appliances, doors, walls and interior finish. This plan review has been conducted in order to verify conformance to minimum requirements of codes adopted by the Carlsbad Fire Department. The items below require correction, clarification or additional information before this plan check can be approved for permit issuance. The items below have all been corrected or clarified with additio,nal information provided, therefore, CB14-3015 is recommended for approval for permit issuance. COMMENTS -Additional comments made shall be generated by response on revised ~;et and Clouded REVISE 'Deferred Submittals' section: Provide the following list of Deferred Submittals and Delete all other existing notes in deferred submittal section: -Fire Sprinkler System -2013 CFC 903 and 2013 NFPA 13 -Fire Alarm System -2013 CFC 907.2 and 2013 NFPA 72 -Commercial Hood & Duct System-2013 CFC Section 904 and NFPA 17A. -Denote adjacent occupancy classifications (See site and/floor plan for occupancy separation provisions) esc 508.4 ~ Revise or Delete the following 'Fire Notes': notes as follows: -Revise note# 2 to read:-All exits shall be openable from inside without use of a key. Main exit doors with keyed deadbolts may have a sign, with minimum one-inch high letters, mounted inside above door that reads "This door to remain unlocked whenever building is occupied". 2013 CBC -Revise Note # 8 to read: Means of egress illumination level shall be not less than '1-foot candle at the walking surface and equipped with minimum 90 minute battery backup where required. CBC1006. -Revise Note # 9 to read: demolition work shall comply with 2013 CFe Chapter 33. -Delete Notes# 12, 13, 14, 15, 17, 19-8, C, D & 20-A & B. Note: All fire protection systems (sprinkler, fire alarm, emergency devices) and any reference to fire protection systems are deferred submittal only. ~ ADD NOTES to 'Fire Department Notes' section as follows: -Add note: the means of Egress shall be illuminated at all times building space is served, in accordance with CA. Building Code, Section 1006.1; 1006.2. And 1006.3. -Add Note: A photometric plan of all occupied areas, that demonstrates compliance with CBC 1006 will be provided upon request by the Carlsbad Fire Dept., Deputy Fire Marshal Greg Ryan (760) 602-4665 -Add note: Address numbers shall be mounted on building in visible location. Numbe1·s shall be minimum 12 inches in height, with 1-1/2 inch stroke and contrast in color to background. **Show location of proposed numeric address on building. CBD 17 .04.320. -Add Note to read: All exits shall be openable from inside without use of a key. Main exit doors with keyed deadbolts may have a sign, with minimum one-inch high letters, mounted inside above door that reads "This door to remain unlocked whenever building is occupied". 2013 esc. -Add Note: Posted sign for Maximum Occupant Load shall be of an approved legible permanent design. esc 1004.3 M UL300 hood & duct extinguishing system shall be designed in accordance with CFC Sections 904.11, 609 and 2009 NFPA 17A. UL 300 hood & duct exhaust and extinguishing system plans to include, but not be limited to, manufacturer's Installation & service manual, plans providing designed details and dimensions of appliances, height of nozzles above cooking surfaces. Hood & duct extinguishing system in accordance with manufacturer's Installation & Service Manual. All work shall be performed by a C-16 licensed fire protection contractor. -Fire Alarm System (Interconnection of Hood Suppression System) Fire alarm system plans shall be submitted to Carlsbad fire department for approval prior to any work being conducted. Location of fire alarm panel, operation and sequence of fire alarm devices and hood suppression system shall comply with Carlsbad Fire Department Requirements, 2013 CFC 907 and 2010 NFPA 72 - A C-16 licensed fire protection contractor shall perform all fire sprinkler system work and fire protection system for cooking appliances work. A C-1 0 licensed fire alarm contractor shall perform all fire alarm system work. No fire protection system work shall be performed without fire dept. approved plans. -The contractor shall contact Carlsbad Fire Department prior to taking existing fire sprinkler system out of service, if system will be out of service overnight. Relocation of fire sprinklers in existing space requires Carlsbad Fire Dept. approval. Revise 'Fire Dept. Notes' as follows: -The type, rating and number of fire extinguishers shall comply with 2013 CFC, section 906.3. A minimum of three (or more) properly spaced fire extinguishers rated at 2A-1 OBC are required for dining area, kitchen and other areas. Maximum Travel distance to fire extinguishers shall not exceed 75 feet. All fire extinguishers shall be mounted in accessible and visible location, not to exceed 5 feet above finished floor to top of extinguisher. When cooking appliances with grease laden vapors are installed; the kitchen will require a class K' fire extinguisher installed within 30 feet of cooking appliances. CFC 906. -Delete Notes in this section that reference 'storage use and dispensing of Hazardous Materials'; they are not applicable. -Delete the note referencing plan submittal for sprinkler system to Anaheim Fire dept. All fire protection system notes are deferred submittal only. A-2.1A Add the following Information on 'Egress Plan': -Provide an egress analysis denoting the occupancy classification as per CBC Chapter 3, the square feet, occupant load factor and occupant load for each room and area based on the function of each area or room. CBC Table 1004.1.1 -Indicate on plan, door swing for all doors that serve an occupant load of 50 or more persons. CBC 1008.1.2 -Where two exits are required, denote the distance between exits. 