HomeMy WebLinkAbout2501 NAVARRA DR; BLDG 1; 73-233; Permit-._t. .- - . . . . - • - P.
BUILDING PERMIT APPLICATION
Permit No7"3 i City of CARLSBAD, CALIFORNIA 92008
Ana/icant to complete numJed spaces on/v. Phone 729-1181 . -.
Z_ta
JO C
___ ___ I (Wi, !XY/ ____ ____ 14 - 1V?tmm
/
o
z
ID
-
0 W
>
-
LEGAL 1 DESCR.
I LOT NO. I '-2
I TRACT _______________ ______________
SEE ATTACHED MEET) 1 I Ia Ot
0 0
OWNER MAUI. ADDRESS ZIP 0112.PHON ,
2 Praz $zss •J*li a"—ta 1744 WL2mi 1W4 $tte 203 7c002
aas4'v iu*i
CONTRACTOR MAIL ADDRESS PHONE LICENSE NO.
ARCHITECT OR DESIGNER • MAIL ADDRESS PHONE
halter Ms. A.11 2301. 17th $tst ta01111111111111111
LICENSE NO.
ENGINEER MAIL ADDRESS PHONE
a Th *
LICENSE NO. -
LENDER MAIL ADDRESS
6 S%*est atis
CRANCH
ii 02110
USE Or RIIILDING
AC2 7 LIa,!*Lte11-V VW
I
8 Class ofwork: INEW DADDITION DAL.TERATION DREPAIR El MOVE DREMOVE
9 Describe work: RM(IJJ *1 1$ L*S S iitXISti,
X d & aiiiiiiiiiii rsd
10 Change of use from
Change Of use to
11 Valuation of work: $ ,../?f ?2/' ' PLAN CHECK FEE PERMIT FEE /_
SPECIAL CONDITIONS: Type of
• Const. (.. , Group Division
-
Size of B
(Total) Sq. wlt/ Stories
Max
0cc. Load
Fire
Zone '
Use
Zone /'j' Fire Sprinklers
Required Dyes Q APPLICATION ACCEPTED BY:
—V
J PLANS
i çf'i
I
APPRO IUANCE BY:
______ No of
Dwelling
OFFSTREET RKINGXnCovered 2
ES
NOTICE
SEPARATE PERMITS ARE REQUIRED FOR ELECTRICAL, PLUMB.
ING. HEATING, VENTILATING OR AIR CONDITIONING.
THIS PERMIT BECOMES NULL AND VOID IF WORK OR CONSTRUC-
TION AUTHORIZED IS NOT COMMENCED WITHIN 60 DAYS. OR IF
CONSTRUCTION OR WORK IS SUSPENDED OR ABANDONED FOR A
PERIOD OF 120 DAYS AT ANY TIME AFTER WORK IS COM-
MENCED.
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE AND CORRECT. ALL PROVISIONS OF LAWS AND ORDINANCES GOVERNING THIS TYPE OF WORK WILL BE COMPLIED WITH WHETHER SPECIFIED HEREIN OR NOT, THE GRANTING OF A PERMIT DOES NOT PRESUME TO GIVE AUTHORITY TO VIOLATE OR CANCEL THE PROVISIONS OF ANY OTHER STATE OR LOCAL LAW REGULATING CONSTRUCTION OR THE PERFORMANCE OF CONSTRUCTION.
Special Approvals Required Received Not Required.
ZONING
HEALTH DEPT.
FIRE DEPT.
SOIL REPORT
OTHER (Specify)
SIGkATI1RE.t CONTRACTOR UTMORIZED AGENT (DATE)
11 , i'l
S,ENA'FUBEOY evk R BUILDER)
WHEN PROPERLY VALIDATED (IN THIS SPACE) THIS IS YOUR PERMIT
PLAN CHECK VALIDATION CK. M.O. CASH PERMIT VALIDATION CK. M.O. CASH
INSPECTOR
Ic'
.. J
INSPECTION RECORD
DATE $EMARKS INSPECTOR
FOUNDATIONS:
SET BACK
TRENCH
REINFORCING
FOUNDATION WALL&
WEATHER PROOFING
1)! 1
CONCRETE SLAB
FRAMING
INT. LATHING OR DRYWALL
EXT._LATHING
MASONRY
Foundation
Pour Colu.
6/8/73
6/1/73
Upper section end wails i3ictg. #1
11 uppor-ca±son capc poured
B. Nelson
B. Nelson
Caison Caps 6/5/73 B. Nelson
FINAL
USE SPACE BELOW FOR NOTES, FOLLOW-UP, ETC.
6/21/73 Upper level Building #1 O.K. B. Nelson
7/3/73 Upper foundation o.k. to grout. Gfouted 7/3/73 B. Nelson
9-6-73 6 lower Units of Bldg. I. Topout O.K. Bnelson
9-14-73 Partial frame O.K. to wrap. B. Nelson
9-26-73 Two hour wall: O.K. B. Nelson
9-28-73 Nailing Drywall: Lower units Bldg #1, no garages. O.K. B. Nelson
10-1-73 Floor nailing: Building #2 O.K. B. Nelon
10-4-73 Drywall Nailing: O.K. B. Nelson
10-17-73 Exterior LM-h: (LX. B. N1son
10-23-73 Lath In Shower: O.K. B. Nelson
11-16-73 Interior Lath: O.K. E. Plude
PLUMBING PERMIT APPLICATION
Permit No. _73-702. City of CARLSBAD, CALIFORNIA
Applicant to complete numbered spaces only. -
JOB ADDRESS 0
Ill
L. 0
1 OESLEGAL CR.
I LOT NO. I i
TK TRACT -
CJ;CE ATTACHED SHEET)
-
I
D
OWNER MAIL ADDRESS ZIP PHONE 2 C,ntie,.mta3. Advisors, 1900 Ave. of the Stars, Suite 730 Los angeles, Ch Pilo
CONTRACTOR MAIL ADDRESS PHONE - LICENSE NO.
Leavert — San Diego, IflC. P.O. B 17480, San Diego, CA
ARCHITECT OR DESIGNER MAIL ADDRESS
waiter Richardson a Assoc.
PHONE LICENSE NO.
-
... \.
ENGINEER MAIL ADDRESS
5 .
PHONE LICENSE NO. -
.
LENDER MAIL ADDRESS BRANCH
6 Con'in.'ta1 Advisors, 1900 Ave., of the Stars, ftita 730 Los Ano1es, CA
USE OF BUILDING -
Private Persidenco
8 Class ofwork: NEW DADOITION DALTERATION 0 REPAIR -
9 Describe work:
— —
PERMIT FEES
No. Type of Fixture or Item Fee
SPECIAL CONDITIONS: 45 WATER CLOSET (TOILET) $72.00
24 BATHTUB 36.00
60 LAVATORY (WASH BASIN) 90.00
6 SHOWER 9 00.
KITCHEN SINK & OISP. 27.00
39 DISHWASHER 2700
APPLICATION ACCEPTED BY: PLANSCI4ECICEOBY: APPROVED FOR ISSUANCE BY:
- LAUNDRY TRAY .
39 CLOTHES WASHER - 27.00
39 WATER HEATER (fflfttC) 27.00
NOTICE
THIS PERMIT BECOMES NULL AND VOID IF WORK OR CONSTRUC.
TION AUTHORIZED IS NOT COMMENCED WITHIN 60 DAYS, OR IF
CONSTRUCTION OR WORK IS SUSPENDED OR ABANDONED FORA
PERIOD OF 120 DAYS AT ANY TIME AFTER WORK IS COM- MENCED. .
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE AND CORRECT. ALL PROVISIONS OF LAWS AND ORDINANCES GOVERNING THIS TYPE OF WORK WILL BE COMPLIED WITH WHETHER SPECIFIED HEREIN OR NOT, THE GRANTING OF A PERMIT DOES NOT PRESUME TO GIVE AUTHORITY TO VIOLATE OR CANCEL THE
CONSTRUCTION OR THE PERFORMANCE OF CONSTRUCTION..
-
URINAL.
-
DRINKING FOUNTAIN
32 FLOOR-SINK OR DRAIN (6 1oof) - 1800 -
SLOP SINK
- ___________________________________ GAS SYSTEMS: NO. OUTLETS - -
- WATER PIPING & TREATING EQUIP. - -
- ____________________________________
WASTE INTERCEPTOR _________________________________
- -
PROVISIONS OF ANY OTHER STATE OR LOCAL LAW REGULATING
-
VACUUM BREAKERS
- -
LAWN SPRINKLER SYSTEM - -
SEWER
- _1-
CESSPOOL -- -
SEPTIC TANK & PIT
SIGkAT01%E OF CONTRCT UTHORIZED AGENT (DATE) - —
PERMIT $ 3 50
TOTAL FEE $ (DATE) 366 so SIGNATURE _OF_ OWNER _(IF _OWNER
WHEN WHEN PROPERLY VALIDATED (IN THIS SPACE) THIS IS YOUR PERMIT -
PLAN CHECK VALIDATION CK. M.O. CASH PERMIT VALIDATION . CK. M.O. CASH
4,
INSPECTOR
77O-
INSPECTION REPORTS
DATE , ITEM REMARKS INSPECTOR
8-27-73 - Underground water and plbg. O.K. B. Nelson
10-29-73 Top out Rough O.K. B. Nelson
USE SPACE BELOW FOR NOTES, FOLLOW-UP, ETC.
- 4 . 4. . ..:,,. ,t__ • •.
/1 0 .CD I *,t I S
ELECTRICAL PERMIT APPLICATION
Permit No. 'fl 441/7 City of CARLSBAD, CALIFORNIA 92008.
Applicant to'complete numbered spaces only. Phone 7 29118t -------...
JOE ADDR £55 25cX lavarza, La Coat* ? 7
LEGAL
LOT NO. ELK TRACT
ATTACHED SHEET) 1
OWNER MAIL ADDRESS ZIP PHONE
2 Px'aver Broa. Cstruction 250O Natar*, La Coeta, Ca. 92008 I36.02
CONTRACTOR MAIL ADDRESS PHONE LICENSE NO.
3 YOU
c Electric Cce1*n7 61% ed ra1 B1v.0 San Diego, Ca. 26322l7 5796
ARCHITECT OR DESIGNER MAUI. ADDRESS. PHONE LICENSE NO.
4
ENGINEER MAIL ADDRESS PHONE LICENSE NO.
