HomeMy WebLinkAbout2525 El Camino Real; 100; CBC2017-0507; PermitPrint Date: 01/31/2020
Job Address:
PermitType:
Parcel No:
Valuation:
Occupancy Group:
# Dwelling Units:
Bedrooms:
Project Title:
2525 El Camino Real, 100
BLDG-Commercial
1563020900
$ 88,136.45
Commercial Permit
Work Class: Tenant Improvement
Lot#:
Reference#:
Construction Type
Bathrooms:
Orig. Plan Check#:
Plan Check#:
Description: THE SHOPPES: T.I. 1,895 SF OFFICE FOR MALL OFFICE-SECURITY/HOUSEKEEPING
FEE
BUILDING PERMIT FEE ($2000+)
BUILDING PLAN CHECK FEE (BLDG)
Owner:
R P I CARLSBAD LP
1114 Avenue Of The Americas, Floor 45
New York, NY 10036-7700
214-660-5232 x215232
ELECTRICAL BLDG COMMERCIAL NEW/ADDITION/REMODEL
MECHANICAL BLDG COMMERCIAL NEW/ADDITION/REMODEL
SB1473 GREEN BUILDING STATE STANDARDS FEE
STRONG MOTION-COMMERCIAL
Total Fees: $ 1,117.59 Total Payments To Date : $ 1,117.59
Ccityof
Carlsbad
Permit No: CBC2017-0507
Status:
Applied:
Issued:
Permit
Fina led:
Inspector:
Final
Inspection:
Closed -Expired
09/25/2017
10/23/2017
MColl
AMOUNT
$578.77
$405.14
$60.00
$45.00
$4.00
$24.68
Balance Due: $0.00
Please take NOTICE that approval of your project includes the "Imposition" of fees, dedications, reservations, or other exactions hereafter
collectively referred to as "fees/exaction." You have 90 days from the date this permit was issued to protest imposition of these
fees/exactions. If you protest them, you must follow the protest procedures set forth in Government Code Section .66020(a), and file the
protest and any other required information with the City Manager for processing in accordance with Carlsbad Municipal Code Section
3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack, review, set aside, void, or annul their
imposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified fees /exactions DOES NOT APPLY to water and sewer connection
fees and capacity changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this
project. NOR DOES IT APPLY to any fees/exactions of which you have previously been given a NOTICE similar to this, or as to which the
statute of limitation has previously otherwise expired.
Building Division
1635 Faraday Avenue, Carlsbad CA 92008-7314 I 760-602-2700 I 760-602-8560 f I www.carlsbadca.gov
THE FOLLOWING APPROVALS REQUIRED PRIOR TO PERMIT ISSUANCE: □PLANNING □ENGINEERING □BUILDING □FIRE □HEALTH 0HAZMATIAPCD
C_cityof
Carlsbad
Building Permit Application
1635 Faraday Ave., Carlsbad, CA 92008
Ph: 760-602-2719 Fax: 760-602-8558
email: building@carlsbadca.gov
www.carlsbadca.gov
Plan Check NoCl ao11 -nt;,/J1
Est. Value l14-..
Plan Ck. Deposit
Date 4 /,3 Jli.. // l lswPPP
JOB ADDRESS 2525 El Camino Real, Carlsbad, CA 92008 SUITE#/SPACEI/UNIT# 216 I APN
CT/PROJECT# I LOT# I PHASE# l # OF UNITS I# BEDROOMS # BATHROOMS !TENANT BUSINESS NAME
RPI Carlsbad, LP
l CONSTR. TYPE I occ. GROUP
DESCRIPTION OF WORK: Include Square Feet of Affected Area(s)
1,895 SF Tenant improvement including new walls, T-bar ceiling and restroom. Multi purpose offices to include restroom,
conference rooms and breakroom.
EXISTING USE
Vacant Suite !
PROPOSED USE
Office space
I GARAGE {SF) PATIOS (SF) 1DECKS (SF) FIREPLACE
YES[), I
AIR CONDITIONING IFIRE SPRINKLERS
N<0 YES[!'.]No □ YES(!'.]No□
APPLICANT NAME
Primary Contact
ADDRESS
Kyle Goda!
2525 El Camino Real
CITY STATE ZIP
Carlsbad CA
PHONE
619.370.6159 IFAX
EMAIL kyle.godat@rouseproperties.com
DESIGN PROFESSIONAL TSArchitects, Inc.