1015.2.1 -Denote the aggregate square footage, required number of exits, required and actual width of exits. CBC 1005 A-2.1A -Show number of occupants exiting at each exit discharge. -Denote the exit designated as the Main Exit. -Denote common paths and lengths of egress travel CBC 1014.3 -Denote common paths and lengths of travel distance to each exit discharge. CBC 1016 -Address egress through intervening rooms. CBC 1014.2 Keyed Note # 1.2: add note to read: New carpet, padding and carpet base shall comply with California State Fire Marshal listings or other acceptance criteria for flame spread and smoke developed index. CFC 804. -Add note: Suspended Ceiling Plan notes that read: Suspended acoustical ceilings shall comply with section 808.1 and 808.1.1.1 of 2010 CBC and meet flame spread and smoke developed ratings. Revise Door Note# 18, A-ll. This note shall read as follows: All exits shall be openable from inside without use of a key. Main exit doors with keyed deadbolts may have a sign, with minimum one-inch high letters, mounted inside above door that reads "This door to remain unlocked whenever bUJilding is occupied". 2013 CBC. -Add note: Address numbers shall be mounted on building in visible location. Numbers shall be minimum 12 inches in height, with 1-1/2 inch stroke and contrast in color to background. **Show location of proposed numeric address on building. CBD 17.04.320. -Add Note to 'General Notes' that reads: All gas piping for water heater and all other gas piping located in interior space shall be labeled every 20 feet and every change of direction with labels that read 'Natural Gas. The gas meter shall be identified with a permanent tag indicating address that gas meter serves suite or address. Delete note# 9 in 'plan check note'. This note referencir'1g type-11 clothes dryers is not applicable. Note# 15, delete this note if a pizza oven is Not going to be installed. -Denote air-moving systems supplying air in excess of 2000 cfm equipped with smoke detectors approved and listed by the California State Fire Marshal. CMC 609. -Denote units provided with smoke detectors on plans. Add Notes to Roof Plan as follows: -Imprint Carlsbad Policy 80-6 on to roof plan. -Intent 8 (Fireman Safety) will be provided on roofs of buildings. -Indicate location of Roof Access. ADD the following notes: -Add Note: Means of egress illumination level shall be not less than 1-foot candle at the walking surface and equipped with minimum 90 minute battery backup where required. CBC1006. -Add Note: Exit signs shall be illuminated at all times and equipped with minimum 90-minute battery backup. CBC 1011.5.3 -Add note: the means of Egress shall be illuminated at all times building space is served, in accordance with CA. Building Code, Section 1006.1; 1006.2. And 1006.3. -Add Note: Additional illuminated 'EXIT' signs may be required on the retail sales floor area or other areas of store to clearly indicate path of exit travel. -Add Note: A photometric plan of all occupied areas, that demonstrates compliance with CBC 1006 will be provided upon request by the Carlsbad Fire Dept., Deputy Fire Marshal Greg Ryan (760) 602-4665 Recommend Approval R. Scott CORRECTION LIST Daryl K. James & Associates, Inc. Page 1 or 4 Checked by: ROBERT SCOTT Date: November 12, 2014 APPLICANT: Nikki Stout PROJECT NAME: Panera Bread JURISDICTION: Carlsbad Fire Department PROJECT ADDRESS: 2501 El Camino Real #220 PROJECT DESCRIPTION: CB14-3015 -Tenant Improvement of 3,600 Q:J in existing Sprinklered, 2 story shell building. Work includes install Type-11 exhaust Hood, HVAC, electrical and plumbing, cooking appliances, doors, walls and interior finish. This plan review has been conducted in order to verify conformance to minimum requirements of codes adopted by the Carlsbad Fire Department. The items below require correction, clarification or additional information before this plan check can be approved for permit issuance. INSTRUCTI(i)Ns FOR EXPEDlTED..PLA1N REMIEW'SERVICE • CORRECTIONS OR MODIFICATIONS TO THE PLANS MUST BE CLOUDED AND PROVIDED WITH NUMBERED DELTAS AND REVISION DATES ALONG WITH A DESCRIPTIVE NARRATIVE OF CORRECTIONS ADDRESSING ALL COMMENTS. PLEASE BE SURE TO PUT FIRE REVISIONS ON THE BUILDING DEPT. PLAN CHECK SET. • PLEASE DIRECT ANY QUESTIONS REGARDING THIS REVIEW TO: ROBERT SCOTT 760- 402-3976 OR FYRWISE07@GMAIL.COM • CORRECTED PLANS, DESCRIPTIVE NARRATIVE OF REVISIONS FOLLOWING EACH COMMENT ON THIS FORM, AND A COPY OF BUILDING DEPARTMENT (ESGIL} • ONE COMPLETE PLAN CHECK SET (initial or revised} MUST BE DELIVERED DIRECTLY TO THE FOLLOWING ADDRESS TO AVOID DELAY: ROBERTSCOTT 4906 ~!iAUC~~AVfE ... S~N DIEGO, CA.,92120 COMMENTS -Additional comments made shall be generated by response on revised set and Clouded G-CS REVISE 