5
LENDER MAIL ADDRESS BRANCH
6
USE OF BUILDING
7
8 Class of work: M NEW 0 ADDITION 0 ALTERATION 0 REPAIR
9 Describe work: -----
I SPECIAL CONDITIONS: I
PERMIT FEES
No. Each
ISSUANCE OF EACH PERMIT
(I- 1,2
Fee
I
NEW CONSTRUCTION, FOR EACH AMPERES OF MAIN SERVICE, SWITCH, PPLICATION ACCEPTED BY: PLANSCHECKEDBY: APPROVED FOR ISSUANCE BY: FUSE OR BREAKER
R A NEW SERVIÔE ON'EISTING BLDG. FOR EA. AMPERE OF INCREASE NOTICE IN MAIN SERVICE, SWITCH, FUSE
THIS PERMIT BECOMES NULL AND VOID IF WORK OR CONSTRUC. OR BREAKER
TION AUTHORIZED IS NOT COMMENCED WITHIN 60 DAYS, OR IF
CONSTRUCTION OR WORK IS SUSPENDED OR ABANDONED FOR A
PERIOD OF 120 DAYS AT ANY TIME AFTER WORK IS COM- REMODEL, ALTERATION, NO CHANGE
MENCED. IN SERVICE, FOR EA. AMPERE OF
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS INCREASE
APPLICATION AND KNOW THE SAME TO BE TRUE AND CORRECT. ALL. PROVISIONS OF LAWS AND ORDINANCES GOVERNING THIS TYPE OF WORK WILL BE COMPLIED WITH WHETHER SPECIFIED HEREIN OR NOT, THE GRANTING OF A PERMIT DOES NOT PRESUME TO GIVE AUTHORITY TO VIOLATE OR CANCEL THE TEMP. SERVICE UP TO AND INCLUD-
PROVISIONS OF ANY OTHER STATE OR LOCAL LAW REGULATING INC 200 AMP. CONSTRUCTION OR THE PERFORMANCE OF CONSTRUCTION.
TEMP. SERVICE OVER 200 AMP. L PER 100
SIGNATURE or CONTRACTOROR AUTHORIZED AGENT /J / MINIMUM PERMIT FEE
WHEN PROPERLY VALIDATED (IN THIS SPACE) THIS IS YOUR PERMIT
PLAN CHECK VALIDATION CK. \ M.O. CASH PERMIT VALIDATION CK. M.O. CASH
INSPECTOR
-I -
INSPECTION REPORTS
DATE ITEM REMARKS . INSPECTOR
10-29-73.. Rough O.K. - B. N1snn
USE SPACE BELOW FOR NOTES, FOLLOW-UP, ETC.
/ ELECTRICAL PERMIT APPLIATIO.N
Permit No
r :..
5.City of CARLSBAD, CALIFORNIA 92008 RX 111 . S
Applicant to cdmpiete numbered spaces only. Phone. 729-1181
JOB ADOR £55 .
I LOT NO. I BLK I TRACT LE SAL 1D .111
OWNER p
2
,
CONTRACTOR (
/L/,j/j,
ARCHITECT OR DESIGNER
4/
MAIL ADDRESS
MAIL ADDRESS
ZIP
d
EJSEE ATTACHED SHEET)
PHONE vq;3.
LICENSE NO. .
LICENSE NO.
VV
6
USE OF BUILDING
7
8 Class of work: gkNEW 0 ADDITION 0 ALTERATION 0 REPAIR
9 Describe work:
PERMIT FEES
I No. I Each
SPECIAL CONDITIONS: I
ISSUANCE OF EACH PERMIT
Fee
1T
NEW CONSTRUCTION, FOR EACH
AMPERES OF MAIN SERVICE, SWITCH,
FUSE OR BREAKER APPLICATION ACCEPTED BY: PLANSCHECICEDBY: APPROVED FOR ISSUANCE BY:
7 /J\ NEW SERVICE ON EXISTING BLDG.
FOR EA. AMPERE OF INCREASE IN MAIN SERVICE, SWITCH, FUSE
-
NOTICE
- I.
THIS PERMIT BECOMES NULL AND VOID IF WORK OR CONSTRUC.
TION AUTHORIZED IS NOT COMMENCED WITHIN 60 DAYS, OR IF CONSTRUCTIONR WORK IS SUSPENDED OR ABANDONED FOR A
PERIOD OF 120 DAYS AT ANY TIME AFTER WORK IS COM.
MENCED.
OR BREAKER
REMODEL, ALTERATION, NO CHANGE
IN SERVICE FOR EA. AMPERE OF
HEREBY CERTIFY THAT I I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE AND CORRECT. ALL PROVISIONS OF LAWS AND ORDINANCES GOVERNING THIS
TYPE OF WORK WILL BE COMPLIED WITH WHETHER SPECIFIED,
HEREIN OR NOT. THE GRANTING OF A PERMIT DOES NOT
PRESUME TO GIVE AUTHORITY TO VIOLATE OR CANCEL THE
PROVISIONS OF ANY OTHER STATE OR LOCAL LAW REGULATING
CONSTRUCTION OR THE PERFORMANCE OF CONSTRUCTION.
INcREAsE .,,,>, /1
TEMP. SERVICE UP TO AND INCLUD-
ING 200 AMP.
TEMP. SERVICE OVER 200 AMP.
I PER 100
PC Sig LLaVOW OPAh AGENT WA)7 ••. -
V MINIMUM PERMIT FEE
SIGNATURE OF OWNER (IF OWNER BUILDER) (DATE)
WHEN PROPERLY VALIDATED (IN THIS SPACE) THIS IS YOUR PERMIT
PLAN CHECK VALIDATION CK. M.O. CASH PERMIT VALIDATION CK. M.O. CASH
INSPECTOR
- APPLICATION FOR SEWER SERVICE
p
Owners Name: 2500 Navarra Investments Receipt No. 2526
Mailing Address: 2500 Navarra Drive
Rancho La Costa, Calif. 92008 Phone No. 436-0124 Stan Prayer.
Job Address: Building No. 1, 2500 Navarra Drive
Lots 46 thru 52
SERVICE REQUESTED: COST
CONNECTION CHARGE LATERAL TO BE INSTALLED IN GOLF COURSE LINE
INTO A MANHOLE for Condominiums (type of building) $_1,375.00
If a multiple unit building, indicate no. of living units - 18
SERVICE LATERAL SURCHARGE FEE 950.00
If service lateral previously installed - No Fee
If service lateral required:
Check size lateral required:
(4 ") (6 ',) Other _8 H
Saddle connection required: Yes_ No
TOTAL CHARGES
Lateral price to be adjusted
Amount Rec.'d $6,550.00
How PaidCk. No. 10559
Date Paid 1-23-73
Re, by: Helen C. Wise
'"-' -.---- 'L42 /
125.00
$_2,450.00
The application must be signed by the owner (or his authorized representative) of the property
to be served. The total charges must be paid to the District at the time tie application is
submitted:
If a service lateral is required, it will be installed by the Leucadia County Water District.
The service lateral is that part of the-,sewer system that extends from the main collection line
in the Street (or easement) to the point in the Street (at or near the applicant's property line)
where the service lateral is connected to the applicant's building sewer.
The applicant is responsible for the construction, at the applicant's expense, of the sewer
pipeline (building sewer) from the applicant's plumbing to the point in the street (or easement)
where a connection is made to the service lateral.
The connection of the applicant's building sewer to the service lateral shall be made by the
applicant at his expense. The connection must be made in conformity with the District's
specifications, rules and regulations; and it must be inspected and annroved by the District
before the sewer system may be used by the applicant. The applicant, or his authorized re
resentative, must notify the District at the time inspection is desired. Any connection made
to the service lateral or collection line without prior approval and inspection by the District
will be considered invalid and will not be acknowledged.
After connection is complete, the property described above is subject to a monthly sewer serv-
ice charge. The rate will be governed by the use of the property - residential, commercial, or
multiple dwelling. Non-payment of the sewer service charge is subject to a 5% penalty per
month, plus disconnection if necessary.
The undersigned hereby agrees that the above information given is correct and agrees to the
conditions as stated: I
ZQnaturo
I Date
MECHANICAL PERMIT APPLICATION
7 -' City of CARLSBAD, CALIFORNIA
ADD//cant to comniete numbered soaces on/v. - '1
JOB ADORESS -
2504 11ava=& orive
LEGAL bESCR.
LOT NO. BLII
La coo"
W
OIA1n*US
TRACT I f (fJSEE ATTACHED SHEET)
;.HER MAIL ADDRESS
2 Prayer $zus. atzuctian 2500 Mavarra Drive
ZIP PHONE
4360124
CONTRACTOR - MAIL ADDRESS
University Ned*. * $ng. Contr. 4464 A1varad Canyon
PHONE LICENSE NO.
M. 293-3181. 335 88552
ARCHITECT OR DESIGNER MAIL ADDRESS
4
PHONE LICENSE NO.
ENGINEER MAIL ADDRESS
5,
PHONE LICENSE NO.
LENDER MAIL ADDRESS
6
BRANCH
USE OF BUILDING
' ssi1snoe
8 Class ofwork: NEW 13 ADDITION DALTERATION 11 REPAIR
9 Describe work:ftftlng and air awifttLanIM for NuUdkq I
18 Units
Type of Fuel: Oil 0 Nat. Gas 0 LPG. 0
PERMIT FEES
—
SPECIAL CONDITIONS: No. Type of Equipment Fee
18 Air Cond. Units—H.P. Ea. 2 ton 90 00
Refrigeration Units—H.P. Ea.
Boilers—H.P. Ea.
Gas Fired A.C. Units—Tonnage Es.
Forced Air Systems—B.T.U. M_Ea.
APPLICATION ACCEPTED BY:
/
PLANS CHECKED BY. APPROVED FOR ISSUANCE BY: - Gravity Systems—B.T.U. M Ea. - -
Floor Furnaces—B.T.U. M
Wall Heaters—B.T.U. M
NOTICE
THIS PERMIT BECOMES NULL AND VOID IF WORK OR CONSTRUC-
CONSTRUCTION OR WORK IS SUSPENDED OR ABANDONED FOR A
PERIOD OF 120 DAYS AT ANY TIME AFTER WORK IS COM.
MENCED.
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS
APPLICATION AND KNOW THE SAME TO BE TRUE AND CORRECT.
ALL PROVISIONS OF LAWS AND ORDINANCES GOVERNING THIS
TYPE OF WORK WILL BE COMPLIED WITH WHETHER SPECIFIED
HEREIN OR NOT, THE GRANTING OF A PERMIT DOES NOT PRESUME TO GIVE AUTHORITY TO VIOLATE OR CANCEL THE
CONSTRUCTION OR THE PERFORMANCE OF CONSTRUCTION.
- Unit Heaters—B.T.U. M
-
Evaporative Coolers
TION AUTHORIZED IS NOT COMMENCED WITHIN 60 DAYS, OR IF
- Clothes Dryers -
- Ventilation Fan - -
-
Range Hood -
-
1$ Air Handling Unit— 1000 C.F.M. 54 00 -
Incinerator
- -
PROVISIONS OF ANY OTHER STATE OR LOCAL LAW REGULATING
- - -
SIGNATURE or CONTRACTOR OR AUTHORIZED AGENT ' (DATE)
- PERMIT $
TOTAL FEE $ 47 00 SIGNATURE OF OWNER (IF OWNER BUILDER) (DATE)
WHEN PROPERLY VALIDATED (IN THIS SPACE) THIS IS YOUR PERMIT
PLAN CHECK VALIDATION CK. M.O. CASH PERMIT VALIDATION CK. M.O. CASH
AUDIT
Form 100.4 9.69 REORDER FROM: INTERNATIONAL CONFERENCE OF BUILDING OFFICIALS 0 50 SO. LOS ROBLES 0 PASADENA. CALIFORNIA 91101
PL(N CHECK LIST
1970 U-11—IFORM B'JZL)ING CODE
Plan Chock No.
