HomeMy WebLinkAbout2623 GATEWAY RD; 101; CB153848; PermitCity of Carlsbad
1635 Faraday Av Carlsbad, CA 92008
12-21-2015 Commercial/Industrial Permit Permit No: CB153848
Building Inspection Request Line (760) 602-2725
Job Address:
2623 GATEWAY RD CBADSt: 101
Permit Type:
TI Sub Type: COMM
Status:
ISSUED
Parcel No:
2131910900 Lot #: 0
Applied:
11/09/2015
Valuation:
$51,594.00 Construction Type: NEW
Entered By:
RMA
Occupancy Group:
Reference #
Plan Approved:
12/21/2015
Issued:
12/21 /2015
Inspect Area
Plan Check #:
Project Title:
BRAVO JEWELERS-1127 SF SHELL
TO RETAIL SPACE
Applicant:
Owner:
JORGE RICO
REGENCY BRESSI L L C
C/O CORNERSTONE REAL ESTATE ADVIS
241 14TH ST
100 WILSHIRE BLVD #700
SAN DIEGO CA 92101
SANTA MONICA CA 90401
619 508-7039
Building Permit
$414.42
Meter Size
Add'I Building Permit Fee
$0.00
Add'I Red. Water Con. Fee
$0.00
Plan Check
$290.09
Meter Fee
$0.00
Add'I Building Permit Fee
$0.00
SDCWA Fee
$0.00
Plan Check Discount
$0.00
CFD Payoff Fee
$0.00
Strong Motion Fee
$14.45
PFF (3105540)
$939.01
Park Fee
$0.00
PFF (4305540)
$0.00
LFM Fee
$0.00
License Tax (3104193)
$0.00
Bridge Fee
$0.00
License Tax (4304193)
$0.00
BTD #2 Fee
$0.00
Traffic Impact Fee (3105541)
$0.00
BTD #3 Fee
$0.00
Traffic Impact Fee (4305541)
$0.00
Renewal Fee
$0.00
PLUMBING TOTAL
$67.00
Add'I Renewal Fee
$0.00
ELECTRICAL TOTAL
$89.00
Other Building Fee
$0.00
MECHANICAL TOTAL
$51.83
Pot. Water Con. Fee
$0.00
Master Drainage Fee
$0.00
Meter Size
Sewer Fee
$0.00
Add'I Pot. Water Con. Fee
$0.00
Redev Parking Fee
$0.00
Red. Water Con. Fee
$0.00
Additional Fees
$0.00
Green Bldg Stands (SB1473) Fee
$3.00
HMP Fee
??
Fire Expedidted Plan Review
$0.00
Green Bldg Standards Plan Chk
??
TOTAL PERMIT FEES
$1,868.80
Total Fees: $1,868.80
Total Payments To Date:
$1,868.80 Balance Due:
$0.00
FINAL APPROVAL
Inspector: Date: 1 "ZG 14� Clearance:
NOTICE Please take NOTICE that apprrnral of your project includes the "Irrpositiori' of fees, dedications, reservations, or other exactions hereafter collectively
referred to as ' fees/exactions." You have 90 days from the date this pernit was issued to protest in position of these feestexactiors. If you protest them, you mst
fdloon the protest procedures set forth in CbiaTiment Cade Section 66020(a), and file the protest and any other required information with the City Manager for
processing in accordance with Carlsbad Ml nidp l Code Section 3.32.030. Failure to timely fdlow that prooedure will bar any subsequent legal action to attack,
review, set aside, void, or annul their irrposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and seiner- connection fees and capacity
changes, nor planning, zoning, grating or other similar application processing or service fees in connection with this project. NOR DOES ITAPPLY to any
THE FOLLOWING APPROVALS REQUIRED PRIOR TO PERMIT ISSUANCE: L PLANNING E ENGINEERING �_JBUILDING =FIRE , �:IHEALTH QHAZMATIAPCD
Building Permit Application
City of 1635 Faraday Ave., Carlsbad, CA 92008
Ph 760-602-2719 Fax: 760-602-8558
email: building@carlsbadca.gov i
Cildr-Isbad
www.carlsbadca.gov
Plan Check No. 5 V..
