HomeMy WebLinkAbout2619 ABEDUL ST; ; 77-3181; Permit...""
DATE REMARKS
FOUNDATIONS:
SET BACK
INSPECTOR
TRENCH
REINFORCING
WEATHER PROOFING FOUNDATION WALL &
I I I
CONCRETE SLAB
I I I
FRAMING I I ~ I INT. LATHING OR DRYWALL I I I
EXT. LATHING
MASONRY
FINAL 1
USE SPACE BELOW FOR NOTES. FOLLOW-UP, ETC.
5-19-77 Fdn. Forms: Q.K. E. Nelson
5-23-77 Pour: O.K. B. Nelson
.5-24-77 Fdn. forms: O.K.
.. .
Dacribc work: kd -6
NOTICE
THIS PERMIT BECOMES NULL AN0 VOID IF WORK OR CONSTRUC. TlON AUTHORIZED IS NOT COMMENCE0 WITHIN 60 DAYS, OR IF CONSTRUCTION OR WORK ISSUSPENDEO OR ABANDONED FOR A
PERIOD OF 120 DAYS AT ANY TIME AFTER WORK IS COM-
MENCED.
APPLICATION AN0 KNOW THE SAME TO BE TRUE AN0 CORRECT. ALL PROVISIONS OF LAWS AN0 ORDINANCES GOVERNING THIS
I HEREBY CERTIFY THAT I HAVE REA0 AN0 EXAMINE0 THIS
TYPE OF WORK WILL BE COMPLIED WITH WHETHER SPECIFIED HEREIN OR NOT THE GRANTING OF A PERMIT DOES NOT PRESUME TO GIVE AUTHORITY TO VIOLATE OR CANCEL THE PROVISIONS OF ANY OTHER STATE OR LOCAL LAW REGULATING CONSTRUCTION OR THE PERFORMANCE OF CONSTRUCTION.
PLAN CHECK VALIDATION CK. M.O. CASU PERMIT VALIDATION CK. M.O. CASU
WHEN PROPERLY VALIDATED IIN THIS SPACE1 THIS IS YOUR PERMIT
~ 'I
INSPECTOR
. ..
REMARKS
USE SPACE BELOW FOR NOTES, FOLLOW-UP. ETC.
5-24-77 Water service: No. E. Nelson
6-7-77 Sewer: O.K. B. Nelson
City of CARLSBAD, CALIFORNIA 92008
yplicant to complete numbered spaces only. Phone 729-1181 Permit No. 77 .' 3!J3
10. .DD"l**
ClkPA M 'H&&i& "/ i ,. ">,"t,
,mu .TT.C*tO .*E111
ZIP WO*I
.".*5*
Clar of work: d NEW 0 AOOITION 0 ALTERATION 0 REPAIR
PERMIT FE
'ECIAL CONDITIONS:
ISSUANCE OF EACH PERMIT
"
NEW CONSTRUCTION, FOR EACH AMPERES OF MAIN SERVICE, SWITCH, 1
VLICATION AaEnED BV: PLAUS CHECKED BV FUSE OR BREAKER
Y. I
NOTICE
DATE NEW SERVICE ON EXISTING BLDG.
IN MAIN SERVICE, SWITCH, FUSE FOR EA. AMPERE OF INCREASE
OR BREAKER
REMODEL, ALTERATION, NO CHANGE IN SERVICE, FOR EA. AMPERE OF INCREASE
I TEMP. SERVICE UP TO AN0 INCLUO- ING 200 AMP.
I TEhlP. SERVICE OVER 200 AMP. PER 1W
T 5 3,. 'L
INSPECTOR
REMARKS INSPECTOR
USE SPACE BELOW FOR NOTES, FOLLOW-UP, ETC.
5-26-77 Temp. Pole: O.K. B. Nelson
MECHANICAL PERMIT APPLICATION
8 %Iau of work: EW 0 ADDITION 0 ALTERATION 0 REPAIR
Type of Fuel: Oil
THIS PERMIT BECOMES NU TlON AUTHORIZED IS NOT CONSTRUCTION OR WORK I PERIOD OF 120 DAYS AT
APPLICATION AN0 KNOW THE SAME TO BE TRUE AND CORRECT. I HEREBY CERTIFY THAT I HAVE READ AND EXAMINE0 THIS
ALL PROVISIONS OF LAWS AN0 ORDINANCES GOVERNING THIS TYPE OF WORK WILL BE COMPLIED WITH WHETHER SPECIFIED HEREIN OR NOT THE GRANTING OF A PERMIT DOES NOT PRESUME TO GlVk AUTHORITY TO VIOLATE OR CANCEL THE PROVISIONS OF ANY OTHER STATE OR LOCAL LAW REGULATING CONSTRUCTION OR THE PERFORMANCE OF CONSTRUCTION.