ADDRESS
PROPERTY OWNER NAME RPICarlsbad,LP
ADDRESS 2525 El Camino Real
CITY STATE ZIP
92008 Carlsbad CA
PHONE
EMAIL
CONTR~~~BUS.NAME •-e;-0~
ADDRESS_ _
2050 S._13_undy Drive._Suite 2 __ 2_5 ___ ---J-_ ZC"jS 5'17'\Jl, _ sr,e.1,,'tl"f0~---
z1P CITY STATE ZIP STATE
Los An!leles
p=H=oN=,-----310.895.7923-~_--_J~'-"'_
EMAIL
Alan Tomasi
CA 90025 ~s_,,:,m-.:, e.,,,_ Cjzoo B
---PHONE l'_A_x ____ --_____ _ --------f--------'---7.;cJ. 434· 4~'1£,
EMAIL
Sc.clc:c,rn €'.o.o /. er-, I STATE UC.#
92008
--------
{Sec. 7031.5 Business and Professions Code: Any City or County which requires a permit to construct, alter, improve, demolish or repair any structure, prior to its issuance, also requires,he applicant for such permit to file a si~ned statement that he is licensed pursuant to the provisions of the Contractor's License Law [Chapter 9, commending with Section 7000 of Division 3 of the Business and Professions Code} or that he is exempt therefrom, and the basis for the alleged exemption. Any violation of Section 7031.5 by any applicant for a permit subjects the applicant to a
civil penalty of not more than five hundred dollars ($500}).
WORKERS' COMPENSATION
Workers' Compensation Declaration: I hereby affirm under penalty of perjury one of the following declarations:
□ I have and wlll maintain a certificate of consent to self-insure for workers' compensation as provided by Section 3700 of the Labor Code, for the performance of the work for which this permit is issued
J2SJ.. I have and will maintain workers' compensation, as required by Section 3700 of the Labor Code, for the performance of the work for which this permit is issued. My workers' compensation insurance carrier and policy
number are: Insurance Co. STA:nf tFcJ,..I () Policy No. Cf OG. / 5" 3 q Expiration Date V ' l S' l 0
This section need not be completed if the permit is for one hundred dollars ($100) or less. 0 Certificate of Exemption: I certify that in the performance of the work for which this permit is issued, I shall not employ any person in any manner so as to become subject to the Workers' Compensation laws of
California. WARNING: Fallure to secure workers' com lion coverage is unlawf and shall subject an employer to criminal penalties and civil fines up to one hundred thousand dollars (&100,000), in •....-~, • ..,.tor in Section 3706 of
I hereby affirm thal I am exempt from Contractor's License Law for the following reason:
□
□
□
I, as owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not intended or offered for sale (Sec. 7044, Business and Professions Code: The Contractor's
License Law does not apply to an owner of property who builds or improves thereon, and who does such work himself or through his own employees, provided that such improvements are not intended or offered for
sale. If, however, the building or improvement is sold within one year of completion, the owner-builder will have the burden of proving that he did not build or improve for the purpose of sale).
I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 704-4, Business and Professions Code: The Contracto(s License Law does not apply to an owner of
property who builds or improves thereon, and contracts for such projects with contraclor(s) licensed pursuant to the Contractor's License Law).
I am exempt under Section ____ B,usiness and Professions Code for this reason:
1. I personally plan to provide the major labor and materials for construction of the proposed property improvement. OYes 0No
2. I (have I have not) signed an application for a building permit for the proposed work.
3. I have contracted with the following person (firm) to provide the proposed construction (include name address/ phone I contractors' license number):
4. I plan to provide portions of the work, butt have hired the following person to coordinate, supervise and provide the major work (include name I address I phone I contractors' license number):
5. I will provide some of the work, but I have contracted (hired) the following persons to provide the work indicated (include name I address I phone I type of work):
25 PROPERTY OWNER SIGNATURE GENT DATE 9-
COMPLETE THIS SECTION FOR NON-RESIDENTIAL BUILDING PERMITS ONLY
Is the applicant or future building occupant required to submit a business plan, acutely hazardous materials registration form or risk management and prevention program under Sections 25505, 25533 or 25534 of lhe
Presley-T annet Hazardous Substance Account Act? Yes No
ls the applicant or future building occupant required tD obtain a permit from the air pollution control district or air auality management district? Yes No
Is the facility to be constructed within 1,000 feet of the outer boundary of a school site? Yes No
IF ANY OF THE ANSWERS ARE YES, A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR IS MEETING THE REQUIREMENTS OF THE OFFICE OF
EMERGENCY SERVICES AND THE AIR POLLUTION CONTROl DISTRICT.