Est. Value
Plan Ck. Deposit
Date '
SWPPP
JOB ADDRESS
SUITE#/SPACES/UN #
APN
CT/PROJECT #
LOT #
PHASE #
# OF UNITS
111BEDROOMS
# BATHROOMS
I
TENANT BUSINESS NAME
p-wo, 3ao---�
CONSTR. TYPE
OCC. GROUP
DESCRIPTION OF WORK: Include Square Feet of AffectedArea(s) 00 CAP(�"-
4LLAJ -IDWr I -nL*P ; (-c,,) I 1 ) a7 SP ISPAf .
A env �5�c w "o-1 0> offi cc- . - �' PI Lrc 016F�
EXISTINGJJSE
PROPOSED SF_
`
LL.
GARAGE (SF)
PATIOS (SF)
CKS (SF)
FIREPLACE
YES# NO[::]YES
DINING
AIR CORIND❑
FIRE SPRIN LERS
YES N0[_]
APPLICANT NAME
Primary
^
PROPERTY OWNER _
ADDRESS
ADDRESS
Ivl
CITY Dolo STATE ZIP
D
CITY �� STAT ZIP6 ^ , 0
(i/►%v)
PHONE
FAX
PHONE
FAX
EMAIL
V
EMAIL
DESIGN OFES ONAL
COT T R BUS. E
e6Nrr
ADDRESS
ADD SS
. z� 1 (_,s
CITY STATE ZIP
CITY � STATE yi q, ZIP 02' 00�
C��
PHONE
FAX
PHONE. r`—
0 - I
FAX
EMAIL
EMAIL
STATE LIC. #
STATE LI .#
CLA S
CITY BUS. t,IC.
(Sec. 7031.5 Business and Professions Code: Any City or County which requires a permit to construct, alter, improve, demolish or repair any structure, prior to its issu�nie, also requires the
applicant for such permit to file a signed statement that he is licensed pursuant to the provisions of the Contractor's License Law (Chapter 9, commendingwith Section 7000 of Division 3 of the
Business and Professions Code) or that he is exempt therefrom, and the basis for the alleged exemption. Any violation of Section 7031.5 by any applicant for a permit subjects the applicantto a
civil penalty of not more than five hundred dollars ($500)).
Workers' Compensation Declaration: I hereby affirm under penalty of perjury one of the following declarations:
❑ I have and will maintain a certificate of consent to self -insure for workers' compensation as provided by Section 3700 of the Labor Code, for the performance of the work for which this permit is issued.
ElI have and will maintain workers' compensation, as required by Section 3700 of the Labor Code, for the performance of the work for which this permit is issued. My workers' compensation insurance carrier and policy
number are: Insurance Co, - Policy No. Expiration Date
This section need not be completed if the permit is for one hundred dollars ($100) or less.
9 Certificate of Exemption: I certify that in the performance of the work for which this permit is issued, I shall not employ any person in any manner so as to become subject to the Workers' Compensation Laws of
California. WARNING: Failure to secure workers' compensation coverage is unlawful, and shall subject an employer to criminal penalties and civil fines up to one hundred thousand dollars (&100,000), in
addition to the cost of compensation, damages as provided for in Section 3706 of the Labor code, interest and attorney's fees.
CONTRACTOR SIGNATURE �—AGENT DATE 12 "-
I hereby affirm that I am exempt from Contractor's License Law for the following reason:
❑ I, as owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not intended or offered for sale (Sec. 7044, Business and Professions Code: The Contractor's
License Law does not apply to an owner of property who builds or improves thereon, and who does such work himself or through his own employees, provided that such improvements are not intended oroffered for
sale. If, however, the building or improvement is sold within one year of completion, the owner -builder will have the burden of proving that he did not build or improve for the purpose of sale).
❑ I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions Code: The Contractor's License Law does not apply to an owner of
property who builds or improves thereon, and contracts for such projects with contractor(s) licensed pursuant to the Contractor's License Law).
