HomeMy WebLinkAbout2623 GATEWAY RD; ; PCR14068; Permit04-28-2014
City of Carlsbad
1635 Faraday Av Carlsbad.CA 92008
Plan Check Revision Permit No:PCR14068
Building Inspection Request Line (760) 602-2725
Job Address:
Permit Type:
Parcel No:
Valuation:
Reference #:
PC #:
Project Title:
2623 GATEWAY RD CBAD
PCR
2131910900 Lot#: 0
$0.00 Construction Type: 5B
CB133168
DEFERRED SUBMITTAL OF TRUSS
Status:
Applied:
Entered By:
Plan Approved:
Issued:
Inspect Area:
ISSUED
04/18/2014
JMA
04/28/2014
04/28/2014
Applicant:
BROCK NEWMAN
714-926-3542
Owner:
REGENCY BRESSI LLC
c/o CORNERSTONE REAL ESTATE ADVIS
100 WILSHIRE BLVD #700
SANTA MONICA CA 90401
Plan Check Revision Fee
Fire Expedited Plan Review
Additional Fees
$125.00
$0.00
$0.00
Total Fees: $125.00 Total Payments To Date: $125.00 Balance Due: $0.00
Inspector:
FINALAPPROVAL
Date: Clearance:
NOTICE: Please take NOTICE that approval of your project includes the "Imposition" of fees, dedications, reservations, or other exactions hereafter collectively
referred to as "fees/exactions." You have 90 days from the date this permit was issued to protest imposition of these fees/exactions. If you protest them, you must
follow the protest procedures set forth in Government Code Section 66020(a), and file the protest and any other required information with the City Manager for
processing in accordance with Carlsbad Municipal Code Section 3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack,
review, set aside, void, or annul their Imposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection fees and capacity
changes, nor planning, zoning, grading or other similar application processing or service tees in connection with this project. NOR DOES IT APPLY to any
fees/exactions of which vou have previously been given a NOTICE similar to this, or as to which the statute of limitations has previously othenwise expired.
^ CITY OF
CARLSBAD
PLAN CHECK REVISION
APPLICATION
B-15
Development Services
Building Division
1635 FaradayAvenue
760-602-2719
www.carisbadca.gov
Plan Check Revision No. ^^^^ IM ' ^8 Original Plan Check No C31^*^/6^
Project Address 2.ifc^'3> G^^^^c^y i^d. Date ^(^'^JM
Contact 9jfoc^ Ai^i^^W JjlM}W^^^f^ Fax
Email •Jir^
Contact Address City_ .Zip. f^s-^)
General Scope of Work QeJ^^'"^ S^L^.^t^ ^^Vr^', ^rr^^^^ks.
Original plans prepared by an architect or engineer, revisions must be signed & stamped by that person.
1 • Elements revised:
Plans Calculations • Soils • Energy • Other ^^^^^ SA^'^-h^f
2.
Describe revisions in detail
3.
List page(s) where
each revision is
shown
4.
List revised sheets
that replace
existing sheets
5. Does this revision, in any way, alter the exterior of the project? • Yes
6. Does this revision add ANY new floor area(s)? QYes No
7. Does this revision affect any fire related issues? O Yes ^ No
tier No
8. Is this a complete set?
js^ Signature:
No
1635 Faraday Avenue, Carisbad, CA 92008 Ph: 760-602- 2719 Fax: 760-602-8558 Email: buiiding@carlsbadca.gov
www.carisbadca.gov
EsGil Corporation
In (Partnersliip witA government for (BuiCding Safety
DATE: April 24, 2014 • APPLICANT
• JURIS.
JURISDICTION: Carisbad • PLANREVIEWER
• FILE
PLANCHECKNO.: 13-3168 REV SET: I
PROJECTADDRESS: 2623 Gateway Rd.
PROJECT NAME: Pad Building A; Bressi Ranch Village Center TRUSSES
I I The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's codes.
^ The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
I I The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
I I The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
I I The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
I I The applicant's copy of the check list has been sent to:
1X1 EsGil Corporation staff did not advise the applicant that the plan check has been completed.
I I EsGil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Telephone #:
Date contacted: (by: ) Email: Fax #:
Mail Telephone Fax In Person
XI REMARKS: Provide evidence that the engineer-of-record (or architect) has reviewed the truss
calculation package prepared by others (i.e., a "review" stamp on the truss calculations or a
letter). \.