CONSTRUCTION LENDING AGENCY
I hereby affirm that there is a construction lending agency for the performance of the work this permit Is issued (Sec 3097 (1) CIvII Code)
Lender's Name Lender's Address
APPLICANT CERTIFICATION
I certllythat I have read the appllcatlon and state lhatthe abo¥9 Information Is conectand that the infonnetlon on the plans Is accurate. I a,ree to complywllh all City ordinances and state laws relatlngto buldlng construction.
I hereby aulhcrim represenlalive ollt-e Cityof Carisbad t> enlor upoo ire above montkx1ed property ilr nspedion pu,poses. I ALSO AGREE TO SAVE, INDEMNIFY AND KEEP HARMLESS THE CnY Of CARLSBAD
AGAINST ALL LLI\BILITIES, JOOGMENTS, COSTS AND EXPENSES WHICH MAY IN ANYWAY ACCRUE AGAINST SAID CnY IN CONSEQUENCE Of THE GRANTING Of THIS PERMIT.
OSHA: NI OSHA permit is required br excavations <N8r 5'0' deep and demolDJl'l or construction of strucues over 3 stories fl heght.
EXPIRATION: Eve!)' permit osued by Ire Bliklfll Official urder Ire prov,sions of lhis Code shaH expn, by .,.._ and berome rMJI and void I ire t,,;~mg ex worl< aulhcxized by such permit o ool cornner<ed v.ihn
180 days from Ire date of such ~cxl~ orworl< aulhcxized ~permit-• suspended or abandoned at anytime allortt-e worl< • commenced for a period of 180 days (Sed<n 106.4.4 Uniilrm Buildmg Coda).
AfAPPLICANT'SSIGNA~ ~ DATE ~ •Z 'r · / 7
• STOP: THIS SECTION NOT REQUIRED FOR BUILDING PERMIT ISSUANCE.
Complete the following ONLY if a Certificate of Occupancy will be requested at final inspection.
Fax (760) 602.a560, Email building@carlsbadca.gov or Mall the completed form to City of Cansbad, Building Division 1635 Faraday Avenue, cansbad, Cal~om~ 92008.
CONTACT NAME
ADDRESS
CnY STA
PHONE
EMAIL
DEUVERY OPTIONS
PICKUP:
MAIL TO:
CONTACT (Listed above)
CONTRACTOR (On Pg. 1)
CONTACT (Listed above)
CONTRACTOR (On Pg. 1)
ZIP
FAX
OCCUPANT (Listed above)
OCCUPANT (Listed above)
MAIL/FAXTOOTHER: _______________ _
A$ APPLICANT'S SIGNATURE
CO#: (Office UH Only)
OCCUPANT NAME
BUILDING ADDRESS
CITY STATE
Carlsbad CA
OCCUPANT'S BUS. LIC. No.
ASSOCIATED CB#------------
NO CHANGE IN USE/ NO CONSTRUCTION
CHANGE OF USE/ NO CONSTRUCTION
DATE
ZIP
" ~ ~ ~ • ~,,-. • -•
· PERMIT INSPECTION .TORY REPORT (CBC2017-0507)
Permit Type: BLDG-Commercial Application Date: 09/25/2017 Owner: R P I CARLSBAD LP
Work Class: Tenant Improvement Issue Date· 10/23/2017 Subdivision: CARLSBAD TCT#76-18
Status: Closed -Expired Expiration Date: 07/11/2018 Address: 2525 El Camino Real , 100
IVR Number: 6515 Carlsbad, CA 92008
Scheduled Actual Inspection Type Inspection No. Inspection Status Primary Inspector Reinspection Complete Date Start Date ·------.. --·--"·
01/05/2018 01/05/2018 BLDG-Final 045164-2018 Failed Michael Collins Reinspection Complete
Inspection
Checklist Item COMMENTS Passed
BLDG-Building Deficiency 01/05/2018, see card for corrections. No
BLDG-Plumbing Final See card No
BLDG-Mechanical Final No
BLDG-Electrical Final No
BLDG-Building Deficiency See card No
01/10/2018 01/10/2018 BLDG-Final 045543-2018 Partia I Pass Michael Collins Reinspection Incomplete
Inspection
Checklist Item COMMENTS Passed
BLDG-Building Deficiency 01/05/2018, see card for corrections. No
BLDG-Building Deficiency TCO only, see card for dressing room Yes
pickup.
