HomeMy WebLinkAbout2600 La Costa Ave; ; CBR2019-0876; PermitPrint Date: 10/16/2019
Job Address:
Permit Type:
Parcel No:
Valuation:
Occupancy Group:
# Dwelling Units:
Bedrooms:
Project Title:
2600 La Costa Ave
BLDG-Residential
2163601500
$37,208.00
Residential Permit
Work Class: Alteration
Lot#:
Reference #:
Construction Type:
Bathrooms:
Orig. Plan Check#:
Plan Check#:
{city of
Carlsbad
Permit No: CBR2019-0876
Status:
Applied:
Issued:
Permit
Finaled:
Closed -Finaled
04/15/2019
05/13/2019
Inspector: CRenf
Final
Inspection: 10/16/2019 2:19:35PI
Description: HIBERT: 800 SF INTERIOR REMODEL (REMODEL KITCHEN, CREATE ADDITIONAL BEDROOM, MASTER BATH REMODEL)
Applicant:
ROBERT BALENTINE CONSULTING
ROBERT BALENTINE
2633 Hartford St
San Diego, CA 92110-2315
858-531-5106
BUILDING PERMIT FEE ($2000+)
BUILDING PLAN CHECK FEE (BLDG)
Owner:
TEKRAN HOLDINGS
6965 El Camino Real, 105
Carlsbad, CA 92009-4101
ELECTRICAL BLDG RESIDENTIAL NEW/ADDITION/REMODEL
MECHANICAL BLDG RESIDENTIAL NEW/ADDITION/REMODEL
PLUMBING BLDG RESIDENTIAL NEW/ADDITION/REMODEL
SB1473 GREEN BUILDING STATE STANDARDS FEE
STRONG MOTION-RESIDENTIAL
Total Fees: $711.48 Total Payments To Date: $711.48
Contractor:
AFFORDABLE TURN KEY CONSTRUCTION
1265 Simpson Way
Escondido, CA 92029-1403
760-297-1305
Balance Due: $0.00
$329.20
$230.44
$41.00
$42.00
$62.00
$2.00
$4.84
Please take NOTICE that approval of your project includes the "Imposition" of fees, dedications, reservations, or other exactions hereafter
collectively referred to as "fees/exaction." You have 90 days from the date this permit was issued to protest imposition of these
fees/exactions. If you protest them, you must follow the protest procedures set forth in Government Code Section 66020(a), and file the
protest and any other required information with the City Manager for processing in accordance with Carlsbad Municipal Code Section
3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack, review, set aside, void, or annul their
imposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection
fees and capacity changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this
project. NOR DOES IT APPLY to any fees/exactions of which you have previously been given a NOTICE similar to this, or as to which the
statute of limitation has previously otherwise expired.
1635 Faraday Avenue, Carlsbad, CA 92008-7314 I 760-602-2700 I 760-602-8560 f I www.carlsbadca.gov
..
{ Cicyof
Carlsbad
RESIDENTIAL
BUILDING PERMIT
APPLICATION
B-1
Plan Check C BR& 619-0X::r:0
Est. Value l/;3·y,c:JO g. C()
PC De posit _1J~,'}~.'Xl~• _. L/~4,__ __
Date __ L-(_-_i S-_-_i ~q~_
JobAddress ~60o t..A Cesr,o Avt)CA~l,~~? Suite: ____ APN: 2/b-¼O-rs:-co
CT/Project#: __________ Lot#: ____ Fire Sprinklers: yes/ no Air Conditioning: yes/ no
~..,..~Ir/,,,.._, KV"\ Q!?J.!L--I e SPu,wf_ ,o COQJe.. t./,Ql;I/ P~-
7 BRIEF DESCRIPTION OF WORK:
□ Addition/New: _____ Living SF, ___ Deck SF, ___ Patio SF, Garage SF
Is this to create an Acc:.ssory Dwelling Unit? Yes/ No New Fireplace? Ye~w many? __
D Remodel: 8{P -SF of affected area Is the area a conversion or change of use ? Yee
Additional Gas or Electrical Features? ___ ... A/4'-'"-0"'--------0 Pool/Spa: __ ,,.--___ SF
□ Solar: ---KW, ------Modules, Mounted: Roof/ Ground , Tilt: Yes/ No, RMA: Yes/ No, Battery: Yes/ No
Panel Upgrade: Yes/ No
D Reroof=---~~-~-------------------------------
D Plumbing/Mechanical/Electrical Only: ________________________ _
D Other: ____________________________________ _
APPLICANT (PRIMARY CONTACT) PROPERTY OWNER
_...J..:...::=---'":"'!.lo.llC=:=~~--,.-,.---.:r-Name: fet<@Ac, Hoc.r:>17£,, Lr -
:,.,....;:...c....,;..,_....:..:_""-'--'---<----'-~-=<----'--'-''-=:...._-:lfddress: &7Gf !:<-Gic,:;: 'J?-r4c ti /d{°"