I am exempt under Section Business and Professions Code for this reason:
1, 1 personally plan to provide the major labor and materials for construction of the proposed property improvement. Eles ❑No
2. 1 (have / have not) signed an application for a building permit for the proposed work.
3. 1 have contracted with the following person (firm) to provide the proposed construction (include name address / phone / contractors' license number):
4. 1 plan to provide portions of the work, but I have hired the following person to coordinate, supervise and provide the major work (include name / address / phone / contractors' license number):
5. 1 will provide some of the work, but I have contracted (hired) the following persons to provide the work Indicated (include name I address / phone / type of work):
PROPERTY OWNER SIGNATURE AGENT DATE
Is the applicant or future building occupant required to submit a business plan, acutely hazardous materials registration form or risk management and prevention program under Sections 25505, 25533 or 25534 of the
Presley -Tanner Hazardous Substance Account Act? Yes No
Is the applicant or future building occupant required to obtain a permit from the air pollution control district or air quality management district? Yes No
Is the facility to be constructed within 1,000 feet of the outer boundary of a school site? Yes No
IF ANY OF THE ANSWERS ARE YES, A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR IS MEETING THE REQUIREMENTS OF THE OFFICE OF
EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT.•
I hereby affirm that there is a construction lending agency for the performance of the work this permit is issued (Sec. 3097 (i) Civil Code).
Lender's Name
Lender's Address
I certify that l have read the application and state thatthe above information is correct and that the information on the plans is accurate. l agree to comptyvdth all City ordinances and State laws relating to building construction.
i
I hereby authorize representative of the City of Carlsbad to enter upon the above mentioned property for inspection purposes. I ALSO AGREE TO SAVE, INDEMNIFY AND KEEP HARMLESS THE CITY OF CARLSBAD
AGAINST ALL LIABILITIES, JUDGMENTS, COSTS AND EXPENSES WHICH MAY IN ANY WAY ACCRUE AGAINST SAID CITY IN CONSEQUENCE OF THE GRANTING OF THIS PERMIT.
OSHA: An OSHA permit is required for excavations over 5'0' deep and demolition or construction of structures over 3 stories in height.
EXPIRATION: Every permit issued by the Building Official under the provisions of this Code shall expire by limitation and become null and void if the building or work authorized by such permit is not commenced within
180 days from the date of such permit or if the building or work authorized by such permit is suspended or abandoned at any time after the work is commenced for a period of 180 days (Section 106.4.4 Uniform Building Code).
APPLICANT'S SIGNATURE DATE
STOP: THIS SECTION NOT REQUIRED FOR BUILDING PERMIT ISSUANCE.
Complete the following ONLY if a Certificate of Occupancy will be requested at final inspection.
Fax (760) 602-8560, Email building(ODCarlsbadca.goV or Mail the completed form to City of Carlsbad, Building Division 1635 Faraday Avenue, Carlsbad, California 92008.
Co#: (Office Use Only)
CONTACT NAME
OCCUPANT NAME
ADDRESS
BUILDING ADDRESS
CITY STATE ZIP
CITY STATE ZIP
Carlsbad CA
PHONE
FAX
EMAIL
OCCUPANT'S BUS. LIC. No.
DELIVERY OPTIONS
PICK UP: CONTACT (Listed above) OCCUPANT (Listed above)
CONTRACTOR (On Pg. 1)
ASSOCIATED CB#
MAIL TO: CONTACT (Listed above) OCCUPANT (Listed above)
CONTRACTOR (On Pg. 1)
NO CHANGE IN USE / NO CONSTRUCTION
MAIL / FAX TO OTHER:
CHANGE OF USE / NO CONSTRUCTION
A!SAPPLICANT'S SIGNATURE
DATE
Inspection List
Permit#: CB153848 Type: TI
COMM
BRAVO JEWELERS-1127 SF SHELL
TO RETAIL SPACE
Date Inspection Item
Inspector
Act
Comments
01/26/2016 89
Final Combo
-
RI
3:00 IF POSSIBLE/NRR
01/26/2016 89
Final Combo
PB
AP
01/22/2016 89
Final Combo
-
RI
AROUND NOON IF POSSIBLE
01/22/2016 89
Final Combo
PB
CA
01/21/2016 85
T-Bar
PB
AP
01/21/2016 89
Final Combo
-
RI
PM PLEASE
01/19/2016 89
Final Combo
PB
NR
01/19/2016 89
Final Combo
-
RI
NRR/10:00 IF POSSIBLE
01/15/2016 19
Final Structural
PB
CA
01/15/2016 89
Final Combo
-
RI
FIRE @ 10/WILL EMAIL CARD/PM
INSPECT
01/06/2016 85
T-Bar
PB
NR
12/28/2015 17
Interior Lath/Drywall
PB
AP
12/25/2015 21
Underground/Under Floor
PB
AP
12/25/2015 31
Underground/Conduit-Wirin
PB
AP
12/25/2015 84
Rough Combo
PB
AP
12/22/2015 84
Rough Combo
PB
NR
Wednesday, January 27, 2016 Page 1 of 1
EsGil Corporation
In Partnership with Government for Bui(ding Safety
DATE: 12/ 17/2015 ❑ PLICANT
JURIS.