BLDG-Plumbing Final See card No
BLDG-Mechanical Final No
BLDG-Electrical Final No
BLDG-Building Deficiency See card No
01/12/2018 01/12/2018 BLDG-Fire Final 044989-2018 Partial Pass Cindy Wong Reinspection Incomplete
Checklist Item COMMENTS Passed
FIRE-Building Final FLS ok -waiting to tie into mall FA system Yes
Checklist Item COMMENTS Passed
FIRE-Building Final All FLS ok. Waiting for tie in to FA mall Yes
system.
February 03, 2020 Page 2 of 2
~: _ . PERMITHIISPECTION ~T0ij¥R~PORT (CBC2017..0507)
Permit Type: BLDG-Commercial Application Date: 09/25/2017 Owner: R P I CARLSBAD LP
Work Class: Tenant Improvement Issue Date: 10123/2017 Subdivision: CARLSBAD TCT#76-18
Status. Closed -Expired Expiration Date: 07/1112018 Address: 2525 El Camino Real , 100
IVR Number: 6515 Carlsbad, CA 92008
Scheduled Actual Inspection Type Inspection No. Inspection Status Primary Inspector Reinspection Complete Date Start Date
10/25/2017 10/25/2017 BLDG-21 038501-2017 Passed Michael Collins Complete
Underground/Under!
loor Plumbing
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Waste to POC Yes
10/30/2017 10/30/2017 BLDG-84 Rough 039011-2017 Failed Michael Collins Reinspection Complete
Combo(14,24,34,44)
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Not ready No
BLDG-14 No
Frame-Steel-Bolting-Welding
(Decks)
BLDG-24 Rough-Topout No
BLDG-34 Rough Electrical No
BLDG-44 No
Rough-Ducts-Dampers
10/31/2017 10/31/2017 BLDG-84 Rough 039087-2017 Passed Michael Collins Complete
Combo(14,24,34,44)
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Wall frame only Yes
BLDG-14 Yes
Frame-Steel-Bolting-Welding
(Decks)
BLDG-24 Rough-Topout Yes
BLDG-34 Rough Electrical Yes
11/02/2017 11/02/2017 BLDG-17 Interior 039423-2017 Passed Michael Collins Complete
Lath/Drywall
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Walls only Yes
11/15/2017 11/15/2017 BLDG-85 T-Bar, 040536-2017 Passed Michael Collins Complete
Ceiling Grids,
Overhead
Checklist Item COMMENTS Passed
BLDG-Building Deficiency See card. Yes
BLDG-14 Yes
Frame-Steel-Bolting-Welding
(Decks)
BLDG-24 Rough-Topout Yes
BLDG-34 Rough Electrical Yes
BLDG-44 Yes
Rough-Ducts-Dampers
11/28/2017 11/17/2017 BLDG-Fire Final 040976-2017 Cancelled Cindy Wong Reinspection Complete
Checkiist Item COMMENTS Passed
FIRE-Building Final No
February 03, 2020 Page 1 of 2
March 14, 2018
Owner(renant
2525 EL CAMINO REAL, Suite 100
Carlsbad CA 92008-1208
{city of
Carlsbad
PERMIT NUMBER: CBC2017-0507
RE: BUILDING PERMIT EXPIRATION ISSUE DATE: 10/23/2017
PERMIT TYPE: BLDG-Commercial, Tenant Improvement ADDRESS: 2525 EL CAMINO REAL, Suite 100
Our records indicate that your building permit will expire by limitation of time on 05/16/2018.
18.04.030 Section 105.5 amended -Expiration:
Every permit issued by the Building Official under the provisions of this code shall expire by limitation and become
null and void if the building or work authorized by such permit is not commenced within 180 calendar days from the
date of such permit, or if the building or work authorized by such permit is stopped at any time after the work is
commenced for a period of 180 calendar days, or if the building or work authorized by such permit exceeds three
calendar years from the issuance date of the permit. Work shall be presumed to have commenced if the permittee
has obtained a required inspection approval of work authorized by the permit by the Building Official within 180
calendar days of the date of permit issuance. Work shall be presumed to be stopped if the permittee has not
obtained a required inspection approval of work by the Building Official within each 180 day period upon the initial
commencement of work authorized by such permit.