'Deferred Submittals' section: Provide the following list of Deferred Submittals and Delete all other existing notes in deferred submittal section: -Fire Sprinkler System -2013 CFC 903 and 2013 NFPA 13 -Fire Alarm System-2013 CFC 907.2 and 2013 NFPA 72 -Commercial Hood & Duct System-2013 CFC Section 904 and NFPA 17A. .t'age 1. or 4 G-GN -Denote adjacent occupancy classifications (See site and/floor plan for occupancy separation provisions) CBC 508.4 >-Revise or Delete the following 'Fire Notes': notes as follows: -Revise note # 2 to read: -All exits shall be openable from inside without use of a key. Main exit doors with keyed deadbolts may have a sign, with minimum one-inch high letters, mounted inside above door that reads "This door to remain unlocked whenever building is occupied". 2013 CBC -Revise Note# 8 to read: Means of egress illumination level shall be not less than 1-foot candle at the walking surface and equipped with minimum 90 minute battery backup where required. CBC1006. -Revise Note # 9 to read: demolition work shall comply with 2013 CFC Chapter 33. -Delete Notes# 12, 13, 14, 15, 17, 19-B, C, D & 20-A & B. Note: All fire protection systems (sprinkler, fire alarm, emergency devices) and any reference to fire protection systems are deferred submittal only. >-ADD NOTES to 'Fire Department Notes' section as follows: -Add note: the means of Egress shall be illuminated at all times building space is served, in accordance with CA. Building Code, Section 1006.1; 1006.2. And 1006.3. -Add Note: A photometric plan of all occupied areas, that demonstrates compliance with CBC 1006 will be provided upon request by the Carlsbad Fire Dept., Deputy Fire Marshal Greg Ryan (760) 602-4665 -Add note: Address numbers shall be mounted on building in visible location. Numbers shall be minimum 12 inches in height, with 1-1/2 inch stroke and contrast in color to background. **Show location of proposed numeric address on building. CBD 17.04.320. -Add Note to read: All exits shall be openable from inside without use of a key. Main exit doors with keyed deadbolts may have a sign, with minimum one-inch high letters, mounted inside above door that reads "This door to remain unlocked whenever building is occupied". 2013 CBC. -Add Note: Posted sign for Maximum Occupant Load shall be of an approved legible permanent design. CBC 1004.3 -UL300 hood & duct extinguishing system shall be designed in accordance with CFC Sections 904.11, 609 and 2009 NFPA 17 A. UL 300 hood & duct exhaust and extinguishing system plans to include, but not be limited to, manufacturer's Installation & service manual, plans providing designed details and dimensions of appliances, height of nozzles above cooking surfaces. Hood & duct extinguishing system in accordance with manufacturer's Installation & Service Manual. All work shall be performed by a C-16 licensed fire protection contractor. -Fire Alarm System (Interconnection of Hood Suppression System) Fire alarm system plans shall be submitted to Carlsbad fire department for approval prior to any work being conducted. Location of fire alarm panel, operation and sequence of fire alarm devices and hood suppression system shall comply with Carlsbad Fire Department Requirements, 2013 CFC 907 and 2010 NFPA 72 - A C-16 licensed fire protection contractor shall perform all fire sprinkler system work and fire protection system for cooking appliances work. A C-10 licensed fire alarm contractor shall perform all fire alarm system work. No fire protection system work shall be performed without fire dept. approved plans. t'age _,or 4 c.O ·-<fS· G-GN -The contractor shall contact Carlsbad Fire Department prior to taking existing fire sprinkler system out of service, if system will be out of service overnight. Relocation of fire sprinklers in existing space requires Carlsbad Fire Dept. approval. A-2.1 Revise 'Fire Dept. Notes' as follows: -The type, rating and number of fire extinguishers shall comply with 2013 CFC, section 906.3. A minimum of three (or more) properly spaced fire extinguishers rated at 2A-1 OBC are required for dining area, kitchen and other areas. Maximum Travel distance to fire extinguishers shall not exceed 75 feet. All fire extinguishers shall be mounted in accessible and visible location, not to exceed 5 feet above finished floor to top of extinguisher. When cooking appliances with grease laden vapors are installed; the kitchen will require a class K' fire extinguisher installed within 30 feet of cooking appliances. CFC 906. -Delete Notes in this section that reference 'storage use and dispensing of Hazardous Materials'; they are not applicable. -Delete the note referencing plan submittal for sprinkler system to Anaheim Fire dept. All fire protection system notes are deferred submittal only. A-2.1A Add the following Information on 'Egress Plan': -Provide an egress analysis denoting the occupancy classification as per CBC Chapter 3, the square feet, occupant load factor and occupant load for each room and area based on the function of each area or room. CBC Table 1004.1.1 -Indicate on plan, door swing for all doors that serve an occupant load of 50 or more persons. CBC 1008.1.2 -Where two exits are required, denote the distance between exits. 