Project 2
el Address
Type of Censtruc __________________
Occupancy Classification If
Fire Zone No. Stories___________
Floor Area:
- Occupant Load
Valuation
1970 Uniform Building Cede
Plan Checker Seismic Zone No. -
GENEIIAL C0NTS:
_Handicapped Facilities .-required (see attached sheet) J Health Department approval reguired.p /3/ r In the absenae of uses specified on floor plans for all areas, the occupant load has been based on one per square test for the unidentified areas. The validity of this should benf1rmed to your satisfaction.
NONSTRUCTURAL CCMMENS:
Ground elevations should be shown at corners of the building and at changes in gro,d slope. The ground elevations thotld be taken at the lowest point between the exterior wall and a point 5 feet out or at the property line, if closer.
Where the xteior wall is parallel to and within 5 feet of a public sidewalk, alley, or other public way, the geu_d elevations should be the elevation of the public way. The number of stories in this building cannot be determined until this data Is tarnished.
______ The basement (cellar) Is considered the first story. See "story" in Section 420.
The building area Includes mezzanines and balconies, except for private balconies or portions thereof projecting beyond the adjacent exterior wall line.
The tet1 tlsr area Is 1izIei to sçu.re feet including
increaros of z T5 No. 3, percent f, -toc.t yard., O0 percent for nu1t1
conditio.1 and tripling tb11ng) tsr sprinklers. Sections 505 and 506.
- Unobstructed yards of teat shuld be zIntaIned on
sides of the building f9r ares. puras. Section 506.
_-hour area separation walls should comply with Section 505 (c).
(a) Extend vertics.11y from the towdatIen to a poin 30 inches above the
roof except u.de the flowing conditions:
If the roof Is of at ls.et twa-ho tire-resistive construction.
If for a two-hour area sepa Ion wall, the roof for 5 feet on
each side of the w 11 is one-hour fir
s
e-resistive- conetructi n. 1. 'e J. (b) Total WC1th Qr all open a limibbd d to 25 percent of (!the wall length
aetorY uder C
o, a ,C ._ve
_4l
4)d)
All openings pr .otsd ith fire assemblies having a fire-resisti
one nd-oneh4lf (threev-s.
Du te th' gh area s .pnratlon walls should be avoided. If allowed,
t xed al1az'e Cd SectIon 43 704,
fin
C A e s aratic.ne need not extend to the outer edi'es of horizontal projecting
dc - ta auth as blconie (rs.et ove'.angs) (ca plea) (marquees) (archi-
t ial projections) if the e7.Eri.r wall at the termination of the riepa-
tion wall and the pro1eeting elecnts above are of net less than one-hour
fire-resistive conqtrub tion for a widt.h equal to the depth of the projecting '
olenents with openings In this width protected with three-fourths-hour tire-
reio lye assemblies. Section 505 (c)-2. 1
City
State
Architect
Engineer
Total Allowable Fleor Area S. Ft. Basis for Increase
,1
-'.- ..
Area 'eparatioai walls at points of a building having different heights .-
may extend only 30 inches above the lower roof level provided the
exterior wall above is ofone-hour r1-resistive construction to a
height of 10 feet above the lower root with openings protected with
three-fourths-hour fire-resistive aeembl1es.
may terminate at the lower roof provided the roof is or at least one-
hour fire-resistive constx'ucti'n wt openings for a width of 10
feet measured from the will. 3eotlon 505 (c)-11.
A -hour fire-resistive occupancy separation in conformance with
Table No. 5-B and Section 503 is required between the following:
- Horizontal oaoupancy .separatins should be supported with a structural system
having equivalent fire-resistive protection. Section 503 (b).
Vertical occupancy separations shci1d extend through underfloor and attic
areas, including areas where fire-resistive ceilings are specified.
The building is limited tä _stories C . feet in
height) as a Type structure. Section 537 and Table No. 5-D.
TYPE OF CONSTRUCTION
Mezzanines should comply with the definition set forth in Section 134.
(a) The floor area cannot exceed one-third the floor area of the room in
which it is located. The policy of the term "total floor area in
that room" is as follows:
The mezzanine must be open to the area below except for handrails.
No rooms directly below the mezzanine floor are allowed except
for bathrooms, entry areas and closets. Kitchens having each
common wall at least 50 percent open to the area are allowed.
(b) The clear height above and below shall be at least 7 feet.
Roof coverings should be fire retardant. Section 1602 (b), 1603 (a) or 17011.
Details or specifications complying with Section 3203 (e) are required.
Fixed partitions should conform with Section 1705 (a). Details are required.
Folding partitions should comply with Section 1705 (b).
Building paper should be applied to exterior walls as specified in Section
Enclosures for floor openings
1706 Dtil should clean hquld comply leljnSection rdicate this.
Minimum No. 9 gauge wire or the euiva1ent is required for horizontal
reinforcement in anchored veneer in Seismic Zone No. 3. Section 30.104 (a)
of U.B.C. Standards. Ties should be anchored to this reinforcement.
Exterior veneer more than 20 feet in height attached to wood framing is not
allowed unless provisions for differential movement are approved by you.
Section 3001 (b).
Anchored veneer over 20 feet in height should be supported with noncombustible,
corrosion-resistant ledgers at a maximum of 12 feet on center above the 20-foot
height. Section 3006 (b).
-
Rooms in which rubbish (linen) chutes terminate should be separated from the
remainder of the building with a one-hour occupancy separation. Section
1706 (c). Note special treatment of chute for shaft protection as it enters
the rubbish room.
0penirgs into rubbish and linen chutes should not be located in required exit
corridors or stairways. Section /? 6 (c)
Nonabsorbent finish and backing for toilet room floors, walls of toilet compartments, and walls around urinals should conform with Section 1711 (a).
Exterior walls of Type III buildings should be noncombustible construction. Section 2001.
A property line should be assumed between court walls to determine wall and
opening protection. Section 504 (c). Also see definition of court. Section 04.
Exterior (court) walls within -________ feet of property lines should be of -hour construction. Section 03 (a).
Fire-resistive rating of exterior walls should be maintained through attic
areas. Section 4304 (c).
Openings in exterior (court) walls within _________ feet of property lines should be protected with three-fourths-hour_ fire assemblies. (Section
Usable space under the first floor except in Oroup I (J) Occupancies should be enclosed as required in Section 1703.
Fire-resistive construction for structural elements in the exterior walls
should comply with Footnote 110. 1 of Table No. 17-A and Section See Section 1702 for clarification.
-3-
- - Combustible materials framed into a tire-resistive wall should have one-halt
the required thickness as end protection. Section 4304 (b).
Eight-inch concrete block walls should be grouted solid to qualify as a four-
hour fire-resistive assembly. Item No. 30, Table No. 43-B, including Footnotes
2 and 7.
Heavy timber construction does not qualify as fire-resistive construction nor
Is it r'cognized in Type V buildings. Table No. 17-A.
Parapet walls not less than inches in height are required. Section
1709.
Rave overhangs and similar architectural pro3eetions àhould comply with
Section 1710.
Shower stall walls should be finished with a hard, nonabsorbent surface to a
height of 6 feet. Section 1711 (b). Fiberglass or other prefabricated finishes
should be covered by a research recommendation or complete justifying data
under Section 106 should be submitted.
Doors and panels of shower and bathtub enclosure should comply with Section •'
1711 Cc to e).
Projections beyond the exterior wall should conform with the least restrictive
of the following:
A point one-third the distance to the property line from an exterior
wall. Section 504 (b).
A point one-third the distance from an assumed vertical plane located
whore fire-resistive protection of openings is first required due to
location of property. Section 5011. (b).
Envelope ceilings should satisfy the following conditions. Section 4303 (b)-6.
ould not be used to provide fire piotection for bean and girders
supporting more than one floor.
Columns should be individually tire protected.
(o) Duct and outlet openings are limited to 100 square inches in each
100 square feet of ceiling area and should be protected with approved
fire 'dampers.
Cd) Electrical outlet boxes should be of steel and not greater than 16.
square inches in area.
Gypsum board or plaster ceilings in conjunction with fire-resistive assemblies
should be supported at intervals not exceeding 16 inches. Items 22 through
27, Table No. 43-C.
Fire-resistive lightweight concrete fill on wood decks at weather-exposed
1p'tions require greater density and strength than for interior conditions.
onformanco with research recommendation conditions is required or justifying
data should be submitted under Section 106.
Unless specifically allowed by a research recommendation or substantiated with
test data under Section 105, special coverings for decks, balconies, patios,
etc., cannot replace any part of a fire-resistive assembly in reference to
Footnote No. 14, Table No. 43-C. Attention is directed to
Fire-resistive systems involving wood trusses. should comply, with applicable
research recommendations. Conventional fire-resistive systems using wood
joists are not applicable. Reference is made, to Item 109 Part II, Research
Recommendation No. 1000; one-hour ceiling construction, Part II, Research
Recommendation No. 1352; or Iten C14, Part II, Research Recommendation No. 1602.
Note that all involve double gypsum board with resilient channels between.
Wood stripping or suspended wood systems for gypsum board ceilings should be
not less than 2-inch nominal thickness. Section 4704 (b). (Section 4703 (b)
for wall stripping.)
Final partition layouts and details should be submitted prior to installation
to justify compliance with occupancy, fire-resistive, structural and exit
requirements.
Escalators should be enclosed unless complying with the Exception in Section
1706 (a)-l.
Justifying test data in conformance with Section 106 or an ICB0 research
recommendation is required for
Group
B-3 Occupancies should be of one-hour fire-resistive construction if located
in abasement or above the first story. Section 702 (b).
B-2 Occupancies with an occupant load of 1030 or more should be in Types I,
XX or III one-hour buildings. The assembly room should not be in a basement
if it contains this high occupant load. Section 702 (b).
The main entrance should front directly upon or have a 20-foot wide access to
a public way at least 20 feet in width. Section 703.
Light and ventilation should comply with Section 705.
-4-
_______ A ore-hourfire-rc-ristive ouparcy s c P 111,1-15lon is i1red between the
boiler or central heating pint and the rest of the building. Section 708.
Exterior cpe.nthgs for rooms cnainirg a b br or central heating plant should be proteet sd with tnre -tsurths-hv fir -resisttv e assemblies
that are fixed, autitis, or self-closing if located-below openings in
another story or if lesa thar. 10 feet fron ether doers or windows in the
same building. Section 708.
An apprcrrcd, conspicuously marked, outside gas shutoff valve-is required. Section 708.
Group C
Buildings hiuslng C Occupancies should be of one-hour fire-resistive con-
struct ion- throughout. Section 802 (a) and Table No. 5-C.
Use of rooms should be clarified. Note that rooms having an occupant load of more than 100 and rooms used for kindergarten, first or second grade cannot
be located above the first story above grade except In Type I construction.
Section 802 (b).
A one-hour fire-resistive separation Is required between laboratories, shops,
storage rooms. These areas should also be separated from other classrooms.
Section 802 (b).
One required exit should front directly upon or have a 20-foot. wide access
to a public way at least 23 feet in width. Seation 803 (a).
Sanitary facilities should be provided ir. accordance with Section 805.