IF WORK OR CONSTRUC- WITHIN 120OAYS.OR IF OR ABANDONED FOR A
City of CARLSBAD, CALIFORNIA 92008
Applicant to complete numbered spaces only. Phone 729-1181 Permit Y:.-j&&Jgl.&J No ... . - ..
PLAN CHECK VALIDATION CK. M.D. USH PERMIT VALIDATION CK. M.O. CASU
WEN PROCZRLV VALIDATED IIN THIS SPACE) THIS IS VWR PERMIT
1,') 1, /
REQUEST FOR
$1 n INSPECTION TIME @b 2.7
Owner
Address. .
BUILDING PLUMBING I ELECTRICAL MISCELLANEOUS .-
lnrulation ................. 0
0 Patio ......................... Temp Pole .............. 0 Water Heater ............ 0 Fdn. Forms .............. 0 0 bch ........................ Pool Bonding .......... Gas .......................... 0 Drywall .................... 0 Plenum & Ducts ....... 0 ................................ 0 .................................. 0
0 Steel 0 Sewer ................ ..................
sheathing 0 Undergrnd. Plbg 0 Underground 0 Sign 0 0 DriAay 0
Lath .......................... 0 Undergrnd. Water .... 0 Ceil bat .............. 0 Wall .......................... 0 hme ...................... Rough ...................... 0 bough .................... 0 Fence ...................... 0 Final ........................ 0 Final ........................ 0
%quested by e:-.
special Instructions -- .............................. _._._.... .... ...._... .... .............................................
Grading .................... Final ......................
........................ ................... ................ .......................... .......... .......
0
bady for Inspection - Mon., lues., Wed., Fri.
- .... - ....... .... -- ..... - ......... - 76 m
..
REQUEST FOR INSPECTION
...................
......................
nspection -- Mon.. lues., Wed.,
eial Instructions ............
Phm number ......................... I ................................. Panon Taking tbpm: ...........I..
..
*
?
..
... G- 19 - 77 .. Permit No. ..............-..___.___. Date
REQUEST FOR INSPECTION TIME
I
Owner
...................
.
.. ? .. ..
REQUEST FOR
INSPECTION
Inspector ......
Drywall ....................
Fdn. Form ..............
. ~ ..
REQUEST FOR
.......................... ................... .....................
special Instructions ....................... 3 -
..... ...... f ......... -. t
Requested by 1 ." .-.
*'
8 ..
n
.
..
I REQUEST FOR INSPECTION
InsPCtor 53d Wmit NO. ....................... Date
BUlLDlNO
Insulation .................
Drywall .................... 0
Mn. Forms .............. 0
bth ......................
Frem .....................
Final .......................
PLUMBING ELECTRICAL
.................................. 0 ................................ C
Water Heeter ._._.; ...... 0 TempPole .............. 0 Gas 0 Pool Emding
0
rgrnd. Water 0 Coil Heat
Plbg. 0 Underground
Rough ...................... 0 Rough .................... 0
a1 ...................... 0
.......................... .......... e ................ ................... . ...... .......... .... ..............
MISCELLANEOUS
Plenum I3 Ducts .......
Pach ........................ 0
Patio ........................ 0
Driverray .................. 0
Sign .......................... 0 wall .......................... 0 Fence ...................... 0 Grading .................... 0
.?. ._ ................... _"
won Taking Ibpat: ____._______._I____
'. . 3 - ,. ,' REQUEST FOR INSPECTION TIME
.. .
1 1: INTERDEPARTMENTAL INFORMATION SHEET 1
', BUILDING DEPARTMENT
I BUILDING ADDRESS: ... P rl I
F C" .