By: Kurt Culver Enclosures: Previously-approved
EsGil Corporation plans
• GA • EJ • MB • PC 4/21/14
9320 Chesapeake Drive, Suite 208 • San Diego, Califomia 92123 • (858) 560-1468 • Fax (858) 560-1576
Carlsbad 13-3168 REV
April 24, 2014
[DO NOT PAY- THIS IS NOTAN INVOICE]
VALUATION AND PLAN CHECK FEE
JURISDICTION: Carlsbad PLANCHECKNO.: 13-3168 REV
PREPARED BY: Kurt Culver DATE: April 24, 2014
BUILDING ADDRESS: 2623 Gateway Rd.
BUILDING OCCUPANCY: TYPE OF CONSTRUCTION:
BUILDING
PORTION
AREA
(Sq. Ft.)
Valuation
Multiplier
Reg.
Mod.
VALUE ($)
Shell 5000 54.12 270,600
Air Conditioning
Fire Sprinklers
TOTAL VALUE 270,600
Jurisdiction Code cb By Ordinance
BIdg. Permit Fee by Ordinance
Plan Check Fee by Ordinance
Type of Review:
• Repetitive Fee
Repeats
• Complete Review
• Other
EsGil Fee
• Structural Only
1
$100.00
Hr. @
$125.00
$100.00
Based on hourly rate
Comments:
Sheet 1 of 1
macvalue.doc +
KPRS
License # 751130
2850 Saturn Street
Brea, CA 92821
SUBMITTAL
NO. 06100-001
PACKAGE NO: 06100
Phone: 714 672-0800
Fax: 714 672-0871
TITLE: Rough Carpentry
PROJECT: Bressi Ranch Village Pad A-Carlsbad
DRAWING:
STATUS: NEW
BIC: MASCWARN
REQUIRED START: 4/15/2014
REQUIRED FINISH: 4/17/2014
DAYS HELD: 0
DAYS ELAPSED: 0
DAYS OVERDUE: -2
RECEIVED FROM
HCC RM
Revision
No. Description / Remarks
SENT TO
MASCWARN AW
RETURNED BY
MASCWARN AW
FORWARDED TO
HCC RM
Received Sent
Drawing
Returned Forwarded Status Sepias Prints Date Held Elapsed
001 Truss Shops 4/15/2014 4/15/2014
Please see attached Truss Shop Drawings for your review and approval.
NEW 0 0 0 0
SUBMITTAL NO
KPRS CONSTRUCTION SERVICES, INC.
SUBMITTAL REVIEW
I X 1 REVIEWED 1^ RESUBMIT
06100-001
REVIEWED FOR GENERAL COMPLIANCE WITH REFERENCE TO PLANS AND
SPECIFICATION ONLY. THIS REVIEW DOES NOT RELIEVE THE
SUBCONTRACTOR OF THE RESPONSIBILITY FOR MAKING THE WORK
CONFORM TO THE REQUIREMENTS OF THE CONTRACT THE
SUBCONTRACTOR IS RESPONSIBLE FOR ALL FIELD CONDITIONS
DIMENSIONS, CURRENT FABRICATION, COORDINATION AND ACCURATE
FIT WITH WORK OF OTHER TRADES.
4/15/2014
Brock Newman BY DATE
^ GSSI Engineers
9 Reviewed as Noted
O Revise and Resubmit
This Review Shall Not Relieve The Contractor
From Full Compliance With The Contract
Documents And Applicable Codes.
Date 4-17-14 B\f B. Schell
No Exceptions Taken
FIRE SPRINKLER ATTACHMENT NOTES:
1. DO MOT MU. MUS. INW MAW tOVM, Ot UK LM BOLTf M IHC KXIW FUMOE tr IrJOttT^ PtPT AJ MOID KUK
LMS k SCnw 10 K MKTULB) IV lURNMe WW k TOO. NOT MMNe MW A HUMGR. 5. COqmtMIC ATTACHMMT OF VWMEt PIPt SKEHBt IHMI I* OMHCIEN AND LMOEK MTH
