HomeMy WebLinkAbout2525 El Camino Real; 134; CBC2019-0236; PermitCcityof
Carlsbad
Print Date: 10/09/2019
Job Address:
Permit Type:
Parcel No:
Valuation:
Occupancy Group:
# Dwelling Units:
Bedrooms:
Project Title:
2525 El Camino Real, 134
BLDG-Commercial
1563022700
$42,649.67
Commercial Permit
Work Class: Tenant Improvement
Lot#:
Reference #:
Construction Type:
Bathrooms:
Orig. Plan Check#:
Plan Check#:
Description: BROWS N MORE: 917 SFT.I. (RETAIL TO RETAIL)
Applicant:
DEEPAK VORA
18218 Sun Maiden Ct
San Diego, CA 92127-3103
BSB-592-9205
BUILDING PERMIT FEE ($2000+)
BUILDING PLAN CHECK FEE (BLDG)
Owner:
R PI CARLSBAD LP
1114 Avenue Of The Americas, Floor 45
New York, NY 10036-7700
214-660-5232 x215232
ELECTRICAL BLDG COMMERCIAL NEW/ADDITION/REMODEL
MECHANICAL BLDG COMMERCIAL NEW/ADDITION/REMODEL
S61473 GREEN BUILDING STATE STANDARDS FEE
STRONG MOTION-COMMERCIAL
Total Fees: $715.98 Total Payments To Date: $715.98
Status:
Applied:
Issued:
Permit
Finaled:
Inspector:
Final
Inspection:
Balance Due:
Please take NOTICE that approval of your project includes the "Imposition" of fees, dedications, reservations, or other exactions hereafter
collectively referred to as "fees/exaction." You have 90 days from the date this permit was issued to protest imposition of these
fees/exactions. If you protest them, you must follow the protest procedures set forth in Government Code Section 66020(a), and file the
protest and any other required information with the City Manager for processing in accordance with Carlsbad Municipal Code Section
3.32.030, Failure to timely follow that procedure will bar any subsequent legal action to attack, review, set aside, void, or annul their
imposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection
fees and capacity changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this
project NOR DOES IT APPLY to any fees/exactions of which you have previously been given a NOTICE similar to this, or as to which the
statute of limitation has previously otherwise expired.
Permit No: CBC2019-0236
Closed -Finaled
05/16/2019
06/27/2019
MColl
10/9/2019 ll:22:37AM
$0.00
$361.20
$252.84
$43.00
$45.00
$2.00
$11.94
1635 Faraday Avenue, Carlsbad, CA 92008-7314 I 760-602·2700 I 760-602-8560 f I www.carlsbadca.gov
( City of
Carlsbad
COMMERCl4L
BUILDING PERMIT
APPLICATl9N
B-2
P I a n C heck C.Wola [ql.. {);(:2 %
Est. Value rtJ'-/Q, (st.J9, {o 7'.
PC Deposit ---------
Date -~£L......,-,µ/ &~..,._-__._J_,<j_
S-oJS C/~H1t) ~ :
Job Address TH€ <-itt4 pf::'/;"S "9r!'.'.R8/ 658 osui~e: 1.:34 APN: __________ _
TenantName: S/24 1,f/,S N MC>l<E"' CT/P~oject#: _________ Lot#: ___ _
Occupancy: !Y:'] Construction Type: 7TT-B Fire Sprinklers:@/ no Air Conditioning: €j) no
BRIEF DESCRIPTION OF WORK: 1)/:Netvr Jme,u(l!f"P'.§"tJCS t.vl"T71 !JJl!;'Ld sTD/2.fipyz.,:,µr £
c ,:,:, 771"-lFT f ~ Ch AIV~ 1D s.4 t-0 R~ •
D Addition/New: ___________ New SF and Use, ___________ New SF and Use,
____ Deck SF, Patio Cover SF (not including flatwork)
g[ Tenant Improvement: 91 7 SF,
_____ SF,
Existing Use _ __.IV[~---Proposed Use _.,v1.,.__,._ ___ _
Existing Use Proposed Use ______ _
□ Pool/Spa: _____ SF Additional Gas or Electrical Features? ____________ _
D Solar: ___ KW, __ Modules, ___ Mounted, Tilt: Yes/ No, RMA: Yes/ No, Panel Upgrade: Yes/ No
D Plumbing/Mechanical/Electrical Only: _________________________ _
D Other: __________________________________ _
APPLICANT (PRIMARY)
Name: OEef'l/:lf, • 1Z -VAY!