City: L,l)rr '->.1~4!~ State: (A i;p: f?;?M ;1
Phone:-:-~"-~~~~---'-:~~------Phone: ___________________ _
Email: f< Email:
DESIGN PROFESSIONAL
Name: _________________ _
Address: ________________ _
City: ________ State: ___ .Zip: ____ _
Phone: _________________ _
Email: _________________ _
Architect State License: ___________ _
---------------------
CONTRACTOR BUSINESS
Name: Rffi:xdo'd R. 71 m 1i;;.1 l coo:zrl: ,
Address: /J_&,r $,.,P,'&>v Wr>-Y 1
City: L~,-, D. .J" State: a4 Zip: '/J.o ,>-1
Phone: 7,:,,0 · clC/7-13°~-o · 7/,a -;1>7-~J-tt'? C'....-
Email: Joh e.-a..#orda..ble E, t ~. '-"..,___
State License:9545)2 Bus. License: 12,?7lQ4J3
(Sec. 7031.S Business and Professions Code: Any City or County which requires a permit to construct, alter, improve, demolish or repair any structure, prior to its
issuance, also requires the applicant for such permit to file a signed statement that he/she is licensed pursuant to the provisions of the Contractor's License Law
{Chapter 9, commending with Section 7000 of Division 3 of the Business and Professions Code} or that he/she is exempt therefrom, and the basis for the alleged
exemption. Any violation of Section 7031.5 by any applicant for a permit subjects the applicant to a civil penalty of not more than five hundred dollars {$500}).
1635 Faraday Ave Carlsbad, CA 92008 Ph: 760-602-2719 Fax: 760-602-8558 Email: Building@carlsbadca.gov
8-1 Page 1 of 2 Rev. 06/18
◄
( OPTION A): WORKERS'COMPENSATION DECLARATION:
I hearby affirm under penalty of perjury one of the following declarations:
□ I have and will maintain a certificate of consent to self-insure for workers' compensation provided by Section 3700 of the labor Code, for the performance of the
work which this permit is issued.
~ave and will maintain worker's compensation, as required by Section 3700 of the Labor Code, for e performpnce of the ~prk fQr which this permit is issued.
My workers' c~pe ation. infUJ~nc carrier aJld olicy number are: lnsuran1,cojpany Nj,me: s,y-It S/1..1,,tA-J-h4 l/1A
Policy No. ,._ W <.:... ~ Expiration Date: / / / '). O I (
□ Certificate of Exemption: I certify that in the performance of the work for which this permit is issued, I shall not employ any person in any manner so as to be come
subject to the workers' compensation Laws of California. WARNING: Failure to secure workers compensation coverage is unlawful, and shall subject an employer to
criminal penalties and civil fines up to $100,000 , in addition the to the cost of compensation, damages as provided for in Section 3706 of the Labor Code,
interest and attorney's fees. "
CONTRACTOR SIGNATURE: □AGENT DATE: ---------
( OPTION B ): OWNER-BUILDER DECLARATION:
I hereby affirm that I am exempt from Contractor's License Law for the following reason:
D I, as owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not intended or offered for sale (Sec.
7044, Business and Professions Code: The Contractor's License Law does not apply to an owner of property who builds or improves thereon, and who does such work
himself or through his own employees, provided that such improvements are not intended or offered for sale. If, however, the building or improvement is sold within
one year of completion, the owner-builder will have the burden of proving that he did not build or improve for the purpose of sale).
D I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions Code: The
Contractor's License Law does not apply to an owner of property who builds or improves thereon, and contracts for such projects with contractor(s) licensed
pursuant to the Contractor's License Law).