Before such work can be recommenced, a new permit shall be obtained to do so, and the fee therefore shall be one
half the amount required for a new permit for such work, and provided that no changes have been made or will be
made in the original plans and specifications for such work, and provided further that such suspension or
abandonment has not exceeded one year. In order to renew action on a permit after expiration, the permittee shall
pay a new permit fee.
Any permittee holding an unexpired permit may apply for an extension oftime within which work may commence
under that permit when the permittee is unable to commence work within the time period required by this section
for good and satisfactory reasons.
Please check below indicating your intentions and return this letter to us.
D Project abandoned. A new permit will be obtained prior to commencing work.
D Permit 180 day extension request, with written explanation including phone number and email address.
Request will not be considered without explanation
D Renewal permit requested.
If the project has been completed and only a final inspection is needed, please call the inspection request line at
(760) 602-2725.
If you have any questions, please contact the Building Inspection Division at 760-602-2700.
Community & Economic Development
Building Division I 1635 Faraday Avenue, Carlsbad, CA 92008-7314 I 760-602-2700 I 760-602-8560 f I www.carlsbadca.gov
DATE: 10/20/2017
JURISDICTION: Carlsbad
PLAN CHECK#.: CBC2017-0507
✓• EsG1I
A SAFEbuslt Company
SET: II
PROJECT ADDRESS: 2525 El Camino Real
□ APPLICANT J' JURIS.
PROJECT NAME: Carlsbad Center Mall Office Tenant Improvement
~ The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's
codes when minor deficiencies identified below are resolved and checked by building
department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
D The check list transmitted herewith is for your information. The plans are being held at EsGil
until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
D The applicant's copy of the check list has been sent to:
~ EsGil staff did not advise the applicant that the plan check has been completed.
D EsGil staff did advise the applicant that the plan check has been completed.
Person contacted: fj Telephone#:
Date contacted: (by:--Wi Email:
Mail Telephone Fax In Person
□ REMARKS:
By: Jason Pasiut Enclosures:
EsGil
□ GA □ EJ □ MB □ PC 10/16/2017
9320 Chesapeake Drive, Suite 208 ♦ San Diego, California 92123 ♦ (858) 560-1468 ♦ Fax (858) 560-1576
DATE: 10/05/2017
JURISDICTION: Carlsbad
PLAN CHECK#.: CBC2017-0507
✓• EsG1I
A SAFEbulit C01np:iny
SET: I
PROJECT ADDRESS: 2525 El Camino Real
CJ_j)PPLICANT
_)-=f JURIS.
PROJECT NAME: Carlsbad Center Mall Office Tenant Improvement
D The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's
codes when minor deficiencies identified below are resolved and checked by building
department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
~ The check list transmitted herewith is for your information. The plans are being held at EsGil
until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
~ The applicant's copy of the check list has been sent to:
Kyle Godat
D EsGil staff did not advise the applicant that the plan check has been completed.
~ EsGil staff did advise the applicant that the plan check has been completed.
Person contacted: Kyle Godat Telephone#: 619-370-6159
Date contacted\ Dil?' (by:jt} Email: kyle.godat@rouseproperties.com
"E5,,ail ~-~ leRhO™i\. Fax In Person v-m 0 REMAR : •
By: Jason Pasiut
EsGil
0 GA O EJ O MB O PC
Enclosures:
9/28/2017
9320 Chesapeake Drive, Suite 208 ♦ San Diego, California 92123 ♦ (858) 560-1468 ♦ Fax (858) 560-1576
C~rlsbad CBC2017-0507
10/05/2017
PLAN REVIEW CORRECTION LIST
TENANT IMPROVEMENTS
PLAN CHECK#.: CBC2017-0507
OCCUPANCY: B
TYPE OF CONSTRUCTION: V-B
ALLOWABLE FLOOR AREA: within
SPRINKLERS?: YES
REMARKS:
DATE PLANS RECEIVED BY
JURISDICTION: 9/25/2017
DATE INITIAL PLAN REVIEW
COMPLETED: 10/05/2017
FOREWORD (PLEASE READ):
JURISDICTION: Carlsbad
USE: Office
ACTUAL AREA: 1,895s.f.
