HomeMy WebLinkAbout2662 Garden House Rd; ; CBR2019-1925; PermitPrint Date: 12/13/2019
Job Address:
Permit Type:
Parcel No:
Valuation:
Occupancy Group:
# Dwelling Units:
Bedrooms:
Project Title:
2662 Garden House Rd
BLDG-Residential
2131500400
$7,627.64
Residential Permit
Work Class: Alteration
Lot#:
Reference #:
Construction Type:
Bathrooms:
Orig. Plan Check#:
Plan Check#:
( City of
Carlsbad
Permit No: CBR2019-1925
Status:
Applied:
Issued:
Permit
Finaled:
Inspector:
Final
Closed -Finaled
07/23/2019
08/29/2019
Inspection: 12/13/2019 9:55:38Ar
Description: MCELROY: CONVERT DEN INTO A BEDROOM// REMOVE LOAD BEARING INTERIOR WALL BETWEEN DINING AND KITCI
Applicant:
ALEX MILLER
2329 Chicago St
San Diego, CA 92110-4104
858-692-2529
BUILDING PERMIT FEE ($2000+)
BUILDING PLAN CHECK FEE (BLDG)
Owner:
COOWNER MCELROY MICHAEL C AND
NENITA J
2662 Garden House Rd
CARLSBAD,CA 92009
SB1473 GREEN BUILDING STATE STANDARDS FEE
STRONG MOTION-RESIDENTIAL
Total Fees: $167.26 Total Payments To Date: $167.26
Contractor:
PRECISION HOME DESIGN AND REMODELINC
4225 Executive Sq, Ste 600
La Jolla, CA 92037-1466
619-919-9161
Balance Due: $0.00
$97.22
$68.05
$1.00
$0.99
Please take NOTICE that approval of your project includes the "Imposition" of fees, dedications, reservations, or other exactions hereafter
collectively referred to as "fees/exaction." You have 90 days from the date this permit was issued to protest imposition of these
fees/exactions. If you protest them, you must follow the protest procedures set forth in Government Code Section 66020(a), and file the
protest and any other required information with the City Manager for processing in accordance with Carlsbad Municipal Code Section
3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack, review, set aside, void, or annul their
imposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection
fees and capacity changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this
project. NOR DOES IT APPLY to any fees/exactions of which you have previously been given a NOTICE similar to this, or as to which the
statute of limitation has previously otherwise expired.
1635 Faraday Avenue, Carlsbad, CA 92008-7314 I 760-602-2700 I 760-602-8560 f I www.carlsbadca.gov
{cicyof
Carlsbad
RESIDENTIAL
BUILDING PERMIT
APPLICATION
B-1
Plan Check('6r?,_at,/ ~ / q,;z
Est. Value jj 1:1 f:ia7j t@
PC Deposit ------~~--
Date I~,;) "1-}9
"1-2-15.-0.,-0• Suite: _____ APN: __ ,., __ ., _______ _
CT /Project #: __________ Lot#:, ____ Fire Sprinklers: yes / !)9.. Air Conditioning: yes / no
BRIEF DESCRIPTION OF WORK: _f:,..,_,'"-a.."'='-'-v-=e."-=1-"'•"'A_.p'-='e~c,'!c:.f'-'-'cµ=c-'-,y"'"=· IT.PrTi'-t,'--'-k-'--•,._ __ .,,._,,._"'_ .. -+,-'-l't--'-l>t>-"---=~=-o...:..,,__-s_-r-'--"'--<!!.. l'-1 Tc.l-<6.0 '
□ Addition/New: _____ Living SF, ____ Deck SF, ____ Patio SF, ____ Garage SF
Is this to create an Accessory Dwelling Unit? Yes/ No New Fireplace? Yes/ No, if yes how many? __
~ Remodel: _l'-.,~4 __ SF of affected area Is the area a conversion or change of use? Yes/ JlLc-...,.