Address: 18218 (VIV me,pr;f) c,r,
City: 51A N pJE(,o State: qi Zip: "i' :Z. /-z. 7
Phone: 8~B-S:12 -92.oC •
Email: dn1Jesthl@ a.ol. con-•
DESIGN PROFESSIONAL
Name: P6F./?A l'-• f.Z.. V~.tl
Address: 18 2, I & S L1A1 QllkP /ii1,I GT:,
City: 5i!&QI Ffa> State: {-I' Zip: '7 ZI 2 7
Phone: e, Cd-rq2-'f-µ,C"
Email: d.. Y 1!G/vifj£1@ a..o( .(m
Architect State License: C :Z. ::,. ::z. I G
PROPERTY OWNER
Name: Bl?-001/'2 FlELJ2 P/2-0pf=f12.T"IE;$
Address: 35P N-O@&ell/5,, 6u/Tlr .,3ao
City: q-,1cp.(cP State: fu,.,,t-'zip: b4l;C4--I.& 07
Phone: ___________________ _
Email: ____________________ _
CONTRACTOR BUSINESS
Name: ~::c---one, &,.+muqzo,1 t;DB/e:l.£)(t1Q{T //NC:,
Address: 'Z G,q5 '.>'lNft %
City: ~¢AO State: (!,A-Zip: CfZ=E;
Phone: ?Ge, 4'34· 43"1(,
Email: I0/0 @ "3<:--r·l=a::>t~. Ga:2
State License:6 I -4'14:'7$4 Bus. License: [24J f?. )2o451t:,
(Sec. 7031.5 Business and Professions Code: Any City or County which requires a permit to construct, alter, improve, demolish or repair any structure, prior to its
issuance, also requires the applicant for such permit to file a signed statement that he/she is licensed pursuant to the provisions of the Contractor's License law
{Chapter 9, commending with Section 7000 of Division 3 of the Business and Professions Code} or that he/she is exempt therefrom, and the basis for the alleged
exemption. Any violation of Section 7031.S by any applicant for a permit subjects the applicant to a civil penalty of not more than five hundred dollars {$500}).
1635 Faraday Ave Carlsbad, CA 92008
B-2
Ph: 760-602-2719 Fax: 760-602-8558
Page 1 of 2
Email: Building@carlsbadca.gov
Rev. 06/18
( OPTION A): WORKERS'COMPENSATION DECLARATION:
I hearby affirm under penalty of perjury one of the following declarations:
□ I have and will maintain a certificate of consent to self-insure for workers' compensation provided by Section 3700 of the labor Code, for the performance of the
work which this permit is issued.
~I have and will maintain worker's compensation, as required by Section 3700 of the Labor Code, for the performance of the work for which this permit is issued.
My workers' compensation insurance carrier and policy number are: Insurance Company Name: S:t?\ yG: rtJ r-lC> ( <l 'J,
Policy No. 7 f, 4:8 "3 ZZ • /Z.. Expiration Date: 3 • I • Z..c>
0 Certificate of Exemption: I certify that in the performance of the work for which this permit is issued, I shall not employ any person in any manner so as to be come
subject to the workers' compensation laws of California. WARNING: Failure to secure workers compensation coverage is unlawful, and shall subject an employer to
criminal penalties and civil fines up to $100,000.00, in dition the to the cost ompensation, damages as provided for in Section 3706 of the Labor Code,
interest and attorney's fees.
( OPTION B ): OWNER-BUILDER DECLARATION:
I hereby affirm that I am exempt from Contractor's License Law for the following reason:
□ I, as owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not intended or offered for sale (Sec.
7044, Business and Professions Code: The Contractor's license law does not apply to an owner of property who builds or improves thereon, and who does such work
himself or through his own employees, provided that such improvements are not intended or offered for sale. If, however, the building or improvement is sold within
one year of completion, the owner-builder will have the burden of proving that he did not build or improve for the purpose of sale).