STORIES: 1
HEIGHT: unchanged
OCCUPANT LOAD: 38
DATE PLANS RECEIVED BY
ESGIL CORPORATION: 9/28/2017
PLAN REVIEWER: Jason Pasiut
This plan review is limited to the technical requirements contained in the California version of
the International Building Code, Uniform Plumbing Code, Uniform Mechanical Code, National
Electrical Code and state laws regulating energy conservation, noise attenuation and access for
the disabled. This plan review is based on regulations enforced by the Building Department.
You may have other corrections based on laws and ordinances enforced by the Planning
Department, Engineering Department, Fire Department or other departments. Clearance from
those departments may be required prior to the issuance of a building permit.
Code sections cited are based on the 2016 CBC, which adopts the 2015 IBC.
The following items listed need clarification, modification or change. All items must be satisfied
before the plans will be in conformance with the cited codes and regulations. Per Sec. 105.4 of
the 2015 International Building Code, the approval of the plans does not permit the violation of
any state, county or city law.
To speed up the recheck process, please note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet number, specification section, etc.
Be sure to enclose the marked up list when you submit the revised plans.
Carlsbad CBC2017-0507
10/05/2017
Please make all corrections, as requested in the correction list. Submit FOUR new
complete sets of plans for commercial/industrial projects (THREE sets of plans for
residential projects). For expeditious processing, corrected sets can be submitted in one
of two ways:
1. Deliver all corrected sets of plans and calculations/reports directly to the City of
Carlsbad Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760) 602-
2700. The City will route the plans to EsGil Corporation and the Carlsbad Planning,
Engineering and Fire Departments.
2. Bring TWO corrected set of plans and calculations/reports to EsGil Corporation, 9320
Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-1468. Deliver all
remaining sets of plans and calculations/reports directly to the City of Carlsbad Building
Department for routing to their Planning, Engineering and Fire Departments.
NOTE: Plans that are submitted directly to EsGil Corporation only will not be reviewed by
the City Planning, Engineering and Fire Departments until review by EsGil Corporation is
complete.
• PLANS
1. Each sheet of the plans must be signed by the person responsible for their
preparation, even if there are no structural changes. California State Law.
2. Please update the occupant load as follows:
a) Lobby -8 occupants
b) Office 2 -3 occupants
c) Equipment Storage -1 occupant
d) Office 1 -1 occupant
e) Lost and found -1 occupant
f) Conference room -12 occupants
g) Break Room -9 occupants
h) Dressing room -1 occupant
i) Office 3 -1 occupant
j) Large storage room -1 occupant TOTAL OCCUPANCY: 38
3. Roof mounted equipment must be screened and roof penetrations should be
minimized (City Policy 80-6).
4. Please update the following sheets/notes:
a) Sheet A-0.02:
Carlsbad CBC2017-0507
10/05/2017
1. entrance note 6 to 34" to 44".
b) Building Department notes:
1. 2 and 21 are unclear. Are separate permits being pulled?
2. 4 per 1010.1.9.
3. 7 per 1008.
4. 8 per 1013.
5. 9 per 2016 code.
6. 13 is unclear.
7. 15 per energy standard 120.4
c) Accessibility notes:
d)
e)
1. 6 please review section 11 B-308 for obstructed and un-obstructed
reach ranges.
Sheet A-2.01 notes:
1. 20 per 1010.1.1.
2. 21per1013.
3. 22 per 2016 code.
Sheet A-2.02 notes:
1. 12and13per1013.
• ACCESSIBILE DRESSING ROOM
4. The bench in the accessible dressing room shall be 17" minimum to 19" maximum
per 11 B-903.5.
5. Proposed coat hooks shall be located within the reach ranges on 11 B-308.
6. Proposed shelves shall be 40" minimum to 48" maximum above the finish floor.
11 B-308.5.
7. Mirrors (54" x 18") shall be installed 20" maximum above the finish floor and shall
provide a view to a person on the bench as well as to a person in a standing
position. 11 B-803.6.
Carlsbad CBC2017-0507
10/05/2017
• ACCESSIBLE SINKS
8. Per Section 11 B-804, non-commercial kitchen sinks (such as at employee break
rooms, etc.) shall provide the following:
a) A clear floor space at least 30"x 48" shall be provided for forward
approach and shall be on an accessible route. The clear space shall
extend a maximum of 19" underneath the sink. Section 11 B-606.2.
b) The accessible sink shall be mounted with the counter or rim no higher
than 34" above finish floor. Knee clearance that is at least 27" high, 30"
side and 19" underneath the sink shall be provided. Hot water and drain
shall be insulated or otherwise configured so as to protect against contact.