□ Pool/Spa: ____ SF Additional Gas or Electrical Features? --------------
□ Solar: ___ KW, ___ Modules, Mounted: Roof/ Ground , Tilt: Yes/ No, RMA: Yes/ No, Battery: Yes/ No
Panel Upgrade: Yes/ No
D Reroof: ____________________________________ _
D Plumbing/Mechanical/Electrical Only: _______________________ _
D Other: __________________________________ _
APPLICANT (PRIMARY CONTACT)
Name: A t.-£1'-MI l-L.,ES:'2-
Address: '2-,1.'\ Ci<lc.-f<ro Si"
City: "iAtv 'l>lp6:-0 State: cft Zip: "(t.rt 0
Phone: (5 S 6 "1,.,--z,.. 51-'{
Email: qlex: ... :fler ........ ,•( 1-@o,-..'1.,;a.., -
DESIGN PROFESSIONAL
Name: JI<-i.-e-y; Ml"~
Address: I '
City: _______ State: ___ .Zlp: ___ _
Phone: ________________ _
Email: _________________ _
Architect State License: C. 3 -I I (. '{
PROPERTY OWNER
Name: Mt t'f:IA:c:;1.., 4 JJe"t-tfr Mc.~z..,fl'1>y
Address: __________________ _
City: ___________ state:. ___ Zip: ____ _
Phone: ____________________ _
Email: ___________________ _
CONTRACTOR BUSINESS
Name: ef1.;rc151,..v pe;,1(r;"-!-t•,.1; ,-_o,PeU ,;G-
Address: "I t.:z,. S ex e,., n~£: S,. ff , e> •
City: 1.-k ::TO v,p., State: CI\ Zip: 9 --.1> 'J "7
Phone: '-I <f 11 "f er/ ~f
Email: r'a.r,, cr.e p,-a c.,,'s,..._-s J · c.""
State License: I "-; '4 5 o ,s Bus. License: ~ tiJ
(Sec. 7031.S Business and Professions Code: Any City or County which requires a permit to construct, alter, improve, demolish or repair any structure, prior to its
issuance, also requires the applicant for such permit to file a signed statement that he/she Is licensed pursuant to the provisions of the Contractor's license Law
{Chapter 9, commending with Section 7000 of Division 3 of the Business and Professions Code} or that he/she ls exempt therefrom, and the basis for the alleged
exemption. Any violation of Section 7031.S by any applicant for a permit subjects the applicant to a civil penalty of not more than five hundred dollars {$500}).
1635 Faraday Ave Carlsbad, CA 92008 Ph: 760-602-2719 Fax: 760-602-8558 Email: Building@carlsbadca.gov
B-1 Page 1 of 2 Rev. 06/18
( OPTION A): WORKERS'COMPENSATION DECLARATION:
I hearby affirm under penalty of perjury one of the following declarations:
~ I have and will maintain a certificate of consent to self-insure for workers' compensation provided by Section 3700 of the Labor Code, for the performance of the
work which this permit is issued.
1] I have and will maintain worker's compensation, as required by Section 3700 of the Labor Code, for the p rforma
My workers' compensation Insurance carrier and policy number are: Insurance /mpa'y Name: /11 I
Polley No. P,iJUWC Q1 'f6:66 U Expiration Date: 1-//'3 ).O '
permit is issue?-
□ Certificate of Exemption: l certify that in the performance of the work for which this permit is issued, l shall not employ any person in any manner so as to be come
subject to the workers' compensation Laws of California. WARNING: Failure to secure workers compensation coverage Is unlawful, and shall subject an employer to
crlmlnal penalties and clvll fines up to $100,000.00, In addition the to the cost of compensation, damages as provided for In Section 3706 of the Labor Code,
Interest and attorney's fees.
CONTRACTOR SIGNATURE: ------4:3..i.;..,..~---------□AGENT DATE: _____ _
( OPTION B ): OWNER-BUILDER DECLARATION:
I hereby affirm that I am exempt from Contractor's License Law for the following reason:
□ I, as owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not Intended or offered for sale (Sec.
7044, Business and Professions Code: The Contractor's License Law does not apply to an owner of property who builds or Improves thereon, and who does such work
hlmself or through his own employees, provided that such Improvements are not Intended or offered for sale. lf, however, the bulldlng or Improvement Is sold within
one year of completion, the owner-builder will have the burden of proving that he did not build or improve for the purpose of sale).
□ I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions Code: The
Contractor's License Law does not apply to an owner of property who builds or improves thereon, and contracts for such projects with contractor(s) licensed
pursuant to the Contractor's license Law).