□ I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions Code: The
Contractor's license law does not apply to an owner of property who builds or improves thereon, and contracts for such projects with contractor(s) licensed
pursuant to the Contractor's license law).
□ I am exempt under Section ________ ,Business and Professions Code for this reason:
1. I personally plan to provide the major labor and materials for construction of the proposed property improvement. □ Yes □ No
2. I (have/ have not) signed an application for a building permit for the proposed work.
3. l have contracted with the following person (firm) to provide the proposed construction (include name address/ phone/ contractors' license number):
4. I plan to provide portions of the work, but I have hired the following person to coordinate, supervise and provide the major work {include name/ address/ phone/
contractors' license number):
5. I will provide some of the work, but I have contracted (hired) the following persons to provide the work indicated (include name/ address/ phone/ type of work):
OWNER SIGNATURE: __________________ □AGENT DATE: _____ _
CONSTRUCTION LENDING AGENCY. IF ANY:
l hereby affirm that there is a construction lending agency for the performance of the work this permit is issued (Sec. 3097 (i) Civil Code).
lender's Name: _____________________ _ lender's Address: _____________________ _
ONLY COMPLETE THE FOLLOWING SECTION FOR NON-RESIDENTIAL BUILDING PERMITS ONLY:
ls the applicant or future building occupant required to submit a business plan, acutely hazardous materials registration form or risk management and prevention
program under Sections 25505, 25533 or 25534 of the Presley-Tanner Hazardous Substance Account Act? □ Yes !!bLo
Is the applicant or future building occupant required to obtain a permit from the air pollution control district or air quality management district? D Yes rg{_No
Is the facility to be constructed within 1,000 feet of the outer boundary of a school site? D Yes ~o
IF ANY OF THE ANSWERS ARE YES, A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR IS MEETING THE
REQUIREMENTS OF THE OFFICE OF EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT.
APPLICANT CERTIFICATION:
I certify that I have read the application and state that the above information is correct and that the information on the plans is accurate. I agree to comply with all
City ordinances and State laws relating to building construction.
thereby authorize representative of the City of Carlsbad to enter upon the above mentioned property for inspection purposes. I ALSO AGREE TO SAVE, INDEMNIFY AND KEEP
HARMLESS THE CITY OF CARLSBAD AGAINST ALL LIABILITIES, JUDGMENTS, COSTS AND EXPENSES WHICH MAY IN ANY WAY ACCRUE AGAINST SAID CITY IN CONSEQUENCE OF
THE GRANTING OF THIS PERMIT.OSHA: An OSHA permit is required for excavations over 5'0' deep and demolition or construction of structures over 3 stories in height.
EXPIRATION: Every permit issued by the Building Official under the provisions of this Code shall expire by limitation and become null and void if the building or work authorized
by such permit is not commenced within 180 da~ rom the date of such pe it or if the building or work authorized by such permit is suspended or abandoned at any time
after the work is commenced f .a period of ays (Section 106.4.4 1form Building Code).