1015.2.1 -Denote the aggregate square footage, required number of exits, required and actual width of exits. CBC 1005 -Show number of occupants exiting at each exit discharge. -Denote the exit designated as the Main Exit. -Denote common paths and lengths of egress travel CBC 1014.3 -Denote common paths and lengths of travel distance to each exit discharge. CBC 1016 -Address egress through intervening rooms. CBC 1014.2 A-2.2 Keyed Note # 1.2: add note to read: New carpet, padding and carpet base shall comply with California State Fire Marshal listings or other acceptance criteria for flame spread and smoke developed index. CFC 804. -Add note: Suspended Ceiling Plan notes that read: Suspended acoustical ceilings shalll comply with section 808.1 and 808.1.1.1 of 2010 CBC and meet flame spread and smoke developed ratings. Yage 4 or 4 A-4.9 Revise Door Note# 18, A-11. This note shall read as follows: All exits shall be openable from inside without use of a key. Main exit doors with keyed deadbolts may have a sign, with minimum one-inch high letters, mounted inside above door that reads "This door to remain unlocked whenever building is occupied". 2013 CBC. A-5.1 -Add note: Address numbers shall be mounted on building in visible location. Numbers shall be minimum 12 inches in height, with 1-1/2 inch stroke and contrast in color to background. **Show location of proposed numeric address on building. CBD 17.04.320. P1.2 -Add Note to 'General Notes' that reads: All gas piping for water heater and all other gas piping located in interior space shall be labeled every 20 feet and every change of direction with labels that read 'Natural Gas. The gas meter shall be identified with a permanent tag indicating address that gas meter serves suite or address. M0.1 Delete note# 9 in 'plan check note'. This note referencing type-11 clothes dryers is not applicable. Note # 15, delete this note if a pizza oven is Not going to be installed. M-1 -Denote air-moving systems supplying air in excess of 2000 cfm equipped with smoke detectors approved and listed by the California State Fire Marshal. CMC 609. -Denote units provided with smoke detectors on plans. M-1.2 Add Notes to Roof Plan as follows: -Imprint Carlsbad Policy 80-6 on to roof plan. -Intent B (Fireman Safety) will be provided on roofs of buildings. -Indicate location of Roof Access. E1.2 ADD the following notes: -Add Note: Means of egress illumination level shall be not less than 1-foot candle at the walking surface and equipped with minimum 90 minute battery backup where required. CBC1006. -Add Note: Exit signs shall be illuminated at all times and equipped with minimum 90-minute battery backup. CBC 1011.5.3 -Add note: the means of Egress shall be illuminated at all times building space is served, in accordance with CA. Building Code, Section 1006.1; 1006.i And 1006.3. -Add Note: Additional illuminated 'EXIT' signs may be required on the retail sales floor area or other areas of store to clearly indicate path of exit travel. -Add Note: A photometric plan of all occupied areas, that demonstrates compliance wiith CBC 1006 will be provided upon request by the Carlsbad Fire Dept., Deputy Fire Marshal Greg Ryan (760) 602-4665 STRUCTURAL CALCULATIONS PROJECT: _ _._Pit__._-1\j-=.il'<fl'-'-"·. f<~ft~-----------Al'HTK STRUCTURAL ENGINE!R§~ U..F' DESIGN ASSUMPTIONS: CONCRETE STRENGTH AT TWENTY EIGHT DAYS: r?c.o_ D PSI ~L-=-==/~--- MASONRY: GRADE "N" CONCRETE BLOCK F! M = ______ PSI MORTAR: TYPE S 1,800 PSI GROUT: 2000 PSI REINFORCING STEEL: A-615 STRUCTURAL STEEL: A-36 LUMBER: DOUGLAS FIR-LARCH JOISTS BEAMS AND POSTS STUDS SEISMIC FORCE: s,~ ::: 0..-'& l.J WIND FORCE: { {6 PAP H/ c DESIGN LOADS: ROOF DEAD LOAD SLOPING ROOFING PLYWOOD JOISTS INSUL. & CLG. MISC. TOTAL= ROOF LIVE LOAD SLOPING= FLAT= GRADE40: GRADE60: #2 #2 #4AND LESS(U.O.N.) #SAND LARGE STUD OR BETTER REPORT BY= ----=-M__,01.._'4 __ c..;;;..._;;.e_c_. _,JML....,;;.....;_';__AI_· __ _ REPORT NO.:------- FLOOR DEAD LOAD INT. FLOORING PLYWOOD JOISTS INSUL & CLG. MISC. TOTAL=---- FLOOR LIVE LOAD INTERIOR BALCONY EXIT WALKWAY 40 PSF 60 PSF (U.O.N.) 100 PSF WALL DEAD LOAD INTERIOR EXTERIOR 10 PS 16PS JAN 2 2 2015 CITY OF CARLSBAD BUILDING DIV!S!ON These calculations are limited only to the items included herein, selected by the client and do not imply approval of any other portion of the structure by this office. These calculations are not valid if altered in any way, or not accompanied by a wet stamp and signature of the Engineer of Record. Job No. Designed By Date .:., ............... '"· ... C6 ., ... q·~·· ·3 Of S w~ rvrJ L(,lll'\i)-= (Ff.1·tt+){O .1lXq1)-=-"'S'flf ~ G&-1~ .. ..,. S~ t~ w·~ -=-(t1(S~J_1-(t 5M)( 0. tD) s 5. ~ ~t· _____ _ r·.. .,. -i 7 Gr~ ~ O,~il\ "> ~ ttss 2.¥2-x Y1 ( s: o~ 1t(T,....~) y ) :.,.. , ' I ~~.'$" w ~ S'-'pH . ~l -::; <;;'9..,. ~ ~t ~,roil= M~:: (s-'-' e\.f )Cs' )fz = 7-oo.#f-t '1reb-:. ~-9-k::-f+-(n'1 ) '=" 0.2'::hA~ o.~fo ~ ~ t ~ ~o(l-f w'2. ':; 112flf M.~\lMc ~ ~~'[..