□ I am exempt under Section ________ Business and Professions Code for this reason:
1. I personally plan to provide the major labor and materials for construction of the proposed property improvement. D Yes D No
2. I (have/ have not) signed an application for a building permit for the proposed work.
3. I have contracted with the following person (firm) to provide the proposed construction {include name address/ phone/ contractors' license number):
4. I plan to provide portions of the work, but I have hired the following person to coordinate, supervise and provide the major work (include name/ address/ phone/
contractors' license number):
5. I will provide some of the work, but I have contracted {hired) the following persons to provide the work indicated (include name/ address/ phone/ type of work):
OWNER SIGNATURE: __________________ □AGENT DATE: _____ _
CONSTRUCTION LENDING AGENCY, IF ANY:
I hereby affirm that there is a construction lending agency for the performance of the work this permit is issued (Sec. 3097 {i) Civil Code).
Lender's Name: _____________________ _ Lender's Address: _____________________ _
ONLY COMPLETE THE FOLLOWING SECTION FOR NON-RESIDENTIAL BUILDING PERMITS ONLY:
Is the applicant or future building occupant required to submit a business plan, acutely hazardous materials registration form or risk management and prevention
program under Sections 25505, 25533 or 25534 of the Presley-Tanner Hazardous Substance Account Act? D Yes □ No
Is the applicant or future building occupant required to obtain a permit from the air pollution control district or air quality management district? D Yes □ No
Is the facility to be constructed within 1,000 feet of the outer boundary of a school site? □ Yes □ No
IF ANY OF THE ANSWERS ARE YES, A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR IS MEETING THE
REQUIREMENTS OF THE OFFICE OF EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT.
APPLICANT CERTIFICATION:
I certify that I have read the application and state that the above information is correct and that the information on the plans is accurate. I agree to comply with all
City ordinances and State laws relating to building construction.
I hereby authorize representative of the City of Carlsbad to enter upon the above mentioned property for inspection purposes. I ALSO AGREE TO SAVE, INDEMNIFY ANO KEEP
HARMLESS THE CITY OF CARLSBAD AGAINST ALL LIABILITIES, JUDGMENTS, COSTS AND EXPENSES WHICH MAY IN ANY WAY ACCRUE AGAINST SAID CITY IN CONSEQUENCE OF
THE GRANTING OF THIS PERMIT.OSHA: An OSHA permit is required for excavations over 5'0' deep and demolition or construction of structures over 3 stories in height.
EXPIRATION: Every permit issued by the Building Official under the provisions of this Code shall expire by limitation and become null and void if the building or work authorized
by such permit is not commenced within 180 days from the date of such permit or if the building or work authorized by such permit is suspended or abandoned at anytime
after the work is commenced for a period of ys ection 106.4.4 Uniform Building Code). /
APPLICANT SIGNATURE: ----''lf'-,£-___..,-=9-_____________ DATE: f/4q~,
1635 Faraday Ave Carlsbad, CA 92008
B-1
Ph: 760-602-2719 Fax: 760-602-8558
Page 2 of 2
Email: Building@carlsbadca.gov
Rev. 06/18
PERMIT INSPECTION HISTORY REPORT (CBR2019-0876)
Permit Type: BLDG-Residential Application Date: 04/15/2019 Owner: TEKRAN HOLDINGS, TRUST
VALDEZ MARTHA E FAMILY
LIVING
Work Class: Alteration Issue Date: 05/13/2019 Subdivision: LA COSTA-SOUTH UNIT# 1
Status: Closed -Finaled Expiration Date: 04/06/2020 Address:
IVR Number: 18387
Scheduled Actual Date Start Date Inspection Type Inspection No. Inspection Status Primary Inspector
10/07/2019 10/07/2019 BLDG-Final