KJOttr LAVDUTMD CALCUUIKMS. UTR HAS AMMW IHAT THCDMMRV nKOW
HAS Aooara^ ran mtnoi VMNLOI uwirBUMnn AM USS
4. PWMU. HOUS OKATDI DUM MAkCIDt NIO FUMGD.
[AIFLWQE CUWP CQWNECTED TO I-JOST BOTTOM CHORO
fSlcOM^H SCREW C0W4ECTED TO I-JOST BOTTOM CHOBD
fclffOD CQNNKJTED TO 2K TROPEZED BE7¥IEEN I~JCHST
[DIROP COWCCTED TO I-JOST WEB RLUR
[EIO-HOOK & F.S. HOD COWNECTEP TD KOIST WEB FILLER
fFlFLWOE CONNECTED TO l-gOST BOTTOM CHORQ
ATTACHMENT DEMILS
IIL
^111
BE DETMLEO AND SUBMrfTED TO UFR POR <•
DTPICAL DETAIL NOTES:
1. PRC-DRU. FOR Ml SCREWS GREATER THAN 1/4*»
2. POINT UMDS CREATOt THAN IXf REOURE A DETAU. PREPAKO
Br OTHERS AW) SUBMrTTED FOR APPROVAL
3. t/4*< SCREWS OR LESS ARE AUJMED M THE ^ OF EITHER THE
TOP OR BOTTOM CHOTO.
'im ii y MAMMOM CQ«H SCREW OR
It -*S2i^ SOSPENOCD CEIUNO ETE BOLT
TO LOCATIOM CONDITION C TO LoSTlKN
V UWOMUM SCREW OR 2-104 MAXMUM NAILS PER
CONNECTKM (2 COWCCTKWS PER TRUSS). OR flO
SCREW INTO SIDE FACE OF TOP OR BOTTOM CHORD
DIRECT APPUED RESHIENT CHANICL Af40/0R I «•
(WPSOM BOARD CEILINO, USE #10 SCREWS urii**"
MAXIMUM, NO RESTRKTiONS
CONDITTON E
AU SCREWS SHALL BE OFFKT FROM WEB
1/2' M CROSS SECTON.
CQNPmON F
FLANOE Cl/MP - NO EXCEPTORS
(T/O SNOMIj l/C SM.)
TOP AND BOTTOM CHORD ATTACHMENT DETAILS
PLUMBINGALECTRICAL/CEIUNG
EL-
i I 4^
BLOCKING P^ANEL iNSTALlATlON
DO NOT CUT TOP AND TOTTOM FLANGES
HOLE a;E ANP LOCATIOH PETAIL
ss
' SX'^'"'*'''*''''^***^-'
WEB STIFFENER ATTACHMENT
tn M{IL1\-^1SJ ASSEMBLY
TyP!f4f. .l^JOfSr PffCUECT NOTES.-
li n» ms HUT NU. K w
A icTAi ISMM MUM Wt vm rm snswe MNMS MAT AIC MUD
It >-Mm MK HOT mw w M««R Mfr rm mmni*
M iSl'liMCHf MM
INSTALLATION OF t-JOISTS
I
Pi
Ql 5
Hi Ill
1
I
I
CQli
SHEET
1 OF 2
I MOTE: AU. MBC STVFENERS/nuER BUtS ARE Wf OTHERS
NOTE: ROTATE ROOF DRAWS
AS REO'D TD FTT BOWEEN
TYP SPACED JOISTS
pimjecTiijwsiJs^ •
SHEETS OATE
AUCHITECTWIL OIMIMNOS
Al.l THRU AB.9 01/31/14 A
smucnMALomimtas
Sl.l THRU S4.2 01/31/14 A
MECHV/iCMatiumas
H0.1 THMJ U3.1 01/31/14 A
DESIGN LOADS
IKX3f
CIW KMC JO
mnrtov •W
M
TOTAL LOMl tf
L/MO
Lcuoouinnai r
WM/IMO-cuf moN RL01
ROSEBURG FOREST PRfXUCTS I-JOIST ESR-t2Sf
art MARK DESCRIPTION L£M8TH
3» RJOl ir RFPl 700 31'-0-
Jfl R»2 18* RTPI 700 SO'-O'
18- RFPI 700 32'-0'
a IU04 18' RFPI 700 Z*'-0"
FARE WS01
FABE WSOI
FME WSOI
FABE WSOI
UEff STJEFEIVERS
an nscRvnoN L£Nam
340 WSOI PLY T/» » 3 1/1 14*
/cc A/ETALS CONNECTORS ESR-2930
OTf MARK OESCRPnON
NAILJM
ROMIXS OTf MARK OESCRPnON HEADER JOST ROMIXS
117 RM01 MTRSftia 2-10(1 X tn SMOLE
18 RH02 nSBIS SK L 28-Z~1H 2-10d • IK • SKEW
a4r-vB
24f-VS
24F- V4 INDUSJniAL APPEARANCE UNO r*K MBTUK cctamr
IMW WOTH DEPTH LEH9TM CAMBER
1 RB01 a i/if 30 3l'-0-0-
1 mo2 9 1/B 30 30--4-3/4-
ma 8 l/B 30 a4'-4" cr
(RC-e'-o*)
<LC-4'-0^
TOSffiWW FO/fEST PfKXHJCTS 3.0 LVL ESR-IZIO
orr MARK WIDTH OEPTH LMTH
2 RB04 7 18 SI'-C
RBOe 8 1/4 1« 1fl'-0'