PLANNING DEPARTMENT
LOT SIZE />-J- 4 LOT WIDTH 73 '
UNITS ALLOWED / ' UNITS PROVIDED ,/)
PARKING SPACES REQUIRED 2" PROVIDED &';% PROVIDED
,, ,' 7. c- PROVIDED
J
FRONT SETBACK: , SIDE SETBACK: 7.3 Ffi?!?- x 2 /]Cj;f
',. LANDSCAPE & IRRIGATION PLAN COMMENTS:
ENVIRONMENTAL PROTECTION REQ:
ENGINEERING DEPARTMENT
R.O.W. Ec/S~&QJNDUSTRIAL WASTE ,+/,A IMPROVEMENTS s/m,&/? oA/. LffA
SEWER CONNECTION L, C I Ld, , DRIVEWAY LOCATIONS OK
GRADING PERMIT G@& p5 ?EASEMENTS HoU.= DRAINAGE Sk/dW
LEGAL DESCRIPTION Lo 7 95 L,C, ~&wouI 9 No. f,
ADDITIONAL COMMENTS
fi78 IPGR/tlT, '
I::.
:. ,, Fj
OK TO ISSUE: DATE PWI OK TO FINAL DATE 1
FIRE DEPARTMENT ._
:, SPRIriKLING SYSTEM FIRE PROTECTION EQUIP.
IRE ALARNS EXITS
IRE HYDRANTS LOCATION
I;::' '"'.,/ *' BDDITIONAL COMMENTS
CORRECTION LIST CITY OF CARLSBAD (714) 729-1181
BUILDING DEPARTMENT
SINGLE FAMILY AND MULTIPLE FAMILY RESIDENTIAL PLAN
*WARNING: PLAN CHECK FEES: Where no action is taken by the applicant in 120 days,
and no building permit is issued, all plan check fees are
Job Address: Owner 4df 5%-
Contractor: Engineer
Basic allowable bldg. area 1st Floor 2nd Floor
occupancy Type of Construction Valuation
3rd Floor 4th Floor
Allowable Increase Dueto
REQUIRED PLANS
1. Plot Plan 6. Structural Details
2. Foundation Plan 7. Elevation Plans
3. Floor Plan 8. Roof Plan
4. General Framing 9. Index Sheet
5. Foundation Details
TO THE APPLICANT
A. Correct Plans where corrections has been circled. Flag
Corrections.
B. Incomplete, Indefinite or Faded Drawings or Calcu-
lations not acceptable.
C. Required Engineer's or Surveyor's Calculations or
Plans shall be signed in ink.
D. Reverse Plans may not be used. Provide correct Plot
Plan, Foundation Plan, Floor Plan and Elevations.
E. The approval of plans and specifications does not
permit the violation of any section of the Building
Code'or other City, County or State Law.
GENERAL
1. Submit fully dimensioned Plot Plan, drawn to scale,
including all easements on property.
2. Show all existing and proposed buildings on Plot Plan.
4. Show all Off Site Improvements, Driveway Approach,
3. Show correct legal description on Plan.
Light Standards, Fire Hydrants, Water Meters, Sub
Structures. Trees. etc. I ~~
7. Survey of Lot required, rt*r p.u
lines OR 0 sfirfi*
Elevations of Garage Floor, and Street and
te all grading to be done.
10. Indicate Centerline and Edge Profile of Driveway.?
flow lines for disposal of surface water./ 0 *I Irl . riveway not to exceed
approval required.
Y
n Diego County Health Dept. approval required.
13bShow all requirements for handicapped. U.B.C.
receipt required.
letter required.
water from 14. Carry
under sidewalk through curb into street with cast
iron pipe.
15. Provide engineering calculations for
16. Provide engineer's moisture report.
17. Grading permit required.
18. Fire Dept. approval required.
19. Specify concrete mix @ 2000 P.S.I. minimum.
20. Dimension footing sizes and clearance from grade.
21. Show depth of footings below natural or undisturbed
22. Indicate pressure treated foundation still, or equal.
23. Show foundation bolt size, spacing and penetration
grade.
into concrete. %" x 17" for masonry.
24. Indicate clearance from grade to bottom of floor joists
25. Show pier size, spacing and depth, into undisturbed
26. Show girder size, spacing and direction.
, soil.
27. Show all conditions of soils report on plans.
28. Show positive drainage away from footings on site
29. Specify minimum 18" x 24" access opening.
30. Where expansive soils exist, planters adjacent to found-
ations are not recommended.
31. Specify underfloor ventilation equal to 2 square feet
for each 25 lineal feet of foundation plus one opening
within 3' of each corner.
and girders.
plan. 5" fall in 6 feet.