1635 Faraday Ave Carlsbad, CA 92008
B-2
Ph: 760-602-2719 Fax: 760-602-8558
Page 2 of 2
Email: Building@carlsbadca.gov
Rev. 06/18
PERMIT INSPECTION HISTORY REPORT (CBC2019-0236)
Permit Type: BLDG-Commercial Application Date: 05/16/2019 Owner: R P I CARLSBAD LP
Work Class: Ten ant Improvement Issue Date: 06/27/2019 Subdivision: CARLSBAD TCT#76-18
Status: Closed -Finaled Expiration Date: 03/10/2020 Address: 2525 El Camino Real , 134
Ca~sbad, CA 92008-1207 IVR Number: 19145
Scheduled Actual
Date Start Date Inspection Type Inspection No. Inspection Status Primary Inspector Relnspection Complete
07/1612019 07/16/2019 BLDG-14 097636-2019 Passed Michael Collins Complete
Frame/SteelfBoltl ng/
Welding (Decks)
Checklist Item COMMENTS Passed
BLOG-Building Deficiency Entry soffit & wing walls only Yes
07/17/2019 07/17/2019 BLDG-17 Interior 097792-2019 Passed Michael Collin8 Complete
LathfOrywall
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Yes
08/19/2019 08/19/2019 BLDG-Final 101167-2019 Failed Michael Collins Relnspectlon Complete
Inspection
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Not ready No
0812112019 08/2112019 BLDG-Final 101475-2019 Failed Michael Collins Reinspectlon Complete
Inspection
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Not ready No
BLDG-Building Deficiency See card No
08/22/2019 08/22/2019 BLDG-Final 101686-2019 Partial Pass Michael Collins Reinspection Incomplete
Inspection
Checklist 1tem COMMENTS Passed
BLDG-Building Deficiency See card No
BLDG-Building Deficiency Not ready No
BLOG-Building Deficiency TCO granted, need new cash wrap counter Yes
installed
BLOG-Electrical Final Yes
09/12/2019 09/12/2019 BLDG-Fire Flnal 100814-2019 Passed Felix Salcedo Complete
Checklist Item COMMENTS Passed
FIRE-Building Final Yes
10l0912019 10/09/2019 BLDG-Final 107092-2019 PaHed Michael Collins Complete
Inspection
Checklist Item COMMENTS Passed
BLOG-Building Deficiency 10/09/19. Accessible base unit at cash Yes
wrap ok, EM/Exit signage ok
BLDG-Building Deficiency See card No
BLDG-Building Deficiency TCO granted, need new cash wrap counter Yes
installed
BLDG-Building Deficiency Not ready No
BLDG-Electrical Final Yes
BLDG-Electrical Final Yes
October 09, 2019 Page 1 of2
✓• EsG1I
A SAFEbuilt-Company
DATE: 6/19/2019
JURISDICTION: Carlsbad
DftPLICANT jA JURIS.
PLAN CHECK#.: CBC2019-0236 SET: II
PROJECT ADDRESS: 2525 El Camino Real #134
PROJECT NAME: Brows n More Tenant Improvement
□
□
□
□
□
~
□
The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
The plans transmitted herewith will substantially comply with the jurisdiction's
codes when minor deficiencies identified below are resolved and checked by building
department staff.
The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
The check list transmitted herewith is for your information. The plans are being held at EsGil
until corrected plans are submitted for recheck.
The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
The applicant's copy of the check list has been sent to:
EsGil staff did not advise the applicant that the plan check has been completed.
EsGil staff did advise the applic7,nt th t the plan check has been completed.
Person contacted: Telephone#:
Date contacted: (by: ) Email:
Mail Telephone Fax In Person
0 REMARKS:
By: Jason Pasiut
EsGil
6/11/2019
Enclosures:
9320 Chesapeake Drive, Suite 208 ♦ San Diego, California 92123 ♦ (858) 560-1468 ♦ Fax (858) 560-1576
DATE: 5/29/2019
JURISDICTION: Carlsbad
PLAN CHECK#.: CBC2019-0236
✓• EsG1I
A SAFEbuilt'Company
SET: I
PROJECT ADDRESS: 2525 El Camino Real #134
PROJECT NAME: Brows n More Tenant Improvement
□ APPLICANT
□ JURIS.
D The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's
codes when minor deficiencies identified below are resolved and checked by building
department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
~ The check list transmitted herewith is for your information. The plans are being held at EsGil
until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
~ The applicant's copy of the check list has been sent to:
Deepak Vora
D EsGil staff did not advise the applicant that the plan check has been completed.
~ EsGil staff did advise the applicant that the plan check has been completed.