Light and ventilation should comply with Section 805.
A one-hour tire-resistive occupancy separation Is required between the boiler
or central heating plant and the rest of the building. Section W.
An approved, conspicuously marked, outside gas shutoff valve is required.
Section 808.
Open plan educational buildings under Section 810 should comply with other
applicable sections. This includes special requirements for fire sprinklers
In Section 3317 (a).
Group D
D-1 Occupancies should be of Type I or IX construction unless complying with
the Exception in Sectióz1902 (b).
D-2 (3) Oocupanc1e hid be of one-hour fire-resistive construction
throughout. Table No. 5-0.
- Light and ventilation should coeply with Section 905.
A one-hour fire-resistive occupancy separation is required between the boiler
or central heating plant and the rest of the building. Section 908.
Exterior openings for rooms containing a boiler or central heating plant
should be protected with three-fourths-hour fire-resistive assemblies that
are fixed, attornatie, or self-closing if located below openings in another
story or If less than 10 feet from other doors or windows in the sane building.
Section 908.
An approved, conspicuously marked, outside gas shutoff valve is required.
Section 938. . . -.
Group .
In order to allow the added story height and/or omission of area sepa-
ration walLs in the parking areas, the following conditions set forth
In Section 1102 (b) should be observed.
The parking level Is of Type I construction.
There is a three-hour noncombustible occupancy separation between
the parking area and the occupancy above.
Structural support for the three-hour floor should have equivalent
fire-resistive protection. Eight-inch concrete block walls, where
used under this condition, must comply with Table No. 43-B or have
all cells grouted. Section 503 (d).
Enclosures for floor openings should be of two-hour construction.
Openings in the enclosure walls should be protected with labeled
one-and-one-half-hour fire assemblies or approved fire dampers.
- The provisions of Section 1102 (b) are applicable to area and story limi-
tations only.
Exiting requirements of Chapter 33 are based on the total number or stories in the building.
Wet and dry standpipos are required In four-story buildings.
Sections 3804 and 3803.
Motor vehicle service stations should be of noncombustible or one-hour
fire-resistive construction. Section 1102 (b). Heavy timber roofs for
one-story service stations are also allowed.
Floors of storage garages should be entirely protected against saturation.
Section 1102 (b).
Storage areas In excess of 1000 square feet in connection with wholesale
or retail sales should be separated from the public areas by a one-hour
fire-resistive occupancy separation. Fire-sprinklers nay bo used to
increase the Prea or waive the separations as set forth in Section 1102 (b).
-5-
Light and ventilation should comply with Scct1on 1105. Mechanical ventila-tion is required in garags eeeding5000 square feet.
Exhaust Ventilation at or near floor level is required by Section 1105.
A onehour fire-resistive occupancy separation is required between a boiler room or central heating plant and the rest of the building. Section 1108.
Groups H and I
An H Occupancy more than two stories in height or having more than 3000 square feet above the first floor shtzld be of one-hour fire-resistive construction throughout. Section 1302 (b).
The follbwing rooms should .have window areas as zsVecified in Section 305 (a) one-half of which is openable.
__________- Mechanical ventilating system in baths should provide five air changes
per hour directly to the outside. Section 1305 (a). Section 1405 (a).
Fan capac.ty should be specified.
Windows from _______________ should not be considered as furnishing required light or ventilation since they do not open to a yard, court, or street in accordance with Section 1305 (a). Section 1405 (a).
Courts bounded on four sides with walls should be at least 10 feet in length. For courts more than two stories in height, the required width
should be increased by 1 foot and the required length by 2 feet for each additional Story. Section 1306 W.
Habitable rooms in cellars are not allayed. See "habitable room" defini-tion in Section 409. The intent is to prohibit such rooms to be formed with retaining walls.
room does not have the minimum ceiling height required in Section 1307 (a). Section 146 (a).
room should have a minimum superficial floor area of ________ square feet. Section 1307 (b). Section 1406 (b).
A toilet room should not open directly into a kitchen. Section 1305 (b).
Section 1405 (b).
Efficiency dwelling units should comply with Section 1308.
A one-hour fire-resistive occupancy separation is required between a boiler
room or central heating plant and the rest of the building. Section 1312.
Every dwelling unit and guest room should have comfort heating facilities as specified in Section 1311. (Section 1409)
J Occupancies are limited to 1000 (3000) square feet in floor area and one story in height. Section 1502.
Exhaust ventilation openings in a garage are required by Section 1504.
Garages should not open directly into a room used for sleeping purposes.
Section 1504.
An approved 1oncombustible material is required for garage floor surfaces. Section 1504.
EXITS:
Conforming exits are required from the areas below as specified in Section 3302 (a).
Exits should have a minimum separation or one-fifth the parlineterot the room or area served. Section 3302 (c). Note that "perimeter" is along the outer
boundary of the room or area served. For irregular shaped buildings or build-
ings with inner courts, it has been the policy to use the perimeter of a square
whose area Is equal to that of the actual building to determine the required minimum separation of exItsv on this basis the distance between exits should
be at least _feet.
AnThccupant load sign is required in tWe,/4L 0 -
Section 3301 (j).
No point in the building should be more than 150 (200) feet from an exterior
exit,. horizontal exit, enclosed stairway, or exit passageway, measured in
the direction or travel. Section 3302 (d).
Exit doors should swing in the direction of egress. Section 3303 (b).
Double acting doors are not allowed where serving a tributary occupant load
of more than 100. Section 3303 (b).
G
Exit doors should be openable from the inside without the use of a key,
special knowledge, or effort. Section 3303 (c). Note also that surface
mounted flush or surface bolts are prohibited. Automatic flush bolts are
allowed on pairs of doors provided the door with the flush bolt .has no knobs
or surface mounted hardware and the unlatching of any leaf requires only a
single operation.
Exit doors should be a minim'-,m size of 31-0!! x 6.1_811 with a miniinumdoor
s-ing ' 90 degrees. Section 3303 (d).
The net dimension (clear width) at doorways should be used in determining
exit widths required by Section 3302 (b). Section 3303 (d). In consideration
of door thicknesses, panic hardware, door swing, etc., the required exit widths
have not been furnished. See door
A floor or landing not more than 2 inches below the threshold is required on
each side of an exit door. Section 3303 (h). (I Occupancies excepted.)
Doors should not project more than 7 inches into the required corridor width
when fully opened or more than one-half into the required corridor width when
In any position. Section 3304 (d).
Revolving (sliding) (overhead) doors are not permitted as exit doors.
Section 3303 (f).
Exit doors should provide immediate access to anapproved means of egress.
Section 3303 (g). Exiting through another room does not comply unless the
room complies as an accessory area in compliance with Section 3302 (e)..
A landing or floor that is level or not more than 2 inches lower than the
threshold is required on each side of an exit door. Section 3304 (h).
Supplementary doors for egress purposes should also comply with all provisions
- of Chapter 33. Section 3303 (j).
Corridors should have a minimum width of 411. Inches. Section 3304 (b).
Corridors serving nonambulatory persons should have an 8-foot minimum width.
Section 3318 (c).
Dead end corridors are limited to 20 feet. Section 3304 (t).
Walls and ceilings of corridors should be of one-hour fire-resistive construction.
Section 3304 (g). An architectural section through the corridor Is necessary to
determine how this is accomplished. See the enclosed sheet of recommended
details.
Exterior exit balconies cannot project into an area where protected openings
are required. 0 -13 0 1 'sMNCff ?Q 5.5 5.c. I ç i )
Interior openings into corridors should be protected as set forth In
Section 3304 (h). Twenty-ninute rating for door assemblies requires
compliance with a specific research recommendation or a labeled fire
assembiy. The latter would result In a 45-mlnute rating since it is
the minimum presently labeled.
Stairway - should have a minimum width of
inches. Trim and handrails should not project more than
)7rinto the required width. Section 3305 (b).
Risers on stairways should not exceed 71/2 Inches and runs should not
be less than 10 inches. Section 3305 (c).
Landings on stairways should have a dimension In the direction of travel
equal to the width of the stairway but need not exceed k feet. Section
3305 (fe).
Basement portion of stairways should have an approved barrier where
continuous to upper floors In an exit enclosure. Section 3305 (g).
Vertical distances between stairway landings are limited to 12 feet.
Section 3305 (h).
Handrail should be placed not less than 30 inches nor more than 34 inches
above the tread. Section 3305 (i). Two handrails are required where
stairways exceed 11.4 Inches In width. (No handrails if less than four risers.)
Guardrails for stairs, balconies, and landings should conform with Sec-
tion 1714. Note that maximum clearance between Intermediate rails is 9 inches and rail height should be 42 inches.
Openings in exterior walls within 10 feet of exterior stairways should be
protected with self-closing three-fourths-hour fire-resistive assemblies.
Section 3305 (Ic).
Enclosed usable space under interior stairways should be protected on the
enclosed side as required for one-hour fire-resistive construction.
Section 3305 (1).
Noncombustible exterior stairs are required. Section 3305 (in).
Exterior stairs should not project into an area (yards or courts) wber.e.
wall openings must be protected. Section 3305 (m).
All required interior stairways which extend to the top floor in any.
building tour or more stories In height shall have provided at the highest
point of the stair shaft an approved hatch openable to the exterior not
less than 16 square feet in area with a minimum dimension of 2 feet.
Section 3305 (1).
One stairway should extend to the root. Section 3305 (n). It must be in
a smokeproof enclosure In buildings over 75 toot above the highest grade.
Section 3309 M.
-7-
-
Six-foot 6-inch minimum headroom clearance for stairways should be indicated
on plans. Section 3305 (o). N6te that this is from a plan' tangent to the
stairway. tread. nosings.
Ramp slopes should not exceed one foot In feet. Section 3306(c)(d).
-- Surface of ramps should be roughened or of a nonslip material. Section 3306 (1).
Stairways should be enclosed as specified In Section 3308.
One (two)-hour fIre•resiative walls are required.
Only exit doors are allowed to open into exit enclosures.
Doors should be labeled one (ene-and-one-hait)-hotr fire assemblies
with additional requirement of maximum 4500P. temperatire rise above ambient after 30 minutes of fire test.
- (d) Exit enclosures should Include a corridor on the ground floor extending
to the exterIoi•. Fire-reiztive construotlon should be as required for
the exit enclosure, Including protected openings. Only exit doors are permitted to open Into the corridor.
(e) An approved barrier is required at the ground floor to prevent people
from accidently continuing to the lower level.
(f) Usable space Is not allowed under the stairs.
One exit from the building should be a smokeproof enclosure complying with Sootión 3309.
Openings into exit courts less than 10 feet wide should be protected with
labeled 45..ninute fire assemblies. Section 3310 (d). Also see "exit court"
definition in Section 3301 (c). Openings more than 10 feet above the court floor are exempted.
No openings other than required exits are permitted In exit passageways. The passageways should be of -hour fire-resistive construction.
Section 3311 (a). Openings should be protected with labeled three-fourths-
hour fire assemblies.
Exit signs should be provided in conformance with Section / P141?T
Aisle (cross aisle) in auditorium should have a minimum width of Section 3313 (b). Section 3313 (e).