□ I am exempt under Section ________ B,usiness and Professions Code for this reason:
1. I personally plan to provide the major labor and materials for construction of the proposed property improvement. □ Yes □ No
2. I (have/ have not) signed an application for a build Ing permit for the proposed work.
3. I have contracted with the following person (firm) to provide the proposed construction (include name address/ phone/ contractors' license number):
4. I plan to provide portions of the work, but I have hired the following person to coordinate, supervise and provide the major work (include name/ address/ phone/
contractors' license number):
5. I will provide some of the work, but I have contracted (hired) the following persons to provide the work indicated (include name/ address/ phone/ type of work):
OWNER SIGNATURE: _________________ □AGENT DATE: _____ _
CONSTRUCTION LENDING AGENCY, IF ANY:
I hereby affirm that there is a construction lending agency for the performance of the work this permit is issued (Sec. 3097 (i) Civil Code).
Lender's Name: _____________________ Lender's Address: ____________________ _
ONLY COMPLETE THE FOLLOWING SECTION FOR NON-RESIDENTIAL BUILDING PERMITS ONLY:
Is the applicant or future building occupant required to submit a business plan, acutely hazardous materials registration form or risk management and prevention
program under Sections 25505, 25533 or 25534 of the Presley-Tanner Hazardous Substance Account Act? □ Yes □ No
Is the applicant or future buildlng occupant required to obtain a permit from the air pollution control district or air quality management district? □ Yes □ No
Is the facility to be constructed within 1,000 feet of the outer boundary of a school site? □ Yes □ No
IF ANY OF THE ANSWERS ARE YES, A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR IS MEETING THE
REQUIREMENTS OF THE OFFICE OF EMERGENCY SERVICES ANO THE AIR POLLUTION CONTROL DISTRICT.
APPLICANT CERTIFICATION:
I certify that I have read the application and state that the above information is correct and that the information on the plans is accurate. I agree to comply with all
City ordinances and State laws relating to bulldlng construction.
l hereby authorize representative of the City of Carlsbad to enter upon the above mentioned property for inspection purposes. I ALSO AGREE TO SAVE, INDEMNIFY ANO KEEP
HARMLESS THE CllY OF CARLSBAD AGAINST ALL LIABILITIES, JUDGMENTS, COSTS ANO EXPENSES WHICH MAY IN ANY WAY ACCRUE AGAINST SAID CllY IN CONSEQUENCE OF
THE GRANTING OF THIS PERMIT.OSHA: An OSHA permit is required for excavations over 5'0' deep and demolition or construction of structures over 3 stories fn height.
EXPIRATION: Every permit issued by the Buildlng Official under the provisions of this Code shall expire by limitation and become null and void if the building or work authorized
by such permit is not commenced within 180 days from the date of such pennit or ff the building or work authorized by such permit Is suspended or abandoned at any time
after the work is commenced for a period of 180 days (Section 106.4.4 Uniform Building Code).
APPLICANT SIGNATURE:
1635 Faraday Ave Carlsbad, CA 92008
B-1
Ph: 760-602-2719 Fax: 760-602-8558
Page 2 of 2
Email: Building@carlsbadca.gov
Rev. 06118
..
. PERMIT INSPECTION HISTORY R_EPORT (CBR2019-1925)
Permit Type: BLDG-Residential Application Date: 07/23/2019 Owner: COOWNER MCELROY MICHAEL C
AND NENITAJ
Work Class: Alteration Issue Date: 08/2912019 Subdivision: CARLSBAD TCT#02-14 BRESSI
RANCH UNIT#03
Status: Closed -Finaled Expiration Date: 04/0612020 Address: 2662 Garden House Rd
IVR Number: 20543 Carlsbad, CA 92009-3089
Scheduled Actual Inspection Type Inspection No. Inspection Status Primary Inspector Reinspection Complete Date Start Date
09/2312019 09123/2019 BLDG-84 Rough 104955-2019 Failed Tony Alvarado Reinspection Complete
Combo(14,24,34,44)
Checklist Item COMMENTS Passed
BLDG-14 No
Frame-Steel-Bolting-Welding
(Decks)
09124/2019 09124/2019 BLDG-11 105172-2019 Passed Tony Alvarado Complete
Foundation/Ftg/Pier
s (Rebar)
09/30/2019 09/3012019 BLDG-84 Rough 105758-2019 Cancelled Paul York Reinspection Complete
Combo(14,24,34,44)
Checklist Item COMMENTS Passed
BLDG-14 No
Frame-Steel-Bolting-Welding
(Decks)
10107/2019 10107/2019 BLDG-84 Rough 106691-2019 Passed Paul York Complete
Combo(14,24,34,44)
Checklist Item COMMENTS Passed
BLDG-14 Yes
Frame-Steel-Bolting-Welding
(Decks)
1211312019 1211312019 BLDG-Final 113654-2019 Passed Tony Alvarado Complete
Inspection
Checklist Item COMMENTS Passed
BLDG-Plumbing Final Yes
BLDG-Mechanical Final Yes
BLDG-Structural Final Yes
BLDG•Electrical Final Yes
December 13, 2019 Page 1 of 1
✓• EsG1I
r\ SAJ-Ebu.lt Co111;);i,'y
DATE: 8/27/2019
JURISDICTION: CARLSBAD
PLAN CHECK#.: 2019-1925 SET III
□ APPLICANT
□ JURIS.