Person contacted: Deepak Vora Telephone#: 858-592-9205
Date contacted: (by: ) Email: drvdesign@aol.com
Mail Telephone
0 REMARKS:
By: Jason Pasiut
EsGil
Fax In Person
Enclosures:
5/20/2019
9320 Chesapeake Drive, Suite 208 ♦ San Diego, California 92123 ♦ (858) 560-1468 ♦ Fax (858) 560-1576
Carlsbad CBC2019-0236
5/29/2019
PLAN REVIEW CORRECTION LIST
TENANT IMPROVEMENTS
PLAN CHECK#.: CBC2019-0236
OCCUPANCY: M
TYPE OF CONSTRUCTION: III-B
ALLOWABLE FLOOR AREA: complies
SPRINKLERS?: YES
REMARKS:
DATE PLANS RECEIVED BY
JURISDICTION: 5/16/2019
DATE INITIAL PLAN REVIEW
COMPLETED: 5/29/2019
FOREWORD (PLEASE READ):
JURISDICTION: Carlsbad
USE: Retail Sales / Service
ACTUAL AREA: 91 7 sf
STORIES: 2
HEIGHT: unchanged
OCCUPANT LOAD: 21
DATE PLANS RECEIVED BY
ESGIL CORPORATION: 5/20/2019
PLAN REVIEWER: Jason Pasiut
This plan review is limited to the technical requirements contained in the California version of
the International Building Code, Uniform Plumbing Code, Uniform Mechanical Code, National
Electrical Code and state laws regulating energy conservation, noise attenuation and access for
the disabled. This plan review is based on regulations enforced by the Building Department.
You may have other corrections based on laws and ordinances enforced by the Planning
Department, Engineering Department, Fire Department or other departments. Clearance from
those departments may be required prior to the issuance of a building permit.
Code sections cited are based on the 2016 CBC, which adopts the 2015 IBC.
The following items listed need clarification, modification or change. All items must be satisfied
before the plans will be in conformance with the cited codes and regulations. Per Sec. 105.4 of
the 2015 International Building Code, the approval of the plans does not permit the violation of
any state, county or city law.
To speed up the recheck process, please note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet number, specification section, etc.
Be sure to enclose the marked up list when you submit the revised plans.
Carlsbad CBC2019-0236
5/29/2019
[DO NOT PAY -THIS IS NOT AN INVOICE]
VALUATION AND PLAN CHECK FEE
JURISDICTION: Carlsbad PLAN CHECK#.: CBC2019-0236
PREPARED BY: Jason Pasiut DATE: 5/29/2019
BUILDING ADDRESS: 2525 El Camino Real #134
BUILDING OCCUPANCY: M
BUILDING AREA Valuation Reg.
PORTION ( Sq. Ft.) Multiplier Mod.
Tl 917 46.51
Air Conditioning
Fire Sprinklers
TOTAL VALUE
Jurisdiction Code cb By Ordinance
I 1997 UBC Building Permit Fee [!J
I 1997 UBC Plan Check Fee @
VALUE
Type of Review: f'7 Complete Review r Structural Only
r Repetitive Fee ., I i(,1-J Repeats
,.
Comments:
r Other
r Hourly
EsGil Fee ,.
($)
42,650
42,650
7
$220.637
Sheet 1 of 1
Carlsbad CBC2019-0236
5/29/2019
Please make all corrections, as requested in the correction list. Submit FOUR new
complete sets of plans for commercial/industrial projects (THREE sets of plans for
residential projects). For expeditious processing, corrected sets can be submitted in one
of two ways:
1. Deliver all corrected sets of plans and calculations/reports directly to the City of
Carlsbad Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760)
602-2700. The City will route the plans to EsGil and the Carlsbad Planning,
Engineering and Fire Departments.
2. Bring TWO corrected set of plans and calculations/reports to EsGil, 9320
Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-1468. Deliver all
remaining sets of plans and calculations/reports directly to the City of Carlsbad
Building Department for routing to their Planning, Engineering and Fire
Departments.
NOTE: Plans that are submitted directly to EsGil only will not be reviewed by the
City Planning, Engineering and Fire Departments until review by EsGil is complete.
• ACCESSIBILITY FOR REMODELS, ADDITIONS, AND REPAIRS
The following disabled access items are taken from the 2016 edition of California Building
Code. Per Section 1.9.1.2, all privately funded public accommodations and commercial
facilities shall be accessible to persons with disabilities.
Where existing elements or spaces are altered, each altered element or space shall
comply with applicable requirements of Division 2, including CBC section 11 B-202.4. CBC
section 11 B-202.4 states that when alterations or additions are made to existing buildings,
an accessible path of travel to the specific area of alteration shall be provided. See
exceptions to 11 B-202.4. If it is known that the accessible path of travel has already been
improved during this or the previous code cycle, please note the permit numbers on the
plans and update the scope of work to state that the accessible path of travel meets
current standards based on work previously done.