1 RBOe 8 1/4 14 IS'-O*
20 RLOl 1 3/4 18 20'-0" {FOJ) CUT tWI/BLKO)
ROOF FRAMING PLAN
PL YWOOD ED^ &.OCKS
OTf MARK DEBCRPTKM UNGTH
840 PCB1 3 K 4 NHL
*/ z-eups BOTH ew» 7/1
90 PEB2 3 « 4 UBU.
W/ Z-CUP ONE EM) r-B 7/18"
H ZCOl LOOK 1-cun
WARNING
DRILUNG, SAHWG, OK UACtmiNG WOOD
PKoucrs cCMKirrs woo ovsr, A SUBSTANCC
mom ro rue srArz or cAunmu ro oiusr CANCER.
A VOD INHAUNO HOOD DUST OR USE A DUST UASK OR
OrHER SAFFOUARDS rOft PERSONAL PROTECnoN. FAemCATION AUTHORIZATION
CUSTOMER; ,,
NOTE:
REFERENCE UANUFACWRERS
PRODVCr GUlOE FOR PRODUCT
INSTALLA VON AND ADDITIONAL
INFORUATION.
<I<]<1<1
§15
5
I
SHEET
2 OF 2
KeyBeani
KeyBeam® 4.600d
kmBeamEngine 4.6026
Materials Datebase 1424
PAD BUILDING "A"
BRESSI RANCH VILLAGE CENTER
CARLSBAD, CA
4-13-14
8:12am
lofl
Member Data
Description:
ROOF JOIST W/ MNSRD & MECH.
Standard Load:
Roof Load: 20 PSF
Dead Load: 15 PSF
Member Type: Joist
Top Lateral Bradng: Continuous
Bottom Lateral Bradng: None
Moisture Condition: Dry
Deflection Criteria: L/360 live, L/240 total
Deck Connection: Nailed
Filename: CALC-1.KYB
Application: Roof
Slope: 0.38/12
Building Code: IBC/IRC
Other Loads
Type
(Description)
Point (PLF)
MECHANICAL UNIT
Point (PLF)
MANSARD
Side
Top
Top
Begin
6' 0.00"
21' 6.00"
End
Otiier
Start
0
0
End
Dead
Start
150
250
End Category
Roof
Roof
r
f
? 29 6 0 ?
Bearings and Reactions
Location
0' 0.000"
29" 6.000"
Type
Wall
Wall
•Material
N/A
N/A
Input
Length
N/A
N/A
Rffin
Required
1.767"
1.902"
Gravity
Reaction
1413#
1463#
Gravity
Uplift
Maximum Load Case Reactions
Used for applying point loads (Of line Ioad5)to canyng memtMis
Roof Dead
1 5g3#(296plf) 820#(410pl0
J 593#(296plf) 870#(435pl0
Design spans
29' 7.938"
Actual Length
29' 6.750"
Product: 18" RFPI-700 24.0" O.C.
Minimum 1.77" Isearing required at t)earing # 1
Minimum 1.90" bearing required at tiearing # 2
Design assumes continuous lateral bracing along the top chord.
Design assumes no lateral bracing along the twttom ctiord.
Lateral support is required at each bearing.
PASSES DESIGN CHECKS
Allowable Stress Design
Positive Moment
Shear
TL Deflection
LL Deflection
Actual
10655.'#
1462.#
1.0378"
0.5961"
Allowable
13062.'#
3219.#
1.4830"
0.9887"
Capacity
81%
45%
L/342
L/597
Location
16.23'
29.5'
14.75'
14.75'
Loading
Total Load D+Lr
Total Load D+Lr
Total Load 0.5D+Lr
Total Load Lr
Control: Pos. Moment
DOLs: Live=100% Snow=115% Roof=125% Wlnd=160%
All product names aie tiademailts of ttieir lespective owners
Cop^ght <C) 2013 try Simpson Stiong-Tie Company Inc. AU. RIGtfTS RESERVED.