¢8 #ft {) ""'"' :.. ~-92-Cj ( \.Z,) ") --·~ L), o :: 2-T\11\.; 0 "' ' ('L'-) l) lt~S 4\(1{\<:~/t~' {~-= 3.to~..,)J OFFICE USE ONLY SAN DIEGO REGIONAL HAZARDOUS MATERIALS QUESTIONNAIRE UPFP# ____________ __ HV# ______________ __ BPDATE __ ~----~--- Business Name Business Contact Telephone# Project Address APN# Mailing Address I• Plan File# Project Contact \(J (/trtct,Y A 0 The following questions re resent the facility's activities, NOT the specific project description. PART 1: FIRE DEPARTMENT-HAZARDOUS MATERIALS DIVISION: OCCUPANCY CLASSIFICATION: Indicate by circling the item, whether your business will use, process, or store any of the following hazardous materials. If any of the items are circled, applicant must contact the Fire Protection Agency with jurisdiction prior to plan submittal. Facility's Square Footage (including proposed project): "'?tt DO Occupancy Rating: {\ -2-. 1. Explosive or Blasting Agents 5. Organic Peroxides 9. Water Reactives 13. Corrosives 2. Compressed Gases 6. Oxidizers 10. Cryogenics t 3. Flammable/Combustible Liquids 7. Pyrophorics 11. Highly Toxic or Toxic Materials 4. Flammable Solids 8. Unstable Reactives 12. Radioactives PART II: SAN DIEGO COUNTY DEPARTMENT OF ENVIRONMENTAL HEALTH-HAZARDOUS MATERIALS DIVISIONS (HMO): If the answer to any of the questions is yes, applicant must contact the County of San Diego Hazardous Materials Division, 5500 Overland Ave., Suite 110, San Diego, CA 92123. Call (858) 505-6700 prior to the issuance of a building permit. ~ FEES ARE REQUIRED. Project Completion Date: ~_t __ t I LL Expected Date of Occupancy: _2__t_l __ t 0 CaiARP Exempt YES NO ~ (for new construction or remodeling projects) ------'-'----~ ~ I~ 1. 0 P-Is your business listed on the reverse side of this form? (check all that apply). 2. 0 1?)' Will your business dispose of Hazardous Substances or Medical Waste in any amount? 0 CaiARP Required 3. 0 y Will your business store or handle Hazardous Substances in quantities equal to or greater than 55 gallons, 500 pounds, 1 _ / 200 cubic feet, or carcinogens/reproductive toxins in any quantity? Date Initials 4. 0 121 Will your business use an existing or install an underground storage tank? 5. 0 JZ( Will your business store or handle Regulated Substances (CaiARP)? 6. 0 ~ Will your business use or install a Hazardous Waste Tank System (Title 22, Article 10)? 7. 0 eJ Will your business store petroleum in tanks or containers at your facility with a total storage capacity equal to or greater than 1,320 gallons? (California's Aboveground Petroleum Storage Act). 0 CaiARP Complete I Date Initials PART Ill: SAN DIEGO COUNTY AIR POLLUTION CONTROL DISTRICT: If the answer to any of the questions below is yes, applicant must contact the Air Pollution Control District (APCD), 10124 Old Grove Road, San Diego, CA 92131-1649, telephone (858) 586-2600 prior to the issuance of a building or demolition permit. Note: if the answer to questions 4 or 5 is yes, applicant must also submit an asbestos notification form to the APCD at least 10 working days prior to commencing demolition or renovation, except demolition or renovation of residential structures of four units or less. Contact the APCD for more information. YES NO 1. 0 )Zf Will the subject facility or construction activities include operations or equipment that emit or are capable of emitting an air contaminant? (See the APCD factsheet at http://vvww.sdancd.org/info/factslpermits.pdf, and the list of typical equipment requiring an APCD permit on the reverse side of this from. Contact APCD if you have any questions). 2. 3. 4. 5. 0 0 0 0 D # (ANSWER ONLY IF QUESTION 1 IS YES) Will the subject facility be located within 1,000 feet of the outer boundary of a school (K through 12)? (Search the California School Directory at http://www.cde,ciUJQ?lf.re/sdL for public and private schools or contact the appropriate school district). Has a survey been performed to determine the presence of Asbestos Containing Materials? Will there be renovation that involves handling of any friable asbestos materials, or disturbing any material that contains non-friable asbestos? Will there be demolition involving the removal of a load supporting structural member? Briefly describe business activities: A.~ P?ffi I declare under penalty of perjury that to the be t of my knowledge and belief the responses made herein are tr e and correct. I I Name of Owner or Authorized Agent Signature of Owner or Authorized Agent Date FOR OFFICIAL USE ONLY: FIRE DEPARTMENT OCCUPANCY CLASSIFICATION: _________________________________________ _ BY: _______________________________________________ __ DATE: __ _,_1 __ --'1'--- EXEMPT OR NO FURTHER INFORMATION REQUIRED RELEASED FOR BUILDING PERMIT BUT NOT FOR OCCUPANCY RELEASED FOR OCCUPANCY COUNTY-HMO* APCO COUNTY-HMO APCO COUNTY-HMO APCO * .. A stamp 1n th1s box only exempts busmesses from completing or updating a Hazardous Matenals Bus1ness Plan. Other perm1tt1ng requirements may st1ll apply. HM-9171 (02/11) County of San Diego-DEH-Hazardous Materials Division LIST OF BUSINESSES WHICH REQUIRE REVIEW AND APPROVAL FROM THE COUNTY OF SAN DIEGO DEPARTMENT OF ENVIRONMENTAL HEALTH-HAZARDOUS MATERIALS DIVISION Check all that apply: AUTOMOTIVE 0 Battery Manufacturing/Recycling 0 Boat Yard 0 Car Wash 0 Dealership Maintenance/Painting 0 Machine Shop 0 Painting 0 Radiator Shop 0 Rental Yard Equipment 0 Repair/Preventive Maintenance 0 Spray Booth 0 Transportation Services 0 Wrecking/Recycling CHEMICAL HANDLING 0 Agricultural supplier/distributor 0 Chemical Manufacturer 0 Chemical Supplier/Distributor 0 Coatings/Adhesive 0 Compressed