JURISDICTION: Carlsbad ❑ PLAN REVIEWER
❑ FILE
PLAN CHECK NO.: CB15-3848 SET: II
PROJECT ADDRESS: 2623 Gateway Rd.
PROJECT NAME: Bravo Jewelers TI
❑ The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
❑ The plans transmitted herewith will substantially comply with the jurisdiction's
codes when minor deficiencies identified below are resolved and checked by building
department staff.
❑ The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
❑ The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
❑ The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
❑ The applicant's copy of the check list has been sent to:
❑ EsGil Corporation staff did not advise the applicant that the plan check has been completed.
❑ EsGil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Telephone #:
Date contacted: ..-- (by*
b Email:
Mail Telephone Fax In Person
❑ REMARKS:
By: John Le Vey Enclosures:
EsGil Corporation
❑ GA ❑ EJ ❑ MB ❑ PC 12/10/2015
9320 Chesapeake Drive, Suite 208 ♦ San Diego, California 92123 ♦ (858) 560-1468 ♦ Fax (858) 560-1576
EsGil Corporation
In Partnership with Government for Buirding Safety
DATE: 11 / 19/2015 Ll.$,PPLICANT
JURIS.
JURISDICTION: Carlsbad ❑ PLAN REVIEWER
❑ FILE
PLAN CHECK NO.: CB15-3848 SET: I
PROJECT ADDRESS: 2623 Gateway Rd.
PROJECT NAME: Bravo Jewelers TI
❑ The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's codes.
❑ The plans transmitted herewith will substantially comply with the jurisdiction's
codes when minor deficiencies identified below are resolved and checked by building
department staff.
❑ The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
❑ The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
❑ The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
❑ The applicant's copy of the check list has been sent to:
❑ EsGil Corporation staff did not advise the applicant that the plan check has been completed.
❑ EsGil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Jorge Rico
Date contacted: \ 8 (by�\�
Mail ephone, Fax In Person
❑ REMAR �.
By: John Le Vey
EsGil Corporation
❑ GA ❑ EJ ❑ MB ❑ PC
Telephone #: 619-508-7039
Email: jorgericodesign@yahoo.com
Enclosures:
11/10/2015
9320 Chesapeake Drive, Suite 208 ♦ San Diego, California 92123 ♦ (858) 560-1468 ♦ Fax (858) 560-1576
Carlsbad CB 15-3848
11/19/2015
PLAN REVIEW CORRECTION LIST
TENANT IMPROVEMENTS
PLAN CHECK NO.: CB15-3848
IOCCUPANCY.- M
TYPE OF CONSTRUCTION: VB
JALLOWABLE FLOOR AREA:
SPRINKLERS?: Yes
REMARKS:
DATE PLANS RECEIVED BY
JURISDICTION: 11/09/2015
DATE INITIAL PLAN REVIEW
COMPLETED: 11/ 19/2015
FOREWORD (PLEASE READ):
JURISDICTION: Carlsbad
USE: jewelry sales
ACTUAL AREA: 1,127
STORIES: 1
HEIGHT: unknown
OCCUPANT LOAD: 23
DATE PLANS RECEIVED BY
ESGIL CORPORATION: 11/10/2015
PLAN REVIEWER: John Le Vey
This plan review is limited to the technical requirements contained in the California version of
the International Building Code, Uniform Plumbing Code, Uniform Mechanical Code, National
Electrical Code and state laws regulating energy conservation, noise attenuation and access for
the disabled. This plan review is based on regulations enforced by the Building Department.