"Passing is defined as wtien ttre memtwr. floorjoist. tieam orgiidei; shown on ttiis drawing meets applicatile design ciiteria tor Loads, l.oading Conditions, and Spans listed on ttils slieet. The designjnust^ejeviewed^a qualitied designer or design pnjg^jgggla^^m|^jbr approval. This deslgn^s^^^^^installatlon Mcgidinfltottiemgm^^
fCeyBeain
KeyBeam® 4.600d
kmBeamEiigine 4.6026
Malerials Database 1424
PAD BUILDING "A"
BRESSI RANCH VILLAGE CENTER
CARLSBAD, CA
4-13-14
8:13am
lofl
Member Data
Descrii^on:
ROOF JOIST W/ TOWER
Standard Load:
Roof Load: 20 PSF
Dead Load: 15 PSF
Member Type: Joist
Top Lateral Bradng: Continuous
Bottom Lateral Bradng: None
Moisture Condition: Dry
Deflection Criteria: U360 live, L/240 total
Deck Connection: Nailed
Filename: CALC-2.KYB
Application: Roof
Slope: 0.38 /12
Building Code: IBC/IRC
Other Loads
Type
(Description)
Point (PLF)
TOWER
Side
Top
Begin
9' 0.00"
End
Other Start 0 End
Dead
Start
270
End Category
Roof
1-
f
?
29 6 0 ?
29 6 0
Bearings and Reactions
Location
0' 0.000"
29' 6.000"
Type
Wall
Wall
Material
N/A
N/A
Input
Length
N/A
N/A
Min
Required
1.767"
1.750"
Gravity
Reaction
1413#
1203#
Gravity
Uplift
Maximum Load Case Reactions
Used tor applying point loads (or line loads) to canying memtieis
Roof Dead
1 5g3#(296plf) 820#(410plO
J 593#(296plf) 610#(305plf) Design spans
29' 7.938"
Actual Length
29' 6.750"
Product: 18" RFPI-700 24.0" O.C.
Minimum 1.77" bearing required at bearing # 1
lUHnimum 1.77' bearing required at t>earing # 2
Design assumes continuous lateral bracing along thetop clrard.
Design assumes no lateral bracing along the bottom chord.
Lateral support is required at each bearing.
PASSES DESiGN CHECKS
Aiiowabie Stress Design
Positive Moment
Shear
TL Deflection
LL Deflection
Actual
10324.'#
1412.#
0.9943"
0.5961"
Allowable
13062.'#
3219.#
1.4830"
0.9887"
Capacity
79%
43%
L«57
L/597
Location
11.79'
0'
14.75'
14.75'
Loading
Total Load D+Lr
Totel Load D+Lr
Total Load 0.5D+Lr
Total Load Lr
Control: Pos. Moment
DOLs: Llve=100% Snow=115% Roof=125% Wlnd=160%
All product names are tiademartrs of their respective owners
Copyright (C) 2013 by Simpson Stiong-Tie Company Inc. AU. RIGHTS RESERVED. **Passlng Is defined as when the member, floorjoist, beam orglrdei; shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The design must be re\newed^y£qu£lfied^desipnef ord^ pro^sjOTg|^^^i^^^^wg|^TOsd^ign assume^^^^^^^jgig^agggj^^jlegwgufacturer's sgeciflcattons^
KeyBemm
KeyBeam® 4.600ci
i kmBeamEngine 4,6026
Materials Database 1424
PAD BUILDING "A"
BRESSI RANCH VILLAGE CENTER
CARLSBAD, CA
4-13-14
8:12am
1 ofl
Member Data
Description:
ROOF JOIST W/ MNSRD & MECH.
Standard Load:
Roof Load: 20 PSF
DeadLoad: 15 PSF
RECEIVED
Member Type: Joist
Top Lateral Bracing: Continuous
Bottom Lateral Bracing: None
Moisture Condition: Dry
Deflection Criteria: L/360 live, L/240 total
Deck Connection: Nailed
Filename: CALC-1.KYB
Application: Roof
Slope: 0.38/12 APR 18 2014
Building Code: IBC/IRC
CITY OF CARLSBAD
BUILDING DIVISION
Other Loads
Type
(Description)
Point (PLF)
MECHANICAL UNIT
Point (PLF)
MANSARD
Side
Top
Top
Begin
6' 0.00"
21' 6.00"
End
other
Start
0
0
End
Dead
Start
150
250
End Category
Roof
Roof
29 6 0
Bearings and Reactions
Location
0' 0.000"
29' 6.000"
Type
Wall
Wall
Material
N/A
N/A
Input
Length
N/A
N/A
Min
Required
1.767"
1.902"
Gravity
Reaction
1413#
1463#
Gravity
Uplift
Maximum Load Case Reactions
Used for applying point loads (orline loads)to canyng niembers
Dead
820#(410plf)
870#(435plf)
Roof
1 593#(296plf)
J 593#(296plf)
Design spans
29' 7.938"
Actual Length
29'6.750"
Product: 18" RFPI-700 24.0" O.C.