There shall be no sharp or abrasive surfaces under the sink. Section 11 B-
606.
c) Faucet controls and operating mechanisms shall be operable with one
hand and shall not require tight grasping, pinching or twisting of the wrist.
Lever operated, push-type and electronically controlled mechanisms are
acceptable. Self-closing valves are allowed if the faucet remains open for
at least 10 seconds. Section 11 B-606.4.
• ACCESSIBLE PATH OF TRAVEL
9. Please show on the plans the location of all proposed egress, exit, and accessible
route signs.
• EXITS
10. Please update the door schedule to show the fire rating requirements of door 112A
as well as the two doors leading to 112A that appear to be on fire rated walls. Such
as you did with existing door 103.
• WALL FRAMING
11. Provide a section view of all new interior partitions. Show:
a) Type, size and spacing of fasteners used at top-of-wall connections for
partitions 1,2, and 3.
b) Specify manufacturer and approval number for framing members or
indicate "to be ICC approved".
c) Provide Special Inspection schedule on the cover sheet indicating which
elements of the project will require Special Inspection. Fill out and turn
into the Carlsbad Building Division the Special Inspection Agreement
form.
• END OF REVIEW
. Carlsbad CBC2017-0507
10/05/2017
[DO NOT PAY -THIS IS NOT AN INVOICE]
VALUATION AND PLAN CHECK FEE
JURISDICTION: Carlsbad
PREPARED BY: Jason Pasiut
BUILDING ADDRESS: 2525 El Camino Real
BUILDING OCCUPANCY: B
BUILDING AREA Valuation
PORTION ( Sq. Ft.) Multiplier
1895 46.51
Air Conditioning
Fire Sprinklers
TOTAL VALUE
Jurisdiction Code cb By Ordinance
Bldg. Permit Fee by Ordinance ____ -~
Type of Review:
D Repetitive Fee
~] Repeats
Comments: .
Complete Review
D Other
D Hourly
EsGil Fee
PLAN CHECK#.: CBC2017-0507
DATE: 10/05/2017
Reg. VALUE ($)
Mod.
88,136
88,136
$573.87!
$373.021
D Structural Only
$327.11 I
Sheet 1 of 1
macvalue.doc +
Carlsbad CBC2017-0507
10/05/2017
To speed up the review process, please note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet, note or detail number, calculation
page, etc.
Please indicate here if any changes have been made to the plans that are not a result
of corrections from this list. If there are other changes, please briefly describe them
and where they are located in the plans.
Have changes been made to the plans not resulting from this correction list?
Please indicate: □ Yes □ No
The jurisdiction has contracted with Esgil Corporation located at 9320 Chesapeake
Drive, Suite 208, San Diego, California 92123; telephone number of 858/560-1468, to
perform the plan review for your project. If you have any questions regarding these plan
review items, please contact Jason Pasiut at Esgil Corporation. Thank you.
SAN DIEGO REGIONAL OFFICE USE ONLY
HAZARDOUS MATERIALS RECORD ID#
PLAN CHECK# ,.._
QUESTIONNAIRE BP DATE
Business Name Business Contact Telephone# 2a zo e:i,-i a-ff ~C,,,5
Project Address City State Zip Code APN#
Z5Z /£L ~ln 0 Kem.. a.z /C, C,ArLl.,St!>AO <Vt-. c;'z_cJC)f,
Mailing Address City State Zip Code Plan File#
Project Contact Applicant E-mail Telephone#
The following questions represent the facility's activities, NOT the specific project description.
PART I: FIRE DEPARTMENT -HAZARDOUS MATERIALS DIVISION: OCCUPANCY CLASSIFICATION: (not required for projects within the City of San
Diego): Indicate by circling the item, whether your business will use, process, or store any of the following hazardous materials. If any of the items are circled,
applicant must contact the Fire Protection Agency with jurisdiction prior to plan submittal.