Gas Supplier/Distributor 0 Dry Cleaning 0 Fiberglass/Resin Application 0 Gas Station 0 Industrial Laundry 0 Laboratory 0 Laboratory Supplier/Distributor 0 Oil and Fuel Bulk Supply 0 Pesticide Operator/Distributor CHEMICAL HANDLING 0 Photographic Processing 0 Pool Supplies/Maintenance 0 Printing/Blue Printing 0 Road Coatings 0 Swimming Pool 0 Toxic Gas Handler 0 Toxic Gas Manufacturer METAL WORKING 0 Anodizing 0 Chemical Milling/Etching 0 Finish-Coating/Painting 0 Flame Spraying 0 Foundry 0 Machine Shop-Drilling/Lathes/Mills 0 Metal Plating 0 Metal Prepping/Chemical Coating 0 Precious Metal Recovery 0 Sand Blasting/Grinding 0 Steel Fabricator 0 Wrought Iron Manufacturing AEROSPACE 0 Aerospace Industry 0 Aircraft Maintenance 0 Aircraft Manufacturing OTHERS AND MISCELLANEOUS 0 A~;phalt Plant 0 Biotechnology/Research 0 Chiropractic Office 0 Co-Generation Plant 0 Dental Clinic/Office 0 Dialysis Center 0 Emer~1ency Generator 0 Frozen Food Processing Facility 0 Hazardous Waste Hauler 0 Hospital/Convalescent Home 0 Laboratory/Biological Lab 0 Medical Clinic/Office 0 Nitrous Oxide (NOx) Control System 0 Pharmaceuticals 0 Public Utility 0 Refrigeration System 0 Rock Quarry 0 Ship Repair/Construction 0 Telecommunications Cell Site 0 Veterinary Clinic/Hospital 0 Wood/Furniture Manufacturing/Refinishing ELECTRONICS 0 Electronic Assembly/Sub-Assembly 0 Electronic Components Manufacturing 0 Prinl:ed Circuit Board Manufacturing NOTE: THE ABOVE LIST INCLUDES BUSINESSES, WHICH TYPICALLY USE, STORE, HANDLE, AND DISPOSE OF HAZARDOUS SUBSTANCES. ANY BUSINESS NOT INCLUDED ON THIS LIST, WHICH HANDLES, USES OR DISPOSES OF HAZARDOUS SUBSTANCES MAY STILL REQUIRE HAZARDOUS MATERIALS DIVISION (HMO) REVIEW OF BUSINESS PLANS. FOR MORE INFORMATION CALL (858) 505-6880. LIST OF AIR POLLUTION CONTROL DISTRICT PERMIT CATEGORIES Businesses, which include any of the following operations or equipment, will require clearance from the Air Pollution Control District. CHEMICAL 4 7 -Organic Gas Sterilizers 32 -Acid Chemical Milling 33-Can & Coil Manufacturing 44-Evaporators, Dryers & Stills Processing Organic Materials 24 -Dry Chemical Mixing & Detergent Spray Towers 35 -Bulk Dry Chemicals Storage 55 -Chrome Electroplating Tanks COATINGS & ORGANIC SOLVENTS 27-Coating & Painting 37-Plasma Arc & Ceramic Deposition Spray Booths 38 -Paint, Stain & Ink Mfg 27-Printing 27 -Polyester Resin/Fiberglass Operations METALS 18 -Metal Melting Devices 19-Oil Quenching & Salt Baths 32 -Hot Dip Galvanizing 39 -Precious Metals Refining ORGANIC COMPOUND MARKETING (GASOLINE, ETC) 25-Gasoline & Alcohol Bulk Plants & Terminals 25 -Intermediate Refuelers 26-Gasoline & Alcohol Fuel Dispensing COMBUSTION 34 -Piston Internal -Combustion Engines 13-Boilers & Heaters (1 million BTU/hr or larger) 14 -Incinerators & Crematories 15 -Burn Out Ovens 16 -Core Ovens 20-Gas Turbines, and Turbine Test Cells & Stands 48 -Landfill and/or Digester Gas Flares ELECTRONICS 29-Automated Soldering 42 -Electronic Component Mfg FOOD 12 -Fish Canneries 12-Smoke Houses 50-Coffee Roasters 35 -Bulk Flour & Powered Sugar Storage SOLVENT USE 28 -Vapor & Cold Degreasing 30 -Solvent & Extract Driers 31 -Dry Cleaning ROCK AND MINERAL 04 -Hot Asphalt Batch Plants 05 -Rocl< Drills 06 -Scmening Operations 07-Sand Rock & Aggregate Plants 08-Concrete Batch, CTB, Concrete Mixers, Mixers &Silos 10-Brick: Manufacturing OTHER 01 -Abrasive Blasting Equipment 03-Asphalt l'<oofing Kettles & Tankers 46 -Reverse Osmosis Membrane Mfg 51 -Aqueous Waste Neutralization 11 -Tire Buffers 17 -Brake De~bonders 23 -Bulk Gra1in & Dry Chemical Transfer & Storage 45 -Rubb•er Mixers 21 -Waste Disposal & Reclamation Units 36 -Grindi111g Booths & Rooms 40 -Asphalt Pavement Heaters 43 -Ceramic Slip Casting 41 -Perlite1 Processing 40-Cooling Towers-Registration Only 91 -Fumigation Operations 56-WWTP (1 million gal/day or larger) & Pump Station NOTE: OTHER EQUIPMENT NOT LISTED HERE THAT IS CAPABLE OF EMITTING AIR CONTAMINANTS MAY REQUIRE AN AIR POLLUTION CONTROL DISTRICT PERMIT. IF THERE ARE ANY QUESTIONS, CONTACT THE AIR POLLUTION CONTROL DISTRICT AT (858) 586-2600. HM-9171 (02/11) County of San Diego-DEH-Hazardous Materials Division INDUSTRIAL WASTEWATER DISCHARGE PERMIT Date U · 1· \4-~S? \ Business Name P ~ f?tta_t/C SCREENING SURVEY ~?.:l.D Street Address 2::15 27 81 ( t~t!VJI.Vl o ~-{V\. [ ?t '2-00tb Email Address 'Rv?<S @. @1! '7S t-LL->TI>UTA;¢Soc, Cn(\/\ PLEASE CHECK HERE IF YOUR BUSINESS IS EXEMPT: {ON REVERSE SIDE CHECK TYPE OF BUSINESS) m Check all below that are present at your facility: "~ Acid Cleaning Ink Manufacturing Nutritional Supplement I Assembly Laboratory Vitamin Manufacturing Automotive Repair Machining I Milling Painting I Finishinf~ Battery Manufacturing Manufacturing Paint Manufacturing Biofuel Manufacturing Membrane Manufacturing Personal Care Products Biotech Laboratory (i.e. water filter membranes) Manufacturing Bulk Chemical Storage Metal Casting I Forming Pesticide Manufac:turing I Car Wash Metal Fabrication Packaging Chemical Manufacturing Metal Finishing Pharmaceutical Manufacturing Chemical Purification Electroplating {including precursors) Dry Cleaning Electroless plating Porcelain Enameling Electrical Component Anodizing Power Generation Manufacturing Coating (i.e. phosphating) Print