32. Step footings when slope exceeds 1: 10.
FRAMING
33. Provide typical framing details.
34. Specify all lumber grades.
35. Specify fire blocking at floor, ceiling cove and mid-
36. Show diagonal bracing at each corner and every 25
37. Clarify bracing of wall.
38. Show size, direction and spacing of floor joists in
39. Double floor joists or
40. Specify header size for openings over 4'. Show double
41. Insufficient beam size at
42. Provide rafter ties where ceiling joists and rafters are
not parallel. 4' O.C.
43. Indicate rafter size, span, spacing and direction.
44. Show purlins on edge and indicate size. Same size as
45. Brace roof framing to partitions.
46. Indicate solid sheathing and 2 x 6 or 3 x 4 studs on
47. Show section through
48. Show planter box details and water proofing, Sec.
51. Provide typical chimney details.
52. Specify 2" minimum clearance between chimney and
53. Specify post protection when bearing on concrete.
54. Provide parapet details.
56. Specify inspection class '
58. Provide drip screed 2" below mud sill.
59. Indicate how required structural and fire resistive
integrity will be maintained. Where penetration will
be made for electrical, mechanical, plumbing and
communications conduits, pipes and similar systems.
Section 301 D.
height of walls over 10' in height.
feet of wall.
are overspanned.
beam under parallel partitions.
headers on edge.
rafters minimum.
first floor of three story construction.
2517 C7.
framing.
required for
60. Clarify dimensions at
61. Show window type, sizes and locations.
62. Light andlor ventilation inadequate in
(1/10 floor area - 12 square feet min. except bath-
room).
63. Provide vertical clearance and
horizontal clearance from range top to combustibles. 64. Indicate attic scuttle (22” x 30” min.)
65. Provide draft separation for attic area in excess of
2500 sq. ft. 66. Separate area between dropped ceiling and floor above
to 1000 sq. ft. max.
67. Specify stall shower min. width 30” minimum floor
area 900 sq. inches.
68. Specify wall finish in shower area not to be adversely
affected by moisture to 6’ above the floor, and provide
shatterproof doors.
69. Water closet area minimum width to be 30”.
70. Show material to be used under tile.
71. Openings closer than
72. Show
73. Show lateral cross bracing at garage plate line.
74. Show bedroom window as exit, section 1304.
to property line shall be of
ceiling height.
hour construction.
4 ELEVATIONS
ndicate attic ventilation per section 3205 (c). 6. Show all eave overhangs and construction details.
77. Dimension chimney height above roof. (2’0” above
78. Indicate finish and natural grade to property line.
79. Show exterior wall finishes.
80. Indicate 15# felt or equal on exterior walls.
roof withing 10’0”).
ROOF
81. Note roof pitch.
82. Indicate roofing material length & weather exposure
83. Show type, size and spacing of roof sheathing.
84. Fire retardant roof required due to location in
on wood shingles.
fire zone.
GARAGES
86. Garages not permitted to open into sleeping room.
87. Provide separation on all walls
88. Specify doorlwindow opening
and ceilings adjacent to living quarters.
from garagelcarport into
STAIRWAYS AND EXITS
90. Provide handrails as required in Section 3305 (i).
92. Provide hour walls for stairwell.
93. Indicate maximum rise and minimum
95. Provide balcony railing at 42” minimum height. 36”
96. Provide intermediate rails @ 9” O.C. or equivalent
97. Indicate 6’ 6“ minimum headroom clearance above
98. Show stairway construction details.
run on stair.
O.K. for single family units.
for open type balcony & stair rails.
stairway.
100. Occupant load require-exits
101. Provide lights over stairways and public corridors.
102. Show change in floor level at doors 1” max. Sec.
3303h.
102aShow handrail extending 6” beyond the top & bottom
risers & terminating in a post or safety terminal Sec.
3305 (i).
from
4iV
PLUMBING
Show temperature and pressure relief valves on water
heaters with d-arqe lines to outside. Sec. 1007.
105. Water heater wo be located in bathroom or under
106. Provide
stairway or landing.
square inches of ventilation at top and
107. Show water heater on 18 inch platform.
bottom of water heater.
108. Provide water pressure regulator. Section 1007 (B).
dicate location of water heater.
+
110. indicate material to be used and location of sewer
line. (If V.C.P. use flexible compression joints only.)
11 1. Show two way clean out in yard box with 5’ of build-
ing.
ELECTRICAL
112. Provide minimum 100 Amp. service. Condos require
panel location.
. panel for each unit.
J warnings systems -.
MECHANICAL
114. Indicate furnace size, locations & registers and return
air. (Size) 3 F TEA+,
e&pment in accordance with chapter
and ventilating
with the uniform
mechanical code. .