PROJECT ADDRESS: 2662 GARDEN HOUSE ROAD
PROJECT NAME: SFD REMODEL FOR McELROY
□
□
□
□
□
cg]
□
□
The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
The plans transmitted herewith will substantially comply with the jurisdiction's
codes when minor deficiencies identified below are resolved and checked by building
department staff.
The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
The check list transmitted herewith is for your information. The plans are being held at EsGil
until corrected plans are submitted for recheck.
The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
The applicant's copy of the check list has been sent to:
ALEX MILLER
EsGil staff did not advise the applicant that the plan check has been completed.
EsGil staff did advise the applicant that the plan check has been completed.
Person contacted: ALEX Telephone#: 858 692 2529
Date contacted~ ·a.7-/7 (by7"(o) Email: ALEXMILLER.MAIL2@GMAIL.COM
Mail Telephone Fax In Person :JV
REMARKS:
By: ALI SADRE, S.E. (FOR B.D.)
EsGil
8/19
Enclosures:
9320 Chesapeake Drive, Suite 208 ♦ San Diego, California 92123 ♦ (858) 560-1468 ♦ Fax (858) 560-1576
DATE: 8/15/2019
JURISDICTION: CARLSBAD
PLAN CHECK#.: 2019-1925
✓• EsG1I
A SAFEbuilfCompany
SET: II
PROJECT ADDRESS: 2662 GARDEN HOUSE ROAD
PROJECT NAME: SFD REMODEL FOR McELROY
□ APPLICANT
□ JURIS.
D The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's codes
when minor deficiencies identified below are resolved and checked by building department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
~ The check list transmitted herewith is for your information. The plans are being held at EsGil
until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
~ The applicant's copy of the check list has been sent to:
ALEX MILLER
D EsGil staff did not advise the applicant that the plan check has been completed.
~ EsGil staff did advise the applicant that the plan check has been completed.
Person contacted: ALEX Telephone#: 858 692 2529
Date contacted: (by: ) Email: ALEXMILLER.MAIL2@GMAIL.COM
Mail Telephone
0 REMARKS:
By: Bert Domingo
EsGil
Fax In Person
Enclosures:
8/7/2019
9320 Chesapeake Drive, Suite 208 ♦ San Diego, California 92123 ♦ (858) 560-1468 ♦ Fax (858) 560-1576
CARLSBAD 2019-1925
8/15/2019
NOTE: The items listed below are from the previous correction list. These
remaining items have not been adequately addressed. The numbers of the items
are from the previous check list and may not necessarily be in sequence. The
notes in bold font are current.
PLANS
1. Please make all corrections, as requested in the correction list. Submit FOUR new
complete sets of plans for commercial/industrial projects (THREE sets of plans for
residential projects). For expeditious processing, corrected sets can be submitted
in one of two ways:
1. Deliver all corrected sets of plans and calculations/reports directly to the City of
Carlsbad Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760)
602-2700. The City will route the plans to EsGil and the Carlsbad Planning,
Engineering and Fire Departments.
2. Bring TWO corrected set of plans and calculations/reports to EsGil, 9320
Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-1468. Deliver all
remaining sets of plans and calculations/reports directly to the City of Carlsbad
Building Department for routing to their Planning, Engineering and Fire
Departments.
NOTE: Plans that are submitted directly to EsGil only will not be reviewed by the
City Planning, Engineering and Fire Departments until review by EsGil is complete.
2. All sheets of plans must be signed by the person responsible for their
preparation. (California Business and Professions Code). This will be checked
on the final.
3. Plans deviating from conventional wood frame construction shall have the
structural portions signed and sealed by the California state licensed engineer or
architect responsible for their preparation, along with structural calcuiations.