Detail on the plans the following elements of the existing path of travel that are required
to comply with the 2016 accessibility standards:
3. Existing primary path of travel to the building or facility entrance, including generic
details for the following:
a) Show the proposed accessible parking dimensions, slope, and cross-slope
in compliance with CBC 11 B-502.
b) Show the existing access aisle dimensions, slope, and cross slope in
compliance with 11 B-502.3.
c) Show the location of detectable warnings at hazardous vehicle areas. 11 B-
705.1.2.5.
Carlsbad CBC2019-0236
5/29/2019
d) Show the proposed curb ramp (if any) 48" minimum width, 48" x 48" turning
space at the bottom, landing length of 48" at the top, slope and cross-slope
in compliance with CBC 11 B-406.
e) Show the existing ramp (if any) slope, cross-slope, 48" minimum width, 60"
x 60" landing at the top, 72" long landing at the bottom, compliant changes
in direction (60" x 72") in compliance with CBC 11 B-405.
f) Show the existing stair (if any) width, riser and tread dimensions,
contrasting stipes, handrail height, gripping surfaces and top/bottom
extensions in compliance with CBC 11 B-504 and 505.
g) Show that the walking surface from the access aisle to the building entrance
has a walking surface in compliance with 11 B-403.
h) Show the existing accessible entrance door threshold, door hardware, door
width, and maneuvering clearances on either side of the door in compliance
with CBC 11 B-206.4.
4. Existing drinking fountains (if any) shall be shown to comply with the accessibility
features of 11 B-602 and 11 B-211.2.
5. Existing accessible parking reflectorized identification including the "van
accessible", "250 fine", and "unauthorized vehicle parking" signs per 11 B-502.6,
11 B-502.6.2, 11 B-502.8.2.
a) Existing accessible parking surface identification. 11 B-502.6.4.1.
b) Existing access isle "NO PARKING" identification per 11 B-502.3.3
c) Provide the address and phone number for the location to reclaim towed
vehicles. 11 B-502.8.2.
• END OF REVIEW
To speed up the review process, please note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet, note or detail number, calculation
page, etc. Please indicate here if any changes have been made to the plans that are
not a result of corrections from this list. If there are other changes. please briefly
describe them and where they are located in the plans.
Have changes been made to the plans not resulting from this correction list?
Please indicate: □ Yes □ No
The jurisdiction has contracted with EsGil, located at 9320 Chesapeake Drive, Suite
208, San Diego, California 92123; telephone number of 858/560-1468, to perform the
plan review for your project. If you have any questions regarding these plan review
items, please contact Jason Pasiut at Esgil. Thank you.
Carlsbad CBC2019-0236
5/29/2019
(._ City of
Carlsbad
PURPOSE
CLIMATE ACTION PLAN
CONSISTENCY CHECKLIST
B-50
Development Services
Building Division
1635 Faraday Avenue
(760) 602-2719
www .carlsbadca.gov
This checklist is intended to assist building permit applicants identify which Climate Action Plan (CAP) ordinance
requirements apply to their projects. Unless none of the requirements apply, the completed checklist must be
included in the building permit application. It may be necessary to supplement the completed checklist with
supporting materials, calculations or certifications, to demonstrate full compliance with CAP ordinance
requirements. For example, projects that propose or require a performance approach to comply with energy-
related measures will need to attach to this checklist separate calculations and documentation as specified by
the ordinances .
..1111 If an item in the checklist is deemed to be not applicable to a project, or is less than the minimum required
by ordinance, an explanation must be provided to the satisfaction of the Building Official.
..1111 Details on CAP ordinance requirements are available on the city's website.
Project Name/Building
Permit No.:
Property Address/APN:
Applicant Name/Co.:
Applicant Address:
Contact Phone:
------------BP No.: C5c-i.u/9-02.36
Vt:o,ePE> B--,r C~ B~,P
s frr,J PL ¢:'.lip , CA-
Contact Email:
Contact information of person completing this checklist (if different than above):
Name:
Company
name/address:
B-50
Contact Phone:
Contact Email:
Applicant Signature: __ -O~_·_R-__ ,_ . ....,\/4 ......... ~~--<~----Date:
Page 1 of 3 Revised 04/19
City of Carlsbad Climate Action Plan Consistency Checklist
Use the table below to determine which sections of the Ordinance Compliance checklist are applicable to your project.