You may have other corrections based on laws and ordinances enforced by the Planning
Department, Engineering Department, Fire Department or other departments. Clearance from
those departments may be required prior to the issuance of a building permit.
Code sections cited are based on the 2013 CBC, which adopts the 2012 IBC.
The following items listed need clarification, modification or change. All items must be satisfied
before the plans will be in conformance with the cited codes and regulations. Per Sec. 105.4 of
the 2012 International Building Code, the approval of the plans does not permit the violation of
any state, county or city law.
To speed up the recheck process, please note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet number, specification section, etc
Be sure to enclose the marked up list when you submit the revised plans
Carlsbad CB 15-3848
11/19/2015
Please make all corrections, as requested in the correction list. Submit FOUR new
complete sets of plans for commercial/industrial projects (THREE sets of plans for
residential projects). For expeditious processing, corrected sets can be submitted
in one of two ways:
1. Deliver all corrected sets of plans and calculations/reports directly to the City of
Carlsbad Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760)
602-2700. The City will route the plans to EsGil Corporation and the Carlsbad
Planning, Engineering and Fire Departments.
2. Bring one corrected set of plans and calculations/reports to EsGil Corporation,
9320 Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-1468.
Deliver all remaining sets of plans and calculations/reports directly to the City of
Carlsbad Building Department for routing to their Planning, Engineering and Fire
Departments.
NOTE: Plans that are submitted directly to EsGil Corporation only will not be
reviewed by the City Planning, Engineering and Fire Departments until review by
EsGil Corporation is complete.
Each sheet of the plans must be signed by the person responsible for their
preparation, even though there are no structural changes. California State Law.
2. Please correct the plans the occupancy is an M not a B
3. Please provide on the door schedule; indicate the type of hardware and
reference the door schedule.
4. Provide a section view of all new interior partitions. Show. -
a) Type, size and spacing of studs. Indicate gauge for metal studs.
b) Method of attaching top and bottom plates to structure. (NOTE: Top of
partition must be secured to roof or floor framing, unless suspended
ceiling has been designed for partition lateral load).
c) Show height of partition and suspended ceiling, and height from floor to
roof framing or floor framing. Your details do not show the connections or
the spacing of the attachment at the sole or the top plate
5. For plans submitted for plan check on or after 7/1/14, provide a Prescriptive or
Performance energy design, demonstrating compliance with current 2013 energy
efficiency standards. Information and Forms are available at: for the mechanical.
also you state no new lighting however I see new pendent lighting on the plans
www.energy.ca.gov/title24/2013standards
6. A complete energy plan check will be performed after completed and/or
corrected energy design has been provided.
7. Please provide a service or laundry sink per the CPC table 422.1
Carlsbad CB 15-3848
11/19/2015
8. When new rooms or spaces are constructed and the existing mechanical system
is not to be altered other than relocation of existing duct work; please note or
show mechanical ventilation will be provided capable of supplying the minimum
rate of outside air required per minute per occupant as shown in table 402.1 of
2013 CMC .
Advisory Note : When alterations, structural repairs or additions are made to an
existing building, that building, or portion of the building affected, is required to
comply with all of the following requirements, per Section 11 B-202.4:
• The area of specific alteration, repair or addition must comply as "new"
construction.
• Please address the following comments that are the result of the alterations.
9. Sales and service counters shall have a portion of the counter which is at least 36"
in length with a maximum height of 34 inches. Section 11 B-904.4.1. or reference
the detail on sheet AD2 to the floor plan
To speed up the review process, note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet, note or detail number,
calculation page, etc.
Please indicate here if any changes have been made to the plans that are not a
result of corrections from this list. If there are other changes, please briefly
describe them and where they are located in the plans.