Shop Fertilizer Manufacturing Chemical Etching I Milling Research and Development Film I X-ray Processing Printed Circuit Board Rubber Manufacturing Food Processing Manufacturing Semiconductor Manufacturing Glass Manufacturing Metal Powders Forming Soap J Detergent Manufacturing Industrial Laundry Waste Treatment I Storage SIC Code(s) (if known):------------------------ Brief description of business activities (Production I Manufacturing Operations): Description of operations generating wastewater (discharged to sewer, hauled or evaporated): Estimated volume of industrial wastewater to be discharged (gal/ day): ________ _ List hazardous wastes generated (type /volume):-----------·---- Date operation began/or will begin at this location: ---------------- Have you applied for a Wastewater Discharge Permit from the Encina Wastewater Authority? . Yes No lfyes,when: ____________________ _ ~ite Contact N lt.~l stuwt Title ~ ~lf\,I\A1V Signature ~ l ~ Phone No. 'D t:70 · 2-4? · ?:>-t...-1-D ENCINA WAs*fEW~RITY, 6200 Avenida Encinas Carlsbad, CA 92011 (760) 438-3941 FAX: (760) 476-9852 DISCHARGE PERMIT EXEMPT LIST The commercial enterprises listed below are a partial listing of businesses that are exempt from industrial wastewater discharge permitting under normal operating conditions. They are exempt because (a) they discharge no process wastewater (i.e., they only discharge sanitary wastewater with no pollutants exceeding any local limits), and (b) they have no potential to negatively impact the EWPCF or other wastewater treatment plants in the ESS. Any questions regarding exemptions should be referred to EWA Source Control staff. Automobile Detailers Barber/Beauty Shops Business/Sales Offices Carpet/Upholstery Cleaning Services Childcare Facilities Churches Community Centers Consulting Services Contractors Counseling Services Educational Services (no auto repair/film developing) Financial Institutions/Services Fitness Centers Gas Stations (no car wash/auto repair) Grocery Stores {no film developing) Home-based Businesses Hotels/Motels (no laundry) Laundromats Libraries Medical Offices (no x-ray developing) Mortuaries Museums Nail Salons Nursing Homes Office Buildings (no process flow) Optical Services Pest Control Services (no pesticide repackaging for sale) Pet Boarding/Grooming Facilities Postal Services Public Storage Facilities ~ars Retail/Wholesale Stores (no auto repair/film developing) Theaters (Movie/Live) 8{. ~Jtt-f -OFFICE USE ONLY SAN DIEGO OFFICE F PP p~~f?o;jf; f57. c.,~2_Djrs ...... w::; ..... DIEGO. CA 92112 Intake Date: I (I 5" I I 1 5500 OVERLAND AVE# 110 SAN DIEGO, CA 92123 (858) 505-6660 FAX (858) 467-9282 J81.NEW FOOD FACJUTY 0 REMODEL OcoNSULT-NEW/ OcoNSULTATION OREVtsroN Oeoov ART CURRENT PERMIT CHANGE OF OWNER CURRENT PERMIT FacilityName: Yo.n.evtt. f!Jre~V1 Facility/ Commissary Address: 2-'? 2 '5 El cam\ no R:cg, I Assessor's Parcel No.:--:------ City: Car Is 1:??\f! z;p: __ _ BUSINESS OWNER: Name1: ·---------:------company: ~&\~n~ OtvtAoprl'Wn+ E:lrovp, LL-G Mailing Address: Z. ??q \ \tb ?tregd= City: Gr\vH'Htzth State:_&A._ Zip:.Ei:Z.O:Z. ~ Phone: (]VOl qA-A-I 0"10Fax: E-Mail: Projected # Meals to be Served: _Breakfast _Lunch __ Dinner Customer Utensils: OSingle Use 18JMulti-Use Is there outdoor dining, outdoor bar, barbecue, wood oven etc. associated with the food facility? DYes If yes. explain: No SEWER: 0Public-0Septic/ Private WATER: 0Public-0Well/ Private (If private contact Land Use at (858) 565-5173) Identify the municipal water and wastewater district(s) ________________ , _____ _ DEH:Fii·l77 (Rev. 02113) FOOD & HOUSING DIVISION-PLAN CHECK P-1 ,.f:OOp FACILITY ONLY J!!PICA T1E THE SERVICES OR TYPE OF FOOd_ FACIUTY PROVIDeD (Check all that apply) ~ RestaurantJOeli 0 Market-Packaged 0 Markei-Prel.cf.catering 0 SchooJ;Preparation Kitchen 0 School Satellite Site 0 Licensed Health Care 0 Boat E1 ~etail Processing ~ Minim,al Ffoct {froze~ce cream dipping, hot dogs, beverages) 0 Commissary-For Food PrepO ~dm~ary-For f.t~.ka~,~ Fo0d.,2f Vendi~g ~achine HQ 0 Wholesale Warehouse 0 Packaged Non-Potentially Hazaf_d~. . ... ~1~ Delivery s .... ~:v~ce1J Ca~~rin.Equipment Rental 0 Swap Meet Vendor : -~ -~ ' ' .. ' ' ~ --~~-·~1>· ' MOBILE FOOD CART:0 PACKAGED FOOD OR PRO"Df:JCE'ONt¥. ) LIMITED FOOD PREPARATION (LFP) Up To 4 Carts May Operate at a SINGLE SITE 0-Num~er ofiP~.trts Number of Packaged Carts __ _ MOBILE SUPPORT UNIT FOR CART REPORTS TO COMMISSAR'/!' 0 MOBILE FOOD TRUCK/VEHICLE ONLY: 0 Packaged/Produce 0 Limited Food Prep (LFP) 0 Full Food Prep MOBILE FOOD FACILITIES MUST SUBMIT COMMISSARY AGREEMENT LETTER (TOILET FACILITY LETIER IF APPLICABLE) NOTE: ALL FOOD FACILITIES INCLUDING MOBILES MUST SUBMIT MENUS WITH APPLICATION BODY ART FAGIL!ry ONLY INDICATE THE SERVICES YOU WILL BE PROVIDING (Check all that apply) 0 Tattooing D Permanent Cosmetics 0 Body Piercing 0 Branding 0 Mobile Vehicle INFECTION PREVENTION & CONTROL PLAN (/PCP) TO BE SUBMITTED FOR REVIEW PRIOR TO OPERATING OTHER AGENCIES: C BLDG DEPARTMENT C FIRE DEPARTMENT C ZONING C WATER/WASTEWATER DISTRICTS C APCD C DEH·LWQ (Note: If you are the sole business owner and an honorably discharged veteran you may be eligible for a fee exemption.) I declare under penalty of pe~ury that to the best of my knowledge