Minimum 1.77" beaiing required at bearing # 1
Minimum 1.90" bearing required at bearing #2
Design assumes continuous lateral bracing along the top chord.
Design assumes no lateral bracing along the bottom chord.
Lateral support is required at each bearing.
PASSES DESIGN CHECKS
Allowable Stress Design
Positive Moment
Shear
TL Deflection
LL Deflection
Actual
10655.'#
1462.#
1.0378"
0.5961"
Allowable
13062.'#
3219.#
1.4830"
0.9887"
Capacity
81%
45%
L/342
L/597
Location
16.23'
29.5'
14.75'
14.75'
Loading
Total Load D+Lr
Total Load D+Lr
Total Load 0.5D+Lr
Total Load Lr
Control: Pos. Moment
DOLs: Live=100% Snow=115% Roof=125% Wind=160%
All product names are trademarits of their respective owners
Copi*ight (C)2013 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.
"Passing is defined as wiien the member, floorjoist. beam orgiidei; shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Sl
The desiqn must be reviewed b^^ajualified designer or design professional as required tbr approval. TMs desiqn assumes product installation accoidinq to the Ijnuft Sjigi^ro ye^
KeyBemm
KeyBeam® 4.600d
kmBeamEngine 4.6026
Materials Database 1424
PAD BUILDING "A"
BRESSI RANCH VILLAGE CENTER
CARLSBAD,CA
4-13-14
8:13am
1 ofl
Member Data
Description:
ROOF JOIST W/ TOWER
Standard Load:
Roof Load: 20 PSF
Dead Load: 15 PSF
Member Type: Joist
Top Lateral Bracing: Continuous
Bottom Lateral Bracing: None
Moisture Condition: Dry
Deflection Criteria: L/360 live, L/240 total
Deck Connection: Nailed
Filename: CALC-2.KYB
Application: Roof
Slope: 0.38/12
Building Code: IBC/IRC
Other Loads
Type
(Description)
Point (PLF)
TOWER
Side
Top
Begin
' 0.00"
End
Other
Start
0
End
Dead
Start
270
End Category
Roof
1 i -!'l»:» '4}M'l!liJ;«-,)-: ;r;.i-4i'i!:.;!-:i:*;5!!;i|:'-*?! ;;:::;;;ilMi.!«!ta?i»<lJS.'!1Ss;.<t85i
Jl
?
29 6 0 —?
29 6 0
Bearings and Reactions
Location
1 0' 0.000"
2 29' 6.000"
Type
Wall
Wall
Material
N/A
N/A
Input Min
Length Required
N/A 1.767"
N/A 1.750"
Gravity Gravity
Reaction Uplift
1413#
1203#
Maximum Load Case Reactions
Used iorapplyng point loads (orline loads)to carrying members
Roof
1 593#(296plf)
2 593#(296plf)
Dead
820#(410plf)
610#(305plf)
Design spans
29' 7.938"
Actual Length
29' 6.750"
Product: 18" RFPI-700 24.0" O.C.
Minimum 1.77" bearing required at bearing # 1
Minimum 1.75" bearing required at bearing # 2
Design assumes continuous lateral bracing along the top chord.
Design assumes no lateral bracing along the bottom chord.
Lateral support is required at each bearing.
PASSES DESIGN CHECKS
Allowable Stress Design
Positive Moment
Shear
TL Deflection
LL Deflection
Actual
10324.'#
1412.#
0.9943"
0.5961"
Allowable
13062.'#
3219.#
1.4830"
0.9887"
Capacity
79%
43%
L/357
L/597
Location
11.79'
0'
14.75'
14.75'
Loading
Total Load D+Lr
Total Load D+Lr
Total Load 0.5D+Lr
Total Load Lr
Control: Pos. Moment
DOLs: Liv6=100% Snow=115% Roof=125% Wind=ie )%
All product names are trademarks of their respective owneis
Copyright (C) 2013 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.
"Passing is defined as when the member, floorjoist, beam or girdec shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet.
TTie^esig^TTus^^ieviewe^^^uali^^