Have changes been made to the plans not resulting from this correction
list? Please indicate: ❑ Yes ❑ No
The jurisdiction has contracted with Esgil Corporation located at 9320
Chesapeake Drive, Suite 208, San Diego, California 92123; telephone number of
858/560-1468, to perform the plan review for your project. If you have any
questions regarding these plan review items, please contact John Le Vey at
Esgil Corporation. Thank you.
Carlsbad CB 15-3848
11/19/2015
ADO NOT PAY- THIS IS NOT AN INVOICE]
VALUATION AND PLAN CHECK FEE
JURISDICTION: Carlsbad PLAN CHECK NO.: CB15-3848
PREPARED BY: John Le Vey DATE: 11/19/2015
BUILDING ADDRESS: 2623 Gateway Rd.
BUILDING OCCUPANCY: M
BUILDING
PORTION
AREA
( Sq. Ft.)
Valuation
Multiplier
Reg.
Mod.
VALUE ($)
TI
51,594
Air Conditioning
Fire Sprinklers
TOTAL VALUE
51,594
Jurisdiction Code Icb IBy Ordinance
Bldg. Permit Fee by Ordinance
Plan Check Fee by Ordinance
Type of Review
❑ Repetitive Fee
Repeats
21 Complete Review
❑ Other
❑ Hourly
EsGil Fee
❑ Structural Only
Hr. @*
$409.96
$266.47
$22 58
Comments: Sheet of
macvalue.doc +
Aft,
74
C ! TY OF
CARLSBAD
PLAN CHECK
REVIEW
TRANSMITTAL
DATE: 11/23/2015 PROJECT NAME: B EWE LE RS Ti
PLAN CHECK NO: 1, SET#: I ADDRESS: 2623 GATEWAY
VALUATION: $51,5914
a
Community & Economic
Development Department
1635 Faraday Avenue
Carlsbad CA 92008
www.carlsbadca.gov
PROJECT ID:CB153848
This plan check review is complete and has been APPROVED by:
LAND DEVELOPMENT ENGINEERING DIVISION
APN: 2131.910900
Final Inspection by the Construction Management Division is required Yes X No
This plan check review is NOT COMPLETE. Items missing or incorrect are listed on
the attached checklist. Please resubmit amended plans as required.
Plan Check Comments have been sent to: JORGERICODESIGN@YAHOO.COM
❑ Linda Ontiveros
760-602-2773
Linda.Ontiveros@carlsbadca.gov
F—z-1 ValRay Nelson
760-602-2741
Val Ray. Nelson@carlsbadca.gov
For questions or clarifications on the attached checklist please contact the reviewer as marked above.
Remarks:
R.I:tAVO JEW l_ERS 1-1
1
E
Outstanding am rnarkod tuith . t'leasc make the necessary coi,rectitirts /'or
cantpliancc with applit-f ble codes and standards and re -submit corrccted plrtrt.s uud!or
specifications Io the Bltildin<,, division. (tents that coat/arm to perinit requirements are
marked 2vit11 / --or- have intentionally beeat left Wank.
1. SITE PLAN
Provide a fully dimensioned site plan drawn to scale.
Show:
V North arrow
V Existing & proposed structures
Property line dimensions
Easements
Show on site plan:
Drainage patterns
Existing & proposed slopes
Existing topography
Retaining Walls (location and height)
Indicate what will happen with soil excavated from pool area.
Include on title sheet:
✓ Site address
V Assessor's parcel number
Legal description/lot number
,d For all commercial/industrial building and tenant improvements, include: total building square
footage with the square footage fore each different use, showing square footage of different
uses (manufacturing, storage, warehouse, office, etc.) Example:
10,900 sf of SHELL to 10,900 sf OFFICE
7,000 sf of SHELL to 7,000 sf STORAGE
3,900 sf of SHELL to 3900 sf MANUFACTURING
Lot / Map No,:
Subdivision/Tract
Reference No(s): ORIGINALLY FEED AS 5000SF OFFICE SPACE
E-37 Page 2 of 4 REV 6/2012
BRAVO IEVVELERS TI
2. GRADING PERMIT REQUIREMENTS
1.