(California Business and Professions Code). This will be checked on the final.
MISCELLANEOUS
5. The calculation's reaction seems to show 5764# greater than the allowable of
3000#. Please clarify. Where is F1. Please show on 1/S1 the location of the
holdown.
CARLSBAD 2019-1925
8/15/2019
To speed up the review process, note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet, note or detail number,
calculation page, etc.
Please indicate here if any changes have been made to the plans that are not a
result of corrections from this list. If there are other changes, please briefly
describe them and where they are located in the plans.
Have changes been made to the plans not resulting from this correction list?
Please indicate:
Yes □ No □
The jurisdiction has contracted with EsGil, located at 9320 Chesapeake Drive,
Suite 208, San Diego, California 92123; telephone number of 858/560-1468, to
perform the plan review for your project. If you have any questions regarding
these plan review items, please contact Bert Domingo at EsGil. Thank you.
✓• EsG1I
A SAFEbuilfCompany
DATE: 8/03/2019
JURISDICTION: CARLSBAD
PLAN CHECK#.: 2019-1925 SET: I
□ APPLICANT
□ JURIS.
PROJECT ADDRESS: 2662 GARDEN HOUSE ROAD
PROJECT NAME: SFD REMODEL FOR McELROY
□
□
□
□
□
~
The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's codes. ·
The plans transmitted herewith will substantially comply with the jurisdiction's
codes when minor deficiencies identified below are resolved and checked by building
department staff.
The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
The check list transmitted herewith is for your information. The plans are being held at EsGil
until corrected plans are submitted for recheck.
The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
The applicant's copy of the check list has been sent to:
ALEX MILLER
EsGil staff did not advise the applicant that the plan check has been completed.
EsGil staff did advise the applicant that the plan check has been completed.
Person contacted: ALEX Telephone#: 858 692 2529
Date contacted: (by: ) Email: ALEXMILLER.MAIL2@GMAIL.COM
Mail Telephone Fax In Person
0 REMARKS:
By: Bert Domingo
EsGil
7/25/2019
Enclosures:
9320 Chesapeake Drive, Suite 208 ♦ San Diego, California 92123 ♦ (858) 560-1468 ♦ Fax (858) 560-1576
CARLSBAD 2019-1925
8/03/2019
PLAN REVIEW CORRECTION LIST
SINGLE FAMILY DWELLINGS AND DUPLEXES
PLAN CHECK#.: 2019-1925 JURISDICTION: CARLSBAD
PROJECT ADDRESS: 2662 GARDEN HOUSE ROAD
FLOOR AREA:
REMARKS:
DATE PLANS RECEIVED BY
JURISDICTION:
DATE INITIAL PLAN REVIEW
COMPLETED: 8/03/2019
FOREWORD (PLEASE READ):
STORIES:
HEIGHT:
DATE PLANS RECEIVED BY
ESGIL CORPORATION: 7/25/2019
PLAN REVIEWER: Bert Domingo
This plan review is limited to the technical requirements contained in the California version of
the International Residential Code, International Building Code, Uniform Plumbing Code,
Uniform Mechanical Code, National Electrical Code and state laws regulating energy
conservation, noise attenuation and access for the disabled. This plan review is based on
regulations enforced by the Building Department. You may have other corrections based on
laws and ordinance by the Planning Department, Engineering Department, Fire Department or
other departments. Clearance from those departments may be required prior to the issuance of
a building permit.
Present California law mandates that construction comply with the 2016 edition of the California
Code of Regulations (Title 24), which adopts the following model codes: 2015 IRC, 2015 IBC,
2015 UPC, 2015 UMC and 2014 NEC.
The above regulations apply, regardless of the code editions adopted by ordinance.
The following items listed need clarification, modification or change. All items must be satisfied
before the plans will be in conformance with the cited codes and regulations. Per Sec. 105.4 of
the 2015 International Building Code, the approval of the plans does not permit the violation of
any state, county or city law.
To speed up the recheck process, please note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet number, specification section, etc.
Be sure to enclose the marked up list when you submit the revised plans.
CARLSBAD 2019-1925
8/03/2019
PLANS
1. Please make all corrections, as requested in the correction list. Submit FOUR new
complete sets of plans for commercial/industrial projects (THREE sets of plans for
residential projects). For expeditious processing, corrected sets can be submitted
in one of two ways:
1. Deliver all corrected sets of plans and calculations/reports directly to the City of
Carlsbad Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760)
602-2700. The City will route the plans to EsGil and the Carlsbad Planning,
Engineering and Fire Departments.