Panic hardware is required on exit doors serving Group B Occupancies having
an occupant load of more than 100. Section 3316 (a). In lieu of this, doors should have no locks or latches.
Main and side exits in conformance with Section 3315 are required for B-2 (1) Occupancies. Section 3316 (a).
Every room in a C-i Occupancy shall be provided with exiting complying with Section 333.7 (a). This requires fire-sprinklers unless the specific require-ments are followed.
Corridors of Group C-i Occupancieb should have a width required by Section
3302 plus 2 feet, but not less than 6 feet. Section 3317 (b).
Each floor above or below the ground floor level of Group C Occupancies should
have no less than two exit stairs. Section 3317 (c).
Exit stairs serving an occupant load of more than 100 in ,a C Occupancy should have a mlnhieuin clear width of 5 feet. Section 3317 (c).
Exit doors cannot be more than 2 feet narrower than the required corridor
width in Group C Occupancies. Section 3317 (d).
Exit doors from schoolrooms should swing in the direction of egress. Section
3317 (d).
Rooms of Group C Occupancies used by pupils and located below grade should have one exit leading directly to the exterior of the building. Section
3317 (e).
Panic hardware is required on exit doors serving rooms containing more than
100 occupants and in corridors of Group C Occupancies. Section 3317 (f).
Every room in a Group P Occupancy should have access to at least two legl
means of ogress. Section 3318 (a).
- Doors from bedrooms and wards of Group D Occupancies and all exit openings.
where nonambulatory patients are housed should have a minimum clear width
of 114 inches. No projections in this width are allowed. SectIi7318 (b).
(92D
Panic hardware is required on exit doors serving more than fifty occupants
In D Occupancies unless there i3 no latch or look. Section 3318 (f).
Every sleeping room below the fourth floor should have one openable window
or exterior door conforming to Section 130 (1404) for emergency exit or
rescue. This includes mezzanines.
FLOOR, ROOF CONSTRUCTION, COVERING, SKYLIGHTS, ROOF STRUCTURES
Venting is required for elevator shafts extending mdre than two stories.
Section 1706 (d). The larger of 3-1/2 percent of the shaft area or 3 square
feet per elevator should be provided.-
_______ The space between wood floor construction and a sutpended ceiling below
should be divided into areas not exceeding 1000 square feet. Section 2517(0.
-- Smoke and heat vents should be previded in accordance with Section 3206 (a).
Attics of combustible material should be divided into areas not exceeding
3000 (900) square feet. Section 3205 (b).
Root drainage should be conducted under the public sidewalk. Section 3207(e).
Overflow drains hiving the same size as roof drains and on independent drain
lines are required. In lieu of this, overflow scuppers three times the size
of roof drains should be installed in parapet walls.. Overflow system should
have inlets located 2 inches above the lo" points of the roof. Section 3207(c).
The aggregate area of penthouses and other roof structures cannot exceed
33-1/3 percent of the supporting roof area. Section 3601 (b).
Concrete floor slabs on grade should not be less than 3-1/2 inches thick.
Section 2629.
PE EXTINGUISHING SYSTEMS .
An approved automatic fire-extinguishing system is required in the
Section 3802. This includes blind spaces enclosed wholly
or partly by combustible construction. U.B.C. Standard No. 38.138(1c).
Dry standpipes are required in buildings four or more stories in height.
Section 3803 (b). .
Wet standpipes are required as specified in Section 38011.
Combination standpipes are required in buildings exceeding 150 feet in height.
Section 3805. They may be substituted for wet and dry standpipes.
Fire -extinguishIng systm plans shot1d be submitted to you to determine
compliance with applicable building, plumbing, and fire codes.
Chimneys should comply with Section 3702.
Firep1ces and barbecues should comply with Section 3.704.
Fir al rm yste as per Title 24 of Chapter 13, Section 8 1316.
FINISH WOR K't12t .. .
The Interior. wall and ceiling finishes zheuld be specified and comply with
Table No. 42-B and Section 4203.
Gypsum wallboard (interior lath and plaster) cannot be installed on weather-
exposed surfaces. See Section 424 for definition.
Glass and glazing should comply with Chapter 54. Type and thickness .øf glass
- should be specified.
Glass and glazing in hazardous locations should comply with Section 5406.
Skylights should comply with Chapter 34. Plastic skylights are allowed only
under the conditions specified In Section 5205.
Ranges should have a vertical clearance of 30 inches above the Cooking top
to unprotected combustible material. This can be reduced to 24 inches if the
combustible material is protected with niniva.1/I4-inch asbestos miliboard,
Na. 28 gauge sheet metal or a metal ventilating hood. Section 1901 (a) -
Uniform Mechanical Code.
Mechanical plans should be filed so compliance with the Uniform Mechanical
Code can be determined. .
STRUCTURAL COMMENTS: .. . ... .. . .. . .. . :.' . .....
Special inspection in conformance with Section 305 is required for the
following work:
Structural concrete where the design is based on an ultimate compres-
sive strength in excess of 2000 pounds per square inch.
All welding except where done in the shop of an approved fabricator.
Installation of high strength bolts.
.(d) Prestressing work. .
.
Soil classification, in conformance with Table No. 29-C and ____ pounds per square foot soil bearing value used in design should be specified
on plans. Value Is subject to your approval. Section 29011.
The foundation investigation report mentioned in plans was not Included In
data forwarded to us. It should be submitted for review.
- Aoceptance of the foundation investigation report is recommended contingent
on compliance with local ordinances.
All masonry or concrete elements resisting seismic forces should qualify as
reinforced elements. Section 2311 (k)-3.
Concrete shear walls should comply. with Sections 2632 and 2617 (j).
Precast concrete wall panels are limited to an h/t ratio of 36 (25). Section
2622 (o).
-9- se..
Wood members may support loads from masonry or concrete only under the condi-
tions specified in Section 2516 (a).
Structural calculations should be submitted to justify the adequacy of the
structural system in resisting seismic and wind loads, and supporting dead and
live loads. This includes foundations. E:ave plans & caics. dated & signed engineer. Juby
tifymg calculations and details should be provided for
The roof should be designed for uplift wind pressures with due consideration
for lateral support of compression flanges of flexural members.
Floor load should consider a 20-pound per square foot partition load. Section
2302 (b).
Marquees should be designed for a 60-pound per square foot live load. Table
No. 23-A.
Garages for the storage of private pleasure cars should be designed for a
minimum 2000-pound wheel load. Section 2302 (b).
2x laminated beams should be spiked together as specified in Table No. 25-0.
- Section 2518 (c).
Live load signs are required. Section 2309. See
Glued-laminated lumber should be fabricated in accordance with U.B.C.
Standard No. 25-10. A certificate of inspection should be submitted to
you.
Allowable stress in glued-laminated members over 12 inches in depth should
consider a depth reduction factor. Section 2511 (d)-4.
Radial stresses in curved glued-laminated members should be within allowable
values. Section 2511 (d)-4. Radial tension stresses are limited to 15 pounds
per square inch. If the radial tension exceeds this allowable, mechanical
fasteners should be used to resist the entire stress.
ood studs are limited to 14 feet in height for 2 x 4 and 3 x 4's and to 20
j - f t for 2 x 61s. Section 2518 (f)-2.
Exterior walls and bearing partitions below the second story In three-story
buildings should be 3 x 4 or 2 x 6 studs. Section 2518 (f)-l.
Bolted connections exposed to the weather are limited to 75 percent of the
allowable load under rrotected conditions. Section 25.1711 (c), Uniform
Building Code Standards.
Spacing of bolts should comply with Section 25.1713, Uniform Building Code
Standards. jported bolts do noLcomp1y with Sode requirements.
(1-dS -
Anchorage of concrete and masonry walls should comply with Section 2313.
Designs which rely on cross grain tension of wood members are not acceptable
since the Code has no allowable value. A positive means of connection such
as joist anchors or clip angles should be provided.
Exterior nonbearing walls should comply with Section 2314 (k)-5. Note that
connections for seismic purposes should be based on a "Cs" factor of two.
Table No. 23-I.
Plywood grades should conform with Table No. 25-B.
Justification is required that sufficient slope or camber is available to
assure adequate roof drainage after long time deflections. In lieu of this,
roofs must be designed for possible pending of water. Section 2305 (f).
Details on stressIng method and hardware along with justifying data are re-
quired on prestressed concrete work. This data should be submitted and
approved prior to. ordering of material. Note that all tendons should comply
with Section 4303 (e)-.3, for fire-resistive purposes.
Welding data or details for steel decking used as a diaphragm should be pro-
vided. Information sheuld comply with a Specific ICB0 research recommendation
or test data submitted In compliance with Section 106.
Details should be provided on roof (floor) diaphragm connections that indicate
how the shears are transferred to vertical shear-resisting elements. Connec-
tions should be justified with structural calculations for compliance with
allowable values.
Straight sheathed deokirig should be justified for diaphragm action since it is
not covered under Section 2514. Justification should be based on the discus-
sion of transverse sheathing, Page 4-126 of the TimberConstruction Manual
issued by the American Institute of Timber Construction.
Nailing for gypsum board (lath, sheathing board) used structurally on shear
walls should be specified and comply with Table No. 47-I.
Shear walls utilizing gypsum board (lath, sheathing board) cannot be used to
resist loads imposed by masonry or c0n3r65e walls. Footnote 1, Table No. 47-I.
-10-
_______
The Code has no previsions for stt'.ecc shear walls unless it cenplies with
a specific ICB0 research rerornner.dat1,r.. Let-in brzccs should cc justified
on the basis of end nailing and angle of 1.rstallton since tho Code has no
provisions for allowable values.
Railings should be desiCned to withstand a 20-pound per foot horizontal
- force. Section 2304.
Ceiling joibta should be designed for total load of not less than 10 pounds
per square foot. Section 230.
Interior partitions should be justified structurally for strength and do-
fleetlon criteria set forth In Section 2312 M.
__________
should comply with a specific ICB0
rcseafieoornsndation or Justifying test data should be submitted in
compliance with Section 106.
Wood members entering masonry or concrete should comply with Section 2517 (c)-5.
Plans should indicate that foundations extend below the frost line.
Lap splicing of No. 14 and No. 18 rebars Is net allowed. Section 2608 (a).
Wood design criteria should be based on industry standards published in
October, 1970. Wood is no longer graded under criteria set forth In the Coda.
Reference Is made to Research Recommendations 2569 and 2180.
AITC laminating specifications should be used foi glue-lam construction since
Industry no longer uses the criteria set forth in the Code. Reference Is made
to Research Necommendaion 2519.
Nailing for plywood diaphragms (shear walls) should be indicated on plans.
Data should agree with calculations. See
Structural specifications should be on plans. This Includes concrete, masonry,
mortar, grout, lumber, plywood, reinforcing bars, structural steel, steel
decking, etc.
Minimum reinforcement should be provided for masonry walls to comply with
Section 21 18 (j)-3.
Minimum reinforcement should be provided for reinforced concrete walls to
-w4$.th..Bection 2622 M.
1971 Uat al ElectricC rd.!. ....yf . ,
- Provide single line drawing and calculations. _IfL! 200 Amp or large
Show panel location and size. /N 0C ,? A
.—All horizontal feeders to be in an approved raceway.