A. Access F. Ducts
B. Location G. Ladder & Light
C. Combustion Air H. Engineer’s
D. Venting Calcs for
117. Indicate location & type of fire dampers. /2.&w#, c rte?“hdW Load h&MI
ELECTRIC
1975 N.E.C.
1. Ground-fault protection required for outdoor and
2. At least one receptical shall be installed outdoon
bathroom receptacles 210-8.
and garages. 210-25b
rrect electric as shown on floor plan.
ice is required. Show on plans.
LLANEOUS ITEMS AMP
1. Bored holes and notching, show detds as per Section
2. Provide . F . re s f h f 11 in :
2518, (F), 10, 11.
E. Place the following note on plans:
These plans comply with the requirements of the
California noise insulation standards.
SIGNED
DATE
TITLE
F. Show details of party wall and floor system and
S.T.C. or I.C.C. rating of each.
4. Have designer sign and date plans.
CHECKED
(DATE)
RECHECKED
(DATE)
THE FOREGOING CORRECTIONS HAVE BEEN MADE
AND ARE UNDERSTOOD BY THE UNDERSIGNED:
OWNER - OR HIS AUTHORIZED AGENT
LEUCADIA COUNTY WATER DISTRICT
APPLICATION FOR SEWER SERVICE
Owner's Name: Hubert 3. Moore Jr. Phone No. 753-3987
Mailing Address: 478 E .Street
Olivenhain CA 92024
Service Address: 2619 Abedul
Trnct Description: La Costa Meadows #1 Lot 95
Type of Building: - Single Family No. Units ~ Connection Charge $600.00
Lateral Size: 4"- 6" __ a" - Saddle: -
Extra footage: @ '$ Easement Connection -
Extra depth: @$ Lateral Charge
Total $600.00 1-1 Amount Rec'd $ 600.00
How Paid ck#385
Rec'd b S. Deibert
5. ae;.kx&
I The application must be signed by the owner (or his authorized representative) of the
application is submitted.
property to be served. The total charges must be paid to the District at the time the
If a service lateral is required, it will be installed by the Leucadia County Water
main collection line in the street (or easement) to the point in the street (at or nea:
District. The service lateral is that part of the sewer system tha.t extends from the
the applicant's property line) where the service lateral is connected to the applicant, S
building sewer. The applicanb. is responsible for the construction,. at the applicant,s
point in the street (or easement) where a connection is made to the service lateral.
expense, of the sewer pipeline (building sewer) from the applicant's plumbing to the
The connection of the applicant's building sewer to the service lateral shall be made
by the applicant at his,expense. The connection must be made in conformity with the
District's specifications, rules and regulations: and IT MUST BE INSPECTED AND APPROVED
BY THE DISTRICT BEFORE THE SEWER SYSTEM MAY BE USED BY THE APPLICANT. THE APPLICANT, OR
ANY CONNECTION MADE TO THE SERVICE LATERAL OR COLLECTION LINE WITHOUT PRIOR APPROVAL AND
HIS AUTHORIZED REPRESEWATIVE, MUST NOTIFY THE DISTRICT AT THE TlME INSPECTION IS DESIRED.
INSPECTION BY THE DISTRICT WILL BE CONSIDERED INVALJD AND WILL NOT BE ACKNOWLEDGED-
After connection is complete, the property described above is subject to a monthly
use of the property, single family, multiple dwelling or comercial.. Non-payment Of
sewer service charge, billed bi-monthly in advance. The rate will be governed by the
the sewer service charge is subject to a 5% penalty per month, plus disconnection if
necessary.
The undersigned hereby agrees that the above information given is Correct and agrees to
the conditions as stated:
6718
Account No.
INSULATION CERTIFICATION q'
t
This is to certify that insulation has been installed in conformance
with the current energy regulations, California Administrative Code,
Title 25, State of California, in the building located at:
EXTER1o~ Owens-Corning ana
Manufacturer Johns- Mansville Thickness/Type '3%"' Friction R-value11
CEILINGS
Batts: Manufacturer Johns-Manville Thickness/Type 6" Kraft R-value&
Owens-Corning ana
Blown: Manufacturer Thickness/Type - R-value-
R-value- Wt./Bag sq. Ft. Covered
FLOORS
Manufacturer Thickness/Type value-
GENERAL CONTRACTOR LICENSE !I
BY TITLE . . DATE
ORs, INC. LICENSE # 221517 C-2
-TITLE Vice Presi'dent DATE I