Inspection
1 011612019 10116/2019 BLDG-Final
Inspection
October 16, 2019
Checklist Item
BLDG-Building Deficiency
BLDG-Plumbing Final
BLDG-Mechanical Final
BLDG-Structural Final
BLDG-Electrical Flnal
106676-2019
Checklist Item
BLDG-Building Deficiency
BLDG-Plumbing Final
BLDG-Mechanical Final
BLDG-Structural Final
BLDG-Electrical Final
107644-2019
Checklist Item
BLDG-Building Deficiency
BLDG-Plumbing Final
BLDG-Mechanical Final
BLDG-Structural Final
BLDG-Electrical Final
COMMENTS
See card for corrections
Failed Chris Renfro
COMMENTS
See card for corrections
Passed Chris Renfro
COMMENTS
2600 La Costa Ave
Carlsbad, CA 92009-7324
Re inspection Complete
Passed
No
No
No
No
No
Reinspection Complete
Passed
No
No
No
No
No
Complete
Passed
Yes
Yes
Yes
Yes
Yes
Page 2 of 2
PERMIT INSPECTION HISTORY REPORT (CBR2019-0876)
Permit Type: BLDG-Residential Application Date: 0411512019 Owner: TEKRAN HOLDINGS, TRUST
VALDEZ MARTHA E FAMILY
LIVING
Work Class: Alteration Issue Date: 05/13/2019 Subdivision: LA COSTA-SOUTH UNIT# 1
Status: Closed -Finaled Expiration Date: 0410612020 Address:
IVR Number: 18387
Scheduled Actual Inspection Type Inspection No. Inspection Status Primary Inspector Date Start Date
05/1712019 05/17/2019 BLOG-SW-Pre-Con 092168-2019 Passed Chris Renfro
Checklist Item COMMENTS
BLDG-Building Deficiency
06/11/2019 06/11/2019 BLDG-84 Rough 094330-2019 Passed Chris Renfro
Combo(14,24,34,44)
Checklist Item COMMENTS
BLDG-Building Deficiency
BLDG-14
Frame-Steel-Bolting-Welding
(Decks)
BLDG-24 Rough-Topout
BLDG-34 Rough Electrical
BLDG-44
Rough-Ducts-Dampers
06/20/2019 06/20/2019 BLDG-82 Drywall, 095235-2019 Partial Pass Chris Renfro
Exterior Lath, Gas
Test, Hot Mop
Checklist Item COMMENTS
BLDG-Building Deficiency
BLDG-17 Interior Lath-Drywall
BLDG-18 Exterior Lath and
Drywall
BLDG-23 Gas-Test-Repairs
06125/2019 0612512019 BLDG-17 Interior 095510-2019 Passed Chris Renfro
Lath/Drywall
Checklist Item COMMENTS
BLDG-Building Deficiency
09/23/2019 09/23/2019 BLDG-Final 104933-2019 Failed Chris Renfro
Inspection
Checklist Item COMMENTS
BLDG-Building Deficiency
BLDG-Plumbing Final
BLDG-Mechanical Final
BLDG-Structural Final No contractor on site. Left a door hanger
called no response
BLDG-Electrical Final
0912512019 09125/2019 BLDG-Final 105362-2019 Failed Chris Renfro
Inspection
October 16, 2019
2600 La Costa Ave
Carlsbad, CA 92009-7324
Reinspection Complete
Complete
Passed
Yes
Complete
Passed
Yes
Yes
Yes
Yes
Yes
Re inspection Incomplete
Passed
Yes
No
Yes
Yes
Complete
Passed
Yes
Reinspection Comp'8te
Passed
No
No
No
No
No
Reinspection Complete
Page 1 of 2
DATE: May 7, 2019
JURISDICTION: Carlsbad
✓• EsG1I
A SAFEL?uilt'Company
PLAN CHECK#.: CBR2019-0876
PROJECT ADDRESS: 2600 La Costa Ave
SET: II
PROJECT NAME: Interior Remodel to Hibert Residence
□ APPLICANT
□ JURIS.
[SI The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's
codes when minor deficiencies identified below are resolved and checked by building
department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
D The check list transmitted herewith is for your information. The plans are being held at EsGil
until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
D The applicant's copy of the check list has been sent to:
[SI EsGil staff did not advise the applicant that the plan check has been completed.
□
Mail Telephone
0 REMARKS:
By: Abe Doliente
EsGil
nt that the plan check has been completed.
Telephone#:
Email:
Fax In P rson
Enclosures:
4/29/19
9320 Chesapeake Drive, Suite 208 ♦ San Diego, California 92123 ♦ (858) 560-1468 ♦ Fax (858) 560-1576
DATE: April 25, 2019
JURISDICTION: Carlsbad
✓• EsG1I
A SAFEbuilfCompany
PLAN CHECK#.: CBR2019-0876
PROJECT ADDRESS: 2600 La Costa Ave
SET: i
PROJECT NAME: Interior Remodel to Hibert Residence
□ APPLICANT
□ JURIS.