The conditions that require a grading permit are found in Section 11.06.030 of the Municipal
Code.
Inadequate information available on site plan to make a determination on grading
requirements. Include accurate grading quantities in cubic yards (cut, fill, import, export and
remedial). This information must be included on the plans. If no grading is proposed
write: "NO GRADING"
Minor Grading Permit required. NOTE: The grading permit must be issued and grading
approval obtained prior to issuance of a building permit. A separate grading plan prepared a
registered civil engineer must be submitted together with the completed application form attached.
Graded Pad Certification required. All required documentation must be provided to your
Construction Management & Inspection division inspector, . The
inspector will then provide the Land Development Engineering counter with a release for the
building permit. See attached checklist for minimum submittal requirements.
3. MISCELLANEOUS PERMITS
V RIGHT-OF-WAY PERMIT is required to do work in city right-of-way and/or private work
adjacent to the public right-of-way.
A separate right-of-way issued by the engineering division is required for the following:
N /A,
Attachments: Engineering Application Storm Water Form Right -of -Way Application/Info V Reference Documents
E-37 Page 3 of 4 REV 6/2012
_WaIVF OF FEES 1 HAT MAY BE DUE FOR THIS PF OjECT***
Fee Calculation Worksheet
ENGINEERING DIVISION
Prepared by: VALRAY NELSON Date:11/2312015 GEO DATA:LFMZ: / B&T:
Address: 2623 GATEWAY Bldg. Permit #: CB153848
Fees Update by: Date: Fees Update by: Date:
EDU CALCULATIONS: List types and square footages for all uses.
Types of Use: OFFICE CREDIT Sq.Ft./Units EDU's:
Types of Use: RETr, .. Sq.Ft./Units EDU's: FEES
Types of Use: Sq.Ft./Units EDU's:
Types of Use: Sq.Ft./Units EDU's:
ADT CALCULATIONS: List types and square footages for all uses.
Types of Use: OFFICE CREDIT Sq.Ft./Units 20/1000 ADT's:
Types of Use , ` ` , [; Sq.Ft./Units '` I k ON
ADT's: � / I ,{r I0 4
Types of Use:
Sq.Ft./Units 112711000=1
ADT's: 1'20=20
Types of Use:
Sq.Ft./Units
ADT's:
FEES REQUIRED:
Within CFD: v YES (no bridge & thoroughfare fee in District #1, reduces Traffic Impact Fee)
1. PARK -IN -LIEU FEE: NW QUADRANT
NE QUADRANT
SE QUADARANT
ADT'S/UNITS:
X FEE/ADT:
=$
23RAFFIC IMPACT FEE:
ADT'S/UNITS: 20
X FEE/ADT: 107
=$ 2140
3. BRIDGE & THOROUGHFARE FEE:
DIST. #1
DIST.#2
ADT'S/UNITS:
X FEE/ADT:
=$
4. FACILITIES MANAGEMENT FEE
ZONE:
ADT'S/UNITS:
X FEE/SQ.FT./UNIT:
=$
5. SEWER FEE
EDU's
BENEFIT AREA:
EDU's
6. DRAINAGE FEES:
ACRES
7. POTABLE WATER FEES:
UNITS ( CODE
X FEE/EDU:
NO
SW QUADRANT
X FEE/EDU: I =$
PLDA: HIGH MEDIUM LOW
X FEE/AC: =$
CONN. FEE I METER FEE I SDCWA FEE
DIST.#3
TOTAL
PLANNING DIVISION Development Services
BUILDING PLAN CHECK
Planning Division
C I T Y O F APPROVAL 1635 Faraday Avenue
AR �,,,, P-29 (760) 602-4610
www.carlsbadca.eov
DATE: 11/10/2015 PROJECT NAME: RETAIL TENANT IMPROVEMENT PROJECT ID:
PLAN CHECK NO: CB153848 SET#: 1 ADDRESS: 2623 GATEWAY APN:
® This plan check review is complete and has been APPROVED by the PLANNING
Division.