Four duplex receptacles maximum on each appiance circuit.
]97Uni f 4chanica1 Code - Ord. #8055. .
47
Show size and laction of F.A.U., venting, combin.tion air.
- return air, ducts and registers. bj' id' / I"J ..
/ Show dryer vent to outside air.
Hechanical plans required.
4 d- v,4 e-
1970 Un rm PluInbg Code - Ord. #8057
SI mperature and pressure re.lief valve and
ischarge line on water heater.1
Indicate height of water heater platform.
andscape and irrigation plans required.- Ord. 09060, Sec.
____& UPC Sec 1003 (h)
4
cro Ftcopy of as-built plans require d.pc ............
/ #4
tOe
INTERDEPARTMENTAL INFORMATION SHEET
BUILDING DEPARTM
BUILDING ADDRESS:
LOT SIZE IZt!,2.c's
PLANNING DEPARTMENT
Ip (t.Ct AC)
WIDTH ZONE R_O•'t.'
UNITS PROVIDED _ALLOWED I2.4_PRKG. SPACES PROVIDED _03 REQJ 0
% OF COVERAGE ALLOWED _ BLDG. HEIGHT _ALLOWED -
FRONT SETBACK SIDE YARD_REAR YARDQJINTRUSIONS
ENVIRONMENTAL PROTECTION REQ P LAN 'TS
IDDITIONAL COMMEN p '
'22
ISSUE PERMIT 4/2 OCCUPANCY _DAT
ENGINEERINGDEPARTMENT 7 •7 2 ?
R.O.W. _56_X_IND UUd, RI AL ASTE_______________________ . ic
IMPROVEMENTS SEWER CONNECTION_t..
DRIVEWAY LOCATIONS_2 C6'A'13P CUTPA'4f/7$ GRADING PERMIT-
EASEMENTS OP&LE44414W DRAINAGE
LEGAL DESCRIPTIO
AD DI TI ON ,c.. COMMENTS 7I - O.'7;Qt 0.4/ a,. - 'c AJ.' D '
E O gc-G/,v,w - S rXO ( 7/4A/. 1 I
ISSUE PERMIT I#Z DATE 73 OCCUPANCY DATE_2.22 74t
FIRE DEPARTMENT 'v :: ••• .. .? 0 -
SPRINKLING SYSTEM
..', .i,:;
FIRE PROTECTION EQUIPMENT FIRE ALARMS_fl
EXITS "..
FIRE HYDRANTS LOCATION______________________________
ADDITIONAL COMMENTS
ISSkjE ?ERMIT DATE OCCUPANCY DATE__________
1IgPEPARTMENT - .' -
CARLSBAD OLIVENHAIN_________ SAN MARCOS_________
ONAL
ISSUEPERMIT DA Fff OCCUPANCY DATE___________
SENT-TO PLAN NI G SENT TO ENG. DEPT.
QTLflNFfl Tr) RI r ori DMCrI ,-r s rr' nr
INTERDEPARTMENTAL INFORMATION SHEET RE C EIV ED
BUILDING DEPARTMENT C.- ( - DATE.
N41.11kY .2 1913
BUILDING ADDR
(
Building Departmcnt
PL .NG DEPARTMENT
LOT SIZ WI DT V NE1\.-t'\
UNITS PROVIDED ALLOWE ______PRKG. SPACE VIDED_REQ.
% OF COVERAGE ALLOWED IGHT ALLOWED
FRONT SETBACK SIDE YARD REAR YARD INTRUSIONS
.1
ENVIRONMENTAL PROTECTION REQ'TS. 0 LANDSCAPE PLAN' _
ADDITIONAL COMMENTS (\P .
ISSUE PERMIT DA UPANCY TE
- I •_.
O C C ',t'CY.,.'2' c7A- 5 /v . Z -
ENGINRINGDEPARTMENT
R.O.W. k- INDUSTRIAL WASTE
IMPROVEMENTS X./7'iC,-SEWER CONNECTI61_-._sc)._
,DRIVEWAY L'jCAONS_GRADING PERMIT____________
EASE1EI.1S_,- _,V/9. _DRAINAGE
LEL.. ..L DESCRIPTI
DITIONAL COMMENTS
SSUE PERMIT #1/ _DATE_ /9-73 OCCUPANCY_ ATE
OccJp44,c' Ok VcS c24'4y loylly -0 11 1_5 °/ç /7g/
FIRE DEPART 'ENT
SPRINKLING SYSTEM ,"Aa f—c=_ lc% %.) (r—C4
ARE PROTECTION EQUIPMENT- /K- &n--_ FIRE ALARMS__________________
EXITS
FIRE HYDRANTS_ ..1e---'-- LOCATION____________________________
ADDITIONAL COMME
ISSUE _hl— OCCUPANCY ATE
WATER DEPARTMENT .
-
C M W D Ab SBAD OLIVENHAIN_________ SAN MARCOS_________
ADD I TI .
ri OCCUPANCY DATE___________
ING _______________ SENT TO ENG. DEPT.
D I rs,- r . • n. , n
ICMRDSQ SSOCITES . I. .
CIITCTS
July 16, 1973
PRAVER CONSTRUCTION CO...
2500 Navarra Drive
Rancho La-Costa, California 92008
Attention Mr. Stanley Prayer
Gentlemen:
Subject: 2500 Navarra - La Costa
WRA Job No. 7223
Due to-field complications that you brought
to my attention concerning detail 9 G-1 and Section
A B-1 the following was resolved.
WRA contacted Mr. Richard Osborn, Head of
the Carlsbad Building Department, explaining to him
that I had personally inspected the site and found
the situation structurally, adequate and pointing out
the fact the 2 layers of 5/8" gypsum wall board
extended beyond the blocking. Mr. Osborn agreed
with me that the 3 additional blocks, which were
virtually impossible to place, could be deleted.
Should you have any questions, please do
not hesitath to contact the undersigned.
Very truly yours,
WRRDSON ASS0CIATESA.I.A.
David L. Ball
0 LB/sm
cc: Mr. Richard Osborn
BT.ZT • .. CO9TA • CI.I'Ot. • e a a • (rl.4) e a.aa
I
The Majestic Company
HUNTINGTON. INDIANA 46750 219/356-8000
REPLY TO:
JOHN J.OXLEV
DISTRICT SALES MANAGER
607 SOUTH PROSPECT
SUITE 7307 September 189 1974
REDONDO BEACH, CALIFORNIA 90277
Phone 213/372-7417
City of Carlsbad Building Department
1200 Elm
Carlsbad, California 92008
Attn: Mr. Bob Nelson
Subject: Special Eybrow-Heat Deflectors and Sidewall Clearances
Dear Mr. Nelson;
Pursuant to Fireplace Distributors installation of our
fireplace systems at 2500 Navarra Street, La Costa for Prayer
Brothers Investment Corporation, there are two questions that have
arisen pertaining to: First, safe clearances to sidewall construction
and Second, the proper design and installation of special heat
deflection eyebrows that have been installed on several of the
fireplaces where a combustable trim was installed above the
fireplace opening (closer than 1211).
Upon our mutual inspection of this application some two weeks
ago, it would be my opinion that the clearances to the sidewall are
adequate and will constitute a safe installation. In the instance
of the special eyebrows, I would consider the gauge of material
and design to be more than adequate to reflect what heat may be
emitted away from the combustable trim piece directly above the
eyebrow.
An American-Standard Company
S - '
- Majestic
The Majestic Company
HUNTINGTON, INDIANA 46750 219 /356-8000
REPLY TO:
JOHN J. OXLEY
DISTRICT SALES MANAGER
607 SOUTH PROSPECT
SUITE 77 307
REDONDO BEACH, CALIFORNIA 90277
Phone 213/372-7417
In summary, the fireplaces at this project are installed in
a safe and operable manor by our distributor, Fireplace
Distributors, Incorporated, 11526 Sorrento Valley Road, San Diego.
I trust this letter will serve to satisfy any questions that
you might have regarding these installation.
Respectfully yours,
John J. Oxley
District Sales Manager
The Majestic Company
- JJO/lw
An knerican-Standard Company
, •
BENTON ENGINEERING. INC. -
APPLIED SOIL MECHANICS - FOUNDATIONS
-
.
6741 EL CAJON EIOULEVARO
SAN DIEGO. CALIFORNIA 92115
PHILIP HENICING SENTON SAN DIEGO: 58-5654
PRESIDENT -CIVIL ENGINEER,.. •.. 'j.. June 23, 1707 L* MEsA: 469.5654
Rancho La Costa, ma.
Route ! Box 2550. ...::.:
Encinitas, California 92024
Subject: .I.Project '-11-23D .
.•.•.• FirralReport on
. . Compacted. Filled Grgund •.
.
• :
•. • : ..' La. Costa South Unit No. 1 • : •. . • - •
Rancho La Costa, California
: Gertlemei .
This is to report the results of tests and observations made in order to inspect the compaction of
filled grciünd p!acedonce'tain areas of Lots 11 3 to 7, inclusive, 14 to 25, inclusive, 34 to 39,:
inclusive,.43.to46;inclusWe,54 to 58, inclusive, 62 to 72, inclusive, 82, 83, 84,86,87,89,
;:• 90, 110 to .120 ,inclusiye,. 122,123, 131, 132, 151 to 154, inclusive, 166 to 177, inclusive,
181 to 184, inclusive, and Portions of La Costa Avenie, Navarra Drive, Viejo Castilla Way,
Nuevo Castilla Way, Sevilla Way, Lev* Street, Galicia Way, and La Corona Place, La Costa
South Unit No. 1, Rancho 'La. Costa; California. The fills, were placed during the periods
between February :4,1969 and May 2,1969. : . . .
The approximateareas and depths of filled ground placed under our inspection inaccordance
with the approved specifications are shown on the attached Drawing No. 1, entitled "Location
of Compacted Fflled:G.round..."..The gradirig plan used for the placement of filled ground was
prepared by.Mclr.flre.& Quiros,: Inc.. dated January, 1968. .
The approximate* locthiostwhich the tests were taken and the Final test results are presented
on page Nos.4io 19, inclusive,. under the"Tableof Test Results." The laboratory determina-
tions of the rnaxhnw dry densities and optimum moisture contents of the major fill materials
are presented on cge No. 20, under the "Laboratory Test Results." Some of the maximum dry
densities shwi in the "Table-of Test Results" were combinations of these. The tests were taken
durino the weekly periods indicated below: •
Test Number ' Week Endirvj
I to 8, inclusive February 8, 1969 -
: 9 to .29,indusive February 15, 1969
30 to 37, inclusive. February 22, 1969
38 to 89, inclusive March 8, 1969
4.0 to 139, inclusive March 15, 1969.
140 to 1911 inclusive March 22, 1969
192 to 2571 inclusive . March 29, 1969
Continued on page two.