D The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's
codes when minor deficiencies identified below are resolved and checked by building
department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
~ The check list transmitted herewith is for your information. The plans are being held at EsGil
until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
~ The applicant's copy of the check list has been sent to:
Rob Balentine
D EsGil staff did not advise the applicant that the plan check has been completed.
~ EsGil staff did advise the applicant that the plan check has been completed.
Person contacted: Rob Balentine
Date contacted:
Mail Telephone
0 REMARKS:
By: Abe Doliente
EsGil
(by: )
Fax In Person
4/18/19
Telephone#: 858-531-5106
Email: robmbalentine@gmail.com
Enclosures:
9320 Chesapeake Drive, Suite 208 ♦ San Diego, California 92123 ♦ (858) 560-1468 ♦ Fax (858) 560-1576
Carlsbad CBR2019-0876
April 25, 2019
PLAN REVIEW CORRECTION LIST
SINGLE FAMILY DWELLINGS AND DUPLEXES
PLAN CHECK#.: CBR2019-0876 JURISDICTION: Carlsbad
PROJECT ADDRESS: 2600 La Costa Ave
FLOOR AREA: Remodel -800 SF
REMARKS:
DATE PLANS RECEIVED BY
JURISDICTION:
DATE INITIAL PLAN REVIEW
COMPLETED: April 25, 2019
FOREWORD (PLEASE READ):
STORIES: 2
HEIGHT: nc
DATE PLANS RECEIVED BY
ESGIL CORPORATION: 4/18/19
PLAN REVIEWER: Abe Doliente
This plan review is limited to the technical requirements contained in the California version of
the International Residential Code, International Building Code, Uniform Plumbing Code,
Uniform Mechanical Code, National Electrical Code and state laws regulating energy
conservation, noise attenuation and access for the disabled. This plan review is based on
regulations enforced by the Building Department. You may have other corrections based on
laws and ordinance by the Planning Department, Engineering Department, Fire Department or
other departments. Clearance from those departments may be required prior to the issuance of
a building permit.
Present California law mandates that construction comply with the 2016 edition of the California
Code of Regulations (Title 24), which adopts the following model codes: 2015 IRC, 2015 IBC,
2015 UPC, 2015 UMC and 2014 NEC.
The above regulations apply, regardless of the code editions adopted by ordinance.
The following items listed need clarification, modification or change. All items must be satisfied
before the plans will be in conformance with the cited codes and regulations. Per Sec. 105.4 of
the 2015 International Building Code, the approval of the plans does not permit the violation of
any state, county or city law.
To speed up the recheck process, please note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet number, specification section, etc.
Be sure to enclose the marked up list when you submit the revised plans.
Carlsbad CBR2019-0876
April 25, 2019
[DO NOT PAY -THIS IS NOT AN INVOICE]
VALUATION AND PLAN CHECK FEE
JURISDICTION: Carlsbad
PREPARED BY: Abe Doliente
BUILDING ADDRESS: 2600 La Costa Ave
BUILDING OCCUPANCY: R3/U
BUILDING AREA Valuation
PORTION ( Sq. Ft.) Multiplier
Remodel 800 46.51
Air Conditioning
Fire Sprinklers
TOTAL VALUE
Jurisdiction Code cb By Ordinance
1997 UBC Buildin Permit Fee g •
1997 UBC Plan Check Fee •
Type of Review:
D Repetitive Fee
• Repeats
Comments:
0 Complete Review
□ Other
0 Hourly
EsGII Fee
PLAN CHECK#.: CBR2019-0876
DATE: April 25, 2019
Reg. VALUE ($)
Mod.
37,208
37,208
□ Structural Only
1--------11 Hr. @ • $201.111
Sheet 1 of 1
Carlsbad CBR2019-0876
April 25, 2019
Please make all corrections, as requested in the correction list. Submit THREE sets of
plans for residential projects). For expeditious processing, corrected sets can be
submitted in one of two ways:
1. Deliver all corrected sets of plans and calculations/reports directly to the City of
Carlsbad Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760) 602-
2700. The City will route the plans to EsGil and the Carlsbad Planning, Engineering and
Fire Departments.