For residential alterations and additions to existi ng buildings, contact the building counter for the building permit valuation.
Building Permit Valuation (BPV) $ ___________ _
I Construction Type I Complete Sectlon(sJ
D Residential
D New construction 1A
D Alterations: D exempt
D BPV ~ $60,000 1A 1-2 family dwellings and townhouses with attached garages
D Electrical service panel upgrade 1A only
Multi-family dwellings only where interior finishes are removed
D BPV ~ $200,000 1A and significant site work and upgrades to structural and
mechanical, electrical, and/or plumbing systems are proposed
'bl] Nonresidential
"□ New construction 1 Band 2
-Q Alterations 2
I
1. Electric Vehicle Charging
A D Residential New construction and major alterations (or electric panel upgrade)*
Please refer to Carlsbad Ordinance CS-349 when completing this section.
D One and two-family residential dwelling or townhouse with attached garage:
D One EVSE ready parking space required D Exception :
□ Multi-family residential· D Exception ·
Total Parking Spaces EVSE Spaces
Proposed Capable I Ready Installed
I
Calculations: Total EVSE spaces = .10 x Total parking (rounded up to nearest whole number)
EVSE Installed= Total EVSE Spaces x .50 (rounded up to nearest whole number)
EVSE other= Total EVSE spaces-EVSE Installed
(EVSE other may be "Capable," "Ready" or "Installed.")
I Total
I
*Major alterations are: (1) for one and two-family dwellings and townhouses with attached garages, alterations have a building permit valuation~ $60,000 or
include an electrical service panel upgrade; (2) for multifamily dwellings (three units or more without attached garages), alterations have a building permit valuation
~ $200,000, interior finishes are removed and significant site work and upgrades to structural and mechanical, electrical, and/or plumbing systems are proposed.
B D Nonresidential new construction (includes hotels/motels) □ Exception ·
Total Parking Spaces EVSE Spaces
Proposed Capable I Ready I Installed I Total
I I I
Calculation· Refer to the table below·
Total Number of Parking Spaces provided Number of reouired EV Spaces Number of required EVSE Installed Spaces
D 0-9 1 1
D 10-25 2 1
D 26-50 4 2
D 51-75 6 3
D 76-100 9 5
D 101-150 12 6
D 151-200 17 9
D 201 and over 10 percent of total 50 percent of Required EV Spaces
Updated 4/12/2019 2
City of Carlsbad Climate Action Plan Consistency Checklist
2. Transportation Demand Management (TDM)
A. List each proposed nonresidential use and gross floor area (GFA) allocated to each use.
B. Employee ADT/1,000 square feet is selected from the table below.
Use GFA Employee ADT for first
1,000 S.F.
Employee ADT for each
subsequent 1,000 S.F.
Total Employee ADT
Total [__---=======-
If total employee ADT is greater than or equal to 110 employee ADT, a TOM plan is required.
TOM plan required: Yes D No)t'
Updated 4/12/2019
Employee ADT Estimation for Various Commercial Uses
ADT for first
1,000 s.f.
EmpADTI
1000 s.f.1
Office (all)2 20
Restaurant 11
Retaib 8
Industrial 4
Manufacturing 4
Warehousin 4
1 Unless otherwise noted, rates estimated from /TE Trip
Generation Manual, 1 (JhEdition
20
11
4.5
3.5
3
1
2 For all office uses, use SAN DAG rate of 20 ADT/1,000 sf to
calculate employee ADT
3 Retail uses include shopping center, variety store, supermarket,
gyms, pharmacy, etc.
Other commercial uses may be subject to special
consideration
Sample calculations:
Office: 20,450 sf
1. 20,450 sf / 1000 x 20 = 409 Employee ADT
Retail: 9,334 sf
1. First 1,000 sf = 8 ADT
2. 9,334 sf -1,000 sf = 8,334 sf
3. 8,334 sf / 1,000 x 4.5 + 8 = 46 Em lo ee ADT
3