La Costa South Unit No.1
lost Number Week Ending
258 to 352, inclusive April 5, 1969
353 to 433, inclusive April 12, 1969
434 to 461, inclusive April 19, 1969
462 to 485, inclusive April 26, 1969
486 to 506, inclusive May 3, 1969
The final resuitsof tesftand:observations indicate that the compacted filled ground has been
placed at 90 percent of the maximum dry der&ty or greater. It has been determined that the
fill materials,.compacted to 90percent of the maximum dry density, have a safe bearing value
of.al I east. I5l0 pounds par square foot for one foot wide continuous footings Founded at a
minimum depth and placed five feet or more inside the top of compacted filled ground slopes.
If Fooflngs are placed closer to the,exposed slopes than 5 feet inside the top of compacted fitted
ground slopes, these should be. deepened one foot below a 1 1/2 horizontal to 1 vertical tine
projected outwand and downward From a point 5 feet horizontally inside the top of compacted
filled ground slopes.. Tests indicate that the compacted filled ground is adequate to satisfactorily
support the proposed one ond two story wood frame dwellings without detrimental settlements.
In our hg ion conducted at this subdivision. (Project N. 68-2--2C
dated March 81. 1968). vie hated that some silty clay and sandy cloy soils had been found on
the site that were expansiie,arid we recommended that each lot be inspected during or after.
grading to:deterrnine..thóss.19b In which such expansive soils exist within the upper 3.0 feet.
This has bsendne,.and.the.iohlowing lots have been found to contain potentially expansive
soils.wi thin the.upper.3.O feet... .. . • . .. . .
Lot Nos. 1 to 81, inclusive
Lot Nos 97 to 109, inclusive
Lot No;. 170 to 1841 inclusive
It is recommended that the following special design precautions be taken for the houses to be
constructed on the abovè-lhted totS : ..
Isolated interior piers should not be used Continuous footings should be used
.:throughout, arid these should be placed at a minimum depth of two feet below
: the loiest adjcicent exterior final ground surface. ..
.::Renforeand interconnect continuously with steel bars all interior and exlerioi
. footirswith two #4 bars at 3 inches above the bottom of all footings and two
#4 bars placed 1 1/2 inches below the top of the stem; of the Footings.
3.:Usaised wood floors that span between continuous Footings, or reinforce all
concrete slabs with 6x 6 — 10/10 woven wire fabric, and provide a minimum of
4 inches of clean sand beneath all concrete slabs. Provide a moisture barrier
2 Inches below slabs under living areas.
DENTOt1 rrIc;IN :d,r INC.
rrOeCT NO. 001 IJtJ - juric 4131 I70
.,o Costa South Unit' No. I.
Separate garage slabs from perimeter footings by 1/2 inch thickness of
construction felt or equivalent, to allow independent movement of garage
stabs relative to perimeter footirjs.
Provide positive drainage away from all perimeter- footings to a horizontal
distance of at least 6 feet outside the house walls.
In additiontolthe filled ground placed and inspected within La Costa South Unit No. 1, there
was an area of fill approximately 180 feet east of he east end of Navarra Drive. This area is
shown on Drawing No. 1, and the tests taken within the area are Test Nos. 27 258, 264 and
270. • .'.: . .
Respectfully submitted,
BENTO N ENG I NEE RI NG, INC -
By 1b
M. V. Pother, Civil Erneer
Disfr: : (4) Add ressee.:::.. . .
. :
(2) McIntire &Quiros, Ince
.Attention Mr. Gary Cumbey . .. . .
(1) Rick Engineering
/\pprOx- L)eprn Maximum
imate of Fill Field Dry Dry
Test Location : at Test Moisture Density Density
No. or Lot No. in Feet % dry wt lb/cu Ft lb/cu ft
252 Navorr Drive- 20 15.0 113.7 125.9
Opp. 55&56
253 . : 12 . 10.0 111.7 120.6
254 37 12 11.0 109.4 120 8
255 38 14 )2.6 109.8 120.8
256 36 . 8;•• : 14.3 . 111.3 120.8
. . 257 180' E.FE......: 2.. . 9.9 . 128.9 131.0
end of Navárra'Dr.; ---
. 258 180' E.,ofE 4'.•. •. .10.3. 124.8 131.0
end of Navarra Dr.
259 35 •••. :' .
;.: 13.9 .114.5 : 120.8
1v160 .• -.16.1 . 112.3 120.8
261 37 16 12.9 107.2 .118.8
262 39 16 12.2'115.4 125.8
263 38 18 9.9 116.6 125 8
264 1801 E. of E 6 13 7 117.0 129.5
end of Navarra Dr.
265 45 4 147 113 5 125.9
266 36 12 14 2 110 9 118 8
267 Navarra Dr 24 14.8 lii 1 120.8
Opp. 54&55
268 37 20 -14.4 1112.3 120.8'
269 39 20 15.1 109 9 120 8
270 180' E. 'of E. -'8 15.5 1.11.0 . 123.5
end of Navarra Dr -
271 55 32 .12 .8 103.4 113 0
272 56.30 15.3 1052 1160
273 58 28 .14 .0 112.5 123.5
274 La Costa Ave.,1'over 13.8 109.5 : 113.0
Storm Drain •:
pipe; .. ...
-
Opp. 23 •':
275 La Costa' Ave..1'.ovèr 14.1 105.4 .. 109.3
. Parkway, Opp.. pipe
. Lot Line 23&24 .
.. ..:..
276 La Costa Ave.' ..1' over 14.9 . 112.9 . 120.6
Opp. Lot ike'.. pipe
24&25 - .
277 54 . 34 17.9 99.6 109.2
278 57 -30 11.5 . 113.0 120.8
279 58 •• . 32 14.5 103.3 113.0
280 38 •22 .. 13.7 . 115.4 125.9
Percent
Compaction' Remarks
90.3
92.5
90.5-
90.9
92.0
98.3
95.3
94.8.
93.0
90.2
91.8
92.8
90.4
90.2
93.3.
92 0
93.1 . •.• -.
9.1.0
90.0
91.6
90.7
91.1.
97.0
97.3 -.
93.7 Reworked
91.2
93.6
91.5
91.6
to Costa South Unit No. 1 .
TABLE OF TEST RESULTS (CONT.)
a fl a a.
LIENTOPS ;Iu.Ic:c.. INC
. • Froect No. 68-11-23D -
.. to Costa South Unit No 1
TABLE OF TEST RESULTS (CONT.)
• Approx-. Depth Maximum
imata of Fill. Field Dry Dry
Test Location at Test Moisture Density Density Percent
No. or Lot No. in feat % dry wt lb/cu ft lb/cu ft Compaction Remark
313 122 . /..: . .4 : 13.9 103.4 113.0 91.5
314 123 .•.9... 13.7 104.5 113.0 92.4 FinishedGrc
315 . 131. 4. 12.3 99.6 108.3 91.9
316 46 6 14 9 108 9 120 8 90.1
317 45 8
-
14.2 105.4 115.8 91.0
318 44 1 17.0 111.2 120.8 92.1
319 44 .. 3 17.1 110 8 120.8 91.6
320 46 10 12 5 108.8 116.0 937
321 45 12 11 2 111.3 116 2 95 9
322 43 , 3 ' 14.2 108.3 119.8 90.4
323 43 5 7.7 101.6 118.8 85.6 Reworked
324 4.3 5 100 1054 1169 903 Check on
325 43 - 7 6 4 105 2 116.9 90.2 Reworked *
326 ' 3 32 134 1135 1190 953
327 La Costa Ave 18 14 9 113 0 119.0 94.9
Opp.3&4
328 4 25 15 1 107.5 114 3 94.1
329 5 22 17.3 104.6 110.6 94.6.
330 6 18 152 105.1 110.6 95.0
331 7 - 24
Navarra Dr 2
12 1
14 3
.110.1
110.2
.116.0
120.8
94 9
91.2
Opp. -45 &46
333 17 _11 13.1 102.3 113.0 906
334 Navarra Dr. 4 11 8 97 6 118 8 82 .2 , Reworked
Opp 45 & 46
Finished Grc
335 4 29 16-.4 - 107.8 118.0 91.3
336 25 21 - 12 3 107 4 116 0 92 6
337 24 34 14.4 109.7 114.8 95.5
338 25 25 A4.0 115.3 120.6 95.5
339
,
23 28 20.5 104.3 114.8 91.0
340 24 38 ' 13.5 112.3 120.6 93.1
341 23 32 13.7 113.6 120.6 94.1 Finished Gra
342 2 2 25 13 0 987 108-3 91.1
343 21 - 25 14.1 106.0 116.0 91.3
3.44 25 • 29 .. : 12.5 119.2 124.3 95.9
345 20 • •. 17. 17.3 104.2 114.5 91.0
346 19 •: 9 16.3 . 107.5 119.0 90.3
347 18 ::. 7 • . 15.9 105.9 116.0 91.2
348 22 • . • 29.:.. • 148 114.0 120.6 94.4
349 20 • 21 • • 13.3 102.5 113.0 90.7
350 19
•
• 13 • 14.4 111.0 119.0 93.2
• * Finished Grade
•
UENTOrI Ff4.:;,ri,uiNG. Ir..
La Costa South Unit No. I
. TABLE OF TEST RESULTS (CONT.)
• Approx- :. D2pth . . Maximum
• mate of FIJI Field Dry Dry
Test Location a Test Moisture Deriy Derity Percent
No. or Lot No. in Feet. % dry wt lb/cu Ft lb/cu ft Compaction Remarks
479 86&87..:. 10. 13.9 104.7 116.0 90.3
480 101 &.102. . 4.:.. .13.3 103.7 114.2 90.8 Finished Grade
481 86&87 . 12 •' 14.2 113.2 120.6 93.9 -
482 72 5• . 15.9 101.6 108.3 93.7 Finished Grade
483 71&Viejo 16 164 110.1 1190 935 Finished Grad,
- Castilk Way
.484 . 86 & :14" . 14.4 112.0 120.6 92.9
485 70 18 :-.r,15.5 107.0 119.0 90.0 Finished Grade
486 69 8 10.8. 101.4 168 .3 93 6 Finished Grade
487 66 16 10.4 108.6 116.8 93.0' Finished Grade
488 65 18 9.1 106.7 115.5 92.3 Finished Grade
489 86 & 142 1055 116.0 91.0 Finished Grade
490 64 14 12.3 109.2 119.0 91.7. Finished Grade
491 63 12 -:14.6 110.4 119.0 92.7 Finished Grade
492 62 11 122 1035 1148 90 1 Finished Grade
493 33 - ' 5 8 0 108 9 119 0 91 6 Finhhed Grade
494 34 12 8 5 109.5 119.0 92.1 Finished Grade
495 Viejo Castilla 10 9.9 117.3 119.0 98.7 Finished Grade
Way Sta 3+71
496 Vie castilla 6 11 3 114.5 119.0 96".2 Finished Grade
Way Sta 4+71 -
497 35 10 13,1 107 8 119 0 90 5 Finished Grade
498 36 - 23 12 3 115.1 123.9 93.0 Finished Grade
499 37 28 - 16.2 105.3 116.9 90.1 Finished Grade
500 38 30 13 7 105.6. 116.9 90.4 Finished Grade
A01 39 30 8.6 117.8 125.0 94.2 Finished Grade
02 46 14 '9.9 107.8 118.8 90.8
503 45 16 12.2 117.8 .125.0 94.2 Finished Grade
504 Navarra Dr 4 74 107.5 118 8 906 Check on #334
Opp. 45 & 46 - Finished Grade
505 54 38 52 1140 1250 91.2 Finished Grade
506 55 36 5.0 115.6 128.0. 90.4
SCN,C).i
TITLE: ELECTRICAL CALCULATIONS
TE #3i-
DATE: 3 APR 82
T. Unit A 1012 Sq. Ft.
General lighting load 3 x 1012 = 3036 watts
Small appliances . 3000
Range 9600
Trash compactor 1200
Dishwasher 1200
Washer/Dryer Combination 5000 1
23,036 watts
First 10KW @-100%:'
.