2. Bring TWO corrected set of plans and calculations/reports to EsGil, 9320 Chesapeake
Drive, Suite 208, San Diego, CA 92123, (858) 560-1468. Deliver all remaining sets of
plans and calculations/reports directly to the City of Carlsbad Building Department for
routing to their Planning, Engineering and Fire Departments.
NOTE: Plans that are submitted directly to EsGil only will not be reviewed by the City
Planning, Engineering and Fire Departments until review by EsGil is complete.
PLANS
1. All sheets of plans must be signed by the person responsible for their
preparation. (California Business and Professions Code).
2. Specify on the Title Sheet of the plans the gross floor area of the remodel..
Section R106.2.
3. Note on the plans that the location of the smoke alarms and the carbon
monoxide alarms will be field verified by the City Building Inspector.
Items 4 & 5 are for information and references only.
4. In existing buildings, when alterations, repairs or additions requiring a permit
occur (or when one or more sleeping rooms are added), the dwelling unit shall
be provided with smoke alarms located as required for new dwellings; the
smoke alarms shall be interconnected and hard wired. Exception: Smoke alarms
in existing areas need not be interconnected and hard wired where the
alterations or repairs do not result in the removal of interior wall or ceiling finishes
exposing the structure, unless there is an attic, crawl space, or basement
available which could provide access for hard wiring and interconnection without
the removal of interior finishes. Section R314.8.1.
5. When alterations, repairs or additions are proposed for dwelling units within
which fuel-burning appliances are installed (and in dwelling units having attached
garages), the dwelling unit shall be provided with carbon monoxide alarms
located as required for new dwellings; the carbon monoxide alarms shall be
interconnected and hard wired. Exception: Carbon monoxide alarms in existing
areas need not be interconnected and hard wired where the alterations or repairs
do not result in the removal of interior wall or ceiling finishes exposing the
structure, unless there is an attic, crawl space, or basement available which
could provide access for hard wiring and interconnection without the removal of
interior finishes. Section R315.2.
Carlsbad CBR2019-0876
April 25, 2019
ELECTRICAL
6. For a single-family dwelling unit, show that at least one receptacle outlet
accessible at grade level will be installed outdoors at the front and back of the
dwelling. CEC Article 210.52(E). This receptacle must be GFCI protected.
7. Show on the plans that countertop receptacle outlets comply with CEC Article
210.52(C): In kitchens a receptacle outlet shall be installed at each counter
space 12 inches or wider; Receptacles shall be installed so that no point along
the wall line is more than 24 inches; Island and peninsular countertops 12 inches
by 24" long (or greater) shall have at least one receptacle. (Counter top spaces
separated by range tops, refrigerators, or sinks shall be considered as separate
counter top spaces).
8. Show on the plans a wall receptacle within 36" of each lavatory in the bathroom.
CEC 210.52(0). Recheck bathrooms 2 & 3.
9. Include a receptacle outlet in any hallways 10 feet or more in length. CEC Article
210.52(H).
10. Show at least one wall switch-controlled lighting outlet to be installed in every
habitable room; in bathrooms, hallways, stairways, attached garages, and
detached garages with electric power; and at the exterior side of outdoor
entrances or exits. At interior stairways show 3-way switching for lighting outlets
at each floor level where there are six or more steps. CEC Article 210.70(A).
RESIDENTIAL GREEN BUILDING STANDARDS
In addition to the ones already shown on the plans, revise or add the following
notes:
11. Note on the plans that when a shower is provided with multiple shower heads,
the sum of flow to all the heads shall not exceed 1.8 gpm @ 80 psi, or the
shower shall be designed so that only one head is on at a time. CGC Section
4.303.1.3.2.
12. Recycling. Note on the plans that a minimum of 65% of construction waste is to
be recycled. CGC Section 4.408.1.
MISCELLANEOUS
13. Delete the references to the City of San Diego under the Building Code Data.
The project is in the City of Carlsbad.
Carlsbad CBR2019-0876
April 25, 2019
14. Revise the label of sheet referring to Conceptual Lighting & Power Plan. To
sheet A-4.1
15. To speed up the review process, note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet, note or detail number,
calculation page, etc.
16. Please indicate here if any changes have been made to the plans that are not a
result of corrections from this list. If there are other changes, please briefly
describe them and where they are located in the plans.