By: VERONICA MORONES
A Final Inspection by the PLANNING Division is required ❑ Yes ® No
You may also have corrections from one or more of the divisions listed below. Approval
from these divisions may be required prior to the issuance of a building permit.
Resubmitted plans should include corrections from all divisions.
This plan check review is NOT COMPLETE. Items missing or incorrect are listed on
the attached checklist. Please resubmit amended plans as required.
Plan Check APPROVAL has been sent to:
For questions or clarifications on the attached checklist please contact the following reviewer as marked:
PLANNING
ENGINEERING
FIRE PREVENTION
760-602-4610
760-602-2750
760-602-4665
Chris Sexton
j Chris Glassen
Greg Ryan
760-602-4624
760-602-2784
760-602-4663
Chris.Sexton@carlsbadca.gov
Christop_her.Glassen@carlsbadca.i�ov
Gre or .Ryan ccarlsbadca-.-g—ov
❑
Gina Ruiz
ValRay Marshall
Cindy Wong
760-602-4675
760-602-2741
760-602-4662
Gina.Ruiz@carlsbadca.ov
VaIRAyMarshall@carl_sbadc__a,goy
Cy_nthia_Wong@carlsbadca.gov
V\jVeronica
Morones�
Linda Ontiveros
C]
Dominic Fieri
760-602-4619
760-602-2773
760-602-4664
Veronica.Morones@carlsbadca.gov
Linda Ontiveros@carlsbadca. ov
Dominiclieri@carlsbadca. ov
Remarks: RETAIL TO RETAIL IN C-L ZONE TENANT IMPROVEMENT: PARTITIONING
OF WALLS; ADDITION OF: SHOWROOM, EMPLOYEE AREA, REPAIR AREA, AND
OFFICE SPACE. HVAC DENOTED IN PLANS IS ADDITION OF EXHAUST VAN ONLY.
Shay Even �Jk91—
From: Christina Wilson
Sent: Monday, November 09, 2015 4:59 PM
To: jorgericodesign@yahoo.com; Building
Subject: CB153848 Bravo Jewelers plans do not need Carlsbad Fire Dept. plan review
Jorge,
CB153848 Bravo Jewelers plans do not need Carlsbad Fire Dept. plan review.
Thank you,
Chris
alto' o
-I lsba .
Christina Wilson
Fire Prevention Secretary
City of Carlsbad
1635 Faraday Ave.
Carlsbad, CA 92008-7314
Uvww.carlsbadca.g ov
P 760-602-4665 phone I F 760-602-8561
Cityof
Carlsbad
Project Address:
PLUMBING,
ELECTRICAL,
MECHANICAL
WORKSHEET
B-18
Development Services
Building Division
1635 Faraday Avenue
760-602-2719
www.carlsbadca.gov
Building@carlsbadca.gov
Permit No.:
Information provided below refers to woriz being done on the above mentioned permit only.
This form must be completed and returned to the Building Division before the permit can be issued.
Building Dept. Fax: (760) 602-8558
Number of new or relocated fixtures, traps, or floor drains .....................................
New building sewer line?......................................................................................... Yes
No
Number of new roof drains?...............................................................................................................
I
IN%
Install/after water line?.........................................................................................................................
Numberof new water heaters?.........................................................................................................
Number of new, relocated or replaced gas outlets?....................................................................
Number of new hose bibs?..................................................................................................................
Residential Permits:
New/expanded service: Number of new amps:
Minor Remodel only. Yes No
Commercial/Industrial:
Tenant Improvement: Number of existing amps involved in this project
Number of new amps involved in this project
New Construction: Amps per Panel:
Single Phase............................................................... Number of new amperes
Three Phase................................................................. Number of new amperes
Three Phase 480........................................................ Number of new amperes
Number of new furnaces, A/C, or heat pumps?.........................................................../............... t
New or relocated duct woriz?.......................................................................... Yes V No
Numberof new fireplaces?.................................................................................................................
Number of new exhaust fans?............................................................................................................
Relocate/install vent?............................................................................................................................ _
Number of new exhaust hoods?........................................................................................................
JSK
Number of new boilers or compressors?........................................................... Number of HP
B-18 Page 1 of 1 Rev. 03/09