2. Bring TWO corrected set of plans and calculations/reports to EsGil, 9320
Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-1468. Deliver all
remaining sets of plans and calculations/reports directly to the City of Carlsbad
Building Department for routing to their Planning, Engineering and Fire
Departments.
NOTE: Plans that are submitted directly to EsGil only will not be reviewed by the
City Planning, Engineering and Fire Departments until review by EsGil is complete.
2. All sheets of plans must be signed by the person responsible for their
preparation. (California Business and Professions Code).
3. Plans deviating from conventional wood frame construction shall have the
structural portions signed and sealed by the California state licensed engineer or
architect responsible for their preparation, along with structural calculations.
(California Business and Professions Code).
PLUMBING
4. Specify on the plans whether the existing house was built before or after 1994.
:=or additions or improveme,,ts to a residence built before 1994, noie on the
plans that existing "noncompliant" fixtures (toilets that use more than 1.6 gallons
of water per flush, urinals that use more than one gallon of water per flush,
showerheads that have a flow capacity of more than 2.5 gallons of water per
minute, and interior faucets that emit more than 2.2 gallons of water per minute)
shall be replaced. Certification of compliance shall be given to the building
inspector prior to final permit approval. California SB407.
MISCELLANEOUS
5. The calculation's reaction seems to show 5764# greater than the allowable of
3000#. Please clarify.
CARLSBAD 2019-1925
8/03/2019
To speed up the review process, note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet, note or detail number,
calculation page, etc.
Please indicate here if any changes have been made to the plans that are not a
result of corrections from this list. If there are other changes, please briefly
describe them and where they are located in the plans.
• Have changes been made to the plans not resulting from this correction list?
Please indicate:
Yes □ No □
The jurisdiction has contracted with EsGil, located at 9320 Chesapeake Drive,
Suite 208, San Diego, California 92123; telephone number of 858/560-1468, to
perform the plan review for your project. If you have any questions regarding
these plan review items, please contact Error! Reference source not found. at
EsGil. Thank you.
CARLSBAD 2019-1925
8/03/2019
[DO NOT PAY -THIS JS NOT AN INVOICE]
VALUATION AND PLAN CHECK FEE
JURISDICTION: CARLSBAD
PREPARED BY: Bert Domingo
PLAN CHECK#.: 2019-1925
DATE: 8/03/2019
BUILDING ADDRESS: 2662 GARDEN HOUSE ROAD
BUILDING OCCUPANCY: R 3
BUILDING I AREA I Valuation Reg.
PORTION (Sq.Fl) Multiplier Mod.
CTY ESTIMATE
Air Conditioning
Fire Sprinklers
TOTAL VALUE
Jurisdiction Code CB By Ordinance
1997 UBC Buildin Permit Fee g 3 ....
_19_97_U_B~C P=l•~n ~Ch_ec_k _Fe_e ___ -~
t "/\I !,a'.
VALUE
Type of Review: 0 Complete Review
□ Other
□ Hou1y
EsGilFee
D Structural Only
D Repetitive Fee
• Repeats
Comments: In addition to the above fee, an additional fee of$
$ /hr.) for the CalGreen review.
($)
is due (
7,628
7,628
$62.951
hour@
Sheet 1 of 1
C cityof
Carlsbad
PURPOSE
CLIMATE ACTION PLAN
CONSISTENCY CHECKLIST
8-50
Development Services
Building Division
1635 Faraday Avenue
(760) 602-2719
www .ca rlsbadca .gov
This checklist is intended to assist building permit applicants identify which Climate Action Plan (CAP) ordinance
requirements apply to their projects. Unless none of the requirements apply, the completed checklist must be
included in the building permit application. It may be necessary to supplement the completed checklist with
supporting materials, calculations or certifications, to demonstrate full compliance with CAP ordinance
requirements. For example, projects that propose or require a performance approach to comply with energy-
related measures will need to attach to this checklist separate calculations and documentation as specified by
the ordinances .
..,. If an item in the checklist is deemed to be not applicable to a project, or is less than the minimum required
by ordinance, an explanation must be provided to the satisfaction of the Building Official.
..,. Details on CAP ordinance requirements are available on the city's website.