10,000 watts
Remaining 13,036 x.4'\
. .5,214 " 1
Air conditioner @ 10011: 2,600
17,814 watts
Unit Feeder Load
17,814
208., 86 amps
Provide: 100 A, 120/208, 10, 3W service
(typical all units)
I
DRAWING NO.
EK~ PROFESSIONAL ENGINEERS SHEET 1 OF
4443 - 30th STREET 9 SAN DIEGO, CALIF. 92116 • 714/282.7616
TITLE: ELECTRICAL CALCULATIONS
2. Unit A—i 1471 Sq. Ft.
General lighting load
Other loads (same as Unit A)
PROJECT: CONDO 5
AKE #385
DATE: 3 APR 82
3 x 1471 = 4413 watts
19000 - 'I
23,413 watts
First 10,000 W @ 104: 10,000 watts
Remaining 13,413 (q, 40%: 5,365 "11
Air conditioner @ 100%: 2,600 "It
17,965 watts
Unit Feeder Load
17,965 = 86 amps
3. Unit B 1304 St. Ft.
General lighting load
Other loads ( same as Unit A)
First 10,000 W Co. 100%:
Reriaining 12,912 @ 40%:
Air Conditioner 10011:
3 x 1304 = 3912 watts
19000 'I It
22,912 watts
10,000 watts
5,165 'I
2,600 "
17,765 watts
Unit Feeder Load
17,76-5 =85
amps 208
DRAWING NO.
EHED PROFESSIONAL ENGINEERS SHEET 2 OF
4443 - 30th STREET • SAN DIEGO, CALIF. 92116 • 714/282-7616
TITLE: ELECTRICAL CALCULATIONS PROJECT: CONDO 5
AKE #385
DATE: 3 APR 82
4. Unit C 1148 Sq. Ft.
General. lighting load 3 x 1148 = 3444 watts
Other loads (same as Unit A) 19000
22,444 watts
First 10,000 W @ 1001.: 10,000 watts
Remaining 12,444 4 40%:
- 4,978 "
Air conditioner @ 100%: 2,600
17,578 watts
Unit Feeder Load
17,578 = 85
amps 208
5. Unit C—i 1743 Sq. Ft.
General lighting load
Other loads (same as Unit A)
First 10,000 W @ 100%:
Remaining 14,229 @ 40%:
Air conditioner @ 104-1:
3 x 1743 = 5229 watts
19000
24,229 watts
10,000 watts
5,692 "
2,600 "
1,292 watts
Unit Feeder Load
18,292 = 88 amps 208
El
DRAWING NO.
LAIKIE PRC)FESSIC:)NAL ENGINEERS I SHEET 3 OF
4443 - 30th STREET • SAN DIEGO, CALIF. 92116 • 114/282-7616
PROJECT: CONDO 5
AKE #385
DATE: 3 APR 82
TITLE: ELECTRICAL CALCULATIONS
TOTAL DWELLING UNIT LOAD
Area: 47 x 1012 = 47,564
5 x 1471 = 7,355
3 x 1304 = 3,912
16 x 1148 = 18,368
7 x 1743 = 122O1
89,400
General lighting: 3 x 89,4000 - 268,200 watts
Small appliance circuits: 3000 x 78 = 234,000 " "
Laundry outlets: 1500 x 78 = 117,000 "
619,200 watts
Net lighting demand: .35 x 619,200 = 216,720 watts
Range load: .16 x 9600 x 78 = 119,808 " 1
Clothes dryer: .25 x 5000 x 78 = 97,500 1 U
Balance of appliances: .75 x 5000 x 78 292,500
Service required Cq 208U, 3—phase: 48,750 " 1
775,278 watts
775,278
= 2160 amps 359
I
DRAWING NO.
FiEI1 PROFESSIONAL ENGINEERS SHEET 4 OF
4443 - 30th STREET • SAN DIEGO, CALIF. 92116 • 714/282-7616
TITLE: ELECTRICAL CALCULATIONS PROJECT: CONDO 5
AXE #385
DATE: 3 APR 82 HOUSE PANELS (see schedules)
LTC Motors
HA: 46 amps 133 amps
HB: 26 amps 138 amps
HC: 42 amps -
HD: 52 amps -
HE: 49 amps -
EM: 13 amps 127 amps
228 amps 398 amps.
House panel total feeder: .35 x 228 + 292 = 625 amps
Total for dwelling units and house panels:
2023
- 625
2023 amps
Provide: 3000 amp service
@ 208y/120v,30,4W
DRAWING NO.
KK: I r= I PROFESSIONAL ENGINEERS SHEET 5 OF
4443 - 30th STREET • SAN DIEGO, CALIF. 92116 • 714/282-7616
TITLE: ELECTRICAL CALCULATIONS
Service capacity for one floor on dwelling units:
General lighting: 3 x 29,700 = 89,100
Small appliance: 3000 .x 27 = 81,000
Laundry outlets: 1500 x 27 = 40,500
210,600
Net lighting demand: .35 x 210,600 =
Range load: .24 x 9600 x 27 =
Clothes dryers: .325 x 2500 x 27 =
Balance of appliances: .75 x 5000 x 27 =
PROJECT: CONDO 5
AKE #385
DATE: 3 APR 82
73,710W
62,200w
21,938W
101,250W
259,098W
Capacity required for each floor:
259,098
1.73x 208 = 720 amps
DRAWING NO.
E1E1J PROFESSIONAL ENGINEERS SHEET 6 OF
4443 - 30th STREET a SAN DIEGO, CALIF. 92116 • 714/282-7616
TITLE: c.r,j O9i (::L C-u L97 /0 ç PROJECT:
38'_
DATE:
oiIy
/-.I.ZcOMc,. I. a'e
1--- r'zos
-3P,2.coo,i,
M •-t .P,c Cn
J-.
IJZTU
. 3P
3c6) 4" &r
MI
Ij
HI
iFi N1 1
:.•
ft111c
2PI
Rv
1)tv'T
p,r(w- I M
\I
typ ,(24)
1v
-
- 'W
HA '15
v— ___ p A'4-(-'21) 3d
)
Mg-L,A, .brn&,ñti
/,• Co eLc-.to Li ej
C)
a, c.. BlkrS
0o4iC.
-• C_m2J&up,c P!cp)
-- I DRAWING • NO.
No. 5552 J PROFESSIONAL ENGINEERS SHEET 7 OF
4443 30th STREET 9 SAN DIEGO, CALIF. 92116 . • 7141282-7616
N .
//-
in
.
21 7a
-
2,Z/ %w/.
/ 7
WOO
1•.
t kVM''4
TRADE 8UBCONACT0R
Qugh Grade Don Pollock Excavating 3310 Kurtz St. San Diego, Ca.
Concrete Foundations Nint'eman Construction Co.- 11465 Morena Blvd. San Diego, Ca
Masonry & Block Wall Woolen Masonry - 1120 S. 1st. St. Encinitas, Calif.
Metal Fire .-Places Fireplace Distrib. - 11526 Sorrento Valley Road, San Diego.
Back Fill & Compaction Leaverton - 76140 Clairmont Mesa, San Diego, Calif.
Rough Lumber Ja Mac Lumber Co. - 30140 Tidelands, National City, Calif.
Electrical Young.Electrie -6176 Federal Blvd, San Diego, Calif.
Plumbing Leaverton - 76140 Clairmont Mesa, San Diego, Calif.
Heating & AirCpnd. University.Mech, & Eng.-1414614 Alvarado Fwy. San Diego, Ca.
Iron & Steel International Iron Prod.- 9630 Aero Drive, San Diego, Ca.
Sheet Metal P, & K. Sheet Metal - 11823 Sherman Way, No. Hollywood Ca.
Stucco G.L. Fromang Plastering-6186 Tooley St, San Diego, Calif.
Dry Wall Mullins & Mitchell - 7922 Armour St, San Diego, Calif.
Paint Hemphill - 14678 Federal Blvd, San Diego, Calif.
Garage Doors Bedford Overhead Door 2120 Vista Frande Place, Vista, Ca.
Hardware Fin,sh Crown City Hardware Co, 10147 N. Allen, Pasadena, Ca.
Roofing R,C, Roofing - 21407 Cudahy St, Huntington Park, Calif.
Finish Carpentry Crown Door & Trim - 7670 Lemon Ave, Lemon Grove, Calif.
Cabinets Parkinson Cab. Shop- 10511 Floyd Smith Drive, El Cajon, Ca.
Cultured Marble Fabricor Products - 205 W. 35th St. Suite C National City,
Tile San Diego Tile, 7905 Balboa Ave. San Diego, Calif.
Windows & Sid, Doors N. San Diego Glass - 14014 E. Grand Ave. Escondido, Calif.
Weather Stripping Capitol Insul. & Weather - 3918 Mason St. San Diego, Ca.
Plastic Laminated Tops Bonded Products Co. 2103 Santa Anita Ave, So. El Monte,C
Appliances Hotpoint - 8227 Complex Drive, San Diego, Calif.
Light Fixtures Wood Lighting Fixture Co. 14020 Campus Dr, Newport Beach, Ca
Light Weight Mills Const, Concrete - 201 West 18th Street, Nat']. City, C
Dex-0.-Tex Venetian Terrazzo & mosaic 3140.8. Palm Ave.Alhambra., Ca
Water Proofing R.C. Roofing Corp. - 11407 Cudahy St. Hunt. Pk. Calif.
Resilient Flooring Glenn's Interiors 2141 West Mission, Escondido, Calif,
Clean-up Construction Clean Service 932 No. Batavia, Orange, Calif.
Sauna Vico Products Mfg. Co. - 1808 Potrero Ave, S. El Monte, Ca.
Fire Alarm System Electronic Systems Engineering - 3822 Sherman St.San Diego.
Tennis Court Fence A A Fenco. Co. Inc, 2763 StateSt. Carlsbad, Calif.
Landscaping Bob's Landscaping Service - 16761 Construction Way W.
Santa Aria, Calif.
/ - 4 Pi
Bominite .. Western Landscape Const. 9053 Olive Dr. Spring Valley, Calif.
Pool . Western Pools, 9053 Olive Dr. Spring Valley, Calif.
Curb, Gutter &
Paving • • Daley Corp. - P.O. Box 20188, San Diego, Calif.
Cable T.V. Electronics Consult antP.0. Box 196, San Clemente, Calif.
-r--r -'
••••
.:. • •. . . • •:
. •
. •
•
• • • •• •
. • .. .•.
I •. • .•.• .•.•, . • ... . • .• •.
n
it