• Have changes been made to the plans not resulting from this correction list?
Please indicate:
Yes □ No □
17. The jurisdiction has contracted with EsGil, located at 9320 Chesapeake Drive,
Suite 208, San Diego, California 92123; telephone number of 858/560-1468, to
perform the plan review for your project. If you have any questions regarding
these plan review items, please contact Abe Doliente at EsGil. Thank you.
( City of
Carlsbad
PURPOSE
CLIMATE ACTION PLAN
CONSISTENCY CHECKLIST
B-50
Development Services
Building Division
1635 Faraday Avenue
(760) 602-2719
www.carlsbadca.gov
This checklist is intended to assist building permit applicants identify which Climate Action Plan (CAP) ordinance
requirements apply to their projects. Unless none of the requirements apply, the completed checklist must be
included in the building permit application. It may be necessary to supplement the completed checklist with
supporting materials, calculations or certifications, to demonstrate full compliance with CAP ordinance
requirements. For example, projects that propose or require a performance approach to comply with energy-
related measures will need to attach to this checklist separate calculations and documentation as specified by
the ordinances.
~ If an item in the checklist is deemed to be not applicable to a project, or is less than the minimum required
by ordinance, an explanation must be provided to the satisfaction of the Building Official.
~ Details on CAP ordinance requirements are available on the city's website.
Project Name/Building
Permit No.:
Property Address/APN:
Applicant Name/Co.:
Applicant Address:
Contact Phone:
Cf'.3/2cl.C/Q · 6r7-<a BP No.:
cem 5?>( _. 57 0 b Contact Email:
Contact information of person completing this checklist (if different than above):
Name:
Company
name/address:
Contact Phone:
Contact Email:
Applicant Signature:-~--------------Date: __ 4_/_1ffi __ l~q __
B-50 Page 1 of 3 Revised 04/19
City o1"Carlsbad Climate Action Plan Consistency Checklist
Use the table below to determine which sections of the Ordinance Compliance checklist are applicable to your project.
For residential alterations and additions to existing buildings, contact the building counter for the building permit valuation.
Building Permit Valuation (BPV) $ tp ,31r c2. 0 8 • QQ.
)s:J Residential
D New construction 1A
~ Alterations: )(exempt
D BPV;?: $60,000
D Electrical service panel upgrade
1A
1A
1-2 family dwellings and townhouses with attached garages
only
D BPV;?: $200,000 1A
Multi-family dwellings only where interior finishes are removed
and significant site work and upgrades to structural and
mechanical, electrical, and/or plumbing systems are proposed
D Nonresidential
D New construction 18 and 2
D Alterations 2
1. Electric Vehicle Charging
A. D Residential New construction and major alterations (or electric panel upgrade)*
Please refer to Carlsbad Ordinance CS-349 when completing this section.
D One and two-family residential dwelling or townhouse with attached garage:
D One EVSE ready parking space required D Exception :
D Multi-family residential· D Exception ·
Total Parking Spaces EVSE Spaces
Proposed Capable Ready
Calculations: Total EVSE spaces = .10 x Total parking (rounded up to nearest whole number)
EVSE Installed= Total EVSE Spaces x .50 (rounded up to nearest whole number)
EVSE other= Total EVSE spaces -EVSE Installed
(EVSE other may be "Capable," "Ready" or "Installed.")
Installed Total
I
*Major alterations are: (1) for one and two-family dwellings and townhouses with attached garages, alterations have a building permit valuation <! $60,000 or
include an electrical service panel upgrade; (2) for multifamily dwellings (three units or more without attached garages), alterations have a building permit valuation
<! $200,000, interior finishes are removed and significant site work and upgrades to structural and mechanical, electrical, and/or plumbing systems are proposed.
B D Nonresidential new construction (includes hotels/motels) D Exception ·
Total Parking Spaces EVSE Spaces
Proposed Capable I Ready I Installed I Total
I I I
Calculation: Refer to the table below:
Total Number of Parking Spaces provided Number of reauired EV Spaces Number of required EVSE Installed Spaces
D 0-9 1 1
D 10-25 2 1
D 26-50 4 2
D 51-75 6 3
D 76-100 9 5
D 101-150 . 12 6
D 151-200 17 9
D 201 and over 10 percent of total 50 percent of Required EV Spaces
Updated 4/12/2019 2