Project Name/Building
Permit No.:
Property Address/APN:
Applicant Name/Co.:
Applicant Address:
Contact Phone: Contact Email:
Contact information of person completing this checklist (if different than above):
Name:
Company
name/address:
Contact Phone:
Contact Email:
Applicant Signature: _______________ Date: _______ _
8-50 Page 1 of 3 Revised 04/19
City of Carlsbad Climate Action Plan Consistency Checklist
Use the table below to determine which sections of the Ordinance Compliance checklist are applicable to your project.
For residential alterations and additions to existing buildings, contact the building counter for the building permit valuation.
Building Permit Valuation (BPV) $ ""'f 1 {o;J. t::f · {o L/
Compllte Sectlon(I) Notes:
Residential
□ New construction 1A
Alterations: )8t exempt
□ BPV ~ $60,000
□ Electrical service panel upgrade
1A
1A
1-2 family dwellings and townhouses with attached garages
only
□ BPV ~ $200,000 1A
Multi-family dwellings only where interior finishes are removed
and significant site work and upgrades to structural and
mechanical, electrical, and/or plumbing systems are proposed
D Nonresidential
□ New construction 1B and 2
□ Alterations 2
1. Electric Vehicle Charging
A. D Residential New construction and major alterations (or electric panel upgrade)*
Please refer to Carlsbad Ordinance CS-349 when completing this section.
□ One and two-family residential dwelling or townhouse with attached garage:
□ One EVSE ready parking space required □ Exception :
□ Multi-family residential· □ Exception ·
Total Parking Spaces EVSE Spaces
Proposed Capable Ready I
I
Calculations: Total EVSE spaces = .10 x Total parking (rounded up to nearest whole number)
EVSE Installed = Total EVSE Spaces x .50 (rounded up to nearest whole number)
EVSE other= Total EVSE spaces -EVSE Installed
(EVSE other may be "Capable," "Ready'' or "Installed.")
Installed Total
*Major alterations are: (1) for one and two-family dwellings and townhouses with attached garages, alterations have a building permit valuation ~ $60,000 or
include an electrical service panel upgrade; (2) for multifamily dwellings (three units or more without attached garages), alterations have a building permit valuation
~ $200,000, interior finishes are removed and significant site work and upgrades to structural and mechanical, electrical, and/or plumbing SY5tems are proposed.
B D Nonresidential new construction (includes hotels/motels) □ Exception ·
Total Parking Spaces EVSE Spaces
Proposed Capable I Ready I Installed I Total
I I I
Calculation · Refer to the table below·
Total Number of ParkinQ Spaces provided Number of reauired EV Spaces Number of reauired EVSE Installed Spaces
D 0-9 1 1
D 10-25 2 1
D 26-50 4 2
D 51-75 6 3
D 76-100 9 5
D 101-150 12 6
D 151-200 17 9
D 201 and over 10 percent of total 50 percent of Required EV Spaces
Updated 4/12/2019 2
City of Carlsbad Climate Action Plan Consistency Checklist
2. D Transportation Demand Management (TOM)
A. List each proposed nonresidential use and gross floor area (GFA) allocated to each use.
B. Employee ADT/1,000 square feet is selected from the table below.
Use GFA Employee ADT for first Employee ADT for each
1,000 S.F. subsequent 1,000 S.F.
Total
If total employee ADT is greater than or equal to 110 employee ADT, a TOM plan is required.
TOM plan required: Yes □ No □
Updated 4/12/2019
Employee ADT Estimation for Various Commercial Uses
ADT for first
1,000 s.f.
EmpADTI
1000s.f.1
Office (all)2 20
Restaurant 11
Retaib 8
Industrial 4
Manufacturing 4
Warehousin 4
1 Unless otherwise noted, rates estimated from /TE Trip
Generation Manual, 1rJhEdition
20
11
4.5
3.5
3
1
2 For all office uses, use SAN DAG rate of 20 ADT/1,000 sf to
calculate employee ADT
3 Retail uses include shopping center, variety store, supermarket,
gyms, pharmacy, etc.
Other commercial uses may be subject to special
consideration
Sample calculations:
Office: 20,450 sf
1. 20,450 sf/ 1000 x 20 = 409 Employee ADT
Retail: 9,334 sf
1. First 1,000 sf = 8 ADT
2. 9,334 sf -1,000 sf= 8,334 sf
3. 8,334 sf/ 1,000 x 4.5 + 8 = 46 Em lo ee ADT
Total Employee ADT
3