Occupancy Rating: Facility's Square Footage (including proposed project):
1. Explosive or Blasting Agents 5. Organic Peroxides 9. Water Reactives 13. Corrosives
2. Compressed Gases 6. Oxidizers 10. Cryogenics 14. Other Health Hazards
3. Flammable/Combustible Liquids 7. Pyrophorics 11. Highly Toxic or Toxic Materials 15. None of These.
4. Flammable Solids 8. Unstable Reactives 12. Radioactives
PART 11: SAN DIEGO COUNTY DEPARTMENT OF ENVIRONMENTAL HEALTH -HAZARDOUS MATERIALS DIVISION (HMD): If the answer to any of the
questions is yes, applicant must contact the County of San Diego Hazardous Materials Division, 5500 Overland Avenue, Suite 110, San Diego, CA 92123.
Call (858) 505-6700 prior to the issuance of a building permit.
0 CalARP Exempt
I FEES ARE REQUIRED Project Completion Date: Expected Date of Occupancy:
1.
2.
3.
4.
5.
6.
7.
8.
YES NO
§ ffi
D D D D
D ~
(for new construction or remodeling projects)
Is your business listed on the reverse side of this form? (check all that apply).
Will your business dispose of Hazardous Substances or Medical Waste in any amount?
Will your business store or handle Hazardous Substances in quantities greater than or equal to 55 gallons, 500
pounds and/or 200 cubic feet?
Will your business store or handle carcinogens/reproductive toxins in any quantity?
Will your business use an existing or install an underground storage tank?
Will your business store or handle Regulated Substances (CalARP)?
Will your business use or install a Hazardous Waste Tank System (Title 22, Article 10)?
Will your business store petroleum in tanks or containers at your facility with a total facility storage capacity equal to
or realer than 1,320 allons? California's Above round Petroleum Stora e Act .
Date Initials
0 CalARP Required
I
Date Initials
0 CalARP Complete
I
Date Initials
PART Ill: SAN DIEGO COUNTY AIR POLLUTION CONTROL DISTRICT (APCD): Any YES* answer requires a stamp from APCD 10124 Old Grove Road, San
Diego, CA 92131 apcdcomp@sdcounty.ca.gov (858) 586-2650). [*No stamp required if Q1 Yes and 03 Yes and Q4-Q6 No). The following questions are intended
to identify the majority of air pollution issues at the planning stage. Projects may require additional measures not identified by these questions. For comprehensive
requirements contact APCD. Residences are typically exempt, except -those with more than one building• on the property; single buildings with more than four
dwelling units; townhomes: condos: mixed-commercial use; deliberate burns; residences forming part of a larger project. (•Excludes garages & small outbuildings.]
1.
2.
3.
4.
5.
6.
YES NO
B ffi D D
D
D
D
l1l
[[I
QJ
Will the project disturb 160 square feet or more of existing building materials?
Will any load supporting structural members be removed? Notification may be required 10 working days prior to commencing demolition.
(ANSWER ONLY IF QUESTION 1 or 2 IS YES) Has an asbestos survey been performed by a Certified Asbestos Consultant or Site Surveillance
Technician?
(ANSWER ONLY IF QUESTION 3 IS YES) Based on the survey results, will the project disturb any asbestos containing material? Notification
may be required 10 working days prior to commencing asbestos removal.
Will the project or associated construction equipment emit air contaminants? See the reverse side of this form or APCD factsheet
(www.sdapcd.org/infolfacts/pennits.pdf) for typical equipment requiring an APCD permit.
(ANSWER ONLY IF QUESTION 5 IS YES) Will the project or associated construction equipment be located within 1,000 feet of a school
bounda
Briefly describe business activities:
'-A-<~1
I declare under penalty of perjury that to the best of my knowledg
'T{../-oi,,M-5 S'?t/&pt,--0~
Name of Owner or Authorized Agent
to I 'Z ~ / I 7
Date
FOR OFFICAL USE ONLY: FIRE DEPARTMENT OCCUPANCY CLASSIFICATION:. ________________________________ _
BY· DATE· I
EXEMPT OR NO FURTHER INFORMATION REQUIRED RELEASED FOR BUILDING PERMIT BUT NOT FOR OCCUPANCY RELEASED FOR OCCUPANCY
COUNTY-HMO' APCD COUNTY-HMO APCO COUNTY-HMO APCO
.. *A stamp in this box only exempts businesses from completing or updating a Hazardous Materials Business Plan. Other permitting requirements may slill apply.
HM-9171 (08115) County of San Diego -DEH -Hazardous Materials Division