and belief, the description of use and information contained on this application and plans are correct and true. I hereby consent to all necessary inspections made pursuant to law and incidental to the issuance of this review and the operation of this business. I also agree to conform to all conditions, orders, and directions, Issued pursuant to the California Health and Safety Code, and all applicable County and City Ordinances. I understand that if the plans are incomplete due to·a lack of any of the required information, the plans will be rejected and upon resubmission, a plan recheck fee will be charged. I am aware that plan check fees are not fully refundable and that plans, once reviewed, will be picked up within 60 days or they wm be discarded. Plans are valid for one year after stamp. Any chang to the released documents will be submitted and filed with the County of San Diego. Department of Environment Heal Date: ....;.l_O_· 2 __ q_._l4 __ _ Print Name and Title Here: (For office use only) PLAN CHECK#/: _______ PERMIT TYPE: ________ CENSUS TRACT:---- ASSIGNED TO: . ROUTE CODE: --r----- PLAN STATUS0APPROVED 0 DISAPPROVED~LUE TAG;PC INITIALS ~ REVIEW DATE _.:.a.{ ~---l... RECHECK STATU$ 0APPROVED0DISAPPROV D0BLUE TAG; R DEH:FH·l77 (Rev. 02113) FOOD & HOUSING DIVISION-PLAN CHECK P-2 Project Address: PLUMBING, ELECTRICAL, MECHANICAL WORKSHEET B-18 Building Division 1635 Faraday Avenue 760-602-2719 Permit No.: (B / f1: -~Jv ( _{ Information provided below refers to worl< being done on the above mentioned permit only. This form must be completed and returned to the Building Division before the permit can be issued. Building Dept. Fax: (760) 602-8558 Number of new or relocated fixtures, traps, or floor draim ..................................................... .. New building sewer line? .Y:::::: ... Ves __ No / rrrAt-"1 Number of new roof drains? ................................................................ ' .............. :!. ............................... __a_ Install/alter water line? ........................................................................................................................ ,,~ Number of new water heaters? .......................................................................................................... _L Number of new, relocated or replaced gas outlets? ..................................................................... ...;z.__ Number of new hose bibs? .................................................................................................................. ...,.b Residential Permits: New/expanded service: Number of new amps: _______ _ Minor Remodel only: Ves__ No Commercial/Industrial: Tenant Improvement: Number of existing amps involved in this project: Number of new amps involved in this project: Amps per Panel: Phase ............................................................... Number of new amperes /-&'O A 12 ·-2aoA, l· $'" t'A Three Phase ................................................................. Number of new amperes ____ -,--__..___ Three Phase 480 ........................................................ Number of new amperes /-?t:t:;. ;:£ Number of new furnaces, A/C, or heat pumps? ... it:.~: .. : .. .t •• ?..·;;;,,..,.,:~~;~.&t.t.l!l;.1:;;:;'1ir: .. :'(. New or relocated duct worl:<? .......................................................................... Ves__.!L_ No __ _ Number of new fireplaces? ............................................................................................................... .. Number of new exhaust fans? ............................................................................................................ -0 Relocate/install vent? ............................................................................................................................ _I_ Number of new exhaust hoods? ...................................................................................................... .. Number of new boilers or compressors? ........................................................... Number of HP 0 8-18 Page i of i Rev. 03/09 CB143015 2501 EL CAMINO REAL 220 PANERA-3,600 SF Tl SHELL TO RESTAURANT Tl rY"'\UU I l\ Lf 1,"-f [1/t'-f/!Lj -ro p~ {6-f\&---{ ~tJJ~ FL (Lb I e"S6-•L "· t\\ll.f~IL/ f3=>&J1...-~ ;(;/,~~~r:;-~ ll u Cu:Jl£ {Jet'--{Jjpz-ol k { /~2( (5 1/"7 /(5 ;{)a)/5 f~s-~ f<--~ ~(l,G ~ ~·es,gOVIille:te- . A;/ f>rtJO \-letn--111 lfT1> :AJ ~ ?' A/ML -(); 1 l>k;) -~ " N tev/' /JJI.J [/J Final Inspection required by: 0 Plan 0 CM&I 0 Fire 0 sw 01SSUED 1 OCV. --------------------------- ~~-d ~e y BUILDING ~~ f) Z,/] /) tti!?P PlANNING /I} !3/•Lf j ~ ENGINEERING _ i I I i .:J-0 i I '-f i V rY-l FIRE Expedite7C:!JNLv/Nn1h J }:A.! )/_C, I [tu DIGITAL FILES Required? Y N I HazMat APCD Health FormsjFees Sent Rec'd Due? By Encina l\141·~ y N Fire y N --HazHealthAPCD t \I 4-lr.....J. y N y N --PE&M 1 nl-+lr'-f u 1..-r '"' School y N Sewer v N -y N -- Speciallnspe51!9n y N -- -Factor: CF~ Y~ L-----------L-------------~-- LandUse: Density: lmpArea: FY: Annex: -PFF7Y} N Comments Date Date Date Date Building I (\ /1'4-{• '"11 l/t3/t) Planning Engineering Fire 111)1'2...-{•¥ Need? ('~~t.,i"'i~ 9£oone *T7!Al:: J)f9Tf 1Jl1 .fllLA--AI ~Done 1-JfALTH 11 frJr U ---:7 )!Coone -, -7 Q Done